Contents
Cause of air leakage
Problems
Sites
Benefits
Ventilation
Air barriers
Locate and seal leaks
Measure leaks Case Studies
Multi – Fan manual available free
Colin Genge
Colin Genge
USACE Manual
free
Colin Genge
Variation in pressure over 11 winter days
Stack Pressure + Holes = Leaks
Stack EffectWarm air rising
Cold air falling
Primary Boundaries for cold climates
14 windows open at -25 Cinset shows open window
Benefits of airtightness 1
CFM 75/ft2 Added energy cost Impact on IAQ
0.1 0% Negligible
0.25 5% Small
0.4 10% Moderate
1.0 25% Large
2.0 40% Uncontrolled, severe
Benefits of airtightness 4
Impact of Air Tightness – Typical Multi-Unit Residential
0
5
10
15
20
25
30
35
No Air Leakage Very Tight Tight – Low Average
Tight – Average Tight – High Average*
Leaky Very Leaky,Windows Open
Annu
al S
pace
Hea
t Con
sum
ptio
n, k
Wh/
m2
Suite Electric Space Heat vs Air Leakage Rate
The impact of air leakage of large buildings 1
© 2010 Retrotec Inc.
Real problems in large buildings 1
Real problems
Real problems in large buildings 2
Real problems in large buildings 3
Real problems in large buildings 4
Real problems in large buildings 5
Benefits of airtightness 7
Benefits of airtightness 8
Benefits of airtightness 3
Benefits of airtightness 6
Disconnect Floors
Seal shafts
Elevator piston effect
Improved Air tightness in Elevator Shafts
“shall pass …0.25 CFM/sq ft …at 75 Pa …”
Why air leakage is measured 1
Standards for air leakage 1
Required House tightness?
Standard Requirement CFM75/ ft2
LEED 1.25 in2 EfLA @ 4 Pa / 100 ft2 0.30
2009 IECC 7.0 ACH50 0.55
2012 IECC 3.0 ACH50 0.25
Cdn R-2000 1.5 ACH50 0.13Passiv Haus 0.6 ACH50 0.05
Looser
Tighter
Large Bldg tightness?
4 story building, 120 x 110 x 40 ft, n= 0.65 CFM75
/ ft2
USA ASHRAE 90.1 Leaky 0.60France 1.2 m3/m3/h @4Pa /m2 0.44USA IECC, Washington State 0.40Russia 1.5 l/s @50Pa /m2 0.385
UK TS-1Commercial, Best 5 m3/h @50Pa /m2 0.36
USA ASHRAE 90.1 Average 0.30
USA USACE, IGCC 0.25
UK TS-1Commercial Tight 2 m3/m3/h @50Pa /m2 0.14USA ASHRAE 90.1 Tight 0.10
Looser
Tighter
0.1 to 0.6 CFM75/ft2 total envelope= 0.4 to 2.3 liters/s @ 50 Pa /m2
Guideline air leakage levels 1
Why air leakage is measured 2
Why air leakage is measured 3
Compartmentalize the laundry room
Recommendations
Assemblies-0.01 cfm /ft2 @75 Walls 0.1 cfm /ft2 @75 Slabs 0.01 cfm /ft2 @75 Paint all block walls Seal all shafts at each floor Enclose elevator lobbies from slab to slab Electronic exhaust fan & fire dampers
© 2010 Retrotec Inc.
Typical air leakage sites 1
Locate leaks with door fan using smoke, infrared, hand
Door fan finds leaks
Door fans and infrared camera
Typical air leakage sites 4
Smoke Testing Used to Confirm Air Barrier Discontinuity
Why air leakage is measured 4
Т=-22⁰С Т=+19⁰С ΔТ=41 ⁰С
ΔP= + 8 Pa
ΔP= - 8 Pa
Without and With depressurization
Sealing air leakage sites
Using a door fan increases effectiveness of air seal crew
Longevity of air sealing
Sealing air leaks
Typical air leakage sites 3
Typical air leakage sites 2
Door-Fan componentspanel + calibrated fan +gauges
Bigger
Seal these
Open interior doors
Setting up the test fans
What components of buildings can be measured?
