ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT PLANT OPERATIONS & MAINTENANCE BUILDING RENOVATIONS 32 PENCE LANE ROAD MIDDLETOWN, VIRGINIA 22645 TRIAD PROJECT NO. 07-19-0037 Submitted to: PAINTER-LEWIS, P.L.C. Attn: Mr. Timothy G. Painter, PE 817 Cedar Creek Grade, Suite 120 Winchester, Virginia 22601 Submitted by: TRIAD ENGINEERING, INC. 200 Aviation Drive Winchester, Virginia 22602 ____________________________________________ Jeffrey H. Mitchell, CPG Senior Environmental Geologist February 26, 2019
Transcript
Page 1: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT PLANT

OPERATIONS & MAINTENANCE BUILDING RENOVATIONS 32 PENCE LANE ROAD

MIDDLETOWN, VIRGINIA 22645

TRIAD PROJECT NO. 07-19-0037

Submitted to:

PAINTER-LEWIS, P.L.C. Attn: Mr. Timothy G. Painter, PE 817 Cedar Creek Grade, Suite 120

Winchester, Virginia 22601

Submitted by:

TRIAD ENGINEERING, INC. 200 Aviation Drive

Winchester, Virginia 22602

____________________________________________

Jeffrey H. Mitchell, CPG Senior Environmental Geologist

February 26, 2019

Page 2: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ACM & LBP Survey Percy D. Miller WTP – Operations & Maintenance Building Renovations

February 26, 2019 Page i

TABLE OF CONTENTS

Page

AREA EVALUATION ................................................................................................................1 

ACM SURVEY ...........................................................................................................................1 

LBP SURVEY .............................................................................................................................3 

USE OF REPORT ........................................................................................................................3 

ATTACHMENTS 1. Asbestos Inspector and Laboratory Licenses 2. SACM Chain of Custody & Asbestos PLM Analytical Result Documentation 3. DMY LBP Survey Report 4. Photographs

LIST OF ACRONYMS

ACM Asbestos-Containing Material

COC Chain of Custody

LBP Lead-Based Paint

NESHAP National Emission Standard for Hazardous Air Pollutants

NVLAP National Voluntary Laboratory Accreditation Program

PLM Polarized Light Microscopy

SACM Suspect ACM

TCLP Toxic Characteristic Leaching Procedure

USEPA United States Environmental Protection Agency

Page 3: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 1

ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT PLANT

OPERATIONS & MAINTENANCE BUILDING RENOVATIONS 32 PENCE LANE ROAD

MIDDLETOWN, VIRGINIA 22645

AREA EVALUATION

On February 12, 2019, Jeffrey H. Mitchell of Triad Engineering, Inc. (Triad) and Brandon J.

Colunga of DMY Capital LLC (DMY) conducted an asbestos-containing material (ACM) and

lead-based paint (LBP) survey of the interior portions of the Operations Building proposed for

renovation, which were identified by Mr. Farrell Owens, the Facility Manager, and the roofs of

the Operations and Maintence Buildings located at the Percy D. Miller Water Treatment Plant

addressed as 32 Pence Lane Road, Middletown, Virginia 22645.

ACM SURVEY

The ACM survey was performed by Jeffrey H. Mitchell; Asbestos Inspector Licensed by the

Virginia Department of Professional and Occupational Regulation (Attachment 1).

Following standard inspection practices, suspect ACM (SACM) samples were collected to

confirm the presence or absence of asbestos. Samples were collected from locations of SACM

using the following procedures: utilizing appropriate tools, a sufficient amount was obtained for

PLM analysis; each SACM sample was placed individually in a sealed bag; and a unique sample

identification number was assigned to each sample material and location.

As follows are the specific SACMs identified and sampled:

Roofing: roofing system layers, sealant, and caulk;

Interior Wall: ceramic tile and grout;

Windows: interior & exterior caulk;

HVAC Systems: caulk; and

Miscellaneous: fiberglass pipe insulation mastic.

