7
12x8 R 8"Ø 12x8 RA SA SUPPLY AIR RETURN AIR R - RISE, D - DROP DUCT SIZE, RECTANGULAR, FLEXIBLE CONNECTION ELBOW, RECTANGULAR(r=1.5W) ACOUSTICAL INSULATION LINING HVAC LEGEND DUCT SIZE, ROUND DUCT SECTION, SUPPLY DUCT SECTION, RETURN OR EXHAUST CHANGE OF ELEVATION FIRST FIGURE IS SIDE SHOWN MA EA EXHAUST AIR MAKE-UP AIR R - RISE, D - DROP CHANGE OF ELEVATION AD ACOUSTICAL INSULATION LINING Ex. OA OUTDOOR AIR EXISTING VD TEE, RECTANGULAR MAIN AND TAP, FOT - FLAT ON TOP, FOB - FLAT ON BOTTOM TEE, RECTANGULAR MAIN AND TAP VOLUME DAMPER TEE RECTANGULAR TRANSITIONS ELBOW, WITH VANES, RECTANGULAR(r=1.5W) WITH DAMPER ELBOW, WITH VANES, RECTANGULAR WYE, RECTANGULAR TYPE CFM SIZE CEILING OR REGISTER DESIGNATION CEILING RETURN GRILLE FD WALL SUPPLY GRILLE OR REGISTER FIRE DAMPER WALL EXHAUST/RETURN GRILLE OF REGISTER CEILING SUPPLY DIFFUSER 24"x24" 'S1' 100 T H THERMOSTAT HUMIDISTAT C CONTROLLER, AS INDICATED S THERMOSTAT REMOTE SENSOR FLOOR OR CEILING SUPPLY FLOOR OR CEILING EXHAUST/RETURN GRILLE OR REGISTER GRILLE OR REGISTER SAN PLUMBING LEGEND SS SS SS SV SD SD SD ABBREVIATION SYMBOL DESCRIPTION SAN VENT STM STM WCO SANITARY DRAIN ABOVE FLOOR/GRADE SANITARY DRAIN BELOW FLOOR/GRADE SANITARY VENT STORM DRAIN ABOVE FLOOR/GRADE STORM DRAIN BELOW FLOOR/GRADE WALL CLEANOUT FCO FLOOR CLEANOUT SS SS LCO LINE CLEANOUT GCO GRADE CLEANOUT DCW DOMESTIC COLD WATER DHW DOMESTIC HOT WATER oo oo STANDPIPE - DHWR DOMESTIC HOT WATER RETURN GAS NATURAL GAS GAS MECHANICAL NOTES MECHANICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS FOR THIS PROJECT. 1 GENERAL: .1 CONFORM WITH APPLICABLE REQUIREMENTS OF THE MINISTRY OF LABOUR, AND THE OCCUPATIONAL HEALTH AND SAFETY ACT AND REGULATIONS FOR CONSTRUCTION PROJECTS. .2 DO COMPLETE INSTALLATION IN ACCORDANCE WITH THE FOLLOWING: .1 ONTARIO BUILDING CODE (OBC); .2 NATURAL GAS AND PROPANE INSTALLATION CODE (GAS CODE); .3 ASHRAE; .4 SMACNA; .5 NFPA; .6 ALL OTHER RELEVANT CODES AND STANDARDS, AS APPLICABLE. .3 OBTAIN ALL PERMITS REQUIRED FOR THE INSTALLATION OF MECHANICAL TRADES WORK, ARRANGE FOR INSPECTIONS AND TESTS, AND PAY ALL FEES AND COSTS FOR THE PERMITS, INSPECTIONS AND FEES. OBTAIN PERMITS IMMEDIATELY AFTER NOTIFICATION OF AWARD OF CONTRACT. .4 PROVIDE THREE COPIES OF COMPLETE OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT FURNISHED UNDER THIS CONTRACT. BIND INSTRUCTIONS IN 3-RING BINDERS. INCLUDE THE FOLLOWING: .1 SCHEMATIC DIAGRAM OF ELECTRICAL SYSTEMS. .2 CONTROL SHOP DRAWINGS AND OPERATING SEQUENCE INCLUDING WIRING OF COMPONENTS. .3 WIRING DIAGRAM OF CONTROL PANELS. .4 OPERATING INSTRUCTIONS, INCLUDING START-UP AND SHUT-DOWN PROCEDURE. .5 MAINTENANCE INSTRUCTIONS INCLUDING PREVENTIVE MAINTENANCE INSTRUCTIONS FOR COMPONENTS OF THE EQUIPMENT. .6 COMPLETE PARTS LIST OF ASSEMBLIES AND THEIR COMPONENT PARTS, SHOWING MANUFACTURER'S NAME, CATALOGUE NUMBER, AND NEAREST REPLACEMENT SOURCE. .7 LIST OF RECOMMENDED SPARE PARTS AND QUANTITY OF EACH ITEM TO BE STOCKED. .8 MANUFACTURERS' WARRANTIES AND GUARANTEES. .5 CLEAN ALL MECHANICAL SYSTEMS AT PROJECT COMPLETION. .6 COMPLETE AS-BUILT DRAWINGS SHOWING ALL CHANGES AS WORK PROGRESSES. 2 CONTRACTOR QUALIFICATIONS: .1 ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE “TRADE QUALIFICATION AND APPRENTICESHIP ACT” AND REGULATIONS, BY PERSONS WHO HOLD THE FOLLOWING CERTIFICATES OF QUALIFICATION (AS APPLICABLE): .1 PLUMBER; .2 REFRIGERATION & AIR CONDITIONING SYSTEMS MECHANIC; .3 RESIDENTIAL AIR CONDITIONING SYSTEMS MECHANIC; .4 SHEET METAL WORKER. .2 ALL FUELS-RELATED WORK TO BE CARRIED OUT IN ACCORDANCE WITH TSSA REQUIREMENTS AND ONTARIO REGULATION 215/01, “FUEL INDUSTRY CERTIFICATES” BY PERSONS WHO HOLD THE APPROPRIATE CERTIFICATES FOR THE WORK BEING PERFORMED. 3 EXISTING FACILITIES AND DEMOLITION: .1 LOCATE AND PROTECT ALL EXISTING EXTERIOR SITE SERVICES. .2 RETAIN AND PROTECT ALL EXISTING INTERIOR SERVICES AND BUILDING FABRIC. MAKE GOOD ANY AND ALL DAMAGE RESULTING FROM THIS WORK. 4 FIXTURES AND EQUIPMENT: .1 PROVIDE SHOP DRAWINGS AND PRODUCT DATA FOR ALL MECHANICAL FIXTURES AND EQUIPMENT FOR APPROVAL, PRIOR TO PROCUREMENT. .2 INSTALL ALL MECHANICAL FIXTURES AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. .3 LOCATE ALL EQUIPMENT WITH CLEARANCES, AS REQUIRED BY THE MANUFACTURER, THE FUEL CODES, AND ALL OTHER CODES AND REGULATIONS, INCLUDING THE FOLLOWING CLEARANCES: .1 TO PERMIT PROPER EQUIPMENT OPERATION; .2 TO PERMIT SUFFICIENT AIRFLOW AROUND EQUIPMENT; .3 FOR EQUIPMENT SERVICE; .4 SUFFICIENT DISTANCE FROM COMBUSTIBLE MATERIAL; .5 WITH SUFFICIENT VENT CLEARANCES; .6 SUFFICIENT DISTANCE FROM ROOF EDGES OR OTHER HAZARDS; .7 SERVICE PLATFORMS FOR APPLIANCES INSTALLED 10 FT OR MORE ABOVE FLOOR; .8 WITH FIXED ACCESS TO ROOF FOR BUILDING HEIGHT GREATER THAN 13', AND STAIRWAY ACCESS TO ROOF GREATER THAN 26'. 5 EQUIPMENT SUPPLIED BY OTHERS: .1 MAKE ALL MECHANICAL SERVICE CONNECTIONS TO EQUIPMENT SUPPLIED BY OTHERS. .2 CONFIRM ALL SERVICE CONNECTIONS WITH MANUFACTURER AND SUPPLIER, PRIOR TO INSTALLATION. THIS SHALL INCLUDE ALL CONNECTION SIZES, LOCATIONS AND DETAILS, AND SHALL TAKE INTO ACCOUNT EQUIPMENT CLEARANCES AND INSTALLATION REQUIREMENTS. 6 PIPING AND ESCUTCHEONS: .1 PROVIDE DIELECTRIC UNIONS AT ALL PIPING LOCATIONS WHERE DISSIMILAR METALS ARE JOINED. .2 PROVIDE ESCUTCHEONS ON ALL PIPES PASSING THROUGH WALLS, PARTITIONS, FLOORS AND CEILINGS, CHROME, NICKEL PLATED BRASS OR TYPE 302 STAINLESS STEEL. 7 ACCESS DOORS: .1 SUPPLY ACCESS DOORS, AS REQUIRED IN DUCTWORK AND WALL/CEILING ASSEMBLIES, TO ALL CONCEALED MECHANICAL EQUIPMENT AND OPERATING DEVICES. ACCESS DOORS IN WALL/CEILING ASSEMBLIES TO BE INSTALLED BY OTHER TRADES. .2 ACCESS DOORS SHALL BE FIRE-RATED TYPE, WHERE USED IN FIRE-RATED ASSEMBLIES, AND SHALL MATCH THE RATING OF THE ASSEMBLY. 8 PIPE INSULATION: .1 INSTALL IN ACCORDANCE WITH THERMAL INSULATION ASSOCIATION OF CANADA (TIAC) NATIONAL STANDARDS. .2 MAX. FLAME SPREAD RATING: 25. .3 MAX. SMOKE DEVELOPED RATING: 50. .4 DOMESTIC COLD WATER (DCW): .1 1” RIGID MOULDED MINERAL FIBRE WITH VAPOUR RETARDER JACKET. .2 INSULATE ALL PIPING IN FLOORS, WALLS AND CEILINGS, TO POINT OF FIXTURE CONNECTIONS. .5 DOMESTIC HOT WATER (DHW): .1 1” RIGID MOULDED MINERAL FIBRE FOR PIPING UP TO 1-1/4” SIZE. .2 INSULATE ALL PIPING IN FLOORS, WALLS AND CEILINGS, TO POINT OF FIXTURE CONNECTIONS. .6 OUTER JACKET: .1 CONCEALED LOCATIONS: ALL SERVICE JACKET. .2 EXPOSED LOCATIONS: PVC JACKET. .3 MECHANICAL/SERVICE ROOMS: PVC JACKET. 9 WATER SERVICE AND WATER SUPPLY PIPING: .1 SUBMERSIBLE WELL PUMP: BLACK POLYETHYLENE PIPE, 150 PSI. .2 ABOVE GROUND: COPPER TUBE, HARD DRAWN, TYPE L. CAN. OR US MANUFACTURE, INCLUDING FITTINGS. LEAD-FREE SOLDER. .3 WATER SUPPLY PIPING IS SHOWN SCHEMATICALLY. ALL PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED. .4 INSTALL TUBING CLOSE TO BUILDING STRUCTURE TO MINIMIZE FURRING, CONSERVE HEADROOM AND SPACE. GROUP EXPOSED PIPING AND RUN PARALLEL TO WALLS. .5 ISOLATE ALL EQUIPMENT, FIXTURES AND BRANCHES WITH VALVES. .6 TEST WATER SYSTEM AT 1½ TIMES SYSTEM OPERATING PRESSURE OR MINIMUM 860 KPA, WHICHEVER IS GREATER. TEST PRESSURE AND TIMEFRAME SHALL BE AS REQUIRED BY OBC 7.3.7.2. .7 FLUSH OUT, DISINFECT AND RINSE SYSTEM, PRIOR TO CONSTRUCTION COMPLETION. .8 WATER HEATERS: .1 SHALL BE PIPED WITH HEAT TRAPS ON THE INLET AND OUTLET PIPING, AS CLOSE AS PRACTICAL TO THE TANK, IN ACCORDANCE WITH OBC 12.3.1.4. .2 TEMPERATURE AND PRESSURE RELIEF VALVES: .1 MAXIMUM TEMPERATURE SETTING OF 210F (99F); .2 MAXIMUM PRESSURE SETTING OF 150 PSI; .3 DISCHARGE PER OBC 7.6.1.12.: .1 TERMINATE WITH AN INDIRECT CONNECTION PIPED TO FLOOR DRAIN, SUMP OR OTHER SAFE LOCATION, WITH A 300mm AIR BREAK; OR .2 TERMINATE AT A DISTANCE NOT LESS THAN 150mm AND NOT MORE THAN 300mm FROM A FLOOR AND DISCHARGE VERTICALLY DOWN, .9 TRAP SEAL PRIMERS AND ACCESS TO THEM, SHALL BE LOCATED IN THE WASHROOM OR AREA THAT THEY SERVE. .10 SUPPLY AND INSTALL WATER HAMMER ARRESTORS AT THE MIDPOINT AND END OF RUNS OF WATER SUPPLY PIPING AS REQUIRED BY OBC 7.6.1.14. 10 DRAINAGE, WASTE AND VENT PIPING: .1 COORDINATE SANITARY SERVICE INSTALLATIONS WITH SUPPLY AUTHORITY. .2 APPROXIMATE SUB-FLOOR PIPING ELEVATIONS HAVE BEEN INDICATED ON THE DRAWINGS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SETTING FINAL INVERTS BASED ON SITE CONDITIONS. .3 BELOW GROUND/FLOOR: .1 ABS DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.1. .2 PVC DWV, TYPE SDR26 SDR35. .4 ABOVE GROUND: .1 PVC DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.2, FOR NONCOMBUSTIBLE CONSTRUCTION (FLAME-SPREAD RATING NOT MORE THAN 25 PER CAN/ULC-S102.2). .2 PVC DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.2, FOR NONCOMBUSTIBLE CONSTRUCTION (FLAME-SPREAD RATING NOT MORE THAN 25 AND SMOKE DEVELOPED CLASSIFICATION NOT MORE THAN 50 PER CAN/ULC-S102.2 - PLENUMS). .5 PROVIDE CLEANOUTS AS REQUIRED BY THE ONTARIO BUILDING CODE. .6 VENT COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH THE ONTARIO BUILDING CODE. 11 PROPANE GAS PIPING: .1 COORDINATE PROPANE SERVICE INSTALLATION WITH SUPPLY AUTHORITY. .2 STEEL PIPE, SCHEDULE 40, SEAMLESS, SCREWED FITTINGS. .3 TEST SYSTEM IN ACCORDANCE WITH NATURAL GAS AND PROPANE INSTALLATION CODE. 12 DUCTWORK: .1 RECTANGULAR DUCT: .1 RIGID GALVANIZED STEEL, LOCK FORMING QUALITY TO ASTM A653/A653M .2 THICKNESS, FABRICATION, REINFORCEMENT AND SUPPORT/ATTACHMENT TO ASHRAE OR SMACNA. .2 ROUND DUCT: .1 RIGID GALVANIZED STEEL, LOCK FORMING QUALITY TO ASTM A653/A653M .2 THICKNESS, FABRICATION, REINFORCEMENT AND SUPPORT/ATTACHMENT TO ASHRAE OR SMACNA. .3 FLEXIBLE BRANCH DUCT (PERMITTED WITHIN 2m/6ft FROM OUTLET): .1 ALL METAL TYPE: TRIPLE LOCK, ALUMINUM CORRUGATED DUCT, MANUFACTURED USING AN ALUMINUM STRIP, WHICH IS SPIRALLY WOUND AND MECHANICALLY JOINED TOGETHER FORMING AN AIR TIGHT AND LEAKPROOF SEAM. .3 SEAL CLASSIFICATION: .1 CLASS A: LONGITUDINAL SEAMS, TRANSVERSE JOINTS, DUCT WALL PENETRATIONS AND CONNECTIONS MADE AIRTIGHT WITH SEALANT AND TAPE. .4 FITTINGS .1 FABRICATION: TO SMACNA. .2 RADIUSED ELBOWS. .1 RECTANGULAR: STANDARD WITH CENTRELINE RADIUS 1.5 TIMES DUCT DIMENSION, WITH SINGLE THICKNESS TURNING VANES. .2 ROUND: FIVE PIECE WITH CENTRELINE RADIUS 1.5 TIMES DIAMETER. .3 MITRED ELBOWS, RECTANGULAR: WITH DOUBLE THICKNESS TURNING VANES. 