GENERAL STRUCTURAL NOTES
5. CONCRETE AND CONCRETE REINFORCING
3. GENERAL
1. GENERAL NOTES
2. DESIGN CRITERIA
4. FOUNDATION
A. DESIGN CODE: 2015 INTERNATIONAL BUILDING CODE WITH CITY OF OKLAHOMA CITY SUPPLEMENTS
B. DESIGN LIVE LOADS
ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 PSF (UNREDUCED)
1ST FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF
2ND FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 PSF
C. DEAD LOADS:
ROOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 PSF
CEILING COLLATERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PSF
MECHANICAL/MISCELLANEOUS COLLATERAL . . . . . . . . . 5 PSF
INSULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PSF
FRAMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTUAL WEIGHT OF MATERIALS
D. LATERAL LOADS:
BASIC WIND SPEED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 MPH
IMPORTANCE FACTOR (I) . . . . . . . . . . . . . . . . . . . . . 1.00
EXPOSURE C
SEISMIC
SEISMIC RISK CATEGORY. . . . . . . . . . . . . . . . . . . . III
SEISMIC IMPORTANCE FACTOR (IE) . . . . . . . . . . . 1.25
SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . . . . . B
SPECTRAL RESPONSE COEFFICIENTS . . . . . . . . . SDS = 0.210g
SD1 = 0.087g
SITE CLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
RESPONSE FACTOR . . . . . . . . . . . . . . . . . . . . . . . . 3.0
BASIC SEISMIC FORCE RESISTING SYSTEM:
STEEL FRAMES NOT SPECIFICALLY DETAILED FOR SEISMIC
ANALYSIS PROCEDURE:
EQUIVALENT LATERAL FORCE PROCEDURE
SEISMIC RESPONSE COEFFICIENT, Cs = 0.087
A. FINISHED FLOOR ELEVATION = 100'-0" IS EQUAL TO MEAN SEA ELEVATION = 1187.50 FT.
B. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY UPON
DISCOVERY OF ANY DISCREPANCY BETWEEN THE STRUCTURAL DRAWINGS AND THE ARCHITECTURAL DRAWINGS, OR
OTHER CONSULTANT'S DRAWINGS.
C. PLANS, SECTIONS AND DETAILS ARE NOT TO BE SCALED FOR DETERMINATION OF QUANTITIES, LENGTHS, OR FIT OF
MATERIALS.
D. VERIFY FLOOR SLAB DEPRESSIONS AND OFFSETS WITH ARCHITECTURAL DRAWINGS.
E. THE SIZE AND LOCATION OF ALL MECHANICAL EQUIPMENT, EQUIPMENT PADS, AND ALL DUCT AND PIPE OPENINGS THROUGH
SLABS AND WALLS SHALL BE VERIFIED WITH MECHANICAL AND ELECTRICAL DRAWINGS PRIOR TO FABRICATION OF
MATERIALS.
F. SHOP DRAWINGS SHALL BE ORIGINAL DRAWINGS PREPARED BY CONTRACTOR'S SUBCONTRACTOR, SUPPLIER, OR
DISTRIBUTOR. REPRODUCTION OF STRUCTURAL CONTRACT DOCUMENTS AS ERECTION PLANS AND DETAILS SHALL NOT BE
PERMITTED.
G. SHOP DRAWINGS SHALL BE CHECKED BY GENERAL CONTRACTOR PRIOR TO BEING SUBMITTED TO THE STRUCTURAL
ENGINEER FOR REVIEW.
H. SHOP DRAWING SUBMITTALS SHALL CONTAIN THREE (3) PHOTOCOPIES OF EACH SHEET OF THE SUBMITTAL. ELECTRONIC
COPIES (PDFs) OF EACH SUBMITTAL ARE ACCEPTABLE.
I. CONTRACTOR SHALL BID AN ALLOWANCE FOR FABRICATION AND ERECTION OF AN ADDITIONAL 2,000 LBS OF STEEL TO BE
USED AT THE DISCRETION OF THE ARCHITECT OR ENGINEER OF RECORD. ALL UNUSED PORTIONS SHALL BE REIMBURSED
TO THE OWNER.
A. CONCRETE MIX SCHEDULE:
CONC STRENGTH AGG AGG SLUMP MAX
CLASS (PSI) TYPE SIZE INCHES W/C
A 3000 HRC 1 1/2" 5-7 0.64
B 3000 HRC 1" 3-5 0.64
NOTE: THE STRENGTH LISTED SHALL BE THE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS. THE REQUIRED AVERAGE
COMPRESSIVE STRENGTH f'cr SHALL CONFORM TO A.C.I. STANDARD 318-14
NOTE: "HRC" REFERS TO HARDROCK CONCRETE HAVING AN AIR DRY UNIT WEIGHT OF APPROXIMATELY 145 POUNDS PER
CUBIC FOOT (PCF).
NOTE: WHERE WATER-TO-CEMENT RATIO IS NOT INDICATED ON THE DRAWINGS OR IN THE PROJECT SPECIFICATIONS, IT
SHALL BE DETERMINED BY THE CONTRACTOR TO MEET OTHER REQUIREMENTS.
B. CONCRETE USAGE SCHEDULE:
DESCRIPTION CONC AIR
OF USE CLASS CONTENT
-FOOTINGS, WALLS A ---
-INTERIOR SLABS-ON-GRADEB ---
-EXTERIOR SLABS-ON-METAL DECK B 4%-6%
C. CLEAR DISTANCES FROM CONCRETE SURFACES TO REINFORCING STEEL SHALL NOT BE LESS THAN AS FOLLOWS, UNLESS
NOTED OTHERWISE:
-FOOTINGS -3 INCHES ALL SIDES
-WALLS (ELEVATOR PIT) -VERTICAL BARS CENTERED IN WALL
-INTERIOR SLABS-ON-GRADE-2 INCHES FROM TOP OF SLAB
D. CONCRETE REINFORCEMENT DETAILS SHALL CONFORM TO A.C.I. STANDARD 318-14, UNLESS NOTED OTHERWISE
E. ALL REINFORCEMENT, #3 BARS AND LARGER, SHALL BE ASTM A615, GR 60
F. LAP ALL REINFORCING BARS 45 BAR DIAMETERS, UNLESS NOTED OTHERWISE
G. PROVIDE CORNER BARS IN BOTH FACES OF ALL FOOTINGS AS REQUIRED EXTENDED A MINIMUM OF 45 BAR DIAMETERS IN
EACH DIRECTION. QUANTITY, SIZE AND SPACING OF CORNER BARS SHALL BE EQUAL TO QUANTITY, SIZE AND SPACING OF
HORIZONTAL REINFORCING BARS WITH WHICH THEY LAP, EXCEPT THAT MAXIMUM CORNER BAR SIZE SHALL BE #6.
H. REINFORCING SHALL BE ADEQUATELY SUPPORTED USING CHAIRS, BOLSTERS OR PRECAST CONCRETE BRICKS HAVING
MINIMUM COMPRESSIVE STRENGTH EQUAL TO OR GREATER THAN THE CONCRETE. USE BOLSTERS OR OTHER SPACING
DEVICES AS REQUIRED TO MAINTAIN PROPER SIDE CLEARANCES BETWEEN FORMS AND REINFORCING BARS.
I. EXTERIOR SLABS SHALL SLOPE AWAY FROM THE BUILDING 1/8" PER FOOT, UNLESS DIRECTED OTHERWISE BY THE
ARCHITECT OR CIVIL ENGINEER.
J. DO NOT WET PLACE DOWELS, ANCHOR BOLTS OR ANY EMBEDDED ITEMS INTO THE CONCRETE. USE TEMPLATES AS
REQUIRED FOR ANCHOR BOLTS.
K. DO NOT WELD REINFORCING BARS UNLESS BARS ARE PER ASTM A706.
L. DO NOT HEAT AND BEND REINFORCING BARS.
M. ALL BAR BENDING SHALL BE IN ACCORDANCE WITH A.C.I. 315-99 AND SP-66 (04), ACI DETAILING MANUAL.
N. DO NOT FLAME CUT REINFORCING BARS.
O. REFER MECHANICAL, ELECTRICAL AND AQUATICS DRAWINGS FOR EQUIPMENT PAD SIZES AND LOCATIONS. EQUIPMENT
PADS SHALL BE PLACED ON TOP OF CONCRETE SLAB-ON-GRADE UNLESS NOTED OTHERWISE. MINIMUM EQUIPMENT PAD
THICKNESS TO BE 4 INCHES UNLESS NOTED OTHERWISE ON MECHANICAL, ELECTRICAL OR AQUATICS DRAWINGS.
REINFORCE EQUIPMENT PAD WITH #4 AT 12 INCHES ON CENTER EACH WAY. PROVIDE 2 INCH CLEARANCE BETWEEN TOP OF
EQUIPMENT PAD AND TOP OF REBAR.
P. PROVIDE 3/4 INCH CHAMFER ON ALL EXPOSED CORNERS AND EDGES, UNLESS NOTED OTHERWISE ON THE ARCHITECTURAL
DRAWINGS.
A. THE STRUCTURAL DRAWINGS ARE INTENDED TO BE USED CONCURRENTLY WITH THE ARCHITECTURAL DRAWINGS. IF ANY
DISCREPANCY EXISTS BETWEEN THE STRUCTURAL DOCUMENTS AND THE ARCHITECTURAL DOCUMENTS, THE CONTRACTOR
SHALL IMMEDIATELY NOTIFY THE ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING WITH CONSTRUCTION.
B. GENERAL NOTES ARE AN INTEGRAL PART OF THE CONSTRUCTION DOCUMENTS AND DESCRIBE CONDITIONS THAT APPLY
GENERALLY THROUGHOUT THE STRUCTURAL DRAWINGS.
C. THE STRUCTURE IS DESIGNED AS A STABLE UNIT AFTER ALL COMPONENTS ARE IN PLACE. THE CONTRACTOR SHALL
PROVIDE TEMPORARILY BRACE THE STRUCTURAL COMPONENTS FOR LATERAL STABILITY UNTIL AFTER ALL PERMANENT
BRACING SYSTEMS ARE COMPLETE. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING
NECESSARY TO ENSURE THE STABILITY OF ANY AND ALL PARTS OF THE BUILDING DURING CONSTRUCTION.
A. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS AND DESIGN VALUES GIVEN IN THE GEOTECHNICAL (SOILS)
REPORT, AS FOLLOWS:
SOILS REPORT BY: INTERTEK PSI
DATE OF REPORT: 1-14-2020
REPORT NUMBER: 05471565
RECOMMENDED FOUNDATION TYPE: SHALLOW FOOTINGS
BEARING STRATUM: 2'-2" MINIMUM OF COMPACTED NON-EXPANSIVE
STRUCTURAL FILL UNDER INTERIOR SLABS
ALLOWABLE SOIL BEARING CAPACITY: 3,200 PSF FOR SPREAD FOOTINGS
2,500 PSF FOR CONTINUOUS FOOTINGS
NOTE: A COPY OF THE SOILS REPORT IS AVAILABLE FROM THE ARCHITECT
B. GRANULAR FILL SHALL BE UNWASHED SIZE NO. 10 (SCREENINGS) PER ASTM D448, LATEST EDITION, HAVING A NOMINAL
AGGREGATE SIZE NO. 4 (4.75mm) AND PERCENTAGES OF PARTICLE SIZES PASSING THRU A NO. 4 SIEVE IN ACCORDANCE
WITH TABLE 1 OF D448:
3/8" (9.5mm) 100%
NO. 4 (4.75mm) 85% TO 100%
NO. 100 (150micrometers) 10% TO 30%
ODOT TYPE "A" SCREENINGS ARE ACCEPTABLE.
C. THE SOIL AT THE BOTTOM OF ALL FOOTING EXCAVATIONS SHALL BE INSPECTED BY A QUALIFIED GEOTECHNICAL ENGINEER
LICENSED IN THE STATE OF OKLAHOMA TO VERIFY THE SOIL MEETS OR EXCEEDS THE ALLOWABLE SOIL BEARING CAPACITY
STATED ON THESE DRAWINGS.
D. UTILITY TRENCHES UNDER THE BUILDING SHALL BE EFFECTIVELY SEALED TO RESTRICT WATER INTRUSION AND FLOW
ALONG THE TRENCHES. PROVIDE A CLAY TRENCH PLUG EXTENDING AT LEAST 5 FEET BEYOND THE EDGE OF THE BUILDING
IN ALL UTILITY TRENCHES UNDER THE BUILDING IN ACCORDANCE WITH THE GEOTECH REPORT.
