GENERAL STRUCTURAL NOTES 5. CONCRETE AND CONCRETE REINFORCING 3. GENERAL 1. GENERAL NOTES 2. DESIGN CRITERIA 4. FOUNDATION A. DESIGN CODE: 2015 INTERNATIONAL BUILDING CODE WITH CITY OF OKLAHOMA CITY SUPPLEMENTS B. DESIGN LIVE LOADS ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 PSF (UNREDUCED) 1ST FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF 2ND FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF C. DEAD LOADS: ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 PSF CEILING COLLATERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PSF MECHANICAL/MISCELLANEOUS COLLATERAL . . . . . . . . . 5 PSF INSULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PSF FRAMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTUAL WEIGHT OF MATERIALS D. LATERAL LOADS: BASIC WIND SPEED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 MPH IMPORTANCE FACTOR (I) . . . . . . . . . . . . . . . . . . . . . 1.00 EXPOSURE C SEISMIC SEISMIC RISK CATEGORY. . . . . . . . . . . . . . . . . . . . III SEISMIC IMPORTANCE FACTOR (IE) . . . . . . . . . . . 1.25 SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . . . . . B SPECTRAL RESPONSE COEFFICIENTS . . . . . . . . . SDS = 0.210g SD1 = 0.087g SITE CLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C RESPONSE FACTOR . . . . . . . . . . . . . . . . . . . . . . . . 3.0 BASIC SEISMIC FORCE RESISTING SYSTEM: STEEL FRAMES NOT SPECIFICALLY DETAILED FOR SEISMIC ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE SEISMIC RESPONSE COEFFICIENT, Cs = 0.087 A. FINISHED FLOOR ELEVATION = 100'-0" IS EQUAL TO MEAN SEA ELEVATION = 1187.50 FT. B. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCY BETWEEN THE STRUCTURAL DRAWINGS AND THE ARCHITECTURAL DRAWINGS, OR OTHER CONSULTANT'S DRAWINGS. C. PLANS, SECTIONS AND DETAILS ARE NOT TO BE SCALED FOR DETERMINATION OF QUANTITIES, LENGTHS, OR FIT OF MATERIALS. D. VERIFY FLOOR SLAB DEPRESSIONS AND OFFSETS WITH ARCHITECTURAL DRAWINGS. E. THE SIZE AND LOCATION OF ALL MECHANICAL EQUIPMENT, EQUIPMENT PADS, AND ALL DUCT AND PIPE OPENINGS THROUGH SLABS AND WALLS SHALL BE VERIFIED WITH MECHANICAL AND ELECTRICAL DRAWINGS PRIOR TO FABRICATION OF MATERIALS. F. SHOP DRAWINGS SHALL BE ORIGINAL DRAWINGS PREPARED BY CONTRACTOR'S SUBCONTRACTOR, SUPPLIER, OR DISTRIBUTOR. REPRODUCTION OF STRUCTURAL CONTRACT DOCUMENTS AS ERECTION PLANS AND DETAILS SHALL NOT BE PERMITTED. G. SHOP DRAWINGS SHALL BE CHECKED BY GENERAL CONTRACTOR PRIOR TO BEING SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW. H. SHOP DRAWING SUBMITTALS SHALL CONTAIN THREE (3) PHOTOCOPIES OF EACH SHEET OF THE SUBMITTAL. ELECTRONIC COPIES (PDFs) OF EACH SUBMITTAL ARE ACCEPTABLE. I. CONTRACTOR SHALL BID AN ALLOWANCE FOR FABRICATION AND ERECTION OF AN ADDITIONAL 2,000 LBS OF STEEL TO BE USED AT THE DISCRETION OF THE ARCHITECT OR ENGINEER OF RECORD. ALL UNUSED PORTIONS SHALL BE REIMBURSED TO THE OWNER. A. CONCRETE MIX SCHEDULE: CONC STRENGTH AGG AGG SLUMP MAX CLASS (PSI) TYPE SIZE INCHES W/C A 3000 HRC 1 1/2" 5-7 0.64 B 3000 HRC 1" 3-5 0.64 NOTE: THE STRENGTH LISTED SHALL BE THE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS. THE REQUIRED AVERAGE COMPRESSIVE STRENGTH f'cr SHALL CONFORM TO A.C.I. STANDARD 318-14 NOTE: "HRC" REFERS TO HARDROCK CONCRETE HAVING AN AIR DRY UNIT WEIGHT OF APPROXIMATELY 145 POUNDS PER CUBIC FOOT (PCF). NOTE: WHERE WATER-TO-CEMENT RATIO IS NOT INDICATED ON THE DRAWINGS OR IN THE PROJECT SPECIFICATIONS, IT SHALL BE DETERMINED BY THE CONTRACTOR TO MEET OTHER REQUIREMENTS. B. CONCRETE USAGE SCHEDULE: DESCRIPTION CONC AIR OF USE CLASS CONTENT -FOOTINGS, WALLS A --- -INTERIOR SLABS-ON-GRADEB --- -EXTERIOR SLABS-ON-METAL DECK B 4%-6% C. CLEAR DISTANCES FROM CONCRETE SURFACES TO REINFORCING STEEL SHALL NOT BE LESS THAN AS FOLLOWS, UNLESS NOTED OTHERWISE: -FOOTINGS -3 INCHES ALL SIDES -WALLS (ELEVATOR PIT) -VERTICAL BARS CENTERED IN WALL -INTERIOR SLABS-ON-GRADE-2 INCHES FROM TOP OF SLAB D. CONCRETE REINFORCEMENT DETAILS SHALL CONFORM TO A.C.I. STANDARD 318-14, UNLESS NOTED OTHERWISE E. ALL REINFORCEMENT, #3 BARS AND LARGER, SHALL BE ASTM A615, GR 60 F. LAP ALL REINFORCING BARS 45 BAR DIAMETERS, UNLESS NOTED OTHERWISE G. PROVIDE CORNER BARS IN BOTH FACES OF ALL FOOTINGS AS REQUIRED EXTENDED A MINIMUM OF 45 BAR DIAMETERS IN EACH DIRECTION. QUANTITY, SIZE AND SPACING OF CORNER BARS SHALL BE EQUAL TO QUANTITY, SIZE AND SPACING OF HORIZONTAL REINFORCING BARS WITH WHICH THEY LAP, EXCEPT THAT MAXIMUM CORNER BAR SIZE SHALL BE #6. H. REINFORCING SHALL BE ADEQUATELY SUPPORTED USING CHAIRS, BOLSTERS OR PRECAST CONCRETE BRICKS HAVING MINIMUM COMPRESSIVE STRENGTH EQUAL TO OR GREATER THAN THE CONCRETE. USE BOLSTERS OR OTHER SPACING DEVICES AS REQUIRED TO MAINTAIN PROPER SIDE CLEARANCES BETWEEN FORMS AND REINFORCING BARS. I. EXTERIOR SLABS SHALL SLOPE AWAY FROM THE BUILDING 1/8" PER FOOT, UNLESS DIRECTED OTHERWISE BY THE ARCHITECT OR CIVIL ENGINEER. J. DO NOT WET PLACE DOWELS, ANCHOR BOLTS OR ANY EMBEDDED ITEMS INTO THE CONCRETE. USE TEMPLATES AS REQUIRED FOR ANCHOR BOLTS. K. DO NOT WELD REINFORCING BARS UNLESS BARS ARE PER ASTM A706. L. DO NOT HEAT AND BEND REINFORCING BARS. M. ALL BAR BENDING SHALL BE IN ACCORDANCE WITH A.C.I. 315-99 AND SP-66 (04), ACI DETAILING MANUAL. N. DO NOT FLAME CUT REINFORCING BARS. O. REFER MECHANICAL, ELECTRICAL AND AQUATICS DRAWINGS FOR EQUIPMENT PAD SIZES AND LOCATIONS. EQUIPMENT PADS SHALL BE PLACED ON TOP OF CONCRETE SLAB-ON-GRADE UNLESS NOTED OTHERWISE. MINIMUM EQUIPMENT PAD THICKNESS TO BE 4 INCHES UNLESS NOTED OTHERWISE ON MECHANICAL, ELECTRICAL OR AQUATICS DRAWINGS. REINFORCE EQUIPMENT PAD WITH #4 AT 12 INCHES ON CENTER EACH WAY. PROVIDE 2 INCH CLEARANCE BETWEEN TOP OF EQUIPMENT PAD AND TOP OF REBAR. P. PROVIDE 3/4 INCH CHAMFER ON ALL EXPOSED CORNERS AND EDGES, UNLESS NOTED OTHERWISE ON THE ARCHITECTURAL DRAWINGS. A. THE STRUCTURAL DRAWINGS ARE INTENDED TO BE USED CONCURRENTLY WITH THE ARCHITECTURAL DRAWINGS. IF ANY DISCREPANCY EXISTS BETWEEN THE STRUCTURAL DOCUMENTS AND THE ARCHITECTURAL DOCUMENTS, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING WITH CONSTRUCTION. B. GENERAL NOTES ARE AN INTEGRAL PART OF THE CONSTRUCTION DOCUMENTS AND DESCRIBE CONDITIONS THAT APPLY GENERALLY THROUGHOUT THE STRUCTURAL DRAWINGS. C. THE STRUCTURE IS DESIGNED AS A STABLE UNIT AFTER ALL COMPONENTS ARE IN PLACE. THE CONTRACTOR SHALL PROVIDE TEMPORARILY BRACE THE STRUCTURAL COMPONENTS FOR LATERAL STABILITY UNTIL AFTER ALL PERMANENT BRACING SYSTEMS ARE COMPLETE. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING NECESSARY TO ENSURE THE STABILITY OF ANY AND ALL PARTS OF THE BUILDING DURING CONSTRUCTION. A. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS AND DESIGN VALUES GIVEN IN THE GEOTECHNICAL (SOILS) REPORT, AS FOLLOWS: SOILS REPORT BY: INTERTEK PSI DATE OF REPORT: 1-14-2020 REPORT NUMBER: 05471565 RECOMMENDED FOUNDATION TYPE: SHALLOW FOOTINGS BEARING STRATUM: 2'-2" MINIMUM OF COMPACTED NON-EXPANSIVE STRUCTURAL FILL UNDER INTERIOR SLABS ALLOWABLE SOIL BEARING CAPACITY: 3,200 PSF FOR SPREAD FOOTINGS 2,500 PSF FOR CONTINUOUS FOOTINGS NOTE: A COPY OF THE SOILS REPORT IS AVAILABLE FROM THE ARCHITECT B. GRANULAR FILL SHALL BE UNWASHED SIZE NO. 10 (SCREENINGS) PER ASTM D448, LATEST EDITION, HAVING A NOMINAL AGGREGATE SIZE NO. 4 (4.75mm) AND PERCENTAGES OF PARTICLE SIZES PASSING THRU A NO. 4 SIEVE IN ACCORDANCE WITH TABLE 1 OF D448: 3/8" (9.5mm) 100% NO. 4 (4.75mm) 85% TO 100% NO. 100 (150micrometers) 10% TO 30% ODOT TYPE "A" SCREENINGS ARE ACCEPTABLE. C. THE SOIL AT THE BOTTOM OF ALL FOOTING EXCAVATIONS SHALL BE INSPECTED BY A QUALIFIED GEOTECHNICAL ENGINEER LICENSED IN THE STATE OF OKLAHOMA TO VERIFY THE SOIL MEETS OR EXCEEDS THE ALLOWABLE SOIL BEARING CAPACITY STATED ON THESE DRAWINGS. D. UTILITY TRENCHES UNDER THE BUILDING SHALL BE EFFECTIVELY SEALED TO RESTRICT WATER INTRUSION AND FLOW ALONG THE TRENCHES. PROVIDE A CLAY TRENCH PLUG EXTENDING AT LEAST 5 FEET BEYOND THE EDGE OF THE BUILDING IN ALL UTILITY TRENCHES UNDER THE BUILDING IN ACCORDANCE WITH THE GEOTECH REPORT. E. EARTH FORMED FOOTINGS ARE ACCEPTABLE AS LONG AS THE SIDES OF THE EXCAVATIONS CAN MAINTAIN A REASONABLY VERTICAL CUT WITHOUT SLOUGHING SOIL INTO THE EXCAVATION DURING REBAR PLACEMENT, DURING CONCRETE PLACEMENT AND THE EXCAVATION CAN MAINTAIN THE FOOTING SHAPE SPECIFIED ON THE DRAWINGS. 7. METAL ROOF DECK 12. STEEL JOISTS A. STEEL JOISTS SHALL MEET OR EXCEED THE LATEST STEEL JOIST INSTITUTE SPECIFICATIONS. JOIST SIZES AND TYPES ARE SHOWN ON THE FRAMING PLANS. B. ALL JOIST SEATS SHALL BE AS FOLLOWS UNLESS NOTED OR DETAILED OTHERWISE: 2 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT FLOORS AND 1/4" PER FOOT ROOF SLOPE 3 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE 5" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1/4" PER FOOT ROOF SLOPE 6 1/2" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE C. STEEL JOISTS SHALL BE FIELD WELDED TO SUPPORTING MEMBERS OR TO PRESET BEARING PLATES IN ACCORDANCE WITH S.J.I. MINIMUM REQUIREMENTS UNLESS NOTED OTHERWISE. D. ERECTION BOLTS CAN BE USED AT JOIST SEATS AT ERECTOR'S DISCRETION. ERECTION BOLTS SHALL BE REMOVED AFTER WELDING IS COMPLETE. E. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1. F. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1. G. ALL WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD TESTING METHODS AT THE INSPECTOR'S DISCRETION. H. JOIST FABRICATOR SHALL PROVIDE ALL BRIDGING AND X-BRIDGING REQUIRED IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE. I. BOTTOM CHORDS OF JOISTS FRAMING TO COLUMNS SHALL BE EXTENDED TO THE COLUMN UNLESS DETAILED OTHERWISE. J. DESIGN ROOF JOISTS FOR NET UPLIFT OF 10 PSF. PROVIDE UPLIFT BRIDGING PER SJI MINIMUMS 13. COLD FORMED METAL FRAMING - STRUCTURAL A. TYPICAL EXTERIOR COLD-FORMED STEEL STUDS SHALL BE 6 INCHES DEEP, 18 GA. CEE-STUDS CONFORMING TO A.I.S.I "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STRUCTURAL MEMBERS", UNLESS NOTED OTHERWISE. B. COLD-FORMED METAL FRAMING LEGEND: MINIMUM PROPERTIES SIZE AND GAUGE A.I.S.I DESIGNATION Ix (IN4) Sx (IN3) AREA (IN2) Rxx (IN) 6 IN, 18 GA. 600S162-43 2.316 0.767 0.447 2.277 6 IN, 16 GA 600S162-54 2.860 0.915 0.556 2.267 8 IN, 16 GA. 800S162-54 5.599 1.228 0.669 2.926 C. COLD-FORMED METAL FRAMING MATERIAL PROPERTIES: MEMBER MATERIAL GRADE Fy (ksi) SHOP COAT STUDS ASTM A653 C 50 GALVANIZE (G60) JOISTS ASTM A653 C 50 GALVANIZE (G60) TRACK ASTM A653 A 50 GALVANIZE (G60) D. VERTICAL SLIDE CLIP CONNECTORS, SLIP TRACK AND OTHER COLD-FORMED METAL CONNECTORS REQUIRED FOR THE PROJECT SHALL BE STANDARD SLIP TRACKS, BRIDGING, CONNECTORS AND CLIPS BY THE COLD-FORMED METAL FRAMING MANUFACTURER. E. APPROVED COLD-FORMED METAL MANUFACTURER: CLARKDIETRICH BUILDING SYSTEMS. F. PROVIDE COLD-FORMED METAL MANUFACTURER'S STANDARD SLIP TRACK TO ACCOMMODATE 1 1/4" MAXIMUM VERTICAL DEFLECTION. A. STEEL ROOF DECK SHALL BE 20 GA., TYPE B DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.201 IN4/FT, In=0.222 IN4/FT, Sn=0.247 IN3/FT, Sp=0.234 IN3/FT, D=1.5 IN B. METAL ROOF DECK CONNECTION SCHEDULE: MARK CONN AT CONN AT SIDELAP SUPPORTS PARALLEL EDGE CONN (W/N) SUPPORTS SPACING NO. PER SPAN I 36/7 12 INCHES 3 W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING. SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS. D. ROOF DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT 8. METAL FLOOR DECK A. STEEL FORM DECK SHALL BE 20 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.088 IN4/FT, In=0.088 IN4/FT, Sn=0.165 IN3/FT, Sp=0.167 IN3/FT, D=1.0 IN B. METAL ROOF DECK CONNECTION SCHEDULE: MARK CONN AT CONN AT SIDELAP SUPPORTS PARALLEL EDGE CONN (W/N) SUPPORTS SPACING NO. PER SPAN I 32/4 12 INCHES 2 W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING. SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS. D. FLOOR DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT 11 METAL DECK AT STAIR LANDING A. STEEL FORM DECK SHALL BE 22 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.024IN4/FT, In=0.024 IN4/FT, Sn=0.070 IN3/FT, Sp=0.070 IN3/FT, D=0.6 IN B. METAL ROOF DECK CONNECTION SCHEDULE: MARK CONN AT CONN AT SIDELAP SUPPORTS PARALLEL EDGE CONN (W/N) SUPPORTS SPACING NO. PER SPAN I 36/4 12 INCHES 2 W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING. SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS. D. FLOOR DECK AT STAIR LANDING SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT 14. CONCRETE MASONRY UNIT (STRUCTURAL) A. STRUCTURAL PROPERTIES: REQUIRED PRISM STRENGTH OF STRUCTURAL ASSEMBLY 1500 PSI REQUIRED 28-DAY COMPRESSIVE STRENGTH, MORTAR 1800 PSI REQUIRED 28-DAY COMPRESSIVE STRENGTH, GROUT 2000 PSI B. ALL LOAD BEARING CMU WALLS 8 INCH (NOMINAL), NORMAL WEIGHT BLOCK. C. TYPICAL VERTICAL REINFORCING IN SOLID GROUTED CELL FULL HEIGHT OF WALL: 8" CMU LOAD BEARING EXTERIOR SHEAR WALLS. . . . #5 VERT AT 24 INCHES O.C. 12" CMU LOAD BEARING EXTERIOR SHEAR WALLS . . . 2-#5 VERT AT 24 INCHES O.C. D. PROVIDE A.C.I. STANDARD HOOK IN BOND BEAM ALONG TOP OF WALLS FOR ALL VERTICAL BARS. E. PROVIDE TROUGH BLOCK BEAM (BOND BEAM) COURSES IN CMU WALLS FILLED WITH GROUT AT DOOR HEADS, WINDOW HEADS, BELOW WINDOWS, AND AT EVERY SIXTH COURSE REINFORCED WITH 2-#4 IN 8" CMU , UNLESS NOTED OTHERWISE. TRUSS TYPE JOINT REINFORCING AT 16" O.C. CAN BE SUBSTITUTED FOR BOND BEAMS. F. HORIZONTAL REINFORCING IN BOND BEAMS SHALL BE LAPPED 18 INCHES AT SPLICES. STAGGER SPLICES IN ADJACENT BARS AT LEAST 4'-0". G. VERTICAL REINFORCING IN GROUTED CELLS SHALL BE LAPPED 24 INCHES AND WIRE TIED AT SPLICES, UNLESS NOTED OTHERWISE. STAGGER SPLICES IN ADJACENT GROUTED CELLS. H. USE HECKMAN NO. 374 OR NO. 376 REBAR POSITIONERS OR APPROVED EQUAL TO LOCATE VERTICAL BARS IN CENTER OF CELLS. PROVIDE A MINIMUM OF 2 POSITIONERS PER 4 FT BAR LENGTHS. I. CONTRACTOR SHALL PROVIDE TEMPORARY LATERAL BRACING FOR ALL CMU WALLS UNTIL AFTER ROOF FRAMING AND ROOF DECK INSTALLATION IS COMPLETE. LATERAL BRACING SHALL BE ADEQUATE TO RESIST WIND AND ANY CONTRUCTION LOADS. 9. METAL ROOF DECK - AT POOL A. REFER PLANS FOR LOCATIONS OF TORIS ACOUSTICAL DECK. B. STEEL FORM DECK SHALL BE 20 GA., TYPE 7A ACOUSTIC, COMPOSITE DECK MANUFACTURED BY EPIC METALS, 11 TALBOT AVENUE, RANKIN, PA. MINIMUM SECTION PROPERTIES SHALL BE Ip=10.04 IN4/FT, Sn=1.66 IN3/FT, Sp=2.31 IN3/FT, D=7 INCHES. C. STEEL FORM DECK SHALL BE GALVANIZED, ETCHED WITH CHEMICAL CONVERSION COATING, STAGE ONE COATED WITH NATACOAT COMPATIBLE PRIMER, COATED WITH NATACOAT EXPOXY PRIMER. SEE PROJECT SPECIFICATION 053500 FOR ADDITIONAL INFORMATION. D. UPPER AND LOWER COMPONENTS SHALL BE FACTORY WELDED. NO MECHANICAL FASTENERS ALLOWED. E. AFTER ASSEMBLY OF UPPER AND LOWER COMPONENTS, THE EXPOSED SURFACES AND INTERIOR SURFACES OF PERFORATIONS SHALL RECEIVE A FACTORY APPLIED NATACOAT EPOXY PRIMER. THE NATACOAT SHALL BE OVEN CURED. SEE PROJECT SPECIFICATION 053500 FOR ADDITIONAL INFORMATION. F. DECK SHALL BE FASTENED TO STRUCTURAL FRAMING AS DIRECTED BY THE MANUFACTURER. G. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER. F. A FIELD APPLIED, 3 MIL COATING OF TNEMEC #113 SHALL BE APPLIED BY THE PAINTING SUBCONTRACTOR AFTER THE DECK IS INSTALLED. 6. STRUCTURAL STEEL A. STRUCTURAL STEEL SHALL MEET THE FOLLOWING ASTM SPECIFICATIONS: STRUCTURAL WIDE FLANGE SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A992 (Fy=50 ksi MIN) STRUCTURAL STEEL PLATES, CHANNELS, ANGLES . . . . . . . . . . . . . . . . . . . . ASTM A36 (Fy=36 ksi MIN) TUBULAR HSS SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A500, GR B OR ASTM A1085 COMMON BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A307 HIGH STRENGTH BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A325 B. BOLTS SHALL BE AS FOLLOWS: BEARING CONNECTIONS FOR STEEL CONNECTIONS . . . . . . . . . . . . . . . . . . . 3/4" DIA, HIGH STRENGTH ANCHOR BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM F1554, GRADE 36 ERECTION BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMMON C. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH A.I.S.C. "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL." D. ALL STRUCTURAL STEEL CONNECTIONS NOT DETAILED OR OTHERWISE NOTED SHALL BE STANDARD A.I.S.C. WELDED OR BOLTED USING ALLOWABLE STRESS DESIGN. DETAIL BOLTED OR WELDED CONNECTIONS TO SUPPORT ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY SHOWN IN THE ALLOWABLE UNIFORM LOAD TABLES OF THE A.I.S.C. MANUAL OF STEEL CONSTRUCTION. E. ALL BOLTS USED IN STEEL CONNECTIONS SHALL BE SNUG-TIGHT AS DEFINED BY A.I.S.C. UNLESS NOTED OTHERWISE. TENSION CONTROL BOLTS ARE AN ACCEPTABLE SUBSTITUTE AT THE ERECTOR'S DISCRETION. F. STANDARD HOLE SIZES SHALL BE USED FOR STEEL BEARING CONNECTIONS. SHORT SLOTTED HOLES ARE NOT ACCEPTABLE FOR BEARING CONNECTIONS. G. OVERSIZED HOLES ARE ACCEPTABLE FOR COLUMN BASEPLATES. WHEN OVERSIZED HOLES ARE USED FOR BASEPLATES, STEEL WASHERS SHALL BE USED BETWEEN THE NUTS AND BASEPLATE. THE WASHERS SHALL BE WELDED TO THE BASEPLATES. REFER ANCHOR BOLT DETAIL. H. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1. I. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1. J. ALL FIELD WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD TESTING METHODS AT THE INSPECTOR'S DISCRETION. K. ALL FIELD BOLTED CONNECTIONS SHALL BE VISUALLY INSPECTED BY A SPECIAL INSPECTOR TO VERIFY ALL BOLTS ARE INSTALLED AND TIGHTENED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. L. DO NOT FLAME CUT HOLES IN THE FIELD FOR FRAMED CONNECTIONS. M. ALL STEEL FRAMING, EMBED PLATES, CONNECTION PLATES ABOVE AND WITHIN THE POOL STORAGE, CHEMICAL STORAGE ROOMS AND POOL EQUIPMENT ROOM SHALL BE HOT-DIPPED GALVANIZED, EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT. ALL EMBED PLATES SHALL BE HOT-DIPPED GALVANIZED AND EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT AFTER WELDING. A. GLULAM BEAMS SHALL BE ARCHITECTURAL APPEARANCE. B. ALL BEAMS FOR THE NATATORIUM ROOF SHALL BE ALASKAN WHITE CEDAR 20F-V3. C. ALL BEAMS FOR THE LOBBY ROOF SHALL BE DOUGLAS-FIR 24F-V8. D. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE. E. SEE PROJECT SPECIFICATION 061813 FOR ADDITIONAL INFORMATION. 15. WOOD BEAMS 10. METAL ROOF DECK - AT LOBBY A. STEEL FORM DECK SHALL BE PAINTED 20 GA., 3 INCH TYPE N CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE I=0.964 IN4/FT, Sn=0.552 IN3/FT, Sp=0.501 IN3/FT, D=3 INCHES. B. ATTACH DECK TO WOOD FRAMING USING NO. 12 WOOD SCREWS AT EACH FLUTE WITH 2" MIN EMBEDMENT INTO BEAM. C. ATTACH DECK TO STEEL EDGE ANGLES USING 1/4" DIA SELF-DRILLING SCREWS AT 12 INCHES O.C.. PRE-DRILL AS REQUIRED. D. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER. GENERAL STRUCTURAL NOTES c These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects. Date: Submission: Drawing Title: No. Sheet No: Reviewed By: Drawn By: Designed By: Key Plan Executive Architect Copyright 2020 © Hornbeek Blatt Architects HORNBEEK BLATT 101 South Broadway, Suite 200 Edmond, Oklahoma 73034 405.340.8552 Telephone 405.340.5707 Fax www.hornbeekblatt.com r a h i t e c t s Project: THE ORIGINAL OF THIS DRAWING IS 30" X 42". 300 SPRUCE STREET SUITE 300 COLUMBUS, OHIO 43215 PHONE: (614) 461-4664 FAX: (614) 280-8881 Design Architect 7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit 9.25.2020 95% Progress Set RCD RD RCD OKC MAPS 3 HEALTH AND WELLNESS CENTER #3 Project Address: N. Lincoln Blvd. and NE 36th St. Oklahoma City, OK 73105 TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE A OKLAHOMA CITY, OK 73159 405.601.0662 405.848.9202 CERTIFICATE OF AUTHORITY NO. 3667 EXPIRES: JUNE 30, 2021 11.30.2020 Issued for Construction S1.1
Transcript
  • GENERAL STRUCTURAL NOTES

