www.eurovent-certification.com www.certiflash.com Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers, consultants and building owners require optimal performances and maximum quality. The Aquaforce liquid chillers are designed to meet current and future requirements in terms of energy efficiency and operating sound levels. They use the best technologies available today: - Twin-rotor screw compressor with a variable capacity valve. - Single refrigerant R-134a. - Low-noise generation IV Flying Bird fans made of composite material. - Aluminium micro-channel heat exchangers (MCHE). - Pro-Dialog+ control system. To meet to all environmental and economic requirements, the Aquaforce is available in two versions: One offers an extremely low noise level while at the same time boasting superior energy efficiency. The other offers unequalled energy efficiency to satisfy the most stringent demands of building owners wanting to reduce operating costs to the minimum. This version is also recommended for applications in geographical zones where the air temperature is very high. 30XAS “A” 242-482 Nominal cooling capacity 232-486 kW 50 Hz Features and advantages Very economical operation Extremely high full load and part load energy efficiency: - Eurovent energy efficiency class A to C, in accordance with EN14511-3:2011. - Standardised Eurovent values in accordance with EN 14511-3:2011: EER up to 3.2 and ESEER up to 4. - Twin-rotor screw compressor equipped with a high- efficiency motor and a variable capacity valve that permits exact matching of the cooling capacity to the load. - All aluminium condenser with high-efficiency micro- channels. - Flooded shell-and-tube evaporator to increase the heat exchange efficiency. - Electronic expansion device permitting operation at a lower condensing pressure and improved utilisation of the evaporator heat exchange surface (superheat control). - Economizer system with electronic expansion device for increased cooling capacity
Transcript
Page 1: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

www.eurovent-certification.comwww.certiflash.com

Unit with option 279 (compressor enclosure)

Air-Cooled Liquid Chillers

The 30XAS Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers, consultants and building owners require optimal performances and maximum quality.

The Aquaforce liquid chillers are designed to meet current and future requirements in terms of energy efficiency and operating sound levels. They use the best technologies available today: - Twin-rotor screw compressor with a variable capacity

valve. - Single refrigerant R-134a. - Low-noise generation IV Flying Bird fans made of

composite material. - Aluminium micro-channel heat exchangers (MCHE). - Pro-Dialog+ control system.

To meet to all environmental and economic requirements, the Aquaforce is available in two versions:

One offers an extremely low noise level while at the same time boasting superior energy efficiency.

The other offers unequalled energy efficiency to satisfy the most stringent demands of building owners wanting to reduce operating costs to the minimum. This version is also recommended for applications in geographical zones where the air temperature is very high.

30XAS “A” 242-482Nominal cooling capacity 232-486 kW

50 Hz

Features and advantages

Very economical operation ■ Extremely high full load and part load energy efficiency:

- Eurovent energy efficiency class A to C, in accordance with EN14511-3:2011.

- Standardised Eurovent values in accordance with EN 14511-3:2011: EER up to 3.2 and ESEER up to 4.

- Twin-rotor screw compressor equipped with a high-efficiency motor and a variable capacity valve that permits exact matching of the cooling capacity to the load.

- All aluminium condenser with high-efficiency micro-channels.

- Flooded shell-and-tube evaporator to increase the heat exchange efficiency.

- Electronic expansion device permitting operation at a lower condensing pressure and improved utilisation of the evaporator heat exchange surface (superheat control).

- Economizer system with electronic expansion device for increased cooling capacity

Page 2: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

2

Low operating sound levels ■ Compressor

- Discharge dampers integrated in the oil separator (Carrier patent).

- Silencer on the economiser return line. - Acoustic compressor and oil separator enclosure

reducing radiated noise (option). ■ Condenser section

- Condenser coils in V-shape with an open angle, allowing quieter air flow across the coil

- Low-noise 4th generation Flying Bird fans, made of a composite material (Carrier patent) are now even quieter and do not generate intrusive low-frequency noise

- Rigid fan mounting preventing start-up noise (Carrier patent)

Easy and fast installation ■ Integrated hydronic module (option)

- Centrifugal high-pressure dual water pump, with operating time balancing and automatic changeover to the back-up pump if a fault develops

- Water filter protecting the water pump against circulating debris

- High-capacity membrane expansion tank ensures pressurisation of the water circuit

- Thermal insulation and aluminium protection (option) - Pressure sensor to check filter pollution and for direct

numerical display of the water flow rate with an estimate of the instantaneous cooling capacity at the control interface

- Water flow control valve ■ Simplified electrical connections

- Main disconnect switch with high trip capacity - Transformer to supply the integrated control circuit

(400/24 V) ■ Fast commissioning

- Systematic factory operation test before shipment - Quick-test function for step-by-step verification of the

instruments, expansion devices, fans and compressor

Environmental care ■ R-134a refrigerant

- Refrigerant of the HFC group with zero ozone depletion potential

- 30% reduction in the refrigerant charge through the use of micro-channel heat exchangers

■ Leak-tight refrigerant circuit - Reduction of leaks as no capillary tubes and flare connec-

tions are used - Verification of pressure transducers and temperature

sensors without transferring refrigerant charge - Liquid line service valve for simplified maintenance

(option)

Absolute reliability ■ Screw compressor

- Industrial-type screw compressor with oversized bearings and motor cooled by suction gas

- All compressor components are easily accessible on site minimising down-time

- Protection increased by an electronic board ■ Air condenser

All aluminium micro-channel heat exchangers (MCHE) with high corrosion resistance. The all aluminium design eliminates the formation of galvanic currents between aluminium and copper that cause coil corrosion in saline or corrosive environments

■ Evaporator Thermal insulation with aluminium sheet finish for perfect resistance to external aggression (mechanical a nd UV protection)

■ Auto-adaptive control - Control algorithm prevents excessive compressor

cycling (Carrier patent) - Automatic compressor unloading in case of abnormally

high condensing pressure. If condenser coil fouling or fan failure occurs, the Aquaforce continues to operate, but at reduced capacity

■ Exceptional endurance tests - Partnerships with specialised laboratories and use of limit

simulation tools (finite element calculation) for the design of critical components.

- Transport simulation test in the laboratory on a vibrating table. The test is based on a military standard and equi-valent to 4000 km by truck.

- Salt mist corrosion resistance test in the laboratory for increased corrosion resistance

■ Control, safety30XAS units are equipped with high-pressure safety switches with manual reset and dual safety valves on the high- and low-pressure side as standard. Each of the safety valves is mounted on a three-way valve to facilitate testing and replacement.

Pro-Dialog+ controlPro-Dialog+ combines intelligence with operating simplicity. The control constantly monitors all machine parameters and precisely manages the operation of compressor, expansion devices, fans and of the evaporator water pump for optimum energy efficiency.

Pro-Dialog+ interface

■ Energy management - Seven-day internal time schedule clock: permits chiller

on/off control and operation at a second set point - Set point reset based on the outside air temperature or

the return water temperature or on the water heat exchanger delta T

- Master/slave control of two chillers operating in parallel with operating time equalisation and automatic change-over in case of a unit fault (accessory)

- Change-over based on the outside air temperature ■ Integrated features

- Night mode: capacity and fan speed limitation for reduced noise level

- With hydronic module: water pressure display and water flow rate calculation

■ Ease-of-use - The new backlighted LCD interface includes a manual

control potentiometer to ensure legibility under any lighting conditions.

- The information is displayed clearly in English, French, German, Italian and Spanish (for other languages please consult Carrier).

- The Pro-Dialog+ navigation uses intuitive tree-structure menus. They are user-friendly and permit quick access to the principal operat-ing parameters: compressor operating, suction/discharge pressure, compressor operating hours, set point, air temperature, entering/leaving water temperature.

\\MAINMENU\STATUS

Circuit B Total Capacity

CAPB_T 0 %DEM_LIM 100 %SP 4.2 °CCTRL_PNT -28.9 °CEMSTOP dsable

ENTERSTART/STOP

PRO-DIALOG+

Page 3: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

3

The Carrier 06T screw compressors benefit from Carrier’s long experience in the development of twin-rotor screw compressors.

The compressor is equipped with bearings with oversized rollers, oil pressure lubricated for reliable and durable operation, even at maximum load.A variable control valve controlled by the oil pressure permits infinitely variable cooling capacity.

This system allows optimal adjustment of the compressor cooling capacity and ensures exceptionally high stability of the chilled water leaving temperature. Among the other advantages: if a fault occurs e.g. if the condenser is fouled or at very high outside temperature, the compressor does not switch off, but continues operation with a reduced capacity (unloaded mode).

The compressor is equipped with a separate oil separator that minimises the amount of oil in circulation in the refri-gerant circuit and with its integrated silencer considerably reduces discharge gas pulsations for much quieter operation.

06T screw compressorRemote management (standard)Aquaforce is equipped with an RS485 serial port that offers multiple remote control, monitoring and diagnostic possi-bilities. Carrier offers a vast choice of control products, specially designed to control, manage and supervise the operation of an air conditioning system. Please consult your Carrier representative for more information.