5 BRANCHES: .1 RECTANGULAR MAIN AND BRANCH: WITH RADIUS ON BRANCH 1.5 TIMES WIDTH OF DUCT 45 DEGREES ENTRY ON BRANCH. .2 ROUND MAIN AND BRANCH: ENTER MAIN DUCT AT 45 DEGREES WITH CONICAL CONNECTION. .3 PROVIDE VOLUME CONTROL DAMPER IN BRANCH DUCT NEAR CONNECTION TO MAIN DUCT. .4 MAIN DUCT BRANCHES: WITH SPLITTER DAMPER. .6 TRANSITIONS: .1 DIVERGING: 20 DEGREES MAXIMUM INCLUDED ANGLE. .2 CONVERGING: 30 DEGREES MAXIMUM INCLUDED ANGLE. .7 FIRE STOPPING .1 RETAINING ANGLES AROUND DUCT, ON BOTH SIDES OF FIRE SEPARATION IN ACCORDANCE WITH SECTION. .2 FIRE STOPPING MATERIAL AND INSTALLATION MUST NOT DISTORT DUCT. .8 DAMPERS: .1 MANUFACTURE TO SMACNA STANDARDS. .2 SINGLE BLADE DAMPERS: .1 FABRICATE FROM SAME MATERIAL AS DUCT, BUT ONE SHEET METAL THICKNESS HEAVIER. V_GROOVE STIFFENED. .2 SIZE AND CONFIGURATION TO RECOMMENDATIONS OF SMACNA. .3 LOCKING QUADRANT (WITH SHAFT EXTENSION TO ACCOMMODATE INSULATION THICKNESS, IF REQUIRED). .4 INSIDE AND OUTSIDE NYLON END BEARINGS. .5 CHANNEL FRAME OF SAME MATERIAL AS ADJACENT DUCT, COMPLETE WITH ANGLE STOP. .9 DUCT LEAKAGE: IN ACCORDANCE WITH SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. .10 ALL DUCT AND SEAL MATERIALS TO HAVE A FLAME SPREAD RATING OF LESS THAN 25 AND A SMOKE DEVELOPED CLASSIFICATION OF LESS THAN 50. .11 PAINT VISIBLE INTERIOR SURFACES OF ALL PLENUM BOXES MATTE BLACK. .12 PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT DUCT CONNECTION POINTS. 13 DUCT INSULATION: .1 REFER TO DRAWING FOR DUCT THAT IS IDENTIFIED TO BE INSULATED. .2 INSTALL IN ACCORDANCE WITH THERMAL INSULATION ASSOCIATION OF CANADA (TIAC) NATIONAL STANDARDS. .3 MAX. FLAME SPREAD RATING: 25. .4 MAX. SMOKE DEVELOPED RATING: 50. .5 THERMAL INSULATION - RECTANGULAR DUCT: .1 1” (R4.3) RIGID MINERAL FIBRE BOARD WITH VAPOUR RETARDER JACKET. .2 ALUMINUM JACKET WITH MOISTURE BARRIER. .6 THERMAL INSULATION - ROUND DUCT: .1 1” (R3.1) MINERAL FIBRE BLANKET WITH VAPOUR RETARDER JACKET. .2 ALUMINUM JACKET WITH MOISTURE BARRIER. .7 ACOUSTIC DUCT LINING: .1 1” (R4.3) ACOUSTIC QUALITY MINERAL FIBRE DUCT LINER, WITH MAT FACING, BACTERIA AND FUNGUS RESISTANT. .2 FASTEN TO INTERIOR SHEET METAL SURFACE WITH 100% COVERAGE OF ADHESIVE AND 5/16” WELD PINS NOT LESS THAN 2 ROWS PER SURFACE AND NOT MORE THAN 16 IN ON CENTRES. .3 SEAL BUTT JOINTS, EXPOSED EDGES, WELD PIN AND CLIP PENETRATIONS AND DAMAGED AREAS OF LINER WITH 2” JOINT TAPE AND SEALER. 14 MECHANICAL FIRE PROTECTION: .1 REFER TO ARCHITECTURAL DRAWINGS, TO VERIFY LOCATION OF ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES. .2 ALL PIPING SHALL BE TIGHTLY FITTED AND SEALED WITH FIRESTOPPING MATERIAL AT ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES. .3 FIRE DAMPERS: .1 FIRE DAMPERS SHALL BE CAN/ULC-S112 (STANDARD METHOD OF FIRE TEST OF FIRE DAMPER ASSEMBLIES) LISTED AND LABELLED. .2 FIRE DAMPERS SHALL BE NFPA 80 (STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES), NFPA 90A (STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS), AND NFPA 101 (LIFE SAFETY CODE) COMPLIANT. .3 DUCTWORK SHALL BE FITTED WITH FIRE DAMPERS AT ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES. .4 SUPPLY AND INSTALL ACCESS DOORS IN ARCHITECTURAL FINISH (WALL, CEILING OR FLOOR) TO ACCESS DUCT, IN COMMON AREA WHERE POSSIBLE. .5 SUPPLY AND INSTALL TIGHTLY-FITTED ACCESS DOOR IN DUCT TO ACCESS, INSPECT AND RESET FIRE DAMPER. .6 TYPES: DYNAMIC - FOR USE IN AIR HANDLING SYSTEMS THAT DO NOT SHUTDOWN UPON FIRE ALARM. .7 RATING: 1-1/2 HR (30MIN TO 2HR FIRE RESISTANCE RATING). .4 ALL MECHANICAL MATERIALS USED WITHIN CEILING RETURN AIR PLENUMS SHALL FLAME-SPREAD RATING NOT MORE THAN 25 AND SMOKE DEVELOPED CLASSIFICATION NOT MORE THAN 50 PER CAN/ULC-S102.2. .5 MOCK-UPS: .1 PREPARE MOCK-UPS OF TYPICAL FIRESTOP INSTALLATION OF THE FOLLOWING, FOR REVIEW AND APPROVAL BY THE OWNER, ENGINEER AND MUNICIPAL BUILDING INSPECTOR: .1 SANITARY PIPING - WALL AND CEILING/FLOOR FIRE SEPARATION; .2 DCW AND DHW PIPING - WALL AND CEILING/FLOOR FIRE SEPARATION; .3 FIRE DAMPER INSTALLATION - WALL AND CEILING/FLOOR FIRE SEPARATION. .2 ALL FIRESTOP INSTALLATIONS SHALL BE COMPLETED IN ACCORDANCE WITH THE APPROPRIATE PRODUCT INSTALLATION INSTRUCTIONS, AND THE REFERENCED UL/ULC LISTING AND/OR TEST STANDARD. .3 SUPPLY A COPY OF THE PRODUCT INSTALLATION INSTRUCTIONS WITH ULC LISTING AND/OR TEST STANDARD REFERENCE, FOR EACH INSTALLATION. .4 MOCK-UP MAY REMAIN AS PART OF WORK. 15 EQUIPMENT IN HAZARDOUS LOCATIONS: .1 THE GARAGE AREA, AND ADJACENT ROOMS, UP TO A LEVEL OF 50mm ABOVE THE FLOOR SHALL BE CONSIDERED A CLASS I (FLAMMABLE GASES OR VAPOURS) ZONE 2 LOCATION. .2 ALL EQUIPMENT USED WITHIN THE AREA SHALL BE APPROVED FOR THE CLASSIFICATION. 16 MECHANICAL IDENTIFICATION: .1 IDENTIFY MECHANICAL EQUIPMENT WITH LAMICOID NAMEPLATES. .2 LABEL ALL PIPING AT LEAST ONCE IN EVERY ROOM, AND AT NO MORE THAN 25 FT CENTERS. 17 EARTHQUAKE LOAD: .1 ALL MECHANICAL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE EARTHQUAKE LOAD AND EFFECTS REQUIRED BY THE ONTARIO BUILDING CODE. .2 MECHANICAL ELEMENTS AND COMPONENTS (EQUIPMENT, PIPES, DUCTS, ETC.), AND THEIR CONNECTIONS TO THE BUILDING SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE SMACNA/ANSI SEISMIC RESTRAINT MANUAL OR OTHER GUIDELINE REFERENCED IN THE ONTARIO BUILDING CODE. .3 PROVIDE SHOP DRAWINGS FOR SUPPORT, CONNECTIONS AND SEISMIC RESTRAINT OF ALL MECHANICAL EQUIPMENT, PIPES AND DUCTS, INCLUDING, BUT NOT LIMITED TO: .1 FURNACES AND ENERGY RECOVERY VENTILATORS; .2 CONDENSING; .3 INFRARED HEATERS; .4 TYPICAL DUCT SUPPORTING SYSTEM; .5 TYPICAL SAN, DCW, DHW PIPE SUPPORTING SYSTEM; .6 TYPICAL PROPANE PIPE SUPPORTING SYSTEM. THESE SHOP DRAWINGS SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER IN THE PROVINCE OF ONTARIO, WITH EXPERIENCE IN SEISMIC ENGINEERING. 18 EQUIPMENT AND MATERIALS SUPPORT: .1 ALL MECHANICAL EQUIPMENT, PIPING, DUCTWORK, AND RELATED ITEMS SHALL BE SECURELY SUPPORTED, ATTACHED AND FASTENED TO BUILDING STRUCTURE. .2 PIPE HANGERS AND SUPPORTS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH MSS STANDARD SP-58, PIPE HANGERS AND SUPPORTS - MATERIALS, DESIGN, MANUFACTURE, SELECTION, APPLICATION, AND INSTALLATION. 19 COORDINATION: .1 INFORMATION INVOLVING ACCURATE DIMENSIONING OF THE BUILDING SHALL BE TAKEN FROM SITE BY CONTRACTOR. .2 DRAWINGS ARE IN DIAGRAMMATIC FORM, INTENDED TO CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT FOR EQUIPMENT. COORDINATE PHYSICAL LOCATION OF ALL EQUIPMENT WITH OTHER TRADES AND ALLOW FOR ANY ADDITIONAL PIPING, DUCTING, FITTINGS, SUPPORTS, ETC., IN ORDER TO AVOID INTERFERENCE AND FACILITATE THE WORK. .3 CONTRACTOR TO MAKE ANY NECESSARY MODIFICATIONS OR ADDITIONS, WITHOUT CHARGE, TO ACCOMMODATE SITE CONDITIONS AND COORDINATION. .4 COORDINATE ALL MECHANICAL EQUIPMENT WIRING, INCLUDING LOW VOLTAGE CONTROL WIRING, WITH ELECTRICAL TRADES. 20 START-UP, COMMISSIONING AND TRAINING: .1 COMMISSIONING: .1 START-UP AND COMMISSION THE FOLLOWING SYSTEMS: .1 PLUMBING FIXTURES; .2 HVAC; .3 GAS DETECTION AND EXHAUST SYSTEM. .2 PERFORM SYSTEMATIC TESTS, PROCEDURES AND CHECKS ON SYSTEMS, AS FOLLOWS: .1 TO VERIFY OPERATION IN ACCORDANCE WITH CONTRACT DOCUMENTS, DESIGN CRITERIA aND INTENT, AND MANUFACTURER'S REQUIREMENTS; .2 TO ENSURE APPROPRIATE DOCUMENTATION IS PROVIDED; .3 TO EFFECTIVELY TRAIN BUILDING OPERATIONAL STAFF. .3 SYSTEMS ARE TO BE OPERATED AT FULL CAPACITY, WITH CORRECTION OF ALL DEFICIENCIES AND ADJUSTMENTS TO MEET OPTIMUM PERFORMANCE. .4 PROVIDE WRITTEN REPORT AT END OF COMMISSIONING OUTLINING EQUIPMENT OPERATIONAL CONDITIONS AND PARAMETERS. .2 TESTING, ADJUSTING AND BALANCING: .1 TEST, ADJUST AND BALANCE (TAB) ALL PLUMBING AND HVAC EQUIPMENT AND SYSTEMS; INCLUDING THE FOLLOWING: .1 FURNACES; .2 CONDENSING UNITS; .3 ENERGY RECOVERY VENTILATORS. .2 TAB PROCEDURE SHALL BE COMPLETED IN ACCORDANCE WITH ASHRAE STANDARD 111, MEASUREMENT, TESTING, ADJUSTING AND BALANCING OF BUILDING HVAC SYSTEMS. .3 PROVIDE DETAILED REPORT AT END OF TAB, IN ACCORDANCE WITH THE REPORTING PROCEDURES OF ASHRAE STANDARD 111. .3 DEMONSTRATION AND TRAINING: .1 DEMONSTRATE OPERATION AND MAINTENANCE OF EQUIPMENT AND SYSTEMS TO OWNER'S PERSONNEL ONE WEEK PRIOR TO DATE OF FINAL INSPECTION .2 PRIOR TO DEMONSTRATION AND TRAINING, ENSURE THAT EQUIPMENT HAS BEEN INSPECTED AND PUT INTO OPERATION, INCLUDING COMPLETION OF COMMISSIONING AND TESTING, ADJUSTING, AND BALANCING. .3 DEMONSTRATE START_UP, OPERATION, CONTROL, ADJUSTMENT, TROUBLE_SHOOTING, SERVICING, AND MAINTENANCE OF EACH ITEM OF EQUIPMENT. .4 INSTRUCT PERSONNEL IN PHASES OF OPERATION AND MAINTENANCE USING OPERATION AND MAINTENANCE MANUALS AS BASIS OF INSTRUCTION. REVIEW CONTENTS OF MANUAL IN DETAIL TO EXPLAIN ASPECTS OF OPERATION AND MAINTENANCE. .5 ENSURE ADEQUATE AMOUNT OF TIME REQUIRED FOR INSTRUCTION OF EACH ITEM OF EQUIPMENT. EXHAUST FAN DISCONNECT SWITCH AND MOTOR STARTER BREAKER & BRANCH CCT. EXHAUST FAN CONTROLLER - MANUAL - - OFF - - AUTO - INTERLOCK EXHAUST FAN ON FOR MANUAL OR AUTO 24V 120V 15A, 120V/1PH BREAKER & BRANCH CCT. DAMPER MOTOR 24V 120V 15A, 120V/1PH BREAKER & BRANCH CCT. 24V 120V 15A, 120V/1PH BREAKER & BRANCH CCT. INTERLOCK DAMPER MOTOR OPEN FOR MANUAL OR AUTO SIGNAL FAN START-UP RELAY OUTPUT CO DETECTION TO EXHAUST FAN CONTROLLER SEQUENCE OF OPERATION MANUAL - DAMPER OPEN - EXHAUST FAN ON AUTO - GAS DETECTION ALARM - DAMPER OPEN - EXHAUST FAN ON EXHAUST SYSTEM - CONTROL SCHEMATIC GAS DETECTION CONTROLLER GAS DETECTION SENSOR/ TRANSMITTER CO 24V 120V EF-2A, EF-2B NOTES: MECHANICAL CONTRACTOR SHALL SUPPLY EQUIPMENT ELECTRICAL CONTRACTOR SHALL WIRE AND CONNECT ALL EQUIPMENT GAS DETECTION SENSOR/ TRANSMITTER NO2 24V 120V 24V 120V 24V 120V SENSOR/TRANSMITTER OUTPUT TO GAS DETECTION CONTROLLER GAS DETECTION SENSOR/ TRANSMITTER CO GAS DETECTION SENSOR/ TRANSMITTER NO2 24V 120V GAS DETECTION SENSOR/ TRANSMITTER CO (MAIN. PIT) REV DATE: Drawing No.: 12/3/2020 MECHANICAL NOTES & LEGENDS MM MM MP 2020-04-27 AS SHOWN - M1 Project Title: Township of South Glengarry MUNICIPAL GARAGE FACILITY ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COP<RIGHT PROPERT< OF THE ENGINEER AND MUST BE RETURNED UPON RE4UEST. REPRODUCTION OF DRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTS IN PART OR WHOLE IS FORBIDDEN WITHOUT THE ENGINEERS WRITTEN PERMISSION. THE CONTRACTOR MUST CHECK AND VERIF< ALL DIMENSIONS ON THE -OB PRIOR TO START OF CONSTRUCTION. DRAWINGS ARE NOT TO BE SCALED Revisions Date By No. Telephone: (613) 499-2077 68 William St. Suite 200 Brockville, Ont. 0 MP 2020-12-01 FOR REVIEW 1 MP 2020-12-03 ISSUED FOR TENDER
Transcript
  • 12x8

