  • Auma India multi-turn electric actuators

    SA 3 - SA 100SAR 3 - SAR 100SA 25.1 - SA 40.1SAR 25.1 - SAR 30.1

  • | 49 Auma Worldwide

    2

    AUM

    A w

    orld

    wid

    e

    48 |AU

    MA

    wor

    ldw

    ide

    Alw

    ays

    refe

    r to:

    for d

    etai

    led

    cont

    act i

    nfor

    mat

    ion.

    Eur

    ope

    AU

    MA

    Rie

    ster

    Gm

    bH &

    Co.

    KG

    Pla

    nt M

    llh

    eim

    DE

    -793

    73 M

    llh

    eim

    Pla

    nt O

    st l

    dern

    -Nel

    linge

    n

    DE

    -737

    47 O

    stfi

    lder

    n

    Ser

    vice

    Cen

    ter C

    olog

    ne

    DE

    -508

    58 K

    ln

    Ser

    vice

    Cen

    ter M

    agde

    burg

    DE

    -391

    67 N

    iede

    rndo

    dele

    ben

    Ser

    vice

    Cen

    ter B

    avar

    ia

    DE

    -853

    86 E

    chin

    g

    AU

    MA

    Arm

    atur

    enan

    trieb

    e G

    mbH

    AT-

    2512

    Tri

    busw

    inke

    l

    AU

    MA

    (Sch

    wei

    z) A

    G

    CH

    -896

    5 B

    erik

    on

    AU

    MA

    Ser

    vopo

    hony

    spo

    l. s.

    r.o.

    CZ-

    250

    01 B

    rand

    s n

    .L.-S

    t.B

    oles

    lav

    OY

    AU

    MAT

    OR

    AB

    FI-0

    2230

    Esp

    oo

    AU

    MA

    Fran

    ce S

    .A.R

    .L.

    FR-9

    5157

    Tav

    erny

    Ced

    ex

    AU

    MA

    ACTU

    ATO

    RS

    Ltd

    .

    GB

    - Cle

    vedo

    n N

    orth

    Som

    erse

    t BS

    21 6

    TH

    AU

    MA

    ITA

    LIA

    NA

    S.r.

    l. a

    soci

    o un

    ico

    IT-2

    0023

    Cer

    ro M

    aggi

    ore

    (MI)

    AU

    MA

    BE

    NE

    LUX

    B.V

    .

    NL-

    2314

    XT

    Leid

    en

    AU

    MA

    Pols

    ka S

    p. z

    o.o

    .

    PL-

    41-2

    19 S

    osno

    wie

    c

    OO

    O P

    RIW

    OD

    Y A

    UM

    A

    RU

    -141

    400

    Khi

    mki

    , Mos

    cow

    reg

    ion

    ER

    ICH

    S A

    RM

    ATU

    R A

    B

    SE

    -200

    39 M

    alm

    GR

    N

    BE

    CH

    & S

    N

    NE

    R A

    /S

    DK

    -245

    0 K

    ben

    havn

    SV

    IBE

    RO

    PLA

    N S

    .A.

    ES

    -280

    27 M

    adri

    d

    D. G

    . Bel

    los

    & C

    o. O

    .E.

    GR

    -136

    73 A

    char

    nai A

    then

    s

    SIG

    UR

    D S

    R

    UM

    A. S

    .

    NO

    -130

    0 S

    andv

    ika

    IND

    US

    TRA

    PT-

    2710

    -297

    Sin

    tra

    ME

    GA

    End

    stri

    Kon

    trol S

    iste

    mie

    ri Ti

    c. L

    td. S

    ti.

    TR-0

    6810

    Ank

    ara

    Afr

    ica

    AU

    MA

    Sou

    th A

    frica

    (Pty

    ) Ltd

    .

    ZA-1

    560

    Spr

    ings

    Sol

    utio

    n Te

    chni

    que

    Con

    trle

    Com

    man

    de

    DZ-

    Bir

    Mou

    rad

    Rai

    s A

    lgie

    rs

    A.T

    .E.C

    .

    EG

    -Cai

    ro

    Am

    eric

    a

    AU

    MA

    Aut

    oma

    o d

    o B

    razi

    l ltd

    a.

    BR

    - Sao

    Pau

    lo

    AU

    MA

    ACTU

    ATO

    RS

    INC

    .

    US

    -PA

    153

    17 C

    anon

    sbur

    g

    AU

    MA

    Chi

    le R

    epre

    sent

    ativ

    e O

    f ce

    CL-

    9500

    414

    Bui

    n

    LOO

    P S

    . A.

    AR

    -C11

    40A

    BP

    Bue

    nos

    Air

    es

    TRO

    Y-O

    NTO

    R In

    c.

    CA

    -L4N

    8X

    1 B

    arri

    e O

    ntar

    io

    Ferr

    osta

    al d

    e C

    olom

    bia

    Ltda

    .

    CO

    - Bog

    ot

    D.C

    .

    PR

    OC

    ON

    TIC

    Pro

    ceso

    s y

    Con

    trol A

    utom

    tic

    o

    EC

    - Qui

    to

    Cor

    susa

    Inte

    rnat

    iona

    l S.A

    .C.

    PE

    - Mir

    alfl

    ores

    - Li

    ma

    PAS

    SC

    O In

    c.

    PR

    -009

    36-4

    153

    San

    Jua

    n

    Sup

    libar

    ca

    VE

    - Mar

    acai

    bo E

    stad

    o, Z

    ulia

    Asi

    a

    AU

    MA

    Act

    uato

    rs M

    iddl

    e E

    ast W

    .L.L

    .

    BH

    - Sal

    mab

    ad 7

    04

    AU

    MA

    Act

    uato

    rs (T

    ianj

    in) C

    o., L

    td.

    CN

    -300

    457

    Tian

    jin

    AU

    MA

    (IND

    IA) P

    RIV

    ATE

    LIM

    ITE

    D

    IN-5

    60 0

    58 B

    anga

    lore

    AU

    MA

    JAPA

    N C

    o., L

    td.

    JP-2

    10-0

    848

    Kaw

    asak

    i-ku

    ,

    Kaw

    asak

    i-sh

    i Kan

    agaw

    a

    AU

    MA

    ACTU

    ATO

    RS

    (Sin

    gapo

    re) P

    te L

    td.

    SG

    -569

    551

    Sin

    gapo

    re

    PE

    RFE

    CT

    CO

    NTR

    OLS

    Ltd

    .

    HK

    - Tsu

    en W

    an, K

    owlo

    on

    DW

    Con

    trols

    Co.

    , Ltd

    .

    KR

    -153

    -702

    Gas

    an-d

    ong,

    Geu

    mC

    hun-

    Gu,

    Seo

    ul

    Pet

    rogu

    lf W

    .L.L

    QA

    - Doh

    a

    Sun

    ny V

    alve

    s an

    d In

    tertr

    ade

    Cor

    p. L

    td.

    TH-1

    0120

    Yan

    naw

    a B

    angk

    ok

    Top

    Adv

    ance

    Ent

    erpr

    ises

    Ltd

    .

    TW- J

    hong

    he C

    ity

    Taip

    ei H

    sien

    (235

    )

    Aus

    tral

    ia

    BA

    RR

    ON

    GJM

    Pty

    . Ltd

    .

    AU

    -NS

    W 1

    570

    Art

    arm

    on

  • Auma India Head Office at Bangalore

    Auma is the worlds leading manufacturer of electric actuators, actuator controls and valve gearboxes for the automation of industrial valves / gates / dampers. Auma has more than 45 years of experience in research & development and manufacturing electric actuators.

    Auma India, a subsidiary of Auma Germany has established itself as the leading brand name in the Indian actuator market, since 1986. Auma India offers the widest range of solutions for torque requirements from 10 Nm to 16000 Nm with or without integral starter for direct actuation and up to 360000 Nm in combination with gearboxes.

    Auma India has state-of-the-art manufacturing facility at Bangalore. It sells its products through the sales offices in Bangalore, Pune, Noida and Kolkata. Auma India has a number of service centers and service representatives across India to ensure prompt after-sales service.

    This brochure provides an overview of the functions and applications of Auma India multi-turn actuators and actuator controls, for potential users. It can be used as the basis to determine the suitability of a device for the chosen application. For latest information on Auma products, visit or contact our sales team.www.auma.co.in

    Introduction

    3

  • 4 Table of Contents

    Introduction 3 Terminal Plan (OPEN - CLOSE Duty) 44 - 48

    Applications 5 Sample Wiring Diagrams 49 - 52

    Type Designation 6 High Torque Actuator Data Sheets 53 - 58

    Multi-turn Actuators 7 Tests & Test Certificates 59

    Design Principle 8 - 9

    Actuator Services 10

    Signaling & Control Accessories 11 - 14

    Motors 15

    Motor Protection 16

    Actuators for Regulating Duty 17

    Position Transmitters & Positioners 18 - 21

    Types of Actuator Controls 22 - 24

    Mechanical Interface 25

    Electrical Interface 26 - 27

    Modularity - Multiple Applications 28

    Actuator Service Conditions 29

    Technical Data for OPEN -CLOSE Duty 30 - 31

    Electrical Data for OPEN -CLOSE Duty 32 - 33

    Technical Data for Regulating Duty 34

    Electrical Data for Regulating Duty 35

    Dimension Sheet, Norm Actuator 36 - 37

    Dimension Sheet, Epac Actuator 38 - 39

    Dimension Sheet, Wall Mountable Epac Actuator

    40

    Dimension Sheet, Semipact Actuator 41

    Dimension Sheet, Output Drives 42

    Dimension Sheet, Linear Thrust Unit 43

  • Auma India multi-turn actuators of SA range can be used wherever automation of valves are required. Auma India offers customized actuation solutions for diverse applications in various industries to automate flow control devices, on account of:

    l Availability of a wide torque range.l Various combination of Auma actuators and valve gearboxes, thus further extending the torque

    range and / or converting the multi-turn actuator into part-turn, lever or linear actuator.l Availability of a large variety of versions, suitable for use in explosion proof applications, nuclear

    power generation applications.l Fieldbus applications.

    5

    Applications

    Energy Sector l Conventional power plants

    (coal, gas, oil)l Co-generation power plantsl Hydroelectric power plantsl Biogas power plantsl Solar thermal power plantsl Nuclear power plants

    Water Sector l Sewage treatment plantsl Water treatment plantsl Drinking water distributionl Seawater desalination

    Others l Air conditioningl Chemical industryl Pharmaceutical industryl Food industryl Shipbuilding industryl Steel millsl Cement worksl Petrochemical complexesl ...

    Explosion proof actuators and actuators for use in nuclear applications are described in separate catalogues.

  • *For High torque actuator specifications refer High torque actuator data sheets.

