AIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon, C.P. 64520 Tel. (81) 8125-7300 E-mail: [email protected]
Transcript
Page 1: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

AIR MAKE - UP&

INDUSTRIAL HEATINGEQUIPMENT

Proveedora Termica del Norte, S.A. de C.V.Nardo 911 ote. Col. Cementos, MonterreyNuevo Leon, C.P. 64520Tel. (81) 8125-7300E-mail: [email protected]

Page 2: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

Titan Air, Inc. began production in 1982, building air make-up equipment for the spray booth industry. After good success in this market, future plans where drawn up. In 1987 Titan Air diversified it’s product line and entered into the HVAC market. This has proved to be a very good decision. While the finishing industry is still a large segment of Titan Air’s business, the HVAC industry has become the greatest contributor to the company’s growth. Titan Air further diversified its product offerings in 1998 with the manufacturing and marketing of pneumatic personnel lifts for use in hazardous environments such as spray booths.

Over the years, Titan Air has specialized in designing and constructing custom air handling equipment. There have been very few projects that Titan Air hasn’t been willing to tackle. Many special project requests are repeat business for similar special equipment built by Titan Air.

Titan Air has been an industry leader in obtaining ETL approvals. It was the first manufacturer to have 2 speed applications (both 100% air make-up and AR/80) and units utilizing a variable frequency drive to vary the air volume output, tested and approved.

In 1999 Titan Air’s product line was tested by ETL according to the new ANSI Z83.4 / CSA 3.9 M99 standard for non recirculating units. Titan Air was the first in the industry to gain ETL approval to this new standard. Also, Titan Air is now recognized as an approved UL508A panel shop which enables us to offer customers an ETL label on specialized remote control panels.

Titan Air also received approval from ETL to label air handlers, evaporative coolers and air handlers utilizing steam, hot water, chilled water, DX and electric coils. We believe we are the first in our industry to offer this also.

Titan Air is located on 6 acres in Osseo Wisconsin and has approximately 70,000 square feet of manufacturing space and 4,000 square feet of office space, plus two additional storage buildings.

Titan Air pledges to continue product improvements and offerings through the use of customer input and new technologies that become available. As a valued customer, we realize that you have come to expect nothing less.

A BRIEF HISTORY...

WELCOME !

A I R I N C O R P O R A T E D

Page 3: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D24 MONTH WARRANTY

Manufacturer hereby warrants its products against defects in material and workmanship for a period of (24) twenty four months from date of shipment . Warranty sheet is due back within (30) thirty days of start-up from date of delivery for 24 month warranty to be effective. After (30) thirty days, and up until (60) sixty days, a (12) twelve month warranty will be observed. All warranties are null and void if warranty sheet is not received within (60) sixty days from start-up or 120 days from date of delivery. NO EXCEPTIONS WILL BE MADE. Manufacturer reserves the right at manufacturers option, to replace or repair free of charge, any part proven to be defective. Prompt notification of defective part must be given and defective part must be returned freight prepaid within (30) days of notification. WARRANTY INCLUDES ONLY PARTS SUPPLIED BY MANUFACTURER INCIDENTAL COSTS AND LABOR CHARGES SHALL BE THE RESPONSIBILITY OF OTHERS. This warranty does not cover fuses, belts, filters or water damaged parts which are the result of improper storage or installation. This warranty is void in event the product is improperly installed and / or operated under conditions other than normal published ratings, improperly maintained, misused or not in compliance with applicable codes: or not in accordance with manufacturer's operating instructions. This warranty is void if attempts to correct or repair any alleged defective part or parts are made by unauthorized personnel without manufacturer's written approval. In no event shall manufacturer be held liable for any damage, incidental or consequential, arising from the installation, performance or operation of the product. This warranty supersedes, voids and / or is in lieu of any other verbal or written understanding which may not be in total accordance with this expressed warranty. Warranty parts must be returned to manufacturer within 60 days to receive credit.

Page 4: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

GENERAL INFORMATION - WARRANTY Series Description / Ordering Info. Needed .................................. Component Descriptions ...............................................................Equipment Selection .....................................................................“TA” - AMU & AR Horizontal Units / Accessory Info. ......................“TAM” Horizontal Unit / Accessory Information ............................. 100% AMU Vertical Unit Assembly ...............................................Air Recirc. Vertical Unit Assembly .................................................Building Pressurization ..................................................................Estimated Unit Weights ................................................................. Accessory Pressure Drops ............................................................

“TAM” Horse Power Chart .............................................................“TA” - AMU & AR Horse Power Charts ..........................................

100% AIR MAKE-UP General Information .......................................................................“TA” - AMU Standard / Optional Features ......................................H.O.T. (paint / bake systems) ........................................................“TAM” Standard / Optional Features .............................................

HORIZONTAL UNIT DIMENSIONS“TAM” Horizontal & Down Discharge ...........................................Horizontal Discharge ....................................................................Down Discharge .............................................................................Vertical Discharge ..........................................................................

OUTDOOR VERTICAL UNIT DIMENSIONS Horizontal Discharge ....................................................................Vertical Discharge ...........................................................................

INDOOR VERTICAL UNIT DIMENSIONS - CONSULT FACTORY AR/80 - AIR RECIRCULATION (Industrial Heating)

Applications ...................................................................................Standard / Optional Features ........................................................General Information ......................................................................

HORIZONTAL UNIT DIMENSIONSHorizontal Discharge ....................................................................Down Discharge ..............................................................................Vertical Discharge ..........................................................................

OUTDOOR VERTICAL UNIT DIMENSIONS Horizontal Discharge ....................................................................Vertical Discharge ...........................................................................

INDOOR VERTICAL UNIT DIMENSIONS - CONSULT FACTORY DEMAND AIR

General Information .......................................................................Standard / Optional Features ........................................................

Energy Savings Examples ..............................................................SWIMMING POOL AREA EQUIP.

General Information .......................................................................Standard / Optional Features ........................................................

EVAPORATIVE COOLING General Information .......................................................................Standard / Optional Features ........................................................

Examples / Definitions ..................................................................... Dimensions ....................................................................................

SPECIAL UNITS Hydronic / DX / Electric Coil Applications .......................................Standard / Optional Features .........................................................

Hydronic / DX / Electric Coil Definitions .......................................... Examples ........................................................................................

ACCESSORIES INTAKE

Hoods, Filters, Dampers .................................................................. DISCHARGE

Dampers, Diffusers ......................................................................... MOUNTING FIXTURES

Curbs ................................................................................................Service Platforms ............................................................................

CONTROLS Control Systems ..............................................................................

TABLE OF CONTENTS

1-1

1-21-31-41-51-61-71-81-9,101-111-121-131-14:18

2-12-22-3,42-5

2-62-72-82-9

2-102-11

3-13-23-3,4

3-53-63-7

3-83-9

4-14-24-3

5-15-2:4

6-16-26-36-4

7-17-27-37-4

8-1

8-2

8-3:58-6

9-1:4

All sizes, configurations and weights of components shown and not shown in this catalog are subject tochange without notice. Do not use measurements for construction purposes unless verified by factory.

TITAN AIR INCORPORATED13901 16th Street P.O. Box 717, Osseo, WI 54758

Phone (715) 597-2050 Fax. (715) 597-3620www.titan-air.com

CATALOG 108 TA-01-04This catalog supersedes all prior.

Printed in U.S.A. ©2004 TITAN AIR INCORPORATED

A I R I N C O R P O R A T E D

Page 5: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DSERIES DESCRIPTION

1-2

SAMPLE MODEL NO. TA - 220 - NG - HRH - AR/80

MODEL DESIGNATIONTWIN BLOWERSBLOWER SIZEHEAT MEDIUMCABINET CONFIGURATIONSPECIALTY SUFFIX

CABINET CONFIGURATION DEFINITIONS :H = Horizontal intake and / or dischargeV = Vertical intake and / or dischargeD = Down dischargeR = Right hand controls (facing controls, intake is left, discharge is right)L = Left hand controls (facing controls, intake is right, discharge is left)

CABINET ARRANGEMENTS READ :INTAKE - CONTROLS - DISCHARGE EXAMPLE: HRH = Horizontal intake, Righthand controls, Horizontal discharge.

SPECIALTY SUFFIX :AR - Unit will operate between 20% & 100% fresh air, and up to 80% return air on AR/80’s.Other percentages availableDA - DEMAND-AIR, (Unit featuring a frequency drive)H.O.T. - High Outlet Temp. (paint / bake system)AH - Air Handler

= FRESH AIR INTAKE

= DISCHARGE DIRECTION

= RETURN AIR INTAKE (ON AR UNITS ONLY)

HEAT MEDIUM :NG - NATURAL GAS BURNERLP - LIQUID PETROLEUM GAS BURNERS - STEAM COILHW - HOT WATER COILE - ELECTRIC COILCOOLING MEDIUM :CW - CHILLED WATER COILDX - DIRECT EXPANSION COILEV - EVAPORATIVE COOLINGCFM RANGES :TA - 109 - 1,200 - 2,800TA - 112 - 2,400 - 5,000TA - 115 - 4,000 - 7,500 TA - 118 - 6,000 - 10,000 TA - 120 - 8,500 - 14,000TA - 122 - 10,000 - 18,000TA - 125 - 15,000 - 21,000TA - 127 - 16,000 - 27,500 TA - 130 - 20,000 - 30,000TA - 133 - 30,000 - 42,000TA - 136 - 31,000 - 46,000TA - 215 - 8,000 - 15,000TA - 218 - 12,000 - 19,000 TA - 220 - 16,000 - 30,000TA - 225 - 26,000 - 42,000TA - 227 - 36,000 - 52,000 TA - 230 - 45,000 - 60,000TA - 233 - 60,000 - 74,000TA - 236 - 70,000 - 85,000TA - 239 - 75,000 - 100,000TA - 242 - 90,000 - 120,000INFO. NEEDED WHEN ORDERING OR QUOTING :Temperature RiseControl System (Room or Discharge) External Static Pressure Discharge Arrangement CFM Required Voltage Available Gas Pressure AvailableOptional AccessoriesIndoor or Outdoor MountAgency : (STD,IRI,FM,etc.)

HLH

HRH HRD

HLD HLV

HRV

VRH VLH VRV / VLV

DISCHARGE ARRANGEMENTS (others available)

rev. 01-04

Page 6: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

WEATHER PROOF ENCLOSURE : Protects interior components from elements.INLET HOOD WITH BIRD SCREEN : Standard hood is 45°, full turn-down and mushroom type hoods are available.FILTER SECTION : Outside and return air (if applicable) available with cleanable or disposable filters.HOOD / FILTER COMBO. : Face of inlet hood has provisions for 1” cleanable filters.ROOF CURB : 18"(std) curb for flat or pitched roofs, shipped uninsulated and unassembled. INTAKE DAMPER : Field mounted on the intake side of unit. Mount near wall or ceiling on indoor units. Prevents outside air from moving through the unit when not operating. (Recommended for indoor units, cover required for outdoor mounting)DISCHARGE DAMPER : Field mounted indoors on discharge side of unit. Prevents building air from moving through the unit when not operating. (Recommended for outdoor units, cover required for outdoor mounting)DISCHARGE DIFFUSERS : 2 & 3 way or 4 way box type outlet arrangements with horizontal and/or vertical (adjustable) turning vanes. Field mounted and adjusted.CASING INSULATION : 1" thick 1.5# density fiberglass insulation, pinned and glued.INTERIOR LINER : Interior sheet metal liner.VIBRATION ISOLATION : Hanging, base or blower / motor isolation. (neoprene is std)EXTENDED GREASE LINES : Extends grease fittings on blower bearings to unit casing.KEY LOCK SWITCHES : Any operation switch can be a key lock switch.TWO SPEED BLOWER MOTOR : Unit CFM will change with High and Low speeds.CLOGGED FILTER LIGHT : Indicates when filters need cleaning or changing.OPERATING LIGHTS : Provide a visual check of system operations at remote panel.SMOKE ALARMS : Alarm will sense the presence of smoke and shut down the system. Can be connected to an audible alarm or light located in remote panel.

HIGH TEMPERATURE LIMIT CONTROL : Standard on all Titan direct fired units. Mounted in discharge, limit will shut down burner when temperature exceeds the set point.LOW TEMPERATURE LIMIT CONTROL : Turns unit off when low temperature air is being discharged from the unit.BURNER "ON - OFF" DUCTSTAT : Will prevent burner operation if outdoor air is above the set point.LOW FIRE START : Timer prevents burner from going to high fire for a short period of time after call for heat.UNNOCCUPIED THERMOSTAT : Unoccupied mode, will cycle unit to maintain a temperature in the building usually 10°-15° lower than occupied setting.TIME CLOCK : Allows the programing of occupied / unoccupied hours.RECIRCULATING CONTROL : Titan Air controls OA / RA dampers automatically by pressure (inside vs. outside) by a remote mounted rotary dial or 2 position control. RECIRCULATING DAMPERS : Dampers to control OA and RA.OVERRIDE STAT : Room thermostat that overrides discharge temperature control by up to 40°.AUDIBLE ALARM : Activated by low temperature, flame failure, etc. FIRST STAGE REGULATOR : Titan gas manifolds can be designed to handle up to 2 psi inlet gas pressure. A high pressure regulator is required for pressures over 2 psi.VARIABLE FREQUENCY DRIVE : Used on DEMAND AIR systems to vary the blower motor speed and delivered CFM for positive building pressurization with substantial energy savings.PHOTOHELIC PRESSURE SWITCH : Provides visual display and set point relative to space pressure. TIMER RELAYS : Used on custom units and control panels to control duration and sequence of unit's operational modes.CIRCUIT ANALYZER : Indication of unit status.Located in unit vestibule.

1-3

A I R I N C O R P O R A T E DCOMPONENT DESCRIPTIONS

rev. 01-04

Page 7: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

1-4

EQUIPMENT SELECTION

Whether selecting direct fired air make-up or industrial heating equipment, for quoting or application, the required information will be the same.

1. Air Volume (CFM) - Each Titan unit is custom designed and manufactured to meet therequirement of a particular application. There are points where several models overlap in air volume capacities. The difference being a larger blower moving the same air volume will typically require less horse power and be somewhat quieter than the smaller blower. At the same time the unit with a larger blower will be more expensive, unless it overlaps with a smaller twin blower unit.

2. External Static Pressure (ESP) - ESP is the static pressure developed by field supplied andinstalled components to the system (ductwork, coils, etc.). The stated ESP on a quote request or equipment order plays a role in determining the motor horsepower required to deliver the required air volume. It is important for the ESP on quote requests and orders to be as accurate as possible. Titan’s Direct Fired equipment will have two fixed point air flow sensing devices to monitor the air movement across the burner. These air flow safeties are designed to shut the burner down if the air flow is above or below the fixed set points. An overstated ESP will cause a high air flow and high pressure drop across the burner. An understated ESP will cause low air flow and low pressure drop across the burner. Either condition can cause the burner circuit to drop out.

3. System Electrical Supply (Volts/Phase/Hertz) - The nominal voltages Titan works with are:120/1/60, 208/1/60, 230/1/60, 208/3/60, 230/3/60, 460/3/60. It is important to research this and pass on the correct information as to system electrical supply. Field changing components to accommodate a different system supply than what was ordered can get expensive.

4. System Gas Supply Pressure - Titan’s gas valve train charts, and pricing, are set up in a fourtier configuration with 7”wc, 14” wc, 1psi or 2psi minimum supply, 2# max. gas pressures at each tier. The lower the stated supply gas pressure is, the larger the gas valve train becomes at any given BTU level. The worst situation here would be stating there is 2 psi supply pressure and only having 7” wc supply on the job. The selected components would not have the flow capacity, at the lower pressure, to support required BTU out put of the burner.

5. Type of Gas - The two types of fuel gases typically used in Direct Fired applications areNatural Gas and LP gas.

6. Agency Requirement (ANSI, IRI or FM) - ANSI is the Standards Agency to which Titanequipment is designed and manufactured. IRI and FM are insurance underwriters that may be involved in insuring a particular building. Each one of the two, IRI & FM, have their own requirements for gas valve trains. It is important to check for the need of either FM or IRI before asking for quotes or issuing purchase orders for equipment.

7. Unit Configuration - For each model there are a number of configurations, including but notlimited to: Horizontal intake w/ horizontal discharge, horizontal intake w/ down discharge, horizontal intake w/ vertical discharge, vertical intake w/ horizontal discharge, vertical intake w/ vertical discharge, etc.

8. Right or Left hand control - All equipment can be ordered with either right or left hand control.This is determined by which way the air moves through the unit. If you where facing the control vestibule and the air is discharging from the unit to your right, it would be a right hand unit.

9. Temperature Rise - Temperature rise is determined by two factors, first, design outdoortemperature and second, desired delivered temperature. The difference between the two will be the temperature rise of the unit. Direct fired burners are purchased in sections and put together at Titan’s factory to supply each unit with the BTU’s required to achieve stated temperature rise. In most cases an individual unit will not have the burner capacity to increase the temperature rise after the fact.

10. Temperature Control Scheme - The suggested temperature control scheme for an Air Make-Up system would be a discharge temperature control. There are two versions of Direct Fired Recirculating heaters (AR80 & AR/75), each having their own requirements for temperature control systems. The AR/80 will be controlled by a Direct Digital Control (DDC) system while the AR/75 can be controlled by a more standard room control scheme. See control section of this catalog for specifics.