SACM descriptions and locations are listed on the chain of custody (COC) documentation

included in Attachment 2. Photographs are included as Attachment 5.

Page 4: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 2

Following standard inspection practices, Triad obtained a sufficient number of samples of the

suspect materials per the federal and state regulations to confirm the presence or absence of

asbestos fibers in the SACMs. Samples of the SACMs were collected using the following

procedures: utilizing appropriate tools, a sufficient amount of a suspect material was obtained for

PLM analysis; each suspect sample was placed individually in a sealed bag; and a unique sample

identification number was assigned to each sample material and location.

The friability characteristics of the material were also evaluated by the inspector during the

sampling and procuring process. The friability of the material is described in two ways. A

designation of “friable” describes material meeting the following characteristics as described in

the U.S. Environmental Protection Agency (USEPA) National Emission Standard for Hazardous

Air Pollutant (NESHAP) for Asbestos 40 Code of Federal Regulation Section 61 Subpart M,

61.141: “that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure”.

A designation of “non-friable” describes a material meeting the following characteristics as

described in the USEPA NESHAP: “that, when dry, cannot be crumbled, pulverized, or reduced

to powder by hand pressure.” Please note however that material currently in a non-friable state

could become friable during demolition activities.

During the ACM Survey, a total of 15 sample sets totaling 45 SACM samples were collected and

submitted for asbestos analysis to SanAir Technologies Laboratory, an independent NVLAP

accredited and Virginia-licensed laboratory. Samples were analyzed using polarized light

microscopy (PLM) and dispersion staining analysis methods USEPA 600/R-93/116 and a total of

64 tests were performed due to multiple layers in some samples.

The following material contained asbestos at a level greater than one percent, which by

regulatory definition is an ACM.

Material Sample ID Location & Estimated Quantity Result

Black Caulk 10-A Upper Roof of the Operations Building (Unknown Quantity)

3% Chrysotile

The black caulk on the upper roof of the Operations Building is considered Category I non-

friable ACM.

Page 5: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3

LBP SURVEY

A copy of the LBP survey report prepared by DMY is included as Attachment 4. In summary,

the following items were identified or should be assumed to have a LBP coated surface:

All cream porcelain tiles within the Filter Operating Floor and Rear Entrance Lobby,

All blue paint located on the stair systems and guard rails,

The orange paint located on the I-beams within the columns of the Filter Operating Floor,

and

The red access doors located on the exterior of the Operations Building.

LIMITATIONS

It was attempted to perform an ACM and LBP survey of the interior portions of the Operations

Building proposed for renovation, which were identified by Mr. Farrell Owens, the Facility

Manager, and the roofs of the Operations and Maintence Buildings located at the Percy D. Miller

Water Treatment Plant located at 32 Pence Lane Road, Middletown, Virginia 22645; however,

some areas may have been hidden or impracticable to access. These areas may include, but are

not necessarily limited to, the sub-grade; flooring located below underlayments; above or behind

ceilings, walls, and roofing; and pipe and utility chases.

Any SACMs or suspect LBP coatings encountered during the renovation that were not tested

should be assumed to be ACM or LBP unless tested to determine asbestos or lead content.

USE OF REPORT

This report has been prepared for the exclusive use of the Client and persons or organizations to

which the Client wishes to make this report available. This report and the findings contained

herein shall not, in whole or in part, be used by or relied upon by any other party, without the

prior written consent of Triad.

Page 6: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

ASBESTOS INSPECTOR AND LABORATORY LICENSES

Page 7: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY
Page 8: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY
Page 9: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

SACM CHAIN OF CUSTODY & ASBESTOS PLM ANALYTICAL RESULT

DOCUMENTATION

Page 10: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Page 11 of 12

Page 11: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Page 12 of 12

Page 12: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

SanAir ID#: 19006538

Project #: 07-19-0037

Project Name: Winchester WTP

Report Date: 2/20/2019

Analysis Report prepared forTriad Engineering, Inc.

