Air ConditioningLight Commercial, Commercial and IndustrialJuly 2020
Air Conditioning
2 systemair
systemair 3
Contents
Systemair Group 4Systemair Air Conditioning 10
Air Cooled Chillers, Heat Pumps, Condensing Units 14Residential Heat Pumps 86Multipurpose Units 93Water Cooled Chillers, Heat Pumps, Condenserless Units 102Free-Cooling modules 120Fan Coil Units 124Water Source Heat Pumps 146Rooftops 160Close Control Units 170Vertical Air Conditioners 183Hydrokit 189
4 systemair
The 36,000 square meters of the headquarters in Skinnskatteberg, Sweden and the 450 professionals who work there are just part of what today has become Systemair. Founded by Gerald Engstrom in 1974, today the company is present in 50 countries on 5 continents with manufacturing locations around the world, and is recognized as a key player in the HVAC industry.
Thanks to its results, Systemair looks with confidence towards the challenges of the future. In Sweden and in the World.
A constant growth company
Our commitment to qualitySystemair is certified in accordance with ISO 9001, ISO 14001, ATEX and European fire safety standard EN 12101-3. Our research and development laboratories are among the most modern in Europe. Our measure-ments are made in accordance with interna-tional standards such as AMCA and ISO.
Save energy and lower running costs!Our “Green Ventilation” label highlights products that combine energy economy with energy efficien-cy, offering end users high energy-saving potential. The ErP symbol indicates that the product fulfills EU demands on energy consumption.
Systemair worldwide
3 Distribution Centers
50 Countries with Sales Subsidiaries
Always close to you!
27 Production Facilities
Systemair Group From Sweden to the World
systemair 5
Net Sales in financial year 2018/19
Highest available credit ratingAAA
Listed on the
NASDAQ OMX Nordic Exchange
The company was founded by Chairman of the Board Gerald Engström with a pioneering idea in developing and introducing the circular in line centrifugal duct fan which has simplified ventilation systems.
1974
8.3 SEK bn (780M€)
10%Average annual growth in sales in the past 10 years
27in 19 countries
50
EmployeesOperating companies
Countries
80 6,300
Countries in which Systemair operates throughout Europe, North & South America, the Middle East, Asia and Africa
Systemairin figures
Production facilities
6 systemair
YOU CAN MEET SYSTEMAIR EVERYWHERE
RESIDENTIALA healthy air and a good tempera-ture in the home are important for us to feel well. Systemair offers complete systems for home venti-lation and air conditioning. Our air handling units with balanced venti-lation and heat recovery are ideal for homes and small offices. In our air handling units, humidity and temperature control come as a standard.
INDUSTRIAL PREMISESLarge factory areas need to be heated/cooled and ventilated. Our products evacuate impure air and ensure that working areas are kept at the right temperature. Our solutions help establish a healthy work environment, which in turn creates the conditions for higher productivity.
DATA CENTRESWith ever-increasing storage capacity and more compact equip-ment, there is a growing need for cooling in data centres. We supply both air handling units and preci-sion cooling units (close control units), to provide energy and cost-efficient cooling in data cen-tres.
MULTI-STOREY CAR PARKSIn multi-storey car parks, good ventilation is a safety issue. Our system of smoke extract fans meets strict requirements for car-bon dioxide control and the evac-uation of dangerous gases in the event of a fire. It can also deliver a reduction of up to 80 percent in energy consumption in day-to-day operation.
Systemair’s products and solutions are everywhere in society. We contribute to an optimal and healthy indoor climate in most places where people move around in day-to-day life. We do this with the conviction that good air quality contributes to a better quality of life. We also do it in an increasingly energy-efficient way, as our contribution to good energy conservation.
P100100101010001011
0010111
MARINE, OIL AND GASGood ventilation is crucial to both comfort and safety on ships. It could be ventilation and air condi-tioning on cruise liners, cargo hold ventilation on freighters or exhaust air ventilation from engine rooms.Quality requirements are high, as conditions are challenging. Our systems meet all requirements and are marine-certified.
systemair 7
SWIMMING POOLSDemands on ventilation in swim-ming pool halls are high. The indoor climate must be comfortable for guests, while continuous dehumidi-fication will protect the building from moisture damage over time.Our products offer reliable, fully automated ventilation, dehumidifi-cation and heating as required – in the most economical way.
HOSPITALS AND THE PHARMACEUTICAL INDUSTRYHospitals are demanding environ-ments in terms of purity and tem-perature of the air. Right AC and ventilation systems, combined with our products and solutions, create an optimal indoor climate. The purity requirements are satis-fied via hygiene-certified units and effective filters.
TUNNELSEffective ventilation is a safety issue both during the construction phase of tunnel projects and when tunnels are in operation.Systemair’s tunnel fans ensure not only good air quality but also smoke evacuation. Our products meet all fire safety requirements and are simple to maintain.
PUBLIC AREAS AND SCHOOLSSchools and public buildings require custom ventilation and air conditioning systems. With our extensive product range, we can create an optimal solution that contributes to a healthy indoor cli-mate in public areas and helps to maintain the well-being of children at school all day.
OFFICES AND HOTELSWith its wide range of ventilation and air conditioning products, Systemair creates a healthy and comfortable indoor climate. We also offer smoke extract fans and exhaust fans, along with other sys-tem solutions to meet specific cus-tomer requirements. Our air han-dling units, chillers and fans are certified by Eurovent.
H
8 systemair
Systemair has an extensive range of products: air handling units from large central units to small residential units with energy recovery, air conditioning products from air cooled or water cooled chillers/heat pumps to water terminal units, fans including smoke extractor, tunnel/car park fans and explosion proof fans, air distribution products and fire dampers. These products are installed in a large variety of locations, including offices, shops, industrial buildings, healthcare premises, tunnels, parking garages, training facilities, sport centres, homes etc.
Air handling units
Air conditioning
Fans
Systemair Group We have all what you need
Systemair has a wide range of fans that covers all your application areas, from small offices to large industrial applications.
Circular and rectangular duct fans, Roof fans,High temperature fans, Explosion-proof fans,Plastic fans, Axial fans, Smoke extraction fans & pressure differential systems, Car park jet fans & control systems.
Systemair’s air conditioning products are suitable for a wide variety of applications such as offices, shopping centers, schools, hotels, public transports, residential buildings, industries and Data centres.
Our extensive range includes everything fromair-cooled and water-cooled chillers and heat pumps to rooftop units, water source heat pumps, water terminals, close control units and vertical air condi-tioners.
Systemair produces a wide range of air handling units for several applications, from small office to large industrial building. The full range has been developed to satisfy strict needs of low energy consumption.
Our range of AHUs includes modular and compact air handling units, as well as a range of products specially designed for residential applications.
systemair 9
Air distribution products
Fire safety products
Residential ventilation
Systemair product solutions are:
• Innovative and energy efficient• Simple to choose, install and maintain• Robust, stable and standardized• Performance tested, measured and documented in every detail.
Systemair develops, produces and delivers airdistribution products, diffusers and air flow control units. These components not only comply with the interior design requirements, but also make their own contribution to a pleasant indoor climate. Diffusers, grilles and air flow control.
Systemair fire and smoke control dampers are used to minimize the property damage and help with evacuation of occupants.Smoke extract fans, Fire and smoke dampers.
Systemair’s line of heat recovery ventilation units is ideal for homes, small offices and similar premises. They offer a high level of comfort both in terms of heating and clean air supply, along with significant energy savings.
Residential units and kitchen hoods.
www.systemair.com
10 systemair
Tillières-sur-Avre, France
Barlassina, Italy
RangeThe factory develops and manufactures a wide range of air conditioning products: Chillers & Heat Pumps, Fan Coil Units, Residential Heat Pumps, Water Source Heat Pumps, Rooftops, Vertical Air Conditioners.
Systemair AC SAS, the French factory of Systemair group, founded in 1947 by Paul Vallet, is a major player in manufacturing and distributing air conditioning systems on the european market.References are numerous and cover all lines of business including many energy-efficient office buildings, industrial sites, hotels, hospitals, shopping centers ... Our sales department is able to design “THE” solutions that fit your needs.The factory is ISO 9001certified and participates in the Eurovent certification programme insuring, by independent laboratories, the check of the technical specifications according to the international standards.
Production The factory in France, extends over a total area of 37.000 sqm with 200 employees.
RangeThe factory develops and manufactures a wide range of air conditioning products: Chillers & Heat Pumps, Condensing Units.
Systemair Srl, the Italian factory of Systemair Group has 70 years of experience in industrial production and is a major manufacturer on the HVAC market. Our 20 to 1.700 kW units are suitable for a wide range of applications of air conditioning and industrial processes.The factory is equipped with high tech equipment and has one of the most modern research centers in Europe for the development and testing of chillers and heat pumps.The range of product, that is Eurovent certified, consists of Air and Water cooled chillers and heat pumps as well as con-densing and condenserless units.
Production The factory in Italy extends over a total area of 33.400 sqm with 200 employees.
Systemair Air Conditioning Factories
systemair 11
AC SELECTThe new Systemair online selection program for all your Air Conditioning projects.
Smart & User-friendly
onlineselectionprogram
1. Connect2. Select “THE” unit that meets your needs3. Customize adding accessories & options4. Generate a price offer5. Download a complete and detailed unit and project report
With AC SELECT, it has never been that simple to use an AC selection program. Select and customize easily and quickly the air conditioning products that perfectly satisfy your requirements. This new program will provide you a performant and helpful asset for your business.
• Be green!• Be quick!• Get instantly all data.• Build complete projects.• Adopt a user-friendly program.
And that’s it! Quick, Easy and Precise
https://acselect.systemair.com
New
systemair 11
12 systemair
R&D laboratory test rig
Test RoomsAir & water cooled chiller and heat pump room
2 Airflow testing rooms
Semi-anechoic room
2 Psychometrics rooms and 1 calorimetric room
Adiabatic room
Prototype room
2 x 5000 liter Tank Vessels
Water Temperature Control
Humidity Control
Dedicated 600 kWHeat Pump
AirTemperatureControl
Dedicated 500 kWHeat Pump
Water temperature and air temperature are regulated thanks to a dedicated heat pump and an external cooling tower; the thermal inertia given by the 10.000 liter tanks assures tolerances within European Standard limits.
Laboratory Plant 500 kW
The Test room for Air Conditioning Chillers and Heat Pumps was built in 2003.
Test room upgrades were in: • 2004 - Test on Water Condensing Chillers. • 2007 - Increase max capacity to 600 kW. • 2012 - Glycoled water. Test at Air Temp. to -15 °C.
Accredited Test Laboratory according Eurovent references.
• 2013 - Brine Application for Industrial application. LWT -15°C and 40% of glycol.
Performance TestValidate technical data under standard and severe conditions
Test Room: Air & Water Cooled Chiller & Heat Pump Calorimetric room
Security TestEliminate any risk at start up
Reliability Test Validate real life of the unit
Acoustic Test Determine and decrease sound emissions
Component Test Qualify new technology advanced components
Witness TestPerformance, Acoustic Part load and seasonal efficiency test
Systemair Air Conditioning Laboratories
Systemair laboratoriesWhere ideas turn into solutions
systemair 13
Thanks to the app "MEDIA CENTER by Systemair", all our documentation is always available on your smartphone or tablet.
• Everywhere: on site, when travelling, in the office• Always available, even offline• Constantly updated Download MEDIA CENTER by Systemair
The world of Systemair is just a click away!
MEDIA CENTER by Systemair
We offer a wide range of online tools to assist in choosing the product or system best suited to your specific needs.All our documentation can be freely viewed online or downloaded without login or password.
14 systemair
RestaurantFlorence, Italy• Air Cooled Chiller: SYSCROLL 85 AIR
MUSEUM OF MASTIC
Chios Island, Greece
• Air Cooled Chillers: 2 SYSCROLL 240 AIR CO
GRAND HOTEL TERME DI AUGUSTO
Ischia, Italy
• Air Cooled Heat Pumps: SYSCROLL 660 AIR EVO HP and MINI SYSAQUA DCI
BEIRUT ARAB UNIVERSITY - FACULTY OF ARTS AND DESIGN
Beirut, Lebanon
• 4 Air Cooled Heat Pumps: SYSCROLL 620 AIR EVO HP
H
14 systemair
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 15
AIR COOLED CHILLERS, HEAT PUMPS, CONDENSING UNITS AND RESIDENTIAL HEAT PUMPS
Energy efficiency, perfect air quality and comfort!
Our hydronic systems offer the perfect combination of comfort and high efficiency. They are perfect for any type of building. The air cooled chiller variant of the system is also a fundamental part of many industrial processes.
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 15
16 systemair
New
AC CLOUD
AC CLOUD
Air Cooled Chillers, Heat Pumps & Condensing units
VLS/VLH/VLC704-1204 176-307 kW 200-337 kW R410A Scroll Plate Air cooledPage 52
HFC
MINI SYSAQUA DCI 05-16 5,0-14,5 kW 6,2-16 kW R410A Rotary Inverter Plate Air cooled DC MotorPage 28
HFC
ErP2018
ErP2018
ErP2018
2021Ready.
ErP20182021
2021Ready.
ErP20182021
SYSCROLL 20-30 AIR EVO HP 20-36 kW 20-34 kW R410A Scroll Inverter Plate Air cooledPage 32
HFC
AQVL/AQVH/AQVC85-140 83-137 kW 91-147 kW R410A Scroll Plate Air cooledPage 44
HFC
SYSCROLL 140-360 AIR EVO CO/HP/RE 144-361 kW 145-361 kW R410A Scroll Plate Air cooledPage 58
HFC
SYSAQUA BLUE L/H 31,7 kW 35,4 kW R290 Scroll Plate Air cooledPage 34
ErP2018
2021Ready.
ErP20182021
SYSAQUA 20-40 L/H/RE 19-41 kW 20-42 kW R410A Scroll Plate Air cooledPage 36
HFC
SYSAQUA 45-125 L/H/RE 47-130 kW 49-119 kW R410A Scroll Plate Air cooledPage 40
HFC
ErP20182021
2021Ready.
2021Ready.
ErP20182021
SYSAQUA 140-210 L/H 125-209 kW 144-218 kW R410A Scroll Plate Air cooledPage 50
HFC
AC CLOUD
AC CLOUD
SYSHP MINI DCI 07-16 6,3-13,8 kW 6,7-16,2 kW R32 Domestic Hot Water DC MotorPage 30
HFC
R290
R32
ECO
2021Ready.
ErP20182021
Q4 2020
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 17
New
SYSCREW 300-1400 AIR CO 295-1.395 kW R134a Screw Shell & Tube Air cooled Industrial processPage 82
HFC
SYSCREW 370-1250 AIR EVO CO 360-1.250 kW R134a R513A Screw Shell & Tube Air cooledPage 76
HFC
SYSCROLL 240-660 AIR CO/HP/RE 238-654 kW 256-679 kW R410A Scroll Plate Air cooledPage 68
HFC
SYSCROLL 400-900AIR EVO CO/HP 399-897 kW 404-902 kW R410A Scroll Plate Air cooledPage 64
HFC
Low-temperature Heat PumpsCOMMISSION REGULATION (EU) No813/2013 Minimum ηsh to be Ecodesign compliant
EcodesignLow-temperature Heat Pumps / Air to Water Comfort chillers
ErP2018
HFOHFC
2021Ready.
ErP20182021
ErP2018
ErP2018
Enter the Era of connected units and make significant savings!
Offering more than reliable products is the Systemair’s aim. From that perspective, we created AC CLOUD. With
this new software, you will get the control of all your units at anytime and from anywhere. And it will help you to decrease your energy consumption and optimize your
maintenance interventions!
NEW
Available with SYSAQUA units
100
110
120
130
140
150
160
170
2015 2016 2017 2018 2019 2020 2021 2022
ηsc / ηsh
149
161
115
125
Sept. 2015
Sept. 2017
Jan. 2018
Jan. 2021
years
161
179
Jan. 2018
Jan. 2021
180
Air to Water Comfort chillersCOMMISSION REGULATION (EU) No2016/2281 <400 kw: Minimum ηsc to be Ecodesign compliant >400 kw: Minimum ηsc to be Ecodesign compliant
SYSCREW 380-1260 AIR EVO CO HSE 366-1.241 kW R134a R513A Screw Shell & Tube Air cooledPage 72
HFC
HFOHFC
2021Ready.
ErP20182021
AC CLOUD
18 systemair
Residential Heat Pumps
AQUASCOP HT V2 5,4-15,6 kW R407C Scroll Plate Air cooledPage 86
HFC
AQUASCOP HT SPLIT 5,4-15,6 kW R407C Scroll Plate Air cooledPage 90
HFC
Product Size Heating Capacity (A7°C/W35°C) COP Flow Rate Acoustic Power dB(A)
Dimensions - outdoor unit (LxHxW)
AQUA
SCOP
HT
V2 AQUASCOP HT V2 12-6 6,3 kW 4,12 1.030 l/h 67 1.457 x 1.308 x 516
AQUASCOP HT V2 14-7 7,4 kW 4,25 1.370 l/h 67 1.457 x 1.308 x 516
AQUASCOPHT V2 18-9 9,0 kW 4,28 1.580 l/h 67 1.457 x 1.308 x 516
AQUA
SCOP
HT
SPLI
T AQUASCOP HT SPLIT 126 6,3 kW 4,12 1.030 l/h 65 1.457 x 1.308 x 516
AQUASCOP HT SPLIT 147 7,4 kW 4,25 1.370 l/h 65 1.457 x 1.308 x 516
AQUASCOP HT SPLIT 18-9 9,0 kW 4,28 1.580 l/h 65 1.457 x 1.308 x 516
Quick selection guide - Residential Heat Pumps
Page 86
Page 90
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 19
Quick selection guide - Air Cooled Heat Pumps: page 23 Quick selection guide - Condensing units: page 25
Quick selection guide - Air Cooled Chillers
Product Size Cooling capacity SEER Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSA
QUA
BLUE
L
SYSAQUA BLUE 35.L
4,33 5,4 83 1.000 x 1.983 x 1.000
SYSA
QUA
20-4
0 L
SYSAQUA20.L 19,3 kW 4,59 3,5 75 1.000 x
1.983 x 1.000
SYSAQUA25.L 24,7 kW 4,45 4,6 75 1.000 x
1.983 x 1.000
SYSAQUA30.L 27,1 kW 4,23 4,9 75 1.000 x
1.983 x 1.000
SYSAQUA35.L 38,2 kW 4,42 6,5 76 1.000 x
1.983 x 1.000
SYSAQUA40.L 40,9 kW 4,21 6,7 76 1.000 x
1.983 x 1.000
SYSA
QUA
45-1
25 L
SYSAQUA45.L 49,8 kW 4,12 8,4 80 2.180 x
1.986 x 1.160
SYSAQUA55.L 56,9 kW 4,12 9,6 80 2.180 x
1.986 x 1.160
SYSAQUA65.L 69,7 kW 4,41 11,9 80 2.180 x
1.986 x 1.160
SYSAQUA75.L 75,8 kW 4,32 12,9 80 2.180 x
1.986 x 1.160
SYSAQUA90.L 97,0 kW 4,23 16,5 83 2.180 x
2.286 x 1.160
SYSAQUA105.L 112,7 kW 4,12 19,1 83 2.180 x
2.286 x 1.160
SYSAQUA125.L 129,8 kW 4,24 22,0 83 2.180 x
2.286 x 1.160
AQVL
85-
140
AQVL 85 83,3 kW 4,1 14,3 85 2.555 x
2.185 x 1.095
AQVL 95 93,3 kW 4,5 16,1 85 2.555 x
2.185 x 1.095
AQVL 105 102,6 kW 4,33 17,6 85 2.555 x
2.185 x 1.095
AQVL 115 110,5 kW 4,35 19,0 85 2.555 x
2.185 x 1.095
AQVL 125 121,6 kW 4,38 21,0 89 3.155 x
2.185 x 1.095
AQVL 140 136,5 kW 4,05 23,5 89 3.155 x
2.185 x 1.095
SYSA
QUA
140-
210
L
SYSAQUA140.L 134,0 kW 4,35 23,1 85 2.856 x
2.295 x 2.210
SYSAQUA150.L 147,0 kW 4,31 25,3 85 2.856 x
2.295 x 2.210
SYSAQUA170.L 161,2 kW 4,40 27,8 87 2.856 x
2.321 x 2.210
SYSAQUA190.L 187,8 kW 4,23 32,3 88 2.856 x
2.321 x 2.210
SYSAQUA210.L 208,8 kW 4,22 36,0 88 2.856 x
2.321 x 2.210
VLS
704-
1204
VLS 704 176,2 kW 3,8 30,4 93 4.300 x
2.300 x 1.100
VLS 804 198,1 kW 3,88 34,1 93 4.300 x
2.300 x 1.100
VLS 904 228,4 kW 3,8 39,3 94 4.300 x
2.300 x 1.100
VLS 1004
3,83 43,1 94 4.300 x 2.300 x 1.100
VLS 1104 3,8 48,0 95 4.300 x 2.300 x 1.100
VLS1204 3,8 52,8 95 4.300 x 2.300 x 1.100
250,3 kW
279,1 kW
306,9 kW
Q4 2020
31,7 kW
Page 34
Page 36
Page 40
Page 44
Page 50
Page 52
20 systemair
Product Size Cooling capacity SEER Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
140
-360
AIR
EVO
CO
SYSCROLL140 AIR EVO CO
144 kW 3,85 24,8 90 4.000 x 2.600 x 1.100
SYSCROLL 170 AIR EVO CO
168,6 kW 3,83 29,1 90 4.000 x 2.600 x 1.100
SYSCROLL 230 AIR EVO CO
229,9 kW 4,08 39,6 92 3.500 x 2.600 x 2.150
SYSCROLL 260 AIR EVO CO
262,6 kW 4,1 45,2 93 3.500 x 2.600 x 2.150
SYSCROLL 280 AIR EVO CO
283,5 kW 4,0 48,8 93 3.500 x 2.600 x 2.150
SYSCROLL 300 AIR EVO CO
309,3 kW 4,03 53,2 94 4.550 x 2.600 x 2.150
SYSCROLL 330 AIR EVO CO
330,3 kW 4,05 56,9 95 4.550 x 2.600 x 2.150
SYSCROLL 360 AIR EVO CO
360,7 kW 4,0 62,1 95 4.550 x 2.600 x 2.150
SYSC
ROLL
400
-900
AIR
EVO
CO
SYSCROLL 400 AIR EVO CO
398,8 kW 4,5 68,6 92 4.580 x 2.500 x 2.175
SYSCROLL 450 AIR EVO CO
446,1 kW 4,43 76,8 93 5.620 x 2.500 x 2.175
SYSCROLL 490 AIR EVO CO
487,7 kW 4,53 84,0 93 6.680 x 2.500 x 2.175
SYSCROLL 530 AIR EVO CO
533,9 kW 4,4 91,9 94 6.680 x 2.500 x 2.175
SYSCROLL 600 AIR EVO CO
597,1 kW 4,58 103 94 7.760 x 2.500 x 2.175
SYSCROLL 670 AIR EVO CO
4,68 115 94 7.760 x 2.500 x 2.175
SYSCROLL 750 AIR EVO CO
4,5 129 95 8.900 x 2.500 x 2.175
SYSCROLL 800 AIR EVO CO
4,5 138 95 8.900 x 2.500 x 2.175
SYSCROLL 850 AIR EVO CO
4,43 146 95 9950 x 2500 x 2175
SYSCROLL 900 AIR EVO CO
4,5 155 96 11.000 x 2.500 x 2.175
SYSC
ROLL
240
-660
AIR
CO
SYSCROLL 240 AIR CO
238,1 kW 3,93 41,0 93 3.500 x 2.600 x 2.150
SYSCROLL 270 AIR CO
267,4 kW 3,8 46,1 93 3.500 x 2.600 x 2.150
SYSCROLL 290 AIR CO
287,4 kW 3,85 49,6 94 3.500 x 2.600 x 2.150
SYSCROLL 320 AIR CO
316,1 kW 3,98 54,4 94 3.500 x 2.600 x 2.150
SYSCROLL 360 AIR CO
362 kW 3,93 62,4 94 4.550 x 2.600 x 2.150
SYSCROLL 420 AIR CO
414,2 kW 4,18 71,4 95 4.550 x 2.600 x 2.150
SYSCROLL 470 AIR CO
469,6 kW 4,13 80,9 95 5.600 x 2.600 x 2.150
SYSCROLL 540 AIR CO
533,7 kW 4,38 92,0 96 5.600 x 2.600 x 2.150
SYSCROLL 590 AIR CO
588,9 kW 4,4 102 96 6.650 x 2.600 x 2.150
SYSCROLL 660 AIR CO
4,43 113 97 6.650 x 2.600 x 2.150
797,9 kW
847,2 kW
896,7 kW
748,3 kW
667,3 kW
654,2 kW
Page 58
Page 64
Page 68
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 21
Product Size Cooling capacity SEER Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
REW
380
-126
0 AI
R EV
O HS
E R5
13A
SYSCREW 380 AIR EVO HSE
365,7 kW 4,53 62,8 97 4.660 x 2.510 x 2.192
SYSCREW 440 AIR EVO HSE
443,0 kW 4,66 76,1 98 5.712 x 2.510 x 2.192
SYSCREW 510 AIR EVO HSE
500,2 kW 4,65 85,9 100 5.712 x 2.510 x 2.192
SYSCREW 590 AIR EVO HSE
565,8 kW 4,80 97,2 100 6.764 x 2.510 x 2.192
SYSCREW 660 AIR EVO HSE
643,5 kW 4,66 111 100 7.816 x 2.510 x 2.192
SYSCREW 730 AIR EVO HSE
704,3 kW 4,56 121 101 7.816 x 2.510 x 2.192
SYSCREW 810 AIR EVO HSE
778,1 kW 4,62 134 101 8.868 x 2.510 x 2.192
SYSCREW 900 AIR EVO HSE
896,9 kW 4,56 154 102 9.920 x 2.510 x 2.192
SYSCREW 980 AIR EVO HSE
983,5 kW 4,60 169 102 10.972 x 2.510 x 2.192
SYSCREW 1060 AIR EVO HSE
1047,4 kW 4,87 180 103 12.024 x 2.510 x 2.192
SYSCREW 1160 AIR EVO HSE
1154,0 kW 4,86 198 103 13.076 x 2.510 x 2.192
SYSCREW 1260 AIR EVO HSE
1240,5 kW 4,85 213 103 13.076 x 2.510 x 2.192
SYSC
REW
370
-125
0 AI
R EV
O CO
R13
4a
SYSCREW 370 AIR EVO CO
364,1 kW 4,13 62,6 97 4.600 x 2.510 x 2.200
SYSCREW 400 AIR EVO CO
414,5 kW 4,13 71,3 98 5.700 x 2.510 x 2.200
SYSCREW 450 AIR EVO CO
445,5 kW 4,13 76,6 98 5.700 x 2.510 x 2.200
SYSCREW 500 AIR EVO CO
502,9 kW 4,13 86,5 98 5.700 x 2.510 x 2.200
SYSCREW 570 AIR EVO CO
562,1 kW 4,13 96,7 99 6.700 x 2.510 x 2.200
SYSCREW 650 AIR EVO CO
625,5 kW 4,13 108 99 6.700 x 2.510 x 2.200
SYSCREW 700 AIR EVO CO
712,9 kW 4,13 123 99 7.800 x 2.510 x 2.200
SYSCREW 750 AIR EVO CO
749,2 kW 4,13 129 100 7.800 x 2.510 x 2.200
SYSCREW 850 AIR EVO CO
839 kW 4,1 144 100 8.800 x 2.510 x 2.200
SYSCREW 950 AIR EVO CO
961,8 kW 4,13 165 101 9.900 x 2.510 x 2.200
SYSCREW 1000 AIR EVO CO
1.019 kW 4,13 175 101 10.900 x 2.510 x 2.200
SYSCREW 1100 AIR EVO CO
1.117,90 kW 4,18 192 102 12.000 x 2.510 x 2.200
SYSCREW 1250 AIR EVO CO 1.249,1 kW 4,22 215 103 13.000 x
2.510 x 2.200
New
Page 72
Page 76
22 systemair
Product Size Cooling capacity SEER Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
REW
300
-140
0 AI
R CO
SYSCREW 300 AIR CO
294,8 kW 2,76 50,8 95 4.600 x 2.550 x 2.200
SYSCREW 360 AIR CO
365 kW 2,63 62,9 96 4.600 x 2.550 x 2.200
SYSCREW 410 AIR CO
413 kW 3,21 71,2 97 4.600 x 2.550 x 2.200
SYSCREW 450 AIR CO
445 kW 3,13 76,7 97 4.600 x 2.550 x 2.200
SYSCREW 480 AIR CO
480 kW 3,02 82,7 97 4.600 x 2.550 x 2.200
SYSCREW 500 AIR CO
505 kW 3,03 86,9 97 4.600 x 2.550 x 2.200
SYSCREW 540 AIR CO
540 kW 2,91 92,9 98 5.700 x 2.550 x 2.200
SYSCREW 580 AIR CO
575 kW 3,22 98,9 98 6.700 x 2.550 x 2.200
SYSCREW 650 AIR CO
652 kW 3,22 112 99 6.700 x 2.550 x 2.200
SYSCREW 720 AIR CO
713 kW 3,22 123 99 6.700 x 2.550 x 2.200
SYSCREW 800 AIR CO
794 kW 3,23 137 99 6.700 x 2.550 x 2.200
SYSCREW 850 AIR CO
851 kW 3,22 147 100 8.800 x 2.550 x 2.200
SYSCREW 910 AIR CO
909 kW 3,22 157 100 8.800 x 2.550 x 2.200
SYSCREW 970 AIR CO
971 kW 3,23 167 100 8.800 x 2.550 x 2.200
SYSCREW 1000 AIR CO
1.008 kW 3,25 174 100 8.800 x 2.550 x 2.200
SYSCREW1070 AIR CO
1.071 kW 3,24 184 100 9.900 x 2.550 x 2.200
SYSCREW1130 AIR CO
1.132 kW 3,3 195 101 10.900 x 2.550 x 2.200
SYSCREW 1170 AIR CO
1.172 kW 3,26 202 101 10.900 x 2.550 x 2.200
SYSCREW 1200 AIR CO
1.218 kW 3,22 210 101 10.900 x 2.550 x 2.200
SYSCREW 1300 AIR CO 3,23 227 102 12.000 x
2.550 x 2.200
SYSCREW1400 AIR CO 3,22 240 103 13.000 x
2.550 x 2.200
1.316 kW
1.395 kWPage 82
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 23
Quick selection guide - Air Cooled Chillers: page 19 Quick selection guide - Condensing units: page 25
Product Size Cooling & Heating capacity SEER SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
MIN
I SYS
AQUA
DCI
M.AQA05 DCI MONO
5 kW 6,2 kW 4,22 3,55 0,86 63 990 x
966 x 354
M.AQA07 DCI MONO
7 kW 8 kW 3,76 3,46 1,12 66 990 x
966 x 354
M.AQA10 DCI MONO
10 kW 11 kW 3,89 3,34 1,72 68 970 x
1.327 x 400
M.AQA12 DCI MONO
11,2 kW 12,3 kW 4,09 3,46 1,92 68 970 x
1.327 x 400
M.AQA12 DCI TRI
11,2 kW 12,3 kW 4,16 3,66 1,92 68 970 x
1.327 x 400
M.AQA14 DCI TRI
12,5 kW 13,8 kW 4,27 3,78 2,15 70 970 x
1.327 x 400
M.AQA16 DCI TRI
14,5 kW 16 kW 4,38 3,40 2,49 72 970 x
1.327 x 400
SYSH
P M
INI D
CI 0
7-16
SYSHP MINI DCI 7
6,45 kW 6,65 kW 4,99 4,47 1,12 60 1210 x
945 x 402SYSHP MINI DCI 9
8 kW 8,6 kW 4,92 4,51 1,37 67 1210 x
945 x 402
SYSHP MINI DCI 12
12,2 kW 12,3 kW 4,85 4,29 2,09 67 1404 x
1414 x 405
SYSHP MINI DCI 16
15,5 kW 16,3 kW 4,54 4,30 2,66 71 1404 x
1414 x 405
SYSC
ROLL
20-
30 A
IR E
VO H
P
SYSCROLL 20 AIR EVO HP
20 kW
20,4 kW3,75 3,43 3,64 74 1.477 x
1.615 x 539
SYSCROLL 30 AIR EVO HP
29 kW
26,1 kW4,07 3,57 5,92 75 1.477 x
1.615 x 539
SYSA
QUA
BLUE
H
SYSAQUA BLUE 35.H
31,7 kW
35,4 kW 4,33 3,54 6,1 83 1.000 x
1.983 x 1.000
SYSA
QUA
20-4
0 H
SYSAQUA20.H 19,4 kW
19,5 kW 3,91 3,37 3,4 75 1.000 x 1.983 x 1.000
SYSAQUA25.H
25,3 kW 26,9 kW 3,87 3,27 4,7 75 1.000 x
1.983 x 1.000
SYSAQUA30.H
26,9 kW 29,7 kW 3,88 3,27 5,2 75 1.000 x
1.983 x 1.000
SYSAQUA35.H
35,8 kW 37,3 kW 3,68 3,36 6,5 76 1.000 x
1.983 x 1.000
SYSAQUA40.H
37,4 kW 41,6 kW 3,91 3,40 7,2 76 1.000 x
1.983 x 1.000
SYSA
QUA
45-1
25 H
SYSAQUA45.H 46,8 kW
48,5 kW 3,70 3,23 8,4 80 2.180 x 1.986 x 1.160
SYSAQUA55.H 53,3 kW 58,2 kW 3,86 3,27 10,2 80 2.180 x
1.986 x 1.160
SYSAQUA65.H 65,8 kW
67,3 kW 4,04 3,43 11,7 80 2.180 x 1.986 x 1.160
SYSAQUA75.H 71,6 kW
75,9 kW 3,99 3,40 13,2 80 2.180 x 1.986 x 1.160
SYSAQUA90.H 91,4 kW
88,1 kW 3,89 3,26 15,3 83 2.180 x 2.286 x 1.160
SYSAQUA105.H 3,88 3,31 17,6 83 2.180 x 2.286 x 1.160
SYSAQUA125.H 3,89 3,35 20,7 83 2.180 x 2.286 x 1.160
Quick selection guide - Air Cooled Heat Pumps
119,1 kW121,9 kW
106,2 kW101 kW
New
Page 28
Page 30
Page 32
Page 34Q4 2020
Page 36
Page 40
24 systemair
Product Size Cooling & Heating capacity SEER SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
AQVH
85-
140
AQVH 85 81 kW
91,5 kW 4,25 3,61 17,2 85 2.555 x 2.185 x 1.095
AQVH 95 90,1 kW
102,4 kW 4,68 3,64 17,8 85 2.555 x 2.185 x 1.095
AQVH 105 99,1 kW 4,63 3,78 19,3 85 2.555 x
2.185 x 1.095
AQVH 115 4,18 3,77 20.6 85 2.555 x 2.185 x 1.095
AQVH 125 4,33 3,47 23,3 89 3.155 x
2.185 x 1.095
AQVH 140 4,28 3,54 25,5 89 3.155 x 2.185 x 1.095
SYSA
QUA
140-
210
H
SYSAQUA140.H 125,4 kW
143,7 kW 3,87 3,32 24,8 85 2.856 x 2.295 x 2.210
SYSAQUA150.H 137,6 kW
153,7 kW 3,87 3,36 26,5 85 2.856 x 2.295 x 2.210
SYSAQUA170.H 150,9 kW
170,1 kW 3,91 3,31 29,6 87 2.856 x 2.321 x 2.210
SYSAQUA190.H 3,69 3,29 33,9 88 2.856 x
2.321 x 2.210
SYSAQUA210.H 3,68 3,23 37,9 88 2.856 x 2.321 x 2.210
VLH
704-
1204
VLH 704 173,2 kW
200,1 kW 3,63 3,41 34,7 93 4.300 x 2.300 x 1.100
VLH 804 197,1 kW
223,2 kW 3,55 3,42 38,6 93 4.300 x 2.300 x 1.100
VLH 904 226,4 kW
254,7 kW 3,35 3,28 43,6 94 4.300 x 2.300 x 1.100
VLH 1004 246,3 kW
270,8 kW 3,5 3,39 47,0 94 4.300 x 2.300 x 1.100
VLH 1104 273,1 kW
302,1 kW 3,53 3,20 52,3 95 4.300 x 2.300 x 1.100
VLH 1204 299,9 kW
3,43 3,19 58,4 95 4.300 x 2.300 x 1.100
SYSC
ROLL
140
-360
AIR
EVO
HP
SYSCROLL 140 AIR EVO HP
136,7 kW 144,9 kW 3,8 3,39 25,1 90 4.000 x
2.600 x 1.100SYSCROLL 170 AIR EVO HP
154,5 kW 165,7 kW 3,95 3,42 28,7 90 4.000 x
2.600 x 1.100SYSCROLL 230 AIR EVO HP
213,6 kW 229 kW 4,13 3,46 39,7 92 3.500 x
2.600 x 2.150SYSCROLL 260 AIR EVO HP
243,7 kW 262,3 kW 4,05 3,48 45,5 93 3.500 x
2.600 x 2.150SYSCROLL 280 AIR EVO HP
261,1 kW 279,6 kW 4,1 3,44 48,5 93 3.500 x
2.600 x 2.150SYSCROLL 300 AIR EVO HP
287,8 kW 305,6 kW 3,83 3,51 53,0 94 4.550 x
2.600 x 2.150SYSCROLL 330 AIR EVO HP
307,4 kW 327,2 kW 3,8 3,44 56,8 95 4.550 x
2.600 x 2.150SYSCROLL 360 AIR EVO HP
340,5 kW 3,93 3,48 62,7 95 4.550 x
2.600 x 2.150
SYSC
ROLL
400
-900
AIR
EVO
HP
SYSCROLL 400 AIR EVO HP
373,5 kW 404 kW 4,65 3,62 70,1 92 5.620 x 2.500
x 2.175SYSCROLL 450 AIR EVO HP
419,2 kW 450,9 kW 4,53 3,62 78,3 93 5.620 x 2.500
x 2.175SYSCROLL 490 AIR EVO HP
454,5 kW 492,7 kW 4,7 3,53 85,5 93 6.680 x 2.500
x 2.175SYSCROLL 530 AIR EVO HP
489,7 kW 532,1 kW 4,55 3,53 92,3 94 6.680 x 2.500
x 2.175SYSCROLL 580 AIR EVO HP
535,7 kW 585,8 kW 4,33 - 102 94 7.760 x 2.500
x 2.175SYSCROLL 620 AIR EVO HP
581,5 kW 627,7 kW 4,35 - 109 95 8.800 x 2.500
x 2.175SYSCROLL 670 AIR EVO HP
625,4 kW 677,8 kW 4,3 - 118 95 8.800 x 2.500
x 2.175SYSCROLL 750 AIR EVO HP
4,3 - 131 95 9.950 x 2.500 x 2175
SYSCROLL 800 AIR EVO HP 4,35 - 140 95 9.950 x 2.500
x 2.175SYSCROLL 850 AIR EVO HP 4,3 - 148 96 11.000 x 2.500
x 2.175
SYSCROLL 900 AIR EVO HP 4,3 - 156 96 11.000 x 2.500
x 2.175
194,9 kW195,4 kW
217,6 kW
337,4 kW
361,4 kW340,5 kW
146,9 kW
134 kW129,6 kW
115,6 kW119 kW
111 kW106,7 kW
901,6 kW838,7 kW
856,9 kW795,2 kW
807,3 kW748,1 kW
758,3 kW701,4 kW
175,8 kW
Page 44
Page 50
Page 52
Page 58
Page 64
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 25
Product Size Cooling capacity EER Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSA
QUA
25-1
25 R
E
SYSAQUA25.RE 32,5 kW 3,57 75 1.000 x
1.983 x 1.000
SYSAQUA30.RE 33,7 kW 3,44 75 1.000 x
1.983 x 1.000
SYSAQUA35.RE 43,1 kW 3,10 76 1.000 x
1.983 x 1.000
SYSAQUA40.RE 44,8 kW 3,18 76 1.000 x
1.983 x 1.000
SYSAQUA45.RE 57,3 kW 3,29 80 2.180 x
1.986 x 1.160
SYSAQUA55.RE 64,5 kW 3,19 79 2.180 x
1.986 x 1.160
SYSAQUA65.RE 72,3 kW 3,21 79 2.180 x
1.986 x 1.160
SYSAQUA75.RE 79,3 kW 3,13 79 2.180 x
1.986 x 1.160
SYSAQUA90.RE 103,9 kW 2,97 82 2.180 x
2.286 x 1.160
SYSAQUA105.RE 3,08 82 2.180 x 2.286 x 1.160
SYSAQUA125.RE 2,89 82 2.180 x 2.286 x 1.160
Product Size Cooling & Heating capacity SEER SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
240
-660
AIR
HP
SYSCROLL 240 AIR HP
216,5 kW 255,9 kW 4,25 3,39 44,3 93 3.500 x
2.600 x 2.150
SYSCROLL 270 AIR HP
251,6 kW 289,1 kW 4,25 3,50 50,0 93 3.500 x
2.600 x 2.150
SYSCROLL 290 AIR HP
263,8 kW 313,3 kW 4,1 3,38 54,2 94 3.500 x
2.600 x 2.150
SYSCROLL 320 AIR HP
287,1 kW 333 kW 3,83 3,59 57,8 94 3.500 x
2.600 x 2.150
SYSCROLL 360 AIR HP
330 kW 382,4 kW 4,18 3,51 66,3 94 4.550 x
2.600 x 2.150
SYSCROLL 420 AIR HP
380,7 kW 444 kW 3,85 3,64 76,9 95 4.550 x
2.600 x 2.150
SYSCROLL 470 AIR HP
435,1 kW 491,5 kW 3,85 3,42 85,2 95 5.600 x
2.600 x 2.150
SYSCROLL 540 AIR HP
481,9 kW 556,4 kW 4,22 - 96,4 96 5.600 x
2.600 x 2.150
SYSCROLL 590 AIR HP
530,7 kW 605 kW 4,3 - 105 96 6.650 x
2.600 x 2.150
SYSCROLL 660 AIR HP
580,6 kW4,25 - 118 97 6.650 x
2.600 x 2.150
Quick selection guide - Condensing units
119,6 kW
136,4 kW
Quick selection guide - Air Cooled Chillers: page 19 Quick selection guide - Air Cooled Heat Pumps: page 23
679,1 kWPage 68
Page 36
26 systemair
Product Size Cooling capacity EER Acousticpower dB(A)
Dimensions (LxHxW) without water tank
AQVC
85-
140
AQVC 85 92,1 kW 3,36 85 2.555 x
2.185 x 1.095
AQVC 95 103,2 kW 3,29 85 2.555 x
2.185 x 1.095
AQVC 105 113,2 kW 3,32 85 2.555 x
2.185 x 1.095
AQVC 115 121,8 kW 3,30 85 2.555 x
2.185 x 1.095
AQVC 125 134,7 kW 3,23 89 3.155 x
2.185 x 1.095
AQVC 140 3,23 89 3.155 x 2.185 x 1.095
VLC
704-
1204
VLC 704 199 kW 2,90 93 4.300 x
2.300 x 1.100
VLC 804 224 kW 3,00 93 4.300 x
2.300 x 1.100
VLC 904 258 kW 2,98 94 4.300 x
2.300 x 1.100
VLC 1004 283 kW 3,12 94 4.300 x
2.300 x 1.100
VLC 1104 315 kW 2,98 95 4.300 x
2.300 x 1.100
VLC 1204
2,90 95 4.300 x 2.300 x 1.100
SYSC
ROLL
140
-360
AIR
EVO
RE
SYSCROLL 140 AIR EVO RE
165 kW 3,61 90 4.000 x 2.600 x 1.100
SYSCROLL 170 AIR EVO RE
193,4 kW 3,48 90 4.000 x 2.600 x 1.100
SYSCROLL 230 AIR EVO RE
250,3 kW 3,36 92 3.500 x 2.600 x 2.150
SYSCROLL 260 AIR EVO RE
288,4 kW 3,42 93 3.500 x 2.600 x 2.150
SYSCROLL 280 AIR EVO RE
312,7 kW 3,42 93 3.500 x 2.600 x 2.150
SYSCROLL 300 AIR EVO RE
337,2 kW 3,39 94 4.550 x 2.600 x 2.150
SYSCROLL 330 AIR EVO RE 3,45 95 4.550 x
2.600 x 2.150
SYSCROLL 360 AIR EVO RE
3,37 95 4.550 x 2.600 x 2.150
SYSC
ROLL
240
-660
AIR
RE
SYSCROLL 240 AIR RE
267,5 kW 3,14 93 3.500 x 2.600 x 2.150
SYSCROLL 270 AIR RE
303,1 kW 2,99 93 3.500 x 2.600 x 2.150
SYSCROLL 290 AIR RE
330,7 kW 3,13 94 3.500 x 2.600 x 2.150
SYSCROLL 320 AIR RE
349,9 kW 3,07 94 3.500 x 2.600 x 2.150
SYSCROLL 360 AIR RE
403,2 kW 3,08 94 4.550 x 2.600 x 2.150
SYSCROLL 420 AIR RE
466,2 kW 3,07 95 4.550 x 2.600 x 2.150
SYSCROLL 470 AIR RE
518,8 kW 3,17 95 5.600 x 2.600 x 2.150
SYSCROLL 540 AIR RE
3,17 96 5.600 x 2.600 x 2.150
SYSCROLL 590 AIR RE
3,23 96 6.650 x 2.600 x 2.150
SYSCROLL 660 AIR RE
3,23 97 6.650 x 2.600 x 2.150
151 kW
347 kW
361,2 kW
394,5 kW
650,4 kW
726,7 kW
594,9 kW
Page 44
Page 52
Page 58
Page 68
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 27
AC CLOUD Enter the Era of connected units and make significant savings!
Decrease your energy consumption! Adjust your units’ settings precisely thanks to a relevant and a real-time energy consumption analysis.
Optimize your maintenance interventions! With one click, watch the operating state of your units, anticipate the dysfunctions and reduce your interventions on site.
Temperature data
AlarmsSet point adjustment
Time schedule
Diagnostic
Different access levels
Consumption’s monitoring
Data history
Units location
+-
˚ CAI
R CO
OLED
CHI
LLER
S&
HEAT
PUM
PS
AC CLOUD
28 systemair
The range at a glance 1 version:
HP (Heat Pump) 7 sizes Cooling capacity from 5,0 to 14,5 kW Heating capacity from 6,2 to 16,0 kW EER up to 3,39 SEER up to 4,38 SCOP up to 3,78 Outdoor Air Temperature (OAT): from -15°C to +46°C Leaving Water Temperature (LWT): from +4°C to +55°C
Equipment One refrigerant circuit with DC compressor Single pump with expansion tank Stainless steel plate heat exchanger with antifreeze
protection Low energy consumption DC fan(s) Blue fin coil Bi-flow electronic expansion valve Variable fan speed controller Softstarter Water differential pressure switch (sizes 10 to 16 only) Water flow switch (sizes 05 and 07 only) Coil guards
Air Cooled Heat PumpsMINI SYSAQUA DCI 05-16
Operating limitsMINI SYSAQUA DCI 05-16 - Heat Pump
CoolingLeaving water temperature °C from +4 to +20Outdoor air temperature °C from -5 to +46
HeatingLeaving water temperature °C from +30 to +55Outdoor air temperature °C from -15 to +27
Advantages
High performance → SCOP Very Quiet → Running most of the time at reduced
speed Wide operating limits in heating mode:
• Min/Max outdoor air temperature → -15/+27 [°C]• Min/Max leaving water temperature →+30/+55 [°C]
DC inverter technology for both compressor and fan(s) to adapt the unit capacity to the building heat demand
Operating with low water content “Plug and Play” units Eurovent certified
5,0-14,5 kW
Plate heat exchangerAir cooled
Rotary Inverter compressorHFC R410A
6,2-16,0 kW
DC Motor
HOTELSOFFICES SHOPS
A+
MINI SYSAQUA DCI 05-16 - Heat Pump M.AQA05 DCI M.AQA07 DCI M.AQA10 DCI M.AQA12 DCI M.AQA12 DCI M.AQA14 DCI M.AQA16 DCI
Minimum water volume L 20 20 20 20 20 20 20
Minimum water volume in the system
SCHOOLS RESIDENTIAL
-15°C
+55°C
Accessories and options
ON/OFF remote control
ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 29
MINI SYSAQUA DCI - Heat Pump M.AQA05 DCI M.AQA07 DCI M.AQA10 DCI M.AQA12 DCI M.AQA12 DCI M.AQA14 DCI M.AQA16 DCI
Cooling
Cooling Capacity1 kW 5,0 7,0 10,0 11,2 11,2 12,5 14,5Power input1 kW 1,55 2,26 3,03 3,38 3,38 3,91 4,68EER / Energy efficiency class1 3,23 / A 3,10 / A 3,39 / A 3,20 / A 3,31 / A 3,20 / A 3,10 /A
SEER4 4,22 3,76 3,89 4,09 4,16 4,27 4,38
hsc4 166 147 153 161 163 168 184
Nominal water flow (in the evaporator) m3/h 0,77 1,08 1,54 1,72 1,72 1,93 2,24
Heating
Heating Capacity2 kW 6,2 8,0 11,0 12,3 12,3 13,8 16,0Power input2 kW 1,90 2,54 3,24 3,78 3,72 4,25 4,85COP2 3,26 3,15 3,40 3,25 3,31 3,25 3,30COP3 4,60 4,10 4,34 4,45 4,56 4,51 4,21
SCOP4 3,55 3,46 3,34 3,46 3,66 3,78 3,40Energy efficiency class4 A+ A+ A+ A+ A+ A+ A+
hsh4 138,9 135,3 130,7 135,4 143,5 148,3 132,6
Nominal water flow (in the evaporator) m3/h 0,86 1,12 1,72 1,92 1,92 2,15 2,49Sound power level dB(A) 63 66 68 68 68 70 72Sound pressure level5 dB(A) 58 58 59 60 59 60 60Power supply V/ph/Hz 230/1/50 400/3+N/50
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Tested 1m away in front of the unit in a semi-anechoic room.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
MINI SYSAQUA DCI - Heat Pump M.AQA05 DCI M.AQA07 DCI M.AQA10 DCI M.AQA12 DCI M.AQA12 DCI M.AQA14 DCI M.AQA16 DCI
Hydraulic dataType of water connections Male gas threadedWater inlet/outlet diameter inch 1" 1" 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4WeightNet / Gross weight kg 81/91 81/91 110/121 110/121 110/121 111/122 111/122DimensionsLength mm 990 990 970 970 970 970 970Width mm 354 354 400 400 400 400 400Height mm 966 966 1.327 1.327 1.327 1.327 1.327
Physical features
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical performance
*ErP2018
30 systemair
SYSHP MINI DCI 07-16
6,3-13,8 kW 6,7-16,2 kW
R32
Domestic Hot Water
Operating limits
Advantages
Leaving water temperature up to 60 [°C] High efficiency and low noise thanks to the
DC Twin-rotary inverter compressor Multiple possibilities of application for heating,
cooling and DHW production Integration with solar panel and gas boiler Smart Grid function for photovoltaic systems Possibility of remote control with dedicated App or
via Modbus interface Operation guaranteed up to -25 °C in heating mode
and DHW production
SYSHP MINI DCI 07-16 - Heat Pump
CoolingLeaving water temperature °C from +5 to +25Outdoor air temperature °C from -5 to +43
HeatingLeaving water temperature °C from +25 to +60Outdoor air temperature °C from -25 to +35
DHW ProductionLeaving water temperature °C from +40 to +60Outdoor air temperature °C from -25 to +43
The range at a glance 1 version:
HP (Heat Pump) 4 sizes Cooling capacity from 6,3 to 13,8 kW Heating capacity from 6,7 to 16,2 kW EER up to 4,78 SEER up to 8,58 SCOP up to 4,51
Equipment One refrigerant circuit Power supply for models M.HP 07, 09 and 12 single
phase; M.HP 16 three-phase model Water circulator included, head 6 m (M.HP 07-09),
head 7.5 m (M.HP 12-16) Backup electric heater (only for M.HP12 DCI MONO
and M.HP16 DCI TRI) Programmable remote control Electronic expansion valve Fan with DC motor Single pump with expansion tank and plate exchanger Control via Wi-Fi
Residential Air Cooled Heat Pumps
+60 °C
up to
HOTELSOFFICES SHOPSRESIDENTIAL
Air cooled
Accessories and options
Electric heater
Rotary Inverter compressor
DC Motor
R32ErP2018
New
HFC
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 31
Physical featuresSYSHP MINI DCI - Heat Pump M.HP07 DCI MONO M.HP09 DCI MONO M.HP12 DCI MONO M.HP16 DCI TRI
Hydraulic dataWater piping connections Diameter inch 1” Female BSP 1 - 1/4” Female BSPWeightNet / Gross weight kg 91/109 91/109 158/178 168/189DimensionsLength mm 1.210 1.210 1.404 1.404Width mm 402 402 405 405Height mm 945 945 1.414 1.414
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical performanceSYSHP MINI DCI - Heat Pump M.HP07 DCI MONO M.HP09 DCI MONO M.HP12 DCI MONO M.HP16 DCI TRI
Cooling
Cooling Capacity1 kW 6,45 8,00 12,2 15,5 Power input1 kW 1,39 1,92 2,55 3,63 EER1 4,64 4,17 4,78 4,27 SEER3 8,58 7,88 7,50 6,78 Cooling Capacity2 kW 6,30 7,95 10,9 13,8 Power input2 kW 2,27 3,15 3,74 5,19 EER2 2,78 2,52 2,91 2,66 SEER3 4,99 4,92 4,85 4,54
Heating
Heating Capacity4 kW 6,65 8,60 12,3 16,3 Power input4 kW 1,35 1,87 2,56 3,63 COP4 4,93 4,60 4,81 4,49 Heating Capacity5 kW 6,70 8,60 12,40 16,20 Power input5 kW 1,88 2,50 3,52 4,70 COP5 3,56 3,44 3,52 3,45 Heating Capacity6 kW 6,80 8,60 11,90 16,10 Power input6 kW 2,42 3,13 4,28 5,83 COP6 2,81 2,75 2,78 2,76
SCOP4 4,47 4,51 4,29 4,30
hsh / Energy class3 176 / A+++ 177,3 / A+++ 168,8 / A++ 168,9 / A++
SCOP6 3,24 3,22 3,23 3,27
hsh / Energy class3 126,5 / A++ 125,7 / A++ 126,0 / A++ 127,9 / A++
Nominal water flow m³/h 1,12 1,37 2,09 2,66Sound power level (cooling)7 dB(A) 61 67 68 71Sound power level (heating) 7 dB(A) 60 67 67 71Power supply V/Ph/Hz 220-240/1/50 380-415/3/50
1 According EN14511-2013: chilled water inlet/outlet temperature: 23/18°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.3 According EN14825.4 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.5 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.6 According EN14511-2013: warm water inlet/outlet temperature: 47/55°C, outdoor ambient temperature 7°C DB/6°C WB.7 Sound power level values refers to ISO 3744 standard.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
*ErP2018
32 systemair
SYSCROLL 20-30 AIR EVO HP
The range at a glance 1 version:
HP (Heat Pump) 2 sizes Cooling capacity from 20,0 to 35,9 kW Heating capacity from 20,4 to 34,0 kW Operating range: from -10 to 45 °C cooling and from
-15 to 20 °C heating
Equipment Inverter driven compressor Plate evaporator (AISI 316) A single inverter driven 3-phase scroll compressor
equipped with brushless motor with variable frequency (20-120 Hz) One refrigerant circuit Bi-flow electronic expansion valve Multistage centrifugal pump as standard Bluefin coil Operating low water content in the plant Automatic circuit breaker Coil grilles Fan speed control Power factor corrector capacitors Sequence phases control Softstarter Water differential pressure switch Water filter
* Below 5°C, glycol is required. For operation below 0°C contact sales office.
Chillers suitable for operation without buffer tank for water content greater than 2,5 liters of water per kW of output.