Aquaforce also communicates with other building manage-ment systems via optional communication gateways. A connection terminal allows remote control of the Aquaforce by wired cable: - Start/stop: opening of this contact will shut down the unit - Dual set-point: closing of this contact activates a second

set-point (example: unoccupied mode) - Demand limit: closing of this contact limits the maximum

chiller capacity to a predefined value - Heat reclaim (option): closing of this contact allows heat

reclaim mode operation - Water pump 1 and 2 control (not available for hydronic

module option 116): these outputs control the contactors of one or two evaporator water pumps

- Operation indication: this volt-free contact indicates that the chiller is operating (cooling load) or that it is ready to operate (no cooling load)

- Alert indication: this volt-free contact indicates the necessity to carry out a maintenance operation or the presence of a minor fault

- Alarm indication: this volt-free contact indicates the presence of a major fault that has led to the shut-down of one or several refrigerant circuits

Remote management (EMM option 156) ■ The Energy Management Module offers extended remote

control possibilities: - Room temperature: permits set-point reset based on the

building indoor air temperature (with Carrier thermostat) - Set point reset: ensures reset of the cooling set-point

based on a 4-20 mA or 0-5 V signal - Demand limit: permits limitation of the maximum chiller

power or current based on a 0-10 V signal - Demand limit 1 and 2: closing of these contacts limits the

maximum chiller power or current to two predefined values.

- User safety: this contact can be used for any customer safety loop; opening of the contact generates a specific alarm

- Ice storage end: when ice storage has finished, this input permits return to the second set-point (unoccupied mode)

- Time schedule override: closing of this contact cancels the time schedule effects

- Out of service: this signal indicates that the chiller is completely out of service

- Chiller capacity: this analogue output (0-10 V) gives an immediate indication of the chiller capacity

Page 4: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

4

All-aluminium micro-channel heat exchanger (MCHE)

Already utilised in the automobile and aeronautical industries for many years, the MCHE micro-channel heat exchanger used in the Aquaforce is entirely made of aluminium. This one-piece concept significantly increases its corrosion resistance by eliminating the galvanic currents that are created when two different metals (copper and aluminium) come into contact in traditional heat exchangers. Unlike traditional heat exchangers the MCHE heat exchanger can be used in moderate marine and urban environments (Carrier recommendation).

From an energy efficiency point-of-view the MCHE heat exchanger is approximately 10% more efficient than a traditional coil and allows a 30% reduction in the amount of refrigerant used in the chiller.

The low thickness of the MCHE reduces air pressure losses by 50% and makes it susceptible to very little fouling (e.g. by sand). Cleaning of the MCHE heat exchanger is very fast using a high-pressure washer.

Page 5: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

5

OptionsOptions No. Description Advantages UseCorrosion protection, traditional coils (for the Middle East only)

2B Factory application of Blygold Polual treatment on the copper/aluminium coils

Improved corrosion resistance, recommended for industrial, rural and marine environments

30XAS 242-482

Corrosion protection, traditional coils (for the Middle East only)

3A Fins made of pre-treated aluminium (polyurethane and epoxy)

Improved corrosion resistance, recommended for moderate marine and urban environments

30XAS 242-482

Unit equipped for air discharge ducting

10 Fans with available pressure equipped with discharge connection flanges

Facilitates connection to the discharge ducts 30XAS 242-482

IP 54 control box 20A Increased leak tightness of control boxes Increased control box protection 30XAS 242-482Grilles 23 Metal grilles on the unit front, rear and sides Enhanced aesthetics, protection against intrusion to

the unit interior30XAS 242-482

Enclosure panels 23A Side panels at each end of the coil Enhanced aesthetics 30XAS 242-482Winter operation 28 Fan speed control via frequency converter Stable unit operation when the air temperature is

between -10°C and -20°C30XAS 242-482

Evaporator frost protection 41A Resistance heater on the evaporator Evaporator frost protection down to -20°C outside temperature

30XAS 242-482

Evaporator and hydronic module frost protection

41B Resistance heater on the evaporator and the hydronic module

Evaporator and hydronic module frost protection down to -20°C outside temperature

30XAS 282-482

Heat reclaim 50 Complete recovery of the heat rejected by the condenser

Free hot-water production as well as cold-water production

30XAS 242-482

Master/slave operation 58 Additional leaving water temperature sensor kit for on-site installation, permitting master/slave operation of two chillers connected in parallel.

Optimised operation of two chillers connected in parallel with operating time balancing.

30XAS 242-482

Service valve 92 Shut-off valves on the compressor suction piping, the economiser line, the compressor discharge piping and at the evaporator inlet

Simplified maintenance 30XAS 242-482

Discharge valve 93A Shut-off valves on the compressor discharge piping Simplified maintenance 30XAS 242-482High-pressure dual-pump hydronic module

116C See hydronic module chapter Easy and fast installation, operating safety 30XAS 282-482

High energy efficiency 119 Improved condenser performance Energy cost reduction, full load operation at higher air temperatures

30XAS 242-482

JBus gateway 148B Two-directional communications board, complies with JBus protocol

Easy connection by communication bus to a building management system

30XAS 242-482

BacNet gateway 148C Two-directional communications board, complies with BacNet protocol

Easy connection by communication bus to a building management system

30XAS 242-482

LON gateway 148D Two-directional communications board, complies with LON protocol

Easy connection by communication bus to a building management system

30XAS 242-482

Energy Management Module EMM

156 See chapter “Energy Management Module” Easy connection by wired connection to a building management system

30XAS 242-482

Dual relief valve installed with three-way valve

194 Three-way valve upstream of the safety valves on the evaporator and the oil separator

Valve replacement and inspection facilitated without refrige-rant loss. Conforms to European standard EN 378/BGVD4

30XAS 242-342

Russian code compliance 199 GOST certification Conformance with Russian regulations (GOST) 30XAS 242-482Australian code compliance 200 Pressure vessels approved in accordance with the

Australian codeConformance with Australian regulations 30XAS 242-482

Traditional coils (Cu/Al) (for the Middle East only)

254 Coils made of copper tubes with aluminium fins Possibility to add specialised condenser treatment 30XAS 242-482

Traditional coils (Cu/Al) without slots (for the Middle East only)

255 Coils made of copper tubes with aluminium fins without slots

Possibility to add specialised condenser treatment. 30XAS 242-482

Suction piping insulation 256 Thermal insulation of the suction piping with flexible, anti-UV insulant

Prevents condensation on the suction piping 30XAS 242-482

Low sound level 257 Compressor sound enclosure and sound insulation of main noise sources

Reduced sound emissions 30XAS 242-482

Very low sound level 258 Compressor sound enclosure and enhanced sound insulation of main noise sources

Reduced sound emissions 30XAS 242-482

MCHE anti-corrosion protection

263 Carrier factory treatment of the MCHE heat exchanger for applications in aggressive environments

The Super Enviro-Shield option was developed to extend the application range of MCHE heat exchangers in severe environmental conditions: this option is compulsory in industrial and coastal environments.

30XAS 242-482

Welded Victaulic evaporator water connection

266 Piping to be welded with Victaulic connection Ease-of-installation 30XAS 242-482

Compressor enclosure 279 Compressor sound enclosure Reduced sound emissions 30XAS 242-482Evaporator with aluminium jacket

281 Evaporator aluminium sheet for thermal insulation protection.

Improved resistance to aggressive climate conditions..

30XAS 242-482

Page 6: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

6

Hydronic module (option 116C)Typical hydronic circuit diagram

Legend Components of unit and hydronic moduleA Pressure sensor (A-B = ∆p evaporator)B Pressure sensorC Pressure sensor (C-D = ∆p water filter)D Pressure sensor1 Victaulic screen filter2 Expansion tank3 Safety valve4 Available pressure pump5 Drain valve6 Water flow control valve7 Evaporator8 Evaporator defrost heater (option)9 Hydronic module defrost heater10 Air vent (evaporator)11 Water purge (evaporator)12 Expansion compensator (flexible connections)13 Flow switch14 Water temperature sensor

System components (supplied by customer)15 Air vent16 Flexible connection17 Shut-down valves18 Charge valve---- Hydronic module (option)

Available static system pressure for unit with hydronic module (option 116C)

Water flow rate, l/s

Avai

labl

e st

atic

pre

ssur

e, k

Pa

1

2

17

16

18

1 2

9

99

11

1012

14

A

5

15

9

9

167

8

17

13

B

C D

6

4

3 14

This option allows a duct connection at the discharge side of the condenser fan. The unit is supplied with axial fans with a speed of 15.8 r/s (option 119), each equipped with a duct connection frame. The chiller can operate up to 60 Pa with reduced performance.

Selection exampleThe base capacities are those of option 119 (page 6 of this document). To obtain capacities at various pressure drops use the correction factors in the table opposite.