E. EARTH FORMED FOOTINGS ARE ACCEPTABLE AS LONG AS THE SIDES OF THE EXCAVATIONS CAN MAINTAIN A REASONABLY
VERTICAL CUT WITHOUT SLOUGHING SOIL INTO THE EXCAVATION DURING REBAR PLACEMENT, DURING CONCRETE
PLACEMENT AND THE EXCAVATION CAN MAINTAIN THE FOOTING SHAPE SPECIFIED ON THE DRAWINGS.
7. METAL ROOF DECK
12. STEEL JOISTS
A. STEEL JOISTS SHALL MEET OR EXCEED THE LATEST STEEL JOIST INSTITUTE SPECIFICATIONS. JOIST SIZES AND TYPES ARE SHOWN ON
THE FRAMING PLANS.
B. ALL JOIST SEATS SHALL BE AS FOLLOWS UNLESS NOTED OR DETAILED OTHERWISE:
2 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT FLOORS AND 1/4" PER FOOT ROOF SLOPE
3 1/2" FOR K-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE
5" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1/4" PER FOOT ROOF SLOPE
6 1/2" FOR LH-SERIES JOISTS BEARING ON STRUCTURAL STEEL AT 1:12 ROOF SLOPE
C. STEEL JOISTS SHALL BE FIELD WELDED TO SUPPORTING MEMBERS OR TO PRESET BEARING PLATES IN ACCORDANCE WITH S.J.I. MINIMUM
REQUIREMENTS UNLESS NOTED OTHERWISE.
D. ERECTION BOLTS CAN BE USED AT JOIST SEATS AT ERECTOR'S DISCRETION. ERECTION BOLTS SHALL BE REMOVED AFTER WELDING IS
COMPLETE.
E. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1.
F. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE
WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1.
G. ALL WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD TESTING
METHODS AT THE INSPECTOR'S DISCRETION.
H. JOIST FABRICATOR SHALL PROVIDE ALL BRIDGING AND X-BRIDGING REQUIRED IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE.
I. BOTTOM CHORDS OF JOISTS FRAMING TO COLUMNS SHALL BE EXTENDED TO THE COLUMN UNLESS DETAILED OTHERWISE.
J. DESIGN ROOF JOISTS FOR NET UPLIFT OF 10 PSF. PROVIDE UPLIFT BRIDGING PER SJI MINIMUMS
13. COLD FORMED METAL FRAMING - STRUCTURAL
A. TYPICAL EXTERIOR COLD-FORMED STEEL STUDS SHALL BE 6 INCHES DEEP, 18 GA. CEE-STUDS CONFORMING TO A.I.S.I "SPECIFICATION
FOR THE DESIGN OF COLD-FORMED STRUCTURAL MEMBERS", UNLESS NOTED OTHERWISE.
B. COLD-FORMED METAL FRAMING LEGEND:
MINIMUM PROPERTIES
SIZE AND GAUGE A.I.S.I DESIGNATION Ix (IN4) Sx (IN3) AREA (IN2) Rxx (IN)
6 IN, 18 GA. 600S162-43 2.316 0.767 0.447 2.277
6 IN, 16 GA 600S162-54 2.860 0.915 0.556 2.267
8 IN, 16 GA. 800S162-54 5.599 1.228 0.669 2.926
C. COLD-FORMED METAL FRAMING MATERIAL PROPERTIES:
MEMBER MATERIAL GRADE Fy (ksi) SHOP COAT
STUDS ASTM A653 C 50 GALVANIZE (G60)
JOISTS ASTM A653 C 50 GALVANIZE (G60)
TRACK ASTM A653 A 50 GALVANIZE (G60)
D. VERTICAL SLIDE CLIP CONNECTORS, SLIP TRACK AND OTHER COLD-FORMED METAL CONNECTORS REQUIRED FOR THE PROJECT SHALL BE
STANDARD SLIP TRACKS, BRIDGING, CONNECTORS AND CLIPS BY THE COLD-FORMED METAL FRAMING MANUFACTURER.
E. APPROVED COLD-FORMED METAL MANUFACTURER: CLARKDIETRICH BUILDING SYSTEMS.
F. PROVIDE COLD-FORMED METAL MANUFACTURER'S STANDARD SLIP TRACK TO ACCOMMODATE 1 1/4" MAXIMUM VERTICAL DEFLECTION.
A. STEEL ROOF DECK SHALL BE 20 GA., TYPE B DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM SECTION
PROPERTIES SHALL BE Ip=0.201 IN4/FT, In=0.222 IN4/FT, Sn=0.247 IN3/FT, Sp=0.234 IN3/FT, D=1.5 IN
B. METAL ROOF DECK CONNECTION SCHEDULE:
MARK CONN AT CONN AT SIDELAP
SUPPORTS PARALLEL EDGE CONN
(W/N) SUPPORTS SPACING NO. PER SPAN
I 36/7 12 INCHES 3
W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET
C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.
SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.
D. ROOF DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT
8. METAL FLOOR DECK
A. STEEL FORM DECK SHALL BE 20 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK
INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.088 IN4/FT, In=0.088 IN4/FT, Sn=0.165 IN3/FT, Sp=0.167 IN3/FT, D=1.0 IN
B. METAL ROOF DECK CONNECTION SCHEDULE:
MARK CONN AT CONN AT SIDELAP
SUPPORTS PARALLEL EDGE CONN
(W/N) SUPPORTS SPACING NO. PER SPAN
I 32/4 12 INCHES 2
W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET
C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.
SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.
D. FLOOR DECK SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT
11 METAL DECK AT STAIR LANDING
A. STEEL FORM DECK SHALL BE 22 GA., HEAVY DUTY, PAINTED, MULTI-RIB FORM DECK CONFORMING TO THE STANDARDS OF THE STEEL DECK
INSTITUTE. MINIMUM SECTION PROPERTIES SHALL BE Ip=0.024IN4/FT, In=0.024 IN4/FT, Sn=0.070 IN3/FT, Sp=0.070 IN3/FT, D=0.6 IN
B. METAL ROOF DECK CONNECTION SCHEDULE:
MARK CONN AT CONN AT SIDELAP
SUPPORTS PARALLEL EDGE CONN
(W/N) SUPPORTS SPACING NO. PER SPAN
I 36/4 12 INCHES 2
W/N = SHEET WIDTH AND NUMBER OF CONNECTIONS PER SHEET
C. SUPPORT AND PARALLEL EDGE CONNECTIONS SHALL BE NO. 12 SELF-DRILLING SCREWS THROUGH THE DECK INTO THE ROOF FRAMING.
SIDELAP CONNECTIONS SHALL BE NO. 10 SELF-DRILLING SCREWS.
D. FLOOR DECK AT STAIR LANDING SHALL BE CONNECTED AS INDICATED FOR MARK I THROUGHOUT
14. CONCRETE MASONRY UNIT (STRUCTURAL)
A. STRUCTURAL PROPERTIES:
REQUIRED PRISM STRENGTH OF STRUCTURAL ASSEMBLY 1500 PSI
REQUIRED 28-DAY COMPRESSIVE STRENGTH, MORTAR 1800 PSI
REQUIRED 28-DAY COMPRESSIVE STRENGTH, GROUT 2000 PSI
B. ALL LOAD BEARING CMU WALLS 8 INCH (NOMINAL), NORMAL WEIGHT BLOCK.
C. TYPICAL VERTICAL REINFORCING IN SOLID GROUTED CELL FULL HEIGHT OF WALL:
8" CMU LOAD BEARING EXTERIOR SHEAR WALLS. . . . #5 VERT AT 24 INCHES O.C.
12" CMU LOAD BEARING EXTERIOR SHEAR WALLS . . . 2-#5 VERT AT 24 INCHES O.C.
D. PROVIDE A.C.I. STANDARD HOOK IN BOND BEAM ALONG TOP OF WALLS FOR ALL VERTICAL BARS.
E. PROVIDE TROUGH BLOCK BEAM (BOND BEAM) COURSES IN CMU WALLS FILLED WITH GROUT AT DOOR HEADS, WINDOW HEADS,
BELOW WINDOWS, AND AT EVERY SIXTH COURSE REINFORCED WITH 2-#4 IN 8" CMU , UNLESS NOTED OTHERWISE. TRUSS TYPE
JOINT REINFORCING AT 16" O.C. CAN BE SUBSTITUTED FOR BOND BEAMS.
F. HORIZONTAL REINFORCING IN BOND BEAMS SHALL BE LAPPED 18 INCHES AT SPLICES. STAGGER SPLICES IN ADJACENT BARS AT
LEAST 4'-0".
G. VERTICAL REINFORCING IN GROUTED CELLS SHALL BE LAPPED 24 INCHES AND WIRE TIED AT SPLICES, UNLESS NOTED
OTHERWISE. STAGGER SPLICES IN ADJACENT GROUTED CELLS.
H. USE HECKMAN NO. 374 OR NO. 376 REBAR POSITIONERS OR APPROVED EQUAL TO LOCATE VERTICAL BARS IN CENTER OF CELLS.
PROVIDE A MINIMUM OF 2 POSITIONERS PER 4 FT BAR LENGTHS.
I. CONTRACTOR SHALL PROVIDE TEMPORARY LATERAL BRACING FOR ALL CMU WALLS UNTIL AFTER ROOF FRAMING AND ROOF
DECK INSTALLATION IS COMPLETE. LATERAL BRACING SHALL BE ADEQUATE TO RESIST WIND AND ANY CONTRUCTION LOADS.
9. METAL ROOF DECK - AT POOL
A. REFER PLANS FOR LOCATIONS OF TORIS ACOUSTICAL DECK.
B. STEEL FORM DECK SHALL BE 20 GA., TYPE 7A ACOUSTIC, COMPOSITE DECK MANUFACTURED BY EPIC METALS, 11 TALBOT AVENUE, RANKIN,
PA. MINIMUM SECTION PROPERTIES SHALL BE Ip=10.04 IN4/FT, Sn=1.66 IN3/FT, Sp=2.31 IN3/FT, D=7 INCHES.
C. STEEL FORM DECK SHALL BE GALVANIZED, ETCHED WITH CHEMICAL CONVERSION COATING, STAGE ONE COATED WITH NATACOAT
COMPATIBLE PRIMER, COATED WITH NATACOAT EXPOXY PRIMER. SEE PROJECT SPECIFICATION 053500 FOR ADDITIONAL INFORMATION.
D. UPPER AND LOWER COMPONENTS SHALL BE FACTORY WELDED. NO MECHANICAL FASTENERS ALLOWED.
E. AFTER ASSEMBLY OF UPPER AND LOWER COMPONENTS, THE EXPOSED SURFACES AND INTERIOR SURFACES OF PERFORATIONS SHALL
RECEIVE A FACTORY APPLIED NATACOAT EPOXY PRIMER. THE NATACOAT SHALL BE OVEN CURED. SEE PROJECT SPECIFICATION 053500 FOR
ADDITIONAL INFORMATION.
F. DECK SHALL BE FASTENED TO STRUCTURAL FRAMING AS DIRECTED BY THE MANUFACTURER.
G. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER.
F. A FIELD APPLIED, 3 MIL COATING OF TNEMEC #113 SHALL BE APPLIED BY THE PAINTING SUBCONTRACTOR AFTER THE DECK IS INSTALLED.
6. STRUCTURAL STEEL
A. STRUCTURAL STEEL SHALL MEET THE FOLLOWING ASTM SPECIFICATIONS:
STRUCTURAL WIDE FLANGE SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A992 (Fy=50 ksi MIN)
STRUCTURAL STEEL PLATES, CHANNELS, ANGLES . . . . . . . . . . . . . . . . . . . . ASTM A36 (Fy=36 ksi MIN)
TUBULAR HSS SHAPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A500, GR B OR ASTM A1085
COMMON BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A307
HIGH STRENGTH BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A325
B. BOLTS SHALL BE AS FOLLOWS:
BEARING CONNECTIONS FOR STEEL CONNECTIONS . . . . . . . . . . . . . . . . . . . 3/4" DIA, HIGH STRENGTH
ANCHOR BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM F1554, GRADE 36
ERECTION BOLTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMMON
C. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH A.I.S.C. "SPECIFICATIONS FOR THE DESIGN, FABRICATION
AND ERECTION OF STRUCTURAL STEEL."
D. ALL STRUCTURAL STEEL CONNECTIONS NOT DETAILED OR OTHERWISE NOTED SHALL BE STANDARD A.I.S.C. WELDED OR BOLTED USING
ALLOWABLE STRESS DESIGN. DETAIL BOLTED OR WELDED CONNECTIONS TO SUPPORT ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY
SHOWN IN THE ALLOWABLE UNIFORM LOAD TABLES OF THE A.I.S.C. MANUAL OF STEEL CONSTRUCTION.
