+ All Categories
Home > Documents > AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation...

AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation...

Date post: 23-Jan-2021
Category:
Upload: others
View: 5 times
Download: 0 times
Share this document with a friend
40
AAF ® -HermanNelson ® Classroom Unit Ventilators ©2002 AAF ® -HermanNelson ® Installation Manual IM 725 Group: Unit Ventilator Part Number: 106506101 Date: January 2002 Vertical Floor Models AVS, AVV, AVB, and AVR Horizontal Ceiling Models AHF, AHB, AHV, and AHR Before beginning installation, please read this publication in its entirety. Develop a thorough understanding before starting the installation procedure. This manual is to be used by the installer as a guide. Each installation is unique, only general topics are covered. The order in which topics are covered may not be those required for the actual installation. IMPORTANT!
Transcript
Page 1: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

AAF®-HermanNelson® Classroom Unit Ventilators

©2002 AAF®-HermanNelson®

Installation Manual IM 725

Group: Unit Ventilator

Part Number: 106506101

Date: January 2002

Vertical Floor Models AVS, AVV, AVB, and AVRHorizontal Ceiling Models AHF, AHB, AHV, and AHR

Before beginning installation, please read this publication in its entirety.Develop a thorough understanding before starting the installation procedure.

This manual is to be used by the installer as a guide. Each installation is unique, only general topics are covered.The order in which topics are covered may not be those required for the actual installation.

IMPORTANT!

Page 2: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

2 IM 725 (1-02)

Table of ContentsSafety Information and Tools Required ............................................................ 2Pre-Installation Considerations ......................................................................... 2Wall Openings, Louvers, and VentiMatic Shutter ............................................ 3Installing Louvers .............................................................................................. 7Installing the VentiMatic Shutter Assembly ...................................................... 8Installing The AV Unit Ventilator .............................................................. 9Step 1 - Uncrate and Inspect the Unit Ventilator(s) .......................................... 9Model AV Data Plate - Specific Information ................................................... 10Step 2 - Position the Unit Ventilator ............................................................ 11-12Step 3 - Make Piping Connections .................................................................. 12In All Systems .................................................................................................. 12In Water Systems ............................................................................................ 13Coil Header, Locations ............................................................................... 14-16

(Heating Only, Cooling Only) ..................................................................... 14(Heat/Cool) ................................................................................................. 15(Reheat) ...................................................................................................... 16

Valves and Piping (diagrams and dimensions) ......................................... 17-192-Way and 3-Way End of Cycle Valves ..................................................... 172-Way and 3-Way Modulating Valves ........................................................ 18End of Cycle (In Steam Systems) Valve Piping ........................................ 19

Typical Coil Piping ...................................................................................... 20-21Condensate Piping .......................................................................................... 22

Unit Ventilator Split Systems Guidelines (DX) Systems ........................... 23-25Step 4 - Make Electrical Connections .............................................................. 26Unit Mounted MicroTech™ Direct Digital Controls (DDC) Components .... 27-28Typical Wall Mounted Room Air Sensor ......................................................... 29Step 5 - Prepare AV Unit Ventilator for Start-up ............................................. 30Installing Unit Ventilator End Panels .............................................................. 30Oiling the Fan Shaft Bearing ........................................................................... 30AV Unit Ventilator Start-Up ............................................................................. 30Model AH Ceiling Unit Installation .......................................................... 31Safety Information and Tools Required .......................................................... 31Model AH Data Plate - Specific Information ................................................... 32Typical Ceiling AH Unit Air Arrangements ................................................ 33-34Pre-Installation Condsiderations ..................................................................... 34Duct System Design for Noise Control ...................................................... 35-36Anchoring The Ceiling Unit ............................................................................. 36Filters ............................................................................................................... 37Same End Piping Connections ....................................................................... 37Remote Two Speed Control Switch ................................................................ 38Prepare AH Ceiling Unit Ventilator for Start-up ............................................. 39Installing AH Unit Ventilator End Panels ........................................................ 39Check, Test and Start Warranty Notice .......................................................... 39Warranty .......................................................................................................... 39

Tools RequiredA forklift or other lifting device is needed to install this product. Applicable tools for lifting, hook-up of piping, electrical and insulation. Unit comeswith an allen wrench and four (4) lagging washers in the envelope in end compartment of the unit. (see photo below)Install this product in accordance with good engineering practices and workmanship, following these general instructions, plus the job-specificAAF®-HermanNelson® submittal drawings provided for specific dimensions, unit arrangements, controls and electrical details, pipe stub-uplocations, etc.

Pre-Installation ConsiderationsStorage – If equipment is stored for any length of time before installation, it should remain in its shipping packaging in a clean, dry, climatecontrolled area.

Safety InformationFollow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available. Follow all warnings andcautions in these instructions and attached to the unit. Consult applicable local building codes and National Electrical Codes (NEC) for special requirements.

Recognize safety information. When you see a safety symbol on the unit or in these instructions, be alert to the potential for personal injury. Understand the meaningsof the words DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards that will result in death or severe personal injury; WARNING meansthe hazards can result in death or severe personal injury; CAUTION identifies unsafe practices that can result in personal injury or product and property damage.

Improper installation, adjustment, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may result in personal injury orproperty damage. This product must be installed only by personnel with the training, experience, skills, and applicable licensing that makes him/her “a qualifiedprofessional HVACR installer.”

DISCONNECT ALL ELECTRICALPOWER BEFORE SERVICING UNITTO PREVENT INJURY OR DEATHDUE TO ELECTRICAL SHOCK.

WARNINGHAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER IN-CLUDING REMOTE DISCONNECTS BEFORESERVICING. FAILURE TO DISCONNECTPOWER BEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.

! CAUTIONUSE COPPER CONDUCTORS ONLY.UNIT TERMINALS ARE NOT DESIGNED TOACCEPT OTHER TYPES OF CONDUCTORS.FAILURE TO DO SO MAY CAUSE DAMAGETO THE EQUIPMENT.

!

Forklift lifting location(see Caution above and table 2, page11 for unit weights)

Shipping Envelope Contents - Located inright end compartment of unit.

CAUTION!

Use 72" length forklift tines, short tines will damage the unitbottom.

! DANGER

Page 3: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 3

Figure 1 – Typical Classroom Unit Ventilator Installation And Louver Details (see installation section for typical warnings and cautions)

Figure 2 – Typical VentiMatic™ Shutter Assembly Installation (see installation section for typical warnings and cautions)

������������������������Unit Gasket

Pipe Tunnel

Lag Screws (By Others)

Weep Holes

Caulk Top AndTwo Sides Of Louver

Sealed Mortar Bed

Caulk

WeepHoles

Floor

Unit Insulating Blanket

Back Of Unit

Unit Bottom Gasket

Seal Under Unit

BirdScreen

Internal Column ForWall Bracing(By Others)

Caulk(top and 2 Sides)

Louvers

Drain Holes(Do Not Block)

Flange(4 Sides)

1" Minimum

Lintels (By Others)

Bird Screen

Sealed Cement MortarPitched Away from UnitToward Louver

Vertical or Horizontal Blade Wall IntakeLouver (Flanged)(Vertical Blade Shown)

Drain Holes(Do NotBlock WithMortar orCaulkingMaterials

Bird ScreenSealed CementMortar PitchedAway from UnitToward Louver

1" Minimum

Vertical or Horizontal Blade Wall Intake Louver(Recessed Without Flange)(Horizontal Blade Shown)

Lintels (By Others)

Louvers

Unit Gasket

Louver

Unit VentilatorOutdoor Air Opening

Outside

Roomside

See figure 1 for typical louver installation

Outside

Roomside

VentiMatic Shutter

Unit Outside Air Opening

Wall Openings, Louvers, and VentiMatic ShutterPrior to unit installation, be sure that the exterior wall openings and louvers, as applicable,are ready and in accordance with the job plans.Vertical Floor Models AVS, AVV, AVB, AVR are typically installed in front of a wallopening containing a properly sized louver that is designed to let in outside air whilepreventing water (such as driving rain) from getting past the louver and into the unit itself.A weather-tight seal keeps unwanted air and moisture from entering the occupied space.See Figures 1 through 18, and table 1 for various louver details.

Building Wall

Page 4: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

4 IM 725 (1-02)

Figure 3 – Horizontal and Vertical Blade Louvers, Without Flange

Figure 4 – Horizontal and Vertical Blade Louvers, Without Flanges With Grille or With Flange Without Grille

Louver drain lipGrille/Louver with weep hole

Vertical Blade LouverHorizontal Blade Louver

Flange

Flange

Outside Air

Outside Air

Outside Air

Bird Screen On Side Toward Unit

Vertical Louver with Flange,without Grille

Horizontal Louver withoutFlange, with Grille

CAUTION!

Locate Weep Hole or Drain Lip at bottom of louver to allowproper drainage.

Page 5: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 5

Figure 6 -165⁄8" (422mm) Deep Unit with Open Pipe Tunnel & High LouverApplication with Chased Wall

1"(25mm)

Sealed CementMortar;Pitch AwayFrom Unit

Louver

Lintel(By Others)

Floor Line

Piping

Louver

Not LessThan 3" (76mm)

Not MoreThan 21" (533mm)

Sealed CementMortar;Pitch AwayFrom Unit

Piping

Floor Line

Figure 5 - The 165/8” (422mm) Deep Unit with Open Pipe Tunnel and StandardLouver Location

Louver Installation With Typical Unit Configurations

Unit Configuration Type AL

1"(25mm)

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Lintel(By Others)

Figure 7 - Above Floor Level Outdoor Air Intake Using Arrangement AV or ALWith Accessory Closed Pipe Tunnel

Piping

Floor Line

Lintel (By Others)

Intake Louver

Not Less Than 3"

Not MoreThan 28"

Insulated ClosurePlate Accessory

ProvideDrainage

1"(25mm)

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Figure 8 - Floor Level Outdoor Air Intake With Window Below Unit Top UsingArrangement AL And 9˝ “Finished” (Painted) Accessory (Uninsulated) ClosedPipe Tunnel

Unit Configuration Type AL

Lintel (By Others)

Intake Louver

Sealed CementMortar;Pitch AwayFrom Unit Sealed Cement

Mortar;Pitch AwayFrom Unit

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Sash Piping

1"(25mm)

Painted Insulated Closure Plate Accessory

Floor Line

ProvideDrainage

Gasket Seal Gasket Seal

Gasket Seal

Accumulated moisture can cause property damage if notproperly drained. Installing contractor must provide suchdrainage.

CAUTION!

Page 6: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

6 IM 725 (1-02)

Figure 11 – The 217/8” (556mm) Deep Full Adapter Back Unit with Closed PipeTunnel, Ducted with Top Intake

Figure 12 – 217/8" (556mm) Deep Partial Adapter Back Unit with Open PipeTunnel

Intake Louver

Not MoreThan 12"

Unit Configuration Type AP Unit Configuration Type AK

Figure 9 - 217⁄8" (556mm) Deep Full Adapter Back Unit With Standard LouverApplication

Figure 10 - 217⁄8" (556mm) Deep Full Adapter Back Unit with High LouverApplication

Not MoreThan 28"(711mm)

FloorLine

Unit Configuration Type AN

1"(25mm)

Sealed CementMortar;Pitch AwayFrom Unit

Louver

Piping

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Lintel(By Others)

Piping

FloorLine

Sealed CementMortar;Pitch AwayFrom Unit

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Louver

Lintel(By Others) Piping

Piping

Important: Gasket sealing surface is required.(see figure 13 & 14 on page 7) Seal under unitrequired.

1"(25mm)

Floor Line

Piping

Piping

Sealed CementMortar;Pitch AwayFrom Unit

Important: Gasket sealingsurface is required. (see figure13 & 14 on page 7) Seal underunit required.

Louver Installation With Typical Unit Configurations

Lintel(By Others)

Gasket Seal Gasket Seal

Floor Line

Gasket Seal

Gasket Seal

Intake Louver

Piping

Piping

Window Sash

“Goose Neck”Insulated Duct (By Others)

Duct Collar (By AAF)

Note:Arrangement AB with full metal back panel, similar toconfiguration type AN. (Outside air opening to be cut andsealed by others.)

Page 7: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 7

Installing Louvers

Typical Installation MethodsIf the fresh air opening has not yet been made, see figures 5 through12 for the recommended locations and the job-specific plans for theexact location. Follow local codes.

Cut the wall opening so that it is slightly larger than the louver beinginstalled. For dimensions, see Table 1. If the opening is already there,measure to be sure there is a minimum of 3/8" (9mm) clearance aroundall sides. For masonry installations, a lintel must be installed above alllouvers.

In thick wall applications, the portion of the wall between the louverand the unit is the outside air plenum. Line this plenum area with 3/8"(9 mm) mortar or other suitable material. In some applications, the jobspecifications require a metal sleeve connection between the louverand the unit. If using such a sleeve, properly caulk it to ensure aweather-tight seal. This is critical in preventing freeze-ups, colddrafts, and air infiltration. Be sure the wall is smooth, square, andprovides a suitable mating surface.

See figure 13. Before setting the louver, construct a sloping, sealedcement mortar base to drain unwanted moisture to the outside. Be surethe mortar base is 1" (25mm) thick at the unit and tapers toward thelouver. The mortar at the unit also acts as a backing against which theopen cell gasket of the unit itself can seal. This is critical in preventingwater leaks and air leaks under the unit. Be sure the sealed cementmortar base is smooth and flush with the interior wall.If it is not possible to construct a sloping mortar base, then field-supplied flashing is required. See figure 14. The flashing should

terminate flush with the exterior of the building. Place a bead of caulkunder the flashing to prevent moisture from wicking back to the unit.Do not caulk the joint between the louver and the flashing. This jointis designed to let unwanted moisture escape.

Personal injury hazard. Avoid contact with sharp edges.

See figures 5 through 12. Before setting the louver, be sure the drainlip or weep holes are at the bottom, and the bird screen is towards theunit. See figures 3 and 4. Place a heavy bead of caulk along the top andthe two vertical sides of the louver, leaving the bottom uncaulked sothat if moisture gets into the area between the louver and the unit, it candrain to the outside, unrestricted.

If the louver is supplied with flanges, (see figure 4) place an additionalbead of caulk on the inside of the top and side flanges that come incontact with the building facade. Do not caulk the bottom flange. Placethe louver in the opening and push it tight against the suppliedbuilding, fastening it to the exterior of the building using fasteners (byothers) appropriate to the installation. Seal the top and sides with awaterproof caulk to make it weather-tight. Do not caulk the bottom ofthe louver; doing so might trap unwanted moisture behind the flange.(See figure 16)

If the louver is supplied with no flanges, (see figure 3) place the louverin the opening so that it is recessed a minimum 1/16" (2mm) beyondthe building facade or as directed in the architectural plans. If specifiedin the plans, secure the louver in the wall using mechanical fasteners(supplied by others) appropriate to the installation. (See figure 15 forsuggested fastening). With the louver solidly in place, run a bead ofcaulk around the perimeter of the louver to seal it weather-tight. Do notplug the weep holes (horizontal louver) or the drip line (verticallouver). This might restrict the flow of unwanted moisture to theoutside (see figure 16)See figure 14. If flashing was used instead of the sloping mortar base,caulk the flashing where it meets the inside of the opening between thelouver and the unit. This helps prevent moisture from getting under theflashing and into the room.

