1 Advance Evaporative Cooling Technologies Commercial Nicholas H. Des Champs, Ph.D., PE, ASHRAE Fellow
Transcript
Page 1: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

1

Advance Evaporative Cooling Technologies – Commercial

Nicholas H. Des Champs, Ph.D., PE, ASHRAE Fellow

Page 2: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

2

Introduction

What is Indirect Evaporative Cooling (IEC)?

Psychrometrics of IEC

What Makes IEC an Attractive Alternative?

Recent Concepts and Designs

Maintenance

Page 3: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

3

Indirect Evaporative Cooling

First recorded use was in the thirties and used cooling tower and coils

First use with the Integral Heat Exchanger/Cooling Tower was in 1975 and it was then that the term “Indirect Evaporative Cooling” was coined.

From 1975 to 1985 IEC was used but a lot of projects failed because of poor designs.

Page 4: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

5

Thermodynamic Processes

DEC

Adiabatic

IEC

Sensible

Heat Transfer

Page 5: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

6

1 2

1

2

DIRECT EVAPORATIVE

COOLING … A CONSTANT

WET BULB PROCESS

HUMIDIFIES AND COOLS

Page 6: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

7

Scavenger Exhaust

Water In

Grooved Grooved

Tube Wall Tube Wall

Entering Air to Be Cooled Cooled Supply Air

Water Water

Flow Flow

Water Reservoir

Integral Cooling Tower & HX

Scavenger Air 10 x Max Evaporation RateΔT Water < 2 F

and ranges from 3

to 10 F above WB

Page 7: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

8

Equal Air Flow

New WB of 56.2 F !!

100 db/65 wb

Page 8: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

9

Using Water from DEC Sump Increases System Efficiency

Page 9: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

10

Page 10: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

11

What Makes IEC an Attractive Alternative?

Green is IN

IEC is Energy Efficient

IEC reduces green house gases

IEC reduces demand charges – it works best on the hottest days

The design mistakes of the past have, for the most part, been corrected

New techniques to condition water have been developed

Page 11: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

12

A Look at the Use of

Water vs. Electricity

Page 14: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

15

With Fossil Fuels

1/3 goes to producing electricity

1/3 goes to waste heat up the stack

1/3 goes to evaporative cooling associated with condensing steam

To produce 1000 Watts requires 3.4 pounds of water to be evaporated

Page 15: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

16

Comparison – Water vs. Fossil Fuel

One Ton of Mechanical cooling with EER of 12 requires 1000 Watts per ton or 3.4 lbs H2O/hr to be evaporated at the power station.

IDEC with EER of 36 requires 12 lbs H2O/hr per ton but produces only 33% of the pollution.

Fossil fuels are not recyclable but water is…over and over for billions of years.

Page 16: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

17

Comparison – Mechanical vs. IEC

Mechanical Cooling Uses Electricity as the Principal Source of Energy

IEC Uses Evaporation of Water as the Principal Source of Energy

EER of Mechanical is Approximately 12

EER of IEC is Approximately 36

IEC Evaporates More Water but Consumes Considerably Less Fuel

Water is Completely Reusable – Fossil Fuels are NOT.

Consumption of Fuels Generate Environmental Problems

Page 17: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

18

Intake Air Capacity = 1.08 x SCFM x (Tdbintake – Tdbsupply)

= 504,000 Btu/hr

IA EER = 40.34

Room EER 32.,0

Explanation of Room EER and IA EER for Evaporative Cooling

Page 18: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

19

New Equipment Designs

Polymer Tube HXs Designed Specifically to Overcome Clogging and Degradation

Direct-Sprayed Heat Pipe

Non-sprayed IEC for Aggressive Environments

Plastic Plate Heat Exchangers

Novel Plastic Heat Exchanger that is Designed to Approach 100% of WB Depression

Indirect Evaporative Cooling Tower that Could Supply Water below WB Temperature

Page 19: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

20

IEC Polymer Tube Exchanger

Page 20: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

21

Page 21: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

22

O/A Entering Polymer Indirect Cooling System

Page 22: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

23

Scavenger Exhaust

Water In

Grooved Grooved

Tube Wall Tube Wall

Entering Air to Be Cooled Cooled Supply Air

Water Water

Flow Flow

Water Reservoir

Integral Cooling Tower & HX

Scavenger Air 10 x Max Evaporation RateΔT Water < 2 F

and ranges from 3

to 10 F above WB

Page 23: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

24

McCarran Airport, Las Vegas, NV

(8) 28,000 CFM Units

(6) 8,000 CFM Units

Page 24: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

25

McCarran Airport

Page 25: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

26

Page 26: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

27

Page 27: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

28

Mist Eliminator

Spray

Nozzle

Exhaust Air

Leaving

Page 28: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

29

Polymer Plate HX IEC Unit

Page 29: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

30

Heat Pipes Used as the Integral HX/Cooling Tower

Page 30: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

31Heat Pipe Heat Exchanger

warm

SURFACE

EVAPORATIVELY

COOLED

R-22 Refrigerant

Liquid evaporates this end

Vapor condenses this end

Extruded, one piece, all aluminum construction

fin tube. 1” I.D. tubes with integral aluminum

fins -- no mechanical bond between fin & tube.