E. ALL BOLTS USED IN STEEL CONNECTIONS SHALL BE SNUG-TIGHT AS DEFINED BY A.I.S.C. UNLESS NOTED OTHERWISE. TENSION CONTROL
BOLTS ARE AN ACCEPTABLE SUBSTITUTE AT THE ERECTOR'S DISCRETION.
F. STANDARD HOLE SIZES SHALL BE USED FOR STEEL BEARING CONNECTIONS. SHORT SLOTTED HOLES ARE NOT ACCEPTABLE FOR BEARING
CONNECTIONS.
G. OVERSIZED HOLES ARE ACCEPTABLE FOR COLUMN BASEPLATES. WHEN OVERSIZED HOLES ARE USED FOR BASEPLATES, STEEL WASHERS
SHALL BE USED BETWEEN THE NUTS AND BASEPLATE. THE WASHERS SHALL BE WELDED TO THE BASEPLATES. REFER ANCHOR BOLT
DETAIL.
H. ALL WELDING SHALL COMPLY WITH A.W.S. STANDARD D1.1.
I. WELDING ELECTRODES SHALL BE E70 UNLESS OTHERWISE NOTED OR REQUIRED BY THE WELDING PROCEDURE SPECIFICATIONS FOR THE
WORK BEING PERFORMED. ALL ELECTRODES USED ON THE PROJECT SHALL BE STORED AS REQUIRED BY A.W.S. D1.1.
J. ALL FIELD WELDS SHALL BE VISUALLY INSPECTED BY A CERTIFIED WELD INSPECTOR. THE WELD INSPECTOR CAN SPECIFY OTHER WELD
TESTING METHODS AT THE INSPECTOR'S DISCRETION.
K. ALL FIELD BOLTED CONNECTIONS SHALL BE VISUALLY INSPECTED BY A SPECIAL INSPECTOR TO VERIFY ALL BOLTS ARE INSTALLED AND
TIGHTENED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
L. DO NOT FLAME CUT HOLES IN THE FIELD FOR FRAMED CONNECTIONS.
M. ALL STEEL FRAMING, EMBED PLATES, CONNECTION PLATES ABOVE AND WITHIN THE POOL STORAGE, CHEMICAL STORAGE ROOMS AND
POOL EQUIPMENT ROOM SHALL BE HOT-DIPPED GALVANIZED, EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT. ALL EMBED
PLATES SHALL BE HOT-DIPPED GALVANIZED AND EPOXY INTERMEDIATE COAT AND POLYURETHANE TOP COAT AFTER WELDING.
A. GLULAM BEAMS SHALL BE ARCHITECTURAL APPEARANCE.
B. ALL BEAMS FOR THE NATATORIUM ROOF SHALL BE ALASKAN WHITE CEDAR 20F-V3.
C. ALL BEAMS FOR THE LOBBY ROOF SHALL BE DOUGLAS-FIR 24F-V8.
D. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE.
E. SEE PROJECT SPECIFICATION 061813 FOR ADDITIONAL INFORMATION.
15. WOOD BEAMS
10. METAL ROOF DECK - AT LOBBY
A. STEEL FORM DECK SHALL BE PAINTED 20 GA., 3 INCH TYPE N CONFORMING TO THE STANDARDS OF THE STEEL DECK INSTITUTE. MINIMUM
SECTION PROPERTIES SHALL BE I=0.964 IN4/FT, Sn=0.552 IN3/FT, Sp=0.501 IN3/FT, D=3 INCHES.
B. ATTACH DECK TO WOOD FRAMING USING NO. 12 WOOD SCREWS AT EACH FLUTE WITH 2" MIN EMBEDMENT INTO BEAM.
C. ATTACH DECK TO STEEL EDGE ANGLES USING 1/4" DIA SELF-DRILLING SCREWS AT 12 INCHES O.C.. PRE-DRILL AS REQUIRED.
D. SIDE LAPS SHALL BE AT 36 INCHES ON CENTER MAXIMUM SPACING. SIDE LAP CONNECTIONS AS DIRECTED BY THE MANUFACTURER.
GENERAL STRUCTURAL
NOTES
c
These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By:
Drawn By:
Designed By:
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200
Edmond, Oklahoma 73034
405.340.8552 Telephone
405.340.5707 Fax
www.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set
8.25.2020 65% Progress Set
8.31.2020 Issued for Permit
9.25.2020 95% Progress Set
RCD
RD
RCD
OKC MAPS 3 HEALTH
AND WELLNESS
CENTER #3
Project Address:
N. Lincoln Blvd. and NE 36th St.
Oklahoma City, OK 73105
TRUMBLE DEAN, LLC
8512 S. PENNSYLVANIA AVE., SUITE A
OKLAHOMA CITY, OK 73159
405.601.0662 405.848.9202
CERTIFICATE OF AUTHORITY NO. 3667
EXPIRES: JUNE 30, 2021
11.30.2020 Issued for Construction
S1.1
IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 17 OF THE 2015 INTERNATIONAL BUILDING CODE, THE
OWNER SHALL SELECT QUALIFIED PERSONNEL TO PERFORM THE SPECIAL INSPECTIONS SHOWN IN THE
SCHEDULES. THE CONTRACTOR SHALL PAY FOR THE SPECIAL INSPECTION SERVICES.
THE SPECIAL INSPECTIONS DO NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY TO PERFORM THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL COOPERATE WITH THE
SPECIAL INSPECTOR TO ALLOW ACCESS TO THE WORK FOR THE REQUIRED INSPECTIONS.
THE CONTRACTOR SHALL NOTIFY THE INSPECTOR AT LEAST 24 HOURS IN ADVANCE OF ALL WORK REQUIRING
INSPECTIONS.
SITE VISITS MADE BY THE STRUCTURAL ENGINEER OF RECORD (E.O.R.) ARE NOT THE SAME AS SPECIAL
INSPECTIONS IN ACCORDANCE WITH CHAPTER 17 OF THE 2015 IBC UNLESS A SEPARATE CONTRACT HAS BEEN
MADE BETWEEN THE OWNER AND E.O.R. FOR THE E.O.R. TO PERFORM THE SPECIAL INSPECTIONS.
THE SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION
REPORTS TO THE BUILDING OFFICIAL, THE ARCHITECT AND ENGINEER OF RECORD. UNLESS OTHERWISE
REQUIRED BY THE BUILDING OFFICIAL IN WRITING AT THE TIME THE BUILDING PERMIT IS ISSUED, THE SPECIAL
INSPECTOR SHALL SUBMIT A FINAL REPORT OF SPECIAL INSPECTIONS TO THE BUILDING OFFICIAL. UNLESS
NOTIFIED IN WRITING OTHERWISE, THE SPECIAL INSPECTOR SHALL SUBMIT MONTHLY WRITTEN INSPECTION
REPORTS AND A COPY OF THE FINAL REPORT OF SPECIAL INSPECTIONS TO THE ARCHITECT AND ENGINEER OF
RECORD. THE ARCHITECT SHALL PROVIDE A COPY OF THE FINAL REPORT OF SPECIAL INSPECTIONS TO THE
OWNER. THE FINAL REPORT OF SPECIAL INSPECTIONS SHALL DOCUMENT THE COMPLETION OF ALL REQUIRED
SPECIAL INSPECTIONS, TESTING AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE MONTHLY
INSPECTION REPORTS. THE FINAL REPORT OF SPECIAL INSPECTIONS SHALL BE SUBMITTED PRIOR TO
ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY.
DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR
CORRECTION. IF SUCH DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCY SHALL BE BROUGHT TO
THE IMMEDIATE ATTENTION OF THE BUILDING OFFICIAL, THE ARCHITECT AND THE ENGINEER OF RECORD. THE
MONTHLY INSPECTION REPORTS SHALL PROVIDE A DETAILED DESCRIPTION OF SUCH DISCREPANCIES AND
THE CORRECTIONS MADE OR NOT MADE. THE DETAILED DESCRIPTION SHALL INCLUDE, BUT IS NOT LIMITED
TO: THE NATURE OF DISCREPANCY, LOCATION OF THE DISCREPANCY WITH RESPECT TO GRID LINES,
CORRECTIONS MADE, AND DOCUMENTATION OF ANY CONVERSATIONS MADE WITH THE BUILDING OFFICIAL,
ARCHITECT AND ENGINEER OF RECORD TO OBTAIN APPROVAL FOR CORRECTIONS.
STATEMENT OF SPECIAL INSPECTIONS
SOILS AND FOUNDATIONS
VERIFICATION AND INSPECTION
IBC SECTION 1705.6, 1705.8
VERIFY IMPORTED STRUCTURAL FILL MATERIAL SATISFIES
REQUIREMENTS IN GEOTECH REPORT
PRIOR TO PLACEMENT OF STRUCTURAL FILL, DETERMINE
THAT THE SITE HAS BEEN PREPARED IN ACCORDANCE WITH
PROJECT GEOTECH REPORT
DURING PLACEMENT AND COMPACTION OF STRUCTURAL FILL,
VERIFY MATERIAL BEING USED AND MAXIMUM LIFT
THICKNESS COMPLIES WITH PROJECT GEOTECH REPORT
TEST IN-PLACE DRY DENSITY OF COMPACTED FILL COMPLIES
WITH PROJECT GEOTECH REPORT
VERIFY EXCAVATIONS FOR FOOTINGS ARE INTO PROPER
BEARING STRATA AS DESCRIBED IN PROJECT GEOTECH
REPORT.
VERIFY EXCAVATIONS FOR FOOTINGS ARE AT THE PROPER
DEPTH AND WIDTH PER DRAWINGS
CONTINUOUS PERIODIC INSPECTOR
IDENTIFICATION
X
X
X
X
X
PE/GE, EIT OR
ETT
PE/GE, EIT OR
ETT
PE/GE, EIT OR
ETT
PE/GE, EIT OR
ETT
PE/GE, EIT OR
ETT
CAST-IN-PLACE CONCRETE
VERIFICATION AND INSPECTION
IBC SECTION 1705.3
INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF CONCRETE MEMBER BEING FORMED
INSPECT REINFORCING STEEL SIZES AND PLACEMENT ARE IN
ACCORDANCE WITH PROJECT DRAWINGS. VERIFY CLEAR
COVER. VERIFY REBAR IS ADEQUATELY SUPPORTED TO
PREVENT DISPLACEMENT DURING CONCRETE POUR
VERIFY ANY WELDED REBAR IS ASTM A706.
INSPECT ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED
ITEMS PRIOR TO CONCRETE PLACEMENT. VERIFY SIZES,
LOCATIONS AND LENGTH OF EMBEDMENT. VERIFY ITEMS ARE
SECURED TO AVOID DISPLACEMENT DURING CONCRETE
POUR
VERIFY USE OF APPROVED MIX DESIGN FOR COMPONENTS
BEING CONSTRUCTED
VERIFY WATER ADDED TO MIX AT JOB SITE DOES NOT RESULT
IN TOTAL WATER CONTENT BEING EXCEEDED PER APPROVED
MIX DESIGN
SAMPLE FRESH CONCRETE PER PROJECT SPECIFICATIONS
VERIFY COLD WEATHER AND HOT WEATHER PROCEDURES
ARE FOLLOWED
OBSERVE CONCRETE PLACEMENT AND VERIFY PROPER
APPLICATION TECHNIQUES USED
VERIFY CURING TECHNIQUES AND MATERIALS SATISFY
PROJECT SPECIFICATIONS AND APPROVED SUBMITTALS
CONTINUOUS PERIODIC INSPECTOR
IDENTIFICATION
X
PE/SE OR EIT
X
X AWS-CWI
X
ACI-CFTT OR
ACI-STT
X
X
X
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
X
X
X
QUALIFICATIONS OF INSPECTORS AND TESTING TECHNICIANS
THE QUALIFICATIONS OF ALL PERSONNEL PERFORMING SPECIAL INSPECTION AND TESTING ACTIVITIES
ARE SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL. THE CREDENTIALS OF ALL INSPECTORS
AND TESTING TECHNICIANS SHALL BE PROVIDED IF REQUESTED. THE OWNER SHALL PROVIDE THE
IDENTITY OF THE SPECIAL INSPECTOR IF REQUESTED BY THE BUILDING OFFICIAL. IF REQUESTED, THE
SPECIAL INSPECTOR SHALL PROVIDE THE IDENTITIES OF ALL PERSONNEL ACTING ON THE SPECIAL
INSPECTOR'S BEHALF DURING THE PROJECT.
THE FOLLOWING DESIGNATIONS APPEAR BELOW THE INSPECTOR IDENTIFICATION ON THE SCHEDULES
AND INDICATE THAT THE INDIVIDUAL PERFORMING THE STIPULATED INSPECTION OR TEST HAS A
SPECIFIC CERTIFICATION OR LICENSE.
