+ All Categories
Home > Documents > Alfa Laval AQ4 - LenntechStandard EN 1092-1 corresponds to GOST 12815-80 and GB/T 9115. Dimensions...

Alfa Laval AQ4 - LenntechStandard EN 1092-1 corresponds to GOST 12815-80 and GB/T 9115. Dimensions...

Date post: 16-Aug-2020
Category:
Upload: others
View: 1 times
Download: 1 times
Share this document with a friend
2
. Alfa Laval AQ4 AlfaQ TM AHRI-certified plate heat exchanger . Applications General heating and cooling duties. Heating by means of steam. Standard design The plate heat exchanger consists of a pack of corrugated metal plates with portholes for the passage of the two fluids between which heat transfer will take place. The plate pack is assembled between a fix frame plate and a movable pressure plate and compressed by tightening bolts. The plates are fitted with a gasket which seals the interplate channel and directs the fluids into alternate channels. The number of plates is determined by the flow rate, physical properties of the fluids, pressure drop and temperature program. The plate corrugations promote fluid turbulence and support the plates against differential pressure. The plate and the pressure plate are suspended from an upper carrying bar and located by a lower guiding bar, both of which are fixed to a support column. Connections are located in the frame plate or, if either or both fluids make more than a single pass within the unit, in the frame and pressure plates. Typical capacities Liquid flow rate Up to 50 kg/s (800 gpm), depending on media, permitted pressure drop and temperature program. Water heating by steam 0.7 to 3.0 MW Plate types AQ4, AQ4-M and AQ4-D, double wall plates. Frame types FM, FG and FD Working principle Channels are formed between the plates and the corner ports are arranged so that the two media flow through alternate channels. The heat is transferred through the plate between the channels, and complete counter-current flow is created for highest possible efficiency. The corrugation of the plates provides the passage between the plates, supports each plate against the adjacent one and enhances the turbulence, resulting in efficient heat transfer. Flow principle of a plate heat exchanger
Transcript
Page 1: Alfa Laval AQ4 - LenntechStandard EN 1092-1 corresponds to GOST 12815-80 and GB/T 9115. Dimensions 695-2400 (27-95") H h 719 (28.3") 225 (8.9") or 231(9.1") W Measurements mm (inch)

.

Alfa Laval AQ4AlfaQTM AHRI-certified plate heat exchanger

.

ApplicationsGeneral heating and cooling duties. Heating by means ofsteam.

Standard designThe plate heat exchanger consists of a pack of corrugatedmetal plates with portholes for the passage of the two fluidsbetween which heat transfer will take place.

The plate pack is assembled between a fix frame plate and amovable pressure plate and compressed by tightening bolts.The plates are fitted with a gasket which seals the interplatechannel and directs the fluids into alternate channels. Thenumber of plates is determined by the flow rate, physicalproperties of the fluids, pressure drop and temperatureprogram. The plate corrugations promote fluid turbulence andsupport the plates against differential pressure.

The plate and the pressure plate are suspended from anupper carrying bar and located by a lower guiding bar, bothof which are fixed to a support column.

Connections are located in the frame plate or, if either or bothfluids make more than a single pass within the unit, in theframe and pressure plates.

Typical capacitiesLiquid flow rateUp to 50 kg/s (800 gpm), depending on media, permittedpressure drop and temperature program.

Water heating by steam0.7 to 3.0 MW

Plate typesAQ4, AQ4-M and AQ4-D, double wall plates.

Frame typesFM, FG and FD

Working principleChannels are formed between the plates and the corner portsare arranged so that the two media flow through alternatechannels. The heat is transferred through the plate betweenthe channels, and complete counter-current flow is createdfor highest possible efficiency. The corrugation of the platesprovides the passage between the plates, supports eachplate against the adjacent one and enhances the turbulence,resulting in efficient heat transfer.

Flow principle of a plate heat exchanger

Page 2: Alfa Laval AQ4 - LenntechStandard EN 1092-1 corresponds to GOST 12815-80 and GB/T 9115. Dimensions 695-2400 (27-95") H h 719 (28.3") 225 (8.9") or 231(9.1") W Measurements mm (inch)

STANDARD MATERIALSFrame plateMild steel, Epoxy painted

NozzlesCarbon steelMetal lined: Stainless steel, TitaniumRubber lined: Nitrile, EPDM

PlatesStainless steel Alloy 316/Alloy 304, Titanium, Alloy 254 SMO,Alloy C276

Gaskets (Clip-on, glued)Nitrile, EPDM, Viton®Other grades and material available on request.

TECHNICAL DATAPressure vessel codes, PED, ASME, pvcALS™Mechanical design pressure (g) / temperature

FL pvcALS™ 0.6 MPa / 130ºCFM pvcALS™ 1.0 MPa / 180ºCFM PED 1.0 MPa / 180ºCFG pvcALS™ 1.6 MPa / 180ºCFG PED 1.6 MPa / 180ºC *FG ASME 150 psig / 356ºFFD PED pvsALS™ 2.5 MPa / 180ºCFD ASME 389 psig / 482ºF*) Frame FG also approved for 1.2 MPa / 200°C to allow use in steam systemswithout safety valves.

Connections

Size: DN100 / NPS 4 / 100AFL pvcALS™ EN 1092-1 PN10, JIS B2220 10K

FM pvcALS™ EN 1092-1 PN10, ASME B16.5 Class150, JIS B2220 10K,

FM PED EN 1092-1 PN10, ASME B16.5 Class150

FG pvcALS™ EN 1092-1 PN16, ASME B16.5 Class150, JIS B2220 10K, JIS B2220 16K,

FG PED EN 1092-1 PN16, ASME B16.5 Class150

FG ASME ASME B16.5 Class 150

FD PED EN 1092-1 PN25, ASME B16.5 Class150, ASME B16.5 Class 300

FD ASME ASME B16.5 Class 300Standard EN 1092-1 corresponds to GOST 12815-80 and GB/T9115.

Dimensions

695-2400 (27-95")

h71

9 (2

8.3"

)H

225 (8.9") or 231(9.1")

W

Measurements mm (inch)

Type H W hAQ4-FM 1084 (42.7") 470 (18.5") 215 (8.5")AQ4-FG 1084 (42.7") 470 (18.5") 215 (8.5")AQ4-FD 981 (38.6") 470 (18.5") 131 (5.2")AQ4-FD ASME 1084 (42.7") 470 (18.5") 215 (8.5")The number of tightening bolts may vary depending on pressure rating.

Maximum heat transfer surfaceAQ4-B 90 m2 (970 sq. ft)AQ4 60 m2 (650 sq. ft)

Particulars required for quotation- Flow rates or heat load- Temperature program- Physical properties of liquids in question (if not water)- Desired working pressure- Maximum permitted pressure drop- Available steam pressure

The thermal performance is third party certified throughthe AHRI Liquid to Liquid Heat Exchangers certificationprogram

.

ECF00367EN 1506 Alfa Laval reserves the right to change specifications without prior notification.

[email protected] Tel. +31-152-610-900www.lenntech.com Fax. [email protected] Tel. +31-152-610-900www.lenntech.com Fax. +31-152-616-289