CAUTION!

Louver

NoCaulk

Unit Gasket

Wall Unit

1" (25mm)

Floor

Caulk(ByOthers)

Flashing(ByOthers)

Figure 14 - Typical Louver Installation with Flashing

Unit Gasket

Sealed CementMortar;Pitch AwayFrom Unit

Floor

Wall

UnitLouver

NoCaulk

1" (25mm)

Figure 13 - Typical Louver Installation with Sloping Sealed Cement MortarBase

Table 1 - Recommended Wall Openings For Wall Louvers (for figures 18 - 20)

Recommended Maximum Number of VentiMatic

Wall Openings VentiMatic Shutters Shutter(s)B C For Wall Louvers Which Can Be Mounted Air Capacity

On Standard Louver MaximumLeng th Height 24" Shutter 36" Shutter c f m L /s

24 " 27 " 245⁄8" 107⁄8"(610) (659) (613) (267) 1 0 500 236

36 " 39 " 365⁄8" 107⁄8"(914) (991) (918) (267) 0 1 750 354

48 " 51 " 485⁄8" 107⁄8"(1219) (1295) (1222) (267) 2 0 1000 472

60 " 63 " 605⁄8" 107⁄8"(1524) (1600) (1527) (267) 1 1 1250 590

72 " 75 " 725⁄8" 197⁄8"(1829) (1905) (1832) (495) 0 2 1500 708

Page 8: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

8 IM 725 (1-02)

Caulk (Top and 2 Sides)

Louvers

Drain Holes (Do Not Block)

Flange (4 Sides)

1" Minimum

Lintels (By Others)

Bird ScreenSealed CementMortar PitchedAway from UnitToward Louver

Vertical or Horizontal BladeWall Intake Louver(Flanged)(Vertical Blade Shown)

Lintels (By Others)

Louvers

Drain Holes(Do NotBlock WithMortar orCaulkingMaterials

Bird ScreenSealed CementMortar PitchedAway from UnitToward Louver

1" Minimum

Vertical or Horizontal BladeWall Intake Louver(Recessed Without Flange)(Horizontal Blade Shown)

Notes:1. Horizontal blade wall louver shown. Vertical blade wall louver also available

with Ventimatic shutter.2. Optional exterior grille matches unit ventilator wall louver in material and

design. Mounted on wall louvers.3. Optional steel interior wall grille should be used to conceal the interior wall

opening whenever the Ventimatic shutter is not located behind shelf cabinetsor DraftStop enclosure. Hardware to mount the interior wall grille is notincluded.

Installing the VentiMatic Shutter Assembly

The VentiMatic Shutter Assembly is mounted on an installed walllouver. For larger units with 100% ventilation air dampers, twoVentiMatic Shutters may be mounted side by side on the same louver.See figure 20.

The size and appearance of the wall louvers with or without optionalgrilles used with the unit ventilator, and the VentiMatic Shutter, areidentical.

Figure 15 - Suggested method for fastening louver (without flange)inside wall opening .

Figure 18 - Louver Details, Dimensions

As DirectedBy Architect

3⁄4" (19mm) Approx.

7"(178mm)

Cement Mortar

Steel Interior Wall Grille(Optional) See Note 3

125⁄8"(314mm)

3⁄4" (19mm) Approx.

BirdScreen

Do Not Block DrainHoles With Caulk orMortar

NotLess

Than 9"(229mm)

Cement Mortar

C(see table 1, page 7)

Wall Opening

Louver(Bird Screen Not Shown)

Angle Iron(by others)

Room Side

Exterior

Figure 16 - Louver Installation Views

Note: Birdscreen and louver are shipped in one (1) piece.

Pre-Installation Considerations

VentiMatic™ Shutter AssemblyIn many installations, an AAF®-HermanNelson® VentiMatic ShutterAssembly is specified. See figure 17. This one-way shutter is acontinuously variable, gravity actuated, room exhaust vent that operatesin direct response to positive static pressure. It opposes any airflowinto the room and allows a slight positive pressure.It is important that the VentiMatic shutter and unit ventilator louversare mounted on the same wall. This neutralizes the effect of the wind.Forcing excess air into the room through the unit ventilator louverovercomes the same wind pressure that works to keep the VentiMaticshutter closed. This prevents room air exhausting from the roomthrough the VentiMatic shutter.

Figure 17 – VentiMatic Shutter Assembly

Outside

Louver

VentiMatic Shutter

RoomsideRelief Air

When installing VentiMatic Shutter(s) on the wall louver, make sureall moving parts are free to operate unobstructed and placed level andplumb for proper operation. If optional steel interior wall grille isfurnished, install as shown in Figure 18.

Page 9: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 9

Plastic packaging is a suffocation hazard, dispose of properly.Keep away from children.

Cleaning agents may cause serious damage to internalcomponents, such as aluminum coils and electronic controls,etc. Do not operate unit ventilator while building maintenancecleaning agents are in use.

Aluminum Wall LouverAssembly with Bird Screen

(See Note 1) 3'' (76mm)

VentiMaticShutterAssembly

Center Cover103⁄8"(264mm)

Figure 20 - Two VentiMatic Shutters & Wall Louver

Aluminum Wall LouverAssembly With Bird Screen(See Note 1)

B(see table 1,

page 7)

SteelVentiMaticShutterAssembly

41⁄8"(105mm)

237⁄8" (606mm)or

357⁄8" (911mm)

2" (51mm)

103⁄8"(264mm)

3" (76mm)

Decorative Exterior Grille Also Available (See Note 2)(Bird Screen not shown)

Figure 19 - Single VentiMatic Shutter & Wall Louver

B(see table 1,

page 7)

Before Installing Unit Ventilator

Check that the lifting equipment can handle the weight of theunit safely. Personal injury may result if proper lifting andmoving methods are not used. (See table 2, page 11 forapproximate shipping weights)

Personal injury hazard. Handle with care to avoid possible cutsand abrasions from exposed edges. Avoid contact with sharpedges.

Improper handling can damage internal components. Do notstand the unit on end or stack.

This product was carefully packed and thoroughly inspectedbefore leaving the factory. Responsibility for its safe deliverywas assumed by the carrier upon acceptance of the shipment.Claims for loss or damage sustained in transit must thereforebe made upon the carrier, as follows:VISIBLE LOSS OR DAMAGEAny external evidence of loss or damage must be noted on thefreight bill or carrier’s receipt, and signed by the carrier’s agent.Failure to adequately describe such external evidence of lossor damage may result in the carrier’s refusing to honor adamage claim. The form required to file such a claim will besupplied by the carrier.CONCEALED LOSS OR DAMAGEConcealed loss or damage means loss or damage which doesnot become apparent until the product has been unpacked. Thecontents may be damaged in transit due to rough handling eventhough the carton may not show external damages. When thedamage is discovered upon unpacking, make a written requestfor inspection by the carrier’s agent within fifteen (15) days ofthe delivery date. File a claim with the carrier since suchdamage is the carrier’s responsibility.

WARNING!

CAUTION!

CAUTION!

NOTICE

WARNING!

WARNING!

Step 1Uncrate and Inspect the Unit Ventilator(s)Carefully remove the packaging, remaining alert to any signs ofshipping damage. Be careful not to discard components that may beincluded with the packaging. (You may want to retain some or all ofthe packaging to provide jobsite unit location information andtemporary protection for the unit ventilator after installation.) Be sureto dispose of plastic packaging and protective cardboard properly, inaccordance with local recycling rules and guidelines.If unit is damaged, file a claim with the carrier. Notify the local AAF®-McQuay Unit Ventilator representative immediately.

Properly Identify Unit Ventilator(s)To be sure the correct unit ventilator(s) is/are installed in the correctlocation(s), the installer must check the packing list and unitidentification/tagging number(s) against the plans. Further, the unitdata plate, (see figure 21) located on the lower right end of the unitventilator, contains specific information of standard components asfollows: (see next page)

Installing The Unit Ventilator

Figure 21 - Unit Ventilator Data Plate and Serial Number Location

Outside

Outside▲

Decorative Exterior Grille Also Available (See Note 2)(Bird Screen not shown)

Directions given in this bulletinfor right and left sides assumea position facing the indoor sideof the unit ventilator

INFORMATION

Page 10: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

10 IM 725 (1-02)

1. Product CategoryU = Unit Ventilator

2. Product Identifier*AVS = Floor, Face and Bypass Damper, Heat/Cool, Heat Only, CoolOnlyAVV = Floor, Valve Control, Hydronic or Electric Heat/Cool, HeatOnly, Cool OnlyAVR = Floor, Valve Control, Hydronic or Electric Reheat/DehumidAVB = Floor, Face and Bypass Damper, Hydronic Reheat* End panels not included; Ordered as accessory, shippedseparately boxed

3. Design Series4 = D Design

4. Nominal Capacity, cubic feet per minute (cfm)S07 = 750S10 = 1000S13 = 1250S15 = 1500

5. Voltage, volts, phase, Hertz (v-Hz-ph)A = 115-60-1C = 208-60-1G = 230-60-1J = 265-60-1D = 208-60-3H = 230-60-3K = 460-60-3

6. Cooling OptionsU = 2-row Chilled Water/Hot Water, 2-pipeD = 3-row Chilled Water/Hot Water, 2-pipeE = 4-row Chilled Water/Hot Water, 2-pipeF = 5-row Chilled Water/Hot Water, 2-pipe1 = 2-row High Capacity Chilled Water/Hot Water, 2-pipe2 = 3-row High Capacity Chilled Water/Hot Water, 2-pipe3 = 4-row High Capacity Chilled Water/Hot Water, 2-pipe4 = 5-row High Capacity Chilled Water/Hot Water, 2-pipeG = Direct Expansion (DX)S = 3-row Chilled WaterV = 2-row Chilled WaterW = 4-row Chilled WaterY = 5-row Chilled Water5 = 2-row High Capacity Chilled Water6 = 3-row High Capacity Chilled Water7 = 4-row High Capacity Chilled Water8 = 5-row High Capacity Chilled WaterZ = None

7. Heating Options00 = None12 = Low Electric Heat, 3-element13 = High Electric Heat, 6-element65 = 1-row, Hot Water66 = 2-row, Hot Water67 = 3-row, Hot Water68 = Low Capacity Steam69 = High Capacity Steam78 = Low Capacity Steam, Opposite End Drain79 = High Capacity Steam, Opposite End Drain

Unit Ventilator (Floor Type) Data Plate - Specific Information

8. Hand Orientation [Right (RH) Left (LH)]A = LH Both Coils (only w Controls by Others)B = RH Both Coils (only w Controls by Others)D = RH Electric Heating, One CoilE = LH Heating, RH CoolingF = RH Heating, LH CoolingG = RH Electric Heating, LH CoolingR = LH Single CoilS = RH Single Coil

9. Controls15 = MicroTech w Unit Mounted Sensor16 = Part Load Variable Air MicroTech w Unit Mounted Sensor and

Humidity Sensor (if required)19 = MicroTech for Remote Wall Sensor (accessory Sensor and

Humidity Sensor (required)20 = Part Load Variable Air MicroTech for Remote Wall Sensor

(accessory Sensor/ Humidity Sensor required)23 = Field Mounted Controls by Others17 = Digital Ready/with Damper Acutators, (3)@ 10k NTC Sensors,

3 Terminal Strips, 75 VA 24 Volt T’fmr, w/o UV Controller

10. DischargeAB = 21-7/8" Unit, Top Bar Grille Discharge, Full Adapter Back wClosed Pipe Tunnel w Solid BackAK = 21-7/8" Unit, Top Bar Grille Discharge, Partial Adapter Back wOpen Pipe TunnelAL = 16-5/8" Unit, Top Bar Grille DischargeAM = 21-7/8" Unit, Top Bar Grille Discharge, 2" Stepdown FullAdapter Back w Closed Pipe TunnelAN = 21-7/8" Unit, Top Bar Grille Discharge, Full Adapter Back wClosed Pipe TunnelAP = 21-7/8" Unit, Top Bar Grille Discharge, Partial Adapter Back wClosed Pipe Tunnel, Top Duct Intake

11. Return Air (RA) / Outside Air (OA)22 = RA Bottom Front / OA Rear Duct Collar24 = 100% RA Bottom Front / No OA Opening / No OA/RA Dampers30 = RA Bottom Front w Draft Stop / OA Rear Duct Collar

12. Power ConnectionG = Box w Switch

13. ColorB = Putty BeigeG = Soft GrayI = Antique IvoryW = Off White

14. SKUB = Standard DeliveryC = Extended Delivery

15. Product Style1

Field-Installed Accessories may accompany Unit Ventilator(s), ormay be shipped separately. These may include: Adapter Backs;Aluminum Louvers; Aluminum Grilles; Auxiliary Drain Pans; Controls/ Sensors; End Panels; Spare Filters; MicroTech Controls, Sensors(temperature, humidity, CO2); End of Cycle DDC Valve; ModulatingDDC Valves; Subbases. See instructions shipped with accessoriesand install according to these and the plans.

Field 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Model U AVS 4 S07 A S 65 E 23 AL 22 G B C 1

Page 11: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 11

ModelsAVS, AVV, Dimension "A"

AVR, AVB Inches (mm)

S07 48" (1219)

S10 60" (1524)

S13 72" (1828)

S15 84" (2133)

Models Shipping Weight Approx. Shipping WeightFilter Size Unit Length* NumberAVS, AVV, lbs. (kg) lbs. (kg) in. (mm) in. (mm) Of Fans

AVR, AVB 165/8"Units 217/8"Units

S07 350 (168) 370 (163) 10 x 36.5 x 1 62 (1575) 2(254 x 927 x 25)

S10 425 (193) 445 (202) 10 x 48.5 x 1 74 (1880) 3(254 x 1232 x 25)

S13 495 (225) 525 (238) 10 x 60.5 x 1 86 (2174) 4(254 x 1551 x 25)

S15 570 (259) 600 (272) Two: 10 x 36.5 x 1 98 (2489) 4(254 x 927 x 25)

Step 2Position the Unit Ventilator

Move the unit ventilator to the correct location. See Table 2 for approximate shipping weights.Carefully remove unit ventilator from wood skid. Be sure to properly dispose of the skid in accordance with local recycling rules and guidelines.

Table 2- Approximate Shipping Weights, Physical Data

* Measurement is without end panels. All unit ventilators are 30" (762 mm) high.

Figure 22 - Front View With End Panels - Mounting Holes Locations

Mounting Holes

Figure 23 - Rear View Without End Panels And Subbase - Piping And Electrical Knockout Locations And Dimensions

131⁄2"(343mm)

7" (178mm)

22"(559mm)

51⁄2"(140mm)

11⁄2"(38mm) 7"

(178mm)

5" (127mm)

4" (102mm)

27/8" (73mm)

8"(203mm)

8"(203mm)

Knockout Opening Between PipeTunnel & End Compartment.

Rear Entry Area or Draftstop Opening Knockouts

30"(762mm)

61⁄2" (165mm)

1" (25mm)

7" (178mm)1" (25mm)

10"(254mm)

231⁄2"(597mm)

Outdoor Air Intake Opening

NOTICE

End compartment Draftstop knockoutsmust be removed for proper Draftstopoperation. (21-7/8" units only)

A(See Table 3)

IMPORTANT!