PE/SE STRUCTURAL ENGINEER - A PROFESSIONAL ENGINEER LICENSED IN THE
STATE OF OKLAHOMA SPECIALIZING IN THE DESIGN OF BUILDING
STRUCTURES.
PE/GE GEOTECHNICAL ENGINEER - A PROFESSIONAL ENGINEER LICENSED IN THE
STATE OF OKLAHOMA SPECIALIZING IN SOIL MECHANICS AND FOUNDATIONS.
EIT ENGINEER-IN-TRAINING - A GRADUATE ENGINEER WHO HAS PASSED THE
FUNDAMENTALS OF ENGINEERING EXAMINATION AND IS REGISTERED WITH
THE STATE OF OKLAHOMA AS AN EIT.
ETT EXPERIENCED TESTING TECHNICIAN - AN EXPERIENCED TESTING TECHNICIAN
WITH A MINIMUM 5 YEARS EXPERIENCE WITH THE STIPULATED TEST OR
INSPECTION.
AMERICAN CONCRETE INSTITUTE (ACI) CERTIFICATION
ACI-CFTT CONCRETE FIELD TESTING TECHNICIAN - GRADE 1
ACI-CCI CONCRETE CONSTRUCTION INSPECTOR
ACI-LTT LABORATORY TESTING TECHNICIAN - GRADE 1 & 2
ACI-STT STRENGTH TESTING TECHNICIAN
AMERICAN WELDING SOCIETY (AWS) CERTIFICATION
AWS-CWI CERTIFIED WELDING INSPECTOR
AWS/AISC-SSI CERTIFIED STRUCTURAL STEEL INSPECTOR
INTERNATIONAL CODE COUNCIL (ICC) CERTIFICATION
ICC-SMSI STRUCTURAL MASONRY SPECIAL INSPECTOR
ICC-SWSI STRUCTURAL STEEL AND WELDING SPECIAL INSPECTOR
ICC-SFSI SPRAY-APPLIED FIREPROOFING SPECIAL INSPECTOR
ICC-PCSI PRESTRESSED CONCRETE SPECIAL INSPECTOR
ICC-RCSI REINFORCED CONCRETE SPECIAL INSPECTOR
NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET)
NICET-CT CONCRETE TECHNICIAN - LEVELS I, II, III & IV
NICET-ST SOILS TECHNICIAN - LEVELS I, II, III & IV
NICET-GET GEOTECHNICAL ENGINEERING TECHNICIAN - LEVELS I, II, III & IV
WHERE FABRICATION OF STRUCTURAL LOAD BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON
THE PREMISES OF A FABRICTOR'S SHOP, THE SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE
REQUIRED BY IBC SECTION 1704.2.5 AND AS REQUIRED ELSEWHERE IN THE BUILDING CODE.
WELDING INSPECTION SHALL BE IN COMPLIANCE WITH AWSD1.1. THE BASIS FOR THE WELDING INSPECTOR
SHALL BE PER AWS D1.1.
SPECIAL INSPECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE QUALITY ASSURANCE
INSPECTION REQUIREMENTS OF AISC 360, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS.
STRUCTURAL MASONRY CONSTRUCTION SHALL BE INSPECTED AND VERIFIED IN ACCORDANCE WITH TMS402,
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES.
STRUCTURAL STEEL CONSTRUCTION
VERIFICATION AND INSPECTION
IBC SECTION 1705.2
MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS
CONTINUOUS PERIODIC INSPECTOR
IDENTIFICATION
XPE/SE OR EITIDENTIFICATION MARKINGS CONFORM TO ASTM
STANDARDS SPECIFIED IN PROJECT CONSTRUCTION
DOCUMENTS
MANUFACTURER'S CERTIFICATE OF COMPLIANCEX
PE/SE OR EIT
INSPECT BOLTED, BEARING-TYPE CONNECTIONS
IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN PROJECT CONSTRUCTION
DOCUMENTS AND APPROVED STEEL SHOP DRAWINGS
MANUFACTURER'S CERTIFIED TEST REPORTS
INSPECT ANCHOR BOLTS PRIOR TO STEEL ERECTION TO VERIFY
BOLTS ARE UNDAMAGED AND READY FOR BASEPLATES
MATERIAL VERIFICATION OF STRUCTURAL STEEL. REVIEW SUBMITTALS FROM FABRICATOR
IDENTIFICATION MARKINGS TO CONFORM TO AWS
SPECIFICATION IN PROJECT CONSTRUCTION DOCUMENTS
- REVIEW PACKAGING
VERIFY FILLER MATERIALS ARE STORED PROPERLY ON
SITE
MATERIAL VERIFICATION OF WELD FILLER MATERIALS
COMPLETE AND PARTIAL PENETRATION GROOVE WELDS
SINGLE PASS FILLET WELDS LESS THAN 5/16"
INSPECTION OF SHOP AND FIELD WELDS FOR STRUCTURAL STEEL
DETAILS FOR BRACING AND STIFFENING
MEMBER LOCATIONS
APPLICATION OF JOINT DETAILS AT EACH CONNECTION
INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE WITH PROJECT CONSTRUCTION DOCUMENTS AND
APPROVED STEEL SHOP DRAWINGS
INSPECTION OF METAL FLOOR AND ROOF DECK SUPPORT AND SIDELAP CONNECTIONS
VERIFY FASTENER SIZES AND LOCATIONS
VERIFY FASTENERS INSTALLED PER MANUFACTURER'S
REQUIREMENTS AND PER PROJECT CONSTRUCTION
DOCUMENTS
XPE/SE OR EIT
XPE/SE OR EIT OR
AWS/AISC-SSI OR
ICC-SBSI
PE/SE OR EIT
PE/SE OR EIT
AWS-CWI
X
X
X
XPE/SE OR EIT
XPE/SE OR EIT
XPE/SE OR EIT
XPE/SE OR EIT
XPE/SE OR EIT
AWS-CWI
AWS-CWI
AWS-CWI
INSTALLATION OF OPEN-WEB STEEL JOISTS
END CONNECTION - WELDED OR BOLTED
BRIDGING - HORIZONTAL OR DIAGONAL
VERIFY BRIDGING INSTALLED IN
ACCORDANCE WITH APPROVED JOIST
SUBMITTALS
STRUCTURAL STEEL FABRICATOR INSPECTIONS
VERIFICATION AND INSPECTION
IBC SECTION 1705.2
FABRICATOR'S PROCEDURES:
AISC CERTIFICATION - FABRICATOR TO PROVIDE COPY OF
CERTIFICATION TO INSPECTOR FOR REVIEW.
-OR-
FABRICATOR TO PROVIDE COPY OF WRITTEN PROCEDURAL
AND QUALITY CONTROL MANUALS AND PERIODIC AUDITING OF
FABRICATION PRACTICES BY AN APPROVED SPECIAL
INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE
APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF
COMPLIANCE TO THE BUILDING CODE OFFICIAL AND OWNER
STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE
WITH THE PROJECT CONSTRUCTION DOCUMENTS.
-OR-
SPECIAL INSPECTION OF THE FABRICATED ITEMS BY OWNER'S
SPECIAL INSPECTOR DURING FABRICATION. INSPECTIONS TO
INCLUDE SHOP WELDED AND BOLTED ITEMS.
CONTINUOUS PERIODIC INSPECTOR
IDENTIFICATION
PE/SE OR EITX
X
PE/GE, EIT OR
ETT
LOAD BEARING CONCRETE MASONRY UNITS (CMU) LEVEL 1
VERIFICATION AND INSPECTION
IBC SECTION 1705.4
AS MASONRY CONSTRUCTION BEGINS, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE.
CONTINUOUS PERIODIC INSPECTOR
IDENTIFICATION
X
AWS-CWI
X
X
X
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
VERIFICATION OF f'm PRIOR TO CONSTRUCTION
PROPRTIONS OF SITE-PREPARED MORTAR.
REVIEW CERTIFICATIONS FOR GROUT AND MORTAR
PRODUCTS TO ENSURE COMPLIANCE WITH PROJECT
SPECIFICATIONS
CONSTRUCTION OF MORTAR JOINTS
LOCATION OF REINFORCEMENT, CONNECTORS AND
ANCHORAGES. VERIFY REBAR POSITIONERS ARE USED
AT LEAST 2 PER EACH LENGTH OF REBAR BETWEEN
SPLICES
DURING CONSTRUCTION THE INSPECTION PROGRAM SHALL VERIFY
SIZE AND LOCATION OF STRUCTURAL ELEMENTS
TYPE, SIZE AND LOCATION OF ANCHORS, INCLUDING
OTHER DETAILS OF ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES OR OTHER
CONSTRUCTION.
SPECIFIED SIZE, GRADE AND TYPE OF RENFORCEMENT
AND ANCHOR BOLTS
WELDING OF REINFORCING BARS AND THAT BARS ARE
WELDABLE PER ASTM A706.
COLD-WEATHER PLACEMENT AND PROTECTION OF CMU
IN TEMPERATURES BELOW 40 DEG. F AND HOT-WEATHER
PLACEMENT AND PROTECTION OF CMU IN
TEMPERATURES ABOVE 90 DEG F.
PRIOR TO GROUTING, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE:
GROUT SPACE IS CLEAN AND FREE OF OBSTRUCTIONS
THAT PREVENT FREE FLOW OF GROUT IN VERTICAL AND
HORIZONTAL CELLS CONTAINING REINFORCING
PLACEMENT OF REINFORCEMENT, CONNECTORS AND
ANCHORAGES.
PROPORTIONS OF SITE-PREPARED GROUT
CONSTRUCTION OF MORTAR JOINTS
GROUT PLACEMENT SHALL BE VERIFIED TO ENSURE
COMPLIANCE WITH CODE AND CONSTRUCTION DOCUMENT
PROVISIONS.
XPE/SE OR EIT
XPE/SE OR EIT
XPE/SE OR EIT
PE/SE OR EIT
PE/SE OR EIT
X
PE/SE OR EIT
X
PE/SE OR EIT
X
PE/SE OR EIT
X
PE/SE OR EIT
X
X
X
X
X
X
X
XPE/SE OR EIT
XPE/SE OR EIT
XPE/SE OR EIT
c
These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By:
Drawn By:
Designed By:
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200
Edmond, Oklahoma 73034
405.340.8552 Telephone
405.340.5707 Fax
www.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set
8.25.2020 65% Progress Set
8.31.2020 Issued for Permit
9.25.2020 95% Progress Set
RCD
RD
RCD
OKC MAPS 3 HEALTH
AND WELLNESS
CENTER #3
Project Address:
