FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
1 of 19
FACTORY ACCEPTANCE TEST
TESTING PROCEDURE
FOR
22 KV HT
SWITCHGEAR
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
2 of 19
AGENDA
Project Name : Amara Hotel Upgrading Project Project No. : SG-46011513 Customer : Kurihara Kogyo Co. Ltd FAT Date : 28 Mar 2012 (14:00 hrs) Location of FAT : ABB Pte Ltd No.2 Ayer Rajah Crescent Singapore 139935 Tentative Testing Schedule 14:00AM – 16:00PM : Testing of IC, and Bus Section Feeders 16:00PM – 16:30PM : Testing on Transformer Feeder 16:30PM _ 17:00PM : Summary of tests carried out and signing off of all test reports
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
3 of 19
FAT Procedure - Table of Contents
Visual Inspection…………………………………………………………………………...4
Function Test ………………………………………………………………………….…...4
Primary Injection Test on CT’s Ratio & Polarity .................................................................5
Secondary Injection Test.......................................................................................................8
Secondary Injection for Pilot Wire Relay Operation Check.................................................9
Figures
Figure 1: Circuit Diagram for CT Ratio & Polarity Check ..................................................6
Figure 2: Circuit Diagram for CT Ratio & Polarity Check ................................................. 6
Figure 3: Circuit Diagram for CT Ratio & Polarity Check ..................................................7
Figure 4: Circuit Diagram for CT Ratio & Polarity Check ..................................................7
Figure 5: Circuit Diagram for Relay Test ............................................................................8
Figure 6: Circuit Diagram for Solkor Relay Test ……........................................................9
Test Form & customer signed-off Form
Form1: Visual Inspection Test …………………………………………………………...10
Form 2: Electrical / Mechanical Function Test …………………………………………..11
Form 3: Primary Injection Test on CT (PI) / Voltmeter Ratio Test ………………………13
Form 4: Overcurrent & Earth Fault Relay Operation Test (SI)…………………………..15
Form 5: Pilot Wire Protection Operation Test …………………………………………...16
Form 6: Attendance List………………... ……………………………………………….17
Form 7: Customer comment & signed off ……………………………………………….18
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
4 of 19
Visual inspection
Panel Arrangement
Built In Equipment
Check Finishing Paint Work
Rating and Equipment Identification Labels
Check Mimic Diagram
Function Test
OC/EF & Pilot Wire Protection Trip
T/F Alarm/trip
Electrical/Mechanical Interlock
CB on/off
Disconnector/Earthing switch on/off operation
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
5 of 19
Primary Injection Test on CT’s Ratio & Polarity
1. Ensure that the switchgear has been de-energized.
2. Note down the particulars of the switchgear and CT’s.
3. Do not remove any wires, use the provided test plugs if applicable or use
clamp meters.
4. Measure the CT’s secondary phases and spill current using a clamp meter.
5. Select all meters to ampere range.
6. Inject a current of 10 to 20A onto the brown and black phases. Check the spill current,
it should be as low as milli-ampere. If the spill current is high, check for CT’s terminal
tightness or any mistake on the wiring.
7. Reduce to zero and off the supply, change the spill current meter (A4) to milliampere
range.
8. Inject a current of 50% and 100% of the CT primary current on brown (L1) and black
(L2) phases. Record the reading.
9. Reduce to zero and off the supply.
10. Repeat item 6 to 8 for black (L2) and grey (L3) phases.
11. Repeat item 6 to 8 for brown (L1) and grey (L3) phases.
12. Select all meters to ampere range.
13. Inject a current of 10 to 20A onto black phases (L2) to earth. Check the spill current
(A4). It should be the same current as the phase current (A2).
14. Inject a current of 50% and 100% of the CT primary current on black (L2) phase to
earth. Record the reading.
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
6 of 19
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
7 of 19
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
8 of 19
Secondary Injection Test 1. Ensure that the switchgear is de-energized.
2. Note down the relay particulars on test form.
3. Check or record the setting of the relay.
4. Increase the current gradually until the relay pick up. Record the reading.
5. Set a current of two times of the plug setting and off the injection set.
6. Press the start button of the injection set and record the tripping time as shown on the
test equipment.
7. Repeat item 5 to 6 for three and five times of the plug setting.
8. Repeat item 5 to 7 for black (L2) and grey (L3) element.
9. Repeat item 4 to 7 for earth element.
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
9 of 19
Secondary Injection for Pilot Wire Relay Operation Check
1. Ensure that the switchgear is de-energized and PTW is issued.
2. Remove the relay from the casing and check the relay connection. It is either
Solkor R or Solkor Rf mode. Typically it is used at Solkor R mode. Change the
connection accordingly to your application.