    A 22

    Output Drive

    A Stem nut

    B Plug sleeve

    C Dog coupling

    D Stub shaft

    E Bore with keyway

    Output Speed

    4 rpm

    5.6 rpm

    8 rpm

    11 rpm

    16 rpm

    22 rpm

    32 rpm

    45 rpm

    63 rpm

    90 rpm

    125 rpm

    180 rpm

    Model: SAR

    Model: SA

    Model: SAR Semipact

    Model: SA Semipact

    Model: SAR Epac

    Model: SA Epac

    Model: SAREx

    Model: SAEx

    Model: SACEx

    Model: SARCEx

    Regulating Duty

    OPEN- CLOSE Duty

    OPEN- CLOSE Duty

    Regulating Duty

    OPEN- CLOSE Duty

    Regulating Duty

    AF Spring loaded stem nutDD Extended shaft

    Model: SA .1

    Model: SAR .1

    CLOSE Duty

    CLOSE Duty

    CLOSE Duty

    12

    proof

    Proof

    Regulating Duty

    Regulating Duty

    Regulating Duty

    Auma epac

    ExplosionNorm

    ExplosionCompact

    SA

    OPEN-

    OPEN-

    OPEN-

    Torque Rating

    12 kgm

    15 kgm

    25 kgm

    30 kgm

    50 kgm

    60 kgm

    100 kgm

    Type Designation: Example

    3 kgm

    6 kgm

    Auma Norm

    Integral Starter

    Proof

    Semipact

    High Torque *

    Auma

    Auma Explosion

    Auma

    Auma

    Type Designation

    SAR Semipact

    Model

    SA Semipact

    SA epac

    SAR epac

    SARCEx

    SAEx

    SAREx

    SACEx

    ActuatorTypes

    SA

    SAR

    6

  • Multi-turn Actuator SA 3 - SA 100

    Multi-turn Actuator SA 3 - SA 100 Multi-turn Actuator SA 25.1 - SA 40.1

    Auma High Torque Actuator

    Multi-turn Actuator SA 3 - SA 100

    with Integral Starter- Auma Epac

    Multi-turn Actuator SA 3 - SA 100

    Explosion Proof - Auma Compact

    Multi-turn Actuator SA 3 - SA 100

    Explosion Proof - Auma Norm

    Auma Semipact

    Auma Norm

    7

    Multi-turn Actuators

  • Change Gears

    Motor

    Manual Operation

    Terminal Compartment

    Reduction Gearing

    Valve Attachment

    Switch Compartment

    8

    Design Principle

  • Design Principle

    9

    Motor

    To unseat valves from end positions high starting torque is required, which is provided by the motors developed by Auma India.

    is tripped, the sliding worm may move back to initial position by the action of torque measuring springs. This allows torque switch to be released. If control system provides continuous signal, this results in hunting of motor. This can be avoided by the use of auxiliary relay.

    Note on Self Locking:

    Self locking gearing does not ensure safe stopping after an operation. If this is required, separate locking arrangement must be provided.

    Change Gears

    Auma actuators are driven by special combination of gears, which are outside the grease filled housing and require no lubrication. If required, output speed can be easily altered by changing the gear pair and / or motor at site.

    Output Speeds Switch Compartment

    With large range of available output speeds, almost every required time can be achieved with Auma actuators.

    The actuator output speed is determined by the motor speed, change gears and reduction gear ratio of worm / worm wheel.

    The output speeds are available from 4 - 180 rpm.

    During trial run, if found necessary, the output speed can be easily changed by exchanging the change wheels at site. The grease filled housing need not be opened for this purpose. The torque switch setting & limit switch setting remains the same. For actuators with output drive A (Stem nut), max. permissible stem velocity must be observed:l For gate valves max. 500 mm / min.l For globe valves max. 250 mm / min.

    For higher velocities, it is recommended to use spring loaded stem nut type AF (special design).

    Reduction Gearing

    A well proved principle of worm gearing is used to reduce the motor speed to required output speed of actuator. Self locking feature is achieved by worm gearing up to 90 rpm at output. Worm shaft and output shaft with worm wheel run in ample sized bearings. The sliding worm is positioned between two sets of springs on worm shaft. The worm moves axially in relation to thrust, which is the measure for torque. Via lever & gears, the torque measure is transmitted to control unit.

    Self Locking

    Auma multi-turn actuators SA / SAR 3 to SA / SAR 100 are self locking (see note) with exception of output speeds 125 & 180 rpm. Actuators with 125 & 180 rpm are having double start worm drive. After torque switch

    Depending upon type of valve, the actuator must be switched off at the end positions by limit switch or torque switch. For this purpose, independent limit switching or torque switching devices are provided in the switch compartment. The switching devices are easily accessible for any setting at site.

    Terminal Compartment

    All electrical connections are terminated inside the terminal compartment through multi-pin plug & socket connector as standard. Multi-pin plug & socket connectors are provided for ease of connection and maintenance. Screw type connectors are also provided as an option. For detailed information, refer page 26.

    Valve Attachment

    The valve mounting flange is according to ISO 5210 / DIN 3210. Various output drives are available for adaption to various types of valves.

    Mounting Position

    Auma actuators with or without integral starters can be operated without restriction in any mounting position.

    Manual Operation

    Electric actuators have a handwheel to enable operation of the actuator during commissioning or in case of power failure. If the actuator motor is switched on again after manual operation, the handwheel is automatically disengaged from the motor drive.

  • 10

    Actuator Services

    OPEN-CLOSE Duty Short Time and Intermittent Duty as per IS 12824

    The characteristic feature of this actuator is open loop control. The normal valve positions in OPEN-CLOSE duty are end positions OPEN and CLOSE. After receiving command, the actuator operates the valve to one of the end positions or if necessary to a preset intermediate position. The frequency of operation of valves can span between a few minutes to several months.

    Auma multi-turn actuators type SA for OPEN-CLOSE service are rated for short time duty S2-15 min, generally.

    Typical Characteristics of OPEN-CLOSE Duty

    Short time duty S2

    Operation at constant load during a given time, less than that required to reach thermal equilibrium, followed by a rest and de-energized period of sufficient duration to re-establish machine temperatures within 2C.

    The duration of short time is limited to 15, 30 or 60 min.

    Intermittent Duty S4

    A sequence of identical duty cycles, each cycle including a significant period of starting, a period of operation at constant load and a rest and de-energized period. These periods being too short to attain thermal equilibrium during one duty cycle.

    The relative on time at S4-25% is limited to 25% of the cycle time.

    Regulating / Modulating Duty

    The characteristic feature of this actuator is closed loop control in which input command signal to actuator is directly influenced by the flow through the valve. Regulating / Modulating duty actuator SAR operates between two set bands between OPEN-CLOSE positions depending upon actual valve position and feedback signal. The motors of these actuators are rated for intermittent duty S4-25%. The mechanical components and motors are designed to withstand a large number of operations required for modulating applications.

    Permissible number of starts-stops depends upon actuator size & speed. The details are available in data sheets.

    Typical Characteristics of Regulating Duty

  • 11

    Signaling & Control Accessories

    Limit Switching

    The limit switching enables actuators to switch off when reaching defined valve position, usually end positions. The valve travel is measured by mechanical counter gear mechanism, which when reaching the set switching points, operate the electrical limit switches by cams. The setting accuracy is 1/10 of a turn of actuator output shaft.

    In limit switching, Two train counter gear and Four train counter gear versions are available. Four Train Counter Gear

    Two Train Counter Gear Torque Switching

    For Two train counter gear, two limit switches, one for each direction of travel having 1 NO + 1 NC or 2 NO + 2 NC contacts are provided. The number of spindle turns can be set between 1 and 480 or 1 and 4800.

    Two Train Counter Gear

    The torque switching enables to switch off the actuator when pre-determined torque is reached. The torque switching works on principle of sliding worm.

    Axial displacement of worm proportional to thrust is transmitted to torque switches. Torque switches operate in closing & opening directions. The required tripping torque can be easily set on the graduated dial and can be read directly in daNm. If limit switch cut off is selected prior to torque switch, then torque switch serves as overload protection.

    For tight seating of certain valves, the actuator must be operated to end position CLOSED with defined force. Such operation can be carried out by torque seating. Limit seating is commonly used in the end position OPEN.

    When torque seating is used at end position, limit switches can be used for signalization. Therefore, actuator controls can differentiate whether actuator was switched off by torque switch or by limit switch. Micro switches of torque switching are provided with 1 NO + 1 NC or 2 NO + 2 NC contacts for both open and close directions.

    Torque Switching

    Four Train Counter Gear

    If limit switching is required at two end positions only, Two train counter gear is used. However, if two additional intermediate switching positions are desired, Four train counter gear is required. This limit switching has four counter gears and four limit switches. Two counter gears are used to switch off at end positions as in Two train counter gear while the other two are available for setting any desired intermediate positions between end positions. After cam actuation, the switches remain actuated till reaching end of valve travel.

    Example of such applications are:l To stop at intermediate position.l Sequence control, that is to start another

    equipment like pump or bypass valve actuator after certain travel of valve.

    The accuracy of setting is 1/10 of a turn of actuator output shaft. For four train counter gear, four limit switches of 1 NO + 1 NC or 2 NO + 2 NC contacts are provided.

    Running Indication

    Blinker switch is provided in the actuator and can be used as running indicator.

    Blinker Switch

  • Technical Data - Micro Switch Ratings

    Type of Switch Type of CurrentRating in Amp at

    Approximate Electrical Contact Rating30 V 75 V 125 V 250 V

    Limit and Torque

    AC, cos = 0.8 Inductive 8 7 6 5

    50,000 cycles at 250 V AC, 5 A

    DC Inductive5 1 0.2 0.1 50,000 cycles at 250 V DC, 0.1 A

    DC Resistive 7 1 0.5 0.25 50,000 cycles at 250 V DC, 0.25 A

    Blinker AC, cos = 0.8 Inductive 4

    Signaling & Control Accessories

    12

    Micro Switches

    With the help of micro switches, mechanical parameters such as travel & torque are converted into electrical signals for actuator control. There are four switches in the basic version:l One limit switch each for the end positions OPEN

    and CLOSE.l One torque switch each for the directions OPEN

    and CLOSE.

    Limit switches are tripped when an end position is reached and torque switches are tripped when the set tripping torque is exceeded.

    The micro switches are individually sealed to enclosure protection class IP 66, as per IS 13947. The micro switches have double break change over potential free contacts. The circuit is interrupted simultaneously at two points. The basic versions of the switch contacts are of silver. For low current ratings, micro switches with gold plated contacts are available as an option.

    l Switching another circuit also with different voltage and current.

    l Safety function, to operate with single switch.

    l Multiplying the available contacts, example for signalization.

    For such applications, a relay is recommended since there may be small differences in tripping points of tandem switches.

    Tandem Micro Switch

    Single and Tandem Micro Switches

    Limit and torque switches are available in single or tandem versions.

