+ All Categories
Home > Documents > ADDENDUM TO LIT91127U EVO 79 - 599 CONFIGURED IN ODD …

ADDENDUM TO LIT91127U EVO 79 - 599 CONFIGURED IN ODD …

Date post: 21-Mar-2022
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
9
34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014 ADDENDUM TO LIT91127U EVO 79 - 599 CONFIGURED IN ODD WATER SYSTEM™ DESIGN WARNING These appliances MUST be installed by a properly licensed individual in the City and State which the unit is being installed. All start up adjustments and subsequent service work must be done by a similarly licensed contractor or a factory trained service individual. Failure to comply could result in loss of warranty and or severe personal injury, death and or substantial property damage. These instructions are required to be kept with the appliance on the left side, in the pocket provided. INNOVATIVE CONDENSING TECHNOLOGY By Hamilton Engineering, Inc.
Transcript

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014

ADDENDUM TO LIT91127U

EVO 79 - 599 CONFIGURED INODD WATER SYSTEM™ DESIGN

WARNING

These appliances MUST be installed by a properly licensed individual in the City and State which the unit is being installed. All start up adjustments and subsequent service work must be done by a similarly licensed contractor or a factory trained service individual. Failure to comply could result in loss of warranty and or severe personal injury, death and or substantial property damage. These instructions are required to be kept with the appliance on the left side, in the pocket provided.

INNOVATIVE CONDENSING TECHNOLOGYBy Hamilton Engineering, Inc.

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014

All safety precautions referenced to in LIT91127U (EVO 79 - 599 Universal Installation and Operating Manual) should be STRICTLY adhered to!

There are two basic system configurations. Please determine which style you have and refer to the specific instructions where indicated. Please contact Hamilton Engineering, Inc. at 800.968.5530 if you have any questions regarding system configurations.

(FIGURE 1) SYSTEM DESIGN A

(FIGURE 2) SYSTEM DESIGN B

This system design employs a storage tank with integral heating coils and will require only one circulating pump.

This system design employs an external heat exchanger and requires one circulating pump for the closed loop (boiler) side and a bronze pump for the fresh water (storage tank) side.

Page 2 of 9

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014

SYSTEM REQUIREMENTS

System requirements beyond what is listed here can be found in LIT91127U (EVO 79-599 Universal Installation and Operating Manual):

Electrical:

System B: 208 – 240 volt amperage per system rating plate, 208-230 volt per stainless steel pump rating plate. Wiring diagram is located on page 9 of this Manual.

Service Clearances:

System B: Provide adequate access to heat exchanger for periodic acid cleaning and or removal for additional service as required

System operation:

System A – The L 4006A storage tank temperature control shall be set at the desired storage tank water temperature (per original design), on approximately a 5°F drop from desired setpoint, the SPST switch in the L 4006A will make, closing the heat enable circuit on the heating boiler. After receiving this signal, the boiler control will start the cast iron pump and initiate a firing sequence and provide the required closed loop water temperature (generally 150°F – 180°F; see system design specifications) as set by user on the red wheel located next to the temperature display on the front of the boiler, to provide the designed recovery rate through the tank heat exchanger. If there is more than one boiler providing the required BTU capacity, the setting and control wiring shall be done on the Lead labeled boiler only.

System B - The L 4006G storage tank temperature control shall be set at the desired storage tank water temperature (per original design), on approximately a 5°F drop from setpoint, the control will close both internal SPST switches, simultaneously starting the bronze circulating pump and closing the heat enable circuit on the heating boiler. After receiving this signal, the boiler control will start the cast iron pump and initiate a firing sequence and provide the required closed loop water temperature (generally 150°F – 180°F; see system design specifications) as set by user on the red wheel located next to the temperature display on the front of the boiler, to provide the designed recovery rate through the external heat exchanger. If there is more than one boiler providing the required BTU capacity, the setting and control wiring shall be done on the Lead labeled boiler only.