    5. CONCRETE AND CONCRETE REINFORCING

    3. GENERAL

    1. GENERAL NOTES

    2. DESIGN CRITERIA

    4. FOUNDATION

    A. DESIGN CODE: 2015 INTERNATIONAL BUILDING CODE WITH CITY OF OKLAHOMA CITY SUPPLEMENTS

    B. DESIGN LIVE LOADS

    ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 PSF (UNREDUCED)

    1ST FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF

    2ND FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF

    C. DEAD LOADS:

    ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 PSF

    CEILING COLLATERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PSF

    MECHANICAL/MISCELLANEOUS COLLATERAL . . . . . . . . . 5 PSF

    INSULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PSF

    FRAMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTUAL WEIGHT OF MATERIALS

    D. LATERAL LOADS:

    BASIC WIND SPEED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 MPH

    IMPORTANCE FACTOR (I) . . . . . . . . . . . . . . . . . . . . . 1.00

    EXPOSURE C

    SEISMIC

    SEISMIC RISK CATEGORY. . . . . . . . . . . . . . . . . . . . III

    SEISMIC IMPORTANCE FACTOR (IE) . . . . . . . . . . . 1.25

    SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . . . . . B

    SPECTRAL RESPONSE COEFFICIENTS . . . . . . . . . SDS = 0.210g

    SD1 = 0.087g

    SITE CLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C

    RESPONSE FACTOR . . . . . . . . . . . . . . . . . . . . . . . . 3.0

    BASIC SEISMIC FORCE RESISTING SYSTEM:

    STEEL FRAMES NOT SPECIFICALLY DETAILED FOR SEISMIC

    ANALYSIS PROCEDURE:

    EQUIVALENT LATERAL FORCE PROCEDURE

    SEISMIC RESPONSE COEFFICIENT, Cs = 0.087

    A. FINISHED FLOOR ELEVATION = 100'-0" IS EQUAL TO MEAN SEA ELEVATION = 1187.50 FT.

    B. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY UPON

    DISCOVERY OF ANY DISCREPANCY BETWEEN THE STRUCTURAL DRAWINGS AND THE ARCHITECTURAL DRAWINGS, OR

    OTHER CONSULTANT'S DRAWINGS.

    C. PLANS, SECTIONS AND DETAILS ARE NOT TO BE SCALED FOR DETERMINATION OF QUANTITIES, LENGTHS, OR FIT OF

    MATERIALS.

    D. VERIFY FLOOR SLAB DEPRESSIONS AND OFFSETS WITH ARCHITECTURAL DRAWINGS.

    E. THE SIZE AND LOCATION OF ALL MECHANICAL EQUIPMENT, EQUIPMENT PADS, AND ALL DUCT AND PIPE OPENINGS THROUGH

    SLABS AND WALLS SHALL BE VERIFIED WITH MECHANICAL AND ELECTRICAL DRAWINGS PRIOR TO FABRICATION OF

    MATERIALS.

    F. SHOP DRAWINGS SHALL BE ORIGINAL DRAWINGS PREPARED BY CONTRACTOR'S SUBCONTRACTOR, SUPPLIER, OR

    DISTRIBUTOR. REPRODUCTION OF STRUCTURAL CONTRACT DOCUMENTS AS ERECTION PLANS AND DETAILS SHALL NOT BE

    PERMITTED.

    G. SHOP DRAWINGS SHALL BE CHECKED BY GENERAL CONTRACTOR PRIOR TO BEING SUBMITTED TO THE STRUCTURAL

    ENGINEER FOR REVIEW.

    H. SHOP DRAWING SUBMITTALS SHALL CONTAIN THREE (3) PHOTOCOPIES OF EACH SHEET OF THE SUBMITTAL. ELECTRONIC

    COPIES (PDFs) OF EACH SUBMITTAL ARE ACCEPTABLE.

    I. CONTRACTOR SHALL BID AN ALLOWANCE FOR FABRICATION AND ERECTION OF AN ADDITIONAL 2,000 LBS OF STEEL TO BE

    USED AT THE DISCRETION OF THE ARCHITECT OR ENGINEER OF RECORD. ALL UNUSED PORTIONS SHALL BE REIMBURSED

    TO THE OWNER.

    A. CONCRETE MIX SCHEDULE:

    CONC STRENGTH AGG AGG SLUMP MAX

    CLASS (PSI) TYPE SIZE INCHES W/C

    A 3000 HRC 1 1/2" 5-7 0.64

    B 3000 HRC 1" 3-5 0.64

    NOTE: THE STRENGTH LISTED SHALL BE THE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS. THE REQUIRED AVERAGE

    COMPRESSIVE STRENGTH f'cr SHALL CONFORM TO A.C.I. STANDARD 318-14

    NOTE: "HRC" REFERS TO HARDROCK CONCRETE HAVING AN AIR DRY UNIT WEIGHT OF APPROXIMATELY 145 POUNDS PER

    CUBIC FOOT (PCF).

    NOTE: WHERE WATER-TO-CEMENT RATIO IS NOT INDICATED ON THE DRAWINGS OR IN THE PROJECT SPECIFICATIONS, IT

    SHALL BE DETERMINED BY THE CONTRACTOR TO MEET OTHER REQUIREMENTS.

