+ All Categories
Home > Documents > Advc U-series Installation

Advc U-series Installation

Date post: 01-Jun-2018
Category:
Upload: nguyen-duy-khuong
View: 233 times
Download: 0 times
Share this document with a friend

of 27

Transcript
  • 8/9/2019 Advc U-series Installation

    1/70

    U-Series 

    Automatic Circuit Recloser 

    with Advanced Controller 

    Installation and Maintenance Manual

  • 8/9/2019 Advc U-series Installation

    2/70

  • 8/9/2019 Advc U-series Installation

    3/70

    iii

    Notices

    Scope of thisManual

    This document describes the installation and

    maintenance procedures for the U-Series

    Automatic Circuit Recloser with Advanced

    Controller.

    Limitations This document is copyright and is provided solely

    for the use of the purchaser. It is not to be copiedin any way, nor its contents divulged to any third

    party, nor to be used as the basis of a tender or

    specification without the express writtenpermission of the manufacturer.

    Disclaimer The advisory procedures and informationcontained within this Technical Manual have been

    compiled as a guide to the safe and effective

    operation of products supplied by Nu-Lec

    Industries Pty Ltd.

    It has been prepared in conjunction with

    references from sub-assembly suppliers and the

    collective experience of the manufacturer.

    In-service conditions for use of the products may

    vary between customers and end-users.

    Consequently, this Technical Manual is offered as

    a guide only. It should be used in conjunction with

    the customers own safety procedures,

    maintenance program, engineering judgement

    and training qualifications.

    No responsibility, either direct or consequential, for

    injury or equipment failure can be accepted by Nu-

    Lec Industries Pty Ltd resulting from the use of this

    Technical Manual.

    Copyright  © 2005 by Nu-Lec Industries Pty Ltd.

    All rights reserved. No part of the contents of this

    document may be reproduced or transmitted in

    any form or by any means without the written

    permission of the manufacturer.

  • 8/9/2019 Advc U-series Installation

    4/70

    U-Series Automatic Circuit Recloser

    iv

  • 8/9/2019 Advc U-series Installation

    5/70

      Installation and Maintanance Manual

    i

    CONTENTS

    1 Scope of this Manual....................................... 1-1General ......................................................................... 1-1

    Equipment Versions Covered by this Manual ............... 1-1

    Software Identification................................................... 1-1

    Abbreviations ................................................................ 1-1

    Symbols ........................................................................ 1-12 Introduction...................................................... 2-1

    Terminology .................................................................. 2-3

    3 Installation........................................................ 3-1Contents of Crate.......................................................... 3-1

    Unpacking Procedure.................................................... 3-1

    Control Cable Connection............................................. 3-1

    Testing & Configuring.................................................... 3-1

    Transport to Site............................................................ 3-2

    Site Installation.............................................................. 3-2

    Tools Required............................................................ 3-2

    Parts Required (Not supplied by the manufacturer).... 3-2

    Site Procedure ............................................................ 3-3

    Surge Arrester Mounting and Terminating.................. 3-4Earthing....................................................................... 3-4

    LV Auxiliary Power from Mains ................................... 3-4

    LV Auxiliary Power from Dedicated Utility Trans......... 3-5

    Auxiliary Power from Integrated Transformer ............. 3-5

    4 Comms and Accessories Installation............ 4-1Radio Antenna .............................................................. 4-1

    Protection of Radio Equipment ................................... 4-1

    The Customer Compartment......................................... 4-2

    Connecting to the Terminal Block ............................... 4-2

    Radio/Modem Power................................................... 4-2

    IOEX2 Installation ......................................................... 4-3

    Communication Ports.................................................... 4-3RS232 ......................................................................... 4-4

    RS485 ......................................................................... 4-4

    V23 FSK...................................................................... 4-5

    Ethernet....................................................................... 4-5

    Windows Switchgear Operating System (WSOS)......... 4-5

    SCADA Protocols.......................................................... 4-6

    5 Testing Your Installation .............................. 5-1Powering Up the ADVC................................................. 5-1

    Battery........................................................................... 5-1

    Connection between the ADVC and the ACR............... 5-2

    Auxiliary Supply............................................................. 5-2

    Work Tag....................................................................... 5-2

    Terminal Designation and Phase Rotation.................... 5-3

    Setting Power Flow Direction........................................ 5-3

    Tripping and Closing ..................................................... 5-3Enable/Disable Switches............................................... 5-3

    Mechanical Trip............................................................. 5-4

    Secondary Injection Testing.......................................... 5-4

    Primary Injection Testing............................................... 5-4

    Power Flow Direction Testing ....................................... 5-4

    On Load Checks ........................................................... 5-5

    6 Control Electronics Operation........................ 6-1Sealing & Condensation................................................ 6-1

    Auxiliary Power Source................................................. 6-1

    Controller....................................................................... 6-1

    PSU Module ................................................................ 6-1CAPE Module.............................................................. 6-1

    Operator Interface/ Door Assembly............................... 6-2WSOS Interface .......................................................... 6-2

    Customer Compartment................................................ 6-2

    7 Operator Control Panel ................................... 7-1

    Description.....................................................................7-1

    Display Groups ..............................................................7-2

    Custom Menu.................................................................7-3

    Changing Settings........................................................7-3

    Operator Settings.........................................................7-3

    Password Protected Settings.......................................7-3Protection Settings.......................................................7-3

    Navigating Within Display Groups .................................7-3

    Page Layout...................................................................7-3

    Quick Keys.....................................................................7-4

    Quick Key Configuration ..............................................7-4

    Using a Quick Key .......................................................7-5

    8 Event Log.......................................................... 8-1Display Updating............................................................8-1

    Event Log Format ..........................................................8-1

    Using the ALT Key .......................................................8-1

    Typical Event Log Displays............................................8-1

    9 Power System Measurements ........................ 9-1

    Power System Frequency..............................................9-1Real Time Displays ........................................................9-1

    Maximum Demand Indicator ........................................9-2

    10 Maintenance .................................................. 10-1ACR Maintenance........................................................10-1

    ADVC Maintenance .....................................................10-1

    Cleaning.....................................................................10-1

    Battery Replacement .................................................10-1

    Battery Heater Accessory ..........................................10-1Door Seal ...................................................................10-2

    Battery Care.................................................................10-2

    Abnormal Operating Conditions...................................10-2Low Power Mode .......................................................10-2

    Excess Close Operations...........................................10-3

    Fault Finding ................................................................10-3

    ADVC Check..............................................................10-3

    Replacement of Electronic Modules and Upgrades.....10-3

    11 Ratings and Specifications .......................... 11-1Equipment and Crating Dimensions ............................11-1

    ACR .............................................................................11-1

    Breaking Duty ............................................................11-2

    Duty Cycle..................................................................11-2

    Terminal Clearance/Creepage...................................11-2

    Current Tranformers ..................................................11-2

    Environmental ............................................................11-3

    ADVC...........................................................................11-3

    General Specifications ...............................................11-3

    Power System measurements .....................................11-4App A Replaceable Parts & Tools................A-1App B Dimensions ........................................B-1

  • 8/9/2019 Advc U-series Installation

    6/70

    U-Series Advanced Controller

    ii

  • 8/9/2019 Advc U-series Installation

    7/70

  • 8/9/2019 Advc U-series Installation

    8/70

    U-Series Automatic Circuit Recloser

    1-2

  • 8/9/2019 Advc U-series Installation

    9/70

  • 8/9/2019 Advc U-series Installation

    10/70

    U-Series Automatic Circuit Recloser

    2-2

    .

    Figure 1: U-Series ACR Construction

  • 8/9/2019 Advc U-series Installation

    11/70

    Introduction

    2-3

    Terminology The U-Series recloser bushings are identified asl, ll, and lll on the same side as the CTs and

    CVTs, which is, by default, the source side. The

    bushings on the other (default load side) are

    identified as X, XX, and XXX.

    Figure 2: ADVC Components

    Operator

    ControlPanel (OCP)

    CustomerEquipment andAccessoriesCompartment

    Control andProtectionEnclosure

    Batteries

    PowerSupplyUnit (PSU)

    (CAPE)

    l

    ll

    lll

    X

    XX

    XXX

    Figure 3: ACR Bushings

  • 8/9/2019 Advc U-series Installation

    12/70

    U-Series Automatic Circuit Recloser

    2-4

  • 8/9/2019 Advc U-series Installation

    13/70

    Installation

    3-1

    3 Installation

    Contents ofCrate

    Each crate includes:

    ACR.

    Pole mounting bracket with clamps if

    ordered. If a substation mounting bracketwas ordered it will be attached to the outside

    of the crate.

    Six connectors if ordered (15TP or 30TP).

    caulking gun.

    The appropriate mounting kit.

    ADVC (which will normally contain two

    batteries unless arrangements have beenmade to ship batteries separately).

    Control cable.

    On receipt, the contents should be checked forshipping damage and the manufacturer

    informed immediately if any is found.

    Ensure that the ADVC is stored

    indoors until installation on site. If

    storage outdoors is unavoidable,

    ensure that the ADVC is kept in an

    upright position.

    UnpackingProcedure

    Tools required:

    Wrecking bar to remove nails.

    Four D shackles, two slings and crane with asafe working load of 200kg to lift the ACR.

    Screw Driver or Battery Drill with 8mm

    socket.

    16mm Spanner or Socket.

    Procedure:

    1 Remove top of crate and lift out the control

    cable. Store carefully in a clean dry place.

