34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014
ADDENDUM TO LIT91127U
EVO 79 - 599 CONFIGURED INODD WATER SYSTEM™ DESIGN
WARNING
These appliances MUST be installed by a properly licensed individual in the City and State which the unit is being installed. All start up adjustments and subsequent service work must be done by a similarly licensed contractor or a factory trained service individual. Failure to comply could result in loss of warranty and or severe personal injury, death and or substantial property damage. These instructions are required to be kept with the appliance on the left side, in the pocket provided.
INNOVATIVE CONDENSING TECHNOLOGYBy Hamilton Engineering, Inc.
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014
All safety precautions referenced to in LIT91127U (EVO 79 - 599 Universal Installation and Operating Manual) should be STRICTLY adhered to!
There are two basic system configurations. Please determine which style you have and refer to the specific instructions where indicated. Please contact Hamilton Engineering, Inc. at 800.968.5530 if you have any questions regarding system configurations.
(FIGURE 1) SYSTEM DESIGN A
(FIGURE 2) SYSTEM DESIGN B
This system design employs a storage tank with integral heating coils and will require only one circulating pump.
This system design employs an external heat exchanger and requires one circulating pump for the closed loop (boiler) side and a bronze pump for the fresh water (storage tank) side.
Page 2 of 9
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014
SYSTEM REQUIREMENTS
System requirements beyond what is listed here can be found in LIT91127U (EVO 79-599 Universal Installation and Operating Manual):
Electrical:
System B: 208 – 240 volt amperage per system rating plate, 208-230 volt per stainless steel pump rating plate. Wiring diagram is located on page 9 of this Manual.
Service Clearances:
System B: Provide adequate access to heat exchanger for periodic acid cleaning and or removal for additional service as required
System operation:
System A – The L 4006A storage tank temperature control shall be set at the desired storage tank water temperature (per original design), on approximately a 5°F drop from desired setpoint, the SPST switch in the L 4006A will make, closing the heat enable circuit on the heating boiler. After receiving this signal, the boiler control will start the cast iron pump and initiate a firing sequence and provide the required closed loop water temperature (generally 150°F – 180°F; see system design specifications) as set by user on the red wheel located next to the temperature display on the front of the boiler, to provide the designed recovery rate through the tank heat exchanger. If there is more than one boiler providing the required BTU capacity, the setting and control wiring shall be done on the Lead labeled boiler only.
System B - The L 4006G storage tank temperature control shall be set at the desired storage tank water temperature (per original design), on approximately a 5°F drop from setpoint, the control will close both internal SPST switches, simultaneously starting the bronze circulating pump and closing the heat enable circuit on the heating boiler. After receiving this signal, the boiler control will start the cast iron pump and initiate a firing sequence and provide the required closed loop water temperature (generally 150°F – 180°F; see system design specifications) as set by user on the red wheel located next to the temperature display on the front of the boiler, to provide the designed recovery rate through the external heat exchanger. If there is more than one boiler providing the required BTU capacity, the setting and control wiring shall be done on the Lead labeled boiler only.
Filling Instructions:
The Odd Water system comes equipped with a pressure reducing fill station for the boiler (closed loop) side of the system, that is pre-piped to EVO system city water connection. Included in this package are a low pressure switch, pressure gauge, air vent, pressure reducing fill valve, expansion tank, check valve, backflow preventer, isolation valves, optional water meter, and a union for easy disassembly. Once the city water connection is made, open the air vent in the fill package and on the top of boiler(s) (models 299-599 ONLY). Once the air vent(s) is open, turn on the city water supply and open the (3) isolation valves, each located on the expansion tank, near the city water connection, and after the pressure reducing valve. When air is no longer bleeding out of the air vent(s), turn the boiler(s) on, which will cycle the pump(s), purging any air remaining in the system.
NOTE: There MUST be a city water supply connected that is regulated down to 12 PSI (via the PRV supplied) for the system to work properly!