11. Accessories - There are a number of factory built accessories available with each model.Intake hoods, intake filters, intake or discharge dampers, discharge diffusers, etc. These accessories are contributors to the total static pressure the fan must work against. Knowing what accessories are to be included at the outset will make a smoother selection process.

rev. 01-04

Page 8: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

1-5

A I R I N C O R P O R A T E D“TA” SERIES UNIT / ACCESSORY INFO.

OBSERVATION PORT(on back)

SERVICE DISCONNECT

CAULKINGOR GASKETMATERIAL(by others)

DISCHARGE DAMPER - (HRD)(some units can have damper built in for an added cost, check with factory)

RETURN AIR FILTER SECTION(AR units only)

TA-233 through 242Filter sections are accessed from both sides.

2 DAMPER ACTUATORS

Split(must seal) INTAKE

HOOD

INTAKEFILTERSECTION

INTAKEDAMPERS

DISCHARGE DAMPER - (HRH)

GAS CONN. &LABELS

REMOTEPANEL

On split units, contractor is responsible for interconnection of components

ELEC. / GASTRAINACCESS

BLOWERACCESS

AR & all two speed (H.O.T. & Demand Air) units have dampers in profile.

INTAKE DAMPER

All components must be caulked to prevent water from entering system.Recaulk lift plates after installation.

Accessories mount with all access doors and damper actuators facing same direction as unit access doors.

Intake or discharge dampers should be mounted at the inside wall or ceiling.If outdoor mounted, a motor cover is required.

Note: All main power wiring must be sized and installed in accordance with applicable local, state or federal codes. Accessories should be supported after installation (supports by others). Note: Most accessories are larger than the openings on the unit. Accessories can be mounted directly to unit, unless otherwise noted.

Due to the infinite installation possibilities, a section of duct or transition may be required for proper accessory mounting. These items are the responsibility of others. TA-233 through 242 Feature 2 pc accessories and need to be assembled, supported and sealed in the field.

INTAKE HOOD orHOOD / FILTER COMBOAll w/ BIRDSCREEN

Lifting plates (larger twin blower units only)

CURB(Field assembled)

INTAKEFILTER SECTION

Mount Indoors

Extended channel(indoor hanging units require a cradle - by others)

Mount Indoors

rev. 01-04

ALL SUBJECT TO CHANGE,CONSULT FACTORY WITH ANY QUESTIONS

Intake damper will be built into filter section if both accessories are ordered for outdoor application. A motor cover is required.

Page 9: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

1-6

A I R I N C O R P O R A T E D“TAM” SERIES UNIT / ACCESSORY INFO.

OBSERVATION PORT(on back or end)

SERVICE DISCONNECT

CAULKINGOR GASKETMATERIAL(by others)

DISCHARGE DAMPER - (HRD)(can be built into unit cabinet for an added cost)

DISCHARGE DAMPER - (HRH)

GAS CONN. &LABELS

REMOTEPANEL

ELEC. / GASTRAINACCESS

BLOWERACCESS

INTAKE DAMPER

All components must be caulked to prevent water from entering system.

Accessories mount with all access doors and damper actuators facing same direction as unit access doors.

Intake or discharge dampers should be mounted at the inside wall or ceiling.If outdoor mounted, a motor cover is required.

Note: All main power wiring must be sized and installed in accordance with applicable local, state or federal codes.

Accessories should be supported after installation (supports by others).

Note: Most accessories are larger than the openings on the unit. Accessories can be mounted directly to unit, unless otherwise noted. Due to the infinite installation possibilities, a section of duct or transition may be required for proper accessory mounting. These items are the responsibility of others.

INTAKE HOOD orHOOD / FILTER COMBO orHOOD / FILTER / DAMPER COMBOAll w/ BIRDSCREEN

CURB(Field assembled)

INTAKEFILTER SECTION

Mount Indoors

Base flange(indoor hanging units require a cradle - by others)

rev. 01-04

Intake damper will be built into hood / filter combo or filter section if both accessories are ordered for outdoor application. A motor cover is required.

HOOD / FILTER /DAMPER COMBO

Mount Indoors

Page 10: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

Larger unitshave more legs.

A I R I N C O R P O R A T E D100% AIR MAKE - UP VERT. UNIT ASSEMBLY

1-7

FIG. 2

Unit Top

Unit Bottom

Sealant

Bolt

Washer

Nut

ELECTRICAL / GAS TRAINACCESS DOOR BURNER /

CONTROLSECTION

1. AMU BOTTOM see FIG. 1for pad attachment detail.2. AMU TOP (blower sec.)mounts on top of AMU bottom, see FIG. 2 for details, mount so discharge opening faces building. Blower and electrical / gas train access doors are on the same end. Align arrows.3. DISCHARGE DAMPER(optional) is mounted indoors. (a size variation may exist) 4. DISCHARGE DIFFUSER(optional) is mounted indoors. Turning vanes are adjusted and secured in the field. Diffuser must be supported in the field. (supports by others)5. O/A FILTER SECTION(optional) slides into AMU bottom section.

Duct work between unit and accessories is supplied by others.

Units ordered without filter sections may be physically smaller. If filters are required at a later date, the filter section must be attached to the unit bottom, and the stand height must be adjusted accordingly. (will have to raise stand height)

Sealant goes between each section before assembly. Bolts and caulking are in packing box. Recaulk seams and lifting plates after assembly.

NOTE: For indoor units, the stand must be enclosed (sometimes height is increased). A transition (by others) must then be made from enclosed stand intake opening to the intake damper or louver (a size variation may exist). Intake damper should be mounted at the building wall or ceiling.

* ALL COMPONENT CONNECTIONS MUST BE CAULKED TO PREVENT WATER FROM ENTERING SYSTEM

1

5

FIG. 1

Nut

Cement

AMU Stand

Stud

Washer

BLOWER / MOTORACCESS DOOR

DISCHARGE

INTAKE

Arrows

rev. 01-04

BLOWER SECTION2

3 4

Many units are 1 piece with a bolt on stand check with factory for your application.

Page 11: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

Larger unitshave more legs.

FIG. 2

Unit Top

Unit Bottom

Sealant

Bolt

Washer

Nut

ELECTRICAL / GAS TRAINACCESS DOOR

1

3

BLOWER / MOTORACCESS DOOR

“AR ” - AIR RECIRC. VERT. UNIT ASSEMBLY

1-8

3. DISCHARGE DAMPER (optional) is mounted indoors. (a size variation may exist) 4. DISCHARGE DIFFUSER (optional) is mounted indoors. Turning vanes are adjusted and secured in the field. Diffuser must be supported in the field. (supports by others)5. O/A FILTER SECTION(not shown) (optional) is sized for up to 25% of the OA. Slides into unit bottom section. 6. O/A & RA FILTER SECTION (optional) is sized for up to 80% unit volume. Slides into unit bottom section above OA & RA dampers and filters the mixed air.(When you order built in OA filters, you also get a mixed air filter section, which filters both OA & RA )

Duct work between unit and accessories is supplied by others.

Units ordered without filter sections may be physically smaller. If filters are required at a later date, the filter section must be attached to the unit bottom, and the stand height must be adjusted accordingly. (will have to raise stand height)

Sealant goes between each section before assembly. Bolts and caulking are in packing box. Recaulk seams and lifting plates after assembly.

DISCHARGE

* ALL COMPONENT CONNECTIONS MUST BE CAULKED TO PREVENT WATER FROM ENTERING SYSTEM

RETURN AIR

1. Unit BOTTOMsee FIG. 1 for pad attachment detail.2. Unit TOP (blower sec.) mounts on top of Unit bottom, see FIG. 2 for details. Mount so discharge opening faces building. Blower and electrical / gas train access doors are on the same end. Align arrows.

FIG. 1

Nut

Cement

Unit Stand

Stud

Washer

NOTE: For indoor units, the stand must be enclosed (sometimes height is increased). A transition (by others) must then be made from enclosed stand intake opening to the intake damper or louver (a size variation may exist). Intake damper should be mounted at the building wall or ceiling.

BLOWER SECTION2

Arrows

INTAKE

rev. 01-04

Many units are 1 piece with a bolt on stand check with factory for your application.

BURNER / CONTROLSECTION

6

4

Page 12: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DCONTROLLED BUILDING PRESSURIZATION

1-9

The term "Sick Building" came into being in the late 70's and early 80's when the energy conservation movement was at its peak. Today, more than ever, the term "Sick Building" has a real meaning. The concern today expands beyond the conservation of energy and into the areas of health and general welfare of the building occupants. The concern has also branched out from office type structures to buildings housing commercial / industrial processes and manufacturing. A "Sick Building" can result from several scenarios including: 1) No ventilation at all.2) A lot of exhaust with no incoming air to make up what has been exhausted.3) Buildings with a high infiltration rate.

The major contributor to the "Sick Building" syndrome is negative building pressure (having more airbeing taken out of the building than what is coming in ). Some of the results of a negative building pressure at varying degrees are as follows :

The building boom of the 50's and 60's saw many buildings built with exhaust systems installed, but without air make up systems. It was believed that it cost too much to operate an air make-up unit, for the benefits returned. The misconception that air make up is expensive to operate may come from persons who purchased units without the benefit of some type of pressure control to vary the amount of incoming air. It will actually cost less to operate a pressure controlled air make up system than it costs to heat the infiltrated air caused by a negative pressure.

EXAMPLE : A building in Minneapolis, MN. operates under a negative pressure of - 0.1'' wc (0.1'' wc pressure is equal to 760 fpm) for 16 hours / day - 5 days / week. Assumed crackage is 50 sq. ft. . The average winter temperature is 29.3 degrees. The average length of winter is 31 weeks. The indoor temperature is kept at 60 degrees.BTU'S TO HEAT INFILTRATED AIR = ((50 SQ FT X 760 FPM) X (60 - 29.3)) X (1.1 ) = 1,283,260 BTU / HR

If this building were under a positive pressure of .03 '' wc ( .03 '' wc is equal to 415 fpm ). With the discharge of the unit controlled at 70 degrees. The btu's to heat exfiltrated air from a controlled source of incoming air will be less than heating the infiltrated air caused from the negative pressure.BTU'S TO HEAT EXFILTRATED AIR = (( 50 SQ FT X 415 FPM ) X (70 - 29.3 )) X (1.1 ) = 928,978 BTU / HR

The difference between the two btu levels is the quantity of btu's saved by controlling the pressure within the building. YEARLY BTU'S SAVED = (1,283,260 BTU/HR - 928,978 BTU/HR) X (2,480 HRS/YR) = 878,619,360 BTU/YR

BUILDING PRESSURIZATION

ADVERSE CONDITION THAT MAY RESULTWorker draft complaints - High velocity draftsthrough doors and windows.Natural draft stacks ineffective - Ventilation through roofexhaust vents and stacks greatly reduced.Carbon monoxide - Back drafting will take place in indirect combustion equipment not provided with an induced draft fan.General mechanical ventilation reduced - Air flow reduced in propeller type fans and low pressure supply and exhaustsystems.Doors difficult to open - serious injury may result fromnon checked slamming doors.Local exhaust impaired - centrifugal fans in fume hoods, etc. have reduced or nonexistent air flow.

NEG PRESS '' WC .01 to .0

.01 to .05

.02 to .05

.03 to 1

.05 to 1

.1 to .25

Page 13: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

Another building factor that comes into play without proper ventilation is the stratification of air and ultimately heat. This is easy to detect during the winter months as the temperature at the upper one third of a building, which does not benefit from controlled pressurization, can be much warmer than the lower portions. If the thermostats in a building were kept at 60 degrees and the temperature at the roof line were to go as high as 80 degrees the actual heat loss of the roof would be one third more than what the building was designed for. EXAMPLE : The building in Minneapolis, MN has a roof area of 10,000 sq. feet and an insulation R-value of 12. The heat losses would be as follows - DESIGN - (( 10,000 SQ FT ) X ( 60 - 29.3 )) X ( 1 / 12 ) = 25,583 BTU/HR ACTUAL - (( 10,000 SQ FT ) X ( 80 - 29.3 )) X ( 1 / 12 ) = 42,250 BTU/HR Again here, the yearly difference can be seen by multiplying the hourly difference by the total yearly hours. (( 42,250 btu/hr - 25,583 btu/hr ) X ( 2,480 HRS/YR )) = 41,334,160 BTU / YR

In todays commercial / industrial environment the consumer will be searching for systems that will create a safe working environment as well as control the cost of operation. Pressurization of the building will help satisfy both of these needs. Today, there are several methods that will control the pressure in a building : 1. A system that incorporates fresh air / return air dampers operated from a differential pressure control. As the pressure in the building decreases, the fresh air dampers will open bringing in more outside air. As the pressure increases, the fresh air dampers will close allowing the majority of the total volume moved by the equipment to be recirculated through the system. 2. A variable volume air make up system will vary the amount of incoming air to the building as the pressure increases and decreases. Of the two methods of varying the air volume (modulating discharge damper and variable frequency drive) the variable frequency drive will be the more cost effective in the long run. (figure 1, is a comparison of variable frequency drive and discharge damper operating parameters)

Besides the term "SICK BUILDING" , there is another term that has surfaced in the last couple of years. The term "DEMAND SIDE MANAGEMENT" relates to the energy conservation side of the industry. By incorporating a pressure control into an air make up or industrial heaters circuitry, modulating the volume of fresh air that is allowed into the building, the system becomes an on demand air make up unit, supplying only the fresh air needed to maintain a positive pressure inside the building.

1-10

CONTROLLED BUILDING PRESSURIZATION

TSP DAMP - "WC

TSP DRIVE - "WC

BHP DAMP

BHP DRIVE

RPM DAMP X 100

RPM DRIVE X 100

0 1 2 3 4 5 6 7 8

Figure 1

12,000 CFM

6000 CFM

Page 14: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

MODELTA - 109TA - 112TA - 115TA - 118TA - 120TA - 122TA - 125TA - 127TA - 130TA - 133TA - 136TA - 215TA - 218TA - 220TA - 225TA - 227TA - 230TA - 233TA - 236TA - 239TA - 242

1-11

A I R I N C O R P O R A T E DESTIMATED UNIT WEIGHTS

IntakeHood

30354580100100150150200200110135130160225310525525690890

IntakeFilter

556075110135135210210250250230230215255300325550550625825

IntakeDamper

45110110125150150235235260260220220250305400425490490650850

Disc.Damper

455055607070100100125125100110130145155200300300350550

ALL WEIGHTS ARE ESTIMATES, AND WILL VARY WITH DIFFERENT GASTRAINS, MOTOR HP, AND SPECIAL ACCESSORIES.

USE FOR FREIGHT ESTIMATION ONLY

MODELTA - 112TA - 115TA - 118TA - 120TA - 122TA - 125TA - 127TA - 130TA - 133TA - 136TA - 215TA - 218TA - 220TA - 225TA - 227TA - 230TA - 233TA - 236TA - 239TA - 242

BasicUnit815950122017002150220027502800325035502000205023003400395046006800760081008600

DownDisc.8151000128018502300235028502900330036002100225024503640430048507600810087009200

VerticalDisc.13001350160025002900295038003850420045003250350043004900615066508100860090009500

CurbKit150150120150200200250250300300160240300400450500--------------------

“AR “ RECIRC. UNITS AND ACCESSORIES

BasicUnit60062077599013001720177024502500290030001670170019503050315042006500710076008100

DownDisc.600620775102014001780183025502600300031001950202522503290340045007100760082008700

VerticalDisc.110011201150170022502650270034503500400041002675285040004600580062507600810087009200

IntakeHood

3030354580100100150150200200110135130160225310525525690890

IntakeFilter

55556075110135135210210250250230230215255300325550550625825

IntakeDamper

4545110110125150150235235260260220220250305400425490490650850

Disc.Damper

45455055607070100100125125100110130145155200300300350550

CurbKit105105105120150200200250250300300160240300400450500--------------------

AIR MAKE-UP UNITS AND ACCESSORIES

rev. 01-04

Page 15: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-12

ACCESSORY PRESSURE DROPS A I R I N C O R P O R A T E D

Model Hood1"

Clean.2"

Clean.2"

Disp.2"

PleatedIntake

DamperDisch.

