Date post: | 14-Apr-2018 |
Category: |
Documents |
Upload: | bilal-al-ali |
View: | 358 times |
Download: | 20 times |
of 18
7/27/2019 AC Air Cycles
1/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
Air Conditioning Systems
Summer airconditioningWinter air conditioning
.))Summer Air Conditioning Systems
225 = CT oR5%50 =R
Room heat load SQ LQ,Room sensible heat factor
RSHF.
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
2/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
(Summer air conditioning system without by pass)
)-(.)-(
Fig. 8-1 Summer air conditioning system
Fig. 8-2 Summer air conditioning processes
Return airFresh air Airhandling unit
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
3/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
S5 ~ 10 oC90 %.
Ro m
S %90=SmS%100=a
,Apparatus dew Point AdpS.
Room heat load SR,)( SRat hhmQ = & (8-1)
Cooling coil capacity and efficiency mSand a,
)( Smacoil hhmQ = & (8-2)
am
Smcoil
hh
hh
= (8-3)
Condensate water through dehumidification process mS,)(
Smawmm = && (8-4)
Example 8-1
An air conditioning room is maintained at 25oC db and RH 50 %. The ambient
conditions are 38oC db and 27
oC wb. The room has sensible heat gain of 40 kW
and latent heat gain of 10 kW. The re-circulated air contains 30 % by weight fresh
air. The re-circulated air is supplied to the room at 14oC. Calculate, the sensible
heat factor, the total amount of conditioned air, the cooling coil dew point, the
cooling coil capacity in TR, the cooling coil efficiency, and the rate of water
removed from the air.
Data: aoo
ooR
o
R mmCtCtRHCt && 3.0,wb27,db38,%50,25o
=====
CtkWQkWQ SLSo14,10,40 ===
Required: wcoila mRCAdpmRSHF && ,,,,,
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
4/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
Solution
As shown in Fig. 8-2 of Psychrometric chart and the air properties are,kgkJhkgkJh
oR/55.84,/34.50 ==
aRao mmmm &&&& 7.0,3.0 ==
kWQQQ LSt 501040 =+=+=
8.01040
40=
+=
+=
LS
S
QRSHF
Heat balance of mixing point m,
maRRoo hmhmhm &&& =+
maaa hmmm &&& 34.507.055.843.0 =+
damm kggkgkJh /5.12,/60.6 ==
Processes mSR, cooling and dehumidification from m to Sat 90 % RH, from
StoR, room total heat released parallel toRSHF.CAdptkgkJhkggkgkJh o
aadaSS9,/27,/7.8,/5.35 =====
Re-circulated air,
skgmmhhmQ aaSRat /369.3),5.3534.50(50),( === &&&
Cooling coil capacity,
TRhhm
RC Sma 162.245.3
)5.356.60(369.3
5.3
)(=
=
=&
Cooling coil efficiency,
%7.74747.0276.60
5.356.60==
=
=
am
Smcoil
hh
hh
Condensate water,
min/768.06010)7.85.12(369.3),( 3 kgmmmwSmaw
===
&&&
Example 8-2
In a summer air conditioning system shown the fresh air is mixed with return air
by equal mass before entering the cooling coil. After pre-cooled the air
adiabatically humidified in air washer to 90 % RH. The outside air conditions
are 35 C db and 17 C wb. The inside air conditions are 27 C db and 21 C wb.
Internal sensible heat gain is 35 kW and latent heat gain is 15 kW. Estimate; the
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
5/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
temperature to which the air is pre-cooled, the temperature to which the sprayed
water must be held, the amount of supplied air, the capacity of the pre-cooler, and
the make up water.
Data: wb17,db35,,wb21,db27 o CtCtCtCt oooo
Ro
R ====
%90,15,35 === SLS RHkWQkWQ
Required: waS mRCmtt && ,,,,1
Solution
From Psychrometric chart and the air properties are,kgkJhkgkJh oR /3.47,/68.60 ==
aRommm &&& 5.0==
kWQQQ LSt 501535 =+=+=
7.01535
35=
+=
+=
LS
S
QRSHF
Heat balance of mixing point m,
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
6/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
maRRoo hmhmhm &&& =+
maaa hmmm &&& 68.605.03.475.0 =+
damm kggkgkJh /9,/54 ==
Processes m1SR, sensible cooling from m to 1, but Sat cross ofRSHFwith
90 %RH, from Sto 1 adiabatic line at cross with sensible cooling m1.
