SplitSkyAirVRV
Packaged Air Conditioners
AIR CONDITIONERSLINE UP
PCG0558
The specifications, designs, and information in this brochure are subject to change without notice.
All rights reservedPrinted in Japan 10/05/003 Y.K.c
DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose anoutdoor unit with anti-corrosion treatment.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer orcontractor to install those parts and accessories. Use of unauthorized parts and accessories orimproper installation of parts and accessories can result in water or refrigerant leakage, electricalshock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides importantsafety instructions and warnings. Be sure to follow these instructions and warnings.
For any inquiries, contact your local distributor.
All Daikin Industries locationsand subsidiaries in Japan havereceived environmentalmanagement system standardISO 14001 certification.
The air conditioners manufacturedby Daikin Industries havereceived ISO 9001 certification forquality assurance.
Certificate Number. JMI-0107JQA-0495JQA-1452
Daikin Industries, Ltd.Domestic GroupCertificate Number. EC99J2044
ISO 14001 is the standard defined by theInternational Organization for Standardization (ISO)relating to environmental management systems.Our group has been acknowledged by aninternationally accredited compliance organisationas having an appropriate programme ofenvironmental protection procedures and activitiesto meet the requirements of ISO 14001.
About ISO 14001
1 2Daikin Industries Head Office
JAPAN
Daikin Europe N.V.
EUROPE
Daikin America
U.S.A.
Shanghai Daikin Airconditioning
Daikin (China) InvestmentDaikin Fluoro Coatings(Shanghai)
Huizhou Daikin SunsAirconditioning
X'ian Daikin Qing'anCompressor
Kanaoka Factory,Sakai Plant
Kashima FactoryShiga Plant
Yodogawa Plant Rinkai Factory,Sakai Plant
Reliability derived from 80 years of achievementSince it's foundation in 1924, Daikin Industries, Ltd. has constantly beendeveloping to become a global leader in an array of fields, such as airconditioning systems, refrigerants, fluorochemicals, electronics and hydraulicmachineries. In particular, Daikin holds the largest market share of bothresidential- and commercial-use air conditioning systems in Japan. It isthe world's sole manufacturer that combines research, development andmanufacturing of air conditioning systems, refrigerants and compressors.
CHINA
Daikin (China) InvestmentGuangzhou Branch
Daikin (China) InvestmentShanghai Branch
Daikin AirconditioningGermany
Daikin AirconditioningFrance
Daikin AirconditioningUK
Daikin IndustriesCzech Republic
Daikin AirconditioningSpain
Daikin AustraliaDaikin AirconditioningSingapore
Daikin Industries (Thailand)
ASIA/OCEANIA
Daikin AirconditioningItaly
Examples of installation
Ministry of Agriculture &Fisheries LaboratoryOmanApril 20027 VRV Plus
Al Nokhba Tower(Elite Residential Suites)KuwaitJune 200311 VRV Plus
Sanabel Tower HotelSaudi ArabiaJanuary 200175 VRV Plus
Awqaf TowerQatarJune 20048 VRV Plus
Contents
29.....Control Systems
42.....Water Chillers
28.....HRV
S P L I T T y pe A i r C o n di t i o n e r s
Air Cooled Split Type Air Conditioners
PACKAGEDAIR CONDITIONERS
The Intelligent Air Conditioning System
3
21
7
33
Osaka Head Office
Tokyo Head Office
Production Site
Overseas Affiliate
Sales Agent
DAIKINASAGLOBALCORPORATE CITIZEN
Osaka Head Office
Tokyo Head Office
Production Site
Overseas Affiliate
Sales Agent
FT60D
Note: Availability of the products shown in this catalog varies by country.
3 4
The Split System is the ideal air conditioning solution for one room oran area of your home. Daikin air conditioners lead the industry withtheir energy savings. Each indoor unit features silent operationfunction, bringing comfort in your living room or bedroom.Daikin now has a new D series. The simple and stylish design softlyharmonizes with your living space.
Wall-mounted type...............................5
Split type air conditioners
SPLIT Type Air Conditioners
Line up
Type
Function listFunction
Model Name
Wall-mountedtype
H/P 60 HzFTY-GA
Capacity class
17,100 20,5001.42 1.72
5.0 6.04,300
BtuRT
kWkcal 5,160
FT-GA C/O 50 Hz
FT-GA C/O 60 Hz
FT-D C/O 60 Hz
Wall-mounted typeFT50/60GA FTY50/60GA
Power-airflow dual flaps
Comfortableairflow
Comfortcontroloperation
Wide-angle louvers
Vertical auto-swing
Horizontal auto-swing
Auto fan speed
W I D EA N G L E
A U T O
Lifestyleconvenience
Healthy &clean
Timer
Worry free
Power airflow flap
Air-purifying filter with photocatalytic deodorizing function
Program dry function
Automatic operation
New powerful operation
Indoor unit On/Off switch
Air-purifying filter
Mold-proof air filter
Washable grille
Filter cleaning indicator
24-hour On/Off timer
Night set mode
Auto-restart after power failure
Self-diagnosis digital display
Anticorrosion treatment of outdoor heat exchanger fin
N E WN E W
S E L F
C L E A N
2 4
Wipe-Clean flat panel
5 6
Wall-mounted type5.0·6.0 kW
Air-Purifying Filter with Photocatalytic Deodorizing Function isable to remove both bacteria and viruses, in addition toeliminating mold and odors. It can be used for approximately3 years with appropriate maintenance.
High Energy SavingsDaikin air conditioners’ advanced technology allows themto achieve significant energy savings with a COP of 2.55even during periods of extended use.
Compact and Stylish Design
The compact and stylish design of Daikin unitsharmonizes with any interior decor. The innovativeflat panel of the new D series enhances this effectand also ensures optimum operation.
SPLIT Type Air Conditioners
FT-D Series
Wall-mounted type
Healthy and Clean
Unique features such as our Vertical auto-swing and Horizontal auto-swingwill keep your home wrapped in a cloud of air-conditioned comfort.
Compact and quietThe rounded contours of the compact, lightweight indoor unit allow it toharmonize smoothly with your interior decor, and an improved fan designmakes operating noise hardly noticeable.
Energy-savingUsing your air conditioner for extended periods of time is now a completelyaffordable luxury thanks to Daikin’s advanced energy-saving technology.
Comfortable
FT(Y)-GA Series
FT60DVMKModel
Indoor unit
23,500/19,1001.96/1.59
Btu/hRT
5,900/4,800kcal/h6.9/5.6kW2.71/3.10kW
19.4 to 542.55
°CDB
Power comsumption *1 (1)/(2)
Operation range (Outdoor unit)COP *1 (1)
Cooling capacity*1 (1)/(2)
R60DVLKOutdoor unit1 phase, 220 V, 60 HzPower Supply
Cooling Only (60 Hz)
Outdoor UnitIndoor Unit
5.0·6.0 kW
FT(Y)50/60GA R50G R60G
RY50G RY60G
FT50GAVEA FT60GAVEAModel
Indoor unit
18,200/18,1001.52/1.51
22,000/21,8001.83/1.82
5.34/5.304,590/4,560
6.44/6.405,540/5,500
2.01/2.00-2.19/2.18 2.42/2.41-2.51/2.502.65-2.43
19.4 to 542.66-2.56
R50GV1K R60GV1KOutdoor unit1 phase, 220-240 V, 50 Hz
Cooling Only (50 Hz)
Wirelessremote controller
ModelIndoor unitOutdoor unit
Power Supply
Cooling Only (60 Hz) Heat Pump (60 Hz)
Outdoor UnitIndoor Unit
Heating Cooling
Brand-New Sleek Flat Panel Design
FT50/60GA
Wirelessremote controller
Affordable Comfort You deserve
FT60DR60D
Notes : •*1:Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB. Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB. Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284 Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
The flap descends to blowwarm air directly downto the floor to quickly warmthe whole room.
The flap flattens out so thatcool air slides off to reachthe farthest corners of theroom.
Btu/hRT
kcal/hkWkW
°CDB
Power comsumption (220-240 V) *1 (1)/(2)
Operation range(Outdoor unit)COP (220-240 V) *1 (2)
Cooling capacity*1 (1)/(2)
Power Supply
Operation range(Outdoor unit)
kWkWPower comsumption
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
CoolingHeating
COP
Btu/hkcal/hkW
RTCooling capacity*1 (2)/(3)
Btu/hkcal/hkW
RTHeating capacity*2(1)/(2)
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB. Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB. Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB. Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2:Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB. Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB. Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Cooling *1 (2)Heating *2 (2)
5.8/5.0 6.5/5.6
19,800/17,1004,990/4,300
22,200/19,1005,590/4,800
1.65/1.42 1.85/1.59
6.3/6.0 7.19/7.10
21,500/20,5005,420/5,200
24,500/24,2006,180/6,100
1.79/1.71 2.04/2.02
2.903.37
1.87/1.852.492.95
2.44/2.46
FT50GAVAL FT60GAVALR50GVAL R60GVAL
1 phase, 220 V, 60 Hz
FTY50GAVAL FTY60GAVALRY50GVAL RY60GVAL
1 phase, 220 V, 60 Hz
—19.4 to 54
-10 to 1519.4 to 54
5.6/4.5 6.8/5.6
19,100/15,4004,800/3,900
23,200/19,1005,850/4,800
1.59/1.28 1.93/1.59
— —
——
——
— —
2.57—
—2.54—
—2.18/2.50 2.68/3.06 2.00/2.30 2.61/2.97
Wipe-CleanFlat Panel
Note: Availability of the products shown in this catalog varies by country.
7 8
Stores often feature the latest in designed decor. This refined beauty attractspeople.Meanwhile, offices have a functional beauty. This encourages those within towork hard and apply intelligence and passion to their tasks.In either situation, a certain elegance should fill the space because thinkingminds require high quality air conditioning. SkyAir by Daikin ensures acomfortable indoor environment. All over the world, stores, offices, and homesprefer the low operating noise, attractive design, complete comfort control,and other benefits brought by SkyAir.
Indoor units.....................................10Specifications..................................11Simultaneous operation system......16
Line UpAir Cooled Split Type Air Conditioners
Type Model Name
Ceilingmountedcassette type
FHC
FH(Y)C
FHYC
FH
FHY
H/P
C/O
H/P
C/O
2 2.5 3 4 5 6 8 10
19100 23200 27600 38900 48800 53900 81900 996001.6
5.6 6.8 8.1 11.4 14.3 15.8 24.0 29.2kWHP
BtuRT 1.9 2.3 3.2 4.1 4.5 6.8 8.3
15 20
163400 19930047.9 58.4
13.6 16.6
Simultaneous operation system
60 Hz
50 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Operation system
Twin
Applicable Models
6 8 1015.8 22.2 26.653900 75700 90800
HPkWBtuRT 4.5 6.3 7.6
Ceilingsuspended type
60 Hz
50 Hz
H/P
C/OCeilingmountedbuilt-in type
50 Hz
H/P
C/OWall mountedtype
60 Hz
50 Hz
H/P
C/OFloor standingtype
60 Hz
50 Hz
H/P
C/ODuctconnectionlow staticpressuretype
Ductconnectionmiddle staticpressuretype
Ductconnectionhigh staticpressuretype
FDBG
FDB
FDYB
FV
FVY
FA
FAY
FHB
FHYB
60 Hz
50 Hz
H/P
C/O60 Hz
50 Hz
60 Hz
50 Hz
H/P
C/O60 Hz
50 Hz
60 Hz
50 Hz
H/P
C/O60 Hz
50 Hz
60 Hz
50 Hz
C/O
Ceiling mountedcassette cornertype FHK 50 Hz
Triple
DoubleTwin
Indoor unit Indoor unit
Outdoorunit
Outdoorunit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
H/P
C/O
FDMG
FD(Y)M
50 Hz
50 Hz
50 Hz
60 Hz
60 Hz
H/P
C/OFD
FDY
60 Hz
50 Hz
60 Hz
50 Hz
*1
*2
*1
*2
Notes: •Specifications for RT, Btu and kW are based on the following conditions; Power supply: 60 Hz; Cooling: Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•The values given for 2 HP to 6 HP are for the FHY(C) model and 8 HP to 20 HP are for the FD model. The values given for simultaneous operation system are for the FHYC model.•*1:FDYB and FDYM model operate for 20·25 (kW) class. •*2:FDYB and FDYM model operate for 20 (kW) class.
Packagedairconditioners
Capacity
Capacity
Outdoorunit
9 10
Air Cooled Split Type Air Conditioners
Wall Mounted TypeCeiling Suspended Type
Floor Standing TypeCeiling Mounted Cassette Corner Type
Ceiling Mounted Cassette Type Ceiling Mounted Built-in Type
Indoor unitsIndoor units
R emote C ontrollerOutdoor Unit
LCD WiredRemote Controller
LCD WirelessRemote Controller
FH(Y)C
On-ceiling installation leaves floorspace unhindered. Extremelyquiet operation enhances thestore's customer service.
FH(Y)
Uni-directional discharge outlet isperfect for corner installation.A thin, 21.5 cm main bodyenables installation even in asmall ceiling overhead space.
FHK
FH(Y)B
FA(Y)
FV(Y)
Floor standing type units are easy toinstall and maintain; their slimness issuitable for installation in high-ceilingstores and offices.
Wall mounted type units featurethe lowest sound levels in theindustry and greatly upgradedcomfort, thanks to the high fanspeed mode.
With the use of simple ducts,discharge outlets can be locatedin a multitude of ways. Top prioritygiven to interior decor, built-intype units realize ideal air currentdistribution.
Quiet,decor-blending form and easyinstallation in new or old buildings.Multiple unit installations maintain aphysical uniformity that isaesthetically pleasing and make iteasier to plan ceiling lightingsystems and to design interiors.