DamperTwoWay

ThreeWay

4-Way Box

2,800 TA/TAM - 109 0.070 0.142 0.196 0.274 0.245 0.033 0.740 0.074 0.089 0.1195,000 TA/TAM - 112 0.135 0.250 0.380 0.500 0.450 0.052 0.500 0.170 0.185 0.2207,500 TA/TAM - 115 0.127 0.265 0.330 0.440 0.390 0.060 0.110 0.100 0.105 0.13010,000 TA/TAM - 118 0.131 0.240 0.340 0.480 0.430 0.083 0.175 0.150 0.165 0.20014,000 TA - 120 0.155 0.298 0.402 0.574 0.517 0.093 0.178 0.155 0.172 0.21218,000 TA - 122 0.116 0.267 0.349 0.466 0.427 0.049 0.202 0.175 0.186 0.21721,000 TA - 125 0.150 0.344 0.450 0.600 0.550 0.063 0.260 0.225 0.240 0.28027,500 TA - 127 0.120 0.220 0.305 0.418 0.375 0.059 0.183 0.157 0.170 0.20530,000 TA - 130 0.137 0.252 0.350 0.480 0.430 0.067 0.210 0.180 0.195 0.23542,000 TA - 133 0.114 0.234 0.332 0.439 0.391 0.053 0.205 0.098 0.103 0.12746,000 TA - 136 0.136 0.281 0.398 0.527 0.469 0.064 0.246 0.117 0.123 0.15215,000 TA - 215 0.127 0.315 0.380 0.490 0.440 0.056 0.110 0.100 0.105 0.13020,000 TA - 218 0.142 0.288 0.408 0.576 0.515 0.067 0.175 0.111 0.116 0.14430,000 TA - 220 0.155 0.260 0.350 0.500 0.450 0.070 0.155 0.100 0.105 0.13042,000 TA - 225 0.150 0.344 0.450 0.600 0.550 0.078 0.260 0.125 0.135 0.16052,000 TA - 227 0.159 0.280 0.400 0.550 0.500 0.073 0.261 0.100 0.105 0.13060,000 TA - 230 0.155 0.252 0.350 0.480 0.430 0.071 0.210 0.100 0.105 0.13075,000 TA - 233 0.106 0.247 0.400 0.450 0.411 0.055 0.210 0.100 0.108 0.13485,000 TA - 236 0.116 0.240 0.340 0.450 0.400 0.064 0.210 0.100 0.105 0.130100,000 TA - 239 0.137 0.250 0.350 0.468 0.418 0.064 0.210 0.100 0.105 0.130120,000 TA - 242 0.100 0.240 0.325 0.440 0.390 0.150 0.210 0.130 0.145 0.165

would have a pressure drop of 0.264" wc vs. 0.185" wc per above chart (0.185" wc -:- 0.70 = 0.264" wc).EXAMPLE: A discharge damper on a TA-112 @ 5,000 CFM, either built in or attached directly to blower outlet,

At 22,000 CFM, 0.135" would be added to external static rather than 0.252" that is tabulated for 30,000 CFM.

Filters

Above accessory pressure drops are listed at maximum CFM for model number. At lower CFM, use the formula:((desired CFM -:- max model CFM)2 x listed static drop for model accessory) = static drop at lower CFM level.

EXAMPLE: What would the pressure drop of 1" cleanable filters be at 22,000 CFM for a TA-130?((22,000 CFM -:- 30,000 CFM)2 x 0.252" wc) = 0.135" wc

Max. CFM per

Model

Accessory Pressure Drops (" wc)

DiffusersDampers

accessory pressure drop.If a discharge accessory is either built in or attached directly to blower outlet, add 30% to listed

Page 16: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-13

“TAM” 100% OA AIR MAKE - UP HP CHART CHART 1 A I R I N C O R P O R A T E D

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.1,200 TAM - 109 1/2 3/4 3/4 3/4 3/4 11,300 TAM - 109 1/2 3/4 3/4 1 1 11,400 TAM - 109 1/2 3/4 3/4 1 1 1 1/21,500 TAM - 109 3/4 3/4 3/4 3/4 1 1 1/21,600 TAM - 109 3/4 3/4 3/4 1 1 1/2 1 1/21,700 TAM - 109 3/4 3/4 1 1 1 1/2 1 1/21,800 TAM - 109 3/4 1 1 1 1/2 1 1/2 1 1/21,900 TAM - 109 3/4 3/4 1 1 1/2 1 1/2 1 1/22,000 TAM - 109 3/4 1 1 1 1/2 1 1/2 1 1/22,100 TAM - 109 1 1 1 1 1/2 1 1/2 22,200 TAM - 109 1 1 1 1/2 1 1/2 1 1/2 22,300 TAM - 109 1 1 1/2 1 1/2 1 1/2 1 1/2 2

TAM - 109 1 1/2 1 1/2 1 1/2 1 1/2 2 2TAM - 112 3/4 1 1TAM - 109 1 1/2 1 1/2 1 1/2 2 2 2TAM - 112 1 1 1 1/2

2,600 TAM - 109 1 1/2 1 1/2 1 1/2 2 2 22,700 TAM - 109 1 1/2 1 1/2 2 2 2 32,750 TAM - 112 1 1 1/2 1 1/22,800 TAM - 109 1 1/2 2 2 2 3 33,000 TAM - 112 1 1 1/2 1 1/2 2 2 23,250 TAM - 112 1 1/2 1 1/2 1 1/2 2 2 33,500 TAM - 112 1 1/2 1 1/2 2 3 3 33,750 TAM - 112 1 1/2 2 2 3 3 3

TAM - 112 2 2 3 3 3 3TAM - 115 1 1/2

4,250 TAM - 112 2 3 3 3 3 3TAM - 112 3 3 3 3 5 5TAM - 115 1 1/2 2 2

4,750 TAM - 112 3 3 3 5 5 5TAM - 112 3 3 5 5 5 5TAM - 115 2 3 3

5,500 TAM - 115 3 3 3 5 5TAM - 115 3 5 5 5 5 5TAM - 118TAM - 115 5 5 5 5 5 5TAM - 118TAM - 115 5 5 5TAM - 118 3 5 5 5 5

7,500 TAM - 118 5 5 5 5 5 7 1/28,000 TAM - 118 5 5 5 5 7 1/2 7 1/2

TAM series units have a MAXIMUM static pressure rating of 2" w.c. Blower performance report may establishlower limits for a given CFM and static pressure combination as shown by shaded areas in the chart above.

5,000

6,000

6,500

7,000

2,400

2,500

4,000

4,500

Motor Horse Power - Air Volume at ESPExternal Static Pressure Plus Accessory Static Drops From Page 1-12

Page 17: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-14

“TA” – SERIES HP CHART 1 A I R I N C O R P O R A T E D

ACCESSORY PRESSURE DROP TO BE ADDED TO EXTERNAL PRESSURE DROP BEFORE SELECTING UNIT MOTOR SIZE

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.1,200 TA - 109 1/2 3/4 3/4 3/4 3/4 11,300 TA - 109 1/2 3/4 3/4 1 1 11,400 TA - 109 1/2 3/4 3/4 1 1 1 1/21,500 TA - 109 3/4 3/4 3/4 3/4 1 1 1/21,600 TA - 109 3/4 3/4 3/4 1 1 1/2 1 1/21,700 TA - 109 3/4 3/4 1 1 1 1/2 1 1/21,800 TA - 109 3/4 1 1 1 1/2 1 1/2 1 1/21,900 TA - 109 3/4 3/4 1 1 1/2 1 1/2 1 1/22,000 TA - 109 3/4 1 1 1 1/2 1 1/2 1 1/22,100 TA - 109 1 1 1 1 1/2 1 1/2 22,200 TA - 109 1 1 1 1/2 1 1/2 1 1/2 22,300 TA - 109 1 1 1/2 1 1/2 1 1/2 1 1/2 2

TA - 109 1 1/2 1 1/2 1 1/2 1 1/2 2 2TA - 112 3/4 1 1TA - 109 1 1/2 1 1/2 1 1/2 2 2 2TA - 112 1 1 1 1/2

2,600 TA - 109 1 1/2 1 1/2 1 1/2 2 2 22,700 TA - 109 1 1/2 1 1/2 2 2 2 32,750 TA - 112 1 1 1/2 1 1/22,800 TA - 109 1 1/2 2 2 2 3 33,000 TA - 112 1 1 1/2 1 1/2 2 2 23,250 TA - 112 1 1/2 1 1/2 1 1/2 2 2 33,500 TA - 112 1 1/2 1 1/2 2 3 3 33,750 TA - 112 1 1/2 2 2 3 3 3

TA - 112 2 2 3 3 3 3TA - 115 1 1/2

4,250 TA - 112 2 3 3 3 3 3TA - 112 3 3 3 3 5 5TA - 115 1 1/2 2 2

4,750 TA - 112 3 3 3 5 5 5TA - 112 3 3 5 5 5 5TA - 115 2 3 3

5,500 TA - 115 3 3 3 5 5TA - 115 3 5 5 5 5 5TA - 118 3 3 3TA - 115 5 5 5 5 5 5TA - 118 3 3 5 5TA - 115 5 5 5 7 1/2 7 1/2 7 1/2TA - 118 3 5 5 5 5TA - 115 5 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2TA - 118 5 5 5 5 5 7 1/2TA - 118 5 5 5 5 7 1/2 7 1/2TA - 215 3 3

TA series units are available at higher static pressure ratings. Blower performance report establishes limits.

7,000

7,500

8,000

Motor Horse Power - Air Volume at ESPExternal Static Pressure Plus Accessory Static Drops From Page 1-12

2,400

2,500

4,000

4,500

5,000

6,000

6,500

Page 18: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-15

“TA” – SERIES HP CHART 2 A I R I N C O R P O R A T E D

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.TA - 118 5 5 7 1/2 7 1/2 7 1/2 7 1/2TA - 120 3 5 5TA - 215 3 3TA - 118 5 5 7 1/2 7 1/2 7 1/2 7 1/2TA - 120 5 5 5TA - 215 3 5 5TA - 118 7 1/2 7 1/2 7 1/2 10 10 10TA - 120 5 5 5 7 1/2 7 1/2TA - 122 5 5TA - 215 5 5 5TA - 120 5 7 1/2 7 1/2 7 1/2 7 1/2TA - 122 5 5 5TA - 215 5 5 7 1/2 7 1/2 7 1/2TA - 120 7 1/2 7 1/2 7 1/2 10 10 10TA - 122 5 5 7 1/2 7 1/2 7 1/2TA - 215 7 1/2 7 1/2 7 1/2 7 1/2 10 10TA - 218 5 5 7 1/2TA - 120 7 1/2 10 10 10 10 15TA - 122 7 1/2 7 1/2 7 1/2 7 1/2 10 10TA - 215 7 1/2 7 1/2 10 10 10 10TA - 218 5 7 1/2 7 1/2 7 1/2TA - 120 10 10 10 10 15 15TA - 122 7 1/2 7 1/2 7 1/2 10 10 10TA - 215 10 10 10 15 15 15TA - 218 7 1/2 7 1/2 7 1/2 10 10TA - 122 10 10 10 10 15 15TA - 125 7 1/2 7 1/2TA - 215 10 15 15 15 15 15TA - 218 7 1/2 7 1/2 10 10 10 15TA - 122 10 10 10 15 15 15TA - 125 7 1/2 7 1/2 7 1/2TA - 127 5TA - 218 7 1/2 10 10 10 15 15TA - 220 5TA - 122 15 15 15 15 15 15TA - 125 7 1/2 10 10 10TA - 127 5TA - 218 10 10 15 15 15 15TA - 220 7 1/2 7 1/2TA - 122 15 15 15 15 20TA - 125 10 10 10 15TA - 127 7 1/2 7 1/2TA - 218 10 10 15 15 15 15TA - 220 7 1/2 7 1/2

9,000

8,500

Motor Horse Power - Air Volume at ESPExternal Static Pressure Plus Accessory Static Drops From Page 1-12

11,000

10,000

12,000

13,000

14,000

15,000

16,000

17,000

18,000

Page 19: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-16

“TA” – SERIES HP CHART 3 A I R I N C O R P O R A T E D

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.TA - 125 10 10 15 15 15TA - 127 7 1/2 7 1/2 7 1/2TA - 218 10 15 15 15 15 20TA - 220 7 1/2 7 1/2 10TA - 125 10 15 15 15 15 15TA - 127 7 1/2 7 1/2 10TA - 130 7 1/2TA - 218 15 15 15 20 20 20TA - 220 10 10 10 15TA - 125 15 15 15 15 15 20TA - 127 7 1/2 10 10 10TA - 130 7 1/2TA - 220 10 10 15 15TA - 127 10 10 10 15 15TA - 130 7 1/2 10TA - 220 10 15 15 15 15 15TA - 127 10 10 15 15 15 15TA - 130 10 10 15TA - 220 15 15 15 15 15 20TA - 127 15 15 15 15 15 20TA - 130 10 10 15TA - 220 15 15 15 15 20 20TA - 127 15 15 15 15 20 20TA - 130 10 15 15 15TA - 220 15 15 20 20 20 20TA - 127 15 15 15 20 20 20TA - 130 15 15 15 15TA - 220 15 20 20 20 20 20TA - 225 10TA - 127 15 15 20 20 20 20TA - 130 15 15 15 20 20TA - 220 20 20 20 20 25 25TA - 225 10 10TA - 127 15 20 20 20 20 25TA - 130 15 15 15 20 20 20TA - 220 20 20 20 25 25 25TA - 225 10 15TA - 130 15 15 20 20 20 25TA - 133 15 15 15 15 20TA - 220 20 20 25 25 25 30TA - 225 10 15TA - 130 15 20 20 20 25 25TA - 133 15 15 15 15 20TA - 220 25 25 25 25 30 30TA - 225 15 15

24,000

Motor Horse Power - Air Volume at ESPExternal Static Pressure Plus Accessory Static Drops From Page 1-12

19,000

20,000

21,000

22,000

23,000

25,000

26,000

27,000

28,000

29,000

30,000

Page 20: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-17

“TA” – SERIES HP CHART 4 A I R I N C O R P O R A T E D

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.TA - 133 15 15 20 20 20 20TA - 136 15 15 20 20 20 20TA - 225 15 15 20TA - 133 15 20 20 20 25 25TA - 136 15 20 20 20 20 25TA - 225 15 20 20 20TA - 133 20 20 20 25 25 25TA - 136 20 20 20 20 25 25TA - 225 20 20 20 25TA - 227 15 15TA - 133 20 25 25 25 30 30TA - 136 20 20 25 25 25 25TA - 225 20 20 25 25 25TA - 227 15 15 20TA - 133 25 25 30 30 30 40TA - 136 20 25 25 25 30 30TA - 225 20 25 25 30 30 30TA - 227 15 20 20TA - 133 25 30 30 30 40 40TA - 136 25 25 30 30 30 40TA - 225 25 25 30 30 30 40TA - 227 20 20 20 25TA - 136 25 30 30 40 40 40TA - 227 20 20 25 25 25TA - 136 30 30 40 40 40 40TA - 227 20 25 25 25 30TA - 230 20 20 20TA - 227 25 25 25 30 30 40TA - 230 20 20 25TA - 227 25 25 30 30 40 40TA - 230 20 25 25 30TA - 227 25 30 30 40 40 40TA - 230 25 25 30 30 30

54,000 TA - 230 25 25 30 30 40 4056,000 TA - 230 25 30 30 40 40 4058,000 TA - 230 30 30 40 40 40 40

TA - 230 30 40 40 40 40 50TA - 233 25 30 30 40 40

65,000 TA - 233 30 40 40 40 40 50TA - 233 40 40 40 50 50 50TA - 236 30 40 40 40 40 50TA - 233 40 50 50 50 60 60TA - 236 40 40 40 50 50 50TA - 239 30 30 40 40 40 50TA - 236 40 50 50 50 60 60TA - 239 30 40 40 40 50 50

Motor Horse Power - Air Volume at ESPExternal Static Pressure Plus Accessory Static Drops From Page 1-12

32,000

34,000

36,000

38,000

40,000

42,000

44,000

46,000

48,000

50,000

52,000

60,000

70,000

75,000

80,000

Page 21: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

1-18

“TA” – SERIES HP CHART 5 A I R I N C O R P O R A T E D

Air Volume Unit Model 1/4" w.c. 1/2" w.c. 3/4" w.c. 1" w.c. 1 1/4" w.c. 1 1/2" w.c.TA - 236 50 50 60 60 60 75TA - 239 40 40 50 50 50 60TA - 239 40 50 50 50 60 60TA - 242 40 40 40 50 50 60TA - 239 50 50 60 60 60 75TA - 242 40 40 50 50 60 60TA - 239 50 60 60 75 75 75TA - 242 40 50 50 60 60 75

105,000 TA - 242 50 50 60 60 75 75110,000 TA - 242 50 60 60 75 75 75115,000 TA - 242 60 60 75 75 75 100120,000 TA - 242 75 75 75 100 100 100

External Static Pressure Plus Accessory Static Drops From Page 1-12Motor Horse Power - Air Volume at ESP

100,000

85,000

90,000

95,000

Page 22: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

APPLICATIONS FOR:AUDITORIUMSBODY SHOPSFACTORIESFOUNDRIESGARAGES KITCHENSNATATORIUMSSPRAY BOOTHSWAREHOUSES, ETC...

Eliminates air starvation.Safe, economical, flexiblesummer / winter ventilation.Cfm ranges: 1,200 - 120,000.100 % thermal efficiency.ETL listed to 120° temp. rise.Constructed for indoor or outdoor mounting.

2-1

ALSO AVAILABLE:INDUSTRIAL HEATERSEVAPORATIVE COOLINGSTEAM UNITSHOT WATER UNITSELECTRIC UNITSVAV SYSTEMS (DEMAND AIR)SPRAY / BAKE SYSTEMS (H.O.T.)

A I R I N C O R P O R A T E D“TA” SERIES 100% AIR MAKE - UP EQUIP.

LISTED

Titan Direct Fired Air Make - Up Heating SystemsTitan’s Air Make - Up Systems are designed to replace the air exhausted from commercial or industrial buildings - and condition the new, fresh air to improve indoor air quality and ventilation.

Air Make - Up Systems by Titan incorporate the advanced components necessary for energy efficient, long term indoor air quality. The direct - fired burner offers 100% thermal efficiency - as opposed to 80% (nominal) efficiency for an indirect fired air make - up heater. The turndown ratio for direct - fired units is much greater than common indirect - fired units. This means better control of discharge air temperatures - and better use of fuel energy to heat the air as it moves across the burner.