To prevent leakage of outdoor air that wastes energy, causes drafts and erratic unit ventilator operation, be sure to heed the following details:At the correct unit ventilator location, examine the wall surface, making sure that it is smooth, plumb, and perpendicular to the floor, (SeeFigure 1). The seals on the rear of the unit ventilator will take up the small irregularities found in normal masonry construction. If the wall isirregular or has mullions, install furring strips to provide a flush surface against which the unit ventilator can seal. If there are moldings onthe floor/wall line, omit them behind the unit ventilator. Provide a sealing surface at the floor line. Install a seal pad under the unit to preventair leakage. Install the unit ventilator against a wall made of non-combustible material, and on a floor made of non-combustible material. Floormust be level, unbroken and structurally strong to support the unit.

Table 3 - Dimension Between Mounting Holes

Note:See Draftstop IM bulletin for suggested installationprocedure.

Page 12: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

12 IM 725 (1-02)

Step 3Make Piping Connections

Be sure the hot and chilled water supply and return system arethoroughly flushed and cleaned before connecting piping to theunit ventilator.

In All SystemsBe sure to install the control valve(s) on the correct unit ventilator.Indiscriminate mixing of valves in the field can result in valvesimproperly sized for the desired flow rate, which can result in pooroperation and coil freezeups. Install control valve so there is at least2" (51mm) minimum clearance to remove the actuator from the valvebody.Be certain that the control valve is installed correctly, with itsorientation vertical. Valves should be installed at least 5° off center.

Be certain that the control valves are installed with the properport orientation to provide proper flow and fail safe operation.Incorrect installation can result in improper unit operation, and/or the possibility of coil freeze-up.

With future servicing considerations in mind, use standard, field-supplied shutoff valves and union connections; this permits easyremoval of the coil or control valve if servicing is required.

While brazing have an extinguisher readily available. Wearappropriate eye and hand protection. Ensure all areas withshared ventilation have ample fresh air ventilation.

Refer to figure 1 and figures 22 through 27 and attach the unitventilator to the wall through the four (4) mounting holes provided,using field-supplied fasteners appropriate to the wall construction andthe washers provided in the brown envelope with these instructions(figure 25). Envelope also contains allen wrench to provide access tounit. Push the unit ventilator tight to the wall structure so that theoutdoor air seals are compressed. Secure the wall fasteners to preventthe unit ventilator from moving and tipping over.

Remove moldingsbehind unit

Before setting the unit ventilator in place, if it is a cooling unit, checkthe condensate drain hand connection to be sure it is the same as thecooling coil hand of connection, and that it agrees with the drain stub-up. If necessary, move condensate drain cap to the opposite end. Donot discard (see figure 24).

Before setting the unit ventilator in position, be sure that field-supplied electrical connections are in place, de-energized and inaccordance with the plans.Move the unit ventilator into position against the wall surface. Checkto see that the unit ventilator is level, from end to end and back to front.Using a 4' level is recommended. Leveling bolts are located at eachend of the front kickplate (see figure 27).

Unit must be anchored to an internal wall column or other suitablesupport (see figure 1, page 3)

11"(279 mm)

7⁄8"22 mm)O.D. Copper

Drain

7⁄8"(22 mm)O.D. Copper

Drain

5"(127 mm)

CondensateDrain

Figure 24 - Move Condensate Drain Cap To Opposite End of Drain Stub-Up.

Left Hand

Front View of End Compartment

Right Hand

11"(279 mm)

Figure 25 - Shipping Envelope Contents

Figure 26 - Setting The Unit Ventilator In Place

Figure 27 - Leveling Legs Location

DANGER!Disconnect all electrical power before servicing unit to preventinjury or death due to electrical shock.

CAUTION!

CAUTION!

WARNING!

CAUTION!

Page 13: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 13

In Water SystemsAfter flushing piping adequately, so all debris is removed, fill thesystem.

At initial operation, vent manually by unscrewing the vent plug one ortwo turns, figure 31. After venting, tighten the vent plug firmly.

Unscrew the vent plug only one or two complete turns. Systemis under pressure and can result in severe personal injury

WARNING!

Figure 31 - Vent and Drain Plug

Unscrew the vent plug one ortwo turns to manually ventsystem.

Water system under pressure. When venting keep face andbody parts well away, and vent slowly.

Figure 28 - Hot Water Coil Connections

Chilled Water Coil

Hot Water Coil

Chilled Water Return

Chilled Water Supply

Hot Water Return

Hot Water Supply

Water Coil ConnectionsHook up water piping in accordance with the below figure’s 28 and 29for hot water and chilled water coil connections.

Figure 29 - Chilled Water Coil Connections

Failure to install water piping to coils properly can result inimproper unit operation and possible coil freeze-ups.

Proper ventilation is required for brazing. When brazing, be sure toprotect unit ventilator components from overheating damage (meltinginsulation, also damage to valves, wiring, electronics, sensors, etc.).Before filling, be sure to flush all piping adequately so that all debrisis removed. Foreign debris can prevent proper valve operation, resultingin overheating, overcooling, etc.Ensure proper insulation of supply and return piping. Proper insulationprevents loss of unit ventilator capacity, overheating of endcompartment, and / or moisture dripping.The piping to and from the unit must be protected from outside air andfreeze conditions. The piping must be suitably insulated forcondensation or heat lose or gain. Penetrations entering the unit endcompartments must be fitted/sealed for unit integrity.

Figure 30 - Protect Components From Overheating Before Brazing

Use A Quenching ClothWhen Brazing, to PreventOverheating The PipingComponents (Avoid ValveDamage and EraticOperation)

Vent

Drain Plug

CAUTION!

WARNING!

Page 14: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

14 IM 725 (1-02)

Heating Coils00 = None

Cooling CoilsV = 2 Row CW CoilS = 3 Row CW Coil

W = 4 Row CW CoilY = 5 Row CW Coil5 = 2 Row High Capacity CW Coil6 = 3 Row High Capacity CW Coil

Heating OnlyFigure 32 - Hot Water Heating Only Unit(Coils 65, 66, 67)

Cooling Only

Unit Series S07 S10 S13 S15 Suction Line O.D. (in/mm) 3⁄4 19 3⁄4 19 7⁄8 22 7⁄8 22 Liquid LIne O.D. (in/mm) 1⁄4 6.35 1⁄4 6 3⁄8 10 3⁄8 10

Notes:1. All coils have same end supply and return connections.2. Steam coils have a factory installed pressure equalizing valve and a 24" (610mm) long

pressure equalizing line which terminates in a 1⁄2" M.P.T. fitting.3. Steam/hot water connections may be same end as cooling coil connections, but they

are recommended to be opposite end to facilitate piping. (Must be opposite end whenusing AAF controls.)

4. Cooling condensate connection is shipped same end as cooling coil connections, butis field reversible.

5. Electric heating coil power connections are right end only. Junction box has 1"(25mm)and 2" (51mm) (trade size) knockouts, 101⁄2" (267mm) from right end of the unit.

6. For limitations with coil combinations see tables 151-1, 151-2, 152-1 and 153-1.7. Coil stubs are 7⁄8" I.D. (female) and terminate 9" (229mm) from the end of the unit.8. Steam coils are 11⁄8" female (sweat) connections and terminate 9” (229mm) from the

end of the unit.9. DX coils (G) have O.D. sweat connections. Interconnecting tube by others. See table

7 for correct tubing size.

Table 6 - Dimensions

Table 7 - DX Coil (G) Connection Tubing

L.H. Connections

A

B

RS

J115⁄8

(295 mm)

133⁄8(340 mm)

133⁄8(340 mm)

115⁄8(295 mm)

SR

A

B

J

S = SupplyR = Return

A

C

R

S

J 73⁄8(187 mm)

115⁄8(295 mm)

115⁄8(295 mm)

S

R

C

A

J73⁄8(187 mm)

JunctionBox

HJ

Electric HeatingOnly

S = SupplyR = Return

R.H. Connections L.H. Connections R.H. Connections R.H. Connections

133⁄4(349 mm)

Table 4 - Heating Only – Coil Position/Combinations In Air Stream(one coil per position) Note: X indicates Available. Face and Bypass Valve

First Position in Air Stream Second Position in Air Stream AVS AVV AVV Elec.65 66 67 68 69 78 79 Z X X

12 13 Z X

Heating Coils65 = 1 Row Hot Water Coil66 = 2 Row Hot Water Coil67 = 3 Row Hot Water Coil

68 = Low Capacity Steam Coil69 = High Capacity Steam Coil78 = Opposite End Drain Low Capacity Steam Coil79 = Opposite End Drain High Capacity Steam Coil12 = Low Electric Heat Coil

13 = High Electric Heat CoilCooling CoilsZ = None

Table 5 - Cooling Only – Coil Position/Combinations In Air Stream(one coil per position) Note: X indicates Available. Face and Bypass Valve

First Position in Air Stream Second Position in Air Stream AVS AVVV S W Y 00

X X5 6 7 8

G 00 X

7 = 4 Row High Capacity CW Coil8 = 5 Row High Capacity CW CoilG = Direct Expansion Coil

L.H. Connections

A

B

S

R

J115⁄8

(295 mm)

133⁄8(340 mm)

133⁄8(340 mm)

115⁄8(295 mm)

R

S

A

B

J

B

D

LL

SL

J113⁄8

(289 mm)

133⁄8(340 mm) 113⁄8

(289 mm)

C

D

J73⁄8(187 mm)

SL

LL

S = SupplyR = Return

Figure 35 - Chilled Water Only Unit(Coils S, W, Y, V, 5, 6, 7, 8) Figure 36 - Direct Expansion Cooling Only Unit (Coil G)

R.H. Connections L.H. Connections R.H. Connections

LL = Liquid LineSL = Suction Line

Air Flow Air Flow

AirFlow

AirFlow

Air Flow

Air Flow Air Flow Air Flow Air Flow

Unit DimensionsDepth A B C D E F G H J

in 165⁄8 63⁄8 105⁄8 45⁄8 65⁄8 4 83⁄8 21⁄4 14 27⁄8 mm 422 162 270 117 168 102 213 57 356 73 in 217⁄8 115⁄8 157⁄8 97⁄8 117⁄8 91⁄4 135⁄8 71⁄2 191⁄4 81⁄8

mm 556 295 403 251 302 235 346 191 489 206

Note: For opposite end drain steam coils (code 78,79) Return (R) is 71⁄4"(184mm) from bottom of unit and C - 27⁄8"(73mm) from back of unit.

Figure 33 - Steam Heating Only Unit(Coils 68, 69, 78, 79)

Figure 34 - Electric Heating Only Unit(Coils 12, 13)

Coil Headers, Locations

Page 15: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 15

Heat/Cool

See Notes and Tables 6 and 7 on page 14

Table 8 - Heat/Cool Position/Combinations In Air Stream (one coil per position) Note: X indicates Available.

Face and Bypass ValveFirst Position in Air Stream Second Position in Air Stream AVS AVS Elec. AVV AVV Elec.

U D E F00 X X

1 2 3 465 66 67 68 69 78 79 V S 5 6 X X

65 66 W 7 X XG 65 66 67 68 69 78 79 X XG 12 13 X

12 13 V S W 5 6 7 XV S W 5 6 7 12 X

Heating Coils65 = 1 Row Hot Water Coil66 = 2 Row Hot Water Coil67 = 3 Row Hot Water Coil68 = Low Capacity Steam Coil

Cooling CoilsU = 2 Row CW/HW 2-Pipe CoilD = 3 Row CW/HW 2-Pipe CoilE = 4 Row CW/HW 2-Pipe CoilF = 5 Row CW/HW 2-Pipe Coil1 = 2 Row High Capacity CW/HW 2-Pipe Coil2 = 3 Row High Capacity CW/HW 2-Pipe Coil3 = 4 Row High Capacity CW/HW 2-Pipe Coil4 = 5 Row High Capacity CW/HW 2-Pipe CoilV = 2 Row CW CoilS = 3 Row CW CoilW = 4 Row CW Coil5 = 2 Row High Capacity CW Coil6 = 3 Row High Capacity CW Coil7 = 4 Row High Capacity CW CoilG = Direct Expansion Coil

69 = High Capacity Steam Coil78 = Opposite End Drain Low Capacity Steam Coil79 = Opposite End Drain High Capacity Steam Coil12 = Low Electric Heat Coil13 = High Electric Heat Coil00 = None

L.H. Connections

A

B

S

R

J115⁄8

(295 mm)

133⁄8(340 mm)

133⁄8(340 mm)

115⁄8(295 mm)

R

S

A

B

J

E

F

R

S

J

137⁄8(352 mm)

155⁄8(397 mm)

133⁄8(340 mm)115⁄8

(295 mm)

R

S

A

B

J

HW C

oilCW

Coil

E

F

S

R

J

115⁄8(295 mm)

73⁄8(187 mm)

R

S

C

A

J

Steam

CW Coil

D

B

J113⁄8

(289 mm)

133⁄8(340 mm)

R

S E

F

J

HW C

oil

137⁄8(352 mm)

155⁄8(397 mm)

R

SG

E

J95⁄8

(244 mm)

137⁄8(352 mm)

JunctionBox

HJ

Figure 37 - Chilled/Hot Water (2-pipe) Unit(Coils D, E, F, U, 1, 2, 3, 4)

Figure 38 - Chilled Water and Hot Water UnitCooling Coils S, W, V, 5, 6, 7 Heating Coils 65, 66, 67

Figure 39 - Chilled Water and Steam UnitCooling Coils S, W, V, 5, 6, 7Heating Coils 68, 69, 78, 79

Figure 40 - Direct Expansion (G) and Hot Water UnitCooling Coil G Heating Coils 65, 66, 67

Figure 41 - Direct Expansion (G) and Steam UnitCooling Coil G Heating Coils 68, 69, 78, 79

Figure 42 - Direct Expansion and Electric HeatingCooling Coils G Heating Coils 12, 13

S = SupplyR = Return

S = SupplyR = Return

S = SupplyR = Return

R.H. Connections L.H. Connections R.H. Connections L.H. Connections R.H. Connections

S = SupplyR = ReturnLL = Liquid LineSL = Suction Line

Heating Dimensions ShownR.H. Connections R.H. Connections

Cooling Dimensions Shown Heating Dimensions Shown

137⁄8(352 mm)

155⁄8(397 mm)

LL

SL

D

B

J113⁄8

(289 mm)

133⁄8(340 mm)

Steam

LL

SL

133⁄4(349 mm)

D

C113⁄8

(289 mm)

73⁄8(187mm)

Air Flow Air Flow

AirFlow

Air Flow

AirFlow

AirFlow

Air Flow

AirFlow

Air Flow

AirFlow

AirFlow

Cooling Dimensions Shown Heating Dimensions Shown

S = SupplyR = ReturnLL = Liquid LineSL = Suction Line

LL

SLLL SL

C

73⁄8(187 mm)

C

LL

SL

73⁄8(187 mm)

JunctionBox

HJ

Figure 44 - Chilled Water (2nd Position) and Electric HeatingCooling Coils V, S, W, 5, 6, 7 Heating Coils 12,13

R.H. Connections

133⁄4(349 mm)

137⁄8(352 mm)

155⁄8(397 mm)

R

S

Air Flow

HJ

Figure 43 - Chilled Water (1st Position) and Electric HeatingCooling Coils V, S, W, 5, 6, 7 Heating Coils 12,13

R.H. Connections

133⁄4(349 mm)

JunctionBox

Air Flow

133⁄8(340 mm)

115⁄8(295 mm)

RS

BA

Cooling Dimensions ShownL.H. Connections

Heating Dimensions ShownR.H. Connections

Cooling Dimensions ShownL.H. Connections

Note: For opposite end drain steam coils (code 78,79) Return (R) is 71⁄4" (184mm) from bottom of unit and C - 27⁄8" (73mm) from back of unit.