SYSCROLL 20-30 AIR EVO HP - Heat Pump
CoolingLeaving water temperature* °C from -8 to +18∆ T water K from 3 to 7Outdoor air temperature °C from -10 to +45
HeatingLeaving water temperature* °C from +25 to +55∆ T water K from 3 to 7Outdoor air temperature °C from -15 to +20
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Inverter Air Cooled Heat Pumps
Air cooled
Scroll Inverter compressorHFC R410A
Advantages
Wide load variation capability:• Cooling operation → down to 30% and up to 140%
of nom. capacity• Heating operation → down to 40% and up to 130%
of nom. capacity Unit optimization for heating operation both for fan
coil and floor application Wide operating limits in heating mode:
• Min/Max outdoor air temperature → -15/+20 [°C]• Min/Max leaving water temperature →+25/+55 [°C]
Aeraulic independence between refrigerant circuit and condensing side
New fan motors (Erp compliant) with integrated grill, nozzle and condensers
20-36 kW 20-34 kW
-15°C
+55°C
HOTELSOFFICES SHOPS SCHOOLS RESIDENTIAL
Accessories and optionsBuffer tank placed under unitCoils treatmentsIn/Out Valve kitRemote on/offWater flow switch
Plate heat exchanger
ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 33
Technical performanceSYSCROLL 20-30 AIR EVO HP - Heat Pump 20 30
Cooling
Cooling Capacity (min/nom/max)2 kW 9,33 20,0 28,0 13,9 29,0 35,9Power input2 kW 2,38 4,15 6,61 3,51 7,24 13,0EER2 3,92 4,82 4,24 3,96 4,01 2,76Energy efficiency class (EER)2 A ACooling Capacity (min/nom/max)4 kW 6,60 20,0 25,2 9,43 28,5 31,1Power input4 kW 2,52 6,64 10,3 3,14 10,7 12,4EER4 2,62 3,01 2,45 3,00 2,66 2,51Energy efficiency class (EER)4 B CEER 75% 3,83 3,65EER 50% 4,53 4,48EER 25% 3,80 4,79
SEER5 3,75 4,08
hsc5 147 160
Nominal water flow (in the evaporator) m³/h 3,64 5,92
Heating
Heating Capacity (min/nom/max)1 kW 9,94 20,4 29,4 11,5 26,1 34,0Power input1 kW 2,98 5,02 8,37 3,01 6,45 9,80COP1 3,34 4,06 3,51 3,82 4,05 3,47Heating Capacity (min/nom/max)3 kW 8,90 20,4 27,4 10,2 26,1 33,9Power input3 kW 3,34 6,44 9,64 3,97 8,42 11,6COP3 2,66 3,17 2,84 2,57 3,10 2,91
SCOP / Energy efficiency class5 3,43 / A+ 3,57 / A+
hsh5 134 140
Nominal water flow (in the evaporator) m³/h 3,64 5,92Sound power level6 dB(A) 74 75Sound pressure level at 10 m7 dB(A) 43 44Power supply V/ph/Hz 400/3+N/50 (Nominal) 400/3+N/50 (Nominal)
1 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.2 According EN14511-2013: chilled water inlet/outlet temperature: 23/18°C, outdoor ambient temperature 35°C. 3 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.5 According EN14825.6 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.7 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
Hydraulic dataType of water connections (evaporator) Male gas threadedWater Inlet/Outlet diameter inch 1” 1/4WeightOperating weight kg 260 275DimensionsLength mm 1.477 1.477Width mm 539 539Height mm 1.615 1.615
Physical featuresSYSCROLL 20-30 AIR EVO HP - Heat Pump 20 30
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
34 systemair
The unit at a glance 2 versions:
L (Cooling only), H (Heat Pump) Cooling/Heating capacities : 31,7 / 35,4 SEER: 4,33 SCOP: 3,54 Leaving Water Temperature (LWT): from -15°C to +60°C Outdoor Air Temperature (OAT): from -20°C to +52°C
Equipment One refrigerant circuit with tandem scroll compressors
for a higher efficiency at partial load Stainless steel plate heat exchanger insulated with closed
cell synthetic foam (SYSAQUA L/H) Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins - Bluefin treatment for SYSAQUA H version
Patented safety system Hydraulic circuit without pump (SYSAQUA L) / without or
with a fixed speed pump (SYSAQUA H) Complete integrated control system with an external con-
trol panel that displays operating parameters and alarms Modbus RTU communication protocol “Night mode” for energy savings and reduced sound
levels Double water set point (SYSAQUA H) Water law for energy savings (SYSAQUA L/H) Return and leaving water temperature control
(SYSAQUA L/H) Water filter & water flow switch (SYSAQUA L/H) Phase sequence monitor
Advantages
A super eco-friendy unit Natural R290 refrigerant (propane) → GWP = 3 Very high performances → SCOP Wide operating limits
• Min/Max outdoor air temperature → -20/+52 [°C] • Min/Max leaving water temperature → -15/+60 [°C] Patented safety system Easy maintenance → great accessibility to the internal
components Low footprint Remotely controllable with AC CLOUD “Smart defrost technology” Optimized for partial load operation 100% factory tested Eurovent certified
Plate heat exchanger
Scroll compressor
31,7 kW
HOTELSOFFICES SHOPS INDUSTRY
Air Cooled Chiller and Heat Pump
35,4 kW
BIM models will be available at www.magicad.com
-20°C
+52°C
AC CLOUD
NewThink GREEN, PICK BLUE !
A+
SYSAQUA BLUE L/H
ErP2018
SCHOOLS HOSPITALS
HSHOPPING CENTERS
ErP20182021
2021Ready.*
R290
Q4 2020
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 35
3GlobalWarmingPotential
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
SYSAQUA BLUE L/H - Cooling only / Heat Pump
Cooling
Leaving water temperature
without glycol °С from +5 to +18
with glycol °С from -15 to +18
Outdoor air temperature °С from -15 to +52
Heating Leaving water temperature °С from +20 to +60Outdoor air temperature °С from -20 to +20
Minimum water volume in the system
1 According EN14511-2018: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2018: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2018: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for
comfort application chillers <400kW (see page 17 for more information).** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-
temperature heat pumps (see page 17 for more information).
SYSAQUA BLUE L - Cooling only 35Comfort application L 111Process application L 317
SYSAQUA BLUE L/H - Cooling only / Heat Pump 35
Cooling
Cooling Capacity 1 kW 31,7Power input 1 kW 10,2EER1 3,10Energy efficiency class (EER) 1 A
SEER 4 4,33hsc
4 170Nominal water flow (in the evaporator) m³/h 5,4
Heating
Heating Capacity 2 kW 35,4Power input 2 kW 10,3COP 2 3,45COP 3 4,16
SCOP 4 3,54Energy efficiency class (SCOP) 4 A+
hsh 4 139
Nominal water flow (in the evaporator) m³/h 6,1Sound power level (STD fan) dB(A) 83Sound pressure level at 10 m (STD fan) 5 dB(A) 55Power supply voltage V/ph/Hz 400/3/50
**ErP2018
Technical performanceSYSAQUA BLUE L/H - Cooling only / Heat Pump 35
Hydraulic data
Type of water connections (evaporator) Male gas threaded
Water Inlet/Outlet diameter inch 1”1/2WeightOperating weight without water tank - 1 pump kg 335Operating weight with water tank - 1 pump kg 500DimensionsLength mm 1.000Width without/ with water tank mm 1.000 / 1.507Height (STD fan) mm 1.983Height (HPF fan) mm 2.025
Physical features
Accessories and optionsAC CLOUDAntivibration mount rubber and Antivibration springBacnet IP or Bacnet MSTPFan speed controlFinned coil Blygold treatment (upon request) or epoxyHigh pressure fanModbus TCP/IPOutdoor coil protection gridPack Nordic (SYSAQUA H)Remote controlShut off valvesSoftstarterSRC - Smart Remote Control (Mini BMS)Variable pumpsWater pressure switchWater tank 100LWithout neutral (upon request)
New
3675 20881000100 3000
R32 R410A
GWP - Measurement scale
One of the most eco-friendly REFRIGERANT
BOOST your capacity
up to 105kW
by combining up to 3 units together.+ +
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation will be available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
SYSAQUA BLUE H - Heat Pump 35Comfort and process applications L 443
36 systemair
SYSAQUA 20-40 L/H/RE
The range at a glance 3 versions:
L (Cooling only), H (Heat Pump), RE (Condensing unit) 5 sizes (SYSAQUA L/H) and 4 sizes (SYSAQUA RE) Cooling capacity from 19,3 to 40,9 kW Heating capacity from 19,5 to 41,6 kW SEER up to 4,59 SCOP up to 3,40 Leaving Water Temperature (LWT): from -10°C to +50°C Outdoor Air Temperature (OAT): from -17°C to +50°C
Equipment One refrigerant circuit with tandem scroll compressors for a
higher efficiency at partial load Stainless steel plate heat exchanger insulated with closed cell
synthetic foam (SYSAQUA L/H) Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins - Bluefin treatment for SYSAQUA H/RE versions
Hydraulic circuit without pump (SYSAQUA L) / without or with a fixed speed pump (SYSAQUA H)
Complete integrated control system with an external control panel that displays operating parameters and alarms
Modbus RTU communication protocol “Night mode” for energy savings and reduced sound levels Double water set point (SYSAQUA H) Water law for energy savings (SYSAQUA L/H) Return and leaving water temperature control (SYSAQUA L/H) Water filter & water flow switch (SYSAQUA L/H) Phase sequence monitor Suction and liquid line shut-off valves + a suction receiver
(SYSAQUA RE)
Advantages
Very high performance → ErP 2021 ready / SCOP A+ Low noise units Wide operating limits
• Min/Max outdoor air temperature → -17/+50 [°C] • Min/Max leaving water temperature → -10/+50 [°C] Easy maintenance → great accessibility to the internal
components Low footprint Remotely controllable with AC CLOUD “Smart defrost technology” → 1 defrost every 130 min
for a constant LWT even at very low OAT (SYSAQUA H) Optimized for partial load operation 100% factory tested Eurovent certified
Plate heat exchangerAir cooled
Scroll compressorHFC R410A
19-41 kW
HOTELSOFFICES SHOPS INDUSTRY
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Air Cooled Chillers, Heat Pumpsand Condensing units
20-42 kW
SYSAQUA 20-40 L/H - Cooling only / Heat Pump
CoolingLeaving water temperature
without glycol °С from +5 to +18
with glycol 45% °С from -10 to +18
Outdoor air temperature °С from -10 to +50
Heating Leaving water temperature °С from +20 to +50Outdoor air temperature °С from -17 to +20
a SYSAQUA L units can’t be Ecodesign compliant with this option.
Enter the era of connected
units!
ErP20182021
2021Ready.*
-17°C
+50°C
AC CLOUD
SYSAQUA 25-40 RE - Condensing unitEvaporating limits °C from +1 to +14Outdoor air temperature °C from -10 to +50
Accessories and optionsAC CLOUDAntivibration mount rubber and Antivibration springBacnet IP or Bacnet MSTPFan speed controlFinned coil Blygold treatment (upon request) or epoxyHigh pressure fanModbus TCP/IPOutdoor coil protection gridPack Nordic (SYSAQUA H only)Remote controlShut off valvesSoftstarterSRC - Smart Remote Control (Mini BMS)Variable or fixeda speed pumpsWater pressure switchWater tank 100LWithout neutral (upon request)
New
SCHOOLS HOSPITALS
HSHOPPING CENTERS
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 37
SYSAQUA 20-40 L - Cooling only 20 25 30 35 40
Cooling Capacity1 kW 19,3 24,7 27,1 38,2 40,9Power input1 kW 6,1 7,7 9,4 12,2 13,4EER1 3,17 3,19 2,89 3,14 3,05Energy efficiency class (EER)1 A A C A B
SEER4 4,59 4,45 4,23 4,42 4,21hsc
4 181 175 166 174 165
Nominal water flow (in the evaporator) m3/h 3,5 4,6 4,9 6,5 6,7Sound power level (STD fan) dB(A) 75 75 75 76 76Sound pressure level at 10 m (STD fan)6 dB(A) 43,4 43,4 43,4 44,4 44,4Power supply voltage V/Ph/Hz 400/3~+N/50
*ErP2018
SYSAQUA 20-40 L - Cooling only 20 25 30 35 40Comfort application L 71 93 99 132 138Process application L 204 266 283 376 393
Minimum water volume in the system
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511-2013 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers <400kW
(see page 17 for more information).** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps
(see page 17 for more information).
SYSAQUA 25-40 RE - Condensing unit 25 30 35 40Cooling capacity5 kW 32,5 33,7 43,1 44,8Power input5 kW 9,1 9,8 13,9 14,1EER5 3,57 3,44 3,10 3,18Sound power level dB(A) 75 75 76 76
Power supply voltage V/Ph/Hz 400/3~+N/50
SYSAQUA 20-40 H - Heat Pump 20 25 30 35 40Comfort and process applications L 244 336 371 466 520
SYSAQUA 20-40 H - Heat Pump 20 25 30 35 40
Cooling
Cooling Capacity1 kW 19,4 25,3 26,9 35,8 37,4Power input1 kW 6,1 8,6 9,3 13,5 13,7EER1 3,18 2,94 2,88 2,65 2,74Energy efficiency class (EER)1 A B C D C
SEER4 3,91 3,87 3,88 3,68 3,91hsc
4 153 152 152 144 153Nominal water flow (in the evaporator) m³/h 3,3 4,3 4,6 6,2 6,4
Heating
Heating Capacity2 kW 19,5 26,9 29,7 37,3 41,6Power input2 kW 6,1 9,3 9,9 13,2 13,5COP2 3,19 2,90 2,99 2,82 3,08COP3 3,96 3,60 3,69 3,52 3,78
SCOP4 3,37 3,27 3,27 3,36 3,40Energy efficiency class (SCOP)4 A+ A+ A+ A+ A+
hsh 4 132 128 128 132 133
Nominal water flow (in the evaporator) m³/h 3,4 4,7 5,2 6,5 7,2Sound power level (STD fan) dB(A) 75 75 75 76 76Sound pressure level at 10 m (STD fan) 6 dB(A) 43,4 43,4 43,4 44,4 44,4Power supply voltage V/Ph/Hz 400/3~+N/50
**ErP2018
Technical performance
BIM models available at www.magicad.com
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
38 systemair
Refrigerant ConnectionsLiquid line inch 5/8” 5/8” 5/8” 5/8”Suction line inch 1”1/8 1”1/8 1”1/8 1”1/8WeightOperating weight kg 260 270 280 280DimensionsLength mm 1.000 1.000 1.000 1.000Width mm 1.000 1.000 1.000 1.000Height mm 1.983 1.983 1.983 1.983
SYSAQUA 25-40 RE - Condensing unit 25 30 35 40
Hydraulic dataType of water connections (evaporator) Male gas threaded BSPP iso 228Water Inlet/Outlet diameter inch 1”1/2WeightOperating weight without water tank - 1 pump kg 285 295 325 335 335Operating weight with water tank - 1 pump kg 450 460 490 500 500DimensionsLength mm 1.000 1.000 1.000 1.000 1.000Width without/ with water tank mm 1.000 / 1.507 1.000 / 1.507 1.000 / 1.507 1.000 / 1.507 1.000 / 1.507Height (STD fan) mm 1.983 1.983 1.983 1.983 1.983Height (HPF fan) mm 2.025 2.025 2.025 2.025 2.025
SYSAQUA 20-40 L/H - Cooling only / Heat Pump 20 25 30 35 40
Physical features
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 39
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
Keep it cool.with Systemair Air Conditioning systems.
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
40 systemair
SYSAQUA 45-125 L/H/RE
The range at a glance 3 versions:
L (Cooling only), H (Heat Pump), RE (Condensing unit) 7 sizes Cooling capacity from 46,8 to 129,8 kW Heating capacity from 48,5 to 119,1 kW SEER up to 4,41 SCOP up to 3,43 Leaving Water Temperature (LWT): from -10°C to +50°C Outdoor Air Temperature (OAT): from -17°C to +50°C
Equipment One refrigerant circuit with tandem scroll compressors for a
higher efficiency at partial load Stainless steel plate heat exchanger insulated with closed
cell synthetic foam (SYSAQUA L/H) Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins - Bluefin treatment for SYSAQUA H/RE versions
Hydraulic circuit without pump Complete integrated control system with an external control
panel that displays the operating parameters and alarms Modbus RTU communication protocol “Night mode” for energy savings and reduced sound levels Double water set point (SYSAQUA H) Water law for energy savings (SYSAQUA L/H) Return and leaving water temperature control
(SYSAQUA L/H) Water filter & water flow switch (SYSAQUA L/H) Phase sequence monitor Suction and liquid line shut-off valves + a suction receiver
(SYSAQUA RE)
ErP20182021
2021Ready.*
Air cooled
HFC R410A
47-130 kW
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Air Cooled Chillers, Heat Pumps and Condensing units
SYSAQUA 45-125 RE - Condensing unitEvaporating limits °C from +1 to +14Outdoor air temperature °C from -10 to +50
Plate heat exchanger
Scroll compressor
Enter the era of connected
units!
Advantages
Very high performance → ErP 2021 ready / SCOP A+ Low noise units Wide operating limits
• Min/Max outdoor air temperature → -17/+50 [°C] • Min/Max leaving water temperature → -10/+50 [°C] Easy maintenance → great accessibility to the internal
components Low footprint Remotely controllable with AC CLOUD “Smart defrost technology” → 1 defrost every 130 min
for a constant LWT even at very low OAT (SYSAQUA H) Optimized for partial load operation 100% factory tested Eurovent certified
a SYSAQUA L units can’t be Ecodesign compliant with this option.
-17°C
+50°C
AC CLOUD
Accessories and optionsAC CLOUDAntivibration mount rubber and Antivibration springBacnet IP or Bacnet MSTPFan speed controlFinned coil Blygold treatment (upon request) or epoxyElectrical Heater High or Low power (SYSAQUA H only)Extra low noise versionHigh pressure fanModbus TCP/IPOutdoor coil protection gridRefrigerant gauges HP/LPRemote controlShut off valvesSoftstarterSRC - Smart Remote Control (Mini BMS)Variable or fixeda speed pumpsWater tank 300LWithout neutral (upon request)Water pressure switch
New
SYSAQUA 45-125 L/H - Cooling only / Heat Pump
CoolingLeaving water temperature
without glycol °С from +5 to +18
with glycol 45% °С from -10 to +18
Outdoor air temperature °С from -10 to +50
HeatingLeaving water temperature °С from +20 to +50Outdoor air temperature °С from -17 to +20
49-119 kW
HOTELSOFFICES SHOPS INDUSTRY SCHOOLS HOSPITALS
HSHOPPING CENTERS
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 41
Minimum water volume in the system
SYSAQUA 45-125 L - Cooling only 45 55 65 75 90 105 125
Cooling Capacity1 kW 49,8 56,9 69,7 75,8 97,0 112,7 129,8Power input1 kW 16,7 18,8 22,1 24,2 32,6 38,6 44,3EER1 2,98 3,02 3,16 3,13 2,98 2,92 2,93Energy efficiency class (EER)1 B B A A B B B
SEER4 4,12 4,12 4,41 4,32 4,23 4,12 4,24
hsc4 162 162 173 170 166 162 167
Nominal water flow (in the evaporator) m³/h 8,4 9,6 11,9 12,9 16,5 19,1 22,0Sound power level (STD fan) dB(A) 80 80 80 80 83 83 83Sound pressure level at 10 m (STD fan)6 dB(A) 48,2 48,2 48,2 48,2 51,1 51,1 51,1Power supply voltage V/Ph/Hz 400/3~+N/50
ErP2018
*
SYSAQUA 45-125 L - Cooling only 45 55 65 75 90 105 125Comfort application L 172 196 242 263 336 392 448Process application L 492 560 691 752 960 1120 1280
SYSAQUA 45-125 RE - Condensing unit 45 55 65 75 90 105 125Cooling capacity5 kW 57,3 64,5 72,3 79,3 103,9 119,6 136,4Power input5 kW 17,4 20,2 22,5 25,3 35 38,8 47,1EER5 3,29 3,19 3,21 3,13 2,97 3,08 2,89Sound power level dB(A) 80 79 79 79 82 82 82Power supply voltage V/Ph/Hz 400/3~+N/50
SYSAQUA 45-125 H - Heat Pump 45 55 65 75 90 105 125Comfort and process application L 606 728 841 950 1103 1263 1498
Technical performance
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511-2013 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers <400kW
(see page 17 for more information).** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps
(see page 17 for more information). BIM models available at www.magicad.com
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
SYSAQUA 45-125 H - Heat Pump 45 55 65 75 90 105 125
Cooling
Cooling Capacity1 kW 46,8 53,3 65,8 71,6 91,4 106,2 121,9Power input1 kW 16,9 19,7 22,1 24,3 34,4 38,1 46,4EER1 2,77 2,71 2,98 2,95 2,66 2,79 2,63Energy efficiency class (EER)1 C C B B D C D
SEER4 3,70 3,86 4,04 3,99 3,89 3,88 3,89hsc
4 145 151 159 157 153 152 153Nominal water flow (in the evaporator) m³/h 8,0 9,2 11,3 12,3 15,7 18,2 21,0
Heating
Heating Capacity2 kW 48,5 58,2 67,3 75,9 88,1 101,0 119,1Power input2 kW 17,3 20,4 22,5 24,3 33,8 38,4 45,5COP2 2,80 2,86 2,99 3,12 2,61 2,61 2,62COP3 3,50 3,56 3,69 3,82 3,31 3,33 3,32
SCOP4 3,23 3,27 3,43 3,40 3,26 3,31 3,35Energy efficiency class (SCOP)4 A+ A+ A+ A+ A+ A+ A+
hsh4 126 128 134 133 128 129 131
Nominal water flow (in the evaporator) m³/h 8,4 10,2 11,7 13,2 15,3 17,6 20,7Sound power level (STD fan) dB(A) 80 80 80 80 83 83 83Sound pressure level at 10 m (STD fan) 6 dB(A) 48,2 48,2 48,2 48,2 51,1 51,1 51,1Power supply voltage V/Ph/Hz 400/3~+N/50
**ErP2018
42 systemair
SYSAQUA 45-125 L/H - Cooling only / Heat Pump 45 55 65 75 90 105 125
Hydraulic dataType of water connections (evaporator) Male gas threaded BSPP iso 228Water Inlet/Outlet diameter inch 2” 2” 2” 2” 2”1/2 2”1/2 2”1/2Weight
Operating weight without water tank - 1 pump kg 545 545 615 615 795 905 925Operating weight with water tank - 1 pump kg 1.010 1.010 1.080 1.080 1.260 1.370 1.390DimensionsLength without water tank mm 2.180 2.180 2.180 2.180 2.180 2.180 2.180Length with water tank mm 2.680 2.680 2.680 2.680 2.680 2.680 2.680Width mm 1.160 1.160 1.160 1.160 1.160 1.160 1.160Height (STD fan) mm 1.986 1.986 1.986 1.986 2.286 2.286 2.286Height (HPF fan) mm 2.025 2.025 2.026 2.026 2.379 2.379 2.379
Physical features
SYSAQUA 45-125 RE - Condensing unit 45 55 65 75 90 105 125
Refrigerant connectionsLiquid line inch 5/8” 5/8” 5/8” 5/8” 7/8” 7/8” 7/8”Suction line inch 1”5/8 1”5w/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8WeightOperating weight kg 490 490 560 560 740 850 870DimensionsLength mm 2.180 2.180 2.180 2.180 2.180 2.180 2.180Width mm 1.160 1.160 1.160 1.160 1.160 1.160 1.160Height mm 1.986 1.986 1.986 1.986 2.286 2.286 2.286
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 43
Offices, Italy• Air Cooled Chiller: SYSCROLL 590 AIR HP
Shopping centres, Italy• Air Cooled Chiller: SYSCROLL 660 AIR CO
44 systemair
AQVL/AQVH/AQVC 85-140Air Cooled Chillers, Heat Pumps and Condensing units
The range at a glance 3 versions:
AQVL (Cooling only), AQVH (Heat Pump), AQVC (Condensing unit)
6 sizes Cooling capacity from 83,3 to 136,5 kW Heating capacity from 91,0 to 146,9 kW 4 versions:
STD (Standard) HSE (High Seasonal Efficiency) HT (High Temperature) HPF (High Pressure Fans)
2 acoustic versions: Standard version
S (Super Low Noise)
Equipment Two refrigerant circuits 4 Scroll compressors (tandem) Plate evaporator (AISI 316) Microprocessor control Low operating water content in the plant Electronic expansion valve as standard “Brine” version for process application “Polar” version for extreme conditions E-Coating coil treatment as standard Compressors acoustic box Compressors jackets (standard on S) Sequence phases control Water flow switch
Advantages
High seasonal performances → SEER up to 4,4 Common configuration for the different versions →
Easy upgrade of the units in stock or on field Electronic expansion device → Excellent control of
superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight Compressors box → Remarkable sound reduction
even for the basic noise version Control platform → Modular architecture, compressor
envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R410A
83-137 kW
ErP20182021
2021Ready.**
HOTELSOFFICES SHOPS SCHOOLS INDUSTRY
91-147 kW
AQVL / AQVH 85-140 - - Cooling only / Heat Pump
Cooling
Leaving water temperature
Water °С from +5 to +18
Water with glycol °С from -8 to +18
Outdoor air temperature
STD °С from +5 to +47S °С from -18 to +44
HT °Сfrom -18 to +50 (85-115)
from -18 to +47 (125-140)
Heating
Leaving water temperaturea °С from +20 to +55
Outdoor air temperature
STD °С from -10 to +20S °С from -4 to +20Polar Version °С from -15 to +20
External static pressureStandard fans P 0HPF P <120
a Leaving water temperature max +55 (°C) [external air temp. min +6 (°C)] to be confirm with AC SELECT selection Software.
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
AQVC 85-140 - Condensing unitEvaporating limit °C from +1 to +15
Outdoor air temperature
STD °C from 0 to +48S °C from -18 to +45HT °C from 0 to +50
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsDesuperheater and Total heat recoveryFan speed controlHydrokit with 1 or 2 pumps with or without buffer tankMechanical gaugesOverload protection for compressorsPower factor corrector capacitorsSoftstarterUnit protection grillesWater differential pressureWater filterWater Pressure switch
Operating limits
Plate heat exchanger
Scroll compressor
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 45
AQVL 85-140 - Cooling only 85 95 105 115 125 140Cooling capacity1 kW 83,3 93,3 102,4 110,1 121,9 136,6Power input1 kW 27,1 31,0 33,6 36,5 41,1 45,9EER1 3,08 3,01 3,05 3,02 2,97 2,97Energy efficiency class (EER)1 B B B B B BEER HSE1 3,19 3,10 3,13 3,09 3,05 3,04Energy efficiency class (EER HSE)1 A A A B B B
SEER/ hsc2 (ErP 2018) 4,1/ 161 4,15/ 163 4,33/ 170 4,35/ 171 4,18/ 164 4,05/ 159
SEER/ hsc2 (ErP 2021) 4,1/ 161 4,15/ 163 4,33/ 170 4,35/ 171 4,18/ 164 -
SEER HSE/ hsc HSE2 (ErP 2021) 4,5/177 4,5/177 4,68/184 4,7/185 4,38/172 4,33/170Nominal water flow (in the evaporator) m³/h 14,3 16,1 17,6 19,0 21,0 23,5Sound power level3 dB(A) 84 84 84 84 88 88Sound pressure level at 10 m4 dB(A) 52 52 52 52 56 56Sound power level HPF3 dB(A) 92 92 92 92 95 95Sound pressure level at 10 m HPF4 dB(A) 60 60 60 60 63 63Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
AQVL 85-140 S - Cooling only 85 95 105 115 125 140Cooling capacity1 kW 80,6 89,9 98,3 105,4 119,1 133,1Power input1 kW 28 32,6 35,5 38,6 41,1 46,5EER1 2,87 2,76 2,77 2,73 2,90 2,86Energy efficiency class (EER)1 C C C C B CEER HSE1 3,00 2,87 2,87 2,81 2,96 2,91Energy efficiency class (EER HSE)1 B C C C B B
SEER/ hsc2 (ErP 2018) 4,03/ 158 4,03/ 158 4,18/ 164 4,18/ 164 4,45/ 175 4,25/ 167
SEER/ hsc2 (ErP 2021) - - 4,18/ 164 4,18/ 164 4,45/ 175 4,25/ 167
SEER HSE/ hsc HSE2 (ErP 2021) 4,58/ 180 4,53/ 178 4,63/ 182 4,65/183 4,65/183 4,5/177Nominal water flow (in the evaporator) m³/h 13,9 15,5 16,9 18,2 20,5 22,9Sound power level3 dB(A) 82 82 82 82 86 86Sound pressure level at 10 m4 dB(A) 50 50 50 50 54 54Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
AQVL 85-140 HT - Cooling only 85 95 105 115 125 140Cooling capacity1 kW 86,2 96,9 107 115 124 139Power input1 kW 28,1 31,6 33,9 36,4 41,1 46EER 3,07 3,06 3,15 3,16 3,02 3,03
SEER/hsc2 (ErP 2018) 4,5 / 177 4,5 / 177 4,68 / 184 4,7 / 185 4,38 / 172 4,33 / 170
SEER/hsc2 (ErP 2021) 4,5 / 177 4,5 / 177 4,68 / 184 4,7 / 185 4,38 / 172 4,33 / 170
Nominal water flow (in the evaporator) m³/h 14,8 16,6 18,3 19,8 21,4 24,0Sound power level3 dB(A) 95 95 95 95 95 95Sound pressure level at 10 m4 dB(A) 63 63 63 63 63 63Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers <400kW (see page 17 for more information).
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
ErP2018
*
ErP2018
*
ErP2018
*
46 systemair
AQVH 85-140 - Heat Pump 85 95 105 115 125 140
Cooling
Cooling capacity1 kW 81 89,9 98,9 106,9 115,8 129,2Power input1 kW 27,5 31,5 34,2 36,9 41,8 46,5EER / Energy efficiency class1 2,95/B 2,85/C 2,89/B 2,89/C 2,77/C 2,78/CEER HSE / Energy efficiency class1 3,05/B 2,94/B 2,97/B 2,96/B 2,84/C 2,84/C
SEER4 4,25 4,68 4,63 4,17 4,33 4,28
hsc4 167 184 182 164 170 168
SEER HSE4 4,6 5,03 4,95 4,55 4,6 4,5
hsc HSE4 181 198 195 179 181 177Nominal water flow (in the evaporator) m³/h 13,9 15,5 17,0 18,4 19,9 22,2
Heating
Heating capacity2 kW 91,8 102,8 110 119 134 146,9Power input2 kW 26,84 30,5 32,2 35,2 40,9 44,8COP2 3,42 3,37 3,42 3,38 3,28 3,28COP HSE2 3,54 3,47 3,52 3,47 3,36 3,36COP3 4,35 4,28 4,36 4,32 4,16 4,17COP HSE3 4,53 4,44 4,52 4,46 4,29 4,28
SCOP /Energy efficiency class4 3,61/ A+ 3,64/ A+ 3,78/ A+ 3,77/ A+ 3,47/ A+ 3,54/ A+
hsh4 141 143 148 148 136 139
Nominal water flow (in the evaporator) m³/h 17,2 17,8 19,3 20,6 23,3 25,5Sound power level5 dB(A) 84 84 84 84 88 88Sound pressure level at 10 m6 dB(A) 52 52 52 52 56 56Sound power level HPF5 dB(A) 92 92 92 92 95 95Sound pressure level at 10 m HPF6 dB(A) 60 60 60 60 63 63Power supply voltage V/Ph/Hz 400/3~+N/50 (Nominal)
AQVH 85-140 S - Heat Pump 85 95 105 115 125 140
Cooling
Cooling capacity1 kW 78,4 86,7 95,1 102 112 124,6Power input1 kW 28,6 33,2 36,0 39,1 43,1 47,6EER / Energy efficiency class1 2,75/C 2,61/D 2,64/D 2,62/D 2,61/D 2,63/DEER HSE / Energy efficiency class1 2,84/C 2,69/D 2,71/C 2,69/D 2,65/D 2,67/D
SEER4 4,25 4,68 4,63 4,17 4,33 4,28
hsc4 167 184 182 164 170 168
SEER HSE4 4,6 5,03 4,95 4,55 4,6 4,5
hsc HSE4 181 198 195 179 181 177Nominal water flow (in the evaporator) m³/h 13,5 14,9 16,3 17,6 19,3 21,5
Heating
Heating capacity2 kW 89,5 99,8 108 115 129 142Power input2 kW 26,4 30,1 32,0 34,7 39,3 43,0COP2 3,39 3,32 3,36 3,32 3,29 3,30COP HSE2 3,55 3,46 3,50 3,45 3,38 3,38COP3 4,32 4,24 4,31 4,25 4,22 4,24COP HSE3 4,58 4,46 4,51 4,44 4,34 4,35
SCOP /Energy efficiency class4 3,61/ A+ 3,64/ A+ 3,78/ A+ 3,77/ A+ 3,47/ A+ 3,54/ A+
hsh4 141 143 148 148 136 139
Nominal water flow (in the evaporator) m³/h 15,6 17,4 18,8 20,1 22,5 24,7Sound power level5 dB(A) 82 82 82 82 86 86Sound pressure level at 10 m6 dB(A) 50 50 50 50 54 54Power supply voltage V/Ph/Hz 400/3~+N/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
*ErP2018
Technical performance
*ErP2018
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 47
AQVH HT 85-140 - Heat Pump 85 95 105 115 125 140
Cooling
Cooling capacity1 kW 83,5 93,4 104 112 118 132Power input1 kW 28,4 32,0 34,4 37 42 46,2EER1 2,94 2,9 3,02 3,02 2,8 2,85SEER4 4,6 5,02 4,95 4,55 4,6 4,5
hsc4 181 198 195 179 181 177
Nominal water flow (in the evaporator) m³/h 14,3 16,0 17,8 19,2 20,3 22,7
Heating
Heating capacity2 kW 93,4 104,9 113,7 121,9 135 148Power input2 kW 29,4 33,1 35,00 37,8 42,2 46,1COP2 3,18 3,17 3,25 3,23 3,21 3,21COP3 3,98 3,98 4,08 4,07 4,06 4,08
SCOP /Energy efficiency class4 3,99/ A++ 3,96/ A++ 4,12/ A++ 4,07/ A++ 3,73/ A+ 3,77/ A+
hsh4 157 155 162 160 146 148
Nominal water flow (in the evaporator) m³/h 16,3 18,3 19,8 21,2 23,6 25,8Sound power level6 dB(A) 95 95 95 95 95 95Sound pressure level at 10 m7 dB(A) 63 63 63 63 63 63Power supply voltage V/Ph/Hz 400/3~+N/50 (Nominal)
*ErP2018
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511-2013 standard. 6 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.7 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
AQVC STD/HSE/HPF 85-140 - Condensing unit 85 95 105 115 125 140Cooling capacity5 kW 92,1 103,2 113,2 121,8 134,7 151,0Power input5 kW 27,4 31,4 34,1 37,0 41,7 46,8Sound power level6 dB(A) 84 84 84 84 88 88Sound pressure level at 10 m7 dB(A) 53 53 53 53 57 57Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
AQVC STD/HSE 85-140 S - Condensing unit 85 95 105 115 125 140Cooling capacity5 kW 89 99,5 108,7 116,6 131,6 147,2Power input5 kW 28,6 33,1 36,1 39,3 41,9 47,3Sound power level6 dB(A) 82 82 82 82 86 86Sound pressure level at 10 m7 dB(A) 51 51 51 51 55 55Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
AQVC HT 85-140 - Condensing unit 85 95 105 115 125 140Cooling capacity5 kW 95 106,8 117,7 127 137,2 153,8Power input5 kW 28,5 32,1 34,4 36,9 41,8 46,7Sound power level6 dB(A) 95 95 95 95 95 95Sound pressure level at 10 m7 dB(A) 64 64 64 64 64 64Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
48 systemair
Physical features
Hydraulic data (AQVL/AQVH 85-140)Type of water connections (evaporator) Male gas threadedWater Inlet/Outlet diameter inch 2”½ 2”½ 2”½ 2”½ 2”½ 2”½Condenser (AQVC 85-140)Connection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”Weight (AQVL 85-140)Operating weight STD/HT kg 1.090 1.105 1.149 1.180 1.227 1.301Operating weight S kg 1.120 1.135 1.179 1.210 1.257 1.331Weight (AQVH 85-140)Operating weight kg 1.058 1.072 1.111 1.143 1.183 1.262Operating weight S kg 1.088 1.102 1.141 1.173 1.213 1.292Operating weight HT kg 1.058 1.072 1.111 1.143 1.183 1.262Weight (AQVC 85-140)Shipping weight kg 971 983 1.013 1.043 1.066 1.142Shipping weight S kg 1.001 1.013 1.043 1.073 1.096 1.172DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185
AQVL/AQVH/AQVC 85-140 - Cooling only/Heat Pump/Condensing unit 85 95 105 115 125 140
3 pump option Energy saving in partial load
True dual circuit evaporatorOptimized heat transfer coefficient
Specialinverter fan(option)
Blue fin coil as standard on HP models
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 49
Shelter, Italy• Air Cooled Chiller: SYSCREW 380 AIR EVO HSE
Molding company, Bulgaria• Air Cooled Heat Pump: SYSCROLL 280 AIR EVO HP
50 systemair
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
SYSAQUA 140-210 L - Cooling only 140 150 170 190 210Comfort application L 469 515 565 658 731Process application L 1340 1470 1612 1878 2088
Air Cooled Chillers and Heat Pumps
a SYSAQUA L units can’t be Ecodesign compliant with this option.
AC CLOUD
Accessories and optionsAntivibration mount rubber and Antivibration springBacnet IP and Bacnet MSTPFan speed controlFinned coil Blygold treatment (upon request) and epoxyHydraulic gaugesModbus TCP/IPOutdoor coil protection gridPack Nordic (SYSAQUA H only)Refrigerant gauges HP/LPRemote controlShut off valvesSoftstarterSRC - Smart Remote Control (Mini BMS)Variable or fixeda speed pumpsWater tank 300LWithout neutralWater pressure switch
New
SYSAQUA 140-210 L/H
The range at a glance 2 versions:
L (Cooling only) and H (Heat Pump) 5 sizes Cooling capacity from 125,4 to 208,8 kW Heating capacity from 143,7 to 217,6 kW SEER up to 4,40 SCOP up to 3,36 Leaving Water Temperature (LWT): from -10°C to +50°C Outdoor Air Temperature (OAT): from -17°C to +50°C
Equipment Two refrigerant circuits, each equipped with tandem
scroll compressors for a higher efficiency at partial load Stainless steel plate heat exchanger insulated with
closed cell synthetic foam Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins - Blue-fin treatment for SYSAQUA H version
Hydraulic circuit without pump Complete integrated control system with an external
control panel that displays the operating parameters and alarms
Modbus RTU communication protocol AC CLOUD (Systemair Cloud connection) Acoustic box around the compressors for super low
noise units Patented antifrost coil (SYSAQUA H) “Night mode” for energy savings and reduced sound
levels Double water set point (SYSAQUA H Water law for energy savings Return and leaving water temperature control Water filter & water flow switch Phase sequence monitor
Minimum water volume in the system
ErP20182021
2021Ready.*
Air cooled
HFC R410A
125-209 kW
Enter the era of connected
units!
144-218 kW
SYSAQUA 140-210 L/H - Cooling only / Heat Pump
CoolingLeaving water temperature
without glycol °С from +5 to +18
with glycol 45% °С from -10 to +18
Outdoor air temperature °С from -10 to +50
Heating Leaving water temperature °С from +20 to +50Outdoor air temperature °С from -17 to +20
SYSAQUA 140-210 H - Heat Pump 140 150 170 190 210Comfort and process application L 935 1000 1106 1268 1415
Plate heat exchanger
Scroll compressor
Advantages
Very high performances → ErP 2021 ready / SCOP A+ Low noise units Wide operating limits
• Min/Max outdoor air temperature → -17/+50 [°C]• Min/Max leaving water temperature → -10/+50 [°C]
Easy maintenance → great accessibility to the internalcomponents
Low footprint Remotely controllable with AC CLOUD Patented antifrost coil “Smart defrost technology” → 1 defrost every 130 min
for a constant LWT even at very low OAT (SYSAQUA H) Optimized for partial load operation 100% factory tested Eurovent certified
HOTELSOFFICES SHOPS INDUSTRY SCHOOLS HOSPITALS
HSHOPPING CENTERS
-17°C
+50°C
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 51
Minimum water volume in the system
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
SYSAQUA 140-210 L - Cooling only 140 150 170 190 210Cooling capacity1 kW 134,0 147,0 161,2 187,8 208,8 Power input1 kW 44,2 49,0 53,7 64,5 72,3EER1 3,03 3,00 3,00 2,91 2,89Energy efficiency class (EER)1 B B B B C
SEER4 4,35 4,31 4,40 4,23 4,22
hsc4 171 169 173 166 166
Nominal water flow (in the evaporator) m³/h 23,1 25,3 27,8 32,3 36,0Sound power level (STD fan) dB(A) 85 85 87 88 88Sound pressure level at 10 m (STD fan)5 dB(A) 53,4 53,4 55,0 56,1 56,1Power supply V/ph/Hz 400/3~+N/50
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 2”1/2WeightOperating weight without water tank - 1 pump kg 1.685 1.705 1.798 1.891 2.201Operating weight with water tank - 1 pump kg 2.139 2.159 2.253 2.343 2.653DimensionsLength without water tank mm 2.856 2.856 2.856 2.856 2.856Length with water tank mm 3.666 3.666 3.666 3.666 3.666Width mm 2.210 2.210 2.210 2.210 2.210Height mm 2.295 2.295 2.321 2.321 2.321
Physical features
SYSAQUA 140-210 H - Heat Pump 140 150 170 190 210
Cooling
Cooling capacity1 kW 125,4 137,6 150,9 175,8 195,4Power input1 kW 43,6 47,8 52,8 64,9 72,7EER1 2,88 2,88 2,86 2,71 2,69Energy efficiency class (EER)1 C C C C D
SEER4 3,87 3,87 3,91 3,69 3,68hsc
4 151,8 151,8 153,4 144,6 144,2Nominal water flow (in the evaporator) m³/h 21,6 23,7 25,9 30,2 33,7
Heating
Heating capacity2 kW 143,7 153,7 170,1 194,9 217,6Power input2 kW 45,8 50,2 55,4 67,5 78,3COP2 3,14 3,06 3,07 2,89 2,78COP3 3,84 3,76 3,77 3,59 3,48
SCOP4 3,32 3,36 3,31 3,29 3,23Energy efficiency class (SCOP)4 A+ A+ A+ A+ A+
hsh4 130 132 129 129 126
Nominal water flow (in the evaporator) m³/h 24,8 26,5 29,6 33,9 37,9Sound power level dB(A) 85 85 87 88 88Sound pressure level at 10 m (STD fan)5 dB(A) 53,4 53,4 55 56,1 56,1Power supply V/ph/Hz 400/3~+N/50
SYSAQUA 140-210 L/H - Cooling only / Heat Pump 140 150 170 190 210
**ErP2018
Technical performance
*ErP2018
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers <400kW
(see page 17 for more information).** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps
(see page 17 for more information). BIM models available at www.magicad.com
52 systemair
VLS/VLH/VLC 704-1204
Air cooled
HFC R410A
176-307 kW The range at a glance 3 versions:
VLS (Cooling only), VLH (Heat Pump) VLC (Condensing unit)
6 sizes Cooling capacity from 176,2 to 307 kW Heating capacity from 200 to 337,4 kW 3 versions:
STD (Standard) HT (High Temperature) HPF (High Pressure Fans) 3 acoustic versions:
Standard version L (Low Noise)
S (Super Low Noise)
Equipment Two refrigerant circuits 4 Scroll compressors (tandem) Plate evaporator (AISI 316) Microprocessor control Microchannel coils (only VLS) Electronic expansion valve Inverter fans and HT “Brine” version for process application (upon request) “Polar” version for extreme conditions (upon request) E-Coating coil treatment Compressors acoustic box Sequence phases control Water differential pressure switch
HOTELSOFFICES SHOPS SCHOOLS INDUSTRY
200-337 kW
Air Cooled Chillers, Heat Pumps and Condensing units
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsCompressors jackets (standard on S)Desuperheater and total heat recovery (TR version)Fan speed control (-18°C)Hydrokit with 1 or 2 pumps with or without buffer tank (500 lt) (+1mt of length)Mechanical gaugesOverload protection for compressorsPower factor corrector capacitorsSoftstarterUnit protection grillesWater filterWater flow switch
Advantages
High seasonal performances → SEER up to 3,9 Small footprint Common configuration for the different versions →
Easy upgrade of the units in stock or on field Electronic expansion device → Excellent control of
superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight Compressors box → Remarkable sound reduction
even for the basic noise version Control platform → Modular architecture, compressor
envelope integration, corrective actions in border line areas, easy-friendly user interface
ErP2018
VLS/VLH 604-1204 - Cooling only / Heat Pump 604 704 804 904 1004 1104 1204
Cooling
Water outlettemperature
Water °C from +6 to +15Water with glycol °C from 0 to +15
Water with glycol(Brine version) °C from -8 to +15
∆ T °C from 3 to 8
Outdoor air temperature
STD °C -5 to +47 -5 to +47 0 to +46 0 to +47 0 to +46 0 to +45 0 to +45L °C -5 to +45 -5 to +45 0 to +44 0 to +45 0 to +44 0 to +42 0 to +42S °C -18 to +41 -18 to +41 -18 to +40 -18 to +41 -18 to +40 -18 to +38 -18 to +38HT °C -18 to +49 -18 to +49 -18 to +48 -18 to +49 -18 to +48 -18 to +47 -18 to +47
Plate heat exchanger
Scroll compressor
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 53
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
VLS STD/HPF 704-1204 - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 176,2 198,1 228,4 250,3 279,1 306,9Power input1 kW 66,0 72,3 83,1 86,9 100,0 114,9EER1 2,67 2,74 2,75 2,88 2,79 2,67Energy efficiency class (EER)1 D C C C C DSEER2 3,83 3,8 3,5 3,4 3,4 3,5Nominal water flow (in the evaporator) m³/h 30,4 34,1 39,3 43,1 48,0 52,8Sound power level3 dB(A) 91 91 92 92 93 93Sound pressure level at 10 m4 dB(A) 59 59 60 60 61 61Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLS 704-1204 L - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 171,2 192,1 222,4 241,3 266,2 292,0Power input1 kW 66,4 73,3 83,6 88,7 104,0 120,2EER1 2,58 2,62 2,66 2,72 2,56 2,43Energy efficiency class (EER)1 D D D C D ESEER2 3,83 3,80 3,83 3,45 3,83 3,83Nominal water flow (in the evaporator) m³/h 29,6 33,1 38,2 41,5 45,9 50,3Sound power level3 dB(A) 87 87 88 88 89 89Sound pressure level at 10 m4 dB(A) 55 55 56 56 57 57Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLS 704-1204 S - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 166,3 186,2 216,5 234,4 258,2 282,1Power input 1 kW 68,7 76,3 86,3 91,2 106,7 124,8EER1 2,42 2,44 2,51 2,57 2,42 2,26Energy efficiency class (EER)1 E E D D E ESEER2 3,83 3,83 3,83 3,48 3,4 3,4Nominal water flow (in the evaporator) m³/h 28,7 32,1 37,2 40,3 44,4 48,6Sound power level3 dB(A) 83 83 84 84 85 85Sound pressure level at 10 m4 dB(A) 51 51 52 52 53 53Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLC 704-1204 - Condensing Unit 704 804 904 1004 1104 1204Evaporating temperature °C from +3 to +15
Outdoor air temperature
STD °C from -5 to +471 from 0 to +461 from 0 to +462 from 0 to +462 from 0 to +452 from 0 to +452
L/S °C from -5 to +451 from 0 to +441 from 0 to +452 from 0 to +442 from 0 to +422 from 0 to +422
HT °C from -18 to +491 from -18 to +481 from -18 to +492 from -18 to +482 from -18 to +472 from -18 to +472
1 Maximum water outlet temperature +50 (°C) [min. temp. outdoor air +0 (°C)] to be confirmed with AC SELECT selection software.2 At high pressure 40,5 bar.Chillers suitable for operation without buffer tank for water content greater than 3 liters of water per kW of output.
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Heating1
Water outlet temperature °C from +30 to +50
Air temperature
STD °C from -10 to + 20L / S °C from - 4 to + 20
External static pressureStandard fans Pa 0Inverter HPF fans Pa <120
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
VLH 604-1204 - Heat Pump
54 systemair
VLS 704-1204 HT - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 178,6 200,9 231,7 254,2 282,4 313,3Power input1 kW 66,1 72,2 83,4 87,6 101 114EER 2,69 2,77 2,77 2,89 2,78 2,74
SEER2 3,8 3,88 3,8 3,83 3,8 3,8
hsc2 149 152 149 150 149 149
Nominal water flow (in the evaporator) m³/h 30,7 34,5 39,8 43,6 48,5 53,8Sound power level3 dB(A) 99 99 100 100 100 100Sound pressure level at 10 m4 dB(A) 67 67 68 68 68 68Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLR HSE 704-1204 - Cooling only 704 804 904 1004 1104 1204Cooling capacity5 kW 176,0 198,0 228,0 250,0 279,0 307,0Power input5 kW 65,9 72,1 82,8 86,8 100 115Heat recovery capacity6 kW 222,8 251,3 288,3 310,7 348,7 388,6EER 2,67 2,74 2,76 2,88 2,78 2,67
SEER2 3,8 3,88 3,8 3,83 3,8 3,8
hsc2 149 152 149 150 149 149
Nominal water flow (in the evaporator) m³/h 30,6 34,8 38,2 43,5 48,2 53,3Power supply voltage V/ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.5 Data refers to 7/12°C evaporator water temperature and 35°C condenser air temperature.6 Data based on 7°C leaving chilled water temperature and 45°C condenser warm water temperature.* ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers <400kW (see page 17 for more information).
VLS HSE 704-1204 S - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 166,3 186,2 216,5 234,4 258,2 282,1Power input 1 kW 66,8 74,2 83,6 88,8 105 122,1EER/ Energy efficiency class1 2,49/E 2,51/D 2,59/D 2,64/D 2,46/E 2,31/E
SEER2 3,95 4,08 3,98 3,83 3,8 3,83
hsc2 155 160 156 150 149 150
Nominal water flow (in the evaporator) m³/h 28,7 32,1 37,2 40,3 44,4 48,6Sound power level3 dB(A) 83 83 84 84 85 85Sound pressure level at 10 m4 dB(A) 51 51 52 52 53 53Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLS HSE 704-1204 - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 176,2 198,1 228,4 250,3 279,1 306,9Power input1 kW 64,3 70,5 80,7 84,85 97,9 113,25EER/ Energy efficiency class1 2,74/C 2,81/C 2,83/C 2,95/B 2,85/C 2,71/C
SEER2 3,8 3,88 3,8 3,83 3,8 3,8
hsc2 149 152 149 150 149 149
Nominal water flow (in the evaporator) m³/h 30,4 34,1 39,3 43,1 48,0 52,8Sound power level3 dB(A) 91 91 92 92 93 93Sound pressure level at 10 m4 dB(A) 59 59 60 60 61 61Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLS HSE 704-1204 L - Cooling only 704 804 904 1004 1104 1204Cooling capacity1 kW 171,2 192,1 222,4 241,3 266,2 292,0Power input1 kW 64,6 71,7 81,5 86,2 100,8 117,7EER/ Energy efficiency class1 2,65/D 2,68/D 2,73/C 2,8/C 2,64/D 2,48/E
SEER2 3,98 3,98 3,98 3,8 3,8 3,8
hsc2 156 156 156 149 149 149
Nominal water flow (in the evaporator) m³/h 29,6 33,1 38,2 41,5 45,9 50,3Sound power level3 dB(A) 87 87 88 88 89 89Sound pressure level at 10 m4 dB(A) 55 55 56 56 57 57Power supply voltage V/ph/Hz 400/3/50 (Nominal)
Technical performance
*ErP2018
*ErP2018
*ErP2018
*ErP2018
*ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 55
VLH STD/HPF 704-1204 - Heat Pump 704 804 904 1004 1104 1204
Cooling
Cooling capacity1 kW 173,2 197,1 226,4 246,3 273,1 299,9Power input1 kW 66,1 72,2 82,6 86,7 99,7 114,0EER / Energy efficiency class1 2,62/D 2,73/C 2,74/C 2,84/C 2,74/C 2,63/D
SEER4 3,63 3,55 3,35 3,5 3,53 3,43
hsc4 142 139 131 137 138 134
SEER HSE4 3,95 3,83 3,65 3,8 3,78 3,68
hsc HSE4 155 150 143 149 148 144Nom. water flow (in the evapor.) m³/h 29,9 33,9 38,8 42,4 47,0 51,6
Heating
Heating capacity2 kW 200,1 223,2 254,7 270,8 302,1 337,4Power input2 kW 67,4 70,4 79,6 87,6 100,0 112,5COP2 2,97 3,17 3,20 3,09 3,02 3,00COP3 3,71 3,96 3,99 3,86 3,78 3,77
SCOP/Energy eff. class 4 3,41 / A+ 3,42 / A+ 3,28 / A+ 3,39 / A+ 3,30 / A+ 3,19 / A+
hsh4 133 134 128 133 129 125
SCOP HSE/Energy eff. class 4 3,44 / A+ 3,4 / A+ 3,32 / A+ 3,33 / A+ 3,37 / A+ 3,3 / A+
Nom. water flow (in the evapor.) m³/h 34,7 38,6 43,6 47,0 52,3 58,4Sound power level5 dB(A) 91 91 92 92 93 93Sound pressure level at 10 m6 dB(A) 59 59 60 60 61 61Power supply voltage V/ph/Hz 400/3/50 (Nominal)
VLH 704-1204 L - Heat Pump 704 804 904 1004 1104 1204
Cooling
Cooling capacity1 kW 168,2 191,2 220,4 237,3 261,2 285,1Power input1 kW 66,2 73,3 83,8 88,5 102,8 119,8EER / Energy efficiency class1 2,54/D 2,61/D 2,63/D 2,68/D 2,54/D 2,38/E
SEER4 3 3 3,1 3,28 3,3 3,23
hsc4 117 117 121 128 129 126
SEER HSE4 3,95 3,83 3,65 3,80 3,78 3,68
hsc HSE4 155 150 143 149 148 144Nom. water flow (in the evapor.) m³/h 29,0 32,9 38,2 40,8 45,0 49,1
Heating
Heating capacity2 kW 195,0 217,1 247,7 261,8 288,9 322,2Power input2 kW 65,2 68,3 76,9 84,7 97,0 109,2COP2 2,99 3,18 3,22 3,09 2,98 2,95COP3 3,77 4,01 4,06 3,9 3,76 3,72
SCOP /Energy eff. class 4 3,41 / A+ 3,42 / A+ 3,28 / A+ 3,39 / A+ 3,20 / A+ 3,19 / A+
hsh4 133 134 128 133 125 125
SCOP HSE/Energy eff. class 4 3,44 / A+ 3,4 / A+ 3,32 / A+ 3,33 / A+ 3,37 / A+ 3,24 / A+
Nom. water flow (in the evapor.) m³/h 33,8 37,5 42,5 45,4 50,0 55,8Sound power level5 dB(A) 87 87 88 88 89 89Sound pressure level at 10 m6 dB(A) 55 55 56 56 57 57Power supply voltage V/ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
*ErP2018
*ErP2018
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
56 systemair
VLH 704-1204 HT - Heat Pump 704 804 904 1004 1104 1204
Cooling
Cooling capacity1 kW 175,6 199,7 229,5 250,1 276,5 305,6Power input1 kW 66,3 72,4 83,6 87,4 101,1 114,2EER / Energy efficiency class1 2,64/D 2,75/D 2,74/D 2,85/D 2,73/D 2,67/DSEER4 3 3 3,1 3,28 3,3 3,23
hsc4 117 117 121 128 129 126
Nom. water flow (in the evapor.) m³/h 30,1 34,3 39,4 42,9 47,5 52,5
Heating
Heating capacity2 kW 200,7 224,0 256,6 273,7 305,5 341,5Power input2 kW 60,6 63,5 71,4 79,3 91,4 103,5COP2 2,97 3,18 3,17 3,07 3,01 3,01COP3 3,66 3,92 3,91 3,79 3,73 3,73
SCOP /Energy eff. class 4 3,44 / A+ 3,40 / A+ 3,32 / A+ 3,33 / A+ 3,37 / A+ 3,26 / A+
hsh4 135 133 130 130 132 127
Nom. water flow (in the evapor.) m³/h 34,9 39,0 44,7 47,6 53,2 59,4Sound power level5 dB(A) 99 99 100 100 100 100Sound pressure level at 10 m6 dB(A) 67 67 68 68 68 68Power supply voltage V/ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.3 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14825.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
*ErP2018
VLH 704-1204 S - Heat Pump 704 804 904 1004 1104 1204
Cooling
Cooling capacity1 kW 164,3 185,2 214,5 230,4 253,3 276,1Power input1 kW 69,0 76,2 86,1 90,7 106,9 124,9EER / Energy efficiency class1 2,38/E 2,43/E 2,49/E 2,54/D 2,37/E 2,21/F
SEER4 3,63 3,55 3,35 3,5 3,53 3,43
hsc4 142 139 131 137 138 134
SEER HSE4 3,95 3,83 3,65 3,8 3,78 3,68
hsc HSE4 155 150 143 149 148 144Nom. water flow (in the evapor.) m³/h 28,3 31,9 36,9 39,7 43,6 47,5
Heating
Heating capacity2 kW 184,9 202,9 232,6 245,7 266,8 297,0Power input2 kW 64,9 67,0 75,8 83,9 95,0 108,0COP2 2,85 3,03 3,07 2,93 2,81 2,75COP HSE2 2,95 3,13 3,19 3,04 2,90 2,83COP3 3,6 3,83 3,88 3,71 3,56 3,48COP HSE3 3,76 3,98 4,07 3,87 3,7 3,59
SCOP /Energy eff. class 4 3,41 / A+ 3,42 / A+ 3,28 / A+ 3,39 / A+ 3,30 / A+ 3,19 / A+
hsh4 133 134 128 133 129 125
SCOP HSE/Energy eff. class 4 3,44 / A+ 3,4 / A+ 3,32 / A+ 3,33 / A+ 3,37 / A+ 3,26 / A+
Nom. water flow (in the evapor.) m³/h 32,0 35,2 40,4 42,5 46,3 51,5Sound power level5 dB(A) 83 83 84 84 85 85Sound pressure level at 10 m6 dB(A) 51 51 52 52 53 53Power supply voltage V/ph/Hz 400/3/50 (Nominal)
Technical performance
*ErP2018
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 57
Hydraulic dataType of water connections (evaporator) Male gas threadedWater Inlet/Outlet diameter inch 2½” 2½” 3” 3” 3” 3”Weight (VLS 704-1204)Operating weight STD/L kg 1.490 1.625 1.770 1.820 1.835 1.840Operating weight S kg 1.525 1.660 1.805 1.860 1.875 1.880Operating weight HT kg 1.520 1.655 1.810 1.860 1.875 1.880Operating weight VLR kg 1.725 1.880 2.101 2.230 2.320 2.329Weight (VLH 704-1204)Operating weight STD/L kg 1.675 1.820 1.980 2.125 2.215 2.225Operating weight S kg 1.710 1.855 2.015 2.165 2.255 2.265Operating weight HT kg 1.705 1.850 2.020 2.165 2.255 2.265Dimensions (VLS/VLH/VLC)Length mm 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300
VLS-VLH STD/HPF 704-1204 - Cooling only / Heat Pump 704 804 904 1004 1104 1204
VLC STD/HPF 704-1204 - Condensing Unit 704 804 904 1004 1104 1204Cooling capacity1 kW 199,0 224,0 258,0 283,0 315,0 347,0Power input1 kW 68,7 74,7 86,6 90,6 106 120Sound power level2 dB(A) 93 93 94 94 95 95Sound pressure level at 10 m3 dB(A) 61 61 62 62 63 63Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
VLC 704-1204 L - Condensing Unit 704 804 904 1004 1104 1204Cooling capacity1 kW 194,0 218,0 251,0 272,5 301,0 330,0Power input1 kW 69,6 76,6 87,8 92,8 109 126Sound power level2 dB(A) 87 87 88 88 89 89Sound pressure level at 10 m3 dB(A) 55 55 56 56 57 57Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
VLC 704-1204 S - Condensing Unit 704 804 904 1004 1104 1204Cooling capacity1 kW 188,5 211,0 244,0 264,5 292,0 319,0Power input1 kW 72,0 79,5 90,5 95,5 112 131Sound power level2 dB(A) 83 83 84 84 85 85Sound pressure level at 10 m3 dB(A) 51 51 52 52 53 53Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
VLC HT 704-1204 - Condensing Unit 704 804 904 1004 1104 1204Cooling capacity1 kW 201,0 226,5 261,0 286,5 318,0 353,0Power input1 kW 68,9 74,9 87,1 91,0 105 119Sound power level2 dB(A) 99 99 100 100 100 100Sound pressure level at 10 m3 dB(A) 67 67 68 68 68 68Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Physical features
Refrigerant connectionInlet diameter inch ⅞” ⅞” 1⅛” 1⅛” 1⅛” 1⅛”Outlet diameter inch 1⅝” 1⅝” 2⅛” 2⅛” 2⅛” 2⅛”WeightShipping weight STD/L kg 1.490 1.615 1.700 1.825 1.910 1.920Shipping weight S kg 1.525 1.650 1.735 1.865 1.950 1.960Shipping weight HT kg 1.520 1.645 1.740 1.865 1.950 1960
VLC 704-1204 - Condensing Unit 704 804 904 1004 1104 1204
1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
58 systemair
The range at a glance 3 versions:
CO (Cooling only), HP (Heat Pump), RE (Condensing unit)
8 sizes Cooling capacity from 144 to 360,7 kW Heating capacity from 144,9 to 361,4 kW 4 versions:
STD (Standard) EC (Inverter Fans) HT (High Temperature) HPF (High Pressure Fans)
3 acoustic versions: Standard version L (Low Noise) S (Super Low Noise)
Equipment 2 refrigerant circuits 4 scroll compressors (tandem) Electronic expansion valve Microchannel coils E-Coating coil treatment “Brine” version: Cooling only for process application
LWT -10°C (CO version) “Polar” version: Heat Pump for extreme conditions
(HP version) Plate heat exchanger evaporator Compressors acoustic box Compressors jackets (standard as Super Low Noise) Fan speed control (standard as Super Low Noise) Sequence phases control Water differential pressure switch
SYSCROLL 140-360 AIR EVO CO - Cooling only
Chilled liquid
Liquid outlettemperature
Water °C from +5 to +18Water with glycola °C from -10 to +5Temperature spread K from 3 to 7
Maximum operating pressure bar 6
Outdoor air tem-perature
Air enteringtemperature cooling
STD °C from +5 to +48L °C from +0 to +46S °C from -14 to +44EC-HT °C from -18 to +50
Externalstatic pressure
Temperature spread Pa 0HPF Pa <120
a For Liquid outlet temperature <0 °C provide Brine Version (available for CO; upon request for HP).