    B. CONCRETE USAGE SCHEDULE:

    DESCRIPTION CONC AIR

    OF USE CLASS CONTENT

    -FOOTINGS, WALLS A ---

    -INTERIOR SLABS-ON-GRADEB ---

    -EXTERIOR SLABS-ON-METAL DECK B 4%-6%

    C. CLEAR DISTANCES FROM CONCRETE SURFACES TO REINFORCING STEEL SHALL NOT BE LESS THAN AS FOLLOWS, UNLESS

    NOTED OTHERWISE:

    -FOOTINGS -3 INCHES ALL SIDES

    -WALLS (ELEVATOR PIT) -VERTICAL BARS CENTERED IN WALL

    -INTERIOR SLABS-ON-GRADE-2 INCHES FROM TOP OF SLAB

    D. CONCRETE REINFORCEMENT DETAILS SHALL CONFORM TO A.C.I. STANDARD 318-14, UNLESS NOTED OTHERWISE

    E. ALL REINFORCEMENT, #3 BARS AND LARGER, SHALL BE ASTM A615, GR 60

    F. LAP ALL REINFORCING BARS 45 BAR DIAMETERS, UNLESS NOTED OTHERWISE

    G. PROVIDE CORNER BARS IN BOTH FACES OF ALL FOOTINGS AS REQUIRED EXTENDED A MINIMUM OF 45 BAR DIAMETERS IN

    EACH DIRECTION. QUANTITY, SIZE AND SPACING OF CORNER BARS SHALL BE EQUAL TO QUANTITY, SIZE AND SPACING OF

    HORIZONTAL REINFORCING BARS WITH WHICH THEY LAP, EXCEPT THAT MAXIMUM CORNER BAR SIZE SHALL BE #6.

    H. REINFORCING SHALL BE ADEQUATELY SUPPORTED USING CHAIRS, BOLSTERS OR PRECAST CONCRETE BRICKS HAVING

    MINIMUM COMPRESSIVE STRENGTH EQUAL TO OR GREATER THAN THE CONCRETE. USE BOLSTERS OR OTHER SPACING

    DEVICES AS REQUIRED TO MAINTAIN PROPER SIDE CLEARANCES BETWEEN FORMS AND REINFORCING BARS.

    I. EXTERIOR SLABS SHALL SLOPE AWAY FROM THE BUILDING 1/8" PER FOOT, UNLESS DIRECTED OTHERWISE BY THE

    ARCHITECT OR CIVIL ENGINEER.

    J. DO NOT WET PLACE DOWELS, ANCHOR BOLTS OR ANY EMBEDDED ITEMS INTO THE CONCRETE. USE TEMPLATES AS

    REQUIRED FOR ANCHOR BOLTS.

    K. DO NOT WELD REINFORCING BARS UNLESS BARS ARE PER ASTM A706.

    L. DO NOT HEAT AND BEND REINFORCING BARS.

    M. ALL BAR BENDING SHALL BE IN ACCORDANCE WITH A.C.I. 315-99 AND SP-66 (04), ACI DETAILING MANUAL.

    N. DO NOT FLAME CUT REINFORCING BARS.

    O. REFER MECHANICAL, ELECTRICAL AND AQUATICS DRAWINGS FOR EQUIPMENT PAD SIZES AND LOCATIONS. EQUIPMENT

    PADS SHALL BE PLACED ON TOP OF CONCRETE SLAB-ON-GRADE UNLESS NOTED OTHERWISE. MINIMUM EQUIPMENT PAD

    THICKNESS TO BE 4 INCHES UNLESS NOTED OTHERWISE ON MECHANICAL, ELECTRICAL OR AQUATICS DRAWINGS.

    REINFORCE EQUIPMENT PAD WITH #4 AT 12 INCHES ON CENTER EACH WAY. PROVIDE 2 INCH CLEARANCE BETWEEN TOP OF

    EQUIPMENT PAD AND TOP OF REBAR.

    P. PROVIDE 3/4 INCH CHAMFER ON ALL EXPOSED CORNERS AND EDGES, UNLESS NOTED OTHERWISE ON THE ARCHITECTURAL

    DRAWINGS.

    A. THE STRUCTURAL DRAWINGS ARE INTENDED TO BE USED CONCURRENTLY WITH THE ARCHITECTURAL DRAWINGS. IF ANY

    DISCREPANCY EXISTS BETWEEN THE STRUCTURAL DOCUMENTS AND THE ARCHITECTURAL DOCUMENTS, THE CONTRACTOR

    SHALL IMMEDIATELY NOTIFY THE ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING WITH CONSTRUCTION.

    B. GENERAL NOTES ARE AN INTEGRAL PART OF THE CONSTRUCTION DOCUMENTS AND DESCRIBE CONDITIONS THAT APPLY

    GENERALLY THROUGHOUT THE STRUCTURAL DRAWINGS.

    C. THE STRUCTURE IS DESIGNED AS A STABLE UNIT AFTER ALL COMPONENTS ARE IN PLACE. THE CONTRACTOR SHALL

    PROVIDE TEMPORARILY BRACE THE STRUCTURAL COMPONENTS FOR LATERAL STABILITY UNTIL AFTER ALL PERMANENT

    BRACING SYSTEMS ARE COMPLETE. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING

    NECESSARY TO ENSURE THE STABILITY OF ANY AND ALL PARTS OF THE BUILDING DURING CONSTRUCTION.

    A. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS AND DESIGN VALUES GIVEN IN THE GEOTECHNICAL (SOILS)

    REPORT, AS FOLLOWS:

    SOILS REPORT BY: INTERTEK PSI

    DATE OF REPORT: 1-14-2020

    REPORT NUMBER: 05471565

    RECOMMENDED FOUNDATION TYPE: SHALLOW FOOTINGS

    BEARING STRATUM: 2'-2" MINIMUM OF COMPACTED NON-EXPANSIVE

    STRUCTURAL FILL UNDER INTERIOR SLABS

    ALLOWABLE SOIL BEARING CAPACITY: 3,200 PSF FOR SPREAD FOOTINGS

    2,500 PSF FOR CONTINUOUS FOOTINGS

    NOTE: A COPY OF THE SOILS REPORT IS AVAILABLE FROM THE ARCHITECT

    B. GRANULAR FILL SHALL BE UNWASHED SIZE NO. 10 (SCREENINGS) PER ASTM D448, LATEST EDITION, HAVING A NOMINAL

    AGGREGATE SIZE NO. 4 (4.75mm) AND PERCENTAGES OF PARTICLE SIZES PASSING THRU A NO. 4 SIEVE IN ACCORDANCE

    WITH TABLE 1 OF D448:

    3/8" (9.5mm) 100%

    NO. 4 (4.75mm) 85% TO 100%

    NO. 100 (150micrometers) 10% TO 30%

    ODOT TYPE "A" SCREENINGS ARE ACCEPTABLE.

    C. THE SOIL AT THE BOTTOM OF ALL FOOTING EXCAVATIONS SHALL BE INSPECTED BY A QUALIFIED GEOTECHNICAL ENGINEER

    LICENSED IN THE STATE OF OKLAHOMA TO VERIFY THE SOIL MEETS OR EXCEEDS THE ALLOWABLE SOIL BEARING CAPACITY

    STATED ON THESE DRAWINGS.

    D. UTILITY TRENCHES UNDER THE BUILDING SHALL BE EFFECTIVELY SEALED TO RESTRICT WATER INTRUSION AND FLOW

    ALONG THE TRENCHES. PROVIDE A CLAY TRENCH PLUG EXTENDING AT LEAST 5 FEET BEYOND THE EDGE OF THE BUILDING

    IN ALL UTILITY TRENCHES UNDER THE BUILDING IN ACCORDANCE WITH THE GEOTECH REPORT.

    E. EARTH FORMED FOOTINGS ARE ACCEPTABLE AS LONG AS THE SIDES OF THE EXCAVATIONS CAN MAINTAIN A REASONABLY

    VERTICAL CUT WITHOUT SLOUGHING SOIL INTO THE EXCAVATION DURING REBAR PLACEMENT, DURING CONCRETE

    PLACEMENT AND THE EXCAVATION CAN MAINTAIN THE FOOTING SHAPE SPECIFIED ON THE DRAWINGS.

    7. METAL ROOF DECK

    12. STEEL JOISTS

    A. STEEL JOISTS SHALL MEET OR EXCEED THE LATEST STEEL JOIST INSTITUTE SPECIFICATIONS. JOIST SIZES AND TYPES ARE SHOWN ON

    THE FRAMING PLANS.

    B. ALL JOIST SEATS SHALL BE AS FOLLOWS UNLESS NOTED OR DETAILED OTHERWISE:

    2 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT FLOORS AND 1/4" PER FOOT ROOF SLOPE

    3 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE

    5" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1/4" PER FOOT ROOF SLOPE

    6 1/2" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE

    C. STEEL JOISTS SHALL BE FIELD WELDED TO SUPPORTING MEMBERS OR TO PRESET BEARING PLATES IN ACCORDANCE WITH S.J.I. MINIMUM

    REQUIREMENTS UNLESS NOTED OTHERWISE.

    D. ERECTION BOLTS CAN BE USED AT JOIST SEATS AT ERECTOR'S DISCRETION. ERECTION BOLTS SHALL BE REMOVED AFTER WELDING IS

    COMPLETE.

    E. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1.

    F. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE

    WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1.

    G. ALL WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD TESTING

    METHODS AT THE INSPECTOR'S DISCRETION.

    H. JOIST FABRICATOR SHALL PROVIDE ALL BRIDGING AND X-BRIDGING REQUIRED IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE.

    I. BOTTOM CHORDS OF JOISTS FRAMING TO COLUMNS SHALL BE EXTENDED TO THE COLUMN UNLESS DETAILED OTHERWISE.

    J. DESIGN ROOF JOISTS FOR NET UPLIFT OF 10 PSF. PROVIDE UPLIFT BRIDGING PER SJI MINIMUMS

    13. COLD FORMED METAL FRAMING - STRUCTURAL

    A. TYPICAL EXTERIOR COLD-FORMED STEEL STUDS SHALL BE 6 INCHES DEEP, 18 GA. CEE-STUDS CONFORMING TO A.I.S.I "SPECIFICATION

    FOR THE DESIGN OF COLD-FORMED STRUCTURAL MEMBERS", UNLESS NOTED OTHERWISE.

    B. COLD-FORMED METAL FRAMING LEGEND:

    MINIMUM PROPERTIES

    SIZE AND GAUGE A.I.S.I DESIGNATION Ix (IN4) Sx (IN3) AREA (IN2) Rxx (IN)

    6 IN, 18 GA. 600S162-43 2.316 0.767 0.447 2.277

    6 IN, 16 GA 600S162-54 2.860 0.915 0.556 2.267

    8 IN, 16 GA. 800S162-54 5.599 1.228 0.669 2.926

    C. COLD-FORMED METAL FRAMING MATERIAL PROPERTIES:

    MEMBER MATERIAL GRADE Fy (ksi) SHOP COAT

    STUDS ASTM A653 C 50 GALVANIZE (G60)

    JOISTS ASTM A653 C 50 GALVANIZE (G60)

    TRACK ASTM A653 A 50 GALVANIZE (G60)

    D. VERTICAL SLIDE CLIP CONNECTORS, SLIP TRACK AND OTHER COLD-FORMED METAL CONNECTORS REQUIRED FOR THE PROJECT SHALL BE

    STANDARD SLIP TRACKS, BRIDGING, CONNECTORS AND CLIPS BY THE COLD-FORMED METAL FRAMING MANUFACTURER.

    E. APPROVED COLD-FORMED METAL MANUFACTURER: CLARKDIETRICH BUILDING SYSTEMS.

    F. PROVIDE COLD-FORMED METAL MANUFACTURER'S STANDARD SLIP TRACK TO ACCOMMODATE 1 1/4" MAXIMUM VERTICAL DEFLECTION.

    A. STEEL ROOF DECK SHALL BE 20 GA., TYPE B DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION

    PROPERTIES SHALL BE Ip=0.201 IN4/FT, In=0.222 IN4/FT, Sn=0.247 IN3/FT, Sp=0.234 IN3/FT, D=1.5 IN

    B. METAL ROOF DECK CONNECTION SCHEDULE:

    MARK CONN AT CONN AT SIDELAP

    SUPPORTS PARALLEL EDGE CONN

    (W/N) SUPPORTS SPACING NO. PER SPAN

    I 36/7 12 INCHES 3

    W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET

    C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.

    SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.

    D. ROOF DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT

    8. METAL FLOOR DECK

    A. STEEL FORM DECK SHALL BE 20 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK

    INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.088 IN4/FT, In=0.088 IN4/FT, Sn=0.165 IN3/FT, Sp=0.167 IN3/FT, D=1.0 IN

    B. METAL ROOF DECK CONNECTION SCHEDULE:

    MARK CONN AT CONN AT SIDELAP

    SUPPORTS PARALLEL EDGE CONN

    (W/N) SUPPORTS SPACING NO. PER SPAN

    I 32/4 12 INCHES 2

    W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET

    C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.

    SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.

    D. FLOOR DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT

    11 METAL DECK AT STAIR LANDING

    A. STEEL FORM DECK SHALL BE 22 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK

    INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.024IN4/FT, In=0.024 IN4/FT, Sn=0.070 IN3/FT, Sp=0.070 IN3/FT, D=0.6 IN

    B. METAL ROOF DECK CONNECTION SCHEDULE:

    MARK CONN AT CONN AT SIDELAP

    SUPPORTS PARALLEL EDGE CONN

    (W/N) SUPPORTS SPACING NO. PER SPAN

    I 36/4 12 INCHES 2

    W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET

    C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.

    SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.

    D. FLOOR DECK AT STAIR LANDING SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT

    14. CONCRETE MASONRY UNIT (STRUCTURAL)

    A. STRUCTURAL PROPERTIES:

    REQUIRED PRISM STRENGTH OF STRUCTURAL ASSEMBLY 1500 PSI

    REQUIRED 28-DAY COMPRESSIVE STRENGTH, MORTAR 1800 PSI

    REQUIRED 28-DAY COMPRESSIVE STRENGTH, GROUT 2000 PSI

    B. ALL LOAD BEARING CMU WALLS 8 INCH (NOMINAL), NORMAL WEIGHT BLOCK.

    C. TYPICAL VERTICAL REINFORCING IN SOLID GROUTED CELL FULL HEIGHT OF WALL:

    8" CMU LOAD BEARING EXTERIOR SHEAR WALLS. . . . #5 VERT AT 24 INCHES O.C.

    12" CMU LOAD BEARING EXTERIOR SHEAR WALLS . . . 2-#5 VERT AT 24 INCHES O.C.

    D. PROVIDE A.C.I. STANDARD HOOK IN BOND BEAM ALONG TOP OF WALLS FOR ALL VERTICAL BARS.

    E. PROVIDE TROUGH BLOCK BEAM (BOND BEAM) COURSES IN CMU WALLS FILLED WITH GROUT AT DOOR HEADS, WINDOW HEADS,

    BELOW WINDOWS, AND AT EVERY SIXTH COURSE REINFORCED WITH 2-#4 IN 8" CMU , UNLESS NOTED OTHERWISE. TRUSS TYPE

    JOINT REINFORCING AT 16" O.C. CAN BE SUBSTITUTED FOR BOND BEAMS.

    F. HORIZONTAL REINFORCING IN BOND BEAMS SHALL BE LAPPED 18 INCHES AT SPLICES. STAGGER SPLICES IN ADJACENT BARS AT

    LEAST 4'-0".

    G. VERTICAL REINFORCING IN GROUTED CELLS SHALL BE LAPPED 24 INCHES AND WIRE TIED AT SPLICES, UNLESS NOTED

    OTHERWISE. STAGGER SPLICES IN ADJACENT GROUTED CELLS.

    H. USE HECKMAN NO. 374 OR NO. 376 REBAR POSITIONERS OR APPROVED EQUAL TO LOCATE VERTICAL BARS IN CENTER OF CELLS.

    PROVIDE A MINIMUM OF 2 POSITIONERS PER 4 FT BAR LENGTHS.

    I. CONTRACTOR SHALL PROVIDE TEMPORARY LATERAL BRACING FOR ALL CMU WALLS UNTIL AFTER ROOF FRAMING AND ROOF

    DECK INSTALLATION IS COMPLETE. LATERAL BRACING SHALL BE ADEQUATE TO RESIST WIND AND ANY CONTRUCTION LOADS.

    9. METAL ROOF DECK - AT POOL

    A. REFER PLANS FOR LOCATIONS OF TORIS ACOUSTICAL DECK.

    B. STEEL FORM DECK SHALL BE 20 GA., TYPE 7A ACOUSTIC, COMPOSITE DECK MANUFACTURED BY EPIC METALS, 11 TALBOT AVENUE, RANKIN,

    PA. MINIMUM SECTION PROPERTIES SHALL BE Ip=10.04 IN4/FT, Sn=1.66 IN3/FT, Sp=2.31 IN3/FT, D=7 INCHES.