Page 23: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

2-2

STANDARD FEATURES:• ETL listed.• Discharge air temperature control, with remote

set point & Summer-Off- Winter selector switch.• Auxiliary contacts for exhaust fan interlock.• All Titan Air units are prepiped, prewired,

and factory tested.(Some field connections required)

• Basic “TA” units are fabricated from angle iron,steel channel and reinforced 16 gauge (min.)galvanized sheet steel.(TA-15 and smaller use 18 gauge min.)

• All units are manufactured with controls, motorand blower drives enclosed within the unit.

• Easy access, hinged and gasketed doors toallow servicing of unit components.

• Air proving differential pressure switches.• Electronic flame supervision. (flame rod

rectification)• Main gas automatic safety shut-off valves.• Gas trains built to meet or exceed

ANSI Z83.41999 / CSA 3.7 M99 standard.• High gas pressure safety switch.• High temperature limit control.• Ignition transformer.• Control voltage transformer(s). (when required)• Non-Fused door interlocked disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor starter & overload protection.• D.W.D.I. forward curved industrial type

blower(s) with solid turned ground andpolished shafting.

• Self aligning ball bearings.• Variable pitch blower drive up to 30 HP.• Lifting provisions on all units.• Vertical “TA” units are built to accept slide - in

filter sections. Integral 36" stand is alsostandard equipment on most unit sizes.

• Vertical units have control panel and gas trainserviceable from ground level.

• G-90 Galvanized exterior.

OPTIONAL FEATURES:• Motorized discharge or intake damper w/ safety interlock contacts.• Filter section with cleanable or disposable filters.• Intake Hood / Filter combination. (1” cleanable filters

on single blower units only)• Screened fresh air intake hood.• Discharge air diffuser.• Roof Curb.• Service platform.• Vibration isolation.• High gas pressure regulator.• Clogged filter indication light.• Operation indication lights.• Circuit analyzer indication lights.• TEFC blower motor.• Low temperature limit control.• Burner "On / Off" Ductstat. (Economizer)• Audible alarm systems.• IRI, FM, or other special requirements.• Room air temperature control with discharge

temperature high and low limits.• Electronic discharge temperature control with digital

display.• Standard color or color match paint.• Unit cabinet insulation.• Fused Disconnect.• 7 Day time clock.• 2 speed blower motor.• Other options available upon request.

rev. 01-04

“TA” SERIES - 100% AIR MAKE - UPFEATURES

Page 24: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DH.O.T. PAINT / BAKE SYSTEMS

The H.O.T. (High - Outlet - Temperature) system combines two systems into one. First, the H.O.T. system works as a standard air make-up heater which provides the air needed to make-up what is being exhausted by the spray booth. Secondly, on low speed, the H.O.T. System provides fresh, hot air in low volume at low velocity - ideal for curing finish coats.Elevated bake temperatures can be achieved with either a low speed bake cycle or recirculation of booth air in bake cycle.Titan Air was the first in the industry to offer an ETL listed, direct fired, 2 speed air make-up system with 160° temperature rise capabilities in bake mode.

DESIGNED WITH THE FINISHING PROFESSIONAL IN MIND.

FEATURES:• CFM ranges: 2,400 - 120,000• Indoor or outdoor construction• Available in a variety of configurations

BENEFITS:• Decreased drying time• Increased productivity• Improved finish quality

LISTED

2-3

Page 25: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

OPTIONAL FEATURES:• Variable frequency drive and booth pressure controls can be supplied for booth exhaust fan.• Timer relays for automating bake cycle and cool down cycle duration.• Temperature controller with multiple set point digital display, or other process controller.• Motorized discharge or intake damper w/ safety interlock contacts.• Filter section with cleanable or disposable filters.• Intake Hood / Filter combination. (1” cleanable filters)• Screened fresh air intake hood.• Discharge air diffuser.• Roof Curb.• Service platform.• Vibration isolation.• High gas pressure regulator.• Clogged filter indication light.• Operation indication lights.• Circuit analyzer indication lights.• TEFC blower motor.• Low temperature limit control.• Burner "On / Off" Ductstat. (Economizer)• Audible alarm systems.• IRI, FM, or other special requirements.• Unit cabinet insulation.• Fused Disconnect.• 7 Day time clock.• Exhaust Starters.• Standard color or color match paint.• Higher discharge temperatures available• Other options available upon request.

• • Interlocks for door switches, paint solenoid, and lighting contactors required and supplied by others.

TITAN AIR IS APPROVED BY ETL TO BUILD AND LABEL CONTROL PANELS TO THE UL508A STANDARD. (which may contain items such as exhaust starters, bake timers, lighting contactors etc.)

A I R I N C O R P O R A T E DH.O.T. PAINT / BAKE SYSTEMS

2-4

STANDARD FEATURES:• ETL listed.• Standard max. discharge temperature is 180°.• Paint / Bake Speed Control.• Interior liner.• Digital electronic discharge air temp. control. • All Titan Air units are prepiped, prewired, and factory tested. (Some field connections required)• Basic units are fabricated from angle iron, steel channel and reinforced 16 gauge (min.) galvanized sheet steel. (TA-15 and smaller use 18 gauge min.)• All units are manufactured with controls, motor and blower drives enclosed within the unit.• Easy access, hinged and gasketed doors to allow servicing of unit components. • Air proving differential pressure switches. • Electronic flame supervision. (flame rod rectification)• Main gas automatic safety shut-off valves.• Gas trains built to meet or exceed ANSI Z83.4 1999 / CSA 3.7 M99 standard. • High gas pressure safety switch. • High temperature limit control.• Ignition transformer.• Control voltage transformer(s). (when required)• Non-Fused disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor starter & overload protection.• D.W.D.I. forward curved industrial type blower(s) with solid turned ground and polished shafting. • Self aligning ball bearings.• Variable pitch blower drive up to 30 HP.• Lifting provisions on all units.• Vertical units are built to accept slide - in filter sections. Integral 36" stand is also standard equipment on most “TA” unit sizes.• Vertical units have control panel and gas train serviceable from ground level.• G-90 Galvanized exterior.

DIMENSIONS AND HORSE POWER CHARTS:H.O.T. units are the same size as comparable 100% Air Make-up units and available in the same configurations. Refer to the 100% Air Make-up section for dimensional data and blower motor horsepower charts. For air recirculation units, contact factory for dimensional data.

rev. 01-04

Page 26: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

“TAM” SERIES - 100% AIR MAKE - UPFEATURES

2-5

rev. 01-04

STANDARD FEATURES: Quick ShipNOTE: Air stream accessories are limited by the total static pressure (2” wc)• ETL listed.• 2psi max. gas supply pressure (Nat. or LP)• All Titan Air units are prepiped, prewired,

and factory tested. (Field connections required)• All units are manufactured with controls, motor

and blower drives enclosed within the unit.• Easy access, hinged and gasketed doors to

allow servicing of unit components.• Electronic flame supervision. (flame rod

rectification)• Main gas automatic safety shut-off valves.• Gas trains built to meet or exceed

ANSI Z83.4 1999 / CSA 3.7 M99 standard.• High temperature limit control.• Ignition transformer.• Control voltage transformer(s). (when required)• Non-Fused through door disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor starter & overload protection.• D.W.D.I. forward curved industrial type blower

with solid turned ground and polished shafting.• Self aligning sealed ball bearings.• Variable pitch blower drive.• G-90 galvanized casing• Direct Ignition (with limitations)• Proved Low Fire Start (with limitations)• 25 to 1 turn down direct fired burner• High / Low air flow proving switches• Flame fail diagnostics• Exhaust interlock contacts (exhaust starts w/

unit starter)• Remote control panel w/ SOW switch and

discharge temperature set point.

OPTIONAL FEATURES: Quick ShipNOTE: Air stream accessories are limited by the total static pressure (2” wc)• Motorized discharge or intake damper w/ safety

interlock contacts.• Intake filter section with cleanable filters (1” or 2”).

Intake filter section with 30% pleated filters (2”).Intake filter section with disposable filters.

• Intake Hood /Filter combination (1” cleanable filters)• Intake Hood / Filter / Damper combination

(1” cleanable filters)• Screened 45° fresh air intake hood.• Roof Curb.• High gas pressure regulator.• Clogged filter indication light. (with limitations)• Operation indication lights.• Low temperature limit control.• Burner "On / Off" Ductstat. (Economizer)• Audible alarm systems.• High gas pressure safety switch.

(over 14” wc supply pressure)• IRI, FM, or other special requirements.• Unit cabinet insulation.• Fused Disconnect. (with limitations)• 7 Day time clock. (with limitations)

OPTIONAL FEATURES: Standard Lead time• Painted Unit and Accessories• Unit mounted dampers• Discharge Diffusers• Evaporative Coolers

Page 27: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

A I R I N C O R P O R A T E D

“TAM” 100% AIR MAKE - UPUNIT DIMENSIONS

2-6

rev. 01-04

F,G, H & J are accessory dimensions. D&E are accessory locations. Intake and discharge accessories may be larger than openings on unit. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. Built in discharge dampers are available on down discharge units only. INDOOR hanging units must utilize a bottom cradle (by others).

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

H2”

B

J CINTAKE

A F E

G

DDISCHARGE

SERVICE SIDE

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

SINGLE BLOWER UNITS - HORIZONTAL DISCHARGE - CHANNEL OR CURB MOUNT

A I R I N C O R P O R A T E D

2”

E5689

B34424652

J20252832

H25324048

MODELTAM-109TAM-112TAM-115TAM-118

C24293236

A55646975

G16182024

D4422

F16182024

Item

Bent channel formounting purposes

2”

H2”

B

J CINTAKE

ASERVICE SIDE

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

SINGLE BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT

A I R I N C O R P O R A T E D

2”

E4689

B34424652

J20252832

H25324048

MODELTAM-109TAM-112TAM-115TAM-118

C24293236

A55646975

G16182024

D4689

F16182024

Item

Bent channel formounting purposes

2”

G D

F

E

PLAN VIEW

BOTTOMDISCHARGE

Gas Inlet

Gas InletPR

ELIM

INAR

Y

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 28: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

H4”

B

J CINTAKE

A F E

G

D

H4”

B

J CINTAKE

F E

G

D

DISCHARGE

A

L M

DISCHARGE

2”channel

Gas Inlet

Gas Inlet

A I R I N C O R P O R A T E D100% AIR MAKE - UP HRH DIMENSIONS

TA-215:230 use 2” channel TA-233:242 use 5” channel

SERVICE SIDE

SERVICE SIDE

2-7

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

SINGLE BLOWER UNITS - HORIZONTAL DISCHARGE - CHANNEL OR CURB MOUNT

A I R I N C O R P O R A T E D

A I R I N C O R P O R A T E D

rev. 01-04

2”

K

K

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations.Intake and discharge accessories may be larger than openings on unit. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. INDOOR hanging units must utilize a bottom cradle (by others).

E488108121214141818

B384654606678789090100100

J2025283242444460607272

H2532404848606072729696

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

C2830323646484866667878

A62696978859595100100110110

G1618242432363644444848

D4722222

2.52.555

F1618242432363644446060

Item K2222222

2.52.52.52.5

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J28324244526072727284

L------------46465656

C32364648586678787890

G24243236424448484848

D22222

2.52.52.52.52.5

F56647290100108132132148168

M------------72727690

MODELTA-215TA-218TA-220TA-225TA-227TA-230*TA-233*TA-236*TA-239*TA-242

A69788595100100118118132146

Item K22222

2.52.52.52.52.5

2” on TA-109, 133 &136

2”

TWIN BLOWER UNITS - HORIZONTAL DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 29: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

SMODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

2”channel

TA-215:230 use 2” channel TA-233:242 use 5” channel

2”

2”H4”

B

J C

K

INTAKE

A

H4”

B

J C

K

INTAKE

A

L M

SINGLE BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT

F

G D

E

Gas Inlet

G D

F

E

Gas Inlet

TWIN BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

SERVICE SIDE PLAN VIEW

SERVICE SIDE PLAN VIEW

2-8

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

A I R I N C O R P O R A T E D

100% AIR MAKE - UP HRD DIMENSIONS

A I R I N C O R P O R A T E D

A I R I N C O R P O R A T E D

BOTTOMDISCHARGE

BOTTOMDISCHARGE

rev. 01-04

E488108121214141818

B384654606678789090100100

J2025283242444460607272

H2532404848606072729696

C2830323646484866667878

A62696978859595100100110110

G1618242432363644444848

D478108121212121414

F1618242432363644446060

Item K2222222

2.52.52.52.5

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J28324244526072727284

L------------46465656

C32364648586678787890

G24243236424448484848

D88813101214143034

F56647290100108132132148168

M------------727290100

MODELTA-215TA-218TA-220TA-225TA-227TA-230*TA-233*TA-236*TA-239*TA-242

A69788595100100118118146156

Item K22222

2.52.52.52.52.5

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations.Intake and discharge accessories may be larger than openings on unit. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes.INDOOR hanging units must utilize a bottom cradle (by others).

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

2” on TA-109, 133 &136

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 30: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

SMODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

rev. 01-04A I R I N C O R P O R A T E D

100% AIR MAKE - UP HRV DIMENSIONS

SINGLE BLOWER UNITS - VERTICAL DISCHARGE - CHANNEL OR CURB MOUNT

TWIN BLOWER UNITS - VERTICAL DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

2-9

E488108121214141818

B384654606678789090100100

J2025283242444460607272

H2532404848606072729696

C2830323646484866667878

A62696978859595100100110110

G1618242432363644444848

D478108121212121414

F1618242432363644446060

Item K2222222

2.52.52.52.5

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J28324244526072727284

L------------46465656

C32364648586678787890

G24243236424448484848

D88813101214143034

F56647290100108132132148168

M------------727290100

MODELTA-215TA-218TA-220TA-225TA-227TA-230*TA-233*TA-236*TA-239*TA-242

A69788595100100118118146156

Item K22222

2.52.52.52.52.5

2”channel

TA-215:230 use 2” channel TA-233:242 use 5” channel

2”

2”H4”

B

J C

K

INTAKE

A

H4”

B

J C

K

INTAKE

A

L M

F

G D

E

Gas Inlet

G D

F

E

Gas Inlet

SERVICE SIDE PLAN VIEW

SERVICE SIDE PLAN VIEW

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

A I R I N C O R P O R A T E D

A I R I N C O R P O R A T E D

TOPDISCHARGE

TOPDISCHARGE

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations. Intake and discharge accessories may be larger than openings on unit. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. INDOOR hanging units must utilize a bottom cradle (by others).

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

2” on TA-109, 133 &136

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 31: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

A I R I N C O R P O R A T E D

N829496100116118118N/AN/AN/AN/A96100116118N/AN/AN/AN/AN/AN/A

AMU VRH DIMENSIONS

G

D

F

B

E

DISCHARGE

K

A

C

SERVICE SIDE

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAINACCESS

(Filter access on opposite side)

Gas conn.

Optional slide in filter sectionM

VERTICAL UNITS - HORIZONTAL DISCHARGE - OUTDOOR MOUNT

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125*TA-127*TA-130*TA-133*TA-136TA-215TA-218TA-220TA-225*TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

G161824243236364444484824243236424448484848

D1.51.51.51.51.52222

2.52.51.51.5222

2.52.52.52.52.5

F161824243236364444606056647290100108132132148168

MN/AN/AN/AN/AN/AN/AN/A112112115115N/AN/AN/AN/A112112115115118118

KN/AN/AN/AN/AN/AN/AN/A60606565N/AN/AN/AN/A606065658286

Item C4050505056707075758686505056707575868692100

A116128130134150152152172172180180130134150152172172180180200204

A I R I N C O R P O R A T E D

E88812121515151528288121316141518182121

B46465868688484949412012094104118138148158198198220248

rev. 01-04

N

34”min.

Bolt on stand from TA-12 to TA-25 & TA-215 to TA-225(2” tubes on unit bottom)

TA-227 & up have 6 legs

2-10

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

Fork lift slots available on some units.

* Units built in two sections, the stand is part of the bottom section and is 36” tall. Stand height may be adjusted to fit customer requirements. Units ordered without filter sections may be physically smaller, but filters can only be mounted externally and unit stand must increase if filters are added later.

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 32: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

A I R I N C O R P O R A T E D

N829496100116118118N/AN/AN/AN/A96100116118N/AN/AN/AN/AN/AN/A

AMU VRV DIMENSIONS

F

B

EDISCHARGE

K

A

C

SERVICE SIDE

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAINACCESS

(Filter access on opposite side)

Gas conn.

Optional slide in filter sectionM

VERTICAL UNITS - HORIZONTAL DISCHARGE - OUTDOOR MOUNT

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125*TA-127*TA-130*TA-133*TA-136TA-215TA-218TA-220TA-225*TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

G161824243236364444484824243236424448484848

D81069888558869118558855

F161824243236364444606056647290100108132132148168

MN/AN/AN/AN/AN/AN/AN/A112112115115N/AN/AN/AN/A112112115115118118

KN/AN/AN/AN/AN/AN/AN/A60606565N/AN/AN/AN/A606065658286

Item C4050505056707075758686505056707575868692100

A116128130134150152152172172180180130134150152172172180180200204

A I R I N C O R P O R A T E D

E88812121515151528288121316141518182121

B46465868688484949412012094104118138148158198198220248

rev. 01-04

N

34”min.