    R

    8"Ø

    12x8

    RASA SUPPLY AIR

    RETURN AIR

    R - RISE, D - DROP

    DUCT SIZE, RECTANGULAR,

    FLEXIBLE CONNECTION

    ELBOW, RECTANGULAR(r=1.5W)

    ACOUSTICAL INSULATION LINING

    HVAC LEGEND

    DUCT SIZE, ROUND

    DUCT SECTION, SUPPLY

    DUCT SECTION, RETURN OR EXHAUST

    CHANGE OF ELEVATION

    FIRST FIGURE IS SIDE SHOWN

    MAEA EXHAUST AIR

    MAKE-UP AIR

    R - RISE, D - DROPCHANGE OF ELEVATIONAD

    ACOUSTICAL INSULATION LINING

    Ex.OA OUTDOOR AIR

    EXISTING

    VD

    TEE, RECTANGULAR MAIN AND TAP,

    FOT - FLAT ON TOP, FOB - FLAT ON BOTTOM

    TEE, RECTANGULAR MAIN AND TAP

    VOLUME DAMPER

    TEE RECTANGULAR

    TRANSITIONS

    ELBOW, WITH VANES, RECTANGULAR(r=1.5W)

    WITH DAMPER

    ELBOW, WITH VANES, RECTANGULAR

    WYE, RECTANGULAR

    TYPE

    CFM

    SIZECEILING OR REGISTER DESIGNATION

    CEILING RETURN GRILLE

    FD

    WALL SUPPLY GRILLE OR REGISTER

    FIRE DAMPER

    WALL EXHAUST/RETURN GRILLE OF REGISTER

    CEILING SUPPLY DIFFUSER

    24"x24"'S1' 100

    T

    H

    THERMOSTAT

    HUMIDISTAT

    C CONTROLLER, AS INDICATED

    S THERMOSTAT REMOTE SENSOR

    FLOOR OR CEILING SUPPLY

    FLOOR OR CEILING EXHAUST/RETURN

    GRILLE OR REGISTER

    GRILLE OR REGISTER

    SAN

    PLUMBING LEGEND

    SS

    SS SS

    SV

    SD

    SD SD

    ABBREVIATIONSYMBOL DESCRIPTION

    SAN

    VENT

    STM

    STM

    WCO

    SANITARY DRAIN ABOVE FLOOR/GRADE

    SANITARY DRAIN BELOW FLOOR/GRADE

    SANITARY VENT

    STORM DRAIN ABOVE FLOOR/GRADE

    STORM DRAIN BELOW FLOOR/GRADE

    WALL CLEANOUT

    FCO FLOOR CLEANOUT

    SS SS LCO LINE CLEANOUT

    GCO GRADE CLEANOUT

    DCW DOMESTIC COLD WATER

    DHW DOMESTIC HOT WATER

    oo oo STANDPIPE-

    DHWR DOMESTIC HOT WATER RETURN

    GAS NATURAL GASGAS

    MECHANICAL NOTES

    MECHANICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS FOR THIS PROJECT.

    1 GENERAL:.1 CONFORM WITH APPLICABLE REQUIREMENTS OF THE MINISTRY OF LABOUR, AND THE OCCUPATIONAL HEALTH

    AND SAFETY ACT AND REGULATIONS FOR CONSTRUCTION PROJECTS..2 DO COMPLETE INSTALLATION IN ACCORDANCE WITH THE FOLLOWING:

    .1 ONTARIO BUILDING CODE (OBC); .2 NATURAL GAS AND PROPANE INSTALLATION CODE (GAS CODE); .3 ASHRAE; .4 SMACNA; .5 NFPA; .6 ALL OTHER RELEVANT CODES AND STANDARDS, AS APPLICABLE.

    .3 OBTAIN ALL PERMITS REQUIRED FOR THE INSTALLATION OF MECHANICAL TRADES WORK, ARRANGE FOR INSPECTIONS AND TESTS, AND PAY ALL FEES AND COSTS FOR THE PERMITS, INSPECTIONS AND FEES. OBTAIN PERMITS IMMEDIATELY AFTER NOTIFICATION OF AWARD OF CONTRACT.

    .4 PROVIDE THREE COPIES OF COMPLETE OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT FURNISHED UNDER THIS CONTRACT. BIND INSTRUCTIONS IN 3-RING BINDERS. INCLUDE THE FOLLOWING: .1 SCHEMATIC DIAGRAM OF ELECTRICAL SYSTEMS. .2 CONTROL SHOP DRAWINGS AND OPERATING SEQUENCE INCLUDING WIRING OF COMPONENTS. .3 WIRING DIAGRAM OF CONTROL PANELS. .4 OPERATING INSTRUCTIONS, INCLUDING START-UP AND SHUT-DOWN PROCEDURE. .5 MAINTENANCE INSTRUCTIONS INCLUDING PREVENTIVE MAINTENANCE INSTRUCTIONS FOR COMPONENTS OF THE

    EQUIPMENT. .6 COMPLETE PARTS LIST OF ASSEMBLIES AND THEIR COMPONENT PARTS, SHOWING MANUFACTURER'S NAME, CATALOGUE

    NUMBER, AND NEAREST REPLACEMENT SOURCE. .7 LIST OF RECOMMENDED SPARE PARTS AND QUANTITY OF EACH ITEM TO BE STOCKED. .8 MANUFACTURERS' WARRANTIES AND GUARANTEES.

    .5 CLEAN ALL MECHANICAL SYSTEMS AT PROJECT COMPLETION.

    .6 COMPLETE AS-BUILT DRAWINGS SHOWING ALL CHANGES AS WORK PROGRESSES.

    2 CONTRACTOR QUALIFICATIONS:.1 ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE “TRADE QUALIFICATION AND APPRENTICESHIP ACT”

    AND REGULATIONS, BY PERSONS WHO HOLD THE FOLLOWING CERTIFICATES OF QUALIFICATION (AS APPLICABLE): .1 PLUMBER; .2 REFRIGERATION & AIR CONDITIONING SYSTEMS MECHANIC; .3 RESIDENTIAL AIR CONDITIONING SYSTEMS MECHANIC; .4 SHEET METAL WORKER.

    .2 ALL FUELS-RELATED WORK TO BE CARRIED OUT IN ACCORDANCE WITH TSSA REQUIREMENTS AND ONTARIO REGULATION 215/01, “FUEL INDUSTRY CERTIFICATES” BY PERSONS WHO HOLD THE APPROPRIATE CERTIFICATES FOR THE WORK BEING PERFORMED.

    3 EXISTING FACILITIES AND DEMOLITION:.1 LOCATE AND PROTECT ALL EXISTING EXTERIOR SITE SERVICES..2 RETAIN AND PROTECT ALL EXISTING INTERIOR SERVICES AND BUILDING FABRIC. MAKE GOOD ANY AND ALL DAMAGE RESULTING

    FROM THIS WORK.

    4 FIXTURES AND EQUIPMENT:.1 PROVIDE SHOP DRAWINGS AND PRODUCT DATA FOR ALL MECHANICAL FIXTURES AND EQUIPMENT FOR APPROVAL, PRIOR TO

    PROCUREMENT..2 INSTALL ALL MECHANICAL FIXTURES AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S

    INSTRUCTIONS..3 LOCATE ALL EQUIPMENT WITH CLEARANCES, AS REQUIRED BY THE MANUFACTURER, THE FUEL CODES, AND ALL

    OTHER CODES AND REGULATIONS, INCLUDING THE FOLLOWING CLEARANCES: .1 TO PERMIT PROPER EQUIPMENT OPERATION; .2 TO PERMIT SUFFICIENT AIRFLOW AROUND EQUIPMENT; .3 FOR EQUIPMENT SERVICE; .4 SUFFICIENT DISTANCE FROM COMBUSTIBLE MATERIAL; .5 WITH SUFFICIENT VENT CLEARANCES; .6 SUFFICIENT DISTANCE FROM ROOF EDGES OR OTHER HAZARDS; .7 SERVICE PLATFORMS FOR APPLIANCES INSTALLED 10 FT OR MORE ABOVE FLOOR; .8 WITH FIXED ACCESS TO ROOF FOR BUILDING HEIGHT GREATER THAN 13', AND STAIRWAY ACCESS TO ROOF GREATER THAN 26'.

