ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

Date post: 17-Apr-2022
Category:
Upload: others
View: 27 times
Download: 0 times
Share this document with a friend
12
AMS TIGHT SHUT - OFF VALVE V T ACV 2 - WAY ACV 3 - WAY CAP - PIPE CHECK VALVE COMBINATION BALANCING, FLOW MEASURING & FLOAT & THERMOSTATIC TRAP ISOLATION VALVE GLOBE VALVE LOCKSHIELD GATE VALVE MANUAL AIR VENT OS&Y GATE VALVE PETCOCK FOR GAUGE CONNECTION PIPE ANCHOR PIPE GUIDE PLUG VALVE PRESSURE GAUGE PRESSURE REDUCING VALVE PRESSURE RELIEF VALVE STRAINER TAKE - OFF FROM BOTTOM OF PIPE TAKE - OFF FROM TOP OF PIPE THERMOMETER THERMOMETER WELL THERMOSTATIC TRAP UNION DESCRIPTION SYMBOL EXISTING SUPPLY PIPING TO REMAIN EXISTING RETURN PIPING TO REMAIN NEW SUPPLY PIPING NEW RETURN PIPING PIPE DOWN PIPE UP DIFFERENTIAL PRESSURE SENSOR DPS INVERTED BUCKET TRAP PIPING LEGEND REDUCER - CONCENTRIC REDUCER - ECCENTRIC 10'-0" FL 1.2 GPM RADIATION I.D. ( TYPE A, 10' - 0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITH DAMPER A 10'-0" FL/D 1.2 GPM A RADIATION I.D. ( TYPE A, 10' - 0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITHOUT DAMPER BUTTERFLY VALVE FD (3 HR) FIRE DAMPER (3 HOUR RATED) FIRE DAMPER (1 1/2 HOUR RATED) BD V ACOUSTICALLY LINED DUCT BACKDRAFT DAMPER DUCT SECTION - SUPPLY/OUTDOOR AIR DUCT SECTION - RETURN AIR DUCT TURNING VANES FLEXIBLE DUCT LOUVER MOTORIZED DAMPER PRESSURE RELIEF DAMPER RETURN OR EXHAUST AIR SMOKE DAMPER STRAINER SUPPLY OR OUTSIDE AIR VOLUME DAMPER SPIRAL DUCT DIAMETER CB COUNTERBALANCED DAMPER DESCRIPTION SYMBOL S PRD M F AIRFLOW MEASURING STATION DUCT MOUNTED SMOKE DETECTOR SD EXISTING DUCTWORK TO REMAIN NEW DUCTWORK DUCT SECTION - EXHAUST AIR STATIC PRESSURE SENSOR SPS Ø FIRE AND SMOKE DAMPER (1 1/2 HOUR RATED) F/S DUCTWORK LEGEND S2 4 400 SUPPLY DIFFUSER ( TYPE 2 ) 400 CFM EA DIFFUSER DESCRIPTION QUANTITY ( SEE REG., GRILLES & DIFF SCHEDULE ) S (SUPPLY) R (RETURN) E (EXHAUST) T (TRANSFER) H HS HUMIDISTAT HUMIDITY SENSOR TEMPERATURE SENSOR THERMOSTAT THERMOSTAT COOLING THERMOSTAT HEATING THERMOSTAT - NIGHT THERMOSTAT - HEATING/COOLING T TS T C H N H/C T T T DESCRIPTION SYMBOL CONTROLS LEGEND A M10.1 SECTION I.D. ( SECTION A SHOWN ON DWG. M10.1) DESCRIPTION SYMBOL EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COMPLETELY REMOVE EQUIPMENT, DUCTWORK, OR PIPING GENERIC LEGEND CONNECT NEW TO EXISTING Key Plan Harriman Project No. PA / PE: Drawn By: Harriman Associates c Proj North Revision Description Rev Date May 17, 2021 GORHAM, MAINE 20478 M00-1 DWS ASG LEGEND & GENERAL NOTES 2021 UNIVERSITY OF SOUTHERN MAINE HILL GYMNASIUM ATHLETIC TRAINING RENOVATIONS ABBREV DESCRIPTION IN INCHES LAT LEAVING AIR TEMPERATURE LPCR LOW PRESSURE CONDENSATE RETURN (LESS THAN 15 PSI) LPS LOW PRESSURE STEAM(LESS THAN 15 PSI) LRA LOCKED ROTOR AMPS LSGV LOCK & SHIELD GATE VALVE LWT LEAVING WATER TEMPERATURE M MOTORIZED DAMPER MAX MAXIMUM MBH 1000 BRITISH THERMAL UNITS MCA MINIMUM CIRCUIT AMPS MIN MINIMUM MOPD MAXIMUM OVERCURRENT PROTECTIVE DEVICE MPCR MEDIUM PRESSURE CONDENSATE RETURN(16-30 PSIG) MPS MEDIUM PRESSURE STEAM (16-30 PSIG) NA NOT APPLICABLE NC NOISE CRITERIA NIC NOT IN CONTRACT NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR OC ON CENTER OED OPEN END DUCT OS&Y OUTSIDE SCREW & YOKE GATE VALVE PD PRESSURE DROP PRD PRESSURE RELIEF DAMPER PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE RET RETURN RL REFRIGERANT LIQUID RLA RATED LOAD AMPERES RPM REVOLUTIONS PER MINUTE RS REFRIGERANT SUCTION S SMOKE DAMPER SP STATIC PRESSURE SS STAINLESS STEEL SUP SUPPLY TEMP TEMPERATURE TT THERMOSTATIC TRAP TYP TYPICAL V VOLUME DAMPER VFD VARIABLE FREQUENCY DRIVE W/ WITH W/O WITHOUT WC WATER COLUMN WG WATER GAUGE WMS WELDED WIRE MESH SCREEN WPD WATER PRESSURE DROP Z ZONE DAMPER PREFIX OF X EXISTING ABBREV DESCRIPTION ACV AUTOMATIC CONTROL VALVE AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ALD ACOUSTICAL LINED DUCT AMS AIRFLOW MEASURING STATION APD AIR PRESSURE DROP ATC AUTOMATIC TEMPERATURE CONTROL B BAROMETRIC DAMPER BD BACKDRAFT DAMPER BHP BRAKE HORSEPOWER BPD BYPASS DAMPER BTU BRITISH THERMAL UNITS CBD COUNTERBALANCED BACKDRAFT DAMPER CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CO CLEANOUT CTE CONNECT TO EXISTING CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY DCW DOMESTIC COLD WATER DEG.F DEGREES FAHRENHEIT DHW DOMESTIC HOT WATER DIA DIAMETER DN DOWN DTR DUAL TEMPERATURE RETURN DTS DUAL TEMPERATURE SUPPLY EAT ENTERING AIR TEMPERATURE ESP EXTERNAL STATIC PRESSURE EWT ENTERING WATER TEMPERATURE EXG EXISTING EXH EXHAUST F&T FLOAT & THERMOSTATIC TRAP F/S FIRE AND SMOKE COMBINATION DAMPER FC FLEXIBLE CONNECTION FD FIRE DAMPER FL FINNED LENGTH OF RADIATION FM FLOW METER FOR FUEL OIL RETURN FOS FUEL OIL SUPPLY FPF FINS PER FOOT FPI FINS PER/INCH FPM FEET PER MINUTE FT FEET FT-HD FEET OF HEAD FT-WG FEET WATER GAUGE FTR FIN TUBE RADIATOR GAL GALLONS GPM GALLONS PER MINUTE HP HORSEPOWER HPCR HIGH PRESSURE CONDENSATE RETURN (OVER 30 PSIG) HPS HIGH PRESSURE STEAM (OVER 30PSIG) HRR HEAT RECOVERY RETURN HRS HEAT RECOVERY SUPPLY HWR HOT WATER RETURN HWS HOT WATER SUPPLY GENERAL NOTES 1 VISIT THE BUILDING SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING CONDITIONS, AND TO TAKE MEASUREMENTS AS NECESSARY FOR COMPLETION OF THE WORK ASSOCIATED WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS. 2 COORDINATE WORK OF MECHANICAL SUBCONTRACTOR WITH WORK OF OTHER TRADES. 3 DUCTWORK, PIPING AND EQUIPMENT ARE INDICATED DIAGRAMMATICALLY. FIELD-VERIFY LOCATIONS. 4 PRIOR TO FABRICATING DUCTWORK, COORDINATE WITH OTHER TRADES TO ENSURE THAT THE DUCTWORK CAN BE INSTALLED WITH THE INDICATED SIZES AND LOCATIONS.FIELD-VERIFY EXISTING DUCT SIZES AND CONDITIONS.SUBMIT ANY DISCREPANCIES OR PROPOSED CHANGES. 5 REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF CEILING DIFFUSERS AND REGISTERS.PROVIDE VOLUME DAMPERS SO THAT EVERY REGISTER, GRILLE AND DIFFUSER (SUPPLY, RETURN, AND EXHAUST) CAN BE INDIVIDUALLY BALANCED. 6 VERIFY INSTALLATION OF EXISTING VOLUME DAMPERS AT EACH BRANCH IN EXISTING SUPPLY DUCT. PROVIDE ADDITIONAL VOLUME DAMPERS WHERE REQUIRED. 7 DUCT ELBOWS SHALL BE LONG-RADIUS TYPE (THROAT RADIUS EQUAL TO OR GREATER THAN DUCT WIDTH IN THE PLANE OF THE TURN) WHEREVER SPACE ALLOWS. IF SPACE IS NOT ADEQUATE, PROVIDE MITERED ELBOWS WITH TURNING VANES. 8 PROVIDE 16 GAUGE SINGLE-THICKNESS TURNING VANES AT MITERED DUCT ELBOWS. VANE EDGES (LEADING AND TRAILING) SHALL BE TANGENTIAL TO AIRFLOW. 9 FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 5'-0" 10 PAINT DUCTWORK VISIBLE THRU CEILING OPENINGS, DUCT OPENINGS, AND REGISTERS, GRILLES, AND DIFFUSERS WITH BLACK PAINT IN ACCORDANCE WITH DIVISION 09 SECTION "PAINTING." 11 MOUNT THERMOSTATS AND TEMPERATURE AND HUMIDITY SENSORS AT 48 INCHES AFF TO TOP OF ITEM. PROVIDE ELECTRICAL WALL BOX ATTACHED TO FRAMING. 12 WHERE THERMOSTATS/TEMPERATURE SENSORS ARE LOCATED NEAR LIGHT SWITCHES, INSTALL SO THAT LIGHT SWITCHES ARE NEARER TO THE DOOR JAMBS. THE INTENT IS TO LOCATE THERMOSTATS/ TEMPERATURE SENSORS SO THEY WILL NOT INTERFERE WITH ACCESSIBILITY OF LIGHT SWITCHES. 13 PIPING INDICATED IN OUTSIDE WALLS SHALL BE RUN ON THE WARM SIDE OF BUILDING INSULATION AND VAPOR BARRIER. BUILDING INSULATION BEHIND SUCH PIPING SHALL BE CONTINUOUS, WITHOUT JOINTS OR GAPS. 14 PIPING SHALL BE CONCEALED EXCEPT IN MECHANICAL ROOMS AND AS INDICATED. WHERE PIPES DROP IN BLOCK WALLS, PROVIDE 1/2" THICK INSULATION MINIMUM. 15 SEAL DUCTWORK AND PIPING THRU MECHANICAL ROOM FLOORS AND PARTITIONS, AND THRU FIRE-RATED ASSEMBLIES, WITH FIRESTOP MATERIAL AS SPECIFIED. 16 PROVIDE ALL REQUIRED PENETRATIONS IN RATED ASSEMBLIES, INCLUDING BUT LIMITED TO WALLS AND FLOORS WITH A UL APPROVED FIRESTOPPING ASSEMBLY INCLUDING LISTING LABEL OF PENETRATION AFTER PASSING THROUGH UTILITIES. CONSTRUCTION DOCUMENTS DEMOLITION NOTES 1 DURING DEMOLITION PROPERLY CAP AND PROTECT ALL PIPING & DUCTWORK THAT WILL REMAIN IN OPERATION 2 WHERE EXISTING INSULATION TO REMAIN IS DAMAGED BY THE REQUIREMENTS OF WORK, REPLACE ANY DAMAGED INSULATION IN KIND 3 MECHANICAL CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR DISTRIBUTION OF RESPONSIBILITY AMONGST CONTRACTORS FOR SPECIFIC PORTIONS OF CUTTING AND PATCHING WORK. PLUMBING CONTRACTOR SHALL COORDINATE ALL CUTTING AND PATCHING WORK WITH ALL OTHER CONTRACTORS INVOLVED AS DEFINED IN THE SPECIFICATIONS 4 LOCATION OF EXISTING PIPING & DUCTWORK AS SHOWN ON DRAWINGS IS APPROXIMATE 5 COMPLETELY REMOVE ALL EQUIPMENT AS INDICATED & OR MISCELLANEOUS ARTICLES IN THEIR ENTIRETY INCLUDING AUXILLARY EQUIPMENT, PIPING, WIRING & CONDUIT 6 INCLUDE ALL DEMOLITION OF SYSTEMS AND COMPONENTS WHERE SYSTEMS SHALL BE REPLACED BY NEW WORK. REFER TO THE DRAWINGS & SPECIFICATIONS FOR SCOPE OF NEW & RECONNECTED WORK. THE INTENT OF THIS REQUIREMENT IS TO HAVE THE CONTRACTOR DISCONNECT, DEMOLISH & REMOVE ALL EXPOSED & CONCEALED WORK WHERE BEING REPLACED OR CONNECTED TO THE PROPOSED LAYOUTS 7 COORDINATE ELECTRICAL POWER DISCONNECTION PRIOR TO DEMOLITION WITH ELECTRICAL CONTRACTOR 8 ALL PIPING & DUCTWORK TO REMAIN SHALL HAVE ENDS TERMINATED IN A NEAT MANNER READY FOR CONNECTION OF NEW WORK. ALL EXPOSED ENDS OF PIPING SHALL BE CAPPED 9 EXISTING PIPING NOT TO BE REUSED, NOT SUPPLYING ANY EQUIPMENT AND NOT SPECIFICALLY NOTED OR SHOWN ON DRAWINGS TO BE ABANDONED, SHALL BE COMPLETELY REMOVED 10 CONTRACTOR SHALL CLEAN UP, REMOVE AND DISPOSE OF ALL DEBRIS AND DISCARDED ITEMS UPON COMPLETION OF CONSTRUCTION TO BE READY FOR A NEW OCCUPANCY CONDITION 11 DEMOLISH & COMPLETLY REMOVE EXISTING CONDITIONS DESIGNATED BY A HEAVY DASHED LINE UNLESS NOTED OTHERWISE. REFER TO LEGEND AND DEMOLITION PLANS FOR SCOPE OF WORK
Transcript
Page 1: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