N. Lincoln Blvd. and NE 36th St.
Oklahoma City, OK 73105
TRUMBLE DEAN, LLC
8512 S. PENNSYLVANIA AVE., SUITE A
OKLAHOMA CITY, OK 73159
405.601.0662 405.848.9202
CERTIFICATE OF AUTHORITY NO. 3667
EXPIRES: JUNE 30, 2021
11.30.2020 Issued for Construction
STATEMENT OF SPECIAL
INSPECTIONS
S1.2
1
1
M
K.2
K
J J
G G
F F
E
D
C
B
A
A
2
2
3
3
3.4
3.4
4
4
5
5
6
6
7
7
8
8
L
E.8
9
9
10 11 12 13 14 15 16 FF
FF
GG
GGEE
DDCCBB
AA
H
P
Q
R
S
T
U
V
K.1
K.4 K.4
11.811.2 12.3
16' - 5 1/2"
3' - 11"
21' - 8"
6' - 6 1/2" 8
' - 3 1/4"
17' - 5 3/4"
6' - 9 3/8"
4' - 6 1/8"
24' - 0"
7' - 2 3/4"
24' - 0"24' - 0"10' - 9 1/4"19' - 4"24' - 0 3/4"
2' - 5 3/4"
16' - 10 5/8"6' - 10"26' - 8"15' - 6 5/8"10' - 5 1/8"
3' - 4 1/8"
3' - 3 5/8"
8' -
11 5
/8"
9' -
9 3/
4"5'
- 0"
20' -
3 7
/8"
2' -
0"
6' -
0 3/
4"11
' - 2
3/4
"26
' - 0
"5'
- 10
"6'
- 7
1/2"
23' -
10
1/2"
22' -
7 3
/4"
13' - 8"
15' - 9 7/8"
15' - 9 7/8"
6' - 3 1/8"
25' - 9"
22' - 5 1/8"
5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)
DD.3
11.910.9
A.13/
8"
5S3.1
2S3.2
POOL FOUNDATION- REFER ARCH AND AQUATICS FOR SIZEAND LOCATION
EDGE OF SLAB ONGRADE AT POOL - TYP
1S3.1
F1
F1
F3F3 F4
F4
C1F3 F3 F8 F3
F4
F9
F3
SEE SHEET S3.1 FOR FOOTING SCHEDULESEE SHEET S6.1 FOR COLUMN SCHEDULE
2S3.1
3S3.1
4S3.1
6S3.1
7S3.1
F5F5 F5 F5
F6F6F6F6
F5 F5 F5
8S3.1
TYP
TYP
F5
F9
F1 F1
F1F3
F1
F3
F1 F4
F5
F1 F1
F7 F7
F1 F1
F1 F1
19' -
9 5
/8"
14' -
9 7
/8"
3' - 9 1/8" 17' - 0 1/8" 3' - 8 3/4"
F3F3 F3 F3
F2
F3
F3
F3F3F3
F2
F3
F3
F1
F3
F3F3
F3
F3F2
F3F1
F1
F3
F3
F1
F3F3
F3
F1
F3
F3
F1
F1
F3
F1
F3F39
S3.1
1S3.2
STEP FOOTING DOWN
STEP FOOTING DOWN
3S3.2
TYPTYP
TYP
TYPTYP
TYP
TYP
8' - 4 1/4"
7' -
5 3/
4"
105.00°
12S3.2
11S3.2
16.1
8" LOAD BEARING CMU- TYP. REFER ARCH FOR WALL LOCATIONS. REFER S7.2 FOR WALL ELEVATION ALONG GRID FF
E.9
8.1
8.1
1' - 6 1/2"
5 1/
4"
13S3.2
F2
C46 C48C54
C5 C5
C56
C5
C5
C4
C55
C4 C55
C4
C2
C11
C10
C11
C9
C4
C3
C3
F2
C6C6
C57
C13 C12 C12 C13
C14 C15
C5 C5
C7C8
C16 C17 C18 C21 C22
1' - 0"19' - 9 1/4"
C25 C26
C19 C20
C23 C24
C27 C28
C58
C30 C29
C59
C31
C34
C32
C34
C34
C35
C36
C37
C75
C38
C42C41
C40
C39
C33
C70
C33
C43
C44
C76
C60
C60
LOAD BEARING SHEAR WALL WITH 6" x 18 GA STUDS AT 16" O.C. TYP
5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)
C52
C51
C2
STEP BACK EDGE OF SLAB1"
RECESS SLAB 1 1/2" -REFER ARCH FOR LOCATION AND EXTENTS - TYP
RECESS SLAB 1 1/2" -REFER ARCH FOR LOCATION AND EXTENTS - TYP
TRENCH DRAIN -REFER ARCH AND MECH. SLOPE SLAB TO DRAIN TYP
RECESS SLAB 3/8" -REFER ARCH FOR LOCATION AND EXTENTS - TYP
20' - 3"
F10
HSS 4X4X5/16 FOR STAIR STRINGER SUPPORT - 2 PLACESCOLUMN C64
C12x20.7 STRINGER TYP -REFER ARCH FOR STAIR DIMENSIONS
D.2
3' -
11 1
/4"
HSS 12x2x1/4 STRINGER TYP - REFER ARCH FOR STAIR DIMENSIONS
4.5
13' - 5"
F1
F1HSS 4X4X5/16 FOR STAIR STRINGER SUPPORT - 2 PLACESCOLUMN C65
12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.1 FOR WALL ELEVATION
SURGE TANK - REFER AQUATICS FOR SIZE AND LOCATION OF TANK AND FLOOR ACCESS HATCH
S.7
AA.9
13' - 4"
1S3.6
8.3 8.8 9.3 10.1 12.8 13.2 13.8
8' - 10 1/8"12' - 0"12' - 0"12' - 0"6' - 2" 11' - 1 3/4" 12' - 0" 12' - 0"
F1F1
F1 F1
L.6
D.6
P.3
9' - 8 7/8"
1S3.4
2S3.4
3S3.4
4S3.4
TYP
5S3.4
6S3.4
7S3.4
TYP8
S3.4
TYP
9S3.4
10S3.4TYP
3S3.1
1S3.2
TYP
3S3.1
3S3.1
7S3.4
TYP
8S3.4
5" CONCRETE SLAB WITH #3 AT 16" O.C. EACH WAY CENTERED IN SLAB OVER 15 MIL VAPOR BARRIER OVER 4" GRANULAR FILL OVER 2'-2" NON-EXPANSIVE STRUCTURAL FILLFINISHED FLOOR ELEV = 100'-0" (1187.50 FT)
C66C67 C68 C69
F3
C70
F3C37
F3C73
TYP
TYP
TYP3
S3.1
3S3.1
3S3.1
3S3.1
3S3.1
9S3.4
10S3.4
TYP
10S3.4
TYP
REFER 4/S3.2 FOR B10 BASEPLATE AT DIAGONAL BRACE - REFER 4/S6.3 FOR BRACE FRAME ELEVATION
SONOTUBE BLOCKOUT AT COLUMN - TYP SIZE AT CONTRACTOR DISCRETION
TYP2' - 6"
4' - 8"
F1
C74
F1
C74
8S3.1
TYP
SONOTUBE BLOCKOUT AT COLUMN - TYP SIZE AT CONTRACTOR DISCRETION
1S3.5
TYP
TYP2' - 3"
2S3.5
3S3.5
TYP
TYP1' - 6"
9" 2' -
3"
1' - 6"
2' - 3"
1' - 6"2' - 3"
7S3.5
TYP
8S3.5
TYP
TYP2' - 0"
TYP
2' -
0"
9S3.5
OFFSET COLUMN 1" EAST FROM GRID BB AT GRIDS S.7 AND T
TYP
10S3.5
1S3.5
TYP
1S3.5
TYP
1S3.5
TYP
TYP
11S3.5
TYP
TYP
TYP
8S3.4
TYP
12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.1 FOR WALL ELEVATION
12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.2 FOR WALL ELEVATION
12" LOAD BEARING CMU SHEAR WALLS TYP - REFER S7.2 FOR WALL ELEVATION
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J. S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.S.J.S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
S.J.
2S3.6
2S3.6
3S3.6
6S5.4
15' - 6 5/8"10' - 5 1/8"3' - 4 1/8"
11.3 11.7
C77
C77 C77
C77
5' - 0" 5' - 0"
RECESS SLAB 1 3/4" -REFER ARCH FOR LOCATION AND EXTENTS - TYP
5S3.6
4S3.6
TYP
TYP
7S4.3
HSS 4x4x5/16 COLUMN FOR GUIDE RAIL SUPPORT - TYP 3 PLACES COORDINATE LOCATIONS WITH ELEVATOR MFRREFER 6/S4.2
c
These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By: RCDDrawn By: RDDesigned By: RCD
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction
11/2
5/20
20 7
:06:
50 A
M
S2.1
FOUNDATION PLAN
OKC MAPS 3 HEALTHAND WELLNESSCENTER #3
3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105
Proj
ect N
umbe
r - O
KC M
APS
3 H
EALT
H A
ND
WEL
LNES
S C
ENTE
R #
3
3/32" = 1'-0"1FOUNDATION PLAN
TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021
N N
1
1
M
K.2
K K
J
GG
FF
E
D
C
B
A
A
2
2
3
3
3.4
3.4
4
4
5
5
6
6
7
7
8
8
L
E.8
9
9
10 11 12 13 14 15 16 FF
FFGG
EE
DDCCBB
AA
H
P
Q
R
S
T
U
V
K.4 K.4
11.811.2 12.3
3' - 3 5/8"
3' - 4 1/8"
10' - 5 1/8" 15' - 6 5/8" 26' - 8" 6' - 10" 16' - 10 5/8"
2' - 5 3/4"
24' - 0 3/4" 19' - 4" 10' - 9 1/4" 24' - 0" 24' - 0" 24' - 0" 4' - 6 1/8"6' - 9 3/8"
17' - 5 3/4"
16' - 5 1/2"
3' - 11"
21' - 8"
6' - 6 1/2" 8
' - 3 1/4"
22' - 5 1/8"
25' - 9"
6' - 3 1/8"
13' - 4"
15' - 9 7/8"
13' - 8"
8' -
11 5
/8"
9' -
9 3/
4"5'
- 0"
20' -
3 7
/8"
2' -
0"
6' -
0 3/
4"11
' - 2
3/4
"26
' - 0
"5'
- 10
"6'
- 7
1/2"
14' -
9 7
/8"
9' -
0 5/
8"22
' - 7
3/4
"8'
- 9
1/2"
W27
X84
W27
X84
W27
X84
W27
X84
W18
X35
W18
X35
W27X84W27X84 W27X84
W27X84W27X84
W27
X84
W27
X84
W27X84 W27X84
W18X35
W18X35
W18
X35
W24
X55
W18
X35
W18
X35
W24X55
W18
X35
W18
X35
W18
X35
W24
X55
W18X35 W18X35 W18X35
W18
X35
W24X55
W27X84
W27
X84
W27X84
W27X84
W18X35W24X55
W27
X84
W14
X22
W14
X22
W14
X22
W14
X22
W21X44
W21X44
W27
X84
W24X55
W24X55
W21
X44
W18
X35
W14
X22
W14
X22
W14
X22
W14X22
HSS
10X6
X3/8
HSS
10X6
X3/8
W14
X22
W18X35
W24
X55
W24
X55
W16X31
W16X31
W16X31
W18X35
W14X22
W12X19
W14X22
W18X35
W30X90
W16X31
W16X31
W14X22
W14X22
W14X22
W14X22
W14X22
W12X19
W12X19
10K1
W14X22
W12X19
W12X19
W12X19
W14X22
W18X35
W30X90
W24X62
W16X31
W16X31
W24X62
W14X22
W30X90
W14X22
W14X22
W16X31
28LH09
28LH09
28LH09
W14X22
W24X68
W18X35
W14X22
W24X55
W24X55
W14X22
W14X22
W14X22
W18X35
W16X31
14K1
14K1
W12X19
W18X35
W24X55
W24X55
W24X55
W27
X84
W24X55W24X55 W14X22
W24X55
W18X35 W14X22
W24X55
28K10
28K10
28K10
28K10
28K10
28K10
5x30
.25
5x30
.25
5x30
.25
5x30
.25
5x30
.25
4" CONCRETE SLAB ON 1.0C x 20 GA. METAL DECK WITH #3 AT 18" O.C. EACH WAY. FINISHED FLOOR ELEV = 115'-4"
3" TYPE N x 20 GAUGE GALVANIZED METAL DECK ABOVE THE GLULAMS
7" EPIC TORIS ACOUSTICAL DECK WITH NATACOAT AND BAGGED INSULATION
1 1/2" x 20 GA WIDE RIB GALVANIZED METAL ROOF DECK - TYP UNLESS NOTED OTHERWISE
DIAGONAL BRACE -REFER 2/S6.3
DIAGONAL BRACE AND WIND GIRTS -REFER 1/S6.3
DIAGONAL BRACES -REFER 1/S6.2
DIAGONAL BRACES AND WIND GIRTS -REFER 1/S6.5
DIAGONAL BRACES AND WIND GIRTS -REFER 3/S6.2
DD.3
5x30
.25
6.75
x48.
125
6.75
x48.
125
6.75
x48.
125
6.75
x48.