    5 EQUIPMENT SUPPLIED BY OTHERS:.1 MAKE ALL MECHANICAL SERVICE CONNECTIONS TO EQUIPMENT SUPPLIED BY OTHERS..2 CONFIRM ALL SERVICE CONNECTIONS WITH MANUFACTURER AND SUPPLIER, PRIOR TO INSTALLATION. THIS SHALL INCLUDE ALL

    CONNECTION SIZES, LOCATIONS AND DETAILS, AND SHALL TAKE INTO ACCOUNT EQUIPMENT CLEARANCES AND INSTALLATIONREQUIREMENTS.

    6 PIPING AND ESCUTCHEONS:.1 PROVIDE DIELECTRIC UNIONS AT ALL PIPING LOCATIONS WHERE DISSIMILAR METALS ARE JOINED..2 PROVIDE ESCUTCHEONS ON ALL PIPES PASSING THROUGH WALLS, PARTITIONS, FLOORS AND CEILINGS,

    CHROME, NICKEL PLATED BRASS OR TYPE 302 STAINLESS STEEL.

    7 ACCESS DOORS:.1 SUPPLY ACCESS DOORS, AS REQUIRED IN DUCTWORK AND WALL/CEILING ASSEMBLIES, TO ALL CONCEALED MECHANICAL

    EQUIPMENT AND OPERATING DEVICES. ACCESS DOORS IN WALL/CEILING ASSEMBLIES TO BE INSTALLED BY OTHER TRADES..2 ACCESS DOORS SHALL BE FIRE-RATED TYPE, WHERE USED IN FIRE-RATED ASSEMBLIES, AND SHALL MATCH THE RATING OF THE

    ASSEMBLY.

    8 PIPE INSULATION:.1 INSTALL IN ACCORDANCE WITH THERMAL INSULATION ASSOCIATION OF CANADA (TIAC) NATIONAL STANDARDS..2 MAX. FLAME SPREAD RATING: 25..3 MAX. SMOKE DEVELOPED RATING: 50..4 DOMESTIC COLD WATER (DCW):

    .1 1” RIGID MOULDED MINERAL FIBRE WITH VAPOUR RETARDER JACKET. .2 INSULATE ALL PIPING IN FLOORS, WALLS AND CEILINGS, TO POINT OF FIXTURE CONNECTIONS.

    .5 DOMESTIC HOT WATER (DHW): .1 1” RIGID MOULDED MINERAL FIBRE FOR PIPING UP TO 1-1/4” SIZE. .2 INSULATE ALL PIPING IN FLOORS, WALLS AND CEILINGS, TO POINT OF FIXTURE CONNECTIONS.

    .6 OUTER JACKET: .1 CONCEALED LOCATIONS: ALL SERVICE JACKET.

    .2 EXPOSED LOCATIONS: PVC JACKET. .3 MECHANICAL/SERVICE ROOMS: PVC JACKET.

    9 WATER SERVICE AND WATER SUPPLY PIPING:.1 SUBMERSIBLE WELL PUMP: BLACK POLYETHYLENE PIPE, 150 PSI..2 ABOVE GROUND: COPPER TUBE, HARD DRAWN, TYPE L. CAN. OR US MANUFACTURE, INCLUDING FITTINGS. LEAD-FREE SOLDER..3 WATER SUPPLY PIPING IS SHOWN SCHEMATICALLY. ALL PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED..4 INSTALL TUBING CLOSE TO BUILDING STRUCTURE TO MINIMIZE FURRING, CONSERVE HEADROOM AND SPACE. GROUP EXPOSED

    PIPING AND RUN PARALLEL TO WALLS..5 ISOLATE ALL EQUIPMENT, FIXTURES AND BRANCHES WITH VALVES..6 TEST WATER SYSTEM AT 1½ TIMES SYSTEM OPERATING PRESSURE OR MINIMUM 860 KPA, WHICHEVER IS GREATER. TEST

    PRESSURE AND TIMEFRAME SHALL BE AS REQUIRED BY OBC 7.3.7.2..7 FLUSH OUT, DISINFECT AND RINSE SYSTEM, PRIOR TO CONSTRUCTION COMPLETION..8 WATER HEATERS:

    .1 SHALL BE PIPED WITH HEAT TRAPS ON THE INLET AND OUTLET PIPING, AS CLOSE AS PRACTICAL TO THE TANK, IN ACCORDANCEWITH OBC 12.3.1.4.

    .2 TEMPERATURE AND PRESSURE RELIEF VALVES: .1 MAXIMUM TEMPERATURE SETTING OF 210F (99F); .2 MAXIMUM PRESSURE SETTING OF 150 PSI; .3 DISCHARGE PER OBC 7.6.1.12.:

    .1 TERMINATE WITH AN INDIRECT CONNECTION PIPED TO FLOOR DRAIN, SUMP OR OTHER SAFE LOCATION, WITH A 300mm AIR BREAK; OR

    .2 TERMINATE AT A DISTANCE NOT LESS THAN 150mm AND NOT MORE THAN 300mm FROM A FLOOR AND DISCHARGE VERTICALLY DOWN,

    .9 TRAP SEAL PRIMERS AND ACCESS TO THEM, SHALL BE LOCATED IN THE WASHROOM OR AREA THAT THEY SERVE.

    .10 SUPPLY AND INSTALL WATER HAMMER ARRESTORS AT THE MIDPOINT AND END OF RUNS OF WATER SUPPLY PIPING AS REQUIRED BY OBC 7.6.1.14.

    10 DRAINAGE, WASTE AND VENT PIPING:.1 COORDINATE SANITARY SERVICE INSTALLATIONS WITH SUPPLY AUTHORITY..2 APPROXIMATE SUB-FLOOR PIPING ELEVATIONS HAVE BEEN INDICATED ON THE DRAWINGS. GENERAL CONTRACTOR SHALL BE

    RESPONSIBLE FOR SETTING FINAL INVERTS BASED ON SITE CONDITIONS..3 BELOW GROUND/FLOOR:

    .1 ABS DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.1. .2 PVC DWV, TYPE SDR26 SDR35.

    .4 ABOVE GROUND: .1 PVC DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.2, FOR NONCOMBUSTIBLE CONSTRUCTION

    (FLAME-SPREAD RATING NOT MORE THAN 25 PER CAN/ULC-S102.2). .2 PVC DWV SOLID WALL SCHEDULE 40, CERTIFIED TO CAN/CSA STANDARD B181.2, FOR NONCOMBUSTIBLE CONSTRUCTION

    (FLAME-SPREAD RATING NOT MORE THAN 25 AND SMOKE DEVELOPED CLASSIFICATION NOT MORE THAN 50 PER CAN/ULC-S102.2 - PLENUMS).

    .5 PROVIDE CLEANOUTS AS REQUIRED BY THE ONTARIO BUILDING CODE.

    .6 VENT COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH THE ONTARIO BUILDING CODE.

    11 PROPANE GAS PIPING:.1 COORDINATE PROPANE SERVICE INSTALLATION WITH SUPPLY AUTHORITY..2 STEEL PIPE, SCHEDULE 40, SEAMLESS, SCREWED FITTINGS..3 TEST SYSTEM IN ACCORDANCE WITH NATURAL GAS AND PROPANE INSTALLATION CODE.

    12 DUCTWORK:.1 RECTANGULAR DUCT:

    .1 RIGID GALVANIZED STEEL, LOCK FORMING QUALITY TO ASTM A653/A653M .2 THICKNESS, FABRICATION, REINFORCEMENT AND SUPPORT/ATTACHMENT TO ASHRAE OR SMACNA.

    .2 ROUND DUCT: .1 RIGID GALVANIZED STEEL, LOCK FORMING QUALITY TO ASTM A653/A653M .2 THICKNESS, FABRICATION, REINFORCEMENT AND SUPPORT/ATTACHMENT TO ASHRAE OR SMACNA. .3 FLEXIBLE BRANCH DUCT (PERMITTED WITHIN 2m/6ft FROM OUTLET):

    .1 ALL METAL TYPE: TRIPLE LOCK, ALUMINUM CORRUGATED DUCT, MANUFACTURED USING AN ALUMINUM STRIP, WHICH IS SPIRALLY WOUND AND MECHANICALLY JOINED TOGETHER FORMING AN AIR TIGHT AND LEAKPROOF SEAM.

    .3 SEAL CLASSIFICATION: .1 CLASS A: LONGITUDINAL SEAMS, TRANSVERSE JOINTS, DUCT WALL PENETRATIONS AND CONNECTIONS MADE AIRTIGHT

    WITH SEALANT AND TAPE.

    .4 FITTINGS .1 FABRICATION: TO SMACNA. .2 RADIUSED ELBOWS.

    .1 RECTANGULAR: STANDARD WITH CENTRELINE RADIUS 1.5 TIMES DUCT DIMENSION, WITH SINGLE THICKNESS TURNING VANES.

    .2 ROUND: FIVE PIECE WITH CENTRELINE RADIUS 1.5 TIMES DIAMETER. .3 MITRED ELBOWS, RECTANGULAR: WITH DOUBLE THICKNESS TURNING VANES.

    5 BRANCHES: .1 RECTANGULAR MAIN AND BRANCH: WITH RADIUS ON BRANCH 1.5 TIMES WIDTH OF DUCT 45

    DEGREES ENTRY ON BRANCH. .2 ROUND MAIN AND BRANCH: ENTER MAIN DUCT AT 45 DEGREES WITH CONICAL CONNECTION. .3 PROVIDE VOLUME CONTROL DAMPER IN BRANCH DUCT NEAR CONNECTION TO MAIN DUCT. .4 MAIN DUCT BRANCHES: WITH SPLITTER DAMPER.

    .6 TRANSITIONS: .1 DIVERGING: 20 DEGREES MAXIMUM INCLUDED ANGLE. .2 CONVERGING: 30 DEGREES MAXIMUM INCLUDED ANGLE.

    .7 FIRE STOPPING .1 RETAINING ANGLES AROUND DUCT, ON BOTH SIDES OF FIRE SEPARATION IN ACCORDANCE WITH

    SECTION. .2 FIRE STOPPING MATERIAL AND INSTALLATION MUST NOT DISTORT DUCT.

    .8 DAMPERS: .1 MANUFACTURE TO SMACNA STANDARDS. .2 SINGLE BLADE DAMPERS:

    .1 FABRICATE FROM SAME MATERIAL AS DUCT, BUT ONE SHEET METAL THICKNESS HEAVIER. V_GROOVE STIFFENED. .2 SIZE AND CONFIGURATION TO RECOMMENDATIONS OF SMACNA. .3 LOCKING QUADRANT (WITH SHAFT EXTENSION TO ACCOMMODATE INSULATION THICKNESS, IF REQUIRED). .4 INSIDE AND OUTSIDE NYLON END BEARINGS. .5 CHANNEL FRAME OF SAME MATERIAL AS ADJACENT DUCT, COMPLETE WITH ANGLE STOP.

    .9 DUCT LEAKAGE: IN ACCORDANCE WITH SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL.

    .10 ALL DUCT AND SEAL MATERIALS TO HAVE A FLAME SPREAD RATING OF LESS THAN 25 AND A SMOKE DEVELOPED CLASSIFICATIONOF LESS THAN 50.

    .11 PAINT VISIBLE INTERIOR SURFACES OF ALL PLENUM BOXES MATTE BLACK.

    .12 PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT DUCT CONNECTION POINTS.

    13 DUCT INSULATION:.1 REFER TO DRAWING FOR DUCT THAT IS IDENTIFIED TO BE INSULATED..2 INSTALL IN ACCORDANCE WITH THERMAL INSULATION ASSOCIATION OF CANADA (TIAC) NATIONAL STANDARDS..3 MAX. FLAME SPREAD RATING: 25..4 MAX. SMOKE DEVELOPED RATING: 50..5 THERMAL INSULATION - RECTANGULAR DUCT:

    .1 1” (R4.3) RIGID MINERAL FIBRE BOARD WITH VAPOUR RETARDER JACKET.

    .2 ALUMINUM JACKET WITH MOISTURE BARRIER..6 THERMAL INSULATION - ROUND DUCT:

    .1 1” (R3.1) MINERAL FIBRE BLANKET WITH VAPOUR RETARDER JACKET.

    .2 ALUMINUM JACKET WITH MOISTURE BARRIER..7 ACOUSTIC DUCT LINING:

    .1 1” (R4.3) ACOUSTIC QUALITY MINERAL FIBRE DUCT LINER, WITH MAT FACING, BACTERIA AND FUNGUS RESISTANT.

    .2 FASTEN TO INTERIOR SHEET METAL SURFACE WITH 100% COVERAGE OF ADHESIVE AND 5/16” WELDPINS NOT LESS THAN 2 ROWS PER SURFACE AND NOT MORE THAN 16 IN ON CENTRES.

    .3 SEAL BUTT JOINTS, EXPOSED EDGES, WELD PIN AND CLIP PENETRATIONS AND DAMAGED AREAS OF LINER WITH 2” JOINTTAPE AND SEALER.

    14 MECHANICAL FIRE PROTECTION:.1 REFER TO ARCHITECTURAL DRAWINGS, TO VERIFY LOCATION OF ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES..2 ALL PIPING SHALL BE TIGHTLY FITTED AND SEALED WITH FIRESTOPPING MATERIAL AT ALL FIRE SEPARATIONS AND FIRE-RATED

    MEMBRANES..3 FIRE DAMPERS:

    .1 FIRE DAMPERS SHALL BE CAN/ULC-S112 (STANDARD METHOD OF FIRE TEST OF FIRE DAMPER ASSEMBLIES) LISTED ANDLABELLED.

    .2 FIRE DAMPERS SHALL BE NFPA 80 (STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES), NFPA 90A (STANDARDFOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS), AND NFPA 101 (LIFE SAFETY CODE)COMPLIANT.

    .3 DUCTWORK SHALL BE FITTED WITH FIRE DAMPERS AT ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES.

