7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 1/19
Air Mixing Handbook
How to Identify and Eliminate Air Stratification Problemswith Properly Designed HVAC Mixing Systems
Published by Blender Products, Inc.
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 2/19
Section Page
1. Introduction ..............................................................2The Company ............................................................2
Why this Manual Was Written...................................2
2. Glossary of Basic Terminology ................................3
3. Discussion of Stratification and Mixing..................4
How Stratification Develops .....................................4
How to Define Mixing Effectiveness ........................4
4. Thermal-Stratification Problems and Solutions .....5
Nuisance Freeze-Stat Trips........................................5
Poor Mixed-Air Control ............................................5
Wasted Energy Due to Sensor Error..........................5
Averaging-Bulb Inaccuracy.......................................5Poor Economizer Control ..........................................7
Excessive Reheat Coil Use........................................7
Stratification Downstream of Face-and-Bypass
Sections .................................................................7
Ineffective Refrigeration-Coil Control ......................8
Stratified Steam-Coil Discharge................................8
Uneven Heating with Direct-Fired Burners ..............8
Uneven Moisture Absorption Across Humidifiers ....8
Improper Filter Loading ............................................8
5. Water-Coil Freeze-Up Problems and Solutions ......9
Glycol Solutions........................................................9
Unit Heaters in Mixed-Air Plenum ...........................9Heat Recovery ...........................................................9
Draining Water Coils ...............................................10
Pumping Fluid at Subfreezing Outside
Air Temperatures.................................................10
Static Mixing Devices .............................................10
Section Page
6. Indoor Air Quality (IAQ) Concerns.......................11Outside Air Dampers Blocked Shut to Eliminate
Stratification Problems........................................11
Dilution of Fresh Ventilation Air Into the
Supply-Air Stream...............................................11
Maintaining Minimum Ventilation Air Under
VAV Conditions...................................................11
7. Application Guidelines for Static Mixing
Devices ....................................................................12
How Much Mixing is Enough? ...............................12
VAV Concerns .........................................................12
Proper Placement of Mixers in HVAC Systems.....12
Effect of a Combination Filter/Mixing Box onMixing Performance............................................14
8. Velocity-Stratification Problems.............................15
Coil Condensate Carryover .....................................15
Coil Inefficiency......................................................15
Filter Loading, Damage, and Particle Bypass .........15
9. Application Guidelines for Velocity-Equalizing
Diffusers..................................................................16
Distance Requirements............................................16
System-Effect Considerations .................................16
Bibliography.................................................................17
1
Table of Contents
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 3/19
The Company
Since 1962, Blender Products, Inc. (formerly known
as RM Products) has pioneered stratification
abatement developments in air-handler mixing
plenums and has been an innovator in the design of
static mixers.
Over the years, the applications personnel at Blender
Products have developed mixing systems for
thousands of applications in HVAC systems and
industrial process systems. As a result, they have
accumulated a large storehouse of knowledge and
valuable expertise in the disciplines of stratification
and static mixing.
Why This Manual Was Written
During its history, Blender Products has published a
great deal of material dealing with stratification and
mixing in HVAC systems. This material has appeared
primarily in technical bulletins, catalogs and articles.
To date, very little about stratification in the HVAC
environment has appeared in textbooks or journals.
Now, due to increased interest in adding ventilation
air to combat IAQ problems, there is an increasing
need to solve the associated stratification problems.
To help meet this demand, Blender Products has
compiled a significant body of technical information
and outside source articles into a single manual. This
manual will prove to be an invaluable resource in the
design and troubleshooting of stratification systems.
Although this reference is a relatively complete text
in itself, a comprehensive study of stratification
would, of necessity, include an investigation of the
references listed in the bibliography.
2
Introduction1
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 4/19
Average Temperature (tavg): The average of the
downstream temperatures. It is found using the
following equation:
t avg= 1
n •
Blow Through System: Usually refers to a system
where the filter or coil is installed downstream of the
supply fan. Therefore the fan is “blowing” through
the coil or filter.
Combination Mixing/Filter Box: A factory-made
section that includes filters within the mixing box.
Economizer System: An air-side economizer systemuses the outside air for “free” cooling during times
when the outside air conditions permit.
Freeze Stat: A low-limit thermostat used to protect
hydronic coils from freezing by activating freeze
protection sequences, such as air-handler shut down,
in the air-handler control system.
Inlet Temperature Difference (dT): The difference
in the temperatures between the two incoming air
streams. It is found using the following equation:
dT = t Hot – t Cold
Mass Flow Rate (m): The mass flow rate of an air
stream. It is found using the following equation:
m = ρ • A • v
Mixing Box: A factory-made section that includes
control dampers and may include one or more static
air mixers.
Mixing Effectiveness: A means of quantifying
mixing in terms of “Range” or “Standard Deviation”
reduction across a static mixing device or other
mixing system (see section 3).
Mixing Section: A factory-made enclosure, which
includes one or more static air mixers, that is designed
to be mounted between sections of an air handling unitand is supplied separately from the mixing box.
Mixing System: The entire mixing system consisting
of the mixing/control dampers and any other mixing
devices such as air mixers.