Page 3 of 9
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014
Equipment ScheduleLetter Description
A EVO UnitB Cast Boiler Side PumpC Condensate NeutralizerD Hydronic Expansion Tank - 12 PSI Air ChargeE Storage tankF L4006A Temperature ControlG Low Pressure SwitchH Pressure GuageI Air VentJ Fill ValveK Check ValveL Water Meter (Optional)M Backflow PreventerN Hot Water ConnectionO Drain ValvesP Cold Water ConnectionQ Domestic Expansion Tank (Optional)
15
5
10
15
0
2025 3030
3535
60
50
40
45
55
A
N
D
B
C
I
City WaterConnection
(Optional)
J
P
K
QE
O
G
H
M
F (Optional)L
Page 4 of 9
LEttEr on dIAgrAm dESCrIptIon
A EVO unitB Cast Boiler Side PumpC Condensate NeutralizerD Hydronic Expansion Tank - 12 PSI air chargeE Storage TankF L4006A Temperature ControlG Low Pressure SwitchH Pressure GaugeI Air VentJ Fill ValveK Check ValveL Water Meter (optional)M Backflow PreventerN Hot Water ConnectionO Drain ValvesP Cold Water ConnectionQ Domestic Expansion Tank (optional)
(TABLE 1) SYSTEM DESIGN A - PARTS
(FIGURE 3)SYSTEM DESIGN A WITH PARTS
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014
SYSTEM B - PARTS
Page 5 of 9
(FIGURE 4)SYSTEM DESIGN B WITH PARTS
LEttEr on dIAgrAm dESCrIptIon
A EVO unitB Electrical DisconnectC Cast Boiler Side PumpD Condensate NeutralizerE Hydronic Expansion Tank - 12 PSI air chargeF Stainless Steel Domestic Hot Water PumpG Brazed Plate Heat ExchangerH Air VentI Pressure GaugeJ Low Pressure SwitchK Fill ValveL Check ValveM Backflow PreventerN Water Meter (optional)O Storage TankP External Heat Exchanger Cleaning and Draining PortsQ Brass Wye StrainerR Normally Closed Cleaning Bypass ValveS Domestic Expansion Tank (optional)T L4006G Temperature Control
(TABLE 2) SYSTEM DESIGN B - PARTS
AB
C D
E
P
G
H I
R
S
City WaterConnection
O
Q
(Optional)
T
P
F
J
K
L M N
Equipment ScheduleLetter Description
A EVO UnitB Electrical DisconnectC Cast Boiler Side PumpD Condensate NeutralizerE Hydronic Expansion Tank - 12 PSI Air ChargeF Stainless Steel Domestic Hot Water PumpG Brazed Plate Heat ExchangerH Air VentI Pressure GuageJ Low Pressure SwitchK Fill ValveL Check ValveM Backflow PreventerN Water Meter (Optional)O Storage TankP External Heat Exchanger Cleaning & Draining PortsQ Brass Wye StrainerR Normally Closed Cleaning Bypass ValveS Domestic Expansion Tank (Optional)T L4006G Temperature Control
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 6 of 9
ADDITIONAL INFORMATION
Both system designs are completely factory assembled and tested prior to shipping, following assembly at the installation site, however, filling the system requires that proper practices be followed:
The boiler is designed to operate in a closed-loop system. As such, the system should be tight and not require make-up water. A high percentage of untreated make-up water may cause premature failure due to buildup of scale; such failure is not covered by warranty.
Scale can also reduce efficiency. For example, a scale thickness of 1/16” will result in a 12.5% loss of efficiency.
NOTE: Minimum system fill pressure is 12 PSI!
Water pH
The pH of the hydronic system fluid must be between 6.5 and 7.5, for untreated water only. A periodic check of the system pH should be conducted to ensure these pH levels are maintained.
IMPORTANT!Glycol and other additives must be approved by the chemical manufacturer for use in 316L stainless steel boilers as well as the circulating pumps used with the boilers and heating system, and you must maintain the required pH levels as recommended by the glycol or treatment chemical manufacturer to prevent damaging the boiler and or pumps.
If the water quality exceeds our known safe thresholds, we wave the red flag of caution:
• Water hardness can be no more than 12 grains (205 ppm or mg/l) • TDS (Total Dissolved Solids) can be no more than 450 ppm (mg/l) • PH - below 6.5 or above 7.5 For total combined hardness over 15 grains (250 ppm or mg/l) or longer pipe lengths, contact Hamilton Engineering for correct pump sizing. Combined, the hardness and TDS can be no more than 450 ppm. Our internal term for this is the TCH (Total Combined Hardness).
The amount of oils, fats, grease, and other organic matter should be limited to 10 ppm.Consult your water conditioning or chemical treatment supplier for analysis and recommendations.
Flushing the System
Before filling the boiler, flush the system to remove any debris from construction or maintenance. Clean and flush old piping thoroughly before installing the boiler.
IMPORTANT!Under no circumstances should the hydronic system be flushed while the boiler is attached to the system since the debris or corrosion products could accumulate in the boiler and plug the boiler heat exchanger.
IMPORTANT!If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected from the system and a bypass installed so that the chemical cleaning solution does not circulate through the boiler. Following chemical cleaning, the system should be thoroughly rinsed to remove cleaning agents prior to reconnecting the boiler to the system.
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 7 of 9
ODD WATER WIRING DIAGRAMS
LEAD OR SINGLE BOILER ONLY - SYSTEMS A & B
ST-1 ST-4 ST-5 ST-7ST-6ST-3ST-2
21 3 4 5 6
SensorIndirect
SensorOutdoor
Sensor orAquastat
External
2826
L1
Power Supply
L2
208-240 Vac
2787
+ -0-10VDC
AdditionalHeat SourceDry Contact Dry Contact
SignalLock Out
1211109 23 2522
L1
24
Pump 3
L2
Pump 1
L1L2
L1
Divertor Valve Indirect
Pump 2-indirect
L1
1917 20 21
L2
18
open closecom.
