Air Circuit Breakers

Motors | Energy | Automation | Coatings

Page 2: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW2

ABW Air Circuit Breaker

Designed for the protection of high power electrical circuits, the ABW Air Circuit Breakers are state of the art in terms of technology and design.The characteristics that make this line stand out, include:

Modular design, with only 3 frames:

ABW16 ABW20...32

ABW40...50

Wide range of current adjustment:

High short circuit interruption capacity, with Ics = 100% Icu in all the line

Icu=Ics @ 480V

ABW16 65 kA

ABW20...32 85 kA

ABW40...50

Available in two installation versions: FIXED and WITHDRAWABLE

Full line of accessories

ABW16 384...1600A

ABW20 480...2000A

ABW25 600...2500A

ABW32 768...3200A

ABW40 480...4000A

ABW50 600...5000A

Microprocessed electronic protection units, with LSI(G)1 functions and the possibility of network communication.

100 kA

1) Further details on page 13.

Page 3: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 3

ABW Air Circuit Breaker

Withdrawable Rack(withdrawable

version only)

Arc extinction chambersControl Terminals

Suspension slots

Protection Unit

Spring loading lever

OffButton

On Button

Status IndicatorOn / Off

Spring Charge Indicator – Charged / Not charged

Opening for withdrawing bar (withdrawable version only)Position locked by padlock (withdrawable version only)

Position Indicator – Inserted / Test / Withdrawn (withdrawable version only)

OperationsCounter

Withdrawing rail (withdrawable version only)

Constructive Characteristics

Page 4: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW4

Applications

ABW16 ABW20 ABW25 ABW32 ABW40 ABW50

Max. Rated Current - In max. (A) (40°C) 1600 2000 2500 3200 4000 5000

Rated Operating Voltage - Ue (V) 690

Rated Insulation Voltage - Ui (V) 1000

Impulse Voltage - Uimp (kV) 8

Frequency (Hz) 50 / 60

Number of poles 3

Versions Fixed and Withdrawable

Protection Units Electronic

Rated ultimate short-circuit breaking capacity

220/380/415V 65 85 100

440V 65 85 100

500V 65 85 100

600V 50 65 85

690V 50 50 50

Rated service short-circuit breaking capacity

220/380/415V 65 85 100

440V 65 85 100

500V 65 85 100

600V 50 65 85

690V 50 50 50

Short circuit supportability - Icw (kA)

1s 65 65 85

2s 60 60 65

3s 50 60 65

Short circuit establishment capacity (peak values) - Icm (kA)

220/380/415V 143 187 220

440V 143 187 220

500V 143 187 220

600V 105 143 187

690V 105 105 105

Use category B

Operating time (ms)Opening ≤ 40

Closing ≤ 80

Mechanical life (nº of operations) 12000 10000

Electrical life (nº of operations) 3000

Altitude (m) ≤ 2000 (1)

Ambient temperatureOperation -5...40°C (2)

Storage -20...60°C

Thermal power dissipation at rated current (W) 52 160 250 410 960 1500

Weight (kg)Withdrawable (3) 64 92 93 95 240 240

Fixed 41 60 61 63 115 115

Connection terminalsWithdrawable Horizontal Vertical

Fixed Horizontal Horizontal

Dimensions Withdrawable 339x435x379 474x435x379 961x459x379

W x H x D (mm) Fixed 315x410x295 450x410x295 840x410x295

(1) For installation above 2000m from sea level, please consider derating factors on page 20.(2) For ambient temperature above 40°C, check maximum rated current values in the table on page 20.(3) Include withdrawable rack.

Page 5: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 5

ABW16D3F-022-A-116-0000

WEG Air Circuit Breaker

Max. Rated Current

16 – 1600A20 – 2000A25 – 2500A32 – 3200A40 – 4000A50 – 5000A

Motorized Operation0 – Without Mot. Operation1 – 110...120 Vac/dc2 – 220...240 Vac/dc3 – 125 Vdc

TypeD – Cir. Breaker I – Interruptor

N° of Poles3 – 3 Poles

VersionF – FixedE – Withdrawable

Auxiliary Contacts

A – 5NO+5NC

Opening Coil2 – 110...240 Vac/dc

Closing Coil2 – 110...240 Vac/dc

Protection UnitStandard Units:116 – LSI (60Hz) for ABW16...32216 – LSIG (60Hz) for ABW40...50

