APT-201 10126883 Linear Device ID: Serial Number: Manufacturer Model: Transfer Function: Printed: 06.05.2015 13:17:03 Printed by: ADMIN CMX version: 2.5.144.0 APT-201 Position Name: POSITION 06-May-15 1:12:46 PM Calibration Date: 0.00 Environment Temp.: CrTD/ Plant Structure: Location: ABB 600T EN 624 EA V M More 06-May-15 1:16:45 PM Approved: S Saha, SO/D Calibrated by: 0.00 to 20.00 bar (A) Abs. Pressure Transmitter (APT) Function: 06-May-17 Next Cal. Date: 06-May-15 1:12:46 PM 0.00 % Humidity: CALIBRATION CERTIFICATE Certificate Number: CrTD-017 POSITION ID: APT-201 DEVICE Operating Range: Operating Temp.: Work Order Number: FUNCTION CALIBRATION EVENT Humidity: Calibration Note: 4.00 to 20.00 mA Range (I/O): 1. As Found FAILED Max Error: 0.35 % of span Nominal Input [bar] Actual Input [bar] Nominal Output [mA] Actual Output [mA] Found Error [% of span] 0.000 0.99 4.00 4.812 0.125 5.000 5.01 8.000 8.046 0.238 10.000 10.02 12.000 12.061 0.281 15.000 15.01 16.000 16.055 0.294 20.000 20.01 20.000 20.064 0.350 15.000 15.03 16.000 16.065 0.256 10.000 10.05 12.000 12.077 0.231 5.000 5.03 8.000 8.059 0.219 0.000 0.99 4.00 4.814 0.138 2. As Left PASSED Max Error: 0.05 % of span Nominal Input [bar] Actual Input [bar] Nominal Output [mA] Actual Output [mA] Found Error [% of span] 0.000 0.98 4.00 4.7852 0.0075 5.000 5.02 8.000 8.0078 -0.0513 10.000 10.00 12.000 12.0084 0.0525 15.000 15.00 16.000 16.0000 0.0000 20.000 20.00 20.000 20.0004 0.0025 15.000 15.00 16.000 16.0004 0.0025 10.000 10.00 12.000 12.0053 0.0331 5.000 5.02 8.000 8.0199 0.0244 0.000 0.97 4.00 4.7840 0.0500 Output Module: Output Calibrator: Input Module: Input Calibrator: Classification: 06-May-17 Due Date: Reject if Error >: 0.075 % of span Adjust To <: 0.00 % of span Calibration Strategy: PROCEDURE 2 years Interval: CALIBRATORS MC4 s/n: 40625 Due Date: Due Date: MC4 s/n: 40625 Due Date: Due Date: Page: 1/ 1
Transcript
  • APT-20110126883

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 06.05.2015 13:17:03Printed by: ADMINCMX version: 2.5.144.0

    APT-201Position Name:POSITION

    06-May-15 1:12:46 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More06-May-15 1:16:45 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 20.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:06-May-17Next Cal. Date:

    06-May-15 1:12:46 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-017

    POSITION ID: APT-201DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.35 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.99 4.00 4.812 0.1255.000 5.01 8.000 8.046 0.238

    10.000 10.02 12.000 12.061 0.28115.000 15.01 16.000 16.055 0.29420.000 20.01 20.000 20.064 0.35015.000 15.03 16.000 16.065 0.25610.000 10.05 12.000 12.077 0.2315.000 5.03 8.000 8.059 0.2190.000 0.99 4.00 4.814 0.138

    2. As Left PASSEDMax Error: 0.05 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.98 4.00 4.7852 0.00755.000 5.02 8.000 8.0078 -0.0513

    10.000 10.00 12.000 12.0084 0.052515.000 15.00 16.000 16.0000 0.000020.000 20.00 20.000 20.0004 0.002515.000 15.00 16.000 16.0004 0.002510.000 10.00 12.000 12.0053 0.03315.000 5.02 8.000 8.0199 0.02440.000 0.97 4.00 4.7840 0.0500

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    06-May-17Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2021012686

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 16:02:35Printed by: ADMINCMX version: 2.5.144.0

    APT-202Position Name:POSITION

    12-May-15 3:59:34 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More12-May-15 4:02:27 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 6.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 3:59:34 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-018