125
W14
X22
W14X22
W14X22
W14X22
11.910.9
A.1
1 1/2" x 20 GA. WIDE RIB GALVANIZED METAL ROOF DECK
DECK BRG EL = 117'-10 1/2"
DECK BRG EL = 120'-11 1/4"
DECK BRG EL =122'-7 3/4" TYP
DECK BRG EL = 113'-8 /4"
SLOPE 1/4:1
2
SLOPE 1:12
SLO
PE 1
:12
SLOPE 1:12SLOPE 3/4:12
SLOPE 1:12
DECK BRG EL = 115'-6"
DECK BRG EL = 115'-8"
DECK BRG EL =113'-8 3/4"
SLOPE 1/4:1
2
DECK BRG EL = 120'-11 1/4 (HIGH)DECK BRG EL = 116'-3 1/16" (LOW)
DECK BRG EL =116'-8 1/4" (LOW)DECK BRG EL = 122'-9 1/4" (HIGH)
DEC
K BR
G E
L =
119'
-11
3/8"
HSS16X8X3/8 DIAGONALCOLUMN TYP 8 PLACESREFER 1/S5.6 AND 2/S5.6
1S5.1
TYP
2S5.1
3S5.1
4S5.1
TYP
TYP
TYP
5S5.1
6S5.1
TYP
7S5.1
TYP
LOW
HIG
H
LOW
LOW
LOW
HIG
H
HIG
H
HIG
H
HIG
H
LOW
TYP
HIG
HLO
W
HIGH
LOW
8S5.1
8' - 4 1/4"13' - 11 1/4"14' - 0"14' - 0"14' - 0"
14' - 0"
DECK BRG EL = 124'-4 3/8"
DECK BRG EL (HIGH) = 128'-6 7/8"
DECK BRG EL = 115'-8" TYP
TYP
1S4.1
2S4.1
TYPTYP
4S4.1
TYP
5S4.1
6S4.1
7S4.1
TYP
TYP
8S4.1
TYP
9S4.1
1S4.2
2S4.2
3S4.2
TYP
DECK BRG EL = 115'-8"
TOP OF CMU WALLAND DECK BRG EL = 115'-8"
DECK BRG EL = 116'-3"
SLOPE 1/4:1
2
SLOPE 1/4:12
16.1
TOP OF CMU WALLEL = 115'-8"
DECK BRG EL = 116'-1 1/2" TYPAT LOW ROOF
SLO
PE 1
/4:1
2
E.9
8.1
8.1
5x30
.25
1' - 6 1/2"3/
8"5
1/4"
C61 C49
C45
C45
C49
C45
C45
C45
C61
C62 C47 C63
C63
C49
C49
C50
6"x16 GA RAFTER AT 24" O.C. TYP
1 1/2" x 20 GA WIDE RIB GALVANIZED METAL ROOF DECK - TYP UNLESS NOTED OTHERWISE
SLOPE 3:12
TOP OF WALLEL = 109'-10 1/4"
TOP OF WALLEL = 107'-10 1/4"
SEE SHEET S6.1 FOR COLUMN SCHEDULE
W14X22
W27X84
DECK BRG EL = 116'-3 1/8"
ALL STEEL BEAMS ABOVE POOL STORAGE,CHEMICAL STORAGE ROOMS AND POOL EQUIPMENT ROOM SHALL HAVE A ZINC RICHPRIMER, PAINTED WITH AN EPOXY INTERMEDIATECOAT AND A POLYURETHANE TOP COAT. ALLEMBED PLATES SHALL BE GALVANIZED AND PAINTED WITH EPOXY PAINT AND POLYURETHANETOP COAT AFTER WELDING.
1' - 0"
(HIGH)
W18X35 (LO
W)
DIAGONAL BRACES -REFER 2/S6.2
DIAGONAL BRACE -REFER 4/S6.3
DIAGONAL BRACES -REFER 3/S6.3
DIAGONAL BRACES -REFER 6/S6.3
DIAGONAL BRACE -REFER 5/S6.3
DIAGONAL BRACE -REFER 5/S6.3
DIAGONAL BRACE -REFER 7/S6.3
W18X35
W18
X35
W24
X55
W27X84 W27X84
W14X22
W14X22
4.5
14K3 AT 2'-6" O.C.14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C.
14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C. 14K3 AT 2'-6" O.C.
W14X22 AT 2'-6" O.C. W12X19 AT 2'-6" O.C. W14X22 AT 2'-6" O.C.
28K6 AT 2'-6" O.C.
14K3 AT 2'-6" O.C.
28K6 AT 2'-6" O.C.
28K6 AT 2'-6" O.C.
20K4 AT 2'-6" O.C.
20K4 AT 2'-6" O.C.
T.O.S. EL = 115'-4" TYP
W12X19
W14X22 AT W14X22 AT W14X22 AT 2'-6" O.C.
2'-6" O.C.2'-6" O.C.
W14X22 AT 2'-6" O.C. W14X22 AT 2'-6" O.C. W14X22 AT 2'-6" O.C.
5 SP
AT
5'-0
" O.C
.
5' -
11"
20LH04 AT 5'-0" O
.C.
20LH06 AT 5'-0" O
.C.
5' - 6"
3' - 4 1/2"
20LH06 AT 5'-0" O
.C.
5' - 0"
5' - 3"2 SP AT 5'-0"
24K6 AT 5'-0" O.C
.
24K6 AT 5'-0" O.C
.
4' - 11 3/4"5' - 0 1/4"
14K1 AT 5'-0" O.C
.
14K1 AT
5'-0" O.C
.
5' - 0"5' - 0"
5' - 0"
10K1 AT 5'-0" O.C
.5' - 0"
3' - 3"10K1 AT 5'-0" O
.C.
EQEQ
S.7W14X
22
W14X22
W14X22
14K1
14K1
14K114K1
14K1
14K1
14K1
14K1
AA.9
DECK BRG EL = 123'-5 5/8"AT HIGH ROOF
DECK BRG EL= 126'-11 7/32"
8.3 8.8 9.3 10.1 12.8 13.2 13.8
HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON GRID WITH +/- 1/4" TOLERANCE. MAXIMUM ALLOWABLE SWEEP = 1/2" FOR BEAMS SUPPORTING LOUVER SCREEN POSTS.
L4x4x1/4 BRACE - TYP EACH POST
HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON CMU WALL WITH +/- 1/4" TOLERANCE FROM CENTER OF WALL. NOTE THAT WALL IS NOT CENTERED ON THE GRID
HSS 4x4x3/8" POSTS FOR LOUVER SCREENS. POSTS TO BE CENTERED ON GRID A.1 WITH +/- 1/4" TOLERANCE. MAXIMUM ALLOWABLE SWEEP = 3/8" FOR BEAMS SUPPORTING LOUVER SCREEN POSTS.
8S4.2
4S5.2
TYP
6S5.2
28K10
TYP7
S5.2
TYP
8S5.2
TYP
9S4.2
L.6
K.3K.3
D.6
P.3
W16X31
9' - 8 7/8"
15' - 9 7/8"
W14X22
WIND GIRTS -REFER 3/S6.5
WIND GIRTS -REFER 1/S6.6
WIND GIRTS -REFER 1/S6.6
WIND GIRT -REFER 4/S6.5
WIND GIRT -REFER 3/S6.6
17' -
5 1
/4"
15' -
3"
S2.41
S2.42
6S5.4
S2.51
S2.52
S2.32
7S5.4
8S5.4
1S4.3
8S4.1
OPPHAND
2S4.3
3S4.3
TYP
4S4.3
5S4.3
6S4.3
7S4.3
TYP
TYP
S2.43
6' -
1 1/
2"
S2.45
S2.44
W21X44
2'-6" O.C.
W14X22 AT
C78 - REFER 3/S6.6
REFER 3/S6.6 FOR WINDOW GIRTS
DIAGONAL BRACES -REFER 2/S6.5
DIAGONAL BRACE -REFER 5/S6.5
15S4.4
C71
C72
c
These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By: RCDDrawn By: RDDesigned By: RCD
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction
11/2
5/20
20 7
:06:
19 A
M
S2.2
SECOND FLOORAND LOW ROOFFRAMING PLAN
OKC MAPS 3 HEALTHAND WELLNESSCENTER #3
3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105
Proj
ect N
umbe
r - O
KC M
APS
3 H
EALT
H A
ND
WEL
LNES
S C
ENTE
R #
3
3/32" = 1'-0"1SECOND FLOOR AND LOW ROOFFRAMING PLAN
TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021
N
1
1
M
K.2
K
G
F
D
B
2
2
3
3
3.4
3.4
4
4
5
5
6
6
7
7
8
8
L
3' - 3 5/8"
3' - 4 1/8"
10' - 5 1/8" 15' - 6 5/8" 26' - 8" 6' - 10" 16' - 10 5/8"
2' - 5 3/4"
14' -
9 3
/4"
31' -
10"
23' -
10
1/2"
22' -
7 3
/4"
8' -
9 1/
2"
W16
X31
W16
X31
W16
X31
W16X31 W16X31 W16X31
W21
X50
W21
X50
W21
X50
W16
X31
W21
X50
W21
X50
W21
X50
W21
X50
W27
X84
W16X31 W16X31W18X35
W18X35 W18X35 W18X35HSS
6X6X
3/8
HSS6X6X3/8
HSS
6X6X
3/8
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
44LH12
W12X19
W12X19
W14
X22
W14
X22
DIAGONAL BRACES -REFER 2/S6.2
DIAGONAL BRACES -REFER 1/S6.2
DIAGONAL BRACES -REFER 4/S6.2
44LH12
A.1
1S5.2
1 1/2" WIDE RIB x 20 GAUGE GALVANIZED METAL ROOF DECK
SLOPE 1:12
HIG
H
LOW
HIG
H
W14
X22
LOW
TYP
2S5.2
E.9
44SLH14 - REFER 1/S5.5 FOR LOAD DIAGRAM
8.1
8.1
SEE SHEET S6.1 FOR COLUMN SCHEDULE
C53
DECK BRG EL = 135'-4 3/4"TYP
DECK BRG EL = 128'-6 1/2" TYP
1 1/2" WIDE RIB x 20 GAUGE GALVANIZED METAL ROOF DECK DECK BRG EL = 124'-8" (LOW)
DIAGONAL BRACES -REFER 2/S6.2
HSS 8X6X5/16 AT 2'-6" O.C. -6 PLACESHSS 6X6X5/16 AT 2'-6" O.C. -
5 PLACESHSS 6X6X5/16 AT 5'-0" O.C. -10 PLACES
W14X22
8' -
11 5
/8"
22' -
9 1
/8"
11' -
2 3
/4"
6' -
7 1/
2"3'
- 7
1/2"
18 S
P AT
5'-0
" O.C
.4'
- 11
1/8
"5'
- 1
1/4"
7 SP
AT
5'-0
" O.C
.5'
- 0"
10' -
2 1
/2"
L.6
K.3
D.6
TYP
TYP
2S5.5
3S5.5
TYP
J J
K.1 K.1
K.4 K.4
11.811.2
12.311.9
11.9
10.9
10.9
2S5.6
10.1
1S5.6
11.3
11.3
11.7
11.7
2S5.6
5 SP
ACES
AT
5'-0
" O.C
.
HSS16X8X3/8
HSS16X8X3/8
HSS10X4X3/8
HSS10X4X3/8
HSS10X4X3/8
HSS10X4X3/8
HSS16X8X3/8
HSS10X4X3/8
HSS10X4X3/8
HSS16X8X3/8
HSS10X4X3/8
HSS10X4X3/8
2' -
2"5
SPAC
ES A
T 5'
-0" O
.C.
HSS
16X8
X3/8
HSS
16X8
X3/8
SLOPE 1:12
c
These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By: RCDDrawn By: RDDesigned By: RCD
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction
11/2
5/20
20 7
:00:
07 A
M
S2.3
ROOF FRAMINGPLANS
OKC MAPS 3 HEALTHAND WELLNESSCENTER #3
3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105
Proj
ect N
umbe
r - O
KC M
APS
3 H
EALT
H A
ND
WEL
LNES
S C
ENTE
R #
3
1/8" = 1'-0"1ROOF FRAMING PLAN - GYMNASIUM
TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021
1/4" = 1'-0"2ENLARGED - ENTRY ROOF FRAMINGPLAN
F F
D
C C
8
8
9
9
10
10
A.1 A.1
3S5.2
8.1
8.1
6S5.3
W14X22 W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22 W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
W18
X35
W24
X68
W14X22 (LOW)
W24X55 (HIGH)
W14X22 (LOW) DECK BRG EL = 116'-1 1/2"
W24X55 (HIGH)
W18
X35
W18
X35
DECK BRG EL = 115'-8"
DECK BRG EL = 126'-11 7/32" (HIGH) AT GRID 8.1
DECK BRG EL = 123'-5 5/8" (HIGH) AT FACE OF CMU
SLO
PE 1
/4:1
2
SLOPE 1:12 (HIGH)
1S5.3
9S5.2
2S5.3
TYP
3S5.3
4S5.3
TYP
TYP
5S5.3
TYP
7S5.3
8S5.3
RTU-1
RTU-5
RTU-4
RTU-3RTU-2
4' -
2 1/
8"5'
- 0"
5' -
0"4'
- 7
1/4"
5' -
0"2'
- 8
1/2"
5' -
0"5'
- 0"
5' -
0"5'
- 0"
5' - 0" TYP
3' -
8 1/
8"
REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING - TYP
F F
A A
16
16
FF
FF
9S5.1
16.1
2S5.4
W8X21
W8X21
W14X22
W14X22
26K6
26K6
26K6
W30X90
4' -
6 3/
8"5'
- 0"
5' -
0"4'
- 7"
5' -
0 1/
2"
5' -
0"5'
- 0"
4' -
6 3/
4"6'
- 3
7/8"
SLOPE 1/4:12
RTU -8
REFER MECH FOR DUCT PENETRATION SIZES AND LOCATIONS
REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING
W8X21
9S5.1
9S5.1
10S5.1
TYP
11S5.1
TYP
12S5.1
TYP
1S5.4
TYP
TYP
W16X313
S5.4
TYP
4S5.4
5S5.4
G G
F
E
6
6
7
7 8
E.8
8.1
W12
X19
W12
X19
W24
X55 W
12X1
9
W24X55
W18
X35
W18
X35
W24X55
W18X35
W12X19 AT 2'-6" O.C.2' - 0" 2' - 10 1/4"
2' - 9" 2' - 8" 2' - 9"
4S4.3
8S4.3
8S4.3
SIM
W12X19
9S4.3
10S4.3
2' - 6"2' - 6"2' - 6"
11S4.3
1S4.4
2S4.4
3S4.4
3S4.4
TYP
TYP
W24
X55
W18
X35
5X30
.25
GLU
LAM
W18
X35
4S4.4
W18
X35
1S4.1
SIM
B
6
W14
X22
W14
X22
W27
X84
W21X44
14K3
14K3
W14X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W24X55
8' -
9"
8' - 9"
3' - 0" 2' - 6"
2' - 6" 3' - 0" 1' - 9" 2' - 6"
14' -
9"
9S4.4
8S4.4
8S4.4
OPPHAND
W21X44
14S4.4
8S4.3SIM
1
D
B
2 3 3.4
W24X55W14X22
W14
X22
28K6
28K6
W27
X84
W14
X22
W14
X22 W14
X22
W18X35
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14
X22
W14X22 1' - 11" 2' - 6" 2' - 4"
1' - 10 1/8" 1' - 11 1/4"2' - 8 1/8"
3' - 0"
2' - 6"
5' - 6 3/4"3' - 8 1/4"
9' -
3"
14' - 9"HSS
10X6
X3/8
T.