Optional Units:115 – LSI (50Hz) for ABW16...32215 – LSIG (50Hz) for ABW40...50316 – LSIG (60Hz) + communica-tion for ABW16...50315 – LSIG (50Hz) + communica-tion for ABW16...50000 – Without Protection Unit

Accessories supplied as standard for all line: Accessories supplied as optionals:

g Motorized Operation

g Under Voltage Coil

g Capacitive trigger unit

g Key lock

g Key interlock

g Door Frame

g Transparent Cover

g Mechanical Interlock

g Door Interlock

g Position Auxiliary Contacts

g Vertical Terminals

Under Voltage Coil00 -Without Under Voltage Coil11 - 110 Vac, instantaneous12 - 220 Vac, instantaneous13 - 380 Vac, instantaneous14 - 460 Vac, instantaneous51 - 110 Vac, timed (3s)52 - 220 Vac, timed (3s)53 - 380 Vac, timed (3s)54 - 460 Vac, timed (3s)

Key lock0 - Without key lock1- Key lock(for 1 circuit breaker)3- Key interlock (for 3 circuit breakers)

Mechanical Interlock0 - Without Mechanical Interlock1- Mechanical Interlock for 2 circuit breakers2- Door interlock

g Auxiliary Contacts (5NO+5NC)

g Alarm Contacts

g Opening Coil 110...240 Vac/dc

g Closing Coil 110...240 Vac/dc

g Operations Counter

g Insulating Plates

g Position Locking with Padlock

(padlock not included) – withdrawable version only

g Position Indicator (Inserted /Test/ Withdrawn) –

withdrawable version only

Codification

Page 6: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW6

Operating System

ABW air circuit breakers operate through a spring system, which can be manually charged through a front lever, or electrically through a motor (supplied as an accessory).

With the springs charged, situation in which the charge indicador shows “CHARGED”, the circuit breaker can be operated locally using the On and Off buttons.

OFF BUTTON

ON / OFFINDICATOR

SPRING CHARGE INDICATOR

CHARGE LEVERON BUTTON

In relation to the installation version, the circuit breakers can be installed as fixed or as withdrawable. The withdrawable version is indicated for applications where eventual replacement or maintenance must be done in the shortest time possible.These curcuit breakers can be positioned at three distinct points in the withdrawable rack:

Inserted: in this position both the power and control circuits are connected. The position indicator shows “CONNECTED”.

Test: position in which the control circuits are connected. The indicator shows “TEST”.

Withdrawn: both circuits are disconnected. The indicator shows “DISCONNECTED”.

Position Indicator

Remote operation is also possible through the closing and opening coils installed inside the circuit breaker. The closing coil is equipped with an “anti-pumping” electronic circuit, which prevents successive re-connections in a single command.

Another feature of the circuit breaker is the indicator on the front showing the status of the product: ON or OFF.

Page 7: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 7

These coils allow remote closing of the circuit breaker through electrical control. This remote control is valid only if the springs of the operating mechanism are charged.Supplied as standard in all circuit breakers.

Auxiliary Contacts

Show circuit breaker status – On or Off.Supplied as standard in all circuit breakers.

Configuration 5NO + 5NC

Switch capacity (A)

Operating Voltage Resistive load Inductive load

125 Vac 10 10

250 Vac 10 10

460 Vac 5 2

30 Vdc 10 6

125 Vdc 0.6 0.6

250 Vdc 0.3 0.3

These contacts are incorporated into the protection units and indicate trigger occurrence for any of the protection functions.

0.85...1.1 x Un

Consumption (A)

Operating voltage Energization Nominal Operation

110...120 Vac/dc 2 1

220...240 Vac/dc 3 1.3

125 Vdc 2.3 1

Closing time (ms) ≤ 80

“Anti-pumping” characteristic Yes, through electronic circuit

Minimum supply time for operation (ms) 100

Supply Voltage Reference

110...220 Vac/dc ABW-CC 110/220V

Configuration 2NO (generic) + 4NO (individual)

Switch capacity (A)

Operating Voltage Switch Capacity

250 Vac 5

380 Vac 3

30 Vdc 5

125 Vdc 1

Minimum application levels 5 Vdc / 10 mA

Alarm Contacts

Closing coil

Accessories

Page 8: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW8

Opening Coil

These coils allow remote opening of the circuit breaker through electric control.Supplied as standard in all circuit breakers.