AMS

TIGHT SHUT-OFF VALVE

V

T

ACV 2 - WAY

ACV 3 - WAY

CAP - PIPE

CHECK VALVE

COMBINATION BALANCING, FLOW MEASURING &

FLOAT & THERMOSTATIC TRAP

ISOLATION VALVE

GLOBE VALVE

LOCKSHIELD GATE VALVE

MANUAL AIR VENT

OS&Y GATE VALVE

PETCOCK FOR GAUGE CONNECTION

PIPE ANCHOR

PIPE GUIDE

PLUG VALVE

PRESSURE GAUGE

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

STRAINER

TAKE - OFF FROM BOTTOM OF PIPE

TAKE - OFF FROM TOP OF PIPE

THERMOMETER

THERMOMETER WELL

THERMOSTATIC TRAP

UNION

DESCRIPTIONSYMBOL

EXISTING SUPPLY PIPING TO REMAIN

EXISTING RETURN PIPING TO REMAIN

NEW SUPPLY PIPING

NEW RETURN PIPING

PIPE DOWN

PIPE UP

DIFFERENTIAL PRESSURE SENSORDPS

INVERTED BUCKET TRAP

PIPING LEGEND

REDUCER - CONCENTRIC

REDUCER - ECCENTRIC

10'-0" FL1.2 GPM

RADIATION I.D. ( TYPE A, 10'-0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITH DAMPERA

10'-0" FL/D

1.2 GPM

A RADIATION I.D. ( TYPE A, 10'-0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITHOUT DAMPER

BUTTERFLY VALVE

FD (3 HR) FIRE DAMPER (3 HOUR RATED)

FIRE DAMPER (1 1/2 HOUR RATED)

BD

V

ACOUSTICALLY LINED DUCT

BACKDRAFT DAMPER

DUCT SECTION - SUPPLY/OUTDOOR AIR

DUCT SECTION - RETURN AIR

DUCT TURNING VANES

FLEXIBLE DUCT

LOUVER

MOTORIZED DAMPER

PRESSURE RELIEF DAMPER

RETURN OR EXHAUST AIR

SMOKE DAMPER

STRAINER

SUPPLY OR OUTSIDE AIR

VOLUME DAMPER

SPIRAL DUCT DIAMETER

CB COUNTERBALANCED DAMPER

DESCRIPTIONSYMBOL

S

PRD

M

F

AIRFLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTORSD

EXISTING DUCTWORK TO REMAIN

NEW DUCTWORK

DUCT SECTION - EXHAUST AIR

STATIC PRESSURE SENSORSPS

Ø

FIRE AND SMOKE DAMPER (1 1/2 HOUR RATED)F/S

DUCTWORK LEGEND

S2 4

400

SUPPLY DIFFUSER ( TYPE 2 )

400 CFM EA

DIFFUSER DESCRIPTION

QUANTITY

( SEE REG., GRILLES & DIFF SCHEDULE )

S (SUPPLY) R (RETURN)

E (EXHAUST) T (TRANSFER)

H

HS

HUMIDISTAT

HUMIDITY SENSOR

TEMPERATURE SENSOR

THERMOSTAT

THERMOSTAT COOLING

THERMOSTAT HEATING

THERMOSTAT - NIGHT

THERMOSTAT - HEATING/COOLING

T

TS

TC

H

N

H/C

T

T

T

DESCRIPTIONSYMBOL

CONTROLS LEGEND

A

M10.1SECTION I.D. ( SECTION A SHOWN ON DWG. M10.1)

DESCRIPTIONSYMBOL

EXISTING EQUIPMENT TO REMAIN

NEW EQUIPMENT

COMPLETELY REMOVE EQUIPMENT, DUCTWORK, OR PIPING

GENERIC LEGEND

CONNECT NEW TO EXISTING

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M00-1

DWS

ASG

LEGEND & GENERALNOTES

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

ABBREV DESCRIPTION

IN INCHES

LAT LEAVING AIR TEMPERATURE

LPCRLOW PRESSURE CONDENSATERETURN (LESS THAN 15 PSI)

LPSLOW PRESSURE STEAM(LESS THAN15 PSI)

LRA LOCKED ROTOR AMPS

LSGV LOCK & SHIELD GATE VALVE

LWT LEAVING WATER TEMPERATURE

M MOTORIZED DAMPER

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPS

MIN MINIMUM

MOPDMAXIMUM OVERCURRENTPROTECTIVE DEVICE

MPCRMEDIUM PRESSURE CONDENSATERETURN(16-30 PSIG)

MPSMEDIUM PRESSURE STEAM (16-30PSIG)

NA NOT APPLICABLE

NC NOISE CRITERIA

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OC ON CENTER

OED OPEN END DUCT

OS&YOUTSIDE SCREW & YOKE GATEVALVE

PD PRESSURE DROP

PRD PRESSURE RELIEF DAMPER

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

RET RETURN

RL REFRIGERANT LIQUID

RLA RATED LOAD AMPERES

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

S SMOKE DAMPER

SP STATIC PRESSURE

SS STAINLESS STEEL

SUP SUPPLY

TEMP TEMPERATURE

TT THERMOSTATIC TRAP

TYP TYPICAL

V VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

W/ WITH

W/O WITHOUT

WC WATER COLUMN

WG WATER GAUGE

WMS WELDED WIRE MESH SCREEN

WPD WATER PRESSURE DROP

Z ZONE DAMPER

PREFIX OF X EXISTING

ABBREV DESCRIPTIONACV AUTOMATIC CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ALD ACOUSTICAL LINED DUCT

AMS AIRFLOW MEASURING STATION

APD AIR PRESSURE DROP

ATCAUTOMATIC TEMPERATURECONTROL

B BAROMETRIC DAMPER

BD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BPD BYPASS DAMPER

BTU BRITISH THERMAL UNITS

CBDCOUNTERBALANCED BACKDRAFTDAMPER

CFM CUBIC FEET PER MINUTE

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CLEANOUT

CTE CONNECT TO EXISTING

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

DCW DOMESTIC COLD WATER

DEG.F DEGREES FAHRENHEIT

DHW DOMESTIC HOT WATER

DIA DIAMETER

DN DOWN

DTR DUAL TEMPERATURE RETURN

DTS DUAL TEMPERATURE SUPPLY

EAT ENTERING AIR TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXG EXISTING