    .4 SUPPLY AND INSTALL ACCESS DOORS IN ARCHITECTURAL FINISH (WALL, CEILING OR FLOOR) TO ACCESS DUCT, IN COMMONAREA WHERE POSSIBLE.

    .5 SUPPLY AND INSTALL TIGHTLY-FITTED ACCESS DOOR IN DUCT TO ACCESS, INSPECT AND RESET FIRE DAMPER.

    .6 TYPES: DYNAMIC - FOR USE IN AIR HANDLING SYSTEMS THAT DO NOT SHUTDOWN UPON FIRE ALARM.

    .7 RATING: 1-1/2 HR (30MIN TO 2HR FIRE RESISTANCE RATING)..4 ALL MECHANICAL MATERIALS USED WITHIN CEILING RETURN AIR PLENUMS SHALL FLAME-SPREAD RATING NOT MORE THAN 25

    AND SMOKE DEVELOPED CLASSIFICATION NOT MORE THAN 50 PER CAN/ULC-S102.2..5 MOCK-UPS:

    .1 PREPARE MOCK-UPS OF TYPICAL FIRESTOP INSTALLATION OF THE FOLLOWING, FOR REVIEW AND APPROVAL BY THEOWNER, ENGINEER AND MUNICIPAL BUILDING INSPECTOR:

    .1 SANITARY PIPING - WALL AND CEILING/FLOOR FIRE SEPARATION; .2 DCW AND DHW PIPING - WALL AND CEILING/FLOOR FIRE SEPARATION;

    .3 FIRE DAMPER INSTALLATION - WALL AND CEILING/FLOOR FIRE SEPARATION..2 ALL FIRESTOP INSTALLATIONS SHALL BE COMPLETED IN ACCORDANCE WITH THE APPROPRIATE PRODUCT INSTALLATION

    INSTRUCTIONS, AND THE REFERENCED UL/ULC LISTING AND/OR TEST STANDARD..3 SUPPLY A COPY OF THE PRODUCT INSTALLATION INSTRUCTIONS WITH ULC LISTING AND/OR TEST STANDARD REFERENCE,

    FOR EACH INSTALLATION..4 MOCK-UP MAY REMAIN AS PART OF WORK.

    15 EQUIPMENT IN HAZARDOUS LOCATIONS:.1 THE GARAGE AREA, AND ADJACENT ROOMS, UP TO A LEVEL OF 50mm ABOVE THE FLOOR SHALL BE CONSIDERED A CLASS I

    (FLAMMABLE GASES OR VAPOURS) ZONE 2 LOCATION..2 ALL EQUIPMENT USED WITHIN THE AREA SHALL BE APPROVED FOR THE CLASSIFICATION.

    16 MECHANICAL IDENTIFICATION:.1 IDENTIFY MECHANICAL EQUIPMENT WITH LAMICOID NAMEPLATES..2 LABEL ALL PIPING AT LEAST ONCE IN EVERY ROOM, AND AT NO MORE THAN 25 FT CENTERS.

    17 EARTHQUAKE LOAD:.1 ALL MECHANICAL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE EARTHQUAKE LOAD AND EFFECTS REQUIRED BY THE

    ONTARIO BUILDING CODE..2 MECHANICAL ELEMENTS AND COMPONENTS (EQUIPMENT, PIPES, DUCTS, ETC.), AND THEIR CONNECTIONS TO THE BUILDING

    SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE SMACNA/ANSI SEISMIC RESTRAINT MANUAL OR OTHER GUIDELINEREFERENCED IN THE ONTARIO BUILDING CODE.

    .3 PROVIDE SHOP DRAWINGS FOR SUPPORT, CONNECTIONS AND SEISMIC RESTRAINT OF ALL MECHANICAL EQUIPMENT, PIPES ANDDUCTS, INCLUDING, BUT NOT LIMITED TO:.1 FURNACES AND ENERGY RECOVERY VENTILATORS;.2 CONDENSING;.3 INFRARED HEATERS;.4 TYPICAL DUCT SUPPORTING SYSTEM;.5 TYPICAL SAN, DCW, DHW PIPE SUPPORTING SYSTEM;.6 TYPICAL PROPANE PIPE SUPPORTING SYSTEM.THESE SHOP DRAWINGS SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER IN THE PROVINCE OF ONTARIO, WITHEXPERIENCE IN SEISMIC ENGINEERING.

    18 EQUIPMENT AND MATERIALS SUPPORT:.1 ALL MECHANICAL EQUIPMENT, PIPING, DUCTWORK, AND RELATED ITEMS SHALL BE SECURELY SUPPORTED, ATTACHED AND

    FASTENED TO BUILDING STRUCTURE..2 PIPE HANGERS AND SUPPORTS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH MSS STANDARD SP-58, PIPE

    HANGERS AND SUPPORTS - MATERIALS, DESIGN, MANUFACTURE, SELECTION, APPLICATION, AND INSTALLATION.

    19 COORDINATION:.1 INFORMATION INVOLVING ACCURATE DIMENSIONING OF THE BUILDING SHALL BE TAKEN FROM SITE BY CONTRACTOR..2 DRAWINGS ARE IN DIAGRAMMATIC FORM, INTENDED TO CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT FOR

    EQUIPMENT. COORDINATE PHYSICAL LOCATION OF ALL EQUIPMENT WITH OTHER TRADES AND ALLOW FOR ANY ADDITIONALPIPING, DUCTING, FITTINGS, SUPPORTS, ETC., IN ORDER TO AVOID INTERFERENCE AND FACILITATE THE WORK.

    .3 CONTRACTOR TO MAKE ANY NECESSARY MODIFICATIONS OR ADDITIONS, WITHOUT CHARGE, TO ACCOMMODATE SITECONDITIONS AND COORDINATION.

    .4 COORDINATE ALL MECHANICAL EQUIPMENT WIRING, INCLUDING LOW VOLTAGE CONTROL WIRING, WITH ELECTRICAL TRADES.

    20 START-UP, COMMISSIONING AND TRAINING:.1 COMMISSIONING:

    .1 START-UP AND COMMISSION THE FOLLOWING SYSTEMS:.1 PLUMBING FIXTURES;.2 HVAC;.3 GAS DETECTION AND EXHAUST SYSTEM.

    .2 PERFORM SYSTEMATIC TESTS, PROCEDURES AND CHECKS ON SYSTEMS, AS FOLLOWS:.1 TO VERIFY OPERATION IN ACCORDANCE WITH CONTRACT DOCUMENTS, DESIGN CRITERIA aND INTENT, AND

    MANUFACTURER'S REQUIREMENTS;.2 TO ENSURE APPROPRIATE DOCUMENTATION IS PROVIDED;.3 TO EFFECTIVELY TRAIN BUILDING OPERATIONAL STAFF.

    .3 SYSTEMS ARE TO BE OPERATED AT FULL CAPACITY, WITH CORRECTION OF ALL DEFICIENCIES AND ADJUSTMENTS TO MEETOPTIMUM PERFORMANCE.

    .4 PROVIDE WRITTEN REPORT AT END OF COMMISSIONING OUTLINING EQUIPMENT OPERATIONAL CONDITIONS ANDPARAMETERS.

    .2 TESTING, ADJUSTING AND BALANCING:.1 TEST, ADJUST AND BALANCE (TAB) ALL PLUMBING AND HVAC EQUIPMENT AND SYSTEMS; INCLUDING THE FOLLOWING:

    .1 FURNACES;

    .2 CONDENSING UNITS;

    .3 ENERGY RECOVERY VENTILATORS..2 TAB PROCEDURE SHALL BE COMPLETED IN ACCORDANCE WITH ASHRAE STANDARD 111, MEASUREMENT, TESTING,

    ADJUSTING AND BALANCING OF BUILDING HVAC SYSTEMS..3 PROVIDE DETAILED REPORT AT END OF TAB, IN ACCORDANCE WITH THE REPORTING PROCEDURES OF ASHRAE STANDARD

    111..3 DEMONSTRATION AND TRAINING:

    .1 DEMONSTRATE OPERATION AND MAINTENANCE OF EQUIPMENT AND SYSTEMS TO OWNER'S PERSONNEL ONE WEEK PRIORTO DATE OF FINAL INSPECTION

    .2 PRIOR TO DEMONSTRATION AND TRAINING, ENSURE THAT EQUIPMENT HAS BEEN INSPECTED AND PUT INTO OPERATION,INCLUDING COMPLETION OF COMMISSIONING AND TESTING, ADJUSTING, AND BALANCING.

    .3 DEMONSTRATE START_UP, OPERATION, CONTROL, ADJUSTMENT, TROUBLE_SHOOTING, SERVICING, AND MAINTENANCEOF EACH ITEM OF EQUIPMENT.

    .4 INSTRUCT PERSONNEL IN PHASES OF OPERATION AND MAINTENANCE USING OPERATION AND MAINTENANCE MANUALSAS BASIS OF INSTRUCTION. REVIEW CONTENTS OF MANUAL IN DETAIL TO EXPLAIN ASPECTS OF OPERATION ANDMAINTENANCE.

    .5 ENSURE ADEQUATE AMOUNT OF TIME REQUIRED FOR INSTRUCTION OF EACH ITEM OF EQUIPMENT.

    EXHAUST FAN

    DISCONNECTSWITCH

    ANDMOTOR

    STARTER

    BREAKER &BRANCH CCT.

    EXHAUST FANCONTROLLER

    - MANUAL -- OFF -

    - AUTO -

    INTERLOCKEXHAUST

    FAN ONFOR MANUAL

    OR AUTO

    24V

    120V

    15A, 120V/1PHBREAKER &

    BRANCH CCT.

    DAMPERMOTOR

    24V

    120V

    15A, 120V/1PHBREAKER &

    BRANCH CCT.

    24V

    120V

    15A, 120V/1PHBREAKER &

    BRANCH CCT.

    INTERLOCKDAMPER MOTOR OPENFOR MANUAL OR AUTOSIGNAL FAN START-UP

    RELAY OUTPUTCO DETECTIONTO EXHAUST FANCONTROLLER

    SEQUENCE OF OPERATION

    MANUAL - DAMPER OPEN- EXHAUST FAN ON

    AUTO - GAS DETECTION ALARM - DAMPER OPEN - EXHAUST FAN ON

    EXHAUST SYSTEM - CONTROL SCHEMATIC

    GASDETECTION

    CONTROLLER

    GASDETECTION

    SENSOR/TRANSMITTER

    CO

    24V

    120V

    EF-2A, EF-2B

    NOTES:MECHANICAL CONTRACTOR SHALL SUPPLY EQUIPMENTELECTRICAL CONTRACTOR SHALL WIRE AND CONNECTALL EQUIPMENT

    GASDETECTION

    SENSOR/TRANSMITTER

    NO2

    24V

    120V

    24V

    120V

    24V

    120V

    SENSOR/TRANSMITTEROUTPUT TOGAS DETECTION CONTROLLER

    GASDETECTION

    SENSOR/TRANSMITTER

    CO

    GASDETECTION

    SENSOR/TRANSMITTER

    NO2

    24V

    120V

    GASDETECTION

    SENSOR/TRANSMITTER

    CO(MAIN. PIT)

    REV DATE:

    Drawing No.:

    12/3/2020

    MECHANICALNOTES & LEGENDS

    MM

    MM

    MP

    2020-04-27

    AS SHOWN

    -M1

    Project Title:

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COP RIGHTPROPERT OF THE ENGINEER AND MUST BE RETURNED UPON RE UEST.

    REPRODUCTION OF DRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTS INPART OR WHOLE IS FORBIDDEN WITHOUT THE ENGINEERS WRITTEN PERMISSION.

    THE CONTRACTOR MUST CHECK AND VERIF ALL DIMENSIONS ON THE OB PRIORTO START OF CONSTRUCTION.

    DRAWINGS ARE NOT TO BE SCALED

    RevisionsDateByNo.

    Telephone: (613) 499-207768 William St. Suite 200Brockville, Ont.

    0 MP 2020-12-01 FOR REVIEW

    1 MP 2020-12-03 ISSUED FOR TENDER

  • ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHTPROPERTY OF THE ENGINEER AND MUST BE RETURNED UPON REQUEST.

    REPRODUCTION OF DRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTS INPART OR WHOLE IS FORBIDDEN WITHOUT THE ENGINEERS' WRITTEN PERMISSION.

    THE CONTRACTOR MUST CHECK AND VERIFY ALL DIMENSIONS ON THE JOB PRIORTO START OF CONSTRUCTION.

    DRAWINGS ARE NOT TO BE SCALED

    RDBN .

    T W S . S

    B , O .

    REV DATE

    D N .

    MECHANICALNOTES & LEGENDS

    MM

    MM

    MP

    AS SHOWN

    M2

    P T

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    MP FOR REVIEW

    MP ISSUED FOR TENDER

  • UP - FUTURE STAIR

    PROVIDE PRE-FRAMING

    SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS

    BUILDINGSAN. CLEANOUTAPPROX. INV. 96.95 FT

    4" SAN @ 1:100REFER TO SITE PLAN

    OIL INTERCEPTORWITH STRUCTURAL STEEL COVERVENT IN ACCORDANCE WITH OBC & MFR REQ'MENTS

    APPROX. INV. AT OILINTERCEPTOR 97.40 FT.