    C. STEEL FORM DECK SHALL BE GALVANIZED, ETCHED WITH CHEMICAL CONVERSION COATING, STAGE ONE COATED WITH NATACOAT

    COMPATIBLE PRIMER, COATED WITH NATACOAT EXPOXY PRIMER. SEE PROJECT SPECIFICATION 053500 FOR ADDITIONAL INFORMATION.

    D. UPPER AND LOWER COMPONENTS SHALL BE FACTORY WELDED. NO MECHANICAL FASTENERS ALLOWED.

    E. AFTER ASSEMBLY OF UPPER AND LOWER COMPONENTS, THE EXPOSED SURFACES AND INTERIOR SURFACES OF PERFORATIONS SHALL

    RECEIVE A FACTORY APPLIED NATACOAT EPOXY PRIMER. THE NATACOAT SHALL BE OVEN CURED. SEE PROJECT SPECIFICATION 053500 FOR

    ADDITIONAL INFORMATION.

    F. DECK SHALL BE FASTENED TO STRUCTURAL FRAMING AS DIRECTED BY THE MANUFACTURER.

    G. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER.

    F. A FIELD APPLIED, 3 MIL COATING OF TNEMEC #113 SHALL BE APPLIED BY THE PAINTING SUBCONTRACTOR AFTER THE DECK IS INSTALLED.

    6. STRUCTURAL STEEL

    A. STRUCTURAL STEEL SHALL MEET THE FOLLOWING ASTM SPECIFICATIONS:

    STRUCTURAL WIDE FLANGE SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A992 (Fy=50 ksi MIN)

    STRUCTURAL STEEL PLATES, CHANNELS, ANGLES . . . . . . . . . . . . . . . . . . . . ASTM A36 (Fy=36 ksi MIN)

    TUBULAR HSS SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A500, GR B OR ASTM A1085

    COMMON BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A307

    HIGH STRENGTH BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A325

    B. BOLTS SHALL BE AS FOLLOWS:

    BEARING CONNECTIONS FOR STEEL CONNECTIONS . . . . . . . . . . . . . . . . . . . 3/4" DIA, HIGH STRENGTH

    ANCHOR BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM F1554, GRADE 36

    ERECTION BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMMON

    C. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH A.I.S.C. "SPECIFICATIONS FOR THE DESIGN, FABRICATION

    AND ERECTION OF STRUCTURAL STEEL."

    D. ALL STRUCTURAL STEEL CONNECTIONS NOT DETAILED OR OTHERWISE NOTED SHALL BE STANDARD A.I.S.C. WELDED OR BOLTED USING

    ALLOWABLE STRESS DESIGN. DETAIL BOLTED OR WELDED CONNECTIONS TO SUPPORT ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY

    SHOWN IN THE ALLOWABLE UNIFORM LOAD TABLES OF THE A.I.S.C. MANUAL OF STEEL CONSTRUCTION.

    E. ALL BOLTS USED IN STEEL CONNECTIONS SHALL BE SNUG-TIGHT AS DEFINED BY A.I.S.C. UNLESS NOTED OTHERWISE. TENSION CONTROL

    BOLTS ARE AN ACCEPTABLE SUBSTITUTE AT THE ERECTOR'S DISCRETION.

    F. STANDARD HOLE SIZES SHALL BE USED FOR STEEL BEARING CONNECTIONS. SHORT SLOTTED HOLES ARE NOT ACCEPTABLE FOR BEARING

    CONNECTIONS.

    G. OVERSIZED HOLES ARE ACCEPTABLE FOR COLUMN BASEPLATES. WHEN OVERSIZED HOLES ARE USED FOR BASEPLATES, STEEL WASHERS

    SHALL BE USED BETWEEN THE NUTS AND BASEPLATE. THE WASHERS SHALL BE WELDED TO THE BASEPLATES. REFER ANCHOR BOLT

    DETAIL.

    H. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1.

    I. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE

    WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1.

    J. ALL FIELD WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD

    TESTING METHODS AT THE INSPECTOR'S DISCRETION.

    K. ALL FIELD BOLTED CONNECTIONS SHALL BE VISUALLY INSPECTED BY A SPECIAL INSPECTOR TO VERIFY ALL BOLTS ARE INSTALLED AND

    TIGHTENED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.

    L. DO NOT FLAME CUT HOLES IN THE FIELD FOR FRAMED CONNECTIONS.

    M. ALL STEEL FRAMING, EMBED PLATES, CONNECTION PLATES ABOVE AND WITHIN THE POOL STORAGE, CHEMICAL STORAGE ROOMS AND

    POOL EQUIPMENT ROOM SHALL BE HOT-DIPPED GALVANIZED, EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT. ALL EMBED

    PLATES SHALL BE HOT-DIPPED GALVANIZED AND EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT AFTER WELDING.

    A. GLULAM BEAMS SHALL BE ARCHITECTURAL APPEARANCE.

    B. ALL BEAMS FOR THE NATATORIUM ROOF SHALL BE ALASKAN WHITE CEDAR 20F-V3.

    C. ALL BEAMS FOR THE LOBBY ROOF SHALL BE DOUGLAS-FIR 24F-V8.

    D. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE.

    E. SEE PROJECT SPECIFICATION 061813 FOR ADDITIONAL INFORMATION.

    15. WOOD BEAMS

    10. METAL ROOF DECK - AT LOBBY

    A. STEEL FORM DECK SHALL BE PAINTED 20 GA., 3 INCH TYPE N CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM

    SECTION PROPERTIES SHALL BE I=0.964 IN4/FT, Sn=0.552 IN3/FT, Sp=0.501 IN3/FT, D=3 INCHES.

    B. ATTACH DECK TO WOOD FRAMING USING NO. 12 WOOD SCREWS AT EACH FLUTE WITH 2" MIN EMBEDMENT INTO BEAM.

    C. ATTACH DECK TO STEEL EDGE ANGLES USING 1/4" DIA SELF-DRILLING SCREWS AT 12 INCHES O.C.. PRE-DRILL AS REQUIRED.

    D. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER.

    GENERAL STRUCTURAL

    NOTES

    c

    These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By:

    Drawn By:

    Designed By:

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200

    Edmond, Oklahoma 73034

    405.340.8552 Telephone

    405.340.5707 Fax

    www.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set

    8.25.2020 65% Progress Set

    8.31.2020 Issued for Permit

    9.25.2020 95% Progress Set

    RCD

    RD

    RCD

    OKC MAPS 3 HEALTH

    AND WELLNESS

    CENTER #3

    Project Address:

    N. Lincoln Blvd. and NE 36th St.

    Oklahoma City, OK 73105

    TRUMBLE DEAN, LLC

    8512 S. PENNSYLVANIA AVE., SUITE A

    OKLAHOMA CITY, OK 73159

    405.601.0662 405.848.9202

    CERTIFICATE OF AUTHORITY NO. 3667

    EXPIRES: JUNE 30, 2021

    11.30.2020 Issued for Construction

    S1.1

  • IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 17 OF THE 2015 INTERNATIONAL BUILDING CODE, THE

    OWNER SHALL SELECT QUALIFIED PERSONNEL TO PERFORM THE SPECIAL INSPECTIONS SHOWN IN THE

    SCHEDULES. THE CONTRACTOR SHALL PAY FOR THE SPECIAL INSPECTION SERVICES.

    THE SPECIAL INSPECTIONS DO NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY TO PERFORM THE

    WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL COOPERATE WITH THE

    SPECIAL INSPECTOR TO ALLOW ACCESS TO THE WORK FOR THE REQUIRED INSPECTIONS.

    THE CONTRACTOR SHALL NOTIFY THE INSPECTOR AT LEAST 24 HOURS IN ADVANCE OF ALL WORK REQUIRING

    INSPECTIONS.

    SITE VISITS MADE BY THE STRUCTURAL ENGINEER OF RECORD (E.O.R.) ARE NOT THE SAME AS SPECIAL

    INSPECTIONS IN ACCORDANCE WITH CHAPTER 17 OF THE 2015 IBC UNLESS A SEPARATE CONTRACT HAS BEEN

    MADE BETWEEN THE OWNER AND E.O.R. FOR THE E.O.R. TO PERFORM THE SPECIAL INSPECTIONS.

    THE SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION

    REPORTS TO THE BUILDING OFFICIAL, THE ARCHITECT AND ENGINEER OF RECORD. UNLESS OTHERWISE

    REQUIRED BY THE BUILDING OFFICIAL IN WRITING AT THE TIME THE BUILDING PERMIT IS ISSUED, THE SPECIAL

    INSPECTOR SHALL SUBMIT A FINAL REPORT OF SPECIAL INSPECTIONS TO THE BUILDING OFFICIAL. UNLESS

    NOTIFIED IN WRITING OTHERWISE, THE SPECIAL INSPECTOR SHALL SUBMIT MONTHLY WRITTEN INSPECTION

    REPORTS AND A COPY OF THE FINAL REPORT OF SPECIAL INSPECTIONS TO THE ARCHITECT AND ENGINEER OF

    RECORD. THE ARCHITECT SHALL PROVIDE A COPY OF THE FINAL REPORT OF SPECIAL INSPECTIONS TO THE

    OWNER. THE FINAL REPORT OF SPECIAL INSPECTIONS SHALL DOCUMENT THE COMPLETION OF ALL REQUIRED

    SPECIAL INSPECTIONS, TESTING AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE MONTHLY

    INSPECTION REPORTS. THE FINAL REPORT OF SPECIAL INSPECTIONS SHALL BE SUBMITTED PRIOR TO

    ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY.

    DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR

    CORRECTION. IF SUCH DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCY SHALL BE BROUGHT TO

    THE IMMEDIATE ATTENTION OF THE BUILDING OFFICIAL, THE ARCHITECT AND THE ENGINEER OF RECORD. THE

    MONTHLY INSPECTION REPORTS SHALL PROVIDE A DETAILED DESCRIPTION OF SUCH DISCREPANCIES AND

    THE CORRECTIONS MADE OR NOT MADE. THE DETAILED DESCRIPTION SHALL INCLUDE, BUT IS NOT LIMITED

    TO: THE NATURE OF DISCREPANCY, LOCATION OF THE DISCREPANCY WITH RESPECT TO GRID LINES,

    CORRECTIONS MADE, AND DOCUMENTATION OF ANY CONVERSATIONS MADE WITH THE BUILDING OFFICIAL,

    ARCHITECT AND ENGINEER OF RECORD TO OBTAIN APPROVAL FOR CORRECTIONS.

    STATEMENT OF SPECIAL INSPECTIONS

    SOILS AND FOUNDATIONS

    VERIFICATION AND INSPECTION

    IBC SECTION 1705.6, 1705.8

    VERIFY IMPORTED STRUCTURAL FILL MATERIAL SATISFIES

    REQUIREMENTS IN GEOTECH REPORT

    PRIOR TO PLACEMENT OF STRUCTURAL FILL, DETERMINE

    THAT THE SITE HAS BEEN PREPARED IN ACCORDANCE WITH

    PROJECT GEOTECH REPORT

    DURING PLACEMENT AND COMPACTION OF STRUCTURAL FILL,

    VERIFY MATERIAL BEING USED AND MAXIMUM LIFT

    THICKNESS COMPLIES WITH PROJECT GEOTECH REPORT

    TEST IN-PLACE DRY DENSITY OF COMPACTED FILL COMPLIES

    WITH PROJECT GEOTECH REPORT

    VERIFY EXCAVATIONS FOR FOOTINGS ARE INTO PROPER

    BEARING STRATA AS DESCRIBED IN PROJECT GEOTECH

    REPORT.

    VERIFY EXCAVATIONS FOR FOOTINGS ARE AT THE PROPER

    DEPTH AND WIDTH PER DRAWINGS

    CONTINUOUS PERIODIC INSPECTOR

    IDENTIFICATION

    X

    X

    X

    X

    X

    PE/GE, EIT OR

    ETT

    PE/GE, EIT OR

    ETT

    PE/GE, EIT OR

    ETT

    PE/GE, EIT OR

    ETT

    PE/GE, EIT OR

    ETT

    CAST-IN-PLACE CONCRETE

    VERIFICATION AND INSPECTION

    IBC SECTION 1705.3

    INSPECT FORMWORK FOR SHAPE, LOCATION AND

    DIMENSIONS OF CONCRETE MEMBER BEING FORMED

    INSPECT REINFORCING STEEL SIZES AND PLACEMENT ARE IN

    ACCORDANCE WITH PROJECT DRAWINGS. VERIFY CLEAR

    COVER. VERIFY REBAR IS ADEQUATELY SUPPORTED TO

    PREVENT DISPLACEMENT DURING CONCRETE POUR

    VERIFY ANY WELDED REBAR IS ASTM A706.

    INSPECT ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED

    ITEMS PRIOR TO CONCRETE PLACEMENT. VERIFY SIZES,

    LOCATIONS AND LENGTH OF EMBEDMENT. VERIFY ITEMS ARE

    SECURED TO AVOID DISPLACEMENT DURING CONCRETE

    POUR

    VERIFY USE OF APPROVED MIX DESIGN FOR COMPONENTS

    BEING CONSTRUCTED

    VERIFY WATER ADDED TO MIX AT JOB SITE DOES NOT RESULT

    IN TOTAL WATER CONTENT BEING EXCEEDED PER APPROVED

    MIX DESIGN

    SAMPLE FRESH CONCRETE PER PROJECT SPECIFICATIONS

    VERIFY COLD WEATHER AND HOT WEATHER PROCEDURES

    ARE FOLLOWED

    OBSERVE CONCRETE PLACEMENT AND VERIFY PROPER

    APPLICATION TECHNIQUES USED

    VERIFY CURING TECHNIQUES AND MATERIALS SATISFY

    PROJECT SPECIFICATIONS AND APPROVED SUBMITTALS

    CONTINUOUS PERIODIC INSPECTOR

    IDENTIFICATION

    X

    PE/SE OR EIT

    X

    X AWS-CWI

    X

    ACI-CFTT OR

    ACI-STT

    X

    X

    X

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    X

    X

    X

    QUALIFICATIONS OF INSPECTORS AND TESTING TECHNICIANS

    THE QUALIFICATIONS OF ALL PERSONNEL PERFORMING SPECIAL INSPECTION AND TESTING ACTIVITIES

    ARE SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL. THE CREDENTIALS OF ALL INSPECTORS

    AND TESTING TECHNICIANS SHALL BE PROVIDED IF REQUESTED. THE OWNER SHALL PROVIDE THE

    IDENTITY OF THE SPECIAL INSPECTOR IF REQUESTED BY THE BUILDING OFFICIAL. IF REQUESTED, THE

    SPECIAL INSPECTOR SHALL PROVIDE THE IDENTITIES OF ALL PERSONNEL ACTING ON THE SPECIAL

    INSPECTOR'S BEHALF DURING THE PROJECT.

    THE FOLLOWING DESIGNATIONS APPEAR BELOW THE INSPECTOR IDENTIFICATION ON THE SCHEDULES

    AND INDICATE THAT THE INDIVIDUAL PERFORMING THE STIPULATED INSPECTION OR TEST HAS A

    SPECIFIC CERTIFICATION OR LICENSE.

    PE/SE STRUCTURAL ENGINEER - A PROFESSIONAL ENGINEER LICENSED IN THE

    STATE OF OKLAHOMA SPECIALIZING IN THE DESIGN OF BUILDING

    STRUCTURES.

    PE/GE GEOTECHNICAL ENGINEER - A PROFESSIONAL ENGINEER LICENSED IN THE

    STATE OF OKLAHOMA SPECIALIZING IN SOIL MECHANICS AND FOUNDATIONS.

    EIT ENGINEER-IN-TRAINING - A GRADUATE ENGINEER WHO HAS PASSED THE

    FUNDAMENTALS OF ENGINEERING EXAMINATION AND IS REGISTERED WITH

    THE STATE OF OKLAHOMA AS AN EIT.

    ETT EXPERIENCED TESTING TECHNICIAN - AN EXPERIENCED TESTING TECHNICIAN

    WITH A MINIMUM 5 YEARS EXPERIENCE WITH THE STIPULATED TEST OR

    INSPECTION.