Page 1 of 12

Page 13: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Dear Jeffrey H. Mitchell,

We at SanAir would like to thank you for the work you recently submitted. The 45 sample(s) were received on Wednesday, February 13, 2019 via FedEx. The final report(s) is enclosed for the following sample(s): 1-A, 1-B, 1-C, 2-A, 2-B, 2-C, 3-A, 3-B, 3-C, 4-A, 4-B, 4-C, 5-A, 5-B, 5-C, 6-A, 6-B, 6-C, 7-A, 7-B, 7-C, 8-A, 8-B, 8-C, 9-A, 9-B, 9-C, 10-A, 10-B, 10-C, 11-A, 11-B, 11-C, 12-A, 12-B, 12-C, 13-A, 13-B, 13-C, 14-A, 14-B, 14-C, 15-A, 15-B, 15-C.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely,

Sandra SobrinoAsbestos & Materials Laboratory ManagerSanAir Technologies Laboratory

Final Report Includes:- Cover Letter- Analysis Pages- Disclaimers and Additional Information

Sample conditions:- 45 samples in Good condition.

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 2 of 12

Page 14: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

1-A / 19006538-001Operations Interior-Ceramic Wall Tile

TanNon-Fibrous

Heterogeneous

100% Other None Detected

1-B / 19006538-002Operations Interior-Ceramic Wall Tile

TanNon-Fibrous

Heterogeneous

100% Other None Detected

1-C / 19006538-003Operations Interior-Ceramic Wall Tile

TanNon-Fibrous

Heterogeneous

100% Other None Detected

2-A / 19006538-004Operations Interior-Ceramic Wall Grout

TanNon-Fibrous

Heterogeneous

100% Other None Detected

2-B / 19006538-005Operations Interior-Ceramic Wall Grout

TanNon-Fibrous

Heterogeneous

100% Other None Detected

2-C / 19006538-006Operations Interior-Ceramic Wall Grout

TanNon-Fibrous

Heterogeneous

100% Other None Detected

3-A / 19006538-007Operations Interior-Upper Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

3-B / 19006538-008Operations Interior-Upper Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

3-C / 19006538-009Operations Interior-Upper Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

4-A / 19006538-010Operations Interior-HVAC Ductwork Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 3 of 12

Page 15: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

4-B / 19006538-011Operations Interior-HVAC Ductwork Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

4-C / 19006538-012Operations Interior-HVAC Ductwork Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

5-A / 19006538-013Operations Exterior-Lower Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

5-B / 19006538-014Operations Exterior-Lower Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

5-C / 19006538-015Operations Exterior-Lower Windows-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

6-A / 19006538-016Operations Lower Roof-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

6-B / 19006538-017Operations Lower Roof-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

6-C / 19006538-018Operations Lower Roof-Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

7-A / 19006538-019Operations Lower Roof-Upper Windows-L. Graye

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

7-B / 19006538-020Operations Lower Roof-Upper Windows-L. Graye

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 4 of 12

Page 16: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

7-C / 19006538-021Operations Lower Roof-Upper Windows-L. Graye

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

8-A / 19006538-022Operations Lower Roof-Sealant

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

8-B / 19006538-023Operations Lower Roof-Sealant

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

8-C / 19006538-024Operations Lower Roof-Sealant

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

9-A / 19006538-025Operations Lower Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

9-A / 19006538-025Operations Lower Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

9-A / 19006538-025Operations Lower Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

9-B / 19006538-026Operations Lower Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

9-B / 19006538-026Operations Lower Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

9-B / 19006538-026Operations Lower Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 5 of 12

Page 17: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

9-C / 19006538-027Operations Lower Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

9-C / 19006538-027Operations Lower Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

9-C / 19006538-027Operations Lower Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

10-A / 19006538-028Operations Upper Roof-Caulk, Roof Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