Packaged Air Conditioners Duct Connection Series
FDB(G)FDYB FD(Y)FD(Y)M
FDMG
For details, please refer to P33-P40.
Low static pressure High static pressureMiddle static pressure
11 12
Air Cooled Split Type Air Conditioners—Specifications
C ooling Only (50 Hz)
Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V,50 Hz/Y1: 3 phase, 380-415 V,50 Hz
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)
Model
Ceiling suspended type
Ceiling mounted cassette type
Power supply
71
7.8/7.7
FH71BVE100
10.6/10.5
FH100BVE125
13.0/12.8
FH125BVE
R125FUY1R71FUV1R71FUY1
R100FUV1R100FUY1
kW
Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
50
5.19/5.1
FH50BVE
R50GV1
60
6.6/6.5
2.2/2.2 3.0/3.0 3.7/3.6RT 1.5/1.4 1.9/1.8
FH60BVE
R60GV1K
26,600/26,3006,700/6,600
36,200/35,8009,100/9,000
44,400/43,70011,200/11,000
Btu/hkcal/h
17,700/17,4004,460/4,400
22,500/22,2005,690/5,600
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
Model
Indoor unitOutdoor unit
Btu/hkcal/h
Cooling capacity*1 (1)/(2)
45
17,700/17,400
FHB45FV1R50GV1
4,500/4,400
60
22,500/22,200
kW 5.19/5.1 6.6/6.5
RT 1.5/1.4 1.9/1.8
FHB60FV1R60GV1K
5,700/5,600
2.23/2.202.33/2.32
2.37/2.362.78/2.76
Ceiling mounted built-in type
Power supply 1 phase, 220-240 V, 50 Hz
Model
45
5.19/5.1
FHK45FV1R50GV1
60
6.6/6.5
FHK60FV1R60GV1K
2.31/2.282.25/2.24
19.4 to 54
2.39/2.372.76/2.74
19.4 to 54
kW
1.5/1.4 1.9/1.8RT
Indoor unitOutdoor unit
17,700/17,4004,460/4,400
22,500/22,2005,690/5,600
Btu/hkcal/h
Ceiling mounted cassette corner type
Power supply 1 phase, 220-240 V, 50 Hz
Model
kW
°CDB
kW
°CDB
kW
°CDB
kWkW 5.34/5.3 6.44/6.4 7.8/7.7 10.6/10.5 13.0/12.8
kWRT 1.5/1.5 1.8/1.8 2.2/2.2 3.0/3.0 3.7/3.6Btu/hkcal/hBtu/hkcal/h
18,200/18,1004,590/4,560
22,000/21,8005,540/5,500
26,600/26,3006,700/6,600
36,200/35,8009,100/9,000
44,400/43,70011,200/11,000
2.64/2.642.02/2.01
2.63/2.622.45/2.44
3.00/2.982.60/2.58
2.87/2.883.69/3.65
2.96/2.944.39/4.35
19.4 to 54 21 to 52
19.4 to 54 21 to 52
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)2.40/2.372.16/2.15
2.36/2.342.8/2.78 2.58/2.56
3.02/3.01 2.80/2.803.79/3.75
2.78/2.764.67/4.63
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)/(2)
Operation range (Outdoor temp.)
50FHC50KVE
R50GV1
60FHC60KVE
R60GV1K R125FUY1
71FHC71KVER71FUV1R71FUY1
100FHC100KVER100FUV1R100FUY1
125FHC125KVE
Model
Model
R71FUV1R71FUY1
R100FUV1R100FUY1
Indoor unit
Outdoor unit
71FA71FVEK
100
RT 2.2/2.2 3.0/3.0
FA100FVEK
3.06/3.042.55/2.53
2.94/2.953.6/3.56
Wall mounted type
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
R125FUY1R71FUV1R71FUY1
R100FUV1R100FUY1
Floor standing type
Indoor unit
Outdoor unit
71FV71LAVE
100FV100LAVE
125
kW 7.80/7.7 10.6/10.5 13.0/12.8
RT 2.2/2.2 3.0/3.0 3.7/3.6
FV125LAVE
Btu/hkcal/h
26,600/26,3006,700/6,600
36,200/35,8009,100/9,000
44,400/43,70011,200/11,000
2.92/2.912.67/2.65
2.82/2.813.76/3.74
2.9/2.884.49/4.45
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
Notes : •*1:Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)
Notes : •*1:Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Notes : •*1:Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)
C ooling Only (60 Hz)
ModelIndoor unit
Outdoor unit
Ceiling mounted cassette type50
FHC50KVE60
FHC60KVE71
FHC71KVE100
FHC100KVE125
FHC125KVE
R50GVAL R60GVAL R125FUTAL
125FHYC125KVE
R125KUYALK
140FHYC140KVER140KUTALKR140KUYALK
R71FUVAL R100FUVAL
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
5.6/4.5 6.8/5.6 8.1/6.7 11.4/9.0 14.3/12.5kW 14.3/12.5 15.8/14.0
1.6/1.3 1.9/1.6 2.3/1.9 3.2/2.6 4.1/3.6RT 4.1/3.6 4.5/4.019,100/15,4004,800/3,900
23,200/19,1005,800/4,800
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,700Btu/hkcal/h 12,300/10,800
48,800/42,70012,300/10,800
53,900/47,80013,600/12,000
2.532.21/2.5
2.492.73/3.14
2.433.34/4.2
2.514.54/5.80
2.356.08/7.00
2.605.50/6.80
2.775.70/
71FH71BVE
100FH100BVE
125FH125BVE
R50GVAL R60GVAL R125FUTALR71FUVAL R100FUVAL
Ceiling suspended type
Indoor unitOutdoor unit
50FH50BVE
60FH60BVE
8.1/6.7 11.4/9.0 14.3/12.55.25/4.5 6.5/5.6kW
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
17,900/15,4004,500/3,900
22,200/19,1005,600/4,800
Btu/hkcal/h
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
2.353.44/4.2
2.444.67/5.80
2.296.25/7.00
2.282.3/2.5
2.292.84/3.2
Cooling capacity*1 (1)/(2)
Cooling capacity*1 (1)/(2)
Model
(For specifications of duct connection series, please refer to P35-P40.)
2.3/1.9 3.2/2.6 4.1/3.61.5/1.3 1.8/1.6RT
kW 10.6/10.57.80/7.7
Btu/hkcal/h
36,200/35,8009,100/9,000
26,600/26,3006,700/6,600
Cooling capacity*1 (1)/(2)
Cooling capacity*1 (1)/(2)
Cooling capacity*1 (1)/(2)
21 to 52
21 to 52
kW
°CDB
kW
°CDB
19.4 to 54 21 to 54
19.4 to 54 21 to 54
kW
°CDB
kW
°CDB
kW
°CDB
KUTALK.....6.80, KUYALK.....7.10
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
13 14
Air Cooled Split Type Air Conditioners—Specifications
Indoor unitOutdoor unit
71FA71FVEK
100
kW 8.1/6.7 11.4/9.5
RT
kW
°CDB
2.3/1.9 3.2/2.7
FA100FVEK
Btu/hkcal/h
27,600/22,9007,000/5,800
38,900/32,4009,800/8,200
2.483.27/4.1
21 to 542.59
4.41/5.70
Wall mounted type
R71FUVAL R100FUVALPower supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz
Floor standing type
Indoor unitOutdoor unit
71FV71LAVE
100FV100LAVE
125FV125LAVER125FUTALR71FUVAL R100FUVAL
8.1/6.7 11.4/9.0 14.3/12.5kW
27,600/22,900 38,900/30,700 48,800/42,7007,000/5,800 9,800/7,700 12,300/10,800
Btu/hkcal/h
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz2.3/1.9 3.2/2.6 4.1/3.6RT
kW
°CDB
3.40/4.3 4.62/5.90 6.20/7.102.38 2.47 2.31
21 to 54
Cooling capacity*1 (1)/(2)
Cooling capacity*1 (1)/(2)
Model
Model
Notes : •*1:Nominal cooling capacities are based on the following conditions:(1) Return air temperature:27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature:29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
ModelIndoor unit
Outdoor unit
Ceiling mounted cassette type50
FHYC50KVE60
FHYC60KVE71
FHYC71KVE100
FHYC100KVE
RY50GVAL RY60GVAL RY125FUTAL RY140KUTALKRY140KUYALK
RY71FUVAL RY100FUVAL
125FHYC125KVE
140FHYC140KVE
Heating capacity*2 (1)/(2)
RTCooling capacity*1 (1)/(2)
Power supply
Power comsumption
COP
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
5.8/5.0 6.5/5.6 8.1/6.7 11.4/9.0 14.3/12.5kW 15.8/14.0
1.6/1.4 1.8/1.6 2.3/1.9 3.2/2.6 4.1/3.6 4.5/4.019,800/17,1004,990/4,300
22,200/19,1005,590/4,800
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
Btu/hkcal/h
53,900/47,80013,500/12,000
6.3/6.0 7.19/7.1 9.0/8.5 12.8/11.8 16.2/15.0kW 18.1/17.0
1.8/1.7 2.0/2.0 2.6/2.4 3.6/3.4 4.6/4.3RT
Power comsumption
COP
Power comsumption
COP
5.1/4.821,500/20,5005,420/5,200
24,500/24,2006,180/6,100
30,700/29,0007,700/7,300
43,700/40,30011,000/10,100
55,300/51,20013,900/12,900
Btu/hkcal/h
61,800/58,00015,600/14,600
2.03/2.34 2.66/3.06
3.372.86
2.922.44
3.72/4.30 4.69/5.90 5.88/6.60
2.592.18
2.902.43
3.012.43
5.70/7.30
3.232.77
1.87/1.85 7.19/7.1 9.0/8.5 12.8/11.8 16.2/15.0 18.1/17.0
71FHY71BVE
100FHY100BVE
125FHY125BVE
RY50GVAL RY60GVAL RY125FUTALRY71FUVAL RY100FUVAL
Ceiling suspended type
Indoor unitOutdoor unit
50FHY50BVE
60FHY60BVE
Heating capacity*2 (1)/(2)
Cooling capacity*1 (1)/(2)
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz
kW 8.1/6.7 11.4/9.0 14.3/12.55.8/5.0 6.5/5.6
RT 2.3/1.9 3.2/2.6 4.1/3.61.6/1.4 1.8/1.6Btu/hkcal/h
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
19,800/17,1004,990/4,300
22,200/19,1005,590/4,800
kW 9.0/8.5 12.8/11.8 16.2/15.06.3/6.0 7.19/7.1
RT 2.6/2.4 3.6/3.4 4.6/4.31.8/1.7 2.0/2.0Btu/hkcal/h
30,700/29,0007,700/7,300
43,700/40,30011,000/10,100
55,300/51,20013,900/12,900
21,500/20,5005,420/5,200
24,500/24,2006,180/6,100
3.82/4.30 4.82/5.90 6.05/6.60
2.502.12
2.802.37
2.902.36
2.14/2.34 2.77/3.06
3.182.71
2.802.35
3.60/3.80 4.57/5.00 5.58/5.421.98/1.86 2.57/2.44
71FHYB71FVAL
100FHYB100FVAL
125FHYB125FVALIndoor unit
Outdoor unit
Ceiling mounted built-in type
RY125FUTALRY71FUVAL RY100FUVAL
9.0/8.5 12.8/11.8 16.2/15.0kW
2.6/2.4 3.6/3.4 4.6/4.3
3.82/4.30 4.76/5.90 6.05/6.70
2.522.12
2.852.39
2.912.36
3.57/3.80 4.49/5.00 5.56/5.60
RT
Heating capacity*2 (1)/(2)
30,700/29,0007,700/7,300
43,700/40,30011,000/10,100
55,300/51,20013,900/12,900
Btu/hkcal/h
8.1/6.7 11.4/9.0 14.3/12.5kW
2.3/1.9 3.2/2.6 4.1/3.6RT
Cooling capacity*1 (1)/(2)
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
Btu/hkcal/h
Power supply VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Model
Model
Heat Pump (60 Hz)
RT
kWkWHeating *2 (1)/(2)
Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2)
Operation range(Outdoor temp.)
19.4 to 54-10 to 15
-5 to 54-10 to 15.5 -10 to 15
°CDB°CWBHeating
Cooling
Operation range(Outdoor temp.)
°CDB°CWBHeating
Cooling
Operation range(Outdoor temp.)
°CDB°CWBHeating
Cooling
kWHeating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2) kW
kWHeating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2) kW
19.4 to 54-10 to 15
-5 to 54-10 to 15.5
-5 to 54-10 to 15.5
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
(For specifications of duct connection series, please refer to P35-P40.)
15 16
Simultaneous Operation System—Twin & Triple & Double Twin Multi Application Operation
Indoor unitOutdoor unit
71FAY71FVE
100FAY100FVE
Wall mounted type
RY71FUVAL RY100FUVAL
9.0/8.5 12.8/11.8kW3.67/4.20 4.61/5.80
2.622.21
2.942.47
3.44/3.70 4.36/4.90
RTHeating capacity*2 (1)/(2)
30,700/29,0007,700/7,300
43,700/40,30011,000/10,100
Btu/hkcal/h
8.1/6.7 11.4/9.0kW
RTCooling capacity*1 (1)/(2)
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
Btu/hkcal/h
Power supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz
Floor standing type71
FVY71LAVE100
FVY100LAVE125
FVY125LAVERY125FUTALRY71FUVAL RY100FUVAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz
Indoor unitOutdoor unit
Heating capacity*2 (1)/(2)
RT
8.1/6.7 11.4/9.0 14.3/12.5kW
Cooling capacity*1 (1)/(2)
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
Btu/hkcal/h
9.0/8.5 12.8/11.8 16.2/15.0kW
RT30,700/29,000 43,700/40,300 55,300/51,2007,700/7,300 11,000/10,100 13,900/12,900
Btu/hkcal/h
Power supply
Model
Model
Branch piping kit
Branch piping kit
Branch piping kit
•Branch piping kit is optionally available.Refrigerant piping uses terminal branching to facilitate installation
•An optional remote controller is required for one of the combination indoor units.•Optional remote controllers are a single item, and cannot operate the air conditioning individually. Indoor units should not therefore be installed in separate rooms.•If operating with optional wireless remote controllers, set one as the main unit and install a light receptor.