    AMERICAN CONCRETE INSTITUTE (ACI) CERTIFICATION

    ACI-CFTT CONCRETE FIELD TESTING TECHNICIAN - GRADE 1

    ACI-CCI CONCRETE CONSTRUCTION INSPECTOR

    ACI-LTT LABORATORY TESTING TECHNICIAN - GRADE 1 & 2

    ACI-STT STRENGTH TESTING TECHNICIAN

    AMERICAN WELDING SOCIETY (AWS) CERTIFICATION

    AWS-CWI CERTIFIED WELDING INSPECTOR

    AWS/AISC-SSI CERTIFIED STRUCTURAL STEEL INSPECTOR

    INTERNATIONAL CODE COUNCIL (ICC) CERTIFICATION

    ICC-SMSI STRUCTURAL MASONRY SPECIAL INSPECTOR

    ICC-SWSI STRUCTURAL STEEL AND WELDING SPECIAL INSPECTOR

    ICC-SFSI SPRAY-APPLIED FIREPROOFING SPECIAL INSPECTOR

    ICC-PCSI PRESTRESSED CONCRETE SPECIAL INSPECTOR

    ICC-RCSI REINFORCED CONCRETE SPECIAL INSPECTOR

    NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET)

    NICET-CT CONCRETE TECHNICIAN - LEVELS I, II, III & IV

    NICET-ST SOILS TECHNICIAN - LEVELS I, II, III & IV

    NICET-GET GEOTECHNICAL ENGINEERING TECHNICIAN - LEVELS I, II, III & IV

    WHERE FABRICATION OF STRUCTURAL LOAD BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON

    THE PREMISES OF A FABRICTOR'S SHOP, THE SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE

    REQUIRED BY IBC SECTION 1704.2.5 AND AS REQUIRED ELSEWHERE IN THE BUILDING CODE.

    WELDING INSPECTION SHALL BE IN COMPLIANCE WITH AWSD1.1. THE BASIS FOR THE WELDING INSPECTOR

    SHALL BE PER AWS D1.1.

    SPECIAL INSPECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE QUALITY ASSURANCE

    INSPECTION REQUIREMENTS OF AISC 360, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS.

    STRUCTURAL MASONRY CONSTRUCTION SHALL BE INSPECTED AND VERIFIED IN ACCORDANCE WITH TMS402,

    BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES.

    STRUCTURAL STEEL CONSTRUCTION

    VERIFICATION AND INSPECTION

    IBC SECTION 1705.2

    MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS

    CONTINUOUS PERIODIC INSPECTOR

    IDENTIFICATION

    XPE/SE OR EITIDENTIFICATION MARKINGS CONFORM TO ASTM

    STANDARDS SPECIFIED IN PROJECT CONSTRUCTION

    DOCUMENTS

    MANUFACTURER'S CERTIFICATE OF COMPLIANCEX

    PE/SE OR EIT

    INSPECT BOLTED, BEARING-TYPE CONNECTIONS

    IDENTIFICATION MARKINGS TO CONFORM TO ASTM

    STANDARDS SPECIFIED IN PROJECT CONSTRUCTION

    DOCUMENTS AND APPROVED STEEL SHOP DRAWINGS

    MANUFACTURER'S CERTIFIED TEST REPORTS

    INSPECT ANCHOR BOLTS PRIOR TO STEEL ERECTION TO VERIFY

    BOLTS ARE UNDAMAGED AND READY FOR BASEPLATES

    MATERIAL VERIFICATION OF STRUCTURAL STEEL. REVIEW SUBMITTALS FROM FABRICATOR

    IDENTIFICATION MARKINGS TO CONFORM TO AWS

    SPECIFICATION IN PROJECT CONSTRUCTION DOCUMENTS

    - REVIEW PACKAGING

    VERIFY FILLER MATERIALS ARE STORED PROPERLY ON

    SITE

    MATERIAL VERIFICATION OF WELD FILLER MATERIALS

    COMPLETE AND PARTIAL PENETRATION GROOVE WELDS

    SINGLE PASS FILLET WELDS LESS THAN 5/16"

    INSPECTION OF SHOP AND FIELD WELDS FOR STRUCTURAL STEEL

    DETAILS FOR BRACING AND STIFFENING

    MEMBER LOCATIONS

    APPLICATION OF JOINT DETAILS AT EACH CONNECTION

    INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE WITH PROJECT CONSTRUCTION DOCUMENTS AND

    APPROVED STEEL SHOP DRAWINGS

    INSPECTION OF METAL FLOOR AND ROOF DECK SUPPORT AND SIDELAP CONNECTIONS

    VERIFY FASTENER SIZES AND LOCATIONS

    VERIFY FASTENERS INSTALLED PER MANUFACTURER'S

    REQUIREMENTS AND PER PROJECT CONSTRUCTION

    DOCUMENTS

    XPE/SE OR EIT

    XPE/SE OR EIT OR

    AWS/AISC-SSI OR

    ICC-SBSI

    PE/SE OR EIT

    PE/SE OR EIT

    AWS-CWI

    X

    X

    X

    XPE/SE OR EIT

    XPE/SE OR EIT

    XPE/SE OR EIT

    XPE/SE OR EIT

    XPE/SE OR EIT

    AWS-CWI

    AWS-CWI

    AWS-CWI

    INSTALLATION OF OPEN-WEB STEEL JOISTS

    END CONNECTION - WELDED OR BOLTED

    BRIDGING - HORIZONTAL OR DIAGONAL

    VERIFY BRIDGING INSTALLED IN

    ACCORDANCE WITH APPROVED JOIST

    SUBMITTALS

    STRUCTURAL STEEL FABRICATOR INSPECTIONS

    VERIFICATION AND INSPECTION

    IBC SECTION 1705.2

    FABRICATOR'S PROCEDURES:

    AISC CERTIFICATION - FABRICATOR TO PROVIDE COPY OF

    CERTIFICATION TO INSPECTOR FOR REVIEW.

    -OR-

    FABRICATOR TO PROVIDE COPY OF WRITTEN PROCEDURAL

    AND QUALITY CONTROL MANUALS AND PERIODIC AUDITING OF

    FABRICATION PRACTICES BY AN APPROVED SPECIAL

    INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE

    APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF

    COMPLIANCE TO THE BUILDING CODE OFFICIAL AND OWNER

    STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE

    WITH THE PROJECT CONSTRUCTION DOCUMENTS.

    -OR-

    SPECIAL INSPECTION OF THE FABRICATED ITEMS BY OWNER'S

    SPECIAL INSPECTOR DURING FABRICATION. INSPECTIONS TO

    INCLUDE SHOP WELDED AND BOLTED ITEMS.

    CONTINUOUS PERIODIC INSPECTOR

    IDENTIFICATION

    PE/SE OR EITX

    X

    PE/GE, EIT OR

    ETT

    LOAD BEARING CONCRETE MASONRY UNITS (CMU) LEVEL 1

    VERIFICATION AND INSPECTION

    IBC SECTION 1705.4

    AS MASONRY CONSTRUCTION BEGINS, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE.

    CONTINUOUS PERIODIC INSPECTOR

    IDENTIFICATION

    X

    AWS-CWI

    X

    X

    X

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    VERIFICATION OF f'm PRIOR TO CONSTRUCTION

    PROPRTIONS OF SITE-PREPARED MORTAR.

    REVIEW CERTIFICATIONS FOR GROUT AND MORTAR

    PRODUCTS TO ENSURE COMPLIANCE WITH PROJECT

    SPECIFICATIONS

    CONSTRUCTION OF MORTAR JOINTS

    LOCATION OF REINFORCEMENT, CONNECTORS AND

    ANCHORAGES. VERIFY REBAR POSITIONERS ARE USED

    AT LEAST 2 PER EACH LENGTH OF REBAR BETWEEN

    SPLICES

    DURING CONSTRUCTION THE INSPECTION PROGRAM SHALL VERIFY

    SIZE AND LOCATION OF STRUCTURAL ELEMENTS

    TYPE, SIZE AND LOCATION OF ANCHORS, INCLUDING

    OTHER DETAILS OF ANCHORAGE OF MASONRY TO

    STRUCTURAL MEMBERS, FRAMES OR OTHER

    CONSTRUCTION.

    SPECIFIED SIZE, GRADE AND TYPE OF RENFORCEMENT

    AND ANCHOR BOLTS

    WELDING OF REINFORCING BARS AND THAT BARS ARE

    WELDABLE PER ASTM A706.

    COLD-WEATHER PLACEMENT AND PROTECTION OF CMU

    IN TEMPERATURES BELOW 40 DEG. F AND HOT-WEATHER

    PLACEMENT AND PROTECTION OF CMU IN

    TEMPERATURES ABOVE 90 DEG F.

    PRIOR TO GROUTING, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE:

    GROUT SPACE IS CLEAN AND FREE OF OBSTRUCTIONS

    THAT PREVENT FREE FLOW OF GROUT IN VERTICAL AND

    HORIZONTAL CELLS CONTAINING REINFORCING

    PLACEMENT OF REINFORCEMENT, CONNECTORS AND

    ANCHORAGES.

    PROPORTIONS OF SITE-PREPARED GROUT

    CONSTRUCTION OF MORTAR JOINTS

    GROUT PLACEMENT SHALL BE VERIFIED TO ENSURE

    COMPLIANCE WITH CODE AND CONSTRUCTION DOCUMENT

    PROVISIONS.

    XPE/SE OR EIT

    XPE/SE OR EIT

    XPE/SE OR EIT

    PE/SE OR EIT

    PE/SE OR EIT

    X

    PE/SE OR EIT

    X

    PE/SE OR EIT

    X

    PE/SE OR EIT

    X

    PE/SE OR EIT

    X

    X

    X

    X

    X

    X

    X

    XPE/SE OR EIT

    XPE/SE OR EIT

    XPE/SE OR EIT

    c

    These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By:

    Drawn By:

    Designed By:

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200

    Edmond, Oklahoma 73034

    405.340.8552 Telephone

    405.340.5707 Fax

    www.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set

    8.25.2020 65% Progress Set

    8.31.2020 Issued for Permit

    9.25.2020 95% Progress Set

    RCD

    RD

    RCD

    OKC MAPS 3 HEALTH

    AND WELLNESS

    CENTER #3

    Project Address:

    N. Lincoln Blvd. and NE 36th St.

    Oklahoma City, OK 73105

    TRUMBLE DEAN, LLC

    8512 S. PENNSYLVANIA AVE., SUITE A

    OKLAHOMA CITY, OK 73159

    405.601.0662 405.848.9202

    CERTIFICATE OF AUTHORITY NO. 3667

    EXPIRES: JUNE 30, 2021

    11.30.2020 Issued for Construction

    STATEMENT OF SPECIAL

    INSPECTIONS

    S1.2

  • 1

    1

    M

    K.2

    K

    J J

    G G

    F F

    E

    D

    C

    B

    A

    A

    2

    2

    3

    3

    3.4

    3.4

    4

    4

    5

    5

    6

    6

    7

    7

    8

    8

    L

    E.8

    9

    9

    10 11 12 13 14 15 16 FF

    FF

    GG

    GGEE

    DDCCBB

    AA

    H

    P

    Q

    R

    S

    T

    U

    V

    K.1

    K.4 K.4

    11.811.2 12.3

    16' - 5 1/2"

    3' - 11"

    21' - 8"

    6' - 6 1/2" 8

    ' - 3 1/4"

    17' - 5 3/4"

    6' - 9 3/8"

    4' - 6 1/8"

    24' - 0"

    7' - 2 3/4"

    24' - 0"24' - 0"10' - 9 1/4"19' - 4"24' - 0 3/4"

    2' - 5 3/4"

    16' - 10 5/8"6' - 10"26' - 8"15' - 6 5/8"10' - 5 1/8"

    3' - 4 1/8"

    3' - 3 5/8"

    8' -

    11 5

    /8"

    9' -

    9 3/

    4"5'

    - 0"

    20' -

    3 7

    /8"

    2' -

    0"

    6' -

    0 3/

    4"11

    ' - 2

    3/4

    "26

    ' - 0

    "5'

    - 10

    "6'

    - 7

    1/2"

    23' -

    10

    1/2"

    22' -

    7 3

    /4"

    13' - 8"

    15' - 9 7/8"

    15' - 9 7/8"

    6' - 3 1/8"

    25' - 9"

    22' - 5 1/8"

    5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)

    DD.3

    11.910.9

    A.13/

    8"

    5S3.1

    2S3.2

    POOL FOUNDATION- REFER ARCH AND AQUATICS FOR SIZEAND LOCATION

    EDGE OF SLAB ONGRADE AT POOL - TYP

    1S3.1

    F1

    F1

    F3F3 F4

    F4

    C1F3 F3 F8 F3

    F4

    F9

    F3

    SEE SHEET S3.1 FOR FOOTING SCHEDULESEE SHEET S6.1 FOR COLUMN SCHEDULE

    2S3.1

    3S3.1

    4S3.1

    6S3.1

    7S3.1

    F5F5 F5 F5

    F6F6F6F6

    F5 F5 F5

    8S3.1

    TYP

    TYP

    F5

    F9

    F1 F1

    F1F3

    F1

    F3

    F1 F4

    F5

    F1 F1

    F7 F7

    F1 F1

    F1 F1

    19' -

    9 5

    /8"

    14' -

    9 7

    /8"

    3' - 9 1/8" 17' - 0 1/8" 3' - 8 3/4"

    F3F3 F3 F3

    F2

    F3

    F3

    F3F3F3

    F2

    F3

    F3

    F1

    F3

    F3F3

    F3

    F3F2

    F3F1

    F1

    F3

    F3

    F1

    F3F3

    F3

    F1

    F3

    F3

    F1

    F1

    F3

    F1

    F3F39

    S3.1

    1S3.2

    STEP FOOTING DOWN

    STEP FOOTING DOWN

    3S3.2

    TYPTYP

    TYP

    TYPTYP

    TYP

    TYP

    8' - 4 1/4"

    7' -

    5 3/

    4"

    105.00°

    12S3.2

    11S3.2

    16.1

    8" LOAD BEARING CMU- TYP. REFER ARCH FOR WALL LOCATIONS. REFER S7.2 FOR WALL ELEVATION ALONG GRID FF

    E.9

    8.1

    8.1

    1' - 6 1/2"

    5 1/

    4"

    13S3.2

    F2

    C46 C48C54

    C5 C5

    C56

    C5

    C5

    C4

    C55

    C4 C55

    C4

    C2

    C11

    C10

    C11

    C9

    C4

    C3

    C3

    F2

    C6C6

    C57

    C13 C12 C12 C13

    C14 C15

    C5 C5

    C7C8

    C16 C17 C18 C21 C22

    1' - 0"19' - 9 1/4"

    C25 C26

    C19 C20

    C23 C24

    C27 C28

    C58

    C30 C29

    C59

    C31

    C34

    C32

    C34

    C34

    C35

    C36

    C37

    C75

    C38

    C42C41

    C40

    C39

    C33

    C70

    C33

    C43

    C44

    C76

    C60

    C60

    LOAD BEARING SHEAR WALL WITH 6" x 18 GA STUDS AT 16" O.C. TYP

    5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)

    C52

    C51

    C2

    STEP BACK EDGE OF SLAB1"

    RECESS SLAB 1 1/2" -REFER ARCH FOR LOCATION AND EXTENTS - TYP

    RECESS SLAB 1 1/2" -REFER ARCH FOR LOCATION AND EXTENTS - TYP

    TRENCH DRAIN -REFER ARCH AND MECH. SLOPE SLAB TO DRAIN TYP

    RECESS SLAB 3/8" -REFER ARCH FOR LOCATION AND EXTENTS - TYP

    20' - 3"

    F10

    HSS 4X4X5/16 FOR STAIR STRINGER SUPPORT - 2 PLACESCOLUMN C64

    C12x20.7 STRINGER TYP -REFER ARCH FOR STAIR DIMENSIONS

    D.2

    3' -

    11 1

    /4"

    HSS 12x2x1/4 STRINGER TYP - REFER ARCH FOR STAIR DIMENSIONS

    4.5

    13' - 5"

    F1

    F1HSS 4X4X5/16 FOR STAIR STRINGER SUPPORT - 2 PLACESCOLUMN C65

    12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.1 FOR WALL ELEVATION

    SURGE TANK - REFER AQUATICS FOR SIZE AND LOCATION OF TANK AND FLOOR ACCESS HATCH

    S.7

    AA.9

    13' - 4"

    1S3.6

    8.3 8.8 9.3 10.1 12.8 13.2 13.8

    8' - 10 1/8"12' - 0"12' - 0"12' - 0"6' - 2" 11' - 1 3/4" 12' - 0" 12' - 0"

    F1F1

    F1 F1

    L.6

    D.6

    P.3

    9' - 8 7/8"

    1S3.4

    2S3.4

    3S3.4

    4S3.4

    TYP

    5S3.4

    6S3.4

    7S3.4

    TYP8

    S3.4

    TYP

    9S3.4

    10S3.4TYP

    3S3.1

    1S3.2

    TYP

    3S3.1

    3S3.1

    7S3.4

    TYP

    8S3.4

    5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)

    C66C67 C68 C69

    F3

    C70

    F3C37

    F3C73

    TYP

    TYP

    TYP3

    S3.1

    3S3.1

    3S3.1

    3S3.1

    3S3.1

    9S3.4

    10S3.4

    TYP

    10S3.4

    TYP

    REFER 4/S3.2 FOR B10 BASEPLATE AT DIAGONAL BRACE - REFER 4/S6.3 FOR BRACE FRAME ELEVATION

    SONOTUBE BLOCKOUT AT COLUMN - TYP SIZE AT CONTRACTOR DISCRETION

    TYP2' - 6"

    4' - 8"

    F1

    C74

    F1

    C74

    8S3.1

    TYP

    SONOTUBE BLOCKOUT AT COLUMN - TYP SIZE AT CONTRACTOR DISCRETION

    1S3.5

    TYP

    TYP2' - 3"

    2S3.5

    3S3.5

    TYP

    TYP1' - 6"

    9" 2' -

    3"

    1' - 6"

    2' - 3"

    1' - 6"2' - 3"

    7S3.5

    TYP

    8S3.5

    TYP

    TYP2' - 0"

    TYP

    2' -

    0"

    9S3.5

    OFFSET COLUMN 1" EAST FROM GRID BB AT GRIDS S.7 AND T

    TYP

    10S3.5

    1S3.5

    TYP

    1S3.5

    TYP

    1S3.5

    TYP

    TYP

    11S3.5

    TYP

    TYP

    TYP

    8S3.4

    TYP

    12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.1 FOR WALL ELEVATION

    12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.2 FOR WALL ELEVATION

    12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.2 FOR WALL ELEVATION

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J. S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.S.J.S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    S.J.