Each tube individually charged and sealed.

PARTITION

WATER SPRAYS

Normally

6-rows

Deep

Page 31: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

32

12

MIST

ELIMINATOR

R/A

OR

SCAVENGER

O/A

E/A

WETTED HEAT

PIPE

O/AS/A

123

3

THE 2-STAGE EVAPORATIVE

COOLER, INDIRECT/DIRECT

WITH SPRAYED HEAT PIPE

INDIRECT EVAPORATIVE COOLING

… SENSIBLE COOLING PROCESS

NEW, LOWER WET BULB

ENHANCES THE DEC’S ABILITY TO COOL

DEC

Page 32: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

33

Lawrence Livermore – Sandia National Laboratories

Page 33: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

34

Page 34: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

35

H=26.04

H=29.15

100% OUTDOOR AIR 2-STAGE EVAPORATIVE

COOLING SYSTEM REQUIRES LESS REFRIGERATION

COOLING THAN 100% RECIRCULATION SYSTEM

H=23.22

(26.04 – 23.22)/(29.15 –23.22) = 0.476

IEC/DEC REDUCES LOAD

BY 52.4% RELATIVE TO 100%

RECIRCULATION SYSTEM

78/64 R/A

Recirculation

IEC/DEC

Page 35: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

37

Salazar Hall, 75 KW AC Photovoltaic System

Seven 26,000 cfm IEC/DEC, CW Air Handlers

Page 36: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

38

Direct Spray Heat Pipes Field Tests - Sandia

Page 37: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

39

Sandia DISL

85% WB Depression

86% Saturation

Efficiency

Page 38: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

48

For the Really Bad WaterPlace Evaporative Cooling Media

in Return Air Stream

OA

2

SA*

*

*

EA RA

CC HC DECHP

* * *

Page 39: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

49

High Desert State Prison north of Las Vegas – 1997

(30) 20,000 CFM Indirect-Direct Units that perform all Cooling

Page 40: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

50

High Desert PrisonIndian Springs, NV

R/A

S/A

E/A

E/A

O/A

Plan View

Elevation View

Page 41: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

51

DEC

XXX

Page 42: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

52

DEC => Wet Bulb in the Limit

IEC => Dew Point in the Limit

So let’s look at some concepts

being investigated to approach

Dew Point with IEC.

Page 43: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

53

Staged IEC can Approach DP in the Limit

Page 44: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

54

Staged IEC >> DP

Page 45: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

55

Pacific Gas & Electric Study

Page 46: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

56

Heat and Mass Exchanger

Page 47: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

57

PG&E Study

Page 48: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

58

PG&E Study

Page 49: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

59

Model of Full Recirculation Air

Dew Point CoolerSprayed Side

Process Approaches in Limit

DEC WB (90%)

IEC WB (85%)

IEC/DEC 84% of DP (78%)

134% of WB depression

IEC/IEC DP is Limit

Page 50: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

60

Dew Point Cooler Test Unit

Page 51: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

61

Page 52: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

62

Most Practical Approach to Increasing

Effectiveness Using Lower WB

Page 53: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

63

Using Water from DEC Sump to Top of IEC is Most Cost

Effective to Increase Overall Performance

Page 54: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

64

Page 55: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

65

Page 56: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

66

Legionnaires’ Disease

“There have been no known cases of Legionnaires’ disease with air washers, wetted media evaporative air coolers/humidifiers, or steam humidifiers.”

“There has been no positive association of Legionnaires’ disease with indirect evaporative air coolers”

Page 57: Advance Evaporative Cooling Technologies Commercial · Indirect Evaporative Cooling First recorded use was in the thirties and used cooling tower and coils First use with the Integral

67

Why?

The water in the sump is not warm enough to allow the Legionella bacteria to proliferate.

Rigid media evaporative coolers do not produce droplets in a size that is conducive to transporting Legionella bacteria.

Evaporative coolers have their sumps cleaned on a regular basis.