    2 Unscrew and remove the four (4) screws

    located on the wall of the crate. The

    mounting bracket, mounting kit and the two

    pieces of wood that the screws have just

    been removed from are all secured together.

    Lift the complete mounting bracket out of the

    crate.

    Take great care not to drop thebracket, which weighs nearly 30kg

    (66lb), onto the ACR.

    3 Fit D-shackles to the lifting points on the

    ACR and lift it out of the crate and on to theground using the crane.

    4 Tip the crate on to its side.

    5 Remove the bolts securing the ADVC and

    slide the unit from the crate.

    The control cubicle weighs

    approximately 40 kg (88lb).

    Control CableConnection

    When installing or testing the ACR it is

    necessary to connect and disconnect the control

    cable either from the ACR, the ADVC or both.

    The control cable is plugged into the base of the

    ACR and the other end into the ADVC at the

    bottom, right-most socket on the Control and

    Protection Enclosure (CAPE).

    To do this successfully requires the correct

    technique:

    Power down the control cubicle by switchingoff all MCBs. This should be done whenever

    connecting or disconnecting the control cable.

    To connect: hold the plug by the long sides,

    check orientation, gently locate it on the socket

    and push firmly home. Check it has locked by

    wriggling the plug. If the plug cannot be

    pushed on with moderate force then it has not

    been located properly. Heavy force is never

    required.

    To disconnect: (1) Hold the plug by the short

    sides and grip hard to release the clips inside

    the plug (not visible). (2) Wriggle the plug to

    allow the clips to release. (3) Then pull the plug

    out.

    Never pull the plug out by the

    cable.

    Testing &Configuring

    The tests can be carried out on site or in the

    workshop as preferred.

    Unpack the crate as above and put the HV

    cables, boots and the control cable in a clean

    safe place where they will not be damaged or

    soiled. Make a temporary earth connection

    between the ADVC and the ACR. 1mm² copper

    wire is adequate for the purpose.

    Figure 4: Handling the control cable plug

  • 8/9/2019 Advc U-series Installation

    14/70

    U-Series Automatic Circuit Recloser

    3-2

    Raise the ACR using a crane or forklift in order

    to safely gain access to the bottom of the ACR.

    Unbolt the cover plate over the switch cable

    entry module (SCEM) on the bottom of the ACR

    and connect the ACR end of the control cable to

    the SCEM.

    Lower the ACR on to props so that the control

    cable is not damaged by being caught between

    the base of the ACR and the floor.

    Then connect the ADVC end of the cable to the

    socket at the lower right-hand corner of theCAPE located inside the ADVC cubicle. (See

    Site Procedure, Step 14. on page 3-3.)

    The LV auxiliary supply (if applicable) should be

    connected as shown in Figure 5 (page 3-5).

    ‘Turn on the battery and auxiliary supply circuit

    breakers at the bottom of the control cubicle and

    carry out the following tests:

    1. Manual trip and close of the ACR.

    2. Insulation test the high voltage connections

    to earth to check for shipping damage on the

    high voltage side of the ACR.

    3. Configure the protection settings.

    4. Perform primary current injection as

    required.

    5. Perform secondary current injection (if

    required by your Authority) using a Test and

    Training Set (TTS).

    6. Fit and test a radio or modem if required.

    7. Attend to the battery using the care

    instructions given in “Battery Care” on

    page 10-2. 

    Connecting the batteries with

    reverse polarity will cause damage

    to the electronic systems.

    An application note detailing workshop and field

    test procedures is available. Contact your agent

    or distributor.

    Transport toSite

    If the unpacking and testing was carried out in

    the workshop then the ACR and ADVC must be

    transported safely to site. It is important the

    following steps are carried out:

    Turn off all ADVC MCBs and disconnect all

    auxiliary power supplies. Disconnect the

    control cable from both ACR and ADVC and

    put back the cover plate on the bottom of the

    ACR.

    Transport the ACR, ADVC and all parts in a

    safe and secure manner to site.

    SiteInstallation

    If you are replacing a pole-top control

    cubicle (PTCC) with an ADVC, the

    following should be considered:

    The ADVC mounting points will be different1.

    The connection to the auxiliary supply enters

    the cubicle at a different point.

    The earth stud is in a different position.

    Accessory cables may need extending.

    Unlike the PTCC which required an

    auxiliary power supply rating of 50VA, the

    ADVC requires 100VA. 

    If the auxiliary supply is provided by an

    external VT connected through the ACR,

    there are limitations to the supply ratings of

    equipment that customers may fit. In ADVC,General Specifications See “Radio/Modem

    Power Supply Continuous Current” on

    page 11-4.

    Unlike the PTCC, the ADVC has locking

    hinges on the door which prevent the door

    from swinging or blowing shut. When you

    open the door to 180°, it locks into that

    position. To close the door, disengage the

    hinge locks by raising the door slightly

    before rotating it.

    Tools Required   Torque wrench and metric socket set,normal engineers tools.

    Tools to prepare pole as required.

    Crane or other lift for ACR and ADVC, four D

    shackles and slings.

    Parts Required(Not supplied bythemanufacturer)

    Two 20mm galvanised or stainless steel

    bolts with washers and nuts etc. to bolt the

    ACR mounting bracket to power pole. See

    Figure 6 (page 3-6). If the optional pole

    clamps have been purchased this is not

    required.

    Mounting parts for the ADVC. Either 20mmsteel strapping or 10mm galvanised or

    stainless steel bolts, nuts, etc.

    Fixing hardware for the control cable. This is

    a 27mm (1 1/16”) diameter sheathed conduit

    and can be fixed to the pole with ties, straps,

    P-clips or saddles.

    Earth wire and lugs for the earthing scheme

    and parts for LV mains auxiliary power

    connection. See Figure 5 (page 3-5),Figure 10 (page 3-10) and Figure 11

    (page 3-11).

    1. An accessory mounting bracket can be purchased to allow the use of the same mounting holes as were used with themanufacturer’s PTCC. (Part No. 99800125)

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/9/2019 Advc U-series Installation

    15/70

    Installation

    3-3

    20mm sealing cable entry glands to suit

    auxiliary supply mains cables, 16mm sealing

    cable entry glands to suit antenna or

    communications cable as required.

    Antenna, antenna feeder cable, and surge

    arrester as required if a radio is fitted (unless

    supplied by the manufacturer).

    Site Procedure To erect and test the ACR and ADVC, carry outthe following steps. Mounting details are given in

    Figure 6 (page 3-6):1. Transport to site and carry out testing prior to

    erection as required.

    2. Connect cable tails and surge arresters

    before raising the ACR. See "Surge Arrester

    Mounting and Terminating" - page 3-4 .

    3. Ensure that the pole is of sufficient strengthto support the ACR. A structural engineer

    may be needed to calculate the stresses

    involved.

    4. Securely mount the ACR mounting bracketon the power pole.

    5. Lift the ACR into position and lower it onto

    the mounting bracket so that it sits on themounting bracket. See Figure 6 (page 3-6) 

    and Figure 8 (page 3-8).

    6. Bolt the ACR to the mounting bracket with

    the four 12mm nuts and bolts provided.

    Tighten to 50 Nm.

    7. Complete the high voltage connections.

    8. Unbolt the SCEM compartment cover plate

    from the bottom of the ACR. Connect the

    control cable to plug P1 on the SCEM

    located inside the ACR. Then bolt up the

    cover.

    See Figure 4 (page 3-1) for the correct way

    to connect/disconnect the control cable.

    9. Run the control cable from the ACR down to

    the ADVC.

    10. If the ADVC is to be bolted to the pole, drill

    the top hole and fit the bolt. If it is to be

    strapped, feed the straps through the slots

    on the upper and lower mounting brackets.

    11. Lift the ADVC into position and bolt or strap it

    to the power pole.

    Note that the

    ADVC mounts

    have key holes as

    shown here, so

    that you can lift

    the ADVC on to

    the mounting bolt

    and slide it into position.

    When mounting the ADVC to a

    wooden pole, use a spirit level to

    ensure correct alignment, andminimise torque on the mounting

    brackets.

    12. Attach the control cable to the power pole

    maintaining maximum available separation

    from the main earth bond (at 200mm for

    wood and concrete poles and 150mm for

    steel poles). Ensure that there is enough

    cable available at each end to permit

    connection to the equipment.

    13. Run the earth connections as described in

    “Earthing” on page 3-4.

    It is vital that the earthing scheme

    is carried out as described.

    14. Push the control cable from the ACR through

    the base of the ADVC

    and then connect it to the switchgear socket

    on the CAPE.

    15. For LV mains supply run auxiliary wiring as

    shown in Figure 10 (page 3-10). Make the

    connection inside the ADVC as shown in

    Figure 5 (page 3-5). 

    16. For LV supply from a dedicated transformer

    supplied by the utility, connect as shown in

    Figure 11 (page 3-11).17. For Integrated supply from an external

    transformer, connect as shown in Figure 11

    (page 3-11). (See also “Auxiliary Power from

    Integrated Transformer” on page 3-5.)

    18. Power down the ADVC by switching off allMCB’s. Note that this should be done

    whenever connecting or disconnecting the

    control cable from the ADVC.

    19. Fit the batteries if they are not already inplace.

    Fitting the batteries with reverse

    polarity will cause damage to the

    electronic systems.