    2S3.6

    2S3.6

    3S3.6

    6S5.4

    15' - 6 5/8"10' - 5 1/8"3' - 4 1/8"

    11.3 11.7

    C77

    C77 C77

    C77

    5' - 0" 5' - 0"

    RECESS SLAB 1 3/4" -REFER ARCH FOR LOCATION AND EXTENTS - TYP

    5S3.6

    4S3.6

    TYP

    TYP

    7S4.3

    HSS 4x4x5/16 COLUMN FOR GUIDE RAIL SUPPORT - TYP 3 PLACES COORDINATE LOCATIONS WITH ELEVATOR MFRREFER 6/S4.2

    c

    These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By: RCDDrawn By: RDDesigned By: RCD

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction

    11/2

    5/20

    20 7

    :06:

    50 A

    M

    S2.1

    FOUNDATION PLAN

    OKC MAPS 3 HEALTHAND WELLNESSCENTER #3

    3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105

    Proj

    ect N

    umbe

    r - O

    KC M

    APS

    3 H

    EALT

    H A

    ND

    WEL

    LNES

    S C

    ENTE

    R #

    3

    3/32" = 1'-0"1FOUNDATION PLAN

    TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021

  • N N

    1

    1

    M

    K.2

    K K

    J

    GG

    FF

    E

    D

    C

    B

    A

    A

    2

    2

    3

    3

    3.4

    3.4

    4

    4

    5

    5

    6

    6

    7

    7

    8

    8

    L

    E.8

    9

    9

    10 11 12 13 14 15 16 FF

    FFGG

    EE

    DDCCBB

    AA

    H

    P

    Q

    R

    S

    T

    U

    V

    K.4 K.4

    11.811.2 12.3

    3' - 3 5/8"

    3' - 4 1/8"

    10' - 5 1/8" 15' - 6 5/8" 26' - 8" 6' - 10" 16' - 10 5/8"

    2' - 5 3/4"

    24' - 0 3/4" 19' - 4" 10' - 9 1/4" 24' - 0" 24' - 0" 24' - 0" 4' - 6 1/8"6' - 9 3/8"

    17' - 5 3/4"

    16' - 5 1/2"

    3' - 11"

    21' - 8"

    6' - 6 1/2" 8

    ' - 3 1/4"

    22' - 5 1/8"

    25' - 9"

    6' - 3 1/8"

    13' - 4"

    15' - 9 7/8"

    13' - 8"

    8' -

    11 5

    /8"

    9' -

    9 3/

    4"5'

    - 0"

    20' -

    3 7

    /8"

    2' -

    0"

    6' -

    0 3/

    4"11

    ' - 2

    3/4

    "26

    ' - 0

    "5'

    - 10

    "6'

    - 7

    1/2"

    14' -

    9 7

    /8"

    9' -

    0 5/

    8"22

    ' - 7

    3/4

    "8'

    - 9

    1/2"

    W27

    X84

    W27

    X84

    W27

    X84

    W27

    X84

    W18

    X35

    W18

    X35

    W27X84W27X84 W27X84

    W27X84W27X84

    W27

    X84

    W27

    X84

    W27X84 W27X84

    W18X35

    W18X35

    W18

    X35

    W24

    X55

    W18

    X35

    W18

    X35

    W24X55

    W18

    X35

    W18

    X35

    W18

    X35

    W24

    X55

    W18X35 W18X35 W18X35

    W18

    X35

    W24X55

    W27X84

    W27

    X84

    W27X84

    W27X84

    W18X35W24X55

    W27

    X84

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W21X44

    W21X44

    W27

    X84

    W24X55

    W24X55

    W21

    X44

    W18

    X35

    W14

    X22

    W14

    X22

    W14

    X22

    W14X22

    HSS

    10X6

    X3/8

    HSS

    10X6

    X3/8

    W14

    X22

    W18X35

    W24

    X55

    W24

    X55

    W16X31

    W16X31

    W16X31

    W18X35

    W14X22

    W12X19

    W14X22

    W18X35

    W30X90

    W16X31

    W16X31

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W12X19

    W12X19

    10K1

    W14X22

    W12X19

    W12X19

    W12X19

    W14X22

    W18X35

    W30X90

    W24X62

    W16X31

    W16X31

    W24X62

    W14X22

    W30X90

    W14X22

    W14X22

    W16X31

    28LH09

    28LH09

    28LH09

    W14X22

    W24X68

    W18X35

    W14X22

    W24X55

    W24X55

    W14X22

    W14X22

    W14X22

    W18X35

    W16X31

    14K1

    14K1

    W12X19

    W18X35

    W24X55

    W24X55

    W24X55

    W27

    X84

    W24X55W24X55 W14X22

    W24X55

    W18X35 W14X22

    W24X55

    28K10

    28K10

    28K10

    28K10

    28K10

    28K10

    5x30

    .25

    5x30

    .25

    5x30

    .25

    5x30

    .25

    5x30

    .25

    4" CONCRETE SLAB ON 1.0C x 20 GA. METAL DECK WITH #3 AT 18" O.C. EACH WAY. FINISHED FLOOR ELEV = 115'-4"

    3" TYPE N x 20 GAUGE GALVANIZED METAL DECK ABOVE THE GLULAMS

    7" EPIC TORIS ACOUSTICAL DECK WITH NATACOAT AND BAGGED INSULATION

    1 1/2" x 20 GA WIDE RIB GALVANIZED METAL ROOF DECK - TYP UNLESS NOTED OTHERWISE

    DIAGONAL BRACE -REFER 2/S6.3

    DIAGONAL BRACE AND WIND GIRTS -REFER 1/S6.3

    DIAGONAL BRACES -REFER 1/S6.2

    DIAGONAL BRACES AND WIND GIRTS -REFER 1/S6.5

    DIAGONAL BRACES AND WIND GIRTS -REFER 3/S6.2

    DD.3

    5x30

    .25

    6.75

    x48.

    125

    6.75

    x48.

    125

    6.75

    x48.

    125

    6.75

    x48.

    125

    W14

    X22

    W14X22

    W14X22

    W14X22

    11.910.9

    A.1

    1 1/2" x 20 GA. WIDE RIB GALVANIZED METAL ROOF DECK

    DECK BRG EL = 117'-10 1/2"

    DECK BRG EL = 120'-11 1/4"

    DECK BRG EL =122'-7 3/4" TYP

    DECK BRG EL = 113'-8 /4"

    SLOPE 1/4:1

    2

    SLOPE 1:12

    SLO

    PE 1

    :12

    SLOPE 1:12SLOPE 3/4:12

    SLOPE 1:12

    DECK BRG EL = 115'-6"

    DECK BRG EL = 115'-8"

    DECK BRG EL =113'-8 3/4"

    SLOPE 1/4:1

    2

    DECK BRG EL = 120'-11 1/4 (HIGH)DECK BRG EL = 116'-3 1/16" (LOW)

    DECK BRG EL =116'-8 1/4" (LOW)DECK BRG EL = 122'-9 1/4" (HIGH)

    DEC

    K BR

    G E

    L =

    119'

    -11

    3/8"

    HSS16X8X3/8 DIAGONALCOLUMN TYP 8 PLACESREFER 1/S5.6 AND 2/S5.6

    1S5.1

    TYP

    2S5.1

    3S5.1

    4S5.1

    TYP

    TYP

    TYP

    5S5.1

    6S5.1

    TYP

    7S5.1

    TYP

    LOW

    HIG

    H

    LOW

    LOW

    LOW

    HIG

    H

    HIG

    H

    HIG

    H

    HIG

    H

    LOW

    TYP

    HIG

    HLO

    W

    HIGH

    LOW

    8S5.1

    8' - 4 1/4"13' - 11 1/4"14' - 0"14' - 0"14' - 0"

    14' - 0"

    DECK BRG EL = 124'-4 3/8"

    DECK BRG EL (HIGH) = 128'-6 7/8"

    DECK BRG EL = 115'-8" TYP

    TYP

    1S4.1

    2S4.1

    TYPTYP

    4S4.1

    TYP

    5S4.1

    6S4.1

    7S4.1

    TYP

    TYP

    8S4.1

    TYP

    9S4.1

    1S4.2

    2S4.2

    3S4.2

    TYP

    DECK BRG EL = 115'-8"

    TOP OF CMU WALLAND DECK BRG EL = 115'-8"

    DECK BRG EL = 116'-3"

    SLOPE 1/4:1

    2

    SLOPE 1/4:12

    16.1

    TOP OF CMU WALLEL = 115'-8"

    DECK BRG EL = 116'-1 1/2" TYPAT LOW ROOF

    SLO

    PE 1

    /4:1

    2

    E.9

    8.1

    8.1

    5x30

    .25

    1' - 6 1/2"3/

    8"5

    1/4"

    C61 C49

    C45

    C45

    C49

    C45

    C45

    C45

    C61

    C62 C47 C63

    C63

    C49

    C49

    C50

    6"x16 GA RAFTER AT 24" O.C. TYP

    1 1/2" x 20 GA WIDE RIB GALVANIZED METAL ROOF DECK - TYP UNLESS NOTED OTHERWISE

    SLOPE 3:12

    TOP OF WALLEL = 109'-10 1/4"

    TOP OF WALLEL = 107'-10 1/4"

    SEE SHEET S6.1 FOR COLUMN SCHEDULE

    W14X22

    W27X84

    DECK BRG EL = 116'-3 1/8"

    ALL STEEL BEAMS ABOVE POOL STORAGE,CHEMICAL STORAGE ROOMS AND POOL EQUIPMENT ROOM SHALL HAVE A ZINC RICHPRIMER, PAINTED WITH AN EPOXY INTERMEDIATECOAT AND A POLYURETHANE TOP COAT. ALLEMBED PLATES SHALL BE GALVANIZED AND PAINTED WITH EPOXY PAINT AND POLYURETHANETOP COAT AFTER WELDING.

    1' - 0"

    (HIGH)

    W18X35 (LO

    W)

    DIAGONAL BRACES -REFER 2/S6.2

    DIAGONAL BRACE -REFER 4/S6.3

    DIAGONAL BRACES -REFER 3/S6.3

    DIAGONAL BRACES -REFER 6/S6.3

    DIAGONAL BRACE -REFER 5/S6.3

    DIAGONAL BRACE -REFER 5/S6.3

    DIAGONAL BRACE -REFER 7/S6.3

    W18X35

    W18

    X35

    W24

    X55

    W27X84 W27X84

    W14X22

    W14X22

    4.5

    14K3 AT 2'-6" O.C.14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C.

    14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C.

    W14X22 AT 2'-6" O.C. W12X19 AT 2'-6" O.C. W14X22 AT 2'-6" O.C.

    28K6 AT 2'-6" O.C.

    14K3 AT 2'-6" O.C.

    28K6 AT 2'-6" O.C.

    28K6 AT 2'-6" O.C.

    20K4 AT 2'-6" O.C.

    20K4 AT 2'-6" O.C.

    T.O.S. EL = 115'-4" TYP

    W12X19

    W14X22 AT W14X22 AT W14X22 AT 2'-6" O.C.

    2'-6" O.C.2'-6" O.C.

    W14X22 AT 2'-6" O.C. W14X22 AT 2'-6" O.C. W14X22 AT 2'-6" O.C.

    5 SP

    AT

    5'-0

    " O.C

    .

    5' -

    11"

    20LH04 AT 5'-0" O

    .C.

    20LH06 AT 5'-0" O

    .C.

    5' - 6"

    3' - 4 1/2"

    20LH06 AT 5'-0" O

    .C.

    5' - 0"

    5' - 3"2 SP AT 5'-0"

    24K6 AT 5'-0" O.C

    .

    24K6 AT 5'-0" O.C

    .

    4' - 11 3/4"5' - 0 1/4"

    14K1 AT 5'-0" O.C

    .

    14K1 AT

    5'-0" O.C

    .

    5' - 0"5' - 0"

    5' - 0"

    10K1 AT 5'-0" O.C

    .5' - 0"

    3' - 3"10K1 AT 5'-0" O

    .C.

    EQEQ

    S.7W14X

    22

    W14X22

    W14X22

    14K1

    14K1

    14K114K1

    14K1

    14K1

    14K1

    14K1

    AA.9

    DECK BRG EL = 123'-5 5/8"AT HIGH ROOF

    DECK BRG EL= 126'-11 7/32"

    8.3 8.8 9.3 10.1 12.8 13.2 13.8

    HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON GRID WITH +/- 1/4" TOLERANCE. MAXIMUM ALLOWABLE SWEEP = 1/2" FOR BEAMS SUPPORTING LOUVER SCREEN POSTS.

    L4x4x1/4 BRACE - TYP EACH POST

    HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON CMU WALL WITH +/- 1/4" TOLERANCE FROM CENTER OF WALL. NOTE THAT WALL IS NOT CENTERED ON THE GRID

    HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON GRID A.1 WITH +/- 1/4" TOLERANCE. MAXIMUM ALLOWABLE SWEEP = 3/8" FOR BEAMS SUPPORTING LOUVER SCREEN POSTS.

    8S4.2

    4S5.2

    TYP

    6S5.2

    28K10

    TYP7

    S5.2

    TYP

    8S5.2

    TYP

    9S4.2

    L.6

    K.3K.3

    D.6

    P.3

    W16X31

    9' - 8 7/8"

    15' - 9 7/8"

    W14X22

    WIND GIRTS -REFER 3/S6.5

    WIND GIRTS -REFER 1/S6.6

    WIND GIRTS -REFER 1/S6.6

    WIND GIRT -REFER 4/S6.5

    WIND GIRT -REFER 3/S6.6

    17' -

    5 1

    /4"

    15' -

    3"

    S2.41

    S2.42

    6S5.4

    S2.51

    S2.52

    S2.32

    7S5.4

    8S5.4

    1S4.3

    8S4.1

    OPPHAND

    2S4.3

    3S4.3

    TYP

    4S4.3

    5S4.3

    6S4.3

    7S4.3

    TYP

    TYP

    S2.43

    6' -

    1 1/

    2"

    S2.45

    S2.44

    W21X44

    2'-6" O.C.