    SS INT-1FD-1

    FCO

    SSSS

    FCO

    SS

    WH-1WATER HEATER- 1" DCW (INSUL) WITH UNION & ISOLATING VALVE- 1" DHW (INSUL) WITH UNION & ISOLATING VALVE- TEMP/PRESS RELIEF VALVE PIPED TO FLOOR- MIXING VALVE & HEAT TRAP

    oooo

    oooo

    oooo

    oooo

    oooo

    FD-1

    FD-1

    WC-2

    LA-2

    LA-1

    WC-1

    4" SAN WITH BASECLEANOUT FROM

    MEZZANINE( FOR FUTURE)

    12" DCW (INSUL)

    12" DHW (INSUL)TO MEZZANINE FLOOR

    CW

    UV LIGHTWATER FILTER

    WATER SOFTENERPRESSURE TANK

    PT-1

    DCWFROM WELL

    OFFICE 1ABOARDROOM

    CORR

    MECH RM

    JAN

    UNIV W/R

    W/R

    STOCK ROOM

    CORR

    CORR

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oooo

    oo

    1" DCW (INSUL)3/4" DHW (INSUL)

    WITH VALVESON U/S OF CEILING

    1" DCW (INSUL)3/4" DHW (INSUL)WITH VALVESON U/S OF CEILING

    HY-1

    SF-1 SF-1SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS

    4" SAN @ 1:100 4" SAN @ 1:100FCOFCO

    APPROX.INV.98.00 FT.

    SF-1SF-1

    TRENCH DRAIN @ 1:100 TRENCH DRAIN @ 1:100

    SF-1

    APPROX.INV. OF TRENCH99.00 FT.

    TRENCH DRAIN @ 1:100 TRENCH DRAIN @ 1:100

    3/4" DCW (INSUL)3/4" DHW (INSUL)

    ON U/S OF CEILING

    3/4" DCW (INSUL)3/4" DHW (INSUL)ON U/S OF CEILING

    APPROX.INV. OF TRENCH

    99.00 FT.

    3/4" DHWR (INSUL)ON U/S OF CEILING

    FCOFCO

    APPROX. INV.OF TRENCH98.12 FT.

    APPROX. INV.OF TRENCH

    98.12 FT.

    SHUT-OFF VALVE &CIRCUIT BALANCINGVALVE

    SHUT-OFF VALVE &CIRCUIT BALANCING

    VALVE

    SF-1

    HY-1

    SCALE: 18" = 1'-0"

    MAIN FLOOR PLAN - PLUMBING

    SSSS

    FIN. FLR. ELEV.100.00 FT (ASSUMED)

    RP-1DHW RECIRC PUMP

    UP - FUTURE STAIR

    PROVIDE PRE-FRAMING

    F-1FURNACE

    - SA 19"x 16" (NOM) OFF UNIT ELBOW WITH TURNING VANES AND TRANSITION TO SUPPLY

    AIR MAIN DUCT- RA 22"x 15" (NOM) OFF UNIT

    WITH FILTER RACK AND FILTER ELBOW WITH TURNING VANES TO RETURN AIR MAIN DUCT

    - 1/2" GAS CONNECTION WITH UNION, ISOLATING VALVE AND DRIP LEG

    - COMBUSTION/VENTILATION AIR PIPED TO WALL TERMINATION- CONDENSATE DRAIN WITH PUMP PIPED TO SANITARY

    CU-1CONDENSING UNIT

    30.1 MCA, 240V/1PH

    D

    SA 20x10 SA 14x10

    D D DD

    DDD

    DDDD

    SA 14x10SA 10x10

    210S114x4

    210S114x4

    210S114x4

    210S114x4

    50S17x475S1

    7x4

    110S18x4

    140S18x4

    140S18x4

    110S18x4

    SA 3

    2x1

    0

    SA 12x4TO MEZZANINE WITH DAMPER SA 12x4

    TO MEZZANINEWITH DAMPER

    SA 12x4TO MEZZANINEWITH DAMPER

    EF-1EXHAUST FANEA10x4 DUCT (INSUL)TO EXTERIOR WALL CAP

    RA 22x10

    RA 1

    0x1

    0

    RA 16x10

    R112x8

    R18x6 R1

    10x8

    R116x16

    RA 18x12TO MEZZANINE WITH

    DAMPER

    ENERGY RECOVERY VENTILATOR- HRV SA 6" DIA. TO FURNACE RETURN AIR MAIN DUCT- HRV RA 6" DIA FROM FURNACE SUPPLY AIR MAIN DUCT- HRV OA 6" DIA. (INSUL) FROM EXTERIOR WALL TERMINATION- HRV EA 6" DIA. (INSUL) TO EXTERIOR WALL TERMINATION- CONDENSATE DRAIN PIPED TO SANITARY

    ERV-1

    OFFICE 1ABOARDROOM

    CORR

    MECH RM

    JAN

    UNIV W/RW/R

    STOCK ROOM

    CORR

    CORR

    EXHAUST FANMOUNT AT 12' AFF

    EF-2A EXHAUST FANMOUNT AT 12' AFF

    EF-2B

    EXHAUST FAN CONTROLLER EF-2A

    GAS DETECTION CONTROLLER

    GAS DETECTION SENSORS /TRANSMITTERS- CO AT 4' AFF- NO2 AT 1' BELOW CEILING

    EXHAUST FAN CONTROLLER EF-2B

    GAS DETECTION CONTROLLER

    GAS DETECTION SENSORS /TRANSMITTERS- CO AT 4' AFF- NO2 AT 1' BELOW CEILING

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS

    INFRARED RADIANT HEATER- 1/2" NAT. GAS CONNECTION WITHUNION, ISOLATING VALVE & DRIP LEG- VENT & COMB. AIR TO EXTERIORWALL TERMINATION

    IR-1

    36 x 24 EXHAUST AIR INLETMOUNTED AT 10' AFFWITH EXTERIOR LOUVER ANDINTERIOR MOTORIZED DAMPERINTERLOCK WITH EXHAUSTFAN EF-2A

    36 x 24 EXHAUST AIR INLETMOUNTED AT 10' AFF WITH

    EXTERIOR LOUVER ANDINTERIOR MOTORIZED DAMPER

    INTERLOCK WITH EXHAUST FANEF-2B

    1-1/2" PROPANE AT U/S OFGARAGE CEILING

    GAS DETECTION (EF-2A)- CO AT 4' AFF- NO2 AT 1' BELOW CEILING

    GAS DETECTION (EF-2B)- CO AT 4' AFF

    - NO2 AT 1' BELOW CEILING

    T

    GAS

    T

    PROPANE DOWNWALL TO LEVEL 1

    INFRARED RADIANT HEATER- 1/2" NAT. GAS CONNECTION WITHUNION, ISOLATING VALVE & DRIP LEG- VENT & COMB. AIR TO EXTERIORWALL TERMINATION

    IR-1

    GAS

    T

    1-1/2" PROPANE AT U/S OFGARAGE CEILING

    GAS DETECTION (EF-2B)CO IN MAINT. PIT

    2" PROPANE AT U/SOF GARAGE

    CEILING

    SCALE: 18" = 1'-0"

    MAIN FLOOR PLAN - HVAC

    TO PROPANE TANKS(REFER TO SITE PLAN)

    T

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    GAS

    114" PROPANE AT U/SOF GARAGE CEILING

    D

    SA 12x4TO MEZZANINEWITH DAMPER

    GASGAS WH-1WATER HEATER3

    4" GAS CONNECTION WITH UNION, ISOLATINGVALVE & DRIP LEGCOMB/VENT AIR TO WALL TERMINATION

    EF-1EXHAUST FANEA10x4 DUCT (INSUL)TO EXTERIOR WALL CAP

    A DRAWIN S, SPECIFICATIONS AND RE ATED DOCUMENTS ARE THE COP RI HTPROPERT OF THE EN INEER AND MUST BE RETURNED UPON RE UEST.

    REPRODUCTION OF DRAWIN S, SPECIFICATIONS, AND RE ATED DOCUMENTS INPART OR WHO E IS FORBIDDEN WITHOUT THE EN INEERS WRITTEN PERMISSION.

    THE CONTRACTOR MUST CHECK AND VERIF A DIMENSIONS ON THE JOB PRIORTO START OF CONSTRUCTION.

    DRAWIN S ARE NOT TO BE SCA ED

    RevisionsDateByNo.

    Telephone: (613) 499-207768 William St. Suite 200Brockville, Ont.

    REV DATE:

    Drawing No.:

    12/3/2020

    MECHANICALMAIN FLOOR PLANS

    MM

    MM

    MP

    2020-11-27

    AS SHOWN

    -M3

    Project Title:

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    0 MP 2020-12-01 FOR REVIEW

    1 MP 2020-12-03 ISSUED FOR TENDER

    AutoCAD SHX TextCD

  • OPEN TO BELOW

    FUTURE MEZZANINE

    FUTURE OFFICE / STORAGE AREA

    DOWN - FUTURE STAIR DOWN - FUTURE STAIR

    PROVIDE PRE-FRAMING

    175S212x4

    175S212x4

    175S212x4

    175S212x4

    SCALE: 14" = 1'-0"MEZZANINE FLOOR PLAN - HVAC

    R218x12

    4" SAN CAPPED FORFUTURE

    SF-1

    WATER SUPPLY - SCHEMATICSCALE: NTS

    SUBMERSIBLEWELL PUMP

    P-1

    INSTALL WATER PIPE ANDPOWER LINES IN BIG 'O' DUCT

    GRADE

    POLYETHYLENE PIPE100 PSI, TO C.A.S. B137.1

    114" POLYETHYLENE PIPEMIN. 1525mm COVER

    PITLESS ADAPTOR

    WELL SHALL MEET THEREQUIREMENTS OF THE

    ONTARIO WATERRESOURCES ACT &

    O.REG.903

    DRAIN VALVE

    PRESSURE SWITCH

    PRESSURE GAUGE

    PT-1PRESSURE

    TANK

    114" DCW

    114" DCWELECTRICAL POWERSUPPLIES

    PUMP CONTROL BOX

    ELECTRICAL POWER SUPPLYAND DISCONNECT SWITCH

    PARTICLE FILTER

    TODISTRIBUTION

    WATER SOFTENER

    UV LIGHT

    SOLENOID VALVE

    10M ANCHORS@ 24"c.c. (MAX.)

    4" Ø SAN. DRAIN W/ TRAPTO BE CONNECTEDTO EXISTING CATCH BASIN

    WATER LEVEL

    6" 2'-0" 6"

    3'-0"

    114"

    4"2"

    13

    4"

    CATCH BASIN DETAIL

    STEEL GRATE TO BE TYPE "B" ASMANUFACTURED BY BORDEN METALPRODUCTS OR APPROVED EQUALMAIN BARS TO BE 112"x

    316"

    10M CONTINUOUSAROUND PERIMETER

    10M BAR @ 12" c.c

    3'-0

    "

    24"x24" 'L' BARS @ 12" c.c( TYP @ CORNERS)

    PROVIDE WATER STOPAT ALL CONSTRUCTION

    JOINTS (TYP)

    ALL ANGLES TO BESHOP PRIMED & PAINTED

    NOTE:AS AN ALTERNATIVE, CONTRACTOR MAYPROVIDE A PRECAST CONCRETE CATCH BASIN,O.P.S.D. 705.10 WITH A CAST IRON, SQUAREFRAME AND FLAT GRATE, O.P.S.D. 400.20 INLIEU OF CAST IN PLACE CONCRETE CATCHBASIN.

    SAN. CLEANOUT

    134"x114"x

    316"

    STEEL ANGLE FRAME

    OIL INTERCEPTORINT-1

    TOP OFOIL INTERCEPTOR98.18 FT.

    APPROX.INV.97.40 FT.

    STRUCTURALSTEEL COVER

    21.8"±

    37.0"

    19.75"

    100 FT.

    TRENCH DETAIL

    ALL DRAWIN S, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COP RI HTPROPERT OF THE EN INEER AND MUST BE RETURNED UPON RE UEST.

    REPRODUCTION OF DRAWIN S, SPECIFICATIONS, AND RELATED DOCUMENTS INPART OR WHOLE IS FORBIDDEN WITHOUT THE EN INEERS WRITTEN PERMISSION.

    THE CONTRACTOR MUST CHEC AND VERIF ALL DIMENSIONS ON THE OB PRIORTO START OF CONSTRUCTION.

    DRAWIN S ARE NOT TO BE SCALED

    RevisionsDateByNo.

    Telephone: (613) 499-207768 William St. Suite 200Brockville, Ont.

    REV DATE:

    Drawing No.:

    12/3/2020

    MECHANICALMEZZANINE FLOOR PLAN

    MM

    MM

    MP

    2020-11-27

    AS SHOWN

    -M4

    Project Title:

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    0 MP 2020-12-01 FOR REVIEW

    1 MP 2020-12-03 ISSUED FOR TENDER

  • P-1

    ELECTRICAL LEGEND

    DESIGNATIONS

    DISTRIBUTION

    M

    3

    M

    NOTE: HEIGHT IS FROM FINISHED FLOOR TO CENTRELINE OF EQUIPMENT, UNLESS OTHERWISE NOTED.