Modified Range Mixing Effectiveness (ERdT): The
absolute amount, expressed as a percentage, that a
mixing box or static air mixer reduces the temperature
spread entering the mixing device. It is typically used
in determining the freeze protection afforded by a
mixing system. See Section 3, page 4.
Range: The maximum temperature less the minimum
temperature for a set of readings.
Range = (T max – T min)Standard Deviation: A statistical calculation applied
to a set of data. In essence it is an average variation
from the average data point. For thermal mixing
analysis the expression is as follows:
SD =1
n – 1
Static mixing device: A mixing device fixed in
position generally consisting of baffles and blades
arranged to induce mixing to a flow of water or air.
Temperature Averaging Bulb: A control sensor
designed to read the average temperature across a
plenum by using a capillary tube or a special
averaging wire approximately 15 to 25 feet long.
Theoretical Mixed Air Temperature: The mixed air
temperature based on a calculation of the combined
mass flow of two air streams. The theoretical mixedair temperature is found using the following equation:
T mix =
Where:mhot = Hot air mass flow (lbs/min)mcold = Cold air mass flowT hot = Hot air temperature (degrees F)T cold = Cold air temperature
3
Glossary of Basic Terminology
∑i=1
n
t i
Where:n = number of temperature readingst i = Individual temperature readings
Where:t Hot = Temperature of hot air
t Cold = Temperature of cold air
Where:ρ = Air density (lbs/ft 3)
A = Area of duct (ft 2)v = Velocity of air stream (ft/min)
∑i=1
n
(T i - T m)2][
.5 Where:
n = Number of samplesT m = Average temperature
T i = Temperature measurement
SD= Standard deviation
mhot • T hot + mcold • T cold
mhot + mcold
2
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 5/194
How Stratification Develops
Stratification is normally thought of in terms of
vertical temperature gradients. However, stratificationwithin an air handler is different. Momentum in the
entering air streams as well as the combined flow
serves to hold the uneven profile of temperatures or
constituents as they are introduced into the combined
flow (see Figure 5, page 8).
One typical misconception about mixing box design
is the idea that cold air introduced high will drop due
to density difference and mix with the warmer air
below. In reality, the momentum of the main air
stream is typically so much greater than the force due
to the density difference that the cold air introducedon top is simply carried downstream before it has
time to drop. In short, any potential mixing action
due to buoyancy forces are far less than the
momentum of the stratified air stream.
The primary conditions which produce stratification
in an air handler are as follows: The mixing-box layout and damper size, relative
to the total plenum, greatly affect the degree of
stratification for a given mixing system. As the opposing air streams approach a 50/50
proportion, the mixing becomes more difficult. Most importantly, as the temperature differential
between the two streams increases, the range of
downstream air temperatures widens.
Stratification is relatively easy to develop, however
mixing two air streams together is neither automatic
nor easy. Without some form of agitation or mixing
a stratified air stream can continue many duct
diameters downstream.
How to Define Mixing Effectiveness
In the absence of independently established standards
that define how effectively a mixing system is
performing, many “rule-of-thumb” standards have
been used. At a minimum, the HVAC mixing system
should mix two air temperatures sufficiently to
eliminate freeze-stat trips and frozen coils, thus at
least ensuring continued operation of the air handler.
A more stringent performance standard defines how
close the mixed-air temperature range approaches the
actual, or theoretical, mixed-air temperature in the
mixed-air plenum. The latter is important to the proper
functioning of mixed-air thermostats and controls.To simply state that a mixing system should provide
a set range of temperatures for all entering air-stream
conditions fails to recognize the variables mentioned
above. This manual recommends using the “Mixing
Effectiveness” method of rating static mixing systems.
This method takes the entering temperature
differential into account when rating a particular
mixing system. The equation is as follows:
E RdT = 1–
Furthermore, it is important to state the mixing
effectiveness required in relation to various outside
air ratios and temperatures. An example of the
characteristic curve of required mixing effectiveness
as a function of percent outside air for various mixed
air temperatures is shown in Figure 1.
Note: Chart based on the following conditions:
TRA = 75°F, TFZ = 37° F TOA = Outside air temperature
Figure 1 – Required mixing effectiveness vs. percent outsideair for various temperatures to eliminate freeze-stat tripswhen freeze-stat is set at T FZ = 37°F.
Discussion Of Stratification And Mixing
Range DS
dT ( )
Percent Outside Air (By Mass)
0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75
6 0
° F
5 5
° F
5 0
° F
T M i x = 4 5
° F
3 0 ° F
2 5 ° F
2 0 ° F
1 5 ° F
1 0 ° F
5 ° F 0 °
F
R e
q u i r e d M i x i n g E f f e c t i v e n e s s ( E R d T )
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
1.00
T OA = 3 5 ° F
3
Where: E RdT = Mixing effectiveness based onrange
Range DS = Maximum temperaturedifference at testing grid (°F,°C)dT = Temperature difference betweenreturn and outside air streams (°F,°C)
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 6/195
Nuisance Freeze-Stat TripsThe low-level thermostat, also called a freeze stat,
is designed with a long element that will trip if any
portion of the element is exposed to a temperature
below the set point. The set point is typically between
35 and 38 degrees F. Although the coil protection
provided by a low-limit thermostat is often beneficial,
the continuous trip out and resulting air-handler shut
down can be a headache for the building facilities
people.