    Single Micro Switch

    Limit or torque switches in tandem version have additional switching contacts. These contacts can be wired for following applications:

  • 13

    Signaling & Control Accessories

    Technical Data - Remote Position Indicator

    Potentiometer

    Standard : 220 Ohms, 3W, Linearity 3%Optional : 100, 560, 1000 Ohms, 3W, Linearity 3%Precision : 200, 500, 1000 Ohms, 5000 Ohms1W, Linearity 0.5%

    Power Supply Unit

    PS 01, Input 220 V, 50 Hz, Output 24 V DC

    Position Meter 0 - 100% in various sizes

    Reduction Gear Unit

    A reduction gear unit (RGU) in the actuator is used for mechanical position indication, remote position indication and for operation of intermediate switches. The output shaft of the actuator drives final output shaft of RGU through a series of reduction gears and final shaft turns by approximately 270 while actuator output shaft performs full number of turns as set on Two train or Four train counter gear unit. The reduction gear ratio needed for each particular case is fitted at works if the ratio is known. For this purpose fixed RGU is supplied. If the ratio needs to be altered at site, variable ratio RGU is available, which allows simple modification at site depending upon number of output shaft for full stroke of valve.

    Reduction Gear Unit (RGU)

    Remote Position Indicator

    The position of the valve can be transmitted as a continuous signal for remote indication. A potentiometer mounted on RGU is used for this purpose. A power supply unit provides necessary voltage to the potentiometer. The potentiometer rotates through 270 for one full stroke of valve & output signal from potentiometer is proportional to valve travel. Thus, the actual position of the valve can be read continuously on position meter calibrated & mounted on control panel.

    Remote Position Indicator

    Digital Remote Position Indicator

    The position display can be provided by digital remote position indicator, which displays open position in percentage.

    Digital Remote Position Indicator

    Position Indicators

    Continuous Mechanical Position Indicator

    Adjustable discs having symbols for OPEN and CLOSE indicate the position of the valve continuously. The discs can be seen through an indicator glass on switch compartment cover. The OPEN-CLOSE discs can be set to coincide with limit switching. The mechanical position indicator requires reduction gear unit for operation.

    *As an option digital mechanical position indicator can be provided in place of mechanical position indicator.

    Continuous Mechanical Position Indicator

  • 14

    Technical Data - Space Heater

    Volts, AC 230 230 110 110 24

    Resistance, Ohms 5 k 2.7 k 1.2 k 0.6 k 120

    Rating, Watts 10 20 10 20 5

    Signaling & Control Accessories

    Intermediate Switches Space Heater

    With this limit switching, additional switching points can be set for each direction of rotation. The switching can be set between 25% and 75% of valve travel in each direction. The switch sub-assembly consisting of 2 or 4 cam switches is mounted on output shaft of RGU. Each micro switch has 1 NO + 1 NC contact.

    Intermediate Switches

    Condensation in the actuator is possible due to wide fluctuation of the ambient temperature. The heater integrated in the control unit prevents the water condensation. The heater is rated for continuous duty.

    *Self regulating space heater and space heater with thermostat can also be provided on request.

    Manual Operation

    During commissioning or in an emergency or when there is no power supply, actuator can be operated by handwheel. The manual drive is engaged by means of a lever. When motor starts running, the manual drive gets disengaged immediately & handwheel does not rotate during power operation.

    In manual operation, hammer blow can be effected with handwheel. The hammer blow makes it possible to open a jammed or rarely operated valve.

    Top Bevel Gear Set

    Using a side mounted handwheel instead of the standard handwheel can further reduce manual effort on the handwheel. Reduction ratios available are:

    SA 3 / 6 / 12 / 15 2:1SA 25 / 30 / 50 / 60 3:1SA 100 4:1

    Instead of handwheel, a chain pulley can also be provided for actuators mounted in inaccessible zones.

    Top Bevel Gear Set

  • 15

    Motors

    Technical Data - Motor

    3 ph AC Motor 1 ph AC Motor** DC Motor*

    Voltages / Frequency

    Std 50 Hz 415 V

    50 Hz 220 V - 240 V

    440 V, 220 V, 110 V, 48 V, 24 V

    Optional

    50 Hz / 60 Hz

    220 V, 380 V, 400 V, 415 V, 440 V, 460 V, 480 V, 500 V, 550 V, 690 V

    Permissible Variation in Voltage 10% 10% 10%

    Motor Standard IS 325 IS 996 IS 4722

    Mounting C Type Flange, B14, IS 2223

    Enclosure Protection IP 67 or IP 68 after mounting IP 55 after mounting

    Type of Cooling Surface Cooled

    Insulation ClassIS 1271

    Std. : F ClassOptional : H Class

    Starting Direct On LineDirect On Line(Not applicable for above 4.0 kW rating motors)

    Type of Duty S2-15 min. or S4-25% as per IS 12824

    Direction of Rotation Bi-directional

    Motor Protection 3 Thermoswitches 2 Thermoswitches 4 Thermoswitches

    Motors

    As a standard, Auma multi-turn actuators are equipped with 3 phase induction motors. Auma motors are class F insulated and withstand winding temperature up to 140C.

    The motors are used for short time duty (S2-15 min. or S4-25% as per IS 12824) and provide approximately three times rated torque for short duration. The size of the motor is smaller compared to continuous duty motor S1 of same output power. This results in reduced inertia of the rotor and therefore less overshoot after switching off the motor. Auma motors are designed for enclosure protection class IP 55 / IP 67 / IP 68 when mounted on the actuator (See Technical data for motor). All motor cables are brought to terminal compartment cover from inside of the actuator thus avoiding terminal box.

    Single Phase AC Motors

    Auma actuators can be supplied with single phase AC motor. The required capacitor is fitted in the terminal compartment cover.

    DC Motors

    Auma actuators are also available with DC motors. These motors operate on 24 V, 48 V, 110 V, 220 V or 440 V DC supply.

    AC Motors with Other Voltages and Frequency

    Three phase induction motors are available in wide range of operating voltages from 220 V to 690 V and operating frequency of 50 or 60 Hz.

    * For detailed information on DC motors, please contact Auma.

    ** 1 ph AC motor for given voltages is available only for 0.06 / 0.12 / 0.25 kW for 1400 rpm.

  • 16

    Technical Data - Thermoswitch

    AC Voltage Switch Rating

    250 V AC Cos =1 2.5 A

    250 V AC Cos =0.6 1.6 A

    Tripping Temp. 140C

    Reset Temp. 90 - 110C

    Technical Data - TPU

    Supply Voltage110 / 230 / 380 / 415 V AC 10%, 50 Hz24 V DC 10%

    Input Max. 6 numbers PTC thermistors

    Ambient Temperature -5C to + 55C

    Output Contacts 2 change over (2 NO + 2 NC) potential free contacts

    Rated at 4 Amps 230 V

    Operational life 1 million on / off operation

    Motor Protection

    Motor Protection

    Thermoswitch

    Motor winding may get overheated if the actuator is run beyond rated duty or if the rotor is stalled for considerable longer time or if too high ambient temperature is encountered. In order to protect the motor against overheating, thermoswitches are embedded in the windings of three phase, single phase AC motors and DC motors. When integrated into the control circuits, they will protect the motor against damage due to excessive winding temperature.

    The thermoswitches interrupt the control circuit as soon as winding temperature of 140C is exceeded. After cooling down to a temperature of approximately 110C, the actuator can be switched on once again.

    Note: The motor protection device must be integrated into the controls, otherwise warranty for motor becomes null & void.

    Thermistors

    Another way of protecting the motor from burnout due to overheat is through Thermistors. Thermistors are temperature sensors, which are basically of two types:l PTC (Positive Temperature Coefficient)l NTC (Negative Temperature Coefficient)

    Normally PTC thermistors are used, which has low resistance under normal conditions and whose resistance increases to a very high value at critical temperature. The response time of thermistor is very less, to the tune of

  • 17

    Actuators for Regulating Duty

    Description of Regulating Duty

    Auma actuators of type SAR are suitable for Regulating duty / Modulating duty. SAR actuator achieves any position of travel between 0 - 100% of valve stroke depending on the remote set point command given by the customers DCS / PLC. SAR actuators differ from SA actuators in several respects:

    l 4 pole motors are used to reduce overshoot.l Worm with high quality finish on flanks for better

    efficiency.l Disc springs on worm shaft are pre-compressed to

    reduce dead band when reversing.

    While selecting Auma actuators for regulating duty applications, following points should be noted:

    l Max. no. of starts - 1200 cycles / hour with motor power up to 0.55 kW and 600 cycles / hour with motor power above 0.55 kW.

    l Output speed of actuator max. 45 rpm.l Torque for regulating duty should not exceed 50%

    of max. torque of actuator.l Max. torque of actuator can be used for seating

    and unseating of the valve.l For reversing service, duration of impulse should

    be minimum of 50 ms. l Electronic position transmitter or precision

    potentiometer should be used for remote position indication.

    l The motor should be short time duty class S4 - 25%.

    The SAR actuator basically consists of control units as explained in following diagram:

    Principle of Operation:

    SAR: Regulating duty actuator

    MSAR: Sensor for actuator, i.e., position transmitter at actuator (potentiometer or inductive LVDT)

    MUSAR: Signal converter for SAR i.e., Electronic position transmitter (RWG 1001 / 2002) or Inductive position Transmitter (IWG 1002 / IWG 1003)

    V : Regulating valve

    W : Reference input

    CU 01: Electronic positioner

    M : Sensor for regulating valve

    MU : Signal converter for sensor

    SE : Setting nominal value

    XR : Input value at controller

    YR : Output value at electronic positioner

  • 18

    Technical Data - RWG 1001

    Configuration 3 Wire

    Supply Voltage 24 V DC Min. 18, Max. 33 V

    Output Current 0 / 4 - 20 mA

    Input Resistance 150 kOhms

    Displacement of zero position, Max. 25%

    Displacement of end position, Max. from 50 to 100%

    Influence of supply voltage variation Max. 0.2%

    Temp. Drift 0.2% 10C

    Linearity not considering potentiometer 0.05%

    Technical Data - RWG 2002

    Configuration 2 Wire

    Supply Voltage 24 V DC Min. 18, Max. 33 V

    Ouput Current 4 - 20 mA

    Input Resistance 150 kOhms

    Displacement of Zero Position, Max. 25%

    Displacement of End Position, Max. From 60 to 100%

    Influence of supply voltage variation Max. 0.15%

    Linearity not considering potentiometer < 1%

    Position Transmitters & Positioners

    Electronic Position Transmitter RWG 1001 Electronic Position Transmitter RWG 2002

    This device is a signal converter for the transformation of resistance value into proportionate current signal. It can also be placed in the actuator where the position determined by the potentiometer is converted into 4 -20 mA current signal.