Advantages
High seasonal performances → SEER up to 4,3 Common configuration for the different versions →
Easy upgrade of the units in stock or on field Electronic expansion device → Excellent control of
superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight Compressors box → Remarkable sound reduction
even for the basic noise version Control platform → Modular architecture, compressor
envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R410A
144-361 kW
HOTELSOFFICES SHOPS SCHOOLS INDUSTRY
145-361 kW
Air Cooled Chillers, Heat Pumps and Condensing units
SYSCROLL 140-360 AIR EVO CO/HP/RE
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsDesuperheater and total heat recovery (TR version)Fan speed control (-14 °C in cooling mode – standard as Super Low Noise version)Hydrokit with 1 or 2 pumps with or without buffer tank (350 lt 140-170, 500 lt 200-360)Mechanical gaugesOverload protection for compressorsPower factor corrector capacitorsSoftstarterSRC - Smart Remote Control (Mini BMS)Unit protection grillesWater filterWater flow switch
Plate heat exchanger
Scroll compressor
ErP20182021
2021Ready.2
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 59
a For Liquid outlet temperature <0 °C provide Brine Version (upon request for HP).
SYSCROLL 140-360 AIR EVO HP - Heat Pump
Chilled liquidok Liquid outlettemperature
Water °С from +5 to +18Water with glycola °С from -10 to +5ΔT K from 3 to 7
Outdoor air temperature Air enteringtemp. Cooling
STD / L / S °С +5 to +48 / 0 to +46 / +14 to +44EC-HT °С from -18 to +50
Warm Liquid Liquid outlettemperature
Water °С from +20 to +55ΔT K from 3 to 7
Outdoor air temperature Air enteringtemp. Heating
STD / L / S / EC °С from -10 to +20Polar Version °С from -13 to +20HT °С from -13 to +20
External static pressureokStandard fans P 0High pressure fans (HPF) P <120
SYSCROLL 140-360 AIR EVO CO - Cooling only 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 144,0 168,6 229,9 262,6 283,5 309,3 330,3 360,7Input power1 kW 44,7 54,2 73,9 83,4 90,3 98,5 103,9 116,0EER1 / Energy efficiency class / EER* 3,2/A/3,2 3,1/A/3,1 3,1/A/3,2 3,1/A/3,2 3,1/A/3,2 3,1/A/3,2 3,2/A/3,2 3,1/A/3,2
SEER / SEER*2 (ErP 2018) 3,85/3,95 3,83/ 3,85 4,08/4,15 4,1/4,18 4,0/4,08 4,03/4,13 4,05/4,13 4,0/4,08
hsc / hsc*2 (ErP 2018) 151/155 150/151 160/163 161/164 157/160 158/162 159/162 157/160
SEER*2/ hsc*2 (ErP 2021) - - 4,15/163 4,18/164 - 4,13/162 4,13/162 -
Nominal water flow (in the evaporator) m³/h 24,8 29,1 39,6 45,2 48,8 53,2 56,9 62,1Sound power level3 dB(A) 90 90 92 93 93 94 95 95Sound pressure level 10 m4 dB(A) 58 58 60 61 61 62 63 63Power supply voltage** V/ph/Hz 400/3/50 (nominal)
SYSCROLL 140-360 AIR EVO CO L - Cooling only 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 139,9 162,9 222,9 255,1 275,0 300,1 321,3 349,5Input power1 kW 45,0 54,9 74,3 83,6 91,1 99,0 103,7 116,5EER1 / Energy efficiency class / EER* 3,1/A/ 3,2 2,97/B/3 3/B/3,04 3,0/B/3,1 3,0/B/3,1 3,0/B/3,1 3,1/A/3,2 3/B/3,04
SEER / SEER*2 (ErP 2018) 4,03/3,85 3,88/4,0 4,2/4,3 4,18/4,28 4,1/4,2 4,08/4,15 4,1/4,18 4,05/4,13
hsc / hsc*2 (ErP 2018) 158/151 152/157 165/169 164/168 161/165 160/163 161/164 159/162
SEER*2/ hsc*2 (ErP 2021) - - 4,3/169 4,28/168 4,2/165 4,15/163 4,18/164 4,13/162
Nominal water flow (in the evaporator) m³/h 24,1 28,1 38,4 43,9 47,4 51,7 55,3 60,2Sound power level3 dB(A) 85 85 87 88 88 89 90 90Sound pressure level 10 m4 dB(A) 53 53 55 56 56 57 58 58Power supply voltage** V/ph/Hz 400/3/50 (nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.5 According EN14511-2013: nominal cooling capacity refers to 7°C leaving chilled water temperature and 45°C leaving warm water temperature.* High Efficiency Units (EC) with inverter fans.** Voltage 400V +/- 10%.***ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
SYSCROLL 140-360 AIR EVO RE - Condensing unitEvaporating temperature °C from +3 to +15
Outdoor air temperature
STD °C from +5 to +48L °C from +0 to +46S °C from -14 to +44EC-HT °C from -18 to +50
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
***ErP2018
***ErP2018
BIM models available at www.magicad.com
60 systemair
SYSCROLL 140-360 AIR EVO CO TR - Cooling only 140 170 230 260 280 300 330 360Nominal cooling capacity5 kW 141,8 169,7 230,5 260,5 283,7 308,1 324,1 359,8Input power5 kW 49,3 59,8 82,6 92,7 94,0 110 115 130EER 2,70 2,56 2,54 2,61 2,93 2,57 2,65 2,54
SEER2 (ErP 2018) 3,95 3,85 4,15 4,18 4,08 4,13 4,13 4,08
hsc2 (ErP 2018) 155 151 163 164 160 162 162 160
SEER/ hsc2 (ErP 2021) - - 4,15/163 4,18/164 - 4,13/162 4,13/162 -
Heat recovery capacity 142 182 248 280 305 331 348 385Nominal water flow (in the evaporator) m³/h 22,8 26,3 36,1 41,5 47,4 48,6 52,4 56,6Power supply voltage** V/ph/Hz 400/3/50 (nominal)
SYSCROLL 140-360 AIR EVO CO HT - Cooling only 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 145,3 170,2 232,0 264,7 286,0 312,0 332,9 363,8Input power1 kW 47,0 56,4 77,6 87,9 94,7 103,7 109,9 121,7EER / Energy efficiency class1 3,09/B 3,02/B 2,99/B 3,01/B 3,02/B 3,01/B 3,03/B 2,99/B
SEER2 (ErP 2018) 3,95 3,85 4,15 4,18 4,08 4,13 4,13 4,08
hsc2 (ErP 2018) 155 151 163 164 160 162 162 160
SEER/ hsc2 (ErP 2021) - - 4,15/163 4,18/164 - 4,13/162 4,13/162 -
Nominal water flow (in the evaporator) m³/h 25,0 29,3 40,0 45,6 49,3 53,7 57,3 62,7Sound power level3 dB(A) 92 92 94 96 96 97 98 98Sound pressure level 10 m4 dB(A) 60 60 62 64 64 65 66 66Power supply voltage** V/ph/Hz 400/3/50 (nominal)
SYSCROLL 140-360 AIR EVO CO S - Cooling only 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 132,5 152,9 209,4 241,0 258,7 282,5 304,3 328,5Input power1 kW 47,0 57,5 78,7 88,0 96,2 104,6 108,7 123,5EER1 / Energy efficiency class /EER* 2,8/C/2,9 2,7/D/2,7 2,7/C/2,7 2,7/C/2,8 2,7/D/2,7 2,7/C/2,7 2,8/C/2,8 2,6/C/2,7
SEER / SEER*2 (ErP 2018) 4,0/4,13 3,83/3,95 4,2/4,33 4,13/4,25 4,0/4,13 4,03/4,13 4,05/4,15 4,0/4,1
hsc / hsc*2 (ErP 2018) 157/162 150/155 165/170 162/167 157/162 158/162 159/163 157/161
SEER*2/ hsc*2 (ErP 2021) 4,13/162 - 4,33/170 4,25/167 4,13/162 4,13/162 4,15/163 4,1/161
Nominal water flow (in the evaporator) m³/h 22,8 26,3 36,1 41,5 44,6 48,6 52,4 56,6Sound power level3 dB(A) 79 79 82 83 83 85 86 86Sound pressure level 10 m4 dB(A) 47 47 50 51 51 53 54 54Power supply voltage** V/ph/Hz 400/3/50 (nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.5 According EN14511-2013: nominal cooling capacity refers to 7°C leaving chilled water temperature and 45°C leaving warm water temperature.* High Efficiency Units (EC) with inverter fans.** Voltage 400V +/- 10%.***ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
***ErP2018
***ErP2018
***ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 61
SYSCROLL 140-360 AIR EVO HP - Heat Pump 140 170 230 260 280 300 330 360
Cooling
Nominal cooling capacity1 kW 136,7 154,5 213,6 243,7 261,1 287,8 307,4 340,5Input power1 kW 45,1 54,6 73,2 83,8 90,7 98,5 103,5 117,0EER/Energy efficiency class1 3,03/B 2,83/C 2,92/B 2,91/B 2,88/C 2,92/B 2,97/B 2,91/BEER* / EER** 3,08/2,86 2,86/2,69 2,96/2,75 2,95/2,73 2,91/2,71 2,96/2,75 3,02/2,78 2,95/2,74SEER / hsc
2 3,8/149 3,95/155 4,13/162 4,05/159 4,1/161 3,83/150 3,8/149 3,93/154SEER* / SEER**2 3,95 4,08 4,22 4,13 4,2 3,93 3,8 4,05hsc
* / hsc**2 155 160 166 162 165 154 149 159
Nominal water flow (in the evaporator) m³/h 23,6 26,6 36,8 42,0 45,0 49,5 52,9 58,6
Heating
Nominal heating capacity3 kW 144,9 165,7 229,0 262,3 279,6 305,6 327,2 361,4Input power3 kW 44,9 51,6 70,9 81,7 87,4 94,9 101,9 112,6COP3 3,23 3,21 3,23 3,21 3,20 3,22 3,21 3,21COP* 3,28 3,25 3,27 3,26 3,25 3,27 3,26 3,26COP** 3,05 3,05 3,03 3,01 3,02 3,02 2,99 3,02Nominal heating capacity4 kW 148,6 170,0 233,8 268,4 285,6 311,0 333,9 367,9Input power4 kW 37,2 43,6 58,7 67,8 72,3 77,8 83,7 92,7COP4 4,00 3,90 3,98 3,96 3,95 4,00 3,99 3,97
SCOP2 3,39 3,42 3,46 3,48 3,44 3,51 3,44 3,48Energy efficiency class 2 A+ A+ A+ A+ A+ A+ A+ A+
hsh2 133 134 135 136 135 137 135 136
Nominal water flow (in the evaporator) m³/h 25,1 28,7 39,7 45,5 48,5 53,0 56,8 62,7Sound power level5 dB(A) 90 90 92 93 93 94 95 95Sound pressure level at 10 m6 dB(A) 58 58 60 61 61 62 63 63Power supply voltage7 V/ph/Hz 400 /3/50 (Nominal)
SYSCROLL 140-360 AIR EVO HP L - Heat Pump 140 170 230 260 280 300 330 360
Cooling
Nominal cooling capacity1 kW 132,9 149,3 207,2 236,9 253,3 279,4 299,1 330,1Input power1 kW 45,2 55,3 73,7 83,7 91,4 99,1 103,1 117,5EER/ Energy efficiency class1 2,94/B 2,70/C 2,81/C 2,83/C 2,77/C 2,82/C 2,90/C 2,81/CEER/ Energy efficiency class* 2,98/B 2,73/C 2,85/C 2,87/C 2,81/C 2,86/C 2,94/B 2,84/CSEER2 3,8 3,95 4,13 4,05 4,1 3,83 3,8 3,93hsc
2 149 155 162 159 161 150 149 154SEER*2 4,58 4,65 3,7 3,65 3,63 2,58 2,65 4,17hsc
*2 180 183 145 143 142 100 103 164Nominal water flow (in the evaporator) m³/h 22,9 25,7 35,7 40,8 43,6 48,1 51,5 56,8
Heating
Nominal heating capacity3 kW 141,0 162,1 223,7 255,6 272,3 299,4 320,8 353,9Input power3 kW 43,5 50,3 69,0 79,4 84,8 92,7 99,6 109,9COP3 3,24 3,22 3,24 3,22 3,21 3,23 3,22 3,22Nominal heating capacity4 kW 144,2 165,8 227,8 260,8 277,3 303,8 326,4 359,2Input power4 kW 35,8 42,2 56,5 65,2 69,8 75,2 81,0 89,8COP4 4,03 3,93 4,03 4,00 3,97 4,04 4,03 4,00COP* 3,32 3,30 3,32 3,31 3,29 3,31 3,31 3,30
SCOP2 3,39 3,42 3,46 3,48 3,44 3,51 3,44 3,48Energy efficiency class2 A+ A+ A+ A+ A+ A+ A+ A+
hsh2 133 134 135 136 135 137 135 136
Nominal water flow (in the evaporator) m³/h 24,5 28,1 38,8 44,3 47,2 52,0 55,7 61,4Sound power level5 dB(A) 85 85 87 88 88 89 90 90Sound pressure level at 10 m6 dB(A) 53 53 55 56 56 57 58 58Power supply voltage7 V/ph/Hz 400 /3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB. 4 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. 7 Voltage 400V +/- 10%.* High Efficiency Units (EC) with inverter fans.** HPF Units with high static pressure fans.*** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
***ErP2018
***ErP2018
62 systemair
SYSCROLL 140-360 AIR EVO HP HT - Heat Pump 140 170 230 260 280 300 330 360
Cooling
Nominal cooling capacity1 kW 137,9 156,0 215,5 245,8 263,4 290,3 309,8 343,4Input power1 kW 47,2 56,7 77,0 88,4 95,1 103,7 109,9 123,1EER/ Energy efficiency class1 2,92/B 2,75/C 2,80/C 2,78/C 2,77/C 2,80/C 2,82/C 2,79/CSEER2 3,68 3,78 3,8 3,73 3,78 4,28 3,95 4,08hsc
2 144 148 149 146 148 168 155 160Nominal water flow (in the evaporator) m³/h 23,7 26,9 37,1 42,3 45,4 50,0 53,3 59,1
Heating
Nominal heating capacity3 kW 147,0 168,5 232,3 266,0 283,7 309,8 331,5 366,5Input power3 kW 47,6 54,5 75,7 87,2 92,7 101,2 109,0 119,8COP3 3,09 3,09 3,07 3,05 3,06 3,06 3,04 3,06COP4 3,79 3,73 3,76 3,73 3,73 3,76 3,73 3,74
SCOP2 3,55 3,58 3,56 3,57 3,53 3,61 3,55 3,58Energy efficiency class2 A+ A+ A+ A+ A+ A+ A+ A+
hsh2 139 140 139 140 138 141 139 140
Nominal water flow (in the evaporator) m³/h 25,5 29,2 40,3 46,1 49,2 53,8 57,5 63,6Sound power level5 dB(A) 92 92 94 96 96 97 98 98Sound pressure level at 10 m6 dB(A) 60 60 62 64 64 65 66 66Power supply voltage7 V/ph/Hz 400 /3/50 (Nominal)
SYSCROLL 140-360 AIR EVO HP S - Heat Pump 140 170 230 260 280 300 330 360
Cooling
Nominal cooling capacity1 kW 125,9 140,3 194,7 224,0 238,5 263,3 283,5 310,5Input power1 kW 47,2 57,7 77,6 88,2 96,6 104,5 108,2 124,2EER/ Energy efficiency class1 2,67/D 2,43/D 2,51/D 2,54/D 2,47/D 2,52/D 2,62/D 2,50/DEER/Energy efficiency class* 2,71/C 2,45/D 2,54/D 2,58/D 2,50/D 2,55/D 2,66/D 2,53/DSEER2 3,8 3,95 4,13 4,05 3,60 3,83 3,8 3,93hsc
2 149 155 162 159 141 150 149 154SEER*2 4,58 4,65 3,7 3,65 3,63 2,58 2,65 4,17hsc
*2 180 183 145 143 142 100 103 164Nominal water flow (in the evaporator) m³/h 21,7 24,2 33,5 38,6 41,1 45,3 48,8 53,5
Heating
Nominal heating capacity3 kW 138,5 159,5 219,8 250,8 267,1 294,7 315,0 348,9Input power3 kW 42,4 48,9 67,2 77,2 82,4 90,4 96,9 107,4COP3 3,27 3,26 3,27 3,25 3,24 3,26 3,25 3,25Nominal heating capacity4 kW 141,3 162,7 223,3 255,3 271,3 298,3 319,7 353,2Input power4 kW 34,9 41,1 55,1 63,5 67,8 73,5 78,9 87,6COP4 4,05 3,96 4,05 4,02 4,00 4,06 4,05 4,03
SCOP2 3,39 3,42 3,46 3,48 3,44 3,51 3,44 3,48Energy efficiency class2 A+ A+ A+ A+ A+ A+ A+ A+
hsh2 133 134 135 136 135 137 135 136
Nominal water flow (in the evaporator) m³/h 24,0 27,7 38,1 43,5 46,3 51,2 54,7 60,5Sound power level5 dB(A) 79 79 82 83 83 85 86 86Sound pressure level at 10 m6 dB(A) 47 47 50 51 51 53 54 54Power supply voltage7 V/ph/Hz 400 /3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB. 4 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. 7 Voltage 400V +/- 10%.* High Efficiency Units (EC) with inverter fans.** HPF Units with high static pressure fans.*** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
***ErP2018
***ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 63
SYSCROLL 140-360 AIR EVO RE - Condensing unit 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 165,0 193,4 250,3 288,4 312,7 337,2 361,2 394,5Input power1 kW 45,7 55,6 74,6 84,4 91,6 99,4 105 117Sound power level2 dB(A) 90 90 92 93 93 94 95 95Sound pressure level at 10 m3 dB(A) 58 58 60 61 61 62 63 63Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
SYSCROLL 140-360 AIR EVO RE L - Condensing unit 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 159,0 186,0 242,3 279,4 302 326 350,8 381Input power1 kW 46,1 56,4 75,4 84,8 92,6 100 105 118Sound power level2 dB(A) 85 85 87 88 88 89 90 90Sound pressure level at 10 m3 dB(A) 53 53 55 56 56 57 58 58Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 140-360 AIR EVO RE S - Condensing unit 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 149 172 225 262 281 305 330 356Input power1 kW 48,5 59,5 80,1 89,6 98,4 107 111 126Sound power level2 dB(A) 79 79 82 83 83 85 86 86Sound pressure level at 10 m3 dB(A) 47 47 50 51 51 53 54 54Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 140-360 AIR EVO RE HT - Condensing unit 140 170 230 260 280 300 330 360Nominal cooling capacity1 kW 166,6 195,6 252,8 291,2 315,9 340,5 364,4 398,4Input power1 kW 48 57,7 78,2 88,9 95,8 105 111 123Sound power level2 dB(A) 92 92 94 96 96 97 98 98Sound pressure level at 10 m3 dB(A) 60 60 62 64 64 65 66 66Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Water Connections (Evaporator)Type To be brazed
Refrigerant In connections inch 1 5/8” 1 5/8” 1 5/8” - 2 1/8”
1 5/8” - 2 1/8”
1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8”
Refrigerant Out connections inch 7/8” 7/8” 7/8” - 1 1/8”
7/8” - 1 1/8”
7/8” - 1 1/8” 1 1/8” 1 1/8” 1 1/8”
WeightShipping weight kg 1.107 1.150 1.695 1.875 1.875 2.364 2.433 2.445DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600
SYSCROLL 140-360 AIR EVO RE - Condensing unit 140 170 230 260 280 300 330 360
Hydraulic dataType of water connections (evaporator) Male gas threadedWater Inlet/Outlet diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Weight (CO version)Operating weight STD / L kg 1.157 1.200 1.617 1.765 1.705 2.286 2.303 2.313Operating weight S kg 1.162 1.205 1.622 1.770 1.770 2.291 2.308 2.318Operating weight HT kg 1.187 1.230 1.667 1.825 1.825 2.356 2.383 2.393Operating weight TR kg 1.342 1.386 2.028 2.250 2.250 2.876 2.969 2.969Weight (HP version)Operating weight STD / L kg 1.312 1.355 1.993 2.216 2.226 2.806 2.899 2.909Operating weight S kg 1.317 1.360 1.998 2.221 2.231 2.811 2.904 2.914Operating weight HT kg 1.342 1.385 2.043 2.276 2.286 2.876 2.979 2.989DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Physical featuresSYSCROLL 140-360 AIR EVO CO/HP - Cooling only / Heat Pump 140 170 230 260 280 300 330 360
Technical performance
64 systemair
SYSCROLL 400-900 AIR EVO CO/HPAir Cooled Chillers and Heat Pumps
The range at a glance 2 versions:
CO (Cooling only) and HP (Heat Pump) 10 sizes (CO version) / 11 sizes (HP version) Cooling capacity from 398,8 to 896,7 kW Heating capacity from 404 to 902 kW 4 versions:
STD (Standard) EC (Invert fans) HT (High Temperature) (only HP version) HPF (High Pressure Fans) 2 acoustic versions:
Standard version S (Super Low Noise)
Equipment Two refrigerant circuits 4/5/6/8 Scroll compressors “Brine” Version: Cooling only for process application
LWT -10°C “Polar” version: Heat Pump for extreme conditions Plate Evaporator Electronic expansion valve Microchannel coils E-Coating coil treatment as standard Compressors acoustic box Compressors jackets (standard as Super Low Noise) Fan speed control (standard as Super Low Noise) Sequence phases control Water differential pressure switch
SYSCROLL 400-900 AIR EVO CO - Cooling only
Chilled liquid
Liquid outlettemperature
Water °C from +5 to +18Water with glycol* °C from -10 to +5ΔT K from 3 to 7
Maximum operating pressure bar 6
Outdoor air tempera-ture
Air enteringtemperature cooling
STD / EC °C from +10 to +48S / EC S °C from -18 to +48HT °C from -18 to +52
Externalstatic pressure
Standard fans Pa 0High pressure fans (HPF) Pa <120
* For Liquid outlet temperature < -3 °C provide Brine Version.
Advantages
High seasonal performances → SEER up to 4.6 Low sound emission and high efficiency level in a
single unit → Super Low Noise version Electronic expansion device → Excellent control of
superheating for the best performance at full and partial load and for a safe operation
E-coated microchannel coils → Significant reduction on refrigerant charge and operating weight and excellent anticorrosion protection with the standard delivery
Compressors box → Remarkable sound reduction even for the basic noise version
Control platform → Modular architecture, compressor envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R410A
399-897 kWHOTELSOFFICES SCHOOLS INDUSTRY
404-902 kW
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsDesuperheater and total heat recovery (TR version)Hydrokit with 1 or 2 pumps with or without buffer tank (500 lt 400-450, 1000 lt 470-670)Mechanical gaugesOverload protection for compressorsPower factor corrector capacitorsSoftstarterSRC - Smart Remote Control (Mini BMS)Unit protection grillesWater filterWater flow switch
Plate heat exchanger
Scroll compressor
ErP20182021
2021Ready.***
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 65
Technical performanceSYSCROLL 400-900 AIR EVO CO - Cooling only 400 450 490 530 600 670 750 800 850 900Nominal cooling capacity1 kW 398,8 446,1 487,7 533,9 597,1 667,3 748,3 797,9 847,2 896,7Input power1 kW 128,6 142,8 157,1 172,1 192,1 215,0 241,7 257,4 272,4 286,7EER / Energy efficiency class1 3,10/A 3,12/A 3,10/A 3,10/A 3,11/A 3,10/A 3,10/A 3,10/A 3,11/A 3,13/AEER / Energy efficiency class*1 3,18/A 3,21/A 3,19/A 3,18/A 3,19/A 3,18/A 3,17/A 3,17/A 3,19/A 3,21/A
SEER/ hsc2 (ErP 2018) 4,5/177 4,43/174 4,53/178 4,4/173 4,58/180 4,68/184 4,5/177 4,5/177 4,43/174 4,5/177
SEER/ hsc2 (ErP 2021) 4,5/177 - - - 4,58/180 4,68/184 - - - -
SEER/ hsc*2 (ErP 2021) 4,68/184 4,6/181 4,68/184 4,58/180 4,83/190 4,85/191 4,65/183 4,68/184 4,6/181 4,63/182
Nom. water flow (in the evaporator) m³/h 68,6 76,8 84,0 91,9 103 115 129 138 146 155Sound power level3 dB(A) 92 93 93 94 94 94 95 95 95 96Sound pressure level at 10 m4 dB(A) 60 61 60 61 61 61 62 62 62 63Power supply voltage** V/ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound power levels is declared in nominal full load condition (cooling operation), referring to ISO standard 9614, in accordance with Eurovent certification program.4 Sound pressure level refer to ISO Standard 3744, parallelepiped shape in a free field on a reflective surface.5 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.* EC version: brushless fan motors version. ** Voltage 400V +/- 10%.*** ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
SYSCROLL 400-900 AIR EVO CO HT - Cooling only 400 450 490 530 600 670 750 800 850 -Nominal cooling capacity1 kW 411,2 455,8 497,3 543,1 607,2 678,7 768,3 820,5 867,0 -Input power1 kW 123,4 138,4 152,2 167,3 186,4 208,9 234,2 249,2 265,0 -EER / Energy efficiency class1 3,33/A 3,29/A 3,27/A 3,25/A 3,26/A 3,25/A 3,28/A 3,29/A 3,27/A -
SEER2 (ErP 2021) 4,8 4,83 4,83 4,83 4,88 4,85 4,7 4,63 4,9 -
hsc2 (ErP 2021) 189 190 190 190 192 191 185 182 193 -
Nom. water flow (in the evaporator) m³/h 70,8 78,5 85,7 93,6 105 117 132 142 150 -Sound power level3 dB(A) 93 93 94 94 94 95 96 96 96 -Sound pressure level at 10 m4 dB(A) 60 61 60 61 61 61 62 62 62 -Power supply voltage** V/ph/Hz 400/3/50 (Nominal)
SYSCROLL 400-900 AIR EVO CO S - Cooling only 400 450 490 530 600 670 750 800 850 -Nominal cooling capacity1 kW 396,0 440,4 480,4 524,8 585,3 651,7 743,4 792,2 838,6 -Input power1 kW 127,2 141,4 156,0 171,4 192,0 215,6 238,6 254,6 269,6 -EER / Energy efficiency class1 3,11/A 3,11/A 3,08/B 3,06/B 3,05/B 3,02/B 3,12/A 3,11/A 3,11/A -EER / Energy efficiency class*1 3,20/A 3,21/A 3,17/A 3,15/A 3,13/A 3,10/A 3,20/A 3,19/A 3,20/A -
SEER/ hsc2 (ErP 2021) 4,53/178 4,63/182 4,58/180 4,8/189 4,8/189 4,72/186 4,72/186 4,72/186 4,78/188 -
SEER/ hsc*2 (ErP 2021) 4,7/185 4,8/189 4,75/187 5,05/199 5,05/199 4,95/195 4,95/195 4,9/193 5/197 -
Nom. water flow (in the evaporator) m³/h 68,1 75,8 82,7 90,4 101 112 128 137 145 -Sound power level3 dB(A) 86 87 87 87 88 88 89 89 89 -Sound pressure level at 10 m4 dB(A) 54 54 54 54 55 55 56 56 56 -Power supply voltage** V/ph/Hz 400/3/50 (Nominal)
SYSCROLL 400-900 AIR EVO TR - Cooling only 400 450 490 530 600 670 750 800 850 900Nominal cooling capacity5 kW 398,8 446,1 487,7 533,9 597,1 667,3 748,3 797,9 847,2 896,7Input power5 kW 128,6 142,8 157,1 172,1 192,1 215,0 241,7 257,4 272,4 286,7EER5 3,10 3,12 3,10 3,10 3,11 3,10 3,10 3,10 3,11 3,13
SEER/ hsc2 (ErP 2018) 4,5/177 4,43/174 4,53/178 4,4/173 4,58/180 4,68/184 4,5/177 4,5/177 4,43/174 4,5/177
SEER/ hsc2 (ErP 2021) 4,68/184 4,6/181 4,68/184 4,58/180 4,83/190 4,85/191 4,65/183 4,68/184 4,6/181 4,63/182
Heat recovery capacity kW 513,1 566,1 620,1 679,2 760,3 851,7 957,9 1.026,6 1.082,3 1.137,6Nom. water flow (in the evaporator) m³/h 68,6 76,8 84 91,9 103 115 129 138 146 155Power supply voltage** V/ph/Hz 400/3/50 (Nominal)
SYSCROLL 400-900 AIR EVO HP - Heat Pump
Chilled liquid Liquid outlettemperature
Water °С from +5 to +18Water with glycol °С from -3 to +5ΔT K from 3 to 7
Outdoor air temperature Air enteringtemp. Cooling
STD / EC °С from +10 to +46S / EC S °С from -18 to +46
Warm Liquid Liquid outlettemperature
Water °С from +25 to +55ΔT K from 3 to 7
Outdoor air temperature Air enteringtemp. Heating
STD °С from -10 to +20S / EC / EC S °С from -10 to +35PH °С from -13 to +35
External static pressureStandard fans P 0High pressure fans (HPF) P <120
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
***ErP2018
***ErP2018
***ErP2018
***ErP2018
66 systemair
SYSCROLL 400-900 AIR EVO HP - Heat Pump 400 450 490 530 580 620 670 750 800 850 900
Cooling
Nominal cooling capacity1 kW 373,5 419,2 454,5 489,7 535,7 581,5 625,4 701,4 748,1 795,2 838,7Input power1 kW 132,3 147,8 160,9 173,0 190,2 206,1 221,5 247,4 263,8 280,5 295,4EER/ Energy efficiency class1 2,82/C 2,84/C 2,82/C 2,83/C 2,82/C 2,82/C 2,82/C 2,84/C 2,84/C 2,83/C 2,84/CEER/ Energy efficiency class*1 2,90/B 2,91/B 2,90/B 2,90/B 2,90/B 2,90/B 2,90/B 2,91/B 2,91/B 2,91/B 2,91/BSEER2 4,65 4,53 4,7 4,55 4,33 4,35 4,3 4,3 4,35 4,3 4,3
hsc2 183 178 185 179 170 171 169 169 171 169 169
SEER*2 4,93 4,83 4,97 4,88 4,5 4,5 4,45 4,45 4,47 4,47 4,47
hsc*2 194 190 196 192 177 177 175 175 176 176 176
Nom. water flow (in the evapor.) m³/h 64,3 72,1 78,2 84,3 92,2 100 108 121 129 137 145
Heating
Nominal heating capacity3 kW 404,0 450,9 492,7 532,1 585,8 627,7 677,8 758,3 807,3 856,9 901,6Input power3 kW 125,9 140,8 153,8 166,3 183,0 195,5 212,0 237,0 252,3 267,2 281,3COP3 3,21 3,20 3,20 3,20 3,20 3,21 3,20 3,20 3,20 3,21 3,21COP4 3,88 3,82 3,85 3,87 3,85 3,88 3,85 3,9 3,87 3,82 3,79
SCOP2 3,46 3,47 3,37 3,38 / / / / / / /Energy efficiency class2 A+ A+ A+ A+ / / / / / / /
hsh2 135 136 132 132 / / / / / / /
COP *3 3,30 3,29 3,29 3,29 3,29 3,31 3,29 3,29 3,29 3,29 3,29COP *4 4,0 3,94 3,98 4,0 3,98 4,01 3,98 4,03 4,0 3,94 3,91
SCOP*2 3,62 3,62 3,53 3,53 / / / / / / /Energy efficiency class2 A+ A+ A+ A+ / / / / / / /hsh
*2 142 142 138 138 / / / / / / /Nom. water flow (in the evapor.) m³/h 70,1 78,3 85,5 92,3 102 109 118 131 140 148 156
Sound power level5 dB(A) 92 93 93 94 94 95 95 95 95 96 96Sound pressure level at 10 m6 dB(A) 60 61 60 61 61 62 62 62 62 63 63Power supply voltage** V/ph/Hz 400 /3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825. 3 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.4 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB.5 Sound power level is declared in nominal full load condition (cooling operation), referring to ISO standard 9614, in accordance with Eurovent certification program.6 Sound pressure level refer to ISO Standard 3744, parallelepiped shape in a free field on a reflective surface.* EC version: brushless fan motors version.** Voltage 400V +/- 10%.*** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
SYSCROLL 400-900 AIR EVO HP S - Heat Pump 400 450 490 530 580 620 670 750 800 - -
Cooling
Nominal cooling capacity1 kW 371,2 417,3 453,4 487,3 531,4 578,6 621,5 701,5 743,2 - -Input power1 kW 128,1 143,6 156,5 167,6 183,3 199,0 214,1 241,4 256,6 - -EER/Energy efficiency class1 2,90/B 2,91/B 2,90/B 2,91/B 2,90/B 2,91/B 2,90/B 2,91/B 2,90/B - -EER/ Energy efficiency class *1 2,98/B 2,99/B 2,98/B 2,99/B 2,98/B 2,99/B 2,99/B 2,99/B 2,98/B - -SEER 2 5,03 4,53 5,1 5,05 4,6 4,6 4,55 4,55 4,58 - -
hsc 2 198 178 201 199 181 181 179 179 180 - -
SEER *2 5,35 5,33 5,45 5,48 4,75 4,72 4,7 4,65 4,65 - -
hsc*2 211 210 215 216 187 186 185 183 183 - -
Nom. water flow (in the evapor.) m³/h 63,9 71,8 78,0 83,9 91,5 99,6 107 121 128 - -
Heating
Nominal heating capacity3 kW 403,6 451,7 490,3 531,2 585,6 627,1 676,7 757,4 805,3 - -Input power3 kW 124,3 138,2 152,2 165,9 182,9 193,2 209,6 234,0 247,7 - -COP3 3,25 3,27 3,22 3,20 3,20 3,25 3,23 3,24 3,25 - -COP4 4,01 3,97 3,97 3,98 3,96 4,01 3,97 4,04 4,01 - -
SCOP2 3,76 3,76 3,69 3,68 / / / / / - -Energy efficiency class2 A+ A+ A+ A+ / / / / / - -
hsh2 147 147 145 144 / / / / / - -
COP *3 3,34 3,37 3,32 3,29 3,30 3,34 3,32 3,34 3,35 - -COP *4 4,16 4,11 4,11 4,12 4,11 4,16 4,11 4,19 4,15 - -
SCOP *2 3,99 3,98 3,91 3,89 / / / / / - -Energy efficiency class2 A++ A++ A++ A++ / / / / / - -
hsh*2 157 156 153 153 / / / / / - -
Nom. water flow (in the evapor.) m³/h 70,0 78,4 85,1 92,2 102 109 117 132 140 - -Sound power level5 dB(A) 86 87 87 87 88 88 88 89 89 - -Sound pressure level at 10 m6 dB(A) 53 54 54 54 55 55 55 56 56 - -Power supply voltage** V/ph/Hz 400 /3/50 (Nominal)
Technical performance
***ErP2018
***ErP2018
***ErP2018
***ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 67
Physical features
Hydraulic data (Evaporator and Condenser)Type of water connections VictaulicWater Inlet/Outlet diameter inch 4" 5" 6" WeightOperating weight STD / EC / HPF kg 3.028 3.367 3.783 4.069 4.317 4.524 5.536 5.607 5.906 6.253Operating weight S / EC S / HT kg 3.318 3.656 4.069 4.369 4.597 4.789 6.111 6.183 6.499 -Operating weight TR kg 3.409 3.763 4.198 4.498 4.832 5.100 6.264 6.365 6.679 7.047DimensionsLength STD / EC / HPF / TR mm 4.580 5.620 6.680 6.680 7.760 7.760 8.900 8.900 9.950 11.000Length S / EC S / HT mm 5.620 6.680 7.760 7.760 8.800 8.800 11.000 11.000 12.050 -Width mm 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
SYSCROLL 400-900 AIR EVO CO - Cooling only 400 450 490 530 600 670 750 800 850 900
SYSCROLL 400-900 AIR EVO HP - Heat Pump 400 450 490 530 580 620 670 750 800 850 900
Hydraulic data (evaporator)Type of water connections VictaulicWater Inlet/Outlet diameter inch 4" 5" 6" WeightOperating weight STD / EC / HPF Kg 3.769 3.938 4.412 4.744 5.214 5.554 5.691 6.790 6.985 7.231 7.408Operating weight S / EC S Kg 4.131 4.293 4.764 5.101 5.567 5.919 6.059 7.497 7.683 - -DimensionsLength STD / EC / HPF mm 5.620 5.620 6.680 6.680 7.760 8.800 8.800 9.950 9.950 11.000 11.000Length S / EC S mm 6.680 6.680 7.760 7.760 8.800 9.850 9.850 12.050 12.050 - -Width mm 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
BIM models available at www.magicad.com
68 systemair
SYSCROLL 240-660 AIR CO/HP/RE
The range at a glance 3 versions:
CO (Cooling only) and HP (Heat Pump) RE (Condensing unit)
10 sizes Cooling capacity from 238,1 to 654,2 kW Heating capacity from 255,9 to 679,1 kW 3 versions:
STD (Standard) HT (High Temperature) HPF (High Pressure Fans)
3 acoustic versions Standard version L (Low Noise) S (Super Low Noise)
Equipment Two refrigerant circuits Plate evaporator (AISI 316) 3/4/5/6 Scroll compressors “Brine” version: Cooling only for process application
LWT -10°C (CO version) Electronic expansion valve E-Coating coil treatment as standard Compressors acoustic box Compressors jackets (standard for S version) Fan speed control (standard for S version) (CO version) Sequence phases control Water differential pressure switch
* For Liquid outlet temperature <0 °C provide Brine Version (available for CO; upon request for HP).
SYSCROLL 240-660 AIR CO - Cooling only
Chilled liquid
Liquid outlettemp.
Water °C from +6 to +18Water with glycol* °C from -10 to +6
Temperature spread K from 3 to 7
Maximum operating pressure bar 6
Outdoor air tem-perature
Air enteringtemp.
STD °C from +10 to +45L °C from +7 to +43S °C from -14 to +43HT-HPF °C from -18 to +47
Externalstatic pressure
Standard fans Pa 0
HPF Pa < 120
Advantages
High seasonal performances → SEER up to 4.4 Common configuration for the different versions →
Easy upgrade of the units in stock or on field Electronic expansion device →Excellent control of
superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight Compressors box → Remarkable sound reduction
even for the basic noise version Control platform → Modular architecture, compressor
envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R410A
238-654 kWHOTELSOFFICES SCHOOLS INDUSTRY
256-679 kW
Air Cooled Chillers, Heat Pumps and Condensing units
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)SYSCROLL 240-660 AIR HP - Heat Pump
Cooling
Liquid outlettemperature
Water °С from +6 to +18Water with glycol* °С from -10 to +6ΔT K from 3 to 7
Air enteringtemp.
STD °С from +5 to +42L °С from +5 to +40S °С from -14 to +40HT-HPF °С from -18 to +44
External static pressure
Standard fans Pa 0HPF Pa <120
Heating
Liquid outlettemperature
Water °С from +20 to +52ΔT K from 3 to 7
Air enteringtemp.
STD / L / S °С from -10 to +20HT °С from -12 to +20
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsDesuperheater and total heat recovery (TR version)Hydrokit with 1 or 2 pumps with or without buffer tankOverload protection for compressorsMechanical gaugesPower factor corrector capacitorsSoftstarterSRC - Smart Remote Control (Mini BMS)Unit protection grillesWater flow switchWater filter
Plate heat exchanger
Scroll compressor
New
ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 69
SYSCROLL 240-660 AIR CO (STD/EC/HPF) - Cooling only 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 238,1 267,4 287,4 316,1 362,0 414,2 469,6 533,7 588,9 654,2Input power1 kW 83,8 99,0 103,4 111,6 128,3 148,7 160,9 183,9 198,1 221,6EER / Energy efficiency class1 2,84/C 2,70/C 2,78/C 2,83/C 2,82/C 2,78/C 2,92/B 2,90/B 2,97/B 2,95/BEER* / EER** 2,87/2,7 2,73/2,6 2,8/2,64 2,86/2,7 2,85/2,7 2,82/2,6 2,95/2,8 2,93/2,8 3,0/2,83 2,99/2,8
SEER2 3,93 3,8 3,85 3,98 3,93 4,18 4,13 4,38 4,4 4,43
hsc2 154 149 151 156 154 164 162 172 173 174
SEER* / SEER**2 4 3,88 3,93 4,05 4 4,2 4,1 4,47 4,47 4,43
hsc* / hsc
**2 157 152 154 159 157 165 161 176 176 174Nom. water flow (in the evaporator) m³/h 41,0 46,1 49,6 54,4 62,4 71,4 80,9 92,0 102 113Sound power level3 dB(A) 93 93 94 94 94 95 95 96 96 97Sound pressure level at 10 m4 dB(A) 61 61 62 62 62 63 63 64 64 64Power supply voltage5 V/Ph/Hz 400/3/50 (Nominal)
Technical performance
SYSCROLL 240-660 AIR CO L - Cooling only 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 230,0 256,9 277,6 303,8 348,5 398,6 451,7 513,1 566,5 628,8Input power1 kW 85,1 101,5 104,9 113,9 131,1 151,6 164,2 187,5 202,2 225,9EER / Energy efficiency class1 2,70/C 2,53/D 2,65/D 2,67/D 2,66/D 2,63/D 2,75/C 2,74/C 2,80/C 2,78/C
SEER2 3,93 3,8 3,85 3,95 3,98 4,18 4,1 4,25 4,3 4,4
hsc2 154 149 151 155 156 164 161 167 169 173
Nom. water flow (in the evaporator) m³/h 39,6 44,3 47,9 52,3 60,0 62,7 77,8 88,4 97,6 108Sound power level3 dB(A) 88 88 89 89 90 91 91 91 92 92Sound pressure level at 10 m4 dB(A) 56 56 57 57 58 59 59 59 59 59Power supply voltage5 V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 240-660 AIR CO S - Cooling only 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 214,4 236,9 259,0 280,6 323,0 368,9 418,3 474,2 524,1 580,9Input power1 kW 91,0 109,9 112,0 122,6 141,3 162,9 176,6 201,5 217,3 242,5EER / Energy efficiency class1 2,36 /E 2,16/F 2,31/E 2,29/F 2,29/F 2,26/F 2,37/E 2,35/E 2,41/E 2,40/E
SEER2 3,85 3,83 3,83 3,83 3,88 4,22 4,13 4,22 4,4 4,2
hsc2 151 150 150 150 152 166 162 166 173 165
Nom. water flow (in the evaporator) m³/h 37,0 40,8 44,7 48,3 55,6 63,6 72,0 81,7 90,3 100Sound power level3 dB(A) 85 86 87 87 88 88 89 89 90 90Sound pressure level at 10 m4 dB(A) 53 54 55 55 56 56 57 57 57 57Power supply voltage5 V/Ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.5 Voltage 400V +/- 10%.* High Temperature Unit (HT) with inverter fans.** HPF Units with high static pressure fans. *** 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
SYSCROLL 240-660 AIR RE - Condensing unitEvaporating temperature °C from +7 to +35
Outdoor air temperature
STD °C from +10 to +45L °C from +7 to +43S °C from -14 to +43HT-HPF °C from -18 to +47
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
SYSCROLL 240-660 AIR TR - Cooling only 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 233,7 266,1 280,1 321,2 365,4 413,9 474,9 535,1 596,3 659,2Input power1 kW 83,9 99 103 112 128 149 161 184 198 222EER1 2,85 2,71 2,79 2,84 2,83 2,80 2,93 2,91 2,98 2,97
SEER2 3,93 3,8 3,85 3,98 3,93 4,18 4,13 4,38 4,4 4,43
hsc2 154 149 151 156 154 164 162 172 173 174
Total heat rejection 313,4 360,3 382,5 422,6 483,2 553,3 622,0 706,5 777,7 864,9Nom. water flow (in the evaporator) m³/h 41,0 46,1 49,6 54,4 62,4 71,4 80,9 92,0 102 113Power supply voltage5 V/Ph/Hz 400/3/50 (Nominal)
***ErP2018
***ErP2018
***ErP2018
***ErP2018
70 systemair
SYSCROLL 240-660 AIR HP (STD/EC/HPF) - Heat Pump 240 270 290 320 360 420 470 540 590 660
Cooling
Nominal cooling capacity1 kW 216,5 251,6 263,8 287,1 330,0 380,7 435,1 481,9 530,7 580,6Input power1 kW 85,5 100,5 105,2 113,9 131,3 151,7 169,1 189,9 207,3 228,3EER/ Energy efficiency class1 2,53/D 2,50/D 2,51/D 2,52/D 2,51/D 2,51/D 2,57/D 2,54/D 2,56/D 2,54/DEER*/EER** 2,56/2,41 2,53/2,4 2,54/2,38 2,55/2,41 2,54/2,4 2,54/2,4 2,60/2,46 2,56/2,42 2,59/2,44 2,57/2,43SEER3 4,25 4,25 4,1 3,83 4,18 3,85 3,85 4,22 4,3 4,25
hsc3 167 167 161 150 164 151 151 166 169 167
SEER*3 3,9 3,9 4,28 3,88 4,2 4,35 4,2 4,3 4,43 4,33
hsc*3 153 153 168 152 165 171 165 169 174 170
Nom. water flow (in the evapor.) m³/h 37,3 43,4 45,5 49,4 56,8 65,6 74,9 83,0 91,4 100
Heating
Nominal heating capacity2 kW 255,9 289,1 313,3 333,0 382,4 444,0 491,5 556,4 605,0 679,1Input power2 kW 92,7 106,8 117 117,4 136,2 159,7 170,5 191,2 209,2 231,1COP2 2,76 2,71 2,68 2,84 2,81 2,78 2,88 2,91 2,89 2,94COP* 2,79 2,73 2,71 2,87 2,84 2,81 2,91 2,94 2,92 2,97COP** 2,63 2,6 2,56 2,71 2,68 2,66 2,75 2,78 2,76 2,81COP4 3,69 3,6 3,56 3,79 3,75 3,71 3,84 3,88 3,85 3,9COP4* 3,74 3,64 3,61 3,84 3,8 3,76 3,9 3,94 3,9 3,95COP4** 3,47 3,41 3,36 3,57 3,53 3,5 3,62 3,66 3,62 3,68
SCOP /Energy eff. class3 3,39/ A+ 3,50/ A+ 3,38/ A+ 3,59/ A+ 3,51/ A+ 3,64/ A+ 3,42/ A+ - - -hsh
3 133 137 132 141 137 143 134 - - -Nom. water flow (in the evapor.) m³/h 44,3 50,0 54,2 57,8 66,3 76,9 85,2 96,4 105 118
Sound power level5 dB(A) 93 93 94 94 94 95 95 96 96 97Sound pressure level at 10 m6 dB(A) 61 61 62 62 62 63 63 64 63 64Power supply voltage7 V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 240-660 AIR HP L - Heat Pump 240 270 290 320 360 420 470 540 590 660
Cooling
Nominal cooling capacity1 kW 204,9 236,3 249,9 269,8 311,1 358,4 409,7 453,2 499,5 545,9Input power1 kW 88,6 105,2 109,0 118,7 137,0 158,0 176,3 197,8 216,1 237,8EER/ Energy efficiency class1 2,31/E 2,24/F 2,29/F 2,27/F 2,27/F 2,27/F 2,32/E 2,29/F 2,31/E 2,30/FSEER3 3,85 3,85 4,18 3,83 4,1 4,25 4,25 4,28 4,3 4,3
hsc3 151 151 164 150 161 167 167 168 169 169
Nom. water flow (in the evapor.) m³/h 35,3 40,7 43,1 46,4 53,6 61,7 70,5 78,1 86,0 94,1
Heating
Nominal heating capacity2 kW 253,0 285,5 309,7 328,9 377,7 438,6 485,4 539,8 597,5 670,7Input power2 kW 90,1 104,1 113,6 114,1 132,3 155,1 165,7 188 202,7 224COP2 2,81 2,74 2,72 2,88 2,86 2,83 2,93 2,87 2,95 2,99COP4 3,78 3,66 3,64 3,87 3,83 3,79 3,93 3,97 3,93 3,98
SCOP /Energy eff. class3 3,39/ A+ 3,50/ A+ 3,38/ A+ 3,65/ A+ 3,51/ A+ 3,64/ A+ 3,49/ A+ - - -
hsh3 133 137 132 143 137 143 137 - - -
Nom. water flow (in the evapor.) m³/h 43,8 49,4 53,6 57,0 65,5 76,0 84,2 93,5 104 116Sound power level5 dB(A) 88 88 89 89 90 91 91 91 92 92Sound pressure level at 10 m6 dB(A) 56 56 57 57 58 59 59 59 59 59Power supply voltage7 V/Ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.2 According EN14511-2013: warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB with 87% R.H.3 According EN14825.4 According EN14511-2013: warm water inlet/outlet temperature: 30/35°C, outdoor ambient temperature 7°C DB/6°C WB with 87% R.H.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.7 Voltage 400V +/- 10%.* High Temperature Unit (HT) with inverter fans. / ** HPF Units with high static pressure fans.*** ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 17 for more information).
SYSCROLL 240-660 AIR HP S - Heat Pump 240 270 290 320 360 420 470 540 590 660
Cooling
Nominal cooling capacity1 kW 186,8 212,3 228,4 243,4 281,5 324,0 370,5 409,0 451,5 492,5Input power1 kW 96,3 115,5 117,9 129,4 149,7 172,0 192,4 215,4 235,6 258,9EER/ Energy efficiency class1 1,94/G 1,84/G 1,94/G 1,88/G 1,88/G 1,88/G 1,93/G 1,90/G 1,92/G 1,90/GSEER3 3,85 3,85 4,18 3,83 4,1 4,25 4,25 4,28 4,3 4,3hsc
3 151 151 164 150 161 167 167 168 169 169Nom. water flow (in the evapor.) m³/h 32,2 36,6 39,4 41,9 48,5 55,8 63,8 70,4 77,7 84,8
Heating
Nominal heating capacity2 kW 249,0 280,7 304,8 323,3 371,4 431,3 477,3 540,4 587,5 659,5Input power2 kW 87,5 101 110 111,1 128,8 150,6 161,4 179,9 197,4 219,8COP2 2,85 2,78 2,77 2,91 2,88 2,86 2,96 3,00 2,98 3,00COP4 3,8 3,67 3,66 3,88 3,84 3,8 3,94 3,99 3,95 4
SCOP /Energy eff. class 5 3,39/ A+ 3,50/ A+ 3,38/ A+ 3,65/ A+ 3,51/ A+ 3,64/ A+ 3,49/ A+ - - -hsh
3 133 137 132 143 137 143 137 - - -Nom. water flow (in the evapor.) m³/h 43,1 48,6 52,7 56,1 64,4 74,7 82,8 93,6 102 114
Sound power level5 dB(A) 85 86 87 87 88 88 89 89 90 90Sound pressure level at 10 m6 dB(A) 53 54 55 55 56 56 57 57 57 57Power supply voltage7 V/Ph/Hz 400/3/50 (Nominal)
Technical performance
***ErP2018
***ErP2018
***ErP2018
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 71
1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound power levels in full load condition refer to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* Voltage 400V +/- 10%.
SYSCROLL 240-360 AIR RE - Condensing unit 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 267,5 303,1 330,7 349,9 403,2 466,2 518,8 594,9 650,4 726,7Input power1 kW 85,3 101 106 114 131 152 164 188 201 225Sound power level2 dB(A) 93 93 94 94 94 95 95 96 96 97Sound pressure level at 10 m3 dB(A) 61 61 62 62 62 63 63 64 64 64Power supply voltage* V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 240-360 AIR RE L - Condensing unit 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 256,7 288,7 316,7 333,9 385,4 444,8 495,9 567,7 621,5 693,4Input power1 kW 87,0 104 108 117 134 156 168 192 206 231Sound power level2 dB(A) 88 88 89 89 90 91 91 91 92 92Sound pressure level at 10 m3 dB(A) 56 56 57 57 58 59 59 59 59 59Power supply voltage* V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 240-360 AIR RE S - Condensing unit 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 236,4 262,0 262,0 304,4 352,6 405,5 453,6 517,5 568,1 632,2Input power1 kW 93,7 114 116 126 146 168 182 207 223 249Sound power level2 dB(A) 85 86 87 87 88 88 89 89 90 90Sound pressure level at 10 m3 dB(A) 53 54 55 55 56 56 57 57 57 57Power supply voltage* V/Ph/Hz 400/3/50 (Nominal)
SYSCROLL 240-660 AIR CO/HP - Cooling only / Heat Pump 240 270 290 320 360 420 470 540 590 660
Hydraulic dataType of water connections (evaporator) Male gas threaded VictaulicWater Inlet/Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Weight (CO version)Operating weight STD / S / L kg 1.912 1.914 1.962 2.034 2.434 2.488 3.158 3.209 3.701 3.759Operating weight TR kg 1.946 1.947 2.039 2.160 2.554 2.665 3.218 3.331 3.793 3.889Weight (HP version)Operating weight kg 2.336 2.336 2.440 2.512 2.955 3.062 3.754 3.875 4.446 4.565DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Physical features
SYSCROLL 240-360 AIR RE - Condensing unit 240 270 290 320 360 420 470 540 590 660
Refrigerant connection
Refrigerant In connections inch 1 5/8” - 2 1/8”
1 5/8” - 2 1/8”
1 5/8” - 2 1/8”
1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8” -
2 5/8”2 1/8” - 2 5/8” 2 5/8” 2 5/8”
Refrigerant Out connections inch 7/8” - 1 1/8”
7/8” - 1 1/8”
7/8” - 1 3/8”
7/8” - 1 3/8”
1 1/8” - 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8”
WeightShipping weight kg 1.670 1.671 1.790 1.802 2.185 2.296 2.747 2.860 3.237 3.333DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
72 systemair
SYSCREW 380-1260 AIR EVO CO HSEAir Cooled Chillers
366-1.241 kW
R134a
Screw compressorR513A
The range at a glance 1 version:
CO (Cooling only) 12 sizes Cooling capacity from 366 to 1.240,5 kW 3 acoustic versions:
STD (Standard) HT (High Temperature) HPF (High Pressure Fans) 2 acoustic versions:
Standard version S (Super Low Noise)
Equipment Two refrigerant circuits Two screw compressors Pure countercurrent shell and tubes direct expansion
heat exchanger Axial type EC fan motors Micro-channels condensers Electronic expansion valve Hydronic / heat recovery options
Advantages
High seasonal efficiency level exceeding Erp 2021 requirements
High durability painting process for casing and frame, offering C4 corrosion category in accordance with ISO 12944
Compressor metal box, providing basic acoustic protection and resistance to atmospheric agents
Side panel on coil ends, protecting from corrosion and damages
EC fan motors, improving part load efficiency, extending envelope operation and reducing noise level in part load operation
Proprietary software logic, optimizing unit efficiency in accordance with plant needs and protecting unit operation with preventing actions
SYSCREW 380-1260 AIR EVO CO HSE - Cooling only
Leaving Water Temperature
Water °С from +5 to +15Brine (brine application) °С from -8 to 0Brine (std application) °С from +0 to +5∆ T K from +3 to +8
Outdoor air temperature
STD °С from -10 to +46S °С from -10 to +44HT °С from -10 to +49Min. Air temperature °C -10
External static pressureStandard fans Pа 0High pressure fans Pа < 120
Shell & Tube evaporator
ErP20182021
2021Ready.*
HOTELSOFFICES INDUSTRYHOSPITALS
H
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
New
Accessories and optionsAntifreeze electric heater for hydraulic manifoldsBMS interfaceChiller grillesCompressor acoustic boxCompressor’ Star Delta StartCompressor suction valveE-Coating treatmentFinned tubes (Al/Cu)Flow switchHydro kit 1P-SP/1P-HP/2P-SP/2PHPMechanical gauges kit (HP and LP manometers)NetTune (managing a network of up to 6 units)Power factor corrector capacitorsSpring AVM isoltor for basic unitVariable pumpWater filter
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 73
SYSCREW AIR EVO CO HSE R134a (STD/HT/HPF) - Cooling only 380 440 510 590 660 730Nominal cooling capacity1 kW 362,0 438,6 495,2 560,2 637,1 697,3Input power1 kW 120,1 139,2 159,7 175,5 199,8 221,5EER/ Energy Efficiency Class1 3,01/B 3,15/A 3,10/A 3,19/A 3,19/A 3,15/AEER CONDITION B (74%) 4,04 4,10 4,08 4,11 4,02 4,04EER CONDITION C (47%) 4,78 4,91 4,94 5,07 4,85 4,75EER CONDITION D (21%) 6,24 6,41 6,43 6,77 6,74 6,34
SEER2 4,63 4,74 4,75 4,88 4,75 4,65ηs,c
2 % 182 187 187 192 187 183Number of refrigerant circuits 2Total capacity steps5 % 22%÷100% 18%÷100% 16%÷100% 14%÷100% 13%÷100% 15%÷100%Sound power level3 dB(A) 97 98 100 100 100 101Sound power level3**/*** dB(A) 102 103 104 104 104 105Sound pressure level at 10 m4 dB(A) 65 66 68 68 68 68Sound pressure level at 10 m4**/*** dB(A) 70 71 72 72 72 72
1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511-2013 standard.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.4 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape. 5 This value can change for BC version or other special applications.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).** High Temperature Units (HT), data with fans at max speed (1100 Rpm).*** HPF Units, data with fans at max speed (1100 Rpm).