    HEIGHT

    GFCIAFCIACAFFCDCWWH

    GROUND FAULT CIRCUIT INTERRUPTERARC FAULT CIRCUIT INTERRUPTERABOVE COUNTERABOVE FINISHED FLOORCLOTHES DRYERCLOTHES WASHERWATER HEATER

    72"/1825mm (TOP)DISTRIBUTION PANEL

    MOTION SENSOR CONTROL - (CEILING)

    DUPLEX RECEPTACLE (WALL) - 15A/120V

    12"/300mmDUPLEX RECEPTACLE (SPLIT) - 15A/120V

    NON-STANDARD RECEPTACLE

    AS NOTEDDIRECT EQUIPMENT CONNECTION

    NON-FUSED DISCONNECT SWITCH

    54"/1370mmFUSED DISCONNECT SWITCH

    MOTOR STARTERBRANCH CIRCUIT

    BRANCH CIRCUIT, SWITCHED

    BRANCH CIRCUIT, HOMERUNS TO PANEL

    12"/300mm

    AS NOTED

    54"/1370mm

    SINGLE POLE TOGGLE SWITCH - 20A/120V 35.5" / 900mm

    3-WAY TOGGLE SWITCH - 20A/120V TO

    MOTION SENSOR CONTROL - (SWITCH) 43.3 / 1100mm

    LIGHTINGF

    F

    FLUORESCENT LIGHT FIXTURE - RECESSED

    FLUORESCENT LIGHT FIXTURE - SURFACE

    LIGHT FIXTUREF - FLUORESCENTH - HIGH INTENSITY DISCHARGEL - INCANDESCENT

    DATA COMMUNICATIONSTELEPHONE OUTLET (WALL)

    TELEPHONE OUTLET (FLOOR)

    DATA OUTLET (WALL)

    DATA OUTLET (FLOOR)

    DATA & TELEPHONE OUTLET (WALL)

    TELEVISION OUTLET (WALL)

    TELEVISION OUTLET (FLOOR)

    12"/300mm

    12"/300mm

    12"/300mm

    12"/300mm

    E1

    E2

    E3

    EXIT & EMERGENCY LIGHTING

    E

    90"/2300mm

    90"/2300mm

    90"/2300mm

    90"/2300mm

    90"/2300mm

    90"/2300mm

    EXIT LIGHT, SURFACE MOUNTED, SINGLE FACE

    EXIT LIGHT, END OR CEILING MOUNTED, SINGLE FACE

    EXIT LIGHT, END OR CEILING MOUNTED, DOUBLE FACE

    COMBINATION EXIT & EMERGENCY LIGHT

    EMERGENCY LIGHT, BATTERY PACK

    EMERGENCY LIGHT, DOUBLE REMOTE

    EMERGENCY LIGHT, SINGLE REMOTE

    WP WEATHERPROOF

    ELECTRICAL NOTES

    ELECTRICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS FOR THISPROJECT.

    1 GENERAL:.1 CONFORM WITH APPLICABLE REQUIREMENTS OF THE MINISTRY OF LABOUR, AND THE OCCUPATIONAL

    HEALTH AND SAFETY ACT AND REGULATIONS FOR CONSTRUCTION PROJECTS..2 DO COMPLETE INSTALLATION IN ACCORDANCE WITH THE FOLLOWING:

    .1 ONTARIO ELECTRICAL SAFETY CODE; .2 ELECTRICAL SAFETY AUTHORITY; .3 ELECTRICAL SUPPLY AUTHORITY.

    .3 SUBMIT TO ELECTRICAL SAFETY AUTHORITY AND SUPPLY AUTHORITY NECESSARY NUMBER OFDRAWINGS AND SPECIFICATIONS FOR APPROVAL PRIOR TO COMMENCEMENT OF WORK.

    .4 COORDINATE AND OBTAIN ELECTRICAL SERVICE LAYOUT FROM THE SUPPLY AUTHORITY.

    .5 PAY ALL ELECTRICAL PERMIT AND INSPECTION FEES.

    .6 GROUND COMPLETE SYSTEM IN ACCORDANCE WITH THE ONTARIO ELECTRICAL SAFETY CODE ANDELECTRICAL SAFETY AUTHORITY.

    .7 IDENTIFICATION AND LABELLING: .1 IDENTIFY ELECTRICAL EQUIPMENT WITH LAMICOID NAMEPLATES, INCLUDING AMPERAGE,

    VOLTAGE, PHASE AND POWER SOURCE. .2 PROVIDE TYPEWRITTEN PANEL DIRECTORIES. .3 PROVIDE ADHESIVE LABEL ON ALL SWITCH, RECEPTACLE AND DEVICE COVER PLATES INDICATING

    SUPPLY CIRCUIT DESIGNATION..8 PROVIDE THREE COPIES OF COMPLETE OPERATING AND MAINTENANCE INSTRUCTIONS FOR

    EQUIPMENT FURNISHED UNDER THIS CONTRACT. BIND INSTRUCTIONS IN 3-RING BINDERS. INCLUDETHE FOLLOWING:

    .1 SCHEMATIC DIAGRAM OF ELECTRICAL SYSTEMS.

    .2 CONTROL SHOP DRAWINGS AND OPERATING SEQUENCE INCLUDING WIRING OF COMPONENTS.

    .3 WIRING DIAGRAM OF CONTROL PANELS.

    .4 OPERATING INSTRUCTIONS, INCLUDING START-UP AND SHUT-DOWN PROCEDURE.

    .5 MAINTENANCE INSTRUCTIONS INCLUDING PREVENTIVE MAINTENANCE INSTRUCTIONS FORCOMPONENTS OF THE EQUIPMENT.

    .6 COMPLETE PARTS LIST OF ASSEMBLIES AND THEIR COMPONENT PARTS, SHOWINGMANUFACTURER'S NAME, CATALOGUE NUMBER, AND NEAREST REPLACEMENT SOURCE.

    .7 LIST OF RECOMMENDED SPARE PARTS AND QUANTITY OF EACH ITEM TO BE STOCKED.

    .8 MANUFACTURERS' WARRANTIES AND GUARANTEES. .9 CLEAN ALL ELECTRICAL SYSTEMS AT PROJECT COMPLETION. .10 COMPLETE AS-BUILT DRAWINGS SHOWING ALL CHANGES AS WORK PROGRESSES.

    2 CONTRACTOR QUALIFICATIONS:.1 ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE “TRADES QUALIFICATION AND

    APPRENTICESHIP ACT” AND REGULATIONS, BY PERSONS WHO HOLD THE FOLLOWING CERTIFICATESOF QUALIFICATION (AS APPLICABLE):.1 ELECTRICIAN: CONSTRUCTION & MAINTENANCE.

    3 EXISTING FACILITIES AND DEMOLITION:.1 LOCATE AND PROTECT ALL EXISTING EXTERIOR SITE SERVICES..2 RETAIN AND PROTECT ALL EXISTING INTERIOR SERVICES AND BUILDING FABRIC. MAKE GOOD ANY

    AND ALL DAMAGE RESULTING FROM THIS WORK.

    4 FIXTURES AND EQUIPMENT:.1 PROVIDE SHOP DRAWINGS AND PRODUCT DATA FOR ALL ELECTRICAL FIXTURES AND EQUIPMENT FOR APPROVAL, PRIOR TO PROCUREMENT..2 INSTALL ALL ELECTRICAL FIXTURES AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S

    INSTRUCTIONS..3 EQUIPMENT AND MATERIAL TO BE CSA CERTIFIED. WHERE THERE IS NO ALTERNATIVE TO SUPPLYING

    EQUIPMENT WHICH IS NOT CSA CERTIFIED, OBTAIN SPECIAL APPROVAL FROM ELECTRICAL SAFETYAUTHORITY.

    5 EQUIPMENT SUPPLIED BY OTHERS:.1 MAKE ALL ELECTRICAL SERVICE CONNECTIONS TO EQUIPMENT SUPPLIED BY OTHERS..2 CONFIRM ALL SERVICE CONNECTIONS WITH MANUFACTURER AND SUPPLIER, PRIOR TO INSTALLATION.

    THIS SHALL INCLUDE ALL CONNECTION SIZES, LOCATIONS AND DETAILS, AND SHALL TAKE INTOACCOUNT EQUIPMENT CLEARANCES AND INSTALLATION REQUIREMENTS.

    6 CONDUITS:.1 RIGID GALVANIZED STEEL, WITH THREADED FITTINGS, WHERE SUBJECT TO MECHANICAL INJURY, IN

    SERVICE AREAS ONLY..2 ELECTRICAL METALLIC TUBING (EMT), HOT DIPPED GALVANIZED STEEL, WITH THREADED

    CONNECTORS AND COUPLINGS, WHERE NOT SUBJECT TO MECHANICAL INJURY, IN SERVICE AREASONLY.

    .3 RIGID PVC CONDUIT BELOW FLOOR AND IN CORROSIVE AREAS.

    7 WIRES AND CABLE:.1 VOLTAGE DROP:

    .1 FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 2% AT DESIGN LOAD. .2 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 3% AT

    DESIGN LOAD..2 BUILDING WIRES: IN CONDUIT SYSTEMS TO BE STRANDED COPPER CONDUCTORS FOR 10 AWG AND

    LARGER, MINIMUM SIZE 12 AWG, TYPE RW90..3 BUILDING WIRES IN CONCEALED LOCATIONS TO BE COPPER, MINIMUM SIZE 12 AWG, TYPE AC90..4 ALL WIRING SHALL BE CONCEALED IN WALLS AND CEILINGS, UNLESS OTHERWISE NOTED OR

    APPROVED. SURFACE-MOUNTED WIRING IS NOT PERMITTED.

    8 DATA AND TELEPHONE:.1 SUPPLY AND INSTALL 2 RUNS, 4” CONDUIT FROM SITE TELEPHONE SERVICE LOCATION TO MAIN ELECTRICAL ROOMS..2 SUPPLY AND INSTALL TELEPHONE BACKBOARD..3 DATA/TELEPHONE: .1 DATA AND TELPHONE WIRES CAT 6.

    .2 DATA AND TELEPHONE OUTLETS SHALL BE PROVIDED IN SEPARATE OUTLET BOXES ANDSEPARATE CONDUIT.

    .3 SUPPLY, INSTALL AND TERMINATE DATA AND TELEPHONE CABLES AT OUTLETS AND AT TELESERVICE SPACE.

    9 SERVICE EQUIPMENT:.1 ELECTRICAL SERVICE EQUIPMENT, PANELBOARDS AND DISCONNECT SWITCHES SHALL BE PRODUCT

    OF ONE MANUFACTURER THROUGHOUT PROJECT - CUTLER-HAMMER, SIEMENS OR SQUARE D..2 LOW-VOLTAGE DRY-TYPE DISTRIBUTION TRANSFORMERS SHALL MEET THE MINIMAL NOMINAL

    EFFICIENCY LEVELS OF ASHRAE 90.1 (TABLE 8.4.4.)..3 CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE..4 WORKING SPACE ABOUT ELECTRICAL EQUIPMENT SHALL BE PROVIDED IN ACCORDANCE WITH THE

    ONTARIO ELECTRICAL SAFETY CODE, INCLUDING THE FOLLOWING: .1 WORKING SPACE OF 3'4” (1m) WITH SECURE FOOTING; .2 MINIMUM HEADROOM OF 7'3” (2.2m).

    10 WIRING DEVICES:.1 WIRING DEVICES OF ONE MANUFACTURER THROUGHOUT PROJECT - HUBBELL OR LEVITON..2 COMMERCIAL PROJECTS:

    .1 OUTLET BOXES: .1 GANG BOXES WHERE WIRING DEVICES ARE GROUPED.

    .2 BLANK COVER PLATES FOR BOXES WITHOUT WIRING DEVICES. .2 SWITCHES:

    .1 HEAVY DUTY, 20A/120V; .2 SINGLE POLE, AND THREE-WAY, AS APPLICABLE; .3 COLOUR: SELECTED BY OWNER.

    .3 DUPLEX RECEPTACLES: .1 EXTRA HARD USE, CSA TYPE 5-15 R, 15A/125V; .2 GFI (GROUND FAULT CIRCUIT INTERRUPTER) WITH DETECT AND TRIP ON GROUND FAULT,

    STATUS INDICATOR LIGHT AND TEST SWITCH; .3 COLOUR: SELECTED BY OWNER.

    .4 COVER PLATES:.1STAINLESS STEEL.

    11 LIGHTING:.1 GENERAL LIGHTING:

    .1 SUPPORT ALL LIGHTING IN ACCORDANCE WITH THE ONTARIO ELECTRICAL SAFETY CODE AND BULLETINS.

    .2 LIGHT FIXTURES SUPPORTED BY SUSPENDED CEILING SYSTEMS SHALL HAVE ADDITIONALSUPPORT TO BUILDING STRUCTURE IN ACCORDANCE WITH ONTARIO ELECTRICAL SAFETY CODEBULLETIN #30-4-11.

    .2 FUNCTIONAL TESTING OF LIGHTING CONTROL, IN ACCORDANCE WITH ASHRAE 90.1 (9.4.3): .1 LIGHTING CONTROL DEVICES AND CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT

    CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED, AND INPROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS ANDMANUFACTURER'S INSTALLATION INSTRUCTIONS.

    .3 EXIT AND EMERGENCY LIGHTING: .1 CONNECT DC CIRCUIT FROM EMERGENCY LIGHT BATTERY PACK TO ALL EXIT AND EMERGENCY

    LIGHTS. .2 SIZE EMERGENCY LIGHTING POWER PACK TO PROVIDE FULL LOAD POWER FOR 30 MIN. .3 EMERGENCY LIGHT BATTERY PACKS (UNIT EQUIPMENT) SHALL BE INSTALLED IN SUCH A MANNER

    THAT IT WILL BE AUTOMATICALLY ACTUATED UPON FAILURE OF THE POWER SUPPLY TO THENORMAL LIGHTING IN THE AREA COVERED BY THAT UNIT EQUIPMENT PER OESC 46-304(4).

    .4 SITE LIGHTING: .1 CONTRACTOR SHALL PROVIDE A FULL PHOTOMETRIC LAYOUT FOR THE PROPOSED SITE LIGHTING

    FIXTURES.

    12 FIRE PROTECTION:.1 REFER TO ARCHITECTURAL DRAWINGS, TO VERIFY LOCATION OF ALL FIRE SEPARATIONS AND

    FIRE-RATED MEMBRANES..2 ALL CABLING AND CONDUIT SHALL BE TIGHTLY FITTED AND SEALED WITH FIRESTOPPING MATERIAL AT

    ALL FIRE SEPARATIONS AND FIRE-RATED MEMBRANES..3 ALL MATERIALS SHALL HAVE A FLAME-SPREAD RATING NOT MORE THAN 25 AND A SMOKE DEVELOPED

    CLASSIFICATION NOT MORE THAN 50..4 MOCK-UPS:

    .1 PREPARE MOCK-UPS OF TYPICAL FIRESTOP INSTALLATION OF THE FOLLOWING, FOR REVIEW ANDAPPROVAL BY THE OWNER, ENGINEER AND MUNICIPAL BUILDING INSPECTOR:.1 CONDUIT AND CABLING - WALL AND CEILING/FLOOR FIRE SEPARATION.