Bolt on stand from TA-12 to TA-25 & TA-215 to TA-225(2” tubes on unit bottom)

TA-227 & up have 6 legs

2-11

GDDISCHARGE

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

Fork lift slots available on some units.

* Units built in two sections, the stand is part of the bottom section and is 36” tall. Stand height may be adjusted to fit customer requirements. Units ordered without filter sections may be physically smaller, but filters can only be mounted externally and unit stand must increase if filters are added later.

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 33: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

100% AIR MAKE - UPVERTICAL INDOOR UNITS

BECAUSE OF THE VARIOUS INDOOR VERTICAL UNITCONFIGURATIONS AVAILABLE, PLEASE CONSULT THE

FACTORY FOR YOUR SPECIFIC APPLICATION.

2-12

Page 34: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

3-1

A LOW COST AIR RECIRCULATION SYSTEM WITH THE ABILITY TO MEET YOUR VARIABLE FRESH AIR NEEDS.TITAN's AR Systems provide even heat distribution, ventilation control, continuous flushing of airborne contaminants, reduces cold air infiltration, and provides a constant fresh air supply, with reduced fuel costs. AR SYSTEMS are ETL listed up 120,000 CFM.ETL listed to 110° temp. rise NG and 90° LP

THE ABILITY TO RECIRCULATE HEATED AIR PROVIDES THE CUSTOMER WITH SUBSTANTIAL ENERGY SAVINGS. Pressurization reduces infiltration by creating a slight positive pressure in the building. Safe, economical, flexible summer and winter ventilation.

APPLICATIONS FOR:AUDITORIUMSFACTORIESFOUNDRIESGARAGES NATATORIUMSWAREHOUSESETC...

• CFM RANGES: 2,400 - 120,000.• 100 % Thermal efficiency.• Indoor or outdoor construction.• Various control systems available.• Efficient natural gas or LP.• Pressurizes building to reduce cold air infiltration.• TITAN's AR/80 SYSTEM ™ features return air by- pass from 0% to 80% with fresh air proportioning

from 100% to 20%.• TITAN's AR/75 SYSTEM ™ features return air by- pass from 0% to 75% with fresh air proportioning

from 100% to 25%.• 100% of heated air is delivered into building, exact

heating and ventilation requirements of your buildingare handled automatically, providing even heatdistribution, while maintaining selected temperaturewithout stratification.

LISTED

AIR RECIRCULATION SYSTEMS

A I R I N C O R P O R A T E D

Electrical /Gas TrainVestibule

Blower &Motor

DISCHARGE

Modulating Return Air Damper

75% or 80%ModulatingOutside Air Damper

TYPICAL BOTTOM RETURN AIR UNIT

RETURNAIR

INTAKE

rev. 01-04

MixingArea

Page 35: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

STANDARD FEATURES:• ETL listed to Z83.18 - 2000.• Recirculating dampers.• Choice of building pressure control, rotary dial damper position, or two position damper control.• Electronic room thermostat working in conjunction with the discharge air sensor.• All Titan Air units are prepiped, prewired, and factory tested. (Some field connections required)• Basic units are fabricated from angle iron, steel tubing and reinforced 16 gauge (min.) galvanized sheet steel. (TA-15 and smaller use 18 gauge min.)• All units are manufactured with controls, motor and blower drives enclosed within the unit.• Easy access, hinged, gasketed and lockable doors to allow servicing of unit components. • Air proving differential pressure switches. • Electronic flame supervision (flame rod rectification).• Main gas automatic safety shut-off valves.• Gas trains built to meet or exceed latest ANSI standard. • High temperature limit control.• Ignition transformer.• Control voltage transformer(s) (when required).• Non-Fused door interlocked disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor starter & overload protection.• D.W.D.I. forward curved industrial type blower (s) with solid turned ground and polished shafting. • Self aligning ball bearings.• Variable pitch blower drive up to 30 HP.• Lifting provisions on all units.• Vertical units are built to accept slide - in filter sections. Integral 36" stand is also standard equipment on most unit sizes.• Vertical units have control panel and gas train serviceable from ground level.• Accurate building pressure sensor or Photohelic® pressure switch on building pressure control systems.• G-90 Galvanized exterior.

OPTIONAL FEATURES:• DDC controller compatible with LonWorks® or Johnson Controls N2 ® communication protocol.• 7 day time clock.• Burner "On - Off" ductstat. (Economizer)• Night thermostat.• Low temperature limit control.• ETL Listed 2 spd blower motor.• Motorized discharge or intake damper w/ safety interlock contacts.• Filter section(s)with cleanable or disposable filters. (O.A. and R.A.)• Intake Hood / Filter combination. (1” cleanable filters on single blower units only)• Screened fresh air intake hood.• Discharge air diffuser.• Roof Curb.• Service platform.• Vibration isolation.• High gas pressure regulator.• Clogged filter indication light.• Operation indication lights.• Circuit analyzer indication lights.• TEFC blower motor.• Audible alarm systems.• IRI, FM, or other special requirements.• Unit cabinet insulation.• Fused Disconnect.• Standard color or color match paint available.• Other options available upon request.

AIR RECIRCULATION FEATURES

3-2

rev. 01-04

Page 36: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

3-3

AIR RECIRCULATION SYSTEMS A I R I N C O R P O R A T E D

Titan Air offers two versions of recirculating direct fired heaters to target specific applications. AR/80™ and AR/75™ models differ in the minimum percentage of outside air (OA) they can supply to a building. Determining which version of recirculating direct fired heater to utilize depends upon outside air requirements. AR/80™ units are intended for applications where the equipment will operate at minimum OA percentage quite often. Operational cost savings of operating at a lower minimum OA percentage will quickly offset higher initial cost of more sophisticated temperature controls. AR/75™ units are intended for applications where requirements for a high OA percentage exist most of the time. Customers benefit from the up-front dollar savings associated with the simpler temperature controls of AR/75™ units. Buildings where space temperature will be controlled below 60°F should utilize a specific temperature controller with AR/75™ units. Refer to controls section for a description of the different approaches utilized in AR/80™ and AR/75™ equipment to prevent build-up of effluents as required by ANSI Z83.18 – 2000. Typical Applications: Warehouses Auditoriums Factories Foundries Garages Natatoriums Etc…….. CFM Ranges: AR/80™ & AR/75™ – 2,400 to 120,000 CFM. Under 4,000 CFM, minimum OA volume is 800 CFM. Min. OA volume increases at altitude. Maximum Available Temperature Rise: 110°F for Natural Gas. 90°F for LP Gas. Minimum Ventilation Rate: AR/80™ - 20% of total unit air volume. AR/75™ - 25% of total unit air volume. Maximum Return Air Percentage: AR/80™ - 80% of total unit air volume. AR/75™ - 75% of total unit air volume.

Titan Air’s direct fired recirculating heaters provide the following benefits:

• Even heat distribution. • Ventilation control. • Constant minimum OA percentage as

OA & RA static pressures vary. • Continuous flushing of airborne

contaminants. • Reduces cold air infiltration (with

building pressure control). • Recirculation of heated building air

when operating at reduced OA percentage. This is an energy savings feature.

Titan Air AR/80™ and AR/75™ equipment is listed by ETL for compliance with ANSI Z83.18-2000 Standard for Recirculating Direct Gas-Fired Heaters. AR/80™ or AR/75™ equipment can vary the volume of outdoor air supply to match exhaust loads and offer a minimum outdoor air mode for efficient space heating. Mechanical exhaust or building relief must always be provided for the minimum outdoor air volume. Titan Air direct fired recirculating equipment provides safe, economical, and flexible heating and ventilation in summer and winter. Proper application provides an effective means of saving energy while improving indoor air quality.

Page 37: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

rev. 01-04

3-4

AIR RECIRCULATION SYSTEMS A I R I N C O R P O R A T E D

ANSI Z 83.18-2000 is a revision of ANSI Z 83.18-1990 covering direct fired recirculating heaters only. Non-recirculating heaters are covered under ANSI Z 83.4/ CSA 3.7-1999 which has also been revised. This revised standard for recirculating direct fired heaters took effect January 1, 2003. This standard has dramatic changes in requirements resulting in equipment and control redesign to certify equipment.

PROVED VENTILATION RATE Under previous versions of direct fired recirculating heater standards, there were no requirements to prove minimum ventilation rate. The new standard requires minimum ventilation rate be maintained at or above minimum certified percentage of outside air (OA) or the burner must be shut down. Titan Air certified AR/80™ equipment to maintain a minimum ventilation rate of 20% of total unit air volume and designed an OA/RA damper/control combination that maintains 20% minimum OA. The same OA/RA damper/control design is utilized on AR/75™ equipment to maintain 25% minimum OA.

EFFLUENT BUILD UP IN SERVED AREA (Attributed to Direct Fired heater) Direct fired equipment inherently carries the products of combustion into the served area. The intention of this standard is to limit the build up of effluents (as a time weighted average, TWA) to the following predetermined levels.

Carbon Dioxide (CO2) = 5,000 PPM Carbon Monoxide (CO) = 25 PPM Nitrogen Dioxide (NO2) = 3 PPM

Research conducted by the Gas Research Institute (GRI) proved that build-up of effluents from a recirculating direct fired heater with a controlled discharge temperature (explained further in next segment) will not exceed these levels in a building with equal relief (mechanical or natural) to the OA volume introduced. These limits are well within OSHA and ACGIH guidelines.

CONTROLLED DISCHARGE AIR TEMPERATURE CO2 is a predictable value as applied to combustion. For every 1000 BTU worth of gas burned, under design air/fuel mixture, there is a given quantity of CO2 (in PPM) produced. Using CO2 maximum values as a base line, combined with the variables of OA temperature, RA temperature and percent ventilation, the maximum equivalent temperature rise and maximum allowable discharge temperature can be calculated.

------------------------------------------------------------------------- EXAMPLE: An AR/80 unit with OA/RA dampers in minimum OA position, OA temperature at 10°F, RA temperature at 62°F.

Temp Rise (equivalent) = ((5000 x (20/100)) -:- (19.63 x 1.04)) Where:

5000 = Maximum PPM CO2 in served area 20/100 = Percent ventilation expressed as a fraction 19.63 = Constant 1.04 = Amount of CO2 formed by combustion of 1000 BTU Nat Gas based on dry standard

conditions. Factor for LP gas is 1.206

Temperature Rise Equivalent = 48.98°F

Knowing the maximum equivalent temperature rise, OA temperature, RA temperature and the percentage of ventilation, the maximum allowable discharge temperature can be calculated.

Max Allowable Disch. Temp.= [(20%OA x (10° + 48.98°)) + (80%RA x (62° + 48.98°))] -:- (20%OA + 80%RA)

Maximum allowable discharge temperature = 100.58°F -------------------------------------------------------------------------

These algorithms are programmed into AR/80™ controllers so as variables (OA temperature, RA temperature and percentage ventilation) change, during the course of operation, the maximum allowable discharge temperature will be recalculated and adjusted accordingly. AR/80™ equipment will feature more sophisticated controllers to continuously calculate maximum allowable discharge temperature. Titan Air also offers AR/75™ equipment with simpler temperature controls that will always assume minimum ventilation rate thereby eliminating OA damper position feedback. Refer to controls section of catalog for comparisons of AR/80™ and AR/75™ control options.

Page 38: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J32424244526072727284

E488108121214141818

B384654606678789090100100

J2832324242444460607272

H2532404848606072729696

A I R I N C O R P O R A T E D

P4”

L------------56565656

C42475254586678787890

G24243236424448484848

D1213872

2.52.52.52.52.5

F56647290100108132132148168

M------------72727690

P19232732373944444848

MODELTA-215TA-218TA-220TA-225TA-227TA-230*TA-233*TA-236*TA-239*TA-242

A69788595100100128128132146

N708096114124132170170184216

H4”

B

J C

K

INTAKE

A

SERVICE SIDE

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

C3542424752545466667878

A62696978859595100100128128

G1618242432363644444848

D13131213888

2.52.52.52.5

F1618242432363644446060

F E

G

D

SINGLE BLOWER UNITS - HORIZONTAL DISCHARGE - CHANNEL OR CURB MOUNT

TWIN BLOWER UNITS - HORIZONTAL DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

H4”

B

J C

K

INTAKE

F E

G

D

AL M

Item

Item

N2026343844545466667676

P1117192327343439395252

P4”N4”

N4”RETURN

RETURN

RETURN

Gas Inlet

Gas Inlet

AIR RECIRC. HRH DIMENSIONS

2”

SERVICE SIDE

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

DISCHARGEA I R I N C O R P O R A T E D

A I R I N C O R P O R A T E DDISCHARGE

RETURN

rev. 01-04

K2222222

2.52.52.52.5

K22222

2.52.52.52.52.5

2”channel

TA-215:230 use 2” channel TA-233:242 use 5” channel

2” on TA-109, 133 &136

2”

3-5

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations. Intake and discharge accessories may be larger than openings on unit. N & P dimensions (max. shown) may vary depending on unit CFM. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. INDOOR hanging units must utilize a bottom cradle (by others).

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

TA-109’s have certain restrictions, consult factory.

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 39: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

RETURN RETURN

A I R I N C O R P O R A T E D

H4”

B

JC

K

INTAKE

ASERVICE SIDE

TWIN BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

H4”

B

J C

K

INTAKE

SERVICE SIDEA

L M

G DPLAN VIEW

F

G DPLAN VIEW

E

F

E

P4”

N

P4”

BOTTOMRETURN N

4”

Gas Inlet

Gas Inlet

BOTTOMRETURN

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

4”

A I R I N C O R P O R A T E D

BOTTOMDISCHARGE

BOTTOMDISCHARGE

A I R I N C O R P O R A T E D

E488108121214141818

B384654606678789090100100

J2832324242444460607272

H2532404848606072729696

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

C3542424752545466667878

A62696978859595114114128128

G1618242432363644444848

D478108121212121414

F1618242432363644446060

Item N2026343844545466667676

P1117192327343439395252

AIR RECIRC. HRD DIMENSIONS

rev. 01-04

K2222222

2.52.52.52.5

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J32424244526072727284

L----------4656565656

C42475254586678787890

G24243236424448484848

D88813101214143036

F56647290100108132132148168

M----------68727290100

P19232732373944444848

MODELTA-215TA-218TA-220TA-225TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

N708096114124132170170184216

Item K22222

2.52.52.52.52.5

A69788595100114128128146156

RETURN RETURN

2”channel

TA-215:230 use 2” channel TA-233:242 use 5” channel

2”

SINGLE BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT

2”

3-6

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations. Intake and discharge accessories may be larger than openings on unit. N & P dimensions (max. shown) may vary depending on unit CFM. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. INDOOR hanging units must utilize a bottom cradle (by others).

TA-109’s have certain restrictions, consult factory.

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

2” on TA-109, 133 &136

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 40: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

RETURN RETURN

A I R I N C O R P O R A T E D

H4”

B

JC

K

INTAKE

ASERVICE SIDE

TWIN BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT UP TO TA-230

H4”

B

J C

K

INTAKE

SERVICE SIDEA

L M

G DPLAN VIEW

F

G DPLAN VIEW

E

F

E

P4”

N

P4”

BOTTOMRETURN N

4”

Gas Inlet

Gas Inlet

BOTTOMRETURN

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAIN

ACCESS

BLOWER /MOTORACCESS

4”

A I R I N C O R P O R A T E D

TOPDISCHARGE

TOPDISCHARGE

A I R I N C O R P O R A T E D

AIR RECIRC. HRV DIMENSIONS

rev. 01-04

H728096120128144180180192216

E8101113141418182121

B92102118138148158198198212244

J32424244526072727284

L----------4656565656

C42475254586678787890

G24243236424448484848

D88813101214143036

F56647290100108132132148168

M----------68727290100

P19232732373944444848

MODELTA-215TA-218TA-220TA-225TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

N708096114124132170170184216

Item K22222

2.52.52.52.52.5

A69788595100114128128146156

RETURN RETURN

2”channel

TA-215:230 use 2” channel TA-233:242 use 5” channel

2”

2”

3-7

* Units are built in two sections. F,G, H & J are accessory dimensions. D,E & K are accessory locations. Intake and discharge accessories may be larger than openings on unit. N & P dimensions (max. shown) may vary depending on unit CFM. All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. INDOOR hanging units must utilize a bottom cradle (by others).

E488108121214141818

B384654606678789090100100

J2832324242444460607272

H2532404848606072729696

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125TA-127TA-130TA-133TA-136

C3542424752545466667878

A62696978859595114114128128

G1618242432363644444848

D478108121212121414

F1618242432363644446060

Item N2026343844545466667676

P1117192327343439395252

K2222222

2.52.52.52.5

SINGLE BLOWER UNITS - DOWN DISCHARGE - CHANNEL OR CURB MOUNT

TA-109’s have certain restrictions, consult factory.

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

2” on TA-109, 133 &136

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 41: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

Q202840485064647272100100708096114124132170170192216

N829496100116118118N/AN/AN/AN/A102110116118N/AN/AN/AN/AN/AN/A

P111617182428283636404019232732373944444548

AR VRH DIMENSIONS

G

D

F

B

E

DISCHARGE

K

A

C

SERVICE SIDE

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAINACCESS

(Filter access on opposite side)

Gas conn.

