8
ABB industrial drives EMC filter disconnecting instructions ACS880-01 drives (+E200, +E202) (0.55 to 250 kW, 0.75 to 350 hp)
Transcript
Page 1: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

ABB industrial drives

EMC filter disconnecting instructionsACS880-01 drives (+E200, +E202)(0.55 to 250 kW, 0.75 to 350 hp)

Page 2: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

List of related manuals

You can find manuals and other product documents in PDF format on the Internet. See section Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative.The QR code below opens an online listing of the manuals applicable to this product.

Drive hardware manuals and guides Code (English)ACS880-01 hardware manual 3AUA0000078093ACS880-01 quick installation guide for frames R1 to R3 3AUA0000085966ACS880-01 quick installation guide for frames R4 and R5 3AUA0000099663ACS880-01 quick installation guide for frames R6 to R9 3AUA0000099689ACS880-01 assembly drawing for cable entry boxes of IP21 frames R5 to R9

3AUA0000119627

ACS-AP assistant control panels user’s manual 3AUA0000085685

Drive firmware manuals and guidesACS880 primary control program firmware manual 3AUA0000085967Quick start-up guide for ACS880 drives with primary control program

3AUA0000098062

Option manuals and quidesManuals and quick guides for I/O extension modules, fieldbus adapters, etc.

3AUA0000125152 Rev AEN

EFFECTIVE: 2012-06-29

© 2012 ABB Oy. All Rights Reserved.

Page 3: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

EMC filter disconnecting instructions 3

EMC filter disconnecting instructions

What this manual containsThis manual gives instructions on how to disconnect drive EMC filters +E200 and +E202.

Electrical safetyThese warnings are intended for all who work on the drive, motor cable or motor.

WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment:

• Only qualified electricians are allowed to install and maintain the drive.

• Never work on the drive, motor cable or motor when main power is applied. After disconnecting the input power, always wait for 5 minutes to let the intermediate circuit capacitors discharge before you start working on the drive, motor or motor cable.

Always ensure by measuring with a multimeter (impedance at least 1 Mohm) that:• voltage between drive input phases L1, L2 and L3 and the frame is close

to 0 V• voltage between terminals UDC+ and UDC- and the frame is close to 0 V.

• Do not work on the control cables when power is applied to the drive or to the external control circuits. Externally supplied control circuits may cause dangerous voltages inside the drive even when the main power on the drive is switched off.

Page 4: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

4 EMC filter disconnecting instructions

Compatibility with IT (ungrounded) systemsEMC filters +E200 and +E202 are not suitable for use in an IT (ungrounded) system. If the drive is equipped with filter +E200 or +E202, disconnect the filter before connecting the drive to the supply network.

WARNING! If a drive with EMC filter +E200 or +E202 is installed on an IT system (an ungrounded power system or a high resistance-grounded [over 30

ohm] power system), the system will be connected to earth potential through the EMC filter capacitors of the drive. This may cause danger, or damage the unit.

Disconnecting the EMC filter of frames R1 to R3

Undo the EMC AC and EMC DC screws.

Disconnecting the EMC filter of frame R4

Please, contact ABB for instructions.

Page 5: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

EMC filter disconnecting instructions 5

Disconnecting the EMC filter of frame R5

Undo the EMC AC and EMC DC screws.

Page 6: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

6 EMC filter disconnecting instructions

Disconnecting the EMC filter of frames R6 to R9

Undo the EMC AC and EMC DC screws.

Page 7: ABB industrial drives EMC filter disconnecting instructions ...Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable

Further information

Product and service inquiriesAddress any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives and selecting Sales, Support and Service network.

Product trainingFor information on ABB product training, navigate to www.abb.com/drives and select Training courses.

Providing feedback on ABB Drives manualsYour comments on our manuals are welcome. Go to www.abb.com/drives and select Document Library – Manuals feedback form (LV AC drives).