10-A / 19006538-028Operations Upper Roof-Caulk, Roof Caulk

BlackNon-Fibrous

Heterogeneous

97% Other 3% Chrysotile

10-B / 19006538-029Operations Upper Roof-Caulk, Roof Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

10-B / 19006538-029Operations Upper Roof-Caulk, Roof Caulk

Not Analyzed

10-C / 19006538-030Operations Upper Roof-Caulk, Roof Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

10-C / 19006538-030Operations Upper Roof-Caulk, Roof Caulk

Not Analyzed

11-A / 19006538-031Operations Upper Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 6 of 12

Page 18: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

11-B / 19006538-032Operations Upper Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

11-C / 19006538-033Operations Upper Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

12-A / 19006538-034Operations Interior-Fiberglass Pipe Insulation Mastic, Insulation

YellowFibrous

Heterogeneous

95% Glass 5% Other None Detected

12-A / 19006538-034Operations Interior-Fiberglass Pipe Insulation Mastic, Mastic

WhiteNon-Fibrous

Heterogeneous

100% Other None Detected

12-B / 19006538-035Operations Interior-Fiberglass Pipe Insulation Mastic, Insulation

YellowFibrous

Heterogeneous

95% Glass 5% Other None Detected

12-B / 19006538-035Operations Interior-Fiberglass Pipe Insulation Mastic, Mastic

WhiteNon-Fibrous

Heterogeneous

100% Other None Detected

12-C / 19006538-036Operations Interior-Fiberglass Pipe Insulation Mastic, Insulation

YellowFibrous

Heterogeneous

95% Glass 5% Other None Detected

12-C / 19006538-036Operations Interior-Fiberglass Pipe Insulation Mastic, Mastic

WhiteNon-Fibrous

Heterogeneous

100% Other None Detected

13-A / 19006538-037Maintenance Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

13-B / 19006538-038Maintenance Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 7 of 12

Page 19: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

13-C / 19006538-039Maintenance Roof Capstones-L. Caulk

GrayNon-Fibrous

Heterogeneous

100% Other None Detected

14-A / 19006538-040Maintenance Roof-Caulk

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

14-B / 19006538-041Maintenance Roof-Caulk

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

14-C / 19006538-042Maintenance Roof-Caulk

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

15-A / 19006538-043Maintenance Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

15-A / 19006538-043Maintenance Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

15-A / 19006538-043Maintenance Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

15-A / 19006538-043Maintenance Roof-Roofing System, Foam

YellowNon-Fibrous

Heterogeneous

100% Other None Detected

15-B / 19006538-044Maintenance Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

15-B / 19006538-044Maintenance Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 8 of 12

Page 20: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Analyst: Vaughan, Nathaniel

Asbestos Bulk PLM EPA 600/R-93/116Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

15-B / 19006538-044Maintenance Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

15-B / 19006538-044Maintenance Roof-Roofing System, Foam

YellowNon-Fibrous

Heterogeneous

100% Other None Detected

15-C / 19006538-045Maintenance Roof-Roofing System, Roofing

BlackNon-Fibrous

Heterogeneous

40% Cellulose 60% Other None Detected

15-C / 19006538-045Maintenance Roof-Roofing System, Felt Paper

BlackFibrous

Heterogeneous

75% Cellulose 25% Other None Detected

15-C / 19006538-045Maintenance Roof-Roofing System, Membrane

BlackNon-Fibrous

Heterogeneous

100% Other None Detected

15-C / 19006538-045Maintenance Roof-Roofing System, Foam

YellowNon-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 2/20/2019 Date: 2/20/2019

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | [email protected]

07-19-0037Project Number:P.O. Number:

Project Name: Winchester WTP

2/12/2019Collected Date:

2/13/2019 10:15:00 AMReceived Date:

2/20/2019 6:28:52 PM

19006538SanAir ID Number

FINAL REPORT

Triad Engineering, Inc.Name:Address: 1097 Chaplin Road

Morgantown, WV 26501

3017976400Phone:

Page 9 of 12

Page 21: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

Disclaimer

The final report cannot be reproduced, except in full, without written authorization from SanAir. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample and information provided by the client. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Samples are held for a period of 60 days. For NY state samples, method EPA 600/M4-82-020 is performed. Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. Asbestos Certifications NVLAP lab code 200870 City of Philadelphia: ALL-460 PA Department of Environmental Protection Number: 68-05397 California License Number: 2915 Colorado License Number: AL-23143 Connecticut License Number: PH-0105 Massachusetts License Number: AA000222 Maine License Number: LB-0075 New York ELAP lab ID: 11983 Rhode Island License Number: AAL-126 Texas Department of State Health Services License Number: 300440 Commonwealth of Virginia 3333000323 Washington State License Number: C989 West Virginia License Number: LT000566 Vermont License: AL166318

Revision Date: 11/30/2017

Page 10 of 12

Page 22: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

DMY LBP SURVEY REPORT

Page 23: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

4400acArthur Boulevard, Suite 304, Washington, DC 20007 • www.dmycapitol.com • Phone: (202) 741-9159 GEOTECHNICAL ● ENVIRONMENTAL ● DRILLING ● INSTRUMENTATION ● MATERIALS TESTING

SPECIAL INSPECTIONS ● THIRD PARTY INSPECTIONS ● FACILITIES

PERCY D. MILLER WATER TREATMENT PLANT

32 PENCE LANE ROAD

MIDDLETOWN, VIRGINIA 22645

DMY PROJECT NO. 02.03044.01

Submitted to:

TRIAD ENGINEERING, INC. Attn: Mr. Jeffrey H. Mitchell, CPG

200 Aviation DriveWinchester, Virginia 22602

Submitted by:

DMY CAPITOL LLC 4400 MacArthur Boulevard, Suite 304

Washington, District of Columbia 20007

Inspector ____________________________________________ Brandon J. Colunga

Senior Environmental Project Manager

February 24, 2019

Page 24: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

4400acArthur Boulevard, Suite 304, Washington, DC 20007 • www.dmycapitol.com • Phone: (202) 741-9159 GEOTECHNICAL ● ENVIRONMENTAL ● DRILLING ● INSTRUMENTATION ● MATERIALS TESTING

SPECIAL INSPECTIONS ● THIRD PARTY INSPECTIONS ● FACILITIES

LEAD-BASED PAINT SURVEY REPORT

On February 12, 2019, DMY Capitol LLC (DMY) conducted a Limited-Scope Lead-Based Paint Survey in the filter basin area in the interior of the operations structure and the roofs of the operations and maintenance structures located at 32 Pence Lane Road in Middletown,Virginia at the request of Mr. Jeffrey H. Mitchell, representing Triad Engineering, Inc. The scope of work for the Survey included an lead-based paint (LBP) analysis of only the areas identified for a pending renovation.

DMY conducted the LBP survey in the structure utilizing an X-ray fluorescence (XRF) unit in general accordance with the procedures and directives described in the U.S. Department of Housing and Urban Development (HUD) guidance document Guidelines for the Evaluation and

Control of Lead-Based Paint Hazards, June 1997. Because removal or management of any identified LBP or surface coatings is considered to be incidental to the renovation project and not intended as a lead abatement activity or to reduce or eliminate a lead-based paint hazard, testing for LBPs was conducted in a survey fashion and representative testing combinations were selected accordingly throughout the structure.

The survey consisted of testing the lead concentrations of painted surfaces using a Innov-X 6000 Alpha Series XRF analyzer. Typical tested surfaces included, but were not necessarily limited to, walls, interior and exterior door components, interior and exterior window components, and casework. Several building components were greater than 1.0 milligrams of lead per square centimeter (mg/cm2) and other building components exhibited detectable concentrations of lead that were below the 1.0 mg/cm2 threshold. With respect to the naming convention of walls within the structure, the “A” Wall refers to the side of the structure facing the addressed street, which in this case is the northwestern face of the site structure. The “B”, “C”,

and “D” Walls are subsequently named in a clockwise fashion. Additionally, in the case of structures such as doors or windows, the individual structures are denoted with sequential numerical subscripts in a clockwise fashion along a given wall. The following table includes all of the analyzed surfaces and those surfaces identified as containing greater than 1.0 mg/cm2 are denoted with bold text.