    As position transmitter, preferably a potentiometer of 4.7 kOhm should be used so that the reference voltage source is not overloaded. This device requires 24 V DC power supply regulated within 15%. Auma power supply unit PS 01 is recommended for this purpose. RWG 1001 is a 3 wire system and is having linearity of 0.05%.

    RWG 1001

    This is basically same as RWG 1001, however with 2 wire system. The linearity is less than 1%.

    RWG 2002

  • Technical Data - RWG 2002 DG

    Supply Voltage 24 V DC10% regulated

    Output 1 (Isolated)Output 2 (Isolated)

    0 / 4 - 20 mA0 / 4 - 20 mA

    Current Drawn 100 mA

    Adjustability of Span 50%

    Adjustability of Zero 25%

    Change in Output due to Input Supply Variation < 0.2%

    Linearity Error for both Outputs < 1%

    Technical Data - IWG 1002

    Configuration 2 Wire

    Supply Voltage 24 V DC15% regulated

    Output Current 4 - 20 mA

    Resistance Max. 600 Ohms

    Displacement of zero position, Max. 25%

    Displacement of end position, max. 60 to 100%

    Temp. drift 0.4% / 10C

    Linearity (not considering LVDT) < 0.3%

    19

    Position Transmitters & Positioners

    Dual Output Position Transmitter RWG 2002 DG Inductive Position Transmitter IWG 1002

    It is a signal converter device for the transformation of resistance value into proportionate galvanically isolated two current outputs. This device requires 24 V DC power supply regulated within 10%. Auma power supply unit PS 01 is recommended for this purpose.

    When using Auma actuators for regulating duty with demand of high accuracy, an inductive position transmitter can be fitted to give precise read out of position.

    The output signal is used as feedback to electronic positioner or for position indicator. The system consists of two parts, a linear variable differential transformer (LVDT) and an electronic unit. The smallest change of magnetic core in the measuring coil is transformed into proportional signal. The transmitter has no moving contacts. This device requires 24 V DC power supply regulated within 15%. Auma power supply unit PS 01 is recommended for this purpose. The linearity of the unit is less than 0.3%.

    IWG 1002

  • Technical Data - CU 01

    Input We1 XE1

    0 - 20 mA (4 - 20 mA)0 - 20 mA (4 - 20 mA)or 0 - Uref

    Time delay 1 - 20 sec.

    Adjustment of zero point 0 - 20%

    Adjustment of end position 60 to 100%

    Sensitivity (dead band) 1% - 10%

    Relay output (max. resistive load) 230 V, 10 A

    Technical Data - IWG 1003

    Configuration 3 Wire

    Supply Voltage 24 V DC15% regulated

    Output Current 0 / 4 - 20 mA

    Resistance Max. 600 Ohms

    Displacement of zero position, Max. 25%

    Displacement of end position, max. 60 to 100%

    Temp. drift 0.4% / 10C

    Linearity (not considering LVDT) < 0.3%

    20

    Technical Data - Potentiometer

    Resistance 4.7 kOhm 0.5%

    Power Rating 3 Watt at 40C

    Angle of Rotation 275 5

    Linearity 0.5%

    Position Transmitters & Positioners

    Inductive Position Transmitter IWG 1003 Electronic Positioner CU 01

    IWG 1003 is similar to IWG 1002 however with 3 wire system.

    IWG 1003

    The electronic positioner CU 01 is designed as a three level positioner for regulating of actuator. By comparing two input signals (reference signal W & regulating signal X), the positioner determines the difference. In case this exceeds a certain value, the actuator is switched on by relays. The direction of rotation (opening or closing) depends upon the plus or minus sign of the deviation. Thus, the regulating signal generated by potentiometer or LVDT changes & when the regulating signal & reference signal become equal, the actuator stops as long as no new correction is required.

    CU 01

    Potentiometer

    A potentiometer is used as sensor for actuator. Single turn wire wound potentiometer with 4.7 kOhm with linearity 0.5% is available for this purpose. It is available in single or tandem version.

  • Technical Data - Signal Isolator

    Power Supply230 V AC 15%110 V AC 15%24 V DC 1 V

    Input Signal 4 - 20 mA1 - 5 V

    Output Signal4 - 20 mA single4 - 20 mA dual4 - 20 mA & 1 - 5 V

    Accuracy 0.1% of output sapn

    Zero & span adjustment 2% min. at zero10% min. at span

    21

    Technical Data - PS 01

    Supply voltage and frequency

    220 V or 115 V (15%)50 Hz or60 Hz

    Power drawn 9 VA

    Output voltage max. 24 V 1 V DC

    Amounting Snap on type for DIN rail 46277

    Position Transmitters & Positioners

    Signal Isolator

    Auma signal isolator are available in various versions:Power supply conditions:230 V AC, 110 V AC or 24 V DCVarious input signals:4 - 20 mA or 1 - 5 V

    Signal IsolatorVarious output signals:4 - 20 mA single or dual or 4 - 20 mA & 1 - 5 V.

    Isolation is provided between input and output and also between two outputs.

    Uo, thus Uc can serve as common reference potential for whole regulating system.

    Supply voltage to PS 01 is 220 V or 110 V 15%, 50 Hz

    The maximum output voltage is Uo = 24 V 1 V DCUc = 5.5 V 0.5 V DC

    Version I

    Version II : For remote position indication with potentiometer 220 Ohms as position transmitter. In this, two additional potentiometers P1 and P2 are provided for positions zero and maximum. A voltmeter of 1 V, calibrated in % is used for visual indication of valve travel. This voltmeter is connected to the PS 01 (Version II) as shown below:

    Version II

    Power Supply Unit PS 01

    This unit gives 24 V DC power supply for electronic positioner CU 01 and electronic position transmitter, in case 24 V DC is not available at site.There are two versions available:

    Version I : For regulating application with CU 01:

    The output voltage Uo & Uc require no trimming potentiometer. The voltage Uc is diverted from voltage

  • 22

    Types of Actuator Controls

    Auma Norm Actuators

    This actuator offers a complete actuator type SA with electric motor, torque switch for OPEN-CLOSE direction, limit switches for both end positions and blinker transmitter for running indication. The required reversing contactor should be installed separately and wired to the motor. For signalization of the switching and to trip the contactors over micro switches, control wires are required from actuator terminal compartment cover to reversing contactor installed separately.

    Auma Norm

    Integral Starter - Auma Epac

    Auma Semipact Actuator

    Aumas semipact actuator is a basic actuator with additional features of selector switch and push button station. Motor controls and switchgear are external to the actuator and are in customers scope. Auma India semipact actuator is available for both isolation and regulating duty services.

    The mode of operation depending on the selector switch position could be:

    l Local: actuator can be operated in the Local mode by using the push button station in the OPEN-STOP-CLOSE position. The running direction can be indicated by the LEDs on the actuator.

    l Remote: actuator can be operated in the Remote mode by supplying controls through the external motor control center. LEDs on the actuator would indicate the running direction of the actuator in the remote mode as well.

    l Stop: actuator can not be operated in either mode.There is a provision to lock the selector switch in any position using a padlock.

    Following additional (optional) accessories can be incorporated:

    l Power Supply Unit PS 01 for 24 V DC output.l Electronic Positioner CU 01. l Electronic Position Transmitter RWG (Contact

    type) / IWG (Non - contact type).

    Auma Semipact

    Auma Integral Starter Actuators

    The purpose of offering integral motor controls for the actuator is to enable the customer to save high installation costs for external controls. Actuators with integral controls include control & switching elements and are supplied ready for use.

    All electrical components such as limit, torque, thermoswitches, all monitoring elements and position transmitters are integrated into modern controls. This results in following simplification:

    l No extensive wiring in the external control cabinet.l Several actuators can be connected to common

    supply cable using isolation switch for each actuator.

    l Actuator signals are processed in the controls, only feedback to process control system is necessary.

    l Integral starter housing can be easily replaced due to multi-pin plug & socket connector between actuator & integral starter unit.

    l Actuator can be operated from Local or Remote position by means of selector switch on the integral starter unit.

  • 23

    Types of Actuator Controls

    Control Versions of Integral Starter Units

    Auma Epac

    The electronic version of Auma India integral starter epac incorporates sophisticated electronic controls with field programming feature. Epac is modular in construction and consists of power supply module, relay module and programmable control logic module.

    Power Supply Module

    Power supply module consists of

    l 24 V DC, 150 mA source.l Mechanically interlocked.l Local controls.

    Relay Module

    Relay module consists of

    l Monitor relay for collective fault signals (Thermoswitch trip, torque switch trip in mid travel) with potential free contacts.

    l Local status annunciation (green) and fault annunciation (red) by LEDs.

    Programmable Control Logic Module

    Programmable control logic module consists of:

    l Inching and non-inching in local mode by dip switches.

    l Inching and non-inching in remote mode by dip switches.

    l Limit switch seating or torque seating by dip switches.

    Different versions of epac and optional features make the actuator controls adaptable to any field situation. Versions and optionals available are:

    Auma Epac

    l Emergency shutdown (ESD).l 2 wire make - break.l Timer board to run the actuator in ON-OFF steps.l OPEN-CLOSE inhibit.

    l Negative switching.l Remote control and local stop.l Electronic positioner for regulating duty with or

    without isolator.l Single phase protection and Automatic phase

    correction.l Remote annunciation relays.l Thermal overload relay.l Positioner with PID features.l Wall mountable controls.

    For detailed literature, refer separate catalogue.

    Fieldbus Interface (Option)

    Auma India integral starter actuators are available with 2 wire control. The actuators follow open industrial protocol conforming to MODBUS RTU standards (other protocols could be provided on request).

    MODBUS is an application layer messaging protocol, which provides Master / Slave communication between various digital automation devices that are interconnected on RS-485 twisted pair cable.

    Transfer Mode

    l RS-485 twisted pair cable.l Auma actuators support baud rates up to 38.4

    kbits

    Bus Access

    l Master (Host) - Slave (Actuators) technique.l Maximum of 247 slaves can be connected on one

    bus, with repeaters after every 32 slaves and without repeaters maximum of 32 slaves.

    Communications

    l Through various read / write registries and coils.l MODBUS RTU protocol.

    Protection Functions

    l Parity check for each byte.l CRC check for each message.

  • 24

    Types of Actuator Controls

    Auma Epac with Wall Mountable Feature Auma High Torque Actuator

    Auma actuators with integral starter can also be provided with the unique feature of wall bracket mounting, where epac controls are mounted on a wall bracket separately.

    Advantages of wall mountable epac actuators

    l Protects actuator electronics from severe environmental conditions.

    l Easy accessability of the epac controls for the operators in difficult to reach positions i.e., when valves with actuators is in pit head or elevation etc.

    l Protection against induced vibration in valves and actuator controls in case of severe vibrations in pipeline.

    l Prevents exposure of actuator controls against high temperature.

    l Normally, maximum distance between actuator and wall mountable epac unit is 100 m.