Coil Headers, Locations (Continued)

Page 16: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

16 IM 725 (1-02)

Face and Bypass ValveFirst Position in Air Stream Second Position in Air Stream AVB AVR AVR Elec.

V S 5 6 65 66 67 68 69 78 79 X XW 7 65 66 X X

G 65 66 67 68 69 78 79 XG 12 13 X

V S W 5 6 7 12 13 X

Reheat

Table 9 - Reheat Coil Position/Combinations In Air Stream (one coil per position) Note: X indicates Available.

Heating Coils65 = 1 Row Hot Water Coil66 = 2 Row Hot Water Coil

Cooling CoilsV = 2 Row CW CoilS = 3 Row CW CoilW = 4 Row CW Coil5 = 2 Row High Capacity CW Coil6 = 3 Row High Capacity CW Coil7 = 4 Row High Capacity CW CoilG = Direct Expansion Coil

67 = 3 Row Hot Water Coil68 = Low Capacity Steam Coil69 = High Capacity Steam Coil

78 = Opposite End Drain Low Capacity Steam Coil79 = Opposite End Drain High Capacity Steam Coil12 = Low Electric Heat Coil13 = High Electric Heat Coil

Figure 48 - Direct Expansion (G) and Hot Water UnitCooling Coil G Heating Coils 65, 66, 67

Figure 49 - Direct Expansion (G) and Steam UnitCooling Coil G Heating Coils 68, 69, 78, 79

Figure 45 - Chilled Water and Hot Water UnitCooling Coils S, W, V, 5, 6, 7 Heating Coils 65, 66, 67

Figure 46 - Chilled Water and Steam UnitCooling Coils S, W, V, 5, 6, 7 Heating Coils 68, 69,78, 79

Figure 47 - Chilled Water and Electric HeatingCooling Coils V, S, W, 5, 6, 7Heating Coils 12, 13

L.H. Connections

A

B

S

R

J

115⁄8(295 mm)

133⁄8(340 mm)

155⁄8(397mm)

137⁄8(352 mm)

R

SE

F

J

137⁄8(352 mm)

95⁄8(244 mm)

R

SG

E

J

Figure 50 - Direct Expansion and Electric HeatingCooling Coils G Heating Coils 12, 13

S = SupplyR = Return

S = SupplyR = Return

R.H. Connections R.H. Connections

CW Coil

HW C

oil

L.H. Connections

CW Coil

Air Flow

AirFlow

AirFlow

Cooling Dimensions Shown Heating Dimensions Shown Cooling Dimensions Shown Heating Dimensions Shown

D

B

J113⁄8

(289 mm)

133⁄8(340 mm)

R

S E

F

J

HW C

oil

137⁄8(352 mm)

155⁄8(397 mm)

R

SG

E

J95⁄8

(244 mm)

137⁄8(352 mm)

S = SupplyR = ReturnLL = Liquid LineSL = Suction Line

LL

SL

D

B

J113⁄8

(289 mm)

133⁄8(340 mm)

Steam

LL

SL

Air Flow

AirFlow

Air Flow

AirFlow

S = SupplyR = ReturnLL = Liquid LineSL = Suction Line

LL SL

C

73⁄8(187 mm)

C

LL

SL

73⁄8(187 mm)

JunctionBox

HJ

R.H. Connections

133⁄4(349 mm)

D

C113⁄8

(289 mm)

73⁄8(187mm)

AirFlow

LL

SL

HJ

R.H. Connections

133⁄4(349 mm)

JunctionBox

Air Flow

133⁄8(340 mm)

115⁄8(295 mm)

RS

BA

Heating Dimensions ShownR.H. Connections

Cooling Dimensions ShownL.H. Connections

Heating Dimensions ShownR.H. Connections

Cooling Dimensions ShownL.H. Connections

A

B

S

R

J

115⁄8(295 mm)

133⁄8(340 mm)

Steam

Air Flow

Note: For opposite end drain steam coils (code 78,79) Return (R) is 71⁄4˝ (184mm) from bottom of unit and C - 27⁄8˝ (73mm) from back of unit.

Coil Headers, Locations (Continued)

Page 17: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 17

Valves and Piping

The optional factory-supplied AAF®-HermanNelson® Control Valve(s)for water applications can be either 2-way or 3-way type, and is / areshipped separate from the unit ventilator itself so no shipping damageoccurs to the piping of the connection stub from the weight of the valveand to provide the installer with maximum flexibility in making thefield piping connection. Before proceeding, see figures 53 through 62as applicable, as well as the job-specific piping drawings.

Face and Bypass2-Way and 3-Way End-of-Cycle Valves

Control 2 PositionElectrical 24 VAC, 50/60 Hz

Stroke Power Stroke 9 to 11 secondsSpring return 4 to 5 seconds

Ambient 32°F to 125°F (0°C to 52°C)

Connections 3⁄4" FNPTStatic Pressure 300 psi (2100 kPa)

Close-Off Pressure 13 psi (90 kPa)

Temperature 32°F to 200°F (0°C to 93°C)

Connections 3⁄4" FNPT, 1" FNPTStatic Pressure 300 psi (2100 kPa)

Close-Off Pressure 13 psi and 15 psi(90 kPa and 103 kPa)

Temperature 32°F to 200°F (0°C to 93°C)

Control 2 PositionElectrical 24 VAC, 50/60 Hz

Stroke Power Stroke 9 to 11 secondsSpring return 4 to 5 seconds

Ambient 32°F to 125°F (0°C to 52°C)

Table 10 - 2-way Actuator

Table 11 - 2-way Valve Body

Table 12 - 3-way Actuator

Table 13 - 3-way Valve Body

Connection Cv X Y Z3⁄4"(19mm) FNPT 7.0 111⁄16" (43mm) 11⁄16" (23mm) 35⁄8" (92mm)*1"(25mm) FNPT 7.0 17⁄8" (47mm) 1" (25mm) 311⁄16" (94mm)

* 1" valve for steam only

Table 14 - EOC Connection

23⁄8"(61mm)

33⁄16"(81mm)

17⁄16"(37mm)

35⁄8"(92mm)

111⁄16"(43mm)

111⁄16"(43mm)

311⁄16"(94mm)

31⁄4"(83mm)11⁄4"

(32mm)

29⁄16"(66mm)

3⁄4"(19mm)

7⁄8"(22mm)

Figure 52 - 3-way EOC Valve

3⁄4"(19mm)

11⁄4"(32mm)

31⁄4"(83mm)

23⁄8"(61mm)

33⁄16"(81mm)

XX

Y

Z

311⁄16"(94mm)

29⁄16"(66mm)

3⁄4"(19mm)

3⁄4"(19mm)

7⁄8"(22mm)

Figure 51 - 2-way EOC Valve

Notes:1. See label furnished on 2-way valve to determine direction of flow through the

valve.2. Adhere to the port orientation shown for the 3-way valve.

For hot water applications and chilled water/hot water (2-pipe) applications, the2-way valve furnished is normally piped open to the coil; the 3-way valve is pipednormally open to the coil.For chilled water applications, the 2-way valve furnished is normally piped closedto the coil; the 3-way valve is piped normally closed to the coil.All water coil stubs are 7/8" I.D. female sweat. Coil connections terminate 9"(229mm) from the end of the unit. Hot water connections may be same end ascooling coil connections, but are recommended to be opposite end to facilitatepiping. When using AAF® MicroTech controls, they must be opposite end.

The 2-way EOC hot water or 2-pipe CW/HW valve is furnishednormally open to the coil. When the valve is de-energized (off) thereis full flow through the coil. Energizing the valve shuts off the waterflow.

Figure 53 - 2-way EOC, Normally Open, Hot Water or 2-pipe CW/HW Valve Piping

The 3-way hot water or 2-pipe CW/HW valve is furnished normallyopen to the coil. When the valve is de-energized (off) there is full flowthrough the coil. Energizing the valve allows the water to bypass thecoil.Figure 54- 3-way EOC, Normally Open, Hot Water or 2-pipe CW/HW Valve Piping

Return

Return

Balancing and Shutoff Valve

Shutoff Valve

Supply

Supply

2-way EOCValve Unit Coil

Unions

A B

Return

Return

Shutoff Valve

Shutoff Valve

Supply

Supply

3-way EOC Valve

Unit Coil

Union

BalancingValveBypass

AB

AB Union

Heating – Hot Water End of Cycle Valve Piping

Page 18: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

18 IM 725 (1-02)

Figure 59 - 2-way Modulating, Normally Open, Hot Water or 2-pipe CW/HWValve Piping

31⁄4"(83mm)

6.9 Max.(175mm)Z

Y

XOptional Factory-Supplied2-way Modulating Valve Optional Factory-Supplied

3-way Modulating Valve

31⁄4"(83mm)

6.9 Max.(175mm)Z

Y

X

Connection Cv X Y Z

1⁄2"(13mm)1.3

3.02" 1.06" 8.02"FNPT

2.2(77mm) (27mm) (204mm)4.4

3⁄4"(19mm) 5.5 3.60" 1.06" 8.02"FNPT 7.5 (91mm) (27mm) (204mm)

*1"(25mm) 10.0 4.60" 1.13" 8.70"FNPT 14.0 (117mm) (25mm) (221mm)

* 1" valve for steam only

Connection Cv X Y Z3⁄4"(13mm) 2.0 3.0" 1.37" 8.02"

FNPT 4.0 (76mm) (36mm) (204mm)3⁄4"(19mm) 6.8 3.60" 1.30" 8.02"

FNPT (91mm) (33mm) (204mm)

Table 15 - 2-Way Connection

Table 16 - 3-way Connection

Figure 57 - 2-Way Modulating Valve Figure 58 - 3-Way Modulating Valve

2-Way and 3-Way Modulating Valves

The 2-way EOC CW valve is furnished normally closed to the coil.When the valve is de-energized (off) there is no flow through the coil.Energizing the valve allows flow through the coil.

The 3-way EOC CW valve is furnished normally closed to the coil.When the valve is de-energized (off) the flow bypasses the coil.Energizing the valve allows flow through the coil.

Figure 55 - 2-way EOC, Normally Closed, Chilled Water Valve Piping Figure 56 - 3-way EOC, Normally Closed, Chilled Water Valve Piping

Return

Return

Balancing and Shutoff Valve

Shutoff Valve

Supply

Supply

2-way EOCValve Unit Coil

Unions

A B

Return

Return

Shutoff Valve

Supply

Unit Coil

Union

Shutoff Valve

Supply

3-way EOC Valve Union

Bypass

A B

AB

BalancingValve

Cooling – Chilled Water EOC Valve Piping

Heating – Hot Water Modulating Valve Piping

The 2-way Modulating hot water (2-pipe CW/HW) valve is furnishednormally open to the coil. When the valve is de-energized (off) thereis full flow through the coil. Energizing the valve reduces the volumeof water flow in a modulating fashion.

Return

Return

Balancing and Shutoff Valve

Shutoff Valve

Supply

Supply

2-WayModulating Valve Unit Coil

Unions

AB

The 3-way Modulating hot water or 2-pipe CW/HW valve is furnishednormally open to the coil. When the valve is de-energized (off) thereis full flow through the coil. Energizing the valve allows a varyingamount of water to bypass the coil.

Figure 60 - 3-way Modulating, Normally Open, Hot Water or 2-pipe CW/HW ValvePiping

Return

Return

Shutoff Valve

Shutoff Valve

Supply

Supply

3-way Modulating Valve

Unit Coil

Union

Union

Balancing Valve

B

ABA

A

CAUTION!

Care must be taken with modulating valves to ensure properwater flow. In freezing conditions, water flow must be maintainedthrough the heating coil or a suitable freeze-prevention solutionemployed to prevent freeze-up. Similarly, the cooling coilshould be drained or a suitable freeze-prevention solutionemployed.

Page 19: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 19

In Steam Systems:The optional factory-supplied AAF®-HermanNelson® ModulatingControl Valve for steam applications is the 2-way type. It is shippedseparately from the unit ventilator to preclude shipping damage, yetprovide the installer with maximum flexibility in making the fieldpiping connection. Before proceeding, see Figure 63, as well as thejob-specific piping drawings.

Return

Shutoff Valve

Shutoff Valve

Supply

Return

Supply

Unit Coil

Equalizing Line

(Note 1)

Steam Trap

See Figures 64 and 65. Connect the 1/4" (6.35mm) vacuum breakertube to the downstream return line. Make this connection downstreamof the trap outlet.

Figure 63 - Typical 2-Way Modulating Valve, Steam Piping

Note: See label furnished on 2-way valve to determine direction of flowthrough the valve.

For steam applications, the 2-way, angle pattern valve furnished isnormally piped open to the coil. All steam coils are 1-1/8" (34mm)female sweat connections. Coil connections terminate 9" (229mm)from the end of the unit.Steam coils have a factory-installed pressure equalizing valve and a24" (610mm) long pressure equalizing line that terminates in a 1/2"M.P.T. fitting.Steam connections may be same end as cooling coil connections, butare recommended to be opposite end to facilitate piping. When usingAAF® MicroTech controls, they must be opposite end.

Figure 64 - Same End Connections (68/69 Coils)

Control Valve: Install OnCenter Coil Connection

Vacuum Breaker(By AAF-HermanNelson)

Vacuum Breaker Tube(By AAF-HermanNelson)

Steam Trap (By Others)

1⁄4˝ Flare By 1⁄2˝ MPTHalf-Union And 1⁄4˝ Flare(By AAF-HermanNelson)

Tee (By Others)

Cooling – Chilled Water Modulating Valve Piping

Figure 62 - 3-way Modulating, Normally Closed, Chilled Water Valve Piping

The 2-way Modulating chilled water valve is furnished normallyclosed to the coil. When the valve is de-energized (off) there is no flowthrough the coil. Energizing the valve allows flow through the coil ina modulating fashion.

The 3-way Modulating chilled water valve is furnished normallyclosed to the coil. When the valve is de-energized (off) the flowbypasses the coil. Energizing the valve allows flow through the coil ina modulating fashion.