Optional slide in filter section

RETURN AIR P

Q 3”

M

VERTICAL UNITS - HORIZONTAL DISCHARGE - OUTDOOR MOUNT

G161824243236364444484824243236424448484848

D1.51.51.51.51.52222

2.52.51.51.5222

2.52.52.52.52.5

F161824243236364444606056647290100108132132148168

MN/AN/AN/AN/AN/AN/AN/A112112115115N/AN/AN/AN/A112112115115118118

KN/AN/AN/AN/AN/AN/AN/A60606565N/AN/AN/AN/A606065658286

Item C5050505060707075758686506066757575868692100

A116128130134150152152172172180180136144150152172172180180200204

A I R I N C O R P O R A T E D

E88812121515151528288121316141518182121

B46465868688484949412012094104118138148158198198220248

rev. 01-04

N

34”min.

Bolt on stand from TA-12 to TA-25 & TA-215 to TA-225(2” tubes on unit bottom)

TA-227 & up have 6 legs

3-8

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

* Units built in two sections, the stand is part of the bottom section and is 36” tall. Stand height may be adjusted to fit customer requirements. Units ordered without filter sections may be physically smaller, but filters can only be mounted externally and unit stand must increase if filters are added later.

Fork lift slots available on some units.

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125*TA-127*TA-130*TA-133*TA-136TA-215TA-218TA-220TA-225*TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 42: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

C

GDDISCHARGE

A I R I N C O R P O R A T E D

Q202840485064647272100100708496114124132170170192216

N829496100116118118N/AN/AN/AN/A102110116118N/AN/AN/AN/AN/AN/A

P111617182428283636404019202732373944444548

AR VRV DIMENSIONS

F

B

EDISCHARGE

K

A

SERVICE SIDE

BLOWER /MOTORACCESS

ELECTRICAL /GAS TRAINACCESS

(Filter access on opposite side)

Gas conn.

Optional slide in filter section

RETURN AIR P

Q 3”

M

VERTICAL UNITS - HORIZONTAL DISCHARGE - OUTDOOR MOUNT

G161824243236364444484824243236424448484848

D131069888558869118558855

F161824243236364444606056647290100108132132148168

MN/AN/AN/AN/AN/AN/AN/A112112115115N/AN/AN/AN/A112112115115118118

KN/AN/AN/AN/AN/AN/AN/A60606565N/AN/AN/AN/A606065658286

Item C5050505060707075758686506066757575868692100

A116128130134150152152172172180180136144150152172172180180200204

A I R I N C O R P O R A T E D

E88812121515151528288121316141518182121

B46465868688484929212012094104118138148158198198220248

rev. 01-04

N

34”min.

Bolt on stand from TA-12 to TA-25 & TA-215 to TA-225(2” tubes on unit bottom)

TA-227 & up have 6 legs

3-9

MODELTA-109TA-112TA-115TA-118TA-120TA-122TA-125*TA-127*TA-130*TA-133*TA-136TA-215TA-218TA-220TA-225*TA-227*TA-230*TA-233*TA-236*TA-239*TA-242

* Units built in two sections, the stand is part of the bottom section and is 36” tall. Stand height may be adjusted to fit customer requirements. Units ordered without filter sections may be physically smaller, but filters can only be mounted externally and unit stand must increase if filters are added later.

Fork lift slots available on some units.

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 43: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

3-10

AIR RECIRCULATIONVERTICAL INDOOR UNITS

BECAUSE OF THE VARIOUS INDOOR VERTICAL UNITCONFIGURATIONS AVAILABLE, PLEASE CONSULT THE

FACTORY FOR YOUR SPECIFIC APPLICATION.

Page 44: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DDEMAND AIR SYSTEMS - GENERAL INFO.

4-1

APPLICATIONS FOR:AUDITORIUMSFACTORIESGARAGESSPRAY BOOTHS NATATORIUMSWAREHOUSESBODY SHOPS, PLUS MANY MORE !

• CFM RANGES: Up to 120,000• Indoor or outdoor construction.• Best air make-up solution for facilities with variable exhaust loads.• Modulating air flow maintains constant building pressure.• Gas flow modulated with air flow to maximize energy savings and maintain a constant temperature rise.

DIRECT FIRED VARIABLE VOLUME AIR MAKE-UP

AveragingSensor

OUTSIDEAIR

LISTED

TITAN's DEMAND-AIR ™provides ventilation control, building pressurization, continuous flushing of airborne contaminants, reduces cold air infiltration and stratification, and provides a constant fresh air supply, with reduced electrical and fuel costs. DEMAND-AIR Systems are ETL listed up to 120,000 CFMat 100° temp. rise.

• Efficient natural gas.• 100 % Thermal efficiency.• Pressurizes building to reduce cold air infiltration and reduce stratification.• Exact ventilation requirements of your building are handled automatically, providing only the make-up air needed to maintain a slight positive building pressure at selected discharge temperature. (Drive shipped loose for indoor mounting and field wired)

VariableFrequency Drive

Pressure Transmitter

Constant Temp. /Variable VolumeDischarge Air

Air Flow Variable to 30% of Unit Volume.

rev. 01-04

Page 45: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

OPTIONAL FEATURES:• Premium Efficiency blower motor.• Filter section with cleanable or disposable filters.• Intake Hood / Filter combination. (1” cleanable filters on single blower units only)• Screened fresh air intake hood.• Discharge air diffuser.• Roof Curb.• Service platform.• Vibration isolation.• High gas pressure regulator.• Clogged filter indication light.• Circuit analyzer indication lights.• TEFC blower motor.• Low temperature limit control.• Audible alarm systems.• IRI, FM, or other special requirements.• Unit cabinet insulation.• Fused Disconnect.• 7 Day time clock.• Unit mounted VFD (some times cabinet is larger) • Standard color or color match paint available.• Other options available upon request.

Air flow variable up to 30% of unit volume.Demand Air equipment rated at less than 4000 cfm will be configured for a minimum air volume of 1200 cfm.

A I R I N C O R P O R A T E DDEMAND AIR FEATURES

4-2

STANDARD FEATURES:• ETL listed.• Variable Frequency Drive.• Additional drive outputs for controlling or sequencing associated external equipment.• Display of numerous operating data parameters (i.e. frequency, kwh, hp, etc.).• Electronic Pressure Control.• Auto / Manual Speed Control.• Electronic discharge air temperature control. • Burner "On / Off" Ductstat. (Economizer).• Low Temperature Limit Control.• Operating Mode Indication.• DDC Controller.• All Titan Air units are prepiped, prewired, and factory tested. (Some field connections required)• Basic units are fabricated from angle iron, steel channel and reinforced 16 gauge (min.) galvanized sheet steel. (TA-15 and smaller use 18 gauge min.)• All units are manufactured with controls, motor and blower drives enclosed within the unit.• Easy access, hinged and gasketed doors to allow servicing of unit components. • Air proving differential pressure switches. • Electronic flame supervision (flame rod rectification).• Main gas automatic safety shut-off valves.• Gas trains built to meet or exceed ANSI Z83.4 1999 / CSA 3.7 M99 standard.• High gas pressure safety switch.• High temperature limit control.• Ignition transformer.• Control voltage transformer(s) (when required).• Non-Fused door interlocked disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor overload protection.• D.W.D.I. forward curved industrial type blower (s) with solid turned ground and polished shafting. • Self aligning ball bearings.• Variable pitch blower drive up to 30 HP.• Lifting provisions on all units.• Vertical units are built to accept slide - in filter sections. Integral 36" stand is also standard equipment on most unit sizes.• Vertical units have control panel and gas train serviceable from ground level.• VFD shipped loose for field installation. • G-90 Galvanized exterior.

rev. 01-04

Page 46: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

DIMENSIONS & HP CHARTSDEMAND-AIR ™units are the same size as Air Make-Up units and are available in the same configurations. Refer to the Air Make-Up section for dimensional data and blower motor horsepower charts.

TITAN AIR has emerged as an industry leader in both innovation and design. In 1988 TITAN AIR was the first to have 2 speed air make-up and 2 speed air recirculating units tested and approved by ETL Testing Laboratories. Now, we have designed the DEMAND-AIR system which incorporates the traditional efficiency of direct fired equipment with the superior* energy savings of a variable frequency drive, the first ETL listed in the industry. Because some customers have an ever changing air make-up demand, we have developed an extremely flexible system to cover both high and low CFM requirements. * Variable frequency drives are significantly more efficient than inlet vane or discharge damper VAV systems.

4-3

TITAN's DEMAND-AIR system meets the demand by using building pressure as a sensing point to signal the frequency drive to change blower speed. By supplying only the make-up air needed, TITAN's DEMAND-AIR system can help you realize operational savings in two ways. First, gas consumption will be reduced each time the blower(s) slow down (gas needed to maintain a discharge temperature will drop in direct proportion to the air flow). Second, horsepower and electrical power needed to move the required air will drop exponentially as the air flow is reduced. Also many utilities offer rebates on the installation of variable speed drives which means additional savings.

THE HIGH QUALITY OF TITAN'S PRODUCTS ARE SECOND TO NONE. High quality along with the high efficiency of the new DEMAND-AIR system, gives you a long lasting money saving system that simply can't be beat!

DEMAND-AIR ENERGY SAVINGS EXAMPLE :

CityAvg. Winter Temp.No. Winter Weeks

Control Temp.Hours / WeekGas $ / CCF

Weighted Avg. Elec. $ / kwhMotor EfficiencyDrive Efficiency

Minneapolis29°3170°80

0.4530.0589%98%

USAGE

LOCATION The table below represents the potential dollarsavings that can be realized by utilizing TITAN's DEMAND-AIR system instead of a fixed volume Air Make-up system. A similar tabulation can quickly be generated (for payback and rebate calculations) on a specific application utilizing the operating parameters at the top of the chart, CFM, HP, and an estimate of the expected modulation cycle(4th column of table).

% AIRFLOW

100907060504030

CFM12,00010,8008,4007,2006,0004,8003,600

MOTORHP10

7.293.432.161.250.640.27

Totals

%TIME

15101015101030100

HOURSGAS /YEAR372248248372248248744

2,480

HOURSELEC. /YEAR624416416624416416

1,2484,160

CCFGAS /YEAR2,0131,208940

1,208671537

1,2087,785

KWH /YEAR5,3372,5941,2201,153445228288

11,265

YEARLYGAS

COST$912$547$426$547$304$243$547

$3,526

YEARLYELEC.COST$267$130$61$58$22$11$14$563

YEARLY GAS COST AT 100% AIR FLOW = $6,080YEARLY ELECTRIC COST AT 100% AIR FLOW = $1,743

Utilizing Titan's DEMAND-AIR system at given parameters yields:POTENTIAL YEARLY SAVINGS IN GAS COSTS = $2,554

POTENTIAL YEARLY SAVINGS IN ELECTRIC COSTS = $1,180

DEMAND AIR SYSTEMS - EXAMPLES

rev. 01-04

Page 47: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

Titan Indoor Pool Area Comfort SystemSuccessful pools offer pool side comfort in which those not in the water can relax and socialize. The Titan Pool Area Heating / Ventilating System comes designed for high efficiency in cold climates. For required ventilation, the Titan system introduces tempered outside air to replace exhausted, corrosive, humid air within the pool enclosure. In winter, the amount of fresh air being supplied is dictated by the level of relative humidity in the pool area. Typically, as the system settles out, less fresh air is needed to control the humidity level. Desirable lower gas consumption is the result. Titan’s direct fired burner offers maximum thermal efficiency. This indoor pool area comfort system is another example of Titan Air engineering working to serve you better.

American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRE) Design Guidelines.1. “Natatoriums are characterized by high latent loads that should be controlled to minimize corrosion and condensation on the building structure. Outdoor air of low moisture content may be used for this purpose.” “Ventilation of the pool enclosure helps control corrosion and condensation.”

In the winter months the outside air is typically very dry. Titan’s AR/80, along with a control scheme specifically designed for the swimming pool environment, takes advantage of this dry outside air to purge the pool area of the unwanted corrosive moisture. Titan’s AR/80 has the capability of modulating the handled air from a high of 100% outside air to a low of 20% outside air. Air not taken from the outside is recirculated, through the heater (after the burner), from the pool area.

As tempered dry air is introduced to the pool area, an equal amount of humid air will be exhausted. As the humidity level rises (increased activity) more fresh air is introduced and in turn more humid air is exhausted.

A I R I N C O R P O R A T E DSWIMMING POOL AREA EQUIPMENT

5-1(Above photo printed with permission of Americinn International, LLC.)

Page 48: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

5-2

SWIMMING POOL AREA EQUIPMENT

2. “The pool area should be isolated from the adjacent building areas, if possible, bycreating a negative pressure in the pool area.”

Part of Titan’s control scheme, designed for swimming pool applications, includes a Variable Frequency Drive to change the speed of the exhaust fan. A pressure differential sensor is employed to determine the pressure differential between the pool area and lobby area (in the case of a motel). The signal from the pressure differential sensor will dictate the speed at which the exhaust fan operates. The controller set point is at a negative. Any time the sensor indicates the pressure is approaching neutral, the speed of the exhaust fan will increase holding the pool area in a negative as compared to the rest of the building.

3. “All components of the pool heating, air handling and air distribution systems thatare exposed directly or indirectly to the moist, corrosive pool atmosphere should be protected from the corrosiveness”.

Proper design of the equipment will include a phenolic coated interior. Heresite, Titan’s phenolic coating of choice, is resistant to chlorine or bromine laden air common in a swimming pool application.

ADDITIONAL FACTORS AFFECTING EQUIPMENT PERFORMANCEDelivering tempered dry air (from Titan’s unit) to a pool enclosure is only part

of a good pool de-humidification and ventilation system. Proper air distribution is essential to prevent condensation on windows and other building components. Air distribution also plays a large role in the volume of water evaporated from a pool surface. Along with air distribution, the control scheme (temperature, humidity and pressure) must be wired, set up and operated properly. Vapor barriers on interior surfaces of pool areas play an important role in keeping moist corrosive air from damaging insulation and other building materials.Titan strongly recommends installing pool heating / ventilation equipment in a mechanical room adjacent to the pool area. Outdoor mounted equipment SHOULD NOT be placed directly over the pool. Additional installation and operational restrictions will apply to outdoor mounted equipment.

Page 49: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DSWIMMING POOL AREA EQUIPMENT

5-3

DUCT WORK AND REGISTERSDuct and registers must be designed, and placed, to deliver an adequate air

volume and velocity to the entire surface area of each window. If the inner surface temperature of a window drops below room air dew point temperature, condensation will occur (see chart 1). The aesthetic appeal of numerous windows (especially those high on the side wall and near a spa or hot tub) should be weighed against the required increased air volume and duct work to prevent condensation. Per ASHRAE’S guidelines, “the use of glass on pool exposures complicates the design problem and adds cost, especially in colder climates. Cold drafts and condensation are difficult and expensive to eliminate if glass walls or exposures are used”.

Air velocity over water surface(s) must be kept at a minimum to reduce water evaporation. Supply air should be directed up or down along perimeter windows and / or walls. Return air and exhaust inlets should be located as high as possible to minimize air velocity over the water surface. The higher the rate of evaporation, the higher the humidity level. A higher humidity level will require a higher volume of outside air to dissipate the humidity creating higher gas consumption to heat the extra volume of outside air.

An outdoor air intake, either hood or louver, should be sized and located to prevent snow and rain from being drawn in. The mechanical room must be large enough to facilitate proper installation and service of the unit, and proper configuration of supply, return and exhaust duct work, filters etc.

CONTROLS, START - UP AND MAINTENANCEThere are three parameters to the control scheme for this type of application.

Humidity, temperature and pressure controls must be properly designed and integrated to ensure all three are optimized efficiently. Titan has selected sensors not affected by the corrosive atmosphere associated with this application. The controllers, for sensors in pool area, will be located in the mechanical room with sensors being wired to them. If mechanical room door is located in the pool area, it should have a good seal to prevent air in pool area from migrating into the mechanical room.

Factory checkout cannot duplicate conditions the equipment will see when installed. A thorough check out of the system must be performed at job site. In addition to job site start - up, detailed operator training should be given to building staff. On a yearly basis, a qualified technician should perform a complete start - up procedure to ensure all sensors and controls are functioning properly and all safety controls are operational.

Temperature at which condensationwill take place on interior surfaces

% RelativeHumidity

Pool Area Temperatures (°F)

40%50%60%

74°485459

76°505661

78°525863

80°546065

82°556167

84°576368

86°596570

chart 1

Page 50: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DSWIMMING POOL AREA EQUIPMENT

5-4

DESIGN CRITERIAThe swimming pool environment can be one of the more difficult

environments to control. When designing a pool area there are several factors that must be taken into account while selecting equipment to heat and ventilate the area.

1) People Comfort - both in and out of pool.

2) Air Movement - air movement at outside perimeters and air velocity across the water surface.

3) Humidity Level - keep humidity in a zone that will provide comfort and building protection.

4) Negative Pressure - pool area should be kept at a negative pressure as compared to rest of facility to avoid destructive, chlorine laden air from migrating out of the pool area.

Chlorine laden moisture, if left to condensate, can and will have devastating effects on most building materials. Studies have proven the optimum relative humidity level for human comfort is 50% to 60%.

Evaporation of water, in a pool area, is the source for high levels of humidity. Of the methods of controlling humidity in a swimming pool environment, dry fresh air is the most effective method. The introduction of fresh air and exhausting of an equal volume of pool air will purge the area of moisture, thus lowering the relative humidity level.