Whenever a “nuisance” trip of the freeze-stat occurs
the building facilities staff gets the job of modifying
the system to eliminate the pesky problem. Often, in
an attempt to solve the problem, the outside air
dampers are wired shut or otherwise disabled to
eliminate cold, outside air altogether. Obviously, this
so-called solution will not allow the proper amount of
ventilation air into the building. Major problems with
the indoor air quality will result (see section 6). The
other common method of eliminating the problem is
to disable or move the freeze-stat. This “solution”
can, of course, meet with catastrophic results should
a freezing condition occur.
Poor Mixed-Air Control
In the past, HVAC mixing applications did not
demand strict performance requirements. As long as
the air-handling unit did not shut down, or a water coil
did not freeze due to stratification, the mixing was
assumed to be satisfactory. However, with the advent
of DDC and as control systems become more precise,
the problems of an improper sensor read become more
pronounced. The root cause of sensor error can often
be traced to a stratification problem in the mixed airplenum1. The following sections address some of the
problems created by temperature stratification in the
control system of a typical HVAC installation.
Wasted Energy Due to Sensor ErrorSubstantial energy is wasted by undetected errors
originating at the mixed-air temperature sensor.
The most common cause for error is temperature
stratification within the mixing plenum2. This
potential error has been accentuated by the use of
single-point electronic temperature sensors in large
mixing plenums. It is very difficult to place a single
temperature sensor in a position where it will read
the average temperature of the ever-changing
temperature profile downstream of mixing dampers.
Another source of error is a thermostat that is outof calibration.
Averaging-Bulb Inaccuracy
A common solution to the stratification problem
has been to place an averaging style temperature
sensor on the face of the filter or coil downstream
of the mixing plenum. This solution has some merit,
provided the sensor capillary or wire is properly
mounted so that it will record a representative
sampling of temperatures. However, taking only
the temperature value at a series of points ignores
the effect of varying velocity or mass flow across
the sample area. In the ASHRAE Fundamentals
Handbook, Chapter 13, titled Measurements and
Instruments3, the Sampling and Averaging section
warns against assuming that a sampling of
temperatures accurately represents the average
temperature at a cross-section of a flowing stream.
The Section goes on to suggest that a weighted
mass-flow average be taken across the stream to
determine the true temperature of the air stream.
In an effort to show the potential error for an
averaging-bulb sensor applied to a mixing box
with a non-uniform velocity profile, a study was
performed at Blender Products. A 25-foot capillary-
Thermal-Stratification Problems andSolutions
1 Co gg an, Dona ld, P.E., “Mixed Air Control with DDC, ” He a ting/P iping/Air Co nditioning, Ma y 1986.
2 Kato, J ame s Y. “S enso r Errors,” AHSRAE Journal , Volume 27, No. 1, America n S oc ity of Hea ting, Refrigera tion and Air Co nditioning
Engineers, Inc., Atlanta , Ge orgia – J anua ry, 1985.
3ASHRAE Fundamentals Handbook, 1985 – Chapte r 13, “Mea surements a nd Instruments,” America n S ociety of Hea ting, Refrige ration a nd
Air Conditioning Engineers, Inc., Atlanta, Georgia – 1985.
4
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 7/196
tube averaging-bulb sensor was mounted to a test
grid as shown on the test setup drawing. Individual
temperature and velocity readings were taken at 25
points across the grid, providing data to calculate the
weighted mass average using the following equation4:
Equation 1a Equation 1bMass Flow Based Simplified Velocity Based
T mix = miT i T mix =
Where: Where:T mix = Mixed air temperature T mix = Mixed air temperature
mt = Total mass flow (lbs/min) T i = Individual temperature
mi = Mass flow in partial areas V i = Individual velocity
T i = Individual temperature sample in equal areas
n = Number of readings
The first test was run for a standard mixing box.
A second test was run with a static mixer installed as
shown in Figure 2. The results are shown in Table I.
Figure 2 – Test setup to determine error in an averaging-
bulb sensor.
In these tests, the averaging bulb was placed in
12 different paths. From Table II (see page 7), it
can be seen that some paths were more accurate
than others. Overall, the error was greatest when
the velocity profile across the bulb was non-uniform.
The study clearly demonstrated that non-uniform
velocity across an averaging bulb will cause the
mixed-air sensor to falsely represent the mixed-air
temperature. In short, an averaging bulb can only
sense the temperature. It cannot sense the mass flow
across a section. Therefore, it is important to mix
the air-stream temperatures and diffuse the velocity
evenly across an averaging bulb to provide the most
accurate temperature reading.