Filling Instructions:

The Odd Water system comes equipped with a pressure reducing fill station for the boiler (closed loop) side of the system, that is pre-piped to EVO system city water connection. Included in this package are a low pressure switch, pressure gauge, air vent, pressure reducing fill valve, expansion tank, check valve, backflow preventer, isolation valves, optional water meter, and a union for easy disassembly. Once the city water connection is made, open the air vent in the fill package and on the top of boiler(s) (models 299-599 ONLY). Once the air vent(s) is open, turn on the city water supply and open the (3) isolation valves, each located on the expansion tank, near the city water connection, and after the pressure reducing valve. When air is no longer bleeding out of the air vent(s), turn the boiler(s) on, which will cycle the pump(s), purging any air remaining in the system.

NOTE: There MUST be a city water supply connected that is regulated down to 12 PSI (via the PRV supplied) for the system to work properly!

Page 3 of 9

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014

Equipment ScheduleLetter Description

A EVO UnitB Cast Boiler Side PumpC Condensate NeutralizerD Hydronic Expansion Tank - 12 PSI Air ChargeE Storage tankF L4006A Temperature ControlG Low Pressure SwitchH Pressure GuageI Air VentJ Fill ValveK Check ValveL Water Meter (Optional)M Backflow PreventerN Hot Water ConnectionO Drain ValvesP Cold Water ConnectionQ Domestic Expansion Tank (Optional)

15

5

10

15

0

2025 3030

3535

60

50

40

45

55

A

N

D

B

C

I

City WaterConnection

(Optional)

J

P

K

QE

O

G

H

M

F (Optional)L

Page 4 of 9

LEttEr on dIAgrAm dESCrIptIon

A EVO unitB Cast Boiler Side PumpC Condensate NeutralizerD Hydronic Expansion Tank - 12 PSI air chargeE Storage TankF L4006A Temperature ControlG Low Pressure SwitchH Pressure GaugeI Air VentJ Fill ValveK Check ValveL Water Meter (optional)M Backflow PreventerN Hot Water ConnectionO Drain ValvesP Cold Water ConnectionQ Domestic Expansion Tank (optional)

(TABLE 1) SYSTEM DESIGN A - PARTS

(FIGURE 3)SYSTEM DESIGN A WITH PARTS

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014

SYSTEM B - PARTS

Page 5 of 9

(FIGURE 4)SYSTEM DESIGN B WITH PARTS

LEttEr on dIAgrAm dESCrIptIon

A EVO unitB Electrical DisconnectC Cast Boiler Side PumpD Condensate NeutralizerE Hydronic Expansion Tank - 12 PSI air chargeF Stainless Steel Domestic Hot Water PumpG Brazed Plate Heat ExchangerH Air VentI Pressure GaugeJ Low Pressure SwitchK Fill ValveL Check ValveM Backflow PreventerN Water Meter (optional)O Storage TankP External Heat Exchanger Cleaning and Draining PortsQ Brass Wye StrainerR Normally Closed Cleaning Bypass ValveS Domestic Expansion Tank (optional)T L4006G Temperature Control

(TABLE 2) SYSTEM DESIGN B - PARTS

AB

C D

E

P

G

H I

R

S

City WaterConnection

O

Q

(Optional)

T

P

F

J

K

L M N

Equipment ScheduleLetter Description

A EVO UnitB Electrical DisconnectC Cast Boiler Side PumpD Condensate NeutralizerE Hydronic Expansion Tank - 12 PSI Air ChargeF Stainless Steel Domestic Hot Water PumpG Brazed Plate Heat ExchangerH Air VentI Pressure GuageJ Low Pressure SwitchK Fill ValveL Check ValveM Backflow PreventerN Water Meter (Optional)O Storage TankP External Heat Exchanger Cleaning & Draining PortsQ Brass Wye StrainerR Normally Closed Cleaning Bypass ValveS Domestic Expansion Tank (Optional)T L4006G Temperature Control

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 6 of 9

ADDITIONAL INFORMATION

Both system designs are completely factory assembled and tested prior to shipping, following assembly at the installation site, however, filling the system requires that proper practices be followed:

The boiler is designed to operate in a closed-loop system. As such, the system should be tight and not require make-up water. A high percentage of untreated make-up water may cause premature failure due to buildup of scale; such failure is not covered by warranty.