Precautions when selecting optional remote controller
Branch piping kit
Branch piping kit
*Typical combination
Twin Multi Application
Triple Multi Application Double Twin Multi Application
Note: This type of system does not allow individual control or independent operation ofindoor units. It is not the best choice for large rooms with partitions.
In a single-floor restaurant, for example, positioning 4 unitsat strategic locations achieves comfortable air flow thatreaches every inch of the room.
Indoor units include the super cassette type, duct connection low and middle static pressure type and ceiling suspended type.(Indoor units are limited to same capacity and type combination.)
In large interior spaces a single indoor unit may not be ableto provide uniform comfort. Installation of 2 to 4 units,distributed to consider sun light and human gatheringpatterns, can provide an effective solution.
Simultaneously operates 2 to 4 indoor units usinga single outdoor unit.
Installing multiple units iseconomical and ensures comfortLower cost of installation than for individual pair typeLess space needed for outdoor unitsEnhanced comfort from distributed indoor units
Air Cooled Split Type Air Conditioners—Specifications
3.78/4.40 4.77/6.00 6.00/6.70
2.542.14
2.832.39
2.932.38
3.55/3.90 4.52/5.15 5.53/5.60
Power comsumption
COP
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Operation range(Outdoor temp.)
°CDB°CWBHeating
Cooling
kWHeating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2) kW
-5 to 54-10 to 15.5
Power comsumption
COP
Operation range(Outdoor temp.)
°CDB°CWBHeating
Cooling
kWHeating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2) kW
-5 to 54-10 to 15.5
2.3/1.9 3.2/2.6
2.6/2.4 3.6/3.4
2.6/2.4 3.6/3.4 4.6/4.3
2.3/1.9 3.2/2.6 4.1/3.6
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
(For specifications of duct connection series, please refer to P35-P40.)
17 18
Simultaneous Operation System—Twin & Triple & Double Twin Multi Application Operation
Model Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Ceiling mounted cassette type
Power supply
200 250FHYC100KVEX2
R200KUY1 R250KUY1
FHYC125KVEX2FHYC71KVEX3
FHYC60KVEX4FHYC50KVEX4
kW 27.1/26.622.5/22.2
RTBtu/hkcal/h
92,500/90,80023,300/22,900
76,800/75,70019,400/19,100
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/Y1: 3 phase, 380-415 V, 50 Hz
Model Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Ceiling mounted cassette typeHeat Pump (50 Hz)
Power supply
200 250
RY200KUY1
FHYC100KVEX2
RY250KUY1
kW 27.1/26.622.5/22.2
RT 7.7/7.66.4/6.3VE: 1 phase, 220-240 V/220 V, 50/60 Hz/Y1: 3 phase, 380-415 V, 50 Hz
Ceiling suspended type
Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Power supplyR200KUY1
200FHY100BVEX2
R250KUY1
250
FHY125BVEX2FHY71BVEX3
FHY60BVEX4FHY50BVEX4
kW 27.1/26.622.5/22.2
RT 7.7/7.66.4/6.3Btu/hkcal/h
92,500/90,80023,300/22,900
76,800/75,70019,400/19,100
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/Y1: 3 phase, 380-415 V, 50 Hz
Model
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)
FHYC71KVEX3FHYC50KVEX4
Btu/hkcal/h 23,300/22,900
76,800/75,70019,400/19,100
92,500/90,800
Heating capacity*2 (1)
kW 28.422.7
RT 8.16.4Btu/hkcal/h 24,400
77,50019,500
96,900
Model Indoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Ceiling suspended type
Power supply
200 250
RY200KUY1
FHY100BVEX2
RY250KUY1
kW
RT
RT
FHY71BVEX3FHY50BVEX4
Btu/hkcal/h
Heating capacity*2 (1)
kW
Btu/hkcal/h
FHYC125KVEX2
FHYC60KVEX4
FHY125BVEX2
FHY60BVEX4
C ooling Only (50 Hz)
COP *1 (1)/(2)
COP *1 (1)/(2)
kW
°CDB -5 to 52
Power comsumption *1 (1)/(2)
Operation range (Outdoor temp.)
kW
°CDB
7.7/7.6 9.7/9.7
7.7/7.6 9.7/9.7
2.92/2.92 2.79/2.74
7.7/7.66.4/6.3
2.92/2.92 2.79/2.74
-5 to 52
Power comsumption *1 (1)/(2)
Operation range (Outdoor temp.)
7.7/7.6 9.7/9.7
3.492.92/2.92
3.092.79/2.74
6.5 9.2Power comsumption
COP
kWHeating *2 (1)Cooling *1 (1)/(2)Heating *2 (1)
Cooling *1 (1)/(2) kW
Power comsumption
COP
kWHeating *2 (1)Cooling *1 (1)/(2)
Heating *2 (1)
Cooling *1 (1)/(2) kW
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
27.1/26.622.5/22.2
7.7/7.66.4/6.3
23,300/22,90076,800/75,70019,400/19,100
92,500/90,800
28.422.7
8.16.4
24,40077,50019,500
96,900
7.7/7.6 9.7/9.7
3.492.92/2.92
3.092.79/2.74
6.5 9.2
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/Y1: 3 phase, 380-415 V, 50 Hz
(For specifications of duct connection series, please refer to P35-P40.)
15.8/14.0 26.6/24.122.2/20.0
19 20
Simultaneous Operation System—Twin & Triple & Double Twin Multi Application Operation
Indoor unit
Outdoor unit
Ceiling mounted cassette type
Cooling capacity*1 (1)/(2)
Power supply
R140KUTALK
140
FHYC71KVEX2
200 250
R200KUTAL
FHYC100KVEX2
R250KUTALR200KUYAL R250KUYAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
C ooling Only (60 Hz)
kW 15.8/14.0 22.2/20.0 26.6/24.1
Btu/hkcal/h
53,900/47,80013,500/12,000
75,700/68,20019,100/17,200
90,800/82,20022,900/20,700
RT
°CDB
kW
°CDB
kW
4.5/4.0 6.3/5.7 7.6/6.8
2.775.70/6.80
21 to 542.71
8.20/10.02.61
10.20/12.5
-5 to 54
4.5/4.0 6.3/5.7 7.6/6.8
2.775.70/6.90
2.718.20/10.0
2.6110.20/12.5
FHYC50KVEX3FHYC71KVEX3FHYC50KVEX4 FHYC60KVEX4
140
FHY71BVEX2
FHY50BVEX3
200FHY100BVEX2FHY71BVEX3FHY50BVEX4
250
FHY125BVEX2
FHY60BVEX4
R140KUTALKR200KUTAL R250KUTALR200KUYAL R250KUYAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
Ceiling suspended type
ModelIndoor unit
Outdoor unit
Cooling capacity*1 (1)/(2)
Power supply
15.8/14.0kW 22.2/20.0 26.6/24.1
RT 6.3/5.753,900/47,80013,500/12,000
Btu/hkcal/h
75,700/68,20019,100/17,200
90,800/82,20022,900/20,700
140FHYC71KVEX2
FHYC50KVEX3
Ceiling mounted cassette type200 250
FHYC100KVEX2FHYC50KVEX4FHYC71KVEX3
FHYC125KVEX2
FHYC60KVEX4
RY140KUTALK RY200KUTAL RY250KUTALRY200KUYAL RY250KUYAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
Indoor unit
Outdoor unit
Heating capacity*2 (1)/(2)
15.8/14.0 26.6/24.122.2/20.0kW
kWkW
4.5/4.0 7.6/6.86.3/5.7
4.5/4.0 7.6/6.86.3/5.7
RTCooling capacity*1 (1)/(2)
18.1/17.0 28.4/28.022.7/22.4kW
5.1/4.8 8.1/8.06.4/6.4RT61,900/58,00015,600/14,600
97,000/95,60024,400/24,100
77,500/76,50019,500/19,300
Btu/hkcal/h
Power supply
Heat Pump (60 Hz)
53,900/47,80013,500/12,000
90,800/82,30022,900/20,700
75,800/68,300Btu/hkcal/h 19,100/17,200
5.7/6.9 10.2/12.5
3.232.77
-5 to 542.932.61
0 to 543.242.71
5.6/5.7 9.7/9.97.0/7.18.2/10.0
RY140KUTALK
140
FHY71BVEX2
FHY50BVEX3RY200KUTAL
200FHY100BVEX2FHY71BVEX3FHY50BVEX4
RY250KUTALRY200KUYAL RY250KUYAL
250
FHY125BVEX2
FHY60BVEX4
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
Ceiling suspended type
Indoor unit
Outdoor unit
Heating capacity*2 (1)/(2)
kW
Cooling capacity*1 (1)/(2)
Power supplyRTBtu/hkcal/h
53,900/47,80013,500/12,000
90,800/82,20022,900/20,700
75,700/68,20019,100/17,200
kW 18.1/17.0 28.4/28.022.7/22.4
RT 5.1/4.8 8.1/8.06.4/6.4Btu/hkcal/h
61,800/58,00015,600/14,600
96,900/95,50024,400/24,100
77,500/76,40019,500/19,300
ModelModel
Model
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Notes : •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
FHYC125KVEX2
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)COP *1 (1)
Operation range (Outdoor temp.)
Power comsumption
Operation range(Outdoor temp.)
COP
Heating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2)
HeatingCooling °CDB
°CWB
kWkW 6.0/7.2 10.2/12.5
3.072.63
2.932.61
3.242.71
5.9/6.0 9.7/9.97.0/7.18.2/10.0Power comsumption
Operation range(Outdoor temp.)
COP
Heating *2 (1)/(2)Cooling *1 (1)
Heating *2 (1)
Cooling *1 (1)/(2)
HeatingCooling °CDB
°CWB
-10 to 15
-5 to 54 0 to 54-10 to 15
-5 to 54
5.7/6.92.77
8.2/10.02.71
10.2/12.52.61
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
(For specifications of duct connection series, please refer to P35-P40.)
Note: Availability of the products shown in this catalogue varies by country.
21 22
Rising energy and general building services running costs have led end users toexpect a truly complete and acceptable air conditioning system. It must be energyefficient, economic to run, easy to install, flexible, reliable and user friendly.Featuring inverter technology and individual control, the VRV systemrevolutionised building air conditioning the world over by meeting all theserequirements, and has been installed in various buildings throughout the world forthe last 20 years.
Line Up
Indoor Units.................................24VRV II Series...............................25
HRV (Heat Reclaim Ventilation)..28
Control Systems..........................29
VRV K Series...............................27
HRV(Heat Reclaim Ventilation)
VAM150 VAM250 VAM350 VAM500 VAM650 VAM800 VAM1000 VAM1500 VAM2000
Air flow rate (m3/h)
VRV K series
Capacity Range (HP)8
The Intelligent Air Conditioning System
Air Treatment Equipment
Note: • Specifications for RT, Btu and kW are based on the following conditions;Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
R410ASeries
Heat pumpType
67.2 72.850.4 56.0 78.4 84.022.4 28.0 44.824 2618 20 28 308 10 16
19.1 20.714.3 15.9 22.3 23.96.4 8.0 12.7229300 248400172000 191100 267500 28660076400
kWHP
RTBtu 95500 152900
Heat pumpType
VRV II Series
50 Hz
60 Hz
Capacity
2324
FXCQ-MVE FXSQ-MVE
FXHQ-MVE FXNQ-MVEFXLQ-MVE
FXKQ-MVEFXFQ-MVE
FXMQ-MVE FXAQ-MVE
Thin, lightweight, and easy toinstall in narrow ceiling space
New super cassette typeis compact, quiet andeasy to install
Slim design for flexibleinstallation
Highly flexible for variousapplication
High static pressure allowsflexible duct design
Slim body with quieterand wider air flow
Sophisticated design andcompact casing harmonized inany interior décor
Perfect unit for perimeterzone air conditioning
Perfect unit to be concealed inthe skirting-wall of perimeter
Ceiling Mounted Cassette<Multi flow> Type
Ceiling Mounted Cassette<Double flow> Type
Ceiling MountedCassette Corner Type
FXDQ-NVE(T)*
Slim design, quietness andstatic pressure switching
Slim Ceiling MountedDuct Type
Ceiling MountedBuilt-in Type
Ceiling Mounted Duct Type Ceiling Suspended Type Wall Mounted Type Floor Standing Type ConcealedFloor Standing Type
Indoor unitsIndoor unitsThe series comprises a wide range of indoor units designedto meet virtually any installation site requirement.