    1

    1

    1

    1

    2

    2

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/9/2019 Advc U-series Installation

    16/70

    U-Series Automatic Circuit Recloser

    3-4

    20. If communications equipment is to be

    installed,next read “Communications and

    Accessories Installation” on page 4-1.

    21. Otherwise, next read “Testing Your

    Installation” on page 5-1.

    Surge ArresterMounting andTerminating

    The ACR is type tested for Impulse Withstand

    Voltages up to 125kV depending on the model.

    See "Ratings and Specifications" - page 11-1

    When there is a possibility that lightning ornetwork switching conditions may produce peak

    voltages in excess of 70% of the Impulse

    Withstand Voltage, the manufacturer

    recommends the use of suitably rated surge

    arresters connected to each terminal of the

    ACR.

    The arresters should be mounted on the

    mounting brackets supplied by the manufacturer

    and earthed as described in Figure 7 (page 3-7)

    and Figure 9 (page 3-9).

     If the arresters are not mounted

    close to the ACR the protection they

    provide is significantly reduced.

    Lightning induced damage to the ACR or ADVC

    voids the warranty if surge arresters are not

    fitted.

    Mounting brackets are provided for surgearresters on the ACR. This is illustrated in

    Figure 6 (page 3-6) and Figure 8 (page 3-8).

    The surge arresters can be mounted on top of

    the brackets or clamped to the side of the

    brackets using the holes provided. Top holes are

    12mm diameter, side holes are 16mm diameter.In this way most types of surge arrester can beaccommodated.

    The user should check that phase/phase andphase/earth clearance will be sufficient for their

    particular surge arresters and line voltages. For

    some types of side clamping surge arresters,the phase/earth clearance may be insufficient at

    the centre phase on the pole side at higher

    voltages. In this case the surge arrester can be

    mounted on the side of the power pole or an

    increased clearance ACR mounting bracket

    fitted.

    Connections from the surge arresters to thecable tails can be made by stripping off the

    cable tail insulation and using a parallel or “T”

    type clamp to make the connection to the cable

    tail. The connection should be made far enough

    up the tail so that phase/phase and phase/earth

    clearances are maintained. It is good practice totape the joint using a bitumen or mastic tape, to

    maintain the cabling system insulation.

    Earthing Figure 10 (page 3-10) shows the earthingcommon to all installations.

    This arrangement earths the ACR frame and the

    surge arresters directly to earth through a main

    earth bond  consisting of a copper conductor of

    70 sq. mm. Any surges will flow down this path.

    Do not earth surge arresters by a

    different path, doing this may

    cause damage to the control

    electronics or ACR. Also, any

    antenna should be bonded to the

    ACR or the main earth bond .

    The control cubicle is connected to this main

    earth bond  by a tee-off. The control cubicle

    electronics are internally protected from

    potential differences which may occur between

    the ACR frame and control cubicle frame whilst

    surge currents are flowing down the main earth 

    bond . No other connections to earth from the

    control cubicle are allowed since surge currents

    will also flow in those paths. Follow this

    arrangement on both conducting and insulating

    power poles.

    Keep the main earth bond  physically separated

    from the control cable, as they run down the

    power pole, by the maximum spacing available

    and at least 150mm.

    LV AuxiliaryPower fromMains

    Where LV mains are connected to the control

    cubicle to provide auxiliary power, the

    connection must connect the neutral of the LV

    system to a tee-off from the main earth bond  as

    shown in Figure 10 (page 3-10). A low voltage

    surge arrester must also be fitted from the LV

    phase connection to this tee-off.

    This connection scheme bonds the LV and HV

    earths and so protects the primary insulation of

    the auxiliary supply transformer in the control

    cubicle when surge currents are flowing. Fit

    additional LV surge arresters to all the other LV

    phases (if they exist), to balance the supply for

    other users connected to the LV system.

    If local conditions or wiring rules prohibit

    bonding the HV and LV systems in this way,

    providing the auxiliary supply to the control

    cubicle from the LV mains system is not

    possible. Instead, use one of the alternative

    arrangements detailed below.

    http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/9/2019 Advc U-series Installation

    17/70

    Installation

    3-5

    LV AuxiliaryPower fromDedicatedUtilityTransformer

    Figure 11 (page 3-11) shows wiring and earthing

    if a dedicated transformer is supplied by the

    utility. Note that this should not be used to

    supply any other equipment without consulting

    the manufacturer to ensure that no hazard is

    caused to the control cubicle electronics.

    Figure 11 (page 3-11) shows that the

    transformer and any steelwork is earthed to the

    switchgear tank and that one side of the

    transformer secondary is earthed to the earth

    stud on the equipment panel inside the control

    cubicle.

    Auxiliary Powerfrom IntegratedTransformer

    The manufacturer can provide a dedicated

    voltage transformer outside the ACR tank which

    connects directly into the control electronics.

    This is called an Integrated Auxiliary Supply .

    An external transformer is mounted on the pole

    as shown in Figure 11 (page 3-11) which also

    shows suggested HV connections. The

    secondary of the external transformer connects

    into the SCEM on the underside of the ACR. To

    connect the transformer secondary, remove the

    SCEM compartment cover plate, pass the cable

    which is pre-fitted with a cable gland through the

    hole, secure the gland, connect the auxiliary

    supply to the screw terminal block on the SCEM

    and replace the compartment cover.

    No additional earthing for Integrated Auxiliary

    Supply is required in addition to the common

    earthing shown in Figure 10 (page 3-10).

    If the secondary of the VT is

    earthed, electronics damage willoccur.

    Figure 5: LV Auxiliary Supply Connection

  • 8/9/2019 Advc U-series Installation

    18/70

    U-Series Automatic Circuit Recloser

    3-6

    Figure 6: ACR End Mounting and Dimensions

  • 8/9/2019 Advc U-series Installation

    19/70

    Installation

    3-7

    Figure 7: End Mounting Example

  • 8/9/2019 Advc U-series Installation

    20/70

    U-Series Automatic Circuit Recloser

    3-8

    Figure 8: Centre Mounting and Dimensions

  • 8/9/2019 Advc U-series Installation

    21/70

    Installation

    3-9

    Figure 9: Centre Mounting Example

  • 8/9/2019 Advc U-series Installation

    22/70

    U-Series Automatic Circuit Recloser

    3-10

    Figure 10: Common Earthing and LV Supply

  • 8/9/2019 Advc U-series Installation

    23/70

    Installation

    3-11

    Figure 11: Utility Auxiliary Transformer

  • 8/9/2019 Advc U-series Installation

    24/70

    U-Series Automatic Circuit Recloser

    3-12

  • 8/9/2019 Advc U-series Installation

    25/70

    Communications and Accessories Installation

    4-1

    4 Communications and Accessories Installation

     Ensure that the ADVC is switched

    off before proceeding with the

    installation of any accessory.

    Radio Antenna Mount the antenna and run the antenna feed to

    the ADVC or run external communications cableto the ADVC. The communication cable/radio

    antenna, enters the cubicle via the 16mm hole

    provided on the underside of the cubicle.

    Figure 12: Cable Entry

    Protection ofRadioEquipment

    It is highly advisable to connect a gas discharge

    type of surge arrester in the antenna feed to the

    radio. Failure to do so will result in loss of radio

    and control electronics protection which could

    lead to complete electronic failure due to

    lightning activity.A failure of this nature is not covered

    by the products general warranty

    arrangements.

    A feed-through or bulkhead type arrester fitted

    to the bottom of the control cubicle is ideal. If

    fitted internally the surge arrester should be

    earthed to an equipment panel mounting stud by

    the shortest possible wire. Holes are provided

    for a bulkhead surge arrester.

    If a surge arrester is not fitted then the co-axial

    earth screen should be earthed to the

    equipment panel by the shortest possible wire.

    Comms cable/ Radio AntennaEntry

    Underside ofcubicle

  • 8/9/2019 Advc U-series Installation

    26/70

    U-Series Automatic Circuit Recloser

    4-2

    The CustomerCompartment

    At the top of the customer equipment

    compartment is an accessory mounting rail for

    installing customer equipment and accessories.

    Equipment installed in this compartment can be

    powered from the terminal block also mounted

    on the rail.

    Connecting to

    the TerminalBlock

    Insert a 4 mm screwdriver or similar tool into the

    square hole above the appropriate wiring point

    on the terminal block. Angle the head of the

    screwdriver slightly upwards and push it in, then

    lever it downwards.

    This action will correctly position the wiring

    clamp so that the stripped end of the cable can

    be inserted. Release and remove the

    screwdriver then gently tug the inserted cable to

    ensure that it is firmly gripped.

    Radio/ModemPower

    The battery-backed power supply for a radio/ 

    modem is provided on the terminal block as

    described above1. See Figure 13 (page 4-2) for

    the correct radio connection point.

    The radio/modem power supply voltage is set by

    the user in System Status

    RADIO - S: Radio Supply 12 Volts page. This isa password protected parameter.

    If the auxiliary power fails, battery power can be

    conserved by automatically shutting down the

    radio/modem power supply. The shutdown takes

    place after the radio holdup time, set in System

    Status  RADIO - S: Radio Hold 60 min. page bythe user, has elapsed. If the Radio Hold time is

    set to zero then the radio supply will not

    shutdown, except under special circumstances

    Figure 13: Accessory Mounting Rail

    Radio

    IOEX

    Heater

    Earth

    (+)TerminalsSupply

    (+)TerminalSupply

    (+)TerminalsSupply

    (-)Terminals

    (-)Terminal

    Figure 14: Inserting a screwdriver into the wiring clamp Figure 15: Inserting stripped cable end

    into wiring point

    1. The power supply is not isolated.

  • 8/9/2019 Advc U-series Installation

    27/70

    Communications and Accessories Installation

    4-3

    or until the unit powers down. The radio/modem

    power supply is restored when the auxiliary

    supply returns to normal.