0,70...1,1 x Un

Consumption (A) 2

Operating Voltage Energization Nominal Operation

110...120 Vac/dc 2 1

220...240 Vac/dc 3 1.3

125 Vdc 2.3 1

Closing time (ms) ≤ 40

Supply Voltage Reference

110...220 Vac/dc ABW-ST 110/220V

Motorized Operation

Motorized operation is used for automatic charging of the circuit breaker springs operating mechanism. Its operation begins immediately after curcuit breaker opening and at the end of this process an auxiliary contact indicates that the springs are charged.Even with the motorized operation installed, it is still possible to charge the springs manually through the front rod.

0.85...1.1 x Un

Consumption (A) 2

Operating Voltage Energization Nominal Operation

110...120 Vac/dc 7 3.5

220...240 Vac/dc 7 3.5

125 Vdc 7 3.5

Operating time (to charge springs) (s) ≤ 5

Charged Spring Auxiliary Contact

Supplied incorporated into the motorized operation.

Supply Voltage Reference

110 Vac/dc ABW-M 110V

220 Vac/dc ABW-M 220V

125 Vdc ABW-M 125VDC

Operating Voltage Resistive load Inductive load

Switch capacity (A)

120...125 Vac 10 10

240...250 Vac 10 10

460 Vac 5 .,5

30 Vdc 10 10

125 Vdc 10 6

250 Vdc 3 1.5

Accessories

Page 9: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 9

Under Voltage Module

Power Supply

Trip Button C NO NC

Auxiliary Contacts

Circuit Breaker

Under Voltage Coil

Under Voltage CoilAutomatically disconnects the circuit breaker in cases of undervoltage or phase loss in control circuit. It consists of a coil and a control module, available in two versions: instantaneous trip or delayed.

Coil ABW-UVT COIL

Supply VoltageReferences

(instantaneous performance)References

(delayed performance)

Module 110 Vac ABW-UVT1 110VAC ABW-UVT5 110VAC

Module 220 Vac ABW-UVT1 220VAC ABW-UVT5 220VAC

Module 380 Vac ABW-UVT1 380VAC ABW-UVT5 380VAC

Module 460 Vac ABW-UVT1 460VAC ABW-UVT5 460VAC

Pick-up voltage 0.85...1.1 x Un

Drop-out voltage 0.3...0.7 x Un

Performance time (instantaneous) ≤200ms

Operation time (with delay) 3s

Connection diagram - Instantaneous version

Connection diagram - Delayed version

Accessories

UC+ UC-

Under Voltage Module

Power Supply

Trip Button

Circuit Breaker

Under Voltage Coil

Page 10: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW10

Position Auxiliary Contacts

Enables remote indication of circuit breaker position inside withdrawable rack.

Key interlock

Circuit Breakers Reference

ABW 16...50 (withdrawable) ABW-PS4

Configuration2NO for INSERTED position

1NO for TEST position1NO for WITHDRAWN position

Resistive load Inductive load

Switch capacity (A)

125 Vac 10 10

250 Vac 10 10

460 Vac 5 2.5

30 Vdc 10 10

125 Vdc 10 6

250 Vdc 3 1.5

Used to interlock 3 circuit breakers in the following configuration:

Circuit Breakers Reference

ABW 16...50 ABW-KI

ABW1 ABW2 ABW3

On Off On

On On Off

Off On On

Vertical Terminals

Used to convert the circuit breaker terminals to the vertical position. They are supplied in individual pieces.

Circuit breakers Terminals References

ABW16 Upper/Lower ABW-VT16

ABW20,25,40,50 Upper ABW-VT25S

ABW20,25,40,50 Lower ABW-VT25I

ABW32 Upper ABW-VT32S

ABW32 Lower ABW-VT32I

Accessories

Page 11: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 11

AccessoriesCapacitive Trigger Unit

This device provides the possibility of turning off the circuit breaker in case of control voltage loss. It acts through the discharge of a capacitor over the opening coil, and the stand-alone running period is indicated in the table below. It comes with a capacitor charge signal light and a button to discharge it. Panel door installation.