    POSITION ID: APT-202DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.53 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]1.00 1.00 6.67 6.648 -0.1171.50 1.50 8.00 8.065 0.4063.00 3.00 12.0 12.075 0.4694.50 4.50 16.0 16.085 0.5316.00 6.00 20.0 20.025 0.1564.50 4.50 16.0 16.085 0.5313.00 3.00 12.0 12.075 0.4691.50 1.50 8.00 8.065 0.4061.00 1.00 6.67 6.648 -0.117

    2. As Left PASSEDMax Error: 0.04 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]1.00 0.99 6.67 6.6413 0.00811.50 1.50 8.00 8.004 0.0253.00 3.00 12.0 12.006 0.0384.50 4.50 16.0 16.002 0.0126.00 6.00 20.0 20.002 0.0124.50 4.50 16.0 16.003 0.0193.00 3.00 12.0 12.005 0.0311.50 1.50 8.00 8.003 0.0191.00 0.99 6.67 6.640 0.000

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    06-May-17Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-203101267

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 13:39:42Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 1:35:35 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T 624 FA

    V M More12-May-15 1:39:29 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 20.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 1:35:35 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-019

    POSITION ID: APT-203DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.34 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.99 4.00 4.8135 0.13445.000 5.000 8.000 8.0338 0.2112

    10.000 10.000 12.000 12.042 0.26215.000 15.000 16.000 16.052 0.32520.000 20.000 20.000 20.008 0.05015.000 15.000 16.000 16.055 0.34410.000 10.000 12.000 12.044 0.2755.000 5.000 8.000 8.041 0.2560.000 0.99 4.00 4.822 0.188

    2. As Left PASSEDMax Error: 0.06 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.98 4.00 4.785 0.0065.000 5.000 8.000 8.009 0.056

    10.000 10.000 12.000 11.999 -0.00615.000 15.000 16.000 16.003 0.01920.000 20.000 20.000 20.001 0.00615.000 15.000 16.000 16.003 0.01910.000 10.000 12.000 11.998 -0.0135.000 5.000 8.000 8.003 0.0190.000 0.98 4.00 4.7850 0.0063

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2041012682

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 16:06:53Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 4:03:52 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T 624 FA

    V M More12-May-15 4:06:50 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 20.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 4:03:52 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-020

    POSITION ID: APT-204DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.52 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.98 4.00 4.8136 0.18505.000 5.00 8.000 8.043 0.269

    10.000 10.00 12.000 12.045 0.28115.000 15.00 16.000 16.082 0.51320.000 20.00 20.000 20.063 0.39415.000 15.00 16.000 16.083 0.51910.000 10.00 12.000 12.045 0.2815.000 5.00 8.000 8.043 0.2690.000 0.98 4.00 4.8136 0.1850

    2. As Left PASSEDMax Error: 0.04 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.000 0.98 4.00 4.784 0.0005.000 5.00 8.000 8.004 0.025

    10.000 10.00 12.000 12.003 0.01915.000 15.00 16.000 16.005 0.03120.000 20.00 20.000 20.004 0.02515.000 15.00 16.000 16.004 0.02510.000 10.00 12.000 12.004 0.0255.000 5.00 8.000 8.006 0.0380.000 0.98 4.00 4.785 0.006

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2051012689

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 14:06:48Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 2:03:49 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More12-May-15 2:06:43 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 6.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 2:03:49 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-021

    POSITION ID: APT-205DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.74 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.00 1.01 4.0 6.7528 0.37171.50 1.50 8.00 8.0177 0.11063.00 3.00 12.0 12.1038 0.64874.50 4.50 16.0 16.1008 0.63006.00 6.00 20.0 20.1184 0.74004.50 4.50 16.0 16.1005 0.62813.00 3.00 12.0 12.1025 0.64061.50 1.50 8.00 8.0156 0.09750.00 1.01 4.0 6.7528 0.3717

    2. As Left PASSEDMax Error: 0.00 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.00 1.00 4.0 6.6667 0.00021.50 1.50 8.00 8.0002 0.00123.00 3.00 12.0 12.0001 0.00064.50 4.50 16.0 16.0002 0.00126.00 6.00 20.0 20.0002 0.00124.50 4.50 16.0 16.0002 0.00123.00 3.00 12.0 12.0001 0.00061.50 1.50 8.00 8.0001 0.00060.00 1.00 4.0 6.6667 0.0002

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2061012679

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 14:25:08Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 2:09:53 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More12-May-15 2:24:49 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 6.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 2:09:53 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-022