Selection at Eurovent conditions30XAS options 119 + 10 Sizes 282-482Fan pressure drop, Pa 0 20 40 60

Correction factorAir flow % l/s 1 -3.5 -7.5 -12.1Cooling capacity % kW 0 -0.5 -1.0 -1.5EER % kW/kW 0 -1.5 -3.5 -5.0Power input % kW 0 +1.0 +2.5 +3.5

Example30XAS 282 with 40 Pa pressure dropValues for option 119 at the following conditions:35°C outside air temperature12/7°C entering/leaving water temperature

30XAS 282 0 Pa Correction factor, % 40 PaAir flow l/s 22569 -7.5 20876Cooling capacity kW 280 -1 277EER kW/kW 3.17 -3.5 3,06Power input kW 88 +3.5 90

Fan with available pressure (option 10)

50

100

150

200

250

300

350

400

3 5 7 9 11 13 15 17 19 21 23 25 27 29 31

Legend

1. 30XAS 2822. 30XAS 3423. 30XAS 4424. 30XAS 482

Electrical data (option 116C)The pumps that are factory-installed in these units have motors with efficiency class IE2. The additional electrical data required by regulation 640/2009 is given in the installation, operation and maintenance manual.

This regulation concerns the application of directive 2005/32/EC on the eco-design requirements for electric motors.

Page 7: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

7

20

2530

3540

4550

5560

65

0 5 10 15

Total heat reclaim (option 50)Suitable for heating, domestic hot water preparation, agriculture and food industry, industrial processes and other hot-water requirements.

With the total heat reclaim option it is possible to reduce the energy consumption bill considerably compared to conventional heating equipment such as fossil fuel boilers or electric water tanks.

Operating principleIf hot water production is required, the compressor discharge gases are directed towards the heat reclaim condenser. The refrigerant releases its heat to the hot water that leaves the condenser at a temperature of up to 60°C. In this way 100% of the heat rejected by the liquid chiller can be used to produce hot water. When the demand for heat is satisfied, the hot gas is again directed towards the air condenser where the heat is rejected to the outside air by the fans. Hot water temperature control is ensured by the chiller Pro-Dialog+ control.

Note: Heat reclaim is only possible, if the unit produces cold water at the same time.

Condenser water temperature (°C) Minimum MaximumEntering temperature at start-up 12.5* 55Entering temperature during operation 20 55Leaving temperature during operation 25 60Evaporator water temperature (°C)Entering temperature at start-up - 45Entering temperature during operation 6.8 21Leaving temperature during operation 3.3 15

* The entering water temperature at start-up must not fall below 12.5°C. For installations with a lower temperature a three-way valve must be used.

Note: If the evaporator leaving water temperature is below 4°C, a glycol-water solution or the frost protection option must be used.

In part-load operation, the limitation of the condenser leaving water temperature is due to the operating range of the screw compressor. If the condenser leaving water temperature is above the limit value given in the curves on the right, the unit will automatically change over to the mode without heat recovery:

Max

imum

con

dens

er le

avin

g wa

ter

tem

pera

ture

, °C

Unit load, %

Con

dens

er le

avin

g wa

ter t

empe

ratu

re, °

C

Evaporator leaving water temperature, °C

Part load operating limits (evaporator leaving water temperature = 7°C)

Full load Part load limit, approx. 60% Minimum load limit, approx. 30%

40

45

50

55

60

30405060708090100

Physical data, option 50These are the same as for the standard unit except:

30XAS heat reclaim mode 282 342 442 482Cooling capacity* kW 278 329 428 475Heating capacity* kW 349 411 538 599Total power input (unit)* kW 77.7 90.2 120.6 136.0Total energy efficiency ratio (EER) kW/kW 3.58 3.65 3.55 3.49 Total coefficient of performance (COP) kW/kW 4.49 4.56 4.46 4.40Operating weight** kg 3260 3320 4190 4280Refrigerant charge kg 73 78 90 95Heat reclaim condenser Flooded shell-and-tube condenserWater volume l 55 55 68 68Water connection VictaulicDiameter inch 4 4 4 4Outside diameter mm 114.3 114.3 114.3 114.3

* Nominal conditions: Entering/leaving water temperature: evaporator 12°C/7°C; heat reclaim condenser: 40°C/45°C; evaporator and heat reclaim condenser fouling factor = 0 m2 K/kW. Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the

water pump to overcome the internal pressure drop in the heat exchanger. ** Weights are for guidance only

Page 8: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

8

Physical data30XAS 242 282 342 442 482Air conditioning application as per EN14511-3:2011*Nominal cooling capacity, standard unit kW 232 284 334 430 467EER kW/kW 2.76 3.00 3.08 2.93 2.87Eurovent class cooling C B B B CESEER kW/kW 3.78 3.93 3.99 3.87 3.96Air conditioning application** Nominal cooling capacity, standard unit kW 233 285 335 432 469EER kW/kW 2.78 3.03 3.11 2.96 2.91ESEER kW/kW 3.85 4.01 4.09 3.97 4.07Air conditioning application as per EN14511-3:2011*Nominal cooling capacity, unit with option 119*** kW 245 285 345 461 486EER kW/kW 2.97 3.15 3.24 3.15 3.09Eurovent class cooling B A A A BESEER kW/kW 3.69 3.69 3.80 3.75 3.79Air conditioning application** Nominal cooling capacity, unit with option 119*** kW 245 286 346 462 488EER kW/kW 2.99 3.18 3.28 3.18 3.13ESEER kW/kW 3.75 3.76 3.90 3.84 3.89Operating weight**** kg 2390 2810 2870 3630 3720With option 116C*** kg - 3070 3190 3990 4150With options 254 or 255*** kg 2540 3060 3140 3950 4070Sound levelsStandard unitSound power level† dB(A) 99 98 98 103 102Sound pressure level at 10 m†† dB(A) 67 66 66 70 70Standard unit + option 279***Sound power level† dB(A) 94 94 93 97 96Sound pressure level at 10 m†† dB(A) 62 62 61 65 64Standard unit + option 257***Sound power level† dB(A) 92 92 91 95 94Sound pressure level at 10 m†† dB(A) 60 60 59 62 61Standard unit + option 258***Sound power level† dB(A) 89 89 88 92 91Sound pressure level at 10 m†† dB(A) 57 57 56 59 58High energy efficiency unit (option 119)***Sound power level† dB(A) 96 96 96 98 98Sound pressure level at 10 m†† dB(A) 64 64 63 66 66High energy efficiency unit (option 119)*** + option 257***Sound power level† dB(A) 95 95 95 97 97Sound pressure level at 10 m†† dB(A) 63 62 62 65 64DimensionsLength mm 2410 3604 3604 4798 4798Depth mm 2253 2253 2253 2253 2253Height mm 2297 2297 2297 2297 2297Compressor 06T semi-hermetic screw compressor, 50 r/sRefrigerant**** R-134a, one circuitRefrigerant charge kg 60 72 73 83 88Refrigerant charge option 254/255*** kg 85 95 105 120 130Capacity control PRO-DIALOG+, electronic expansion valve (EXV)Minimum capacity % 30 30 30 30 30Condensers All aluminium micro-channel heat exchangerCondenser fans Axial Flying Bird IV fans with rotating shroud - standard speed = 11.7 r/s; speed with option 119 = 15.7 r/sStandard units and units with option 119 - 254***Quantity 4 5 6 7 8Total air flow, standard unit l/s 13667 17083 20500 23917 27333Total air flow - unit with option 119*** l/s 18055 22569 27083 31597 36111Evaporator Flooded shell-and-tube typeWater content l 53 53 53 75 75Without hydronic module Diameter 5 in, outside diameter 141.3 mm, Victaulic water inlet and outlet connectionsMax. water-side pressure kPa 1000 1000 1000 1000 1000With hydronic module (option 116C)*** Diameter 4 in, outside diameter 114.3 mm, Victaulic water inlet and outlet connectionsExpansion tank volume l - 50 50 50 50Max. water-side pressure kPa - 400 400 400 400Chassis paint colour Colour code: RAL7035

* Eurovent-certified performances in accordance with standard EN14511-3:2011. Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W

** Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger.

Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W *** Options: 116C = high-pressure dual-pump hydronic module; 119 = high energy efficiency units; 254 = units with copper/aluminium coils with slots; 255 = units with copper/aluminium coils with

plain fins; 257 = low sound level; 258 = very low sound leve; 279 = compressor enclosure. **** Weights are guidelines only. The refrigerant charge is also given on the unit nameplate. † 10-12 W - In accordance with ISO 9614-1 and certified by Eurovent. †† Average sound pressure level, unit in a free field on a reflective surface. In accordance with ISO 9614-1 (10-12 W). For information, calculated from the sound power level Lw(A)

Note: Option 119 (high energy efficiency) can be used together with options 254 and 255. Contact your Carrier representative to obtain the performances.