    The radio/modem power supply can be turned

    on and off by the operator for radio maintenance

    without passwords in System Status

     RADIO - S: Radio Supply ON page. If the radiosupply has shutdown it will be indicated on  System Status: RADIO - S.

    IOEX2Installation

    The Input Output Expander (IOEX2) module

    provides optically isolated inputs and voltagefree outputs to allow connection to external

    devices. It is installed in a die cast, sealed

    enclosure which is mounted on, and earthed via,

    the DIN rail in the customer enclosure as shownin the following picture: (See Appendix B for

    IOEX2 dimensions.)

    The IOEX2 is suspended from the DIN rail by

    two fittings on its rear surface:

    To fit the IOEX2:

    1 Holding the IOEX2 perpendicular, place theupper hooks of the hanging fittings over the

    top edge of the DIN rail.

    2 Push the IOEX2 firmly against the back

    surface of the Customer compartment until

    the lower end of the hanging fittings engagewith the bottom edge of the DIN rail.

    3 Push the green/yellow earth terminal firmly

    on to the DIN rail until it is engaged at both

    the top and bottom.

    4 Connect the IOEX2 supply using the cable

    provided to the terminal block connection

    point as shown in Figure 13 (page 4-2).

    5 Connect the communications cable to Port Bon the CAPE. This RS 232 port is assigned

    by default to the IOEX2. Excess cable

    should be run through the cable duct.

    CommunicationPorts

    The ADVC has numerous communications ports

    available to the user:

    Not all ports are available for use at the same

    time. The ports can be enabled/disabled via

    WSOS.

    Permanently available ports are:

    RS232 Port D Serial Port E (dedicated to the OCP)

    10 base T Ethernet

    Any 3 of the 5 following ports are available:

    Figure 16: IOEX 2 Module

    Earth(-)Terminals

    IOEX2 Power Supply

    RS232 Controller Port

    Figure 17: Rear of IOEX 2 Module

  • 8/9/2019 Advc U-series Installation

    28/70

    U-Series Automatic Circuit Recloser

    4-4

    RS 232 Port A (enabled by default)

    RS232 Port B (enabled by default)

    RS 232 Port C (enabled by default)

    RS485 (disabled by default)

    V23 FSK (disabled by default)

    The ports typically have three uses:

    WSOS communications

    SCADA communications

    IOEX communications

    RS232 Four RS232 ports (A to D) are provided toconnect to conventional modems that providethe correct signalling for the communications

    network used, e.g. optical fibre modem, or

    telephone dial up modem, or RS232 radiomodem. All four ports have standard 9 pin D

    male connectors and have the following pin

    connections: 

    All RS-232 ports are not isolated from one

    another or from the controller electronics. They

    therefore can only be connected to devices

    inside the controller that are powered by the

    controller radio supply, including modems,

    optical isolators, and radios.

    Use of serial ports to connect

    directly to other devices outside

    the controller can cause damage

    and void warranty. If connections

    to other devices are required then isolation

    interfaces MUST be used.

    RS485 An RS485 port has been provided to enablehigher speed multi-drop connections that often

    occur within substations. The RS-485 port is a

    female RJ45 connector.

    RS232

    Pin NoDirection Use

    Port

    A B C D

    1 To ADVC Data Carrier Detect (DCD) Yes Yes

    2 To ADVC Rx Data (RxD) Yes Yes Yes Yes

    3 From

    ADVC

    Tx Data (TxD) Yes Yes Yes Yes

    4 From

    ADVC

    Data Terminal ready

    (DTR)

    Yes Yes

    5 0V (ground/earth) Yes Yes Yes Yes

    6 Not connected

    7 From

    ADVC

    Request to Send (RTS) Yes Yes

    8 To ADVC Clear to Send (CTS) Yes Yes

    9 Resered Yes

    Table 1: RS232 Pin Connections

    Pin Direction Use

    1 Not connected

    2 To ADVC Rx Data (Rx +)

    3 Not connected

    4 To ADVC Rx Data (Rx -)

    5 Not connected

    6 From ADVC Tx Data (Tx +)

    7 Not connected

    8 From ADVC Tx Data (Tx -)

    9 Shield

    Table 2: RS485 Pin Connections

  • 8/9/2019 Advc U-series Installation

    29/70

    Communications and Accessories Installation

    4-5

    V23 FSK An in-built FSK modem provides half-duplexV23 signalling at 1200 bits per second. This

    interface is primarily designed for use with voice

    frequency radio systems and provides additional

    signals for this purpose.

    The V23 connector is RJ45:

    The Push to Talk (PTT) signal is used to key up

    a radio transmitter. PTT is implemented using a

    Field Effect Transistor (FET) with an on

    resistance of 3.3 ohm. When PTT is asserted

    the transistor is turned on and connects the PTT

    signal to 0V.

    A busy signal can be provided by the radio to

    indicate receive channel busy. High level is

    +2.0V to +3.3V, and low level is 0V to +0.5V.The busy signal should be driven by an open

    collector output or current limited to 10 mA.

    Levels in excess of ±13V should

    not be applied. The FET is rated for

    a maximum of +32V and negative

    voltages are not permitted.

    Transmit and receive are unbalanced signals

    relative to 0 volts and are not isolated. If a

    DC level is imposed by the radio on the

    transmit line then this should be less than

    2.5 VDC.

    If multiple ACRs are in use in a substation

    application they can be connected to a singleradio using the 600ohm line isolator accessory

    available from the manufacturer.

    Ethernet The controller has a 10 base T Ethernet port.The port is a RJ45 female connector.

    If the controller is connected to a

    LAN or WAN then it is stronglyrecommended that:

    1.Firewalls be used to limit user

    access to the controller

    2.Ethernet switches be used to

    limit the volume of Ethernet data

    reaching the controller's 10Base-T

    port. (Use of Ethernet hubs is not

    recommended.)

     

    WindowsSwitchgearOperatingSystem(WSOS)

    Windows Switchgear Operating System

    (WSOS) is a software package available on a

    PC that enables configuration, control and

    monitoring of the controller.

    The controller has its hatch port physically

    connected to Port A via an interconnecting

    cable. The default WSOS communications via

    the port are 57600 baud, 8 bit, no parity, and 1

    stop bit. WSOS communication set up

    parameters are user configurable.

    Pin Direction Use

    1 To ADVC Receive, 10 kOhm impedance

    Sensitivity 0.1 – 2V pk-pk

    2 0 Volts (ground/earth)

    3 Not connected

    4 To ADVC Busy, 5 kOhm impedance

    5 Not connected

    6 From ADVC Transmit, 600 Ohm impedance

    Level 2.5V pk-pk

    7 Not connected

    8 From ADVC Push to talk (PTT)

    9 Shield

    Table 3: V23 Pin Connections

    Pin Direction Use

    1 From ADVC Tx Data (Tx -)

    2 From ADVC Tx Data (Tx +)

    3 To ADVC Rx Data (Rx +)

    4 Not connected

    5 Not connected

    6 To ADVC Rx Data (Rx -)

    7 Not connected

    8 Not connected

    Table 4: Ethernet Pin Connections

  • 8/9/2019 Advc U-series Installation

    30/70

    U-Series Automatic Circuit Recloser

    4-6

    SCADAProtocols

    SCADA communications are available on the

    controller and supported protocols can be

    assigned to any of the RS232 ports as well as

    the V23 port.

    All currently supported protocols can be viewed

    on  SYSTEM STATUS - OPTIONS 4. Protocolsmust be available before they will appear in the

    communications menu. Once you make a SCADA protocol available,

    the communication parameters can beconfigured. Refer to the Operator Manual and

    protocol technical information for more detail.

    - - - - - - - - - - - - - OPTION 4 - - - - - - - - - - - - SDNP Available RDI Available

    Trace Available

  • 8/9/2019 Advc U-series Installation

    31/70

    Testing Your Installation

    5-1

    5 Testing Your Installation

    The following sections give details of how the

    ACR and ADVC, installed as described in

    “Installation” on page 3-1, should be prepared

    for operation.

    Check that the installation and

    external connections have been

    carried out as described in this

    manual and in accordance with

    local regulations.

    Ensure that earthing has been carried

    out as described in “Earthing” on

    page 3-4.

    Check that no visible damage has occurred

    during the installation.

    Carry out any visual and electrical tests, such as

    insulation and contact resistance, considerednecessary to prove that the installation is sound.

    Powering Upthe ADVC

    1 Turn on the battery circuit breaker,

    The batteries are capable of

    supplying very high currents.

    Always turn off the battery circuit

    breaker before connecting or

    disconnecting the batteries in the cubicle.

    Never leave flying leads connected to the

    battery.

    2 Turn on the auxiliary supply circuit breaker ifthe auxiliary supply is being provided by

    either an LV mains or dedicated auxiliary

    transformer.

    3 Turn on the VT supply to cubicle circuit

    breaker if the auxiliary supply is being

    provided by an integrated transformer.

    4 Powering up the ADVC with the ACR

    connected will cause the ADVC to read data

    from the ACR. This will take up to 60

    seconds during which the message:

    “READING - Do NOT disconnect

    Switchgear” will flash at the top of thedisplay. The System OK LED on the OCP

    should flash to indicate that the ADVC is

    powered and functioning.