m
oCt == 11 dbt,6.23
CAdptCtkggkgkJh oao
SdaSS 6.16db,9.17,/5.11,/47 =====
Re-circulated air,
skgmmhhmQ aaSRat /655.3),4768.60(50),( === &&&
Cooling capacity of pr-cooler,
TRhhm
RC ma 31.75.3
)4754(655.3
5.3
)( 1=
=
=&
Air washer efficiency,
%43.18143.06.166.23
9.176.23
1
1==
=
=
a
Swasher
tt
tt
Make up water in air washer,
min/5483.06010)95.11(655.3),( 31 kgmmm wSaw ===
&&&
(Summer air conditioning system with by pass)
Fig. 8-3 Summer air conditioning system with by pass
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
7/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
)-(
)-(S
.
Fig. 8-4 Summer air conditioning processes with by pass
Example 8-3
A summer air conditioning systems consists of water chiller and air re-heater as
shown below. The return air is mixed partially before the water chiller and by
passed after it with equal masses. The inside conditions are 25C db and 50 % RH
and outside conditions are 38 C db and 26C wb. Fresh air for ventilation is 0.5
m3/s. The internal sensible heat gain is 21 kW and internal latent heat gain is 7
kW. The air leaving water chiller saturated at 10oC and the temperature difference
between inside and supply air is 8 C db. Determine the refrigeration capacity of
the water chiller and the heating capacity of the air reheated.
Data: smmCtCtRHCt oo
ooR
o
R/5.0,wb26,db38,%50,25 3o ===== &
CtRHCtkWQkWQ oSLS 10%,100,17825,7,21 11o
======
Required: reha PowerRCmRSHF ,,, & Solution
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
8/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
As shown in Fig. 8-4 of Psychrometric chart and the air properties are,
kgkJhmkgkJhkgkJh ooR /5.29/kg,9047.0v,/05.80,/34.50 13
====
skgV
mmmo
ooRR /5527.0
9047.0
5.0
v,21 ====
&&&&
kWQQQ LSt 28721 =+=+=
75.028
21===
t
S
Q
QRSHF
State Sis at cross ofRSHFwith ts= 17oC
/5.37 kgkJhS =
skgmmhhmQaaSRat
/181.2),5.3734.50(28),( === &&&
skgmmmmmm
RR
oaRR
/8142.02/)5527.0181.2(21
21
===
=+
&&
&&&&
Heat balance of mixing point m,
mRoRRoohmmhmhm )(
11&&&& +=+
kgkJhh mm /35.62,)8142.0(0.552734.508142.005.805527.0 =+=+
Heat balance of mixing point 1 withR and 2Rm& ,
2211 )( hmhmhmm aRRRo &&&& =++
kgkJhh /28.37,2.18134.508142.05.29)8142.05527.0( 22 ==++
Cooling capacity water chiller,
TRhhm
RC ma 47.205.3
)5.2935.62(181.2
5.3
)( 1=
=
=&
Capacity of re-heater,
kWhhmPowerSa
479.0)28.375.37(181.2)(2 === &
.Example 8-4
In an air conditioning unit, air is supplied at a rate of 0.65 m3/s with 25C db and
60 % RH. The unit consists of a cooling coil where air is cooled and dehumidified
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
9/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
to 5C db and 4 C wb. Then, the air passes through an electric heater and leaves it
at 20C db. After that, air passes through an air washer, where it is humidified to
90 % RH. Part of the air is by passed across the air washer to have final air relative
humidity of 60 %. Calculate, the capacity of cooling coil, the heater power, the by
pass factor for air washer, and the bypassed low rate.
Data: smmCtCtRHCt oo
o
o
o /65.0,wb4,db5,%60,253
1
o
1 ===== &
%60%,90,25 3o
2 === SRHRHCt
Required: ,,, bwasher mBFPowerRC &
Solution
From Psychrometric chart and the air properties are,kgkJhhhkgkJhkgkJh So /33,/6.16,/55 321 =====
kgmkggkggodada
/8613.0v,/2.8,/8.4 332 ===
daadaS kggkgg /5.8,/8.6 ==
skgV
mo
oo /755.0
8613.0
65.0
v===
&&
TRkWRChhmRCoo
283.8992.28)6.1655(755.0),(1
==== &
kWPowerhhmPower o 61.16)3355(755.0),( 12 === &
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
10/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
Air washer efficiency and bypass factor,
%89.919189.08.45.8
8.42.8
2
23==
=
=
a
washer
%1.8081.09189.011 ==== washerwashweBF
Mass balance of air after bypassed and air washer,
Sobbommmm &&&& =+ 23)(
8.6755.08.42.8)755.0(,)( 23 =+=+ bbSobbo mmmmmm &&&&&&
skgmb /311.0=&
))Air Conditioning SystemsWinter
Pre-
heaterAir washer Re-heater)-(.