    Auma Epac with Wall Mountable Feature

    Auma offers a range of multi-turn high torque actuators SA 25.1 - SA 40.1 and SAR 25.1 - SAR 30.1 for applications demanding high torque with low operating time. The maximum output torque ranges from 2000 Nm to 16000 Nm for OPEN-CLOSE duty and 2000 Nm to 4000 Nm for regulating duty applications. For detailed information, refer Technical, Electrical data sheets and dimension sheets of high torque actuator.

    High Torque Actuator

    Note : Please contact Auma for additional information on high torque actuator for regulating duty application.

    Auma India Master Station (AIMS)

    Auma India has introduced a Master Station solution known as AIMS, which is used to integrate actuators into an automation environment. It has a modular design suitable for open Fieldbus protocols such as MODBUS RTU. It has GUI based interface and can be adapted to most conditions while using an identical interface. AIMS master station is a significant part of a commissioning support system, network manager, data concentrator or diagnostic tool and can be integrated to any DCS using open industrial protocols.

    Auma India Master Station

  • Flange Sizes

    Actuators size SA / SAR

    Max. Torque Nm ISO 5210 DIN 3210

    3 30 F10 G0

    6 60 F10 G0

    12 120 F10 G0

    15 150 F10 G0

    25 250 F14 G1/2

    30 300 F14 G1/2

    50 500 F14 G1/2

    60 600 F14 G1/2

    100 1000 F16 G3

    Technical Data

    Linear Thrust Unit

    Tr. Thread

    Max. Thrust kN

    Stroke Length mm

    LTU 6 24 x 5 20 50 & 100

    LTU 12 32 x 6 35 60 & 120

    LTU 25 40 x 7 63 80 & 160

    LTU 50 50 x 8 100 80 & 160

    LTU 100 60 x 9 175 130

    25

    Mechanical Interface

    Output Drives

    Various output drive types according to ISO 5210 / DIN 3210 are available in order to adapt the actuators to different types of valves. Special sizes can be supplied on request.

    Output Drive Type - A (Stem nut)

    The output drive has stem nut for rising or non-rotating valve stem. The mounting flange together with stem nut and thrust bearing form one assembly, which is suitable for accepting thrust loads.

    Output Drive Type - B (Plug sleeve)

    Plug sleeve has bore and keyway and is designed for transmission of torque.

    Output Drive Type - C (Dog coupling)

    This is similar to type B, however with dog coupling for torque transmission.

    Output Drive Type - D (Stub shaft)

    The shaft with key engages with bore and keyway of mating part.

    Output Drive Type - E (Bore with keyway)

    This type is mainly used for connecting to a gearbox, example Auma gearbox type GS (worm / worm wheel) or GK (bevel gearbox).

    Linear Thrust Unit (LTU)

    With the linear thrust unit, the rotary movement of the actuator output shaft is converted into an axial movement. Thus, the multi-turn actuator becomes linear actuator. Different stroke lengths can be provided.

    Output Drive Type - AF (Spring-loaded stem nut)

    Spring-loaded stem nut for rising and non-rotating valve stems. The springs compensate for dynamic thrust for high speeds or even for thermal expansion of valve stem.

    Valve Attachment

    Valve attachment is according to ISO 5210 or DIN 3210.

    Stem Protection Tube

    To protect rising valve stem, optionally a protection tube can be fitted to the handwheel hub. Internal threads are provided in the handwheel hub as a standard. If protection tube is not required, the bore of the handwheel hub is closed with lid.

    Stem Protection Tube

  • 26

    Electrical Interface

    Technical Data

    Power Earth Controls

    50 Pin Plug & Socket Connector, Circular

    No. of Contacts 6 (3 Used) 1 50

    Voltage Max. 750 V - 250 V

    Current Max. 25 A - 16 A

    Type of connections for customer use

    Screws Screws Screws

    Cross sec. max. (sq. mm.)

    6 6 2.5

    Technical Data

    Power Earth Controls

    64 Pin Plug & Socket Connector, 32 x 2 & 3 + 1

    No. of Contacts 3 1 64

    Voltage Max. 750 V - 500 V

    Current Max. 25 A - 16 A

    Type of connections for customer use

    Stud Screws Screws

    Cross sec. max. (sq. mm.)

    6 6 2.5

    Technical Data

    Power Earth Controls

    72 Pin Plug & Socket Connector, 24x 3 & 3 + 1

    No. of Contacts 3 1 72

    Voltage Max. 750 V - 250 V

    Current Max. 25 A - 16 A

    Type of connections for customer use

    Stud Screws Screws

    Cross sec. max. (sq. mm.)

    6 6 2.5

    Electrical Connection

    Terminals

    Plug & Socket Connector

    The actuators are equipped with plug & socket connectors in three versions as a standard.

    Version I:

    50 pin circular connector for control6 + 1 = 7 pins for power

    50 Pin Circular Plug & Socket Connector

    Version II:

    32 x 2 = 64 pins for control 3 + 1 = 4 pins for power

    64 Pin Plug & Socket Connector

    Version III:

    24 x 3 = 72 pins for control 3 + 1 = 4 pins for power

    72 Pin Plug & Socket Connector

  • 27

    Technical Data

    Power Earth Controls

    Screw Type Connector

    No. of Contacts 3 1 64

    Voltage Max. 750 V - 500 V

    Current Max. 34 A - 25 A

    Type of connections for customer use

    Screws / Stud

    Screws / Stud

    Screws

    Cross sec. max. (sq. mm.)

    4 4 2.5

    Electrical Interface

    Electrical Connection

    Terminals (Optional)

    Screw Type Connector

    Screw type connectors are also used for electrical connection as optional. Stud type terminals can be provided for power connections. Terminals are DIN rail mountable and are available as single or double decker versions also.

    Screw Type Connector

    From epac to customer connections:

    50 pin circular connector or 64 pin connector or 72 pin connector can be provided at the customer end connection depending on number of terminals required.

    Optional: As an option screw type connectors can also be provided on case to case basis.

    Threads for Cable Glands

    As a standard, Auma actuators are supplied with 3 cable glands with Metric threads having 2 glands of size M32x1.5, and 1 gland of size M25x1.5. The cable glands are directly tightened on the threads provided in cable entry cover. The cable gland holes are plugged with metallic plugs and o-rings to prevent ingress of dust and water during transportation and storage. The plugs can be retained in unused openings during usage.

    Additional cable gland of size M20x1.5 and M16x1.5 can also be provided as per the requirement. For additional protection under extreme conditions for weather proof and water proof applications, double compression cable glands in various sizes can be supplied.

    Optional

    BSC and NPT threads can also be provided on request. Maximum numbers of cable glands that can be provided in the KLK (screw type) cover are 6 and in Terminal (plug & socket type) cover are 5.

    Note: Please note other cable gland options such as different number of cable glands and sizes can be provided on request.

    Electrical Connection for Integral Starter Versions

    Between actuator and epac:

    Depending on number of terminals required, 50 pin circular connector or 64 pin connector or 72 pin connector can be provided between actuator and epac. This simplifies troubleshooting at site.

  • 28

    Modularity - Multiple Applications

    Actuator - Gearbox Combinations

    Combination with Worm Gearboxes

    In combination with worm gearboxes of type GS 63.2 to GS 500, a multi-turn actuator is converted into part-turn actuator usually for 90 movements. This is an ideal solution for large part-turn valves with high torque requirements. The torque range goes up to 360000 Nm.

    Actuator with GS Gearbox

    Combination with Bevel Gearboxes

    By combining multi-turn actuators with bevel gearboxes GK 10.1 to GK 40.1, the torque speed ranges are considerably extended. Output torques up to 16000 Nm and thrust load up to 1375 kN are possible.

    Actuator with GK Gearbox

    Combination with Foot Mounted Worm Gearboxes

    Louvers, dampers or valves, which are operated via lever arrangement require foot mounted worm gearboxes. For such applications, multi-turn actuator is combined with foot mounted worm gearbox type GF 63 to GF 315. The torque range goes up to 90000 Nm.

    Actuator with GF Gearbox

    For additional details, refer Auma India gearbox catalogue.

    Trunion Mounted Linear Actuators

    Auma also offers customized actuation solution for dampers, chutes, gates, diverters or flap applications, based on thrust and stroke length requirement. Auma trunion mounted actuators provide linear travel. An attachment to the actuator converts output torque of multi-turn actuator into an axial thrust.

    Actuator with Trunion Mounting

  • 29

    Type Actuator Type Temperature Range

    SA Standard Multi-turn actuator

    -20 to +80C

    SAR Multi-turn actuator for Regulating duty

    -20 to +60C

    SAExSARExSACExSARCEx

    Explosion Proof actuators, standard, compact and regulating duty

    -20 to +50C

    Type of Paint Epoxy

    Standard Color DA Grey IS 5

    Primer Thinkness 40 microns min.

    Paint Thickness 75 microns min.

    Actuator Service Conditions

    Actuator Models

    Actuator Type Model

    Explosion ProofNorm (OPEN-CLOSE Duty)

    SAEx 3 / 6 / 12 / 15 SAEx 25 / 30 / 50 / 60SAEx 100

    Explosion ProofNorm (Regulating Duty)

    SAREx 6 / 12 / 15 SAREx 25 / 30 / 50 / 60SAREx 100

    Explosion ProofCompact (OPEN-CLOSE Duty)

    SACEx 3 / 6 / 12 / 15 SACEx 25 / 30 / 50 / 60SACEx 100

    Explosion ProofCompact (Regulating Duty)

    SARCEx 6 / 12 / 15 SARCEx 25 / 30 / 50 / 60SARCEx 100

    Enclosure Protection Painting

    Auma actuators conform to enclosure protection IP 68 as per IS 13947 (Part I) : 1993, Appendix C / IEC 60947 - 1 : 2004. The definition of IP 67 & IP 68 as per standard is as follows :

    IP : Ingress Protection

    First Numeral 6 : Dust tight, prevents ingress of dust.

    Second Numeral 7 : Protected against the effects of immersion. Test is made by completely immersing the equipment in water so that:

    l Surface of water is at least 150 mm above highest point of equipment.

    l The lowest point of equipment is at least 1 m below the surface of water.

    l Duration of test is 30 min.

    Under above conditions, ingress of water in harmful quantity shall not be possible.

    Second Numeral 8 : Test conditions as above, however no ingress of water is permitted.

    Other paints & color can be provided based on mutually agreed customer requirement.

    Explosion Proof / Flame Proof Actuators

    For installation of actuators in potentially hazardous or explosive area, special protective measures are required. These are specified in Indian Standard IS 2148-2004 Specifications for Flame Proof Enclosures of Electrical Apparatus. Auma India actuators developed for this purpose are suitable for group II gases and in application other than coal mines. The enclosures of explosion proof / flame proof actuators are designed in consideration of clauses specified in IS 2148-2004 and the actuators have been tested and certified by CIFMR, Dhanbad.