    5 If the configuration file containing the

    settings to be used in operation has notpreviously been loaded, it should be loaded

    now using WSOS, or the settings should be

    entered via the OCP.

    The ACR and ADVC are now ready for

    operation. Prior to energising the ACR, you

    should perform the checks detailed below, to

    confirm that the equipment is fully operational

    and properly configured.If you are familiar with navigating

    Operator Control Panel display

    groups, proceed with the checks

    described below. Otherwise, please

    read the chapter, “Operator Control Panel” on

    page 7-1 before continuing.

    Battery For this and all subsequent tests youwill need to check settings on display

    group pages (See “Display Groups” on

    page 7-2.) You may also have to

    check the Event Log (See “Event Log” on

    page 8-1.)

    1 In the System Status group, go to page

     SWITCHGEAR STATUS - S2 Check the Battery status.

    The battery may be in any one of four states:Normal; OFF; Low; High. At this point, the

    battery state should be Normal with a

    voltage within the range 23 to 29.5V.

    - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - SWork Tag OFFAux Supply Normal Battery Normal 27.5VSwitch Connected Switch Data Valid

  • 8/9/2019 Advc U-series Installation

    32/70

    U-Series Automatic Circuit Recloser

    5-2

    Ensure the Aux Supply status is Normal. If

    not, you cannot perform the remaining

    battery checks at this stage.

    3 Switch the battery circuit breaker off and

    check that the battery status changes to

    OFF. (Allow 3 - 5 seconds.)

    4 Go to page  EVENT LOG and check that

    the bottom line of the display (the most

    recent event) contains the Battery OFF

    event.

    When the battery status is Low Volts,

    but the voltage is close to the normal

    range lower limit, the battery will

    charge up when the auxiliary supply is

    turned on. If the voltage is very low, replace the

    battery.

    5 Switch the battery back on.

    Connectionbetween theADVC and theACR

    1 In the System Status group, go to page

     SWITCHGEAR STATUS - S2 Check the Switch status.

    It may be in either of two states: Connected

    or Disconnected. “Connected” is the normal

    state. If Switch is “Disconnected”, check the

    control cable at both ends. If the status

    remains “Disconnected”, the cable may be

    faulty.

    3 Check that the Switch Data status is Valid.

    In normal operation, if Switch status is

    “Connected”, Switch Data will be “Valid”.

    If the control cable has been unplugged

    (Switch “Disconnected”, Switch Data

    “Invalid”) then re-plugged (Switch status

    “Connected”), the Switch Data status will

    remain “Invalid” during the time taken to read

    switch data from the SCEM, and a message

    to that effect is displayed.

    If Switch Data remains “Invalid”, check the

    following:

    Examine each end of the control cable,

    checking for bent or broken pins and rectify if

    found. Also check the socket at both the

    SCEM and P1 in the ADVC for damage.

    If the pins are OK, the cable itself may be

    faulty1, therefore test the control cable for

    continuity.

    If Switch Data remains “Invalid”, check the

    power supply to the SCEM by checking the

    voltage on Pins 2 and 5 of the control cable.

    The voltage should be approximately 36VDC

    if the auxiliary supply is present or

    approximately 26VDC if running on

    batteries.

    AuxiliarySupply

    1 In the System Status group, go to page

     SWITCHGEAR STATUS - S2 Check the Aux Supply status.

    The auxiliary supply may be in either of two

    states: Normal or Fail.Ensure the battery status is Normal.

    3 If using LV auxiliary supply, switch the

    auxiliary supply off, OR if using integrated

    auxiliary supply and the VT is energised,

    switch off the VT supply to cubicle circuit

    breaker. Check that the Aux Supply status

    changes to Fail. (Allow 3 - 5 seconds.)

    4 Check that the battery voltage has dropped

    by approximately 2V, and that the battery

    remains in Normal state.

    If the battery voltage continues

    dropping, and the battery state is

    LOW, the batteries may be flat. If

    the batteries are flat, replace

    them.

    5 Go to page

      EVENT LOG and check that

    the bottom line of the display (the most

    recent event) contains the Aux Supply Off

    event.

    6 Switch the auxiliary supply back on.

    Work Tag 1 In the System Status group, go to page OPERATOR SETTINGS 1 - S. Check thatLOCAL CONTROL is ON.

    2 In the System Status group, go to page

     SWITCHGEAR STATUS - S3 Check the Work Tag status.

    - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - SWork Tag OFF SF6 Normal 37kPagAux Supply Normal Battery Normal 27.5VSwitch Connected Switch Data Valid

    1. It is possible for the Switch status to be showing “Connected” though thecontrol cablet core is faulty, causing the SwitchData to show “Invalid”.

    - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - SWork Tag OFFAux Supply Normal Battery Normal 27.5VSwitch Connected Switch Data Valid

     - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - SWork Tag OFFAux Supply Normal Battery Normal 27.5VSwitch Connected Switch Data Valid

  • 8/9/2019 Advc U-series Installation

    33/70

    Testing Your Installation

    5-3

    The tag has two possible settings: Applied or

    OFF. OFF is the default.

    4 Press the SELECT key to select the work tag

    field.

    5 Press  to change the setting to Appliedand then press ENTER to activate the setting.

    The message: “WORK TAG APPLIED” will

    flash at the top of the display.

    6 Go to page  EVENT LOG and check thatthe bottom line of the display (the most

    recent event) contains the Work Tag Applied

    event.

    7 Return to page

     SWITCHGEAR STATUS - S and change thesetting back to OFF.

    TerminalDesignationand PhaseRotation

    The power system phase assigned to each set

    of bushings on the ACR must be correctly

    indicated at the time of installation of the ADVC.

    This process is called “setting the phasing”.

    Setting the phasing affects all the displays,

    events, etc., concerned with recloser terminals,

    for example: voltage measurements, live/dead

    terminal displays and maximum current events.

    Normal/default phasing is A, B and C for

    bushings I + X, II + XX and III + XXX. Normal/ 

    default phase rotation is ABC.

    If the phasing at the ACR and/or phase rotation

    of the network are different from the default, you

    must set the phasing and/or the phase rotation.

    Phasing is set from the System Status page

     TERMINAL DESIGNATION/ROTATION - S

    1 Press the SELECT key to select the Phasing

    field.

    2 Press  to change the setting.

    3 Press the ENTER key when you have the

    required phase combination. The controller

    then orientates the currents and voltages to

    match the selection.

    4 In the Phasing field, select the phase

    rotation - either ABC or ACB.

    5 Go to page  EVENT LOG and check thatthe bottom line of the display (the most

    recent event) contains the Phasing order

    event.

    6 After the phasing has been set, you should

    record the details on the label on the rear of

    the control cubicle door (above the operator

    panel) to indicate the relationship between

    the bushings and phases.

    Power FlowDirectionSetting

    The ACR is a symmetrical device meaning that

    either side can be connected to the power

    source. However, the power source would

    normally be connected to the side with the

    CVTs. The bushings on that side are labelled l,

    ll, and lll.

    Consequently, after installation, the controller

    must be configured to designate the source

    side.

    The power flow direction is configured on page

     SYSTEM STATUS - PHASE VOLTAGE and POWERFLOW:

    and may be either

    Source I, Load X or Source X, Load I.

    When changed, this reverses the power flow

    direction but not the phasing.

    Power flow direction setting is used to

    determine:

    Whether the source or load corresponds to

    (I) or (X) on the voltage measurementdisplays.

    Which direction is positive power flow for useon the kWh totals in the Maximum Weekly

    Demand display and APGS.

    Which is the source or load for Live Load

    Blocking. Which is the source or load for Directional

    Blocking/Protection.

    Tripping andClosing

    If system conditions allow, tripping or closing

    can be carried out at this point.

    1 Trip and close the ACR from the ADVC. See

    “Operator Control Panel” on page 7-1. for

    information on the Trip and Close controls.

    2 Tripping and closing should cause the LED

    on the appropriate TRIP/CLOSE button to

    illuminate which should agree with the

    position of the pointer on the ACR.

    Enable/DisableSwitches

    For each of the CLOSE and TRIP keys in turn, test

    ENABLE and DISABLE by:

    1 Disable either mechanism e.g. CLOSE.

    When the CLOSE or TRIP mechanism

    is disabled, the message

    The TRIP or CLOSE circuit is isolated

     - - - - - TERMINAL DESIGNATION/ROTATION- - - - - SA Phase = Bushings I + X Phasing ABCB Phase = Bushings II + XXC Phase = Bushings III+XXX

  • 8/9/2019 Advc U-series Installation

    34/70

    U-Series Automatic Circuit Recloser

    5-4

    will flash in every display page title, alternately

    with the actual title of the page.

    2 Go to page  EVENT LOG and check thatthe bottom line of the display (the most

    recent event) contains the Close Coil Isolate

    event. (For the same test of the TRIP

    mechanism the Event Log should display

    Trip Coil Isolate.)

    3 With both mechanisms disabled, check that

    pressing each of the CLOSE and TRIP keys

    is ineffective.

    4 Enable both CLOSE and TRIP mechanisms.

    MechanicalTrip

    1 Use a hook stick to manually trip the ACR

    via the manual trip lever.

    2 Go to page  EVENT LOG and check thatthe bottom line of the display (the mostrecent event) contains the Mechanical Trip

    event.