Figure 61 - 2-way Modulating, Normally Closed, Chilled Water Valve Piping

Return

Return

Balancing and Shutoff Valve

Shutoff Valve

Supply

Supply

2-WayModulating Valve Unit Coil

Unions

AAB

End of Cycle Steam Valve Piping

Return

Shutoff Valve

Supply

Supply

3-wayModulating Valve

Union

Balancing Valve

A

B

Return

Shutoff Valve

Unit Coil

Union

AB

Page 20: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

20 IM 725 (1-02)

Typical Hot Water Coil PipingFigure 65 - Face and Bypass With End-of-Cycle Valve

(Piping Within Unit End Compartment)Figure 66 - Face and Bypass With End-of-Cycle Valve (Piping Outside Unit End Compartment)

Figure 67 - 3-Way Modulating Valve Control(Piping Within Unit End Compartment)

Figure 68 - 3-Way Modulating Valve Control(Piping Outside Unit End Compartment)

11

21

3

45

15

67

15

2

3

4

567

8

2

3

4

5

67

8

2

3

4

5

6

7

15

15

1515

15

11

1

15

Coil PipingHeating valve actuators should be mounted in an upright positionabove the centerline of the valve body and should be piped normallyopen to the coil. Modulating valve actuators for hot water applicationsmay be positioned above the valve body a maximum of 75° from thevertical. For steam applications only, mount the modulating valveactuator above the valve body at 45° from the vertical. Two-position,end-of-cycle (EOC) valves used with face and bypass damper controlledunits may be positioned above the valve body a maximum of 85° fromthe vertical. All control valves are shipped loose so no shippingdamage occurs to the piping or the coil connection stub from the

weight of the valve and to provide the installing contractor withmaximum flexibility in making the field piping connections. Refer toAAF-HermanNelson factory instruction sheet shipped with the unitfor port orientation and a piping schematic. Control valves must beinstalled on the units in which they are shipped. Indiscriminate mixingof valves among units can result in valves not properly sized for thedesired flow rate. Control valves should be installed so that there is 2"minimum clearance to remove the actuator from the valve body. As afuture service consideration, provide unions for removal of the unitcoil and/or the control valve.

DescriptionsThree-way control valve (AAF-HermanNelson)

Coil air vent (AAF-HermanNelson)

Coil drain (AAF-HermanNelson)

Shutoff valve (Others)

Balancing shutoff valve(s) (Others)

Supply

Return

Unions (Others)—Must disconect below floor line

2

1

3

6

4

5

7

8 15

14

13

12

11

10

9 Two-way, two-posiiton valve (AAF-HermanNelson)

Union: Half attached to coil, half attached to valve

Modulating control valve (AAF-HermanNelson)

All piping, fittings and unions by others (not AAF-HermanNelson) except as

noted

Check valve and pressure equalizing line (AAF-HermanNelson)

Float and thermostaic steam trap (Others)

Supply and return coil connection and stub-up unions by others

Page 21: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 21

Typical Steam Coil Piping

Figure 69 - Face and Bypass With End-of-Cycle Valve - Same End DrainConnection (Piping Within Unit End Compartment)

Figure 70 - Face and Bypass With End-of-Cycle Valve - Same End DrainConnection (Piping Outside Unit End Compartment)

Figure 71 - 2-Way Modulating Valve Control - Same End Drain Connection(Piping Within Unit End Compartment)

14

1313

4

6

7

8

15

9

14

4

6 7

15

9 15

15

14

13

4

67

8

15

11

Figure 72 - Opposite End Drain Connection – (78/79 Coils)

Left Hand Steam Supply and Right Hand Steam Return (Shown)

Control Valve: Install On Center Coil Connection

Drain Line(By AAF-HermanNelson)

Vacuum Breaker Tube(By AAF-HermanNelson)

Vacuum Breaker(By AAF-HermanNelson)

Steam Supply

Steam Return

Vacuum Breaker Tube(By AAF-HermanNelson)

Steam Trap (By Others)1⁄4˝ Flare By 1⁄2˝ MPT Half-Union And1⁄4˝ Flare (By AAF-HermanNelson)

Tee (By Others)

Right End ViewLeft End View

Page 22: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

22 IM 725 (1-02)

Direct-Expansion R-22 (DX) PipingDX coils have O.D. sweat connections. Interconnecting tubing isfield-supplied. See Table 17, page 24 and job-specific drawings forcorrect tubing sizes.

Wrap TXV valve with a quenching cloth and remove bulb fromsuction line to avoid valve damage while brazing.

CAUTION!

Condensate piping:AAF®-HermanNelson® cooling unit ventilators are designed forcondensate removal into a condensate disposal system. Do not connectthe unit drain connection so that condensate exits to the outside and/or is exposed to freezing temperatures. Installer is responsible forany damage that might be caused from freezing condensate. Inapplications with an end compartment auxiliary drain pan, see theinstallation instructions shipped with the auxiliary drain pan itself.

STOP! Before BrazingTXV (Thermal ExpansionValve) Protected FromOverheating

BulbRemoved ToPreventOverheatingDamage

Use A Quenching ClothWhen Brazing, to PreventOverheating The TXV ValveBody (Avoid Valve Damageand Eratic Operation)

Figure 74 - Wrap TXV Valve Before Brazing

Proper ventilation is required for brazing. When brazing, be sure toprotect unit ventilator components from overheating damage (meltinginsulation, also damage to valves, wiring, electronics, sensors, etc.).During brazing, bleed nitrogen through the piping. Using field-supplied material suitable for insulating refrigerant lines, wrap thethermal expansion valve (TXV) bulb and the piping between the TXVand the point where it enters the coil with at least one thickness of thematerial. Likewise, insulate the suction line. (See figures 76 -80 fortypical piping and wiring)Ensure proper insulation of supply and return piping. Proper insulationprevents loss of unit ventilator capacity, overheating of endcompartment, and / or moisture dripping.

Piping Stub-up Within Cabinet

Unit End Compartment

Piping Stub-up Within 6" End Panel End Panel 6"

Application and Dimension

Wall Line 111⁄2

103⁄4

Left Endof unit(Less end panel)

Caution: Space available in left endcompartment for piping stub-up.Stub-up including unions and shutoffvalves must disconnect below floorline for unit installation and removal.

1

Space available at left end of unitfor piping stub-up when 6" endpanel is used.

Left End of unit(Less end panel)

Wall Line

4

1

Unit End Compartment

6

All dimensions in inches

Figure 73 - Piping Stub-Up Details, 6" End Panel

Page 23: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 23

Figure 75 - Typical Piping and Wiring for Split System

2 Wires(+) Ground

To Open Sight Drain

TXV(ThermalExpansion Valve)

Filter Drier(Field Supplied)

Moisture IndicatorSight Glass(Field Supplied)

WeatherproofFused Disconnect Per NEC

2 Wires(+) Ground

InsulatedSuction Line

FusedDisconnect

Unit Ventilator Split Systems Guidelines

The following provides basic guidelines that will provide propersystem cooling and operation of an R-22 commercial DX/hot watersystem for school applications. DX system components must bematched and sized correctly (not oversized) for the load.

The DX system must incorporate the following, provided by others,for proper operation:� Size piping per ASHRAE Refrigeration Handbook (correct

refrigerant and compressor oil flow), see figure 75 and table 17.� Use clean sealed refrigerant grade piping (prevent system

contamination)� Install Liquid Line Filter Dryer (clean/dry system to prevent

damage of operating components), see figure 75.� Install Liquid Line Sight Glass (indicates refrigerant dryness and

if liquid in liquid line - do not use the sight glass to determinewhen refrigerant system is charged correctly), see figure 75.

� Install High Pressure Switch at condensing unit wired in condensercontrol system (protects compressor and refrigerant system fromexcessive pressures - condenser fan failure or overcharging), seefigure 79.

� Install Low Pressure Switch at condensing unit wired in thecondenser control system (low refrigerant pressure switch protectsthe system under low refrigerant suction conditions), seefigure 79.

� Install Low Ambient Temperature Switch at condensing unitwired in the condenser control system (locks out mechanicalcooling below 60°F - proper system operation and free economizerusage), see figure 79.

� Incorporate Compressor Time Delay (5 minute) in condensingunit control system (reduces excessive compressor cycling), seefigure 79.

� Incorporate Low Refrigerant Temperature Sensor (T4) incondensing unit control system (T4 protects the system underlow refrigerant suction conditions) see figure 79.

� UV fans must continue to run upon Low Refrigerant Temperaturetrip of T4 (evaporator air flow dissipates residual low coil surfacetemperatures - suction pressures raised, coil frosting reduced),see figure 79.

� UV fans must continue to run for set time period during unoccupiedmode after satisfaction of the space sensor (dissipates residuallow evaporator coil surface temperatures - reducing coil frosting),see figure 79.

� Lock the Face and Bypass Damper (actuator spring return to fullface when de-energized) in the full face position during mechanicalcooling (full air through evaporator coil reduces low refrigerantsuction conditions, potential coil frosting)

� When Brazing bleed Nitrogen through piping (reduced oxidesand blockage in piping/TXV)

� Use Heat Sink when brazing to prevent overheating the TXVvalve body and bulb (avoid valve damage and erratic operation),see figure 74.

� Verify the TXV bulb securely attached at 2 or 10 o’clock for 7/8" and smaller diameter suction line piping (proper suction gassensing and reduced hunting) See figure 75

� Insulate the TXV bulb (reacts to refrigerant temperatures and notambient), see figure 77.

� Insulate the suction line piping (minimum heat pickup), seefigure 75 and 77.

� Evacuate and properly charge the refrigerant system, see figure78.

� Charge to subcooling at the condensing unit per the condensingunit manufacturer’s instructions, typically 9°F to 12°F subcoolingat 95°F outdoor ambient (results in correct refrigerant distributionat the coil to prevent low suction temperatures)

� Adjust TXV for correct superheat to eliminate/minimize hunting,see figure 80.

� Set superheat to 5°F to 7°F at the UV coil suction line when 95°Foutdoor ambient (proper system superheat for optimumperformance). Allow system to settle for 20 to 30 minutes toreach stable steady state conditions and then recheck/adjustsuperheat if necessary, see table 19.

� Compensate both subcooling and superheat for actual outdoorambient and indoor air temperatures

� In windy areas, add wind baffles to condensing unit or build aparapet (eliminate wind effect on condensing unit coil for properTXV refrigerant flow at lower ambient)

� For lower ambient conditions install variable speed condenserfan head pressure control to maintain head pressures between180psig and 280psig (for proper TXV refrigerant flow at lowerambient), see figure 79.

Figure 76 - TXV Piping Detail & Descriptions (Left Hand Piping Shown)

TXV Superheat Adjustment

TXV (Thermal Expansion Valve)

Return (Suction Line)

Bulbattached in the 2 or10 o'clock position

Equalization Tube

Drain Cap

Supply (Liquid Line)

Page 24: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

24 IM 725 (1-02)

Hazardous Voltage!Disconnect all electric power including remote disconnectsbefore servicing. Failure to disconnect power before servicingcan cause severe personal injury or death.

Sight Glass

TXV (Thermal Expansion Valve)

Insulate Bulb(Reacts ToRefrigerantTemperature andNot Ambient)Insulate TheSuction Line Piping(Minimum HeatPickup)

Return (Suction Line)

Supply (Liquid Line)

Figure 77 - Insulate Bulb and Suction Line Piping Figure 78- Typical Split System Evacuation/Charging Set-up

Suction Line Service Valve

Liquid Line Service Valve

Outdoor Fan

Compressor

Gauge Bar Hoses

Vacuum Pump

StrainerDrier

TXV

Indoor Fans

ChargingCylinder

Indoor Coil

Outdoor Coil

Low PressureGauge

Outdoor Condensing Unit

Unit Ventilator

High PressureGauge

Figure 79 - Typical Unit Ventilator/Condensing Unit Wiring Diagram

Compressor

CompressorContactor

Capacitor

HeadPressureController(Optional)

FanMotor

HighPressureSwitch

LowPressureSwitch

TDR = Time Delay RelayTB = Terminal Block

T4

23

1

Rec3

Line Voltage

Factory WiredField Wired (By Others)

TDR or TB

Low AmbientTemp. Switch

T1 T2

L2L1

L2

L1

24V

24V

Checking System ChargeThe system charge should be checked under design conditions [95°Foutside air, 80°F/67°F (DB/WB) indoor air]. Refer to condensing unitmanufacturer's guidelines.Before adjusting refrigerant charge, verify that the unit ventilator isoperating at normal design cfm. Nominal cfm is determined with a drycoil, and cfm will be reduced during air conditioning operation witha wet coil. Filters and coil must be clean and fan speed set at high.temperature to obtain subcooling.

Determining SubcoolingTo determine correct subcooling:

1. Measure outdoor ambient. It must be between 65°F and 105°F.2. Measure liquid line temperature 6 inches from the TXV inlet.3. Measure liquid line pressure near the TXV.4. Determine saturated liquid temperature from saturated temperature

pressure chart (table 18).5. Subtract measured liquid line temperature from saturated liquid

temperature to obtain subcooling.6. Adjust charge per condensing unit manufacturer recommendation

to obtain 9 - 12°F subcooling.

(By Others)(By Others)

Note:Table 17 piping dimensions are for systems with up to 30 ft. (9.14 m) verticalseparation and up to 100 ft (30.47 m) horizontal separation from the outdoorcondensing unit.

Table 17 - Dimensions, DX Tubing inches (mm)

Models AVS, AVV, AVB, AVR Suction Line O.D. Liquid Line O.D.

S07 3/4" (19mm) 1/4" (6mm)

S10 3/4" (19mm) 1/4" (6mm)

S13 7/8" (22mm) 3/8" (10mm)

S15 7/8" (22mm) 3/8" (10mm)

Typical Condensing Unit

Typical Unit Ventilator Interface

WARNING!

Page 25: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 25

Table 18 —Saturated Temperature - Pressure Chart

(°F) R22-PSIG (°F) R22-PSIG (°F) R22-PSIG32 57.5 44 74.5 80 143.633 58.8 45 76.0 85 155.734 60.1 46 77.6 90 168.435 61.5 47 79.2 95 181.836 62.8 48 80.8 100 195.837 64.2 49 82.4 105 210.838 65.6 50 84.0 110 226.439 67.1 55 92.6 115 242.740 68.5 60 101.6 120 259.941 70.0 65 111.2 125 277.942 71.4 70 121.4 130 296.843 73.0 75 132.2 140 337.3

Determining System SuperheatAfter the subcooling has been determined, check system superheat.

1. Determine required superheat from superheat range, table 18.2. Measure suction line temperature 6 inches from service valve.3. Measure suction line pressure at service valve and determine

saturated suction temperature from table 18.4. Subtract saturated suction temperature from measured temperature

to obtain superheat.5. Refer to table 19 and adjust charge as required for correct superheat

at ambient conditons.

Note:Each time that charge is added or removed from the system, allow the system torun approximately 20 - 30 minutes before pressure and temperature readings aretaken and superheat calculations made.

Note:If system hunting occurs or subcooling is reduced, it may be necessary to adjustTXV to obtain correct superheat.

Filter(s)With AAF-HermanNelson’s single-filter design, filter changeouttakes only seconds.

Turn off the unit, (fan speed switch or unit on/off switch is locatedbehind the right front end compartment panel). Remove the centerfront panel, pull out the filter and replace with a clean filter. Replacethe center panel and restart the unit.

Filters should be replaced during the first week of placing into serviceto prevent dirt carry-over into the internals of the unit and back into theclassroom, (see figure 81). A periodic filter changeout program shouldbe established. Filters are included in all units. AAF®-HermanNelson®

single-use filters are standard on all but electric heat units, which comewith permanent wire mesh filters. Permanent wire mesh and renewablemedia filters are available for non-electric heat units, in lieu ofsingle-use filters.

• Single-use filters feature Amerglas media. They are designed tobe used once and discarded.

• Permanent filters are metal filters that may be removed forcleaning and reused numerous times.