O.S
. EL
= 11
5'-4
"
W12
X19
3' - 4 1/8"
5S4.4
TYP
6S4.4
7S4.4
8S4.4
9S4.4
8S4.4
OPPHAND
10S4.4
11S4.4
12S4.4
13S4.4
c
These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By: RCDDrawn By: RDDesigned By: RCD
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction
11/2
5/20
20 6
:57:
17 A
M
S2.4
ENLARGEDFRAMING PLANS
OKC MAPS 3 HEALTHAND WELLNESSCENTER #3
3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105
Proj
ect N
umbe
r - O
KC M
APS
3 H
EALT
H A
ND
WEL
LNES
S C
ENTE
R #
3
1/4" = 1'-0"1ENLARGED - LOW ROOF FRAMING PLAN- MECH COURTYARD
TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021
1/4" = 1'-0"2ENLARGED - LOW ROOF FRAMING PLAN- RTU8
1/4" = 1'-0"3ENLARGED - SECOND FLOOR FRAMINGPLAN
1/4" = 1'-0"5ENLARGED - SECOND FLOOR FRAMINGPLAN - NE
1/4" = 1'-0"4ENLARGED - SECOND FLOOR FRAMINGPLAN - NW
FF
GG
DD
Q
R
28LH09
28LH09
28LH09
W16X31
W18X35 (HIG
H)W18X
35 (LOW)
W14X22 (H
IGH
)
W14X22 (LO
W)
RTU 7
W14X22
W12X19
REFER MECH FOR DUCT PENETRATION SIZES AND LOCATIONS
REFER 9/S5.3 FOR CURB AND DUCT PENETRATION SUPPORT FRAMING
J
FF
DD
BB
H
DD.3
20LH04
20LH04
20LH04
W14X22
20LH06
20LH06
20LH06
20LH06
20LH06
20LH06
W12X19
14K1
W16X31
W41X22 (HIGH)
W30X90 (LOW)
W30X90
W16X31
W16X31
RTU-6
REFER MECH FOR SIZES AND LOCATIONS OF DUCT PENETRATIONS REFER 9/S5.3 FOR CURB AND DUCT
PENETRATION SUPPORT FRAMING
RTU-9
c
These documents & images are the sole property of Hornbeek Blatt Architects & are not to be reproduced or copied, either wholly or in part in any form without written permission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By: RCDDrawn By: RDDesigned By: RCD
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200Edmond, Oklahoma 73034405.340.8552 Telephone405.340.5707 Faxwww.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set 8.25.2020 65% Progress Set 8.31.2020 Issued for Permit9.25.2020 95% Progress Set11.30.2020 Issued for Construction
11/2
5/20
20 6
:51:
51 A
M
S2.5
ENLARGEDFRAMING PLANS
OKC MAPS 3 HEALTHAND WELLNESSCENTER #3
3820 N. LINCOLN BLVDOKLAHOMA CITY, OK 73105
Proj
ect N
umbe
r - O
KC M
APS
3 H
EALT
H A
ND
WEL
LNES
S C
ENTE
R #
3
TRUMBLE DEAN, LLC 8512 S. PENNSYLVANIA AVE., SUITE AOKLAHOMA CITY, OK 73159405.601.0662 405.848.9202CERTIFICATE OF AUTHORIZATION NO. 3667EXPIRES: JUNE 30, 2021
1/4" = 1'-0"1ENLARGED - LOW ROOF FRAMING PLAN- RTU7
1/4" = 1'-0"2ENLARGED - LOW ROOF FRAMING PLAN- RTU6 AND RTU9
STEEL COLUMN - REFER PLAN
AND COLUMN SCHEDULE
BLOCKOUT
CONCRETE SLAB
REFER PLAN
2" NON-SHRINK GROUT
SPREAD FOOTING CENTERED ON
COLUMN - REFER PLAN
GRANULAR FILL
REFER PLAN
VAPOR
BARRIER
8"
BASEPLATE - REFER
COLUMN SCHEDULE
2'-0"
2'-0"
2'-0"
#3 AT 32" O.C.
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
2 - #6 TOP AND BOTTOM
WITH CORNER BARS
3/4"= 1'-0"
SECTION1
S3.1
1/2" DIA ANCHOR BOLT WITH 6" x 18 GA x 0'-6" COLD
FORMED METAL BLOCKING AT 4'-0" O.C. PROVIDE
1/4" x 3" x 3" STEEL WASHER UNDER NUT. PROVIDE
4 - #10 SELF DRILLING SCREWS THRU EACH SIDE
OF TRACK INTO BLOCKING.
ALT: 1/2" DIA SIMPSON TITEN-HD SCREW ANCHOR
WITH 6" EMBED INTO CONC.
FIN. FLOOR EL.=
REFER PLAN
#3 STIRRUPS
AT 24" O.C.
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
1'-6"
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
8"
6" x 18 GA COLD FORMED
METAL STUDS AT 16" O.C.
7"
CONTRACTOR NOTE:
CONCRETE SLAB
REFER PLAN
2 1/2"
6"
SAWCUT JOINTS MAY BE USED ONLY IF CUTS ARE MADE WITH "SOFF CUT" SAW AND CUT AS
SOON AS CONCRETE WILL SUPPORT THE WEIGHT OF A MAN AND EQUIPMENT WITHOUT
LEAVING IMPRINTS IN CONCRETE.
EVERY THIRD SLAB
REINFORCING BAR SHALL BE
CONTINUOUS THRU THE
SAWJOINT. CUT REMAINING
BARS 3" EACH SIDE OF JOINT
CONCRETE
SLAB
GRANULAR FILL
FORMED SHEAR KEY
6"
VAPOR BARRIER
1'-6"1-6"
CONTRACTOR NOTE:
CONSTRUCTION JOINTS CAN BE USED AT CONTRACTOR DISCRETION INSTEAD OF SAWCUT
JOINTS.
8"
1'-6
"
8"
8"
#4 AT 12" O.C. EACH WAY
CENTER IN SLAB
#3 AT 12" O.C. AROUND
SUMP PIT
WATERPROOFING ALL
AROUND ELEVATOR PIT-
REFER ARCH.
CONT. VOLCLAY
WATERSTOP - TYP
AROUND SUMP PIT
1'-6"
CONCRETE SLAB SLOPED
TO SUMP PIT - REFER 9/S3.1
CONCRETE WALL -
REFER 9/S3.1
COORDINATE SUMP PIT LOCATION WITH
ELEVATOR MFR
3/4"X3/4" CHAMFER-TYP
#4 AT 12" O.C. EACH WAY
CENTERED IN SLAB
#5 VERT AT 16" O.C. WITH ACI
STD. 90 HOOK IN SLAB. CENTER
BARS IN WALL
#4 AT 12" O.C. WITH CORNER
BARS
WATERPROOFING ALL
AROUND ELEVATOR PIT
- REFER ARCH.
SLOPE SLAB TO SUMP
GRANULAR FILL
VAPOR BARRIER
CONCRETE SLAB REFER
PLAN
#3 DOWELS AT 32" O.C.
REFER 1/S3.1
5'-0"
8"
REFER ARCH FOR
ELEVATOR PIT
DIMENSIONS
VOLCLAY RX-101
WATERSTOP CONT
AROUND PIT
3/16
1/2" x 4 1/2" x 0'-10" PLATE WITH 2 -
5/8" DIA HILTI EXPANSION
ANCHORS EMBEDED 4" INTO
CONC
HSS4x4x5/16 COLUMN FOR GUIDE RAIL
SUPPORT - TYP EACH SIDE OF ELEV -
FACE OF COLUMN FLUSH WITH
SHAFTWALL. COORDINATE LOCATIONS
AND QUANTITY OF COLUMNS WITH
ELEVATOR MANUFACTURER
6"
1'-6"
1'-0
"
8"
GRANULAR FILL
2 - #5 WITH CORNER BARS
VAPOR BARRIER
INSULATION - REFER
ARCH
GRID
11 1/2"
EDGE OF SLAB AND
FACE OF STUD
F1
SIZE OF FOOTING
F3
MARK
FOOTING SCHEDULE
REINFORCING
5'-0" x 5'-0" x 1'-0"
5 - #5 EACH WAY
EQUALLY SPACED BOTTOM
F4 6'-0" x 6'-0" x 1'-0"
6 - #5 EACH WAY
EQUALLY SPACED BOTTOM
F5
F6
F7
3'-0" x 3'-0" x 1'-0"
3 - #5 EACH WAY
EQUALLY SPACED BOTTOM
7'-0" x 7'-0" x 1'-0"
7 - #6 EACH WAY
EQUALLY SPACED BOTTOM
11'-0" x 11'-0" x 2'-0"
11 - #6 EACH WAY EQUALLY
SPACED TOP AND BOTTOM
1/4" WIDE x 1 1/4" DEEP
8'-0" x 8'-0" x 1'-6"
8 - #6 EACH WAY EQUALLY
SPACED BOTTOM
2'-0"
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
2 - #6 TOP AND BOTTOM
WITH CORNER BARS
3/4"= 1'-0"
SECTION2
S3.1
ANCHOR - REFER 1/S3.1
FIN. FLOOR EL.=
REFER PLAN
#3 STIRRUPS
AT 24" O.C.
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
1'-6"
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
8"
6" x 18 GA COLD FORMED
METAL STUDS AT 16" O.C.
7"
INSULATION - REFER
ARCH
3"
EDGE OF SLAB AND
FACE OF STUD
A.1
DOWEL - REFER 1/S3.1
2'-0"
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
2 - #6 TOP AND BOTTOM
WITH CORNER BARS
3/4"= 1'-0"
SECTION3
S3.1
ANCHOR - REFER 1/S3.1
FIN. FLOOR EL.=
REFER PLAN
#3 STIRRUPS
AT 24" O.C.
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
1'-6"
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
8"
6" x 18 GA COLD FORMED
METAL STUDS AT 16" O.C.
7"
INSULATION - REFER
ARCH
3"
EDGE OF SLAB AND
FACE OF STUD
GRID
DOWEL - REFER 1/S3.1
CONCRETE SLAB
REFER PLAN
PAVING - REFER
CIVIL
3/4"= 1'-0"
SECTION4
S3.1
ANCHOR - REFER 1/S3.1
FOOTING -
REFER 1/3.1
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
6" x 18 GA COLD FORMED
METAL STUDS AT 16" O.C.
7"
INSULATION - REFER
ARCH
3"
EDGE OF SLAB AND
FACE OF STUD
1
DOWEL - REFER 1/S3.1
3
VAPOR BARRIER
GRANULAR FILL
REFER PLAN
FOOTING - REFER
1/3.1
ANCHOR - REFER 1/S3.1
6" x 18 GA COLD FORMED
METAL STUDS AT 16" O.C.
2'-0"
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
2 - #6 TOP AND BOTTOM
WITH CORNER BARS
3/4"= 1'-0"
SECTION5
S3.1
FIN. FLOOR EL.=
REFER PLAN
#3 STIRRUPS
AT 24" O.C.