    SecondaryInjectionTesting

    If secondary injection testing is required to test

    protection settings but operation of the ACR is

    not possible, secondary injection can be

    performed with a suitable current injection set

    with the Test and Training Set (TTS) in

    standalone mode connected to the ADVC, andthe ACR disconnected.

    If tripping and closing of the ACR is possible and

    preferred, perform secondary injection testing

    with the TTS in parallel mode.

    Any secondary injection must use a

    frequency which corresponds to the

    frequency set in the controller.

    PrimaryInjectionTesting

    If the ACR can be isolated from the network,

    primary injection testing can be performed if

    required.

    Power FlowDirectionTesting

    This test is to ensure that the source and load

    designations are correct.

    This test is valid only if the ACR is

    being supplied from a single sourceand can be energised before closing.

    Since either side of the recloser can be

    connected to the power source, the controller

    must be configured to designate the source

    side.

    The power flow direction is configured in System

    Status on the  PHASE VOLTAGE and POWERFLOW - S page.

    If the I -side bushings are connected to the

    source, the setting should be Source I,

    Load X.1 Display the page and check the Source,

    Load configuration.

    The correct power flow setting can be confirmed

    by energising the ACR while it is open.

    2 With the recloser energized but still open, in

    System Measurement, go to  SOURCESIDE VOLTAGES - M

    3  Check the source side voltages - eitherphase to earth (ground) or phase to phase

    e.g.

    4 In the System Status group, go to page

     LIVE/DEAD INDICATION - S

    5 If Steps 3 and 4 indicate an incorrect power

    flow setting, return to Step 1, change the

    setting and repeat Steps 2-4.

    1

     - - - - - - PHASE VOLTAGE and POWER FLOW - - - - - S“LIVE” if > 2000V Supply Timeout 4.0sPower Signed Source I, Load XDisplay Ph/Earth Volt

    1

    SOURCE - - - - - - - - VOLTAGE - - - - - - - - - LOAD M< 2000 A-G

  • 8/9/2019 Advc U-series Installation

    35/70

    Testing Your Installation

    5-5

    On LoadChecks

    Once the ACR is closed and taking load, the

    following on-load checks can be carried out. To

    confirm correct operation, check the current

    against a known reading.

    1 Go to the System Measurement page  CURRENT e.g.

    2 Then to  SYSTEM MEASUREMENTS e.g.

    U

    se this page to confirm that system

    measurements and power flow signs are asexpected.

    3 Go to the System Measurement page  SOURCE VOLTAGE LOAD e.g.

    External CVTs must be fitted in order

    to obtain load side voltages.

    This page displays the system voltage either as

    phase to ground or phase to phase values as

    configured on the System Status, Phase Voltage

    and Power Flow page.

    Source and load side voltages should be the

    same when the ACR is closed.

    4 Go to  MAXIMUM DEMAND INDICATOR.

    Press SELECT to display RESETMAXIMUM DEMAND INDICATOR -M.Press SELECT again to reset the flags.

     - - - - - - - - - - - - - CURRENT- - - - - - - - - - - - - MA Phase 123 A0 Earth 0 A 0B Phase 123 A240 Ipps 123 A 240C Phase 123 A120 Inps 0 A 120

     - - - - - - - - - SYSTEM MEASUREMENTS - - - - - - - - MCurrent 100 Amp Power P 1829 kWVoltage 6350 Volt Power Q 533 kVARFrequency 50.0Hz PF 0.96

    SOURCE - - - - - - - - VOLTAGE- - - - - - - - - LOAD M11000 Volt A-P 11000 volt11000 Volt B-P 11000 volt11000 Volt C-P 11000 volt

  • 8/9/2019 Advc U-series Installation

    36/70

    U-Series Automatic Circuit Recloser

    5-6

  • 8/9/2019 Advc U-series Installation

    37/70

    Control Electronics Operation

    6-1

    6 Control Electronics Operation

    The ADVC is purposely designed for outdoor

    pole mounted operation. The cubicle is vented

    and insulated to minimise internal temperature

    variation and maximise battery life.

    Figure 24 (page B-2) shows the cubicle’s

    dimensions.

    Sealing &CondensationAll cubicle vents are screened against verminentry and the cubicle door is sealed with

    replaceable foam tape.

    Complete sealing against water entry under all

    conditions is not expected e.g. during operation

    in the rain. Instead, the design is such that if any

    water does enter, it will run out of the bottom

    without affecting the electrical or electronic

    parts. The extensive use of stainless steel and

    other corrosion proof materials ensures that the

    presence of moisture has no detrimental effects.

    Condensation can be expected to form undersome atmospheric conditions such as tropical

    storms. However, condensation will be on metal

    surfaces where it is of no consequence. The

    water runs out in the same way as any other

    water entering the cubicle. Condensation will

    run out of the bottom or be dried by ventilation

    and self heating.

    All electronic modules are fully sealed and have

    self heating.

    AuxiliaryPower Source

    The auxiliary supply is used to maintain charge

    on the sealed lead-acid batteries that provide

    standby power when auxiliary power is lost. The

    controller monitors the status of both the

    auxiliary and battery supplies.

    A low power mode is activated when the

    batteries are nearly exhausted due to loss of the

    auxiliary supply. This mode minimises power

    consumption while still maintaining basic

    functionality.

    Controller The controller comprises 3 modules (SeeFigure 18 (page 6-3):

    Power supply unit (PSU)

    Control and protection enclosure (CAPE)

    Basic Display Unit (BDU).

    The ADVC block diagram is given in Figure 19

    (page 6-4).

    PSU Module The PSU module supplies power to the CAPE,and to the customer compartment. The PSU

    module:

    connects to the batteries

    controls the supply from external auxiliary

    sources

    filters these supplies and manages the

    battery power level.

    It also performs battery testing and has a non-

    volatile, real time clock. A general purpose

    power outlet is available as an optional extra

    (country customizable). The incoming power is

    protected and isolated by a circuit breaker. The

    supply from the batteries is protected and

    isolated by a circuit breaker.

    The electronic components are contained inside

    a housing that provides environmental

    protection, sealing and EMI shielding. The

    power outlet, circuit breakers and switches are

    easily accessible when the ADVC door is

    opened. The batteries are located and retained

    on the exterior top of the PSU module.

    CAPE Module The CAPE Module comprises two printed circuitboard assemblies and the trip and close

    capacitors housed in a die-cast aluminium

    enclosure. The two printed circuit board

    assemblies are:

    PCOM: Protection and Communication

    Module

    SWGM: Switchgear Module

    The CAPE enclosure is manufactured from

    pressure die-cast aluminium. The front surface

    with the user and switchgear connectors, andthe rear surface, are gasketed to provide an

    IP65 Degree of Protection. The enclosure also

    provides EMC shielding for the CAPE

    electronics.

    The PCOM is the heart of the ADVC and

    includes the data acquisition hardware

    (including a powerful Digital Signal Processor)

    and communications hardware (Ethernet,

    RS232, RS485 and V23). All user-interface,

    measurement, protection, communication andcontrol functionality is provided by software

    running on the PCOM.

    The SWGM contains the switchgear interface

    hardware, SCEM interface hardware, EMCprotection and filtering devices and high voltage

    inverters for the trip and close capacitors.

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/9/2019 Advc U-series Installation

    38/70

  • 8/9/2019 Advc U-series Installation

    39/70

    Control Electronics Operation

    6-3

    Figure 18: Advanced Controller

    Operator Control Panel Customer Equipment Compartment

    PSUCAPE Batteries

     

  • 8/9/2019 Advc U-series Installation

    40/70

    U-Series Automatic Circuit Recloser

    6-4

    Figure 19: ADVC Block Diagram

  • 8/9/2019 Advc U-series Installation

    41/70

  • 8/9/2019 Advc U-series Installation

    42/70

    U-Series Automatic Circuit Recloser

    7-2

     As well as each isolate/enableswitch affecting its associated

    button, isolating the TRIP button

    while the ACR is tripped will prevent

    the operation of the CLOSE button thuspreventing a manual close on to a fault.

    DisplayGroups

    The OCP displays are organized into logical

    groups called Display Groups. Within each

    group is a menu of pages and some pages have

    sub-pages.

    (There are labels similar to that shown below

    affixed to the door of the ADVC.)

    Each page consists of fields. A field may contain

    either:

    a setting, which can be changed - ON/OFF

    is the most common; or

    a status..

    Configurable

    Quick Key

    Default linkage is to PROT GROUP. See “Quick Keys” on page 7-4.

    Configurable

    Quick Key

    Default linkage is to EARTH PROT. See “Quick Keys” on page 7-4.

    Configurable

    Quick Key

    Default linkage is to LOCAL/REMOTE. See “Quick Keys” on page 7-4.

    RIGHT scrollkey  Select the next screen in a display group or, if a setting is selected, increase its

    value.

    SELECT key Press to SELECT a setting.

    LEFT scroll

    key Select the previous screen in a display group or, if a setting is selected, decreaseits value.

    MENU scroll

    key

    Displays the first page of the next group. Pressing the MENU key after changing a

    setting causes the setting change to take effect.

    ALT The alternative function key gives access to an alternative Event Log display.

    Number Item Description

    Table 5: Operator Control Panel Keys

    10

    11

    12

    13

    14

    15

    16

    17

    11

  • 8/9/2019 Advc U-series Installation

    43/70

    Operator Control Panel

    7-3

    Custom Menu It is possible to configure a custom menucomprising those display group pages which are

    particularly required, or those used most

    frequently. Please see the Operation Manual for

    more information. Where a custom menu has

    been configured, you access it by pressing the

    Custom Menu button on the OCP.

