Variable orifice cast iron double regulating valve Fig. 9555PFlanged PN16 according to EN1092-2 (ex DIN2533)Lengths according to EN558-1 series 1 (ex DIN3202 F1)Alkyd/acrylic single layer waterpaint coating (50-100µm)
Stainless steel wafer metering station Fig. 9450For EN1092 PN16 flanges
Tolerance on nominal Kv for completely open valve ±5%(test according to BS7350)Gost compliant
PN16
Working conditions:● Water: -10°C to +120°C
below 0°C only for water with added antifreezing fluidsover 100°C only for water with added anti-boiling fluids
N.1234567891011121314151718192021222324
Plug Steel6 C35E
1DN65 excluded2Two-pieces bonnet for DN≥200, with bottom part in ductile iron EN-GJS-500-7 JL105028.8 A2A steel joint screws3X5CrNi18-10 steel for DN≥2004CuZn40Pb2 brass screw and washer for DN≥20055 A2A steel for DN≥2006Caps with carbamide rubber gaskets7Test points with EPDM gaskets and polypropylene ties
Test point DZR Brass7 EN12164 CW602N
Body Stainless steel AISI 316Extension Stainless steel AISI 316
Handwheel screw Brass5 CW508LCap Polyamide PA6.6
Bushing DZR Brass EN12164 CW602NHandwheel Polyamide4 PA6.6
Stem O-ring EPDM -Screw Brass3 CW508L
Washer DZR Brass EN12164 CW602NStem DZR Brass EN12164 CW602N
Memory stop DZR Brass EN12164 CW602NMem. stop O-ring EPDM Perox -
Bonnet2 Cast iron EN-GJL-250 JL1040Screws Carbon steel 8.8 A2A
Shut./bon. O-ring1 EPDM -Body/bon. O-ring EPDM -
Gasket disc EPDM -Shutter Composite material -
Cone screw Stainless steel A2Balancing cone Composite material -
Part Material NormBody Cast iron EN-GJL-250 JL1040
9565P9565P9565P9565PCast Iron Double Reg. Valve And
Stainless Steel Metering Station
Via Circonvallazione, 1013018 Valduggia (VC), Italy
Tel: +39 0163 47891Fax: +39 0163 47895
www.vironline.com
valvoindustria ing.Rizzio s.p.a.
Description
Part List
110512
1
7
6
4
3
2
5
8
14
13
11
10
12
17
16
15
19
18
20
9
22
23
24
21
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
1Suggested flow range applicability (BS7350)
If used with measuring manometers different from those proposed by VIR please verify that sensibility of the measuring device is compatiblewith indicated minimum flow (see flow measurement paragraph)
Formula linking flow Q (in l/s) and ∆pmeasured at test points (in kPa). Kvdepends on handwheel position asindicated on table.Minimum flow that can be measuredfor each diameter may be calculatedby using in the formula minimum ∆pthat can be measured by usedmanometer.Valves are anyway designed for bestperformances when used on rangepreviously suggested and as indicatedby BS7350.
18,0 385,0 210,5 94,16-255,99850 535 310 283,0300 460 410 12x2818,0 330,0 159,0 66,58-156,78730 525 310 255,0250 405 355 12x2818,0 274,0 114,5 41,86-100,47600 480 310 227,0200 340 295 12x2318,0 219,0 48,5 23,71-56,91480 285 130 200,0150 285 240 8x2318,0 193,0 34,0 16,85-39,75400 260 130 187,0125 250 210 8x1918,0 163,0 22,7 10,85-26,04350 240 130 172,0100 220 180 8x1918,0 143,0 17,8 6,40-15,36310 220 130 162,0080 200 160 8x1918,0 127,0 12,9 3,02-6,95290 205 130 154,0065 185 145 4x19
(mm) (mm) (kg) (l/s)(mm) (mm) (mm) (mm)OL ØOD Peso Flow range 1L H ØV OHDN ØF ØE NxØD
(mm) (mm) (mm)
H
L
ØF ØE
NxØD
ØV
Dimensions
110512
Via Circonvallazione, 1013018 Valduggia (VC), Italy
Tel: +39 0163 47891Fax: +39 0163 47895
www.vironline.com
OH
ØOD
OL
100,00
10,00
1,00
∆pT
P [k
Pa]
Flow [l/s]1,00 10,00 1000,00100,00
36
TPvs pK
Q∆⋅
=
DN65, Kvs 88,2
DN80, Kvs 123,0
DN100, Kvs 215,6
DN125, Kvs 336,9
DN150, Kvs 458,6
DN200, Kvs 803,9
DN250, Kvs 1249,0
DN300, Kvs 1836,0
Lowpressuretest point
∆pTP
Highpressuretest point
Q (flow)
Flow Measurement
100,00
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
Formula linking flow Q (in l/s) and theoretical valve headloss ∆p (in kPa).Kv depends on handwheel position as indicated on table.
To obtain the best performances valve must be installed on a pipe with its samenominal size preceded and followed by straight pipe lengths as per figureindications.
132022,0 - - - - - 634,6 1041 1361
- - 619,0 101521,0 - - -
123520,0 - - - - - 603,5 987,4 1278
- - 586,8 957,219,0 - - -
114818,0 - - - - - 567,3 924,1 1192
254,6 348,9 544,6 888,217,0 - - 165,1
104016,0 74,3 101,4 160,2 244,3 339,3 521,3 850,5 1098
233,2 327,4 500,6 812,015,0 70,6 97,6 154,2
886,714,0 67,3 93,5 146,7 220,8 313,3 477,8 769,6 969,8
206,3 297,1 447,5 721,313,0 63,9 88,8 137,4
714,612,0 59,7 83,1 126,8 190,2 278,5 411,5 660,7 798,9
173,3 257,9 373,9 597,711,0 54,0 75,0 115,5
494,210,0 45,9 62,5 103,1 154,8 235,6 331,7 526,9 622,0
132,0 211,3 278,4 441,99,0 36,0 45,0 88,3
201,68,0 26,8 30,9 70,1 104,7 178,8 213,7 341,0 329,9
76,3 130,1 147,8 237,77,0 19,6 21,8 50,0
110,16,0 14,7 16,7 33,9 51,0 83,2 99,7 163,4 140,6
33,0 51,7 71,1 115,65,0 11,7 13,8 22,9
72,24,0 9,3 11,8 16,6 23,7 29,7 54,6 87,2 89,8
17,8 19,1 45,6 73,13,0 7,0 9,9 12,8
44,92,0 5,2 7,9 9,6 13,0 14,8 38,6 62,3 57,1
250 3001,0 3,6 5,9 5,6 8,3 7,9 27,5 43,5
Handwheel position
Kv (m3/h @ 1bar)065 080 100 125 150 200
VIRmetering station
Fig.9450
Min 2xDN
Headloss calculation
236
⋅=∆VK
Qp
Installation
Via Circonvallazione, 1013018 Valduggia (VC), Italy
Tel: +39 0163 47891Fax: +39 0163 47895
www.vironline.com
Min 5xDN(10xDN if installed
on pump outlet)
∆p(headloss)
Q (flow)
VIRbalancing valve
Fig.9555P
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.