+ All Categories
Home > Documents > Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE...

Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE...

Date post: 29-Mar-2015
Category:
Upload: maliyah-perrin
View: 222 times
Download: 6 times
Share this document with a friend
Popular Tags:
27
Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48, NO. 1, FEBRUARY 1999 周周周 MA12B201
Transcript
Page 1: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

Accurate Measurement of Power System Frequency

Using a Digital Signal Processing Technique

IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48, NO. 1, FEBRUARY 1999

周永強MA12B201

Page 2: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

OUTLINE

• I. ABSTRACT• II. INTRODUCTION• III. THE PROPOSED TECHNIQUE • IV. IMPLEMENTATION• V. PERFORMANCE EVALUATION• VI. CONCLUSIONS

Page 3: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

I. ABSTRACT• This paper describes the design, computational

aspects, and implementation of a digital signal processing technique for measuring the operating frequency of a power system.

• The technique provides correct and noise-free estimates for near nominal, nominal, and off-nominal frequencies in about 25 ms, and it requires modest computations.

• The proposed technique is implemented using a DSP-based board and has been extensively tested using voltage signals obtained from a dynamic frequency source and from a power system.

Page 4: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

II. INTRODUCTION

• FREQUENCY is an important operating parameter of a power system.

• A decrease in system frequency also reduces the reactive power balance and an increase in system frequency can damage the blade of generator.

• the system frequency should be maintained at its nominal frequency as quickly as possible.

• Frequency relays having a measurement range from 40 Hz to 70 Hz are adequate for over- and under-frequency relaying.

• Accuracy of electromagnetic relays range from 0.1 to 0.2 Hz of the set frequency.

Page 5: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Microprocessor relays use algorithms that process the sampled and digitized values of the system voltage to estimate the frequency

• These techniques are adversely affected by the presence of harmonics in the signals. Also, they may take from 50 ms to few seconds to provide accurate estimates of the frequency.

• It is necessary to detect underfrequency and overfrequency condition very quickly so that necessary corrective actions can be taken.

• the problem is that of fast and accurate determination of the frequency of the power system using voltage waveforms which may be corrupted by noise and harmonic components

• This paper presents a technique for frequency estimation that provides accurate estimates in about 25 ms and requires modest computations.

• The proposed technique was tested using voltage signals obtained from a dynamic frequency source and from the Power system

Page 6: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

III. THE PROPOSED TECHNIQUE

• The technique uses digitized values of samples of the voltage taken at a prespecified sampling rate.

• Consider a voltage signal having a fundamental frequency of f0.• The signal may also contain harmonics and noise. It is possible to

use orthogonal FIR digital filters to extract real and imaginary parts of the fundamental frequency component of the signal.

• These filters must be designed so that they minimize noise effect and are not affected by the presence of harmonics.

• This means that the frequency response of the filters must have nulls at the harmonic frequencies that are expected to be present in the signal.

Page 7: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Consider that the desired FIR filter is of length and has real values coefficients

• The frequency response of the filter can be expressed as (1)

• For a frequency response corresponding to a frequency of f, the following two equations can be written: (2)&(3)

Page 8: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• where Re and Im are the operators that provide real and imaginary parts, respectively, and Fs is the sampling frequency.

• This will provide equations 2m which can be expressed in matrix form as follows: (4)

Page 9: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• The design of filters requires the following parameters :

• 1) Sampling rate.• 2) The harmonic components that need to be

eliminated and hence the value of in (4).• 3) Filter length (n) which also equals the number of

consecutive samples of the voltage signal needed to compute real and imaginary parts. These consecutive samples are also termed as data window.

Page 10: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Sampling rate is fixed by the application. Generally, in power system measurement and control applications, a sampling rate in the range of 600 Hz to 1440 Hz is used.

• Composition of the signal is assumed based on the prior knowledge of the voltage waveforms and their harmonic content

• The data window size affects the noise suppression capabilities. It can be seen from (4) that the minimum data window size or filter length (n) must equal 2m .