EXH EXHAUST

F&T FLOAT & THERMOSTATIC TRAP

F/SFIRE AND SMOKE COMBINATIONDAMPER

FC FLEXIBLE CONNECTION

FD FIRE DAMPER

FL FINNED LENGTH OF RADIATION

FM FLOW METER

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPF FINS PER FOOT

FPI FINS PER/INCH

FPM FEET PER MINUTE

FT FEET

FT-HD FEET OF HEAD

FT-WG FEET WATER GAUGE

FTR FIN TUBE RADIATOR

GAL GALLONS

GPM GALLONS PER MINUTE

HP HORSEPOWER

HPCRHIGH PRESSURE CONDENSATERETURN (OVER 30 PSIG)

HPSHIGH PRESSURE STEAM (OVER30PSIG)

HRR HEAT RECOVERY RETURN

HRS HEAT RECOVERY SUPPLY

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

GENERAL NOTES1 VISIT THE BUILDING SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING CONDITIONS, AND TO TAKE

MEASUREMENTS AS NECESSARY FOR COMPLETION OF THE WORK ASSOCIATED WITH THE DESIGN INTENT OFTHE CONTRACT DOCUMENTS.

2 COORDINATE WORK OF MECHANICAL SUBCONTRACTOR WITH WORK OF OTHER TRADES.

3 DUCTWORK, PIPING AND EQUIPMENT ARE INDICATED DIAGRAMMATICALLY. FIELD-VERIFY LOCATIONS.

4 PRIOR TO FABRICATING DUCTWORK, COORDINATE WITH OTHER TRADES TO ENSURE THAT THE DUCTWORKCAN BE INSTALLED WITH THE INDICATED SIZES AND LOCATIONS.FIELD-VERIFY EXISTING DUCT SIZES ANDCONDITIONS.SUBMIT ANY DISCREPANCIES OR PROPOSED CHANGES.

5 REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF CEILING DIFFUSERS ANDREGISTERS.PROVIDE VOLUME DAMPERS SO THAT EVERY REGISTER, GRILLE AND DIFFUSER (SUPPLY, RETURN,AND EXHAUST) CAN BE INDIVIDUALLY BALANCED.

6 VERIFY INSTALLATION OF EXISTING VOLUME DAMPERS AT EACH BRANCH IN EXISTING SUPPLY DUCT. PROVIDEADDITIONAL VOLUME DAMPERS WHERE REQUIRED.

7 DUCT ELBOWS SHALL BE LONG-RADIUS TYPE (THROAT RADIUS EQUAL TO OR GREATER THAN DUCT WIDTH INTHE PLANE OF THE TURN) WHEREVER SPACE ALLOWS. IF SPACE IS NOT ADEQUATE, PROVIDE MITEREDELBOWS WITH TURNING VANES.

8 PROVIDE 16 GAUGE SINGLE-THICKNESS TURNING VANES AT MITERED DUCT ELBOWS. VANE EDGES (LEADINGAND TRAILING) SHALL BE TANGENTIAL TO AIRFLOW.

9 FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 5'-0"

10 PAINT DUCTWORK VISIBLE THRU CEILING OPENINGS, DUCT OPENINGS, AND REGISTERS, GRILLES, ANDDIFFUSERS WITH BLACK PAINT IN ACCORDANCE WITH DIVISION 09 SECTION "PAINTING."

11 MOUNT THERMOSTATS AND TEMPERATURE AND HUMIDITY SENSORS AT 48 INCHES AFF TO TOP OF ITEM.PROVIDE ELECTRICAL WALL BOX ATTACHED TO FRAMING.

12 WHERE THERMOSTATS/TEMPERATURE SENSORS ARE LOCATED NEAR LIGHT SWITCHES, INSTALL SO THATLIGHT SWITCHES ARE NEARER TO THE DOOR JAMBS. THE INTENT IS TO LOCATE THERMOSTATS/ TEMPERATURESENSORS SO THEY WILL NOT INTERFERE WITH ACCESSIBILITY OF LIGHT SWITCHES.

13 PIPING INDICATED IN OUTSIDE WALLS SHALL BE RUN ON THE WARM SIDE OF BUILDING INSULATION AND VAPORBARRIER. BUILDING INSULATION BEHIND SUCH PIPING SHALL BE CONTINUOUS, WITHOUT JOINTS OR GAPS.

14 PIPING SHALL BE CONCEALED EXCEPT IN MECHANICAL ROOMS AND AS INDICATED. WHERE PIPES DROP INBLOCK WALLS, PROVIDE 1/2" THICK INSULATION MINIMUM.

15 SEAL DUCTWORK AND PIPING THRU MECHANICAL ROOM FLOORS AND PARTITIONS, AND THRU FIRE-RATEDASSEMBLIES, WITH FIRESTOP MATERIAL AS SPECIFIED.

16 PROVIDE ALL REQUIRED PENETRATIONS IN RATED ASSEMBLIES, INCLUDING BUT LIMITED TO WALLS ANDFLOORS WITH A UL APPROVED FIRESTOPPING ASSEMBLY INCLUDING LISTING LABEL OF PENETRATION AFTERPASSING THROUGH UTILITIES.

CONSTRUCTION DOCUMENTS

DEMOLITION NOTES1 DURING DEMOLITION PROPERLY CAP AND PROTECT ALL PIPING & DUCTWORK THAT WILL REMAIN IN

OPERATION

2 WHERE EXISTING INSULATION TO REMAIN IS DAMAGED BY THE REQUIREMENTS OF WORK, REPLACE ANYDAMAGED INSULATION IN KIND

3 MECHANICAL CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR DISTRIBUTION OF RESPONSIBILITYAMONGST CONTRACTORS FOR SPECIFIC PORTIONS OF CUTTING AND PATCHING WORK. PLUMBINGCONTRACTOR SHALL COORDINATE ALL CUTTING AND PATCHING WORK WITH ALL OTHER CONTRACTORSINVOLVED AS DEFINED IN THE SPECIFICATIONS

4 LOCATION OF EXISTING PIPING & DUCTWORK AS SHOWN ON DRAWINGS IS APPROXIMATE

5 COMPLETELY REMOVE ALL EQUIPMENT AS INDICATED & OR MISCELLANEOUS ARTICLES IN THEIR ENTIRETYINCLUDING AUXILLARY EQUIPMENT, PIPING, WIRING & CONDUIT

6 INCLUDE ALL DEMOLITION OF SYSTEMS AND COMPONENTS WHERE SYSTEMS SHALL BE REPLACED BY NEWWORK. REFER TO THE DRAWINGS & SPECIFICATIONS FOR SCOPE OF NEW & RECONNECTED WORK. THEINTENT OF THIS REQUIREMENT IS TO HAVE THE CONTRACTOR DISCONNECT, DEMOLISH & REMOVE ALLEXPOSED & CONCEALED WORK WHERE BEING REPLACED OR CONNECTED TO THE PROPOSED LAYOUTS

7 COORDINATE ELECTRICAL POWER DISCONNECTION PRIOR TO DEMOLITION WITH ELECTRICAL CONTRACTOR

8 ALL PIPING & DUCTWORK TO REMAIN SHALL HAVE ENDS TERMINATED IN A NEAT MANNER READY FORCONNECTION OF NEW WORK. ALL EXPOSED ENDS OF PIPING SHALL BE CAPPED

9 EXISTING PIPING NOT TO BE REUSED, NOT SUPPLYING ANY EQUIPMENT AND NOT SPECIFICALLY NOTED ORSHOWN ON DRAWINGS TO BE ABANDONED, SHALL BE COMPLETELY REMOVED

10 CONTRACTOR SHALL CLEAN UP, REMOVE AND DISPOSE OF ALL DEBRIS AND DISCARDED ITEMS UPONCOMPLETION OF CONSTRUCTION TO BE READY FOR A NEW OCCUPANCY CONDITION

11 DEMOLISH & COMPLETLY REMOVE EXISTING CONDITIONS DESIGNATED BY A HEAVY DASHED LINE UNLESSNOTED OTHERWISE. REFER TO LEGEND AND DEMOLITION PLANS FOR SCOPE OF WORK

Page 2: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

HA HB HC HD HE HF HG

H1

H2

H3

AH

A17

A18

A19

D001

D001

D002

EXISTING UNIT HEATER

EXISTING FINTUBE

EXISTING BASEBOARD

EXISTING BASEBOARD

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic Scale

0 4' 8' 12'

1/8" = 1'-0"

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M05-1

DWS

ASG

FIRST FLOORDEMOLITION DUCTWORK

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

DEMO KEY NOTESCODE DESCRIPTION

D001 COMPLETELY REMOVE EXISTING EXHAUST DUCTWORK AND EXHAUST FAN;EXISTING SOFFIT EXHAUST GRILLE AND WALL PENETRATION TO BE REUSED FORNEW DUCTWORK AS SHOWN ON M

D002 COMPLETELY REMOVE EXHAUST FAN AND ASSOCIATED CONTROLS

D003 COMPLETELY REMOVE FINTUBE, FLOOR MOUNTED CABINET UNIT HEATERS ANDALL ASSOCIATED CONTROLS; DEMO AND CAP PIPING ABOVE CEILING

D004 COMPLETELY REMOVE CEILING MOUNTED UNIT HEATER AND ASSOCIATEDCONTROLS; 1" HWS/R PIPING TO BE REUSED FOR FUTURE CONNECTION TO NEWFLOOR MOUNTED RADIANT PANELS AS SHOWN ON M20-1