Indoor Units
Ceiling Mounted Cassette (Double flow)Ceiling Mounted Cassette (Multi flow) Super Cassette
FXCQ-MVE
Type Modelname
FXFQ-MVE
New Ceiling Suspended Cassette FXUQ-MV1
Type Modelname
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 3 HP 4 HP 5 HP
7500 9600 12300 15400 19100 27300 38200 478000.6 ton
20 25 31.25 40 50 71 100 125IndexHP
BtuRT 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.3 ton 3.2 ton 4.0 ton
ConnectableOutdoorUnit
Cooling Only & Heat Pump
1 phase, 220-240 V/220 V, 50/60 HzPower supplyIndoor unit 20Model
Cooling capacity (1)/(2)
25
2,000/1,900
2,200
32
2,500/2,400
2,800
40
3,200/3,100
3,400
50
4,000/3,900
4,300
63
5,000/4,800
5,400
6,300/6,100
6,900
80
8,000/7,700
8,600
71
7,100/6,900
7,700
100
10,000/9,600
10,800
125
12,500/12,000
13,800
200
19,800/19,300
21,500
250
kW 2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.08.3/8.0 11.6/11.2 14.5/14.0 23.0/22.4 28.8/28.0
RT 0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.62.4/2.3 3.3/3.2 4.1/4.0 6.5/6.4 8.2/8.0Btu/h 7,800/7,500 9,900/9,600 12,600/12,300 16,000/15,400 19,800/19,100 24,900/24,200 31,700/30,70028,300/27,300 39,600/38,200 49,500/47,800 78,500/76.400 98,300/95,500
24,800/24,100
27,100Heating capacity
2.5 3.2 4.0 5.0 6.3 8.0 10.09.0 12.5 16.0 25.0 31.5kW
0.7 0.9 1.1 1.4 1.8 2.3 2.82.6 3.6 4.5 7.1 8.9RT8,500 10,900 13,600 17,000 21,500 27,300 34,10030,700 42,700 54,600 85,300 107,500Btu/h
kcal/h
kcal/h
Notes: • Cooling capacity is based on indoor temp.(1)27°CDB, 19.5°CWB, and outdoor temp. 35°CDB.(2)27°CDB, 19.0°CWB, and outdoor temp. 35°CDB.
• Heating : Indoor temp. of 20°CDB, of 7°CDB, 6°CWB.• Equivalent piping length : 7.5 m.• Level difference : 0 m.
Ceiling Mounted Cassette Corner
Ceiling Mounted Built-in
Ceiling Suspended
Floor StandingConcealed Floor Standing
Ceiling Mounted DuctFXHQ-MVEFXAQ-MVE
FXSQ-MVE
FXKQ-MVE
FXLQ-MVEFXNQ-MVE
FXMQ-MVE
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 8 HP 10 HP
7500 9600 12300 15400 19100 24200 30700 38200 47800 76400 955000.6 ton
20 25 31.25 40 50 62.5 80 100 125 200 250IndexHP
BtuRT 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton 6.4 ton 8.0 ton
Slim Ceiling Mounted Duct FXDQ-NVE
Wall Mounted
Floor StandingFXAQ-MHV1FXLQ-MHV1
Wall Mounted
FXAQ-MHV1 FXLQ-MHV1
Wall Mounted Floor S tanding
FXUQ-MV1
New C eiling S uspendedC assette
*FXDQ-NVE: with a drain-up pump (750 mm lift) as a standard accessoryFXDQ-NVET: without a drain-up pump
FXDQ-NVET
Connection unit series (50 Hz only)
• Indoor units in the 63 class are not available for the above models.• Connection unit BEVQ-M is necessary for each indoor unit.
BEVQ-MVE
C onnec tion unit for indoor unit
H/P
H/P
H/P
H/P: Heat Pump Type
withdrain-up pumpwithoutdrain-up pump
Capacity
Capacity
Notes: • Specifications for RT and Btu are based on the following conditions;Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
Note: • Specifications for RT and Btu are based on the following conditions; Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
25
Line Up
Series
8 10 16 18 20 24 26 28 30
6.4 8.0 12.7 14.3 15.9 19.1 20.7 22.3 23.976400
HP22.4 28.0 44.8 50.4 56.0 67.2 72.8 78.4 84.0kW
RTBtu 95500 152900 172000 191100 229300 248400 267500 286600
Heat pump type RXYQ24MY1K(E)RXYQ26MY1K(E)RXYQ28MY1K(E)RXYQ30MY1K(E)
RXYQ16MY1K(E)RXYQ18MY1K(E)RXYQ20MY1K(E)
HEAT PUMP TYPE
16, 18, 20 HP
RXYQ8MY1K(E)RXYQ10MY1K(E)
8, 10 HP 24, 26, 28, 30 HP
(50 Hz) RXYQ24MYLK(E)RXYQ26MYLK(E)RXYQ28MYLK(E)RXYQ30MYLK(E)
RXYQ16MYLK(E)RXYQ18MYLK(E)RXYQ20MYLK(E)
16, 18, 20 HP
RXYQ8MYLK(E)RXYQ10MYLK(E)
8, 10 HP 24, 26, 28, 30 HP
(60 Hz)
HEAT PUMP TYPE
Note : 1. Optional models (-E type) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric component box, in addition to the fins ofthe heat exchanger. These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
(*2) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 46°CDB.(*3) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35°CDB.(*4) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 46°CDB.
•Heating : (*5) Indoor temp. of 20°CDB, and outdoor temp. 7°CDB/6°CWB.•Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Outdoor units (50Hz) Outdoor units (60Hz)
Heat Pump Type (50 Hz) Heat Pump Type (60 Hz)
26
Capacity
Note: • Specifications for RT, Btu and kW are based on the following conditions;Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
Line Up
Series
8 10 16 18 20 24 26 28 30
6.4 8.0 12.7 14.3 15.9 19.1 20.7 22.3 23.976400
HP22.4 28.0 44.8 50.4 56.0 67.2 72.8 78.4 84.0kW
RTBtu 95500 152900 172000 191100 229300 248400 267500 286600
Heat pump type
Capacity
Note: • Specifications for RT, Btu and kW are based on the following conditions;Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
Heating capacity(*5)
Cooling capacity(*1)/(*2)
Btu/hkcal/h
kW
Btu/hkcal/h
Power supply
25.021,50085,300
31.527,100107,500
50.043,000170,600
19,900/19,600
6.6/6.5
24,300/20,700
8.0/6.8
39,700/39,200
13.1/13.0
56.548,600192,800
44,100/40,300
14.6/13.3
63.054,200215,000
7.1 8.9 14.2 16.0 17.9
48,500/41,500
16.0/13.778,800/77,800 96,200/82,200 157,600/155,600 175,000/160,000 192,400/164,500
kW
RT
23.1/22.8 28.2/24.1 46.2/45.6
28.0/24.1 44.8/44.8
51.3/46.9
50.4/46.5
56.4/48.2
56.0/48.2
Power consumption Cooling (*3)/(*4) kWHeating (*5)
6.01/9.16 7.58/9.56 12.0/18.35.82 7.40 11.6
13.6/18.713.2
15.2/19.1Cooling (*1)/(*2) 6.31/9.41 7.60/9.58 12.6/18.8 13.9/19.0 15.2/19.2
14.8
Operation range CoolingHeating
°CDB°CWB
-5 to 50-20 to 16
Operation range CoolingHeating
°CDB°CWB
-5 to 50-20 to 16
COP (Cooling) (*3)/(*4)COP (Heating) (*5)
3.73/2.45 3.69/2.52 3.73/2.454.30 4.26 4.30
3.71/2.484.27
3.69/2.52COP (Cooling) (*1)/(*2) 3.66/2.42 3.71/2.52 3.66/2.42 3.69/2.47 3.71/2.52
4.26
3 phase, 380–415V, 50Hz
RXYQ8MY1K(E) RXYQ10MY1K(E) RXYQ16MY1K(E) RXYQ18MY1K(E) RXYQ20MY1K(E)MODEL
RT
Cooling capacity(*3)/(*4)
Btu/hkcal/h 19,300/19,300
6.4/6.4
24,100/20,700
8.0/6.8
38,500/38,500
12.7/12.7
43,300/40,000
14.3/13.2
48,200/41,500
15.9/13.776,400/76,400 95,500/82,200 152,900/152,900 172,000/158,700 191,100/164,500
kW 22.4/22.4
RT
ConstituentUnits — — RXYQ8MY1K(E)
RXYQ8MY1K(E)RXYQ8MY1K(E)RXYQ10MY1K(E)
RXYQ10MY1K(E)RXYQ10MY1K(E)
Power supply
75.064,500255,900
81.570,100278,100
88.075,700300,300
94.581,300322,400
21.3 23.1 25.0 26.8
59,600/58,800
19.7/19.4
64,000/59,900
21.1/19.8
68,400/61,100
22.6/20.2
72,800/62,200
24.0/20.5236,500/233,400 253,900/237,800 271,300/242,300 288,700/246,700
57,800/57,800
19.1/19.1
62,600/59,300
20.7/19.6
67,400/60,700
22.3/20.1
72,200/62,200
23.9/20.5229,300/229,300 248,400/235,100 267,500/240,900 286,600/246,700
69.3/68.4 74.4/69.7 79.5/71.0
67.2/67.2 72.8/68.9 78.4/70.6
84.6/72.3
84.0/72.3
Power consumption Cooling (*3)/(*4) kWHeating (*5)
18.0/27.5 19.6/27.9 21.2/28.317.5 19.0 20.6
22.7/28.7Cooling (*1)/(*2) 18.9/28.2 20.2/28.4 21.5/28.6 22.8/28.7
22.2
COP (Cooling) (*3)/(*4)COP (Heating) (*5)
3.73/2.45 3.71/2.47 3.70/2.504.30 4.28 4.27
3.69/2.52COP (Cooling) (*1)/(*2) 3.66/2.42 3.68/2.45 3.70/2.49 3.71/2.52
4.26
RXYQ24MY1K(E) RXYQ26MY1K(E) RXYQ28MY1K(E) RXYQ30MY1K(E)MODEL
3 phase, 380–415V, 50Hz
ConstituentUnits
RXYQ8MY1K(E)RXYQ8MY1K(E)RXYQ8MY1K(E)
RXYQ8MY1K(E)RXYQ8MY1K(E)RXYQ10MY1K(E)
RXYQ8MY1K(E)RXYQ10MY1K(E)RXYQ10MY1K(E)
RXYQ10MY1K(E)RXYQ10MY1K(E)RXYQ10MY1K(E)
Heating capacity(*5)
Cooling capacity(*1)/(*2)
Btu/hkcal/h
kW
Btu/hkcal/h
kW
RT
RT
Cooling capacity(*3)/(*4)
Btu/hkcal/hkW
RT
Operation range CoolingHeating
°CDB°CWB
-5 to 50-20 to 16
Heating capacity(*5)
Cooling capacity(*1)/(*2)
Btu/hkcal/h
kW
Btu/hkcal/h
Power supply
25.021,50085,300
31.527,100107,500
50.043,000170,600
19,900/19,600
6.6/6.5
24,300/20,700
8.0/6.8
39,700/39,200
13.1/13.0
56.548,600192,800
44,100/40,300
14.6/13.3
63.054,200215,000
7.1 8.9 14.2 16.0 17.9
48,500/41,500
16.0/13.778,800/77,800 96,200/82,200 157,600/155,600 175,000/160,000 192,400/164,500
kW
RT
23.1/22.8 28.2/24.1 46.2/45.6
28.0/24.1 44.8/44.8
51.3/46.9
50.4/46.5
56.4/48.2
56.0/48.2
Power consumption Cooling (*3)/(*4) kWHeating (*5)
6.01/9.16 7.58/9.56 12.0/18.35.82 7.40 11.6
13.6/18.713.2
15.2/19.1Cooling (*1)/(*2) 6.31/9.41 7.60/9.58 12.6/18.8 13.9/19.0 15.2/19.2
14.8
COP (Cooling) (*3)/(*4)COP (Heating) (*5)
3.73/2.45 3.69/2.52 3.73/2.454.30 4.26 4.30
3.71/2.484.27
3.69/2.52COP (Cooling) (*1)/(*2) 3.66/2.42 3.71/2.52 3.66/2.42 3.69/2.47 3.71/2.52
4.26
3 phase, 380 V, 60Hz
RXYQ8MYLK(E) RXYQ10MYLK(E) RXYQ16MYLK(E) RXYQ18MYLK(E) RXYQ20MYLK(E)MODE
RT
Cooling capacity(*3)/(*4)
Btu/hkcal/h 19,300/19,300
6.4/6.4
24,100/20,700
8.0/6.8
38,500/38,500
12.7/12.7
43,300/40,000
14.3/13.2
48,200/41,500
15.9/13.776,400/76,400 95,500/82,200 152,900/152,900 172,000/158,700 191,100/164,500
kW 22.4/22.4
RT
ConstituentUnits — — RXYQ8MYLK(E)
RXYQ8MYLK(E)RXYQ8MYLK(E)RXYQ10MYLK(E)
RXYQ10MYLK(E)RXYQ10MYLK(E)
Operation range CoolingHeating
°CDB°CWB
-5 to 50-20 to 16
Power supply
75.064,500255,900
81.570,100278,100
88.075,700300,300
94.581,300322,400
21.3 23.1 25.0 26.8
59,600/58,800
19.7/19.4
64,000/59,900
21.1/19.8
68,400/61,100
22.6/20.2
72,800/62,200
24.0/20.5236,500/233,400 253,900/237,800 271,300/242,300 288,700/246,700
57,800/57,800
19.1/19.1
62,600/59,300
20.7/19.6
67,400/60,700
22.3/20.1
72,200/62,200
23.9/20.5229,300/229,300 248,400/235,100 267,500/240,900 286,600/246,700
69.3/68.4 74.4/69.7 79.5/71.0
67.2/67.2 72.8/68.9 78.4/70.6
84.6/72.3
84.0/72.3
Power consumption Cooling (*3)/(*4) kWHeating (*5)
18.0/27.5 19.6/27.9 21.2/28.317.5 19.0 20.6
22.7/28.7Cooling (*1)/(*2) 18.9/28.2 20.2/28.4 21.5/28.6 22.8/28.7
22.2
COP (Cooling) (*3)/(*4)COP (Heating) (*5)
3.73/2.45 3.71/2.47 3.70/2.504.30 4.28 4.27
3.69/2.52COP (Cooling) (*1)/(*2) 3.66/2.42 3.68/2.45 3.70/2.49 3.71/2.52
4.26
RXYQ24MYLK(E) RXYQ26MYLK(E) RXYQ28MYLK(E) RXYQ30MYLK(E)MODE
3 phase, 380 V, 60Hz
ConstituentUnits
RXYQ8MYLK(E)RXYQ8MYLK(E)RXYQ8MYLK(E)
RXYQ8MYLK(E)RXYQ8MYLK(E)RXYQ10MYLK(E)
RXYQ8MYLK(E)RXYQ10MYLK(E)RXYQ10MYLK(E)
RXYQ10MYLK(E)RXYQ10MYLK(E)RXYQ10MYLK(E)
Heating capacity(*5)
Cooling capacity(*1)/(*2)
Btu/hkcal/h
kW
Btu/hkcal/h
kW
RT
RT
Cooling capacity(*3)/(*4)
Btu/hkcal/hkW
RT
Note : 1. Optional models (-E type) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric component box, in addition to the fins ofthe heat exchanger. These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
(*2) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 46°CDB.(*3) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35°CDB.(*4) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 46°CDB.