    ChangingSettings

    Three types of settings can be changed:

    Operator settings

    Password protected settings

    Protection settings

    A separate procedure is used to change each ofthe setting types.

    OperatorSettings

    Find the display page containing the setting to

    be changed:

    1 Press the MENU key to display the group

    you require.

    2 Press  to display the page you require.

    3 Press SELECT to highlight the setting. A

    highlighted setting “blinks”.

    Alternatively, if a QUICK KEY is linked to the

    setting, you can use it to go directly to relevant

    display page where you will find the highlighted

    setting. (See “Quick Keys” on page 7-4.)

    4 Once you have selected the setting to be

    changed, use  or  to change itssetting.

    5 Press ENTER or MENU to activate the new

    setting.

    PasswordProtectedSettings

    Some settings are password protected. You will

    be prompted for a password before you can

    change the setting. To enter the password:

    1. Press either of the  keys until thefirst character of the password is displayed.

    2. Press the SELECT key.

    3. Repeat Steps 1 and 2 until the password is

    complete.

    4. Press Enter.

    While the operator panel is ON you will not be

    required to enter the password again.

    The default factory password is AAAA but you

    can change it using the Windows Switchgear

    Operator System (WSOS) program. The factory

    password does not have to be remembered -

    the controller prompts you for it automatically.

    Communications Group (only) is

    divided into subgroups for different

    protocols. Press SELECT to display

    the subgroup you require.

    ProtectionSettings

    Protection settings are password protected. To

    change a protection setting, follow the steps

    detailed in the Operator Settings section above

    but, in addition, enter the password when

    prompted. When you have completed the

    setting change by pressing ENTER, the

    following message will flash at the top of the

    screen:

    Active Protection Setting has changed.

    At this point, the changed setting will bedisplayed but not in service. If further setting

    changes are required, they can be made now.

    When you have completed making all the

    setting changes you require, press ENTER. The

    following text will be displayed:

    CHANGED ACTIVE PROTECTION SETTING

    [A]

    The changed active PROTECTION SETTINGS

    are now in service. Select the MENU or

    ENTER key to continue.

    The changed settings are now in service. PressMENU or ENTER to return to the normal menu

    display.

    NavigatingWithin DisplayGroups

    Refer to the diagram inside the OCP hatch, the

    ADVC door or to the Operations Manual fordetails of navigation within groups.

    Page Layout The display area consists of four lines, eachforty characters long.The top line of the display

    is the page title. To the right of the title is a letter,

    indicating the display group to which the page

    belongs:

  • 8/9/2019 Advc U-series Installation

    44/70

    U-Series Automatic Circuit Recloser

    7-4

     

    The next three lines are the data on display.

    Most pages have six data fields.

    Quick Keys The operator settings that you will frequentlychange can each be linked to a Quick Key. You

    use a Quick Key for instant display and selection

    of the linked setting which, otherwise, you would

    have to find by navigation.

    You can link operator settings to individual Quick

    Keys using the operator control panel or WSOS.

    For more detail, refer to the Operations manual.

    A Quick Key can be set to Blank, if it is not

    required.

    Otherwise, any one of the following settings can

    be linked to one of the four Quick Keys:.

    Quick Key

    Configuration

    The Quick Keys default configuration is given in

    Table 5: (page 7-1). The ability to re-configurethe Quick Keys must be made available from the

     SYSTEM STATUS - OPTIONS 3 page:

    If Config QK is Available, make changes on the

     SYSTEM STATUS - QUICK KEY SELECTION

    page:

     To configure a Quick Key, press SELECT or

    ENTER. The following screen is displayed with

    the first setting selected (blinking)

    .

    Press  or  to scroll through the list ofsettings that can be linked to Quick Keys.

    Press MENU or ENTER when the required setting

    is displayed.

    To configure another Quick Key, press SELECT 

    and repeat the above procedure.

    Each setting can only be assigned to oneQuick Key.

    If the operator selects a function that has

    been assigned to another Quick Key that

    selection will revert to a blank setting.

    When a Quick Key is changed an event is

    generated in the Event Log.

    Changing the quick keys

    configuration requires updating of

    the OCP quick keys using

    adhesive labels supplied with the

    ADVC. Failure to match software

    and panel may cause incorrect

    operation of controller.

    S System Status Display Group

    E Event Log

    M Measurement Display Group

    P Protection Display Group

    A Automation Display Group

    C Communications Setup

    LOCAL/Remote / Hit & Run

    Loop Auto ON/OFF

    Prot Group

    Reset Flags

    Work Tag ON/OFF

    Auto ON/OFFProtection OFF

    Negative Phase Sequence

    (NPS) ON/OFF/Alarm

    Cold Load ON/OFF

    Earth Prot

    Live Block

    Table 6: Quick Key Configurable Settings

     - - - - - - - - - - - - -OPTIONS 3 - - - - - - - - - - - -SConfig QK Available APGS Not AllowedU/O Freq Available

     - - - - - - -CHANGE QUICK KEY SELECTION - - - - - -S

    LOCAL/Remote Earth ProtWork Tag Enter Loop Auto

     - - - - - - - - - QUICK KEY SELECTION- - - - - - - - -S

    LOCAL/Remote Earth ProtAuto ON/OFF Enter Prot Group

  • 8/9/2019 Advc U-series Installation

    45/70

    Operator Control Panel

    7-5

    Using a QuickKey

    1 Press a Quick Key at any time to display the

    relevant page, with the linked setting

    selected:

    2 Press the same Quick Key again to display

    the next setting option for that setting.

    Repeat until you have displayed the setting

    you require.

    3 Press the ENTER or MENU key to activate the

    displayed setting AND, after a short delay, to

    return to the page that was displayed when

    you first pressed the Quick Key.1

    Whenever a Quick Key is in use the  and SELECT keys are disabled.

    1. A particular option may not be available to the operator if it has been disabled on the “SYSTEM STATUS-OPTIONS” page

  • 8/9/2019 Advc U-series Installation

    46/70

    U-Series Automatic Circuit Recloser

    7-6

  • 8/9/2019 Advc U-series Installation

    47/70

    Event Log

    8-1

    8 Event Log

    When the status of the control electronics or

    switchgear changes, events  are generated

    which are recorded in an Event Log  for display

    to the operator. Examples of such events are

    ‘Load Supply On’ or ‘Lockout’.

    Events are viewed on the Event Log pages and

    can also be up-loaded and viewed with the

    Windows Switchgear Operating System.

    The event log display looks like this:

    Events are dated, time stamped, and displayed

    in the order in which they occurred.

    The  key scrolls the display downward  toshow older events, the  key scrolls thedisplay upward  to show more recent events.

    Pressing the  key removes the title of thedisplay to make more room for events. The title

    will only be restored when the event log is

    selected again from the top level menu.

    Display

    Updating

    The event log display will update automatically

    with new events, provided the most recent eventis on the bottom line of the screen. When new

    events occur they are entered at the bottom of

    the screen and the older events are scrolled up.

    Event LogFormat

    Each event occupies one line of the event log.

    The standard display contains (reading from the

    left):

    the date of the event,

    the time of the event, and

    the event description.

    Additional information e.g. event source isrecorded and can be made visible if you press

    the ALT key while the event is displayed.

    Using the ALTKey

    If the Alt key is pressed whilst the event log is on

    display, the date and time details may bereplaced with extra information that includes, at

    far left, the event source and followed by, if

    applicable, additional event details. Examples of

    source codes are:

    Additional event details are available where the

    combination of the source plus event descriptionalone will not precisely identify the event e.g.

    protection events or events sourced to WSOS.

    Examples of additional details are:

    the protection group

    curve

    trip number

    port identification

    protocol.

    Typical EventLog Displays

    A typical sequence of events for a phase/phase

    fault, which had instantaneous protection on the

    first trip and inverse time protection on the

    second trip, with two trips to lockout might be as

    shown in Figure 21 (page 8-2).

    However, if the fault was cleared after the first

    trip has occurred, the controller will generate a

    ‘Sequence Reset’ event once the Sequence

    Reset Time has expired, as shown in Figure 22(page 8-2).