Fig. 8-5 Winter air conditioning system
)-(CTTS RS o10~5+=
RRSS
7/27/2019 AC Air Cycles
11/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
SRRRSHFRRS\S \>
S\RRRSHF .Humidification
Fig. 8-6 Winter air conditioning processes
Example 8-5
Air flow of 11 m3/min is supplied to air conditioning room at 24
oC db and 50 %
RH. The outside air conditions at 10oC db and 90 % RH. The return air is mixed
with the fresh air before entering the primary heater in ratio of 2 to 1 by weight.
The air is first preheated until its wet bulb temperature is equal to the room wet
bulb temperature. Then, the air is adiabatic saturated in air washer to 90 % RH.Finally the air is reheated to 35
oC before being supplied to the room. Determine
the heat added in both two heaters in kW, the mass of water evaporated in the air
washer, and the air washer efficiency.
Data: min/11,%90,db10,%50,db24 3o mmRHCtRHCt aooRo
R ===== &
%90,db35,2/ 2o
=== RHCtmm SoR &&
Required: washerPowerPower ,, 21
SolutionFrom Psychrometric chart as Fig. 8-6 and the air properties are,
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
12/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
kgmkgkJhkgmkgkJh ooRR /8111.0v,/35.27,/8546.0v,/83.4733
====
skgv
Vm
R
aa /215.0
8546.060
11=
==
&&
Heat balance of mixed point m,
ooRaoRmaRRoo mmmmmmhmhmhm &&&&&&&&& 3,2/, =+===+
moooo hmmmm )2(83.47235.27 &&&& +=+
skghhhskgh Rm /83.47,/41 21 ====
Process m12S, sensible heating from m to 1at h1 = hR , adiabatic air washer
from 1 to 2 at 90 %RH, sensible heating from 2 to Sat 35oC db.
daadadaS kggkggkggkgkJh /3.12,/8.11,/5.8,/3.65 21 ====
kWhhmPower ma 468.1)4183.47(215.0)( 11 === &
kWhhmPower Sa 756.3)83.473.65(215.0)( 22 === &
%84.8684.86.05.83.12
5.88.11
1
12==
=
=
a
washer
Example 8-6
A winter air conditioning unit, consists of preheating coil, adiabatic air washer and
reheating coil is used to maintain the condition inside a room at 25oC db and 50 %
RH. The re-circulated air is mixed with fresh air at equal parts by weight before
the preheating coil. An amount of 56.6 m3/min fresh air is supplied to the unit at 5
oC db and 90 % RH. The air leaves the humidifier at 85 % RH and leaves the
reheating coil at 33oC db and 35 % RH. Representation the processes on the
Psychrometeric chart and calculate the heating capacity of each heating coil, the
rate of water to be consumed in the humidifier, and the humidifying efficiency.
Data: oRooRoR mmRHCtRHCt && ===== ,%90,db5,%50,db25 o %35,db33%85/min,6.56 o2
3==== SSo RHCtRHmV
&
Required: washerwmPowerPower ,,, 21 &
Solution
From Psychrometric chart as Fig. 8-5 and the air properties are,
kgmkgkJhkgkJh ooR /7943.0v,/23.17,/34.503
===
skgv
Vm
o
oo /188.1
7943.060
6.56=
==
&&
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
13/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
Heat balance of mixing process stateR with state o by equal mass,
skgmmmmmmhmhmhm ooRaoRmaRRoo /376.2188.122,, ===+===+ &&&&&&&&&
skgmmmmmm ooRaoR /376.2188.122, ===+== &&&&&&
mooo hmmm &&& 223.1734.50 =+
skghm /79.33=
State Sat, %35,db33 o == SS RHCt , daSS kggkgkJh /01.11,/42.61 ==
Process S2, sensible heating from 2 to S, state 2 atRH = 85 %
daS kggkgkJh /01.11,/1.46 22 ===
Process 12, adiabatic air washer from 1 to 2 at 85 %RH,daadam kggkggkgkJh /5.11,/4.7,/1.46 11 ====
kWhhmPower ma 249.29)79.331.46(376.2)( 11 === &
kWhhmPower Sa 4.36)1.4642.61(376.2)( 22 === &
skgmm aw /515.06010)4.701.11(376.2)(3
12 ===&&
%05.888805.04.750.11
4.701.11
1
12==
=
=
a
washer
Example 8-7
A winter air conditioning unit consists of a preheating coil a spray system and a
reheating coil. The unit is designed to handle 3200 kg of air per hour and 100 % of
which is fresh air. The heat loss from the space is 9 kW. The outside air enters the
unit at 7 C db and 4 C wb. The air leaves the spray system at 90 % RH. The unit
delivers the air at 33C db and 30 % RH. Note that SHF=1, determine the
condition maintained inside the space, and the heating capacities of preheating and
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
14/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
reheating coil.