•Heating : (*5) Indoor temp. of 20°CDB, and outdoor temp. 7°CDB/6°CWB.•Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
27 28
Heat Reclaim Ventilation
VAM150FAVE VAM350FAVE
VAM500FAVE VAM1000FAVE
VAM1500FAVE VAM2000FAVE
HRV Remote Controller
Daikin's HRV recovers heat energy lost through ventilation and holdsdown room temperature changes caused by ventilation, therebymaintaining a comfortable and clean environment.The HRV is interlocked to Daikin's system, SkyAir and other airconditioning systems and automatically switches over ventilation mode,further increasing the effects of energy conservation.First-Class Compactness in the Industry has been achieved by employinga originally developed High Efficiency Paper (HEP) element, and using anoptimized fan and airflow passage design.First-Class Energy Conservation in the IndustryA total of 28% reduction of air conditioning load has been achievedthrough a combined use of total heat exchange mode, linked operationwith an air conditioner, and pre-heat/pre-cool control.
R emote C ontroller
The HRV creates a high-quality environmentby interlocking with the air conditioner
Indoor unit
Daikin air conditioner
LCD remote controllerfor indoor unit
• Operating mode signal• Filter cleaning signal• Failure detection signal
• ON/OFF signal• Cooling/Heating mode signal• Set temperature signal• Ventilation signal• Humidifier ON/OFF signal
HRV
• Coffee shop and restaurant • Dressmakingshop• Super market • Other variety shops• Office• Small and medium size office building• Large house• Amusement center
Shops
O f f i c e
HousingOthers
Cooling Only & Heat Pump
3 phase, 220 V, 60 HzPower supplyRSNY8KTALModel
Cooling capacity (*1)/(*2) Btu/h6.4/7.1
76,400/85,300
85,300
19,300/21,50022.4/25.07.1Heating capacity (*3) RT
RT
kWkcal/h
Btu/h
118.9/8.5Power comsumption kW
kW
2.272.52/2.94COP
Cooling (*1)/(*2)HeatingCooling (*1)/(*2)Heating
25.021,500kcal/h
kW
Notes: 1. Optional models (-E type) feature components treated for heat and rust corrosionresistance, such as external panels, fan motor, and electric component box, inaddition to the fins of the heat exchanger. Please contact Daikin for moreinformation.
RSNY8KTAL22.4kw(8HP)
Different capacity and different typeof indoor unit can be connected atthe capacity ratio of 50 to 100% ofthe outdoor unit, and up to 6 indoorunits can be connected withindividual control.
The individual control of the air conditioning system for 4–5 rooms can be realizedby more simple and lesser installation work.
Outdoor Unit
VRV K Series—Outdoor Units
Ceiling Mounted Cassette (Double flow)Ceiling Mounted Cassette (Multi flow) Super Cassette
FXC-LVE
Type Modelname
FXFL-LVECeiling Mounted Cassette Corner FXK-LVE
1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 8 HP
12300 15400 19100 24200 30700 38200 47800 765001.0 ton
31.25 40 50 62.5 80 100 125 200IndexHP
BtuRT 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton 6.4 ton
Ceiling Mounted Built-in
Ceiling Suspended
Floor StandingConcealed Floor Standing
Ceiling Mounted DuctFXH-LVEFXA-LVE
FXS-LVE
FXL-LVEFXN-LVE
FXM-LVE
Wall Mounted
Ceiling Mounted Duct FXYD-KAVE
Cooling Only & Heat Pump
VE: 1 phase, 220-240/220 V, 50/60 HzPower supplyIndoor unitModel
Cooling capacity (1)/(2)RTBtu/h
31.25 40
1.1/1.012,600/12,300
1.113,600
3,200/3,100
3,400
50
1.3/1.316,000/15,400
1.417,100
4,000/3,900
4,300
62.5
1.6/1.619,800/19,100
1.821,500
5,000/4,800
5,400
2.1/2.024,900/24,200
2.327,300
6,300/6,100
6,900
80
2.6/2.631,700/30,700
2.834,100
8,000/7,700
8,600
100
3.3/3.239,600/38,200
3.642,700
10,000/9,600
10,800
125
4.1/4.049,500/47,800
4.554,600
12,500/12,000
13,800
200
6.5/6.4
kW 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 11.6/11.2 14.5/14.0 23.0/22.4
78,500/76,400
7.185,300
19,800/19,300
21,500Heating capacity
RT
4.0 5.0 6.3 8.0 10.0 12.5 16.0 25.0kW
Btu/h
kcal/h
kcal/h
Notes: Specifications are based on the following conditions;(1)Cooling : 27°CDB, 19.5°CWB, and outdoor temp. 35°CDB.(2)Cooling : 27°CDB, 19.0°CWB, and outdoor temp. 35°CDB.
• Heating : Indoor temp. of 20°CDB, of 7°CDB, 6°CWB.• Equivalent piping length : 7.5 m.• Level difference : 0 m.
2. Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27.0°CDB, 19.0°CWB, Outdoor temp.: 35.0°CDB
(*2) Indoor temp.: 29.0°CDB, 19.0°CWB, Outdoor temp.: 46.0°CDB•Heating: (*3) Indoor temp.: 20.0°CDB, Outdoor temp.: 7.0°CDB/6.0°CWB.
VAM150FAVE VAM250FAVE VAM350FAVE VAM500FAVE
58/64(58/66)
64/69(64/71)
58/62(58/63)
64/68(64/69)
61/67(61/68)
65/70(65/71)
58/63(58/65.5)
62/67(62/68.5)% For heating50 Hz (60 Hz)% For cooling50 Hz (60 Hz)
Model
Enthalpy exchangeefficiency (H/L)
74/79(74/80) 72/77(72/77) 75/80(75/81) 74/77(74/78.5)
VAM650FAVE VAM800FAVE VAM1000FAVE VAM1500FAVE
58/63(58/65)
63/66(63/68)
60/62(60/63)
65/67(65/68)
61/63(61/66)
66/68(66/71)
61/64(61/64)
66/68(66/68)
74/77(74/78) 74/76(74/76) 75/76.5(75/78) 75/78(75/78)
VAM2000FAVE
61/66(61/66)
66/70(66/70)
75/78(75/78)% 50 Hz (60 Hz)Temp. exchangeefficiency (H/L)
(50 Hz/60 Hz)
1 phase, 220-240 V/220 V, 50 Hz/60 HzPower supply150/150 250/250 350/350 500/500Ultra-High150/150 250/250 350/350 500/500High110/110 155/145 230/210 350/300Low
Air Flow Rate (m3/h)[50 Hz/60 Hz]
69/98 64/98 98/142 98/147Ultra-High39/54 39/54 70/85 54/54High20/24 20/20 25/15 25/20Low
External StaticPressure (Pa)[50 Hz/60 Hz]
650/650 800/800 1,000/1,000 1,500/1,500650/650 800/800 1,000/1,000 1,500/1,500500/440 670/660 870/800 1,200/1,20093/162 137/225 157/196 137/20639/69 98/118 98/108 98/11825/34 49/69 78/69 49/69
2,000/2,0002,000/2,0001,400/1,400137/19678/8859/69
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Capacity
Note:• Specifications for RT and Btu are based on the following conditions; Cooling : Indoor temp. of 27-°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
29 30
Individual Control Systems Centralized Control SystemsControl Systems Control Systems
Large liquid crystal screen displayscomplete operating status.Digital display lets you settemperature in 1°C units.Lets you individually program bytimer the respective times foroperation start and stop within amaximum of 72 hours.Equipped with a thermostat sensor inthe remote controller that makespossible more comfortable roomtemperature control.Enables you to select cool/heat/fanoperation mode with the indoorremote controller of your choicewithout using the cool/heat selector.
Constantly monitors malfunctions inthe system for 80 items, and isequipped with a "self-diagnosisfunction" that lets you know bymessage immediately when amalfunction occurs.Lets you carry out various fieldsettings by remote controller.
Wired remote controller (Optional)
Wired remote controller
The remote controller hascentralized its frequently usedoperation selectors andswitches (on/off, operationmode, temperature setting andairflow volume), making itselfsuitable for use in hotel roomsor conference rooms.
Signal receiver unit(Separate type)
Wireless remotecontroller
The concealed-type remote controller smartly fits into anight table or console panel in a hotel room.
Exposed type
Concealed type(For hotel use)
Wireless remote controller (Optional)
Simple remote controller (Optional)
The same operation modes and settings as with wired remote controllers arepossible.
• A light receiving unit for a ceiling-mounted cassette (double-flow, multi-flow) type,ceiling-suspended type and wall-mounted type is mounted into the indoor unit.
Signal receiver unit(Installed type)
Signal receiving unit can beinstalled on the panelex. Ceiling mounted cassette (multi-flow) type
Note : 1. Installation box for adaptor must be procured on site.
Central remote controller (Optional)64 groups (zones) of indoor units can becontrolled individually same as LCD Remote controller.Max.64 groups (128 indoor units controllable)Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers,which can control from 2 different places.Zone controlMalfunction code displayMax. wiring length 1,000 m (Total : 2,000 m)Combination with Unified ON/OFF controller, schedule timer and BMS systemAirflow volume and direction can be controlled individually for indoor units in each group operation.Ventilation volume and mode can be controlled for Heat Reclaim Ventilation (HRV).Up to 4 Operation/Stop pairs can be set per day by connecting a schedule timer.
Unified ON/OFF controller (Optional)16 groups of indoor units can be operatedsimultaneously/individually.Max. 16 groups (128 indoor units) controllable2 remote controllers can be used to control from 2 different places.Operating status indication (Normal operation, Alarm)Centralized control indicationMax. wiring length 1,000 m (Total : 2,000 m)Compact size casing (Thickness : 16 mm)Combination with Central Remote controller, Schedule timer and BMS system
Schedule timer (Optional)Max.128 indoor units can be operated asprogramed schedule.Max. 128 indoor units controllableWhen used in combination with a central remote controller, a maximum of 8 weekly schedulepatterns can be set, while the central controller can be used to select desired zones. Up to 4Operation/Stop pairs can be set per day.Max. 48 hours back up power supplyMax. wiring length 1,000 m (Total : 2,000 m)Compact size casing (Thickness : 16 mm)Combination with Central Remote controller, Unified ON/OFF controller and BMS system
Part name Model No. Function
Unification adaptor for computerized control DCS302A52
Interface between the central monitoring board and centralcontrol units. Combined with the central remote controller,this adaptor enables the central monitoring board tocentralize such functions as the on/off control, operationstatus monitoring, and normal/malfunction monitoring.(*1)
Interface adaptor for SkyAir series DTA102A52
Wiring adaptor for other air-conditioner DTA103A51
DTA107A55
Adaptors required to connect products other than those ofthe VRV System to the high-speed DIII-NETcommunication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must beinstalled on the product unit to be controlled.
Central control adaptor kitFor UAT(Y)-K(A), FD-K
For SkyAir, FD(Y)M-FA, FDYB-KA, FDY-KAFVY(P)J-A, FXUQ-MH, FXLQ-MH
For air conditioners other than mentioned above.
DCS302C61
DCS301B61
DST301B61
Set back time clock (Optional)
Set back time clock
Connected to LCD wired remote controller(BRC type), this time clock can set 2 setsof on/off times in an increment of 30 minutes within a day. For each on/off setting atemperature setting is also possible.
31 32
Daikin's advanced air-conditioning control systemsControl Systems
Contact signal
Ai unit
Light/Fan
Daikin CentralAir ConditioningSystem
Localmonitoring& control
WatchDOGRemoteMulti-PC
Ethernet
Remote PC Sub PC
SecurityFire alarm
D -NET
D -NET
D -NETD -NET
Wiring adaptor required for connection withother equipment not compatible with D -NET
DAM602A51/52/53*2
Viainternet
HRV
VRV System
Centralized control system for easy provision of effective control andmonitoring of VRV system functionsFloor visual navigationGraphical reportRemote intelligent managerMulti-PC accessWatch dog function for remote error monitoringPower limit controlSliding temperature <optional (DAM101A51) unit required>Automatic heat/cool change-overECO modeTemperature limitationAir Conditioning Network Service System (Optional Maintenance Service)
Ethernet
Local Controller
Please contact Daikin for compatibility with BMS system
SecurityPower supply facility
Fire alarm
ElevatorPumpLighting...etc
BMS
HRV
VRV System
Integrated control systems that recognize the trend of open control systems
*1Air ConditioningNetwork Service System(Optional Maintenance Service)
Compatibility with BMS enhanced by utilizing the international communication standards,BACnet® or LONWORKS®.
XIF file for confirming of specifications of the units.Connectable up to 10 outdoor units and 64 indoor unit groups.