Page 9: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

9

Electrical data30XAS 242 282 342 442 482Power circuitNominal power supply V-ph-Hz 400-3-50Voltage range V 360-440Maximum supply cable section mm2 2 x 150 2 x 95 2 x 150 2 x 150 2 x 240Short-circuit stability current (TN system)* kA 38 50 50 50 50Control circuit 24 V via internal transformerStart-up current** A 303 388 388 587 587Standard unitCosine Phi maximum*** 0.89 0.88 0.88 0.87 0.87Cosine Phi nominal**** 0.85 0.85 0.86 0.84 0.85Maximum power input† kW 101 113 134 184 213Nominal current draw**** A 141 153 174 258 278Maximum current draw (Un)† A 165 185 218 305 353Maximum current draw (Un -10%)*** A 180 198 231 324 375High energy efficiency unit (option 119)Cosine Phi maximum*** 0.88 0.88 0.88 0.87 0.87Cosine Phi nominal**** 0.84 0.85 0.85 0.83 0.84Maximum power input† kW 105 118 139 190 221Nominal current draw**** A 141 153 175 254 271Maximum current draw (Un)† A 172 194 229 318 368Maximum current draw (Un -10%)*** A 187 207 242 337 390

* kA eff: efficiency value: rms for English version ** Instantaneous start-up current (locked rotor current in star connection of the compressor). *** Values obtained at operation with maximum unit power input. **** Values obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C. † Values obtained at operation with maximum unit power input. Values given on the unit name plate.

Note: Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A Start-up current: 8.4 A Power input: 760 W

Electrical data notes and operating conditions for 30XAS units:

• 30XAS 242-482 units have a single power connection point located immediately upstream of the main disconnect switch.

• The control box includes the following standard features:-- One-general-disconnect-switch-- Starter-and-motor-protection-devices-for-the-compressor,-the-fans-and-the-

pump-- Control-devices

Field connections• All connections to the system and the electrical installations must be in full

accordance with all applicable local codes.• The Carrier 30XAS units are designed and built to ensure conformance with

these codes. The recommendations of European standard EN 60 204-1 (corresponds to IEC 60204-1) (machine safety - electrical machine compo-nents - part 1: general regulations) are specifically taken into account, when designing the electrical equipment.

IMPORTANT• Generally the recommendations of IEC 60364 are accepted as compliance

with the requirements of the installation directives.• Conformance with EN 60 204 is the best means of ensuring compliance with

the Machines Directive § 1.5.1. • Annex B of EN 60204-1 describes the electrical characteristics used for the

operation of the machines.

• The operating environment for the 30XAS units is specified below:1. Environment* - Environment as classified in EN 60 721 (corresponds to IEC

60721) :-- outdoor-installation*-- ambient-temperature-range:-‑20°C-to-+55°C,-class-4K4H* - altitude: ≤ 2000 m (see note for table 4.3 in the IOM)-- indoor-installation*-- presence-of-hard-solids,-class-4S2*-(no-significant-dust-present)-- presence-of-corrosive-and-polluting-substances,-class-4C2-(negligible)

2. Power supply frequency variation: ± 2 Hz.3. The neutral (N) line must not be connected directly to the unit (if necessary

use a transformer).4. Overcurrent protection of the power supply conductors is not provided with

the unit.5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type

suitable for power interruption in accordance with EN 60947-3 (corresponds to IEC 60947-3).

6. The units are designed for simplified connection on TN(s) networks (IEC 60364). For IT networks derived currents may interfere with network monitoring elements, and it is recommended to create an IT type divider for the system units that require this and/or a TN type divider for Carrier units. Please consult the appropriate local organisations to define the monitoring and protection elements and carry out the electrical installation.

NOTE: If particular aspects of an actual installation do not conform to the conditions described above, or if there are other conditions which should be considered, always contact your local Carrier representative.

* The required protection level for this class is IP43BW (according to reference document IEC 60529). All 30XAS units are protected to IP44CW and fulfil this protection condition.

Page 10: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

10

Part load performancesWith the rapid increase in energy costs and the care about environmental impacts of electricity production, power consumption of air conditioning equipment has become an important topic. The energy efficiency of a liquid chiller at full load is rarely representative of the actual performance of the units, as on average a chiller works less than 5% of the time at full load.

IPLV (in accordance with AHRI 550/590)The IPLV (integrated part load value) allows evaluation of the average energy efficiency based on four operating conditions defined by the AHRI (Air Conditioning, Heating and Refrigeration Institute). The IPLV is the average weighted value of the energy efficiency ratios (EER) at different operating conditions, weighted by the operating time.

IPLV (integrated part load value)Load % Air temperature °C Energy efficiency Operating time %100 35 EER1 175 26.7 EER2 4250 18.3 EER3 4525 12.8 EER4 12IPLV = EER1 x 1% + EER2 x 42% + EER3 x 45% + EER4 x 12%

The heat load of a building depends on many factors, such as the outside air temperature, the exposure to the sun and the building occupancy.

Consequently it is preferable to use the average energy efficiency, calculated at several operating points that are representative for the unit utilisation.

ESEER (in accordance with EUROVENT)The ESEER (European seasonal energy efficiency ratio) permits evaluation of the average energy efficiency at part load, based on four operating conditions defined by Eurovent. The ESEER is the average value of energy efficiency ratios (EER) at different operating conditions, weighted by the operating time.

ESEER (European seasonal energy efficiency ratio)Load % Air temperature °C Energy efficiency Operating time %100 35 EER1 375 30 EER2 3350 25 EER3 4125 20 EER4 23ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23%

30XAS 242 282 342 442 482Standard unitsIPLV kW/kW 4.23 4.55 4.72 4.55 4.60ESEER kW/kW 3.78 3.93 3.99 3.87 3.96High-efficiency units (option 119)IPLV kW/kW 4.16 4.23 4.44 4.36 4.41ESEER kW/kW 3.69 3.69 3.80 3.75 3.79

ESEER Calculations according to standard performances (in accordance with EN14511-3:2011) and certified by Eurovent. IPLV Calculations according to standard performances (in accordance with AHRI 550-590)

Page 11: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

11

Sound spectrum

30XAS - standard unitOctave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 85 94 97 95 89 84 db(A) 99282 dB 88 93 98 93 88 80 db(A) 98342 dB 86 94 95 94 89 87 db(A) 98442 dB 89 98 98 100 93 89 db(A) 103482 dB 89 94 97 100 91 85 db(A) 102

30XAS - standard unit with option 257*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 85 94 91 85 79 74 db(A) 92282 dB 88 93 93 83 78 71 db(A) 92342 dB 86 94 90 85 79 77 db(A) 91442 dB 89 98 92 89 82 79 db(A) 95482 dB 89 94 92 90 81 76 db(A) 94

30XAS - unit with option 279*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 85 94 94 88 82 76 db(A) 94282 dB 88 93 96 86 81 73 db(A) 94342 dB 86 94 92 87 82 79 db(A) 93442 dB 89 98 95 93 86 81 db(A) 97482 dB 89 94 95 93 84 78 db(A) 96

30XAS - unit with option 258*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 85 91 88 83 76 71 db(A) 89282 dB 88 90 89 82 76 68 db(A) 89342 dB 86 91 85 83 77 74 db(A) 88442 dB 89 96 89 87 78 75 db(A) 92482 dB 89 91 89 87 78 73 db(A) 91

30XAS - unit with option 119*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 96 95 98 96 90 85 db(A) 100282 dB 96 95 99 94 89 82 db(A) 99342 dB 97 95 96 95 90 88 db(A) 99442 dB 98 99 98 101 94 89 db(A) 103482 dB 98 96 98 101 92 87 db(A) 103

30XAS - unit with option 119 + 257*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 96 95 93 89 84 80 db(A) 95282 dB 96 95 94 89 84 80 db(A) 95342 dB 97 95 92 90 85 82 db(A) 95442 dB 98 99 94 92 86 83 db(A) 97482 dB 98 96 94 93 86 82 db(A) 97

30XAS - unit with option 119 + 279*Octave bands, Hz Sound power

levels125 250 500 1k 2k 4k242 dB 96 95 95 91 85 81 dB(A) 96282 dB 96 95 96 90 85 80 dB(A) 96342 dB 97 95 94 91 86 82 dB(A) 96442 dB 98 99 96 94 88 84 dB(A) 98482 dB 98 96 96 94 87 83 dB(A) 98

* Options: 119 = high energy efficiency units; 257 = low sound level; 258 = very low sound level; 279 = compressor enclosure

Page 12: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

12

Operating limitsEvaporator water temperature °C Minimum MaximumWater entering temperature at start-up - 45*Water entering temperature during operation 6.8 21Water leaving temperature during operation 3.3 15

Note: If the leaving water temperature is below 4°C, a glycol/water solution or the frost protection option must be used.

Condenser air temperature °C Minimum MaximumStorage -20 68Operation:Standard unit -10 55**With option 28: winter operation -20 55**With option 119: high energy efficiency*** -10 55****

Note: If the air temperature is below 0°C, a glycol/water solution or the frost protection option must be used.

* Based on the installation type and the air temperature ** Part load, based on the water temperature *** Recommended for operation above 46°C **** Part-load operation

Evaporator leaving water temperature, °C

Air e

nter

ing

tem

pera

ture

, °C

Evaporator water flow rate (l/s)30XAS Minimum Maximum*242 3.2 30.7282 3.7 30.7342 4.4 30.7442 5.8 41.0482 6.5 41.0

* The maximum water flow rate corresponds to a pressure drop of 100 kPa.