Page 3: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

HA HB HC HD HE HF HG

H1

H2

H3

AG

AH

A15

A16

A17

A18

A19

D003D003

D003

D004

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic Scale

0 4' 8' 12'

1/8" = 1'-0"

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M06-1

DWS

ASG

FIRST FLOORDEMOLITION PIPING

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

DEMO KEY NOTESCODE DESCRIPTION

D001 COMPLETELY REMOVE EXISTING EXHAUST DUCTWORK AND EXHAUST FAN;EXISTING SOFFIT EXHAUST GRILLE AND WALL PENETRATION TO BE REUSED FORNEW DUCTWORK AS SHOWN ON M

D002 COMPLETELY REMOVE EXHAUST FAN AND ASSOCIATED CONTROLS

D003 COMPLETELY REMOVE FINTUBE, FLOOR MOUNTED CABINET UNIT HEATERS ANDALL ASSOCIATED CONTROLS; DEMO AND CAP PIPING ABOVE CEILING

D004 COMPLETELY REMOVE CEILING MOUNTED UNIT HEATER AND ASSOCIATEDCONTROLS; 1" HWS/R PIPING TO BE REUSED FOR FUTURE CONNECTION TO NEWFLOOR MOUNTED RADIANT PANELS AS SHOWN ON M20-1

Page 4: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

V

V

V

V

V

T

T

T

M

M

V

V

V

V

V

V

V

V

ERV-1

AHU-1

20"x10" SU

P

6"ø S

UP

6"ø S

UP

24"x10" SU

P

10"ø S

UP

24"x10" RET

6"ø R

ET

10"ø R

ET

12"ø R

ET

12"ø R

ET

24"x10" RET

12"ø S

UP

S2

100

1

R2

400

1S3

400

1

E1

70

1S1

S1

400

400

R1

1075

1

M003

M004

M006

M006

M006

M002

M005

M001

M007

BALANCE OA TO 25 CFM (TYP OF 3)

10"ø S

UP

10"ø S

UP

20"x10" SU

P

10'-0" M

IN36"x12" PLENUM SIZED TO MATCH LOUVER

DIMENSIONS

4"ø S

UP

6"ø S

UP

6"ø S

UP

IU-3

IU-2

IU-1

S2

100

1

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic Scale

0 4' 8' 12'

1/8" = 1'-0"

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M10-1

DWS

ASG

FIRST FLOOR DUCTWORK

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

KEY NOTESCODE DESCRIPTION

M001 AHU-1 TO BE SUPPORTED BY BEAM FLANGECLAMPS ON TOP BEAM FLANGE ; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES

M002 ERV-1 TO BE INSTALLED ON FLOOR MOUNTEDEQUIPMENT STAND; INSTALL MANUFACTUREROA/RA MOD AS NECESSARY; ALL OA DUCT TO BEDOUBLE WRAPPED WITH 1.5" FIBERGLASSINSULATION A MINIMUM 4' FROM EXTERIOR WALLPLENUM; ALL FA DUCT TO BE WRAPPED WITH 1.5"FIBERGLASS INSULATION; REFER TOMANUFACTURER'S DOCUMENTS FOR EQUIPMENTINSTALLATION AND CLEARANCE REQUIREMENTS

M003 RE-USE EXISTING 36"X12" EXHAUST REGISTER ANDWALL SLEEVE FOR NEW 12" ERV EXHAUST DUCT;DEMO EXISTING AUTOMATIC DAMPER ASNECESSARY

M004 INSTALL NEW WALL SLEEVE AND INTAKE LOUVER10' FROM EXHAUST OUTLET; INTAKE LOUVER TOBE INSTALLED IN SOFFIT; INTAKE LOUVER TO BE36x10 GREENHECK ESD-435 OR EQUIVALENT

M005 ERV-1 12" EA/FA DUCT TAKEOFFS TO BE A MINIMUM5' APART; FA DUCT TO BE INSULATED WITH 1.5"FIBERGLASS WRAP; BALANCE EA AND FA TO AHU-1TO 585 CFM

M006 NEW 4-WAY CEILING CASSETTES TO BECONNECTED WITH 4" SA FROM AHU-1; EACHCASSETTE TO BE CONTROLLED BY WALLMOUNTED THERMOSTAT AND PROVIDED WITH ANINTEGRALL RELAY TO ENERGIZE BASEBOARDZONE CONTROL VALVE AS NECESSARY DURINGDEFROST MODE

M007 INSTALL OU-1 ON CONCRETE PAD; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES

Page 5: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

T

T

T

HA HB HC HD HE HF HG

H1

H2

H3

AH

A16

A17

A18

A19

A10' - 0" FL1.0 GPM

A10' - 0" FL1.0 GPM

A10' - 0" FL1.0 GPM

AHU-1

RL- 3/8"

RS- 5/8"

RL-

3/8"

RS-1 1/4"

RL-

3/8"

RS-3/4"

RL- 3/8"

RS- 5/8"

RS- 5/8"

RL- 3/8"

RL-

3/8"

RS-5/8"

RS-5/8"

RL-

3/8"

HWS- 1 1

/2"

HWR- 1 1

/2"

HW

R-1 1/4"H

WS-1 1/4"

HW

R-1"H

WS-1"

HW

R-1 1/4"

HW

S-1 1/4"

HWR- 3/4

"

HWR- 3/4

"

HW

R-1 1/4"

HW

S-1"

ERV-1

INSTALL NEW 1/2" RADIANT ZONE CONTROL VALVE; CONTROL VALVE TO BE INTERLOCKED WITH CEILING CASSETTE RELAY

(TYP OF 3)

M007

M001

M002

M006

M006

M006

HW

R-3/4"

HW

R-3/4"

HWR- 3/4

"

5/8" RS / 3/8 RLPIPING DOWN TO AHU-1

OU-1

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic Scale

0 4' 8' 12'

1/8" = 1'-0"

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M20-1

DWS

ASG

FIRST FLOOR PIPING

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

KEY NOTESCODE DESCRIPTION

M001 AHU-1 TO BE SUPPORTED BY BEAM FLANGECLAMPS ON TOP BEAM FLANGE ; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES

M002 ERV-1 TO BE INSTALLED ON FLOOR MOUNTEDEQUIPMENT STAND; INSTALL MANUFACTUREROA/RA MOD AS NECESSARY; ALL OA DUCT TO BEDOUBLE WRAPPED WITH 1.5" FIBERGLASSINSULATION A MINIMUM 4' FROM EXTERIOR WALLPLENUM; ALL FA DUCT TO BE WRAPPED WITH 1.5"FIBERGLASS INSULATION; REFER TOMANUFACTURER'S DOCUMENTS FOR EQUIPMENTINSTALLATION AND CLEARANCE REQUIREMENTS

M003 RE-USE EXISTING 36"X12" EXHAUST REGISTER ANDWALL SLEEVE FOR NEW 12" ERV EXHAUST DUCT;DEMO EXISTING AUTOMATIC DAMPER ASNECESSARY

M004 INSTALL NEW WALL SLEEVE AND INTAKE LOUVER10' FROM EXHAUST OUTLET; INTAKE LOUVER TOBE INSTALLED IN SOFFIT; INTAKE LOUVER TO BE36x10 GREENHECK ESD-435 OR EQUIVALENT

M005 ERV-1 12" EA/FA DUCT TAKEOFFS TO BE A MINIMUM5' APART; FA DUCT TO BE INSULATED WITH 1.5"FIBERGLASS WRAP; BALANCE EA AND FA TO AHU-1TO 585 CFM

M006 NEW 4-WAY CEILING CASSETTES TO BECONNECTED WITH 4" SA FROM AHU-1; EACHCASSETTE TO BE CONTROLLED BY WALLMOUNTED THERMOSTAT AND PROVIDED WITH ANINTEGRALL RELAY TO ENERGIZE BASEBOARDZONE CONTROL VALVE AS NECESSARY DURINGDEFROST MODE

M007 INSTALL OU-1 ON CONCRETE PAD; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES

Page 6: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

NOTE

ORIENT CONDENSING UNIT ON STANDSUCH THAT CONDENSER FAN WILLBLOW AIR TOWARD THE NEARBY BUILDING WALL AS RECOMMENDED BY THE MANUFACTURER

METAL SLEEVE TYPICAL ATPENETRATIONS. VERIFY SIZE & NUMBER. PROVIDE WATER-TIGHT SEAL TO FLASHING. PROVIDETWO (2) PIECE FIELD FABRICATED FLASHING WITH STAINLESS STEELCLAMPING RING OVER METAL SLEEVE

INSULATE VAPOR, LIQUID, ANDCONDENSATE DRAIN PIPING.PIPING EXPOSED INDOORS AND OUTDOORS: PROVIDE FULL PVCJACKET AND FITTINGS, WITH SEAMS SEALED AND LAPPEDDOWNWARD TO DRAIN.

PROVIDE SUPPORTS AND PENETRATIONS ASREQUIRED FOR PIPING AND ELECTRICAL

DHP INDOOR UNIT(EVAPORATOR FAN-COIL)

COND., PITCHTO DRAIN

FLOOR

BUILDING EXTERIORWALL

CONCRETE PAD

GRADE

BI-FLOW LIQUID-LINESOLENOID VALVE WITHIN2 FEET OF UNIT, ARROWPOINTING TOWARD UNIT

16-INCH-HIGH SNOWSTAND, FASTEN TO PAD

AND TO UNIT

LIQUID-LINE MOISTURE-AND LIQUID INDICATINGSIGHT GLASS

GALVANIZED STEEL PIPE STAND,FASTENED TO CONCRETE PAD

CEILING

FILTER-DRIER FURNISHEDWITH HEAT PUMP

PROVIDE TEST VALVES

HEATING ACCURATER DEVICEFURNISHED WITH HEAT PUMP

COOLING ACCURATERDEVICE INSIDE UNIT

DHP OUTDOORCONDENSING UNIT

VAPOR LINE

LIQUID LINE

INVERTED TRAP INVAPOR LINE.