    W14X22 AT

    C78 - REFER 3/S6.6

    REFER 3/S6.6 FOR WINDOW GIRTS

    DIAGONAL BRACES -REFER 2/S6.5

    DIAGONAL BRACE -REFER 5/S6.5

    15S4.4

    C71

    C72

    c

    These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By: RCDDrawn By: RDDesigned By: RCD

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction

    11/2

    5/20

    20 7

    :06:

    19 A

    M

    S2.2

    SECOND FLOORAND LOW ROOFFRAMING PLAN

    OKC MAPS 3 HEALTHAND WELLNESSCENTER #3

    3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105

    Proj

    ect N

    umbe

    r - O

    KC M

    APS

    3 H

    EALT

    H A

    ND

    WEL

    LNES

    S C

    ENTE

    R #

    3

    3/32" = 1'-0"1SECOND FLOOR AND LOW ROOFFRAMING PLAN

    TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021

  • N

    1

    1

    M

    K.2

    K

    G

    F

    D

    B

    2

    2

    3

    3

    3.4

    3.4

    4

    4

    5

    5

    6

    6

    7

    7

    8

    8

    L

    3' - 3 5/8"

    3' - 4 1/8"

    10' - 5 1/8" 15' - 6 5/8" 26' - 8" 6' - 10" 16' - 10 5/8"

    2' - 5 3/4"

    14' -

    9 3

    /4"

    31' -

    10"

    23' -

    10

    1/2"

    22' -

    7 3

    /4"

    8' -

    9 1/

    2"

    W16

    X31

    W16

    X31

    W16

    X31

    W16X31 W16X31 W16X31

    W21

    X50

    W21

    X50

    W21

    X50

    W16

    X31

    W21

    X50

    W21

    X50

    W21

    X50

    W21

    X50

    W27

    X84

    W16X31 W16X31W18X35

    W18X35 W18X35 W18X35HSS

    6X6X

    3/8

    HSS6X6X3/8

    HSS

    6X6X

    3/8

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    44LH12

    W12X19

    W12X19

    W14

    X22

    W14

    X22

    DIAGONAL BRACES -REFER 2/S6.2

    DIAGONAL BRACES -REFER 1/S6.2

    DIAGONAL BRACES -REFER 4/S6.2

    44LH12

    A.1

    1S5.2

    1 1/2" WIDE RIB x 20 GAUGE GALVANIZED METAL ROOF DECK

    SLOPE 1:12

    HIG

    H

    LOW

    HIG

    H

    W14

    X22

    LOW

    TYP

    2S5.2

    E.9

    44SLH14 - REFER 1/S5.5 FOR LOAD DIAGRAM

    8.1

    8.1

    SEE SHEET S6.1 FOR COLUMN SCHEDULE

    C53

    DECK BRG EL = 135'-4 3/4"TYP

    DECK BRG EL = 128'-6 1/2" TYP

    1 1/2" WIDE RIB x 20 GAUGE GALVANIZED METAL ROOF DECK DECK BRG EL = 124'-8" (LOW)

    DIAGONAL BRACES -REFER 2/S6.2

    HSS 8X6X5/16 AT 2'-6" O.C. -6 PLACESHSS 6X6X5/16 AT 2'-6" O.C. -

    5 PLACESHSS 6X6X5/16 AT 5'-0" O.C. -10 PLACES

    W14X22

    8' -

    11 5

    /8"

    22' -

    9 1

    /8"

    11' -

    2 3

    /4"

    6' -

    7 1/

    2"3'

    - 7

    1/2"

    18 S

    P AT

    5'-0

    " O.C

    .4'

    - 11

    1/8

    "5'

    - 1

    1/4"

    7 SP

    AT

    5'-0

    " O.C

    .5'

    - 0"

    10' -

    2 1

    /2"

    L.6

    K.3

    D.6

    TYP

    TYP

    2S5.5

    3S5.5

    TYP

    J J

    K.1 K.1

    K.4 K.4

    11.811.2

    12.311.9

    11.9

    10.9

    10.9

    2S5.6

    10.1

    1S5.6

    11.3

    11.3

    11.7

    11.7

    2S5.6

    5 SP

    ACES

    AT

    5'-0

    " O.C

    .

    HSS16X8X3/8

    HSS16X8X3/8

    HSS10X4X3/8

    HSS10X4X3/8

    HSS10X4X3/8

    HSS10X4X3/8

    HSS16X8X3/8

    HSS10X4X3/8

    HSS10X4X3/8

    HSS16X8X3/8

    HSS10X4X3/8

    HSS10X4X3/8

    2' -

    2"5

    SPAC

    ES A

    T 5'

    -0" O

    .C.

    HSS

    16X8

    X3/8

    HSS

    16X8

    X3/8

    SLOPE 1:12

    c

    These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By: RCDDrawn By: RDDesigned By: RCD

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction

    11/2

    5/20

    20 7

    :00:

    07 A

    M

    S2.3

    ROOF FRAMINGPLANS

    OKC MAPS 3 HEALTHAND WELLNESSCENTER #3

    3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105

    Proj

    ect N

    umbe

    r - O

    KC M

    APS

    3 H

    EALT

    H A

    ND

    WEL

    LNES

    S C

    ENTE

    R #

    3

    1/8" = 1'-0"1ROOF FRAMING PLAN - GYMNASIUM

    TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021

    1/4" = 1'-0"2ENLARGED - ENTRY ROOF FRAMINGPLAN

  • F F

    D

    C C

    8

    8

    9

    9

    10

    10

    A.1 A.1

    3S5.2

    8.1

    8.1

    6S5.3

    W14X22 W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22 W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W14X22

    W18

    X35

    W24

    X68

    W14X22 (LOW)

    W24X55 (HIGH)

    W14X22 (LOW) DECK BRG EL = 116'-1 1/2"

    W24X55 (HIGH)

    W18

    X35

    W18

    X35

    DECK BRG EL = 115'-8"

    DECK BRG EL = 126'-11 7/32" (HIGH) AT GRID 8.1

    DECK BRG EL = 123'-5 5/8" (HIGH) AT FACE OF CMU

    SLO

    PE 1

    /4:1

    2

    SLOPE 1:12 (HIGH)

    1S5.3

    9S5.2

    2S5.3

    TYP

    3S5.3

    4S5.3

    TYP

    TYP

    5S5.3

    TYP

    7S5.3

    8S5.3

    RTU-1

    RTU-5

    RTU-4

    RTU-3RTU-2

    4' -

    2 1/

    8"5'

    - 0"

    5' -

    0"4'

    - 7

    1/4"

    5' -

    0"2'

    - 8

    1/2"

    5' -

    0"5'

    - 0"

    5' -

    0"5'

    - 0"

    5' - 0" TYP

    3' -

    8 1/

    8"

    REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING - TYP

    F F

    A A

    16

    16

    FF

    FF

    9S5.1

    16.1

    2S5.4

    W8X21

    W8X21

    W14X22

    W14X22

    26K6

    26K6

    26K6

    W30X90

    4' -

    6 3/

    8"5'

    - 0"

    5' -

    0"4'

    - 7"

    5' -

    0 1/

    2"

    5' -

    0"5'

    - 0"

    4' -

    6 3/

    4"6'

    - 3

    7/8"

    SLOPE 1/4:12

    RTU -8

    REFER MECH FOR DUCT PENETRATION SIZES AND LOCATIONS

    REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING

    W8X21

    9S5.1

    9S5.1

    10S5.1

    TYP

    11S5.1

    TYP

    12S5.1

    TYP

    1S5.4

    TYP

    TYP

    W16X313

    S5.4

    TYP

    4S5.4

    5S5.4

    G G

    F

    E

    6

    6

    7

    7 8

    E.8

    8.1

    W12

    X19

    W12

    X19

    W24

    X55 W

    12X1

    9

    W24X55

    W18

    X35

    W18

    X35

    W24X55

    W18X35

    W12X19 AT 2'-6" O.C.2' - 0" 2' - 10 1/4"

    2' - 9" 2' - 8" 2' - 9"

    4S4.3

    8S4.3

    8S4.3

    SIM

    W12X19

    9S4.3

    10S4.3

    2' - 6"2' - 6"2' - 6"

    11S4.3

    1S4.4

    2S4.4

    3S4.4

    3S4.4

    TYP

    TYP

    W24

    X55

    W18

    X35

    5X30

    .25

    GLU

    LAM

    W18

    X35

    4S4.4

    W18

    X35

    1S4.1

    SIM

    B

    6

    W14

    X22

    W14

    X22

    W27

    X84

    W21X44

    14K3

    14K3

    W14X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W24X55

    8' -

    9"

    8' - 9"

    3' - 0" 2' - 6"

    2' - 6" 3' - 0" 1' - 9" 2' - 6"

    14' -

    9"

    9S4.4

    8S4.4

    8S4.4

    OPPHAND

    W21X44

    14S4.4

    8S4.3SIM

    1

    D

    B

    2 3 3.4

    W24X55W14X22

    W14

    X22

    28K6

    28K6

    W27

    X84

    W14

    X22

    W14

    X22 W14

    X22

    W18X35

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14

    X22

    W14X22 1' - 11" 2' - 6" 2' - 4"

    1' - 10 1/8" 1' - 11 1/4"2' - 8 1/8"

    3' - 0"

    2' - 6"

    5' - 6 3/4"3' - 8 1/4"

    9' -

    3"

    14' - 9"HSS

    10X6

    X3/8

    T.

    O.S

    . EL

    = 11

    5'-4

    "

    W12

    X19

    3' - 4 1/8"

    5S4.4

    TYP

    6S4.4

    7S4.4

    8S4.4

    9S4.4

    8S4.4

    OPPHAND

    10S4.4

    11S4.4

    12S4.4

    13S4.4

    c

    These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By: RCDDrawn By: RDDesigned By: RCD

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction

    11/2

    5/20

    20 6

    :57:

    17 A

    M

    S2.4

    ENLARGEDFRAMING PLANS

    OKC MAPS 3 HEALTHAND WELLNESSCENTER #3

    3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105

    Proj

    ect N

    umbe

    r - O

    KC M

    APS

    3 H

    EALT

    H A

    ND

    WEL

    LNES

    S C

    ENTE

    R #

    3

    1/4" = 1'-0"1ENLARGED - LOW ROOF FRAMING PLAN- MECH COURTYARD

    TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021

    1/4" = 1'-0"2ENLARGED - LOW ROOF FRAMING PLAN- RTU8

    1/4" = 1'-0"3ENLARGED - SECOND FLOOR FRAMINGPLAN

    1/4" = 1'-0"5ENLARGED - SECOND FLOOR FRAMINGPLAN - NE

    1/4" = 1'-0"4ENLARGED - SECOND FLOOR FRAMINGPLAN - NW

  • FF

    GG

    DD

    Q

    R

    28LH09

    28LH09

    28LH09

    W16X31

    W18X35 (HIG

    H)W18X

    35 (LOW)

    W14X22 (H

    IGH

    )

    W14X22 (LO

    W)

    RTU 7

    W14X22

    W12X19

    REFER MECH FOR DUCT PENETRATION SIZES AND LOCATIONS

    REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING

    J

    FF

    DD

    BB

    H

    DD.3

    20LH04

    20LH04

    20LH04

    W14X22

    20LH06

    20LH06

    20LH06

    20LH06

    20LH06

    20LH06

    W12X19

    14K1

    W16X31

    W41X22 (HIGH)

    W30X90 (LOW)

    W30X90

    W16X31

    W16X31

    RTU-6

    REFER MECH FOR SIZES AND LOCATIONS OF DUCT PENETRATIONS REFER 9/S5.3 FOR CURB AND DUCT

    PENETRATION SUPPORT FRAMING

    RTU-9

    c

    These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By: RCDDrawn By: RDDesigned By: RCD

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction

    11/2

    5/20

    20 6

    :51:

    51 A

    M

    S2.5

    ENLARGEDFRAMING PLANS

    OKC MAPS 3 HEALTHAND WELLNESSCENTER #3

    3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105

    Proj

    ect N

    umbe

    r - O

    KC M

    APS

    3 H

    EALT

    H A

    ND

    WEL

    LNES

    S C

    ENTE

    R #

    3

    TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021

    1/4" = 1'-0"1ENLARGED - LOW ROOF FRAMING PLAN- RTU7

    1/4" = 1'-0"2ENLARGED - LOW ROOF FRAMING PLAN- RTU6 AND RTU9

  • STEEL COLUMN - REFER PLAN

    AND COLUMN SCHEDULE

    BLOCKOUT

    CONCRETE SLAB

    REFER PLAN

    2" NON-SHRINK GROUT

    SPREAD FOOTING CENTERED ON

    COLUMN - REFER PLAN

    GRANULAR FILL

    REFER PLAN

    VAPOR

    BARRIER

    8"

    BASEPLATE - REFER

    COLUMN SCHEDULE

    2'-0"

    2'-0"

    2'-0"

    #3 AT 32" O.C.

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    2 - #6 TOP AND BOTTOM

    WITH CORNER BARS

    3/4"= 1'-0"

    SECTION1

    S3.1

    1/2" DIA ANCHOR BOLT WITH 6" x 18 GA x 0'-6" COLD

    FORMED METAL BLOCKING AT 4'-0" O.C. PROVIDE

    1/4" x 3" x 3" STEEL WASHER UNDER NUT. PROVIDE

    4 - #10 SELF DRILLING SCREWS THRU EACH SIDE

    OF TRACK INTO BLOCKING.

    ALT: 1/2" DIA SIMPSON TITEN-HD SCREW ANCHOR

    WITH 6" EMBED INTO CONC.

    FIN. FLOOR EL.=

    REFER PLAN

    #3 STIRRUPS

    AT 24" O.C.

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    1'-6"

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    8"

    6" x 18 GA COLD FORMED

    METAL STUDS AT 16" O.C.

    7"

    CONTRACTOR NOTE:

    CONCRETE SLAB

    REFER PLAN

    2 1/2"

    6"

    SAWCUT JOINTS MAY BE USED ONLY IF CUTS ARE MADE WITH "SOFF CUT" SAW AND CUT AS

    SOON AS CONCRETE WILL SUPPORT THE WEIGHT OF A MAN AND EQUIPMENT WITHOUT

    LEAVING IMPRINTS IN CONCRETE.

    EVERY THIRD SLAB

    REINFORCING BAR SHALL BE

    CONTINUOUS THRU THE

    SAWJOINT. CUT REMAINING

    BARS 3" EACH SIDE OF JOINT

    CONCRETE

    SLAB

    GRANULAR FILL

    FORMED SHEAR KEY

    6"

    VAPOR BARRIER

    1'-6"1-6"

    CONTRACTOR NOTE:

    CONSTRUCTION JOINTS CAN BE USED AT CONTRACTOR DISCRETION INSTEAD OF SAWCUT

    JOINTS.

    8"

    1'-6

    "

    8"

    8"

    #4 AT 12" O.C. EACH WAY

    CENTER IN SLAB

    #3 AT 12" O.C. AROUND

    SUMP PIT

    WATERPROOFING ALL

    AROUND ELEVATOR PIT-

    REFER ARCH.

    CONT. VOLCLAY

    WATERSTOP - TYP

    AROUND SUMP PIT

    1'-6"

    CONCRETE SLAB SLOPED

    TO SUMP PIT - REFER 9/S3.1

    CONCRETE WALL -

    REFER 9/S3.1

    COORDINATE SUMP PIT LOCATION WITH

    ELEVATOR MFR

    3/4"X3/4" CHAMFER-TYP

    #4 AT 12" O.C. EACH WAY

    CENTERED IN SLAB

    #5 VERT AT 16" O.C. WITH ACI

    STD. 90 HOOK IN SLAB. CENTER

    BARS IN WALL

    #4 AT 12" O.C. WITH CORNER

    BARS

    WATERPROOFING ALL

    AROUND ELEVATOR PIT

    - REFER ARCH.

    SLOPE SLAB TO SUMP

    GRANULAR FILL

    VAPOR BARRIER

    CONCRETE SLAB REFER

    PLAN

    #3 DOWELS AT 32" O.C.

    REFER 1/S3.1

    5'-0"

    8"

    REFER ARCH FOR

    ELEVATOR PIT

    DIMENSIONS

    VOLCLAY RX-101

    WATERSTOP CONT

    AROUND PIT

    3/16

    1/2" x 4 1/2" x 0'-10" PLATE WITH 2 -

    5/8" DIA HILTI EXPANSION

    ANCHORS EMBEDED 4" INTO

    CONC

    HSS4x4x5/16 COLUMN FOR GUIDE RAIL

    SUPPORT - TYP EACH SIDE OF ELEV -

    FACE OF COLUMN FLUSH WITH

    SHAFTWALL. COORDINATE LOCATIONS

    AND QUANTITY OF COLUMNS WITH

    ELEVATOR MANUFACTURER

    6"

    1'-6"

    1'-0

    "

    8"

    GRANULAR FILL

    2 - #5 WITH CORNER BARS

    VAPOR BARRIER

    INSULATION - REFER

    ARCH

    GRID

    11 1/2"

    EDGE OF SLAB AND

    FACE OF STUD

    F1

    SIZE OF FOOTING

    F3

    MARK

    FOOTING SCHEDULE

    REINFORCING

    5'-0" x 5'-0" x 1'-0"

    5 - #5 EACH WAY

    EQUALLY SPACED BOTTOM

    F4 6'-0" x 6'-0" x 1'-0"

    6 - #5 EACH WAY

    EQUALLY SPACED BOTTOM

    F5

    F6

    F7

    3'-0" x 3'-0" x 1'-0"

    3 - #5 EACH WAY

    EQUALLY SPACED BOTTOM

    7'-0" x 7'-0" x 1'-0"

    7 - #6 EACH WAY

    EQUALLY SPACED BOTTOM

    11'-0" x 11'-0" x 2'-0"

    11 - #6 EACH WAY EQUALLY

    SPACED TOP AND BOTTOM

    1/4" WIDE x 1 1/4" DEEP

    8'-0" x 8'-0" x 1'-6"

    8 - #6 EACH WAY EQUALLY

    SPACED BOTTOM

    2'-0"

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    2 - #6 TOP AND BOTTOM

    WITH CORNER BARS

    3/4"= 1'-0"

    SECTION2

    S3.1

    ANCHOR - REFER 1/S3.1

    FIN. FLOOR EL.=

    REFER PLAN

    #3 STIRRUPS

    AT 24" O.C.