Operating range

30XAS standard unit 30XAS high energy efficiency unit or option 119

Evaporator leaving water temperature, °C

Air e

nter

ing

tem

pera

ture

, °C

Legend

Operating range, unirt equipped with option 28 "Winter operation"

Below 0°C air temperature the unit must either be equipped with the evaporator frost protection option (41A or 41B), or the water loop must be protected against frost by using a frost protection solution (by the installer).

Part load average

Page 13: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

13

LegendAll dimensions are given in mm.

Required clearances for maintenance and air flow

Recommended space for evaporator tube removal

Water inlet

Water outlet

Air outlet – do not obstruct

Power supply connection

Control circuit connection

1

2

C

Dimensions/clearances30XAS 242

30XAS 282-342

30XAS 442-482

Note: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request·

Page 14: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

14

Dimensions/clearances30XAS 282-342 - heat reclaim unit (option 50)

30XAS 442-482 - heat reclaim unit (option 50)

Specific elements for option 50

Attention: The Victaulic flange sleeves of the condenser are not installed, but supplied with the unit. The sealing joints are in the control box. The temperature sensors and the condenser flow switch are wired and fixed in the machine. They must be installed as described in the chapter “Condenser water connections” in the Installation Manual.

Note: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings supplied with the unit or available on request.

For the positioning of the fixing points, weight distribution and centre of gravity coordinates please refer to the dimensional drawings.

LegendAll dimensions are given in mm.

Required clearances for maintenance and air flow

Recommended space for evaporator tube removal

Water inlet

Water outlet

Air outlet – do not obstruct

Power supply connection

Control circuit connection

1

2

C

Page 15: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

15

Cooling capacities in accordance with EN14511-3 : 2011SI system

30XAS standard unit and unit with high energy efficiency (option 119)

Condenser entering air temperature, °C20 25 30 35 40 46

LWT Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp°C kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa

30XAS standard unit242 5 243 3.88 11.8 16 236 3.46 11.4 15 227 3.08 11.0 14 219 2.73 10.6 13 209 2.40 10.1 12 197 2.05 9.5 12282 296 4.18 13.5 21 287 3.72 13.1 20 277 3.30 12.7 19 266 2.92 12.2 17 255 2.58 11.7 16 241 2.20 11.0 14342 348 4.28 16.4 31 336 3.81 15.8 29 325 3.39 15.3 27 312 2.99 14.7 25 299 2.63 14.1 23 281 2.23 13.2 20442 451 4.09 21.1 32 436 3.65 20.4 30 421 3.24 19.7 28 405 2.87 18.9 26 388 2.52 18.2 24 367 2.14 17.2 22482 488 4.04 23.0 37 472 3.61 22.2 35 455 3.20 21.4 33 437 2.83 20.5 30 417 2.48 19.6 28 392 2.10 18.5 25242 7 257 3.91 12.4 18 249 3.50 12.0 17 240 3.11 11.6 15 231 2.76 11.2 14 222 2.44 10.7 13 202 2.13 9.8 12282 314 4.27 14.4 24 304 3.81 13.9 22 294 3.38 13.5 21 283 3.00 12.9 19 271 2.64 12.4 18 256 2.26 11.7 16342 369 4.38 17.4 35 357 3.91 16.9 32 345 3.47 16.3 30 331 3.07 15.6 28 317 2.70 14.9 26 299 2.29 14.1 23442 479 4.17 22.4 35 463 3.72 21.7 33 446 3.31 20.9 31 429 2.92 20.1 29 410 2.57 19.2 27 380 2.21 17.8 23482 519 4.12 24.5 41 502 3.67 23.6 39 483 3.25 22.8 36 464 2.87 21.9 34 444 2.52 20.9 31 418 2.14 19.7 28242 10 278 3.96 13.5 20 269 3.54 13.0 19 260 3.15 12.6 18 250 2.80 12.1 16 239 2.48 11.6 15 212 2.23 10.3 12282 343 4.39 15.8 28 332 3.92 15.2 26 320 3.49 14.7 24 308 3.10 14.1 22 295 2.74 13.6 21 279 2.34 12.8 18342 404 4.51 19.1 41 391 4.03 18.5 38 377 3.59 17.8 35 362 3.18 17.1 33 346 2.79 16.3 30 326 2.37 15.4 27442 522 4.27 24.5 41 504 3.82 23.7 38 485 3.39 22.8 36 466 3.00 21.9 33 446 2.64 20.9 30 389 2.33 18.2 24482 567 4.24 26.8 48 548 3.78 25.9 45 527 3.35 24.9 42 506 2.96 23.9 39 483 2.60 22.8 36 421 2.28 19.9 2830XAS high energy efficiency unit (option 119)242 5 253 4.07 11.9 16 246 3.66 11.6 16 238 3.26 11.2 15 229 2.90 10.8 14 220 2.57 10.3 12 209 2.21 9.8 12282 294 4.26 13.8 22 285 3.82 13.4 21 276 3.42 13.0 20 266 3.05 12.5 18 256 2.70 12.0 17 243 2.33 11.4 15342 356 4.38 16.8 32 345 3.93 16.2 31 334 3.51 15.7 29 321 3.12 15.1 26 308 2.76 14.5 24 291 2.36 13.7 22442 478 4.26 21.7 34 463 3.83 21.1 32 448 3.43 20.4 30 432 3.06 19.6 28 415 2.71 18.9 26 394 2.32 17.9 24482 504 4.21 23.7 40 489 3.80 23.0 37 473 3.41 22.2 35 456 3.04 21.4 33 438 2.70 20.6 31 414 2.32 19.5 28242 7 268 4.14 12.6 18 260 3.72 12.3 17 252 3.32 11.9 16 243 2.96 11.4 15 234 2.63 11.0 14 222 2.26 10.4 13282 313 4.38 14.7 25 303 3.94 14.3 23 293 3.52 13.8 22 283 3.14 13.3 20 272 2.79 12.8 19 258 2.41 12.2 17342 380 4.53 17.9 36 368 4.06 17.3 34 355 3.63 16.7 32 342 3.23 16.1 30 328 2.86 15.5 27 311 2.45 14.6 24442 508 4.38 23.1 37 492 3.94 22.4 35 476 3.53 21.7 33 458 3.14 20.9 31 440 2.78 20.0 29 418 2.39 19.0 26482 535 4.29 25.2 44 518 3.86 24.4 41 501 3.45 23.6 39 483 3.08 22.8 36 464 2.73 21.9 34 440 2.35 20.7 31242 10 292 4.23 13.7 21 283 3.80 13.3 20 273 3.40 12.9 19 264 3.03 12.4 17 253 2.69 11.9 16 240 2.32 11.3 14282 342 4.56 16.2 29 332 4.10 15.7 27 321 3.68 15.1 26 310 3.28 14.6 24 298 2.92 14.0 22 282 2.52 13.3 20342 417 4.74 19.7 43 404 4.26 19.1 41 390 3.81 18.4 38 376 3.40 17.8 35 361 3.01 17.0 32 341 2.58 16.1 29442 557 4.54 25.4 43 539 4.09 24.6 41 520 3.66 23.7 38 501 3.26 22.8 36 481 2.89 21.9 33 455 2.49 20.8 30482 586 4.46 27.7 51 567 4.01 26.8 48 547 3.59 25.8 45 526 3.19 24.8 42 505 2.83 23.8 39 477 2.42 22.5 35

Application data

Standard units, refrigerant: R-134a Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4 (m2 K)/W Performances in accordance with EN14511-3:2011.