Conformance class 3 (ASHRAE 135–1995)Standard BACnet® Device B-ASC (ASHRAE 135–2001)BACnet® OPC server compatibilityBACnet®/IP over EthernetUp to 40 outdoor units and 256 indoor uit groups on one gateway. (optional adapter)
DMS504B51 Interface for use in LONWORKS®
DMS502A51 Interface for use in BACnet®
NewNew
Dio unit
Interfacing requirements vary depending on model, and some systems may not be suitable. Please contact your distributor for details.
Local dealers
I/F unit*5Automatic data transfer
Mainfunction informationby E-mail
INTERNET
*1. There are restrictions in applicable areas and release times, therefore please consult us separately for details.*2. Model name varies upon the system size.*3. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).*4. LONWORKS® is a registered trade mark of Echelon Corporation.*5. For an I/F unit, one of the following can be selected: L oc al C ontroller, intelligent touch Controller, or intelligent Manager II.*6. Ethernet is a registered trademark of Xerox Corporation.
ACC center
Maintenance services that boost profitsand customer satisfaction
Air ConditioningNetwork Service System
24 hour on-line diagnostic systemEnergy saving and extention of aircon operating lifeMaintenance management via A/C network service system reportsReliable service at shortest lead time
BACnet® LONWORKS®Interface for and
DMS502A51(Interface for use in BACnet®)
DMS504B51(Interface for use in LONWORKS®)
N e w F u n c t io n sN e w F u n c t io n s
• Features control and monitoring functions for centralA/C products and an Air Conditioning NetworkService function.
• Using an external contact via DIII-NET, monitors andcontrols equipment such as lighting, fans, orbuilding security systems.
NewNew
Color LCD touch panel icon displaySmall manageable sizeSimplified engineeringMulti language (English, French, Italian, German, Spanish and Chinese)Yearly scheduleP.P.D. (Power Proportinal Distribution function) (Optional)Auto heat/cool change-overTemperature limitationHistory of 500 actionsAir Conditioning Network Service System (Optional Maintenance Service)Simple Interlock Function
New communication functions in the user-friendly icon-based multilingualcontroller simplify centralized control of the VRV system.
Support for centralized control from elsewhereusing a PC with a Web browser (Optional)Sending of e-mail alerts to a specified addresswhen malfunctions occur (Optional)Built-in modem for connecting toAirnet Service System (Optional)
Built-in Ethernet port for connecting tothe Internet or an intranetManagement of facilities / equipmentother than A/C units(Compatible with Dio unit and Di unit)
Doubling of number of control pointsby adding a D -NET Plus Adapter (Optional)
ACC center• Air Conditioning Network Service System
Forced OFF from the fire alarm
Pi Port
• Connection to power consumptionmeter when using power proportionaldistribution function. (Optional)
DIII-NETPlus Adapter(option)
Number of indoor unit expanded from 64 to 128.
Indoor Unit
RS-232CControl pump,lighting
Monitoring of roomenter/exit sign
Simple Interlock Function
Public phone line
Air ConditioningNetwork Service Systemmodem for connections
• CSV output of powerproportional distributionresults (Optional)
PCMCIAFlashMemory
Mobile PhoneTrouble reports
Forced OFF contact input
HRV
Dio Unit
Di Unit
D -NET
NewFunction 6
NewFunction 1
Remote monitoring and control
NewFunction 5
NewFunction 3
NewFunction 2
NewFunction 4
NewFunction 6
NewFunction 1
NewFunction 3
NewFunction 5
NewFunction 3
NewFunction 2
NewFunction 4
NewFunction 6
NewFunction 7
NewFunction 7
NewFunction 1
NewFunction 3
NewFunction 5
NewFunction 3
NewFunction 2
NewFunction 4
NewFunction 1New
Function 1
NewFunction 2New
Function 2
NewFunction 3New
Function 3
NewFunction 4New
Function 4
NewFunction 5New
Function 5
NewFunction 6New
Function 6
NewFunction 7New
Function 7 Simple Interlock Function
N e w F u n c t io n sN e w F u n c t io n s
Trouble reports
DCS601C51
Unification adaptorfor computerized control
[DCS302A52]
Unified ON/OFF andstatus monitoring fromthe central monitoring panel
Upgrade
Upgrade
NewNew
Note: Availability of the products shown in this catalogue varies by country.
Note: •Specifications for RT, Btu and kW are based on the following conditions; Power supply: 60 Hz; Cooling: Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•The values given for 2 HP to 3 HP are for the FDB model, 4 HP to 6 HP are for the FDM model and 8 HP to 20 HP are for the FD model.The values given for 30 HP are for the UAT model and based on the following conditions; Power supply: 50 Hz; Cooling: Indoor temp. of 27°C DB, 19.5°C WB, and outdoor temp. of 35.0°C DB.
33 34
Daikin’s duct connection type packaged air conditioners are the best choicefor stores and offices. By placing the air conditioner in the ceiling, the designand finish of all areas remain attractive and unblemished. With minimaloperating sound, people nearby are almost unaware of the unit’s presence.And simultaneous operation of 2 to 4 indoor units with a single outdoor unit ispossible. When indoor units are distributed taking sunlight and humanoccupation patterns into consideration, a comfortable air flow is effectivelyspread throughout the room.Air cooled packaged water chillers are also available.Such systems can easily meet all the air-conditioning requirements offactories and other large areas.
Air Cooled Packaged Air ConditionersDuct Connection Series....................................... 35Air Cooled Single Packaged Air Conditioners......41Air Cooled Packaged Water Chillers....................42
Line Up
Packaged air conditioners
PACKAGEDAIR CONDITIONERS
Type Model Name
Air cooledpackagedduct connectionseriesLow staticpressure type
5.6 6.5 8.1 11.4 14.3 15.8 24.0 29.2 47.9 58.4kW 97.1HP 2 2.5 3 4 5 6 8 10 15 20 30
19100 22200 27600 38900 48800 53900 81900 99600 163400 199300Btu 331000RT 1.6 1.8 2.3 3.2 4.1 4.5 6.8 8.3 13.6 16.6 27.5
C/O60 Hz
50 HzFDBG
FDB
FDMG
FD(Y)M
H/P60 Hz
50 HzFDYB
FD
FDY
Air cooledpackagedduct connectionseriesMiddle staticpressure type
C/O60 Hz
50 Hz
FDM H/P60 Hz
50 Hz
Air cooledpackagedduct connectionseriesHigh staticpressure type
C/O60 Hz
50 Hz
H/P60 Hz
50 Hz
UAT
UATY
Air cooledsingle packagedair conditionersRoof top type
C/O
C/O
50 Hz60 Hz
H/P 50 Hz60 Hz
Simultaneousoperationsystem
UWAAir cooledpackagedwater chillers 60 Hz
50 Hz
50 100 150 200 250 300 400 500 600 700kW 800
PACKAGEDAIR CONDITIONERS
WATER CHILLERS
Capacity
Type Model Name HP 2 2.5 3 4 5 6 7.5 10 15 20 30
Operation range(Outdoor temp.)
Operation range(Outdoor temp.)
35 36
Duct Connection Series Low Static Pressure Type
PACKAGEDAIR CONDITIONERS
Air Cooled Packaged Air Conditioners—FD(Y)B(G) Series Air Cooled Packaged Air Conditioners—FD(Y)M Series
Duct Connection Series Low Static Pressure TypePerfect for quiet, beautiful, living spaceslike condominiums and apartments,houses and hotels, and similar living areas
R emote C ontroller Outdoor Unit
Whisper QuietIndoor unit with the industry's lowest level of sound
HandySmall, lightweight and easy-to-install outdoor unit
DurableThe special acryl precoated fin (PE fin) for anti-corrosiontreatment on the outdoor unit heat exchanger ensuresgreater resistance against salt damage and atmosphericpollution than ever.
Easy to UseEasy to read LCD wired remote controller (Optionalaccessory for heat pump type) (FDYB only)
Duct Connection Series Middle Static Pressure TypeDuct Connection Series Middle Static Pressure TypeMain unit can be mountedin the ceiling, and air can bedelivered freely by duct.
DurableThe special acryl precoated fin (PE fin)for anti-corrosion treatment on theoutdoor unit heat exchanger ensuresgreater resistance against salt damageand atmospheric pollution than ever.
Easy to UseEasy to read LCD wired remotecontroller. (Optional accessory)(FDYM only)
Central controlMany options are available for use withlarge-scale and advanced-functioncentrally controlled systems.(FDYM only)
FDBG50AVEFDB50KVE
FDBG60/71AVEFDB60/71KVE
FDYB50KAVE FDYB60/71KAVE
Digital RemoteController
LCD WiredRemoteController (Only for Heat Pump)
RemoteController
For Cooling Only Type For Heat Pump Type
SignalReceiverUnit
Wireless Remote Controller
Cooling Only (50 Hz)
Cooling Only (60 Hz) Heat Pump (60 Hz)
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
• Shows net capacities. When cooling it is the value minus the heat of the indoor unit fan motor. When heating, the heat of the fan motor is added.
ModelIndoor unit
Btu/hkcal/hkW
Cooling capacity*1 (1)/(2)
Outdoor unit
Power Supply VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
R50GV1
FDBG50AVE50
R60GV1K
FDBG60AVE60
FDBG71AVER71FUV1R71FUY1
71
18,200/18,1004,590/4,5605.34/5.30
24,000/23,8006,050/6,0007.03/6.97
26,600/26,3006,700/6,6007.80/7.70
°CDB
kWCOP *1 (1)/(2)Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)2.59/2.592.06/2.05
2.55/2.5319.4 to 54
2.76/2.752.77/2.7521 to 52
2.82/2.8
°CDB
kWCOP *1 (1)/(2)Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)
°CDB
kWCOP *1 (2)Operation range (Outdoor temp.)
Power comsumption *1 (2)/(3)
2.79/2.783.15/3.13
2.60/2.604.08/4.04
2.68/2.6621 to 52
4.89/4.85
kWkWPower comsumption
2.00/2.022.64
2.20/2.502.44/2.502.37
2.70/3.303.30/3.302.31
3.50/4.20
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
CoolingHeating
COP
19.4 to 54-10 to 15
3.15 2.95-5 to 54-10 to 15.5
2.73kWkWPower comsumption
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
CoolingHeating
COP
-10 to 15.5-5 to 54
-10 to 15
RT 1.5/1.5 2.0/2.0 2.2/2.2
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz
FDB50KVE FDB60KVE FDB71KVER50GVAL R60GVAL R71FUVAL
19,100/17,1004,820/4,3005.60/5.0
22,200/19,1005,590/4,8006.50/5.6
27,600/22,9007,000/5,8008.10/6.7
1.6/1.4 1.8/1.6 2.3/1.9
———
———
———
— — —
2.67—
—2.41—
—2.45—
—19.4 to 54
—21 to 54—
—2.10/2.41 2.70/3.29 3.30/3.78
50 60 71
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz
FDYB50KAVE FDYB60KAVE FDYB71KAVERY50GVAL RY60GVAL RY71FUVAL
19,800/17,4004,990/4,3905.80/5.11
21,800/19,5005,500/4,9106.40/5.71
27,600/24,6007,000/6,2008.10/7.20
50 60 71
Model
Btu/hkcal/hkW
1.6/1.5 1.8/1.6 2.3/2.0RTCooling capacity*1 (2)/(3)
21,500/21,3005,420/5,3706.30/6.25
24,500/24,3006,180/6,1407.19/7.13
30,700/30,7007,700/7,7009.00/9.00
Btu/hkcal/hkW
1.8/1.8 2.0/2.0 2.6/2.6RTHeating capacity*2 (1)/(2)
Power SupplyOutdoor unitIndoor unit
FD(Y)M03FAVAL FD(Y)M04FAVALFDYM05/06FAVAL
LCD wiredremotecontroller
SignalReceiverUnit
Wireless RemoteController
Cooling Only (50 Hz)
V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
FDMG71AV1 FDMG100AV1 FDMG125AV1R100FUV1
8.80/8.7 10.6/10.5 13.1/12.9
71 100 125
R100FUY1R71AV1R71AY1
R125FUV1ModelIndoor unit
30,000/29,7007,600/7,500
36,200/35,8009,100/9,000
44,700/44,00011,200/11,000
Btu/hkcal/hkW
2.5/2.5 3.0/3.0 3.7/3.7RTCooling capacity*1 (1)/(2)
Outdoor unit
Power Supply
Cooling Only (60 Hz)
VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 HzR71FUVALFDM03FAVAL
71
R100FUVALFDM04FAVAL
100
R125FUTALFDM05FAVAL
125FDYM06FAVALR140KUTALK
140
8.10/6.7 11.40/9.0 14.3/12.5 15.8/14.03.44/3.92 4.61/5.27 6.25/7.102.35 2.47 2.29 2.72
21 to 54
5.80/7.00
ModelIndoor unit
27,600/22,900 38,900/30,700 48,800/42,7007,000/5,800 9,800/7,700 12,300/10,800
53,900/47,80013,500/12,000
Btu/hkcal/hkW
2.3/1.9 3.2/2.6 4.1/3.6 4.5/4.0RTCooling capacity*1 (2)/(3)
Outdoor unitPower Supply
ModelIndoor unit
8.1/6.7 11.4/9.0 14.3/12.5 15.8/14.0
27,600/22,9007,000/5,800
38,900/30,7009,800/7,700
48,800/42,70012,300/10,800
53,900/47,80013,500/12,000
Btu/hkcal/hkW
2.3/1.9 3.2/2.6 4.1/3.6 4.5/4.0RTCooling capacity*1 (2)/(3)
9.00/8.50 12.80/11.80 16.20/15.00 18.10/17.00
30,700/29,0007,700/7,300
43,700/40,30011,000/10,100
55,300/51,20013,900/12,900
61,800/58,00015,600/14,600
Btu/hkcal/hkW
2.6/2.4 3.6/3.4 4.6/4.3 5.1/4.8
2.122.52
3.57/3.592.392.85
4.49/4.512.362.91
5.56/5.602.723.12
5.80/5.903.82/4.37 4.76/5.25 6.05/6.71 5.80/7.00
RT
Heat Pump (60 Hz)
RY140KUTALKRY100FUVALRY71FUVAL RY125FUTALOutdoor unit
Heating capacity*2(1)/(2)
VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 HzPower Supply
FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL FDYM06FAVAL71 100 125 140
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2:Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
• Shows net capacities. When cooling it is the value minus the heat of the indoor unit fan motor. When heating, the heat of the fan motor is added.• For FDMG models, capacities show gross capacities which do not include a deduction for evaporator fan motor heat.