TOP SHALL BE ABOVE TOP OF

INDOOR UNIT

PENETRATE CEILINGCLOSE TO UNIT, WITHESCUTCHEONS

SPACE BETWEENUNIT AND WALL

FOR INTAKE DUCT

60" MAX

1"

NOTES:1. REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES.2. ATTACH HANGERS TO TOP CHORD OF JOISTS.3. DO NOT EXCEED ALLOWABLE LOAD LIMITS.

STRAP OR ANGLE

ROD

SIZE BOLT(S) FOR LOAD

STRAP

24" DIA MAX36" DIA MAX

10" DIA MAX

BAND OF SAME SIZEAS HANGER STRAP

ROD

HANGERS MUST NOTDEFORM DUCT SHAPEBAND ONE HALF-ROUND MAY BEUSED IF DUCT SHAPE IS MAINTAINED

LOCKNUTS(TYPICAL)

ANGLES

SCREWS

UNLESS FOOT OF STRAPIS PLACED UNDER ABOTTOM REINFORCEMENT

SCREWS MAY BE OMITTEDIF HANGER LOOPS

HANGER STRAPS

HANGER

SECUREWIRE

LOAD RATEDFASTENERS

HANGER RODS,WIRES, ORSTRAPS

ALTERNATE ROD LOCATION(VERIFY UPPER TRAPEZELOAD CAPACITY)

TRAPEZE HANGERSSTRAP HANGERS

PLENUM(INSULATE AS

FOR DUCTWORK)

SURFACE MOUNTEDAIR DEVICE

DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL

PLENUM(INSULATE AS

FOR DUCTWORK)2 x INLET

DUCT HEIGHT

LAY-IN CEILING

ANGLES TOSUPPORT PLENUM ONCEILING GRID

MAINDUCT

LAY-IN AIRDEVICE

DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL

LAY-IN CEILING

STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.

SEE AIR DEVICEDETAILS BELOW FOR CONNECTION TO MAIN DUCT

LAY-IN AIRDEVICE

LAY-IN CEILING

MAINDUCT

SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR

SURFACE MOUNTED CEILING AIR DEVICE

ROUND-NECK DIFFUSER CONNECTION

LAY-IN AIR DEVICE UNDER DUCT

2 x INLETDUCT HEIGHT

SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR

STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.

SURFACE MOUNTEDAIR DEVICE

DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL

LAY-IN CEILING

ANGLES TOSUPPORT PLENUM ONCEILING GRID

MAINDUCT

SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR

STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.

ANGLES TOSUPPORT PLENUM ONCEILING GRID

OR

OR

VOLUME DAMPERS:1) PROVIDE STAND-OFF BRACKETS ON INSULATED DUCTS.

2) INSULATE UNDER BRACKETS, SEAL VAPOR BARRIER TO BRACKETS

3) PROVIDE LOCKING, INDICATING QUADRANTS.

MAIN DUCT

CLOSE OPENINGS AT

CORNERS

BRANCH DUCT

45° ENTRY

BRANCH TAKE-OFF

STAND-OFF MOUNTING

BRACKET

OPPOSED BLADE BALANCING DAMPER

PROVIDE CONTINUOUS INSULATION BETWEEN

BRACKET AND DUCT WHILE LEAVING DAMPER HANDLE

EXPOSED.

1/4 OF DUCT WIDTH, MINIMUM OF 4".

HANG SURVEYOR'S TAPE FROM VOLUME DAMPER WHERE CONCEALED ABOVE CEILINGS SO THAT BALANCER CAN LOCATE DAMPER LOCATIONS. TAPE IS NOT REQUIRED WHERE DUCTS ARE EXPOSED.

DIRECTION OF AIR FLOW RETURN/EXHAUST)

DIRECTION OF AIR FLOW (SUPPLY)

PLAN VIEW

ISOMETRIC VIEW

.

CLOSE OPENINGAT CORNERS

MAIN DUCT

BRANCHDUCT

HANG SURVEYOR'S TAPE FROMVOLUME DAMPERS SO THAT BALANCER CAN LOCATE DAMPER LOCATIONS

DUCT TAKE-OFF FROMTOP OF DUCT

45° TAKE-OFF

DIRECTION OFFLOW (RETURN)

DIRECTION OFFLOW (SUPPLY)

VOLUME DAMPER

OPPOSED BLADEBALANCING DAMPER

BRANCHTAKE-OFF

PROVIDE CONTINUOUSINSULATION BETWEEN

BRACKET AND DUCT

INSULATED SUPPLY AND RETURN DUCTWORK SHALL BE INSTALLED WITHSTAND-OFF MOUNTING BRACKETS FOR VOLUME/BALANCING DAMPEROPERATORS. ALLOW CLEARANCE BETWEEN DUCT AND OPERATOR OF NOTLESS THAN INSULATION THICKNESS.

ISOMETRIC VIEW

PLAN VIEW

STAND-OFF MOUNTING BRACKET

1/2" PLUGGED TEEFOR DRAIN

PITCH UP

PITCH UP

COMBINATION BALANCING, FLOW MEASURING, & TIGHT SHUT-OFF VALVE

SHUT-OFF VALVE

UNION

STRAINER

ACV

V

V

AIR VENT

R =2WO

R =W

VANES, SINGLE THICKNESS, FULL 2-IN. RADIUS, 90° TURN, MINIMUM 16-GAUGE, FILLING ENTIRE CROSS SECTION

USE MITERED ONLY WHERE SPACE IS TOO TIGHT FORRADIUS, OR WHERE INDICATED ON DRAWINGS.

RADIUSES MITERED

W

W

I

1 1/2"

SHEET METAL DUCTWORK

WALL

OUTER EDGE OF DUCT OR OUTER LIMIT OF DUCT INSULATION

1" SPACE BETWEEN DUCT & SLEEVE

NON COMBUSTIBLE GLASS FIBER INSULATION USED FOR BACKING BETWEEN DUCT AND SLEEVE

20 GAUGE CLOSURE COLLARS SEE SPECIFICATION SECTION 233300 FOR

ATTACHMENT REQUIREMENTS FOR DIFFERENT WALL AND FLOOR PENETRATIONS

20 GAUGE GALVANIZED SHEET METAL DUCT SLEEVE SHALL BE FABRICATED WITH LONGITUDINAL PITTSBURGH LOCK. EXPOSED ENDS OF DUCT SHALL BE HEMMED

SLEEVE SHALL BE FLUSH WITH WALL OR FLOOR UNLESS OTHERWISE NOTED

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M50-1

DWS

ASG

DETAILS

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0"1

DUCTLESS HEAT PUMP UNIT

SCALE: 1" = 10'-0"2

LOWER HANGER ATTACHMENT

SCALE: 1/8" = 1'-0"7

CEILING AIR DEVICE

SCALE: 1" = 10'-0"5

SIDE BRANCH TAKE-OFF

SCALE: 1" = 10'-0"4

TOP BRANCH TAKE-OFF

SCALE: 1/8" = 1'-0"3

HOT WATER RADIATIONSCALE: 1 1/2" = 1'-0"

6DUCT ELBOW

SCALE: 1/8" = 1'-0"8

DUCT SLEEVE

Page 7: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Key Plan

Harriman Project No.

PA / PE:

Drawn By:Harriman Associates

c

Proj North

Revision DescriptionRev Date

May 17, 2021

GORHAM, MAINE

20478

M60-1

DWS

ASG

SCHEDULES

2021

UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM

ATHLETIC TRAININGRENOVATIONS

CONSTRUCTION DOCUMENTS

AIR HANDLER SCHEDULE

TAG MANUFACTURER MODEL SERVICE

TOTALCAPACITY(BTU/HR) Airflow

MIN.OUTDOOR

AIR(CFM)

WEIGHT(LBS)

FAN SECTION FILTERS

FAN MOTOR

DIMENSIONS (IN.) EFF'YTYPEE.S.P

(IN.WG) VOLTSAHU-1 Mitsubishi Electric TPVFYP048 SEE PLANS 48000 1400 585 172 FORWARD

CURVED.80 208 20x24x1 MERV 8

DUCTLESS AIR CONDITIONER SCHEDULE

TAG MANUFACTURER MODEL SERVICE

COOLINGCAPACITY

(MBH)

INDOOR UNIT PIPING SIZES ELECTRIC

NOTES

AIR FLOWHI/MED/LOW

(CFM)NOISE

(HI SPEED dB(A))HEIGHT

(IN)WIDTH

(IN)DEPTH

(IN)SUCTION

(IN)LIQUID

(IN)

MAXLENGTH

(FT) VOLTS PHASEMCA

(AMPS)MAX FUSE

(AMPS)IU-1 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15

IU-2 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15

IU-3 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15

FINTUBE RADIATION SCHEDULE

TAG MANUFACTURER MODELPIPE SIZE

(IN.)CAPACITY

BTU/FT ROWS

ENCLOSUREDIMENSIONS

W x H (IN.) NOTESA STERLING PR2-03 3/4" 994 3 8-5/8"x 10'

ENERGY RECOVERY VENTILATOR SCHEDULE

TAG MFR MODEL

FA AIRFLOW(CFM)

EXT SP(IN) HP

EA AIRFLOW(CFM)

EXT SP(IN) HP

OUTDOOR AIR INDOOR AIR SUPPLY AIR ELECTRICAL FILTER

WEIGHT(LBS) NOTES

SUMMERDB

(DEG.F)

SUMMERWB

(DEG.F)

WINTERDB

(DEG.F)

WINTERWB

(DEG.F)

SUMMERDB

(DEG.F)

SUMMERWB(%)

WINTERDB

(DEG.F)

WINTERWB(%)

SUMMERDB

(DEG.F)

SUMMERWB

(DEG.F)

WINTERDB

(DEG.F)

WINTERWB

(DEG.F) VOLTS PHASE MCA EFF'Y QTYERV-1 RenewAire HE1XINH 585 1.0 0.5 655 1 0.5 87 °F 71 °F 0 °F -2 °F 75 °F 62.5 70 °F 54.4 78 °F 66 °F 54 °F 44 °F 208 V 1 10.8 MERV 13 2 275.00 lb/ft³