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
2'-0"
MASONRY VENEER-
REFER ARCH
12" CMU
8"
8"
INSULATION - REFER
ARCH
7 7/8"
A
3'-6
"
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
#4 HORIZ AT 12" O.C. WITH
CORNER BARS - TYP EACH
FACE
3/4"= 1'-0"
SECTION6
S3.1
L6x6x3/8 x 0'-6" WITH 1/2" DIA x 0'-6"
HEADED STUD ON EACH LEG - TYP
AT EACH CHANNEL
#5 VERT AT 16" O.C. -
CENTERED IN WALL -
TYP
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
8"
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
8"
C6x8.2 AT EACH END OF WINDOW
AND AT 4'-0" O.C. MAX BETWEEN
ENDS OF WINDOW
7"
INSULATION - REFER
ARCH
3
11 1/2"
EDGE OF SLAB AND
FACE OF STUD
1'-0" 1'-4"
1'-0"
3-#6 CONT EQ SPACED. WITH
CORNER BARS - TYP
#5 AT 12"
O.C. - TYP
DOWEL - REFER 1/S3.1
3'-6
"
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
#4 HORIZ AT 12" O.C. WITH
CORNER BARS - TYP EACH
FACE
3/4"= 1'-0"
SECTION7
S3.1
#5 VERT AT 16" O.C. -
CENTERED IN WALL -
TYP
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
8"
MASONRY VENEER-
REFER ARCH
SHEATHING-
REFER ARCH
8"
7"
INSULATION - REFER
ARCH
M
11 3/4"
EDGE OF SLAB AND
FACE OF STUD
1'-0" 1'-4"
1'-0"
3-#6 CONT EQ SPACED. WITH
CORNER BARS - TYP
#5 AT 12"
O.C. - TYP
DOWEL - REFER 1/S3.1
3/4"= 1'-0"
SECTION8
S3.1 3/4"= 1'-0"
SECTION - ELEVATOR PIT9
S3.1 3/4"= 1'-0"
SECTION - ELEVATOR SUMP PIT10
S3.1
NOT TO SCALE
SAWCUT JOINT DETAIL11
S3.1
NOT TO SCALE
KEYED CONSTRUCTION JOINT DETAIL12
S3.1
#5 DOWEL AT 24" O.C. -
LAP 2'-0" WITH VERT
BARS IN WALL - TYP
F2 4'-0" x 4'-0" x 1'-0"
4 - #5 EACH WAY
EQUALLY SPACED BOTTOM
F8 5-0" x 9'-0" x 1'-0"
#5 AT 12" O.C. EACH WAY
BOTTOM
F9 7'-0" x 9'-0" x 1'-0"
#5 AT 12" O.C. EACH WAY
BOTTOM
F10 6'-0" x 6'-0" x 2'-0"
6 - #5 EACH WAY EQUALLY SPACED
TOP AND BOTTOM
WINDOW - REFER
ARCH
EACH FLANGE AND
EACH SIDE OF WEB TYP
1/4
C6x8.2 FULL WIDTH OF WINDOW
STEEL CHANNEL AT EACH END OF
WINDOWS AND AT 4'-0" O.C. MAX
BETWEEN ENDS OF WINDOWS -
REFER 6/S3.1 FOR ADDITIONAL
INFORMATION
WINDOW - REFER
ARCH
S3.1
FOUNDATION SECTIONS
AND DETAILS
c
These documents & images are the sole property ofHornbeek Blatt Architects & are not to be reproduced orcopied, either wholly or in part in any form without writtenpermission from Hornbeek Blatt Architects.
Date: Submission:
Drawing Title:
No.
Sheet No:
Reviewed By:
Drawn By:
Designed By:
Key Plan
Executive Architect
Copyright 2020 © Hornbeek Blatt Architects
HORNBEEK BLATT
101 South Broadway, Suite 200
Edmond, Oklahoma 73034
405.340.8552 Telephone
405.340.5707 Fax
www.hornbeekblatt.com
ra h i t e c t s
Project:
THE ORIGINAL OF THIS DRAWING IS 30" X 42".
300 SPRUCE STREETSUITE 300COLUMBUS, OHIO 43215
PHONE: (614) 461-4664FAX: (614) 280-8881
Design Architect
7.28.2020 35% Progress Set
8.25.2020 65% Progress Set
8.31.2020 Issued for Permit
9.25.2020 95% Progress Set
RCD
RD
RCD
OKC MAPS 3 HEALTH
AND WELLNESS
CENTER #3
Project Address:
N. Lincoln Blvd. and NE 36th St.
Oklahoma City, OK 73105
TRUMBLE DEAN, LLC
8512 S. PENNSYLVANIA AVE., SUITE A
OKLAHOMA CITY, OK 73159
405.601.0662 405.848.9202
CERTIFICATE OF AUTHORITY NO. 3667
EXPIRES: JUNE 30, 2021
11.30.2020 Issued for Construction
AutoCAD SHX TextGRID
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX Text° HOOK IN SLAB. CENTER
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
AutoCAD SHX TextSCALE:
AutoCAD SHX Text.
CONCRETE SLAB
REFER PLAN
PAVING - REFER CIVIL
CONT FOOTING -
REFER 1/S3.1
GRANULAR FILL
VAPOR BARRIER
8"
DOOR OR WINDOW-
REFER ARCH
DOWEL - REFER 1/S3.1
INSULATION - REFER
ARCH
J
1'-0"
1'-4"
NORMAL
REINFORCING
2 VERTICAL BARS AT
CORNERS AND EACH SIDE OF
OPENING
VERTICAL WALL REINFORCING SHALL
EXTEND CONTINUOUSLY FROM
FOUNDATION AND AT LEAST 6" INTO
BOND BEAM AT TOP OF WALL
LINTEL REINF. ABOVE DOOR
OPENING- REFER PLAN AND
LINTEL SCHEDULE
BOND BEAM AT TOP OF WALL - REFER GEN
STRUCT NOTES FOR BOND BEAM REINF
FOR VERT. CMU REINFORCING PROVIDE STD
90^ HOOK INTO BOND BEAM AT TOP OF WALL
BEAM OR
JOIST
PROVIDE 2 BARS FULL
HEIGHT OF WALL AT BEAM
OR JOIST BEARING.
LINTEL ABOVE DOOR
OPENING - EXTEND AT
LEAST 8" EACH SIDE OF
OPENING
LINTEL REINF. ABOVE
WINDOW OPENING- REFER
PLAN AND LINTEL SCHEDULE
2 VERTICAL BARS AT
CORNERS AND EACH SIDE
OF OPENINGS
TYPICAL BOND BEAM -
REFER GEN STRUCT NOTES
BOND BEAM BELOW
WINDOW - EXTEND BOND
BEAM AT LEAST 8" BEYOND
EDGE OF OPENING - TYP
FOUNDATION DOWEL SHALL EXTEND A
MINIMUM OF 30 DIAMETERS INTO
FOUNDATION AND 40 DIAMETERS INTO
MASONRY WALL UNLESS NOTED
OTHERWISE. DOWELS TO MATCH SIZE
AND SPACING OF WALL REINFORCING
3/4"= 1'-0"
SECTION1
S3.2
11.2
PAVING - REFER CIVIL
FOOTING - REFER PLAN AND
SCHECULE2'-6"
STEEL COLUMN - REFER
PLAN
#5 VERT AT EACH CORNER
AND MIDDLE OF EACH FACE
OF PEDESTAL - TYP
4 - #3 TIES EQ SPACED
AT PEDESTAL - TYP
3/4"= 1'-0"
SECTION2
S3.2
8"
1'-4"
11.8
BRACE - REFER FRAME
ELEVATIONS. PROVIDE
ERECTION BOLT AT
FABRICATOR DISCRETION
3/8" PLATE TYP
B10 BASEPLATE
CONC SLAB - REFER
PLAN
2" NON-SHRINK
GROUT TYP
TYP EACH SIDE OF BRACE,
EACH SIDE OF GUSSET PLATE
EACH SIDE OF GUSSET PLATE
TO BASEPLATE AND COLUMN
TYP
5/16
TOP OF CONC
FOOTING
3/4"= 1'-0"
SECTION4
S3.2
GRID
STEEL COLUMN -
REFER PLAN
BRACE - REFER FRAME ELEVATIONS.
PROVIDE ERECTION BOLT AT
FABRICATOR DISCRETION
5/16 6
TYP EACH SIDE OF
BRACE, EACH SIDE
OF GUSSET PLATE
5/16 6
BASEPLATE AND
ANCHORS - REFER
COLUMN SCHEDULE
AND 2/S3.3
CONC SLAB - REFER
PLAN
2" NON-SHRINK
GROUT TYP
TOP OF CONT
FOOTING
EACH SIDE OF
GUSSET PLATE
TYP
5/16
SPREAD FOOTING - REFER
PLAN AND SCHEDULE
3/4"= 1'-0"
DETAIL5
S3.2
3/8" PLATE TYP
NOT TO SCALE
CMU WALL REINFORCING DETAIL - TYP6
S3.2
HECKMAN TYPE 374 OR 376
REBAR POSITIONER AT 24" O.C. -
TYP AT EACH VERT BAR.
HORIZONTAL REINFORCING
AT BOND BEAM - TYP
TYP VERTICAL REINFORCING -
REFER GEN NOTES
NOT TO SCALE
PLAN DETAIL - TYPICAL 8" CMU7
S3.2
HORIZONTAL REINFORCING
AT BOND BEAM - TYP
TYP VERTICAL REINFORCING
- REFER GEN NOTES
HECKMAN TYPE 374 OR 376
REBAR POSITIONER AT 24" O.C. -
TYP AT EACH VERT BAR.
NOT TO SCALE
PLAN DETAIL - TYPICAL 12" CMU8
S3.2
CMU LINTEL SCHEDULE
L3 2 - #5 B12 x 24
LI
MARK
WIDTH x DEPTH
12 x 8
NOMINAL
REINFORCING
2 - #5 B
REMARKS
EXTEND LINTEL AT LEAST 8 INCHES EACH SIDE OF OPENING
L2 12 x 16 2 - #5 B
L5 2 - #5 B8 x 8
L4 2 - #5 B12 x 32
SO
LID
G
RO
UT
FU
LL D
EP
TH
O
F
LIN
TE
L
REINFORCING BARS
1" C
LE
AR
TY
P
LINTEL
WIDTH
8 x 24L6 2 - #5 B
NOT TO SCALE
LINTEL SCHEDULE AND DETAIL9
S3.2
HORIZONTAL REINFORCING
AT BOND BEAM - TYP
TYP VERTICAL REINFORCING
- REFER GEN NOTES
HECKMAN TYPE 374 OR 376
REBAR POSITIONER AT 24" O.C. -
TYP AT EACH VERT BAR.
NOT TO SCALE
PLAN DETAIL - TYPICAL CMU PILASTER10
S3.2
CONTROL JOINT ON ONE
SIDE OF PILASTER - REFER
PLAN FOR LOCATIONS
16" x 16" PILASTER
GRID
6 - #7 VERT IN GROUT FILLED
CELLS FULL HEIGHT OF
PILASTER - TYP
#3 TIES AT 16" O.C. FULL
HEIGHT OF PILASTER
3"
TY
P
3"
TY
P
3" TYP
EACH FACE
EQ
TYP
EQ
TYP
EQ
TYP
EQ
TYP
3"
TY
P
3"
TY
P
EQ
TY
P
EQ
TY
P
2'-0"
CONCRETE SLAB
REFER PLAN
2 - #6 TOP AND BOTTOM
WITH CORNER BARS
3/4"= 1'-0"
SECTION11
S3.2
FIN. FLOOR EL.=
REFER PLAN
#3 STIRRUPS
AT 24" O.C.
GRANULAR FILL
REFER PLAN
VAPOR BARRIER
1'-6"
8" CMU
8"
#5 DOWEL AT 24" O.C. -
LAP 2'-0" WITH VERT
BARS IN WALL - TYP
5 1/4"
HORIZONTAL BAR INTO
PILASTER - EXTEND 2'-0"
INTO WALL - TYP
#4 AT 12" O.C. EACH WAY
CENTERED IN SLAB
#5 VERT AT 16" O.C. WITH ACI
STD. 90 HOOK IN SLAB.
CENTER BARS IN WALL
#4 AT 12" O.C. WITH
CORNER BARS
WATERPROOFING ALL
AROUND ELEVATOR PIT
- REFER ARCH.
SLOPE SLAB TO SUMP
GRANULAR FILL
VAPOR BARRIER
CONCRETE SLAB
REFER PLAN
#3 DOWELS AT 32" O.C.
REFER 1/S3.1
5'-0"
8"
VOLCLAY RX-101
WATERSTOP CONT
AROUND PIT
6"
1'-6"
1'-0"
8"
GRANULAR
FILL
2 - #5 WITH
CORNER BARS
TYP
VAPOR
BARRIER
3/4"= 1'-0"
SECTION - PUMP PIT12
S3.2
12" CMU
#5 DOWEL AT 24" O.C. -
LAP 2'-0" WITH VERT
BARS IN WALL - TYP
16