L1L2
not i
n us
e
ThermostatRemote
+ -Cascade
Connection
161513 14
Optional C
onnectionM
ust connect + to + and - to - between appliances in cascade
Optional C
onnectionU
sed for storage tank or comm
on line sensing
Optional C
onnectionC
onnection from L 4006 therm
ostat
Optional C
onnectionB
uilding managem
ent system
Optional C
onnectionFor use w
ith Central heating for outdoor reset To G
round
Optional C
onnection
Optional C
onnection
For use with additional heat needed w
/cascade
For use with alarm
bell / light
Service S
witch
A B C D E F G H I J K L M
Optional C
onnectionU
sed for indirect tank
Optional C
onnectionP
ump 2: U
sed in a boiler system w
ith both CH
& D
HW
Pum
p 1: Boiler P
ump
Pum
p 3: Heater P
ump
Fused switch or from a maximum 15 ampdedicated circuitbreaker
Optional C
onnectionU
sed in a boiler system w
ith both CH
& D
HW
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 8 of 9
ODD WATER WIRING DIAGRAMS
LEAD OR SINGLE BOILER ONLY - SYSTEM A
NTS
Dw
g.
By:
34
00
0 A
utr
y S
t.Li
vo
nia
, MI
481
50
PH
: (80
0)
96
8-5
53
0F
ax
: (73
4)
419
-02
09
Description:
Date:
Scale:
Customer:
HAMILTON
ENGINEERING
Dw
g.
No
.:
Ch
ecke
d.
By:
L L G
24
0v
Pow
er
Supply
24
0V
Boile
r
Pum
p
Tank S
tat
TST 6
30
00
Pre
ssu
re S
witch
HY
D 4
7001
Se
rvic
e D
isco
nn
ect
SERV
ICE
RESET
BU
RN
ER O
N
TEM
PERA
TU
RE
SETPO
INT
-+
20
8 -
24
0 v
1 p
h
Pow
er
Supply
EV
O P
ow
er/
Contr
ol Term
inal Str
ip
21
34
56
28
26
23
25
22 L1
L1
Sensor
Indirect
Sensor
Outd
oor
Div
ert
or
Valv
e I
ndirect
L1
Pow
er
Supply
ST-4
ST-2
ST-6
Sensor
or
Aquasta
tPum
p 2
-indirect
L1
24
ST-3
87
Addit
ional
Heat
Sourc
e
Dry
Conta
ct
Dry
Conta
ct
Sig
nal
Lock O
ut
Exte
rnal
L2
12
11
10
9
+
-C
ascade
Connecti
on
ST-1
19
17
16
15
13
14
Pum
p 3
L2
+ -
0-1
0
VD
C
20
21
L2
Pum
p 1
20
8-2
40 V
ac
18
27
L1
L2
open
clo
se
co
m.
L1
L2
ST-5
not in use
ST-7
Therm
osta
t
Rem
ote
AE
10/29/10
Contr
ol w
irin
g d
iagra
m f
or
Odd
Wate
r sy
stem
Type A
(w
ith
Indirect
tank)
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 9 of 9
LEAD OR SINGLE BOILER ONLY - SYSTEM B
BD
06/17/09
NTS
Dw
g.
By:
34
00
0 A
utr
y S
t.Li
vo
nia
, MI
481
50
PH
: (80
0)
96
8-5
53
0F
ax
: (73
4)
419
-02
09
Description:
Date:
Scale:
Customer:
HAMILTON
ENGINEERING
Dw
g.
No.:
Ch
ecke
d.
By:
24
0V
Tank
Sid
e P
um
pSERV
ICE
RESET
BU
RN
ER O
N
TEM
PERA
TU
RE
SETPO
INT
-+
20
8 -
24
0 v
1 p
h
Pow
er
Supply
L L G
24
0v
Pow
er
Supply
EV
O P
ow
er/
Contr
ol Term
inal Str
ip
24
0V
Boile
r
Sid
e P
um
p
Tank A
quasta
t
TST 5
40
06
Pre
ssu
re S
witch
HY
D 4
7001
Se
rvic
e D
isco
nn
ect
21
34
56
28
26
23
25
22 L1
L1
Sensor
Indirect
Sensor
Outd
oor
Div
ert
or
Valv
e I
ndirect
L1
Pow
er
Supply
ST-4
ST-2
ST-6
Sensor
or
Aquasta
tPum
p 2
-indirect
L1
24
ST-3
87
Addit
ional
Heat
Sourc
e
Dry
Conta
ct
Dry
Conta
ct
Sig
nal
Lock O
ut
Exte
rnal
L2
12
11
10
9
+
-C
ascade
Connecti
on
ST-1
19
17
16
15
13
14
Pum
p 3
L2
+ -
0-1
0
VD
C
20
21
L2
Pum
p 1
20
8-2
40 V
ac
18
27
L1
L2
open
clo
se
co
m.
L1
L2
ST-5
not in use
ST-7
Therm
osta
t
Rem
ote
Boile
r #
2
Boile
r #
1
Contr
ol w
irin
g d
iagra
m f
or
Odd W
ate
r syste
m T
ype B