13
FTXL-G Wall Mounted Unit Air Conditioners Technical Data www.daikin.eu
Transcript
Page 1: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

FTXL-G

W a l l M o u n t e d U n i t

Air Conditioners

Technical Data

w w w . d a i k i n . e u

EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34 PM

Page 2: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

FTXL-G

W a l l M o u n t e d U n i t

Air Conditioners

Technical Data

w w w . d a i k i n . e u

EEDEN10-003_01_FTXL-G2V1B.pdf 2 7/6/2010 4:01:43 PM

Page 3: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Split - Sky Air® • Indoor Units 1

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

TABLE OF CONTENTSFTXL-G2V1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 5Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

!

EEDEN10-003_01_FTXL-G2V1B.pdf 3 7/6/2010 4:01:44 PM

Page 4: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

• Split - Sky Air® • Indoor Units2

1 Features

Indoor Unit Split - Sk FTXL-G2V1B Wall Mounte • Energy efficient: full range A class energy labels (COP = 4.58/EER = 4.55)

• High heating capacity: up to 6.6 kW

• 2 area intelligent eye: air flow is sent to the area in a room where no person is detected

• Energy saving during stand by mode: reduction of energy from 10W to 2W

• Weekly timer: allows to program the unit on a weekly basis

• Flat front panel: its stylish appearance blends easily within any interior décor and is more easy to clean.

• Comfort mode reassures draught free operation

• 3D air flow

• Dual air discharge flow for better air distribution

• ECONO mode decreases power consumption so that other appliances that need large power supply can be used

• Indoor / outdoor unit silent operation

• Powerful mode can be selected for rapid cooling or heating

• Titanium apatite photocatalytic air purification filter absorbs microscopic particles, decomposes odours and even deactivates bacteria and viruses

standard

integrated titanium apatite

EEDEN10-003_01_FTXL-G2V1B.pdf 4 7/6/2010 4:01:44 PM

Page 5: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Split - Sky Air® • Indoor Units 3

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

2 Specifications

2-1 For indoor units only FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B

Nominal input (Indoor only)

Cooling kW 0.026 0.024 0.026Heating kW 0.028 0.030 0.032

2-2 Technical Specifications FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B

Casing Colour WhiteDimensions Packing Height mm 366 366 366

Width mm 870 870 870Depth mm 274 274 274

Unit Height mm 295 295 295Width mm 800 800 800Depth mm 215 215 215

Weight Unit kg 10 10 10Packed Unit kg 14 14 14

Heat Exchanger Dimensions Length mm 605 + 602.7Nr of Rows 2 + 1Fin Pitch mm 1.2 + 1.6Nr of Stages 18 + 12

Tube type ø6.35 Hi-XUFin Type ML fin (Multi louvre)

Fan Type Cross flow fanAir Flow Rate Cooling High m³/min 10.4 9.1 10.2

Medium m³/min 7.7 7.7 8.6Low m³/min 4.8 6.3 7.0Silent Operation m³/min 3.5 5.4 6.0

Heating High m³/min 10.6 11.2 11.0Medium m³/min 8.5 9.4 9.3Low m³/min 6.4 7.7 7.6Silent Operation m³/min 5.4 6.8 6.7

Cooling High cfm 367 321 360Medium cfm 270 273 305Low cfm 170 221 246Silent Operation cfm 125 190 212

Heating High cfm 374 395 388Medium cfm 302 333 330Low cfm 226 271 267Silent Operation cfm 191 240 236

Fan Motor Model KFD-280-23-8ANumber of steps 5 steps, silent and auto

Motor Speed (cooling) High rpm 1,370 1,310 1,390Medium rpm 1,090 1,170 1,230Low rpm 800 1,020 1,060Silent Operation rpm 670 930 960

Speed (heating) High rpm 1,370 1,410 1,440Medium rpm 1,160 1,230 1,270Low rpm 940 1,050 1,090Silent Operation rpm 840 960 1,000

Fan Motor Output (high) W 23 23 23Cooling Sound Power High dBA 58 58 59

Sound Pressure High dBA 42 42 43Medium dBA 34 38 39Low dBA 26 33 34Silent Operation dBA 23 30 31