Averaging-Bulb Test Results
Temperature and Velocity Traverse Without Air Blender Units
F° 90.8 103.5 109.2 100.1 87.1 77.2
FPM 125 50 50 38 50 162F° 86.7 104.0 105 90.4 86.5 78.4
FPM 125 150 200 125 250 500
F° 79.4 84.9 86.1 82.2 77.3 75.4FPM 650 600 475 675 625 925
F° 69.3 71.1 71.2 73.2 72.7 69.4FPM 900 1000 975 1200 1050 1075
To ta l Flo w = 12,500 C FM Ta vg = 84.6° F
THo t = 133° F Tmix = 76.9° F
TCold = 68° F Error = Ta vg - Tmix = 7.7°F
DT= (TH-TC) = 65° F
Temperature and Velocity Traverse With Air Blender Units
F° 90.7 89.8 81.5 83.3 91.3 91.1FPM 475 525 500 650 575 525
F° 91.7 92.9 84.3 80.6 95.0 89.2FPM 450 375 525 575 400 450
F° 102.7 93.2 84.7 81.8 88.1 89.5FPM 500 300 500 525 300 300
F° 83.6 83.3 75.6 75.4 79.3 75.2
FPM 425 400 350 325 350 425
To ta l Flo w = 12,500 C FM Ta vg = 86.6° F
THo t = 139° F Tmix = 86.5° F
TCold = 68° F Error = Ta vg - Tmix = 0.1°FDT= (TH-TC) = 71° F
Tavg = Arithmetic avera ge tem perature ba se d on multipoint
or averag ing b ulb sens or.
Tmix = Velocity weighted mixed air temperature ba sed on
equations 1a and 1b as show n above.
Table I – Averaging-bulb test results.
4ASHRAE Standard, 41.1-1986 “S tand ard Method for Temperature Meas urement,” America n S ociety o f Hea ting, Refrige ration a nd
Air Conditioning Engineers, Inc., Atlanta, Georgia – 1987.
Return Air Da mpers
Pa tented Air Blender
TestSensorGrid
Outside AirDampers
36"
∑i=1
n
1mt
∑i=1
n
T iV i
∑i=1
n
V i
®
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 8/197
Path1
No Mixer With Static Mixer
Tavg Tmix Error Tavg Tmix Error
1 88.10 76.90 11.20 85.50 86.50 -1.00
2 82.40 76.90 5.50 88.00 86.50 1.503 90.10 76.90 13.20 84.30 86.50 -2.20
4 87.30 76.90 10.40 87.80 86.50 1.30
5 87.30 76.90 10.40 83.50 86.50 -3.00
6 80.20 76.90 3.30 85.80 86.50 -0.70
7 91.80 76.90 14.90 89.90 86.50 3.40
8 80.90 76.90 4.00 90.00 86.50 3.50
9 88.40 76.90 11.50 88.90 86.50 2.40
10 84.30 76.90 7.40 90.90 86.50 4.40
11 87.80 76.90 10.90 89.40 86.50 2.90
12 82.70 76.90 5.80 84.10 86.50 -2.40
Average Error 9.04 0.84
1 The 12 pa ths use d a re represe ntative of paths used in a
typica l system.
2 Error is d etermined b y using this eq uation: Error= Tavg -Tmix
Table 2 – Error comparison with and without static mixer.
Poor Economizer Control
Generally, an air-side economizer offers free cooling
when outside air temperatures fall below 50 degrees F,provided the dew-point temperature is low enough.
Most economizers operate well down to about
35 degrees F. However, as the outside air temperature
approaches freezing, the freeze stat is likely to trip.
When this happens, the economizer is often abandoned
in the interest of keeping the unit operational. In the
absence of free cooling, the mechanical cooling
system is often used. This not only wastes energy, it
also robs the building of fresh air during sub-freezing
temperatures. A properly operating mixing system
extends the economizer operation time.
Economizer systems may also be abandoned for
ineffective operation as the outside air temperature
approaches the mixed-air set point. The problem often
stems from a leaky return-air damper. Leaking return-
air dampers can allow up to 15% of the warmer return
air into the mixing plenum, thereby causing the
mixed-air temperature to rise 5 degrees F or more.
For an economizer to function properly, it is important
to squeeze as much free cooling from the outside air
by using only cool air and exhausting all the return air.
For instance if the return-air damper leaks 12% into
the mixing plenum, the mixed air will be 55 degrees F
when the outside air is only 51 degrees F. This
effectively shuts down the economizer cycle at 51
degrees, or 4 degrees higher than necessary. In a citylike Omaha, this premature shut-down results in a loss
of 580 hours of potential free cooling. It also causes
earlier start-up of mechanical cooling equipment.
In order to keep economizers operating at maximum
efficiency, mixing systems must have tight seals on
both outside- and return-air dampers to insure positive
shut-off of either air stream.
Excessive Reheat Coil Use
Reheat coils are routinely used to heat the airdownstream of the mixed-air plenum. Often these
coils are controlled by an outside-air sensor and
will run continuously at subfreezing temperatures.
Obviously, this wastes large amounts of energy.
Additionally, if the heating-coil valve cannot be
turned down sufficiently, the cooling-coil valve may
open, or outside air may be introduced, wasting
additional energy.
Stratification Downstream of
Face-and-Bypass SectionsFace-and-bypass sections provide a good way to
control temperature and humidity in the air handling
system. However, control of the discharge temperature
downstream of a face-and-bypass coil is difficult
when the bypass air is located at the top or bottom of
the coil. A means of mixing the two air streams should
be incorporated to assure proper control of the damper
modulation, as shown in Figure 3.
Figure 3 – Internal face-and-bypass with Air Blender static
mixer to mix bypass air with coil discharge air, or to diffuse
bypass air across a plenum.