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    1'-6"

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    8"

    6" x 18 GA COLD FORMED

    METAL STUDS AT 16" O.C.

    7"

    INSULATION - REFER

    ARCH

    3"

    EDGE OF SLAB AND

    FACE OF STUD

    A.1

    DOWEL - REFER 1/S3.1

    2'-0"

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    2 - #6 TOP AND BOTTOM

    WITH CORNER BARS

    3/4"= 1'-0"

    SECTION3

    S3.1

    ANCHOR - REFER 1/S3.1

    FIN. FLOOR EL.=

    REFER PLAN

    #3 STIRRUPS

    AT 24" O.C.

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    1'-6"

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    8"

    6" x 18 GA COLD FORMED

    METAL STUDS AT 16" O.C.

    7"

    INSULATION - REFER

    ARCH

    3"

    EDGE OF SLAB AND

    FACE OF STUD

    GRID

    DOWEL - REFER 1/S3.1

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER

    CIVIL

    3/4"= 1'-0"

    SECTION4

    S3.1

    ANCHOR - REFER 1/S3.1

    FOOTING -

    REFER 1/3.1

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    6" x 18 GA COLD FORMED

    METAL STUDS AT 16" O.C.

    7"

    INSULATION - REFER

    ARCH

    3"

    EDGE OF SLAB AND

    FACE OF STUD

    1

    DOWEL - REFER 1/S3.1

    3

    VAPOR BARRIER

    GRANULAR FILL

    REFER PLAN

    FOOTING - REFER

    1/3.1

    ANCHOR - REFER 1/S3.1

    6" x 18 GA COLD FORMED

    METAL STUDS AT 16" O.C.

    2'-0"

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    2 - #6 TOP AND BOTTOM

    WITH CORNER BARS

    3/4"= 1'-0"

    SECTION5

    S3.1

    FIN. FLOOR EL.=

    REFER PLAN

    #3 STIRRUPS

    AT 24" O.C.

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    2'-0"

    MASONRY VENEER-

    REFER ARCH

    12" CMU

    8"

    8"

    INSULATION - REFER

    ARCH

    7 7/8"

    A

    3'-6

    "

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    #4 HORIZ AT 12" O.C. WITH

    CORNER BARS - TYP EACH

    FACE

    3/4"= 1'-0"

    SECTION6

    S3.1

    L6x6x3/8 x 0'-6" WITH 1/2" DIA x 0'-6"

    HEADED STUD ON EACH LEG - TYP

    AT EACH CHANNEL

    #5 VERT AT 16" O.C. -

    CENTERED IN WALL -

    TYP

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    8"

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    8"

    C6x8.2 AT EACH END OF WINDOW

    AND AT 4'-0" O.C. MAX BETWEEN

    ENDS OF WINDOW

    7"

    INSULATION - REFER

    ARCH

    3

    11 1/2"

    EDGE OF SLAB AND

    FACE OF STUD

    1'-0" 1'-4"

    1'-0"

    3-#6 CONT EQ SPACED. WITH

    CORNER BARS - TYP

    #5 AT 12"

    O.C. - TYP

    DOWEL - REFER 1/S3.1

    3'-6

    "

    CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    #4 HORIZ AT 12" O.C. WITH

    CORNER BARS - TYP EACH

    FACE

    3/4"= 1'-0"

    SECTION7

    S3.1

    #5 VERT AT 16" O.C. -

    CENTERED IN WALL -

    TYP

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    8"

    MASONRY VENEER-

    REFER ARCH

    SHEATHING-

    REFER ARCH

    8"

    7"

    INSULATION - REFER

    ARCH

    M

    11 3/4"

    EDGE OF SLAB AND

    FACE OF STUD

    1'-0" 1'-4"

    1'-0"

    3-#6 CONT EQ SPACED. WITH

    CORNER BARS - TYP

    #5 AT 12"

    O.C. - TYP

    DOWEL - REFER 1/S3.1

    3/4"= 1'-0"

    SECTION8

    S3.1 3/4"= 1'-0"

    SECTION - ELEVATOR PIT9

    S3.1 3/4"= 1'-0"

    SECTION - ELEVATOR SUMP PIT10

    S3.1

    NOT TO SCALE

    SAWCUT JOINT DETAIL11

    S3.1

    NOT TO SCALE

    KEYED CONSTRUCTION JOINT DETAIL12

    S3.1

    #5 DOWEL AT 24" O.C. -

    LAP 2'-0" WITH VERT

    BARS IN WALL - TYP

    F2 4'-0" x 4'-0" x 1'-0"

    4 - #5 EACH WAY

    EQUALLY SPACED BOTTOM

    F8 5-0" x 9'-0" x 1'-0"

    #5 AT 12" O.C. EACH WAY

    BOTTOM

    F9 7'-0" x 9'-0" x 1'-0"

    #5 AT 12" O.C. EACH WAY

    BOTTOM

    F10 6'-0" x 6'-0" x 2'-0"

    6 - #5 EACH WAY EQUALLY SPACED

    TOP AND BOTTOM

    WINDOW - REFER

    ARCH

    EACH FLANGE AND

    EACH SIDE OF WEB TYP

    1/4

    C6x8.2 FULL WIDTH OF WINDOW

    STEEL CHANNEL AT EACH END OF

    WINDOWS AND AT 4'-0" O.C. MAX

    BETWEEN ENDS OF WINDOWS -

    REFER 6/S3.1 FOR ADDITIONAL

    INFORMATION

    WINDOW - REFER

    ARCH

    S3.1

    FOUNDATION SECTIONS

    AND DETAILS

    c

    These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.

    Date: Submission:

    Drawing Title:

    No.

    Sheet No:

    Reviewed By:

    Drawn By:

    Designed By:

    Key Plan

    Executive Architect

    Copyright 2020 © Hornbeek Blatt Architects

    HORNBEEK BLATT

    101 South Broadway, Suite 200

    Edmond, Oklahoma 73034

    405.340.8552 Telephone

    405.340.5707 Fax

    www.hornbeekblatt.com

    ra h i t e c t s

    Project:

    THE ORIGINAL OF THIS DRAWING IS 30" X 42".

    300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215

    PHONE: (614) 461-4664FAX: (614) 280-8881

    Design Architect

    7.28.2020 35% Progress Set

    8.25.2020 65% Progress Set

    8.31.2020 Issued for Permit

    9.25.2020 95% Progress Set

    RCD

    RD

    RCD

    OKC MAPS 3 HEALTH

    AND WELLNESS

    CENTER #3

    Project Address:

    N. Lincoln Blvd. and NE 36th St.

    Oklahoma City, OK 73105

    TRUMBLE DEAN, LLC

    8512 S. PENNSYLVANIA AVE., SUITE A

    OKLAHOMA CITY, OK 73159

    405.601.0662 405.848.9202

    CERTIFICATE OF AUTHORITY NO. 3667

    EXPIRES: JUNE 30, 2021

    11.30.2020 Issued for Construction

    AutoCAD SHX TextGRID

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX Text° HOOK IN SLAB. CENTER

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

    AutoCAD SHX TextSCALE:

    AutoCAD SHX Text.

  • CONCRETE SLAB

    REFER PLAN

    PAVING - REFER CIVIL

    CONT FOOTING -

    REFER 1/S3.1

    GRANULAR FILL

    VAPOR BARRIER

    8"

    DOOR OR WINDOW-

    REFER ARCH

    DOWEL - REFER 1/S3.1

    INSULATION - REFER

    ARCH

    J

    1'-0"

    1'-4"

    NORMAL

    REINFORCING

    2 VERTICAL BARS AT

    CORNERS AND EACH SIDE OF

    OPENING

    VERTICAL WALL REINFORCING SHALL

    EXTEND CONTINUOUSLY FROM

    FOUNDATION AND AT LEAST 6" INTO

    BOND BEAM AT TOP OF WALL

    LINTEL REINF. ABOVE DOOR

    OPENING- REFER PLAN AND

    LINTEL SCHEDULE

    BOND BEAM AT TOP OF WALL - REFER GEN

    STRUCT NOTES FOR BOND BEAM REINF

    FOR VERT. CMU REINFORCING PROVIDE STD

    90^ HOOK INTO BOND BEAM AT TOP OF WALL

    BEAM OR

    JOIST

    PROVIDE 2 BARS FULL

    HEIGHT OF WALL AT BEAM

    OR JOIST BEARING.

    LINTEL ABOVE DOOR

    OPENING - EXTEND AT

    LEAST 8" EACH SIDE OF

    OPENING

    LINTEL REINF. ABOVE

    WINDOW OPENING- REFER

    PLAN AND LINTEL SCHEDULE

    2 VERTICAL BARS AT

    CORNERS AND EACH SIDE

    OF OPENINGS

    TYPICAL BOND BEAM -

    REFER GEN STRUCT NOTES

    BOND BEAM BELOW

    WINDOW - EXTEND BOND

    BEAM AT LEAST 8" BEYOND

    EDGE OF OPENING - TYP

    FOUNDATION DOWEL SHALL EXTEND A

    MINIMUM OF 30 DIAMETERS INTO

    FOUNDATION AND 40 DIAMETERS INTO

    MASONRY WALL UNLESS NOTED

    OTHERWISE. DOWELS TO MATCH SIZE

    AND SPACING OF WALL REINFORCING

    3/4"= 1'-0"

    SECTION1

    S3.2

    11.2

    PAVING - REFER CIVIL

    FOOTING - REFER PLAN AND

    SCHECULE2'-6"

    STEEL COLUMN - REFER

    PLAN

    #5 VERT AT EACH CORNER

    AND MIDDLE OF EACH FACE

    OF PEDESTAL - TYP

    4 - #3 TIES EQ SPACED

    AT PEDESTAL - TYP

    3/4"= 1'-0"

    SECTION2

    S3.2

    8"

    1'-4"

    11.8

    BRACE - REFER FRAME

    ELEVATIONS. PROVIDE

    ERECTION BOLT AT

    FABRICATOR DISCRETION

    3/8" PLATE TYP

    B10 BASEPLATE

    CONC SLAB - REFER

    PLAN

    2" NON-SHRINK

    GROUT TYP

    TYP EACH SIDE OF BRACE,

    EACH SIDE OF GUSSET PLATE

    EACH SIDE OF GUSSET PLATE

    TO BASEPLATE AND COLUMN

    TYP

    5/16

    TOP OF CONC

    FOOTING

    3/4"= 1'-0"

    SECTION4

    S3.2

    GRID

    STEEL COLUMN -

    REFER PLAN

    BRACE - REFER FRAME ELEVATIONS.

    PROVIDE ERECTION BOLT AT

    FABRICATOR DISCRETION

    5/16 6

    TYP EACH SIDE OF

    BRACE, EACH SIDE

    OF GUSSET PLATE

    5/16 6

    BASEPLATE AND

    ANCHORS - REFER

    COLUMN SCHEDULE

    AND 2/S3.3

    CONC SLAB - REFER

    PLAN

    2" NON-SHRINK

    GROUT TYP

    TOP OF CONT

    FOOTING

    EACH SIDE OF

    GUSSET PLATE

    TYP

    5/16

    SPREAD FOOTING - REFER

    PLAN AND SCHEDULE

    3/4"= 1'-0"

    DETAIL5

    S3.2

    3/8" PLATE TYP

    NOT TO SCALE

    CMU WALL REINFORCING DETAIL - TYP6

    S3.2

    HECKMAN TYPE 374 OR 376

    REBAR POSITIONER AT 24" O.C. -

    TYP AT EACH VERT BAR.

    HORIZONTAL REINFORCING

    AT BOND BEAM - TYP

    TYP VERTICAL REINFORCING -

    REFER GEN NOTES

    NOT TO SCALE

    PLAN DETAIL - TYPICAL 8" CMU7

    S3.2

    HORIZONTAL REINFORCING

    AT BOND BEAM - TYP

    TYP VERTICAL REINFORCING

    - REFER GEN NOTES

    HECKMAN TYPE 374 OR 376

    REBAR POSITIONER AT 24" O.C. -

    TYP AT EACH VERT BAR.

    NOT TO SCALE

    PLAN DETAIL - TYPICAL 12" CMU8

    S3.2

    CMU LINTEL SCHEDULE

    L3 2 - #5 B12 x 24

    LI

    MARK

    WIDTH x DEPTH

    12 x 8

    NOMINAL

    REINFORCING

    2 - #5 B

    REMARKS

    EXTEND LINTEL AT LEAST 8 INCHES EACH SIDE OF OPENING

    L2 12 x 16 2 - #5 B

    L5 2 - #5 B8 x 8

    L4 2 - #5 B12 x 32

    SO

    LID

    G

    RO

    UT

    FU

    LL D

    EP

    TH

    O

    F

    LIN

    TE

    L

    REINFORCING BARS

    1" C

    LE

    AR

    TY

    P

    LINTEL

    WIDTH

    8 x 24L6 2 - #5 B

    NOT TO SCALE

    LINTEL SCHEDULE AND DETAIL9

    S3.2

    HORIZONTAL REINFORCING

    AT BOND BEAM - TYP

    TYP VERTICAL REINFORCING

    - REFER GEN NOTES

    HECKMAN TYPE 374 OR 376

    REBAR POSITIONER AT 24" O.C. -

    TYP AT EACH VERT BAR.

    NOT TO SCALE

    PLAN DETAIL - TYPICAL CMU PILASTER10

    S3.2

    CONTROL JOINT ON ONE

    SIDE OF PILASTER - REFER

    PLAN FOR LOCATIONS

    16" x 16" PILASTER

    GRID

    6 - #7 VERT IN GROUT FILLED

    CELLS FULL HEIGHT OF

    PILASTER - TYP

    #3 TIES AT 16" O.C. FULL

    HEIGHT OF PILASTER

    3"

    TY

    P

    3"

    TY

    P

    3" TYP

    EACH FACE

    EQ

    TYP

    EQ

    TYP

    EQ

    TYP

    EQ

    TYP

    3"

    TY

    P

    3"

    TY

    P

    EQ

    TY

    P

    EQ

    TY

    P

    2'-0"

    CONCRETE SLAB

    REFER PLAN

    2 - #6 TOP AND BOTTOM

    WITH CORNER BARS

    3/4"= 1'-0"

    SECTION11

    S3.2

    FIN. FLOOR EL.=

    REFER PLAN

    #3 STIRRUPS

    AT 24" O.C.

    GRANULAR FILL

    REFER PLAN

    VAPOR BARRIER

    1'-6"

    8" CMU

    8"

    #5 DOWEL AT 24" O.C. -

    LAP 2'-0" WITH VERT

    BARS IN WALL - TYP

    5 1/4"

    HORIZONTAL BAR INTO

    PILASTER - EXTEND 2'-0"

    INTO WALL - TYP

    #4 AT 12" O.C. EACH WAY

    CENTERED IN SLAB

    #5 VERT AT 16" O.C. WITH ACI

    STD. 90 HOOK IN SLAB.

    CENTER BARS IN WALL

    #4 AT 12" O.C. WITH

    CORNER BARS

    WATERPROOFING ALL

    AROUND ELEVATOR PIT

    - REFER ARCH.

    SLOPE SLAB TO SUMP

    GRANULAR FILL

    VAPOR BARRIER

    CONCRETE SLAB

    REFER PLAN

    #3 DOWELS AT 32" O.C.

    REFER 1/S3.1

    5'-0"

    8"

    VOLCLAY RX-101

    WATERSTOP CONT

    AROUND PIT

    6"

    1'-6"

    1'-0"

    8"

    GRANULAR

    FILL

    2 - #5 WITH

    CORNER BARS

    TYP

    VAPOR

    BARRIER

    3/4"= 1'-0"

    SECTION - PUMP PIT12

    S3.2