REGISTERS, GRILLES & DIFFUSERS SCHEDULE

TAG MANUFACTURER MODEL TYPENOMINAL FACE

SIZE (IN)NECK

SIZE (IN) MAX NC MAX SP DAMPER FINISH BORDERE1 PRICE INDUSTRIES 530 SERIES LOUVERED 8 x 8 6" 20 0.09 in-wg NONE BAKED ENAMEL

WHITESURFACE

MOUNT

R1 PRICE INDUSTRIES 530 SERIES LOUVERED 24 x 24 22 x 22 20 0.09 in-wg NONE BAKED ENAMELWHITE

TYPE 3 LAY IN

R2 PRICE INDUSTRIES 530 SERIES LOUVERED 12 x 12 12 x 12 20 0.09 in-wg NONE BAKED ENAMELWHITE

SURFACEMOUNT

S1 PRICE INDUSTRIES SCD CEILING DIFFUSER 24 x 24 10" 20 0.09 in-wg NONE BAKED ENAMELWHITE

TYPE 3 LAY IN

S2 PRICE INDUSTRIES SCD CEILING DIFFUSER 24 x 24 6" 20 0.09 in-wg NONE BAKED ENAMELWHITE

TYPE 3 LAY IN

S3 PRICE INDUSTRIES 520 SERIES LOUVEREDSUPPLY

12 x 12 10" 20 0.09 in-wg NONE BAKED ENAMELWHITE

SURFACEMOUNT

VRV SCHEDULE

TAG MANUFACTURER MODEL SERVICE

TOTALHEATING

CAPACITY(MBH)

TOTALCOOLINGCAPACITY

(MBH)DIMENSIONS(W x H x D) in

MOUNTINGTYPE

ELECTRICAL

NOTESMOPD PHASE VOLTSOU-1 Mitsubishi Electric TUHYE1203 SEE PLANS 135,000 120,000 48-7/8" x 71-5/8" x 29-3/16"

"PAD 60 3 208 V

Page 8: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

REF:A1

--

NOTES

1.

2.

3.

5.

6.

7.

LIGHTING FIXTURE NOTES

4.

8. ALL LIGHT FIXTURES SHALL MEET UTILITY COMPANY INCENTIVE

REQUIREMENTS.INCENTIVE FORMS SHALL BE COMPLETED BY

ELECTRICAL CONTRACTOR. ALL INCENTIVES SHALL BE PAID

DIRECTLY TO OWNER.

THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL

LIGHTING FIXTURES COMPLETE WITH MOUNTING

ACCESSORIES TO MEET JOB REQUIREMENTS.

ALL FIXTURES SHALL BE SUPPORTED FROM THE BUILDING

STRUCTURE, INDEPENDENT OF HUNG CEILINGS.

THE ELECTRICAL CONTRACTOR SHALL VERIFY FIXTURE

MOUNTING AND LOCATION AGAINST PLANS, ELEVATIONS,

AND DETAIL DRAWINGS. EXACT LOCATION OF ALL

FIXTURES SHALL BE CONFIRMED WITH THE ARCHITECT

PRIOR TO ROUGHING IN.

FIXTURE LETTERS SHOWN ON A CONTINUOUS ROW OF

FIXTURES SHALL BE TYPICAL FOR THAT ROW UNLESS

OTHERWISE NOTED.

9. OCCUPANCY SENSOR SHALL CONTROL THE LIGHTING CIRCUIT

SERVING THE ROOM AHEAD OF SWITCH CONTROLS. PROVIDE

POWER PACKS AS REQUIRED FOR A FULLY FUNCTIONING SYSTEM.

1.

2.

3.

4.

5.

6.

7.

8.

UNLESS OTHERWISE NOTED, WIRING SHALL BE 2#12 AWG

CONDUCTORS & #12 GND. HOMERUNS FED FROM 20A, SINGLE

POLE CIRCUITS IN EXCESS OF 100 FEET SHALL BE #10 AWG

UNLESS INDICATED OTHERWISE. INSULATION TYPE SHALL BE

THHN/TWHN, 75 DEG. C, AND 600V CLASS UNLESS SPECIFIED

OTHERWISE.

FLEXIBLE CONNECTIONS TO MOTORS SHALL BE

FLEXIBLE LIQUID TIGHT CONDUIT.

9.

10.

11.

12.

13.

14.

15.

16.

UNLESS OTHERWISE NOTED, ALL WIRING SHALL

BE 600V, COPPER WITH THHN-THWN INSULATION.

WHERE IT IS INDICATED THAT EXISTING WIRING

IS TO BE REUSED, THE ELECTRICAL SUBCONTRACTOR

SHALL VERIFY THAT THE INTEGRITY OF THE INSULATION

IS ADEQUATE FOR REUSE. ALL SUSPECT WIRING SHALL

BE REPLACED BY THE SUBCONTRACTOR.

GENERAL NOTES GENERAL NOTES (CON'T)

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH

THE LATEST EDITION OF NFPA 70, NATIONAL ELECTRICAL

CODE (NEC), OSHA REGULATIONS, AS WELL AS APPLICABLE

REGULATIONS OF THE PERTINENT FEDERAL, STATE, COUNTY,

AND CITY AGENCIES. PROVIDE MATERIALS AND EQUIPMENT

THAT COMPLY WITH ANSI, IEEE, IES, AND NEMA STANDARDS.

WHERE APPLICABLE, PROVIDE ONLY MATERIALS THAT ARE

U.L. LISTED AND LABELED.

THE ELECTRICAL SUBCONTRACTOR SHALL VISIT THE SITE

AND INSPECT EXISTING CONDITIONS, SERVICES, CONDUITS,

SPATIAL CONSIDERATIONS AND ALL OTHER PERTINENT

CONDITIONS TO FULLY FAMILIARIZE HIMSELF WITH

CONDITIONS TO BE ENCOUNTERED IN THE PERFORMANCE

OF THIS WORK. THE ELECTRICAL SUBCONTRACTOR SHALL

COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR

DURING CONSTRUCTION. FAILURE TO DO SO WILL NOT

RELIEVE THE ELECTRICAL SUBCONTRACTOR OF THE

RESPONSIBILITY FOR FULL COMPLETION OF THE WORK

IN ACCORDANCE WITH APPLICABLE DRAWINGS AND

SPECIFICATIONS. VERIFY EXISTING SYSTEMS THAT WILL BE

UTILIZED FOR CONNECTION TO THE NEW SYSTEM. IF

DISCREPANCIES EXIST BETWEEN THE CONTRACT DRAWINGS

AND THE ACTUAL EXISTING CONDITIONS, THE ELECTRICAL

SUBCONTRACTOR SHALL NOTIFY THE ENGINEER/OWNER

PRIOR TO PROCEEDING WITH THE INSTALLATION.

ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND MOTOR

STARTERS THAT ARE NOT PROVIDED BY OTHER DIVISIONS,

SHALL BE PROVIDED BY DIVISION 26, UNLESS SPECIFICALLY

NOTED OTHERWISE.

ALL PENETRATIONS THROUGH FIRE-RATED FLOORS, WALLS

AND PARTITIONS SHALL BE SEALED WITH UL APPROVED

FIRE SEALANT MATERIAL TO MAINTAIN THE RATING

OF THE SEPARATION.

WHERE MATERIAL IS CALLED OUT IN THE LEGEND BY

MANUFACTURER, TYPE OR CATALOG NUMBER, SUCH

DESIGNATIONS ARE TO ESTABLISH STANDARDS OR

DESIRED QUALITY. ACCEPTANCE OR REJECTION OF

THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT

TO THE APPROVAL OF THE OWNER.

REFER TO ARCHITECTURAL DRAWINGS FOR EXACT

LOCATION OF EQUIPMENT, DEVICES, AND FURNITURE

REQUIREMENTS, PRIOR TO ROUGHING IN FOR SAME.

ALL GENERAL NOTES, SYMBOLS, LISTS, ABBREVIATIONS

AND DETAILS ARE TO BE CONSIDERED APPLICABLE TO

ALL ELECTRICAL DRAWINGS FOR THIS PROJECT.

IN AREAS AFFECTED BY THIS RENOVATION, THE

ELECTRICAL SUBCONTRACTOR SHALL MAINTAIN

CONTINUITY OF EXISTING ELECTRICAL SERVICE.

PRIOR TO REMOVAL OF EQUIPMENT, THE OWNER WILL

INDICATE WHICH EXISTING DEVICES OR MATERIALS

SHALL BE SALVAGED AND TURNED OVER FOR STORAGE.

WHERE EXISTING EQUIPMENT AND DEVICES ARE TO BE

RELOCATED, ALL ASSOCIATED WIRING, CONDUIT AND

ACCESSORIES SHALL BE EXTENDED, RELOCATED OR

REPLACED WHERE REQUIRED.

17.NEW DEVICES SHALL BE RECESSED. SURFACE MOUNTED

DEVICES SHALL ONLY BE USED WHEN SPECIFICALLY

APPROVED BY OWNER AND ARCHITECT. WHEN SURFACE

MOUNTED DEVICES ARE APPROVED THEY SHALL BE

INSTALLED IN A FINISHED WIREMOLD TYPE BOX AND

WIREMOLD WIREMANAGEMENT SYSTEM. SURFACE

MOUNTED CONDUIT AND JUNCTION BOXES WITH

KNOCKOUT LOCATIONS WILL NOT BE ACCEPTED.ALL LIGHT FIXTURES ARE TO BE STANDARD COLOR

3500K UNLESS OTHERWISE NOTED.

ALL LED DRIVERS SHALL HAVE A MINIMUM 5 YEAR

MANUFACTURER'S WARRANTY.

NOT USED.

CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. INSTALL

CONDUIT WITH A MINIMUM OF BENDS RECTILINEAR TO

BUILDING LINES CONSIDERING THE BUILDINGS

CONSTRUCTION AND OBSTRUCTIONS, EXCEPT WHERE

OTHERWISE NOTED.

WHERE A DISCREPANCY OCCURS BETWEEN THE

DRAWINGS AND THE SPECIFICATIONS, THE MOST

STRINGENT SHALL PREVAIL. CONTACT THE

ENGINEER FOR CLARIFICAION WHEN SUCH A

SITUATION OCCURS.