Supply Voltage References

100...110 Vac ABW-CTD 100-110VAC

200...220 Vac ABW-CTD 200-220VAC

Operating voltage 0.85...1.1 x Un

Capacitor charging time (s) ≤ 5

Stand-alone Running period (minutes)3 (ABW-CTD 100-110VAC)

2 (ABW-CTD 200-220VAC)

Connection diagram

Capacitive trigger unit

AC (input)

OFF Button

Circuit Breaker

Opening Coil

SW1To discharge the capacitor

DC (Output)

Page 12: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW12

Circuit Breakers References

ABW16 ABW-DF16

ABW20...50 ABW-DF32

Protection Degree IP 3x

Key lock

Circuit breaker locked in off position.

Circuit Breakers Reference

ABW16...50 ABW-KL

Door frame

Finish frame for panel door.

Transparent cover

Curcuit breaker can be viewed without having to open the panel door.

Circuit Breakers References

ABW16 ABW-DC16

ABW20...50 ABW-DC32

Protection Degree IP 5x

Mechanical Interlock

Enables two circuit breakers to be connected simultaneously through flexilbe cables.

Door Interlock

Prevents panel door from being opened when circuit breaker is on.

Circuit Breakers Reference

ABW16...50 ABW-DI

Cable length (m) 1.6

Accessories

Circuit Breakers Reference

ABW16...50 ABW-MI1

Cable length (m) 1.6

Page 13: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 13

Accessories

On ABW air circuit breakers, protection against over currents is performed through the ABW-OCR electronic protection units. The ABW-OCR116 is supplied as standard for the ABW16...32 circuit breakers and offers protection against overload (L), timed short circuit (S) and instantaneous short circuit (I), adjusted through selectors on the front. The ABW-OCR216 unit is supplied as standard for ABW40...50 circuit breakers and beside the protections listed above, provides protection against Ground loss (G). Supplied as an option, the ABW-OCR316 unit further enables network communication.

ABW-OCR116 ABW-OCR115 ABW-OCR216 ABW-OCR215 ABW-OCR316 ABW-OCR315

For circuit breakers ABW16...32 ABW40...50 ABW16...50

Supply voltage 110...220 Vac/dc 110...220 Vac/dc 110...220 Vac/dc

Consumption 5 VA 5 VA 5 VA

Supply frequency 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz

Protection functions

L - Overload

S - Short circuit (timed)

I - Short circuit (instantaneous)

G - Ground loss -

Trigger pre-alarm

Discrimination / Indication of trigger cause

Events record (losses)

Nº of storage records 10 10 10

Events sequence -

Loss current value information

Performance time information

Parameterization

Front adjustment knobs - -

Display+navigation keys -

Parameterization password -

Instantaneous current by phase indication

Self-diagnosis function

Test function (trigger, auxiliary contacts and LEDs)

Network communication - -

Door - - RS485

Protocol - - DNP 3.0

Transmission rate - - 9600 bps

(4) Except for protection function I (instantaneous short circuit).(5) The display enables the adjusted values to be viewed on the SETTING menu.

ProtectionUnits

(4) (4) (4)

(5)

Page 14: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW14

Technical Characteristics

UABW-OCR116

The characteristics of the ABW-OCR116 protection unit meet all requirements for most systems and applications. This unit offers the main protections (L, S and I) and has a wide current and trigger time adjustment range. It is standard supplied for ABW16...32. circuit breakers

Display

Its initial screen displays the instantaneous currents by phase. Other information can also be accessed through other menus.

Signalling LEDs

Indicates general status of circuit breaker.

LED FUNCTION

RUN Indicates circuit breaker on

LTD Indicates trigger by overload (L)

STD Indicates trigger by timed short circuit (S)

INST Indicates trigger by instantaneous short circuit (I)

PAL Indicates pre-alarm

PICK UP Indicates start of trigger timing

Navigation keys

Selector switches for protection functions

Parameters Function / Adjustment Ranges

InRated Current (0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0) x In max.