Data: skghrkgmRHCtCt aoo
o /889.0/3200,%90,wb4,db7 2o
===== &
%30,db33,1,9 o ==== SSt RHCtRSHFkWQ
Required: 21 ,,conditionsRoom PowerPower Solution
From Psychrometric chart, and the air properties are,kgkJhkgkJhkgkJh oS /6.16,/5.38,/5.57 2 ===
Process 2S, sensible heating and state Sat 33o
Cdb and 30 %RH. The state 2 isat the horizontal line atRH= 90 %.
dakggkgkJh /6.9,/5.38 22 ==
Process 12, adiabatic air washer and state 1 at cross with sensible heating line
from state o which at 7oCdb and 4
oCwb.
dakggkgkJh /8.3,/5.38 11 ==
Room heat load from state Sto stateR horizontal line, SHF = 1kgkJhhhhmQ RRRSat /4.47),5.57(889.09),( === &
%55db,231 == R
o RHCt
kWhhmPower oa 469.19)6.165.38(889.0)( 11 === &
kWhhmPower Sa 891.16)5.385.57(889.0)( 22 === &
Example 8-8
In air conditioning system shown below, all dehumidification occurs in the
adsorbent dehumidifier (Adiabatic dehumidification). Sketch the cycle on the
Psychrometric chart and find the condition of air leaving the adsorbent
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
15/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
dehumidifier, and the amount of water required for cooling the air in each cooler.
Data: CttmVCtCt oo 27min,/8.70,wb24,db35 523
1
o
11 =====&
min/127,wb5.17,db27 38
o
88mVCtCt o === &
min/42min,/85
33
mVmV ba== &&
%30,db33,1,9 o ==== SSt RHCtRSHFkWQ
Required: 21 ,4,stateofConditions ww mm &&
Solution
From Psychrometric chart, and the air properties are,dakggkgmkgkJh /24.14,/8931.0v,/75.71 1
3
11 ===
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
16/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
dakggkgmkgkJh /58.8,/8622.0v,/06.49 83
88 ===
skgv
Vm a /321.1
8931.060
8.70
1
11 =
==
&&
skgv
V
m
b
b /643.18622.060
85
8
1
1=
==
&&
skgv
Vm bb /812.0
8622.060
42
8
22 =
==
&&
Process 12, sensible cooling and state 2 at 27oCdb, kgkJh /49.632 =
Heat balance at mixing point b1, to locate state 3 at 27oC.
3118111)( hmmhmhm
bb&&&& +=+
3)643.1321.1(06.49643.175.71321.1 h+=+
dakggkgkJh /5.12,/17.59 33 ==
Supplied air and room total heat load,skgmmmm bba /776.3)812.0643.1321.1()( 211 =++=++= &&&&
kgkJhhhhmQ at /32.38),06.49(776.363),( 7778 === &
Room latent heat load, sensible heat, and room sensible heat factor,kgkJhmQ fgwL /62.278.2437)60/68.0( === &
kgkJQQQ LtS /37.3562.2763 ===
56.06337.35/ === tS QQRSHF
State 7 at cross ofRSHFwith h7,
Process 67 sensible cooling and state 6 at 27oCdb, kgkJh /5.41
6
=
Heat balance at mixing point b2, to locate state 5 at at 27oCdb.