R134a
SYSCREW AIR EVO CO HSE R134a (STD/HT/HPF) - Cooling only 810 900 980 1060 1160 1260Nominal cooling capacity1 kW 770,4 888,1 973,8 1037,1 1142,6 1228,2Input power1 kW 245,6 281,2 312,3 321,7 358,9 395,5EER/ Energy Efficiency Class1 3,14/A 3,16/A 3,12/A 3,22/A 3,18/A 3,11/AEER CONDITION B (74%) 3,96 3,89 3,99 4,20 4,23 4,28EER CONDITION C (47%) 4,83 4,77 4,80 5,03 5,16 5,12EER CONDITION D (21%) 6,69 6,39 6,33 6,81 6,84 6,81
SEER2 4,71 4,63 4,66 4,91 4,96 4,94ηs,c
2 % 185 182 183 193 195 195Number of refrigerant circuits 2Total capacity steps5 % 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%Sound power level3 dB(A) 101 102 102 103 103 103Sound power level3**/*** dB(A) 105 106 106 107 108 108Sound pressure level at 10 m4 dB(A) 68 69 69 70 70 70Sound pressure level at 10 m4**/*** dB(A) 72 73 73 74 75 75
SYSCREW AIR EVO CO HSE S R134a - Cooling only 380 440 510 590 660 730Nominal cooling capacity1 kW 359,2 437,4 493,3 557,5 633,7 695,6Input power1 kW 122,2 140,4 162,8 178,4 202,8 224,4EER/ Energy Efficiency Class1 2,94/B 3,12/A 3,03/B 3,13/A 3,12/A 3,10/AEER CONDITION B (74%) 4,00 4,11 4,08 4,10 4,05 4,07EER CONDITION C (47%) 4,81 5,18 5,18 5,32 5,04 5,01EER CONDITION D (21%) 6,54 6,93 6,86 7,04 7,01 6,76
SEER2 4,66 4,92 4,90 5,00 4,87 4,82ηs,c
2 % 184 194 193 197 192 190Number of refrigerant circuits 2Total capacity steps5 % 22%÷100% 18%÷100% 16%÷100% 14%÷100% 13%÷100% 15%÷100%Sound power level3 dB(A) 94 94 97 97 97 98Sound pressure level at 10 m4 dB(A) 62 62 65 65 65 65
SYSCREW AIR EVO CO HSE S R134a - Cooling only 810 900 980 1060 1160 1260Nominal cooling capacity1 kW 768,3 884,2 971,2 1035,1 1139,2 1222,6Input power1 kW 248,4 285,6 316,3 325,1 363,4 403,9EER/ Energy Efficiency Class1 3,09/B 3,10/A 3,07/B 3,18/A 3,13/A 3,03/BEER CONDITION B (74%) 3,98 3,91 4,13 4,25 4,25 4,29EER CONDITION C (47%) 5,09 5,06 5,11 5,33 5,35 5,41EER CONDITION D (21%) 6,97 6,71 6,52 7,12 7,31 7,17
SEER2 4,84 4,79 4,85 5,08 5,10 5,09ηs,c
2 % 191 189 191 200 201 201Number of refrigerant circuits 2Total capacity steps5 % 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%Sound power level3 dB(A) 98 99 99 99 100 100Sound pressure level at 10 m4 dB(A) 65 66 66 66 67 67
Technical performance
*ErP2018
*ErP2018
*ErP2018
*ErP2018
74 systemair
SYSCREW AIR EVO CO HSE R513A (STD/HT/HPF) - Cooling only 380 440 510 590 660 730Nominal cooling capacity1 kW 365,7 443,0 500,2 565,8 643,5 704,3Input power1 kW 123,9 142,9 165,6 181,1 206,2 228,6EER/ Energy Efficiency Class1 2,95/B 3,10/A 3,02/B 3,12/A 3,12/A 3,08/BEER CONDITION B (74%) 3,95 4,01 3,99 4,02 3,93 3,95EER CONDITION C (47%) 4,66 4,81 4,81 5,03 4,76 4,66EER CONDITION D (21%) 6,14 6,31 6,33 6,65 6,62 6,23
SEER2 4,53 4,66 4,65 4,80 4,66 4,56ηs,c
2 % 178 183 183 189 183 179Number of refrigerant circuits 2Total capacity steps5 % 22%÷100% 18%÷100% 16%÷100% 14%÷100% 13%÷100% 15%÷100%Sound power level3 dB(A) 97 98 100 100 100 101Sound power level3**/*** dB(A) 102 103 104 104 104 105Sound pressure level at 10 m4 dB(A) 65 66 68 68 68 68Sound pressure level at 10 m4**/*** dB(A) 70 71 72 72 72 72
R513A
SYSCREW AIR EVO CO HSE R513A (STD/HT/HPF) - Cooling only 810 900 980 1060 1160 1260Nominal cooling capacity1 kW 778,1 896,9 983,5 1047,4 1154,0 1240,5Input power1 kW 253,4 290,2 322,3 332,0 370,4 408,1EER/ Energy Efficiency Class1 3,07/B 3,09/B 3,05/B 3,15/A 3,12/A 3,04/BEER CONDITION B (74%) 3,89 3,82 3,98 4,10 4,14 4,20EER CONDITION C (47%) 4,72 4,68 4,72 5,10 5,06 5,02EER CONDITION D (21%) 6,62 6,32 6,22 6,69 6,70 6,68
SEER2 4,62 4,56 4,60 4,87 4,86 4,85ηs,c
2 % 182 179 181 192 191 191Number of refrigerant circuits 2Total capacity steps5 % 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%Sound power level3 dB(A) 101 102 102 103 103 103Sound power level3**/*** dB(A) 105 106 106 107 108 108Sound pressure level at 10 m4 dB(A) 68 69 69 70 70 70Sound pressure level at 10 m4**/*** dB(A) 72 73 73 74 75 75
SYSCREW AIR EVO CO HSE S R513A - Cooling only 380 440 510 590 660 730Nominal cooling capacity1 kW 362,8 441,8 498,2 563,1 640,0 702,5Input power1 kW 126,1 144,9 168,0 184,0 209,3 231,5EER/ Energy Efficiency Class1 2,88/C 3,05/B 2,97/B 3,06/B 3,06/B 3,03/BEER CONDITION B (74%) 3,90 4,03 3,99 4,00 3,96 3,97EER CONDITION C (47%) 4,69 5,04 5,05 5,21 4,95 4,91EER CONDITION D (21%) 6,44 6,82 6,75 6,92 6,93 6,64
SEER2 4,56 4,82 4,79 4,89 4,78 4,73ηs,c
2 % 180 190 189 193 188 186Number of refrigerant circuits 2Total capacity steps5 % 22%÷100% 18%÷100% 16%÷100% 14%÷100% 13%÷100% 15%÷100%Sound power level3 dB(A) 94 94 97 97 97 98Sound pressure level at 10 m4 dB(A) 62 62 65 65 65 65
SYSCREW AIR EVO CO HSE S R513A - Cooling only 810 900 980 1060 1160 1260Nominal cooling capacity1 kW 775,9 893,1 980,9 1045,5 1150,6 1234,8Input power1 kW 256,4 294,7 326,4 335,5 375,0 416,8EER/ Energy Efficiency Class1 3,03/B 3,03/B 3,01/B 3,12/A 3,07/B 2,96/BEER CONDITION B (74%) 4,01 3,84 4,18 4,15 4,22 4,31EER CONDITION C (47%) 4,98 4,94 5,02 5,24 5,36 5,30EER CONDITION D (21%) 6,71 6,60 6,55 7,00 7,24 7,04
SEER2 4,77 4,69 4,82 4,98 5,07 5,03ηs,c
2 188 185 190 196 200 198Number of refrigerant circuits 2Total capacity steps5 % 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%Sound power level3 dB(A) 98 99 99 99 100 100Sound pressure level at 10 m4 dB(A) 65 66 66 66 67 67
Technical performance
*ErP2018
*ErP2018
*ErP2018
*ErP2018
1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511-2013 standard.2 According EN14825.3 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.4 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape. 5 This value can change for BC version or other special applications.* 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).** High Temperature Units (HT), data with fans at max speed (1100 Rpm).*** HPF Units, data with fans at max speed (1100 Rpm).
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 75
Physical features
WeightOperating Weight kg 3.896 4.259 4.897 5.241 5.620 6.207 6.531 7.326 7.764 8.491 8.875 9.074Operating Weight S kg 3.981 4.352 4.990 5.323 5.702 6.293 6.617 7.412 7.852 8.579 8.963 9.162DimensionsLength mm 4.660 5.712 5.712 6.764 7.816 7.816 8.868 9.920 10.972 12024 13.076 13.076Width mm 2.192 2.192 2.192 2.192 2.192 2.192 2.192 2.192 2.192 2.192 2.192 2.192Height mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510Height S mm 2.590 2.590 2.590 2.590 2.590 2.590 2.590 2.590 2.590 2.590 2.590 2.590
SYSCREW 380-1260 AIR EVO CO HSE - Cooling only 380 440 510 590 660 730 810 900 980 1060 1160 1260
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
BIM models available at www.magicad.com
AIREC brushless fan motor technology
REFRIGERANTInverter driven compressor technology and electronic expansion valve
WATERInverter driven pumptechnology
Improved part load efficiency Continuous capacity control Flexible offer in plant integration
�
�
�
Technologic Innovation All-round variable volume flow management
76 systemair
SYSCREW 370-1250 AIR EVO COAir Cooled Chillers
ErP2018
HFOHFC R513A
SYSCREW 370-1250 AIR EVO CO - Cooling only
Leaving water temperature
Water °С from +5 to +15Water + glycol °С from 0 to +15Water + glycol (Brine Version) °С from -8 to +15∆ T K from 3 to 8
Outdoor air temperature
STD °С from +0 to +49L/S °С from +0 to +47HT °С from -10 a +51
Minimum Air temperature Polar Version °C -18
External static pressureStandard fans Pа 0Inverter fans Pа < 120
The range at a glance 1 version:
CO (Cooling only) 13 sizes Cooling capacity from 360 to 1.250 kW 3 acoustic versions:
Standard version L (Low Noise) S (Super Low Noise)
Equipment Two refrigerant circuits Two Screw compressors One S&T evaporator Electronic expansion valve “Brine” version for process application LWT -8°C “Polar” version for air temperature -18°C E-Coating coil treatment as standard Compressors acoustic box Sequence phases control
Advantages
High performances → EER up to 3.3, SEER up to 4.1 Common configuration for the different versions →
Easy upgrade of the units in stock or on field Electronic expansion device → Excellent control of
superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight New generation of pure counter-current shell&tube
evaporators → Maximum efficiency and new levels of competitiveness
Compressors box → Remarkable sound reduction Control platform → Modular architecture, compressor
envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R134a
360-1.250 kWHOTELSOFFICES INDUSTRYHOSPITALS
H
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsCompressor stepless controlDesuperheater and total heat recovery (TR)Hydrokit with 1 or 2 pumpsMechanical gaugesPressostatic fan speed controlPower factor corrector capacitorsSoftstarterSRC - Smart Remote Control (Mini BMS)Unit protection grillesWater filterWater flow switch
Screw compressor
Shell & Tube evaporator
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 77
SYSCREW 370-1250 AIR EVO CO R134a - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 364,1 414,5 445,5 502,9 562,1 625,5 712,9Power input1 kW 112,7 130,4 143,5 159,9 176,5 197,7 223,5EER / Energy efficiency class1 3,23/A 3,18/A 3,11/A 3,15/A 3,18/A 3,16/A 3,19/A
SEER2 4,13 4,18 4,18 4,18 4,18 4,18 4,18
hsc2 162 164 164 164 164 164 164
Sound power level3 dB(A) 97 98 98 98 99 99 99Sound pressure level at 10 m4 dB(A) 65 66 66 66 67 67 67Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R134a L - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 354,6 401,7 438,5 478,8 547,5 610,5 702,3Power input1 kW 111,8 126,4 142,5 159,0 176,4 199,6 224,3EER / Energy efficiency class1 3,17/A 3,18/A 3,08/B 3,01/B 3,10/A 3,06/B 3,13/A
SEER2 4,23 4,28 4,25 4,2 4,2 4,15 4,15
hsc2 166 168 167 165 165 163 163
Sound power level3 dB(A) 91 92 92 92 93 93 94Sound pressure level at 10 m4 dB(A) 59 60 60 60 61 61 61Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R134a S - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 354,6 401,7 438,5 478,8 547,5 610,5 702,3Power input1 kW 111,8 126,4 142,5 159,0 176,4 199,6 224,3EER / Energy efficiency class1 3,17/A 3,18/A 3,08/B 3,01/B 3,10/A 3,06/B 3,13/A
SEER2 4,1 4,15 4,18 4,15 4,15 4,18 4,18
hsc2 161 163 164 163 163 164 164
Sound power level3 dB(A) 87 88 88 88 89 89 90Sound pressure level at 10 m4 dB(A) 55 56 56 56 57 57 58Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
Physical features
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 6" 6" 6" 8" 8" 8" 8"WeightOperating weight STD/L kg 3.580 3.930 3.960 4.900 5.260 5.290 5.660Operating weight S kg 3.660 4.030 4.050 4.990 5.340 5.370 5.740DimensionsLength mm 4.600 5.700 5.700 5.700 6.700 6.700 7.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height STD/L mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510Height S mm 2.610 2.610 2.610 2.610 2.610 2.610 2.610
SYSCREW 370-700 AIR EVO CO R134a - Cooling only 370 400 450 500 570 650 700
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
*ErP2018
*ErP2018
R134a
78 systemair
Physical features
Water connection (Evaporator)Type of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 8" 8" 8" 10" 10" 10"WeightOperating weight STD/L kg 6.610 6.970 7.760 8.210 8.610 9.010Operating weight S kg 6.690 7.050 7.850 8.300 8.700 9.100DimensionsLength mm 7.800 8.800 9.900 10.900 12.000 13.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200Height STD/L mm 2.510 2.510 2.510 2.510 2.510 2.510Height S mm 2.610 2.610 2.610 2.610 2.610 2.610
SYSCREW 750-1250 AIR EVO CO R134a - Cooling only 750 850 950 1000 1100 1250
SYSCREW 370-1250 AIR EVO CO R134a - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 749,2 839,0 961,8 1.019,0 1.117,9 1.249,1Power input1 kW 237,4 261,2 288,6 312,8 340,0 394,0EER1 / Energy efficiency class 3,16/A 3,21/A 3,33/A 3,26/A 3,29/A 3,17/A
SEER2 4,18 4,15 4,18 4,18 4,18 4,20
hsc2 164 163 164 164 164 165
Sound power level3 dB(A) 100 100 101 101 102 103Sound pressure level at 10 m4 dB(A) 67 67 68 68 69 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R134a L - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 722,2 814,4 922,4 981,4 1.086,0 1.213,9Power input1 kW 237,7 264,2 288,3 309,8 339,3 395,4EER1 / Energy efficiency class 3,04/B 3,08/B 3,20/A 3,17/A 3,20/A 3,07/B
SEER2 4,15 4,15 4,15 4,18 4,23 4,35
hsc2 163 163 163 164 166 171
Sound power level3 dB(A) 94 94 95 95 96 97Sound pressure level at 10 m4 dB(A) 61 61 62 62 63 64Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R134a S - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 722,2 814,4 922,4 981,4 1.086,0 1.213,9Power input1 kW 237,7 264,2 288,3 309,8 339,3 395,4EER1 / Energy efficiency class 3,04/B 3,08/B 3,20/A 3,17/A 3,20/A 3,07/B
SEER2 4,15 4,18 4,18 4,18 4,18 4,25
hsc2 163 164 164 164 164 167
Sound power level3 dB(A) 90 90 91 91 92 93Sound pressure level at 10 m4 dB(A) 57 57 58 58 59 60Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
*ErP2018
*ErP2018
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
R134a
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 79
SYSCREW 370-1250 AIR EVO CO R513A - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 360,4 410,4 441,1 497,9 556,4 619,2 705,8Power input1 kW 118,6 137,3 151,0 168,2 186,1 208,5 235,3EER / Energy efficiency class1 3,04/B 2,99/B 2,92/B 2,96/B 2,99/B 2,97/B 3,00/B
SEER2 4,10 4,10 4,10 4,10 4,10 4,10 4,10
hsc2 161 161 161 161 161 161 161
Sound power level3 dB(A) 97 98 98 98 99 99 99Sound pressure level at 10 m4 dB(A) 65 66 66 66 67 67 67Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R513A L - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 351,1 397,7 434,2 474,0 542,0 604,4 695,2Power input1 kW 117,8 133,0 149,7 167,5 186,3 209,9 236,5EER / Energy efficiency class1 2,98/B 2,99/B 2,90/B 2,83/C 2,91/B 2,88/C 2,94/B
SEER2 4,14 4,20 4,18 4,13 4,13 4,10 4,10
hsc2 163 165 164 162 162 161 161
Sound power level3 dB(A) 91 92 92 92 93 93 94Sound pressure level at 10 m4 dB(A) 59 60 60 60 61 61 61Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R513A S - Cooling only 370 400 450 500 570 650 700Cooling capacity1 kW 354,6 401,7 438,5 478,8 547,5 610,5 702,3Power input1 kW 117,8 133,0 149,7 167,5 186,3 209,9 236,5EER / Energy efficiency class1 2,98/B 2,99/B 2,90/B 2,83/C 2,91/B 2,88/C 2,94/B
SEER2 4,10 4,10 4,10 4,10 4,10 4,10 4,10
hsc2 161 161 161 161 161 161 161
Sound power level3 dB(A) 87 88 88 88 89 89 90Sound pressure level at 10 m4 dB(A) 55 56 56 56 57 57 58Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Physical features
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 6" 6" 6" 8" 8" 8" 8"WeightOperating weight STD/L kg 3.580 3.930 3.960 4.900 5.260 5.290 5.660Operating weight S kg 3.660 4.030 4.050 4.990 5.340 5.370 5.740DimensionsLength mm 4.600 5.700 5.700 5.700 6.700 6.700 7.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height STD/L mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510Height S mm 2.610 2.610 2.610 2.610 2.610 2.610 2.610
SYSCREW 370-700 AIR EVO CO R513A - Cooling only 370 400 450 500 570 650 700
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
*ErP2018
*ErP2018
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
R513A
80 systemair
Physical features
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 8" 8" 8" 10" 10" 10"WeightOperating weight STD/L kg 6.610 6.970 7.760 8.210 8.610 9.010Operating weight S kg 6.690 7.050 7.850 8.300 8.700 9.100DimensionsLength mm 7.800 8.800 9.900 10.900 12.000 13.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200Height STD/L mm 2.510 2.510 2.510 2.510 2.510 2.510Height S mm 2.610 2.610 2.610 2.610 2.610 2.610
SYSCREW 750-1250 AIR EVO CO R513A - Cooling only 750 850 950 1000 1100 1250
SYSCREW 370-1250 AIR EVO CO R513A - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 740,8 829,4 952,1 1008,8 1106,7 1236,6Power input1 kW 251,1 276,5 304,2 329,7 358,2 415,0EER / Energy efficiency class1 2,95/B 3,00/B 3,13/B 3,06/B 3,09/B 2,98/B
SEER2 4,10 4,10 4,10 4,10 4,10 4,13
hsc2 161 161 161 161 161 162
Sound power level3 dB(A) 100 100 101 101 102 103Sound pressure level at 10 m4 dB(A) 67 67 68 68 69 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R513A L - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 714,9 806,3 913,2 971,6 1075,2 1201,7Power input1 kW 250,0 278,0 303,4 326,0 357,2 415,9EER / Energy efficiency class1 2,86/C 2,90/B 3,01/B 2,98/B 3,01/B 2,89/C
SEER2 4,10 4,10 4,10 4,10 4,15 4,28
hsc2 161 161 161 161 163 168
Sound power level3 dB(A) 94 94 95 95 96 97Sound pressure level at 10 m4 dB(A) 61 61 62 62 63 64Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 370-1250 AIR EVO CO R513A S - Cooling only 750 850 950 1000 1100 1250Cooling capacity1 kW 722,2 814,4 922,4 981,4 1.086,0 1.213,9Power input1 kW 250,0 278,0 303,4 326,0 357,2 416,0EER / Energy efficiency class1 2,86/C 2,90/B 3,01/B 2,98/B 3,01/B 2,89/C
SEER2 4,10 4,10 4,10 4,10 4,10 4,18
hsc2 161 161 161 161 161 164
Sound power level3 dB(A) 90 90 91 91 92 93Sound pressure level at 10 m4 dB(A) 57 57 58 58 59 60Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
*ErP2018
*ErP2018
*ErP2018
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
R513A
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 81
Microchannel coils
Made of 100% aluminium (fins, tubes and headers) with the exception of cop-per pipe couplings
Significant reduction on refrigerant charge and operating weight
Available for:
VLS 704-1204 SYSCROLL 140-360 AIR EVO CO
SYSCROLL 400-900 AIR EVO CO
SYSCROLL 240-660 AIR CO
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
82 systemair
SYSCREW 300-1400 AIR COAir Cooled Chillers
The range at a glance 1 version:
CO (Cooling only) 21 sizes Cooling capacity from 295 to 1.395 kW 2 versions:
STD (Standard) HT (High Temperature)
3 acoustic versions: Standard version L (Low Noise) S (Super Low Noise)
Equipment Two refrigerant circuits Screw compressors Electronic expansion valve “Brine” version for process application LWT-8°C “Polar” version for air temperature -18°C E-Coating coil treatment as standard Compressors acoustic box Sequence phases control
SYSCREW 300-1400 AIR CO - Cooling only
Leaving water temperature
Water °С from +5 to +15Water + glycol °С from 0 to +15Water + glycol (Brine Version) °С from -8 to +15∆ T K from 3 to 8
Outdoor air temperature
STD °С from 0 to +48L °С from 0 to +46S °С from -10 to +42HT °С from -10 to +50Minimum Air temperature Polar Version °C -18
External static pressureStandard fans Pа 0Inverter fans Pа < 120
Industrial process
Advantages
Common configuration for the different versions → Easy upgrade of the units in stock or on field
Electronic expansion device → Excellent control of superheating for the best performance at full and partial load and for a safe operation
Microchannel coils → Significant reduction on refrigerant charge and operating weight New generation of pure counter-current shell&tube
evaporators → Maximum efficiency and new levels of competitiveness
Compressors box → Remarkable sound reduction even for the basic noise version
Control platform → Modular architecture, compressor envelope integration, corrective actions in border line areas, easy-friendly user interface
Air cooled
HFC R134a
295-1.395 kWHOTELSOFFICES INDUSTRYHOSPITALS
H
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Accessories and optionsAutomatic circuit breakerBMS interfaceCoils treatmentsCompressors stepless controlDesuperheater and total heat recoveryFan speed controlHydrokit with 1 or 2 pumps with or without buffer tankMechanical gaugesPower factor corrector capacitorsSoftstarterSRC - Smart Remote Control (Mini BMS)Unit protection grillesWater filterWater flow switch
Screw compressor
Shell & Tube evaporator
New
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 83
SYSCREW 300-580 AIR CO - Cooling only 300 360 410 450 480 500 540 580Cooling capacity1 kW 295 365 413 445 480 505 540 575Power input1 kW 108,8 134,4 151,5 167,7 176,3 184,1 198,6 212,5EER / Energy efficiency class1 2,71/C 2,71/C 2,73/C 2,65/D 2,72/C 2,74/C 2,72/C 2,70/CSEPR2* 2,76 2,63 3,21 3,13 3,02 3,03 2,91 3,22Sound power level3 dB(A) 95 96 97 97 97 97 98 98Sound pressure level at 10 m4 dB(A) 63 64 65 65 65 65 66 65Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 300-580 AIR CO L - Cooling only 300 360 410 450 480 500 540 580Cooling capacity1 kW 283 357 405 436 470 495 529 563Power input1 kW 102,5 133,4 149,2 166,0 174,9 183,0 197,1 210,5EER / Energy efficiency class1 2,76/D 2,68/D 2,72/C 2,63/D 2,69/D 2,70/C 2,68/D 2,68/DSEPR2* 3,05 2,91 3,5 3,41 3,22 3,24 3,09 3,35Sound power level3 dB(A) 89 90 91 91 91 91 92 92Sound pressure level at 10 m4 dB(A) 57 58 59 59 59 59 60 59Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 300-580 AIR CO S - Cooling only 300 360 410 450 480 500 540 580Cooling capacity1 kW 276 339 385 414 446 469 502 535Power input1 kW 105,7 140,4 157,0 174,7 184,1 192,8 207,6 221,6EER / Energy efficiency class1 2,61/D 2,42/E 2,45/E 2,37/E 2,43/E 2,43/E 2,42/E 2,41/ESEPR2* 2,96 2,82 2,82 3,39 3,31 3,12 3,13 3,02Sound power level3 dB(A) 85 86 87 87 87 87 88 88Sound pressure level at 10 m4 dB(A) 53 54 55 55 55 55 56 55Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 5” 5” 6” 6” 6” 6” 6” 6”WeightOperating weight STD/L/HT kg 3.270 3.300 3.670 3.990 4.290 4.320 4.550 4.800Operating weight S kg 3.350 3.380 3.760 4.080 4.390 4.410 4.640 4.900DimensionsLength mm 4.600 4.600 4.600 4.600 4.600 4.600 5.700 6.700Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510 2.510
Physical featuresSYSCREW 300-580 AIR CO - Cooling only 300 360 410 450 480 500 540 580
SYSCREW 300-580 AIR CO HT - Cooling only 300 360 410 450 480 500 540 580Cooling capacity1 kW 301 372 422 454 489 515 550 586Power input1 kW 106,7 138,1 156,9 172,8 181,2 188,8 204,1 218,8EER / Energy efficiency class1 2,82/C 2,69/D 2,69/D 2,63/D 2,70/C 2,73/C 2,70/D 2,68/DSEPR2* 2,84 2,71 3,28 3,19 3,07 3,08 2,96 3,25Sound power level3 dB(A) 101 102 103 103 103 103 104 104Sound pressure level at 10 m4 dB(A) 69 70 71 71 71 71 72 71Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
84 systemair
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 6” 6” 8” 8” 8” 8” 8”WeightOperating weight STD/L/HT kg 5.330 5.760 6.220 6.750 6.830 7.090 7.180Operating weight S kg 5.430 5.860 6.320 6.850 6.930 7.190 7.280DimensionsLength mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510
SYSCREW 650-1000 AIR CO S - Cooling only 650 720 800 850 910 970 1000Cooling capacity1 kW 606 663 738 792 846 903 938Power input1 kW 246,1 264,3 286,3 311,6 335,0 356,1 366,0EER / Energy efficiency class1 2,46/E 2,51/D 2,58/D 2,54/D 2,53/D 2,54/D 2,56/DSEPR2* 3,26 3,26 3,27 3,33 3,32 3,33 3,29Sound power level3 dB(A) 89 89 89 89 90 90 90Sound pressure level at 10 m4 dB(A) 56 56 56 56 57 57 57Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 650-1000 AIR CO HT - Cooling only 650 720 800 850 910 970 1000Cooling capacity1 kW 665 727 809 868 927 990 1.028Power input1 kW 244,7 261,0 285,0 307,7 328,7 349,6 360,6EER / Energy efficiency class1 2,72/C 2,79/C 2,84/C 2,82/C 2,82/C 2,83/C 2,85/CSEPR2* 3,24 3,23 3,25 3,28 3,27 3,28 3,27Sound power level3 dB(A) 105 105 105 106 106 106 106Sound pressure level at 10 m4 dB(A) 72 72 72 73 73 73 73Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 650-1000 AIR CO - Cooling only 650 720 800 850 910 970 1000
SYSCREW 650-1000 AIR CO - Cooling only 650 720 800 850 910 970 1000Cooling capacity1 kW 652 713 794 851 909 971 1.008Power input1 kW 236,8 253,4 275,7 298,9 320,2 340,5 350,7EER / Energy efficiency class1 2,75/C 2,81/C 2,88/C 2,85/C 2,84/C 2,85/C 2,87/CSEPR2* 3,22 3,22 3,23 3,22 3,22 3,23 3,25Sound power level3 dB(A) 99 99 99 100 100 100 100Sound pressure level at 10 m4 dB(A) 66 66 66 67 67 67 67Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
Physical features
SYSCREW 650-1000 AIR CO L - Cooling only 650 720 800 850 910 970 1000Cooling capacity1 kW 639 699 778 835 891 952 988Power input1 kW 233,7 250,9 272,0 296,0 318,2 338,2 347,8EER / Energy efficiency class1 2,73/C 2,78/C 2,86/C 2,82/C 2,80/C 2,81/C 2,84/CSEPR2* 3,29 3,37 3,31 3,44 3,43 3,44 3,4Sound power level3 dB(A) 93 93 93 94 94 94 94Sound pressure level at 10 m4 dB(A) 60 60 60 61 61 61 61Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
AIR
COOL
ED C
HILL
ERS
& HE
AT P
UMPS
systemair 85
Physical features
Hydraulic dataType of water connections (evaporator) VictaulicWater Inlet/Outlet diameter inch 8” 8” 8” 8” 10” 10”WeightOperating weight STD/L/HT kg 7.880 8.150 8.350 8.560 8.940 9.245Operating weight S kg 7.980 8.250 8.450 8.660 9.040 9.345DimensionsLength mm 9.900 10.900 10.900 10.900 12.000 13.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.510 2.510 2.510 2.510 2.510 2.510
SYSCREW 1070-1400 AIR CO S - Cooling only 1070 1130 1170 1200 1300 1400Cooling capacity1 kW 996 1.053 1.090 1.133 1.224 1.324Power input1 kW 388,5 409,3 428,7 450,2 485,8 511,3EER / Energy efficiency class1 2,56/D 2,57/D 2,54/D 2,52/D 2,52/D 2,59/DSEPR2* 3,28 3,39 3,24 3,26 3,26 3,26Sound power level3 dB(A) 90 91 91 91 92 93Sound pressure level at 10 m4 dB(A) 57 58 58 58 59 60Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 1070-1400 AIR CO HT - Cooling only 1070 1130 1170 1200 1300 1400Cooling capacity1 kW 1.092 1.155 1.195 1.242 1.342 1.415Power input1 kW 382,2 402,9 422,3 443,6 479,8 494,9EER / Energy efficiency class1 2,86/C 2,87/C 2,83/C 2,80/C 2,80/C 2,86/CSEPR2* 3,25 3,35 3,22 3,24 3,29 3,25Sound power level3 dB(A) 106 107 107 107 108 109Sound pressure level at 10 m4 dB(A) 73 74 74 74 75 76Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 1070-1400 AIR CO - Cooling only 1070 1130 1170 1200 1300 1400
SYSCREW 1070-1400 AIR CO - Cooling only 1070 1130 1170 1200 1300 1400Cooling capacity1 kW 1.071 1.132 1.172 1.218 1.316 1.395Power input1 kW 371,8 391,8 410,5 431,2 465,9 482,6EER / Energy efficiency class1 2,88/C 2,89/C 2,85/C 2,82/C 2,82/C 2,89/CSEPR2* 3,24 3,3 3,26 3,22 3,23 3,22Sound power level3 dB(A) 100 101 101 101 102 103Sound pressure level at 10 m4 dB(A) 67 68 68 68 69 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 1070-1400 AIR CO L - Cooling only 1070 1130 1170 1200 1300 1400Cooling capacity1 kW 1.050 1.110 1.148 1.193 1.290 1.346Power input1 kW 368,8 388,6 407,0 427,4 461,4 491,2EER / Energy efficiency class1 2,85/C 2,86/C 2,82/C 2,79/C 2,80/C 2,74/CSEPR2* 3,38 3,5 3,34 3,37 3,37 3,29Sound power level3 dB(A) 94 95 95 95 96 97Sound pressure level at 10 m4 dB(A) 61 62 62 62 63 64Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
1 According EN14511-2013: chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB. 2 According EN14825. 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 17 for more information).
86 systemair
Plate heat exchanger
AQUASCOP HT V2
The range at a glance 3 sizes Monobloc system COP up to 4,28 Heating capacities from 5,4 to 15,6 kW Production of hot water at 65°C with outdoor tempera-
ture down to -20°C, while guaranteeing a high COP
Equipment Bodywork & structure: Steel bodywork coated with
oven-baked epoxy paint coating. Removable panels on all sides allow access to the internal components.
Refrigerant circuit: A complete Systemair patented refrigerat circuit enables the 2 compressors to be used independently or in two-stage mode.
Water side exchanger: Brazed plate construction oper-ating on a counter flow configuration in Winter mode to ensure excellent heating performance.
Air side exchanger: Treated with a hydrophilic coating to assist condensed water drainage.
Hydraulic kit comprising: 3 speed circulation pump, flow controller, automatic bleed, drain, pressure gauge, safety valve (3.5 bars).
Fans: Reinforced polypropylene, low-speed helicoidal fans with optimised fan blade profiles to ensure effi-cient air flow at an extremely low sound level.
Electrical box: The electrical box contains all the components for heat pump operation and notably the system’s protection device.
Electronic controller and its keypad screen. The units are also equipped with main disconnect
switch, Start-up current limiter (depending on mod-els), Phase sequence controller (three phase models), Exchanger protection grille, Water filter, 1 filter stop valve, 4 pads for sound insulation under the casing.
Monobloc - High Temperature Heat Pumps
Scroll compressorR407C
Operating limits
10
15
20
25
30
35
40
45
50
55
60
65
70
-15- 10 -5 05 10 15 20-20-25 25
Double étage - mini retour d'eau
Double étage - maxi départ d'eau
Mono étage - maxi départ d'eau
MONO ÉTAGE
Outside temperature °C
Double stage – water return min.
DOUBLE STAGE
SINGLE STAGE
Double stage – water starting max.
Single stage – water starting max.
Wat
er fl
ow s
etpo
int (
°C)
SYSTEMAIR
PATENTED[ ]
5,4-15,6 kW
HFC
Accessories1” hose kit, length 1 mBuffer tank / mixing tank 140-litreDecanting filter (sludge pot)Dual-zone kit for radiators and floor (without valve)Electric heater 6 kWHydraulic connection kit with/without three-way valveKit domestic hot water tank 300-litrePlate exchanger & circulator pump kit for domestic hot waterProgrammable and communicating ambient thermostatRemote wireless ambient sensorShock-absorbing support feetShut-off valve with pressure tapThree-phase starting intensity limiter (STD on single-phase)Three-way valve alone for domestic hot water management or boiler backupWater filter
°C-
OUTDOOR OPERATING LIMITS IN HEATING MODE
HIGH TEMPERATURE
UP TO 65°C
BOILER BACKUP
BOILER REPLACEMENT
DOMESTIC HOT WATER
LOW TEMPERATURE
HEATER
BI-ZONE CE STANDARDLOW-TEMPERATURE
RADIATOR
WATER PROGRAMME
PATENTED
RESIDENTIAL
Advantages Very high leaving water temperature → up to 65°C Very high performance
SCOP class A++ / COP up to 4,28 Silent units Ideal for renovations as well as for new construction No refrigerant links to be made Keypad screen with diagnosis assistance New “antifreeze” evaporator → 2 hours without
defrosting Easy maintenance Dual zone management (kit available as an accessory) Possibility of installing several heat pumps in cascade
(upon request)
systemair 87
RESI
DENT
IAL
HEAT
PUM
PS
Technical performanceAQUASCOP HT V2 12-6 14-7 18-9
Outdoor air condition+7 °C / +6 °C WB
Water condition 30/35 °CHeating capacity single-compressor kW 6,30 7,40 8,98Power input kW 1,53 1,74 2,10COP 4,12 4,25 4,28Water condition 45 °CHeating capacity single-compressor kW 5,86 7,93 9,46Power input kW 1,86 2,35 2,67COP 3,15 3,37 3,54Water condition 55 °CHeating capacity dual-compressor kW 5,36 7,22 8,75Power input kW 2,30 2,85 3,27COP with defrost 2,33 2,53 2,68
Outdoor air condition+2 °C / +1 °C WB
Water condition 35 °CHeating capacity dual-compressor kW 10,52 13,26 15,63Power input kW 2,99 3,82 4,39COP with defrost 3,52 3,47 3,56
Outdoor air condition-7 °C / -8 °C WB
Water condition 35 °CHeating capacity dual-compressor kW 8,21 10,89 12,46Power input kW 2,78 3,64 4,11COP with defrost 2,95 2,99 3,03Water condition 55 °CHeating capacity dual-compressor kW 8,57 10,92 12,69Power input kW 3,74 4,63 5,29COP with defrost 2,29 2,36 2,40Water condition 65 °CHeating capacity dual-compressor kW 8,49 10,90 12,25Power input kW 4,45 5,30 5,92COP with defrost 1,91 2,06 2,07
Outdoor air condition-15 °C
Water condition 35 °CHeating capacity dual-compressor kW 7,95 10,44 11,94Power input kW 2,78 3,58 4,04COP with defrost 2,86 2,92 2,96
Outdoor air condition-20 °C
Water condition 55 °CHeating capacity dual-compressor kW 8,03 10,32 11,28Power input kW 3,95 4,73 5,22COP with defrost 2,03 2,18 2,16
AQUASCOP HT V2 12-6 14-7 18-9Nominal water flow m3/h 1.030 1.370 1.580Available hydraulic pressure - High speed kPa 55 48 55Operating limits (outdoor temperature) °C -20Outlet water temperature Min. / Max. °C +25/+65
WB : Wet bulb.
Note: Seasonal space heating energy efficiency class according to the Delegated Regulation No. 811/2013 of the European Commission.
Water conditionAQUASCOP HT V2
12-6 14-7 18-9
55°C A+ A+ A+
35°C A++ A++ A++
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
88 systemair
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Physical features
Electrical features
AQUASCOP HT V2 12-6 14-7 18-9RefrigerantType R407CHydraulic connectionsWater inlet gas 1" FemaleWater outlet gas 1" FemaleWater flowNominal l/h 1.030 1.370 1.580Minimum l/h 890 1.170 1.340Maximum l/h 1.160 1.530 1.775FansFans (x2) 206 W - 700 rpm - 6000 m3/hSound levelsSound power levels dB(A) 67 67 67
AQUASCOP HT V2 12-6 14-7 18-9SUPPLY VOLTAGE 400 V/3 Ph/50 HzStarting current with limiter A < 60Max. current A 15 16 18SUPPLY VOLTAGE 230 V/ 1 Ph/50 HzStarting current with limiter A < 45Max. current A 28 32 -
systemair 89
RESI
DENT
IAL
HEAT
PUM
PS
90 systemair
AQUASCOP HT SPLIT
The range at a glance 3 sizes Split system COP up to 4,28 Heating capacities from 5,4 to 15,6 kW Production of hot water at 65°C with outdoor tempera-
ture down to -20°C, while guaranteeing a high COP
Equipment
Outdoor unit: Steel bodywork coated with oven-baked epoxy paint
coating. Removable panels on all sides allow access to the internal components.
Air side exchanger treated with a hydrophilic coating to assist condensed water drainage.
A complete Systemair patented refrigerant circuit ena-bles the 2 compressors to be used independently or in two-stage mode.
The electrical box contains all the components for heat pump operation and notably the system’s protection device.
Indoor unit: An elegant casing with smallest dimensions of the mar-
ket including a high performance plate heat exchanger, multi-speed circulating pump, a real flowmeter (value displayed on the screen in l/h), an electronic water pressure sensor (available on the screen), a safety valve, an air vent, etc..
AQUASCOP HT SPLIT units are also equipped with main disconnect switch, Start-up current limiter (depending on models), Phase sequence controller (three phase models), Exchanger protection grille, Water filter, 1 filter stop valve, 4 pads for sound insulation under the casing.
Split units - High Temperature Heat Pumps
Operating limits
10
15
20
25
30
35
40
45
50
55
60
65
70
-15- 10 -5 05 10 15 20-20-25 25
Double étage - mini retour d'eau
Double étage - maxi départ d'eau
Mono étage - maxi départ d'eau
MONO ÉTAGE
Outside temperature °C
Double stage – water return min.
DOUBLE STAGE
SINGLE STAGE
Double stage – water starting max.
Single stage – water starting max.
Wat
er fl
ow s
etpo
int (
°C)
SYSTEMAIR
PATENTED[ ]
5,4-15,6 kW
Accessories1” hose kit, length 1 mBuffer tank / mixing tank 140-litreDecanting filter (sludge pot)Dual-zone kit for radiators and floor (without valve)Electric heater 6 kWHydraulic connection kit with/without three-way valveKit domestic hot water tank 300-litrePlate exchanger & circulator pump kit for domestic hot waterProgrammable and communicating ambient thermostatRemote wireless ambient sensorShock-absorbing support feetShut-off valve with pressure tapThree-phase starting intensity limiter (STD on single-phase)Three-way valve alone for domestic hot water management or boiler backupWater filter
Advantages Very high leaving water temperature → up to 65°C Very high performance
SCOP class A++ / COP up to 4,28 Silent units Ideal for renovations as well as for new construction No refrigerant links to be made Keypad screen with diagnosis assistance New “antifreeze” evaporator → 2 hours without
defrosting Easy maintenance Dual zone management (kit available as an accessory) Possibility of installing several heat pumps in cascade
(upon request) Aesthetic and compact indoor unit (700x400x260 cm)
with aluminum finish
°C-
OUTDOOR OPERATING LIMITS IN HEATING MODE
HIGH TEMPERATURE
UP TO 65°C
BOILER BACKUP
BOILER REPLACEMENT
DOMESTIC HOT WATER
LOW TEMPERATURE
HEATER
BI-ZONE CE STANDARDLOW-TEMPERATURE
RADIATOR
WATER PROGRAMME
PATENTED
Plate heat exchanger
Scroll compressorR407CHFC
RESIDENTIAL
systemair 91
RESI
DENT
IAL
HEAT
PUM
PS
Note: Seasonal space heating energy efficiency class according to the Delegated Regulation No. 811/2013 of the European Commission.
Water conditionAQUASCOP HT SPLIT
12-6 14-7 18-9
55°C A+ A+ A+
35°C A++ A++ A++
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical performance
AQUASCOP HT SPLIT 12-6 14-7 18-9
Outdoor air condition+7 °C / +6 °C WB
Water condition 30/35 °CHeating capacity single-compressor kW 6,30 7,40 8,98Power input kW 1,53 1,74 2,10COP 4,12 4,25 4,28Water condition 45 °CHeating capacity single-compressor kW 5,74 7,77 9,27Power input kW 1,86 2,35 2,67COP 3,09 3,31 3,47Water condition 55 °CHeating capacity dual-compressor kW 5,25 7,08 8,58Power input kW 2,30 2,85 3,27COP with defrost 2,28 2,48 2,62
Outdoor air condition+2 °C / +1 °C WB
Water condition 35 °CHeating capacity dual-compressor kW 10,31 13,00 15,32Power input kW 2,99 3,82 4,39COP with defrost 3,45 3,40 3,49
Outdoor air condition-7 °C / -8 °C WB
Water condition 35 °CHeating capacity dual-compressor kW 8,21 10,89 12,46Power input kW 2,78 3,59 4,05COP with defrost 2,95 3,03 3,08Water condition 55 °CHeating capacity dual-compressor kW 8,40 10,71 12,44Power input kW 3,74 4,63 5,29COP with defrost 2,25 2,31 2,35Water condition 65 °CHeating capacity dual-compressor kW 8,33 10,69 12,01Power input kW 4,45 5,30 5,92COP with defrost 1,87 2,02 2,03
Outdoor air condition-15 °C
Water condition 35 °CHeating capacity dual-compressor kW 7,79 10,24 11,71Power input kW 2,78 3,58 4,04COP with defrost 2,80 2,86 2,90
Outdoor air condition-20 °C
Water condition 55 °CHeating capacity dual-compressor kW 7,87 10,12 11,06Power input kW 3,95 4,73 5,22COP with defrost 1,99 2,14 2,12
WB : Wet bulb.
AQUASCOP HT SPLIT 12-6 14-7 18-9Nominal water flow m3/h 1.030 1.370 1.580Available hydraulic pressure - High speed kPa 55 48 55Operating limits (outdoor temperature) °C -20Outlet water temperature Min. / Max. °C +25/+65
92 systemair
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
* Depending on system configuration, the indoor unit can be separately powered or powered from the outdoor unit (one upstream general protection only).
Electrical features
AQUASCOP HT SPLIT 12-6 14-7 18-9RefrigerantType R407CRefrigerant connectionsGas refrigerant piping (0 to 25 meters) inch 5/8Liquid refrigerant piping (0 to 25 meters) inch 3/8Gas refrigerant pipings (0 to 45 meters) inch 3/4Liquid refrigerant piping (0 to 45 meters) inch 1/2FansFans (x2) 206 W - 700 rpm - 6000 m3/hSound levelsOutdoor unit sound power levels dB(A) 65 65 65
Physical features
AQUASCOP HT SPLIT 12-6* 14-7* 18-9Refrigerant connectionsGas line inch 5/8Liquid line inch 3/8Hydraulic connectionsInlet water gas 1" female / Rotating nutOutlet water gas 1" female / Rotating nutWater flowNominal l/h 1.030 1.370 1.580Minimum l/h 890 1.170 1.340Maximum l/h 1.160 1.530 1.775Sound levelsIndoor unit sound power levels dB(A) 41 41 41
* Indoor unit is common for outdoor units 12-6 and 14-7.
AQUASCOP HT SPLIT 12-6 14-7 18-9POWER SUPPLY 400 V/3 Ph/50 HzStarting current with limiter A < 60Max. current - Outdoor unit only A 12,2 13,2 15,2Max. current. - Outdoor unit + Indoor unit + Accessories* A 15,5 16,5 18,5POWER SUPPLY 230 V/ 1 Ph/50 HzStarting current with limiter A < 45Max. current - Outdoor unit only A 25,7 27,2 -Max. current - Outdoor unit + Indoor unit + Accessories* A 29 30,5 -
AQUASCOP HT SPLIT 12-6 14-7 18-9POWER SUPPLY 230 V/ 1 Ph/50 HzMax. current - Indoor unit only A 1,8 1,8 1,8Max. current - Indoor unit + Accessories A 3,3 3,3 3,3
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
MUL
TIPU
RPOS
EUN
ITS
systemair 93
MULTIPURPOSE UNITS
Simultaneous heating and cooling with only one unit!
The high efficiency air/water heat pumps are designed for 4-pipes air conditioning and heating systems, which allow the production of cold water for cooling and hot water for heating at the same time or sepa-rately with very high energy efficiencies.The units are supplied with an additional exchanger, used as a condenser for hot water, the production of which is independent of the operation mode of the unit.
Notes:Heating: Ambient temperature 7°C DB, 6°C WB, water temperature 30/35°C, according EN14511-2013 standard. Cooling: Ambient air temperature 35°C, evaporator water temperature in/out 12/7 °C, according EN14511-2013 standard.
SYSCROLL 20-400 AIR 4P/2+2P 17-416 kW 22-479 kW R410A Scroll Plate Air cooledPage 98
HFC
SYSCROLL 20-400 AIR EVO 4P/2+2P 18-405 kW 23-475 kW R410A Scroll Plate Air cooledPage 100
HFC4 pipe systems Production of hot water and cold water simultane-ously and/or separately.