Scale can also reduce efficiency. For example, a scale thickness of 1/16” will result in a 12.5% loss of efficiency.

NOTE: Minimum system fill pressure is 12 PSI!

Water pH

The pH of the hydronic system fluid must be between 6.5 and 7.5, for untreated water only. A periodic check of the system pH should be conducted to ensure these pH levels are maintained.

IMPORTANT!Glycol and other additives must be approved by the chemical manufacturer for use in 316L stainless steel boilers as well as the circulating pumps used with the boilers and heating system, and you must maintain the required pH levels as recommended by the glycol or treatment chemical manufacturer to prevent damaging the boiler and or pumps.

If the water quality exceeds our known safe thresholds, we wave the red flag of caution:

• Water hardness can be no more than 12 grains (205 ppm or mg/l) • TDS (Total Dissolved Solids) can be no more than 450 ppm (mg/l) • PH - below 6.5 or above 7.5 For total combined hardness over 15 grains (250 ppm or mg/l) or longer pipe lengths, contact Hamilton Engineering for correct pump sizing. Combined, the hardness and TDS can be no more than 450 ppm. Our internal term for this is the TCH (Total Combined Hardness).

The amount of oils, fats, grease, and other organic matter should be limited to 10 ppm.Consult your water conditioning or chemical treatment supplier for analysis and recommendations.

Flushing the System

Before filling the boiler, flush the system to remove any debris from construction or maintenance. Clean and flush old piping thoroughly before installing the boiler.

IMPORTANT!Under no circumstances should the hydronic system be flushed while the boiler is attached to the system since the debris or corrosion products could accumulate in the boiler and plug the boiler heat exchanger.

IMPORTANT!If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected from the system and a bypass installed so that the chemical cleaning solution does not circulate through the boiler. Following chemical cleaning, the system should be thoroughly rinsed to remove cleaning agents prior to reconnecting the boiler to the system.

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 7 of 9

ODD WATER WIRING DIAGRAMS

LEAD OR SINGLE BOILER ONLY - SYSTEMS A & B

ST-1 ST-4 ST-5 ST-7ST-6ST-3ST-2

21 3 4 5 6

SensorIndirect

SensorOutdoor

Sensor orAquastat

External

2826

L1

Power Supply

L2

208-240 Vac

2787

+ -0-10VDC

AdditionalHeat SourceDry Contact Dry Contact

SignalLock Out

1211109 23 2522

L1

24

Pump 3

L2

Pump 1

L1L2

L1

Divertor Valve Indirect

Pump 2-indirect

L1

1917 20 21

L2

18

open closecom.

L1L2

not i

n us

e

ThermostatRemote

+ -Cascade

Connection

161513 14

Optional C

onnectionM

ust connect + to + and - to - between appliances in cascade

Optional C

onnectionU

sed for storage tank or comm

on line sensing

Optional C

onnectionC

onnection from L 4006 therm

ostat

Optional C

onnectionB

uilding managem

ent system

Optional C

onnectionFor use w

ith Central heating for outdoor reset To G

round

Optional C

onnection

Optional C

onnection

For use with additional heat needed w

/cascade

For use with alarm

bell / light

Service S

witch

A B C D E F G H I J K L M

Optional C

onnectionU

sed for indirect tank

Optional C

onnectionP

ump 2: U

sed in a boiler system w

ith both CH

& D

HW

Pum

p 1: Boiler P

ump

Pum

p 3: Heater P

ump

Fused switch or from a maximum 15 ampdedicated circuitbreaker

Optional C

onnectionU

sed in a boiler system w

ith both CH

& D

HW

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 8 of 9

ODD WATER WIRING DIAGRAMS

LEAD OR SINGLE BOILER ONLY - SYSTEM A

NTS

Dw

g.