2 2
Coil
Bypass
AirFlow
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 9/19
Ineffective Refrigeration-Coil Control
A staggered DX refrigeration coil-array will often
create stratified temperatures downstream, making
it difficult for the discharge thermostat to sense the
average temperature. A high reading will cause the
compressor to operate excessively and can lead to acoil condensate freeze-up. A cold reading will result
in unnecessarily high supply-air temperatures and
resulting loss of the cooling load. Furthermore, the
resulting stratified air streams will often persist into
and through a tee fitting downstream resulting in
cooler air flowing down one duct and warmer air
flowing down the other duct. This condition creates
significant control and comfort problems.
Stratified Steam-Coil Discharge
Steam coils often result in a 20 to 50 degrees Fstratification. This stratified state creates problems
when a single downstream sensor is used to control
the coil valve. Control hunting is the usual result. The
addition of a static mixing device downstream has
proven effective in providing more precise steam-coil
control. In addition, it results in more homogenous
temperatures across processes downstream.
Uneven Heating with Direct-FiredBurners
The temperatures downstream of a direct-fired burner,
which combines hot combustion gases with the air to
be heated (Figure 4), are highly stratified. The air
stream requires some form of mixing to ensure homo-
geneous temperatures at the controlling temperature
sensor, as well as for any process downstream. Static
mixers are ideal choices for these applications. They
have been used with much success on many projects.
Figure 4 – Direct-fired burner with Air Blender device to
mix air with products of combustion.
Uneven Moisture Absorption AcrossHumidifiers
Temperature stratification can create problems with all
plenum-mounted humidification systems. Normally,
the cooler the air stream the longer the vapor travel
downstream as shown in Figure 5. This conditionmay cause problems such as air-filter saturation or
condensation on turning vanes or duct walls. The
best solution is to insure that the temperature of the
air stream is homogeneous and sufficient to absorb
the moisture.
Figure 5 – Extended vapor travel in a stratified plenum.
Improper Filter Loading
A potential problem with stratified air streams in themixing plenum is uneven filter loading. This occurs
when one air stream has a greater particulate
concentration than another. An example would be
a street-level outside air intake that would introduce
larger amounts of particulate than the indoor air
stream. If the outside air stream is not adequately
mixed with the return air stream, the filter will have
a higher concentration of outside air particulate in
one localized area. This uneven loading may cause
excessive velocities across the balance of the filter
face, which will result in inconsistent velocity acrossthe downstream coil. To insure proper filter loading,
some form of mixing device should be used ahead of
the filter.
8
Air
Flow
Flame
TOA
Cold
Hot TRA
Extend ed Vap or Travel in
Cold Area of P lenum
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 10/199
The most troublesome problem arising from
stratification is hydronic-coil freeze-up. If the air
handler is running and the mixing-damper-control
sequence is operational when the coil freezes, the
freeze-up is most likely due to thermal stratification.
In addition to a functioning low-limit freeze stat,
there are a number of ways to protect coils from
freezing. This section will explore the various options
to provide coil-freeze-up protection.
Glycol Solutions
Mixtures of ethylene or propylene glycol with water
are often used to protect hydronic coils during
subfreezing weather conditions. The advantage of
glycol solutions is their ability to protect all
components under any situation. For example, if the
Figure 6 – Effects of various concentrations of ethylene
glycol.
power shuts down, and the outside air damper staysopen, the glycol mixture will protect the coil and
associated piping. However, there are a number of
disadvantages of using glycol as a freeze-protection
additive. The higher viscosity requires increased
pump horsepower. In addition, the lower specific heat
constant inhibits heat transfer, which requires higher
water flow and/or larger heat-transfer surfaces. It is
also important to point out that some provision for
volume expansion must be included to protect the
heat exchangers in the system. Figure 6 shows coil
derating as ethylene glycol concentration is increased.
Unit Heaters in Mixed-Air Plenum
Unit heaters are sometimes placed in mixing plenums,
as shown in Figure 7, in an attempt to maintain a
minimum mixed-air temperature and thus protect
against coil freeze up or freeze-stat trips. Although a
unit heater may be a reasonable way to heat the mixed
air plenum during air-handler shut down, it is largely
ineffective when the air handler is operational. Theprimary reason for this failure is inherent in the unit-
heater design. They are designed to heat a relatively
static air space. However, a mixed-air plenum has air
flowing at 400 to 500 FPM. This leaves little time for
the unit heater to turbulate the air stream. Furthermore,
any heat introduced into the air stream serves only to
create more stratification downstream, thus creating
problems for mixed-air sensors, freeze stats, and coils.
The only reasonable use for unit heaters in mixed-air
plenums is during air handler shut-down to protect
water coils from cold outside-air migration through
leaky outside-air dampers, as shown in Figure 8.
Figure 7 – Typical unit heater in plenum configuration,
without Air Blender unit.
Heat Recovery
Heat-recovery systems can be beneficial in reducing
the problems of stratification by preheating the cold
outside air with warm exhaust air. These systems
Water-Coil Freeze-Up Problems andSolutions
Ethylene Glycol Concentrationin % by Weight
C a p a c i t y a s % o f
C a p a c i t y a t 0 %
E t h y l e n e G l y c o l
C o n c e n t r a t i o n
0 10 20 30 40 50 60
100
110
120
130
140
150
40
50
60
70
80
90
100
P r e s s u r e D r o p a s %
o f P r e s s u r e D r o p
a t 0 % E
t y l e n e G l y c o l C o n c e n t r a t i o n
Pressure
Capacity
5
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 11/19
tend to be costly and
are often difficult to
design into a
restricted mechanical
layout because the
exhaust-air streams
must be brought to asingle point and in
close proximity to the
outside air stream.
