Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 06.05.2015 13:17:03Printed by: ADMINCMX version: 2.5.144.0
APT-201Position Name:POSITION
06-May-15 1:12:46 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More06-May-15 1:16:45 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 20.00 bar (A)
Abs. Pressure Transmitter (APT)Function:06-May-17Next Cal. Date:
06-May-15 1:12:46 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-017
POSITION ID: APT-201DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.35 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.99 4.00 4.812 0.1255.000 5.01 8.000 8.046 0.238
10.000 10.02 12.000 12.061 0.28115.000 15.01 16.000 16.055 0.29420.000 20.01 20.000 20.064 0.35015.000 15.03 16.000 16.065 0.25610.000 10.05 12.000 12.077 0.2315.000 5.03 8.000 8.059 0.2190.000 0.99 4.00 4.814 0.138
2. As Left PASSEDMax Error: 0.05 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.98 4.00 4.7852 0.00755.000 5.02 8.000 8.0078 -0.0513
10.000 10.00 12.000 12.0084 0.052515.000 15.00 16.000 16.0000 0.000020.000 20.00 20.000 20.0004 0.002515.000 15.00 16.000 16.0004 0.002510.000 10.00 12.000 12.0053 0.03315.000 5.02 8.000 8.0199 0.02440.000 0.97 4.00 4.7840 0.0500
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
06-May-17Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2021012686
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 16:02:35Printed by: ADMINCMX version: 2.5.144.0
APT-202Position Name:POSITION
12-May-15 3:59:34 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More12-May-15 4:02:27 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 6.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 3:59:34 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-018
POSITION ID: APT-202DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.53 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]1.00 1.00 6.67 6.648 -0.1171.50 1.50 8.00 8.065 0.4063.00 3.00 12.0 12.075 0.4694.50 4.50 16.0 16.085 0.5316.00 6.00 20.0 20.025 0.1564.50 4.50 16.0 16.085 0.5313.00 3.00 12.0 12.075 0.4691.50 1.50 8.00 8.065 0.4061.00 1.00 6.67 6.648 -0.117
2. As Left PASSEDMax Error: 0.04 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]1.00 0.99 6.67 6.6413 0.00811.50 1.50 8.00 8.004 0.0253.00 3.00 12.0 12.006 0.0384.50 4.50 16.0 16.002 0.0126.00 6.00 20.0 20.002 0.0124.50 4.50 16.0 16.003 0.0193.00 3.00 12.0 12.005 0.0311.50 1.50 8.00 8.003 0.0191.00 0.99 6.67 6.640 0.000
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
06-May-17Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-203101267
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 13:39:42Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 1:35:35 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T 624 FA
V M More12-May-15 1:39:29 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 20.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 1:35:35 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-019
POSITION ID: APT-203DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.34 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.99 4.00 4.8135 0.13445.000 5.000 8.000 8.0338 0.2112
10.000 10.000 12.000 12.042 0.26215.000 15.000 16.000 16.052 0.32520.000 20.000 20.000 20.008 0.05015.000 15.000 16.000 16.055 0.34410.000 10.000 12.000 12.044 0.2755.000 5.000 8.000 8.041 0.2560.000 0.99 4.00 4.822 0.188
2. As Left PASSEDMax Error: 0.06 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.98 4.00 4.785 0.0065.000 5.000 8.000 8.009 0.056
10.000 10.000 12.000 11.999 -0.00615.000 15.000 16.000 16.003 0.01920.000 20.000 20.000 20.001 0.00615.000 15.000 16.000 16.003 0.01910.000 10.000 12.000 11.998 -0.0135.000 5.000 8.000 8.003 0.0190.000 0.98 4.00 4.7850 0.0063
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2041012682
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 16:06:53Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 4:03:52 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T 624 FA
V M More12-May-15 4:06:50 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 20.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 4:03:52 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-020
POSITION ID: APT-204DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.52 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.98 4.00 4.8136 0.18505.000 5.00 8.000 8.043 0.269
10.000 10.00 12.000 12.045 0.28115.000 15.00 16.000 16.082 0.51320.000 20.00 20.000 20.063 0.39415.000 15.00 16.000 16.083 0.51910.000 10.00 12.000 12.045 0.2815.000 5.00 8.000 8.043 0.2690.000 0.98 4.00 4.8136 0.1850
2. As Left PASSEDMax Error: 0.04 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.000 0.98 4.00 4.784 0.0005.000 5.00 8.000 8.004 0.025
10.000 10.00 12.000 12.003 0.01915.000 15.00 16.000 16.005 0.03120.000 20.00 20.000 20.004 0.02515.000 15.00 16.000 16.004 0.02510.000 10.00 12.000 12.004 0.0255.000 5.00 8.000 8.006 0.0380.000 0.98 4.00 4.785 0.006
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2051012689