R emote C ontroller Outdoor Unit
Cooling*1 (2)Heating *2 (1)
Cooling *1 (2)Heating *2 (1)
FDMG71AV1 FDMG100/125AV1
Digital RemoteController
RemoteController
For FD(Y)M modelsFor FDMG models
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284 Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
37 38
PACKAGEDAIR CONDITIONERS
Air Cooled Packaged Air Conditioners—FD(Y) Series
Duct Connection Series High Static Pressure TypeDuct Connection Series High Static Pressure TypeRecommended for spacious and large-volume areas because ofits flexible installation. Suitable for large stores, factories, andother large areas, and for use with housing ducts in homes.
Highly Adaptable InstallationHigh static pressure and long piping enable flexibleinstallation and use wherever the unit is placed.
CompactSpace-saving outdoor unit also enables lateralconnection.
DurableHighly durable outdoor unit employs PE fins, resistssalt damage and atmospheric pollution.
Super QuietIndoor unit with the industry's lowest level of sound.
Central controlMany options are available for use with large-scaleand advanced-function centrally controlledsystems.
FD03KY1FD03KVAL
FD04KY1FD04KVAL
FD05KY1FD05KTAL
FD(Y)10K(A)Y1FD(Y)10K(A)TAL·YAL
FD(Y)15KAY1FD(Y)15KATAL·YAL
FD06KY1FD06KTAL
FD(Y)08K(A)Y1FD(Y)08K(A)TAL·YAL
FD(Y)20KAY1FD(Y)20KATAL·YAL
RemoteController
(Only for Cooling Only)
LCD wiredremote controller
(Only for Heat Pump)(Only for Heat Pump)
SignalReceiverUnit
Wireless Remote Controller
FD03KY1R71FUY1
FD04KY1R100FUY1
FD05KY1R125FUY1
FD06KY1RU06KY1
ModelIndoor unitOutdoor unit
8.1/7.9 11.0/10.8 14.0/13.8 17.4/17.2
FD08KY1RU08K(U)Y1
24.3/24.0
FD10KY1RU10K(U)Y1
FD15KY1RU08K(U)Y1X2
29.7/29.2 48.6/47.9
FD20KY171 100 125 140 200 250 400 500
RU10K(U)Y1X2
59.3/58.4
3.24/3.19 3.13/3.10 3.34/3.33 3.05/3.022.5/2.48 3.52/3.48 4.19/4.15 5.7/5.7
3.24/3.247.5/7.4
3.00/2.98 3.24/3.249.9/9.8 15.0/14.8
2.99/2.9821 to 52
19.8/19.6
27,600/27,0007,000/6,800
37,500/36,8009,500/9,300
47,800/47,10012,000/11,800
59,400/58,70015,000/14,800
82,900/81,90020,900/20,600
101,300/99,60025,500/25,100
165,800/163,40041,800/41,200
202,300/199,30051,000/50,200
Btu/hkcal/hkW
2.3/2.2 3.1/3.1 4.0/3.9 4.9/4.9 6.9/6.8 8.4/8.3 13.8/13.6 16.8/16.6RTCooling capacity*1 (1)/(2)
Cooling Only (50 Hz)
Y1: 3 phase, 380-415 V, 50 HzPower Supply
71 100 125 140 200 250 400 500FD03KVALR71FUVAL
FD04KVALR100FUVAL
FD05KTALR125FUTAL
FD06KTALRU06KTAL
8.5/7.1 11.9/9.0 15.2/14.1 17.3/15.7
FD08KTALRU08K(U)TAL
24.0/21.9
FD10KTALRU10K(U)TAL
FD15KTALRU08K(U)TALX2
29.2/26.7 47.9/43.8
FD20KTALRU10K(U)TALX2
58.4/53.3
2.6421 to 542.72 2.59 2.66
3.22/3.70 4.37/5.02 5.88/6.73 6.50/7.902.89
8.30/10.102.83 2.89
10.30/12.60 16.60/20.202.83
20.60/25.30
ModelIndoor unitOutdoor unit
29,000/24,2007,300/6,100
40,600/30,70010,200/7,700
51,900/48,10013,100/12,100
59,000/53,60014,900/13,500
81,900/74,70020,600/18,800
99,600/91,10025,100/23,000
163,400/149,40041,200/37,700
199,300/181,90050,200/45,800
Btu/hkcal/hkW
2.4/2.0 3.4/2.6 4.3/4.0 4.9/4.5 6.8/6.2 8.3/7.6 13.6/12.4 16.6/15.1RTCooling capacity*1 (2)/(3)
Cooling Only (60 Hz)
VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 HzPower Supply
kW
Cooling capacity*1 (2)/(3)
23.2/22.9 29.5/29.1 44.8/44.6 56.8/56.6
22.2/19.8 27.1/24.3 43.5/38.7
Btu/hkcal/h
75,700/67,60019,100/17,000
92,500/82,90023,300/20,900
148,400/132,00037,400/33,300
180,800/161,40045,600/40,70053.0/47.3
RT 6.3/5.6 7.7/6.9 12.4/11.0 15.1/13.4
79,200/78,10020,000/19,700
100,700/99,30025,400/25,000
152,900/152,20038,500/38,400
193,800/193,10048,800/48,700
Btu/hkcal/hkW
6.6/6.5 8.4/8.3 12.7/12.7 16.1/16.1RTHeating capacity*2(1)/(2)
TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 HzPower Supply
ModelIndoor unit
RY250KUTALX2RY250KUYALX2
Outdoor unit
200 250 400 500
RY200KUTALX2RY200KUYALX2
RY250KUTALRY250KUYAL
RY200KUTALRY200KUYAL
FDY20KATALFDY20KAYAL
FDY15KATALFDY15KAYAL
FDY10KATALFDY10KAYAL
FDY08KATALFDY08KAYAL
Heat Pump (60 Hz)
kW
Cooling capacity*1 (1)/(2)
79,20020,000
100,70025,400
153,00038,500
194,00048,800
22.5/22.2 27.6/27.1 44.0/43.5
79,20020,000
100,70025,400
152,90038,500
193,80048,800
Btu/hkcal/h
76,800/75,70019,300/19,100
94,200/92,50023,700/23,300
150,000/148,00037,800/37,400
184,000/181,00046,400/45,600
76,800/75,70019,300/19,100
94,200/92,50023,700/23,300
150,100/148,40037,800/37,400
183,900/180,800RT 76,800/75,700 94,200/92,500 150,000/148,000 184,000/181,0006.4/6.3 7.8/7.7 12.5/12.4 15.3/15.1
46,400/45,60053.9/53.0
23.2 29.5 44.8 56.8
76,800/75,70019,300/19,100
94,200/92,50023,700/23,300
150,000/148,0007.2/7.1 9.3/9.2 14.4/14.2
37,800/37,400184,000/181,00046,400/45,600
3.8 3.35 3.67 3.23
6.13.13/3.13
8.82.97/2.95
12.23.06/3.06
17.62.91/2.90
18.5/18.3
Btu/hkcal/h
23.2 29.5 44.8 56.823.2 29.5 44.8 56.8kW
23.2 29.5 44.8 56.86.6 8.4 12.7 16.1RTHeating capacity*2(1)
Y1: 3 phase, 380-415 V (4 wires), 50 HzPower Supply
ModelRY250KUY1X2
200 250 400 500
RY200KUY1X2RY250KUY1FDY20KAY1FDY15KAY1FDY10KAY1
Heat Pump (50 Hz)
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Outdoor unitFDY08KAY1RY200KUY1
Indoor unit
R emote C ontroller Outdoor Unit
°CDB
kWCOP *1 (1)/(2)
Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)
°CDB
kWCOP *1 (2)Operation range (Outdoor temp.)
Power comsumption *1 (2)/(3)
kWkWPower comsumption
Heating*2 (1)Cooling*1 (2)/(3)
COP Cooling*1 (1)/(2)Heating *2 (1)/(2)
0 to 54-10 to 15
7.7/9.4 9.7/11.9 15.3/18.8
3.52 3.17 3.39 3.05
6.6/6.72.88
9.3/9.52.79
13.2/13.42.84
18.6/19.02.73
19.4/23.8
Operation range(Outdoor temp.)
CoolingHeating
kWkWPower comsumption
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
COP Cooling*1 (2)Heating *2 (1)
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
39 40
PACKAGEDAIR CONDITIONERS
Simultaneous Operation System—Twin, Triple & Double Twin Multi Application Operation
In large interior spaces a single indoor unit may not be able to provide uniform comfort. Installation of 2 to 4 units, distributed toconsider sun light and human gathering patterns, can provide an effective solution.
In a single-floor restaurant, for example, positioning 4 units at strategic locations achieves comfortable air flow that reachesevery inch of the room.
Simultaneously operates 2 to 4 indoor units usinga single outdoor unit.
Installing multiple units is economical and ensures comfort
Lower cost of installation than for individual pair typeLess space needed for outdoor unitsEnhanced comfort from distributed indoor units
Note: This type of system does not allow individual control or independent operation of indoor units. It is not the best choice for large rooms with partitions.
Branch piping kit Branch piping kitBranch piping kit
Branch piping kit
ModelIndoor unit FDYM04FAV1X2Outdoor unit R200KUY1
76,800/75,70019,400/19,10022.5/22.2
FDYM05FAV1X2R250KUY1
92,500/90,80023,300/22,90027.1/26.6
FDYM03FAV1X3200 250 200
R200KUY1
76,800/75,70019,400/19,10022.5/22.2
7.7/7.62.92/2.92
9.9/9.92.74/2.69
8.0/7.92.81/2.81
-5 to 52
Btu/hkcal/hkW
6.4/6.3 7.7/7.6 6.4/6.3RTCooling capacity*1(1)/(2)
Cooling Only (50 Hz)
V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 HzPower Supply
ModelIndoor unit FDYM04FAVALX2
Outdoor unitR200KUTAL
75,700/68,20019,100/17,20022.0/20.0
FDYM05FAVALX2R250KUTAL
90,800/82,20022,900/20,70026.6/24.1
FDYM03FAVALX3200 250 200
R200KUTALR200KUYAL R250KUYAL R200KUYAL
75,700/68,20019,100/17,20022.2/20.0
2.718.2/10.0
2.5610.4/12.7
2.61-5 to 54
8.5/10.3
Btu/hkcal/hkW
6.3/5.7 7.6/6.8 6.3/5.7RTCooling capacity*1(2)/(3)
Cooling Only (60 Hz)
VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 HzPower Supply
ModelIndoor unitOutdoor unit
Btu/hkcal/hkW
RTCooling capacity*1(2)/(3)
Btu/hkcal/hkW
75,700/68,20019,100/17,200
90,800/82,20022,900/20,700
75,700/68,20019,100/17,200
22.2/20.0 26.6/24.1 22.2/20.0
6.3/5.7 7.6/6.8 6.3/5.7
77,500/76,40019,500/19,30022.7/22.4
96,900/95,50024,400/24,10028.4/28.0
77,500/76,40019,500/19,30022.7/22.4
7.0/7.12.71
8.2/10.09.7/10.02.61
10.2/12.67.0/7.12.71
8.20/10.00
3.24 2.930 to 54-10 to 15
3.24
6.4/6.4 8.1/8.0 6.4/6.4
75,700/68,20019,100/17,200
90,800/82,20022,900/20,700
75,700/68,20019,100/17,200
22.2/20.0 26.6/24.1 22.2/20.0
6.3/5.7 7.6/6.8 6.3/5.7
77,500/76,40019,500/19,30022.7/22.4
96,900/95,50024,400/24,10028.4/28.0
77,500/76,40019,500/19,30022.7/22.4
7.0/7.12.71
8.2/10.09.9/10.12.56
10.4/12.57.3/7.42.61
8.5/10.3
3.24 2.870 to 54-10 to 15
3.11
6.4/6.4 8.1/8.0 6.4/6.4
RTHeating capacity*2(1)/(2)
Heat Pump (60 Hz)
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 HzPower SupplyRY200KUTAL·YAL RY250KUTAL·YAL RY200KUTAL·YALFDYB50KAVEX4 FDYB60KAVEX4 FDYB71KAVEX3
200 250 200
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Notes: •*1: Nominal cooling capacities are based on the following conditions:(1) Return air temperature: 27°CDB, 19.5°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 27°CDB, 19.0°CWB, Outdoor temperature: 35°CDB Equivalent ref. piping: 5 m (Horizontal)(3) Return air temperature: 29°CDB, 19.0°CWB, Outdoor temperature: 46°CDB, 24°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
•*2: Nominal heating capacities are based on the following conditions:(1) Return air temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 5 m (Horizontal)(2) Return air temperature: 21°CDB, Outdoor temperature: 7°CDB, 6°CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
°CDB
kWCOP *1 (1)/(2)Operation range (Outdoor temp.)
Power comsumption *1 (1)/(2)Operation range(Outdoor temp.)
CoolingHeating
kWkWPower comsumption
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
COP Cooling*1 (2)Heating *2 (1)
ModelIndoor unitOutdoor unit
Btu/hkcal/hkW
RTCooling capacity*1(2)/(3)
Btu/hkcal/hkW
RTHeating capacity*2(1)/(2)
Heat Pump (60 Hz)
VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 HzPower SupplyRY200KUTAL·YAL RY250KUTAL·YAL RY200KUTAL·YALFDYM04FAVALX2 FDYM05FAVALX2 FDYM03FAVALX3
200 250 200
Operation range(Outdoor temp.)