• However, to achieve better noise suppression capabilities, the data window size should be larger than 2m . The larger the data window, the better is the noise suppression capability of the filters. On the other hand, a larger data window means more delay in the filter output.

Page 11: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• As the next sample arrives, the data window is shifted by one sample. The real and imaginary parts of the fundamental frequency phasor, Vr(n+1) and Vi(n+1) , corresponding to the (n+1) th data window can be computed using the data from the (n+1) th window and the filters’ coefficients as discussed earlier.

• Fig. 1 depicts the fundamental frequency phasors corresponding to n th and (n+1) th data windows.

Page 12: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• The filter coefficients are multiplied with the corresponding samples of the voltage signal within a data window and the results are accumulated.

• Multiplication and accumulation using the filters’ coefficients provide the real and imaginary parts of the fundamental frequency component of the signal.

• The real and imaginary parts computed using samples corresponding to the n th data window can be used to represent the signal in the phasor form as follows:(5)

• Where Vrn and Vin are the real and imaginary parts computed using samples from the n th data window

Page 13: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• The amount of this rotation can be estimated by using real and imaginary parts of the phasors corresponding to n th and (n+1) th data windows as follows: (6)

• This rotation for a phasor having fundamental frequency of f0 will equal to

• the basis for frequency estimation and• estimate of the frequency can be obtained as

follows: (7)

Page 14: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• One of the following two situations can exist.• 1) The estimated frequency is equal to the

fundamental frequency assumed for designing the filters that computed the phase angles difference . This means that the estimated frequency is also the fundamental frequency of the signal.

• 2) The estimated frequency is not equal to the fundamental frequency assumed for designing the filters. This means that the estimated frequency is not the fundamental frequency of the signal. This can be achieved by using an iterative procedure as follows:

Page 15: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• a) Design new filters by assuming the fundamental frequency of the signal being equal to the latest estimate of the frequency obtained from (7).

• b) Compute the phase angles rotation, Qn+1 - Qn, by using (6), the filters designed in step i), the samples corresponding to data windows n and n+1 .

• c) Estimate the frequency using (7) and the phase angles rotation computed in step b).

• d) Check if the estimated frequency from step c) is equal to the fundamental frequency assumed for designing the filters in step a). If it is, the estimated frequency in step c) is the fundamental frequency of the signal. Otherwise, the process reverts to step a).

Page 16: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

IV. IMPLEMENTATION• The proposed technique was implemented by using a DSP.

• Fig. 2. Frequency responses of typical FIR filters used for extracting (a) real part and (b) imaginary part of a signal.

Page 17: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Fig. 3. Block diagram of DSP-based hardware used for implementing the proposed technique.

Page 18: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

V. PERFORMANCE EVALUATION

A. Test Results Using Signals from a Dynamic Frequency Source and a Power System• The voltage was set at 110 V and frequency

was selected in the 40 Hz to 70 Hz range.• The voltage level was reduced by using a

voltage module of the isolation and analog scaling block of the general-purpose hardware.

• The reduced voltage signal was applied to a channel of the data acquisition card.

Page 19: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Fig. 4 shows the frequency estimates of a 59 Hz signal. The figure shows that the maximum estimation error is approximately 0.02 Hz.

Page 20: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Figs. 5–7 show the frequency estimates of 44 Hz, 60 Hz, and 65 Hz signals. It can be seen from the figures that the maximum estimation error for nominal, near-nominal and offnominal frequencies ranges from about 0.015 Hz to 0.02 Hz.

Page 21: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Fig. 8 shows the estimated frequency when data recorded from a power system was used. As the true frequency of the power system was not known, therefore, estimation errors can not be specified. However, the quality of estimates can be judged from the their consistency.

Page 22: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• The maximum variation in the estimates about the mean value is about 0.02 Hz. This demonstrates the effectiveness of the proposed technique for measuring power system frequency.