MUL
TIPU
RPOS
EUN
ITS
94 systemair
Product Size Heating capacity SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
AIR
2+2
P L
SYSCROLL 20AIR 2+2P L
17,8 Kw 3,27 3,78 75 1.910 x 1.470 x 900 22 Kw
SYSCROLL 25AIR 2+2P L
24,1 Kw 3,58 4,93 75 1.910 x 1.470 x 900 28,7 Kw
SYSCROLL 30AIR 2+2P L
28,4 Kw 3,41 5,94 75 1.910 x 1.470 x 900 34,5 Kw
SYSCROLL 40AIR 2+2P L
38,8 Kw 3,34 8,14 75 2.200 x 1.670 x 900 47,2 Kw
SYSCROLL 45AIR 2+2P L
42,7 Kw 3,48 8,75 77 2.200 x 1.670 x 900 50,9 Kw
SYSCROLL 50AIR 2+2P L
48,2 Kw 3,54 9,76 77 2.200 x 1.670 x 900 56,8 Kw
SYSCROLL 55AIR 2+2P L
55,2 Kw 3,43 11,16 77 2.905 x 1.820 x 1.150 64,9 Kw
SYSCROLL 60AIR 2+2P L
60,2 Kw 3,47 12,6 78 2.905 x 1.820 x 1.150 73,2 Kw
SYSCROLL 75AIR 2+2P L
69,7 Kw 3,42 13,79 79 2.905 x 1.820 x 1.150 80,2 Kw
SYSCROLL 85AIR 2+2P L
83,3 Kw 3,5 16,67 82 3.965 x 1.820 x 1.150 97 Kw
SYSCROLL 95AIR 2+2P L
91,6 Kw 3,39 18,18 83 3.965 x 1.820 x 1.150 105,7 Kw
SYSCROLL 110AIR 2+2P L
102,6 Kw 3,5 21,03 85 3.965 x 1.820 x 1.150 122,3 Kw
SYSCROLL 120AIR 2+2P L
115,6 Kw 3,5 23,4 86 3.965 x 1.820 x 1.150 136 Kw
SYSCROLL 140AIR 2+2P L
131,9 Kw 3,48 27,07 86 3.965 x 2.220 x 1.150 157,3 Kw
SYSCROLL 150AIR 2+2P L
143 Kw 3,46 29,05 86 3.965 x 2.220 x 1.150 169 Kw
SYSCROLL 180AIR 2+2P L
173 Kw 3,45 33,80 89 4.505 x 2.305 x 1.150 196,6 Kw
SYSCROLL 200AIR 2+2P L
197,2 Kw 3,24 36,97 90 4.505 x 2.305 x 1.150 215 Kw
SYSCROLL 210AIR 2+2P L
192,3 Kw 3,25 36,43 87 5.315 x 2.305 x 1.150 211,8 Kw
SYSCROLL 220AIR 2+2P L
210,8 Kw 3,23 38,88 89 5.315 x 2.305 x 1.150 226,1 Kw
SYSCROLL 240AIR 2+2P L
231,8 Kw 3,26 44,5 90 5.315 x 2.305 x 1.150 258,8 Kw
SYSCROLL 280AIR 2+2P L
286,3 Kw 3,25 56,88 90 4.265 x 2.350 x 2.210 330,6 Kw
SYSCROLL 320AIR 2+2P L
312,9 Kw 3,27 61,49 90 4.265 x 2.350 x 2.210 357,4 Kw
SYSCROLL 360AIR 2+2P L
349,4 Kw 3,24 67,64 92 4.805 x 2.350 x 2.210 393,3 Kw
SYSCROLL 400AIR 2+2P L
401,8 Kw 3,34 74,27 93 4.805 x 2.350 x 2.210 431,7 Kw
Quick selection guide - Multipurpose Units
Page 98
MUL
TIPU
RPOS
EUN
ITS
systemair 95
Product Size Heating capacity SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
AIR
2+2
P L
SYSCROLL 20AIR 4P L
17,8 Kw 3,27 3,78 75 1.910 x 1.470 x 900 22 Kw
SYSCROLL 25AIR 4P L
24,1 Kw 3,58 4,93 75 1.910 x 1.470 x 900 28,7 Kw
SYSCROLL 30AIR 4P L
28,4 Kw 3,41 5,94 75 1.910 x 1.470 x 900 34,5 Kw
SYSCROLL 40AIR 4P L
38,8 Kw 3,34 8,17 75 2.200 x 1.670 x 900 47,2 Kw
SYSCROLL 45AIR 4P L
42,7 Kw 3,48 8,75 77 2.200 x 1.670 x 900 50,9 Kw
SYSCROLL 50AIR 4P L
48,2 Kw 3,54 9,7 77 2.200 x 1.670 x 900 56,8 Kw
SYSCROLL 55AIR 4P L
55,2 Kw 3,5 11,52 77 2.905 x 1.820 x 1.150 67 Kw
SYSCROLL 60AIR 4P L
60,2 Kw 3,54 12,96 78 2.905 x 1.820 x 1.150 75,4 Kw
SYSCROLL 75AIR 4P L
69,7 Kw 3,52 14,22 79 2.905 x 1.820 x 1.150 82,6 Kw
SYSCROLL 85AIR 4P L
83,3 Kw 3,58 17,39 82 3.965 x 1.820 x 1.150 101 Kw
SYSCROLL 95AIR 4P L
91,6 Kw 3,46 18,58 83 3.965 x 1.820 x 1.150 107,9 Kw
SYSCROLL 110AIR 4P L
102,6 Kw 3,56 21,67 85 3.965 x 1.820 x 1.150 125,9 Kw
SYSCROLL 120AIR 4P L
115,6 Kw 3,57 24,08 86 3.965 x 1.820 x 1.150 140 Kw
SYSCROLL 140AIR 4P L
131,9 Kw 3,54 27,83 86 3.965 x 2.220 x 1.150 161,8 Kw
SYSCROLL 150AIR 4P L
143 Kw 3,54 29,84 86 3.965 x 2.220 x 1.150 173,5 Kw
SYSCROLL 180AIR 4P L
173 Kw 3,51 34,85 89 4.505 x 2.305 x 1.150 202,7 Kw
SYSCROLL 200AIR 4P L
197,2 Kw 3,39 38,34 90 4.505 x 2.305 x 1.150 222,9 Kw
SYSCROLL 210AIR 4P L
192,3 Kw 3,3 37,55 87 5.315 x 2.305 x 1.150 218,3 Kw
SYSCROLL 220AIR 4P L
210,8 Kw 3,27 40,39 89 5.315 x 2.305 x 1.150 234,8 Kw
SYSCROLL 240AIR 4P L
231,8 Kw 3,28 46,19 90 5.315 x 2.305 x 1.150 268,5 Kw
SYSCROLL 280AIR 4P L
286,3 Kw 3,33 58,64 90 4.265 x 2.350 x 2.210 341 Kw
SYSCROLL 320AIR 4P L
312,9 Kw 3,34 63,61 90 4.265 x 2.350 x 2.210 369,9 Kw
SYSCROLL 360AIR 4P L
349,4 Kw 3,28 69,88 92 4.805 x 2.350 x 2.210 406,2 Kw
SYSCROLL 400AIR 4P L
401,8 Kw 3,38 76,54 93 4.805 x 2.350 x 2.210 444,9 KwPage 98
96 systemair
Product Size Heating capacity SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
AIR
EVO
2+2
P L
SYSCROLL 20AIR EVO 2+2P L
18,1 Kw 3,4 3,82 75 1.910 x 1.470 x 900 22,2 Kw
SYSCROLL 25AIR EVO 2+2P L
24,5 Kw 3,69 5,08 75 1.910 x 1.470 x 900 29,6 Kw
SYSCROLL 30AIR EVO 2+2P L
30,8 Kw 3,53 6,41 75 2.200 x 1.670 x 900 37,3 Kw
SYSCROLL 40AIR EVO 2+2P L
39,9 Kw 3,57 8,06 75 2.200 x 1.670 x 900 46,9 Kw
SYSCROLL 45AIR EVO 2+2P L
44,2 Kw 3,67 8,71 76 2.200 x 1.670 x 900 50,7 Kw
SYSCROLL 50AIR EVO 2+2P L
52,3 Kw 3,97 10,51 76 2.905 x 1.820 x 1.150 61,2 Kw
SYSCROLL 55AIR EVO 2+2P L
57,4 Kw 3,91 11,59 77 2.905 x 1.820 x 1.150 67,3 Kw
SYSCROLL 60AIR EVO 2+2P L
62,2 Kw 3,87 12,49 78 2.905 x 1.820 x 1.150 72,6 Kw
SYSCROLL 75AIR EVO 2+2P L
79,8 Kw 3,7 16,02 82 2.905 x 1.820 x 1.150 93,1 Kw
SYSCROLL 85AIR EVO 2+2P L
89,6 Kw 3,67 18 83 2.905 x 1.820 x 1.150 104,7 Kw
SYSCROLL 95AIR EVO 2+2P L
97,8 Kw 3,69 19,69 85 2.905 x 1.820 x 1.150 114,4 Kw
SYSCROLL 110AIR EVO 2+2P L
117 Kw 3,7 23,62 86 3.965 x 1.820 x 1.150 137,2 Kw
SYSCROLL 120AIR EVO 2+2P L
129,5 Kw 3,74 25,92 87 3.965 x 1.820 x 1.150 150,8 Kw
SYSCROLL 140AIR EVO 2+2P L
144,5 Kw 3,69 28,76 87 3.965 x 1.820 x 1.150 167,2 Kw
SYSCROLL 150AIR EVO 2+2P L
153,9 Kw 3,62 31,32 87 3.965 x 1.820 x 1.150 182 Kw
SYSCROLL 180AIR EVO 2+2P L
180,2 Kw 3,76 36,07 89 3.965 x 2.220 x 1.150 209,7 Kw
SYSCROLL 200AIR EVO 2+2P L
199,7 Kw 3,83 41,15 91 3.965 x 2.220 x 1.150 239,2 Kw
SYSCROLL 210AIR EVO 2+2P L
197,4 Kw 3,65 39,31 88 4.265 x 2.350 x 2.210 228,6 Kw
SYSCROLL 220AIR EVO 2+2P L
230,1 Kw 3,63 46,48 89 4.265 x 2.350 x 2.210 270,2 Kw
SYSCROLL 240AIR EVO 2+2P L
257,2 Kw 3,65 50,83 90 4.265 x 2.350 x 2.210 295,6 Kw
SYSCROLL 280AIR EVO 2+2P L
288,2 Kw 3,66 57,64 90 4.265 x 2.350 x 2.210 335 Kw
SYSCROLL 320AIR EVO 2+2P L
325,6 Kw 3,73 62,46 90 4.805 x 2.350 x 2.210 363,1 Kw
SYSCROLL 360AIR EVO 2+2P L
366 Kw 3,61 69,59 92 4.805 x 2.350 x 2.210 404,5 Kw
SYSCROLL 400AIR EVO 2+2P L
405 Kw 3,63 78,91 92 4.805 x 2.350 x 2.210 458,7 KwPage 100
MUL
TIPU
RPOS
EUN
ITS
systemair 97
Product Size Heating capacity SCOP Flow ratem3/h
Acousticpower dB(A)
Dimensions (LxHxW) without water tank
SYSC
ROLL
AIR
EVO
2+2
P L
SYSCROLL 20AIR EVO 4P L
18,1 Kw 3,47 3,92 75 1.910 x 1.470 x 900 22,9 Kw
SYSCROLL 25AIR EVO 4P L
24,5 Kw 3,76 5,26 75 1.910 x 1.470 x 900 30,5 Kw
SYSCROLL 30AIR EVO 4P L
30,8 Kw 3,53 6,41 75 2.200 x 1.670 x 900 37,3 Kw
SYSCROLL 40AIR EVO 4P L
39,9 Kw 3,57 8,06 75 2.200 x 1.670 x 900 46,9 Kw
SYSCROLL 45AIR EVO 4P L
44,2 Kw 3,67 8,71 76 2.200 x 1.670 x 900 50,7 Kw
SYSCROLL 50AIR EVO 4P L
52,3 Kw 4,04 10,94 76 2.905 x 1.820 x 1.150 63,6 Kw
SYSCROLL 55AIR EVO 4P L
57,4 Kw 4 11,9 77 2.905 x 1.820 x 1.150 69,6 Kw
SYSCROLL 60AIR EVO 4P L
62,2 Kw 3,95 12,9 78 2.905 x 1.820 x 1.150 75 Kw
SYSCROLL 75AIR EVO 4P L
79,8 Kw 3,76 16,63 82 2.905 x 1.820 x 1.150 96,6 Kw
SYSCROLL 85AIR EVO 4P L
89,6 Kw 3,73 18,61 83 2.905 x 1.820 x 1.150 108,3 Kw
SYSCROLL 95AIR EVO 4P L
97,8 Kw 3,78 20,30 85 2.905 x 1.820 x 1.150 118,1 Kw
SYSCROLL 110AIR EVO 4P L
117 Kw 3,76 24,44 86 3.965 x 1.820 x 1.150 142,2 Kw
SYSCROLL 120AIR EVO 4P L
129,5 Kw 3,81 26,86 87 3.965 x 1.820 x 1.150 156,2 Kw
SYSCROLL 140AIR EVO 4P L
144,5 Kw 3,83 29,84 87 3.965 x 1.820 x 1.150 173,5 Kw
SYSCROLL 150AIR EVO 4P L
153,9 Kw 3,77 32,47 87 3.965 x 1.820 x 1.150 188,7 Kw
SYSCROLL 180AIR EVO 4P L
180,2 Kw 3,85 37,19 89 3.965 x 2.220 x 1.150 216,2 Kw
SYSCROLL 200AIR EVO 4P L
199,7 Kw 3,96 42,59 91 3.965 x 2.220 x 1.150 247,7 Kw
SYSCROLL 210AIR EVO 4P L
197,4 Kw 3,68 40,57 88 4.265 x 2.350 x 2.210 235,9 Kw
SYSCROLL 220AIR EVO 4P L
230,1 Kw 3,63 48,06 89 4.265 x 2.350 x 2.210 279,5 Kw
SYSCROLL 240AIR EVO 4P L
257,2 Kw 3,74 52,70 90 4.265 x 2.350 x 2.210 306,4 Kw
SYSCROLL 280AIR EVO 4P L
288,2 Kw 3,74 58,07 90 4.265 x 2.350 x 2.210 337,5 Kw
SYSCROLL 320AIR EVO 4P L
325,6 Kw 3,75 64,12 90 4.805 x 2.350 x 2.210 372,8 Kw
SYSCROLL 360AIR EVO 4P L
366 Kw 3,63 71,71 92 4.805 x 2.350 x 2.210 417 Kw
SYSCROLL 400AIR EVO 4P L
405 Kw 3,66 81,65 92 4.805 x 2.350 x 2.210 474,8 KwPage 100
98 systemair
SYSCROLL 20-400 AIR 4P/2+2P
The range at a glance 24 sizes
4 pipes or 2+2 pipes system EC (low consumption) or AC fan motors 2 acoustic versions:
L (Low Noise) S (Super Low Noise) Cooling capacity from 17 to 416 kW Heating capacity from 22 to 479 kW
Equipment Water Flow switch Fan speed control Outdoor air temperature sensor for weather com-
pensation + user probes remoting kit
High efficiency 4 pipes system air to water heat pumps
SYSCROLL 20-400 AIR 4P/2+2PLeaving water temperature (Cooling mode) °C from 4 to 18Leaving water temperature (Heating mode) °C from 25 to 55Power supply V/ph/Hz 400/3+N/50 (Nominal)
Operating limits
Accessories and optionsCascade control system via RS485Condensate discharge drip tray + antifreeze heaterElectronic expansion valveHydrokit with 1 or 2 pumps with or without buffer tankPressure gaugesRemote control panelRubber / spring anti-vibration dampersSerial interface card Modbus RS485SoftstarterUser + Recovery heat exchangers antifreeze kit
Advantages
Simultaneous heating and cooling with only one unit High efficiency and sustainability Very good performances and large working range Low sound level
ErP2018
17-416 kW 22-479 kW
Air cooled
HFC R410A
Plate heat exchanger
Scroll compressor
HOTELSOFFICES INDUSTRYHOSPITALS
HSHOPPING CENTERS
Simultaneous heating and cooling with only one unit
These units are able to produce hot water and cold water simultaneously and/or separately with very high energy efficiencies
MUL
TIPU
RPOS
EUN
ITS
systemair 99
SYSCROLL AIR 2+2P L 20 25 30 40 45 50 55 60 75 85 95 110
Heating
Heating capacity 1 kW 22,0 28,7 34,5 47,2 50,9 56,8 64,9 73,2 80,2 97,0 105,7 122,3Total input power 1 kW 5,8 7,3 9,1 12,2 12,6 14,4 16,0 17,9 20,8 24,3 27,3 30,7COP 1 3,83 3,93 3,80 3,86 4,04 3,94 4,06 4,10 3,86 4,00 3,87 3,98Energy Class 2 A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,27 3,58 3,41 3,34 3,48 3,54 3,43 3,47 3,42 3,50 3,39 3,50hsh
2 % 127,9 140,1 133,3 130,4 136,3 138,6 134,3 135,9 133,7 137,1 132,7 136,9
Cooling
Cooling capacity 3 kW 17,8 24,1 28,4 38,8 42,7 48,2 55,2 60,2 69,7 83,3 91,6 102,6Total input power 3 kW 7,1 9,8 11,7 15,0 16,4 19,8 21,9 24,5 29,3 32,7 37,7 42,6EER 3 2,52 2,45 2,42 2,58 2,61 2,43 2,52 2,46 2,38 2,55 2,43 2,41TER 4 8,76 9,43 9,02 8,58 9,28 9,55 9,58 9,29 9,13 9,34 9,14 9,23
Sound power 5 dB(A) 75 75 75 75 77 77 77 78 79 82 83 85Sound pressure 6 dB(A) 43 43 43 43 45 45 45 46 47 50 51 53
Performances are referred to the following conditions:1 Heating: Ambient temperature 7°C DB, 6°C WB, water temperature 30/35°C, according EN14511-2013 standard. 2 Average conditions, low temperature, variable - Reg EU 811/2013.3 Cooling: Ambient air temperature 35°C, evaporator water temperature in/out 12/7 °C, according EN14511-2013 standard.4 TER: Total Energy Ratio - cold circuit 12/7°C, hot circuit 30/35°C.5 Sound power level in accordance with ISO 3744.6 Sound pressure level at 10 mt from the unit in free field conditions in accordance with ISO 3744.
Physical featuresSYSCROLL AIR 4P/2+2P L 20-30 40-50 55-75 85-120 140-150 180-200 210-240 280-320 360-400DimensionsLength mm 1.910 2.200 2.905 3.965 3.965 4.505 5.315 4.265 4.805Width mm 900 900 1.150 1.150 1.150 1.150 1.150 2.210 2.210Height mm 1.470 1.670 1.820 1.820 2.220 2.305 2.305 2.350 2.350
Technical performance
ErP2018
SYSCROLL AIR 2+2P L 120 140 150 180 200 210 220 240 280 320 360 400
Heating
Heating capacity 1 kW 136,0 157,3 169,0 196,6 215,0 211,8 226,1 258,8 330,6 357,4 393,3 431,7Total input power 1 kW 34,6 40,3 43,4 51,5 60,4 58,2 64,8 71,9 85,2 93,8 103,0 116,4COP 1 3,93 3,90 3,89 3,82 3,56 3,64 3,49 3,60 3,88 3,81 3,82 3,71Energy Class 2 A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,50 3,48 3,46 3,45 3,24 3,25 3,23 3,26 3,25 3,27 3,24 3,34hsh
2 % 137,0 136,1 135,5 134,8 126,5 127,1 126,1 127,2 127,0 127,8 126,4 130,4
Cooling
Cooling capacity 3 kW 115,6 131,9 143,0 173,0 197,2 192,3 210,8 231,8 286,3 312,9 349,4 401,8Total input power 3 kW 47,2 53,8 63,6 68,9 76,7 76,0 87,5 97,8 106,0 121,8 138,1 153,4EER 3 2,45 2,45 2,25 2,51 2,57 2,53 2,41 2,37 2,70 2,57 2,53 2,62TER 4 9,25 9,33 9,39 9,34 9,40 9,06 8,97 8,94 9,42 9,50 9,24 9,37
Sound power 5 dB(A) 86 86 86 89 90 87 89 90 90 90 92 93Sound pressure 6 dB(A) 54 54 54 57 58 55 57 58 58 58 60 61
SYSCROLL AIR 4P L 20 25 30 40 45 50 55 60 75 85 95 110
Heating
Heating capacity 1 kW 22,0 28,7 34,5 47,2 50,9 56,8 67,0 75,4 82,6 101,0 107,9 125,9Total input power 1 kW 5,8 7,3 9,1 12,2 12,6 14,4 16,1 18,0 21,0 24,5 27,5 31,0COP 1 3,83 3,93 3,80 3,86 4,04 3,94 4,17 4,19 3,94 4,12 3,92 4,06Energy Class 2 A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,27 3,58 3,41 3,34 3,48 3,54 3,50 3,54 3,52 3,58 3,46 3,56hsh
2 % 127,9 140,1 133,3 130,4 136,3 138,6 137,1 138,5 137,9 140,0 135,4 139,3
Cooling
Cooling capacity 3 kW 17,8 24,1 28,4 38,8 42,7 48,2 55,2 60,2 69,7 83,3 91,6 102,6Total input power 3 kW 7,1 9,8 11,7 15,0 16,4 19,8 21,9 24,5 29,3 32,7 37,7 42,6EER 3 2,52 2,45 2,42 2,58 2,61 2,43 2,52 2,46 2,38 2,55 2,43 2,41TER 4 8,76 9,43 9,02 8,58 9,28 9,55 9,58 9,29 9,13 9,34 9,14 9,23
Sound power 5 dB(A) 75 75 75 75 77 77 77 78 79 82 83 85Sound pressure 6 dB(A) 43 43 43 43 45 45 45 46 47 50 51 53
SYSCROLL AIR 4P L 120 140 150 180 200 210 220 240 280 320 360 400
Heating
Heating capacity 1 kW 140,0 161,8 173,5 202,7 222,9 218,3 234,8 268,5 341,0 369,9 406,2 444,9Total input power 1 kW 35,0 39,4 43,6 51,9 59,1 59,5 66,2 73,6 85,4 93,8 105,2 118,7COP 1 4,00 4,11 3,98 3,90 3,77 3,67 3,55 3,65 3,99 3,94 3,86 3,75Energy Class 2 A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,57 3,54 3,54 3,51 3,39 3,30 3,27 3,28 3,33 3,34 3,28 3,38hsh
2 % 139,6 138,4 138,4 137,4 132,5 128,8 127,7 128,3 130,2 130,6 128,0 132,2
Cooling
Cooling capacity 3 kW 115,6 131,9 143,0 173,0 197,2 192,3 210,8 231,8 286,3 312,9 349,4 401,8Total input power 3 kW 47,2 53,8 63,6 68,9 76,7 76,0 87,5 97,8 106,0 121,8 138,1 153,4EER 3 2,45 2,45 2,25 2,51 2,57 2,53 2,41 2,37 2,70 2,57 2,53 2,62TER 4 9,25 9,33 9,39 9,34 9,40 9,06 8,97 8,94 9,42 9,50 9,24 9,37
Sound power 5 dB(A) 86 86 86 89 90 87 89 90 90 90 92 93Sound pressure 6 dB(A) 54 54 54 57 58 55 57 58 58 58 60 61
ErP2018
ErP2018
ErP2018
100 systemair
SYSCROLL 20-400 AIR EVO 4P/2+2P
The range at a glance 24 sizes
EVO high efficiency version 4 pipes or 2+2 pipes system EC (low consumption) or AC fan motors 2 acoustic versions:
L (Low Noise) S (Super Low Noise) Cooling capacity from 18 to 405 kW Heating capacity from 23 to 475 kW
Equipment Water Flow switch Fan speed control Outdoor air temperature sensor for weather com-
pensation + user probes remoting kit
SYSCROLL 20-400 AIR EVO 4P/2+2PLeaving water temperature (Cooling mode) °C from 4 to 18Leaving water temperature (Heating mode) °C from 25 to 60Power supply V/ph/Hz 400/3+N/50 (Nominal)
Operating limits
Advantages
Simultaneous heating and cooling with only one unit High efficiency and sustainability Very good performances and large working range Low sound level
Air cooled
HFC R410A
High efficiency 4 pipes system air to water heat pumps
18-405 kW 23-475 kW
HOTELSOFFICES INDUSTRYHOSPITALS
HSHOPPING CENTERS
Plate heat exchanger
Scroll compressor
Accessories and optionsCascade control system via RS485Condensate discharge drip tray + antifreeze heaterElectronic expansion valveHydrokit with 1 or 2 pumps with or without buffer tankPressure gaugesRemote control panelRubber / spring anti-vibration dampersSerial interface card Modbus RS485SoftstarterUser + Recovery heat exchangers antifreeze kit
ErP2018
Simultaneous heating and cooling with only one unit
These units are able to produce hot water and cold water simultaneously and/or separately with very high energy efficiencies
MUL
TIPU
RPOS
EUN
ITS
systemair 101
Performances are referred to the following conditions:1 Heating: Ambient temperature 7°C DB, 6°C WB, water temperature 30/35°C, according EN14511-2013 standard. 2 Average conditions, low temperature, variable - Reg EU 811/2013.3 Cooling: Ambient air temperature 35°C, evaporator water temperature in/out 12/7 °C, according EN14511-2013 standard.4 TER: Total Energy Ratio - cold circuit 12/7°C, hot circuit 30/35°C.5 Sound power level in accordance with ISO 3744.6 Sound pressure level at 10 mt from the unit in free field conditions in accordance with ISO 3744.
Physical featuresSYSCROLL AIR EVO 4P/2+2P L 20-25 30-45 50-95 110-150 180-200 210-280 320-400DimensionsLength mm 1.910 2.200 2.905 3.965 3.965 4.265 4.805Width mm 900 900 1.150 1.150 1.150 2.210 2.210Height mm 1.470 1.670 1.820 1.820 2.220 2.350 2.350
Technical performanceSYSCROLL AIR EVO 2+2P L 20 25 30 40 45 50 55 60 75 85 95 110
Heating
Heating capacity 1 kW 22,2 29,6 37,3 46,9 50,7 61,2 67,3 72,6 93,1 104,7 114,4 137,2Total input power 1 kW 5,3 7,1 9,0 11,4 12,0 13,6 15,4 17,0 22,1 25,3 28,4 32,4COP 1 4,11 4,12 4,13 4,11 4,22 4,49 4,38 4,27 4,21 4,14 4,03 4,24Energy Class 2 A+ A+ A+ A+ A+ A++ A++ A++ A+ A+ A+ A+
SCOP 2 3,40 3,69 3,53 3,57 3,67 3,97 3,91 3,87 3,70 3,67 3,69 3,70hsh
2 % 132,9 144,7 138,0 139,6 143,8 155,7 153,4 151,6 145,1 143,7 144,4 144,8
Cooling
Cooling capacity 3 kW 18,1 24,5 30,8 39,9 44,2 52,3 57,4 62,6 79,8 89,6 97,8 117,0Total input power 3 kW 7,0 9,6 10,9 15,0 16,3 18,4 21,5 24,5 27,2 31,7 36,5 43,8EER 3 2,57 2,56 2,84 2,65 2,72 2,84 2,67 2,55 2,93 2,83 2,68 2,67TER 4 9,05 9,43 9,56 9,54 10,41 10,48 10,42 10,43 9,84 9,63 9,46 9,91
Sound power 5 dB(A) 75 75 75 75 76 76 77 78 82 83 85 86Sound pressure 6 dB(A) 43 43 43 43 44 44 45 46 50 51 53 54
ErP2018
SYSCROLL AIR EVO 2+2P L 120 140 150 180 200 210 220 240 280 320 360 400
Heating
Heating capacity 1 kW 150,8 167,2 182,0 209,7 239,2 228,6 270,2 295,6 335,0 363,1 404,5 458,7Total input power 1 kW 35,8 41,3 45,4 50,3 55,8 56,7 67,0 74,1 83,5 90,3 105,1 116,4COP 1 4,21 4,05 4,01 4,17 4,29 4,03 4,03 3,99 4,01 4,02 3,85 3,94Energy Class 2 A+ A+ A+ A+ A++ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,74 3,69 3,62 3,76 3,83 3,65 3,63 3,65 3,66 3,73 3,61 3,63hsh
2 % 146,4 144,7 141,9 147,3 150,3 143,1 142,0 142,9 143,3 146,1 141,4 142,0
Cooling
Cooling capacity 3 kW 129,5 144,5 159,3 180,2 199,7 197,4 230,1 257,2 288,2 325,6 366,0 405,0Total input power 3 kW 44,3 51,8 58,8 66,3 74,5 73,1 81,9 91,5 105,6 116,7 136,1 155,2EER 3 2,92 2,79 2,71 2,72 2,68 2,70 2,81 2,81 2,73 2,79 2,69 2,61TER 4 9,87 9,99 9,90 9,79 9,74 9,27 9,18 9,60 9,68 9,71 9,62 9,50
Sound power 5 dB(A) 87 87 87 89 91 88 89 90 90 90 92 92Sound pressure 6 dB(A) 55 55 55 57 59 56 57 58 58 58 60 60
SYSCROLL AIR EVO 4P L 20 25 30 40 45 50 55 60 75 85 95 110
Heating
Heating capacity 1 kW 22,9 30,5 37,3 46,9 50,7 63,6 69,6 75,0 96,6 108,3 118,1 142,2Total input power 1 kW 5,6 7,3 9,0 11,4 12,0 13,7 15,5 17,1 22,3 25,5 28,7 32,6COP 1 4,11 4,20 4,13 4,11 4,22 4,64 4,50 4,39 4,33 4,24 4,11 4,36Energy Class 2 A+ A+ A+ A+ A+ A++ A++ A++ A+ A+ A+ A+
SCOP 2 3,47 3,76 3,53 3,57 3,67 4,04 4,00 3,95 3,76 3,73 3,78 3,76hsh
2 % 135,7 147,4 138,0 139,6 143,8 158,5 156,8 155,0 147,4 146,1 148,3 147,3
Cooling
Cooling capacity 3 kW 18,1 24,5 30,8 39,9 44,2 52,3 57,4 62,6 79,8 89,6 97,8 117,0Total input power 3 kW 7,0 9,6 10,9 15,0 16,3 18,4 21,5 24,5 27,2 31,7 36,5 43,8EER 3 2,57 2,56 2,84 2,65 2,72 2,84 2,67 2,55 2,93 2,83 2,68 2,67TER 4 9,05 9,43 9,56 9,54 10,41 10,48 10,42 10,43 9,84 9,63 9,46 9,91
Sound power 5 dB(A) 75 75 75 75 76 76 77 78 82 83 85 86Sound pressure 6 dB(A) 43 43 43 43 44 44 45 46 50 51 53 54
SYSCROLL AIR EVO 4P L 120 140 150 180 200 210 220 240 280 320 360 400
Heating
Heating capacity 1 kW 156,2 173,5 188,7 216,2 247,7 235,9 279,5 306,4 337,5 372,8 417,0 474,8Total input power 1 kW 36,0 40,5 45,3 50,6 56,1 58,1 68,5 74,6 83,5 92,1 107,2 118,9COP 1 4,34 4,28 4,17 4,27 4,41 4,06 4,08 4,11 4,04 4,05 3,89 3,99Energy Class 2 A+ A++ A+ A++ A++ A+ A+ A+ A+ A+ A+ A+
SCOP 2 3,81 3,83 3,77 3,85 3,96 3,68 3,63 3,74 3,74 3,75 3,63 3,66hsh
2 % 149,2 150,0 147,8 151,0 155,5 144,2 142,2 146,5 146,6 146,8 142,0 143,5
Cooling
Cooling capacity 3 kW 129,5 144,5 159,3 180,2 199,7 197,4 230,1 257,2 288,2 325,6 366,0 405,0Total input power 3 kW 44,3 51,8 58,8 66,3 74,5 73,1 81,9 91,5 105,6 116,7 136,1 155,2EER 3 2,92 2,79 2,71 2,72 2,68 2,70 2,81 2,81 2,73 2,79 2,69 2,61TER 4 9,87 9,99 9,90 9,79 9,74 9,27 9,18 9,60 9,68 9,71 9,62 9,50
Sound power 5 dB(A) 87 87 87 89 91 88 89 90 90 90 92 92Sound pressure 6 dB(A) 55 55 55 57 59 56 57 58 58 58 60 60
ErP2018
ErP2018
ErP2018
102 systemair
Expo 2015, China pavillionMilan, Italy• Water Cooled Heat Pump: WQH 75
FISH FACTORY JURASSIC
Poland
• Water Cooled Heat Pumps: 3 WQH 1004
CERRO DEL ÀGUILA HYDROELECTRIC POWER STATION
Peru
• Water Cooled Chillers: 3 WQL 90
AIR AMBULANCE BASE
Førde, Lebanon
• Air & Water Cooled Chillers and Heat Pump: WQL 604, WQL 45, SYSCROLL 75 Air HP
H
102 systemair
systemair 103
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
WATER COOLED CHILLERS & HEAT PUMPS
Quality and comfort for all your projects!
Perfect for any type of building, the system consists of water cooled chillers or heat pumps that provide cold or hot water to water terminals.This system is particularly well suited for applications such as office buildings, hotels, shopping centers and hospitals. The air cooled chiller variant of the system is also a fundamental part of many industrial processes.
systemair 103
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
104 systemair
Water Cooled Chillers, Heat Pumps and Condenserless units
WQL/WQH/WQRC 20-190 21-193 kW 24-212 kW R410A Scroll PlatePage 108
WQL/WQH/WQRC 524-1604 154-478 kW 170-532 kW R410A Scroll PlatePage 112
SYSCREW 440-1550 WATER EVO CO/HP/RC 444-1.567 kW 488-1.715 kW R134a Screw Shell & TubePage 116
HFC
HFC
HFC
ErP2018
EcodesignWater to Water chiller
ErP2018
100
120
140
160
180
200
2015 2016 2017 2018 2019 2020 2021 2022
ηsc / ηsh
200
115Sept. 2015
125Sept. 2017
196
Jan. 2021
years
Low-temperature Heat PumpsCOMMISSION REGULATION (EU) No813/2013 Minimum ηsh to be Ecodesign compliant
220
240
260
280
Jan. 2018
227Jan.
2018
252Jan.
2021245
Jan. 2018
272Jan.
2021
Air to Water Comfort chillersCOMMISSION REGULATION (EU) No2016/2281 <400 kw: Minimum ηsc to be Ecodesign compliant >400 kw and <1500 kw: Minimum ηsc to be Ecodesign compliant >1500 kw: Minimum ηsc to be Ecodesign compliant
2021Ready.
ErP20182021
2021Ready.
ErP20182021
systemair 105
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
Quick selection guide - Water Cooled Chillers and Heat Pumps
Product Size Cooling Capacity SEER Flow ratem3/h
Acoustic Power
Dimensions (LxHxW) mm
WQL
20-
190
WQL 20 21,2 kW 5,58 3,67 65 dB(A) 821 x
1.350 x 455
WQL 25 26,2 kW 5,6 4,54 67 dB(A) 821 x
1.350 x 455
WQL 30 31,1 kW 5,45 5,40 67 dB(A) 821 x
1.350 x 455
WQL 35 34,8 kW 5,5 6,05 68 dB(A) 821 x
1.350 x 455
WQL 40 39,2 kW 5,35 6,80 68 dB(A) 821 x
1.350 x 455
WQL 45 46,6 kW 5,83 8,06 70 dB(A) 821 x
1.350 x 455
WQL 50 50,9 kW 5,9 8,78 70 dB(A) 1.210 x
1.500 x 850
WQL 60 61,1 kW 6,13 10,55 70 dB(A) 1.210 x
1.500 x 850
WQL 75 77,3 kW 6,08 13,36 72 dB(A) 1.210 x
1.500 x 850
WQL 90 91,1 kW 6,2 15,73 73 dB(A) 1.210 x
1.500 x 850
WQL 120 118,4 kW 6,13 20,45 78 dB(A) 1.210 x
1.500 x 850
WQL 150 147,1 kW 6,38 25,38 81 dB(A) 1.210 x
1.500 x 850
WQL 170 170 kW 5,95 29,34 81 dB(A) 1.210 x
1.500 x 850
WQL 190 192,7 kW 6,7 33,26 81 dB(A) 1.210 x
1.500 x 850
Product Size Cooling & Heating capacity SEER SCOP Flow rate m3/h
Acoustic Power
Dimensions (LxHxW) mm
WQH
20-
190
WQH 20 20,8 Kw 5,13 5,65 4,07 65 dB(A) 821 x 1.350 x 455 23,7 Kw
WQH 25 26 Kw 5,0 5,40 4,97 67 dB(A) 821 x 1.350 x 455 28,9 Kw
WQH 30 30,1 Kw 4,88 5,24 5,80 67 dB(A) 821 x 1.350 x 455 33,6 Kw
WQH 35 34 Kw 5,1 5,23 6,62 68 dB(A) 821 x 1.350 x 455 38,5 Kw
WQH 40 38,2 Kw 5,0 5,18 7,38 68 dB(A) 821 x 1.350 x 455 42,9 Kw
WQH 45 45,5 Kw 5,48 5,46 8,82 70 dB(A) 821 x 1.350 x 455 51,2 Kw
WQH 50 49,9 Kw 4,7 5,06 9,83 70 dB(A) 1.210 x 1.500 x 850 57,7 Kw
WQH 60 58,9 Kw 4,88 5,57 11,63 70 dB(A) 1.210 x 1.500 x 850 68,2 Kw
WQH 75 76,1 Kw 4,47 5,28 14,72 72 dB(A) 1.210 x 1.500 x 850 86,3 Kw
WQH 90 88,6 Kw 4,83 5,05 17,42 73 dB(A) 1.210 x 1.500 x 850 102,2 Kw
WQH 120 114,9 Kw 4,93 5,50 22,46 78 dB(A) 1.210 x 1.500 x 850 132 Kw
WQH 150 144,3 Kw 4,97 5,12 28,01 81 dB(A) 1.210 x 1.500 x 850 164,2 Kw
WQH 170 165,7 Kw 5,65 5,21 32,40 81 dB(A) 1.210 x 1.500 x 850 190,1 Kw
WQH 190 185,4 Kw 5,1 5,34 36,18 81 dB(A) 1.210 x 1.500 x 850 212,3 Kw
Page 108
Page 108
106 systemair
Product Size Cooling Capacity SEER Flow rate m3/h
Acoustic Power
Dimensions (LxHxW) mm
WQL
524
-160
4
WQL 524 154,3 kW 5,55 26,64 81 dB(A) 2.250 x
1.845 x 850
WQL 604 181,8 kW 6,28 31,36 82 dB(A) 2.250 x
1.845 x 850
WQL 704 208,9 kW 6,1 36,04 85 dB(A) 2.250 x
1.845 x 850
WQL 804 232,6 kW 5,75 40,32 87 dB(A) 2.250 x
1.845 x 850
WQL 904 265,8 kW 6,1 45,72 89 dB(A) 2.250 x
1.845 x 850
WQL 1004 295,6 kW 6,1 50,76 90 dB(A) 2.250 x
1.845 x 850
WQL 1104 338 kW 6,2 58,32 90 dB(A) 2.250 x
1.845 x 850
WQL 1204 379,2 kW 6,25 65,52 90 dB(A) 2.250 x
1.845 x 850
WQL 1404 429,1 kW 6,2 73,80 90 dB(A) 2.250 x
1.845 x 850
WQL 1604 478,4 kW 5,88 82,44 90 dB(A) 2.250 x
1.845 x 850
Product Size Cooling & Heating capacity SEER SCOP Flow rate m3/h
Acoustic Power
Dimensions (LxHxW) mm
WQH
524
-160
4
WQH 524 150,7 Kw 4,65 5,19 29,16 81 dB(A) 2.250 x 1.845 x 850 170,2 Kw
WQH 604 176,2 Kw 4,93 5,31 34,45 82 dB(A) 2.250 x 1.845 x 850 201,1 Kw
WQH 704 204,5 Kw 4,93 5,25 39,60 85 dB(A) 2.250 x 1.845 x 850 231,8 Kw
WQH 804 225,4 Kw 4,68 5,14 43,92 87 dB(A) 2.250 x 1.845 x 850 256,5 Kw
WQH 904 263,1 Kw 5,15 5,56 50,76 89 dB(A) 2.250 x 1.845 x 850 295,6 Kw
WQH 1004 291,3 Kw 5,1 5,52 56,88 90 dB(A) 2.250 x 1.845 x 850 331 Kw
WQH 1104 332 Kw 5,28 5,76 64,80 90 dB(A) 2.250 x 1.845 x 850 376,6 Kw
WQH 1204 370,5 Kw 5,3 5,54 72,00 90 dB(A) 2.250 x 1.845 x 850 418,5 Kw
WQH 1404 423,4 Kw 6,14 - 82,44 92 dB(A) 2.250 x 1.845 x 850 477,5 Kw
WQH 1604 466,9 Kw 6,09 - 91,80 94 dB(A) 2.250 x 1.845 x 850 532 Kw
Page 112
Page 112
systemair 107
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
Product Size Cooling Capacity SEER Flow rate m3/h
Acoustic Power
Dimensions (LxHxW) mm
SySc
rew
440
-155
0 W
ater
EVO
CO
SYSCREW 440 WATER EVO CO
444,3 kW 5,9 76,68 95 dB(A) 3.620 x 1.750 x 1.350
SYSCREW 490 WATER EVO CO
494,4 kW 5,92 84,96 95 dB(A) 3.620 x 1.750 x 1.350
SYSCREW 570 WATER EVO CO
570,4 kW 6,2 98,28 95 dB(A) 4.210 x 1.750 x 1.350
SYSCREW 630 WATER EVO CO
636,2 kW 6,13 109,80 95 dB(A) 4.210 x 1.750 x 1.350
SYSCREW 700 WATER EVO CO
708,5 kW 5,98 122,04 95 dB(A) 4.180 x 1.750 x 1.350
SYSCREW 770 WATER EVO CO
787,1 kW 6,3 135,72 95 dB(A) 4.180 x 1.750 x 1.350
SYSCREW 860 WATER EVO CO
875,5 kW 5,92 150,98 98 dB(A) 4.400 x 1.710 x 1.520
SYSCREW 920 WATER EVO CO
936 kW 5,92 161,50 98 dB(A) 4.400 x 1.710 x 1.520
SYSCREW 990 WATER EVO CO
998,6 kW 5,9 172,30 98 dB(A) 4.600 x 1.710 x 1.520
SYSCREW 1070 Water EVO CO
1.071,4 kW 6,35 184,90 98 dB(A) 4.650 x 1.710 x 1.520
SYSCREW 1130 WATER EVO CO
1.132,9 kW 5,95 195,59 98 dB(A) 4.650 x 1.710 x 1.520
SYSCREW 1220 WATER EVO CO
1.224,1 kW 5,95 211,00 98 dB(A) 4.650 x 1.710 x 1.520
SYSCREW 1280 WATER EVO CO
1.285,2 kW 5,9 221,62 98 dB(A) 4.650 x 1.710 x 1.520
SYSCREW 1400 Water EVO CO 1.428,5 kW 5,87 246,71 98 dB(A) 5.350 x
1.710 x 1.520
SYSCREW 1550 WATER EVO CO
1.576 kW 6,0 270,79 98 dB(A) 5.350 x 1.710 x 1.520
Product Size Cooling & Heating capacity SEER COP Flow ratem3/h
Acoustic Power
Dimensions (LxHxW) mm
SySc
rew
440
-155
0 W
ater
EVO
HP
SYSCREW 440 WATER EVO HP
383,4 kW 5,95 4,68 97,49 95 dB(A) 3.620 x 1.750 x 1.350 487,7 kW
SYSCREW 490 WATER EVO HP
433,6 kW 6,0 4,75 110,30 95 dB(A) 3.620 x 1.750 x 1.350 549,1 kW
SYSCREW 570 WATER EVO HP
498,1 kW 6,0 4,65 126,79 95 dB(A) 4.210 x 1.750 x 1.350 634,6 kW
SYSCREW 630 WATER EVO HP
554,5 kW 5,87 4,61 141,08 95 dB(A) 4.210 x 1.750 x 1.350 707,9 kW
SYSCREW 700 WATER EVO HP
619,1 kW 5,92 4,58 157,39 95 dB(A) 4.180 x 1.750 x 1.350 791,9 kW
SYSCREW 770 WATER EVO HP
676,8 Kw 5,92 4,65 172,12 95 dB(A) 4.180 x 1.750 x 1.350 862,1 kW
SYSCREW 860 WATER EVO HP
755,9 kW 5,92 4,70 192,20 98 dB(A) 4.400 x 1.710 x 1.520 960,2 kW
SYSCREW 920 WATER EVO HP
813,8 kW 5,9 4,71 207,00 98 dB(A) 4.400 x 1.710 x 1.520 1.033,2 kW
SYSCREW 990 WATER EVO HP
874,6 kW 5,87 4,73 222,41 98 dB(A) 4.600 x 1.710 x 1.520 1.109,2 kW
SYSCREW 1070 WATER EVO HP
934,6 kW 6,52 4,67 237,71 98 dB(A) 4.650 x 1.710 x 1.520 1.189,3 kW
SYSCREW 1130 WATER EVO HP
985,3 kW 6,0 4,63 250,60 98 dB(A) 4.650 x 1.710 x 1.520 1.257 kW
SYSCREW 1220 WATER EVO HP
1.069,6 kW 5,92 4,68 271,80 98 dB(A) 4.650 x 1.710 x 1.520 1.359,9 kW
SYSCREW 1280 WATER EVO HP
1.122,1 kW 5,9 4,68 285,19 98 dB(A) 4.650 x 1.710 x 1.520
SYSCREW 1400 WATER EVO HP
1.241,5 kW 5,9 4,53 315,79 98 dB(A) 5.350 x 1.710 x 1.520
SYSCREW 1550 WATER EVO HP
1.341,5 kW 5,95 4,60 341,39 98 dB(A) 5.350 x 1.710 x 1.520
1.593,1 kW
1.714,6 kW
1.426,9 kW
Page 116
Page 116
108 systemair
The range at a glance 3 versions:
WQL (Cooling only) WQH (Heat Pump) WQRC (Condenserless unit)
14 sizes Cooling capacity from 21,2 to 192,7 kW Heating capacity from 23,7 to 212,3 kW 2 acoustic versions:
Standard version S (Super Low Noise)
2 frames: F1 (size from 20 to 45) F2 (size from 50 to 190)
Equipment One refrigerant circuit One or two Scroll compressors Plate evaporator (AISI 316) Compressors acoustic box (standard on S) Differential pressure switch Electronic expansion valve
(standard WQRC 170-190) Sequence phases control
Water Cooled Chillers, Heat Pumps and Condenserless units
WQL/WQH/WQRC 20-190
Accessories and optionsBMS interfaceCompressors jacketsDesuperheater available for frame 2Hydrokit with 1 or 2 pumps for evaporator and condenserMechanical gauges kitPower factor corrector capacitorsSoftstarterWater filterWater flow switch
WQL/WQH/WQRC 20-190 - Cooling only/Heat Pump/Condenserless unit
Leaving water temperature (cooling)
Water °C from +5 to +18
Water + glycol °C -8 / +5 (with glycol + electronic expansion valve);+5/+18 (standard)
∆ T °C from 3 to 8Only WQL-WQH 20-190Leaving water temperature (heating)
Water °C from +25 to +55
∆ T °C from 3 to 15
Note: maximum % glycol (ethylenic or propilenic): 40%.
Advantages
High full load efficiency → EER up to 4,5, COP up to 3,9 High seasonal performances → SEER up to 6.7 Compressor box → Remarkable sound reduction Reduced refrigerant charge → less than 10 [kg] per
circuit for units up to size 90 Advanced electronic controller → auto-adaptive
function to reduce water content in the piping system Condensing pressure control option suitable for well
application Wide range of “plug and play” hydrokit → easy
hydraulic installation DHW function available on the controller with 3-way
valve available as accessory → integration with plant Desuperheater heat exchanger available as option
(50-190 sizes)
Water cooled
HFC R410A
21-193 kW 24-212 kW
HOTELSOFFICES SHOPS SCHOOLS INDUSTRY
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Plate heat exchanger
Scroll compressor
ErP20182021
2021Ready.2
systemair 109
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
WQL 20-45 - Cooling only 20 25 30 35 40 45Cooling capacity1 kW 21,2 26,2 31,1 34,8 39,2 46,6Input power1 kW 4,56 5,67 6,84 7,54 8,60 10,1EER/ Energy efficiency class1 4,67/C 4,65/C 4,57/C 4,64/C 4,58/C 4,65/C
SEER2 5,58 5,6 5,45 5,5 5,35 5,83
hsc2 215 216 210 212 206 225
Sound power level3/4* dB(A) 65/62 67/64 67/64 68/65 68/66 70/67Sound pressure level at 10 m3/4** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
WQH 20-45 - Heat Pump 20 25 30 35 40 45
Cooling
Cooling capacity1 kW 20,8 26,0 30,1 34,0 38,2 45,5Power input1 kW 4,67 5,82 7,03 7,82 8,80 10,4EER/ Energy efficiency class1 4,45/C 4,47/C 4,28/C 4,35/C 4,34/C 4,39/CSEER2 5,13 5 4,88 5,1 5 5,48
hsc2 197 192 187 196 192 211
Heating
Heating capacity5 kW 23,7 28,9 33,6 38,5 42,9 51,2Power input5 kW 6,11 7,51 9,01 10,2 11,4 13,3COP/ Energy efficiency class5 3,88/C 3,85/C 3,73/D 3,79/D 3,77/D 3,85/CCOP6 5,43 5,34 5,18 5,27 5,19 5,02
SCOP /Energy eff. class 7 5,65/ A+++ 5,40/ A+++ 5,24/ A+++ 5,23/ A+++ 5,18/ A+++ 5,46/ A+++
hsh7 218 208 202 201 199 210
Sound power level3/4* dB(A) 65/62 67/64 67/64 68/65 68/66 70/67Sound pressure level at 10 m3/4** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
WQRC 20-45 - Condenserless unit 20 25 30 35 40 45Cooling capacity8 kW 18,3 22,7 27,1 30 34,2 43,1Power input8 kW 5,70 6,97 8,07 9,15 10,1 12,2Sound power level3/4* dB(A) 65/62 67/64 67/64 68/65 69/66 70/67Sound pressure level at 10 m3/4** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Physical featuresWQL 20-45 - Cooling only 20 25 30 35 40 45Water connection
EvaporatorConnection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”
CondenserConnection type VictaulicInlet/outlet diameter inch 1½˝ 1½” 1½” 1½” 1½” 1½”
WeightOperating weight kg 162 182 179 185 191 214DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350
WQH 20-45 - Heat Pump 20 25 30 35 40 45Water connection
EvaporatorConnection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”
CondenserConnection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”
WeightOperating weight kg 165 187 184 190 195 219DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350
Technical performance
1 According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C.2 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 104 for more information).3 Standard version.4 S version.5 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.6 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 30°C/35°C.7 ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 104 for more information).8 Data refered to evaporator water temperature 12/7°C and condensing temperature 50°C.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
ErP2018
ErP2018
110 systemair
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
Technical performance
WQRC 50-190 - Condenserless unit 50 60 75 90 120 150 170 190Cooling capacity8 kW 45 53,4 67,5 80,1 104 128 148 168Power input8 kW 13,7 16 20,1 23,9 30,8 38,1 44,2 49,7Sound power level3/4* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m3/4** dB(A) 39/37 39/37 41/39 42/40 47/45 50/48 50/48 50/48Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C.2 2021 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 104 for more information).3 Standard version.4 S version.5 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condens EWT/LWT 40°C/45°C.6 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 30°C/35°C.7 ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 104 for more information).8 Data refered to evaporator water temperature 12/7°C and condensing temperature 50°C.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
WQL 50-190 - Cooling only 50 60 75 90 120 150 170 190Cooling capacity1 kW 50,9 61,1 77,3 91,1 118,4 147,1 170,0 192,7Power input1 kW 11,7 13,5 17,1 20,7 26,5 33,0 37,7 42,8EER/ Energy efficiency class1 4,35/C 4,53/C 4,52/C 4,40/C 4,48/C 4,47/C 4,51/C 4,51/C
SEER2 6,13 6,38 5,95 6,7 5,90 6,13 6,08 6,2
hsc2 237 247 230 260 228 237 235 240
Sound power level3/4* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m3/4** dB(A) 39/37 39/37 40/39 42/40 47/45 50/48 50/48 50/48Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
WQH 50-190 - Heat Pump 50 60 75 90 120 150 170 190
Cooling
Cooling capacity1 kW 49,9 58,9 76,1 88,6 114,9 144,3 165,7 185,4Power input1 kW 12,0 13,9 17,5 21,1 27,0 33,3 38,2 43,3EER/ Energy efficiency class1 4,15/D 4,24/D 4,36/C 4,20/D 4,26/C 4,34/C 4,34/C 4,28/CSEER2 4,7 4,88 4,47 4,83 4,93 4,97 5,65 5,1
hsc2 180 187 171 185 189 191 218 196
Heating
Heating capacity5 57,7 68,2 86,3 102,2 132,0 164,2 190,1 212,3Power input5 kW 15,1 17,9 22,0 26,3 33,7 41,6 48,4 54,0COP / Energy efficiency class5 kW 3,83/D 3,81/D 3,92/C 3,89/C 3,92/C 3,95/C 3,93/C 3,93/CCOP6 5,09 4,95 5,24 5,08 5,16 5,25 5,2 5,2
SCOP /Energy efficiency class7 5,06 / A+++
5,57 / A+++
5,28 / A+++
5,05 / A+++
5,50 / A+++
5,12 / A+++
5,21 / A+++
5,34 / A+++
hsh7 194 215 203 194 212 197 200 205
Sound power level3/4* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m3/4** dB(A) 39/37 39/37 40/39 42/40 47/45 50/48 50/48 50/48Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
WQRC 20-45 - Condenserless unit 20 25 30 35 40 45
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”Remote condenser refrigerant connectionsConnection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅝” ⅝”Outlet diameter inch ⅝” ⅞” ⅞” ⅞” ⅞” ⅞”WeightOperating weight kg 144 164 166 166 172 172DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350
ErP2018
ErP2018
systemair 111
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Water connection (Condenser)Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”WeightOperating weight kg 352 371 392 411 597 666 701 745DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500
WQL 50-190 - Cooling only 50 60 75 90 120 150 170 190
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Water connection (Condenser)Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”WeightOperating weight kg 360 379 403 422 610 683 718 762DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500
Physical features
WQH 50-190 - Heat Pump 50 60 75 90 120 150 170 190
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Remote condenser refrigerant connectionsConnection type To be brazedInlet diameter inch ⅝” ⅝” ⅞” ⅞” ⅞” ⅞” 1⅛” 1⅛”Outlet diameter inch ⅞” ⅞” 1⅛” 1⅛” 1⅜” 1⅝” 1⅝” 1⅝”WeightOperating weight kg 332 344 365 376 558 612 643 674DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500
WQRC 50-190 - Condenserless unit 50 60 75 90 120 150 170 190
112 systemair
The range at a glance 3 versions:
WQL (Cooling only) WQH (Heat Pump) WQRC (Condenserless unit)
10 sizes Cooling capacity from 154,3 to 478,4 kW Heating capacity from 170,2 to 532 kW 2 acoustic versions:
Standard version S (Super Low Noise)
Equipment Two refrigerant circuits Four scroll compressors (tandem) Plate evaporator (AISI 316) Differential pressure switch Electronic expansion valve
(standard WQRC 1104-1204) Sequence phases control
Water Cooled Chillers, Heat Pumps and Condenserless units
WQL/WQH/WQRC 524-1604
Accessories and optionsDesuperheaterHydrokit with 1 or 2 pumps for evaporator and condenserMechanical gaugesSoftstarterWater filterWater flow switch
WQL/WQH/WQRC 524-1604 - Cooling only/Heat Pump/Condenserless unit
Leaving water temperature(cooling)
Water °C from +5 to +18
Water + glycol °C -8 / +5 (with glycol and electronic expansion valve);+5/+18 (standard)
∆ T °C from 3 to 8Only WQL-WQH 524-1604Leaving water temperature(heating)
Water °C from +25 to +55
∆ T °C from 3 to 15
Note: maximum % glycol (ethylenic or propilenic): 40%.
Advantages
High full load efficiency → EER up to 4,6, COP up to 4,1 High seasonal performances → SEER up to 6.3 Advanced electronic controller → auto-adaptive
function to reduce water content in the piping system Condensing pressure control option → suitable for well
application Wide range of “plug and play” hydrokit → easy
hydraulic installation Desuperheater heat exchanger available as option →
heating capacity for free thanks to heat recovery
154-478 kW 170-532 kW
Water cooled
HFC R410A
HOTELSOFFICES SHOPS SCHOOLS INDUSTRY
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Plate heat exchanger
Scroll compressor
ErP20182021
2021Ready.2
systemair 113
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
WQL 524-1604 - Cooling only 524 604 704 804 904 1004 1104 1204 1404 1604Cooling capacity1 kW 154,3 181,8 208,9 232,6 265,8 295,6 338,0 379,2 429,1 478,4Input power1 kW 34,2 41,6 47,5 53,3 59,3 65,7 74,9 83,4 95,2 107,4EER/ Energy efficiency class1 kW/kW 4,51/C 4,37/C 4,40/C 4,36/C 4,48/C 4,51/C 4,51/C 4,56/C 4,52/C 4,47/C
SEER2 (ErP 2018) 5,55 6,28 6,1 5,75 6,1 6,1 6,2 6,25 6,2 6,125
hsc2 (ErP 2018) 214 243 236 222 236 236 240 242 240 237
SEER2 (ErP 2021) 5,55 6,28 6,1 5,75 6,1 6,1 6,2 6,25 - -
hsc2 (ErP 2021) 214 243 236 222 236 236 240 242 - -
Sound power level3/4* dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84 90/84 90/84Sound pressure level at 10 m3/4** dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52 58/52 58/52Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C.2 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 104 for more information).3 Standard version. 4 S version.5 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.6 According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 30°C/35°C.7 ERP Compliant: Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps (see page 104 for more information).8 Data refered to evaporator EWT/LWT 12 °C/7 °C and condensing temperature 50 °C.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
WQH 524-1604 - Heat Pump 524 604 704 804 904 1004 1104 1204 1404 1604
Cooling
Cooling capacity1 kW 150,7 176,2 204,5 225,4 263,1 291,3 332,0 370,5 423,4 466,9Input power1 kW 34,9 42,7 48,3 54,3 59,8 66,4 76,2 85,2 96,8 107,6EER/ Energy efficiency class1 kW/kW 4,32/C 4,13/D 4,23/D 4,15/D 4,40/C 4,39/C 4,36/C 4,35/C 4,38/C 4,34/CSEER2 4,65 4,93 4,93 4,68 5,15 5,1 5,28 5,3 6,14 6,09
hsc2 178 189 189 179 198 196 203 204 238 236
Heating
Heating capacity5 kW 170,2 201,1 231,8 256,5 295,6 331,0 376,6 418,5 477,5 532Input power5 kW 44,2 53,6 60,2 68,4 77,4 84,0 95,6 106,2 117,7 133,5COP/ Energy efficiency class5 kW/kW 3,85/C 3,75/D 3,85/C 3,75/D 3,82/C 3,94/C 3,94/C 3,94/C 4,06/C 3,98/CCOP6 5,22 4,96 5,11 4,96 5,24 5,34 5,22 5,22 5,25 5,19
SCOP7 5,19 5,31 5,25 5,14 5,56 5,52 5,76 5,54 - -Energy eff. class7 A+++ A+++ A+++ A+++ A+++ A+++ A+++ A+++ - -
hsh7 200 204 202 198 214 213 222 214 - -
Sound power level3/4* dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84 92/86 94/88Sound pressure level at 10 m3/4** dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52 60/54 62/56Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
WQRC 524-1604 - Condenserless unit 524 604 704 804 904 1004 1104 1204 1404 1604Cooling capacity8 kW 130,0 155,3 177,6 196,5 224,2 247,2 285,9 316,1 369 410Input power8 kW 43,2 51,5 59,5 66,4 74,8 83 95 106 117 132Sound power level3/4* dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84 92/86 94/88Sound pressure level at 10 m3/4** dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52 60/54 62/56Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
ErP2018
ErP2018
114 systemair
Internal heat exchanger water connectionsType VictaulicInlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4” 4”Remote condenser refrigerant connectionsType To be brazedInlet diameter inch 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8”Outlet diameter inch 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8”WeightOperating weight kg 770 812 988 1.163 1.188 1.241 1.328 1.388 1.414 1.440Operating weight S kg 873 915 1.091 1.266 1.291 1.344 1.431 1.491 1.517 1.543DimensionsLength mm 2.250Width mm 8501/8542/8851/3- 1.0052/3
Height mm 1.8451/1.8502
Internal heat exchangerType VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4” 4”External heat exchangerType VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4” 4”WeightOperating weight kg 909 989 1.187 1.360 1.376 1.500 1.598 1.704 1.735 1.761Operating weight S kg 1.012 1.092 1.290 1.463 1.479 1.603 1.701 1.807 1.833 1.859DimensionsLength mm 2.250Width mm 8501/8542/8851/3- 1.0052/3
Height mm 1.8451/1.8502
WQH 524-1604 - Heat Pump 524 604 704 804 904 1004 1104 1204 1404 1604
WQRC 524-1604 - Condenserless unit 524 604 704 804 904 1004 1104 1204 1404 1604
1 Standard version. 2 S version.3 Only for handling.
Water connection (Evaporator)Type VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4” 4”Water connection (Condenser)Type VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4” 4”WeightOperating weight kg 890 971 1.156 1.329 1.340 1.453 1.552 1.660 1.668 1.716Operating weight S kg 993 1.074 1.259 1.432 1.443 1.556 1.655 1.763 1.791 1.819DimensionsLength mm 2.250Width mm 8501/8542/ 8851/3 - 1.0052/3
Height mm 1.8451/ 1.8502
Physical featuresWQL 524-1604 - Cooling only 524 604 704 804 904 1004 1104 1204 1404 1604
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
systemair 115
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
Kazansky railway stationMoscow, Russia• Water Cooled Chiller SWR 4602
116 systemair
Water Cooled Chillers, Heat Pumps and Condenserless units
SYSCREW 440-1550 WATER EVO CO/HP/RC
Accessories and optionsAutomatic circuit breakerBMS interfaceCompressor stepless controlMechanical gaugesPower factor corrector capacitorsSoftstarterWater filterWater flow switch
The range at a glance 3 versions:
CO (Cooling only) HP (Heat Pump water side) RC (Condenserless unit)
15 sizes Cooling capacity from 444 to 1.567 kW 2 acoustic versions:
Standard version S (Super Low Noise)
Equipment 1/2 refrigerant circuit Screw compressors Shell & Tube evaporator and condenser Electronic expansion valve Compressors acoustic box (standard for S version) Sequence phases control
MODELSSYSCREW
WATER EVO CO - Cooling only
SYSCREW WATER EVO HP -
Heat Pump
SYSCREW WATER EVO RC -Condenserless
unit
Evaporator Leaving watertemperature
Water °C from 5 to 15from 5 to 15Water + glycol °C from -8 to 5∆ T °C from +3 to 7
Condenser
Leaving water temperature °C from 25 to 45 from 25 to 60 -Condensing Temperature °C - - from 30 to 63
Leaving water + glycol temperature °C from +3 to +8 with tower water15 with well water -
Advantages
High full load performances → EER up to 5,1 High seasonal performances → SEER up to 6,3 Compressor optimization (high / low pressure ratio),
according application → Maximum benefit in terms of efficiency design
Electronic expansion device → Excellent control of superheating for the best performance at full and partial load and for a safe operation New generation of pure counter-current shell&tube
evaporators and condensers → Maximum efficiency and new levels of competitiveness
Control platform → Modular architecture, compressor envelope integration, corrective actions in border line areas, easy-friendly user interface
R134a
444-1.567 kW 488-1.715 kW
Water cooled
HFC
HOTELSOFFICES INDUSTRYHOSPITALS
H
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
Screw compressor
Shell & Tube evaporator
ErP2018
systemair 117
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
SYSCREW 440-770 WATER EVO CO - Cooling only 440 490 570 630 700 770Cooling capacity1 kW 444,3 494,4 570,4 636,2 708,5 787,1Power input1 kW 87,9 97,8 112,4 125,4 140,2 155,7EER/ Energy efficiency class1 5,06/A 5,05/A 5,07/A 5,07/A 5,05/A 5,06/A
SEER2 5,9 5,925 6,2 6,125 5,975 6,3
hsc2 228 229 240 237 231 244
Sound power level STD3 dB(A) 95 95 95 95 95 95Sound pressure level at 1 m STD4 dB(A) 76 76 76 76 76 76Sound power level S3 dB(A) 85 85 85 85 85 85Sound pressure level at 1 m S4 dB(A) 66 66 66 66 66 66Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
1 According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C.2 2018 ERP Compliant: Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers (see page 104 for more information). 3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.5 According to EN145113:2011 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.6 According to EN145113:2011 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 47°C/55°C.7 According to EN145113:2011 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 30°C/35°C.