Legend LWT Leaving water temperature, °C Qc Cooling capacity, kW EER Energy efficiency ratio, kW/kW q Evaporator water flow rate, l/s Δp Evaporator pressure drop, kPa

Page 16: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

16

Cooling capacities - SI system30XAS standard unit and unit with high energy efficiency (option 119)

Condenser entering air temperature, °C20 25 30 35 40 46

LWT Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp°C kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa

30XAS standard242 5 244 3.92 11.8 16 236 3.49 11.4 15 228 3.10 11.0 14 219 2.74 10.6 13 210 2.42 10.1 12 198 2.07 9.5 12282 297 4.23 13.5 21 287 3.76 13.1 20 277 3.33 12.7 19 267 2.95 12.2 17 256 2.59 11.7 16 241 2.21 11.0 14342 349 4.35 16.4 31 337 3.86 15.8 29 325 3.42 15.3 27 313 3.02 14.7 25 299 2.65 14.1 23 282 2.24 13.2 20442 452 4.15 21.1 32 438 3.70 20.4 30 422 3.28 19.7 28 406 2.89 18.9 26 389 2.54 18.2 24 368 2.15 17.2 22482 490 4.11 23.0 37 474 3.66 22.2 35 456 3.24 21.4 33 438 2.86 20.5 30 418 2.50 19.6 28 393 2.12 18.5 25242 7 258 3.95 12.4 18 249 3.53 12.0 17 241 3.14 11.6 15 232 2.78 11.2 14 222 2.46 10.7 13 202 2.14 9.8 12282 315 4.32 14.4 24 305 3.85 13.9 22 294 3.42 13.5 21 283 3.02 12.9 19 272 2.66 12.4 18 257 2.27 11.7 16342 371 4.45 17.4 35 358 3.96 16.9 32 346 3.51 16.3 30 332 3.10 15.6 28 318 2.72 14.9 26 299 2.31 14.1 23442 480 4.23 22.4 35 464 3.77 21.7 33 447 3.35 20.9 31 430 2.95 20.1 29 411 2.59 19.2 27 381 2.22 17.8 23482 521 4.19 24.5 41 503 3.72 23.6 39 485 3.29 22.8 36 465 2.90 21.9 34 445 2.54 20.9 31 419 2.15 19.7 28242 10 279 4.01 13.5 20 270 3.58 13.0 19 260 3.18 12.6 18 250 2.82 12.1 16 239 2.50 11.6 15 213 2.24 10.3 12282 344 4.45 15.8 28 333 3.97 15.2 26 321 3.53 14.7 24 309 3.13 14.1 22 296 2.76 13.6 21 280 2.36 12.8 18342 405 4.60 19.1 41 392 4.10 18.5 38 378 3.64 17.8 35 363 3.21 17.1 33 347 2.82 16.3 30 327 2.39 15.4 27442 523 4.35 24.5 41 505 3.88 23.7 38 486 3.44 22.8 36 467 3.03 21.9 33 447 2.67 20.9 30 390 2.35 18.2 24482 569 4.33 26.8 48 549 3.85 25.9 45 529 3.40 24.9 42 507 3.00 23.9 39 485 2.62 22.8 36 422 2.30 19.9 2830XAS high energy efficiency unit (option 119)242 5 254 4.12 11.9 16 246 3.69 11.6 16 238 3.29 11.2 15 230 2.92 10.8 14 221 2.59 10.3 12 209 2.22 9.8 12282 295 4.31 13.8 22 286 3.86 13.4 21 276 3.45 13.0 20 267 3.07 12.5 18 256 2.72 12.0 17 243 2.34 11.4 15342 357 4.45 16.8 32 346 3.98 16.2 31 334 3.55 15.7 29 322 3.15 15.1 26 309 2.78 14.5 24 292 2.38 13.7 22442 479 4.32 21.7 34 464 3.88 21.1 32 449 3.47 20.4 30 433 3.08 19.6 28 416 2.73 18.9 26 395 2.34 17.9 24482 506 4.28 23.7 40 490 3.85 23.0 37 474 3.45 22.2 35 457 3.07 21.4 33 439 2.72 20.6 31 415 2.34 19.5 28242 7 269 4.19 12.6 18 261 3.75 12.3 17 252 3.35 11.9 16 244 2.98 11.4 15 234 2.64 11.0 14 222 2.28 10.4 13282 313 4.44 14.7 25 304 3.98 14.3 23 294 3.56 13.8 22 284 3.17 13.3 20 273 2.82 12.8 19 259 2.43 12.2 17342 381 4.61 17.9 36 369 4.12 17.3 34 356 3.68 16.7 32 343 3.27 16.1 30 329 2.89 15.5 27 311 2.47 14.6 24442 510 4.45 23.1 37 494 3.99 22.4 35 477 3.57 21.7 33 460 3.18 20.9 31 441 2.81 20.0 29 419 2.41 19.0 26482 537 4.37 25.2 44 520 3.92 24.4 41 502 3.50 23.6 39 484 3.12 22.8 36 465 2.76 21.9 34 441 2.37 20.7 31242 10 292 4.28 13.7 21 283 3.84 13.3 20 274 3.43 12.9 19 264 3.06 12.4 17 254 2.71 11.9 16 241 2.34 11.3 14282 343 4.63 16.2 29 333 4.16 15.7 27 322 3.72 15.1 26 310 3.32 14.6 24 298 2.95 14.0 22 283 2.54 13.3 20342 419 4.84 19.7 43 405 4.34 19.1 41 392 3.87 18.4 38 377 3.44 17.8 35 362 3.05 17.0 32 342 2.60 16.1 29442 558 4.62 25.4 43 540 4.15 24.6 41 522 3.71 23.7 38 502 3.30 22.8 36 482 2.92 21.9 33 457 2.51 20.8 30482 588 4.56 27.7 51 569 4.09 26.8 48 549 3.65 25.8 45 528 3.24 24.8 42 506 2.86 23.8 39 479 2.44 22.5 35

Application data

Standard units, refrigerant: R-410A Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4 (m2 K)/W Gross performances, not in accordance with EN14511-3:2011. These performances do not take

into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger.

Legend LWT Leaving water temperature, °C Qc Cooling capacity, kW EER Energy efficiency ratio, kW/kW q Evaporator water flow rate, l/s Δp Evaporator pressure drop, kPa

Page 17: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

17

Cooling capacities - SI system30XAS standard unit and unit with high energy efficiency (option 119) for Middle East conditions

Condenser entering air temperature, °C35.0 40.6 46.1 47.8 51.7 54.4

LWT Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp°C kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa kW kW/