    Necessary approvals from statutory authorities have been obtained.

    For details, refer separate Flame proof / Explosion proof catalogue.

    Ambient Temperature

    * Other ambient temperature requirement can be provided on request.

    - CE Marking

    Auma has certified its weather proof actuators and valve gearboxes as CE marked to indicate conformity with the essential health and safety requirements at the place of use.

  • 30

    Technical Data OPEN-CLOSE Duty

    SA 3 - SA 100

    Model

    Output Speed at 50Hz

    rpm

    1) Torque RangeS2-15min

    Running 2) Torque

    S2-15min Nm

    Valve Attachment Stem Dia. O/P drive Type A

    Max. mm

    Permissible Thrust for

    Type A Max. kN

    Hand- wheel

    Dia. Std. mm

    Handwheel Ratio

    Weight (without epac unit)4) approx.

    Min.Nm Max.NmStandard DIN:3210

    Option ISO:5210 Std.

    With TBG* Std. kg With TBG* kg

    SA 3

    11

    20 30 11 G 0 F 10 26 25 250 1:1 2:1 33 39

    162232456390

    3)1253)180

    SA 3.5 16 20 35 11.5 G 0 F 10 26 25 250 1:1 2:1 33 39

    SA 6

    4

    20 60 21 G 0 F 10 26 40 250 1:1 2:1 33 39

    5.6811162232456390

    3)125 553)180

    SA 12

    4

    40 120 42 G 0 F 10 38 60 250 1:1 2:1 33 39

    5.6811162232456390

    3)125 1103)180

    SA 15

    4

    50 150 53 G 0 F 10 38 60 250 1:1 2:1 33 39

    5.68111622324563

    SA 25

    4

    100 250 88 G F 14 52 120 360 1:1 3:1 71 87

    5.6811162232456390

    3)125 2203)180

    1) Tripping torque adjustable for both direction.2) Permissible average torque for the whole travel.3) Non Self locking.4) The approximate weight of an epac unit is 16 Kg.

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

    20

    40

    100

    Technical Data for OPEN - CLOSE Duty

  • .

    31

    Technical Data OPEN-CLOSE Duty

    SA 3 - SA 100

    Model

    Output Speed at 50Hz

    rpm

    1) Torque RangeS2-15Min.

    Running 2) Torque

    S2-15min Nm

    Valve Attachment Stem Dia. O/P drive Type A

    Max. mm

    Permissible Thrust for

    Type A Max. kN

    Hand-wheel

    Dia. Std. mm

    Handwheel Ratio

    Weight (without epac unit)4) approx.

    Min.Nm Max.NmStandard DIN:3210

    Option ISO:5210 Std.

    With TBG* Std. kg

    With TBG* kg

    SA 30

    4

    100 300 105 G F 14 52 120 360 1:1 3:1 71 87

    5.6811162232456390

    3)125 2643)180

    SA 50

    4

    200 500 175 G F 14 52 160 640 1:1 3:1 99 116

    5.6811162232456390

    3)125 4503)180

    SA 60

    4

    200 600 210 G F 14 52 160 640 1:1 3:1 99 116

    5.6811162232456390

    3)125 5403)180

    SA 100

    4

    400 1000 350 G 3 F 16 65 190 800 1:1 4:1 131 152

    5.6811162232456390

    3)125 9003)180

    Enclosure: IP68 - IS:13947 (Part I) :1993, Appendix C / IEC 60947 - I : 2004.

    Actuators are rated for short time duty S2-15 min, based on 40C ambient temperature. The nominal current is based on running torqueapproximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat a valve) and the current can riseto max. value, refer corresponding column for current at max. torque in Electrical Data.

    Note : Revolution for Full Stroke (Min./Max.) - 1 - 480 or 1 - 4800 * - Top Bevel Gear Set.

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

    100

    200

    200

    400

    Technical Data for OPEN - CLOSE Duty

  • 32

    Electrical Data for OPEN - CLOSE Duty

    11 0.06 1400 63 0.29 0.31 1.216 0.06 1400 63 0.29 0.38 1.222 0.06 1400 63 0.29 0.50 1.232 0.12 1400 63 0.65 0.87 2.345 0.18 2800 63 0.58 0.9 3.363 0.18 2800 63 0.58 1.3 3.390 0.37 2800 63 1.32 1.9 5.7125 0.37 2800 63 1.32 1.6 5.7180 0.37 2800 63 1.32 2.2 5.7

    SA3.5 16 35 0.06 1400 63 0.29 0.42 1.24 0.06 1400 63 0.29 0.29 1.2

    5.6 0.06 1400 63 0.29 0.31 1.28 0.06 1400 63 0.29 0.38 1.2

    11 0.12 1400 63 0.65 0.7 2.316 0.12 1400 63 0.65 0.87 2.322 0.12 1400 63 0.65 1.2 2.332 0.18 2800 63 0.58 1.3 3.345 0.37 2800 63 1.32 1.9 5.763 0.37 2800 63 1.32 2.4 5.790 0.55 2800 71 1.5 3.08 9.0125 0.55 2800 71 1.5 2.45 9.0180 0.55 2800 71 1.5 3.52 9.04 0.06 1400 63 0.29 0.38 1.2

    5.6 0.12 1400 63 0.65 0.7 2.38 0.12 1400 63 0.65 0.87 2.3

    11 0.12 1400 63 0.65 1.2 2.316 0.25 1400 71 1.2 1.45 4.622 0.25 1400 71 1.2 1.80 4.632 0.37 2800 63 1.32 2.5 5.745 0.55 2800 71 1.5 3.08 9.063 1.1 2800 71 2.9 4.58 16.090 1.1 2800 71 2.9 6.50 16.0125 1.1 2800 71 2.9 5.10 16.0180 1.1 2800 71 2.9 7.50 16.04 0.06 1400 63 0.29 0.45 1.2

    5.6 0.12 1400 63 0.65 0.8 2.38 0.12 1400 63 0.65 1.2 2.3

    11 0.25 1400 71 1.2 1.36 4.616 0.25 1400 71 1.2 1.66 4.622 0.37 2800 63 1.32 2.2 5.732 0.55 2800 71 1.5 2.75 9.045 1.1 2800 71 2.9 4.26 16.063 1.1 2800 71 2.9 5.67 16.04 0.12 1400 63 0.65 0.95 2.3

    5.6 0.25 1400 71 1.2 1.29 4.68 0.55 1400 71 1.75 1.64 7.6

    11 0.55 1400 71 1.75 1.92 7.616 0.55 1400 71 1.75 2.60 7.622 0.55 1400 71 1.75 3.58 7.632 1.1 2800 71 2.9 4.75 16.045 1.1 2800 71 2.9 6.58 16.063 2.2 2800 90 4.1 8.44 3590 2.2 2800 90 4.1 12.5 35125 2.2 2800 90 4.1 8.95 35180 2.2 2800 90 4.1 13.6 35

    250

    220 8585

    75758585

    67

    67

    30

    150

    60

    55

    120

    110

    6475

    6767

    75755060

    50506060

    75757548

    60647575

    50505060

    75757548

    50656464

    48485050

    64644848

    0.880.880.88

    48484850656564

    0.530.5

    0.720.88

    0.660.72

    0.66

    0.660.66

    0.720.6

    0.530.53

    0.53

    0.530.5

    0.53

    0.710.710.710.6

    0.6

    0.660.610.61

    0.72

    0.60.60.6

    0.530.660.660.610.610.61

    0.72

    SA 12

    Three phase Squirrel cage AC Motor 415V, 50 Hz

    Nominal Output

    kW

    Speed rpm Size

    Nominal Current / Full Load Current *

    A

    Current at Max.

    Torque1) A

    Starting Current

    A

    0.71

    0.50.610.710.72

    SA 3

    Power Factor Cos Full Load Efficiency (%)

    0.72

    0.60.60.6

    0.530.53

    Electrical Data SA 3 - SA 100OPEN-CLOSE Duty

    Torque

    0.53

    max. Nm

    Model

    Output Speed at 50Hz

    rpm

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

    1) Current at max. torque. We recommended to select switch gear and cables suitable for those values.

    SA 6

    0.72

    0.50.61

    SA 25

    SA 150.5

    * Whenever actuators are supplied with integral starter with TOLR, the tripping current set on the TOLR is same as nomial current / Full Load current.

  • 33

    Electrical Data for OPEN - CLOSE Duty

    4 0.12 1400 63 0.65 1.2 2.35.6 0.25 1400 71 1.2 1.39 4.68 0.55 1400 71 1.75 1.77 7.6

    11 0.55 1400 71 1.75 2.20 7.616 0.55 1400 71 1.75 3.08 7.622 1.1 1400 90 2.9 3.95 25.032 1.1 2800 71 2.9 5.72 16.045 1.25 2800 90 2.7 8.65 22.063 2.2 2800 90 4.1 10.0 3590 2.5 2800 90 4.7 15.5 35125 2.5 2800 90 4.7 11.5 35180 4.0 2800 90 9.0 16.5 604 0.25 1400 71 1.2 1.48 4.6

    5.6 0.55 1400 71 1.75 1.95 7.68 0.55 1400 71 1.75 2.60 7.6

    11 0.55 1400 71 1.75 3.58 7.616 1.1 1400 90 2.9 4.80 25.022 1.1 1400 90 2.9 6.65 25.032 2.2 2800 90 4.1 8.52 3545 2.2 2800 90 4.1 12.5 3563 4.0 2800 90 9.0 17.1 6090 4.0 2800 90 9.0 26.0 60125 4.0 2800 90 9.0 18 60180 4.0 2800 90 9.0 30 604 0.25 1400 71 1.2 1.67 4.6

    5.6 0.55 1400 71 1.75 2.2 7.68 0.55 1400 71 1.75 3.08 7.6

    11 0.55 1400 71 1.75 5.15 7.616 1.1 1400 90 2.9 5.75 25.022 2.2 1400 90 5.7 7.92 3532 2.2 2800 90 4.1 10.04 3545 4.0 2800 90 9.0 15.05 6063 4.0 2800 90 9.0 21.08 6090 4.0 2800 90 9.0 36 60125 5.0 2800 112 10.8 22.5 90180 5.0 2800 112 10.8 35.5 904 0.55 1400 71 1.75 2.55 7.6

    5.6 0.55 1400 71 1.75 3.85 7.68 0.75 1400 90 1.85 4.65 12.0

    11 1.1 1400 90 2.9 6.65 25.016 2.2 1400 90 5.7 9.06 3522 2.2 1400 90 5.7 12.5 3532 4.0 2800 90 9 17.5 6045 4.0 2800 90 9 26.0 6063 7.5 2800 112 15 40.0 116.090 7.5 2800 112 15 60.0 116.0125 7.5 2800 112 15 44.6 116.0180 7.5 2800 112 15 68.0 116.0

    Nominal Output

    kW

    Speed Sizerpm

    Nominal Current / Full Load Current *

    A

    Current at Max.