3. Connect the circuit on Brown (L1) and neutral phase as shown on the diagram.
4. Increase the current gradually until relay pick up. Record reading A1, A2, A3 and A4
on the test form
5. Increase the current furthermore until the dummy relay pick up.
6. Record reading A1 on the test form.
7. Repeat step 3 to 5 for Black-E, grey-E, Brown-Black, Black-Grey and Grey-brown.
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
10 of 19
FAT Test Form
1. VISUAL INSPECTION TickBox / Remark
Panel Arrangement
Built In Equipment
Check Finishing Paint Work
Rating and Equipment Identification Labels
Check Mimic Diagram (if any)
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : _________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
11 of 19
2. ELECTRICAL / MECHANICAL FUNCTION TEST
TickBox / Remark
Local CB Close Operation
Local CB Open Operation
Remote CB Close Operation
Remote CB Open Operation
Local / Remote CB “OFF” Indication
Local / Remote CB “ON” Indication
Disconnector switch Close Operation (GIS)
Disconnector switch Open Operation (GIS)
Earthing switch Close Operation, if any
Earthing switch Open Operation, if any
Electrical Interlock Operation
Mechanical interlock
Earthing switch mechanism
Circuit Breaker mechanism
3-way switch mechanism (GIS)
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
12 of 19
OCEF Trip REF Trip, if any
PW Trip, if any
T/F Temperature Trip/Alarm, if any
T/F Pressure Trip/Alarm, if any
T/F Low Oil Trip/Alarm, if any
T/F Winding Temp Trip/Alarm, if any
T/F Door Open Trip/Alarm, if any
Intertrip receive, if any
Intertrip send, if any
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : _________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
13 of 19
3. PRIMARY INJECTION TEST ON CT/VOLTMETER RATIO TEST
CT Data
CT Ratio:__________ CT Class: _____________ VA / Vkp:__________________
CT Serial No
L1: ___________________ L2: _______________ L3 : _______________
Panel No. ___________
Primary
Connectio
n
Primary
Injectio
n
Current
(A)
CT Ratio Spill
Current
(<50mA
)
Primary Primary
Injection
Current
(A)
CT Ratio Spill
Current
(<50mA) L1 L2 L3
Connectio
n L1 L2 L3
L1L2 2.5 2.5
L1L2 2.5 2.5
5.0 5.0 5.0 5.0
L2L3 2.5 2.5
L2L3 2.5 2.5
5.0 5.0 5.0 5.0
L3L1 2.5 2.5
L3L1 2.5 2.5
5.0 5.0 5.0 5.0
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________
Date : : __________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
14 of 19
AMMETER CALIBRATION CURRENT TRANSDUCER
I/P O/P
Primary Current (A) NA NA NA L1 NA A NA mA
Meter Reading (A) NA NA NA L2 NA A NA mA
PT S / NO. L1: NA L3 NA A NA mA
L2 : NA
L3 : NA CURRENT / VOLTAGE TRANSDUCER
I/P
O/P
P.T. VOLTMETER RATIO TEST
L1 NA
A / V
NA mA
Primary Voltage ( kV ) L2 NA A / V NA mA
Meter Reading ( kV ) L3 NA
A / V NA mA
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : _________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
15 of 19
4. OVECURRENT AND EARTH FAULT RELAY OPERATION TEST (I/C)
Particular of Relays:
Make
Type Tripping
Characteristics
Rating
S/No
O/C Relay
E/F Relay
Test Results of HT Installation: Panel No / Circuit Name: /
O/C Relay
E/F Relay
Plug
Setting A
Sec
Cur, A
Operation Time, sec
Plug
SettingA
Sec
Cur, A
Opn
Time, sec
TM
Setting
Std
Time, sec
L1
L2
L3
2.5
5.0
5.0
25
10
10
1.0
2.0
1.0
10
4
2
1.0
1.0
0.1
Plug Setting, A
Starting Current, A
Plug
Setting A
Starting
Current, A
L1
L2
L
2.5 5.0
1.0
2.0
High Set, A
Operating Current, A
High Set, A
Operating Current, A
L1
L2
L3
30
15
Secondary Wiring Insulation Resistance: M
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : __________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
16 of 19
4. OVECURRENT AND EARTH FAULT RELAY OPERATION TEST (T/F)
Particular of Relays:
Make
Type Tripping
Characteristics
Rating
S/No
O/C Relay
E/F Relay
Test Results of HT Installation: Panel No / Circuit Name: /
O/C Relay
E/F Relay
Plug
Setting A
Sec
Cur, A
Operation Time, sec
Plug
SettingA
Sec
Cur, A
Opn
Time, sec
TM
Setting
Std
Time, sec
L1
L2
L3
0.5
1.0
1.0
5
2
2
1.0
2.0
1.0
10
4
2
1.0
1.0
0.1
Plug Setting, A
Starting Current, A
Plug
Setting A
Starting
Current, A
L1
L2
L
0.5 1.0
1.0
2.0
High Set, A
Operating Current, A
High Set, A
Operating Current, A
L1
L2
L3
6
3
Secondary Wiring Insulation Resistance: M
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : __________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
17 of 19
5. PILOT WIRE PROTECTION RELAY OPERATION TEST Particulars of Relays: Test Relay Make: Reyrolle Type: Rolkor R S/No.:___________
Dummy Relay Make: Reyrolle Type: Rolkor R S/No.:___________
Panel No. _________ Test Mode : ____________________________
Test Result
Relay Operating Coil Current Pilot Wire Secondary Operating
Current Amp D.C. mA Current
Test Relay Dummy Relay
Test Relay Dummy Relay AC mA
L1 - E
L2 - E
L3 - E
L1 - L2
L2 - L3
L3 - L1
Tested By (Name & Signature) : __________________________________________ Witnessed By (Name & Signature) : __________________________________________ Date : : __________________________________________
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
18 of 19
6. Attendance List
PROJECT: __________________________ FAT DATE:__________________________
NAME DESIGNATION COMPANY INITIAL
FACTORY ACCEPTANCE TEST
(HT SWITCHGEAR) AMARA HOTEL UPGRADING Project
Date: 28 Mar 2012 Rev.:0
19 of 19
7. Customer comment & signed-off Form Remarks :
Tested By : 1. ________________________________________ (ABB Pte Ltd) Witnessed By : 1. ________________________________________
(Kurira Kogyo Co. Ltd) : 2. ________________________________________
: 3. ________________________________________