IcTrigger current by overload (protection function L) (0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0) x In

LTDCurrent delay time Ic(15 - 30 - 60 - 120 - 240 - 480)s @ 1.5 x Ic [Tolerance: ±10%]

Is

Trigger current by timed short circuit (Protection function S)(2 - 3 - 4 - 6 - 8 - 10 - OFF) x In [Tolerance: ±15%]

STDCurrent delay time Is(0.05 - 0.1 - 0.2 - 0.3 - 0.4 - 0.5)s @ 10 x In [Tolerance: ±15%]

li

Trigger current by instantaneous short circuit (protection function I)(4 - 6 - 8 - 10 - 12 - 16 - OFF) x In [Tolerance: ±20%]

lpPre-alarm current(0.7 - 0.8 - 0.9 - 0.95 - 1.0 - OFF) x Ic [Tolerance: ±10%]

Used for navigating among the available menus.

Page 15: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 15

Protection Units

Characteristic Curves - ABW-OCR116

Current (%)

Per

form

ance

Tim

e (%

)

Pre-alarm current Ip

Time LTD (s)

Current Is

Current Is

Current Is

Time STD (s)

Current Ii

Page 16: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW16

Connection Diagram - ABW-OCR116

Protection Units

T0~T

5 A

larm

Con

tact

s (in

divi

dual

s)R

+ R

2-P

rote

ctio

n U

nit P

ower

Sup

ply

M+

M-

Mot

oriz

ed O

pera

tion

T0C

omm

onA

l1+

Al1

-A

larm

con

tact

s (g

ener

ics)

TS+

TS

-C

harg

ed S

prin

gs A

uxilia

ry C

onta

cts

T1-

Func

tion

L (o

verlo

ad)

Al2

+ A

l2-

B6~

B10

Aux

iliary

Con

tact

s (N

C)

T2-

Func

tion

S (t

imed

sho

rt-ci

rcui

t)U

+ U

-U

nder

Vol

tage

Coi

l (*)

A1~

A5

Aux

iliary

Con

tact

s (N

O)

T3Fu

nctio

n I (

inst

anta

neou

s sh

ort-

circ

uit)

S+

S-

Ope

ning

Coi

lC

LP

ositi

on A

uxilia

ry C

onta

cts

(with

draw

able

C

ircui

t Bre

aker

onl

y)

T5P

re-a

larm

CC

+ C

C-

Clo

sing

Coi

l

(*) C

onne

ct o

n un

derv

olta

ge m

odul

e -

see

page

9

PR

OTE

CTI

ON

UN

IT

Page 17: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 17

ABW-OCR216 / 316

Protection Units

These units were developed to meet the demands of appplications and electrical systems with high technical requirements.In addition to the main protection functions (L, S and I), they offer protection against Ground loss (G) and have a greater trigger current and time adjustment range.The ABW-OCR316 model is further equipped with a RS485 communication door which, through DNP3.0 communication protocol, enables the monitoring of instantaneous currents, circuit breaker status and the occurrence of events.The ABW-OCR216 unit is supplied as standard for the ABW40...50 circuit breakers, while the ABW-OCR316 unit is supplied as an option for the entire line.

Technical Characteristics

Display

Its initial screen displays the instantaneous currents by phase. Other information can also be accessed through other menus.

Navigation keys

Used for navigating among the available menus and protection function adjustment.

Parameter Function / Adjustment Range

InRated current (0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0) x In max.

Ic

Trigger current by overload(protection function L) (0.6 - 0.65 - 0.7 - 0.75 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0) x In

LTDCurrent delay time Ic(15 - 20 - 25 - 30 ... 465 - 470 - 475 - 480 - NO)s @ 1.5 x Ic [Tolerance: ±10%]

Is

Trigger current by timed short circuit (Protection function S)(1.5 - 2 - 2.5 - 3.0 ... 8.5 - 9 - 9.5- 10 - NO) x In [Tolerance: ±15%]

STD

Current delay time Is(0,05 - 0,06 - 0,07 ... 0,48 - 0,49 - 0,5)s @ IO x In [Tolerance: ±15%]

li

Trigger current by instantaneous short circuit (protection function I)ABW16...40: (2 - 3 - 4 ... 14 - 15 - 16 - NO) x In [Tolerance: ±15%]ABW50: (2 - 3 - 4 ... 10 - 11 - 12 - NO) x In [Tolerance: ±15%]

lpPre-alarm current(0.7 - 0.8 - 0.9 - 1.0) x Ic [Tolerance: ±10%]

Ig

Ground loss current(0,2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0 - NO) x .n max. [Tolerance: ±20%]

GTD Current delay time Ig(0.1 - 0.2 - 0.3 ... 2.8 - 2.9 - 3.0)s [Tolerance: ±20%]

LED FUNCTION

RUN Indicates circuit breaker on

PICK UP Indicates start of trigger timing

FAULT Indicates trigger

Signalling LEDs

Indicates general status of circuit breaker.