FIRE ALARM RED

BLUE

SIGNAL (NURSE CALL, PA)

AUDIO VISUAL

480V

277V

120V

208V

PURPLE

WHITE

BROWN

ORANGE

BLACK

JUNCTION BOX IDENTIFICATION

COLOR CODE CHART

1.

a.

2.

b.

FIRE ALARM

SYSTEM NOTES

REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES

AND LOCATIONS OF ALL FIRE ALARM DEVICES

ASSOCIATED WITH FIRE PROTECTION SYSTEMS.

c. MAKE ALL CONNECTIONS AS REQUIRED.

PROVIDE ALL REQUIRED PROGRAMMING.d.

MODIFY THE EXISTING NOTIFIER

MAIN FIRE ALARM CONTROL PANEL TO

ACCOMMODATE THE NEW DEVICES INDICATED.

PROVIDE NEW ZONES(IDENTIFY AS REQUIRED).

NEW CONTACTS, ADDITIONAL POWER SUPPLIES

AND ALL OTHER ACCESSORIES FOR A COMPLETE

AND OPERATIONAL SYSTEM.

PROVIDE NEW FIRE ALARM

SPEAKER/STROBES WHERE INDICATED.

PROVIDE NEW FIRE ALARM

STROBES WHERE INDICATED.

E L E C T R I C A L L E G E N D

CIRCUIT NUMBER(S)

PANEL DESIGNATION

WIRING CONCEALED IN WALL OR CEILING

GFI GFCI DUPLEX CONVENIENCE RECEPTACLE - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE

SAME AS ASSOCIATED RECEPTACLE

EXISTING PANELBOARD

PANELBOARD

AC/BATTERY POWERED EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - CEILING MOUNTED

AC/BATTERY POWERED EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - WALL MOUNTED

DIRECTLY ABOVE DOOR

EXISTING ITEMS SHOWN DASHED

DUPLEX CONVENIENCE RECEPTACLE WITH DUAL USB CHARGING PORTS - MOUNTED C/L UP 24" UNLESS NOTED OTHERWISE

DOUBLE DUPLEX CONVENIENCE RECEPTACLE WITH FOUR USB CHARGING PORTS - MOUNTED C/L UP 24" UNLESS NOTED OTHERWISE

THREE-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER INDICATES SWITCH CONTROL

OC WATTSTOPPER DT-300 OCCUPANCY SENSOR AND POWER PACK - PROVIDE NUMBER OF POWER PACKS REQUIRED TO ALLOW FOR NUMBER OF

OCCUPANCY SENSORS AND SWITCHING SHOWN

DIMMER SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - LUTRON DIVA LED 0-10V DIMMING SWITCH MODEL DVSTV

VOICE AND DATA OUTLET - JUNCTION BOX WITH 1" CONDUIT TO 6" ABOVE DROP CEILING - MOUNT UP

REF:B1

--

LIGHT FIXTURE SCHEDULE

REF:B2

--

LEGEND

SINGLE POLE SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER INDICATES SWITCH CONTROL

LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION

ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NO. MTG. VOLTNO. WATT

LAMPS

TYPEREMARKS/BALLAST INFORMATION

LEDUNVRA

3500K

LED

LEDUNVR3500K

LED

LITHONIA38

AE PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.38

LEDUNVS

LED E PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.LQM-S-W-3-R-MVOLT-ELN1

FIRE ALARM LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED - 15/75 WHERE NOT

OTHERWISE INDICATED ON PLANS - CEILING MOUNTED

OTHERWISE INDICATED ON PLANS - CEILING MOUNTED

S

FIRE ALARM SPEAKER/LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED - 15/75 WHERE NOT

EMERGENCY BATTERY UNIT WITH TWO HEADS

LP-1#3 HOMERUN TO PNLBRD

W

WIRELESS ACCESS POINT (WAP)

MANUAL MOTOR STARTER WITH OVERLOAD PROTECTION

J JUNCTION BOX

LED 2x4 FLAT PANEL WITH EMERGENCY BATTERY PACK

LED 2x4 FLAT PANEL

EPANL-2x4-4000-80CRI-35K-MIN10-MVOLT

LED EXIT SIGN WITH EMERGENCY BATTERY PACK - SINGLE OR DOUBLE FACE AND CHEVRONS AS INDICATED ON DRAWINGS

SAME AS ASSOCIATED RECEPTACLE

VOICE OUTLET - JUNCTION BOX WITH 1" CONDUIT TO 6" ABOVE DROP CEILING - MOUNT UP

LITHONIA

LITHONIA

CR

DC

REX

CARD READER- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER

DOOR POSITION SWITCH- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER

ELECTRIC STRIKE- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER

REQUEST TO EXIT PASSIVE INFRARED SENSOR- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER

1.

a.

b.

c.

PROVIDE NEW CARD READERS

WHERE INDICATED.

PROVIDE NEW DOOR CONTACTS

WHERE INDICATED.

PROVIDE NEW REQUEST TO EXIT

DEVICES WHERE INDICATED.

2.

3.

d.

e. PROVIDE NEW ELECTRIC STRIKES

WHERE INDICATED.

CARD ACCESS

SYSTEM NOTES

COORDINATE ALL CARD ACCESS WORK WITH USM

CAMPUS POLICE DEPARTMENT.

ACCESS CONTROL WORK SHALL BE DONE BY

USM SECURITY SYSTEM VENDOR. CONTACT

USM FOR CONTACT INFORMATION OF SECURITY

SYSTEM VENDOR.

PROVIDE CONNECTION TO FIRE

ALARM SYSTEM AS REQUIRED.

MODIFY THE EXISTING CARD ACCESS

SYSTEM PRESENTLY SERVING THE

BUILDING TO ACCOMMODATE THE NEW

DEVICES INDICATED. PROVIDE EXPANSION CARDS

ADDITIONAL POWER SUPPLIES, CABLES AND

ALL OTHER ACCESSORIES FOR A COMPLETE AND

OPERATIONAL SYSTEM.

EPANL-2x4-4000-80CRI-35K-MIN10-MVOLT-E10WCP

LEDUNVRBE

3500K

LED 20

EXTERIOR 20" WIDE MULLION MOUNTED LED LIGHT FIXTURE WITH PHOTOCELL AND REMOTE INVERTER/BATTERY

BLD-24IN-NODIM-2DRV-20W-2100LM-40K-MVOL-DP-SIL-LITHONIA

EMB20R-PC

LEDUNVRA1

3500K

LED

LEDUNVR3500K

LED

LITHONIA45

A1E PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.45

LED 2x4 FLAT PANEL WITH EMERGENCY BATTERY PACK

LED 2x4 FLAT PANEL

EPANL-2x4-4800-80CRI-35K-MIN10-MVOLT

LITHONIA EPANL-2x4-4800-80CRI-35K-MIN10-MVOLT-E10WCP

Harriman Project No.

Drawing Scales

PA / PE:

Drawn By:Harriman Associates

c 2021

Proj NorthKey Plan

GORHAM, MAINE

20478

RENOVATIONS

ATHLETIC TRAINING

HILL GYMNASIUM

SOUTHERN MAINE

UNIVERSITY OF

MAY 17, 2021

CONSTRUCTION DOCUMENTS

Rev Date Revision Description

LEGENDS, NOTES

AND

SCHEDULES

JWT

APG

E00-1

Page 9: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

H1

H2

H3

1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"

GFI

GFI

GFI

UNIT HEATER

PLUGMOLD

C

GFI

OC

OC

OC

OC

W

OC

DEMOLITION NOTES:

LEGEND:

EXISTING EQUIPMENT TO BE DEMOLISHED IS INDICATED AS BOLD AND DASHED:

EXISTING EQUIPMENT TO REMAIN IS INDICATED BY LIGHT AND DASHED:

EXISTING EQUIPMENT TO BE BE MODIFIED IS INDICATED AS BOLD AND DASHED WITH TEXT ADJACENT:(XRE)

DOTTED INDICATES EXISTING EQUIPMENT

(REFER TO LEGEND FOR TYPE)

(EN)EXISTING IN NEW LOCATION

EXISTING

EQUIPMENT LEGEND

(XN)EXISTING TO BE REPLACED WITH NEW

(XRE)EXISTING TO BE RELOCATED

1. ELECTRICAL INDICATED IS AS GENERALLY FOUND (APRIL

2021). THE INTENT OF THE DEMOLITION PLAN(S) IS TO

DOCUMENT EXISTING CONDITIONS. HOWEVER, ALL ELECTRICAL

DEVICES MAY NOT NECESSARILY BE INDICATED ON THE

DRAWINGS. FIELD VERIFY AND ADJUST WORK TO SUIT ALL FOUND.

2. REFER TO FLOOR PLANS TO DETERMINE EXTENT OF WORK

IN EACH AREA, INCLUDING WHETHER DEVICES ARE TO REMAIN,

BE REMOVED, REPLACED, ETC... EXCEPT AS NOTED, GENERALLY

THE INTENT IS THAT IF EXISTING DEVICES ARE SHOWN ON THE

DEMOLITION PLANS AND NEW DEVICES ARE SHOWN ON THE FLOOR

PLANS THEN EXISTING DEVICES ARE TO BE REMOVED. IF EXISTING

DEVICES ARE SHOWN ON BOTH THEN DEVICES ARE TO REMAIN.

3. ALL EXISTING ITEMS INTENDED FOR REMOVAL SHALL BE REMOVED

WITH ALL ASSOCIATED HARDWARE INCLUDING, BUT NOT LIMITED TO:

CONDUIT, BOXES, WIRING, CABLES, HANGERS, ETC...

4. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR

MECHANICAL AND PLUMBING EQUIPMENT TO BE REMOVED. REMOVE

ALL ASSOCIATED CONDUIT, BOXES, WIRING, ETC...

5. CONDUIT IN GOOD CONDITION AND PROPERLY LOCATED MAY BE

REUSED WHERE APPLICABLE, UNLESS NOTED OTHERWISE.

6. IN AREAS NOT RENOVATED BY THIS CONTRACT VERIFY THAT

ELECTRICAL POWER, LIGHTING AND SYSTEMS ARE NOT AFFECTED

BY THE ALTERATIONS. PROVIDE ALL WORK AS REQUIRED TO

MAINTAIN POWER AND PROPER OPERATION OF SYSTEMS.