     

    - - - - - - - - - - - - -EVENT LOG - - - - - - - - - - - -E10/01/01 12:09:02.06 Battery Normal10/01/01 12:09:03.95 Panel close req10/01/01 12:09:37.95 Load Supply ON

    Identifier Event (settings change) source

    WSOS Windows SOS change

    OCP Operator control panel change

    PTCL SCADA protocol change

    IOEX IOEX change

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/9/2019 Advc U-series Installation

    48/70

    U-Series Automatic Circuit Recloser

    8-2

     

    Figure 21: Event Log example - Phase to Phase fault

     - - - - - - - - - - EVENT LOG- - - - - - - - - - E

    07/01/01 07:02:53.90 Pickup Start of fault

    07/01/01 07:02:53.92 Prot Group A Active Protection Group A

    07/01/01 07:02:53.92 Phase Prot Trip Phase Element caused trip

    07/01/01 07:02:53.92 Prot Trip 1 1st trip 20ms after pickup

    07/01/01 07:02:53.92 A Max 543 AMP Peak A phase current

    07/01/01 07:02:53.92 B Max 527 AMP Peak B phase current

    07/01/01 07:02:54.76 Automatic Reclose 1st Reclose

    07/01/01 07:02:54.77 Pickup Pickup again

    07/01/01 07:02:57.24 Prot Group A Active Protection Group A

    07/01/01 07:02:57.24 Phase Prot Trip Phase Element caused trip

    07/01/01 07:03:04.24 Prot Trip 2 2nd trip 2.47 sec later

    07/01/01 07:03:04.24 A Max 453 AMP Peak A phase current

    Figure 22: Sequence Reset example

    - - - - - - - - - EVENT LOG- - - - - - - - - E

    07/01/01 07:02:53.90 Pickup Start of fault

    07/01/01 07:02:53.92 Prot Group A Active Protection Group A

    07/01/01 07:02:53.92 Phase Prot Trip Phase Element caused trip

    07/01/01 07:02:53.92 Prot Trip 1 1st trip 20ms after Pickup

    07/01/01 07:02:53.92 A Max 543 AMP Peak A phase current

    07/01/01 07:02:53.92 B Max 527 AMP Peak B phase current

    07/01/01 07:02:54.76 Automatic Reclose 1st Reclose

    07/01/01 07:02:64.76 Sequence Reset Reclose Successful

  • 8/9/2019 Advc U-series Installation

    49/70

    Power System Measurements

    9-1

    9 Power System Measurements

    The current transformer (CT) signals and

    voltage screen (CVT) signals from the recloser

    are digitised by the ADVC and used to provide a

    variety of data for the operator.

    The ADVC measures up to 10 power system

    components:

    A, B, C, phase and spill currents, phase-earth voltage on all six terminals.

    The ADVC uses the above measurements to

    derive many system measurements including:

    frequency,

    phase to phase voltages,

    total and per phase power (kW, kVA, kVAR),

    total and per phase power factor,

    harmonics,

    earth current, and

    sequence components.

    In addition the ADVC also measures severalinternal values such as:

    CAPE temperature,

    switchgear temperature1

    auxiliary voltage,

    battery voltage.

    Power SystemFrequency

    The controller must be set for the correct power

    system frequency – either 50 or 60 Hz.

    This is set on page

    SYSTEM STATUS - PHASE VOLTAGE and POWERFLOW

    Real TimeDisplays

    The first five screens of the System

    Measurements group contain real time displays.

    They are:

    1 System Measurements

    2 Current (includes phase angles)

    3 Voltage

    4 Sequence Voltage

    5 Power

    The ninth screen, Maximum demand Indicator,

    also contains some real time data.

    Data displayed is as follows:

    System Measurements

    This is a summary page. The current and

    voltage values displayed are an average of

    the three phases.

    Frequency is measured on the first available

    bushing. Frequency is Unavailable if allbushings are dead.

     

    Current

    This screen displays, for each phase, the

    current and phase angle.

    The earth current.

    The Positive Phase Sequence Current

    (IPPS) and Negative Phase Sequence

    Current (Inps).

    Voltage

    The voltages displayed can be either phase

    to phase or phase to earth.This is a selectable item from

    page

     SYSTEM STATUS - PHASE VOLTAGE andPOWER FLOW: Display Ph-Ph Vol

     

    Sequence VoltageThis screen displays the Zero, Positive and

    Negative phase sequence voltages.

    1. The ADVC measures the temperature of the SCEM in the ACR and from that, calculates the switchgear temperature.

     - - - - - - - - - SYSTEM MEASUREMENTS - - - - - - - - MCurrent 100 Amp Power (P) 1638 kWVoltage 6350 Volt Power (Q) 476 kVAR

    Frequency 50.0Hz Power Factor 0.86

     - - - - - - - - - - - - - CURRENT - - - - - - - - - - - - - MA Phase 123 Amp Earth 6 AmpB Phase 128 Amp Ipps 120C Phase 121 Amp Inps 10

    SOURCE- - - - - - - - - VOLTAGE - - - - - - - - - LOAD M11000 Volt A-P 11,000 Volt11000 Volt B-P 11,000 Volt11000 Volt C-P 11,000 Volt

     - - - - - - - - - - SEQUENCE VOLTAGE- - - - - - - - - - MUzps 100 VoltUpps 11,000 VoltUnps 200 Volt

  • 8/9/2019 Advc U-series Installation

    50/70

    U-Series Automatic Circuit Recloser

    9-2

    Power

    This screen displays real and reactive

    power, as well as the power factor on a per

    phase basis.

    Real Power (kW), this is a signed quantity

    unless Power Flow Unsigned has been

    selected on page

     SYSTEM STATUS - PHASE VOLTAGE andPOWER FLOW: Power Flow Signed/Unsigned

    Power Factor (PF), this is an unsigned

    quantity.

    MaximumDemandIndicator

    As stated above, the first five System

    Measurements screens are real time. The next

    four screens contain historical data, except for

    the ninth screen which contains a mixture of real

    time and historical data.

     - - - - - - - - - - - - - - POWER- - - - - - - - - - - - - - MA P 540 kW Q 158 kVAR PF 0.86B P 551 kW Q 167 kVAR PF 0.86C P 547 kW Q 151 kVAR PF 0.86

     - - - - - - - MAXIMUM DEMAND INDICATOR - - - - - - -MA 0A Max 0A 01/01 00:00:00B 0A Max 0A 01/01 00:00:00C 0A Max 0A 01/01 00:00:00

  • 8/9/2019 Advc U-series Installation

    51/70

    Maintenance

    10-1

    10 Maintenance

    Maintenance can be carried out using standard

    electricians’ and mechanics’ tools.

    Be careful to ensure that if working

    on the ADVC with the door open in

    heavy rain, water does not enter

    the circuit breakers or general

    power outlet.

    ACRMaintenance

    No user maintenance of the ACR mechanism isrequired.

    The ACR should be returned to the

    manufacturer for refurbishment if the

    mechanical duty or breaking duty is exceeded.

    This is checked by examining the remaining

    contact life on the Operator Control Panel.

    When the remaining contact life in any phase

    approaches zero, the ACR has reached the end

    of its life and must be replaced.

    A warning is displayed in the event logwhen the remaining contact life reaches

    20%.

    Every five years the bushing boots should be

    checked, cleaned if necessary and the pointer

    checked to ensure it is free from mechanical

    obstructions. In areas of high atmospheric

    pollution more frequent cleaning may be

    appropriate.

    ADVCMaintenance

    Maintenance of the ADVC is required every fiveyears. The manufacturer recommends the workdescribed below.

    Cleaning Check for excessive dirt on the cubicle,particularly the roof, and clean off.

    Ensure that the mesh covering the air vents and

    the water drainage holes in the base are clean.

    BatteryReplacement

    Battery replacement is recommended after a

    period of five years. See "Battery Care" -

    page 10-2 . 

    The procedure is:

    1 Turn off the battery circuit breaker.

    2 Unplug batteries and replace with new

    batteries.

    Ensure that battery polarity is

    correct.

    3 Turn on the battery circuit breaker and

    ensure that “Battery Normal status”, is

    restored on the page

     SYSTEM STATUS-SWITCHGEAR STATUS

    Battery HeaterAccessory

    Where the battery heater accessory has been

    fitted the following procedure should be

    followed:

    1 Turn off the battery circuit breaker.

    2 Disconnect batteries and heater.

    3 Open straps and remove heater box.The battery heater box is heavy

    and should be removed with

    caution. Do not tilt the heater box.

    The cover may slide off and the

    batteries may fall out.

    4 Remove batteries and replace with new

    batteries.

    Ensure that battery polarity is

    correct.

    5 Replace the heater box, close straps.

    6 Reconnect batteries and heater.

    7 Turn on the battery circuit breaker and

    ensure that “Battery Normal status”, is

  • 8/9/2019 Advc U-series Installation

    52/70

    U-Series Automatic Circuit Recloser

    10-2

    restored on the page

     SYSTEM STATUS-SWITCHGEAR STATUS

    Battery heater failure will be reported in

    the Event Log.

    Door Seal Check the door sealing rubber for perishing orundue hardening. If necessary renew the seal.

    Battery Care The battery is predicted to provide goodperformance for the recommended five year

    service period. This is based on the battery

    manufacturer's data. No battery warranty isgiven by the manufacturer of the ADVC.

    Once in service, batteries need little care.

    Procedures for storage and other contingencies

    are as follows:

    Batteries should be stored at a temperature

    of between 0°C to 30°C (32°F to 86°F) and

    cycled every six months. Batteries should be

    stored for a maximum of one year.

    Batteries should be cycled prior to putting

    into service if they have not been cycled

    within three months. When shipped by the

    manufacturer the batteries will have been

    cycled within the previous 30 days.

    If the batteries become exhausted in service

    and are left for more than two weeks without

    auxiliary supply being restored to the ADVC

    they should be taken out, cycled and have

    their capacity checked before being returned

    to service.

    To cycle a battery, discharge with a 10 Ohm 15Watt resistor to a terminal voltage of 10V. Next,

    recharge it with a voltage regulated DC supply

    set to 13.8V. A 3A current limited supply is

    appropriate.

    Battery type, either standard or extended

    temperature, is given in Appendix A (page A-1). 

    More information on the battery care is available

    from the battery manufacturer.

    These batteries are capable of

    supplying very high currents.

    Always turn off the battery circuit

    breaker before connecting or

    disconnecting the batteries in the cubicle.

    Never leave flying leads connected to the

    battery.

    AbnormalOperatingConditions

    The operation of the capacitor charging inverter

    can be affected under abnormal condi


Recommended