Room Name Side Structure Component Condition Substrate Color Lead

(mg/cm3)

Filter Operating

Floor A Wall - Intact Porcelain Cream 2.87

Filter Operating

Floor A Stairs Newel Post Intact Metal Blue >5.00

Filter Operating Floor A Stairs Handrail Intact Metal Yellow 0.02 Filter Operating

Floor B Wall - Intact Porcelain Cream 1.86

Filter Operating Floor B Ceiling Beam Intact Concrete Cream 0 Filter Operating Floor B Ceiling - Intact Concrete Cream 0

Filter Operating Floor B Floor Pedastal Intact Concrete Light Blue 0

Filter Operating

Floor B Wall Guard Rail Intact Metal Blue 5

Filter Operating D Wall I-Beam Column Intact Metal Orange 5

Page 25: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

February 24, 2019 DMY Project No. 02.03044.01

Limited-Scope LBP Survey Report Percy D. Miller Water Treatment PlantMiddletown, Virginia Page 2

Room Name Side Structure Component Condition Substrate Color Lead

(mg/cm3)

Floor

Filter Operating Floor D Ceiling Beam Intact Concrete Cream 0 Filter Operating Floor D Ceiling Conduit Intact Metal Cream 0

Filter Operating Floor D Wall Controls - Filter #4 Intact Metal Gray-

Green 0

Filter Operating Floor D Wall Fan Bracket Intact Metal Brown 0.01 Filter Operating Floor D Wall Fan Intact Metal Tan 0 Filter Operating Floor D Wall Fan Intact Metal Brown 0

Rear Entrance Lobby A Wall - Intact Porcelain Cream 3.23

Rear Entrance Lobby A Wall Pipe Intact Cast Iron Black 0.4 Rear Entrance Lobby A Ceiling Beam Intact Concrete Cream 0 Rear Entrance Lobby A Ceiling - Intact Concrete Cream 0

Rear Entrance Lobby B Wall Master Filter Alarm Panel #3 Intact Metal Gray-

Green 0

Rear Entrance Lobby D Stairs Newel Post Intact Metal Blue 5 Rear Entrance Lobby D Stairs Handrail Intact Metal Yellow 0.17

Exterior B Wall Access Door Intact Metal Red 1.44

RECOMMENDATIONS

Based on the results of Limited-Scope LBP Survey at the site, DMY recommends the following:

LBP Survey – The planned renovations will not be designed as or intended to constitutea lead abatement activity or to reduce or eliminate a lead-based paint hazard. However,care should be taken during any renovation activity that will involve removal ordisturbance of LBP or lead-containing surface coatings to prevent contamination of thework area or adjacent spaces by lead dust or debris. Furthermore, any renovation workduring which employees may be occupationally exposed to lead must be conducted inaccordance with OSHA lead-safe work practices as set forth in 40 CFR 1926.62. Thisincludes any disturbance of LBP or any lead-containing surface coating.

The following items were identified or should be assumed to have a LBP coated surface: o All cream porcelain tiles within the Filter Operating Floor and Rear Entrance Lobby,o All blue paint located on the stair systems and guard rails,o The orange paint located on the I-beams within the columns of the Filter Operating

Floor, ando The red access doors located on the exterior of the Operations Building.