Heating Sound Power High dBA 58 58 60Sound Pressure High dBA 42 42 44

Medium dBA 36 38 39Low dBA 29 33 34Silent Operation dBA 26 30 31

Refrigerant Type R-410A

EEDEN10-003_01_FTXL-G2V1B.pdf 5 7/6/2010 4:01:44 PM

Page 6: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

• Split - Sky Air® • Indoor Units4

2 Specifications

Piping connections Liquid (OD) Diameter (OD) mm 6.35 6.35 6.35Gas Diameter (OD) mm 9.52 9.52 12.7Drain Diameter (OD) mm 18 18 18Heat Insulation Both liquid and gas pipes

Air Filter Removable/washable/Mildew proofAir direction control Right, Left, Horizontal, DownwardTemperature control Microcomputer controlStandard Accessories Item Titanium apatite photocatalytic air purification filter

Quantity 2 2 2Item Operation manualQuantity 2 2 2Item Installation manualQuantity 1 1 1Item Wireless remote controlQuantity 1 1 1Item BatteriesQuantity 2 2 2Item Remote control holderQuantity 1 1 1Item Indoor unit fixing screwsQuantity 2 2 2Item Mounting plateQuantity 1 1 1

2-3 Electrical Specifications FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B

Power Supply Name V1Phase 1~Frequency Hz 50Voltage V 220-230-240

Current Nominal running current (RLA)

Cooling A 0.12-0.12-0.11 0.11-0.11-0.10 0.12-0.12-0.11Heating A 0.13-0.13-0.12 0.14-0.14-0.13 0.15-0.14-0.14

Wiring connections For Power Supply Quantity 3 3 3Remark 4 for interunit wiring (including earth wiring)

2-2 Technical Specifications FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B

EEDEN10-003_01_FTXL-G2V1B.pdf 6 7/6/2010 4:01:44 PM

Page 7: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Split - Sky Air® • Indoor Units 5

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

3 Dimensional drawing & centre of gravity3 - 1 Dimensional drawingFTXL20-25G

3D058919A

Air flow (Indoor)The mark (→) shows piping direction

50 MinSpace for

maintenanceSpace for

maintenance

50 Min

REQUIRED SPACE

30 M

inSp

ace f

or pe

rform

ance

Gas pipe Ø9.5 CuT(The length of pipe outside the unit: about 350) Liquid pipe Ø6.4 CuT(The length of pipe outside the unit: about 400)

Drain hose (Connecting part I.D. Ø14O.D. Ø18The hose length of outside the unit is approx. 465)

Wall hole for embedded piping Ø65 hole Wall hole

Ø65 hole

STANDARD LOCATIONS OF WALL HOLES

Right/left (automatic)

Heating FanCooling, dry

INFRARED REMOTE CONTROL(ARC452A3)

Signal transmitterModel name plate

BLADE ANGLES

Left Right

Rear

Front panel fixed screws(inside)

Bottom Flaps Signal receiverIntelligent eye sensor

Operation lampTimer lampIntelligent eye lampIndoor unit ON/OFF switchRoom temp. thermistor (Inside)

Terminal block with earth terminal

Name plate

Including mounting plate

Up/down(Automatic)

FTXL35G

3D058920A

Air flow (Indoor)The mark (→) shows piping direction

50 MinSpace for

maintenanceSpace for

maintenance

50 Min

REQUIRED SPACE

30 M

inSp

ace f

or pe

rform

ance

Gas pipe Ø12.7 CuT(The length of pipe outside the unit: about 350) Liquid pipe Ø6.4 CuT(The length of pipe outside the unit: about 400)

Drain hose (Connecting part I.D. Ø14O.D. Ø18The hose length of outside the unit is approx. 465)

Wall hole for embedded piping Ø65 hole Wall hole

Ø65 hole

STANDARD LOCATIONS OF WALL HOLES

Right/left (automatic)

Heating FanCooling, dry

INFRARED REMOTE CONTROL(ARC452A3)

Signal transmitterModel name plate

BLADE ANGLES

Left Right

Rear

Front panel fixed screws(inside)

Bottom Flaps Signal receiverIntelligent eye sensor

Operation lampTimer lampIntelligent eye lampIndoor unit ON/OFF switchRoom temp. thermistor (Inside)

Terminal block with earth terminal

Name plate

Including mounting plate

Up/down(Automatic)

EEDEN10-003_01_FTXL-G2V1B.pdf 7 7/6/2010 4:01:44 PM

Page 8: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

• Split - Sky Air® • Indoor Units6

3 Dimensional drawing & centre of gravity3 - 2 Centre of gravity

FTXL20-35G

4D059112B

EEDEN10-003_01_FTXL-G2V1B.pdf 8 7/6/2010 4:01:49 PM

Page 9: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Split - Sky Air® • Indoor Units 7

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

4 Piping diagram

FTXL20-25G

4D058897C

INDOOR UNIT

Heat exchanger

Thermistor on heat exch.