• Renewable media filters (figure 81) consist of a heavy paintedmetal structural frame and renewable Amerglas media

12" Left FrontAccess Panel

Filter

Motor

12" Right Front Access Panel

Renewable Media (Single-use AndPermanent Wire Mesh Filters Also Available.)

StructuralFrame

Top AccessDoors

Figure 81 - Filter installation

Superheat Adjustment1. Remove the seal cap from thermal expansion valve (see figure 80).2. Turn the adjustment screw clockwise to increase superheat and

counterclockwise to decrease superheat (see figure 80). Onecomplete 360° turn changes the superheat approximately 3-4°F,regardless of the refrigerant type. As much as 30 minutes may berequired for the system to stabilize after the adjustment is made.

3. Replace and hand-tighten seal cap.

Figure 80- Superheat Adjustment of TXV

SuperheatAdjustment Screw

Counterclockwise ToDecrese Superheat Clockwise To Increse

Superheat

CAUTION!

Remove Seal Cap

Do not force adjustment stem of TXV. When adjusting superheatsetting, there are a maximum of 10 turns on the stem. Turningadjustment stem after reaching stop will damage valve.

OutdoorIndoor Coil Air Inlet Temp.

Ambient DB/WB (50% RH)75/63 80/67 85/71

105 * * 8-10100 * 3-5 9-1195 * 5-7 11-1390 * 9-11 13-1585 5-7 10-12 15-1780 8-10 12-14 18-2075 10-12 15-17 21-2370 13-15 19-21 24-2665 15-17 21-23 26-28

Table 19 —Superheat Range

CAUTION!

TURN OFF UNIT BEFORE SERVICING

CAUTION!

Units must have a filter installed when operating.

Page 26: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

26 IM 725 (1-02)

Table 20 - Floor AV Electrical Data/Motor Data and Unit Amp

Unit CFM L/s Motor Unit Current #

Series (Nom.) HP Watts115V 208V 230V 265V

S07 750 354 1/4 164 1.8 1.0 0.9 0.8

S10 1000 472 1/4 244 3.1 1.7 1.5 1.3

S13 1250 590 1/4 306 3.5 1.9 1.8 1.5

S15 1500 708 1/4 334 3.7 2.0 1.8 1.6

# Amps at unit voltage, 60 Hz, single phase

Step 4Make Electrical Connections

To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes,and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s).

Power supply to unit must be disconnected when making field connections. To avoid electrical shock, personal injury or death, be sure torigorously adhere to field wiring procedures regarding proper lockout and tagout of components.

See Table 20, and Figures 82 - 87 and the job-specific electricaldrawings before proceeding with field power and control wiring. Seealso the wiring diagram provided on the unit ventilator right frontaccess panel.In addition, those unit ventilators equipped with optional electricheating coil have electric heating coil power connections at right endonly.

Instructions1. Provide power supply to right end compartment to match unit

nameplate.

2. Wire leads provided from unit ventilator electric connection boxto load side of unit power switch (switch provided by AAF).The junction box has 1"(25mm) and 2"(51mm) knockouts, located10-1/2"(267mm) from right end of unit.

3. Provide ground wire from grounding screw in switch junction boxto switch ground terminal.

4. Wire field power supply to line side of unit power switch. Wireground conductor to switch ground terminal.

5. Mount unit power switch in switch junction box and install switchcover plate (provided).

Note:On units with electric heat, the 2 pole unit power switch is replaced by a 3 poleswitch and is mountd as shown on figure 82. (A) shows switch location for valvecontrol units and (B), (C) and (D) show location for Face & Bypass control units.(B) is for 208, 230 and 265 volt vertical (AV) and horizontal (AH) units. (C) showslocation for 460 volt vertical (AV) units and (D) shows location for 460 volthorizontal (AH) units.Also, on electric heat units with controls by others, wiring to the field mountedcontroller is done in the left end compartment. See specific wiring diagram fordetails.

WARNING!

WARNING!

Wire Raceway

Figure 83 - Electric Connection Box in Right Front End Compartment

Switch Junction Box

Fuse

High-Med.-Low-Off Motor Speed Switch

Auto Transformer

Figure 84 - Back View of Electric Connection Box

Molex Plug for Motor

115V Receptacle

Jumper PlugSupplied For"Controls By Others"

CAUTION!

Use copper conductors only. Use of aluminum conductors mayresult in equipment failure and overheating hazards. All wiringin right hand compartment must be class 1.

Figure 82 - Electric Heat Unit Power Switch Locations and Wire Raceway

A

B

C

D

Note:Unit wire sizing should be determined in accordance with NEC and localcodes.

Unit Power Switch

Page 27: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 27

Figure 85 - Typical Electrical Locations, Vertical Floor Models AVS, AVV,AVB, AVR, Front View, Access Panels Removed

Unit Mounted Microtech™ Direct Digital Controls (DDC) ComponentsThis Drawing shows the location of the standard and optional AAF®-HermanNelson® MicroTech™ control items. The following is a generaldescription of these components.

1. MicroTech Unit Ventilator Controller: This is a factorymounted microprocessor-based DDC control device which iscapable of stand-alone control or network control from a frontend computer. The controller can support sixteen (16) inputsand sixteen (16) outputs. Each input supports either analogsensing and/or binary contact closure. Each output consists ofa binary contact closure to operate controlled devices. Thecontroller will provide status of either the outputs or the inputsupon request from a personal computer connected either to anetwork or an individual controller. The controller containsself-diagnostic capability to maintain constant reliability. Thecontroller provides heating and cooling control in response tovarious inputs as well as the room sensor which may be eitherunit mounted or wall mounted. Damper actuators are preciselypositioned by means of step-and-wait parameters built intocontrol software. Two-position functions such as DX cooling/heating and electric heating are also initiated by the controller.Room temperature adjustment, unoccupied temperature offsetand outdoor air damper minimum position are all adjustable atthe controller. In a network system, these three adjustmentsare not operative and are done as part of the network controlplan.The controller provides a visual means of fault detection withthe use of status LED on board.

2. Room Temperature Adjustments: This item controls the roomtemperature setpoint.

3. Terminal Strips as required: Provides convenient connectionpoints for the following:a. Modulating steam or water control valve (factory wired).b. Wall mounted room sensor.c. Condensing unit control circuit (field wired by others).

4. Damper Actuator(s): These devices position the outdoor androom air dampers and bypass dampers (when furnished) inresponse to the unit ventilator controller. Factory mounted,wired and adjusted.

5. Sampling Chamber: This enclosure houses the room air sensorwhenever a unit mounted sensor is specified. Room air iscontinuously drawn through the sampling chamber to insurefast accurate response to temperature changes within the room.

*6. Time Clock Accessory: This device automatically cycles unitthrough occupied and unoccupied modes in accordance with auser programmed time schedule. Programming instructionsare included. Time clocks have battery backup so they will notrequire resetting if electric power is interrupted. Located infront of the room air fan motor.

7. Electric Connection Box: Contains the motor speed switch,motor speed transformer and fusetron(s) when furnished.Wiring connections to the day/night relay and vent relay aremade in this box. Refer to the unit wiring diagram forspecifics.

8. “High-Med-Low-Off” Motor Speed Switch: Allows user toselect the fan speed desired. The “Off” position shuts unitdown completely.

9. Right End Compartment:Class 1 wiring required.

10. Unit Main Power “On-Off” Switch: Disconnects main powerto unit for servicing the unit or when unit is to be shut down foran extended period.

11. Left End Compartment: Class 2 wiring permitted.

*Not furnished with network units since the function is handled through thecommunication network.

Motor 5

48

9

1011

7

2

1

3 6*

J6 J7 J8 J9

LED RELAY OUT AUX OUT STATUS POWER PWRG 0 H 1 2 3 4 5 6 7 8 V 9 10 G 24V

1 2 3 1 2 3 4 5 6 R 5 4 3 2 1 0 G S G S G S G S G S G S G S G S G S1 S0COMMB COMM A DIGITAL INPUT IN 13 IN 12 IN 7 IN 6 IN 5 IN 4 IN 3 IN 2 IN 1. 0

J1 J2 J3 J4 J5

MicroTech®

325 ControllerThis devise complies with Part 15 of the FCC rules.Operation is subject to the following 2 conditions:(1) This device may not cause harmful interference.(2) This device must accept any interference received, including interference that may cause undesired operation.

File E159169Model 325

Part No. 107627201

J1 J2 J3

J4

J5

COOLING SETPOINT ISFACTORY SET 6°F ABOVE

HEATING SETPOINT

HI LO

NETWORKADDRESS

% °F °FMINIMUM OA UNOCCUPIED HEATING SETPOINT

POSITION OFFSET

30 40

5020

10 75

0 100 0 20

10

155

70

65 75

60 80

J6 J7 J8 STATUS POWER J9

0123456789ABC

DEF 0123456789ABC

DEF

Remote StatusLED Output

RelayOutputs

AuxiliaryOutputs(TRIAC)

StatusLED

Power SupplyLED

Electro-MechanicalRelays

HexSwitches

DigitalInputs

CommunicationPorts Analog

Inputs

Heating Setpoint Pot

Minimum OADamperPosition Pot

UnoccupiedOffset Pot

Figure 87 - MicroTech Controller

Figure 86 - Sensor Locations

Discharge Air Sensor Room Air Sensor

Holes in FrontAccess Panel Outdoor Air Sensor

Outdoor AirOpening

Page 28: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

28 IM 725 (1-02)

Exhaust Fan Interlock

Master/Slave Wiring

Pneumatic Day/NightChangeover Control

Ventilation Lockout ControlNetwork Wiring

Day/Night ChangeoverControl

(Stand-Alone Units Only)

Remote Condensing UnitControl Wiring

MicroTech™ orControls By Others

(Stand-Alone Units Only) (Stand-Alone Units Only)

(Stand-Alone Units Only)

Unit Wiring Terminations Fan/Radiation Interlock

Factory WiringFurnished OnlyAs Required

Left End Compartment

BLK

WHT

RED

GRN

ORG

BLU

Y

C1

O

R

W1

COM

PNK

GRY

RED

For FurtherInformationSee AppropriateField WiringDetail

For Further InformationSee Appropriate FieldWiring Detail

Motor Speed Control Box - Right End

Electric Heat Control Box - Right End

19

20

YEL

36

37

BRN

GroundMain Power SupplyNon Electric Heat Units

1

2

3

SW-1

L1

L2

L3

SW-1 — Main Power “On-Off” Switch

Main PowerSupply ElectricHeat Units(Omit L3 ForSingle PhaseApplications)

Left End Compartment

Y

C1

O

R

W1

COM

(24 Vac. Class II)To Remote CondensingUnit Contactor Coil Day/Night

Changeover (4VAInRush) EnergizeTo Put Unit InNight Mode

Motor Speed Control Box - Right End

19

20

YEL

36

37

BRN

Left End Compartment

BLK

WHT

RED

GRN

ORG

BLU

PNK

GRY

First Unit

ORG

BLU

PNK

GRY

Additional Unit

ORG

BLU

PNK

GRY

Last Unit

Attach Wires (2 Twisted Conductor Shielded),Belden 8761 Or Equivalent, From Unit To UnitIn Daisy Chain Fashion, In Any Order.

BLK

WHT

RED

GRN

ORG

BLU

PNK

GRY

ORG

BLU

PNK

GRY

ORG

BLU

PNK

GRY To LocalMaster Panel

Vent Lockout (4VA InRush)Energize To Close TheOutdoor Air Damper

Motor Speed Control Box - Right End

19

20

YEL

36

37

BRN

Exhaust Fan Interlock (4VAInRush) Energize To OpenOutdoor Air Damper

19

20

YEL

36

37

BRN

Pneumatic/Electric SwitchClose Contacts To Put UnitIn Night Mode (24VACClass II. 1Amp)

Motor Speed Control Box - Right End

19

20

YEL

36

37

BRN

Factory WiringFurnished OnlyAs Required

Ground

Attach Wires (2 Twisted Conductor Shielded),Belden 8761 Or Equivalent, From Unit To UnitIn Daisy Chain Fashion, In Any Order.

Left End Compartment

First Unit

Additional Unit

Last Unit

X3

24 VAC

UVCDI-2

DI-3

DI-4

DI-5

DI-R

Digital InputWiring Example

Auxiliary Output Wiring Example

UVC

AO-10AO-V

+29vdc @ 30mA

294vdcRelay Coil

(Wiring By Others)

Diode(Wiring By Others)

Figure 88 - Typical Power and Control Field Wiring (See Unit Right Front Panel or Unit Wiring Diagram for Electrical / Control Electrical Hookups)

Page 29: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 29

Typical Wall Mounted Room Air Sensor

Figure 90 - Wall Sensor With Tenant Override, Setpoint Adjustment,Communications Port, and Thermometer (Shown) or without Thermometer

Installation

1. Installer must be qualified, experienced technician.2. Disconnect power supply before installation to prevent

electrical shock and damage to equipment.3. Make all connections in accordance with electrical wiring

diagrams, and in compliance with national and local codes.Use copper conductors only.

4. Do not exceed ratings of the device. This is a low voltagedevice: Never apply more than 12VAC/VDC to any lead ordamage will result.

5. Avoid locations where excessive moisture, corrosive fumes,or vibrations are present.

.280" 7.11mm Dia. (2)

Communications Port80

Setpoint Adjustment

2.75"(69.85m

1.38"(35.05mm)

3.28"(83.31mm) 60

70

.61"(15.5mm)

4.50"(11.43mm)

Thermometer °F (Optional)

Tenant Override Switch

Green LED

Left End Compartment

22 AWG Stranded Wire( Blk, Wht, Grn, Org, Blu, Red)

6.00"(162.40mm)

.76"(19.30mm)

Blk

Wht

Red

Grn

Org

Blu

Note:All sensors have black (common) + white (thermistor sensor) + red (LED)wires. Orange and blue wires are provided for communications and a greenwire for tenant override and set point adjustment

Mounting Procedure For Standard Electrical Box1. Feed the cable from the electrical box.2. Strip 1⁄4" of installation from the end of wires.3. Connect wires to appropriate colored leads. See MicroTech™

unit controller wiring diagram.4. Dress wires down and inside the electrical box.5. Using the two 6-32 x 5⁄8" “flathead screws provided, mount the

sensor to the electrical box.

Mounting Procedure For Wallboard Mounting1. Feed the cable through a hole in the wallboard.2. Strip 1⁄4" of installation from the end of wires.3. Connect wires to appropriate colored leads. See MicroTech unit

controller wiring diagram.4. Dress wires down and inside the hole in the wallboard.5. Using the appropriate mounting screws and plastic anchors (not

provided), mount the sensor to the wallboard.

Window Exposure

Window Exposure

Window

Exposure

Interior Wall

Interior Wall

Interior WallInterior Wall

Unit

Unit

= Correct Sensor LocationFigure 91 - Correct Wall Sensor Locations

Note:Avoid placing wall sensor near drafty areas such as doors or windows. Avoid external walls, or dead spots near exposed columns. Avoid direct sunlight on wall sensor.

Window Exposure

= Incorrect Sensor Location

Window Exposure

Interior Wall

Interior Wall

Window Exposure

Unit

Unit

Interior Wall

Interior Wall

Window Exposure

Cubicle Wall

Shelving

File Cabinet

Shelving

Figure 92 - Incorrect Unit and Wall SensorLocations

WARNING!