The benefits of this
type of system are in
their potential to
recover otherwise
wasted energy.
Draining Water CoilsA widely used practice to guard against water-coil
freezing, is to drain the water and isolate the coil
during periods of subfreezing weather. This method is
obviously effective when all the required maintenance
is done in a “timely” manner. Potential problems occur
when warmer-than-normal temperatures occur in early
spring or late fall (when the cooling coil is drained)
and the building requires mechanical cooling.
Pumping Fluid at Subfreezing
Outside Air Temperatures
Control systems are often designed with a control
sequence to turn on the water pumps at subfreezing
outside-air temperatures to prevent water-coil
freezing. This sequence is effective as long as the
pump is properly maintained and the control system
is functioning. The primary downside is the use of
additional pump horsepower and run time.
Static Mixing Devices
Static mixing devices, such as the one shown in
Figure 9, provide excellent freeze protection for
hydronic coils by continuously mixing the cold
outside air into the warm
return air whenever air
is flowing across the
device. A static mixer
is the only option that
provides excellent freeze
protection without the
need for maintenance.
Furthermore, the device
provides a high degree
of flexibility during seasonal changeovers, when
chilled water cooling may be needed. In addition to
freeze protection, the static mixer provides a solution
to problems created by stratified temperatures in the
mixed-air plenum. These include mixed-air control-
sensor error and uneven air distribution across filters
and coils.
A summary of various coil-protection alternatives is
shown in Table III.
10
Figure 9 – Typical static
mixing device.
Consideration
Maintenance Reliability Flexibility Protection
Protection Attention Operating For Freeze During During AHUAlternative First Cost Required Cost Protection Changeover Shutdown
Add Glycol High High High Med High Yes
Unit Heaters High Med Med Low Low Yes
Heat Recovery High Low Med Med High No
Drain Coil Low High Low Med Low Yes
Pump Fluid Low High Med Med High YesBelow 32°F
Static Mixing Med None Med High High NoDevice
Table III – Summary of coil-protection alternatives.
Figure 8 – Large bank of
outside air dampers could cause
outside air migration.
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 12/19
IAQ has become one of the most heavily discussed
topics in the HVAC industry. This issue will affect
the HVAC industry, and the design of systems, foryears to come. The following section discuss how the
application of ASHRAE Standard 62-1989 creates
new challenges for HVAC designers and building
engineers relative to stratification in the mixing
plenum.
Outside Air Dampers Blocked Shut toEliminate Stratification Problems
Control malfunctions due to equipment failure or
improper maintenance procedures can cause IAQ
problems. As discussed earlier, a typical practice
involves disabling the outside air dampers, or blocking
the damper shut, to eliminate freeze-stat trips or
frozen-coil problems. One situation was documented
in which an outside-air intake was blocked shut by
a 2x4 to prevent the water coil from freezing in the
winter. However, the 2x4 was left in place for years,
preventing the controls from functioning5.
Dilution of Fresh Ventilation Air IntoThe Supply-Air Stream
One of the principal concerns in the IAQ discussion
is the ability to prove that adequate and proportional
ventilation air is delivered to each building occupant.
Without a static mixing device there is concern that
outside ventilation air may stratify and favor one side
of a centrifugal fan or duct branch fitting. The endresult can be a greater percentage of outside air
delivery to one portion of the building at the expense
of the rest of the building. Obviously, the ventilation
system should be designed to properly diffuse the
ventilation air into the return air stream. Figure 10
shows such a design.
Maintaining Minimum VentilationAir Under VAV Conditions
ASHRAE Standard 62-1989 requires a minimum of
15-20 CFM of ventilation air per person. This
translates to about 15-20% fixed outside air based on
maximum airflow. If the 15% rate is used, and the
supply airflow turns down to 30%, the proportion of
fixed outside air increases to 50% of the total air
supply, as shown in Figure 11. This increased
percentage of sub-freezing outside air gives rise to
freeze-stat trip and potential frozen coils. To guard
against freeze problems the heating coil is often
activated as soon as the outside air drops below
freezing.
Figure 11 – Outside air percentage based on fixed outside
air with varying supply air.
11
Indoor Air Quality (IAQ) Concerns
5 Rob erso n, Wa yne K. “Troublesho oting IAQ Troublesp ots ,” Engineered Systems , J uly/Aug us t 1993.
Return air
Fresh outside air
Fresh air is evenlydistributed in supply air
Without Air Blender,fresh air and return aircan stratify throughcoils, fans and branchtake-offs downstream
Air Blender static mixer insures that fresh air isevenly distributed throughout supp ly airstream
Figure 10 – Design toeffectively diffuse
ventilation air into thereturn air stream.
Varying Supply Air (SA) Flow
100% 90% 80% 70% 60% 50% 40% 30% 20% 10%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
Full Flow
Turn Do wnPercentage A
c t u a l O u t i s d e A i r ( O A ) F l o w
P e r c e n t a g e
1 5 %
M i n
O A
.