6258255 )( hmmhmhm bb &&&& +=+
5.41)812.0643.1321.1(06.49812.0)643.1321.1( 5 ++=++ h
kgkJh /43.395 =
Process 45 sensible cooling and state 4 at the intersect of adiabatic line from
state 3 and horizontal line from state 5.
da
o kggCtkgkJh /8.4db,5.45,/17.59 444 ===
Heat balance of cooler 1,
)( 2111 hhmtCm wPw w = && kg/s5801.0),49.6375.71(321.1)135.17(18.4 11 == ww mm &&
Heat balance of cooler 2,)( 7662 hhmtCm wPw w = &&
kg/s8308.1),38.325.41(776.3)135.17(18.4 22 == ww mm &&
Problems
1.
A certain building is to be air conditioned in summer. The following data aregiven. The outside air is 38 C db, 25 C wb, and inside air 24 C db, 50 % RH.
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
17/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
Estimated heat from the building is 17.6 kW, electric lighting and machines are
40 kW. The total number of persons is 100, and sensible heat per person is 80
W and latent heat per person is 103 W. The ratio of return air and fresh air is
2:1 by mass. The air leaves the cooling coil at 90 % R.H. Determine the
sensible heat factor, the total amount of conditioned air, the cooling coil dew
point, the cooling coil capacity in TR, the cooling coil efficiency, and the rate
of water removed from the air.
2. In a summer air conditioning system, employing evaporative cooling equalmasses of fresh air and return air, after mixing air first pre-cooled then
adiabatically humidified to 100 % R.H by passing through a spray water
system. The outside air conditions are 35 C db and 17 C wb. The inside air
conditions are 27 C db, and 21 C wb. Internal sensible heat gain is 30 kW and
latent heat gain is 15 kW. Find the temperature to which the air is pre-cooled,
the temperature to which the sprayed water must be held, the amount of
supplied air, the capacity of the pre-cooler, and the make up water.
3. The following information was obtained in designing the summer airconditioning plant. The outside design conditions are 38 C db, 28 C wb and
the inside design conditions are 21 C db, 70 % RH. Internal sensible heat gain
is 175 kW and internal latent heat gain is 65 kW. Outside fresh air to total air is
50 % by mass. Temperature difference between supply air and return air is 8 C
db. Determine the conditions of the supply air, the quantity of supply air, the
cooling capacity of the plant, the cooling coil efficiency and by pass factor, and
the rate of water removed from the air.
4. A summer air conditioning systems consists of water chiller and by pass. Usesreturn air before the water chiller and by pass air after it. The given data are,
inside conditions 26C db & 50 % R.H and outside conditions 35C db & 26C
wb. Fresh air for ventilation is 2 m3/s. The internal sensible heat gain is 40 kW
and internal latent heat gain is 17.5 kW. The relative humidity of air leaving
water chiller is 90 % and the temperature difference between inside and supply
http://guider55.4t.com/http://guider55.4t.com/7/27/2019 AC Air Cycles
18/18
Website: http://guider55.4t.com Refrigeration and Air Conditioning
air is 9 C db. Equal masses for return and by pass air. Determine the
refrigerating capacity of the water chiller and the condensate water by lit/min.
5. A winter air conditioning unit, consists of preheating coil, adiabatic air washerand reheating coil is used to maintain the condition inside a room at 25 oC db
and 50 % RH. The re-circulated air is mixed with fresh air at equal parts by
weight before the preheating coil. An amount of 56.6 m3/min fresh air is
supplied to the unit at 5oC db and 90 % RH. The air leaves the humidifier at 85
% RH and leaves the reheating coil at 30oC db and 45 % RH. Draw a sketch
for this unit and its representation on the Psychrometeric chart. Then calculate
the heating capacity of each heating coil, the rate of water to be consumed in
the humidifier, and the humidifying efficiency.
6. A winter air conditioning unit consists of air pre-heater, air washer and airreheater. The re-circulated air is admitted partially as return air before the air
preheated and the rest is by passed after the air washer. Inside condition is 25
C db and 50 % RH. Outside condition is 5 C db and 70 % RH. Fresh air
enters the systems at the rate of 28 m3
/min. Temperature of air leaving pre-heater equal 21 C db and the relative humidity of air leaving air washer is 95
%. The temperature difference of supply air is high than room air by 7 C db.
Equal masses of fresh air, return air and by-pass air are used, draw the system
with its all details and represent it in the Psychrometric chart, then calculate the
capacity of both pre-heater and re-heater, internal heating load, and make up
water.
http://guider55.4t.com/http://guider55.4t.com/