kWl/s kPa

30XAS standard242 5.6 234 2.94 9.9 12 223 2.57 9.4 12 213 2.23 9.0 12 209 2.14 8.8 12 201 1.93 8.5 12 160 1.77 6.7 12282 272 3.10 11.5 15 260 2.71 11.0 14 247 2.36 10.5 13 243 2.26 10.3 12 234 2.04 9.9 12 209 1.90 8.8 12342 328 3.18 13.9 22 313 2.77 13.2 20 297 2.40 12.6 18 292 2.29 12.3 18 280 2.05 11.8 16 223 1.93 9.4 12442 440 3.11 18.0 24 421 2.71 17.2 22 401 2.35 16.4 20 395 2.25 16.1 19 364 2.04 14.9 17 271 1.88 11.1 12482 465 3.09 19.7 28 445 2.70 18.8 26 423 2.34 17.9 23 416 2.24 17.6 23 399 2.01 16.9 21 297 1.88 12.6 12242 6.7 241 2.97 10.2 12 231 2.60 9.8 12 220 2.26 9.3 12 216 2.17 9.1 12 200 1.97 8.4 12 166 1.82 7.0 12282 281 3.16 11.9 16 269 2.76 11.4 15 256 2.41 10.8 13 252 2.31 10.7 13 242 2.08 10.2 12 207 1.95 8.8 12342 340 3.25 14.4 24 325 2.83 13.7 22 308 2.45 13.0 19 303 2.34 12.8 19 281 2.11 11.9 16 194 1.94 8.2 12442 455 3.16 18.6 25 435 2.76 17.8 23 414 2.39 16.9 21 408 2.29 16.7 21 368 2.08 15.1 17 284 1.93 11.6 12482 480 3.11 20.3 29 459 2.72 19.4 27 437 2.36 18.5 25 430 2.26 18.2 24 406 2.05 17.2 22 311 1.93 13.1 13242 7.8 249 3.00 10.5 13 238 2.63 10.1 12 227 2.29 9.6 12 224 2.19 9.5 12 199 2.02 8.4 12 164 1.86 6.9 12282 291 3.21 12.3 17 278 2.81 11.8 16 265 2.45 11.2 14 261 2.35 11.0 14 251 2.12 10.6 13 215 2.00 9.1 12342 352 3.32 14.9 25 336 2.89 14.2 23 319 2.50 13.5 21 314 2.39 13.3 20 281 2.17 11.9 16 203 2.01 8.6 12442 471 3.21 19.3 27 450 2.80 18.4 24 428 2.43 17.5 22 422 2.32 17.2 22 372 2.13 15.2 17 296 1.99 12.1 12482 495 3.14 20.9 31 473 2.74 20.0 28 450 2.38 19.1 26 443 2.28 18.7 25 407 2.10 17.2 22 325 1.98 13.7 14242 8.9 257 3.03 10.9 13 245 2.65 10.4 12 234 2.31 9.9 12 230 2.21 9.7 12 197 2.07 8.3 12 171 1.91 7.2 12282 300 3.26 12.7 18 288 2.86 12.2 17 274 2.49 11.6 15 269 2.39 11.4 15 259 2.16 11.0 14 213 2.05 9.0 12342 365 3.38 15.4 27 348 2.95 14.7 24 330 2.55 14.0 22 325 2.43 13.7 21 279 2.22 11.8 16 211 2.07 8.9 12442 486 3.26 19.9 28 464 2.84 19.0 26 442 2.47 18.1 23 435 2.36 17.8 23 375 2.17 15.4 17 309 2.04 12.6 12482 512 3.19 21.7 33 488 2.78 20.7 30 464 2.40 19.6 27 456 2.29 19.3 26 413 2.1 17.5 22 339 2.04 14.4 15242 10.0 264 3.06 11.2 14 253 2.68 10.7 13 241 2.33 10.2 12 237 2.24 10.0 12 204 2.11 8.6 12 142 1.89 6.0 12282 311 3.32 13.2 19 297 2.91 12.6 18 283 2.54 12.0 16 279 2.43 11.8 16 259 2.22 11.0 14 211 2.11 8.9 12342 378 3.45 16.0 29 360 3.01 15.3 26 342 2.60 14.5 24 336 2.48 14.2 23 289 2.27 12.3 17 220 2.13 9.3 12442 503 3.30 20.6 30 480 2.88 19.7 27 457 2.50 18.7 25 449 2.39 18.4 24 337 2.28 13.8 14 302 2.08 12.4 12482 529 3.24 22.4 34 504 2.82 21.4 32 479 2.44 20.3 29 471 2.33 19.9 28 369 2.3 15.6 18 353 2.08 14.9 1630XAS high energy efficiency unit (option 119)242 5.6 230 2.82 9.7 12 220 2.46 9.29 12 209 2.13 8.8 12 205 2.04 8.7 12 171 1.85 7.2 12 113 1.56 4.8 12282 270 3.00 11.4 15 258 2.62 10.9 14 245 2.28 10.4 12 241 2.18 10.2 12 222 1.98 9.4 12 178 1.83 7.5 12342 326 3.08 13.8 22 311 2.68 13.1 20 294 2.31 12.4 18 289 2.21 12.2 17 239 2.02 10.1 12 184 1.81 7.8 12442 437 3.00 17.8 23 417 2.62 17.1 22 397 2.26 16.2 20 391 2.16 16.0 19 281 1.98 11.5 12 249 1.77 10.2 12482 461 2.97 19.5 27 440 2.59 18.6 25 418 2.25 17.7 23 411 2.15 17.4 22 368 1.97 15.6 18 294 1.81 12.4 12242 6.7 238 2.85 10.1 12 227 2.49 9.6 12 216 2.16 9.1 12 212 2.07 9.0 12 169 1.89 7.2 12 119 1.61 5.0 12282 279 3.05 11.8 16 267 2.67 11.3 15 254 2.32 10.7 13 250 2.23 10.6 13 222 2.03 9.4 12 151 1.80 6.4 12342 337 3.14 14.3 23 322 2.74 13.6 21 305 2.36 12.9 19 300 2.25 12.7 18 237 2.07 10.0 12 178 1.82 7.5 12442 451 3.05 18.5 25 431 2.65 17.6 23 410 2.30 16.8 21 404 2.20 16.5 20 294 2.04 12.0 12 261 1.83 10.7 12482 475 2.99 20.1 29 454 2.61 19.2 27 431 2.26 18.2 24 424 2.16 17.9 23 321 2.03 13.6 14 307 1.86 13.0 13242 7.8 245 2.87 10.4 12 234 2.51 9.9 12 223 2.18 9.4 12 212 2.12 9.0 12 176 1.94 7.5 12 125 1.67 5.3 12282 289 3.11 12.2 17 276 2.72 11.7 16 263 2.36 11.1 14 258 2.27 10.9 14 220 2.08 9.3 12 159 1.86 6.7 12342 350 3.20 14.8 25 333 2.79 14.1 23 316 2.41 13.4 20 311 2.30 13.1 20 210 2.12 8.9 12 186 1.89 7.9 12442 467 3.09 19.1 26 446 2.69 18.2 24 424 2.33 17.3 22 409 2.24 16.7 20 306 2.09 12.5 12 254 1.86 10.4 12482 491 3.03 20.8 30 468 2.63 19.8 28 445 2.28 18.8 25 437 2.18 18.5 25 335 2.08 14.2 15 298 1.90 12.6 12242 8.9 253 2.90 10.7 13 241 2.53 10.2 12 229 2.20 9.7 12 219 2.15 9.3 12 174 1.99 7.4 12 131 1.73 5.5 12282 298 3.16 12.6 18 285 2.76 12.1 16 271 2.40 11.5 15 267 2.30 11.3 14 229 2.13 9.7 12 166 1.93 7.0 12342 362 3.27 15.3 26 345 2.84 14.6 24 327 2.45 13.8 22 321 2.34 13.6 21 219 2.18 9.3 12 178 1.89 7.6 12442 482 3.14 19.7 28 460 2.73 18.8 25 437 2.37 17.9 23 413 2.29 16.9 21 319 2.15 13.1 13 265 1.92 10.9 12482 507 3.08 21.5 32 484 2.67 20.5 29 459 2.30 19.4 27 438 2.23 18.5 25 350 2.13 14.8 16 311 1.95 13.2 13242 10.0 260 2.92 11.0 14 249 2.56 10.5 12 236 2.22 10.0 12 218 2.21 9.2 12 181 2.03 7.6 12 137 1.79 5.8 12282 308 3.21 13.1 19 295 2.81 12.5 18 280 2.45 11.9 16 276 2.34 11.7 15 227 2.19 9.6 12 174 2.00 7.4 12342 375 3.33 15.9 28 357 2.89 15.1 26 339 2.50 14.3 23 322 2.41 13.6 21 228 2.25 9.6 12 186 1.96 7.9 12442 498 3.19 20.4 29 475 2.78 19.5 27 452 2.40 18.5 24 418 2.34 17.1 21 332 2.20 13.6 14 256 1.94 10.5 12482 524 3.13 22.2 34 500 2.72 21.2 31 474 2.34 20.1 28 438 2.29 18.6 24 364 2.18 15.4 17 301 1.99 12.8 12

Application data

Standard units, refrigerant: R-134a Evaporator entering/leaving water temperature difference: 5.6 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4 (m2 K)/W Performances in accordance with the conditions of AHRI-550/590.

Legend LWT Leaving water temperature, °C Qc Cooling capacity, kW EER Energy efficiency ratio, kW/kW q Evaporator water flow rate, l/s Δp Evaporator pressure drop, kPa

Page 18: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

18

Cooling capacities, Imperial system30XAS standard unit and unit with high energy efficiency (option 119) for Middle East conditionst

Condenser entering air temperature, °F95 105 115 118 125 130

LWT Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp Qc EER q Δp°F tons Btu/