Page 18: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW18

Protection Units

Characteristic Curves - ABW - OCR 216/316

Current (%)

Per

form

ance

tim

e (%

)

Pre-alarm current Ip Time LTD (s)

Time GTD (s) Current Is

Current Ig

Time STD (s)

Current Ii

Page 19: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 19

Connection diagram - ABW-OCR216/316

Protection Units

T0~T

5 A

larm

Con

tact

s (in

divi

dual

s)R

+ R

2-P

rote

ctio

n U

nit P

ower

Sup

ply

M+

M-

Mot

oriz

ed O

pera

tion

T0C

omm

onA

l1+

Al1

-A

larm

con

tact

s (g

ener

ics)

TS+

TS

-C

harg

ed S

prin

gs A

uxilia

ry C

onta

cts

T2Fu

nctio

n L

(ove

rload

)A

l2+

Al2

-B

6~B

10A

uxilia

ry C

onta

cts

(NC

)

Func

tion

S (t

imed

sho

rt-ci

rcui

t)U

+ U

-U

nder

Vol

tage

Coi

l (*)

A1~

A5

Aux

iliary

Con

tact

s (N

O)

T3Fu

nctio

n I (

inst

anta

neou

s sh

ort-

circ

uit)

S+

S-

Ope

ning

Coi

lC

LP

ositi

on A

uxilia

ry C

onta

cts

(with

draw

able

C

ircui

t Bre

aker

onl

y)

T4Fu

nctio

n G

(Gro

und

Loss

)C

C+

CC

-C

losi

ng C

oil

485+

485

-C

omm

unic

atio

n (D

NP

3.0

)

T5P

re-a

larm

(*) C

onne

ct o

n un

derv

olta

ge m

odul

e -

see

page

9

PR

OTE

CTI

ON

UN

IT

COMMUNICATION

Page 20: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW20

Protection Units

For ABW circuit breaker application in environments with temperatures exceeding 40°C, refer to the maximum rated current values shown in the following table.

Maximum Rated Current (A)

Ambient Temperature ABW16 ABW20 ABW25 ABW32 ABW40 ABW5040°C 1600 2000 2500 3200 4000 5000

45°C 1600 2000 2500 3200 4000 5000

50°C 1600 2000 2500 3200 4000 5000

55°C 1550 2000 2450 3000 3900 4850

60°C 1500 2000 2350 2900 3750 4700

Altitude Influence

For ABW circuit breaker application in altitudes exceeding 2000m, refer to the rated voltage and current reduction factors presented in the following table.

Altitude - hRated Voltage

Reduction FactorRated current Reduction Factor

h ≤ 2000m 1.00 1.00

2000 < h ≤ 2600m 0.95 0.99

2600 < h ≤ 3900m 0.80 0.96

Temperature Influence

Page 21: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 21

Dimensions (mm)

ABW16 – Fixed Version

Door seat for ABW16...50 (Fixed) (without frame)

ABW16 (Fixed) - Front View

Reference Line of theCircuit Breaker

ABW16 (Fixed)

ABW16 (Fixed) - Side View ABW16 (Fixed) - Rear View

Reference Line of theCircuit Breaker

Mounting Points

Module

Undervoltage

Page 22: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW22

Dimensions (mm)

ABW16 – Withdrawable version

ABW 16 (Withdrawable) Side View ABW 16 (Withdrawable)

Rear View

ABW 16 (Withdrawable)Front View

ABW 16 (Withdrawable) Horizontal Terminals

Door seat ABW 16...32 (Withdrawable) (without frame)

Reference Line of the Circuit Breaker

Mounting Points

Mounting Points

Pos. Disconnected

Position Auxiliary Contacts

Insulating Plates

Pos. TestPos. Connected

under voltage module

15

Page 23: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 23

Dimensions (mm)

ABW20...32 – Fixed Version

20

ABW20...32 (Fixed)Front View

Door seat for ABW16...50 (fixed) (without frame)