    Torque1) A

    Starting Current

    A

    Power Factor Cos Full Load Efficiency (%)

    Electrical Data SA 3 - SA 100OPEN-CLOSE Duty

    Model

    0.53 50

    Output Speed at 50Hz

    rpm

    Torque max. Nm

    Three phase Squirrel cage AC Motor 415V, 50 Hz

    SA 30

    0.5 60

    670.66 67

    0.66 670.66

    0.72 750.72 750.81 790.88 850.88 84

    0.5 600.66 67

    0.88 840.82 82

    0.66 670.66 670.72 750.72 750.88 850.88 850.82 820.82 82

    0.5 600.66 67

    0.82 820.82 82

    0.66 670.66 670.72 750.7 77

    0.88 850.82 820.82 820.82 82

    0.66 670.66 67

    0.84 880.84 88

    0.75 750.72 750.7 770.7 77

    0.82 840.82 84

    0.82 820.82 82

    0.82 840.82 84

    below there will be reduction of nominal output.Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our Warranty is void if those thermoswitches are not connected in control circuit.

    Permissible voltage variation: 10%, Permissible frequency variation : 5%, Permissible combined variation: 10% if voltage drops

    Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.* Whenever actuators are supplied with integral starter with TOLR, the tripping current set on the TOLR is same as nomial current / Full Load current.

    1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.

    300

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

    264

    SA 50500

    450

    SA 60600

    540

    SA 1001000

    900

  • 34

    Technical Data for Regulating Duty

    Technical Data Regulating duty

    SAR 3 - SAR 100

    Model

    Output Speed at 50Hz

    rpm

    Torque 1) Range S4-

    25%

    Modulating 2) Torque

    S4-25% Nm

    Valve Attachment Number of starts

    max. c/h

    Stem Dia. O/P drive

    Type A Max.mm

    Permissible Thrust for

    Type A Max. kN

    Hand-wheel

    Dia. Std. mm

    Handwheel Ratio

    Weight (without epac unit)4)

    approx.

    Min.Nm Max.Nm Standard DIN:3210 Option ISO:5210 Std.With TBG*

    Std. kg

    With TBG* kg

    SAR 3

    11

    20 30 20 G 0 F 10 1200 26 25 250 1:1 2:1 33 3916223245

    SAR 6

    4

    30 60 30 G 0 F 10 1200 26 40 250 1:1 2:1 33 39

    5.681116223245

    SAR 12

    4

    60 120 60 G 0 F 10 1200 38 60 250 1:1 2:1 33 39

    5.681116223245 900

    SAR 15

    4

    60 150 75 G 0 F 10 1200 38 60 250 1:1 2:1 33 39

    5.6811162232

    SAR 25

    4

    120 250 125 G F 14 1200 52 120 360 1:1 3:1 71 87

    5.68111622 900

    60032

    SAR 30

    45

    150 300 150 G F 14 1200 52 120 360 1:1 3:1 71 87

    45.681116

    6002232

    SAR 50

    45

    250 500 250 G F 14

    1200

    52 160 640 1:1 3:1 99 116

    45.6811 900

    600162232

    SAR 60

    45

    300 600 300 G F 14

    1200

    52 160 640 1:1 3:1 99 116

    45.68

    6001622

    SAR 100

    32

    500 1000 500 G 3 F 16 65 190 800 1:1 4:1 131 152

    4 12005.6 900

    60081116223245

    1) Tripping torque adjustable for both direction.

    3) The approximate weight of an epac unit is 16 kg.2) Permissible average torque for the whole travel.

    Encloser: IP68 - IS:13947 (Part I) : 1993, Appendix C / IEC 60947 - I : 2004

    Actuators are rated for intermittent duty S4-25% ED, based on 40 C ambient temperature. The nominal current is based on modulating torque of approximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat a valve ) and the current can raise to max. value, refer corresponding column for current at max. torque in Electrical Data.

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

  • 35

    Electrical Data for Regulating Duty

    11 0.06 1400 63 0.29 0.31 1.216 0.06 1400 63 0.29 0.38 1.222 0.06 1400 63 0.29 0.50 1.232 0.12 1400 63 0.65 0.87 2.345 0.18 1400 71 0.69 1.0 4.24 0.06 1400 63 0.29 0.29 1.2

    5.6 0.06 1400 63 0.29 0.31 1.28 0.06 1400 63 0.29 0.38 1.2

    11 0.12 1400 63 0.65 0.7 2.316 0.12 1400 63 0.65 0.87 2.322 0.12 1400 63 0.65 1.2 2.332 0.25 1400 71 1.2 1.45 4.645 0.25 1400 71 1.2 1.86 4.64 0.06 1400 63 0.29 0.38 1.2

    5.6 0.12 1400 63 0.65 0.7 2.38 0.12 1400 63 0.65 0.87 2.3

    11 0.12 1400 63 0.65 1.2 2.316 0.25 1400 71 1.2 1.45 4.622 0.25 1400 71 1.2 1.80 4.632 0.55 1400 71 1.75 2.52 7.645 0.55 1400 71 1.75 3.52 7.64 0.06 1400 63 0.29 0.45 1.2

    5.6 0.12 1400 63 0.65 0.8 2.38 0.12 1400 63 0.65 1.2 2.3

    11 0.25 1400 71 1.2 1.36 4.616 0.25 1400 71 1.2 1.66 4.622 0.55 1400 71 1.75 2.20 7.632 0.55 1400 71 1.75 3.08 7.64 0.12 1400 63 0.65 0.95 2.3

    5.6 0.25 1400 71 1.2 1.29 4.68 0.25 1400 71 1.2 1.64 4.6

    11 0.55 1400 71 1.75 1.92 7.616 0.55 1400 71 1.75 2.60 7.622 0.55 1400 71 1.75 3.58 7.632 1.1 1400 90 2.9 4.80 25.045 1.1 1400 90 2.9 6.67 25.04 0.12 1400 63 0.65 1.2 2.3

    5.6 0.25 1400 71 1.2 1.39 4.68 0.25 1400 71 1.2 1.77 4.6

    11 0.55 1400 71 1.75 2.20 7.616 0.55 1400 71 1.75 3.08 7.622 1.1 1400 90 2.9 3.95 25.032 1.1 1400 90 2.9 5.75 25.045 2.2 1400 90 5.7 8.0 354 0.25 1400 71 1.2 1.48 4.6

    5.6 0.55 1400 71 1.75 1.95 7.68 0.55 1400 71 1.75 2.60 7.6

    11 0.55 1400 71 1.75 3.58 7.616 1.1 1400 90 2.9 4.80 25.022 1.1 1400 90 2.9 6.65 25.032 2.2 1400 90 5.7 9.06 3545 2.2 1400 90 5.7 13.4 354 0.25 1400 71 1.2 1.67 4.6

    5.6 0.55 1400 71 1.75 2.2 7.68 0.55 1400 71 1.75 3.08 7.6

    16 1.1 1400 90 2.9 5.75 25.022 2.2 1400 90 5.7 7.92 3532 2.2 1400 90 5.7 11.1 354 0.55 1400 71 1.75 2.55 7.6

    5.6 0.55 1400 71 1.75 3.85 7.68 0.75 1400 90 1.85 4.65 12.0

    11 1.1 1400 90 2.9 6.65 25.016 2.2 1400 90 5.7 9.06 3522 2.2 1400 90 5.7 12.5 3532 4.0 1400 112 8.3 18.5 5645 4.0 1400 112 8.3 27 56

    0.54 67

    SAR 3 20

    0.6 480.6 480.6 48

    0.53 50

    * Whenever actuators are supplied with integral starter with TOLR, the tripping current set on the TOLR is same as nomial current / Full Load current.

    Full Load Efficiency (%)

    Nominal Current / Full Load Current *

    A

    Current at Max.

    Torque1) A

    Starting Current

    A

    Power Factor Cos

    7575

    84

    77776767

    606767

    Electrical Data SAR 3 - SAR 100Regulating duty

    Modulating

    75

    Torque Nm

    Model

    Output Speed at 50Hz

    rpm

    Three phase Squirrel cage AC Motor 415V, 50 Hz

    Nominal Output

    kW

    Speed rpm Size

    Permissible voltage variation: 10%, Permissible frequency variation : 5%, Permissible combined variation: 10% if voltage drops

    Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our Warranty is void if those thermoswitches are not connected in control circuit.Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.

    We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

    below there will be reduction of nominal output.

    1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.

    75757777

    60676767

    67757577

    50606067

    67677575

    50606067

    60606767

    67485050

    50606067

    60485050

    0.72

    0.7

    0.8

    48484850505060

    0.70.660.660.75

    0.660.660.720.7

    0.720.70.70.5

    0.660.660.660.72

    0.720.720.70.5

    0.50.5

    0.660.66

    0.660.720.720.53

    0.50.5

    0.660.66

    0.50.660.660.53

    0.60.530.530.5

    0.50.5

    0.660.66

    0.60.530.530.53

    0.530.530.50.5

    0.60.60.6

    0.53

    SAR 60 300

    SAR 100 500

    SAR 30 150

    SAR 50 250

    SAR 15 75

    SAR 25 125

    SAR 6 30

    SAR 12 60

    0.8 84

    0.7 7777

  • 36

    Dimension Sheet, Norm Actuator

  • 37

    Dimension Sheet, Norm Actuator

  • 38

    Dimension Sheet, Epac Actuator

  • 39

    Dimension Sheet, Epac Actuator

  • 40

    Dimension Sheet, Wall Mountable Epac Actuator

    E

  • 41

    Dimension Sheet, Semipact Actuator

  • Dimension Sheet, Output Drives

    42

  • Sam

    ple

    Term

    inal

    Pla

    n an

    dW

    irin

    g D

    iagr

    ams

    for

    SA

    (R)3

    - S

    A(R

    )100

    43

    Dim

    ensi

    on S

    heet

    , Lin

    ear

    Thru

    st U

    nit

  • Te

    rmin

    al P

    lan

    (OP

    EN

    -CLO

    SE

    Dut

    y)

    44

  • 45

    Ter

    min

    al P

    lan

    (OP

    EN

    -CLO

    SE

    Dut

    y)

  • 46

    Te

    rmin

    al P

    lan

    (OP

    EN

    -CLO

    SE

    Dut

    y)

  • 47

    Ter

    min

    al P

    lan

    (OP

    EN

    -CLO

    SE

    Dut

    y)

  • 48

    Te

    rmin

    al P

    lan

    (OP

    EN

    -CLO

    SE

    Dut

    y)