2 0 %
M i n
O A .
2 5 %
M i n
O A .
1 0 %
M i n
O A
.
5 % M i n
O A
6
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 13/19
How Much Mixing is Enough?
Mixing performance levels are defined in various
ways. Blender Products has chosen the range-mixing-
effectiveness method as the most definitive way to
rate a mixer’s ability to mix. Generally effectiveness
can be grouped into three categories. Low-efficiency
mixing includes standard mixing boxes available
on typical air handlers. Medium-efficiency mixing
systems include some form of static mixing device
mounted after the mixing box. High-efficiency
systems include a specially designed damper
configuration in combination with a static mixing
device to provide the highest possible level of mixing
performance. Figure 12, taken from the article “How
Much Mixing is Enough?”6 provides a way to
determine the level of mixing required to prevent
freeze-stat problems. It should be stressed that these
levels represent the minimum mixing required. It is
also necessary to provide good mixing to ensure
proper mixed-air control performance.
Figure 12 – Mixing required to prevent freeze-stat
problems.
VAV Concerns
The mixing performance of the Air Blender static
mixing device requires a minimum amount of airflow
to maintain adequate mixing action. Generally, if the
velocity through the Air Blender mixer is 400 FPM
or above, the mixer will perform properly, as shown
in Figure 13. Therefore, if a 3 to 1 turndown is desired,
the design velocity through the mixing device should
be no less than 1200 FPM.
Figure 13 – Air Blender performance under variable air-
volume conditions.
Proper Placement of Mixers in HVAC
Systems
There are a number of constraints on the proper
placement of static mixers in an air-handling system.
The first is to ensure that each mixing unit is
positioned so that a proportionate amount of each
stream is introduced into each mixer. It is also
important to provide the proper mixing distance
downstream so there is adequate time for the airstream to turbulate after flowing through the mixing
blades. Normally the static mixing units are centered
in the plenum top to bottom and side to side. Figure
14 shows correct and incorrect placements of static
mixers.
12
Application Guidelines For Static MixingDevices
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A AA A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
A A
6 Robinson, Keith D., P.E., “How Much Air Mixing is Enough?” Heating/Piping/Air Conditioning, November 1995.
Feet Per Minute (FPM) Velocity
E f f e c t i v e n e s s
200 400 600 800 1000 1200 1400
30%
40%
50%
60%
70%
80%
90%
7
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 14/1913
Patented
Air B lender
Units
Turning
Vanes
AirFlow
PatentedAir Blende rUnits Filter
AirHandler
Side Elevation Front View
FilterAirHandler
Top View
OA
RA
OA
RA
FilterAirHandler
Top View
OA
RA
RA
OA
Air Flow
Air Flow
• Use only in one single line.
• Each Air Blender device must see eq ual amo unts of da mper area a nd air flow.
• Inlet ducts c an c ause an uneq ual effect on air flow. Fresh a ir and return air dampers should be the sa me length. Use turning vanes ,
as shown in (A), to equalize flow across Air Blender units when air enters from the side.
• Mixing dampers must open so that air streams face eac h other.
• . When a minimum outside da mper is us ed it must be the full width of the return air damper and supply equal amo unts of a ir to eac h
mixer. Note that a minimum air damper is available as an option on the BlenderBox™ mixing bo x.
• Blender Products tes ts, plus independent lab tes ts, s how that multiple mixer configurations d o perform when a pplied properly.• When looking a t ava ilab le mixers, a lwa ys q uestion whether they have been tested under all sta nda rd operating and installation
co nditions , including:
– Multiple mixer co nfigurations ,
– VAV Sys tems to 33% turn-down.
• Sketch 2 show s tw o misapplica tions o f multiple Air Blender units.
• P arallel or opposed b lad e da mpers with blad e axles ac ross the short dimensions of the dampe r opening w ill ca use a ir flow to fa vor
the side of the mixing plenum and should not be used with multiple Air Blender applications. Blade axles should be oriented across
the long d imensions of the da mper opening a s s hown in Sketch 1.
A
Sketc h 1 – Corr ect Placement
Sketc h 2 – Inco rrec t Placem ent
Figure 14 – Comparison of correct and incorrect configurations when using static mixers.
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 15/19
Effect of a Combination Filter/MixingBox on Mixing Performance
Filters are sometimes placed in mixing boxes to
save space in the air handler. Placing air filters in
this seemingly “unused” space causes a significant
reduction in mixing effectiveness, as shown in
Figure 15. The preferred method is to place the
static mixer before the filter section. This provides
better mixing and diffusion across the filter and the
coil downstream.
14
Figure 15 – Comparisons of mixing effectiveness with various filter configurations.
Combination Filter/Mixing BoxWithout Air BlenderMixing Efficienc y = 45%
Lowes t Tempera ture
at Coil Face = 28°F
Standard Mixing Box withFilter Section Downstream
No Air BlenderMixing Efficienc y = 55%
Lowes t Tempera ture
at Coil Face = 32°F
Standard Mixing Box withBlender Section and FilterSection DownstreamMixing Efficienc y = 80%
Lowes t Tempera ture
at Co il Face = 45° F
BlenderBox Mixing Box withFilter Section Downstream
Mixing Efficienc y = 85%Lowes t Tempera ture
at Co il Face = 47° F
Notes:Lowes t temperature at c oil fac e is b as ed on return air tempera ture = 75°F, outside a ir = 15°F, 55°F mixed a ir tempera ture.