Contact your Titan Air Representative for sizing information.

Outside Air

Return Air

Exhaust Air

Titan AR/80

Mechanical Room

Pool Enclosure

Windows

PVC coated below grade duct

Page 51: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DEVAPORATIVE COOLING - GENERAL INFO.

6-1

EVAPORATIVE COOLING EFFECTIVENESS: The performance of an evaporative cooler is based on the ratio of the number of degrees it can cool the air compared to the WET BULB DEPRESSION. This rating is the "evaporative EFFECTIVENESS" or (evaporative EFFICIENCY) of the cooler. The number of degrees the DRY BULB TEMPERATURE (DBT) of the air can be lowered is a percentage of the WET BULB DEPRESSION of (DBT - WBT) x EVAPORATIVE EFFECTIVENESS.

0.000

0.004

0.008

0.012

0.016

0.020

0.024

0.028

0.032

3040

50

60

70

80

90

DRY BULB TEMPERATURE, (DEGREES F)

72°

102°

ILLUSTRATIONOF AN 89% EFFECTIVEEVAPORATIVE COOLER

102°

72°

20 30 40 50 60 70 80 90 100 110 120

EXAMPLE: FRESNO, CA.AIR FLOW 1% DESIGN DRY BULB 1% DESIGN WET BULB HUMIDITY RATIO (INCOMING AIR)COOLER EFFECTIVENESSLEAVING DRY BULBLEAVING WET BULBHUMIDITY RATIO (DISCHARGE AIR)

102° - ((102° - 72°) X (89 / 100)) = 75°

20,000 CFM102°72°.01124 lbw / lba89% @ 500 fpm75°72°.01745 lbw / lba

At design conditions the evaporation rate to reduce the dry bulb temp. from 102° to 75° will be 59 gph. To keep the reservoir water fresh, it is necessary to bleed some water off at all times. Depending on the water conditions, the bleed off rate can be equal to the evaporation rate. The total make-up water rate can be as high as 118 gph with this example.

COOLING = .89 x (102-72)=26.7

Page 52: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DEVAPORATIVE COOLING - FEATURES

6-2

STANDARD FEATURES:• Rigid cellulose media• Service vestibule housing contains the submersible pump, float valve, bleed line, fill / drain / overflow ports, gauges, flow control valve.• Media removal through service vestibule.• Stainless steel sump.• Standard unit casing is reinforced 18 gauge (min.) galvanized sheet steel.• Properly designed distribution header, media supports, and nominal 500 fpm face velocity to prevent moisture carryover.

MAINTENANCE:• Detailed installation, water treatment, and maintenance instructions are provided with each unit.• Proper flow / bleed rates, regular media flushing / drying, and routine sump cleaning are the most effective techniques to control scale buildup and biological fouling.• Proper bleed off rates vary with local water conditions (harder water requires higher bleed off rates). Maximum bleed off rate is equal to the evaporation rate.• Softened water should NOT be used because of the tendency to "leach" the resins out of the media.• Non-oxidizing biocides can be used but, are frequently not required.

GENERAL:• CFM RANGES: 1,200 - 30,000 standard ranges, other sizes available on a design basis.• Indoor or outdoor construction.• 12" media has 89% evaporative efficiency at 500 fpm face velocity.• Process relies solely on water evaporation with extremely low energy consumption.• Consistent predictable performance with minimal maintenance.• Service vestibule, stainless steel sump and tightly sealed seams indicative of Titan reliability, serviceability and workmanship.• Properly maintained media will function as a secondary, self-cleaning air filter.• Rigid cellulose media - the industry standard with the highest efficiency, lowest pressure drop, and highest drift free velocity plus a compact design.

OPTIONAL FEATURES:• Remote Auto / Fill Drain Solenoid / Switch kit.• Cooling stat (room or ductstat).• Auto Flush / Dry Timer Switch.• Daily Dry Cycle Timer.• Staged humidification / Temperature control for spray booth or other special applications.• Flame retardant fiberglass media.• Screened fresh air intake hood.• Filter section.• Hood / filter combination• Ductwork transition from evaporative cooler to air make-up unit.• Applications with size limitations can be sized at 750 fpm face velocity (this is maximum drift free velocity, static pressure increases by a factor of .2" WC).• Pump power supply.• GFI outlet.

APPLICATIONS FOR:FACTORIESFOUNDRIESSPRAY BOOTHSKITCHENSGREENHOUSESGYMNASIUMSWAREHOUSESLIVESTOCK CONFINEMENTLAUNDRIES, PLUS MANY MORE !

rev. 01-04

Page 53: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DEVAPORATIVE COOLING

6-3

A MORE COMFORTABLE ENVIRONMENT WITH EVAPORATIVE COOLING Titan Air evaporative coolers feature high quality rigid cellulose media or flame retardant fiberglass media. The temperature shown on an ordinary thermometer is called the dry bulb temperature. The cooling effect of evaporative pads is measured by the wet bulb temperature, which is a function of the relative humidity. Figure 1 illustrates the relationship between the wet bulb temperature and the dry bulb temperature. The wet bulb temperature is directly related to the relative humidity. The drier the air, the faster the water evaporates and the cooler the sock becomes. An evaporative cooler works the same way. It cools the air to a temperature close to the wet bulb temperature. In the continental United States, the average wet bulb temperature during the summer ranges between 70°F and 80°F. Evaporative cooling media pads can cool air within 2° or 3° of the wet bulb temperature. With proper maintenance, they can operate for years at high air volumes without loss of cooling efficiency or water carryover. In practical terms, this clearly means a more comfortable environment. To permit optimum design of contact material for each application, the media pads are manufactured in a variety of flute heights and pad depths. Alternative media types, originally designed as air filters, are not practical for central HVAC systems. The research and development by Munters has changed the way HVAC Engineers and Architects utilize evaporative cooling. Rigid media equipped systems do not require long air travel. There are no high pressure nozzles to maintain. Nor do they require yearly pad changes. Performance is predictable and consistent year after year. Rigid media systems are not restricted by size. The nominal face velocity of TITAN's evaporative cooling models is 500 FPM, giving each model an average evaporative cooling efficiency of 89%. This means that the discharge temperature of TITAN's evaporative coolers will be 89% of the difference between the entering dry bulb temperature and the entering wet bulb temperature. See figure 2. Even in the most humid areas, the temperature of supply air can be reduced, creating a cooler more comfortable work environment especially in kitchens, laundries and dry cleaning facilities.

fig. 2

100%

90%

80%

70%

60%

200 300 400 500 600 700 800

Face Velocity (FPM)

Example:105° DB 75° WB

fig. 1

105°

75°

rev. 01-04

Page 54: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E D

6-4

DF

B

EC

G

A

SIDE VIEW

All dimensions subject to manufacturing tolerances.Do not use dimensions for construction purposes unless verified by factory.

FRONT VIEW

CFM RANGE Up to 2,000 Up to 4,500 Up to 6,000 Up to 8,000 Up to 10,000 Up to 12,500 Up to 15,000 Up to 18,000 Up to 21,000 Up to 24,000 Up to 30,000

Fill, drainand overflowconnectionson this end

AIR FLOW

MODELTA-24/24 EVTA-36/36 EVTA-36/48 EVTA-48/48 EVTA-48/60 EVTA-60/60 EVTA-60/72 EVTA-72/72 EVTA-72/84 EVTA-72/96 EVTA-72/120 EV

* Equipment above 30,000 CFM also available.

ACCESS

D20324444565668688092120

MODELTA-24/24 EVTA-36/36 EVTA-36/48 EVTA-48/48 EVTA-48/60 EVTA-60/60 EVTA-60/72 EVTA-72/72 EVTA-72/84 EVTA-72/96 EVTA-72/120 EV

C3648486060727284848484

A2222222222222222222222

F22222222222

G66666666666

E2436364848606072727272

B364860607272848496108136

EVAPORATIVE COOLING DIMENSIONS

A I R I N C O R P O R A T E D

INTAKE(dischargesame size)

rev. 01-04SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 55: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A CUSTOM SYSTEM DESIGNED AND BUILT BY EXPERIENCED PROFESSIONALS CAN BE YOUR BEST AND MOST ECONOMICAL COIL BASED HVAC SOLUTION.TITAN's hydronic, DX, and electric coil units are designed using a conservative application of coil and blower manufacturers' design recommen-dations to meet a customer's specific requirements. You can be assured of proper heating/cooling and airflow without paying for an undersized or oversized "standard" unit. Call for quotations and sizing considerations.

THE HEART OF YOUR COIL BASED HVAC SYSTEM IS TESTED TO MEET INDUSTRY STANDARDS. All hydronic and DX coils are tested and rated by the manufacturer in accordance with Air Conditioning and Refrigeration Institute (ARI) Standard 410 and certified in accordance with the ARI certification program. Electric Coils are UL Listed.

7-1

APPLICATIONS FOR PRIMARY HEATING/ COOLING OR AIR MAKE-UP IN:COMMERCIAL/RESIDENTIAL BUILDINGSAUDITORIUMSFACTORIESFOUNDRIESGARAGES NATATORIUMSWAREHOUSESETC...• Indoor or weather proof construction.• Optional fresh air and return air mixing chambers with mixed air temperature control, building pressure control or other options.• Coil size and configurations optimized based upon each customer's heating/cooling medium specifications (steam pressure, entering water temperature, etc...).• Horizontal or vertical unit configurations. • Units are built on a design-build basis and sized accordingly (based upon coil selection, control arrangement, and other considerations).• Solid construction, attention to details, and service considerations are representative of Titan's commitment to quality.• Variable frequency motor drive can be adapted to Hydronic systems.

A I R I N C O R P O R A T E D rev. 01-04

HYDRONIC, DX, AND ELEC. COIL UNITS

Page 56: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

OPTIONAL FEATURES:(Common to all coil units)• Fresh air and return air mixing sections with controls.• Building pressure control with modulating fresh air and return air dampers or variable frequency drive.• Temperature / humidity control system (see unit specific features on next page).• Serpentine element freeze stat for hydronic coils. • 2 spd blower motor.• Motorized discharge or intake damper w/ safety interlock contacts.• Filter section(s) with cleanable or disposable filters. (O.A. and R.A.)• Intake Hood / Filter combination (1” cleanable filters.)• Screened fresh air intake hood.• Discharge air diffuser.• Roof Curb.• Service platform.• Vibration isolation.• Clogged filter indication light.• Operation indication lights.• Circuit analyzer indication lights.• TEFC blower motor.• Audible alarm systems.• Unit cabinet insulation.• Fused door interlocked disconnect.• 7 Day time clock.• Standard color or color matched paint.• Other optional available upon request.

A I R I N C O R P O R A T E DHYDRONIC, DX, AND ELEC. COIL UNITS

7-2

STANDARD FEATURES:(Common to all coil units)• ETL listed to UL 1995 standard for heating and cooling equipment.• Blower and factory installed controls are prewired and tested. (Some field connections required)• Basic units are fabricated from angle iron, steel channel and reinforced 16 gauge (min.) galvanized sheet steel. (TA-15 and smaller use 18 gauge min.)• Stainless steel pitched drain pans for cooling coils.• All units are manufactured with controls, motor and blower drives enclosed within the unit.• Easy access, hinged and gasketed doors to allow servicing of unit components. • Control voltage transformer(s) (when required).• Non-Fused disconnect switch.• 1.15 Service factor ODP blower motor.• Adjustable motor base.• Blower motor starter & overload protection.• D.W.D.I. forward curved industrial type blower (s) with solid turned ground and polished shafting. • Self aligning ball bearings.• Variable pitch blower drive up to 30 HP.• Lifting provisions on all units.• Vertical units are built to accept slide - in filter sections. Integral 36" stand is also standard equipment on most unit sizes.• Vertical units have control panel serviceable from ground level.• G-90 Galvanized exterior.

MODEL DESIGNATION:Air Handler Models : TAH-AAA-BBB-CC-DD-EE-FFFAAA - is the largest steam, fluid or DX coil square feet. Any number between 1 and 300. If airhandler does not include a steam, fluid or DX coil, this designator will not appear.BBB - is blower quantity and wheel diameter and will typically be one of the following : 109, 112, 115, 118, 120, 122, 125, 127, 130, 133, 136, 139, 142, 148, 215, 218, 220, 222, 225, 227, 230, 233, 236, 239, 242, 248. CC - designates blower type. FC - Forward Curved, BI - Backward Inclined, BA - Backward Airfoil, PN - Plenum, PG - Plug, PR - Propeller, RA - Radial Blade, TA - Tube Axial, VA - Vane Axial. DD - can be CW - Chilled Water, DX - Direct Expansion Coil, HW - Hot Water Coil, ST - Steam Coil, EL - Electric Coil, EV - Evaporative Cooler, FP - Flat Plate Heat Recovery, RR - Rotary Energy Recovery. Multiple items may be designated in succession. EE - can be AR - Mixed outside air & recirculated air, OA - 100% outside air, RA - 100% recirculated air. FF - HRH, HRD, HRV, HLH, HLD, HLV, VRH, VRV, VDRH, VLH, VLV, VDLH.

rev. 01-04

Page 57: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DHYDRONIC, DX, AND ELEC. COIL UNITS

7-3

STEAM COIL UNITS:• Feature Jet Tube Distributing Coils with steam supply and condensate return connections on the same end of the coil. This tube within a tube construction offers superior freeze resistance.• Free Floating steam coil core.• Factory installed face & bypass dampers

available.• Integral face & bypass dampers available.

HOT WATER COIL UNITS:• Standard coils feature vents and drains.• Temperature controlled by modulating face and

bypass dampers (factory installed and tested )or modulating hot water valve.

• Integral face & bypass dampers available.

CHILLED WATER COIL UNITS:• Standard coils feature vents and drains.• Units available with humidity control capability

(reheat coil following cooling coil).• Stainless steel condensate drain pan.

DIRECT EXPANSION (DX) COIL UNITS:• Coils are counterflow circuited and equipped with pressure type distributors.• Stainless steel condensate drain pan.• Units available with humidity control capability

(reheat following cooling coil).• Evaporator coils available in normal, face, row,

or interlaced control coil circuiting.• Special coils available for ammonia refrigerant

systems.

ELECTRIC COIL UNITS:• Coil manufacturer supplied integral controls include: 1) Dual over temperature protection,

2) Over current protection, 3) Loss of airflow protection, 4) Contactors, 5) Door disconnect.• Coil watt density is properly matched with air velocity.• High grade nickel-chrome heating elements available upon request.• Electronic room or discharge temperature control of up to 8 stages is available.• SCR also available.

HeatedAir

FACE AND BYPASS DAMPER CONFIGURATION

Outside orMixed Air

SteamSupply

CondensateReturn

JET TUBE DISTRIBUTING COIL

EVAPORATOR COOLING COIL CIRCUITINGS

Single Circuit Row Control

Face Control Interlaced

Bypass

Face

rev. 01-04

Page 58: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

7-4

A I R I N C O R P O R A T E DHYDRONIC, DX, AND ELEC. COIL UNITS

SAMPLE DESIGN:Electric Coil Unit• 8000 CFM• 0.7 in. w.c. external static pressure. • 67 degree temperature rise (TR) w/ 8 stages controlled by electronic sequential controller.• Load Requirement: KW = CFM x TR / 3160 = 170 Manufacturer's coil rated at 174 KW.• Coil area (A): Recommended internal air velocity between 800 and 900 fpm. A ≤ CFM / 800 = 10 sq. ft. Select 9.5 sq. ft coil face.• Watt density: KW / sq. ft. face area = KW / A = 18.3 This watt density requires derated elements.• Coil Dimensions: 38" wide x 36" high with integral control panel (48" long x 36" high) mounted at right angle to coil.• Accessories: Customer requested an intake damper and outside air filter section. • Blower / motor selection: Based upon CFM and static pressure drop of coil, accessories, unit and external static, Lau Industries' selection program chose an A18-18A blower operating at 900 rpm with a 5 hp motor.

SAMPLE DESIGN:Steam Coil Unit• 30000 CFM• 0.375 in. w.c. external static pressure. • 70 degree temperature rise (TR) w/ face and bypass damper discharge temperature control. • Coil criteria: Jet Tube Distributing Coil. 1 row, 11 fins per inch. Based on TA-225 HRD width of 138"; Finned length = 128". Finned height = 39" Aluminum fins - .0075" thick. Copper Tubes - .020" wall thickness. Steam Pressure = 15#.• Heatcraft coil selection program selected model number 5JA1101C 39" X 128".• Face and bypass damper dimensions: Face damper height = total coil height of 42" (finned height + 3"). Face and bypass damper length = coil finned length of 128". Bypass damper height chosen to equate pressure drop (and airflow) in 100% bypass airflow with pressure drop in 100% face airflow.• Accessories: Customer requested an outside air filter section.• Blower / motor selection: Based upon CFM and static pressure drop of coil, accessories, unit and external static, Lau Industries' selection program chose two A25-25H blowers operating at 466 rpm with a 15 hp motor.

rev. 01-04

Page 59: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A252532324040484848607296728096120128144180180192216

C28283232464646464646464646464646464646464646

A252532324040484848607296728096120128144180180192216

C24322936323636464448647632364448566476767688

A30303737454553535365771017785101125133149185185197221

A I R I N C O R P O R A T E DINTAKE ACCESSORIES

All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. Intake dampers are designed to be mounted indoors, if outdoor mounting is required, you must order a weather hood for damper actuator(s), damper may be built into hood and or filter section. Intake dampers on TA-230 - 242 have 2 actuators, all accessories for these units are built in 2 sections, some field assembly may be required. All intake hoods feature bird screen. Mushroom hoods can be flange mounted, consult factory. 1" flange is typical for all components listed above. Intake accessories may be larger than intake opening. Return air filter sections will be larger than return air opening.

