+ All Categories
Home > Devices & Hardware > A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Date post: 17-Aug-2014
Category:
Upload: emerson-exchange
View: 9,417 times
Download: 12 times
Share this document with a friend
Description:
Presented by Emerson's Alan Dewey at the 2011 Emerson Exchange in Nashville, TN USA.Abstract: Emerson has recently introduced a quick and easy way for users to connect directly to a FOUNDATION fieldbus segment with their portable laptop or notebook computer. Using Emerson's newly available USB Fieldbus Interface, users can easily connect their laptop or PC to a fieldbus network either in the field or on the bench. This enables users to experience the benefits of applications such as AMS Device Manager without having to use the control system. This workshop will highlight the capabilities of this useful new device and provide a live demonstration of how it can be used.
Popular Tags:
23
A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface Emerson User Exchange, 2011 Nashville, TN
Transcript
Page 1: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

A Quick and Easy Way to Connect to

FOUNDATION fieldbus using Emerson’s USB

Fieldbus Interface

Emerson User Exchange, 2011Nashville, TN

Page 2: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Presenters

Alan Dewey

Page 3: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Introduction

Background Features Using with AMS Device Manager Utility Program Packaging Fieldbus Foundation Profiles Demonstration

Page 4: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Background

Originally available internally from Rosemount as 770

Original objective was to help Rosemount sales force demonstrate FOUNDATION fieldbus devices

Page 5: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

“Productizing” by Emerson AO Packaging Enhancements to Utility Official Device Manager Support Documentation Pricing Support Agency Approvals Additional Testing and Beta Testing

Page 6: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Objective of Product

Provide a convenient means to connect a standard PC or laptop computer to a FOUNDATION fieldbus segment.

Not intended to be used to implement a permanent fieldbus Host system.

Page 7: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Features Fully compliant with FF Specifications Joins the fieldbus segment as a Visitor Two Power Modes

– USB provides power to FF segment (85 ma)– Use with segments that are already powered

Provides two Fieldbus terminators for segment Does not draw more than 12 ma from FF Segment CE and UL/CSA Approval Indicator lights for communication and power Uses standard USB cable Uses standard leadset (like the 475 Field Communicator)

Page 8: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Power Mode Handling

No Power Detected Power Detected onSegment

USB is ProvidingPower (will not be allowed if powerdetected).Default Case

Page 9: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Approvals

IEC 61626-1 EMC

Immunity

IEC 60950-1

IEC/UL/CSA

Safety Approvals

Also:

FCC 47CFRFF Physical Layer Test

Page 10: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Use with AMS Device Manager - Simple

Page 11: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Full Featured Device Dashboard Displays

Page 12: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Supported starting with Version 11.5 of AMS Device Manager

Shows up under the “FF HSE” branch

Requires AMS Device Manager HSE License– Special Pricing Available

Consistent Functionality with other FF interfaces supported in AMS Device Manager

Deployment with AMS Device Manager

Page 13: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Utility Program Features

Sets Power Mode Show Devices Connected to the segment Allows User to:

– Set the Device Tag– Set the Device Address– Commission / Decommission a Device– Change Device from Link Master to Basic

Provided on CD with product

Not provided in AMS Device Manager

Page 14: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Utility Program Display – Simple!

One Device on Segment

(TT-101)

Address of USB Interface

on FF Segment

Indicates that segment is

already powered.

Page 15: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Utility Program Display – Simple!

Select this if you want laptop to

provide power to the segment via

USB.

A message warns you not to connect power to segment that is already powered.

Page 16: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Utility Program Display – Simple!

Simply Select this to commission device Enter Device Tag Here. Device Address will be

selected automatically orcan be entered.

Page 17: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Future Supported Applications

Rosemount Radar Master

Fisher Valvelink

Page 18: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Product Positioning

Page 19: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Packaging

Interface Module

USB Cable

Fieldbus Lead Set

Installation CD

User Manual

Page 20: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Fieldbus Foundation Profile Coverage

USB Fieldbus Interface (with AMS Device

Manager) will initially conform to this profile

Page 21: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Summary

The previous Rosemount 770 Fieldbus Modem is now available as the USB Fieldbus Interface to customers.

Extend your laptop with AMS Device Manager beyond HART to FOUNDATION fieldbus devices

Page 22: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Where To Get More Information

AMS Device Manager Web Site

Page 23: A Quick and Easy Way to Connect to FOUNDATION fieldbus using Emerson’s USB Fieldbus Interface

Expected Release Date – Spring, 2012.


Recommended