Building components that can be measured 1
Building components that can be measured 2
Building components that can be measured 3
Building components that can be measured 4
Building components that can be measured 5
Measuring apartment air leakage
Measure Entire Envelope
Measure Entire Envelope
Slab leakage – total floor leakage
© 2010 Retrotec Inc. © 2010 Retrotec Inc.
Building components that can be measured 5
Building components that can be measured 6
Building components that can be measured 7
CanadaCGSB 149.10USAASTM E-779-10
UK
EuropeEN13829
Standards for air leakage 1
CanadaCGSB 149.15
UK TS-1
EuropeEN13829
USAAir Leakage Protocol
Standards for air leakage 1
ASTM USACE Reason
Bias readings 2 288 accuracy
Max. bias 42% 30% & 10 % accuracy
Height restriction Yes No Flexibility
Temperature & wind restriction Yes No Flexibility
Min. test pressure 10 Pa 25 Pa stability
Min. # building/flow readings 5 120 accuracy
Min. test point interval 10s 20s accuracy
Gauge accuracy 5% 1% accuracy
© 2010 Retrotec Inc.
© 2010 Retrotec Inc.
Standard ASTM CGSB EN13829 ATTMA USACE LEED
Origin USA Canada Europe UK USAWA State
World
Acceptable conditions
41 to 95°F< 5 mph wind
<12.4 mph wind
<13.4 mph windheight x ΔT<500m°C
<13.4 mph windheight x ΔT<250m°C
95% confidenceinterval
41 to 95°F< 5 mph wind
Standardized measurement methods 1
Standard ASTM CGSB EN13829 ATTMA USACE WA State LEED
Origin USA Canada Europe UK USA WA State North America
Range 10 to 60 Pa 15 to 50 Pa 10 to 50 Pa 10 to 60 Pa 25 to 75 Pa 25 to 80 Pa 10 to 60 Pa
Standardized measurement methods 2
Standard ASTM CGSB EN13829 ATTMA USACE WA State LEED
Number ofpoints
5-10 1, 2, or 7 5 7 10 10 5
© 2010 Retrotec Inc.
Standardized measurement methods 3
Standard ASTM CGSB EN13829 ATTMA USACE WA State LEED
Direction Both Depress. Both Both Both Both
Standardized measurement methods 4
Standard ASTM CGSB EN13829ATTMA
USACE LEED IECC
Origin USA Canada Europe USAWA State
North America
Results EfLA 4ACH50CFM50
EqLA10ACH50
m3/h50/m2
m3/h4/m2
ACH50
CFM75/ft2 EfLA 4 ACH50CFM25/100 ft2
Suggest using only:ACH50 EqLA 50/Floor area x 1,000,000
•Unitless•Always whole number•Calibrate against holes of known sizes•Always reference results to 50 Pa
Standardized measurement methods 5
Numerous Apartment Buildings Tested
Leakage on all 6 sidescm2/m2 @ 50 Pa
3.1 1.0 1.5 2.3 6.5
0
5
10
15
20
25
30
Exterior Walls
Exterior Walls - Normalized Leakage Area @ 50 Pa
12.85
21.77
4.792.52
4.14 2.68
0
5
10
15
20
25
Bldg. 2 -Polyethyelene/ SBPO
Housewrap
Bldg. 4 -Polyethylene/Building
Paper
Bldg. 3 608 - Peel andStick/Gypsum
Bldg.3 311 - Peel andStick/Gypsum
Bldg. 3 611 - Peel andStick/Gypsum
Bldg. A - Peel andStick/Gypsum
No
rmali
zed
Leakag
e A
rea (
cm
2/m
2)
Party Walls