A

B

C

45° HOOD HOOD / FILTER COMBO

A

B

C

FULL TURN DOWN HOOD

A

B

C

8-1

B

A12”

DAMPERRA FILTER SECTION

A

B

C

rev. 01-04

MUSHROOM HOOD

B A

C

D

30”

Curb mounted

INTAKEDAMPER

MODELTA & TAM -109TA-109 ARTA & TAM -112TA-112 ARTA & TAM -115TA-115 ARTA & TAM -118TA-118 ARTA-120TA-122 & 125TA-127 & 130TA-133 & 136TA-215TA-218TA-220TA-225TA-227TA-230TA-233TA-236TA-239TA-242

45° INTAKEHOOD

FRESH AIRFILTER

SECTION

Item

HOOD /FILTERCOMBO

FULL TURNDOWN HOOD

MUSHROOMHOOD

(curb mounted)

OA FILTER SECTION

RETURN AIRFILTER

SECTION

B20282532283232424244607228324244526072727284

B20282532283232424244607228324244526072727284

B20282532283232424244607228324244526072727284

B20282532283232424244607228324244526072727284

A252532324040484848607296728096120128144180180192216

B20282532283232424244607228324244526072727284

C22302734303434444446586030344446545860606060

C4141494548454339676881nanananananananananana

D556366737377778797101135157737797101117135157157157195

C45454848505050505556657050505556606570707075

B25333037333737474749657733374749576577777789

A252532324040484848607296728096120128144180180192216

A252532324040484848607296728096120128144180180192216

B20282532283232424244607228324244526072727284

C28282828323232323232323232323232323232323232

A252532324040484848607296728096120128144180180192216

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 60: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DDISCHARGE ACCESSORIES

DAMPER2 WAY

DIFFUSER

A

B

C

3 WAYDIFFUSER

Item

A

B

CB A

C

4 WAYBOXDIFFUSER

Item - 2 WAY DIFFUSER

B

A12”

Item - DAMPER

Item - 3 WAY DIFFUSER

Item - 4 WAY BOX DIFFUSER

E

8-2

D

rev. 01-04

All dimensions subject to manufacturing tolerances and subject to change, verify with factory before using for any construction purposes. Discharge dampers are designed to be mounted indoors, if outdoor mounting is required, you must order a weather hood for damper actuator(s). Discharge dampers on TA-233 - 242 have 2 actuators, some field assembly may be required. Single blower, down discharge units can have a discharge damper built into unit (price add). Two way diffusers for TA-9 & 12 may be box type. 1" flange is typical for all components listed above. Discharge accessories may be larger than discharge opening.

E22243026303842505436364448545660606060

A16182420243236446056647290100108132132148168

B16182420243236444824243236424448484848

C10101212121818222212121518202224242428

MODELTA & TAM-109TA & TAM-112TA-115TAM-115TA & TAM-118TA-120TA-122 & 125TA-127 & 130TA-133 & 136TA-215TA-218TA-220TA-225TA-227TA-230TA-233TA-236TA-239TA-242

A16182420243236446056647290100108132132148168

B16182420243236444824243236424448484848

A16182420243236446056647290100108132132148168

B16182420243236444824243236424448484848

C17172222222426283026263030384444464646

C14141616162020202224242632343842424646

A16182420243236446056647290100108132132148168

B16182420243236444824243236424448484848

D222430263038425072687684102112120144144160180

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 61: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 62: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 63: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 64: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

A I R I N C O R P O R A T E DSERVICE PLATFORMS

8-6

*Standard VRH Units only require a service platform on the blower section, consult factory. Service platforms can also incorporate filter access on horizontal units, add 46” to “A” dim. (Filter section must be attached to AMU) Any INDOOR hanging units must utilize a bottom cradle (by others).

4"

A

42"Chain

Bolts to unit in field, attachment provisions provided, hardware by others.

ExpandedMetal Floor

50”

rev.01-04

A62696978859510011069788595100100118118132146

A62697278859510011069788595100100118118146156

AIR RECIRC.HRHA62696978859510012869788595100100128128132146

HRDMODELTA-109TA-112TA-115TA-118TA-120TA-122 & 125TA-127 & 130TA-133 & 136TA-215TA-218TA-220TA-225TA-227TA-230TA-233TA-236TA-239TA-242

Item A62697278859511412869788595100114128128146156

AIR MAKE-UPHRH HRD

MODELTA-109TA-112TA-115TA-118TA-120TA-122 & 125TA-127 & 130TA-133 & 136TA-215TA-218TA-220TA-225TA-227TA-230TA-233TA-236TA-239TA-242

Item

SUBMITTAL USE ONLY - DO NOT USE FOR CONSTRUCTION PURPOSES

PREL

IMIN

ARY

NO

T FO

R C

ON

STR

UC

TIO

N P

UR

POSE

S

Page 65: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

9-1

A I R I N C O R P O R A T E DSTANDARD TEMPERATURE CONTROLS

Titan Air offers control systems designed to optimize performance of our various direct-fired equipment configurations. These systems vary from simple temperature control for a constant volume air make-up unit to “network-ready” DDC controllers for more adaptable equipment such as variable air volume or recirculating units. Furthermore, all control systems can be customized for an application.

The controls catalog section is divided into 4 segments. 1. STANDARD TEMPERATURE CONTROLS2. STANDARD AIRFLOW CONTROLS3. SELECTED APPLICATION-SPECIFIC CONTROL SYSTEM MODIFICATIONS4. STANDARD TEMP. CONTROLS BASED ON UNIT TYPE & AIRFLOW CONTROLS

Discharge Air Temperature Controls: Tempering make-up air is typically accomplished with a modulating discharge air temperature controller. Gas flow to the burner is modulated to achieve the selected discharge air temperature setpoint. Discharge air temperature controls are typically utilized on units designed to replace exhausted air with tempered outside air. These units can be either constant volume, two speed, or variable air volume. A discharge air temperature sensor that varies its resistance based on airstream temperature is typically utilized. Refer to table at the end of this section for standard controllers available.

Room Override Thermostat w/ Discharge Air Temperature Controls: Operation is similar to discharge air temperature control (above) with a room temperature thermostat added. If room temperature falls

below the setpoint of the room thermostat, the discharge air temperature controller setpoint is automatically increased. Refer to table in this section for standard controllers available. Room Temperature Controls: Room temperature control of a direct-fired unit is a “cascade control” system where discharge temperature is automatically adjusted between a minimum and maximum value based on room temperature. As room temperature decreases below its setpoint, the discharge temperature setpoint is automatically increased by the controller. The opposite applies as the room temperature increases. A small change in room temperature produces a large change in the discharge temperature setpoint. Minimum and maximum discharge temperature setpoints minimize stratification from floor to ceiling. Room temperature controls are typically utilized for industrial heating and ventilating applications on AR/80™ or AR/75™ units featuring air recirculation capability. Refer to table at the end of this section for standard controllers available.

1 2 3 4 5 6 7 8

Power/Status

Model No. DFC-3

- +

RTCSolutions

ADJUST

CO

LD

HO

T

Page 66: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

9-2

A I R I N C O R P O R A T E DSTANDARD AIR FLOW CONTROLS

DEMAND-AIR™ Variable Air Volume: DEMAND-AIR™ units are capable of varying outside air volume between a unit’s rated CFM and 30% of rated CFM. A variable frequency drive (VFD) varies supply fan speed. Fan speed is typically controlled based on building relative pressure. In a building with variable exhaust volumes, relative pressure in the building will drop as additional exhaust fans start. VFD output frequency increases to bring building relative pressure back up to an adjustable setpoint. Most applications utilize positive pressure setpoints to realize the benefits of controlled building pressurization. Titan Air introduced the first ETL listed variable air volume direct-fired make-up air units. Through continuous product improvement practices, DEMAND-AIR™ units remain the benchmark of direct-fired VAV systems. AR/80™ or AR/75™ Outside Air (OA)/Return Air Percentage (RA) Control: Titan Air offers direct-fired recirculating industrial heating and ventilating units certified to recently revised ANSI Standard Z83.18. Two versions of these units are available with either 80% maximum recirculated air (AR/80™) or 75% maximum recirculated air (AR/75™). Typical OA/RA percentage control applications involve:

1. Building pressure control, 2. Two position control, 3. Manual rotary dial control, 4. Humidity control.

Titan Air employs a unique control scheme that modulates recirculated air volume based on outside air pressure drop across the burner profile. This keeps minimum OA percentage at

rated value when field installed ductwork and filter conditions vary from design conditions. Maintaining rated minimum OA percentage maximizes operational cost savings and improves indoor air quality.

Occupied and unoccupied operation modes are often added to AR systems. A time clock sets occupied/unoccupied periods. In the occupied mode, the blower operates continuously with space temperature controlled by modulating supply air temperature. In the unoccupied mode, the unit is typically off and only cycles on if space temperature falls below a separate unoccupied temperature setpoint. OA volume is forced to minimum in the unoccupied mode.

ANSI Z83.18 requires control practices that prevent build-up of space effluent levels. AR/80™ systems accomplish this by limiting maximum gas flow as the OA percentage decreases towards a minimum of 20%. AR/80™ systems perform well in all applications where recirculation of room air is practical and should always be selected for facilities with periods when minimum OA is required. AR/75™ units are intended for applications with ventilation requirements that will almost always force higher OA percentages. AR/75™ units on facilities where space temperature will occasionally be controlled at less than 59°F need a temperature controller that does not force a higher OA percentage due to low space temperature.

Page 67: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

9-3

A I R I N C O R P O R A T E D

SPECIFIC CONTROL SYSTEM MODIFICATIONS

Titan Air provides value-added modifications to standard control packages by incorporating custom control components in a factory packaged and tested assembly to meet virtually any control sequence. Examples of control systems customized for an application are presented below.

Enclosed Parking Garage Ventilation: A packaged control system for enclosed parking garage ventilation is available. In addition to standard discharge air temperature control of a constant volume AMU, the following optional components are typically included:

1. Space CO detectors to start the AMU ifspace CO concentration rises.

2. Inlet ductstat automatically enablesburner operation based on OA temp. (delete Summer-Off-Winter switch).

3. Timer or mechanical “pin-type” time clockto operate unit for 15 minutes per hour.

Some parking garage applications utilize two speed or variable air volume units so that exhaust zones can be controlled independently. Local code requirements may vary.

Demand-Air™ w/ Multiple Exhaust Fan Interlock Speed Control: Facilities that do not lend themselves well to controlled building pressurization can benefit from automatic control of supply volume with this modified control system. Installation technicians enter the exhaust volume percentage for each exhaust fan on a password protected digital interface screen. The programmable controller calculates current total exhaust volume by adding entered percentages for each operating exhaust fan (as determined from dry contact closures). Supply VFD speed is set to match total exhaust volume. Up to five exhaust fans can be interlocked with the standard programmable controller. Interlocking supply VFD speed with more than five exhaust volumes requires expanded controller input capacity.

Space Relative Humidity Control for Metal Storage Facilities: Relative humidity levels in metal storage facilities must be kept down to limit corrosion. A space humidistat can be added to an AR/80™ unit to enable burner operation and override discharge temperature setpoint when humidity rises.

Waste Water Treatment Plants: Corrosive and potentially hazardous areas within waste water treatment plants are often served by outdoor mounted air make-up units with explosion proof thermostats providing unoccupied start and room temperature override functions. A lighting circuit interlock establishes occupied mode operation. Low leak discharge dampers with coated non-ferrous blades provide a quality seal between the unit cabinet and corrosive building air. Supply fan can be started prior to opening the discharge damper. Airflow switches and pre-purge in unit ensure safe ignition.

Indoor Swimming Pool Enclosure Ventilation: AR/80™ Industrial Heating and Ventilating units customized for indoor swimming pool enclosure ventilation in northern climates is a common application. See separate catalog section.

Supply Air Relative Humidity or Dewpoint Control for Process Applications: Industrial finishing operations and laboratory environments are common applications for equipment capable of controlling supply air temperature and moisture content. Heating, cooling, humidification and dehumidification components are selected based upon local weather extremes and custom controls are utilized to condition outside air to specified supply air conditions.

Paint Booth Spray/Bake System: Non-recirculating two speed or recirculating single speed H.O.T. ™ units are available with packaged controls to provide: 1. Booth pressure control via exhaust VFD2. Purge/bake/cool timers & temp. setpoints3. Lighting contactor4. Compressed air solenoid enable logic5. Enhanced diagnostics to minimize downtime.See separate catalog section on H.O.T.™ units.

Page 68: AIR MAKE - UP INDUSTRIAL HEATING · PDF fileAIR MAKE - UP & INDUSTRIAL HEATING EQUIPMENT Proveedora Termica del Norte, S.A. de C.V. Nardo 911 ote. Col. Cementos, Monterrey Nuevo Leon,

9-4

A I R I N C O R P O R A T E D

STANDARD TEMPERATURE CONTROLS BASED ON UNIT TYPE AND OA VOLUME CONTROLS

100% OA

AMU

Two Speed AMU

Demand-Air

VAV AMU

AR/80 Recirc.

Ind. Heat & Vent

AR/75 ³ Recirc.

Ind. Heat & Vent

None Discharge 1, 3, 5, 8 na na na naNone Disch. w/ Ovrd. 2, 4, 6, 8 na na na naNone Room 7, 9, 12 na na na na

100% OA or 50% OA¹ Discharge na 1, 3, 5, 8 na na na100% OA or 50% OA¹ Disch. w/ Ovrd. na 2, 4, 6, 8 na na na100% OA or 50% OA¹ Room na 7, 9, 12 na na na

OA VAV-Building Pressure Control Disch. w/ Ovrd. na na 8 na naOA VAV-Building Pressure Control Room na na 9 na na

OA VAV-VFD Speed Control by Others Disch. w/ Ovrd. na na 8 na naOA VAV-VFD Speed Control by Others Room na na 9 na naOA VAV-Manual VFD Speed Control Disch. w/ Ovrd. na na 8 na naOA VAV-Manual VFD Speed Control Room na na 9 na naOA/RA % Control-Building Pressure Discharge na na na 8, 10 5OA/RA % Control-Building Pressure Disch. w/ Ovrd. na na na 8 6OA/RA % Control-Building Pressure Room na na na 9, 11 7, 12

OA/RA % Control-Manual Rotary Dial Discharge na na na 8, 10 5OA/RA % Control-Manual Rotary Dial Disch. w/ Ovrd. na na na 8 6OA/RA % Control-Manual Rotary Dial Room na na na 9, 11 7, 12

OA/RA % Control-Two Position¹ Discharge na na na 8, 10 5OA/RA % Control-Two Position¹ Disch. w/ Ovrd. na na na 8 6OA/RA % Control-Two Position¹ Room na na na 9, 11 7, 12

OA/RA % Control-By Others² Discharge na na na 8, 10 5OA/RA % Control-By Others² Disch. w/ Ovrd. na na na 8 6OA/RA % Control-By Others² Room na na na 9, 11 7, 12

OA/RA % Fixed at Minimum OA Discharge na na na 8, 10 5OA/RA % Fixed at Minimum OA Disch. w/ Ovrd. na na na 8 6OA/RA % Fixed at Minimum OA Room na na na 9, 11 7

Small italic numerals represent non-typical room control w/ 100% OA.

4. Maxitrol Series 14 w/ Room Override Stat & Maxitrol Modulator/Regulator Valve3. Maxitrol Series 14 & Maxitrol Modulator/Regulator Valve2. RTC DFC-3 w/ Room Override Stat & Eclipse Butterfly Valve - Belimo Actuator (standard for TAM series)

7. JCI FX-05 w/ Configured for Room Control & Eclipse Butterfly Valve - Belimo Actuator

1. RTC DFC-3 & Eclipse Butterfly Valve - Belimo Actuator (standard for TAM series)Typical Controller List 11/01/2003 (other controllers available)

5. JCI FX-05 Configured for Disch. Control & Eclipse Butterfly Valve - Belimo Actuator6. JCI FX-05 Configured for Disch. Control w/ Room Override Stat & Eclipse Butterfly Valve - Belimo Actuator

² Actuator by Titan Air for position feedback on AR/80 or to force higher OA % on AR/75 if space temp. drops.

UNIT TYPE

TEMP. CONTROLS

OA VOLUME CONTROLS

Footnotes:¹ Specify event that signals OA volume change.

H.O.T. units excluded from this table.

12. Maxitrol Series 44F & Maxitrol Modulator/Regulator Valve

8. JCI FX-10 / MUI Disch. Control (Room Override Selectable) & Eclipse Butterfly Valve - Belimo Actuator9. JCI FX-10 / MUI Configured for Room Control & Eclipse Butterfly Valve - Belimo Actuator10. Maxitrol Series DFM14 & Maxitrol Modulator/Regulator Valve11. Maxitrol Series DFM44 & Maxitrol Modulator/Regulator Valve

³ AR/75 forces higher OA % if space temp. < 59°F unless equipped with controls to calculate max. disch. temp. (i.e. FX-05).