DMY made a reasonable effort to locate and sample all potential LBP associated with the pending renovation during the field survey as indicated by the field contact, Mr. Farrell Owens, the Facility Manager. However, DMY stresses that the LBP Survey was inherently limited to those conditions readily accessible to the DMY team during the field surveys. Conditions inside enclosed walls, pipe chases, or other inaccessible areas inside the site structure or historical conditions not previously divulged to DMY may not have been identified or otherwise assessed during this survey. DMY makes no other warranty, either expressed or implied, as to the

Page 26: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

February 24, 2019 DMY Project No. 02.03044.01

Limited-Scope LBP Survey Report Percy D. Miller Water Treatment Plant Middletown, Virginia Page 3

professional services described herein. This report has been prepared by DMY for the use of the Triad Engineering, Inc. If you should have any questions or require further assistance, please contact the undersigned.

LIMITATIONS

It was attempted to perform a Limited-Scope LBP Survey of the structure located at 32 Pence Lane Road; however, some areas may have been hidden or impracticable to access. These areas may include, but are not necessarily limited to, the sub-grade; above or behind ceilings and walls; and pipe and utility chases.

The demolition and/or abatement contractor has the responsibility for determining actual quantities of all materials.

USE OF REPORT

This report has been prepared for the exclusive use of the Client and persons or organizations to which the Client wishes to make this report available. This report and the findings and recommendations contained herein shall not, in whole or in part, be used by or relied upon by any other party, without the prior written consent of DMY.

We appreciate the opportunity to assist you with this project. If you have any questions or require further assistance, please do not hesitate to contact the undersigned.

Sincerely, DMY Capitol, LLC

Brandon J. Colunga Senior Project Environmental Scientist

Page 27: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

PHOTOGRAPHS

Page 28: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

PROJECT NO. 07-19-0037 Page 1 of 4

DATE: February 12, 2019

CLIENT: Painter-Lewis, P.L.C. PROJECT NAME: Percy D. Miller Water Treatment Plant – Operations & Maintenance Building Renovations - ACM & LBP Survey 32 Pence Lane Road Middletown, Virginia 22645

Photograph # 1

View of a Sample 10-A Operations Upper Roof – Gray Caulk sampling location, which according to the asbestos laboratory, is underlain by black caulk that contains 3% Chrysotile Asbestos and is therefore

asbestos-containing material (ACM).

Photograph # 2

View of the porcelain tile that contain a lead-based coated surface.

Page 29: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

PROJECT NO. 07-19-0037 Page 2 of 4

DATE: February 12, 2019

CLIENT: Painter-Lewis, P.L.C. PROJECT NAME: Percy D. Miller Water Treatment Plant – Operations & Maintenance Building Renovations - ACM & LBP Survey 32 Pence Lane Road Middletown, Virginia 22645

Photograph # 3

View of the porcelain tile that contain a lead-based coated surface.

Photograph # 4

View of the blue guard rails that contain a lead-based paint (LBP) surface.

Page 30: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

PROJECT NO. 07-19-0037 Page 3 of 4

DATE: February 12, 2019

CLIENT: Painter-Lewis, P.L.C. PROJECT NAME: Percy D. Miller Water Treatment Plant – Operations & Maintenance Building Renovations - ACM & LBP Survey 32 Pence Lane Road Middletown, Virginia 22645

Photograph # 5

View of the blue guard rails that contain a LBP surface.

Photograph # 6

View of the orange steel I-beam column that contains a LBP surface.

Page 31: ACM & LBP SURVEY PERCY D. MILLER WATER TREATMENT … · ACM & LBP Survey February 26, 2019 Percy D. Miller WTP – Operations & Maintenance Building Renovations Page 3 LBP SURVEY

PROJECT NO. 07-19-0037 Page 4 of 4

DATE: February 12, 2019

CLIENT: Painter-Lewis, P.L.C. PROJECT NAME: Percy D. Miller Water Treatment Plant – Operations & Maintenance Building Renovations - ACM & LBP Survey 32 Pence Lane Road Middletown, Virginia 22645

Photograph # 7

View of the red access door that contains a LBP surface.


Recommended