W·hgpm feet

WGtons Btu/

W·hgpm feet

WGtons Btu/

W·hgpm feet

WGtons Btu/

W·hgpm feet

WGtons Btu/

W·hgpm feet

WGtons Btu/

W·hgpm feet

WG30XAS standard unit242 42 66.5 10.04 157 4.0 63.5 8.76 150 4.0 60.4 7.61 142 4.0 59.4 7.29 140 4.0 57.0 6.57 134 4.0 45.4 6.04 107 4.0282 77.2 10.58 182 5.1 73.9 9.26 174 4.7 70.3 8.06 166 4.2 69.2 7.72 163 4.1 66.5 6.96 157 4.0 59.3 6.48 140 4.0342 93.3 10.87 220 7.4 89.1 9.47 210 6.8 84.5 8.18 199 6.1 83.1 7.81 196 5.9 79.6 7.00 187 5.4 63.4 6.60 149 4.0442 125.2 10.62 285 7.9 119.7 9.26 273 7.3 114.0 8.02 260 6.7 112.3 7.68 256 6.5 103.6 6.97 236 5.6 77.0 6.40 175 4.0482 132.2 10.54 311 9.3 126.5 9.21 298 8.6 120.2 7.99 283 7.8 118.2 7.64 278 7.6 113.4 6.87 267 7.1 84.6 6.40 199 4.1242 44 68.6 10.15 162 4.0 65.7 8.87 155 4.0 62.5 7.71 147 4.0 61.5 7.39 145 4.0 56.8 6.73 134 4.0 47.3 6.20 111 4.0282 79.9 10.77 188 5.4 76.5 9.43 180 5.0 72.8 8.21 172 4.5 71.7 7.87 169 4.4 68.9 7.10 162 4.0 59.0 6.65 139 4.0342 96.7 11.09 228 7.9 92.3 9.66 217 7.2 87.6 8.35 206 6.5 86.1 7.98 203 6.3 79.8 7.19 188 5.4 55.2 6.62 130 4.0442 129.4 10.79 295 8.4 123.8 9.41 282 7.7 117.8 8.16 268 7.1 116.0 7.81 264 6.9 104.7 7.11 239 5.7 80.6 6.60 184 4.0482 136.5 10.62 322 9.8 130.5 9.28 307 9.1 124.2 8.05 293 8.3 122.2 7.71 288 8.0 115.5 6.99 272 7.2 88.3 6.58 208 4.4242 46 70.8 10.25 167 4.2 67.8 8.97 160 4.0 64.6 7.81 152 4.0 63.6 7.48 150 4.0 56.5 6.89 133 4.0 46.7 6.34 110 4.0282 82.7 10.96 195 5.8 79.1 9.60 187 5.3 75.4 8.37 178 4.8 74.2 8.02 175 4.6 71.3 7.24 168 4.3 61.2 6.81 144 4.0342 100.2 11.32 236 8.4 95.6 9.87 226 7.7 90.8 8.52 214 6.9 89.2 8.15 210 6.7 79.8 7.39 188 5.4 57.6 6.84 136 4.0442 133.9 10.96 305 8.9 127.9 9.56 292 8.2 121.8 8.29 278 7.5 119.9 7.93 273 7.2 105.8 7.26 241 5.8 84.1 6.79 192 4.0482 140.8 10.72 332 10.3 134.6 9.35 317 9.5 128.1 8.12 302 8.7 126.0 7.76 297 8.4 115.6 7.16 273 7.2 92.3 6.76 218 4.8242 48 72.9 10.34 172 4.5 69.8 9.05 165 4.1 66.5 7.88 157 4.0 65.4 7.55 154 4.0 55.9 7.06 132 4.0 48.6 6.51 115 4.0282 85.4 11.14 202 6.1 81.7 9.76 193 5.6 77.8 8.51 184 5.1 76.6 8.15 181 4.9 73.7 7.35 174 4.6 60.7 6.99 143 4.0342 103.7 11.54 245 9.0 99.0 10.06 234 8.2 93.9 8.69 222 7.4 92.3 8.30 218 7.1 79.5 7.59 187 5.3 60.1 7.06 142 4.0442 138.2 11.11 315 9.3 132.1 9.70 301 8.6 125.7 8.41 287 7.9 123.7 8.05 282 7.6 106.7 7.41 244 5.8 87.7 6.98 200 4.1482 145.5 10.89 343 10.9 138.8 9.48 328 10.0 131.8 8.19 311 9.1 129.6 7.82 306 8.8 117.5 7.28 277 7.4 96.4 6.94 227 5.1242 50 75.2 10.43 177 4.7 71.9 9.14 170 4.3 68.4 7.96 162 4.0 67.4 7.63 159 4.0 58.0 7.21 137 4.0 40.5 6.44 96 4.0282 88.3 11.32 209 6.5 84.5 9.92 200 5.9 80.5 8.65 190 5.4 79.2 8.30 187 5.2 73.7 7.57 174 4.5 60.0 7.18 142 4.0342 107.4 11.76 254 9.6 102.5 10.26 242 8.7 97.3 8.86 230 7.9 95.6 8.47 226 7.6 82.3 7.76 194 5.6 62.6 7.28 148 4.0442 142.9 11.28 326 9.9 136.5 9.84 311 9.1 129.8 8.54 296 8.3 127.7 8.17 292 8.0 95.8 7.78 219 4.7 85.7 7.09 196 4.0482 150.3 11.05 355 11.5 143.4 9.62 339 10.6 136.1 8.31 321 9.6 133.8 7.95 316 9.3 104.8 7.70 247 6.0 100.4 7.11 237 5.530XAS high energy efficiency unit (option 119)242 42 65.5 9.62 154 4.0 62.5 8.39 147 4.0 59.3 7.28 140 4.0 58.3 6.96 137 4.0 48.7 6.30 115 4.0 32.3 5.31 76 4.0282 76.6 10.24 181 5.0 73.3 8.95 173 4.6 69.7 7.78 164 4.2 68.6 7.45 162 4.0 63.2 6.75 149 4.0 50.6 6.23 119 4.0342 92.6 10.51 218 7.3 88.3 9.15 208 6.6 83.7 7.89 197 6.0 82.2 7.53 194 5.8 67.9 6.89 160 4.0 52.2 6.19 123 4.0442 124.2 10.24 283 7.8 118.7 8.92 270 7.2 112.9 7.72 257 6.6 111.2 7.39 253 6.4 79.9 6.75 182 4.0 70.9 6.05 161 4.0482 131.0 10.14 309 9.2 125.2 8.85 295 8.4 118.8 7.67 280 7.7 116.8 7.33 275 7.4 104.7 6.74 247 6.1 83.5 6.19 197 4.0242 44 67.6 9.72 159 4.0 64.7 8.49 152 4.0 61.4 7.37 145 4.0 60.4 7.05 142 4.0 48.2 6.45 113 4.0 33.8 5.50 80 4.0282 79.3 10.41 187 5.3 75.9 9.11 179 4.9 72.1 7.93 170 4.4 71.0 7.59 167 4.3 63.0 6.92 148 4.0 42.9 6.13 101 4.0342 95.9 10.72 226 7.8 91.5 9.33 216 7.1 86.7 8.05 204 6.4 85.2 7.68 201 6.2 67.4 7.08 159 4.0 50.5 6.22 119 4.0442 128.3 10.40 292 8.3 122.6 9.06 279 7.6 116.7 7.85 266 6.9 114.8 7.50 262 6.7 83.5 6.95 190 4.0 74.2 6.26 169 4.0482 135.1 10.21 318 9.7 129.1 8.91 304 8.9 122.7 7.72 289 8.1 120.6 7.38 284 7.8 91.2 6.91 215 4.7 87.2 6.36 205 4.3242 46 69.7 9.81 164 4.1 66.7 8.57 157 4.0 63.4 7.45 150 4.0 60.2 7.24 142 4.0 50.1 6.61 118 4.0 35.4 5.70 84 4.0282 82.0 10.60 193 5.7 78.4 9.27 185 5.2 74.6 8.07 176 4.7 73.5 7.73 173 4.6 62.6 7.11 148 4.0 45.1 6.36 106 4.0342 99.4 10.93 234 8.3 94.8 9.52 224 7.6 89.9 8.21 212 6.8 88.3 7.84 208 6.6 59.7 7.22 141 4.0 52.8 6.44 125 4.0442 132.7 10.55 303 8.7 126.7 9.19 289 8.0 120.5 7.96 275 7.3 116.2 7.66 265 6.8 87.0 7.14 198 4.0 72.1 6.33 164 4.0482 139.6 10.33 329 10.2 133.1 8.97 314 9.3 126.4 7.77 298 8.5 124.3 7.43 293 8.2 95.3 7.10 225 5.1 84.8 6.48 200 4.1242 48 71.8 9.89 170 4.3 68.6 8.65 162 4.0 65.2 7.52 154 4.0 62.2 7.33 147 4.0 49.5 6.78 117 4.0 37.1 5.89 88 4.0282 84.8 10.78 200 6.0 81.1 9.43 191 5.5 77.1 8.20 182 5.0 75.9 7.86 179 4.8 65.0 7.27 153 4.0 47.3 6.59 112 4.0342 102.9 11.14 243 8.8 98.1 9.70 231 8.0 93.0 8.37 219 7.2 91.4 7.99 216 7.0 62.2 7.44 147 4.0 50.7 6.46 120 4.0442 137.0 10.70 313 9.2 130.8 9.32 298 8.4 124.3 8.07 284 7.7 117.5 7.81 268 6.9 90.7 7.32 207 4.3 75.4 6.54 172 4.0482 144.3 10.50 340 10.8 137.5 9.12 325 9.9 130.4 7.86 308 8.9 124.6 7.61 294 8.2 99.4 7.27 235 5.4 88.4 6.66 209 4.4242 50 74.0 9.97 175 4.6 70.7 8.72 167 4.2 67.2 7.59 159 4.0 61.9 7.54 146 4.0 51.3 6.93 121 4.0 39.0 6.09 92 4.0282 87.7 10.96 207 6.4 83.8 9.60 198 5.9 79.7 8.35 188 5.3 78.4 8.00 185 5.1 64.5 7.47 152 4.0 49.6 6.82 117 4.0342 106.5 11.35 251 9.4 101.5 9.88 240 8.6 96.3 8.52 227 7.7 91.5 8.21 216 7.0 64.7 7.66 153 4.0 53.0 6.69 125 4.0442 141.7 10.87 323 9.7 135.2 9.47 309 8.9 128.4 8.20 293 8.1 118.8 7.97 271 7.0 94.5 7.51 216 4.6 72.8 6.63 166 4.0482 149.1 10.67 352 11.3 142.1 9.27 335 10.4 134.7 7.99 318 9.4 124.7 7.80 294 8.2 103.4 7.43 244 5.8 85.6 6.80 202 4.1

Application data

Standard units, refrigerant: R-134a Evaporator entering/leaving water temperature difference: 10°F Evaporator fluid: chilled water Fouling factor: 0.001 h ft2 °F/Btu Performances in accordance with the conditions of AHRI-550/590.

Legend LWT Leaving water temperature, °F Qc Cooling capacity, tons EER Energy efficiency ratio, Btu/W·h q Evaporator water flow rate, gpm Δp Evaporator pressure drop, feet WG

Page 19: Air-Cooled Liquid Chillers - AHI Carrierahi-carrier.ae/download.asp?frm=docs/pd_048.pdf · Unit with option 279 (compressor enclosure) Air-Cooled Liquid Chillers The 30XAS Aquaforce

Order No.: 13466-20, 10.2012. Supersedes order No.: 13466-20, 03.2010 Manufactured by: Carrier SCS, Montluel, France.Manufacturer reserves the right to change any product specifications without notice. Printed in the European Union.The cover illustration is solely for illustration purposes and not contractually binding.