Page 30: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

30 IM 725 (1-02)

Remove debris, heavy dust anddirt or any obstruction from thearea in front of the return air intakegrille at the floor,(approximately3' - see shaded area) as this willaffect unit performance. If adraftstop system has beeninstalled be sure that all draftstopintake grilles are unobstructed.

NOTICE

See Figure 95 for oiling points. Access to fan shaft bearing is throughleft top access door. Access to the motor bearing is through the righttop access door. Lift the oiler cap. Oil, using a few drops of high gradeSAE 20 or 30 nondetergent oil. Do not over-oil.

Access To Fan Shaft BearingThrough Left Top Access Door Bearing Oiler Cap

Figure 95 - Oiling Points

Figure 93 - Cabinet(s) Meeting Unit Ventilator

Step 5Prepare Unit Ventilator(s) for Start-up

Installing Unit Ventilator End Panels:See Figure 94. Accessory end panels are shipped separately withhardware and kickplate. Align each end panel with the top and frontedges of the unit ventilator. Attach each end panel to the unit ventilatorusing the hardware provided.

Tinnerman Clips

Tinnerman Clips

Screws(insert through endpanel and thread intotinnerman clips on unitsubbase)

Screws(insert through upper mounting holes inside unit endcompartment, and thread into tinnerman clips on endpanel)

End Panel

Figure 94 - Install End Panels With Provided Hardware (1" End PanelShown)

Fit Front Alignment Bar Into WeldedNotches Permitting Alignment Of StorageAccessories With The Unit Ventilator

Adjustable Kick PlateAnd Leg Levelers

Alignment Slot

Access To Motor Through RightTop Access Door

Oil

Oiling the Fan Shaft Bearing and Motor:

Do not attempt to operate the unit fans until the fan bearingshave been oiled.

Unit Ventilator Start-upAfter the unit ventilator has been properly installed, activate unitelectrical power and applicable chilled water/hot water/steam/refrigerant systems.Before proceeding inspect the fan system, ensure all parts are alignedproperly and move freely. Inspect fans and fan discharge area forobstructions. Rotate fan manually. Check that a clean filter is installedand area in front of unit ventilator is free of debris (see figure 93).Using the applicable control, activate the unit ventilator. Dependingon the operating mode selected, the dampers, fans, and othercomponents should operate as needed.Run the unit ventilator for ten minutes, listening and observing. Fansshould be operating correctly, and rotating in the proper direction,without unusual noise. Likewise, the unit should be free of sheet metalrattles and / or unusual noises. All panels should be in place andproperly fastened, and checked for air leaks and condensation.

Step 6Complete Check, Test and Start Procedure(see page 39)

CAUTION!

Page 31: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 31

Tools RequiredA forklift or other lifting device to install this product (See figure 97).Install this product in accordance with good engineering practices andworkmanship, following these general instructions, plus the job-specific AAF®-HermanNelson® submittal drawings provided forspecific dimensions, unit arrangements, controls and electrical details,pipe stub-up locations, etc.

Apply protective material to lifting support(s) that come incontact with unit to prevent scratching or denting the unit.Support the unit across the entire length to prevent twisting orracking, throughout the process of mounting.

Model AH Ceiling Unit Ventilator InstallationModels AHF, AHB, AHV and AHR Ceiling Units

ImportantBefore beginning installation, please read this publication in its entirety.

Refer to AV installation instructions, page 2.

Exposed

Soffit

Partially Recessed

Concealed

Figure 97 - Suggested Lifting Method

AH Ceiling Unit

Lifting Device

Protective Material To PreventScratching and Denting of Unit.Support Across Entire Length ofUnit to Prevent Twisting orRacking.

Figure 96 - Ceiling Unit Arrangements

Step 1Lifting Ceiling Unit Into Position

CAUTION!

DISCONNECT ALL ELECTRICALPOWER BEFORE SERVICING UNITTO PREVENT INJURY OR DEATHDUE TO ELECTRICAL SHOCK.

WARNINGHAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER IN-CLUDING REMOTE DISCONNECTS BEFORESERVICING. FAILURE TO DISCONNECTPOWER BEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.

! CAUTIONUSE COPPER CONDUCTORS ONLY.UNIT TERMINALS ARE NOT DESIGNED TOACCEPT OTHER TYPES OF CONDUCTORS.FAILURE TO DO SO MAY CAUSE DAMAGETO THE EQUIPMENT.

!! DANGER

Safety InformationFollow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available. Follow all warnings andcautions in these instructions and attached to the unit. Consult applicable local building codes and National Electrical Codes (NEC) for special requirements.

Recognize safety information. When you see a safety symbol on the unit or in these instructions, be alert to the potential for personal injury. Understand the meaningsof the words DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards that will result in death or severe personal injury; WARNING meansthe hazards can result in death or severe personal injury; CAUTION identifies unsafe practices that can result in personal injury or product and property damage.

Improper installation, adjustment, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may result in personal injury orproperty damage. This product must be installed only by personnel with the training, experience, skills, and applicable licensing that makes him/her “a qualifiedprofessional HVACR installer.”

Page 32: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

32 IM 725 (1-02)

1. Product CategoryU = Unit Ventilator

2. Product Identifier*AHF = Ceiling, Face & BypassAHV = Ceiling, Valve ControlAHR= Ceiling, Valve Control with Reheat.AHB = Ceiling, Face & Bypass with Reheat.* End Panels Ship Installed

3. Design Series4 = D Design

4. Nominal Capacity S07 = Low static 750 cfmS07 = Low static 750 cfmS10 = Low static 1000 cfmS13 = Low static 1250 cfmS15 = Low static 1500 cfmS20 = Low static 2000 cfmH07 = High static 750 cfmH10 = High static 1000 cfmH13 = High static 1250 cfmH15 = High static 1500 cfmH20 = High static 2000 cfm

5. Voltage, volts, phase, Hertz (v-Hz-ph)A = 115 - 60 - 1C = 208 - 60 - 1G = 230 - 60 - 1J = 265 - 60 - 1D = 208 - 60 - 3H = 230 - 60 - 3K = 460 - 60 - 3

6. Cooling OptionsU = 2 Row CW/HW 2 pipe 1 = 2 Row HiCap CW/HW 2 pipeD = 3 Row CW/HW 2 pipe 2 = 3 Row HiCap CW/HW 2 pipeE = 4 Row CW/HW 2 pipe 3 = 4 Row HiCap CW/HW 2 pipeF = 5 Row CW/HW 2 pipe 4 = 5 Row HiCap CW/HW 2 pipeG = DXV = 2 Row CW 5 = 2 Row HiCap CWS = 3 Row CW 6 = 3 Row HiCap CWW = 4 Row CW 7 = 4 Row HiCap CWY = 5 Row CW 8 = 5 Row HiCap CWZ = None

7. Heating Options00 = None65 = HW One Row66 = HW Two Row67 = HW Three Row68 = Steam Low Capacity69 = Steam High Capacity12 = Low Electric Heat (3 element)13 = High Electric Heat (6 element)

8. Coil ConnectionsE = LH Htg / RH CoolF = RH Htg / LH CoolR = Single Coil LHS = Single Coil RHA = LH Both Coils (only with Controls By Others)B = RH Both Coils (only with Controls By Others)D = RH Electric Heat, One CoilG = RH Elec Ht / LH Cool

9. Controls19 = MicroTech for Remote Wall Sensor (Sensor accessory required)40 = DCV MicroTech for Remote Wall Sensor & Wall CO2 Sensor

(Sensor & CO2 accessories required)17 = Digital Ready (With Damper Actuators, (3) @ 10 K NTC Sensors,

3 Terminal Strips, 75 VA 24 volt Tfmr, Wired; w/o UV Controller)23 = Field Mounted Controls By Others20 = Part Load Variable Air MicroTech for Remote Sensor (Sensor

accessory required)42 = Part Load Variable Air DCV MicroTech for Remote Wall Sensor &

Wall CO2 (Sensor accessories required)

Part Load Variable Air MicroTech Control/Coil CombinationsField 9 Part Load Variable Air MicroTechField 6, 7 2 Pipe or 4 Pipe Water System Only

10. DischargeAJ = Front Discharge Duct Collar, 30 1/2" Length Unit (except S20,

H20)AU = Front Bar Grille Discharge, 30 1/2" Length Unit (except S20, H20)

AH = Front Discharge Duct Collar, 36" Length Unit (w/plenum)AT = Front Discharge Double Deflection Grille, 36" Length Unit (w/

plenum)BD = Down Discharge Double Deflection Grille, 40" Length Unit (w/

plenum)

11. Return Air/Outside Air26 = R.A. Bottom Grille / O.A.Top Duct Collar.27 = R.A. Bottom Grille / O.A.Rear Duct Collar.28 = R.A. Rear Duct Collar / O.A.Top Duct Collar.29 = R.A. Rear Duct Collar / O.A.Rear Duct Collar.25 = 100% RA / RA Bottom Grille / No OA Opening / No OA/RA

Dampers

12. Power ConnectionG = box with Switch

13. ColorW = Off White

14. SKUB = Standard DeliveryC = Extended Delivery

15. Product Style1

Field-Installed Accessories may accompany Unit Ventilator(s), ormay be shipped separately. These may include: Adapter Backs;Aluminum Louvers; Aluminum Grilles; Auxiliary Drain Pans; Controls/ Sensors; End Panels; Spare Filters; MicroTech Controls, Sensors(temperature, humidity, CO2); End of Cycle DDC Valve; ModulatingDDC Valves; Subbases. See instructions shipped with accessoriesand install according to these and the plans.

Unit Ventilator (Ceiling Type) Data Plate - Specific Information

Field 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Model U AHF 4 S07 A Z 65 R 19 AH 26 G W B 1

Page 33: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 33

See table 21 for dimension “A”

Typical Ceiling AH Unit Air Arrangements

Discharge Air Arrangements 301⁄2˝ (750 to 1500 CFM)

Discharge Air Arrangement 40˝ (750 to 2000 CFM)

Discharge Air Arrangements 36˝ (750 to 2000 CFM)

Figure 99 - Arrangement AJ Front Discharge With Duct Collar

Figure 98 - Arrangement AU Front Discharge With Bar Grille

301⁄2"(775mm)

36"(914mm)

73⁄4" (200mm)Max. Recess

16 5⁄8"(422mm)

301⁄2"(775mm)

301⁄2"(775mm)Shown With Return

Air Grille

13⁄4" (44mm)

7" (178mm) x A

3⁄4" (19mm)

77⁄8" (200mm)16 5⁄8"(422mm)

301⁄2"(775mm)

165⁄8"(422mm)

7" (178mm) x A

40" (1016mm)

AirFlow

AirFlow

AirFlow

Figure 101 - Arrangement AH Unit Mounted Plenum With Front Discharge Duct Collar

55⁄8" (143mm)

7" (178mm) x A

4" (102mm) 3⁄4" (19mm)

36"(914mm)

165⁄8"(422mm)

Shown With ReturnAir Grille

AirFlow

Figure 100 - Arrangement AT Unit Mounted Plenum With Front Discharge Double Deflection Grille

41⁄2"(114mm)

Max.Recess

165⁄8"(422mm)

36"(914mm)

36"(914mm)

Grille Finish IsClear AnodizedAluminumAir

Flow

NOTE:1. For all recessed applications (full or partial) it is necessary to carefully examine

both the inlet air and the discharge air physical locations. This must be donefor each location individually and in combination with each other to ensure theyare compatible with the specific installation.

2. Duct collars shipped loose for field installation not by AAF®-HermanNelson®.3. It is important also to verify there is sufficient clearance to open and remove

the bottom access panels and end panels for routine maintenance.4. All dimensions approximated.

Shown With ReturnAir Grille

40"(1016mm)

Grille Finish Is ClearAnodized Aluminum

Discharge Grille Detail

Grille Blades Curved To DirectAir Horizontally Along Ceiling

Figure 102 - Bottom Discharge With Double Deflection Grille

Page 34: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

34 IM 725 (1-02)

Inlet Air Arrangements

Typical Ceiling AH Unit Air Arrangements (Continued)

Outdoor Air

Return Air

51⁄4"(133mm)x A3⁄4"

(19mm) 11⁄2"(38mm)

Outdoor Air

Return Air

1" (25mm)

Figure 104 - Arrangement 26 Return Air Bottom Grille/Outdoor AirTop Duct Collar

Figure 105 - Arrangement 27 Return Air Bottom Grille/Outdoor AirRear Duct Collar

Figure 106 - Arrangment 28 Return Air Rear Duct Collar/Outdoor Air TopDuct Collar

Outdoor Air

Return Air

4" (102mm)

Outdoor Air

Return Air

Outdoor Air

Return Air

3⁄4"(19mm)

51⁄4"(133mm)x A

Outdoor Air

Return Air

3⁄4"(19mm)

51⁄4"(133mm)x A

11⁄2"(38mm)

51⁄4"(133mm)x A

3⁄4"(19mm)

Figure 103 - Arrangement 25 Recirculating Room Air(No Room Air/Outside Air Dampers)

Return AirReturn Air

Unit Series 07 10 13 15 20

Ainches 36 48 60 72 72

mm 914 1219 1524 1829 1829

Table 21 - Dimensions

Outdoor Air

Return Air

1" (25mm)

11⁄8"(29mm)

4" (102mm)

Figure 107 - Arrangement 29 Return Air Rear Duct Collar/Outdoor AirRear Duct Collar

Outdoor Air

Return Air

3⁄4"(19mm)

51⁄4"(133mm) x A

51⁄4"(133mm) x A

3⁄4"(19mm)

NOTE:1. For all recessed applications (full or partial) it is necessary to carefully exam-

ine both the inlet air and the discharge air physical locations. This must bedone for each location individually and in combination with each other to en-sure they are compatible with the specific installation.

2. Duct collars shipped loose for field installation not by AAF®-HermanNelson®.3. It is important also to verify there is sufficient clearance to open and remove

the bottom access panels and end panels for routine maintenance.4. All dimensions approximated.

Pre-Installation ConsiderationsPrior to unit installation, be sure that the exterior wall openings andlouvers, as applicable, are ready and in accordance with the job plans.Horizontal Ceiling Models AHF, AHB, AHV and AHR ceiling unitsare typically installed in the ceiling with a variety of exposures,including completely exposed, partially exposed, partially or fullyrecessed, or completely concealed, (see figure 96). Each installationshould contain a properly sized louver that is designed to let in freshair while preventing water (such as driving rain) from getting past thelouver and into the unit itself. A weather-tight seal keeps unwanted airand moisture from entering the occupied space. See Figures 1 - 3 forvarious louver details. Follow typical installation methods for louversand flashing by others to prevent moisture and air infiltration damage.

Recess FlangesWith Unit ShownFully Recessed

Figure 108 - Fully Recessed Unit

The Cross Tee Must Be RemovableFor Access To Removable End

Panels

Main TeesCross Tees

Ceiling SuspendedIndependent Of Unit

Step 2Wall Openings, Louvers, andVentiMatic Shutter

Page 35: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 35

Duct Design For Noise ControlProper acoustics is often a design requirement for schools. Most of theproblems that are associated with HVAC generated sound can beavoided by properly selecting and locating the components of thesystem. There are some general do’s and don’ts:

The following suggestions can reduce the amount of sound thatreaches the occupied room:• Use flexible duct connections.• Make the discharge duct the same size as the unit discharge openingfor the first five feet.• Line the first 5 feet of the supply duct.• Make two 90-degree turns in the supply and return ducts.• Keep duct velocity low and follow good duct design procedures.• Mount and support the ductwork independent of the unit.• Line the first five feet of the return duct.• Locate the return air intake away from the unit discharge.• Provide multiple discharges.