Suite Demising Walls by Type - Normalized Leakage Area @ 50 Pa
0.38 0.17
5.13
0.47 0.42
1.99
3.30
1.88
4.24
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Concrete -Bldg. A - 802-
801
Concrete -Bldg. A - 802-
803
Wood Frame -Bldg. 2 - 401-
Stair
Wood Frame -Bldg. 2 - 401-
402
Wood Frame -Bldg. 4 - 309-
308
SS Gypsum -Bldg. 3. - 608-
lounge
SS Gypsum -Bldg. 3. - 608-
609
SS Gypsum -Bldg. 3. - 311-
309
SS Gypsum -Bldg. 3. - 611-
609
No
rmali
zed
Leakag
e A
rea (
cm
2/m
2)
Floor Leakage
Floors by Type - Normalized Leakage Area @ 50 Pa
1.16
0.00 0.000.16
0.57
0.12 0.07 0.090.0
0.5
1.0
1.5
2.0
Wood - Building2
Wood/ConcTopped - Building
4 (4th)
Wood/ConcTopped - Building
4 (3rd)
Concrete -Building A (8th)
Concrete -Building A (9th)
Concrete -Building 3 (3rd)
Concrete -Building 3 (4th)
Concrete -Building 3 (6th)
Norm
aliz
ed L
eaka
ge A
rea
(cm
2 /m2 )
Air leakage Test Protocol for U.S. Army Corps Buildings
Requirements
Proper design Plan review Ongoing inspection Mock up building materials Pass air leakage protocol o easyo not just the ASTM E779 standard
Need to know the Air Barrier
113
Guiness World Record15,000,000 cubic feet
Hallenumfang = 1,2 km
9 x 2-Kanaldruckmessdosen mit Referenzschlauch ins Gebäudeinnere
Ian Jack’s Guiness test in Germany… Video embedded
Year of Construction
Year of Air-barrier retrofit?
Number of Stories
Floor Area
Enclosure Area Tested Permeablity
ft2 ft2 cfm/ft2 @75Pa2011 - 7 96,882 76,084 0.292011 - 7 96,882 76,084 0.392011 - 7 96,882 76,084 0.481987 2000 4- - 0.921987 2000 4- - 0.651985 2006 23- - 0.371985 2006 23- - 0.142001 - 4- - 3.052001 - 4- - 0.431990 2001 6- - 0.291990 2001 6- - 0.201990 2001 6- - 0.241990 2001 6- - 0.341990 2001 6- - 0.351990 2001 6- - 0.231978 - 7- - 1.771978 2010 7- - 0.901973 - 22- - 0.441973 2008 22- - 0.37
average 0.62
Year of Construction
Year of Air-barrier retrofit?
Number of Stories
Floor Area
Enclosure Area
Tested Permeablity
ft2 ft2 cfm/ft2 @75Pa2012 -2009 -
average 0.17
USACE test of 300 buildings 0.17
Real life test: EMAD
Antwerp, Belgium• Envelope Area = 11,250 m2
• 0.601 CFM/ft2 @ 75Pa• 8.22 m3/h/m2
Real life test: BTC
South Carolina, USA• Envelope A = 136,820ft2
• 0.08 CFM/ft2 @ 75Pa
Real life test: Retrotec
Vancouver, Canada• Envelope Area = 25,000 ft2
• 0.4 CFM/ft2 @ 75Pa• 7.3 m3/h/m2
Imbalanced flow can be caused by individual set points.
Colin Genge
Individual set point between zones Common set point within a zone.
Colin Genge
Virtual Gauge
1-855-738-7683 | [email protected] | www.retrotec.com
Simulated Mode with results. Monitor & Control several gauges simultaneously
GFI compatible
Links to other fans
Breaker
Adjust max speed
Common Control
Common Control
Individual Control
© 2010 Retrotec Inc.
Types of door fan tests 3