  • 49

    Sample Wiring Diagram for ON-OFF DutyIn

    tegr

    al S

    tarte

    r sui

    tabl

    e fo

    r RE

    MO

    TE-O

    PE

    N-S

    TOP

    -CLO

    SE

    Dig

    ital S

    igna

    l

  • Sample Wiring Diagram for ON-OFF Duty

    50

    Inte

    gral

    Sta

    rter s

    uita

    ble

    for R

    EM

    OTE

    -OP

    EN

    -STO

    P-C

    LOS

    E D

    igita

    l Sig

    nal

  • 51

    Sample Wiring Diagram for Regulating DutyIn

    tegr

    al S

    tarte

    r with

    Pos

    ition

    er s

    uita

    ble

    for R

    emot

    e 4-

    20 m

    A S

    igna

    l / O

    PE

    N-S

    TOP

    -CLO

    SE

    Dig

    ital S

    igna

    l

  • Sample Wiring Diagram for Regulating Duty

    52

    Inte

    gral

    Sta

    rter w

    ith P

    ositi

    oner

    sui

    tabl

    e fo

    r Rem

    ote

    4-20

    mA

    Sig

    nal /

    OP

    EN

    -STO

    P-C

    LOS

    E D

    igita

    l Sig

    nal

  • 53

    High Torque Actuator Data Sheet

    Technical data Multi-turn actuators for OPEN - CLOSE duty with 3-phase AC motors

    SA 25.1 SA 40.1

    Output speed

    rpm Torque range1) For S2-15 min

    Running torque2) for type of duty

    Valve attachment

    Handwheel

    50 Hz

    60 Hz

    min. Nm

    max. Nm

    max. Nm Standard

    EN ISO

    5210

    Option

    DIN

    3210

    Valve stem diameter

    for a rising valve stem3)

    max. mm

    mm

    Reduc-

    tion ratio

    approx.

    kg5)

    4 4.8 45:1

    5.6 6.7 32:18 9.6 45:1

    11 13 32:116 19 45:122 26 32:1

    150

    32 38 45:145 54 32:163 75 45:1

    SA 25.1

    90 108

    630

    2,000 700 F 25 G4

    95 400

    32:1

    160

    4 4.8 45:1

    5.6 6.7 32:18 9.6 45:1

    11 13 32:116 19 45:122 26 32:1

    190

    32 38 45:145 54 32:163 75 45:1

    SA 30.1

    90 108

    1,250

    4,000 1,400 F 30 G5

    115 500

    32:1

    260

    4 4.8 180:1

    5.6 6.7 125:18 9.6 180:1

    11 13 125:116 19 180:1

    22 26 125:1

    410

    324)

    384)

    90:1

    SA 35.1

    454)

    4544)

    2,500

    8,000 2,800 F 35 G 6 155 400

    64:1 425 4 4.8 180:1

    5.6 6.7 125:18 9.6 180:1

    11 13 125:116 19 180:1

    22 26

    16,000

    125:1

    SA 40.1

    324)

    384)

    5,000

    14,000

    5,600

    F 40 G 7 175 500

    90:1

    510

    General information

    Multi-turn actuators Auma Norm require electric controls. Auma offers the actuator epac controls.

    Type of duty

    6)

    Standard: Short-time duty S2 15 min

    Motors 3-ph AC asynchronous motor

    Insulation Class Standard: F,

    Tropicalized Option: H, Tropicalized

    Motor Protection Standard: Thermoswitches (NC)

    Self locking Yes, for out speeds 4 to 90 rpm and from size SA 35.1 for output speeds from 4 to 22 rpm

    1)

    Tripping

    torque adjustable for both directions.

    2)

    Permissible

    average torque for the whole travel.

    3)

    For output drives type A and B1.

    4)

    Non Self locking.

    5)

    Weight for multi-turn actuator Auma Norm with 3-phase AC motor,

    standard electrical

    connection, output drive type B1 and handwheel. 6)

    For nominal voltage and

    20 C ambient temperature at

    an average load with running torque.

    We

    reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of

    this

    document.

    Type

  • 54

    Technical data Multi-turn actuators for OPEN - CLOSE duty with 3-phase AC motors

    SA 25.1 SA 40.1

    Limit switching

    Counter gear mechanism for end positions CLOSED and OPEN

    For 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)

    Standard: Single switch (1 NC and 1 NO) for each end position, not galvanically isolated

    Options: Tandem switch (2 NC and 2 NO) for each end position, switches galvanically isolated

    Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated

    Intermediate position switch (DUO limit switching), available for any intermediate position.

    Torque switching

    Torque switching for direction OPEN and CLOSE, infinitely

    adjustable

    Standard: Single switch (1 NC and 1 NO) for each direction, not galvanically isolated

    Options: Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated

    Position feedback signal, analogue (options)

    Potentiometer or 0/4 20 mA (RWG / IWG)

    Mech. position indicator

    (option) Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED

    Running indication Blinker transmitter

    Heater in

    switch

    compartment Space heater,

    10

    / 20 W,

    110 240 V AC

    Manual operation Manual drive for setting and emergency operation,

    handwheel does not

    rotate during electric operation.

    Option:

    Handwheel

    lockable

    Electrical connection Control connections on Auma

    plug & socket connector

    Motor connection on terminals

    Threads for cable glands Standard: Metric threads

    Options:

    Other threads on request

    Terminal plan

    Will be provided based on the requirement.

    Output drive types

    A, B1, B2, B3, B4 according to EN ISO 5210 (Refer page 58)

    A, B, D, E according to DIN 3210

    C according to DIN 3338

    Special output drives on request.

    Service Conditions

    Enclosure protection Standard: IP

    67

    Options: IP

    68

    Color Standard:

    DA Grey

    Option:

    Other colors on request

    Ambient temperature

    Standard:

    -20 to +80 C We

    reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of

    this

    document.

    High Torque Actuator Data Sheet

  • 55

    High Torque Actuator Data Sheet

    Electrical data multi-turn actuators for OPEN-CLOSE duty with 3 phase AC motors Short-time duty S2 - 15 min., 415 V / 50 Hz

    SA 25.1 SA 40.1

    Multi-turn actuator

    Motor

    Type

    Speed

    rpm Torque

    max. Nm

    Type

    Power PN (kW)

    Speed rpm

    Nominal current1)

    IN (A) Current2)

    approx. Imax. (A)

    Starting

    current IA (A)

    Cos 4 5.6

    AD00 90-8/130 AD00 90-8/130

    1.1

    1.1700 700

    6.4

    6.4

    8.2

    9.2

    16 16

    0.48 0.48

    8

    11

    AD00 90-4/130 AD00 90-4/130

    3.0

    3.01,400 1 400

    6.4

    6.410 11

    35 35

    0.80 0.80

    16

    22

    AD00 90-2/130 AD00 90-2/130

    4.0

    4.02,800 2 800

    9.2

    9.215 18

    53 53

    0.78 0.78

    32

    45

    AD00 132-4/140 AD00 132-4/140

    7.5

    7.51,400 1 400

    20 20

    37 44

    110 110

    0.65 0.65

    SA 25.1

    63

    90

    2,000

    AD00 132-2/180 AD00 132-2/180

    15 15

    2,800 2 800

    27 27

    55

    6 4174

    1740.90 0.90

    4 5.6

    AD00 112-8/140 AD00 112-8/140

    2.2

    2.2700 700

    10 10

    14 15

    33 33

    0.58 0.58

    8

    11

    AD00 112-4/110 AD00 112-4/110

    5.5

    5.51,400 1 400

    12 12

    18 21

    55 55

    0.77 0.77

    16

    22

    AD00 112-2/140 AD00 112-2/140

    7.5

    7.52,800 2 800

    16 16

    26 27

    110 110

    0.78 0.78

    32

    45

    AD00 160-4/160 AD00 160-4/160

    15 15

    1,400 1 400

    40 40

    53 61

    201 201

    0.63 0.63

    SA 30.1

    63

    90

    4,000

    AD00 160-2/215 AD00 160-2/215

    30 30

    2,800 2 800

    60 60

    119 13 7

    339

    339

    0.88 0.88

    4 5.6

    AD00 132-8/150 AD00 132-8/150

    4

    4700 700

    18 18

    27 32

    64 64

    0.44 0.44

    8

    11

    AD00 132-4/140 AD00 132-4/140

    7.5

    7.51,400 1 400

    20 20

    44 50

    110 110

    0.65 0.65

    16

    22

    AD00 132-2/180 AD00 132-2/180

    15 15

    2,800 2 800

    27 27

    55 64

    174 174

    0.90 0.90

    SA 35.1

    32

    45

    8,000

    AD00 160-2/214 AD00 160-2/214

    20 20

    2,800 2 800

    37 37

    73

    8 7238 238

    0.90 0.90

    4 5.6

    AD00 160-8/165 AD00 160-8/165

    7.5

    7.5700 700

    27 27

    50 53

    85 85

    0.50 0.50

    8

    11

    AD00 160-4/160 AD00 160-4/160

    15 15

    1,400 1 400

    40 40

    64 80

    201 201

    0.63 0.63

    16

    22

    16,000

    AD00 160-2/215 AD00 160-2/215

    30 30

    2,800 2 800

    60 60

    137 156

    339 339

    0.88 0.88

    SA 40.1

    3 2 14,000 AD00 160-2/215 30 2,800 60 183

    339

    0.88

    Motor data are approximate. Due to usual manufacturing tolerances, there may be deviations from the values given. The permissible fluctuation of the nominal voltage is 10 %. If the voltage drops below, there is a reduction of the nominal output torque. To protect against overheating, thermoswitches are embedded in the

    motor windings. For actuators

    without integral

    controls (Auma Norm), these have to be connected to the external control circuit.

    If thermoswitches are not connected, warranty for motor becomes void:

    Rating

    of the thermoswitches:

    For further details refer to Technical data multi-turn actuators for OPEN-CLOSE duty

    with 3-phase AC motors SA 25.1 SA 40.1 .

    1) Current

    at running torque according to Technical data SA 25.1 SA 40.1 2) Current at max. torque. We

    recommend to select switching

    devices according to these

    values.

    We

    reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of

    this

    document.

    AC

    DC

    250 V. 50 60 Hz

    60 V

    1.0 A

    Cos = 1

    2.5 A

    42 V

    1.2 A

    Cos = 0.6

    1.6 A

    24 V

    1.5 A

  • 56

    High Torque Actuator Data Sheet

  • 57

    High Torque Actuator Data Sheet

  • 58

    Output drives DimensionsAUMAmulti-turn actuator type

    SA 25.1 SA 30.1 SA35.1 SA40.1

    EN ISO 5210 F25 F30 F35 F40

    F max.kN 380 460 875 1375

    d1 300 350 415 475

    d2 f8 200 230 260 300

    d3 254 298 356 406

    d4 M16 M20 M30 M36

    d5 100 120 160 180

    d6 max. 95 115 155 175

    g 130 160 185 225

    h 5 5 5 8

    h3 20 25 38 45

    L 126 156 175 210

    Z 8 8 8 8

    Weight kg 35 56 125 2001)b


Recommended