• Restrict use of high pressure drop flexible ducting.• Size the outdoor air and return air ducts to handle 100% of the totalcfm to accommodate economizer or morning warm-up operation.

If a supply air duct with improper duct work is placed too closeto the unit discharge, it will result in substantial noise. Avoidsuch forms of connections when designing ductwork wheresound attenuation is critical. Figures 109 through 111 showssuggested duct considerations per SMACNA and ASHRAE.

Sound control applies to the return side of the duct design as well asthe supply side. Figure 110 illustrates suggested installation of return-air duct. Note the return air opening, and the sizing and changes indirection of the ductwork. Figure 111 illustrates suggested installationof outside air ducting.

Duct System Considerations

NOTICE

Flexible Boot

5 FeetSame Size AsUnit Discharge

Accoustically Lined

Two 90° Turns

Ductwork SizedBased On Airflow

Ductwork Supported Independent Of UnitUnit Ventilator Discharge

Accoustically LinedFlexible Boot

Ductwork Supported Independent Of Unit

Two 90° Turns

5 FeetSame Size AsUnit Return

Unit Ventilator Return

Figure 109 - Discharge Air Duct Work

Figure 110 - Intake/Return Air Duct Work

Page 36: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

36 IM 725 (1-02)

Figure 113 - Install AH Ceiling Unit Flange

The following general suggestions are offered only to stresstheir importance; however, there are additional importantfactors that must be considered. Assistance in the design ofductwork can be found in the ASHRAE Handbook and SMACNApublications, as well as other recognized authorities.

NOTICE

Anchor the unit using the four unit mounting holes. The unit must besuspended from these holes (figure 112). Do not attempt to suspendthe unit at any other locations. When hanging the horizontal AH unitventilator, the unit should be level both front to back and side to side.This aids in condensate removal from the drain pan, and reduction ofsound. Use a 4' level to determine the unit is not twisted or pitched.

Ceiling Unit Ventilators can be mounted in an exposed position, in asoffit, partially recessed, fully recessed and concealed (see figure 96).For partially and fully recessed units, wall guard flanges are a standardaccessory to provide a finished appearance at the ceiling (figure 113).

Do not attach or hang the ceiling off of the unit ventilator.

Flexible Boot

5 FeetSame Size AsUnit Discharge

Accoustically Lined

Insulated Ductwork to PreventSweating, Heat Loss or Heat Gain

Unit VentilatorIntake

Louver

Outdoor Air

Figure 111 - Outdoor Air Intake and Insulated Duct Work

Assemble Recess Flange and then attach to ceiling T bar or plasterboard. Recess Flange must not make contact with unit, to preventtransmission of any vibration, (see figure 108 and 113).

Recess Flange

NOTICE

Note:36˝ horizontal clearance recommended at right end for service (24˝ minimum).Amount of recess must consider location of end panel fasteners. Recess flangesmust not interfere with access to these fasteners.

Figure 112 - Remove Ceiling Unit End Panels For Access To Mounting Holes

One-inch duct collars are provided for field duct attachment to thesupply-air outlet. The duct collars are field installed. Locate the unitventilator as close as practical to the outdoor air intake opening.Insulate the outdoor air duct to reduce sweating or temperature rise.

End Panel

Release End PanelFasteners To GainAccess To InteriorMounting Holes

Mountings Holes (4)

AH CeilingUnit Ventilator

7"(178mm)Without

End Panel

7"(178mm)

131/2"(343mm)

Step 3Anchoring The Ceiling Unit

Page 37: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 37

Figure 115 - Fully Recessed Unit

Safety Chains

FiltersSee page 25 for information. Model AH filter is removed by openingthe hinged access door, removing the sealing plate and then replacingthe filter, reinstalling the sealing plate and securing the access door,(see figure 115).

Suggested Condensate TrappingThe condensate trap provides for discharge of water from the unitventilator drain pan during the cooling mode, while the water seal(water level in the condensate trap), prevents the flow of air from theunit ventilator end compartment into the coil section during normaloperation.Improper trapping can lead to several problems. If the trap is too tall,negative pressure will prevent drainage, causing condensate backup.If the trap is too short the seal will be destroyed or nonexistent,producing the same effect as a non-trapped system.The trap should be constructed of 7/8" clear plastic piping. Thecondensate piping from the drain trap must be sloped to facilitateproper drainage. The clear plastic trap should be clamped and removablefor cleaning. It may be necessary to manually fill the trap at systemstart-up, or to run the unit for sufficient time to build a condensate seal.The condensate trap and condensate piping drainage should be free ofany foreign debris. Foreign debris can prevent proper operationresulting in condensate buildup.

A B C

Standard Static Pressure 11/4" 5/8" 23/4"

High Static 11/2" 3/4" 31/8"

Figure 114 - Recommended Condensate Piping

A

C

7/8" I.D. Clear Plastic

B

1/4" Flare by 1/2" MPT Half-Union and 1/4" Flare (by AAF-HermanNelson)

Tee (by Others)

Steam Trap (by Others)

Vacuum Breaker Tube(by AAF-HermanNelson)

Vacuum Breaker(by AAF-HermanNelson) Control Valve: Install on Center

Coil Connection

Figure 116 - Same End Connections - Model AH 68/69 Coils

Steam Supply

Steam Return

Note:Refer to front section of this installation manual for proper considerations on piping, coil connections, electrical, etc.

Table 22 - Condensate Drain Static Pressures

Step 4Make Piping Connections (see AV procedures beginning on page 12)

Page 38: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

38 IM 725 (1-02)

Notes:1. The auxiliary contact of the Remote Speed Switch is closed at “HI” and “LO”

positions and open at “OFF” position.2. Refer to detailed wiring diagram furnished with unit for internal connections.3. Mount remote speed switch in UL listed outlet box. Class 1 Wiring (Both Field

Supplied).4. Remove wire 501 from Unit Ventilator speed switch “SW-2” terminal “T6” in

control box.5. Connect one side of auxiliary contact of the remote speed switch (Blk), to

terminal “T6” of speed switch. Connect the other side of the auxiliary contact(Blk) of the remote speed switch to wire 501.

6. Remove transformer “X1” connections Common (Blk), Hi (Brn), Med (Blu) andLo (Yel) from unit speed switch “SW-2” in Unit Ventilator control box.

7. a. If unit speed switch “SW-2” has Hi, Med and Lo terminals jumpered together,connect Hi speed (Brn Wire) to Hi (Yel Wire) and Lo (Blu Wire) of remote speedswitch. Using field supplied wire nuts cap the blue and yellow wires previouslyremoved from speed switch “SW-2”.

b. If speed switch “SW-2” does not have Hi (Brn), Med (Blu) and Lo (Yel) terminalsjumpered, connect as follows: common (Blk) to red on remote speed switch Hi(Brn) to Hi (Yel) on remote speed switch Lo (Yel) to Lo (Blu) on remote speedswitch. Cap Blue wire with field supplied wire nut.

8. Place label in suitable location for future use.

Figure 117 - Remote Two Speed Control Switch

All WiringClass 1

Motor SpeedTransformerConnected per

Unit Schematic

MBlk

Red

Blk

Red

501

500SW2

6 5

X1

Red

YelBrn

YelBrn

Blu

X1

Blu

Yel

YelBlu

Blk

Red

Blk

Off

LoHi

1

2

Blu

AuxiliaryContact

4 1⁄2" (114mm)

2 3⁄4"

(70mm)

UNIT CONTROL

OFFHI LO

FieldWiringbyOthers

Remote Speed Switch Unit Ventilator Switch Box LocatedIn Right Hand Compartment

6 " (152mm)Long Pigtails

Juction Box(By Others)

Step 5Make Electrical Connections

To avoid electrical shock, personal injury or death, be sure thatfield wiring complies with local and national fire, safety, andelectrical codes, and voltage to the system is within the limitsshown in the job-specific drawings and unit electrical dataplate(s).Power supply to unit must be disconnected when making fieldconnections. To avoid electrical shock, personal injury ordeath, be sure to rigorously adhere to field wiring proceduresregarding proper lockout and tagout of components.

WARNING!

Table 24 - Floor AH Electrical Data/Motor Data and Unit Amp

Unit CFM L/sESP Motor Unit Current #

Series (Nom.) in. H2O PA HP Watts 115V 208V 230V 265V

S07750 354

0.0-0.2 0-50 1/4 164 1.8 1.0 0.9 0.8

H07 0.21-0.45 52.5-112.5 1/2 239 2.0 1.1 1.0 0.9

S101000 472

0.0-0.2 0-50 1/4 244 3.1 1.7 1.5 1.3

H10 0.21-0.45 52.5-112.5 1/2 356 3.4 1.9 1.7 1.5

S131250 590

0.0-0.2 0-50 1/4 306 3.5 1.9 1.8 1.5

H13 0.21-0.45 52.5-112.5 1/2 447 3.8 2.1 1.9 1.7

S151500 708

0.0-0.2 0-50 1/4 334 3.7 2.0 1.8 1.6

H15 0.21-0.45 52.5-112.5 1/2 488 4.0 2.2 2.0 1.7

S202000 944

0.0-0.2 0-50 1/3 249 7.0 3.9 3.5 3.0

H20 0.21-0.45 52.5-112.5 1/2 373 7.6 4.2 3.8 3.3

# Amps at unit voltage, 60 Hz, single phase

Note:Unit wire sizing should be determined in accordance withNEC and local codes.* External static pressure ranges must be strictly

adhered to.

See Table 24, and Figures 82 - 87 and the job-specific electricaldrawings before proceeding with field power and control wiring. Seealso the wiring diagram provided on the unit ventilator right frontaccess panel.In addition, those unit ventilators equipped with optional electricheating coil have electric heating coil power connections at right endonly.

Instructions1. Provide power supply to right end compartment to match unit

nameplate.

2. Wire leads provided from unit ventilator electric connection boxto load side of unit power switch (switch provided by AAF).The junction box has 1"(25mm) and 2"(51mm) knockouts, located10-1/2"(267mm) from right end of unit.

3. Provide ground wire from grounding screw in switch junction boxto switch ground terminal.

4. Wire field power supply to line side of unit power switch. Wireground conductor to switch ground terminal.

5. Mount unit power switch in switch junction box and install switchcover plate (provided).

Note:On units with electric heat, the 2 pole unit power switch is replaced by a 3 pole switchand is mountd as shown in figure 82 page 26. (A) shows switch location for valvecontrol unitrs and (B), (C) and (D) show location for Face & Bypass control units. (B)is for 208, 230 and 265 volt vertical (AV) and horizontal (AH) units. (C) shows locationfor 460 volt vertical (AV) units and (D) shows location for 460 volt horizontal (AH) units.Also, on electric heat units with controls by others, wiring to the field mountedcontroller is done in the left end compartment. See specific wiring diagram for details.

CAUTION!Use copper conductors only. Use of aluminum conductors mayresult in equipment failure and overheating hazards. All wiringin right hand compartment must be class 1.

Page 39: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

IM 725 (1-02) 39

Remove front access panels. Rotate fans manually, all parts should bealigned properly and move freely. Also, inspect fans for obstructions.

Installing Unit Ventilator End Panels:Align each end panel with the top and front edges of the ceiling unitventilator. Attach each end panel to the unit ventilator using thehardware provided.

Run the unit ventilator for ten minutes, listening and observing. Fansshould be operating correctly and rotating in proper direction, withoutunusual noise. Likewise, the unit should be free of sheet metal rattlesand / or unusual noises. All panels should be in place and properlyfastened, and checked for air leaks and condensation.

Step 6Prepare Unit Ventilator(s) for Start-up

Unit Ventilator Warranty Registration Form and Check, Test And Start Procedure

The check, test and start (Warranty Registration, Form 573882Y) must be completely filled out and returned to, AAF-HermanNelson WarrantyDepartment within ten days in order to comply with the terms of the AAF-HermanNelson warranty. Forms should be returned to AAF-HermanNelson Warranty Department, P.O. Box 9030, Auburn, NY 13021-9030.

IMPORTANT!

For trouble free operation, the filter must be cleaned or replaced on aregular basis. Dirty filters result in poor performance. To service filteropen hinged access door with 5/32" hex head wrench. Remove metalplate and change filter. Filters should be checked monthly or more ifconditions indicate.

Complete the check-start list and return to the AAF®-HermanNelson®

representative to start the warranty.

AAF®-HermanNelson® McQuay International will not be responsible for:

1. Shipping Damage2. Normal maintenance.3. Damage or repairs required as a consequence of faulty installation or application by others.4. Failure to start due to voltage conditions, blown fuses, open circuit breakers, or other damages due to the inadequacy or interruption of electrical

service.5. Controls supplied by others and improper operations/hook up of such that impact unit operation or performance.6. Damage or repairs needed as a consequence of any misapplication, abuse, improper servicing, unauthorized alteration, or improper operation.7. Damage as a result of floods, winds, fires, lightning, accidents, corrosive atmosphere, or other conditions beyond the control of AAF®-

HermanNelson® McQuay International .8. Parts not supplied or designated by AAF®-HermanNelson® McQuay International.9. AAF®-HermanNelson® McQuay International product installed outside the United States or Canada.10. Any special, indirect, consequential, property, or commercial damage of any nature whatsoever.

Limitations of WarrantyTHIS WARRANTY IS EXCLUSIVE AND IN LIEU OF IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY AND ALL OTHER WARRANTIES

EXPRESSED OR IMPLIED. THE REMEDIES PROVIDED FOR THIS WARRANTY ARE EXCLUSIVE AND SHALL CONSTITUTE THE ONLY LIABILITIES ON THE PART OF AAF®-HERMANNELSON® MCQUAY INTERNATIONAL.

For service or repair, follow these steps in order:

1. Contact the installing contractor.2. Contact the local AAF®-HermanNelson® McQuay International representative.3. Contact AAF®-HermanNelson® McQuay International directly.

One Year Warranty: This AAF®-HermanNelson® McQuay International product is warranted to be free from defects in material andworkmanship under normal use and maintenance for a period of one year from date of start-up not to exceed 18 months from date of shipment.A new or rebuilt part to replace any defective part will be without charge, provided the defective part is returned to the distributor. The replacementpart assumes the unused portion of the warranty.

This warranty does not include labor or other cost incurred for repairing, removing, installing, shipping, servicing, or handling either defectiveparts or replacement parts.

Model AV/AH – AAF®-HermanNelson® Unit Ventilator Limited Warranty

Page 40: AAF -HermanNelson Classroom Unit VentilatorsIM 725 (1-02) 7 Installing Louvers Typical Installation Methods If the fresh air opening has not yet been made, see figures 5 through 12

©2002 McQuay International • www.mcquay.com • 800-432-1342 IM 725 (1/02)

®

The information in this bulletin supersedes and replaces previous [catalogs][bulletins] with regard to AAF®-HermanNelson® unit ventilator products. Illustrations coverthe general appearance of AAF-HermanNelson unit ventilator products at the time of publication. AAF-HermanNelson reserves the right to make changes in designspecifications and construction at any time without notice.


Recommended