Date post: | 05-Jan-2016 |
Category: |
Documents |
Upload: | elijah-jacobs |
View: | 213 times |
Download: | 1 times |
AIAGuidelines for
Design and Construction of
Hospital and Healthcare Facilities
Presented By:
Michael A. Rogers, PE
It’s not a Code or Standard,
why do I need to use it?
LAWYERS!
Facilities Covered
• Hospitals (chapter 7)
• Nursing Facilities (chapter 8)
• Outpatient Facilities (chapter 9)
• Rehabilitation Facilities (chapter 10)
• Psychiatric Hospitals (chapter 11)
When do I need to use it?
•Additions and Renovations•Medical Equipment Addition or Replacement•Roof Replacement
•Room Function Change
•Equipment Replacement
Provisions for Disaster
• Wind Loading / Earthquake• Supplies Storage
– Capacity of the following for 4 days of continuous operation :•Food and drinking water•Sterile supplies•Pharmacy supplies•Linens•Water for sanitation
Energy Conservation
• Energy Conservation efforts shall not adversely affect patient health, safety, or comfort levels
Pollution Control
• Boilers• Waste incinerators• Sterilizers• Storage tanks• Storm water control• Hazardous materials• Medical waste
Construction
• Protection of patients
• Infection control
• Construction barriers
• Traffic flow
• Disruption of utility services
• Air flow control
ConstructionExhaust
OutsideAir Intake
HVAC Criteria
Redundant SteamCapacity
• Hospitals– Hot water for clinical,
dietary and patient use– Steam for sterilization and
dietary– Heating for operating, LDR,
ICU, nursery, and general patient rooms
Redundant SteamCapacity
• Nursing Facilities– Hot water for clinical,
dietary and resident use– Steam for dietary– Heating for general patient
rooms (unless ASHRAE 99% design heating dry bulb is above 25 degrees F)
Redundant SteamCapacity
• Outpatient and Rehabilitation Facilities– Hot water for clinical, dietary
and patient use– Steam for sterilization and
dietary– Heating for operating, LDR,
ICU, and general patient rooms (unless ASHRAE 99% design heating dry bulb is above 25 degrees F)
Ventilation
• Table 7.2– Hospitals– Outpatient Facilities– Rehabilitation Facilities– Psychiatric Facilities
• Table 8.1– Nursing Facilities
Table 7.2Ventilation
Table 8.1Ventilation
Area Designation Pres
Outside Total Outside Total Outside Total
SURGURY & CRITICAL CAREOperating Room (recirc system) P 3 15 5 25 3 15 NOOperating Room (All outdoor system) P na na 15 15 na na NODelivery Room (recirc system) P 3 15 5 25 4 15 NODelivery Room (All outdoor system) P na na 15 15 na na NORecovery Room E 2 6 2 6 2 6 NONursery Suite P 2 6 5 12 2 6 NOTrama Room P 3 15 5 12 3 15 NOEndoscopy N 2 6 2 6 na na NOBronchoscopy N 2 12 2 10 na na YES NOAnasthesis Storage (Check codes) N - 8 - 8 - 8 YES NO
Room Recirculation
All Exhaust
AIA Table 7.2
ASHRAE Table 3
NC Table 1
Air Change Comparison
Air Filtration
• Table 7.3– Hospitals– Rehabilitation
Facilities
• Table 8.2– Nursing
Facilities
• Table 9.1– Outpatient
Facilities
• Table 11.1– Psychiatric
Facilities
Table 7.3 Filtration
Plumbing Criteria
Medical Gases
• Table 7.5– Hospitals– Rehabilitation Facilities– Psychiatric Facilities
• Table 9.2– Outpatient Facilities
Table 7.5 Gas Outlets
Table 9.2 Gas Outlets
Electrical Criteria
Normal Electrical
• Install per NFPA 70 and 99
• Lighting Levels per IES
• Reading light in all patient rooms
• Special Lighting for procedures and examination on separate circuit from general lighting
Emergency Electrical
• Install per NFPA 99, 101, and 110
• Minimum 24 hours fuel storage.
giving shape to healthcare
Questions ?