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 16/19
This section defines the problems that occur with an
uneven velocity profile and suggests practical
remedies to rectify these problems.
Coil Condensate Carryover
When a coil begins to remove moisture from the air
stream, water is formed as droplets on the coil fins.
Normally the droplets fall to a condensate drain pan
at the bottom of the coil and are drained away.
However, if the velocity profile across the coil is
uneven some of the condensate will “spit off” and
miss the drain pan. This carryover causes problems
by wetting the downstream areas such as duct liner
and other equipment. Equalizing the velocity profileis very important to ensure that the coil condensate
stays on the face of the coil and drains harmlessly
into the drain pan.
Coil Inefficiency
Non-homogeneous velocity through a coil also
degrades coil performance. Coils are generally tested
with even velocity across the face. However, when a
coil is applied in a system, the velocity across the coil
face is far from homogeneous. This is especially true
if the coil is applied in a blow-through configurationdown-stream of a fan discharge. The effect of this
velocity variation is difficult to quantify, but it is
obvious that performance will not be the same as that
shown by the test data.
Filter Loading, Damage and Particle
Bypass
Velocity variations across a bank of filters often
cause the filters to load unevenly or in some cases
to be damaged. This improper loading, coupled with
the high localized velocity, will often cause particle
bypass. Again, this condition occurs downstream of
a fan discharge.
15
Velocity-Stratification Problems8
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 17/19
In blow-through applications, coils and/or filtersare located downstream of a fan discharge. These
components require relatively low velocities to
operate correctly. This typically requires a large
change in area downstream of a fan.
Distance Requirements
To minimize the pressure loss of this expansion, it is
necessary to install a full-length outlet duct ahead of
the expansion, as shown in Figure 16. Although this
duct minimizes the pressure loss, its length can bequite large, especially with large fans. An additional
drawback is that it provides no diffusion of the fan
discharge jet. There is still a need for a diffusion
device or an extremely long diffusion distance
between the fan outlet and downstream coil. A long
distance is needed because the discharge jet expands
at an angle of about 15°.
Figure 16 – Full-length outlet duct, providing an ideal
installation for system effect.
System-Effect Considerations
The “No-outlet duct arrangement,” shown in Figure
17, may be used to save space. Like the full-length
outlet-duct arrangement, this configuration does not
provide additional diffusion of the air stream. Thus
the distance between the fan outlet and downstream
component must be sufficient for the jet to naturally
expand and fill the plenum. This arrangement has a
large system-effect penalty.
To enhance the diffusion of the no-outlet duct
arrangement, a diffuser plate or target plate can be
mounted between the fan outlet and the downstream
Figure 17 – No-outlet duct arrangement.
coil/filter, as shown in Figure 18. Like the no-outlet
duct arrangement, this configuration has a substantial
system-effect penalty. It can provide velocity diffusion,
but it is difficult to predict how well a system will
work until after system startup. In general, the closera diffuser plate is to the fan discharge, the better the
velocity profile. Unfortunately, as the diffuser plate
is moved closer to the fan, the system-effect penalty
increases rapidly.
Figure 18 – Target plate, vertical diffuser plate and angled diffuser plate configurations.
The use of the BlenderConeTM fan diffuser/mixer
(Figure 19) provides an alternative approach. The
pressure drop of the BlenderCone is greater than the
pressure drop of the full outlet duct, but is less than
half the pressure drop of the other arrangements.
The distance required by the BlenderCone is less
than the distance required by the full-outlet duct and
is essentially the same as that required by the other
arrangements.
Figure 19 – Short BlenderCone, for retrofit applications in
tight spaces, and the more efficient long BlenderCone for
new construction.
16
Application Guidelines For Velocity-Equalizing Diffusers9
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 18/19
Bibliography
Amoroso Jr., Victor, P.E. & Gjestvang, Ryan, P.E., “Air Handling Units for Hospitals,” Consulting/Specifying
Engineer, October 1989.
Faison Jr., T.K., Davis, J.C., & Achenbach, P.R., “Performance of Louvered Devices as Air Mixers,” Building
Science Series 27, US Dept. of Commerce, National Bureau of Standards, March 1970.
Haines, Roger W., “HVAC Systems Design Handbook,” Section 4.8 (pp 109-111) TAB Books, 1988.
Haines, Roger W., “Stratification,” Heating/Piping/Air Conditioning, November 1980.
Hallstrom, Arthur D., “Fixing the Frozen Coil Problem,” Contracting Business, October 1986.
Robinson, Keith D., P.E., “Blender Cone Basics,” Blender Products, Inc., December 1992.
Robinson, Keith D., P.E., “Fan Basics,” Blender Products, Inc., December 1992.
Application Guidelines For Velocity-Equalizing Diffusers
7/23/2019 airmix
http://slidepdf.com/reader/full/airmix 19/19
5010 Cook Street, Denver, CO 80216
Toll-Free: 800-523-5705
Fax: 303-296-1520
Phone: 303-295-6111