CoolingHeating
kWkWPower comsumption
°CDB°CWB
Heating*2 (1)/(2)Cooling*1 (2)/(3)
COP Cooling*1 (2)Heating *2 (1)
°CDB
kWCOP *1 (2)Operation range (Outdoor temp.)
Power comsumption *1 (2)/(3)
76,800/75,70019,400/19,100
6.4/6.376,800/75,70019,400/19,100
6.4/6.392,500/90,80023,300/22,900
7.7/7.6Btu/hkcal/h
RT
22.5/22.2 22.5/22.2 27.1/26.6kW
Cooling capacity*1(1)/(2)
77,50019,500
6.477,50019,500
6.496,90024,400
8.1
6.52.92/2.92
7.7/7.66.5
2.92/2.92
7.7/7.69.2
2.79/2.74
9.7/9.7
3.49 3.49 3.09
Btu/hkcal/h
RT
22.7 22.7 28.4kW
Heating capacity*2(1)
ModelIndoor unit FDYB50KAVEX4Outdoor unit RY200KUY1
FDYB71KAVEX3RY200KUY1
FDYB60KAVEX4RY250KUY1
Heat Pump (50 Hz)
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 HzPower Supply
kWkWPower comsumption
Heating*2 (1)Cooling*1 (1)/(2)
COP Cooling*1 (1)/(2)Heating *2 (1)
76,800/75,70019,400/19,100
6.4/6.376,800/75,70019,400/19,100
6.4/6.392,500/90,80023,300/22,900
7.7/7.6Btu/hkcal/h
RT
22.5/22.2 22.5/22.227.1/26.6kW
Cooling capacity*1(1)/(2)
77,50019,500
6.477.50019,500
6.496,90024,400
8.1
6.52.92/2.92
7.7/7.66.8
2.81/2.81
8.0/7.99.4
2.69/2.74
9.9/9.9
3.49 3.343.02
Btu/hkcal/h
RT
22.7 22.728.4kW
Heating capacity*2(1)
ModelIndoor unit FDYM04FAV1X2Outdoor unit RY200KUY1
FDYM05FAV1X2RY250KUY1
FDYM03FAV1X3RY200KUY1
Heat Pump (50 Hz)
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 HzPower Supply
kWkWPower comsumption
Heating*2 (1)Cooling*1 (1)/(2)
COP Cooling*1 (1)/(2)Heating *2 (1)
Twin Multi Application Triple Multi Application Double Twin Multi Application
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284
41 42
PACKAGEDAIR CONDITIONERS WATER CHILLERS
Air Cooled Single Packaged Air Conditioners—UAT(Y) Series Air Cooled Packaged Water Chillers—UWA Series
Model
kcal/hCooling capacity *1(50/60 Hz)
Btu/h
Cooling capacity *2(50/60 Hz)
Btu/h
Model
Cooling capacity *1(50/60 Hz)
UATY06KY1UATY06KTALUATY06KYAL
UATY08KY1UATY08KTALUATY08KYAL
UATY09KY1UATY09KTALUATY09KYAL
UATY10KY1(50 Hz Only)
UATY12KTALUATY12KYAL(60 Hz Only)
UATY15KY1UATY15KTALUATY15KYAL
Heating capacity *3(50/60 Hz)
Cooling capacity *2(50/60 Hz)
52,900 67,600 81,200 96,600 107,800 135,200
UATY18KY1UATY18KTALUATY18KYAL
UATY21KY1UATY21KTALUATY21KYAL
17.7 22.0 26.4 31.4 35.1 43.9kW 52.7 61.6
5 6 7.5 9 10 12.5RT 15 17.5
kcal/h60,300 75,000 90,000 107,200 120,000 150,00015,200 18,900 22,700 27,000 30,200 37,800
Btu/h 180,000 210,40045,300 53,000
18.1 23.0 26.9 32.1 36.1 46.1kW 54.2 62.8kcal/h
62,000 78,600 91,700 109,600 123,000 157,20015,600 19,800 23,100 27,600 31,000 39,600
Btu/h 185,000 214,40046,600 54,000
EER *3(Cooling)
5.8 6.3 8.2 9.9 — 13.0 17.1 19.8
YAL8.26 9.74 9.18 — 8.86 9.528.28 9.78 9.21 — 8.94 9.52
TAL 8.64 8.988.64 9.00
162,100 189,40015.5 19.8 23.8 28.3 31.6 39.6 47.5 55.5kW
Btu/h
Heat Pump (50 Hz/60 Hz)
UAT06KAUATY06K
UAT08·09·10·12KAUATY08·09·10·12K
UAT15·18·21KAUATY15·18·21K
UAT30H
52,900 67,600 81,200 107,800 135,200
15,200 18,900 22,700 30,200 37,80060,300 75,000 90,000 120,000 150,000
UAT06KAY1UAT06KATALUAT06KAYAL
UAT08KAY1UAT08KATALUAT08KAYAL
UAT09KAY1UAT09KATALUAT09KAYAL
UAT12KATALUAT12KAYAL(60 Hz Only)
UAT15KAY1UAT15KATALUAT15KAYAL
162,100
45,300180,000
UAT18KAY1UAT18KATALUAT18KAYAL
189,400
53,000210,400
UAT21KAY1UAT21KATALUAT21KAYAL
96,600
27,000107,200
UAT10KAY1(50 Hz Only)
284,000/330,700kW 15.5 19.8 23.8 31.6 39.6 47.5 55.528.3 83.1/96.9
EER *3(Cooling)
TAL 8.26 9.74 9.18 8.86 9.52 8.64 8.98— —YAL 8.28 9.78 9.21 8.94 9.52 8.64 9.00— —
83,500/92,600331,000/368,000
kW 17.7 22.0 26.4 35.1 43.9 52.7 61.631.4 97.1/107.7
RT 5 6 7.5 10 12.5 15 17.59 27.5/30
UAT30HY1UAT30HTO
Digital Remote Controller Remote Controller(Only for Cooling Only)
Cooling Only (50 Hz/60 Hz)
Notes: 1. The above data marked with *1 are rated in accordance with JIS C-9612. 27°CDB (80°FDB)/ 19.5°CWB (67°FWB) indoor temp. And 35°CDB (95°FDB) outdoor temp.2. The above data marked with *2 are rated in accordance with SSA-385/386, 29°CDB (84°FDB)/ 19°CWB (66°FWB) indoor temp. And 46°CDB (115°FDB) outdoor temp.3. The figures of *2 are reference value.4. Capacity (*1, 2) is gross capacity which does not include a deduction for evaporator fan motor heat.5. *3: EER conditions: 27°CDB (80°FDB) and 19.5°CWB (67°FWB) for indoor temp. 35°CDB (95°FDB) for outdoor temp.
Notes: 1. Cooling capacities marked with *1 are based on 27°CDB (80°FDB) 19.5°CWB (67°FWB) indoor temp. and 35°CDB (95°FDB) outdoor temp.2. Cooling capacities marked with *2 are based on 29°CDB (84°FDB) 19.0°CWB (66°FWB) indoor temp. and 46°CDB (115°FDB) outdoor temp.3. Heating capacities are based on 21°CDB for indoor temp. 7°CDB/6°CWB for outdoor temp.4. The figures of *2 is reference value.5. *3: EER Cooling conditions: 27°CDB (80°FDB) and 19.5°CWB (67°FWB) for indoor temp. 35°CDB (95°FDB) for outdoor temp.6. *4: EER Heating conditions: 20°CDB for indoor temp. 7°CDB/6°CWB for outdoor temp.
Y1: 3 phase, 380-415 V, 50 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz/TO: 3 phase, 200/200-220 V, 50/60 HzPower Supply
Y1: 3 phase, 380-415 V, 50 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 HzPower Supply
UWA80JATJUWA138JY1UWA55JAY1
Model
USRTCooling capacity *1
UWA37JAY1 UWA47JAY1 UWA55JAY1 UWA63JAY1
369,800 468,200 550,400 634,900108.4 137.2 161.3 186.0
30.8 39.0 45.8 52.9
kWBtu/h
USRTCooling capacity *2 332,500 425,800 511,500 571,400
97.4 124.8 149.9 167.4
27.7 35.4 42.6 47.6
kWBtu/h
Model
USRTCooling capacity *1
UWA27JATJ UWA32JATJ UWA43JATJ UWA53JATJ
269,800 320,600 426,600 553,50079.0 94.3 125.0 162.0
UWA62JATJ
632,100185.0
22.4 26.7 35.5 46.1 52.6
kWBtu/h
USRTCooling capacity *2 242,000 280,900 378,900 494,000
71.0 82.0 111.0 145.0584,100171.0
20.1 23.4 31.5 41.0 48.6
kWBtu/h
Cooling Only (60 Hz)
Model
USRTCooling capacity *1
UWA120JY1 UWA138JY1 UWA162JY1 UWA192JY1
1,201,500 1,380,800 1,620,600 1,921,500351.6 404.4 474.7 562.8
UWA228JY1 UWA270JY1
2,280,400 2,700,800667.9 791.0
99.9 115.0 135.0 160.0 189.9 224.7
kWBtu/h
Cooling Only (50 Hz)
Cooling Only (50 Hz)
3 phase, 380-415 V, 50 HzPower supply
Model
USRTCooling capacity *1
UWA75JAY1 UWA80JAY1
747,600 855,100219.1 250.6
62.3 71.2
kWBtu/h
USRTCooling capacity *2 672,600 769,400
197.1 225.5
56.0 64.1
UWA93JAY1 UWA109JAY1
930,500 1,089,200272.7 319.2
77.5 90.7
855,900 991,200250.8 290.5
71.3 82.6
kWBtu/h
3 phase, 380-415 V, 50 HzPower supply
3 phase, 380-415 V, 50 HzPower supply
*1 Cooling capacity is based on the following conditions: Leaving chilled water temp. 6.7°C (44°F), entering water temp. 12.2°C (54°F) outdoor temp. 35°C (95°FDB).*2 Cooling capacity is based on the following conditions: Leaving chilled water temp. 6.7°C (44°F), entering water temp. 12.2°C (54°F) outdoor temp. 46.0°C (115°FDB).
Notes :
3 phase, 208-230 V, 60 HzPower supply
Model
USRTCooling capacity *1
UWA70JATJ
722,200212.0
60.0
kWBtu/h
USRTCooling capacity *2 653,100
191.0
54.2
UWA80JATJ UWA90JATJ
865,000 936,400253.0 274.0
72.0 78.0
746,400 845,200219.0 248.0
62.1 70.4
UWA108JATJ UWA122JATJ
1,107,000 1,262,000324.0 370.0
92.2 105.0
972,200 1,145,000285.0 335.0
81.0 95.3
kWBtu/h
3 phase, 208-230 V, 60 HzPower supply
R emote C ontroller
Roof Top TypeRoof Top TypeEasy to install on rooftop or veranda, requiring only ducting,power line and drain piping.In addition to its high efficiency, the scroll compressor is 10%lighter and 30% more compact than conventionalreciprocating compressors. This makes this series among theindustry's most lightweight and compact than previous models.Also, since the scroll compressor generates less vibration, thisseries has greatly improved its durability and achieved theindustry's lowest operation sound. (UAT(Y)-K Series)Efficient cross fin coils are used: the unique waffle louverfins*1 maximize heat exchange efficiency, while the Hi-XAcopper tube*2, featuring an inner spiral groove, fully exploitsrefrigerant turbulence to help increase heat exchangeefficiency. The result is substantial energy savings.U.S. PAT. *1; No.4,434,844 *2; No.4,480,684
Wide Operation Range:Operative high outdoor temperature.UWA37JAY1–109JAY1: 5 to 52°CUWA27JATJ, 37JATJ: 15 to 49°CUWA43JATJ–122JATJ: 5 to 49°CUWA120JY1–270JY1: 5 to 49°C
Equipped with a compact andpowerful semi-hermetically sealedreciprocating compressor.
Energy saving.
Capacity can be controlled in multiple steps from 3 to 7 steps to saveenergy.
(UWA37JAY1–109JAY1, UWA43JATJ–122JATJ, UWA120JY1–270JY1)
Two independent refrigerant circuit.
The selector switch makes it possible to operate only one refrigerant circuitwhile one need repairing.
(UWA63JAY1–109JAY1, UWA70JATJ–122JATJ, UWA120JY1–270JY1)
EER *4(Heating)
5.3 5.7 7.7 9.4 — 11.8 15.8 18.5
YAL9.45 11.44 10.22 — 9.81 11.239.47 11.49 10.25 — 9.87 11.24
TAL 9.74 9.999.74 10.01
YAL
Power comsumption *1(Cooling) 6.8 6.8 8.9 — 11.8 13.6
6.8 6.8 8.9 — 11.8 13.6
Y1TAL 18.6 20.6
18.6 20.6
YAL
Power comsumption(Heating) 6.2 5.7 8.3 — 11.3 12.4
6.2 5.7 8.3 — 11.3 12.4
Y1TAL
kW
kW 17.4 19.417.4 19.4
Net capacity (Btu/h)Unit power comsumption (W)(Compressor + Outdoor fan motor)
EER =
Net capacity (Btu/h)Unit power comsumption (W)(Compressor + Outdoor fan motor)
EER =
°CDB 21 to 52 (UAT06KAY1/TAL/YAL–UAT21KAY1/TAL/YAL, UAT30HY1)
-10 to 15.55 to 52
Operation range (Outdoor temp.)
Operation range(Outdoor temp.)
CoolingHeating
°CDB°CWB