D01 EXISTING 20 POLE, SUB PANEL 1 PANELBANELBOARD TO BE DEMOLISHED AND REPLACED WITH NEW PANEL P IN ADJACENT MECHANICAL ROOM.

EXISTING 100A SUB PANEL 1 FEEDER TO BE EXTENDED TO NEW PANEL P. ALL EXISTING BRANCH CIRCUITS REMAINING AFTER DEMOLITION TO

BE EXTENDED TO NEW MATCHING BREAKERS IN NEW PANEL P.

D01

J

DOOR

SUB PANEL 1

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

(XRE)

Harriman Project No.

Drawing Scales

PA / PE:

Drawn By:Harriman Associates

c 2021

Proj NorthKey Plan

GORHAM, MAINE

20478

RENOVATIONS

ATHLETIC TRAINING

HILL GYMNASIUM

SOUTHERN MAINE

UNIVERSITY OF

MAY 17, 2021

CONSTRUCTION DOCUMENTS

Rev Date Revision Description

PART

PLAN

EXISTING CONDITIONS

JWT

APG

E05-1

1/8" = 1'-0"

0 4' 8' 12'

Page 10: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

OFFICE

116

OFFICE

113

OFFICE

114

OFFICE

115

SUPPLY ROOM

112S

TOILET

112T

OFFICE

117

WET ROOM

112W

ATHLETIC TRAINING

112

MENS GA LOCKER

ROOM

120

CORRIDOR

111

MECHANICAL

129

H1

H2

H3

ICE

HEAT

1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"

1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"

(EN)

(EN)

(EN)

(EN)

L01

AE

CIRCUIT NEW FIXTURE TO LIGHTING CIRCUIT AND CONTROLS SERVING CORRIDOR 111. PROVIDE UNSWITCHED LEG OF LIGHTING CIRCUIT FOR

EMERGENCY BATTERY BACKUP.

E

L01

CIRCUIT NEW EXIT SIGN TO UNSWITCHED LEG OF LIGHTING CIRCUIT SERVING CORRIDOR 111. L02

L02

(EN)

OC

OC

(EN)

CIRCUIT TO UNSWITCHED LEG OF LIGHTING CIRCUIT SERVING THE ROOM 120. L03

E OC

OC

OC

OC

OC

OC

OC

OC

OC

OC

E

L03

L03

CIRCUIT RELOCATED FIXTURE TO LIGHTING CIRCUIT AND CONTROLS SERVING CORRIDOR ROOM 120.L04

L04

L04

L04

A

A

A

A

A

A

A

A

A

A

AEBE

L01

A1

A1E

A1E

A1E

A1E

A1EA1

A1

A1

A1 A1

A1

A1

A1

A

P#21

PANEL P

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

2121

21

21

21

21

21

Harriman Project No.

Drawing Scales

PA / PE:

Drawn By:Harriman Associates

c 2021

Proj NorthKey Plan

GORHAM, MAINE

20478

RENOVATIONS

ATHLETIC TRAINING

HILL GYMNASIUM

SOUTHERN MAINE

UNIVERSITY OF

MAY 17, 2021

CONSTRUCTION DOCUMENTS

Rev Date Revision Description

PART

PLAN

LIGHTING

JWT

APG

E10-1

1/8" = 1'-0"

0 4' 8' 12'

Page 11: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

OFFICE

116

OFFICE

113

OFFICE

114

OFFICE

115

SUPPLY ROOM

112S

TOILET

112T

OFFICE

117

WET ROOM

112W

ATHLETIC TRAINING

112

MENS GA LOCKER

ROOM

120

CORRIDOR

111

MECHANICAL

129

H1

H2

H3

ICE

HEAT

1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"

C

GFI

J

DOOR

1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"

(EN)

(EN)

CR

DC

J DOORRE

X

WP GFI

GFI

W(EN)

PANEL P

15cd

30cd

GFI

GFI

GFI

75cd

ICE

TUB

P#28

P#26

P#30

P#32

P#24

P#22

P#29

P#37

P#31

P#35

P#21

P#23

P#27

P#25

P01 CIRCUIT NEW DOOR CONTROLLER TO EXISTING CIRCUIT SERVING ADJACENT CARD ACESS CONTROLLED DOOR.

P01

P02 EXTEND EXISTING 100A CIRCUIT FROM EXISTING SUB PANEL 1 PANELBOARD BEING DEMOLISHED TO NEW PANEL P. PROVIDE SPLICE BOX

AND NEW WIRE AND CONDUIT AS REQUIRED. EXTEND EXISTING BRANCH CIRCUITS REMAINING FROM SUB PANEL A AFTER DEMOLITION TO

MATCHING SPARE BREAKERS IN NEW PANEL P. PROVIDE ALL WIRE, CONDUIT AND SPLICE BOXES AS REQUIRED TO EXTEND EXISTING BRANCH

CIRCUITS.

P02

(EN) 75cd

15cd

21

21

21

21

21

2323

23

23

25

25

25

25

27

27

33

3131

31

31

31

33

P#33

35

35

3535

3737

37

37

22

24

26

28

30

32

27

27

MOUNT RECEPTACLE AT 48" AFF.P03

P03

P03

P03

P03

P03

P03

GFI

GFI TUB

TUB

P03

P03

P03

P03

P03

29

29

GFI

P0322

22

27

39

P#39

HEAT BOX

AHU-1

ERV-1

IU-1

IU-3

IU-2

OU-1

WP

P#38,40

P#34,36

34,3638,40

J ATC

J ATC

P#41

41

41

3#4+1#10G IN 1"C.P04

P04

P04

P#42,44

42,44

42,44

42,44

P#46,48,50

46,48,50

Harriman Project No.

Drawing Scales

PA / PE:

Drawn By:Harriman Associates

c 2021

Proj NorthKey Plan

GORHAM, MAINE

20478

RENOVATIONS

ATHLETIC TRAINING

HILL GYMNASIUM

SOUTHERN MAINE

UNIVERSITY OF

MAY 17, 2021

CONSTRUCTION DOCUMENTS

Rev Date Revision Description

PART

PLAN

POWER

JWT

APG

E20-1

1/8" = 1'-0"

0 4' 8' 12'

Page 12: ABBREV DESCRIPTION PIPING LEGEND DUCTWORK LEGEND GENERAL NOTES

ID ID

WATT LOADS

MOUNTING:

LOCATION:

LOAD DESCRIPTION

AM

P

PO

LE

CRKTDWG

NO. PO

LE

WATTSPH A PH B PH C

WATTS

PO

LE

CRKTDWG

NO. PO

LE

AM

P

LOAD DESCRIPTION

FEEDER:AIC RATING:MAIN BREAKER:VOLTAGE:

BUSES:PH & WIRES:

120/208

3P 4W

225

100A MAIN BRKR

10K AIC

SURFACE

MECHANICAL RM

SEE DRAWINGP

TUB 1 OF 1 - REMARKS:

RELOCATED EXISTING LOAD 20 1 1 400 800 --- --- 400 2 2 1 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 15 2 3 3 2496 --- 1648 --- 400 4 4 1 20 EXISTING RELOCATED LOAD

- - - 5 --- --- 1648 400 6 6 1 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 20 1 7 7 400 800 --- --- 400 8 8 1 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 20 1 9 9 400 --- 800 --- 400 10 10 1 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 20 2 11 11 3328 --- --- 2064 400 12 12 1 20 EXISTING RELOCATED LOAD

- - - 13 2064 --- --- 400 14 14 1 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 20 1 15 15 400 --- 2064 --- 3328 16 16 2 20 EXISTING RELOCATED LOAD

RELOCATED EXISTING LOAD 20 1 17 17 400 --- --- 2064 18 - - -

RELOCATED EXISTING LOAD 20 1 19 19 400 800 --- --- 400 20 20 1 20 EXISTING RELOCATED LOAD

OFFICE 113 RCPTS 20 1 21 1200 --- 1800 --- 600 22 1 20 RM 112W RCPT

OFFICE 114 RCPTS 20 1 23 23 1000 --- --- 2000 1000 24 24 1 20 RM 112W RCPT

OFFICE 114 RCPTS 20 1 25 25 1000 2000 --- --- 1000 26 26 1 20 RM 112W RCPT

ROOM 112 RCPTS 20 1 27 27 1000 --- 2000 --- 1000 28 28 1 20 RM 112W RCPT

ROOM 112 RCPTS 20 1 29 29 800 --- --- 1800 1000 30 30 1 20 RM 112W RCPT

ROOM 112 RCPTS 20 1 31 31 800 1800 --- --- 1000 32 32 1 20 RM 112W RCPT

ROOM 112/112T RCPTS 20 1 33 33 400 --- 986 --- 1171 34 2 15 ERV-1

OFFICE 116 RCPTS 20 1 35 35 1000 --- --- 1586 36 - - -

OFFICE 117 RCPTS 20 1 37 37 1000 2123 --- --- 2246 38 38 2 15 ERV-1

ROOM 112 HEAT BOX RCPT 20 1 39 1000 --- 2123 --- 40 - - -

ATC J-BOXES 20 1 41 200 --- --- 368 337 42 2 15 IU-1, IU-2, IU-3

SPARE 20 1 43 0 168 --- --- 44 - - -

SPARE 20 1 45 0 --- 4803 --- 14410 46 46 3 60 OU-1

SPARE 20 1 47 0 --- --- 4803 48 - - -

SPARE 30 3 49 0 4803 --- --- 50 - - -

- - - 51 --- 0 --- 0 52 1 20 SPARE

- - - 53 --- --- 0 0 54 1 20 SPARE

TOTAL AMPS: 133.1 15358 16223 16333 TOTAL WATTS: 47914

REMARKS:

04/28/2021

Harriman Project No.

Drawing Scales

PA / PE:

Drawn By:Harriman Associates

c 2021

Proj NorthKey Plan

GORHAM, MAINE

20478

RENOVATIONS

ATHLETIC TRAINING

HILL GYMNASIUM

SOUTHERN MAINE

UNIVERSITY OF

MAY 17, 2021

CONSTRUCTION DOCUMENTS

Rev Date Revision Description

PANEL

SCHEDULES

JWT

APG

E60-1