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 14:06:48Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 2:03:49 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More12-May-15 2:06:43 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 6.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 2:03:49 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-021
POSITION ID: APT-205DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.74 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.00 1.01 4.0 6.7528 0.37171.50 1.50 8.00 8.0177 0.11063.00 3.00 12.0 12.1038 0.64874.50 4.50 16.0 16.1008 0.63006.00 6.00 20.0 20.1184 0.74004.50 4.50 16.0 16.1005 0.62813.00 3.00 12.0 12.1025 0.64061.50 1.50 8.00 8.0156 0.09750.00 1.01 4.0 6.7528 0.3717
2. As Left PASSEDMax Error: 0.00 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.00 1.00 4.0 6.6667 0.00021.50 1.50 8.00 8.0002 0.00123.00 3.00 12.0 12.0001 0.00064.50 4.50 16.0 16.0002 0.00126.00 6.00 20.0 20.0002 0.00124.50 4.50 16.0 16.0002 0.00123.00 3.00 12.0 12.0001 0.00061.50 1.50 8.00 8.0001 0.00060.00 1.00 4.0 6.6667 0.0002
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2061012679
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 14:25:08Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 2:09:53 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More12-May-15 2:24:49 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 6.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 2:09:53 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-022
POSITION ID: APT-206DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.18 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.00 1.00 4.0 6.6762 0.05961.50 1.50 8.00 8.007 0.0443.00 3.00 12.0 12.013 0.0814.50 4.50 16.0 16.022 0.1376.00 6.00 20.0 20.028 0.1754.50 4.50 16.0 16.023 0.1443.00 3.00 12.0 12.014 0.0871.50 1.50 8.00 8.005 0.0310.00 1.00 4.0 6.6862 0.1221
2. As Left PASSEDMax Error: 0.00 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.00 1.00 4.0 6.6669 0.00151.50 1.50 8.00 8.0001 0.00063.00 3.00 12.0 12.0001 0.00064.50 4.50 16.0 16.0002 0.00126.00 6.00 20.0 20.0003 0.00194.50 4.50 16.0 16.0004 0.00253.00 3.00 12.0 12.0001 0.00061.50 1.50 8.00 8.0001 0.00060.00 1.00 4.0 6.6668 0.0008
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2071012688
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 14:19:23Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 2:17:08 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More12-May-15 2:19:17 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 6.00 bar (A)
Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 2:17:08 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-023
POSITION ID: APT-207DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: -0.12 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]1.00 1.00 6.67 6.6845 0.11151.50 1.50 8.00 7.9822 -0.11133.00 3.00 12.0 11.9828 -0.10754.50 4.50 16.0 15.9811 -0.11816.00 6.00 20.0 19.9822 -0.11134.50 4.50 16.0 15.9854 -0.09123.00 3.00 12.0 11.9825 -0.10941.50 1.50 8.00 7.9823 -0.11061.00 1.00 6.67 6.6844 0.1108
2. As Left PASSEDMax Error: 0.01 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]1.00 1.00 6.67 6.6678 0.00711.50 1.50 8.00 7.9994 -0.00383.00 3.00 12.0 11.9993 -0.00444.50 4.50 16.0 15.9998 -0.00126.00 6.00 20.0 20.0003 0.00194.50 4.50 16.0 15.9997 -0.00193.00 3.00 12.0 11.9994 -0.00381.50 1.50 8.00 7.9999 -0.00061.00 1.00 6.67 6.6679 0.0077
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To
APT-2081012687
Linear
Device ID:Serial Number:Manufacturer Model:
Transfer Function:
Printed: 12.05.2015 15:58:16Printed by: ADMINCMX version: 2.5.144.0
Position Name:POSITION
12-May-15 3:56:06 PMCalibration Date:
0.00Environment Temp.:
CrTD/Plant Structure:Location: ABB 600T EN 624 EA
V M More12-May-15 3:58:05 PM
Approved: S Saha, SO/DCalibrated by:
0.00 to 6.00 bar (A)
Abs. Pressure Transmitter (APT)Function:12-May-17Next Cal. Date:
12-May-15 3:56:06 PM
0.00 %Humidity:
CALIBRATION CERTIFICATECertificate Number: CrTD-024
POSITION ID: APT-208DEVICE
Operating Range:Operating Temp.:
Work Order Number:
FUNCTION CALIBRATION EVENTHumidity:
Calibration Note:
4.00 to 20.00 mARange (I/O):
1. As Found FAILEDMax Error: 0.84 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.98 0.98 6.6 6.663 0.3101.50 1.50 8.00 8.068 0.4253.00 3.00 12.0 12.135 0.8444.50 4.50 16.0 16.132 0.8256.00 6.00 20.0 20.083 0.5194.50 4.50 16.0 16.132 0.8253.00 3.00 12.0 12.135 0.8441.50 1.50 8.00 8.068 0.4250.98 0.98 6.6 6.665 0.323
2. As Left PASSEDMax Error: 0.03 % of span
NominalInput[bar]
ActualInput[bar]
NominalOutput[mA]
ActualOutput[mA]
FoundError
[% of span]0.98 0.98 6.6 6.6176 0.02671.50 1.50 8.00 7.9999 -0.00063.00 3.00 12.0 12.0031 0.01944.50 4.50 16.0 16.0024 0.01506.00 6.00 20.0 20.0021 0.01314.50 4.50 16.0 16.0021 0.01313.00 3.00 12.0 12.0003 0.00191.50 1.50 8.00 8.0010 0.00620.98 0.98 6.6 6.6180 0.0292
Output Module:Output Calibrator:Input Module:Input Calibrator:
Classification:
Due Date:Reject if Error >: 0.075 % of span Adjust To