ABW20...32 (Fixed) Side View

ABW20...32 (Fixed) Rear View

ABW20...32 (Fixed) Horizontal Terminals

Reference Line of theCircuit Breaker

Undervoltage module

Reference Line of theCircuit Breaker

Mounting Points

Page 24: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW24

Dimensions (mm)ABW20...32 – Withdrawable version

ABW20...32 (Withdrawable) Front view

Door seat ABW 16...32 (Withdrawable) (without frame)

Door seat for ABW 20 (Withdrawable) Horizontal Terminals

Door seat ABW 20...32 (Withdrawable)

Door seat ABW 20 (Withdrawable) Horizontal Terminals

Reference Line of theCircuit Breaker

Reference Line of theCircuit Breaker

Mounting Points

Mounting Points

Undervoltage module

Pos. Disconnected Pos. Test

Pos. ConnectedPosition Auxiliary Contacts

* Applicable for circuit breaker ABW32

* Applicable for circuit breaker ABW32

Insulating Plates

20 (2

5)*

20 (2

5)*

Page 25: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 25

Dimensions (mm)ABW40...50 – Fixed Version

ABW40...50 (Fixed) Horizontal Terminals

ABW40...50 (Fixed) - Side View ABW40...50 (Fixed) - Rear View

ABW40...50 (Fixed) - Front View

Door seat forABW 16...50 (Fixed) (without frame)

Reference Line of theCircuit Breaker

Mounting Points

Reference Line of theCircuit Breaker

Undervoltage module

Page 26: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW26

Dimensions (mm)

ABW40...50 – Withdrawable Version

14

14

ABW40...50 (Withdrawable) - Front View Door seat ABW40...50 (Withdrawable) (without frame)

ABW40...50 (Withdrawable) - Side View ABW40...50 (Withdrawable) - Rear View

ABW40...50 (Withdrawable) Vertical Terminals

Reference Line of theCircuit Breaker

Reference Line of theCircuit Breaker

Reference Line of theCircuit Breaker

Mounting Points

Mounting Points

Undervoltage module

Projection of the base plate

Pos. DisconnectedPos. Test

Pos. ConnectedPosition Auxiliary Contacts

Insulating Plates

Page 27: ABW Air Circuit Breaker

www.weg.net

Air Circuit Breaker ABW 27

Dimensions (mm)

ABW-DF16

ABW-DF32

ABW-CTD Installation – Free Space

ABW-CTD

ABW-DF32 - Front / Side View ABW-DF32 - Door seat

ABW-DF16 - Door seatABW-DF16 - Front / Side View

* Applicable for circuit breaker ABW40 and ABW50

(withdrawable)

Page 28: ABW Air Circuit Breaker

1005

.00/

0420

09 -

Sub

ject

to a

ltera

tions

with

out p

rior

notic

e.

The

info

rmat

ion

cont

aine

d is

for

refe

renc

e on

ly.

WEG Worldwide Operations

ARGENTINAWEG EQUIPAMIENTOS ELECTRICOS S.A.(Headquarters San Francisco-Cordoba)Sgo. Pampiglione 4849Parque Industrial San Francisco2400 - San FranciscoPhone(s): +54 (3564) 421484Fax: +54 (3564) [email protected]/ar

AUSTRALIAWEG AUSTRALIA PTY. LTD.3 Dalmore DriveCarribean Park Industrial EstateScoresby VIC 3179 - MelbournePhone(s): 61 (3) 9765 4600Fax: 61 (3) 9753 [email protected]/au

BELGIUM WEG BENELUX S.A.Rue de l’Industrie 30 D, 1400 NivellesPhone(s): + 32 (67) 88-8420Fax: + 32 (67) 84-1748 [email protected]/be

CHILEWEG CHILE S.A.Los Canteros 8600 La Reina - SantiagoPhone(s): (56-2) 784 8900Fax: (56-2) 784 [email protected]/cl

CHINAWEG (NANTONG) ELECTRIC MOTOR MANUFACTURING Co., Ltd.No. 128 - Xinkai Nan Road,Nantong Economic and Technological Development AreaJiangsu Province, China PC226010 Phone(s): 86 513 8598 9329Fax: 86 513 8592 [email protected]/cn

COLOMBIAWEG COLOMBIA LTDACalle 46A N82 - 54Portería II - Bodega 7 - San Cayetano II - BogotáPhone(s): (57 1) 416 0166Fax: (57 1) 416 [email protected]/co