SYSCREW 440-770 WATER EVO HP - Heat pump 440 490 570 630 700 770Cooling Capacity1 kW 383,4 433,6 498,1 554,5 619,1 676,8Power input1 kW 104,3 115,6 136,4 153,4 172,8 185,2Cooling Capacity6 kW 339,5 383,8 441,3 491,4 548,0 599,1Power input6 kW 117,1 130,3 152,2 172,0 195,5 208,9SEER2 5,95 6,00 6,00 5,875 5,925 5,925
hsc2 230 232 232 227 229 229
Heating Capacity5 kW 487,7 549,1 634,6 707,9 791,9 862,1COP5 4,68 4,75 4,65 4,61 4,58 4,65COP7 5,67 5,75 5,65 5,71 5,58 5,65Heating Capacity6 kW 456,6 514,1 593,5 663,4 743,5 808,0COP6 3,90 3,95 3,90 3,86 3,80 3,87Sound Power level STD3 dB(A) 95 95 95 95 95 95Sound Pressure level at 1 m STD4 dB(A) 76 76 76 76 76 76Sound Power Level S3 dB(A) 85 85 85 85 85 85Sound Pressure Level at 1 m S4 dB(A) 66 66 66 66 66 66Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
Technical performance
SYSCREW 860-1550 WATER EVO HP - Heat Pump 860 920 990 1070 1130 1220 1280 1400 1550Cooling Capacity1 kW 755,9 813,8 874,6 934,6 985,3 1.069,6 1.122,1 1.241,5 1.341,5Power Input1 kW 204,3 219,4 234,6 254,7 271,7 290,3 304,8 351,6 373,1Cooling Capacity6 kW 669,3 720,7 774,4 827,8 872,7 946,6 993,3 1.100,0 1.189,1Power input6 kW 230,2 246,6 264,0 286,2 305,1 327,7 343,8 395,2 417,5SEER2 5,925 5,9 5,875 6,525 6 5,925 5,9 5,9 5,95
hsc2 229 228 227 253 232 229 228 228 230
Heating Capacity5 kW 960,2 1.033,2 1.109,2 1.189,3 1.257,0 1.359,9 1.426,9 1.593,1 1.714,6COP5 4,70 4,71 4,73 4,67 4,63 4,68 4,68 4,53 4,60COP7 5,72 5,74 5,75 5,68 5,63 5,67 5,68 5,57 5,65Heating Capacity6 kW 899,5 967,3 1.038,4 1.114,0 1.177,8 1.274,3 1.337,1 1.495,2 1.606,6COP6 3,91 3,92 3,93 3,89 3,86 3,89 3,89 3,78 3,85Sound power level STD3 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level at 1 m STD4 dB(A) 79 79 79 79 79 79 79 79 79Sound power level S3 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level at 1 m S4 dB(A) 70 70 70 70 70 70 70 70 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 860-1550 WATER EVO CO - Cooling only 860 920 990 1070 1130 1220 1280 1400 1550Cooling capacity1 kW 875,5 936,0 998,6 1.071,4 1.132,9 1.224,1 1.285,2 1.428,5 1.567,0Power input1 kW 173,1 185,2 197,6 211,7 223,8 241,0 253,9 282,4 309,9EER/ Energy efficiency class1 5,06/A 5,05/A 5,05/A 5,06/A 5,06/A 5,08/A 5,06/A 5,06/A 5,06/A
SEER2 5,925 5,925 5,9 6,35 5,95 5,95 5,9 5,875 6
hsc2 229 229 228 246 230 230 228 227 232
Sound power level STD3 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level at 1 m STD4 dB(A) 79 79 79 79 79 79 79 79 79Sound power level S3 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level at 1 m S4 dB(A) 70 70 70 70 70 70 70 70 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
ErP2018
ErP2018
118 systemair
SYSCREW 860-1550 WATER EVO RC - Condenserless unit 860 920 990 1070 1130 1220 1280 1400 1550Cooling capacity1 kW 760,8 820,0 880,4 941,7 993,6 1.074,2 1.127,6 1.253,8 1.357,3Power input1 kW 201 215 231 250 266 288 301 345 363EER1 3,78 3,81 3,81 3,76 3,73 3,74 3,74 3,64 3,74Sound power level STD2 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level at 1 m STD3 dB(A) 79 79 79 79 79 79 79 79 79Sound power level S2 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level at 1 m S3 dB(A) 70 70 70 70 70 70 70 70 70Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 860-1550 WATER EVO CO - Cooling only 860 920 990 1070 1130 1220 1280 1400 1550
Water connection
EvaporatorConnection type VictaulicInlet/outlet diameter inch 8" 8" 10" 10" 10" 10" 10" 10" 10"
CondenserConnection type Female gas threadedInlet/outlet diameter inch 4" 4" 4" 4"/5" 5" 5" 5" 5" 5"
WeightOperating weight kg 5.540 5.576 5.787 5.909 6.016 6.087 6.136 6.754 6.849Operating weight S kg 5.900 5.936 6.147 6.269 6.376 6.447 6.496 7.114 7.209
DimensionsLength mm 4.400 4.400 4.600 4.650 4.650 4.650 4.650 5.350 5.350Length S mm 4650 4650 4650 4650 4650 4.650 4.650 5400 5400Width mm 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520Height mm 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710Height S mm 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770
1 Data refered to evaporator EWT/LWT 12 °C/7 °C and condensing temperature 50 °C.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
Physical features
SYSCREW 440-770 WATER EVO RC - Condenserless unit 440 490 570 630 700 770Cooling capacity1 kW 386,3 435,7 502,8 561,0 621,9 680,6Power input1 kW 102 114 133 150 172 183EER1 3,78 3,81 3,78 3,75 3,62 3,72Sound power level STD2 dB(A) 95 95 95 95 95 95Sound pressure level at 1 m STD3 dB(A) 76 76 76 76 76 76Sound power level S2 dB(A) 85 85 85 85 85 85Sound pressure level at 1 m S3 dB(A) 66 66 66 66 66 66Power supply voltage V/Ph/Hz 400/3/50 (Nominal)
SYSCREW 440-770 WATER EVO CO - Cooling only 440 490 570 630 700 770
Water connection
EvaporatorConnection type VictaulicInlet/outlet diameter inch 6" 6" 6" 6" 8" 8"
CondenserConnection type Female gas threadedInlet/outlet diameter inch 4" 4" 5" 5" 5" 5"
WeightOperating weight kg 2.683 2.718 2.911 3.033 3.516 3.590Operating weight S kg 2.863 2.898 3.091 3.213 3.696 3.770DimensionsLength mm 3.620 3.620 4.210 4.210 4.180 4.180Width mm 1.350 1.350 1.350 1.350 1.350 1.350Height mm 1.650 1.650 1.650 1.650 1.650 1.650Height S mm 1.750 1.750 1.750 1.750 1.750 1.750
SYSCREW 440-770 WATER EVO HP - Heat Pump 440 490 570 630 700 770
Water connection
EvaporatorConnection type VictaulicInlet/outlet diameter inch 6" 6" 6" 6" 8" 8"
CondenserConnection type VictaulicInlet/outlet diameter inch 4" 4" 5" 5" 5" 5"
WeightOperating weight kg 2.690 2.725 2.918 3.040 3.523 3.597Operating weight S kg 2.884 2.919 3.112 3.234 3.717 3.791
systemair 119
WAT
ER C
OOLE
D CH
ILLE
RS
& HE
AT P
UMPS
SYSCREW 440-770 WATER EVO RC - Condenserless unit 440 490 570 630 700 770
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 6" 6" 6" 6" 8" 8"Remote condenser refrigerant connectionsConnection type To be brazedInlet diameter circuit 1 inch 1"5/8 1"5/8 2"1/8 2"1/8 2"1/8 2"1/8Outlet diameter circuit 1 inch 3"1/8 3"1/8 3"5/8 3"5/8 4"1/8 4"1/8WeightOperating weight kg 2.295 2.305 2.449 2.469 2.945 2.985Operating weight kg 2.475 2.485 2.629 2.649 3.125 3.165DimensionsLength mm 3.620 3.620 4.210 4.210 4.180 4.180Width mm 1.350 1.350 1.350 1.350 1.350 1.350Height mm 1.650 1.650 1.650 1.650 1.650 1.650Height S mm 1.750 1.750 1.750 1.750 1.750 1.750
SYSCREW 440-770 WATER EVO HP - Heat Pump 440 490 570 630 700 770
DimensionsLength mm 3.620 3.620 4.210 4.210 4.180 4.180Width mm 1.350 1.350 1.350 1.350 1.350 1.350Height mm 1.650 1.650 1.650 1.650 1.650 1.650Height S mm 1.750 1.750 1.750 1.750 1.750 1.750
SYSCREW 860-1550 WATER EVO HP - Heat Pump 860 920 990 1070 1130 1220 1280 1400 1550
Internal heat exchanger
EvaporatorConnection type VictaulicInlet/outlet diameter inch 8" 8" 10" 10" 10" 10" 10" 10" 10"
CondenserConnection type VictaulicInlet/outlet diameter inch 4" 4" 4" 4"/5" 5" 5" 5" 5" 5"
WeightOperating weight kg 5.579 5.615 5.826 5.948 6.055 6.126 6.175 6.793 6.888Operating weight S kg 5.966 6.002 6.213 6.335 6.442 6.513 6.562 7.180 7.275
DimensionsLength mm 4.400 4.400 4.600 4.650 4.650 4.650 4.650 5.350 5.350Length S mm 4650 4650 4650 4650 4650 4.650 4.650 5400 5400Width mm 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520Height mm 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710Height S mm 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770
SYSCREW 860-1550 WATER EVO RC - Condenserless unit 860 920 990 1070 1130 1220 1280 1400 1550
Water connection (Evaporator)Connection type VictaulicInlet/outlet diameter inch 8" 8" 10" 10" 10" 10" 10" 10" 10"Remote condenser refrigerant connectionsConnection type To be brazedInlet diameter circuit 1 inch 1"5/8 1"5/8 1"5/8 2"1/8 2"1/8 2"1/8 2"1/8 2"1/8 2"1/8Outlet diameter circuit 1 inch 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 4"1/8 4"1/8Inlet diameter circuit 2 inch 1"5/8 1"5/8 1"5/8 2"1/8 2"1/8 2"1/8 2"1/8 2"1/8 2"1/8Outlet diameter circuit 2 inch 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 3"1/8 4"1/8 4"1/8WeightOperating weight kg 4.765 4.775 4.959 5.032 5.092 5.131 5.151 5.557 5.637Operating weight S kg 5.125 5.135 5.319 5.392 5.452 5.491 5.511 5.917 5.997
DimensionsLength mm 4.400 4.400 4.600 4.650 4.650 4.650 4.650 5.350 5.350Length S mm 4650 4650 4650 4650 4650 4.650 4.650 5400 5400Width mm 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520Height mm 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710Height S mm 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770
ConfigurationFollowing modules are available in order to cover a wide capacity range: 1V: equipped with two coils and two fan motors 2V: equipped with four coils and four fan motors 3V: equipped with six coils and six fan motors 4V: equipped with eight coils and eight fan motors
Each module is be available in further versions, according coil row number, sound level emission.
Following table is summarizing allowed combination between free-cooling modules and SyScroll Air range.The table is valid for Slave version.
SYSCROLL AIR CO Free-cooling module SYSCROLL AIR FC
Assembly view Size Assembly view Size Assembly view
240270290320
232432
360420
3334
470540
3334
590660
4344
+ =
SYSCROLL AIR EVO CO Free-cooling module SYSCROLL AIR EVO FC
Assembly view Size Assembly view Size Assembly view
200 22
230260280
232432
300330360
232432
+ =
V VV VVV VVVV
Stand-alone Slave / Stand-alone
85 200 300 400 550
Cooling Capacity (kW)
Following picture is showing cooling capacity field where it is possible to have stand-alone, slave or both configuration.
Free-cooling modules
120 systemair
FREE-COOLING MODULES
Flexibility and Energy savings
Our freecooling modules are available in two versions: • Slave: the module can be linked to a SyScroll unit with structural and hydronic links. In this case the chill-
er and the free-cooling module will be delivered as a monoblock unit from factory.• Stand-alone: an independent module to link to a Systemair existing air cooled unit (already on field),
acting as an intelligent pre-cooler.
SYSFREECOOL 100-550 kW Free-coolingPage 122
systemair 121
FREE
-COO
LING
MOD
ULES
SYSFREECOOL
The range at a glance 10 sizes Cooling capacity from 100 to 550 kW Free-cooling option is developed in 2 versions:
Slave Stand-alone
2 acoustic versions: Standard version L (Low Noise)
2 fans versions: EC Version (Inverter Fans) HPF Version (High Pressure Fans)
Equipment Fan speed control Hour meter Sequence phase control Set point timer/clock card
Free-cooling modules
Accessories and optionsAutomatic circuit breakerBrushless fan motors (EC Version)Coil grillesCoils with cooper finsE-coating for AL/CU finsFree-cooling grillesHigh static pressure fan motors (HPF Version)Main switchModBus protocol kitPower supply without neutralRemote keyboard panelRemote ON/OFF controlWater filter
Free-cooling
SYSFREECOOL 12 14 22 23 24 32 33 34 43 44
BrineMinimum temperature1 °C -10Maximum operating pressure bar 6
AmbientOutdoor air temperature °C from -20 to +50
External static pressure
Standard fans Pa 0High pressure fans(HPF) Pa < 120
Power supply2 V/Ph/Hz 400/3/50 (Nominal)
1 Liquid with appropriate % of glycol.2 Voltage 400V +/- 10%.
Advantages
Flexibility: thanks to the fact that the module is physically independent from the unit it is possible to choose the best size matching, according required free-cooling capacity and sound level
Fan deck independency: there is no need to find a compromise between chiller and free-cooling fan deck management
Energy saving thanks to free-cooling technology Rapid investment pay back Remarkable CO2 seasonal indirect production
decrease
100-500 kWINDUSTRYOFFICES DATA CENTRES
100100101010001011
0010111
Operating limits (to be confirmed with AC SELECT - https://acselect.systemair.com)
122 systemair
Water ConnectionsType Male gas threadedInlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”Outlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”WeightOperating weight kg 669 733 1.002 1.075 1.139DimensionsLength mm 2.146 2.124Width mm 1.097 2.146Height mm 2.519 2.519
Water ConnectionsType Male gas threaded VictaulicInlet Diameter inch 3” 4” 4” 5” 5”Outlet Diameter inch 3” 4” 4” 5” 5”WeightOperating weight kg 1.466 1.574 1.670 2.070 2.198DimensionsLength mm 3.176 4.228Width mm 2.146 2.146Height mm 2.519 2.519
Physical features
1 Data refers to 15 (°C) return brine temperature, 10 (°C) leaving brine temperature, 0 (°C) outdoor air temperature; 30% EG.2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.3 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
SYSFREECOOL (STD -HPF) 12 14 22 23 24Nominal capacity1 kW 101 156 206 245 275Nominal water flow (in the evaporator) m3/h 19,0 29,4 38,7 46,0 51,7Total pressure drop1 kPa 44 83 74 43 49Sound power level2 dB(A) 88 88 91 91 91Sound pressure level at 10 m3 dB(A) 56 56 59 59 59
SYSFREECOOL (STD -HPF) L 12 14 22 23 24Nominal capacity1 kW 84,4 123,5 170,3 197,0 215,9Nominal water flow (in the evaporator) m3/h 15,9 23,2 32,0 37,0 40,6Total pressure drop1 kPa 31 52 50 28 30Sound power level2 dB(A) 79 79 82 82 82Sound pressure level at 10 m3 dB(A) 47 47 50 50 50
SYSFREECOOL (STD -HPF) 12 14 22 23 24
SYSFREECOOL (STD -HPF) 32 33 34 43 44Nominal capacity1 kW 309 367 413 490 550Nominal water flow (in the evaporator) m3/h 58,0 69,0 77,5 92,0 103,4Total pressure drop1 kPa 70 51 57 43 49Sound power level2 dB(A) 93 93 93 94 94Sound pressure level at 10 m3 dB(A) 61 61 61 62 62
SYSFREECOOL (STD -HPF) L 32 33 34 43 44Nominal capacity1 kW 255,4 295,5 323,8 394,0 431,8Nominal water flow (in the evaporator) m3/h 48,0 55,5 60,8 74,0 81,1Total pressure drop1 kPa 48 33 35 28 30Sound power level2 dB(A) 84 84 84 85 85Sound pressure level at 10 m3 dB(A) 52 52 52 53 53
Physical featuresSYSFREECOOL (STD -HPF) 32 33 34 43 44
Technical performance
Technical performance
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
systemair 123
FREE
-COO
LING
MOD
ULES
NEW airport of IstanbulTurkey• 5,000 Fan Coil Units
HOSPITAL
Orleans, France
• 1,000 Cassettes &
other Fan Coil Units
CASINO, BUILDING B1
Vitry-sur-Seine, France
• 1,200 Fan Coil Units DUCTYS
MUCEM HISTORY MUSEUM
Marseille, France
• 80 Fan Coil Units
124 systemair
systemair 125
FAN COIL UNITS
A large range of fan coil units dedicated to :
Energy savings & ComfortLow consumption solutions High efficiency fan motor
High level of energy performances
Silence Optimized fan speed staging Reinforced acoustic insulation Profiled air diffusers
Flexibility & QualityMany factory-mounted options Control, Valve, Air diffusion, Condensate drain pump ...
Products fully customizable to satisfy your requirements Choice of service side for hydraulic and electrical connections Version with or without cabinet ...
ErP2018
SRCNew mini BMS
New
systemair 125
FAN
COIL
UNI
TS
126 systemair
FAN COIL UNITS
All Systemair terminal units are ERP compliant following COMMISSION REGULATION (EU) No2016/2281.
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection program https://acselect.systemair.com
ErP2018
ErP2018
ErP2018
ErP2018
ErP2018
Quick selection guideFloor/Ceiling
Product Size Cooling & Heating Capacities * Acoustic *(at MS)
Airflow *(m3/h)
Fan Dimensions With cabinet & without feet (LxWxH)
SYSC
OIL
COM
FORT
SCC10 NR 33 108-417 AC/EC 766 x 225 x 477
SCC20 NR 33 98-413 AC/EC 766 x 225 x 477
SCC30 NR 36 145-585 AC/EC 951 x 225 x 477
SCC40 NR 30 170-678 AC/EC 1.136 x 225 x 477
SCC50 NR 37 203-816 AC/EC 1.321 x 225 x 477
SCC60 NR 40 245-912 AC/EC 1.506 x 225 x 477
SCC70 NR 40 350-1.050 AC/EC 1.319 x 225 x 575
SCC80 NR 42 685-1.398 AC/EC 1.506 x 225 x 575
* EC fan / 2-pipe versions
ErP2018
2,1 kW2,4 kW2,4 kW2,8 kW3,1 kW2,8 kW
4,2 kW4,5 kW5,0 kW5,2 kW5,2 kW5,8 kW6,9 kW7,6 kW8,8 kW9,8 kW
SYSCOIL COMFORT 0,5-9,6 kW 0,6-13,6 kW 91-1.398 m3/h EC Fan(s)Pages 128 to 131
DUCTYS 0,6-6,7 kW 0,4-7,1 kW 44-1.293 m3/h EC FanPage 138
VH 3,2-26,4 kW 2,5-29,6 kW 320-3.736 m3/h EC FanPages 140 to 143
SYSQUARE 1,3-9,6 kW 1,1-14,0 kW 360-1.598 m3/h EC FanPages 132 to 135
HAWAIR 0,9-3,9 kW 1,0-4,1 kW 150-850Page 136
New
Page 128
systemair 127
FAN
COIL
UNI
TS
Cassettes
Product Size Cooling & Heating Capacities * Acoustic *(at MS)
Airflow *(m3/h)
FanDimensions
Casing + IRYS COANDA 360 diffuser (LxWxH)
SYSQ
UARE
SQ20 NR 27 360-659 AC/EC 595 x 595 x 341
SQ30 NR 30 320-734 AC/EC 595 x 595 x 341
SQ40 NR 34 486-900 AC/EC 595 x 595 x 341
SQ50 NR 26 529-979 AC/EC 849 x 849 x 358
SQ60 NR 32 500-1.159 AC/EC 849 x 849 x 358
SQ70 NR 38 601-1.598 AC/EC 849 x 849 x 358
Quick selection guide
Wall-mounted
Product Size Cooling & Heating Capacities Acoustic(at MS)
Airflow(m3/h)
Fan Dimensions (LxWxH)
HAW
AIR
HaWair 7 NR 36 282-360 AC 845 x 180 x 275
HaWair 9 NR 39 367-551 AC 845 x 180 x 275
HaWair 18 NR 43 532-680 AC 940 x 200 x 298
HaWair 22 NR 46 617-850 AC 940 x 200 x 298
Ducted
Product Size Cooling & Heating Capacities * Acoustic *(at MS)
Airflow *(m3/h)
Pressure(Pa)
FanDimensions
Configuration: rectangular return and discharge (LxWxH)
DUCT
YS
DUCTYS 10 NR 30 48-161 0-70 EC 633 x 631 x 223
DUCTYS 15 NR 32 255-491 0-100 EC 733 x 631 x 223
DUCTYS 20 NR 35 360-599 0-100 EC 833 x 631 x 223
DUCTYS 25 NR 34 448-642 0-100 EC 933 x 631 x 223
DUCTYS 40 NR 34 347-1.293 0-100 EC 1.233 x 653 x 223
Product Size Cooling & Heating Capacities * Acoustic *(at MS)
Airflow *(m3/h)
Pressure(Pa)
FanDimensions
Configuration: rectangular return and discharge (LxWxH)
VH
VH07 NR 34 703-1.125 0-110 AC/EC 1.200 x 698 x 250
VH15 NR 40 960-2.830 0-200 AC/EC 1.380 x 798 x 375
VH18 NR 40 960-2.830 0-200 AC/EC 1.380 x 798 x 375
VH21 NR 40 960-2.830 0-200 AC/EC 1.380 x 798 x 375
VH24 NR 44 2.040-2.925 0-220 AC/EC 1.500 x 798 x 450
VH27 NR 44 2.040-2.925 0-220 AC/EC 1.500 x 798 x 450
* EC fan / 2-pipe versions
* EC fan / 2-pipe versions
* AC fan / 2-pipe versions
2,4 kW2,7 kW4,0 kW3,7 kW4,7 kW5,3 kW6,1 kW6,8 kW7,2 kW8,5 kW9,6 kW
11,0 kW
1,7 kW1,7 kW2,4 kW2,5 kW3,5 kW3,7 kW3,9 kW4,1 kW
0,9 kW0,9 kW2,0 kW2,6 kW2,7 kW2,6 kW3,2 kW3,4 kW
6,7 kW7,1 kW
5,6 kW7,8 kW
13,3 kW15,5 kW
13,9 kW18,0 kW
17,0 kW17,8 kW19,0 kW
20,9 kW21,9 kW21,5 kW
Page 132
Page 136
Page 138
Page 140
128 systemair
The range at a glance 8 sizes 5-speed AC fan(s) - Standard factory
set speeds : S1,S3,S5 Cooling Capacities from 0,7 to 8,1 kW Heating Capacities from 0,7 to 10,3 kW Airflow from 95 to 1.397 m3/h Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Configuration: Universal installation units (vertical
or horizontal) with or without cabinet Left or Right water connections Many air inlet / outlet configurations G2 air filter (G3 as an option)
Accessories & Options2-way or 3-way valves4 pipes kit (additional coil)
Circuit breakersCustomer markDrain pumpElectric heaters (from 500W to 2500W)
Feet with/without gridFuse holdersG3 filterHorizontal or vertical drain guard (with valve)
Individual packagingMany air inlet/oulet configurationsMechanical sensor for automatic change overModbus communication board for SYSLOGIC **MRC/WRC/BRC : remote controls for SYSLOGIC **Other speeds configuration (Standard factory set speeds : S1,S3,S5)
SRC - Smart Remote Control (Mini BMS) **Suspension kitSYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controllers (other electromechanical or electronic control systems also available) **
Operating limitsSYSCOIL COMFORTEntering water temperature (without glycol) from +5°C to +90°CIndoor air temperature from +5°C to +32°C
SYSCOIL COMFORT Floor & Ceiling Fan Coil UnitsCooling and heating HOSPITALS
HHOTELSOFFICES
ErP2018
BIM models available at www.magicad.com
WRC remote control
(accessory)
SHOPS PUBLIC TRANSPORT
SCHOOLS
SRC **
New mini BMS New
New Electronic controllersT-Control POD **
New
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
Advantages
Silent units New casing design for an increased robustness Universal units for either vertical or horizontal installation Harmonious and aesthetic RAL 9003 painted cabinet Valves, condensate drain pan and drain pump factory
mounted 100% factory tested Eurovent certified
0,7-8,1 kW 0,7-10,3 kW
95-1.397 m3/h
New
New
systemair 129
FAN
COIL
UNI
TS
Technical features
* Fan standard factory set speeds
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 The sound pressure levels are based on (NR) characteristics of a room having volume of 100 m3 with reverberation of 0,5 seconds.5 Pressure loss by corresponding nominal flow.
SYSCOIL COMFORTSCC10 SCC20 SCC30 SCC40 SCC50 SCC60 SCC70 SCC80
S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 *
Capacities - 2 pipes
Cooling 1
Total cooling capacity kW 0,72/1,00/1,45 0,74/1,24/1,68 1,00/1,98/2,50 1,20/2,40/3,18 1,72/3,16/4,63 2,71/4,55/5,82 3,41/6,14/7,27 4,63/6,08/8,13
Sensible capacity kW 0,53/0,77/1,05 0,55/0,93/1,30 0,82/1,52/1,90 0,87/1,75/2,34 1,24/2,23/3,27 1,90/3,30/4,47 2,37/4,32/5,10 3,41/4,57/6,29
Water flow l/h 124/172/250 127/213/289 172/341/430 206/413/547 296/544/798 466/784/1003 587/1058/1252 798/1048/1400
Water pressure drop5 kPa 10,7/19,5/39,2 1,8/3,9/6,3 6,3/19,3/28,8 5,4/17,1/28 7,5/22,8/46,9 13,9/37,4/60,2 4,8/15,4/21,5 11,9/19,3/32,5
Heating 2 Heating capacity kW 0,73/1,18/1,71 0,76/1,26/1,86 1,05/1,96/2,62 1,21/2,39/3,35 1,72/3,46/4,81 2,58/4,44/5,93 3,63/6,59/7,80 4,95/6,80/9,90
Capacities - 4 pipes
Cooling 1
Total cooling capacity kW 0,66/0,92/1,30 0,63/1,12/1,56 0,96/1,90/2,40 1,13/2,25/3,00 1,65/3,03/4,34 2,60/4,39/5,61 3,34/5,92/6,93 4,50/5,92/8,01
Sensible capacity kW 0,48/0,70/0,96 0,47/0,84/1,20 0,79/1,46/1,83 0,82/1,65/2,21 1,19/2,15/3,07 1,82/3,18/4,28 2,33/4,16/4,87 3,30/4,44/6,19
Water flow l/h 114/159/225 109/192/268 165/327/414 194/388/517 284/522/748 449/756/967 575/1019/1193 775/1020/1380
Water pressure drop5 kPa 8,3/15,2/29 1,5/3,4/5,6 3/9,5/14,4 7,2/22,3/36,8 4,2/12,8/25,1 10,3/27,7/44,5 5,9/17,9/24,4 19,3/31,1/53,6
Heating 3
Heating capacity kW 0,66/1,05/1,49 0,78/1,24/1,60 1,34/1,91/2,24 1,36/2,32/3,00 2,11/3,36/4,30 2,71/4,24/5,33 3,84/5,26/6,21 5,66/8,06/10,30
Water flow l/h 57/90/128 37/106/137 116/165/193 117/200/259 182/290/370 234/365/459 331/453/535 487/685/888
Water pressure drop5 kPa 1,2/2,2/3,5 1/1,7/2,8 3/5,2/6,6 6/15,1/24,1 6,2/13,8/21,3 11,7/24,7/37 38,6/66,3/89 18,7/35,1/54,8
Sound Levels - 2 pipesSound power level dB(A) 33/40/49 31/43/50 30/45/52 30/44/51 34/46/56 38/51/58 43/56/61 50/55/64
Sound pressure level 4 dB(A) 24/31/40 22/34/41 21/36/43 21/35/42 25/37/47 29/42/49 34/47/52 41/46/55
NR 4 19/26/35 17/29/36 16/31/38 16/30/37 20/32/42 24/37/44 29/42/47 36/41/50
Sound Levels - 4 pipes
Sound power level dB(A) 33/40/49 31/43/50 30/45/52 30/44/51 34/46/56 38/51/58 43/56/61 50/55/64
Sound pressure level 4 dB(A) 24/31/40 22/34/41 21/36/43 21/35/42 25/37/47 29/42/49 34/47/52 41/46/55
NR 4 19/26/35 17/29/36 16/31/38 16/30/37 20/32/42 24/37/44 29/42/47 36/41/50
Ventilation
Number of fan(s) 1 1 1 2 2 2 2 3
Airflow - 2 pipes m³/h 111/190/283 105/179/265 138/274/390 173/357/499 253/486/716 350/640/933 480/893/1064 660/936/1397
Airflow - 4 pipes m³/h 95/168/253 89/161/241 132/263/369 162/335/467 242/466/671 334/614/885 470/859/1012 634/905/1370
Filter G2
Electrical Data
Power supply V/Ph/Hz 230/1/50 - 230/1/60
Consumption - 2 pipes W 13/24/36 10/18/29 16/37/45 15/37/56 28/55/72 37/75/105 53/100/147 90/112/188
Consumption - 4 pipes W 13/24/36 10/18/28 16/37/44 15/37/55 28/54/70 37/74/104 53/99/145 90/112/188
Electric heater W 500 500 500/1000 1250/2500 1250/2500 1250/2500 1250/2500 1250/2500
Water ConnectionsType Gas female threaded
2 pipes or 4 pipes “cooling” inch 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 3/4" 3/4"
4 pipes “heating” inch 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2” 1/2”
DimensionsWith cabinet - without feet (LxWxH) mm 766x225x477 766x225x477 951x225x477 1136x225x477 1321x225x477 1506x225x477 1319x225x575 1506x225x575
Without cabinet (LxWxH) mm 570x220x430 570x220x430 753x220x430 938x220x430 1122x220x430 1307x220x430 1121x220x530 1316x220x530
WeightWith cabinet - 2 pipes versions kg 19 19 22 27 30 35 35 47
With cabinet - 4 pipes versions kg 20 20 23 29 32 37 37 49
Without cabinet - 2 pipes versions kg 13 13 15 20 22 26 27 38
Without cabinet - 4 pipes versions kg 14 14 16 22 24 28 29 40
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
130 systemair
The range at a glance 8 sizes Low energy consumption EC fan(s) : 100% controllable
via a 0-10V signal or 3 operating speeds Cooling Capacities from 0,5 to 9,6 kW Heating Capacities from 0,6 to 13,6 kW Airflow from 91 to 1.548 m3/h Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Configuration: Universal installation units (vertical
or horizontal) with or without cabinet Left or Right water connections Many air inlet / outlet configurations G2 air filter (G3 as an accessory)
Accessories & Options2-way or 3-way valves4 pipes kit (additional coil)
Circuit breakersCustomer markDrain pumpEcospeed card for EC fans **Electric heaters (from 500W to 2500W)
Feet with/without gridFuse holdersG3 filterHorizontal or vertical drain guard (with valve)
Individual packagingMany air inlet/oulet configurationsMechanical sensor for automatic change overModbus communication board for SYSLOGIC **MRC/WRC/BRC : remote controls for SYSLOGIC **Other speeds configuration (Standard factory set speeds in “Technical features” table)
SRC - Smart Remote Control (Mini BMS) **Suspension kitSYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controllers (other electromechanical or electronic control systems also available) **
Operating limitsSYSCOIL COMFORT ECEntering water temperature (without glycol) from +5°C to +90°CIndoor air temperature from +5°C to +32°C
SYSCOIL COMFORT ECFloor & Ceiling Fan Coil UnitsCooling and heating
ErP2018
WRC remote control
(accessory)
EC fan(s)
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
SRC **
New mini BMS New
New Electronic controllersT-Control POD **
New
Advantages
Excellent performances → FCEER & FCCOP up to Low energy consumption EC fan(s) Silent units New casing design for an increased robustness Universal units for either vertical or horizontal installation Harmonious and aesthetic RAL 9003 painted cabinet Valves, condensate drain pan and drain pump factory
mounted 100% factory tested Eurovent certified
0,5-9,6 kW 0,6-13,6 kW
91-1.548 m3/h
Energy efficiency class
SYSCOIL COMFORT EC SCC10 SCC20 SCC30 SCC40 SCC50 SCC60 SCC70 SCC80
2 pipesFCEER B B B A A A B B
FCCOP C C B B A B B B
4 pipesFCEER C C B A A B B A
FCCOP C C B A A B B A
BC
AB B B A A B B
C
C
C
C
C
B
B
B
A
A
A
A
A
B
B
B
B
B
B
B
A
A
New
New
A
According to Eurovent
systemair 131
FAN
COIL
UNI
TS
BIM models available at
www.magicad.com
Technical features
* Fan standard factory set speeds (Voltage)
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 The sound pressure levels are based on (NR) characteristics of a room having volume of 100 m3 with reverberation of 0,5 seconds.5 Pressure loss by corresponding nominal flow.
SYSCOIL COMFORT ECSCC10 EC SCC20 EC SCC30 EC SCC40 EC SCC50 EC SCC60 EC SCC70 EC SCC80 EC
2V / 5V / 10V * 2V / 5V / 10V * 2V / 6V / 10V * 2V / 5V / 10V * 2V / 7V / 10V * 2V / 7V / 10V * 4V / 8V / 10V * 3V /4,1V / 6,4V *
Capacities - 2 pipes
Cooling 1
Total cooling capacity kW 0,62/1,22/2,07 0,64/1,38/2,36 0,86/2,06/3,09 1,34/2,94/4,19 1,34/3,97/4,98 1,98/4,45/5,24 2,69/5,85/6,90 5,10/6,45/8,80
Sensible capacity kW 0,51/1,05/1,85 0,49/1,12/1,91 0,64/1,61/2,40 0,95/2,10/3,00 1,05/3,00/3,70 1,35/3,51/4,02 2,01/4,31/5,22 3,69/4,75/6,61
Water flow l/h 107/210/356 110/237/406 148/354/532 230/506/722 231/685/858 341/767/903 463/1008/1189 879/1111/1516
Water pressure drop5 kPa 8,2/28,2/76,9 1,5/4,6/11 5/20,5/42,1 6,4/24,4/46,3 4,9/35,1/53,9 7,7/35,8/49,1 3/14/19,4 14,1/21,4/37,6
Heating 2 Heating capacity kW 0,71/1,37/2,43 0,71/1,61/2,80 0,84/1,81/2,80 1,11/2,48/4,46 1,38/4,35/5,19 1,95/4,93/5,82 3,21/6,12/7,55 5,15/6,73/9,77
Capacities - 4 pipes
Cooling 1
Total cooling capacity kW 0,53/1,07/1,90 0,56/1,19/2,18 0,75/1,86/2,86 1,02/2,28/3,40 1,23/3,63/4,62 1,78/4,11/4,94 2,57/5,14/6,38 4,96/6,21/9,55
Sensible capacity kW 0,43/0,92/1,69 0,43/0,96/1,76 0,55/1,45/2,23 0,74/1,65/2,46 0,97/2,75/3,45 1,18/3,21/3,83 1,93/3,80/4,77 3,58/4,57/7,21
Water flow l/h 92/185/327 97/206/375 129/321/493 205/457/681 212/625/796 306/707/851 443/886/1099 855/1070/1644
Water pressure drop5 kPa 5,7/20,1/59,2 1,3/3,7/9,7 3,4/9,2/19,7 7,9/29,6/60,1 2,5/17,9/28,2 5/24,3/34,8 3,5/13,6/20,8 22,8/33,9/73,9
Heating 3
Heating capacity kW 0,64/1,19/1,97 0,78/1,33/2,09 1,43/2,03/2,56 1,52/2,61/3,60 2,30/3,51/4,31 1,91/4,26/5,07 3,63/4,92/5,82 6,42/8,47/13,60
Water flow l/h 55/103/170 68/115/180 123/175/221 147/253/349 198/302/372 164/367/436 313/423/502 553/729/1170
Water pressure drop5 kPa 1,2/2,6/5,2 <1/2,0/4,8 7,4/5,7/8,3 8,9/23,1/41,6 7,1/14,8/21,5 6,6/25/33,8 35,2/58,8/79,5 23,3/38,2/91,5
Sound Levels - 2 pipesSound power level dB(A) 34/47/60 34/47/60 31/50/59 29/44/56 30/51/57 32/54/58 40/54/59 51/56/64
Sound pressure level 4 dB(A) 25/38/51 25/38/51 22/41/50 20/35/43 21/42/48 23/45/49 31/45/50 42/47/55
NR 4 20/33/46 20/33/46 17/36/45 <16/30/38 16/37/43 18/40/44 26/40/45 37/42/50
Sound Levels - 4 pipes
Sound power level dB(A) 34/47/60 34/47/60 31/50/59 29/44/52 30/51/57 32/54/58 40/54/59 51/56/64
Sound pressure level 4 dB(A) 25/38/51 25/38/51 22/41/50 20/35/43 31/42/48 23/45/49 31/45/50 42/47/55
NR 4 20/33/46 20/33/46 17/36/45 <16/30/38 <16/37/43 18/40/44 26/40/45 37/42/50
Ventilation
Number of fan(s) 1 1 1 2 2 2 2 3
Airflow - 2 pipes m³/h 108/228/417 98/234/413 145/380/585 170/412/678 203/645/816 245/737/912 350/850/1050 685/927/1398
Airflow - 4 pipes m³/h 91/199/379 84/200/380 123/342/540 148/298/524 185/587/755 205/668/845 329/798/989 660/884/1548
Filter G2
Electrical Data
Power supply V/Ph/Hz 230/1/50 - 230/1/60
Consumption - 2 pipes W 5/11/41 5/13/41 4/16/42 2/13/43 2/24/46 2/30/54 11/44/77 23/42/108
Consumption - 4 pipes W 5/11/39 5/13/40 6/15/40 2/12/42 2/23/44 2/28/52 11/43/75 22/41/116
Electric heater W 500 500 500/1000 1250/2500 1250/2500 1250/2500 1250/2500 1250/2500
Water ConnectionsType Gas female threaded
2 pipes or 4 pipes “cooling” inch 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 3/4" 3/4"
4 pipes “heating” inch 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2” 1/2”
DimensionsWith cabinet - without feet (LxWxH) mm 766x225x477 766x225x477 951x225x477 1136x225x477 1321x225x477 1506x225x477 1319x225x575 1506x225x575
Without cabinet (LxWxH) mm 570x220x430 570x220x430 753x220x430 938x220x430 1122x220x430 1307x220x430 1121x220x530 1316x220x530
WeightWith cabinet - 2 pipes versions kg 19 19 22 27 30 35 35 47
With cabinet - 4 pipes versions kg 20 20 23 29 32 37 37 49
Without cabinet - 2 pipes versions kg 13 13 15 20 22 26 27 38
Without cabinet - 4 pipes versions kg 14 14 16 22 24 28 29 40
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
132 systemair
The range at a glance 6 sizes 3-speed AC fan Cooling Capacities from 1,3 to 8,6 kW Heating Capacities from 1,1 to 12,8 kW Airflow from 360 to 1.447 m3/h
Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Integrated condensate drain pump G1 cleanable air filter
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281 (a) from SQ20 to SQ40 with IRYS COANDA diffusers** see pages 144-145 for more details
SYSQUAREEntering water temperature (without glycol) from +2°C to +80°CIndoor air temperature from +5°C to +32°C
WRC remote control(accessory)
Operating limits
SYSQUARECassette Fan Coil UnitsCooling and heating
1,3-8,6 kW 1,1-12,8 kW
360-1.447 m3/h
ErP2018
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS
Coanda effect measurements taken in our SYSTEMAIR development center.
IRYS COANDA diffusers
IRYS COANDA 180180° air diffusion
IRYS COANDA 360360° air diffusion
For a unique design & a strong coanda effect
SRC **
New mini BMS New
Advantages
Aesthetic and design IRYS COANDA diffusers with strong coanda effect
Silent units Easy installation & maintenance → all connections on the
same side. Electrical box and valves outside of the unit Low built-in-height Perfect integration into standard 600x600 ceiling tiles (a)
Valves and drain pump factory mounted Eurovent certified
Accessories & Options2 way or 3 way valvesAuxiliary drain panElectric heaters (from 1500W to 3000W)
Fresh air intakeIRC : Infrared remote control for SYSLOGIC **Modbus communication board for SYSLOGIC **Plastic or metallic (IRYS COANDA) diffusers (mandatory)SRC - Smart Remote Control (Mini BMS) **SYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controllers (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
New
New
New Electronic controllersT-Control POD **
New
systemair 133
FAN
COIL
UNI
TS
SYSQUARESQ20 SQ30 SQ40 SQ50 SQ60 SQ70
R3 / R2 / R1 * R3 / R2 / R1 * R3 / R2 / R1 * R3 / R2 / R1 * R3 / R2 / R1 * R3 / R2 / R1 *
Capacities - 2 pipes
Cooling 1
Total cooling capacity kW 1,54/1,76/2,36 1,87/2,87/3,99 2,78/3,49/4,69 3,35/4,43/6,07 3,69/5,46/7,18 4,04/6,48/8,61Sensible capacity kW 1,29/1,48/1,98 1,41/2,17/3,04 2,08/2,67/3,62 2,52/3,35/4,47 2,67/4,06/5,42 2,97/4,85/6,34Water flow l/h 265/303/404 323/493/683 478/597/801 576/762/1042 636/937/1233 695/1111/1476Water pressure drop kPa 4,0/5,0/10,0 3,0/7,0/14,0 6,0/10,0/18,0 7,0/12,0/22,0 3,0/6,0/11,0 5,0/12,0/20,0
Heating 2 Heating capacity kW 1,92/2,17/2,74 1,94/3,15/3,68 3,16/3,92/5,28 3,80/5,08/6,84 3,85/6,26/8,51 4,38/7,95/10,28Capacities - 4 pipes
Cooling 1
Total cooling capacity kW 1,29/1,48/1,97 1,99/2,68/3,37 2,55/3,21/4,00 - 2,97/4,96/6,63 3,17/6,01/7,55Sensible capacity kW 1,18/1,38/1,84 1,49/2,07/2,65 2,03/2,58/3,30 - 2,23/3,77/5,06 2,38/4,68/5,95Water flow l/h 232/258/359 342/465/576 437/563/683 - 511/851/1137 543/1030/1294Water pressure drop kPa 6,0/8,0/13,0 4,0/7,0/11,0 6,0/10,0/15,0 - 5,0/14,0/24,0 6,0/20,0/30,0
Heating 3
Heating capacity kW 1,09/1,27/1,67 3,10/4,40/5,46 4,32/5,00/5,80 - 5,28/7,79/10,04 6,43/10,07/12,77Water flow l/h 94/109/144 267/379/470 372/431/500 - 455/671/865 554/867/1100Water pressure drop kPa 15,0/17,0/28,0 7,0/13,0/20,0 13,0/17,0/23,0 - 4,0/7,0/11,0 5,0/11,0/16,0
Sound Levels - 2 pipesSound power level dB(A) 38/42/49 35/47/53 42/48/57 35/40/49 38/46/54 40/52/59Sound pressure level 4 dB(A) 27/31/40 26/35/44 33/39/48 26/31/40 29/37/45 31/43/50NR 4 23/27/35 20/30/39 28/34/43 21/26/35 22/32/40 25/38/50Sound Levels - 4 pipesSound power level dB(A) 37/41/49 35/47/53 42/48/57 - 38/46/54 40/52/59Sound pressure level 4 dB(A) 27/31/40 26/35/44 33/39/48 - 29/37/45 31/43/50NR 4 23/27/35 20/30/39 28/34/43 - 22/32/40 25/38/45
Ventilation
Number of fan 1Airflow m³/h 360/450/659 320/504/734 486/626/900 529/720/979 500/824/1159 601/1080/1447Filter G1Electrical Data
Power supply V/Ph/Hz 230/1/50 - 230/1/60
Consumption- 2 pipes W 25/35/58 17/34/58 38/58/99 28/41/66 34/61/88 44/92/125Consumption - 4 pipes W 25/35/58 17/34/58 38/58/99 - 34/61/88 44/92/125Electric heater W 1500 2500 2500 2x1500 2x1500 2x1500 Water ConnectionsType Gas female threaded2 pipes or 4 pipes “cooling” inch 3/4’’ 3/4’’ 3/4’’ 1’’ 1’’ 1’’4 pipes “heating” inch 1/2’’ 1/2’’ 1/2’’ - 3/4’’ 3/4’’Weight and DimensionsWeight kg 14,8 16,5 16,5 37,1 37,1 39,6
Dimensions - LxWxH(with metallic diffuser)
IRYS COANDA 180 mm 595x595x353 595x595x353 595x595x353 849x849x366 849x849x366 849x849x366IRYS COANDA 360 mm 595x595x341 595x595x341 595x595x341 849x849x358 849x849x358 849x849x358
Dimensions - LxWxH(with plastic diffuser) mm 720x720x334 720x720x334 720x720x334 960x960x339 960x960x339 960x960x339
Technical features
* Fan speeds
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 Information data considering an hypothetical sound attenuation of the room and installation of -9 dB(A).
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
134 systemair
The range at a glance 6 sizes Low energy consumption EC fan: 100% controllable
via a 0-10V signal or 3 operating speeds Cooling Capacities from 1,3 to 9,6 kW Heating Capacities from 1,1 to 14,0 kW Airflow from 360 to 1.598 m3/h
Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Integrated condensate drain pump G1 cleanable air filter
WRC remote control(accessory)
SYSQUARE ECCassette Fan Coil UnitsCooling and heating
1,3-9,6 kW 1,1-14,0 kW
360-1.598 m3/h
ErP2018
EC fan
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS
SYSQUARE ECEntering water temperature (without glycol) from +2°C to +80°CIndoor air temperature from +5°C to +32°C
Operating limits
Coanda effect measurements taken in our SYSTEMAIR development center.
IRYS COANDA diffusers
IRYS COANDA 180180° air diffusion
IRYS COANDA 360360° air diffusion
For a unique design & a strong coanda effect
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281(a) from SQ20 EC to SQ40 EC with IRYS COANDA diffusers** see pages 144-145 for more details
Advantages
Excellent performances → FCEER & FCCOP up to Low energy consumption EC fan Aesthetic and design diffusers with strong coanda effect Silent units Easy installation & maintenance → all connections on the
same side. Electrical box and valves outside of the unit Low built-in-height Perfect integration into standard 600x600 ceiling tiles (a)
Valves and drain pump factory mounted Eurovent certified
Accessories & Options2 way or 3 way valvesAuxiliary drain panEcospeed card for EC fans **Electric heaters (from 1500W to 3000W)
Fresh air intakeIRC : Infrared remote control for SYSLOGIC **Modbus communication board for SYSLOGIC **Plastic or metallic (IRYS COANDA) diffusers (mandatory)SRC - Smart Remote Control (Mini BMS) **SYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controllers (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
New
New
Energy efficiency class
SYSQUARE EC SQ20 SQ30 SQ40 SQ50 SQ60 SQ70
2 pipesFCEERFCCOP
4 pipesFCEER /FCCOP /
A
C
B
B
B
B
A
A
B
B
B
B
A
A
A
A
A
A B
B
A
A
A
According to Eurovent
New mini BMS SRC **
New Electronic controllersT-Control POD **
NewNew
systemair 135
FAN
COIL
UNI
TS
Technical features
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 Information data considering an hypothetical sound attenuation of the room and installation of -9 dB(A).
SYSQUARE ECSQ20 EC SQ30 EC SQ40 EC SQ50 EC SQ60 EC SQ70 EC
2V / 6V / 10V * 2V / 6V / 10V * 2V / 6V / 10V * 2V / 6V / 10V * 2V / 6V / 10V * 2V / 6V / 10V *
Capacities - 2 pipes
Cooling 1
Total cooling capacity kW 1,55/1,77/2,38 1,88/2,88/4,00 2,79/3,51/4,71 3,36/4,44/6,09 3,71/5,48/7,20 4,05/6,51/9,61Sensible capacity kW 1,30/1,49/2,00 1,42/2,18/3,05 2,09/2,69/3,64 2,53/3,36/4,49 2,69/4,08/5,44 2,98/4,88/7,21Water flow l/h 267/306/409 325/497/688 481/604/808 579/765/1050 640/944/1243 700/1119/1649Water pressure drop kPa 4,0/5,0/10,0 3,0/7,0/14,0 6,0/10,0/18,0 7,0/12,0/22,0 3,0/6,0/11,0 5,0/12,0/25,0
Heating 2 Heating capacity kW 1,92/2,17/2,74 1,94/3,15/3,68 3,16/3,92/5,28 3,80/5,08/6,84 3,85/6,26/8,51 4,38/7,95/11,03Capacities - 4 pipes
Cooling 1
Total cooling capacity kW 1,30/1,49/1,99 2,00/2,69/3,38 2,56/3,23/4,02 - 2,99/4,98/6,65 3,18/6,04/7,97Sensible capacity kW 1,19/1,39/1,86 1,50/2,08/2,66 2,04/2,60/3,32 - 2,25/3,79/5,08 2,39/4,71/6,34Water flow l/h 234/262/344 344/464/581 442/556/690 - 516/858/1144 549/1041/1366Water pressure drop kPa 6,0/8,0/13,0 4,0/7,0/11,0 6,0/10,0/15,0 - 5,0/14,0/24,0 6,0/20,0/33,0
Heating 3
Heating capacity kW 1,09/1,27/1,67 3,10/4,40/5,46 4,32/5,00/5,80 - 5,28/7,79/10,00 6,43/10,67/13,99Water flow l/h 94/109/144 267/379/470 372/431/500 - 455/671/865 554/867/1205Water pressure drop kPa 13,0/17,0/28,0 7,0/13,0/20,0 13,0/17,0/23,0 - 4,0/7,0/11,0 5,0/11,0/19,0
Sound Levels - 2 pipesSound power level dB(A) 36/40/49 35/44/53 42/48/57 35/40/49 38/46/54 40/52/61Sound pressure level 4 dB(A) 27/31/40 26/35/44 33/39/48 26/31/40 29/37/45 31/43/50NR 4 23/27/35 20/30/39 28/34/43 21/26/35 22/32/40 25/38/45Sound Levels - 4 pipesSound power level dB(A) 36/40/49 35/44/53 42/48/57 - 38/46/54 40/52/61Sound pressure level 4 dB(A) 27/31/40 26/35/44 33/39/48 - 29/37/45 31/43/50NR 4 23/27/35 20/30/39 28/34/43 - 22/32/40 25/38/45
Ventilation
Number of fan 1Airflow m³/h 360/450/659 320/504/734 486/626/900 529/720/979 500/824/1159 601/1080/1598Filter G1Electrical Data
Power supply V/Ph/Hz 230/1/50 - 230/1/60
Consumption- 2 pipes W 9/13/29 7/14/33 13/23/57 7/12/25 9/23/45 11/40/115Consumption - 4 pipes W 9/13/29 7/14/32 13/22/57 - 9/23/45 11/40/115Electric heater W 1500 2500 2500 2x1500 2x1500 2x1500 Water ConnectionsType Gas female threaded2 pipes or 4 pipes “cooling” inch 3/4’’ 3/4’’ 3/4’’ 1’’ 1’’ 1’’4 pipes “heating” inch 1/2’’ 1/2’’ 1/2’’ - 3/4’’ 3/4’’Weight and DimensionsWeight kg 14,8 16,5 16,5 37,1 37,1 39,6
Dimensions - LxWxH(with metallic diffuser)
IRYS COANDA 180 mm 595x595x353 595x595x353 595x595x353 849x849x366 849x849x366 849x849x366IRYS COANDA 360 mm 595x595x341 595x595x341 595x595x341 849x849x358 849x849x358 849x849x358
Dimensions - LxWxH(with plastic diffuser) mm 720x720x334 720x720x334 720x720x334 960x960x339 960x960x339 960x960x339
* Fan standard factory set speeds (Voltage)
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
136 systemair
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
WRC remote control(accessory)
HAWAIRWall-mounted Fan Coil UnitsCooling and heating
0,9-3,9 kW 1,0-4,1 kW
150-850 m3/h
ErP2018
The range at a glance 4 sizes 3-speed AC fan Cooling Capacities from 0,9 to 3,9 kW Heating Capacities from 1,0 to 4,1 kW Airflow from 150 to 850 m3/h
Versions (2-Pipes) : - Infrared without valve (IR SV) - Infrared with valve (IR AV) - Terminal block without valve (TB SV) G1 cleanable air filter
HOSPITALS
HHOTELSOFFICES SHOPS
HAWAIR
Entering water temperature (without glycol) from +5°C to +60°C
Indoor air temperature from +6°C to +40°C
Operating limits
New mini BMS SRC **
Advantages
Reversible Aesthetic design Light for easy installation Silent units Very easy servicing through a removable front panel Cleanable synthetic-type air filter Eurovent certified
Accessories & Options2 way or 3 way valvesModbus communication board for SYSLOGIC **SRC - Smart Remote Control (Mini BMS) **SYSLOGIC controller (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
New
New
systemair 137
FAN
COIL
UNI
TS
Technical features
* Fan standard factory set speeds
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.
HAWAIR2-Pipes, without valve
HaWair 7 HaWair 9 HaWair 18 HaWair 22
S2 / S3 / S4 * S2 / S3 / S4 * S2 / S3 / S4 * S2 / S3 / S4 *
Capacities
Cooling 1
Total cooling capacity kW 1,00 / 1,34 / 1,67 1,57 / 1,69 / 2,43 2,81 / 2,95 / 3,54 2,92 / 3,11 / 3,89Sensible capacity kW 0,72 / 0,97 / 1,20 1,21 / 1,32 / 1,87 2,12 / 2,26 / 2,74 2,27 / 2,48 / 3,11Water flow l/h 172 / 231 / 287 270 / 291 / 418 483 / 508 / 609 502 / 535 / 669Water pressure drop kPa 18,5 / 24,9 / 30,9 25 / 27/ 40 38,1 / 41,3 / 55,6 31,1 / 33,7 / 45,2
Heating 2 Heating capacity W 1,42 / 1,62 / 1,72 1,57 / 1,88 / 2,53 2,73 / 3,01 / 3,69 2,91 / 3,49 / 4,07Sound levelsSound power level dB(A) 45 / 49 / 51 47 / 52 / 57 49 / 53 / 56 53 / 57 / 63Sound pressure level 3 dB(A) 30 / 33 / 35 32 / 36 / 40 39 / 41 / 43 39 / 43 / 48NR 3 32 / 36 / 38 34 / 39 / 44 40 / 43 / 46 43 / 46 / 50VentilationNumber of fan 1 1 1 1Airflow m³/h 282 / 321 / 360 367 / 413 / 551 532 / 592 / 680 617 / 709 / 850Filter G1Electrical dataPower supply V/Ph/Hz 230/1/50Consumption W 39 / 42 / 62 45 / 47 / 59 45 / 50 / 55 50 / 55 / 70Water connectionsType Gas female threadedConnections inch 1/2” 1/2” 1/2” 1/2”Dimensions and WeightDimensions (LxWxH) mm 845 x 180 x 275 845 x 180 x 275 940 x 200 x 298 940 x 200 x 298Weight kg 11 11 13 13
HAWAIR2-Pipes, with valve
HaWair 9 HaWair 22
S2 / S3 / S4 * S2 / S3 / S4 *
Capacities
Cooling 1
Total cooling capacity kW 0,92 / 1,16 / 1,25 2,01 / 2,31 / 2,75Sensible capacity kW 0,61 / 0,92 / 1,07 1,51 / 1,66 / 1,97Water flow l/h 158 / 200 / 215 346 / 397 / 473Water pressure drop kPa 30,8 / 39,4 / 42,6 29,7 / 35,5 / 44,8
Heating 2 Heating capacity W 1,04 / 1,22 / 1,57 2,23 / 2,56 / 3,01Sound levelsSound power level dB(A) 47 / 52 / 47 54 / 58 / 62Sound pressure level 3 dB(A) 32 / 36 / 40 39 / 43 / 48NR 3 27 / 31 / 37 34 / 37 / 41VentilationNumber of fan 1 1Airflow m³/h 150 / 250 / 400 290 / 400 / 600Filter G1Electrical dataPower supply V/Ph/Hz 230/1/50Consumption W 40 / 40 / 45 55 / 60 / 65Water connectionsType Gas female threadedConnections inch 1/2” 1/2”Dimensions and WeightDimensions (LxWxH) mm 845 x 180 x 275 940 x 200 x 298Weight kg 11 13
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
138 systemair
Operating limits
WRC remote control(accessory)
DUCTYSMedium static pressureductable Fan Coil UnitsCooling and heating
0,6-6,7 kW 0,4-7,1kW
44-1.293 m3/h EC fan
The range at a glance 5 sizes Low energy consumption EC fan: 100% controllable
via a 0-10V signal or 3 operating speeds Cooling Capacities from 0,6 to 6,7 kW Heating Capacities from 0,4 to 7,1 kW Airflow from 44 to 1.293 m3/h
Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Static pressure up to 100 Pa Many air inlet / outlet configurations (a)
Left or Right water / electric connections
(a) Air inlet / outlet configurations
Rectangular return and discharge (standard)
Rectangular return and circular discharge
Circular return and discharge
Circular return and discharge
I configurations J configuration
Circular return and discharge
L configuration
Circular return and discharge
U configuration
DUCTYSEntering water temperature (without glycol) from +5°C to +90°CIndoor air temperature from +5°C to +32°C
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS
Energy efficiency class
DUCTYS DUCTYS 10
DUCTYS 15
DUCTYS 20
DUCTYS 25
DUCTYS 40
2 pipesFCEERFCCOP
4 pipesFCEERFCCOP C
B
A
A
B
B
B
A
A
A
A
A
A
C
C
C B
A
B
A
According to Eurovent
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
Advantages
Excellent performances → FCEER & FCCOP up to Silent units → internal acoustic & thermal insulation Highly customizable → Many aeraulic configurations
+ selection of hydraulic & electric service side Low energy consumption EC fan Ease of installation → very low height (223mm) Available static pressure up to 100 Pa Easy maintenance → Direct access to the internal
components Monobloc drain pan 100% factory tested Eurovent certified
ErP2018
Accessories and options2 way or 3 way valvesCircuit breakersCondensate drain pumpEcospeed card for EC fans **Electric heaters (from 500W to 2500W)
Fresh air intakeFuse holderG2/G3 filterIndividual packagingMany air inlet / outlet configurations (a)
Mechanical sensor for automatic change overModbus communication board for SYSLOGIC **Other speeds configuration (Standard factory set speeds in “Technical features” table)
SRC - Smart Remote Control (Mini BMS)**Suspension kitSYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controller (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
New
New
A
New mini BMS SRC **
New Electronic controllersT-Control POD **
NewNew
systemair 139
FAN
COIL
UNI
TS
Technical features
DUCTYS I configuration with rect. return & dischargeand G2 (DT15/DT20/DT25) or G3 (DT10/DT40) filter
DUCTYS 10 DUCTYS 15 DUCTYS 20 DUCTYS 25 DUCTYS 40
2V / 7,35V / 10V * 3,8V / 6,05V / 8,2V * 4,8V / 7,15V / 8,9V * 3,1V / 3,9V / 4,85V * 2,1V / 5,5V / 10V *
Capacities - 2 Pipes
Cooling 1
Total cooling capacity kW 0,6 / 0,83 / 0,94 1,39 / 1,88 / 2,06 1,83 / 2,42 / 2,74 2,42 / 2,77 / 3,2 2,4 / 4,94 / 6,66Sensible capacity kW 0,58 / 0,77 / 0,87 1,16 / 1,6 / 1,96 1,46 / 1,92 / 2,21 1,96 / 2,24 / 2,63 1,8 / 4,1 / 6,13Water flow l/h 104 / 143 / 162 239 / 324 / 355 315 / 416 / 472 416 / 477 / 551 413 / 851 / 1148Water pressure drop kPa 1,9 / 3,0 / 3,7 6,1 / 9,3 / 10,5 9,5 / 15,5 / 19,5 15,9 / 20,5 / 26,8 8,2 / 29,7 / 51,7
Heating 2 Heating capacity kW 0,35 / 0,70 / 0,88 1,45 / 2,07 / 2,55 2,07 / 2,47 / 2,59 2,58 / 3,02 / 3,39 2,4 / 5,1 / 7,06
Capacities - 4 Pipes
Cooling 1
Total cooling capacity kW 0,59 / 0,80 / 0,91 1,34 / 1,78 / 2,18 1,78 / 2,38 / 2,74 2,19 / 2,69 / 2,94 2,22 / 4,76 / 6,37Sensible capacity kW 0,57 / 0,74 / 0,83 1,11 / 1,52 / 1,73 1,42 / 1,9 / 2,22 1,73 / 2,16 / 2,39 1,77 / 4,02 / 5,63Water flow l/h 101 / 137 / 156 231 / 306 / 375 306 / 410 / 472 377 / 463 / 506 382 / 821 / 1097Water pressure drop kPa 1,9 / 2,9 / 3,5 5,8 / 8,5 / 11,4 9,1 / 15,1 / 19,5 13,3 / 19,4 / 22,9 7,2 / 27,8 / 47,5
Heating 3
Heating capacity kW 0,45 / 0,78 / 0,95 1,79 / 2,54 / 2,88 2,6 / 3,02 / 3,12 3,16 / 3,59 / 4,03 2,64 / 5,05 / 6,61Water flow l/h 39 / 67 / 82 154 / 219 / 248 224 / 260 / 269 308 / 344 / 385 227 / 435 / 569Water pressure drop kPa <1 / 1,7 / 2,2 4 / 7,5 / 9,4 7,3 / 10,9 / 11,9 11,5 / 14,9 / 18,9 3,5 / 37,3 / 68,9
Sound levels - 2 PipesSound power Return + Radiated 4 dB(A) 29 / 52 / 55 44 / 55 / 60 46 / 57 / 61 50 / 55 / 61 42 / 58 / 68Sound power Discharge 4 dB(A) 27 / 51 / 55 41 / 52 / 58 50 / 57 / 61 50 / 56 / 61 34 / 57 / 70Sound pressure 5 dB(A) <16 / 35 / 38 26 / 37 / 42 31 / 40 / 44 33 / 39 / 44 23 / 39 / 52NR 5 <16 / 30 / 33 21 / 32 / 37 26 / 35 / 39 28 / 34 / 39 18 / 34 / 47Sound levels - 4 PipesSound power Return + Radiated 4 dB(A) 31 / 52 / 55 44 / 55 / 60 50 / 57 / 61 50 / 55 / 61 43 / 58 / 68Sound power Discharge 4 dB(A) 31 / 51 / 55 41 / 52 / 58 46 / 57 / 61 50 / 56 / 61 38 / 54 / 70Sound pressure 5 dB(A) <16 / 35 / 38 26 / 37 / 42 31 / 40 / 44 33 / 39 / 44 24 / 39 / 52NR 5 <16 / 30 / 33 21 / 32 / 37 26 / 35 / 39 28 / 34 / 39 19 / 34 / 47VentilationNumber of fan 1Airflow - 2 Pipes 4 m³/h 48 / 123 / 161 255 / 383 / 491 360 / 501 / 599 448 / 541 / 642 347 / 848 / 1293Airflow - 4 Pipes 4 m³/h 44 / 112 / 147 228 / 351 / 452 331 / 467 / 560 413 / 503 / 602 319 / 802 / 1228External static pressure - 2 pipes Pa 7,6/50/85,7 22/50/82 26/50/72 34/50/70 8/50/116External static pressure - 4 pipes Pa 7,7/50/86,1 21/50/83 25/50/72 34/50/72 8/50/117Electrical dataPower supply V/Ph/Hz 230/1/50 - 230/1/60Consumption - 2 Pipes W 7 / 16 / 29 11 / 29 / 56 19 / 50 / 70 25 / 41 / 64 10 / 62 / 197Consumption - 4 Pipes W 7 / 16 / 29 10 / 28 / 53 18 / 47 / 67 26 / 41 / 69 10 / 60 / 188Electric heater W 500 600 / 1000 600 / 1000 1000 / 2000 1250 / 2500Water connectionsType Gas Female threaded2 pipes or 4 pipes “cooling” inch 1/2" 1/2" 1/2" 1/2" 3/4"4 pipes “heating” inch 1/2" 1/2" 1/2" 1/2" 1/2"Dimensions and WeightDimensions without drain pan (LxWxH) mm 633 x 631 x 223 733 x 631 x 223 833 x 631 x 223 933 x 631 x 223 1233 x 653 x 223
Weight kg 14 16 18 20 19
* Fan standard factory set speeds (Voltage)
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 According to Eurovent 6/10 (Airflow test method) and 8/12 (Sound test method).5 Informative data, considering an hypothetical sound attenuation of the room and installation of 20 dB. Please add 2dB for a non-ducted configuration.