    POSITION ID: APT-206DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.18 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.00 1.00 4.0 6.6762 0.05961.50 1.50 8.00 8.007 0.0443.00 3.00 12.0 12.013 0.0814.50 4.50 16.0 16.022 0.1376.00 6.00 20.0 20.028 0.1754.50 4.50 16.0 16.023 0.1443.00 3.00 12.0 12.014 0.0871.50 1.50 8.00 8.005 0.0310.00 1.00 4.0 6.6862 0.1221

    2. As Left PASSEDMax Error: 0.00 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.00 1.00 4.0 6.6669 0.00151.50 1.50 8.00 8.0001 0.00063.00 3.00 12.0 12.0001 0.00064.50 4.50 16.0 16.0002 0.00126.00 6.00 20.0 20.0003 0.00194.50 4.50 16.0 16.0004 0.00253.00 3.00 12.0 12.0001 0.00061.50 1.50 8.00 8.0001 0.00060.00 1.00 4.0 6.6668 0.0008

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2071012688

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 14:19:23Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 2:17:08 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More12-May-15 2:19:17 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 6.00 bar (A)

    Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 2:17:08 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-023

    POSITION ID: APT-207DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: -0.12 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]1.00 1.00 6.67 6.6845 0.11151.50 1.50 8.00 7.9822 -0.11133.00 3.00 12.0 11.9828 -0.10754.50 4.50 16.0 15.9811 -0.11816.00 6.00 20.0 19.9822 -0.11134.50 4.50 16.0 15.9854 -0.09123.00 3.00 12.0 11.9825 -0.10941.50 1.50 8.00 7.9823 -0.11061.00 1.00 6.67 6.6844 0.1108

    2. As Left PASSEDMax Error: 0.01 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]1.00 1.00 6.67 6.6678 0.00711.50 1.50 8.00 7.9994 -0.00383.00 3.00 12.0 11.9993 -0.00444.50 4.50 16.0 15.9998 -0.00126.00 6.00 20.0 20.0003 0.00194.50 4.50 16.0 15.9997 -0.00193.00 3.00 12.0 11.9994 -0.00381.50 1.50 8.00 7.9999 -0.00061.00 1.00 6.67 6.6679 0.0077

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To

  • APT-2081012687

    Linear

    Device ID:Serial Number:Manufacturer Model:

    Transfer Function:

    Printed: 12.05.2015 15:58:16Printed by: ADMINCMX version: 2.5.144.0

    Position Name:POSITION

    12-May-15 3:56:06 PMCalibration Date:

    0.00Environment Temp.:

    CrTD/Plant Structure:Location: ABB 600T EN 624 EA

    V M More12-May-15 3:58:05 PM

    Approved: S Saha, SO/DCalibrated by:

    0.00 to 6.00 bar (A)

    Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:

    12-May-15 3:56:06 PM

    0.00 %Humidity:

    CALIBRATION CERTIFICATECertificate Number: CrTD-024

    POSITION ID: APT-208DEVICE

    Operating Range:Operating Temp.:

    Work Order Number:

    FUNCTION CALIBRATION EVENTHumidity:

    Calibration Note:

    4.00 to 20.00 mARange (I/O):

    1. As Found FAILEDMax Error: 0.84 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.98 0.98 6.6 6.663 0.3101.50 1.50 8.00 8.068 0.4253.00 3.00 12.0 12.135 0.8444.50 4.50 16.0 16.132 0.8256.00 6.00 20.0 20.083 0.5194.50 4.50 16.0 16.132 0.8253.00 3.00 12.0 12.135 0.8441.50 1.50 8.00 8.068 0.4250.98 0.98 6.6 6.665 0.323

    2. As Left PASSEDMax Error: 0.03 % of span

    NominalInput[bar]

    ActualInput[bar]

    NominalOutput[mA]

    ActualOutput[mA]

    FoundError

    [% of span]0.98 0.98 6.6 6.6176 0.02671.50 1.50 8.00 7.9999 -0.00063.00 3.00 12.0 12.0031 0.01944.50 4.50 16.0 16.0024 0.01506.00 6.00 20.0 20.0021 0.01314.50 4.50 16.0 16.0021 0.01313.00 3.00 12.0 12.0003 0.00191.50 1.50 8.00 8.0010 0.00620.98 0.98 6.6 6.6180 0.0292

    Output Module:Output Calibrator:Input Module:Input Calibrator:

    Classification:

    Due Date:Reject if Error >: 0.075 % of span Adjust To


Recommended