By:

34

00

0 A

utr

y S

t.Li

vo

nia

, MI

481

50

PH

: (80

0)

96

8-5

53

0F

ax

: (73

4)

419

-02

09

Description:

Date:

Scale:

Customer:

HAMILTON

ENGINEERING

Dw

g.

No

.:

Ch

ecke

d.

By:

L L G

24

0v

Pow

er

Supply

24

0V

Boile

r

Pum

p

Tank S

tat

TST 6

30

00

Pre

ssu

re S

witch

HY

D 4

7001

Se

rvic

e D

isco

nn

ect

SERV

ICE

RESET

BU

RN

ER O

N

TEM

PERA

TU

RE

SETPO

INT

-+

20

8 -

24

0 v

1 p

h

Pow

er

Supply

EV

O P

ow

er/

Contr

ol Term

inal Str

ip

21

34

56

28

26

23

25

22 L1

L1

Sensor

Indirect

Sensor

Outd

oor

Div

ert

or

Valv

e I

ndirect

L1

Pow

er

Supply

ST-4

ST-2

ST-6

Sensor

or

Aquasta

tPum

p 2

-indirect

L1

24

ST-3

87

Addit

ional

Heat

Sourc

e

Dry

Conta

ct

Dry

Conta

ct

Sig

nal

Lock O

ut

Exte

rnal

L2

12

11

10

9

+

-C

ascade

Connecti

on

ST-1

19

17

16

15

13

14

Pum

p 3

L2

+ -

0-1

0

VD

C

20

21

L2

Pum

p 1

20

8-2

40 V

ac

18

27

L1

L2

open

clo

se

co

m.

L1

L2

ST-5

not in use

ST-7

Therm

osta

t

Rem

ote

AE

10/29/10

Contr

ol w

irin

g d

iagra

m f

or

Odd

Wate

r sy

stem

Type A

(w

ith

Indirect

tank)

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91167U REV 2/2014Page 9 of 9

LEAD OR SINGLE BOILER ONLY - SYSTEM B

BD

06/17/09

NTS

Dw

g.

By:

34

00

0 A

utr

y S

t.Li

vo

nia

, MI

481

50

PH

: (80

0)

96

8-5

53

0F

ax

: (73

4)

419

-02

09

Description:

Date:

Scale:

Customer:

HAMILTON

ENGINEERING

Dw

g.

No.:

Ch

ecke

d.

By:

24

0V

Tank

Sid

e P

um

pSERV

ICE

RESET

BU

RN

ER O

N

TEM

PERA

TU

RE

SETPO

INT

-+

20

8 -

24

0 v

1 p

h

Pow

er

Supply

L L G

24

0v

Pow

er

Supply

EV

O P

ow

er/

Contr

ol Term

inal Str

ip

24

0V

Boile

r

Sid

e P

um

p

Tank A

quasta

t

TST 5

40

06

Pre

ssu

re S

witch

HY

D 4

7001

Se

rvic

e D

isco

nn

ect

21

34

56

28

26

23

25

22 L1

L1

Sensor

Indirect

Sensor

Outd

oor

Div

ert

or

Valv

e I

ndirect

L1

Pow

er

Supply

ST-4

ST-2

ST-6

Sensor

or

Aquasta

tPum

p 2

-indirect

L1

24

ST-3

87

Addit

ional

Heat

Sourc

e

Dry

Conta

ct

Dry

Conta

ct

Sig

nal

Lock O

ut

Exte

rnal

L2

12

11

10

9

+

-C

ascade

Connecti

on

ST-1

19

17

16

15

13

14

Pum

p 3

L2

+ -

0-1

0

VD

C

20

21

L2

Pum

p 1

20

8-2

40 V

ac

18

27

L1

L2

open

clo

se

co

m.

L1

L2

ST-5

not in use

ST-7

Therm

osta

t

Rem

ote

Boile

r #

2

Boile

r #

1

Contr

ol w

irin

g d

iagra

m f

or

Odd W

ate

r syste

m T

ype B


Recommended