BIM models available at www.magicad.com
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
140 systemair
VHEntering water temperature (without glycol) from +5°C to +90°CIndoor air temperature from +5°C to +32°C
WRC remote control(accessory)
VHHigh static pressureductable Fan Coil UnitsCooling and heating
4,1-26,4 kW 4,7-29,6 kW
586-3.736 m3/h
ErP2018 Accessories and options
2 way or 3 way valvesAuxiliary drain panCircuit breakersCondensate drain pumpDouble skin acoustic insulationElectric heaters (from 1000W to 3000W)
Fresh air intakeFuse holder
G3/G4 filter
Individual packagingMechanical sensor for automatic change overModbus communication board for SYSLOGIC **Other speeds configuration (Standard factory set speeds in “Technical features” table)
SRC - Smart Remote Control (Mini BMS) **Suspension kitSYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controller (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
The range at a glance 6 sizes Cooling Capacities from 4,1 to 26,4 kW Heating Capacities from 4,7 to 29,6 kW Airflow from 586 to 3.736 m3/h Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes 5 or 4-speed AC fan - Standard factory set speeds:
VH07/15/18/21 -> S1,S3,S5 (5-speed fan motor) VH24/27 -> S1,S2,S3 (4-speed fan motor) High available static pressure up to 220 Pa Left or Right water / electric connections
Operating limits
SRC **
New mini BMS New
New Electronic controllersT-Control POD **
New
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
Advantages
Very low acoustic level at low speed (double skin insulation available as an accessory)
Selection of hydraulic & electric service side Available static pressure up to 220 Pa Ease of installation and maintenance 100% factory tested Eurovent certified
New
New
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS SHOPPING
CENTERSINDUSTRY
systemair 141
FAN
COIL
UNI
TS
Technical features
VHI Configuration with Circular return and discharge (3x Ø200) for VH07, Rectangular return and discharge from VH15 to VH27
VH07 VH15 VH18 VH21 VH24 VH27
S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S3 / S5 * S1 / S2 / S3 * S1 / S2 / S3 *
Capacities - 2 Pipes
Cooling 1
Total cooling capacity kW 4,43 / 5,32 / 5,59 6,90 / 11,48 / 13,33 6,32 / 11,48 / 13,87 7,07 / 13,7 / 17 14,78 / 16,67 / 19,03 16,4 / 18,9 / 21,9
Sensible capacity kW 3,14 / 3,97 / 4,25 5,04 / 9,19 / 11,23 4,94 / 9,48 / 11,89 4,93 / 9,94 / 12,5 10,68 / 12,27 / 14,23 11,4 / 13,3 / 15,5
Water flow l/h 762 / 915 / 962 1187 / 1979 / 2289 1087 / 1979 / 2391 1218 / 2357 / 2928 2546 / 2873 / 3268 2820 / 3250 / 3766
Water pressure drop kPa 27,4 / 39,2 / 43,5 7,9 / 19,8 / 26,1 6,8 / 19,6 / 27,6 8,5 / 28,7 / 43,5 14,7 / 18,3 / 23,3 13,6 / 17,6 / 23,0
Heating 2 Heating capacity kW 4,7 / 6,4 / 7,76 6,6 / 12 / 15,48 7,2 / 14 / 18,01 6,95 / 13,9 / 17,8 15 / 17,4 / 20,9 15,4 / 17,9 / 21,5
Capacities - 4 Pipes
Cooling 1
Total cooling capacity kW 4,05 / 4,84 / 5,08 6,38 / 10,08 / 11,33 6,77 / 11,18 / 12,83 7,75 / 14,38 / 17,43 13,68 / 15,27 / 17,13 14,78 / 16,77 / 19,13
Sensible capacity kW 2,86 / 3,57 / 3,8 4,76 / 8,42 / 10,13 5,01 / 9,13 / 11,13 5,45 / 10,58 / 13,23 10,18 / 11,67 / 13,33 10,68 / 12,27 / 14,23
Water flow l/h 697 / 833 / 874 1098 / 1739 / 1945 1165 / 1928 / 2203 1333 / 2478 / 2994 2357 / 2632 / 2942 2546 / 2890 / 3286
Water pressure drop kPa 31 / 43 / 47,2 5,8 / 13,3 / 16,9 6,9 / 17,1 / 22,6 11,1 / 34,9 / 50,9 15,3 / 18,8 / 23,3 13,5 / 17 / 21,5
Heating 3
Heating capacity kW 5,5 / 7 / 7,7 9,6 / 17 / 21 9,7 / 17,06 / 21 9,7 / 17,1 / 21 10,9 / 12,9 / 15,2 18,5 / 25 / 29,6
Water flow l/h 474 / 603 / 663 827 / 1464 / 1809 835 / 1473 / 1809 835 / 1473 / 1809 939 / 1111 / 1309 939 / 1111 / 1309
Water pressure drop kPa 9,0 / 13,3 / 15,0 32,7 / 92,1 / 134 20,2 / 56,1 / 80 20,2 / 56,1 / 80 30,8 / 39 / 49,5 38,8 / 67,2 / 82
Sound levels
Sound power Return + Radiated 4 dB(A) 54 / 60 / 63 52 / 66 / 72 54 / 66 / 74 52 / 66 / 72 65 / 69 / 73 65 / 69 / 73
Sound power Discharge 4 dB(A) 53 / 59 / 62 52 / 64 / 71 52 / 64 / 71 52 / 64 / 71 64 / 67 / 72 64 / 67 / 72
Sound pressure 5 dB(A) 33 / 39 / 42 31 / 45 / 51 31 / 45 / 51 31 / 45 / 51 44 / 48 / 52 44 / 48 / 52
NR 5 27 / 34 / 37 27 / 40 / 47 27 / 40 / 47 27 / 40 / 47 40 / 44 / 48 40 / 44 / 48
Ventilation
Number of fan 1
Filter G3
Airflow - 2 Pipes 4 m³/h 703 / 977 / 1125 960 / 2112 / 2830 960 / 2112 / 2830 960 / 2112 / 2830 2040 / 2413 / 2925 2040 / 2413 / 2925
Airflow - 4 Pipes 4 m³/h 586 / 824 / 974 960 / 2112 / 2830 960 / 2112 / 2830 960 / 2112 / 2830 2040 / 2413 / 2925 2040 / 2413 / 2925
External static pressure - 2 pipes Pa 26/50/67 11/50/91 11/50/91 11/50/91 35/50/74 35/50/74External static pressure - 4 pipes Pa 24/50/68 11/50/91 11/50/91 11/50/91 35/50/74 35/50/74
Electrical data
Power supply V/Ph/Hz 230/1/50 - 230/1/60Consumption W 132 / 182 / 222 180 / 421 / 675 180 / 421 / 675 180 / 421 / 675 420 / 530 / 673 420 / 530 / 673Electric heater W 2000 3000 3000 3000 3000 3000
Water connections
Type Gas Female threaded Gas Male threaded
2 pipes inch 1/2" 1" 1”1/4 1”1/4 1”1/4 1”1/4
4 pipes "cooling" inch 1/2” 1” 1” 1” 1”1/4 1”1/4
4 pipes "heating" inch 1/2" 3/4" 3/4" 3/4” 3/4” 3/4”
Dimensions
Rectangular return and discharge configuration (LxWxH) mm 1200 x 698 x 250 1380 x 798 x 375 1380 x 798 x 375 1380 x 798 x 375 1500 x 798 x 450 1500 x 798 x 450
Circular return and discharge configuration (LxWxH) mm 1200 x 1014 x 250 - - - - -
Weight
Rect. return and discharge configuration kg 42 63 65 67 76 80
Circ. return and discharge configuration kg 48 - - - - -
* Fan standard factory set speeds
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 According to Eurovent 6/10 (Airflow test method) and 8/12 (Sound test method).5 Informative data, considering an hypothetical sound attenuation of the room and installation of 21 dB.
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
142 systemair
EC fan
Energy efficiency class
VH EC VH15 EC VH18 EC VH21 EC VH24 EC VH27 EC
2 pipesFCEERFCCOP
4 pipesFCEERFCCOP
B
A
A
According to EuroventB
B
A
A
A
A
A
A
A
A
A
B
B
A
A
A
B
SRC **
New mini BMS New
New Electronic controllersT-Control POD **
NewVH ECEntering water temperature (without glycol) from +5°C to +90°CIndoor air temperature from +5°C to +32°C
VH ECHigh static pressureductable Fan Coil UnitsCooling and heating
3,2-21,9 kW 2,5-23,9 kW
320-3.568 m3/h
ErP2018 Accessories and options
2 way or 3 way valvesAuxiliary drain panCircuit breakersCondensate drain pumpDouble skin acoustic insulationEcospeed card for EC fans **Electric heaters (from 1000W to 3000W)
Fresh air intakeFuse holder
G3/G4 filter
Individual packagingMechanical sensor for automatic change overModbus communication board for SYSLOGIC **Other speeds configuration (Standard factory set speeds in “Technical features” table)
SRC - Smart Remote Control (Mini BMS) **Suspension kitSYSLOGIC controller (other electromechanical or electronic control systems also available) **T-CONTROL POD controller (other electromechanical or electronic control systems also available) **WRC : Wall mounted remote control for SYSLOGIC **
The range at a glance 6 sizes Cooling Capacities from 3,2 to 21,9 kW Heating Capacities from 2,5 to 23,9 kW Airflow from 320 to 3.568 m3/h Versions: 2-Pipes, 2-Pipes + electric heater, 4-Pipes Low energy consumption EC fan: 100% controllable
via a 0-10V signal or 3 operating speeds High available static pressure up to 220 Pa Left or Right water / electric connections
Operating limits
Advantages
Excellent performances → FCEER & FCCOP up to Low energy consumption EC fan Very low acoustic level at low speed
(double skin insulation available as an accessory)
Selection of hydraulic & electric service side Available static pressure up to 220 Pa Ease of installation and maintenance 100% factory tested Eurovent certified
WRC remote control(accessory)
A
New
New
HOSPITALS
HHOTELSOFFICES SHOPS PUBLIC
TRANSPORTSCHOOLS SHOPPING
CENTERSINDUSTRY
ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281** see pages 144-145 for more details
systemair 143
FAN
COIL
UNI
TS
Technical features
VH ECI Configuration with Rectangular return and discharge
VH07 EC VH15 EC VH18 EC VH21 EC VH24 EC VH27 EC
3,33V / 5,87V / 8,67V 2V / 4V / 5V * 2V / 4V / 5V * 2V / 4V / 5V * 2V / 5V / 7V * 2V / 5V / 7V *
Capacities - 2 Pipes
Cooling 1
Total cooling capacity kW 3,26 / 4,90 / 5,88 7,93 / 10,1 / 11,1 8,98 / 11,7 / 12,8 9,79 / 12,7 / 13,9 10,6 / 16,1 / 17,6 11,7 / 18,1 / 19,9
Sensible capacity kW 2,05 / 3,59 / 4,56 6,08 / 8,05 / 8,9 6,71 / 9,02 / 10 7,14 / 9,55 / 10,6 7,84 / 12,4 / 13,7 8,4 / 13,6 / 15,1
Water flow l/h 562 / 844 / 1013 1366 / 1744 / 1905 1547 / 2010 / 2207 1686 / 2182 / 2393 1825 / 2766 / 3024 2022 / 3120 / 3420
Water pressure drop kPa 15 / 33,5 / 48,1 13,2 / 19,8 / 23 9,1 / 14,2 / 16,7 10,2 / 15,4 / 17,9 8,0 / 18,4 / 21,4 7,6 / 19,1 / 22,5
Heating 2 Heating capacity kW 2,47 / 5,61 / 9,26 8,66 / 11,7 / 13 9,48 / 13,1 / 14,6 9,99 / 14,1 / 15,8 10,9 / 17,6 / 19,5 16,4 / 19,1 / 21,4
Capacities - 4 Pipes
Cooling 1
Total cooling capacity kW 3,22 / 4,74 / 5,54 6,57 / 8,21 / 8,91 7,4 / 9,26 / 10 8,92 / 11,3 / 12,4 9,51 / 14 / 15,2 10,2 / 15,3 / 16,8
Sensible capacity kW 2,12 / 3,48 / 4,25 5,2 / 6,76 / 7,43 5,7 / 7,48 / 8,24 6,66 / 8,75 / 9,64 7,13 / 11 / 12,1 7,52 / 11,8 / 13,1
Water flow l/h 555 / 817 / 954 1131 / 1415 / 1536 1275 / 1594 / 1730 1536 / 1952 / 2128 1638 / 2409 / 2624 1749 / 2641 / 2894
Water pressure drop kPa 20,6 / 41,4 / 55,3 6,6 / 10,2 / 12 8 / 11,2 / 12,7 11,2 / 16,7 / 19,4 9,4 / 18,7 / 21,9 6,6 / 13,9 / 16,4
Heating 3
Heating capacity kW 3,93 / 6,81 / 9,05 5,85 / 7,45 / 8,13 10 / 12,9 / 14,2 10 / 12,9 / 14,2 8 / 11,9 / 13 7,71 / 11,7 / 12,9
Water flow l/h 338 / 586 / 779 504 / 642 / 700 863 / 1112 / 1219 863 / 1112 / 1219 689 / 1026 / 1118 664 / 1010 / 1109
Water pressure drop kPa 5,6 / 12,5 / 19,5 14,1 / 21,4 / 25,0 23,0 / 35,0 / 40,9 22,8 / 34,8 / 40,8 13,5 / 27,5 / 32,1 5,2 / 11,3 / 13,4
Sound levels - 2 Pipes
Sound power Return + Radiated 4 dB(A) 54 / 60 / 63 56 / 65 / 67 56 / 65 / 67 56 / 65 / 67 58 / 69 / 73 58 / 69 / 73
Sound power Discharge 4 dB(A) 53 / 59 / 62 56 / 64 / 65 56 / 64 / 65 56 / 64 / 65 58 / 67 / 72 58 / 67 / 72
Sound pressure 5 dB(A) 33 / 39 / 42 35 / 44 / 46 35 / 44 / 46 35 / 44 / 46 37 / 48 / 52 37 / 48 / 52
NR 5 27 / 34 / 37 31 / 40 / 42 31 / 40 / 42 31 / 40 / 42 33 / 44 / 48 33 / 44 / 48
Sound levels - 4 Pipes
Sound power Return + Radiated 4 dB(A) 54 / 60 / 63 56 / 65 / 67 56 / 65 / 67 56 / 65 / 67 58 / 69 / 73 58 / 69 / 73
Sound power Discharge 4 dB(A) 53 / 59 / 62 56 / 64 / 65 56 / 64 / 65 56 / 64 / 65 58 / 67 / 72 58 / 67 / 72
Sound pressure 5 dB(A) 33 / 39 / 42 35 / 44 / 46 35 / 44 / 46 35 / 44 / 46 37 / 45 / 52 37 / 45 / 52
NR 5 27 / 34 / 37 31 / 40 / 42 31 / 40 / 42 31 / 40 / 42 33 / 44 / 48 33 / 44 / 48
Ventilation
Number of fan 1
Filter G3
Airflow - 2 Pipes 4 m³/h 347 / 849 / 1293 1360 / 2044 / 2335 1360 / 2044 / 2335 1360 / 2044 / 2335 1519 / 2700 / 3098 1519 / 2700 / 3098
Airflow - 4 Pipes 4 m³/h 320 / 803 / 1229 1360 / 2044 / 2335 1360 / 2044 / 2335 1360 / 2044 / 2335 1519 / 2700 / 3098 1519 / 2700 / 3098
External static pressure - 2 pipes Pa 8/50/116 22/50/65 22/50/65 22/50/65 16/50/66 16/50/66External static pressure - 4 pipes Pa 8/50/117 22/50/65 22/50/65 22/50/65 16/50/66 16/50/66
Electrical data
Power supply V/Ph/Hz 230/1/50 - 230/1/60
Consumption - 2 Pipes W 10 / 62 / 197 60 / 171 / 246 61 / 172 / 246 61 / 172 / 246 57 / 237 / 364 57 / 237 / 364
Consumption - 4 Pipes W 10 / 60 / 189 61 / 172 / 246 61 / 172 / 246 61 / 172 / 246 57 / 237 / 364 57 / 237 / 364
Electric heater W 2000 3000 3000 3000 3000 3000
Water connections
Type Gas Male threaded
2 pipes inch 1/2” 1" 1”1/4 1”1/4 1”1/4 1”1/4
4 pipes "cooling" inch 1/2” 1” 1” 1” 1”1/4 1”1/4
4 pipes "heating" inch 1/2” 3/4" 3/4" 3/4” 3/4” 3/4”
Dimensions
Rectangular return and discharge configuration (LxWxH) mm 1200 x 698 x 250 1380 x 798 x 375 1380 x 798 x 375 1380 x 798 x 375 1500 x 798 x 450 1500 x 798 x 450
Circular return and discharge configuration (LxWxH) mm 1200 x 1014 x 250 - - - - -
Weight
Rect. return & discharge config. kg 42 63 65 67 76 80
* Fan standard factory set speeds (Voltage)
1 According to Eurovent standard. Air: 27°C DB/19°C WB, Chilled water: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Hot water: 45°C/40°C.3 According to Eurovent standard. Air: 20°C, Hot water: 65°C/55°C.4 According to Eurovent 6/10 (Airflow test method) and 8/12 (Sound test method).5 Informative data, considering an hypothetical sound attenuation of the room and installation of 21 dB.
*
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
144 systemair
Fan coil control systems A full range to cover all your needsElectro-Mechanical Control systems
TBMV TRM-FA 2 Pipes2 Reversible Pipes2 Pipes + Electric heaters - -2 Reversible Pipes + Electric heaters - -4 PipesActionChange over Manual ManualFan speed selection Manual ManualFan operation Cyclic 2 Cyclic 2
Master/slaves - -Fan CompatibilityACEC * *Valve CompatibilityON/OFF 230V 4
Mounting typeWall mounted or mounted on the unit Unit Wall
ControllerSystem
Compatibilities
SYSCOIL COMFORT SYSQUARE HAWAIR DUCTYS VHTBMV (a) - - - -TRM-FA (b)
TAE20 - (b)
SYSLOGIC (b)
T-CONTROL POD (b)
T-CONTROL EASY (b)
RCL-PFC-207 -PBB-230 -
ProductController
SRCSmart Remote Control New Mini Building Management System Supervise Systemair Fan Coil Units, Chillers/Heat pumps,
Air Handling Units and Water Source Heat Pumps ** Can be used as a mini BMS or a remote control Manage up to 15 zones and 31 units Communicate via Modbus protocol Time programming function A modern and refined design 3,5’’ color touchscreen Wall mounting
New
(a) only for vertical units with cabinet.(b) using this controller the shutters can be only manually adjusted.
systemair 145
FAN
COIL
UNI
TS
1 Continuous: Fan continues running after the set point is reached.2 Cyclic: Fan stops when the set point is reached.3 Smart: fan is Continuous in occupation mode and cyclic in inoccupation mode.4 Other kinds, please contact special affairs department.5 S.Q. - Special Quotation (upon request)6 Minimum order of 50 units* With Ecospeed card**Consult documentation for more details*** For 0-10V : Special Quotation (upon request)Note: Electrical heaters maximum power may vary according to the controller without a relay
ElectronicControl systems
New
MB2 - Modbus Board
Fan speed selection
ON/OFF
Temperature set point
Wall mounted
Allows the connection to
a Modbus communication protocol
An individual address to each fan coil
inside the communication bus system
BRCRemote control
WRC / MRCRemote controls
IRCInfrared remote control
LHMI (A)
LBHMI (C)
BHMI (B)
Two-way communication
Advanced control performance
Integrated temperature sensor
Display of temperature
Fan speed selection
Wall mounted (WRC) or mounted on
the unit (MRC)
Backlit LCD screen
Occupation mode button
Integrated temperature sensor
Easy installation with RJ-45 cable
Wall mounted
Integrated temperature sensor
Control in occupation mode
Fan speed selection
Precise control of temperature
Wall mounted
ControllerSystem
New
New
New
New
LCD screen Integrated temperature sensor Occupation mode button Display of temperature Wall mounted
A full range to cover all your needs
TAE20 SYSLOGIC T-CONTROL EASY T-CONTROL POD RCL-PFC-207 6 PBB-230 6
2 Pipes2 Reversible Pipes2 Pipes + Electric heaters -2 Reversible Pipes + Electric heaters - -4 Pipes
Communication protocol - Modbus (with MB2 board) - Modbus LON Bacnet MSTP
SRC mini BMS compatibility - - - -Time programming - - - - -
Compatibility with light & sun blind control modules - - - - -
ActionChange over Auto Manual or Auto Manual or Auto Manual or Auto Manual or Auto Manual or AutoFan speed selection Manual Manual or Auto Manual or Auto Manual or Auto Manual or Auto Manual or Auto
Fan operation Continuous 1 or cyclic 2
Continuous 1 or cyclic 2
Continuous 1 or cyclic 2
Continuous 1 or cyclic 2
Continuous 1, cyclic 2 or Smart 3
Continuous 1, cyclic 2 or Smart 3
Master/slaves - Up to 15 slave units - -
Up to 64slave units
Up to 64slave units
Fan CompatibilityAC S.Q.5
EC * *Valve CompatibilityON/OFF 230V *** ***Mounting typeWall mounted or mounted on the unit Wall Unit Wall Wall Unit Unit
(A) Compatible with RCL-PFC-207 controller(B) Compatible with PBB-230 controller(C) Compatible with RCL-PFC-207 and PBB-230 controllers
McArthurGlen Provence OutletMiramas, France• 160 Water Source Heat Pumps SYSHRW
146 systemair
CHALLENGER, Bouygues Construction Head office
Guyancourt, France
• 240 Water Source Heat Pumps SYSHRW
HOTEL BARRIERE LE ROYAL 5*
La Baule, France
• 132 Water Source Heat Pumps SYSHRW
WATER GARDEN SHOPPING MALL
Istanbul, Turkey
• 37 Water Source Heat Pumps SYSHRW
WATER SOURCE HEAT PUMPS
One building, different needs!
Water source heat pumps are ideal for large shopping centers, hotels or offices whose climate conditions change during the day or when, at the same time, the different areas of a building have different needs.
systemair 147
SRCNew mini BMS
New
WAT
ER S
OURC
EHE
AT P
UMPS
148 systemair
R513A
Discover SYSLOOP EVOp. 152
148 systemair
Q4 2020
systemair 149
WAT
ER S
OURC
EHE
AT P
UMPS
WATER SOURCE HEAT PUMPS
Product Size Cooling & Heating Capacities(kW)
Acoustic(at MS)
Airflow (nominal*)
Pressure(Pa)
Fan Dimensions (LxWxH) - mm
SYSL
OOP SL15 NR 26 435 m³/h
0-140 EC
900x530x250(a)
SL20 NR 30 465 m³/h 900x530x250(a)
SL30 NR 34 525 m³/h 900x530x250(a)
SYSL
OOP
EVO
SLE NR25,8*** 525 m³/h 0-140 EC 900x636x250(a)
SYSH
RW
SYSHRW 19 NR 37 1.250 m³/h >50 Pa
AC
900x600x439
SYSHRW 27 NR 34 1.190 m³/h >50 Pa 1.050x600x460
SYSHRW 27 HE NR 34 1.180 m3/h >50 Pa
1.050x660x460SYSHRW 30 NR 35 1.490 m³/h >100 Pa
SYSHRW 30 HE NR 35 1.500 m3/h >100 Pa
SYSHRW 36 NR 37 1.580 m³/h >100 Pa
SYSHRW 36 HE NR 37 1.580 m3/h >100 Pa
1.250x705x513
SYSHRW 42 NR 40 2.040 m³/h >100 Pa
SYSHRW 42 HE NR 40 2.040 m3/h >100 Pa
SYSHRW 48 NR 43 2.750 m³/h >100 Pa
SYSHRW 60 NR 43 2.840 m³/h >100 Pa
SYSHRW 60 HE NR 43 2.840 m3/h >100 Pa 1.250x705x583
SYSHRW 72 NR 39 3.570 m³/h >100 Pa 1.250x705x513
SYSHRW 72 HE NR 39 3.800 m3/h >100 Pa
1.680x955x770SYSHRW 96 NR 54 4.700 m³/h >100 Pa
SYSHRW 96 HE NR 54 4.700 m3/h >100 Pa
SYSHRW 120 NR 53 5.600 m³/h >200 Pa
SYSC
W-A
R CW-AR07 NR 37 400 m³/h
0 Pa AC/EC
1.138x251x821**
CW-AR09 NR 38 460 m³/h 1.138x251x821**
CW-AR12 NR 40 510 m³/h 1.138x251x821**
* At high speed** Standard unit with cabinet and feet*** At min. thermal load(a) without air inlet/outlet options
HEversions
very High Energy
efficiency
complem
entary range
complem
entary range
In line with
In line with BREEAM
BREEAM
requirements !
requirements !
SYSHRW 5,3-30,0 kW 5,8-38,1 kW 1.180-5.600 m3/h R407C Rotary/Scroll compressor
Plate heat exchanger
Page 154
HFC
SYSCW-AR 1,9-2,7 kW 2,4-3,2 kW 250-510 m3/h R407C Rotary compressor
Plate heat exchanger
EC fan (option)
Page 156
HFC
Quick selection guide
1,51,92,22,52,9
3,7
5,35,8
7,48,3
7,59,3
8,79,8
8,910,010,1
11,011,1
12,211,4
14,412,5
14,513,0
14,914,3
16,116,7
18,817,1
21,520,6
22,621,7
26,624,5
28,530,0
38,1
SYSLOOP 1,5-2,9 kW 1,9-3,7 kW 435-525 m3/h R410A Rotary compressor
Coaxial heat exchanger
EC fanPage 150
HFCHFC
SYSLOOP EVO 1,7-2,9 kW 2,0-3,8 kW 290-525 m3/h R513A Inverter Rotary compressor
Coaxial heat exchanger
EC fanPage 152
HFOHFC
2,93,8
1,92,4
2,12,52,7
3,2
Page 154
Page 156
Q4 2020
Q4 2020
Page 150
Page 152
150 systemair
EC fan
R410A
Rotary compressor
HFC
Coaxial heat exchanger
SYSLOOP
Water inlet temperatureCooling
Min 16 °CMax 45°C
HeatingMin 11°CMax 32°C
Air inlet temperatureCooling
Min 21°C db / 15°C wbMax 32°C db / 23°C wb
HeatingMin 15°CMax 26°C
Maximum water pressure 10 bars
SYSLOOPWater source heat pumpsCooling only / Reversible
1,5-2,9 kW 1,9-3,7 kW
435-525 m3/h The range at a glance 3 sizes Cooling only (CO) or Reversible (HP) units Horizontal installation EER up to 5,05 & COP up to 5,70 Cooling capacities from 1,5 to 2,9 kW Heating capacities from 1,9 to 3,7 kW Nominal airflow from 435 to 525 m3/h Low energy consumption EC fan Many air & water available configurations 140 Pa maximum external static pressure Operating range : from +15°C to +32°C ambient
air temperature Water inlet temperature from +11°C to +45°C
Equipment The refrigerant circuit comprises a rotary type her-
metic compressor, a cycle reversal valve (for revers-ible unit only), a water/refrigerant heat exchanger, a liquid receiver, a capillary expansion device, a finned coil, HP and LP pressure switches and two Schrader valves (HP & LP).
The rotary type hermetic compressor, mounted on spring anti-vibration mounts, is integrated in a com-partment coated with a reinforced acoustic insulation. It is also equipped with an internal thermal protection.
The water/refrigerant heat exchanger is of copper/ stainless steel coaxial type for an increased efficiency.
The units are equipped with the Stand-alone STORM2 control system *.
The casing is made of galvanised steel sheet. Condensate drain pan with an anti-corrosion treat-
ment. The electrical box is located on the hydraulic service
side with a wide access panel. The units are equipped with multi-position brackets for
easy installation.
Operating limits Accessories & Options
Air outlet silencerBasic or G3M1 filterCircuit breakerController with Modbus RTU / BACnet MSTP * (LON and Modbus TCP/IP available upon request)
Drain outletDrain pumpElectric heatersFlow switch controlGeneral defaulte reportInsulation around the fanMany air inlet/outlet & water connection configurationsPressostatic valve (cooling only)RCS remote control (for controller with com. protocols) *RCX remote control (for STORM2 controller) *Room temperature sensorSRC - Smart Remote Control *
* see pages 158-159 for more details
Advantages
Very high performances → EER up to 5,05 COP up to 5,70 Extra silent units → NR<35 at medium speed
+ reinforced insulation Low energy consumption EC fan Low height for an easy integration → only 250 mm Highly customizable → Many aeraulic configurations
+ Selection of the hydraulic service side Increased robustness → coaxial heat exchanger Easy access to the internal components → Large
electrical panel + filter accessible from 3 sides 100% factory tested
RCS remote control(option)
HOSPITALS
HHOTELSOFFICESSHOPS PUBLIC
TRANSPORTSCHOOLSSHOPPING
CENTERS
New
systemair 151
WAT
ER S
OURC
EHE
AT P
UMPS
SRCSmart Remote
Control
New
SYSLOOP SL15 SL20 SL30Total cooling capacity 1 W 1.507 2.151 2.902Sensible cooling capacity 1 W 1.371 1.733 2.355Heating capacity 2 W 1.934 2.510 3.680COP 5,49 5,70 4,97EER 4,51 5,05 4,25VentilationNumber of fan 1Nominal airflow m³/h 435 465 525Motor power W 24 38 53Air filter - Number / Efficiency 1/ Basic or G3M1Hydraulic circuitNumber of coaxial heat exchanger 1Maximum water pressure bar 10Nominal water flow l/h 317 444 617WPD at nominal water flow kPa 8 12 18Connections - Inlet/Outlet (Ø) inch 1/2’’ Gas maleCondensate outlet - External Ø mm 16Refrigerant circuitNumber of circuit 1Compressor Type RotaryLoad g 415 565 565Electrical dataElectrical power supply V / Ph / Hz 230/1/50 ±10%Power input (Cooling mode) 3 W 365 471 742Power input (Heating mode) 3 W 389 491 806Electric heating coil - Number/Capacity 4 -/W 1/600+600 1/800+800 1/1.000+1.000Heating coil power input 4 W 1.200 1.600 2.000Sound levels (LS/MS/HS) - without acoustic optionsSound Power - Radiated dB(A) 41,9/43,1/44,4 42,7/44,5/46,5 45/46,8/48,9Sound Power - Discharge dB(A) 45,6/49,1/53 49,1/53,6/58,3 51,7/57,2/61,9Sound Pressure 5 dB(A) 27,1/30/33,5 30/34,1/38,4 32,7/37,6/42NR 5 22,4/25,7/29,4 25,8/30,1/34,4 28,6/33,6/37,9Sound levels (LS/MS/HS) - with air outlet silencer & Insulation around the fanSound Power - Radiated dB(A) 42,3/43,2/44,5 42,7/44,4/46,5 44,4/46,6/48,9Sound Power - Discharge dB(A) 32,2/35,2/38,5 34,7/38,5/42,5 36,1/40,6/44,6Sound Pressure 5 dB(A) 23,2/25/27,3 24,8/27,7/31 27/30,6/34NR 5 18,8/20,4/22,7 20,1/23/26,4 23,2/25,9/29,5 Dimensions - without air inlet / outlet optionsLength mm 900 900 900Width mm 530 530 530Height mm 250 250 250 Weight - without air inlet / outlet optionsOperating kg 48 48 48
1 Nominal cooling capacities based on entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of 30 °C.2 Nominal heating capacities based on entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of 20 °C.3 Power input at nominal conditions (compressor + fan at high speed).4 Electric heating coil is available as an option.5 Informative data, considering an hypothetical sound attenuation of the room and installation of 21 dB. In-line configuration with filter.
Technical features
BIM models available at www.magicad.com
*
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
152 systemair
EC fan
R513A
Inverter Rotary compressor
Coaxial heat exchanger
SYSLOOP EVO
Water inlet temperatureCooling
Min 16 °CMax 45°C
HeatingMin 11°CMax 32°C
Air inlet temperatureCooling
Min 21°C db / 15°C wbMax 32°C db / 23°C wb
HeatingMin 15°CMax 26°C
Maximum water pressure 10 bars
SYSLOOP EVOWater source heat pumpCooling only / Reversible
1,7-2,9 kW 2,0-3,8 kW
290-525 m3/h The range at a glance Unique size available in Cooling only (CO) or Reversible
(HP) versions Horizontal installation EER up to 4,25 & COP up to 4,53 Cooling capacities from 1,7 to 2,9 kW Heating capacities from 2,0 to 3,8 kW Airflow from 290 to 525 m3/h Low energy consumption EC fan Inverter compressor technology Many air & water configurations available 140 Pa maximum external static pressure Operating range : from +15°C to +32°C ambient
air temperature Water inlet temperature from +11°C to +45°C
Equipment The refrigerant circuit comprises an Inverter rotary
type hermetic compressor, a cycle reversal valve (for reversible unit only), a water/refrigerant heat ex-changer, a liquid receiver, a capillary expansion device, a finned coil, HP and LP pressure switches and two Schrader valves (HP & LP).
The Inverter rotary type hermetic compressor, mounted on spring anti-vibration mounts, is integrated in a compartment coated with a reinforced acoustic insulation. It is also equipped with an internal thermal protection.
The water/refrigerant heat exchanger is of copper/ stainless steel coaxial type for an increased efficiency.
The unit is equipped with a complete control system (Modbus RTU or BACnet MSTP protocol communica-tion)*.
The casing is made of galvanised steel sheet. Condensate drain pan with an anti-corrosion
treatment. The electrical box is located on the hydraulic service
side with a wide access panel. The units are equipped with multi-position brackets for
easy installation.
Operating limits Accessories & Options
Air outlet silencerBasic or G3M1 filterCircuit breakerDrain outletDrain pumpElectric heatersFlow switch controlGeneral defaulte reportInsulation around the fanMany air inlet/outlet & water connection configurationsRCS remote control (for controller with com. protocols) *Room temperature sensorSRC - Smart Remote Control ** see pages 158-159 for more details
Advantages
Eco-friendly → R513A refrigerant with very low GWP (631) + Low energy
consumption EC fan Economic → Inverter compressor adapting its speed
according to the required capacity Extra silent unit → NR<26 at low speed
+ reinforced insulation Very high-performance → EER up to 4,25
COP up to 4,53 Low height for an easy integration → only 250 mm Highly customizable → Many aeraulic configurations
+ Selection of the hydraulic service side Increased robustness → coaxial heat exchanger Easy access to the internal components → Large
electrical panel + filter accessible from 3 sides 100% factory tested
RCS remote control(option)
HOSPITALS
HHOTELSOFFICESSHOPS PUBLIC
TRANSPORTSCHOOLSSHOPPING
CENTERS
compressor
R513A
Q4 2020
New
systemair 153
WAT
ER S
OURC
EHE
AT P
UMPS
SYSLOOP EVOSLE
MIN ** MAX **Total cooling capacity 1 W 1.687 2.948Sensible cooling capacity 1 W 1.363 2.337EER 4,25 3,06Heating capacity 2 W 2.004 3.769COP 4,53 3,45VentilationNumber of fan 1Nominal airflow (at Low & High speeds) m³/h 290 525Motor power (at Low & High speeds) W 13 54Air filter - Number / Efficiency 1 / Basic or G3Hydraulic circuitNumber of cohaxial heat exchanger 1Maximum water pressure bar 10Nominal water flow - Cooling l/h 354 662Nominal water flow - Heating l/h 458 789WPD at nominal water flow - Cooling 6 kPa 9 19,5WPD at nominal water flow - Heating 6 kPa 12,3 24,6Connections - Inlet/Outlet (Ø) inch 1/2’’ Gas maleCondensate outlet - External Ø mm 16Refrigerant circuitNumber of circuit 1Compressor Type Inverter rotaryLoad g 514
1 Nominal cooling capacities based on entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of 30 °C.2 Nominal heating capacities based on entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of 20 °C.3 Power input at nominal conditions (compressor + fan at high speed).4 Electric heating coil is available as an option.5 Informative data, considering an hypothetical sound attenuation of the room and installation of 21 dB. In-line configuration with filter.6 without valve** Thermal load
Technical features
BIM models will be available at www.magicad.com
*
SYSLOOP EVO SLE
Electrical data MIN ** MAX **Electrical power supply V/Ph/Hz 230/1/50 ±10%Power input - Cooling 3 W 397 964Power input - Heating 3 W 442 1.093
Electric heating coil - Number/Capacity 4 -/W 1/600 + 600
1/1.000 + 1.000
Electric heating coil power input 4 W 1.200 2.000Sound levels - without acoustic optionsSound Power - Radiated dB(A) 41,9 51,5Sound Power - Discharge dB(A) 47,9 62,8Sound Pressure 5 dB(A) 29,3 43NR 5 25,8 39,2Sound levels - with air outlet silencer & Insulation around the fanSound Power - Radiated dB(A) 42,3 51,6Sound Power - Discharge dB(A) 33,2 44,4Sound Pressure 5 dB(A) 24,5 35NR 5 19,5 30,4 Dimensions - without air inlet / outlet optionsLength mm 900Width mm 636Height mm 250 Weight - without air inlet / outlet optionsOperating weight kg 51
SRCSmart Remote Control
New
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation will be available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
154 systemair
Advantages
Low sound levels → Acoustic insulation between ventilation & compressor compartments Very High Efficiency versions (HE) → EER up to 4,74
COP up to 4,46 In-line or perpendicular air blowing Easy access to components through wide removable panels Condensate drain pan with an anti-corrosion treatment
and a float-type safety system 100% factory tested
R407C
Rotary/Scroll compressor
HFC
Plate heat exchanger
SYSHRWWater source heat pumpsCooling only / Reversible
5,3-30,0 kW 5,8-38,1 kW
1.180-5.600 m3/h
RCS remote control(option)
HEversions
very High Energy
efficiency
complem
entary range
complem
entary range
In line with
In line with BREEAM
BREEAM
requirements !
requirements !
The range at a glance 10 sizes Cooling only (L) or Reversible (H) units Vertical installation Versions: Standard or HE (very High Efficiency) in-line
with BREEAM requirements EER up to 4,74 & COP up to 4,46 Cooling capacities from 5,3 to 30,0 kW Heating capacities from 5,8 to 38,1 kW Nominal airflow from 1.180 to 5.600 m3/h AC fan : 3-speed direct drive fan motor for sizes 19 to
72 and belt drive with variable pitch pulley for sizes 96 and 120
In-line or perpendicular air blowing Operating range : from +15°C to +38°C ambient
air temperature Water inlet temperature from +13°C to +48°C
Equipment The refrigerant circuit comprises a scroll or rotary
type hermetic compressor, a cycle reversal valve (for reversible unit only), a water/refrigerant heat exchanger, a liquid receiver, a bi-flow thermostatic expansion valve and a finned coil, HP and LP pressure switches and two Schrader valves (HP & LP).
The rotary or scroll type hermetic compressor, mounted on rubber anti-vibration mounts, is inte-grated in a compartment coated with a reinforced acoustic insulation. It is also equipped with an internal thermal protection.
The water/refrigerant heat exchanger is made of brazed stainless steel plates, for improved efficiency.
The units are equipped with the Stand-alone STORM2 control system and with RCX remote thermostat *
Condensate drain pan with an anti-corrosion treat-ment and a float-type safety system.
A G2-M1air filter is provided within the unit.
Accessories & OptionsCircuit breaker
Controller with Modbus RTU / BACnet MSTP *(LON and Modbus TCP/IP available upon request)
Electric heatersGeneral alarm dry contactMain switchMotorized water valveRCS remote control (for controller with com. protocols) *Room sensorSRC - Smart Remote Control *
SYSHRW 19-72 96-120
Water inlet temperatureCooling
Min 18°C 20°CMax 44°C 48°C
HeatingMin 13°CMax 34°C
Air inlet temperatureCooling
Min 21°C db/15°C wbMax 38°C db/28°C wb
HeatingMin 15°CMax 27°C 25°C
Maximum water pressure 16 bars
Operating limits
* see pages 158-159 for more details
HOSPITALS
HHOTELSOFFICESSHOPS PUBLIC
TRANSPORTSCHOOLSSHOPPING
CENTERSINDUSTRY
New
systemair 155
WAT
ER S
OURC
EHE
AT P
UMPS
SRCSmart Remote
Control
New1 Nominal cooling capacities based on : entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of 30°C.2 Nominal heating capacities based on : entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of 20°C.3 Absorbed power (compressor + fan) at nominal conditions.
SYSHRW 19 27 27HE 30 30
HE 36 36 HE 42 42
HE 48 60 60 HE 72 72
HE 96 96 HE 120
Total cooling capacity 1 W 5.278 7.419 7.320 8.691 8.710 10.138 11.060 11.366 12.500 12.965 14.344 16.700 17.174 20.600 21.743 24.500 29.951
Sensible cooling capacity 1 W 4.257 5.824 5.600 6.315 6.676 7.278 9.070 8.849 9.542 10.051 10.988 13.900 13.536 17.700 17.986 19.500 24.413
Heating capacity 2 W 5.826 8.342 9.252 9.759 9.960 11.036 12.200 14.422 14.450 14.904 16.147 18.800 21.500 22.600 26.637 28.500 38.109
COP 4,40 3,69 4,214,21 3,50 4,304,30 3,38 4,284,28 3,84 4,364,36 4,25 3,33 4,204,20 3,15 4,234,23 3,54 4,464,46 4,25
EER 4,20 3,72 4,00 3,77 4,15 3,77 4,31 3,44 4,00 4,03 3,23 4,44 3,26 4,74 3,84 4,61 4,21
VentilationNumber of fan 1Nominal airflow m³/h 1.250 1.190 1.180 1.490 1.500 1.580 1.580 2.040 2.040 2.750 2.840 2.840 3.570 3.800 4.700 4.700 5.600
Motor Power W 450 450 450 950 950 950 950 950 950 1.500 1.500 1.500 1.500 736 1.100 1.100 1.500
Air filters - Number / Efficiency 2 / G2-M1
Hydraulic circuitNumber of plate heat exchanger 1
Maximum water pressure bar 16
Nominal water flow l/h 921 1.540 1.620 1.764 1.800 2.030 2.306 2.592 2.600 2.822 3.348 3.550 3.924 4.300 4.860 4.960 6.408
WPD at nominal water flow kPa 13 17 13 23 20 25 21 33 28 34 40 35 61 50 55 55 80,5
Connections - Inlet / Outlet (Ø) inch ISO G 3/4” INTISO G 1”1/4
ISO G 3/4” INT
ISO G 1”1/4
Condensate outlet - External Ø mm 19 22
Refrigerant circuitNumber of circuit 1
Compressor Type Rotary ScrollLoad g 1.160 1.483 2.534 1.594 1.950 1.950 3.200 3.200 2.800 3.200 3.200 3.400 2.700 3.800 5.100 5.100 5.100
Electrical data
Electrical power supplyV/Ph/
Hz230/1/ 50
±10%400/3/50 +Neutral
Power input (Cooling mode) 3 W 1.557 2.118 1.981 2.658 2.357 3.044 2.909 3.584 3.423 4.200 4.989 4.278 6.280 5.279 6.317 5.954 8.547
Power input (Heating mode) 3 W 1.611 2.332 2.382 2.983 2.475 3.460 3.203 3.920 3.479 4.300 5.150 5.098 7.347 6.188 7.895 7.115 10.224
Electric heating coil - Number/Capacity -/W
2/1.500+750
1/3.750
1/3.750
1/3.750
1/3.750
1/4.500
1/4.500
1/5.400
1/5.400
1/6.500
1/7.500
1/7.500
1/9.000
1/9.000
1/13.000
1/13.000
1/16.000
Sound levels (LS/MS/HS)
Sound Power - Radiated dB(A) 51/54/58
54/56/57
54/56/57
53/54/57
53/54/57
53/56/58
53/56/58
54/56/58
54/56/58
55/59/63
55/59/63
55/59/63
57/60/63
55/59/62
70/69/68
70/69/68
72/69/70
NR 34/37/40
33/34/37
33/34/37
33/35/38
33/35/38
34/37/41
34/37/41
36/40/43
36/40/43
39/43/46
39/43/46
39/43/46
36/39/44
36/39/44
56/54/52
56/54/52
56/53/50
DimensionsLength mm 900 1.050 1.050 1.050 1.050 1.050 1.250 1.250 1.250 1.250 1.250 1.250 1.250 1.680 1.680 1.680 1.680
Width mm 600 600 660 660 660 660 705 705 705 705 705 705 705 955 955 955 955
Height mm 439 460 460 460 460 460 513 513 513 513 513 583 513 770 770 770 770
WeightOperating kg 80 100 112 100 100 112 133 133 135 140 144 149 149 253 253 259 262
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical features
*
156 systemair
HOSPITALS
Advantages
Low sound levels → Acoustic insulation between ventilation & compressor compartments Design and Elaborate finish cabinet enabling
harmonious integration (RAL9010) Low energy consumption EC fan (option) Selection of hydraulic & electric service side Easy access to components through a large front panel Brazed stainless steel plate heat exchanger for
improved efficiency 100% factory tested
HHOTELSOFFICES
EC fan (option)
R407C
Rotary compressor
HFC
Plate heat exchanger
SYSCW-ARWater source heat pumpsCooling and heating
1,9-2,7 kW 2,4-3,2 kW
250-510 m3/h
RCS remote control(option)
The range at a glance 3 sizes Reversible units (cooling and heating) Vertical installation Versions:
VC: standard version with cabinet, VCL: low height version with cabinet, VN: standard version without cabinet, VNL: low height version without cabinet. EER up to 3,52 & COP up to 3,74 Cooling capacities from 1,9 to 2,7 kW Heating capacities from 2,4 to 3,2 kW Nominal airflow from 250 to 510 m3/h 3-speed AC fan (or optional low consumption EC fan) Many hydraulic & electric available configurations Front or bottom air intake Operating range : from +15°C to +32°C ambient
air temperature Water inlet temperature from +12°C to +42°C
Equipment The refrigerant circuit comprises a rotary type hermet-
ic compressor, a cycle reversal valve, a water/refriger-ant heat exchanger, a liquid receiver, a finned coil, HP and LP pressure switches and two Schrader valves (HP & LP).
The rotary type hermetic compressor, mounted on spring anti-vibration mounts, is integrated in a com-partment coated with a reinforced acoustic insulation. It is also equipped with an internal thermal protection.
The water/refrigerant heat exchanger is made of brazed stainless steel plates, for improved efficiency.
The units are equipped with the Stand-alone STORM2 control system and with RCX remote thermostat (not mounted) *
RAL9010 painted cabinet for versions VC and VCL. Condensate drain pan with an anti-corrosion treatment. A G2 air filter is provided within the unit.
Accessories & Options
Controller with Modbus RTU / BACnet MSTP *(LON and Modbus TCP/IP available upon request)
EC fanFeet General remote alarm contactLow noiseMany electric, hydraulic and aeraulic configurationsRCS remote control (for controller with com. protocols) *RCX remote control mounted (for STORM2 controller) *SRC - Smart Remote Control *Thermal overload
SYSCW-AR
Water inlet temperatureCooling
Min 23°CMax 42°C
HeatingMin 12°CMax 34°C **
Air inlet temperatureCooling
Min 21°C db/15°C wbMax 32°C db/23°C wb
HeatingMin 15°CMax 27°C
Maximum water pressure 10 bars
Operating limits
* see pages 158-159 for more details** 32°C for SYSCW-AR07 in low speed
New
systemair 157
WAT
ER S
OURC
EHE
AT P
UMPS
SRCSmart Remote
Control
New
SYSCW-AR CW-AR07 CW-AR09 CW-AR12Total cooling capacity 1 W 1.942 2.136 2.743Sensible cooling capacity 1 W 1.526 1.775 2.340Heating capacity 2 W 2.431 2.542 3.156COP 3,56 3,74 3,49EER 3,41 3,52 3,25VentilationNumber of fan 1Airflow (LS/MS/HS) m³/h 250/340/400 340/400/460 400/460/510Motor power - AC/EC W 75/40 75/40 75/40Air filter - Number/Efficiency 1/G2Hydraulic circuitNumber of plate heat exchanger Nbr 1Maximum water pressure bar 10Nominal water flow l/h 428 479 616
WPD at nominal water flow kPa 5 3,4 12
Connections - inlet/outlet (ø) inch ISO G 1/2” INTCondensate outlet - external ø mm 15x20Refrigerant CircuitNumber of circuit 1Compressor Type RotaryLoad g 490 430 750Electrical DataElectrical power supply V/Ph/Hz 230/1/50 ±10%Power input (cooling mode) - AC fan 3 W 598 647 892Power input (heating mode) - AC fan 3 W 710 720 954Sound Levels - AC fan (LS/MS/HS)Sound pressure level 4 dB(A) 41/42/43 42/43/45 43/45/46NR 4 36/37/38 37/38/40 38/40/41Dimensions (LxWxH)Standard with cabinet (VC) mm 1.138 x 251 x 720min/750max (821 with feet)Low height with cabinet (VCL) mm 1.323 x 251 x 580min/610max (683 with feet)Standard without cabinet (VN) mm 1.043,5 (1.086 with feet) x 229 x 667,5min/697,5max (769,5 with feet)Low height without cabinet (VNL) mm 1.182,5 (1.183 with feet) x 229 x 525min/555max (8627 with feet)WeightWithout cabinet / with cabinet - operating kg 55/70 58/73 60/75
1 Nominal cooling capacities based on: entering air temperature of 27°C DB/19°C WB, with entering water temperature of 30°C.2 Nominal heating capacities based on: entering air temperature of 20°C DB/15°C WB, with entering water temperature of 20°C.3 Absorbed power (compressor + fan) at nominal conditions.4 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical features
*
158 systemair
Water source heat pumps
Control Systems
Product Advantages Measurement of the room air temperature Anti-short cycle to protect the compressor Variable sequential start-up function avoiding a power surge Emergency shut-down / stand-by / night setback Automatic HP reset pressure and/or lack of water flowrate Automatic BP reset pressure Default isothermal motor ventilator Anti-freeze safety function Low/High temperature limit in cooling/heating mode Antifreeze default in cooling mode Managing of motorized water valves
RCX remote control Main functions LCD operation display START/STOP button Display of the room temperature Operation mode selection button: COOLING, HEATING, AUTO COOL/HEAT, DRY, FAN Room temperature UP/DOWN buttons Airflow direction MANUAL positioning control /AUTO-CONTROL buttons FAN SPEED and AUTO FAN buttons TIMER SET / CLEAR / UP / DOWN buttons NIGHT button Infrared signal transmitter Master/slaves control up to 10 units with only one remote control
STORM2 Stand-alone control system
RCXRemote control
SRCSmart Remote Control Supervise Systemair Fan Coil Units, Chillers/Heat pumps,
Air Handling Units and Water Source Heat Pumps Manage up to 31 units Communicate via Modbus protocol Time programming function A modern and refined design 3,5’’ color touchscreen Wall mounting
New
systemair 159
WAT
ER S
OURC
EHE
AT P
UMPS
Ventilation
• Compatibility: 3-speed AC fan motor or EC fan motor
• Manual speed (3 levels)
• Automatic speed
Communication
• Modbus RTU or BACnet MSTP
• Modbus TCP/IP or LON upon request
Operating mode • OFF / Comfort / ECO
Function type • Summer • Winter • Ventilation • Auto changeover (adjustment of the
automatic mode according to the setpoint)
Setpoint • Extract air temperature • Room thermostat • BMS
RCSRemote control
RCS remote controlMain functions
• ON/OFF• Comfort / ECO modes• Operating mode setting• Setpoint adjustment• Room temperature (OFF)• Ventilation setting (manual or automatic)• Time display and setting• Sum alarm• Zoning (up to 15 units)• Scheduling
Control system with communication protocols W
ATER
SOU
RCE
HEAT
PUM
PS
AKI SupermarketChaves, Portugal• SYSAER.120.H Rooftops (x2)
BLAISE DIAGNE AIRPORT
Dakar, Senegal
• SYSAER.200.L Rooftops (x2)
TIRSAN KARDAN
Manisa, Turkey
• SYSAER.140.L Rooftops (x1)
AL-RAYAN DAIRIES FACTORY
Basra, Irak
• RTL.110 Rooftops (x11)
160 systemair
ROOFTOPS
A complete monobloc solution for large buildings
With a rooftop units, you get a complete monobloc solution to heat and cool large buildings such as shopping centers, industries or airports that need high capacities. It is also a space saving solution, easy to install, directly on the roof.
ErP2018
systemair 161
ROOF
TOPS
162 systemair
ROOFTAIR 31,8-48,7 kW 33,5-51,8 kW 5.500-9.200 m3/h R410A Scroll compressors
Page 164
HFC
SYSAER 48,1-219,1 kW 50,7-214,4 kW 7.760-38.400 m3/h R410A Scroll compressors
EC fan(s)Page 166
HFC
ErP2018
ErP20182021
2021Ready.
Minimum ηsh to be Ecodesign compliant
Minimum ηsc to be Ecodesign compliant
EcodesignAir to Air Rooftops
ErP2018
COMMISSION REGULATION (EU) No2016/2281
100
110
120
130
140
150
2015 2016 2017 2018 2019 2020 2021 2022
ηsc / ηsh
138
115Jan.
2018
125Jan.