WEG Equipamentos Elétricos S.A.International Division Av. Prefeito Waldemar Grubba, 3000 89256-900 - Jaraguá do Sul - SC - Brazil Phone: 55 (47) 3276-4002 Fax: 55 (47) 3276-4060 www.weg.net

FRANCEWEG FRANCE SASZI de Chenes – Le Loup13 Rue du Morellon – BP 73838297 Saint Quentin FallavierPhone(s): +33 (0) 4 74 99 11 35Fax: +33 (0) 4 74 99 11 [email protected]/fr

GERMANYWEG GERMANY GmbHAlfred-Nobel-Str. 7-9D-50226 FrechenPhone(s): +49 (2234) 9 5353-0Fax: +49 (2234) 9 [email protected]/de

INDIAWEG Electric (India) Pvt. Ltd.#38, Ground Floor, 1st Main Road, Lower Palace Orchards,Bangalore – 560 003Phone(s): +91-80-4128 2007 +91-80-4128 2006 Fax: +91-80-2336 7624 [email protected]/in

ITALYWEG ITALIA S.R.L.V.le Brianza 20 - 20092 - Cinisello Balsamo - MilanoPhone(s): (39) 02 6129-3535Fax: (39) 02 [email protected]/it

JAPANWEG ELECTRIC MOTORSJAPAN CO., LTD.Matsumoto Bldg. 2F, 3-23-7 Kamata, Ohta-ku,Tokyo, Japan 144-0052Phone(s): (81) 3 3736-2998Fax: (81) 3 [email protected]/jp

MEXICOWEG MEXICO, S.A. DE C.V.Carretera Jorobas-Tula Km. 3.5, Manzana 5, Lote 1 Fraccionamiento Parque Industrial - Huehuetoca, Estado de México - C.P. 54680Phone(s): + 52 (55) 5321 4275Fax: + 52 (55) 5321 [email protected]/mx

NETHERLANDSWEG NETHERLANDS Sales Office of WEG Benelux S.A.Keulenstraat 4E 7418 ET DeventerPhone(s): +31 (0) 570-620550Fax: +31 (0) [email protected]/nl

PORTUGALWEG EURO - INDÚSTRIA ELÉCTRICA, S.A.Rua Eng. Frederico UlrichApartado 6074 4476-908 - MaiaPhone(s): +351 229 477 705Fax: +351 229 477 [email protected]/pt

RUSSIAWEG RUSSIA Pochainskaya Str. 17 Nizhny Novgorod 603001 - Russia Phone(s): +7-831-2780425 Fax: [email protected] www.weg.net/ru

SPAINWEG IBERIA S.L. Avenida de la Industria,2528823 Coslada - MadridPhone(s) : (34) 916 553 008Fax : (34) 916 553 [email protected]/es

SINGAPOREWEG SINGAPORE PTE LTD159, Kampong Ampat, #06-02A KA PLACE. Singapore 368328.Phone(s): +65 6858 9081Fax: +65 6858 [email protected]/sg

SWEDENWEG SCANDINAVIA ABBox 10196Verkstadgatan 9434 22 KungsbackaPhone(s): (46) 300 73400Fax: (46) 300 [email protected]/se

UKWEG ELECTRIC MOTORS (U.K.) LTD.28/29 Walkers RoadManorside Industrial EstateNorth Moons Moat - RedditchWorcestershire B98 9HEPhone(s): 44 (0)1527 596-748Fax: 44 (0)1527 [email protected]/uk

UNITED ARAB EMIRATESWEG MIDDLE EAST FZEJAFZA – JEBEL ALI FREE ZONETower 18, 19th Floor, Office LB181905Dubai – United Arab [email protected]/ae

USAWEG ELECTRIC CORP1327 Northbrook Parkway, Suite 490Suwanee 30024Phone(s): 1-770-338-5656Fax: [email protected] www.weg.net/us

VENEZUELAWEG INDUSTRIAS VENEZUELA C.A.Parcela T-4-A Transversal 9 Urb. Industrial Carabobo Catastral 79-101 Edf. ELIMECA Loc. ELI-MECA, Zona Postal 2003, Va-lencia, Edo. CaraboboPhone(s): (58) 241 838 9239Fax: (58) 241 838 [email protected]/ve


Recommended