Fan motor

Cross flow fan

Field piping

Field piping9.5CuT9.5CuT

6.4CuT

Refrigerant flowCooling

Heating

6.4CuT

FTXL35G

4D058898C

INDOOR UNIT

Heat exchanger

Thermistor on heat exch.

Fan motor

Cross flow fan Field piping

Field piping9.5CuT12.7CuT

6.4CuT

Refrigerant flowCooling

Heating

6.4CuT

EEDEN10-003_01_FTXL-G2V1B.pdf 9 7/6/2010 4:01:50 PM

Page 10: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

• Split - Sky Air® • Indoor Units8

5 Wiring diagram5 - 1 Wiring diagram

FTXL20-35G

NOTES

1 Size: length 70 x width 120.2 Refer to purchasing specification AS303002, unless otherwise specified.3 This drawing was drawn on CAD system.

3D058246B

INFRARED REMOTE

CONTROL

: Frame ground: Fuse: Pilot lamp: Fan motor: Swing motor: Printed circuit board: Thermistor: Connector: Operation switch: Terminal strip: Protective earth

RECTIFIER

TRANSMISSION CIRCUIT

WIRING DIAGRAM

FGF1UH1P~H3PM1FM1S~M3SPCB1~PCB4R1T, R2TS1~S49S1WX1M

CAUTIONNote that operation will restart automatically if the main power supply is turned off and than back on again.

FIELD WIRING

INDOOR

INTELLIGENT EYE SENSOR

SIGNAL RECEIVER

OUTDOOR

EEDEN10-003_01_FTXL-G2V1B.pdf 10 7/6/2010 4:01:53 PM

Page 11: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Split - Sky Air® • Indoor Units 9

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

6 Sound data6 - 1 Sound pressure spectrum

EEDEN10-003_01_FTXL-G2V1B.pdf 11 7/6/2010 4:01:56 PM

Page 12: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

• Indoor Units • Wall Mounted Unit • FTXL-G2V1B

• Split - Sky Air® • Indoor Units10

6 Sound data6 - 1 Sound pressure spectrum

!

EEDEN10-003_01_FTXL-G2V1B.pdf 12 7/6/2010 4:01:57 PM

Page 13: Air Conditioners Technical Data - ΚΛΙΜΑΜΗΧΑΝΙΚΗ · 2017-05-05 · FTXL-G Wall Mounted Unit Air Conditioners Technical Data EEDEN10-003_01_FTXL-G2V1B.pdf 1 7/6/2010 4:01:34

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

Daikin’s unique position as a manufacturer of air

conditioning equipment, compressors and refrigerants

has led to its close involvement in environmental issues.

For several years Daikin has had the intention to become

a leader in the provision of products that have limited

impact on the environment. This challenge demands the

eco design and development of a wide range of products

and an energy management system, resulting in energy

conservation and a reduction of waste.

Daikin Europe N.V. is participating in the EUROVENT

Certification Programme. Products are as listed in the

EUROVENT Directory of Certified Products. Multi units are

Eurovent certified for combinations up to 2 indoor units

Daikin products are distributed by:

EE

DE

N1

0-0

03

• 0

6/1

0 •

Co

py

rig

ht

Da

ikin

Th

e p

rese

nt

pu

blic

ati

on

su

pe

rse

de

s E

ED

EN

09

-00

3

Pre

par

ed

in B

elg

ium

by

Lan

no

o (

ww

w.la

nn

oo

pri

nt.

be

), a

com

pan

y w

ho

se c

on

cern

for

the

en

viro

nm

en

t is

se

t in

th

e E

MA

S an

d IS

O 1

40

01

sys

tem

s.

Re

spo

nsi

ble

Ed

ito

r: D

aik

in E

uro

pe

N.V

., Z

an

dv

oo

rde

stra

at

30

0,

B-8

40

0 O

ost

en

de

The present publication is drawn up by way of information only and does not constitute an offer binding

upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its

knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for

particular purpose of its content and the products and services presented therein. Specifications are subject

to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect

damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All

content is copyrighted by Daikin Europe N.V..

EEDEN10-003_01_FTXL-G2V1B.pdf 13 7/6/2010 4:01:57 PM