2021
117
Jan. 2021
years
ROOFTOPS
*
* from size 55 to 95
systemair 163
ROOF
TOPS
Product Size Cooling & Heating Capacities(kW)
Nominal airflow(m3/h)
Sound Power(lwo - dB(A))
Dimensions (LxHxW - mm)
ROOF
TAIR
RTH 30 5.500 83 2.484 x1.450 x 1.877
RTH 40 7.650 85 2.484 x1.450 x 1.877
RTH 50 9.200 88 2.484 x1.450 x 1.877
SYSA
ER
SR55.H.EC 9.720 80 3.250 x 1.800 x 2.030
SR65.H.EC 11.500 83 3.250 x 1.800 x 2.030
SR80.H.EC 14.300 80 3.250 x 1.800 x 2.030
SR95.H.EC 17.500 81 3.740 x 2.110 x 2.285
SR105.H.EC 19.200 85 3.740 x 2.110 x 2.285
SR120.H.EC 21.500 87 3.740 x 2.110 x 2.285
SR140.H.EC 25.500 91 3.740 x 2.110 x 2.285
SR160.H.EC 28.000 91 5.505 x 2.110 x 2.285
SR190.H.EC 30.000 92 5.505 x 2.110 x 2.285
SR210.H.EC 32.000 94 5.505 x 2.110 x 2.285
Quick selection guide
31,8
33,5
41,9
44,3
47,2
51,8
48,1
50,7
61,0
59,7
76,7
76,6
92,3
90,7
107,8
107,0
116,3
117,1
137,9
148,7
160,1
157,9
191,2
187,3
212,6
214,4
RTH : Reversible versionSR.H.EC : Reversible version with EC fans
Page 164
Page 166
164 systemair
ErP2018
Cooling modeTemperature before indoor coil (wet bulb) °C from +12 to +26Outdoor temperature (dry bulb) °C from -10* to +46Heating modeTemperature before indoor coil (dry bulb) °C from +10 to +27Outdoor temperature (dry bulb) °C from -10 to +21
Advantages
Compact, light & single piece design. Many aeraulic configurations Wide operating limits → from -10°C* to +46°C OAT 100% factory tested Eurovent certified
OFFICESINDUSTRYSHOPPING CENTERS
HOSPITALS
H
R410A
Scroll compressors
HFC
ROOFTAIRRooftop unitsCooling only / Reversible
31,8-48,7 kW 33,5-51,8 kW
5.500-9.200 m3/h The range at a glance 3 sizes Cooling only (RTL) or Reversible (RTH) units SEER up to 3,43 & SCOP up to 3,07 Cooling capacities from 31,8 to 48,7 kW Heating capacities from 33,5 to 51,8 kW Nominal airflow from 5.500 to 9.200 m3/h Operating range : from -10°C to +46°C outdoor air
temperature Additional heaters available Many aeraulic configurations
Equipment The refrigerant circuit comprises Scroll tandem com-
pressors, an indoor coil, an outdoor coil, a condensing pressure tab, a moisture indicator, a thermal expansion valve, a 4-way reversible valve (RTH only), an expan-sion device, a filter dryer and a sight glass.
Scroll compressors for higher efficiency with better resistance to liquid return and less vibration. Each compressor is equipped with crankcase heater to eliminate refrigerant migration and improve start up in winter.
Controls are located in a watertight compartment iso-lated from the air stream. They are fully tested at the factory and shipped READY-TO-START. The electrical equipment is compliant with CE Standards and EN 60204-1.
The outdoor and indoor heat exchangers are made of seamless copper tubes mechanically expanded into aluminium fins.
The casing of the unit is compact, light and single piece design. A galvanized steel single base rail en-sures a very high structural rigidity.
It is Insulated with glass wool MO 62 kg/m3 – CE certified. All panels are painted and there is no visible screws to prevent corrosion. The unit is also equipped with a sloped roof to ease rain water drainage.
Under the indoor heat exchanger, an extractible con-densate drain pan allows hygienic cleaning.
For a full unit access, service panels are all removable. The indoor fan is a belt driven centrifugal dual inlet
blower with forward curved blades (equipped with a flexible connection to eliminate vibration transfer to the cabinet and a frequency driver). A single speed motor is supplied with adjustable pulleys to fit operat-ing conditions on site. It is mounted on an independ-ent platform with adjusting spanner screw to ease alignment and belt tension. These units also offer the choice of factory-fitted supply and return air configu-rations (Down, Side, Front or Up).
Accessories & OptionsAirflow pressure switch Hot water coil with modulating valveAntivibration mount Low ambient kit
AVM kit Many aeraulic configurations (Down, side, front, up)
Clogged filter Moisture eliminator on fresh airDouble skin insulation Outdoor coil gridsElectric heaters Remote room sensorExaust blower Roof curbsFresh air intake Several control optionsG4, G4+F6 or G4+F7 filters Smoke sensorHigh external static pressure Soft start main blower
Operating limits
* For lower than 18°C outdoor air temperature, use low ambient kit (option).
PUBLIC TRANSPORT
SCHOOLSCINEMAS POOLS
systemair 165
ROOF
TOPS
ROOFTAIR - RTL (cooling only) RT 30 RT 40 RT 50
Cooling
Cooling capacity 1 kW 32,7 43,1 48,7Power input 1 kW 11,35 13,86 15,76EER / Energy efficiency class (EER) 1 2,88 / B 3,11 / A 3,09 / APdesignC 2 3 kW 32,7 43,1 48,7SEER 2 3 3,17 3,43 3,37ηsc
2 3 124 134 132ROOFTAIR - RTH (reversible)
Cooling
Cooling capacity 1 kW 31,8 41,9 47,2Power input 1 kW 11,40 13,87 15,68EER / Energy efficiency class (EER) 1 2,79 / C 3,02 / A 3,01 / APdesignC 2 3 kW 31,8 41,9 47,2SEER 2 3 3,08 3,33 3,28ηsc
2 3 120 130 128
Heating
Heating capacity 1 kW 33,5 44,3 51,8Power input 1 kW 10,2 12,3 14,3COP / Energy efficiency class (COP) 1 3,30 / B 3,62 / A 3,62 / APdesignH 2 3 kW 30,0 40,0 49,0SCOP 2 3 2,96 3,07 3,06ηsh
2 3 115 120 119Electrical dataPower supply V/ph/Hz 400/3+N/50Maximum operating intensity A 42 46 57Maximum start intensity A 104 132 179RefrigerantType R410ANumber of refrigeration circuit 1CompressorsType ScrollNumber 2Capacity steps % 0/50/100Indoor coilType Copper tubes & aluminum finsNumber of rows 3 3 3Front surface m² 1,17 1,60 1,60Indoor fanType Forward curved centrifugalNumber 1Nominal airflow m3/h 5.500 7.650 9.200Motor power kW 1,5 1,5 2,5Outdoor coilType Copper tubes & aluminium finsNumber of rows 2 2 2Front surface m² 1,92 3,00 3,00Outdoor fanType PropellerNumber 2 2 2Diameter mm 610 610 610Nominal airflow m3/h 16.000 16.000 16.000Motor power kW 1,14 1,14 1,14Sound levelsSound power level (lwo) - outside dB(A) 83 85 88Sound power level (lwi) - in supply duct dB(A) 79 82 86Dimensions and WeightLength mm 2.484 2.484 2.484Width mm 1.877 1.877 1.877Height mm 1.450 1.450 1.450Weight (without option) kg 600 650 700
1 Following EN 14511 2018.2 Following EN 14825 2017. 3 Following COMMISSION REGULATION (EU) No2016/2281 for air to air Rooftops (see page 162 for more information).
Complete documentation available on www.systemair.com and the app MEDIA CENTER by Systemair
Technical features
166 systemair
ErP20182021
2021Ready.
R410A
Scroll compressors
HFC
SYSAERRooftop unitsCooling only / Reversible
48,1-219,1 kW 50,7-214,4 kW
7.760-38.400 m3/h EC fan(s) (option) The range at a glance 10 sizes Cooling only (L) or Reversible (H) units SEER up to 3,94 & SCOP up to 3,23 Cooling capacities from 48,1 to 219,1 kW Heating capacities from 50,7 to 214,4 kW Nominal airflow from 9.720 to 32.000 m3/h Operating range : from -15°C to +50°C outdoor air tem-
perature Additional heaters available Many aeraulic configurations 3 performant energy recovery systems
(RECO, TRECO, FRECO)
Equipment 2 refrigerant circuits for an optimized defrosting logic.
They are both completely closed in a separate compart-ment in order to reduce noise level. Each circuit compris-es Scroll compressor(s) (2 per circuit from size SR160), Indoor and outdoor coils, a 4-way reversible valve (SR.H only), a filter dryer, a sight glass, a thermostatic or elec-tronic expansion valve, high and low pressure switches, a defrosting pressure switch, an intake temperature sensor and a liquid accumulation bottle (for sizes from SR160 to SR210).
2 or 4 Scroll compressors - 1 per circuit from SR55 to SR140 and 2 per circuit assembled together to form tandem from SR160 to SR210.
Each compressor is equipped with a crankcase heater and are mounted on rubber pads to eliminate noise and vibration transmissions. The motors are equipped with an overload protection and have a direct start-up.
A phase sequence monitor is supplied as standard. The controls are grouped and wired in the unit, factory
tested and shipped READY TO USE. They are located in a sealed compartment that is isolated
from the air flow. The electrical equipment is compliant with EC standards and EN60204-1.
The outdoor and indoor heat exchangers are made of seamless copper tubes mechanically expanded into aluminium fins. Outdoor coils are largely dimensioned in order to optimize performance and defrosting cycles. They are also equipped with a protective grille to prevent shocks - Bluefin treatment for reversible versions.
The casing of the unit is of heavy duty galvanized steel, painted with a special process to ensure a perfect protec-tion against corrosion (RAL 7040).
The complete unit is covered with double skin panels to ensure a perfect thermal insulation. For a full unit access, service panels are all removable. Under the indoor heat exchanger, an extractible condensate drain pan allows hygienic cleaning.
The indoor fan(s) are PLUG FAN type with AC or EC motors; Low Pressure or High pressure according to the configuration selected by the customer.
Advantages
Very high performances → A class EER & COP → ErP 2021 ready 3 performant Energy recovery systems Low energy consumption EC fan(s) Many aeraulic configurations Wide operating limits → from -15°C to +50°C OAT Leak detection according to BREEAM standard Thermal/acoustic insulation → Double skin (25mm glasswool)
100% factory tested Eurovent certified *
*
Accessories & OptionsAC HPF plug fan G4, G4+F7 or G4+F9 filtersAdjustable roof curb Gas burnerAntivibration mounts Hot water coilClogged filter sensor (1 or 2 stages) Local & additional Remote KeyboardCompatible container transportation
Many aeraulic configurations (Down, side, front, up)
Compressor Softstarter Modbus / BacnetEC or EC HPF plug fan RECO, TRECO or FRECO Electric heaters Room temperature SensorEnergy recovery system Sensors (VOC, Enthalpy, CO2)Epoxy treatment (indoor/outdoor coils) Smoke detector
Fan Speed Control
* from size 55 to 95
OFFICESINDUSTRYSHOPPING CENTERS
HOSPITALS
HPUBLIC
TRANSPORTSCHOOLSCINEMAS POOLS
systemair 167
ROOF
TOPS
FRECO Additionnal heating capacity
Mixed air T° = 20°C +60%
Mixed air T° = 0°C +130%
Water +30% Glycol 45/40°C
Pc EER Ph COP
3 dampers + RECO 30% fresh air +1% +2% +7% +4%
3 dampers + RECO 60% fresh air +2% +4% +14% +8%
Pc EER Ph COP
3 dampers + TRECO 20% fresh air +21% 0% +20% +3%
3 dampers + TRECO 60% fresh air +20% -2% +21% +4%
Nominal conditions
Nominal conditions
Cooling modeTemperature before indoor coil (wet bulb) °C from +12 to +26Outdoor temperature (dry bulb) °C from -10 (a) to +50Heating modeTemperature before indoor coil (dry bulb) °C from +10 to +27Outdoor temperature (dry bulb) °C from -15 to +18
Operating limits (to be confirmed by AC SELECT)
(a) Using Fan Speed Control option
RECO - Standard energy RECOvery (3 Dampers)Energy recovery on the exhaust air
TRECO - Thermodynamic energy RECOvery (3 Dampers)Active energy recovery between the exhaust air and the fresh air using dedicated thermodynamic system
FRECO - Food refrigeration energy RECOveryIn supermarkets, FRECO technology allows our rooftop units to recover the heat generated out from the condensers of the cooling systems.
Energy recovery systems
Hot water
Cold waterCondensing unit from
food refrigeration system
Heating mode
Heating mode
Heating mode
Fresh air
Supply airReturn air
Exhaust air
Exhaust air
Return air
Supply airFresh air
168 systemair
SYSAER - SR.L.EC (cooling only) SR55.EC SR65.EC SR80.EC SR95.EC SR105.EC SR120.EC SR140.EC SR160.EC SR190.EC SR210.EC
Cooling
Cooling capacity 1 kW 49,60 62,80 79,00 95,10 111,08 119,87 142,09 164,98 197,06 219,12Power input 1 kW 15,85 19,44 23,24 30,68 33,56 37,10 47,09 51,19 60,61 71,54EER / Energy efficiency class (EER) 1 3,13/A 3,23/A 3,40/A 3,10/A 3,31/A 3,23/A 3,02/A 3,22/A 3,25/A 3,06/APdesignC 2 3 kW 49,57 62,81 78,99 95,13 111,08 119,87 142,09 164,98 197,06 219,12SEER 2 3 3,57 3,58 3,74 3,54 3,66 3,57 3,52 3,91 3,94 3,71ηsc
2 3 140 140 147 139 143 140 138 154 154 145SYSAER - SR.H.EC (reversible)
Cooling
Cooling capacity 1 kW 48,10 61,00 76,70 92,30 107,81 116,34 137,88 160,10 191,21 212,60Power input 1 kW 15,82 19,49 23,24 30,66 33,56 37,10 45,69 51,19 60,61 70,47EER / Energy efficiency class (EER) 1 3,04/A 3,13/A 3,30/A 3,01/A 3,21/A 3,14/A 3,02/A 3,13/A 3,15/A 3,02/APdesignC 2 3 kW 48,12 60,95 76,67 92,34 107,81 116,34 137,88 160,10 191,21 212,60SEER 2 3 3,53 3,52 3,63 3,52 3,55 3,52 3,52 3,80 3,82 3,65ηsc
2 3 138,15 137,98 142,23 137,81 139,17 137,83 137,67 148,92 149,82 143,15
Heating
Heating capacity 1 kW 50,65 59,65 76,63 90,66 106,95 117,10 148,70 157,90 187,31 214,37Power input 1 kW 14,81 17,49 21,77 26,59 30,38 34,14 42,85 46,17 54,29 62,68COP / Energy efficiency class (COP) 1 3,42/A 3,41/A 3,52/A 3,41/A 3,52/A 3,43/A 3,47/A 3,42/A 3,45/A 3,42/APdesignH 2 3 kW 48,00 58,00 67,00 85,00 100,00 112,00 145,00 155,00 180,00 210,00SCOP 2 3 3,20 3,22 3,22 3,23 3,22 3,21 3,20 3,19 3,23 3,19ηsh 2 3 125,00 126,00 126,00 126,00 126,00 125,00 125,00 125,00 126,00 125,00
Electrical dataPower supply 400V / 3~ +N / 50HzMaximum operating intensity A 46,30 57,60 74,60 83,80 89,80 103,00 123,00 157,80 161,80 178,60Start intensity (without soft starter) A 156,10 175,00 184,60 225,80 276,80 290,00 347,00 266,80 303,80 365,60Start intensity (with soft starter) A 69,96 85,68 113,60 125,40 139,20 152,40 185,40 198,10 203,40 228,00Refrigerant Type R410ANumber of refrigeration circuits 2 2 2 2 2 2 2 2 2 2 CompressorsType ScrollNumber 2 2 2 2 2 2 2 4 4 4Mounting type Single Tandem
Capacity steps % 0/50/100 0/50/100 0/50/100 0/50/100 0/50/100 0/50/100 0/50/100 0/25/50/75/100
0/25/50/75/100
0/25/50/75/100
Crankcase heater W 2 x 70 2 x 70 2 x 70 2 x 70 2 x 70 2 x 70 2 x 120 4 x 70 4 x 70 2 x 70 - 2 x 120
Indoor coilType Copper tubes & aluminum finsNumber of rows 3 3 4 3 4 4 4 4 6 6Front surface m² 1,50 1,80 2,25 2,25 3,24 3,24 3,24 3,24 3,24 3,24Indoor fan(s) - EC typeType Backward curved centrifugalNumber 1 1 2 2 2 2 2 2 2 2
Airflow rateMinimum m3/h 7.760 9.200 11.440 14.000 15.600 17.200 20.400 24.000 25.400 27.500Nominal m3/h 9.700 11.500 14.300 17.500 19.500 21.500 25.500 28.000 30.000 32.000Maximum m3/h 11.640 13.800 17.160 21.000 23.400 25.800 30.600 33.600 36.000 38.400
Motor power kW 3,5 5,7 5,8 7 7 11,4 11,4 13,5 13,5 13,5Outdoor coilType Copper tubes & aluminum finsNumber of rows 2 2 3 2 3 3 3 2 3 3Front surface m² 0,76 1,01 1,01 1,50 1,50 1,50 1,50 2,70 2,70 2,70Outdoor fansType AxialNumber 2 2 2 2 2 2 2 4 4 4Diameter mm 630 710 710 800 800 800 800 800 800 800Airflow rate Nominal m3/h 9.800 13.000 13.000 20.000 20.000 20.000 20.000 15.500 15.500 20.500Motor power kW 0,62 0,94 0,94 1,65 1,65 1,65 1,65 0,84 0,84 1,65Sound levelsSound power level (lwo) - outside dB(A) 80 83 80 81 85 87 91 91 92 94Sound power level (lwi) - in supply duct dB(A) 87 94 89 90 91 95 100 91 92 88Dimensions and Weight
LengthTotal mm 3.250 3.250 3.250 3.740 3.740 3.740 3.740 5.505 5.505 5.505Floor mm 2.895 2.895 2.895 3.295 3.295 3.295 3.295 5.050 5.050 5.050
Width mm 2.030 2.030 2.030 2.285 2.285 2.285 2.285 2.285 2.285 2.285Height mm 1.800 1.800 1.800 2.110 2.110 2.110 2.110 2.110 2.110 2.110Weight (without option) kg 1.085 1.155 1.225 1.470 1.685 1.805 1.855 2.350 2.555 2.705
1 Following EN 14511 2018. 2 Following EN 14825 2017. 3 Following COMMISSION REGULATION (EU) No2016/2281 for air to air Rooftops (see page 162 for more information)
Technical features
systemair 169
ROOF
TOPS
AC SELECTSmart & User-friendly
The NEW Air Conditioningselection programhttps://acselect.systemair.com
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
New
St. Petersburg Kirov State TechnicalUniversity of Forest, Russia• Air Handling Unit DV Comapct, SysTemp ST OPA 071 with TMC
100100101010001011
0010111DATA CENTRES Slovakia
• 6 unit ST UPA 141b + TMC 19
170 systemair
CLOSE CONTROL UNITS
Efficiency and energy saving!
The wide range of models and accessories enables an optimal configuration of the air conditioning system. The minimum dimensions of the plan and the possibility of modulating operation for all components allow the development of solutions tailored to the real needs of the infrastructure, as well as ensuring future expansion without high additional costs.Close Control units are designed to meet the requirements of environmentally sustainable development.
systemair 171
CLOS
E CO
NTRO
L UNI
TS
ON 100% ON 100% STAND BY
ON 60% ON 60% ON 60%
ON 100% STAND BY
ON 60% ON 60%
Smart NetThe intelligent local network
Smart Net
DUTY / STAND-BY
The units of the SysTemp close control air conditioning range are equipped with an innovative control system in a local network (LAN) which allows them to be managed and serviced more easily while improving operational safety.
Active distribution of workloadThe innovative Smart Net system allows the concept of local network to be revolutionized. Taking advantage of the modula-tion capabilities of its components, this system makes it possible to actively share the workload among all the units in the local network.Compared to the latent redundancy Duty / Stand-by (n+1 or n+n) system, where the backup units were stationary waiting for the onset of a problem, the Smart Net system allows the units con-nected to the network to be kept always active the Smart Net system allows the units to work in unison to monitor thermo-hy-grometric conditions and air pressure, ensuring there are no “hot spots” due to inactive units.
Efficiency and energy savingThanks to the distribution of workload, system efficiency can be increased by partialising the request to the main components such as fans, compressors, electric batteries and humidifiers.This partialisation directly translates into an energy saving of up to 60% compared to redundant-type networks (n+1 or n+n). Indeed, instead of having active units working at 100% of their performance while one or several machines are stationary, the Smart Net system allows the entire group of units to operate at 50 or 60% of the their maximum load.
A safe and reliable networkIn the Smart Net system, each unit is able to take control of the local network even if communication among units is defective (broken or damaged cable), or in the case of shutdown of one of the units.
172 systemair
Close control units
SysTemp P Direct expansion 7-100 kWChilled water 10-160 kWPage 174
SysTemp G Direct expansion 50-100 kWChilled water 43-170 kWPage 178
TMC 5-116 kWPage 182
SysTemp R Direct expansion 8-30 kWChilled water 20-35 kWPage 180
systemair 173
CLOS
E CO
NTRO
L UNI
TS
174 systemair
The range at a glance
Very high EER (Energy Efficiency Ratio) Limited footprint Dark gray RAL 7024 metal structure Panels with thermo-acoustic insulation Electrical panel complete with control and safety
devices SySmart control microprocessor with LCD graphic
display G4-class efficiency air filters with dirty filter alert Return air temperature sensor Supply air temperature sensor Electronic EC fans R410A scroll compressors Electronic expansion valves with SysDrive system Three-way control valves Unit shutdown system for the presence of fire RS485 Modbus® RTU and TCP/IP slave card Check valves on the supply and liquid pipes
SysTemp PDirect Expansion and Chilled WaterClose control units
7-100 kW Direct ExpansionChilled water10-160 kW
The P Series close control air conditioners have constructional and operating characteristics suitable for environments where thermal loads of a sensitive nature prevail.
Although optimised for data centers, the technical characteris-tics of the P series make these units suitable for various types of special applications, such as metrology laboratories, TV pro-duction studios, recording and conservation rooms for musical instruments, museums and archives, control rooms in power stations and railway junctions. In addition, their application proves ideal for various industrial sectors: optics, electronics, electromedical equipment, production of electrical or electronic equipment, production of musical instruments, etc.
Equipment
Direct expansion: Brushless DC compressors with inverter regulation Power supply line for remote condenser Power supply line with speed regulator for remote
condenser Condensing regulation with 0-10V signal for remote
condenser with EC fans LAC valve for operation with low temperature outside
air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing
temperature control valve
Chilled water: Three-way control valves Inlet and outlet water temperature sensors Energy valve kit
Other accessories: Heating accessories Humidification accessories BACnet IP and MS/TP serial communication cards F7 / M5-class efficiency air filters Supply air fan control Air flow interception damper Fire/smoke detection system Condensate drain pump Local network management Water detection system Power supply accessories Packing options Air distribution accessories
Advantages
Temperature and humidity close control.
A high delivered cooling capacity to footprint ratio, which makes it easier to design the environments to be air conditioned.
Very high values of energy efficiency, which trans-late into lower CO2 emissions into the environment, and in particularly low operating costs.
High flexibility of use, thanks to the wide range of accessories which can be selected.
DATA CENTRES
100100101010001011
0010111
systemair 175
CLOS
E CO
NTRO
L UNI
TS
SySmart Control New generation electronic control system
High connectivityThanks to the integrated RS485 Modbus® card and BACnet, Lon-Works® and SNMP gateway interfac-es, easily and quickly interfacing with supervision systems and building management systems (BMS) is pos-sible.
InnovativeThanks to the control via Mod-bus® Master protocol, all key components of the unit are con-tinuously supervised, with over 50 different variables that ensure the real-time monitoring of all operating cycles.
SimpleThanks to the wide Full Graphic LCD display, access to all operating parameters is guaranteed in a sim-ple and intuitive way.
FlexibleWith digital inputs and outputs which, depending on the needs of the sys-tem, can be configured with specific features designed to simplify the in-stallation and use of the unit.
EfficientWith specific features dedicated to energy savings and the optimized management of all the unit direct ex-pansion and chilled water operating cycles.
ReliableThanks to predictive safety systems designed to prevent unwanted shut-down failures, and to an advanced system for recording alarms and hours of operation.
Operational safetyThe SysDrive system actively man-ages 10 different safety function, designed to provide high opera-tional safety.
• Low evaporation pressure and high condensing pressure of the circuit
• Low operating pressure and high operating pressure of the circuit
• Compressor low compression ratio
• Low and high superheat values
• Low and high de-superheat values
• Refrigerant high discharge tem-perature
Active control of operating conditionsThe SysDrive system allows the dis-play and monitoring of the operating conditions of the whole cooling cycle, from both the local display and the supervision systems as well as build-ing management systems (BMS).Using suitable probes and pressure transducers helps to detect pressure and temperatures of an evapora-tor, compressors, a condenser and suction and discharge lines. Thanks to these figures, superheat, de-super-heat and subcooling of the refrigerant are calculated.If a DC inverter compressor is installed, actual speed and electri-cal power consumption will also be monitored.
SysDrive Cooling circuit advanced management system
Air Conditioners with downflow air supply
ST UPU: Chilled water air conditioners with downflow air supply
Notes:(1) Performance refers to: R410A refrigerant; con-
densing temperature 45°C; incoming air 24°C-45%Rh; water 7/12°C; external static pres-sure 30 Pa. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load.
(2) EER (Energy Efficiency Ratio) = total cooling capac-ity / compressors power consumption + fans pow-er consumption (air cooled condensers excluded).
(3) Sound levels at a 2 m distance, in a free field, in accordance with UNI EN ISO 3744:2010.
Standard version with top air intake and downflow air supply, with stand for raised floors.
Version with top air intake and front air supply through air distribution plenum with adjustable grilles.
Version with top air intake and front air supply through front panel.
ST UPU 10 20 30 50 80 110 160 220PerformanceTotal cooling capacity 1 kW 9,9 17,2 30,0 41,0 65,4 80,0 110,0 160,0
Sensible cooling capacity kW 9,3 14,9 27,8 36,2 61,8 73,0 99,7 146,0EER 2 32,1 24,6 27,0 20,9 23,2 19,8 24,4 19,8
Air flow rate m3/h 2.200 3.200 7.000 8.000 16.000 18.000 24.000 36.000Noise level 3 dB(A) 51 57 57 62 62 63 63 66
Dimensions and weightsWidth mm 750 750 860 860 1.750 1.750 2.640 3.496
Depth mm 601 601 872 872 871 871 871 871Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990
Net weight kg 115 130 225 220 340 360 620 720Two Sources
ST UPA 71 141 211 251 301 302 361 422 461 512 662 852 932PerformanceTotal cooling capacity 1 kW 8,1 14,7 21,0 26,2 32,2 29,8 37,7 43,1 47,7 54,4 67,3 85,1 93,6Sensible cooling capacity kW 7,8 12,9 21,0 25,2 29,9 28,9 37,7 43,1 46,7 52,0 66,2 73,9 85,7EER 2 3,69 3,31 3,23 3,21 3,09 3,24 3,46 3,37 3,55 3,37 3,15 3,20 3,55Air flow rate m3/h 2.200 3.200 7.000 7.000 8.000 8.000 14.000 14.000 14.000 14.000 18.000 18.000 21.000Noise level 3 dB(A) 51 57 57 58 60 59 59 59 59 59 63 63 62Dimensions and weightsWidth mm 750 750 860 860 1.410 1.410 1.750 1.750 1.750 1.750 2.300 2.300 2.640Depth mm 601 601 872 872 872 872 871 871 871 871 871 871 871Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990Net weight kg 150 205 260 285 365 390 440 485 450 500 645 665 705Free CoolingTwo Sources
ST UPA: Direct expansion air conditioners with downflow air supply and aircooled or watercooled condensers
176 systemair
ST OPA 71 141 211 251 301 302 361 422 461 512 662 852 932PerformanceTotal cooling capacity 1 kW 8,1 14,7 21,0 26,2 32,2 29,8 37,7 43,1 47,7 54,4 67,3 85,1 93,6Sensible cooling capacity kW 7,8 12,9 21,0 25,2 29,9 28,9 37,7 43,1 46,7 52,0 66,2 73,9 85,7EER 2 3,78 3,42 3,29 3,26 3,17 3,33 3,54 3,43 3,61 3,42 3,26 3,29 3,59Air flow rate m3/h 2.200 3.200 7.000 7.000 8.000 8.000 14.000 14.000 14.000 14.000 18.000 18.000 21.000Noise level 3 dB(A) 51 57 56 57 58 58 58 58 58 59 61 61 61Dimensions and weightsWidth mm 750 750 860 860 1.410 1.410 1.750 1.750 1.750 1.750 2.300 2.300 2.640
Depth mm 601 601 872 872 872 872 871 871 871 871 871 871 871Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990
Net weight kg 150 205 260 285 365 390 440 485 450 500 645 665 705Free CoolingTwo Sources
Air Conditioners with upflow air supply
ST OPA: Direct expansion air conditioners with upflow air supply and aircooled or watercooled condensers
ST OPU: Chilled water air conditioners with upflow air supplyNotes:(1) Performance refers to: R410A refrigerant; con-
densing temperature 45°C; incoming air 24°C-45%Rh; water 7/12°C; external static pres-sure 30 Pa. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load.
(2) EER (Energy Efficiency Ratio) = total cooling capac-ity / compressors power consumption + fans pow-er consumption (air cooled condensers excluded).
(3) Sound levels at a 2 m distance, in a free field, in accordance with UNI EN ISO 3744:2010.
ST OPU 10 20 30 50 80 110 160 220PerformanceTotal cooling capacity 1 kW 9,9 17,2 30,0 41,0 65,4 80,0 110,0 160,0
Sensible cooling capacity kW 9,3 14,9 27,8 36,2 61,8 73,0 99,7 146,0EER 2 38,3 31,8 30,0 24,5 24,8 24,2 29,3 24,2
Air flow rate m3/h 2.200 3.200 7.000 8.000 16.000 18.000 24.000 36.000Noise level 3 dB(A) 51 57 56 60 61 62 62 65
Dimensions and weightsWidth mm 750 750 860 860 1750 1750 2640 3496
Depth mm 601 601 872 872 871 871 871 871Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990
Net weight kg 115 130 225 220 340 360 620 720Two Sources
Standard version with front air intake and upflow air supply.
Version with front air intake and supply, through air distribution plenum with adjustable grilles.
Version with air intake from the bottom, stand for raised floor, blind front panel and upflow air supply.
systemair 177
CLOS
E CO
NTRO
L UNI
TS
178 systemair
The range at a glance
Very high EER (Energy Efficiency Ratio) Limited footprint Dark gray RAL 7024 metal structure Panels with thermo-acoustic insulation Electrical panel complete with control and safety
devices SySmart control microprocessor with LCD graphic
display G4-class efficiency air filters with dirty filter alert Return air temperature sensor Supply air temperature sensor Electronic EC fans R410A scroll compressors Electronic expansion valves with SysDrive system Three-way control valves Unit shutdown system for the presence of fire RS485 Modbus® RTU and TCP/IP slave card Check valves on the supply and liquid pipes
SysTemp GDirect Expansion and Chilled Water Close control units
G series close control air conditioners have constructional and operating characteristics suitable for meeting the design criteria of the latest generation data centers.When designing air conditioning systems for large data centers, the need for electrical cable housing and the enormous air volumes required to cool down the servers have made it es-sential to increase the height of raised floors up to the current 550/1,000-millimeter level. A large space below the air condi-tioner for the installation of an adjustable stand has thus created. It was therefore decided to use this large space to house supply fans.Without increasing the footprint of the machine, and only exploiting space where it is provided, great advantages have been obtained.
Equipment
Direct expansion: Brushless DC compressors with inverter regulation Power supply line for remote condenser Power supply line with speed regulator for remote
condenser Condensing regulation with 0-10V signal for remote
condenser with EC fans LAC Valve for operation with low temperature outside
air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing
temperature control valve
Chilled water: Three-way control valves Inlet and outlet water temperature sensors Energy valve kit
Other accessories: Heating accessories Humidification accessories BACnet IP and MS/TP serial communication cards M5-class efficiency air filters Supply air fan control Air flow interception damper Fire/smoke detection system Condensate drain pump Local network management Water detection system Power supply accessories Packing options Air distribution accessories
Advantages
With the same air conditioner footprint, it has been possible to increase the front section of the coil by about 40-50% by reducing the pressure drop on the air side, and thus the fan energy consumption.
Increasing the size of the air filters installed upstream of the cold coil allows a significant reduction in load losses and replacement frequency for maintenance.
Increased efficiency of the fans which, installed in the stand, expel treated air horizontally and com-pletely unobstructed.
50-100 kW Direct ExpansionChilled water43-170 kW
DATA CENTRES
100100101010001011
0010111
systemair 179
CLOS
E CO
NTRO
L UNI
TS
Air Conditioners with downflow air supply
ST UGA: Direct expansion air conditioners with downflow air supply and aircooled or water cooled condensers
ST UGA 461 612 932PerformanceTotal cooling capacity 1 kW 43,6 55,5 82,6
Sensible cooling capacity 1 kW 36,5 43,4 71,0EER 2 3,51 2,92 3,41Air flow rate m3/h 9.000 10.000 19.000Noise level 3 dB(A) 54 56 55Dimensions and weightsWidth mm 1.490 1.490 2.390Depth mm 921 921 921Height mm 1.990+550Net weight kg 500 500 720
Notes:1 Performance refers to: R410A refrigerant; condensing temperature 45°C; incoming air 32°C-30%Rh;water 15/20°C; external static pressure 30 Pa, ventilated plenum,
height 1000 mm. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load.2 EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded).3 Sound levels at a 2 m distance, in a free field, in accordance with UNI EN ISO 3744:2010.
Standard version for data center perimetral installation: The height of the raised floor must be at least 550 mm.
Standard version for data center perimetral installation with raised floor height less than 550 mm. In this case the stand, having a fixed height of 550 mm provided with side clos-ing panels, must be installed above the floor. However, please make sure that the ceiling height allows good air intake.
Version for installation outside the data center, with no raised floor and rear supply line. In this case the stand, having a fixed height of 550 mm, is provided with side closing panels and rear supply grilles. The in-stallation of a plenum with a rear air intake system is optional, in the absence of a duct system.
ST UGU: Chilled water air conditioners with downflow air supply
ST UGU 70 150 230 300PerformanceTotal cooling capacity 1 kW 56,9 98,1 153,1 190,5
Sensible cooling capacity 1 kW 46,6 83,6 130,4 172,3EER 2 51,2 46,9 52,8 40,2Air flow rate m3/h 9.000 18.000 28.000 40.000Noise level 3 dB(A) 54 56 58 60Dimensions and weightsWidth mm 1.320 1.840 2.740 4.020Depth mm 921 921 921 921Height mm 1.990+550Net weight kg 400 620 930 1.250
180 systemair
The range at a glance
Very high EER (Energy Efficiency Ratio) Limited footprint Dark gray RAL 7024 metal structure Panels with thermo-acoustic insulation Front and rear accessibility for easy maintenance Cooling, electric and water top/bottom connections Electrical panel complete with control and safety
devices SySmart control microprocessor with LCD graphic
display G2-class efficiency air filters with dirty filter alert Return air temperature sensor Supply air temperature sensor Electronic EC fans Brushless DC compressors with R410A inverter
regulation Electronic expansion valves with SysDrive system Three-way control valves Unit shutdown system for the presence of fire RS485 Modbus® RTU and TCP/IP slave card Check valves on the supply and liquid pipes
SysTemp RDirect Expansion and Chilled Water Close control units
R series close control air conditioners are built and sized in such a way that they can be installed alongside data center racks. In air conditioning systems for large data centers, the adoption of the following design concepts has in fact become an established custom:
The racks containing servers are increasingly positioned ac-cording to the Hot Aisle and Cold Aisle layout.
Air temperatures are allowed to rise up to 30-35°C in the hot aisle and 20-25°C in the cold one, with very low humidity (never above 30%).
Server performance is increasingly on the rise, while server sizes are increasingly reduced. As a result, many more servers can be installed in a rack, so some of these racks can be elim-inated as they are empty. At the same time, heat dissipation increases, thereby requiring more power from air conditioners. R series air conditioners are designed and built so as to fit into this plant layout perfectly.
Equipment
Direct expansion: Power supply line for remote condenser Power supply line with speed regulator for remote
condenser Condensing regulation with 0-10V signal for remote
condenser with EC fans LAC Valve for operation with low temperature outside
air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing
temperature control valve
Chilled water: Three-way control valves Inlet and outlet water temperature sensors Energy valve kit
Other accessories: Heating accessories Humidification accessories BACnet IP and MS/TP serial communication cards G4-class efficiency air filters Supply air fan control Fire/smoke detection system Condensate drain pump Local network management Water detection system Power supply accessories Packing options
Advantages
They exploit the space left free from racks and allow cold air to be distributed as close as possible to serv-ers, that is, where heat is generated.
They feature rear intake from the hot aisle and front supply to the cold aisle with a horizontal flow. The horizontal flow reduces internal pressure drop, with a consequent reduction in the power draw of the fan.
8-30 kW Direct ExpansionChilled water20-35 kW
DATA CENTRES
100100101010001011
0010111
systemair 181
CLOS
E CO
NTRO
L UNI
TS
Air Conditioners with horizontal air supply
ST HRA: Direct expansion air conditioners with horizontal supply
ST HRA 121 201 231 361PerformanceTotal cooling capacity 1 kW 10,9 20,9 21,5 34,4
Sensible cooling capacity kW 10,9 19,3 21,0 33,6EER2 3,54 3,35 3,50 3,69
Air flow rate m3/h 3.200 3.600 5.400 6.600Noise level 3 dB(A) 51 53 50 53
Dimensions and weightsWidth mm 300 300 600 600
Depth mm 1.200 1.200 1.222 1.222Height mm 1.975 1.975 1.985 1.985
Net weight kg 200 215 215 215Free CoolingTwo Sources
Notes:1 Performance refers to: R410A refrigerant; condensing temperature 45°C; incoming air 30°C-30%Rh; water 14/20°C; external static pressure 30 Pa. The declared
performance does not take into account the heat generated by fans, which must be added to the system thermal load.2 EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded).3 Sound levels at a 2 m distance, in a free field, in accordance with UNI EN ISO 3744:2010.
Version for "in row" installation with front and side air supply
ST HRU 20 40PerformanceTotal cooling capacity 1 kW 20,1 30,6
Sensible cooling capacity kW 20,1 30,6EER2 19,0 24,9
Air flow rate m3/h 5.600 9.000Noise level 3 dB(A) 53 61
Dimensions and weightsWidth mm 300 600
Depth mm 1.200 1.222Height mm 1.975 1.985
Net weight kg 120 190Two Sources
ST HRU: Chilled water air conditioners with horizontal supply
182 systemair
The range at a glance
Versions for horizontal and vertical installation and with V-shaped structure.
Turbocoil heat exchangers made of hot dipped galva-nized metal sheet with copper tubes expanded into aluminium fins
Casing made of galvanised steel, powder coated Epoxy-Polyester RAL 9003 resistant to corrosion
High-efficiency, low-consumption motors, statically and dynamically balanced, with permanently greased bearings, in-built overheat protection and integrated protection grilles
Valid for units with direct expansion circuit only.
Equipment
Air-cooled condenser and dry cooler
Latest generation EC fans for high-energy savings, re-duced noise levels and better regulation of the number of revolutions
Fins coated with ALUPAINT for better aluminium corro-sion protection (ACC only)
Configuration with multiple circuits or sub cooling cir-cuits
Vibration-damping kits Electrical panel complete with control, safety devices
and fans wiring The Whisperer silencers Dry and Spray system Water Spray System.
TMCRemote condensers and dry coolers for Close control units
Advantages
Air cooled condensers and dry coolers which can be matched to close control air conditioners, or meet any system requirement.
EC fans for high-energy savings, reduced noise levels and better regulation of the number of revolutions
5-116 kW Remote condensersDry coolers11-120 kW
DATA CENTRES
100100101010001011
0010111
systemair 183
VERT
ICAL
AIR
CO
NDIT
IONE
RS
VERTICAL AIR CONDITIONERS
XARAir cooled models 12,3-55 kW R407C Scroll compressor
Page 184
HFC
CX - XAOWater cooled models 8,0-45,7 kW R407C Scroll compressor
Coaxial heat exchanger
Page 186
HFC
Product Size Capacity Airflow(m3/h)
Sound pressuredB(A)
Dimensions (LxHxW) mm
Air Cooled Models
X1200.AR 12,3 kW 2.000 51 890 x 1.540 x 430
X1900.AR 16,2 kW 3.200 56 1.000 x 1.735 x 500
X2450.AR 19,8 kW 4.500 59 1.300 x 1.840 x 600
X3250.AR 29,0 kW 5.800 65 1.530 x 1.830 x 600
X4650.AR 38,9 kW 9.000 61 1.715 x 1.970 x 790
X6450.AR 55,0 kW 12.000 69 1.980 x 1.970 x 790
Water Cooled Models
CX25 8,0 kW 1.500 52 800 x 1.280 x 407
X1200.AO 15,0 kW 2.000 51 890 x 1.540 x 430
X1900.AO 18,0 kW 3.200 55 1.000 x 1.735 x 500
X2450.AO 23,0 kW 4.500 58 1.300 x 1.840 x 600
X3250.AO 32,4 kW 5.800 64 1.530 x 1.830 x 600
X4650.AO 45,7 kW 9.000 60 1.715 x 1.970 x 790
Quick selection guide
VERT
ICAL
AIR
CO
NDIT
IONE
RS
184 systemair
XARVertical air conditionersAir cooled models
UC - Outdoor unit(accessory)
Minimum temperature
Indoor temperatureThi +13 °CTsi +17 °C
Outdoor temperatureTse +19 °CTse -10 °C *
Maximum temperature
Indoor temperatureThi +22 °CTsi +32 °C
Outdoor temperature Tse +47 °C
* With “All seasons kit” optionThi : Wet bulb indoor temperatureTsi : Dry bulb indoor temperatureTse : Dry bulb outdoor temperature
Advantages
Robust unit with mechanical control Easy installation and maintenance Small footprint casing Different air intake and discharge configurations Heating systems available (options)
INDUSTRY
R407C
Scroll compressor
HFC
The range at a glance 6 sizes Cooling capacities from 12,3 to 55 kW Configuration : Split system
UC outdoor condensing unit available as an accessory Air intake : On the front grilles or on the rear with duct Discharge : Vertical with or without duct or horizontal
with a plenum Temperature controlled by thermostat 2 heating options : integrated electric or hot water coils
Equipment Refrigerant circuit with an hermetic type compressor
and an evaporator composed of copper tubes with aluminium fins
Panels and intake grilles made of profiled sheet steel covered with enamel finish, baked in a high temperature oven Electrical & refrigerant connections on the right or left side Thermal and acoustic insulation of the unit 3-speed fan motor Integrated unit control M1 filters Electrical, refrigeration and thermal protection devices
Operating limits (for standard unit)
Accessories & OptionsAir distribution duct frameElectric heatersFresh air intakeFront air distribution plenumHigh Ventilation (provided as standard for sizes 1200 and 1900)
Hot water coilON/OFF switch and room thermostatPipe link 10m - 1 circuitRemote fault reportingSet of female valves (mandatory)Total rear intake duct frameUC outdoor condensing unit
DATACENTERS
1010011010101110001100 000111
12,3-55 kW
systemair 185
VERT
ICAL
AIR
CO
NDIT
IONE
RS
XAR X1200.AR X1900.AR X2450.AR X3250.AR X4650.AR X6450.ARCooling capacity 1
Nominal cooling capacity W 12.300 16.200 19.800 29.000 38.900 55.000Nominal cooling capacity BTU/hr 42.000 55.300 67.600 99.000 137.000 189.200AirflowNominal treated air m3/h 2.000 3.200 4.500 5.800 9.000 12.000Min./max. treated air m3/h 1.500/2.500 2.500/3.800 3.600/5.400 4.600/7.000 7.200/10.800 9.500/14.500Nominal fresh air (with accessory) m3/h 180 285 420 500 1.300 1.650Available static pressure 2
Standard unit daPa 0/13 0/21 0/20 0/25 0/23 0/29Sound pressure - indoor unit 3
Normal speed dB(A) 51 56 59 65 61 69Electrical dataNominal voltage 400V/3N~/50HzVoltage range V 360/440 360/440 360/440 360/440 360/440 360/440Total power input 1 W 4.808 8.076 8.900 12.630 16.950 24.000Power input ventilation : Min./Max. - standard unit W 260/510 380/580 500/1.100 700/1.800 1.600/2.400 3.100/4600
DimensionsDimensions (LxWxH) mm 890x430x1540 1.000x500x1.735 1.300x600x1.840 1.530x600x1.830 1.715x790x1.970 1.980x790x1.970
1 International standard ISO 51.51 conditions.27°C/19°C wet bulb - Outside air : 35°C/24°C wet bulb.Wasted water : inlet + 15°C - Recycled water inlet/outlet : 30°C/35°C.2 Pressure in air flow range at nominal voltage, without accessories.3 Total sound pressure dB(A) (4m) under nominal conditions in a room of 1000m3 (reverberation 0.83s).4 Total sound pressure dB(A) (4 m) under nominal conditions in free field on reflecting surface.
UC Outdoor condensing unit (accessory) UC34 UC54 UC74 UC104Compatible with / number of necessary outdoor unit(s) X1200.AR / 1 X1900.AR / 1 X2450.AR / 1
X4650.AR / 2X3250.AR / 1 X6450.AR / 2
Airflow m3/h 8.600 7.600 8.550 14.000Power input W 530 611 611 1.222Sound pressure 4 dB(A) 52 53 56 56
DimensionsDimensions (LxWxH) mm 885x825x840 885x825x840 1.141x885x840 1.546x885x840
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
Technical features
186 systemair
Minimum temperature
Maximum temperature
Air temperature at evaporator inlet
WB +15 °C +23 °CDB +21 °C +32 °C
Water temperature +10 °C +34 °C
DB : Dry bulbWB : Wet bulb
CX - XAOVertical air conditionersWater cooled models
Advantages
Robust unit with mechanical control Easy installation and maintenance Small footprint casing Different air intake and discharge configurations Heating systems available (options)
R407C
Scroll compressor
HFC
Coaxial heat exchanger
The range at a glance 6 sizes Cooling capacities from 8,0 to 45,7 kW Configuration : Monobloc system Wasted or Recycled water operation Air intake : On the front grilles or on the rear with duct Discharge : Vertical with or without duct or horizontal
with a plenum Temperature controlled by thermostat 2 heating options : integrated electric or hot water coils
(hot water coil not available for CX25)
Equipment Complete refrigerant circuit with an hermetic type com-
pressor, an evaporator composed of copper tubes with aluminium fins, a coaxial condenser with counter flow circulation (equipped with finned copped tube in a steel cover) and a pressostatic valve.
Panels and intake grilles made of profiled and a sheet steel covered with enamel finish, baked in a high temperature oven Electrical, water & refrigerant connections on the right or
left side Thermal and acoustic insulation of the unit 3-speed fan motor (2-speed fan motor for CX25) Integrated unit control M1 filters Electrical, refrigeration and thermal protection devices
Operating limits (for standard unit)
Accessories & OptionsAir distribution duct frameElectric heatersFresh air intakeFront air distribution plenumHigh Ventilation (provided as standard for CX25, X1200.AO and X1900.AO)
Hot water coilON/OFF switch and room thermostatRemote fault reportingSum heating resistanceTotal rear intake duct frame
8,0-45,7 kW
INDUSTRY DATACENTERS
1010011010101110001100 000111
systemair 187
VERT
ICAL
AIR
CO
NDIT
IONE
RS
XAO X1200.AO X1900.AO X2450.AO X3250.AO X4650.AOCooling capacity 1
Nominal cooling capacity W 15.005 18.000 23.000 32.400 45.700Nominal cooling capacity BTU/hr 51.200 61.400 78.500 110.550 157.200AirflowNominal treated air m3/h 2.000 3.200 4.500 5.800 9.000Min./max. treated air m3/h 1.500/2.500 2.500/3.800 3.600/5.400 4.600/7.000 7.200/10.800Nominal fresh air (with accessory) m3/h 180 285 420 500 1.300Available static pressure 2
Standard unit daPa 0/13 0/21 0/20 0/25 0/23Sound pressure 3
Normal speed dB(A) 51 55 58 64 60Electrical dataNominal voltage V/~/Hz 400/3N/50Voltage range V 360/440 360/440 360/440 360/440 360/440Total power input 1 W 4.843 6.616 7.100 9.800 13.900Power input ventilation : Min./Max. - standard unit W 260/510 380/580 500/1.100 700/1.800 1.600/2.400
Water circuit 1
Wasted water - Flow L/h 914 950 1.000 1.700 2.800Wasted water - Pressure drop kPa 37 30 22 35 18Recycled water - Flow L/h 3.161 3.050 3.500 5.780 8.300Recycled water - Pressure drop kPa 80 65 45 40 56DimensionsDimensions (LxWxH) mm 890x430x1.540 1.000x500x1.735 1.300x600x1.840 1.530x600x1.830 1.715x790x1.970
CX CX25Cooling capacityNominal cooling capacity (Water : 18 °C - Air : 19 °C Wet Bulb) W 8.000
Nominal cooling capacity (Water : 18 °C - Air : 19 °C Wet Bulb) BTU/hr 27.300
AirflowNominal treated air m3/h 1.500Motor power input W 245Electrical dataPower supply V/~/Hz 230/1/ 50 400/3N/ 50Cooling + ventilationNominal input A 12,28 5,28Input Max. A 14,85 6,38aM fuse A 16 8ASE/VDE fuse A 16 10Electric heater + ventilationNominal input A 26 9,6Input Max. A 31 11,61aM fuse A 32 12ASE/VDE fuse A 35 16DimensionsDimensions (LxWxH) mm 800x407x1.280
Technical features
Technical documentationComplete documentation available
on www.systemair.com and the app MEDIA CENTER by Systemair
1 International standard ISO 51.51 conditions.27°C/19°C wet bulb - Outside air : 35°C/24°C wet bulb.Wasted water : inlet + 15°C - Recycled water inlet/outlet : 30°C/35°C.2 Pressure in air flow range at nominal voltage, without accessories.3 Total sound pressure dB(A) (4m) under nominal conditions in a room of 1000m3 (reverberation 0.83s).
188 systemair
Hydronic systems: HPT*
Hydronic systems: VKB*
VKBChiller/heat pump
Device
Chiller/heat pump
DeviceHPT
* example of a plant
* example of a plant
systemair 189
HYDR
OKIT
HYDROKIT
systemair 189
HYDR
OKIT
Satisfy all your needs!
The broad range of pump-tank combinations makes it possible to meet all the requirements. The range of stand-alone hydronic kits provides a flexible choice of inertial tanks and circulating pumps to be combined with our hydronic chiller and heat pump units.
HPTPage 190
VKBPage 192
VKB
Chiller/heat pump
Device
190 systemair
The range at a glance
48 sizes Structurally equipped of tank, expansion tank, pump,
filter, control valves, electrical box 6 volumes of the storage tank from 300 to 2.500
litres 14 different pumps models Two versions:
with one or two water pumps Anti freezer protection
HPT Hydrokit
1 Tank
2 Circulator
3 Expansion vessel
4 On/Off valve
5 Automatic ventilation system
6 Pressure relief valve
7 Filling tap
8 Automatic filling unit
9 Switchboard
10 Control valve (version with 2 pumps)
11 Drain
12 Anchoring point (4-6 holes m12/ ø14)
13 Inlet power grid
14 Water outlet
15 Water inlet
6
19
8
3
14
1312 4
5
210
11
15
7
Sistemi IdroniciHPT: componenti
Componenti
1 Serbatoio
2 Circolatore
3 Vaso d’espansione
4 Valvola on-off
5 Sistema di ventilazione automatica
6 Valvola di sfiato aria
7 Rubinetto di riempimento
8 Gruppo di riempimento automatico
9 Quadro elettrico
10 Valvola di ritegno (versione con 2 pompe solo)
11 Scarico
12 Punti d’ancoraggio (n. 4-6 holes M12/ø14)
13 Ingresso rete elettrica
14 Mandata all’impianto
15 Ritorno dall’impianto
Systemair | 5
Advantages
Designed to reduce the production time of condition-ing and cooling systems
The broad range of pump-tank combinations makes it possible to meet all requirements
Numerous versions with a single or a double pump and with tanks with a capacity from 300 to 2.500 lt
systemair 191
HYDR
OKIT
Pumpmodel
Tank volume Wsb1 Wsb2 F.L.I.F.L.A. F.L.A.
Q MIn H Max Q Max H Min Ve(400/3/50) (230/3/50)
lt kg kg kW A A m3/h кPа m3/h кPа lt
A300 186 216 1,1 2,5 4,3 6 188 24 83 25500 208 238 1,1 2,5 4,3 6 188 24 83 25
В300 188 220 1,5 3,2 5,5 6 220 24 122 25500 210 242 1,5 3,2 5,5 6 220 24 122 25
С300 188 220 1,5 3,4 5,9 10 170 45 61 25500 210 242 1,5 3,4 5,9 10 170 45 61 25
D300 191 225 2,2 4,8 8,3 10 230 45 112 25500 213 247 2,2 4,8 8,3 10 230 45 112 25
E300 194 231 3 5,6 9,7 10 230 45 112 25500 215 253 3 5,6 9,7 10 248 45 137 25
F
750 341 428 3 6,2 10,8 30 191 72 103 251.000 364 455 3 6,2 10,8 30 191 72 103 251.500 513 586 3 6,2 10,8 30 191 72 103 2 x 252.500 565 638 3 6,2 10,8 30 191 72 103 3 x 25
G
750 370 485 5,5 11 — 30 308 84 145 251.000 392 512 5,5 11 — 30 308 84 145 251.500 565 696 5,5 11 — 30 308 84 145 2 x 252.500 613 732 5,5 11 — 30 308 84 145 3 x 25
H
750 373 493 5,5 11 — 48 210 108 137 251.000 396 520 5,5 11 — 48 210 108 137 251.500 569 696 5,5 11 — 48 210 108 137 2 x 252.500 617 740 5,5 11 — 48 210 108 137 3 x 25
I
750 377 501 7,5 14,6 — 48 260 120 180 251.000 400 528 7,5 14,6 — 48 260 120 180 251.500 569 696 7,5 14,6 — 48 260 120 180 2 x 252.500 617 740 7,5 14,6 — 48 260 120 180 3 x 25
L
750 377 501 11 21,2 — 48 342 120 249 251.000 400 528 11 21,2 — 48 342 120 249 251.500 569 696 11 21,2 — 48 342 120 249 2 x 252.500 617 740 11 21,2 — 48 342 120 249 3 x 25
M1.500 628 814 15 28,6 — 48 405 138 288 2 x 252.500 680 866 15 28,6 — 48 405 138 288 3 x 25
О1.500 634 826 15 28,6 — 84 330 180 220 2 x 252.500 686 878 15 28,6 — 84 330 180 220 3 x 25
P1.500 646 850 18,5 34,2 — 84 385 216 220 2 x 252.500 698 902 18,5 34,2 — 84 385 216 220 3 x 25
Q1.500 660 878 22 40,3 — 84 475 180 325 2 x 252.500 712 930 22 40,3 — 84 475 180 325 3 x 25
F.L.I. - Full load power.F.L.A. - Full load current.Q Min - Minimum flow. Q Max - Maximum flow.H Min - Minimum pressure.H Max - Maximum pressure.Wsb1 - Shipping weight with pump.Wsb2 - Shipping weight with two pumps.Ve - Expansion tank capacity.PVe - Tank pressure.PS - Maximum operating pressure.T Min - Minimum water temperature.
PVe PS T Minbar bar °C1,5 3 -10
Phisical features
Legend:
192 systemair
The range at a glance
4 sizes: 250 lt, 500 lt, 1000 lt, 1500 lt Structurally equipped of insulated buffer tank, expan-
sion vessel, safety valve, deaerator, fill/drain valve and manometer
VKB Hydrokit
1 Storage tank
2 Fill-up valve
3 Automatic safety valve
4 Drain
5 Supporting structure
6 Expansion vessel
7 Manometer
8 Predisposition for electrical resistance
9 Predisposition for thermostat
Advantages
Designed to significantly reduce the set-up time for the conditioning and cooling devices
The tank, which is hydraulically inserted between the cooling station and the fan-coils, makes the water content in the entire installation increase, by increasing the pause between the shut-dvown of the compressor and the next start-up: the number of start-ups is significantly reduced, which improves the life span and performance of the compressor
The broad range of storage tanks makes it possible to meet every requirement
systemair 193
HYDR
OKIT
Capacity Vessel Vessel calibration Safety valve Couplings W D H A B
lt lt bar bar inch mm mm mm mm mm250 12 1 3 2” 590 750 1600 420 1220
500 18 1,5 3 3” 750 1000 1850 420 1470
1000 25 1,5 3 4” 1100 1100 1850 610 1410
1500 2x25 1,5 3 4” 1200 1200 1950 650 1450
Phisical features
Capacity Dimensions Weight
lt mm kg250 590x750x1600 95,00
500 750x1000x1850 155,00
1000 1100x1100x1850 255,00
1500 1200x1200x1950 313,00
www.systemair.com
| Air cooled Chiller & Heat Pump194
Syst
emai
r · Ju
ly 2
020
· AIR
CO
NDI
TIO
NIN
G CA
TALO
GUE
10GB
· E3
4015
As p
art o
f our
ong
oing
pro
duct
impr
ovem
ent p
rogr
amm
e, o
ur p
rodu
cts
are
subj
ect t
o ch
ange
with
out p
rior n
otic
e. N
on c
ontr
actu
al p
hoto
s.
Systemair srlVia XXV Aprile, 2920825 Barlassina (MB) Italy
Tel. +39 0362 680 1Fax +39 0362 680 693
Systemair AC SASRoute de Verneuil 27570 Tillières-sur-Avre France