• It can be seen from Figs. 4–8 that the measurement time taken to provide the correct estimates is about 25 ms.

• Above results represent a significant improvement, in terms of accuracy and speed, in comparison to the results previously reported in the literature.

Page 23: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

B. Results Using Synthesized Signals

• To demonstrate the effectiveness of the proposed technique for estimating frequencies in presence of harmonics, an input signal having fundamental frequency of 59 Hz, a 20% third harmonic component (177 Hz), and 10% fifth harmonic component (295 Hz) was synthesized

• Frequency of the synthesized signal was estimated by using the proposed technique.

Page 24: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• Fig. 9. (a) A 59 Hz voltage signal containing third and fifth harmonic components and (b) its frequency estimates.

Page 25: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

• The estimated values are nearly equal to the true value despite the presence of harmonic components. The initial deviation from the true value is due to the fact that the initial estimate is taken to be 60 Hz and this transient usually lasts for about 3 ms to 5 ms.

Page 26: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

VI. CONCLUSIONS• Design and implementation of a new technique for

measuring the operating frequency of a power system have been described in the paper.

• The proposed technique is suitable for measuring near-nominal, nominal, and off-nominal frequencies.

• Maximum estimation errors observed during testing are of the order of 0.02 Hz for nominal, near-nominal, and off-nominal frequencies.

• Performance test results, using signals from a dynamic frequency source and from a power system, indicate that the proposed technique can provide accurate estimates within 25 ms.

• The proposed technique provides accurate estimates in presence of noise and harmonics.

Page 27: Accurate Measurement of Power System Frequency Using a Digital Signal Processing Technique IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 48,

REFERENCES• [1] Relay and Telecommunication Div., Westinghouse Electric Corp., “Applied protective relaying,” Carol Springs,

FL, 1982.• [2] A. G. Phadke, J. Thorp, and M. Adamiak, “A new measurement technique for tracking voltage phasors, local

system frequency and rate of change of frequency,” IEEE Trans. Power Apparat. Syst., vol. 102, no. 5, pp. 1025–1038, 1983.

• [3] M. S. Sachdev and M. M. Giray, “A least square technique for determining power system frequency,” IEEE Trans. Power Apparat. Syst., vol. PAS-104, no. 2, pp. 437–443, 1985.

• [4] A. A. Girgis and T. L. D. Hwang, “Optimal estimation of voltage phasors and frequency deviation using linear and nonlinear Kalman filtering,” IEEE Trans. Power Apparat. Syst., vol. PAS-103, no. 10, pp. 2943–2949, 1984.

• [5] H. Tao and I. F. Morrison, “The measurement of power system frequency using a microprocessor,” Elect. Power Syst. Res., vol. 11, pp. 103–108, 1986.

• [6] S. A. Soliman, “An algorithm for frequency relaying based on least absolute value approximations,” Elect. Power Syst. Res., vol. 19, pp. 73–84, 1990.

• [7] V. V. Terzija, M. B. Djuric, and B. D. Kovacevic, “Voltage phasor and local system frequency estimation using Newton-type algorithms,” IEEE Trans. Power Delivery, vol. 9, no. 3, pp. 1368–1374, 1994.

• [8] T. S. Sidhu, M. S. Sachdev, and R. Das, “Modern relays: Research and teaching using PC’s,” IEEE Comput. Applicat. Power, vol. 10, pp. 50–55, Apr. 1997.

• [9] A. Y. Zayezdny and I. Druckman, “Short time measurement of frequency and amplitude in the presence of noise,” IEEE Trans. Instrum. Meas., vol. 41, pp. 397–402, June 1992.

• [10] M. K. Mahmood, J. E. Allos, and M. A. Abdul-Karim, “Microprocessor implementation of a fast and simultaneous amplitude and frequency detector for sinusoidal signals,” IEEE Trans. Instrum. Meas., vol. IM-34, pp. 413–417, 1985.


Recommended