    .2 ALL FIRESTOP INSTALLATIONS SHALL BE COMPLETED IN ACCORDANCE WITH THE APPROPRIATEPRODUCT INSTALLATION INSTRUCTIONS, AND THE REFERENCED UL/ULC LISTING AND/OR TESTSTANDARD.

    .3 SUPPLY A COPY OF THE PRODUCT INSTALLATION INSTRUCTIONS WITH ULC LISTING AND/OR TESTSTANDARD REFERENCE, FOR EACH INSTALLATION.

    .4 MOCK-UP MAY REMAIN AS PART OF WORK.

    13 EARTHQUAKE LOAD:.1 ALL ELECTRICAL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE EARTHQUAKE LOAD AND

    EFFECTS REQUIRED BY THE ONTARIO BUILDING CODE..2 ELECTRICAL ELEMENTS AND COMPONENTS (FIXTURES, EQUIPMENT, CONDUIT, ETC.), AND THEIR

    CONNECTIONS TO THE BUILDING SHALL BE CONSTRUCTED IN ACCORDANCE WITH THESMACNA/ANSI SEISMIC RESTRAINT MANUAL OR OTHER GUIDELINE REFERENCED IN THE ONTARIOBUILDING CODE.

    .3 PROVIDE SHOP DRAWINGS FOR SUPPORT, CONNECTIONS AND SEISMIC RESTRAINT OF ALLELECTRICAL FIXTURES, EQUIPMENT, AND CONDUIT, INCLUDING, BUT NOT LIMITED TO:

    .1 SERVICE AND DISTRIBUTION EQUIPMENT; .2 LIGHT FIXTURES AND CEILING FANS; .3 ELECTRIC HEATING UNITS; .4 TYPICAL CONDUIT AND CABLE SUPPORTING SYSTEM. THESE SHOP DRAWINGS SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER IN THE

    PROVINCE OF ONTARIO, WITH EXPERIENCE IN SEISMIC ENGINEERING.

    14 LOAD BALANCE:.1 MEASURE PHASE CURRENT TO PANELBOARDS WITH NORMAL LOADS (LIGHTING) OPERATING AT TIME

    OF ACCEPTANCE. ADJUST BRANCH CIRCUIT CONNECTIONS AS REQUIRED TO OBTAIN BEST BALANCEOF CURRENT BETWEEN PHASES AND RECORD CHANGES.

    .2 SUBMIT, AT COMPLETION OF WORK, REPORT LISTING PHASE AND NEUTRAL CURRENTS ON PANELBOARDS, OPERATING UNDER NORMAL LOAD. STATE HOUR AND DATE ON WHICH EACH LOADWAS MEASURED, AND VOLTAGE AT TIME OF TEST.

    15 HAZARDOUS LOCATIONS AND OTHER SPECIAL CASES:.1 THE GARAGE AREA, AND ADJACENT ROOMS, UP TO A LEVEL OF 50mm ABOVE THE FLOOR SHALL BE

    CONSIDERED A CLASS I (FLAMMABLE GASES OR VAPOURS) ZONE 2 LOCATION..2 ALL ELECTRICAL EQUIPMENT USED WITHIN THE AREA SHALL BE APPROVED FOR THE CLASSIFICATION..3 ALL WIRING PRACTISES SHALL BE DONE IN ACCORDANCE WITH THE ONTARIO ELECTRICAL SAFETY

    CODE FOR THE ABOVE CLASSIFICATION.

    16 EQUIPMENT SUPPORT:.1 ALL ELECTRICAL EQUIPMENT, CONDUIT, WIRING, LIGHTING, DEVICES, AND RELATED ITEMS SHALL BE

    SECURELY SUPPORTED, ATTACHED AND FASTENED TO BUILDING STRUCTURE..2 HANGERS AND SUPPORTS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH MSS

    STANDARD SP-58, PIPE HANGERS AND SUPPORTS - MATERIALS, DESIGN, MANUFACTURE,SELECTION, APPLICATION, AND INSTALLATION.

    .3 PLATFORMS SHALL BE FABRICATED FROM STRUCTURAL GRADE STEEL MEETING THEREQUIREMENTS OF THE ONTARIO BUILDING CODE, INCLUDING CSA STANDARD W59 WELDED STEELCONSTRUCTION, AND THE REQUIREMENTS OF THE CANADIAN WELDING BUREAU.

    .4 SUPPLY AND INSTALL ALL EQUIPMENT MOUNTING SUPPORTS FOR ALL ELECTRICAL EQUIPMENT ANDDEVICES.  ALL SUPPORTS SHALL BE FABRICATED FROM GALVANIZED STRUCTURAL GRADE STEELMEETING THE REQUIREMENTS OF CSA STANDARD W59 WELDED STEEL CONSTRUCTION AND THEREQUIREMENTS OF THE CANADIAN WELDING BUREAU.  SHOP DRAWINGS FOR ALL EQUIPMENTMOUNTING SUPPORTS, INCLUDING ATTACHMENT DETAILS, SHALL BE SUBMITTED FOR REVIEW. THESE SHOP DRAWINGS SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER IN THEPROVINCE OF ONTARIO.

    17 COORDINATION:.1 INFORMATION INVOLVING ACCURATE DIMENSIONING OF THE BUILDING SHALL BE TAKEN FROM SITE

    BY CONTRACTOR..2 DRAWINGS ARE IN DIAGRAMMATIC FORM, INTENDED TO CONVEY THE SCOPE OF WORK AND

    GENERAL ARRANGEMENT FOR EQUIPMENT. COORDINATE PHYSICAL LOCATION OF ALL EQUIPMENTWITH OTHER TRADES AND ALLOW FOR ANY ADDITIONAL CONDUIT, WIRING, FITTINGS, SUPPORTS,ETC., IN ORDER TO AVOID INTERFERENCE AND FACILITATE THE WORK.

    .3 CONTRACTOR TO MAKE ANY NECESSARY MODIFICATIONS OR ADDITIONS, WITHOUT CHARGE, TOACCOMMODATE SITE CONDITIONS AND COORDINATION.

    .4 COORDINATE AND VERIFY ALL ELECTRICAL BRANCH CIRCUIT REQUIREMENTS FOR EQUIPMENTSUPPLIED BY OTHERS, PRIOR TO MATERIAL PROCUREMENT OR INSTALLATION.

    .5 PROVIDE ALL WIRING TO ALL MECHANICAL EQUIPMENT, INCLUDING WIRING BELOW 50V.COORDINATE ALL MECHANICAL EQUIPMENT WIRING WITH MECHANICAL TRADES.

    .6 ALL DEVICE AND OUTLET LOCATIONS SHALL BE CAREFULLY COORDINATED WITH THE GENERALCONTRACTOR OR OWNER, TO ACCOMMODATE ALL FEATURES, INCLUDING PLUMBING FIXTURES,EQUIPMENT AND MILLWORK.

    18 START-UP, COMMISSIONING AND TRAINING:.1 START-UP AND COMMISSION THE FOLLOWING SYSTEMS:

    .1 MAIN ELECTRICAL SERVICE EQUIPMENT;

    .2 GENERAL LIGHTING;

    .3 EXIT AND EMERGENCY LIGHTING;

    .4 ELECTRIC HEATING UNITS..2 PERFORM SYSTEMATIC TESTS, PROCEDURES AND CHECKS ON SYSTEMS, AS FOLLOWS:

    .1 TO VERIFY OPERATION IN ACCORDANCE WITH CONTRACT DOCUMENTS, DESIGN CRITERIA ANDINTENT,

    AND MANUFACTURER'S REQUIREMENTS;.2 TO ENSURE APPROPRIATE DOCUMENTATION IS PROVIDED;.3 TO EFFECTIVELY TRAIN BUILDING OPERATIONAL STAFF.

    .3 SYSTEMS ARE TO BE OPERATED AT FULL CAPACITY, WITH CORRECTION OF ALL DEFICIENCIES ANDADJUSTMENTS TO MEET OPTIMUM PERFORMANCE.

    .4 PROVIDE WRITTEN REPORT AT END OF COMMISSIONING OUTLINING EQUIPMENT OPERATIONALCONDITIONS AND PARAMETERS.

    REV DATE:

    Drawing No.:

    12/3/2020

    ELECTRICALNOTES & LEGENDS

    MM

    MM

    MP

    2020-04-27

    AS SHOWN

    -E1

    Project Title:

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    A DRAWIN S, SPE IFI ATIONS AND RE ATED DO UMENTS ARE THE OP RI HTPROPERT OF THE EN INEER AND MUST BE RETURNED UPON RE UEST.

    REPRODU TION OF DRAWIN S, SPE IFI ATIONS, AND RE ATED DO UMENTS INPART OR WHO E IS FORBIDDEN WITHOUT THE EN INEERS WRITTEN PERMISSION.

    THE ONTRA TOR MUST HE AND VERIF A DIMENSIONS ON THE OB PRIORTO START OF ONSTRU TION.

    DRAWIN S ARE NOT TO BE S A ED

    RevisionsDateByNo.

    Telephone: (613) 499-207768 William St. Suite 200Brockville, Ont.

    0 MP 2020-12-01 FOR REVIEW

    1 MP 2020-12-03 ISSUED FOR TENDER

  • OPEN TO BELOW

    FUTURE MEZZANINE

    FUTURE OFFICE / STORAGE AREA

    DOWN - FUTURE STAIR DOWN - FUTURE STAIR

    PROVIDE PRE-FRAMING

    F1

    3

    SCALE: 18" = 1'-0"

    MEZZANINE FLOOR PLAN - ELECTRICAL

    10

    M

    PNL.'P1'200A120/240V1PH,3W

    MANUALTRANSFERSWITCH600A120/240V1PH, 3W

    METER

    DISCONNECTMAIN SERVICE600A120/240V1PH, 3W

    200A 125A

    COMPRESSOR

    ELECTRICAL CONTRACTOR SHALL ASSUME FULLRESPONSIBILITY FOR COORDINATION OF NEWELECTRICAL SERVICE WITH SUPPLY AUTHORITY.

    PRIMARY CABLE INSTALLATION:- BY HYDRO ONE

    SECONDARY CABLE INSTALLATION:- BY ELECTRICAL CONTRACTOR- OESC DIAGRAM D11

    MAIN SERVICE SHORT CIRCUIT CURRENT RATING (SCCR):- 25 kA (TO BE VERIFIED BASED ON FINAL CABLE LENGHT)

    SECONDARY CONDUCTOR SIZING:- OESC TABLE 2: 75 deg.C

    350 MCM COPPERTWO CABLES PER PHASEALLOWABLE AMP 620A

    - OESC TABLE D11A: 350 MCM COPPERTWO CABLES PER PHASEALLOWABLE AMP 714A

    600A3P

    ELECTRICAL - SINGLE LINE DIAGRAM

    GENERAL NOTES:

    PNL.'P2'400A120/240V1PH,3W

    600A - TWO CABLES PER PHASEEACH 3 x 350 MCM COPPER IN CONDUIT WITHCONCRETE ENCASEMENT(SIZE IS SUBJECT TO FINAL CABLE LENGTHAND VOLTAGE DROP)

    POLEMOUNTTRANSFORMERPRIMARY: TBDSECONDARY: 120/240VPHASE: 1

    400A

    12.0000 (150mm)

    12.0000 (150mm)

    1'0" (100mm)

    2'6" (760mm)

    TIMECLOCK&PHOTOCELLCONTROL

    SPLITTER600A120/240V1PH, 3W

    CLEAN BACKFILL MATERIAL

    TELE/DATA CONDUIT2 x 4" (100mm) CONDUIT WITH FISHROPE MARKING TAPE TO OESC 12-012(11)

    UNDERGROUND ELECTRICALSECONDARY CONDUCTORS

    CLEAN SAND

    UNDISTURBED SOIL

    TRENCH DETAIL - UNDERGROUND PRIMARY

    UNDISTURBED SOILCLEAN SAND

    UNDERGROUND ELECTRICALSECONDARY CONDUCTORS

    CLEAN BACKFILL MATERIAL

    TELE/DATA CONDUIT 2x4" (100mm)CONDUIT WITH FISHROPE MARKING TAPE TO OESC 12-012(11)

    TRENCH DETAIL - UNDERGROUND SECONDARYEXTERIOR LIGHTING CONTROL SCHEMATIC

    120V, CCT. P-1- CCT 4

    TC

    PHOTOCELLC

    CELL

    CCT. P-1 - 6LIGHTING

    CONTACTOR

    TIMECLOCK

    SPARE

    SPARE

    CCT. P-1 - 8

    REV DATE:

    Drawing No.:

    12/3/2020

    ELECTRICALSCHEDULES & DETAILS

    MEZZANINE FLOOR PLAN

    MM

    MM

    MP

    2020-04-27

    AS SHOWN

    -E2

    Project Title:

    Township of South Glengarry

    MUNICIPAL GARAGEFACILITY

    ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHTPROPERTY OF THE ENGINEER AND MUST BE RETURNED UPON RE UEST.

    REPRODUCTION OF DRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTS INPART OR WHOLE IS FORBIDDEN WITHOUT THE ENGINEERS' WRITTEN PERMISSION.

    THE CONTRACTOR MUST CHECK AND VERIFY ALL DIMENSIONS ON THE JOB PRIORTO START OF CONSTRUCTION.

    DRAWINGS ARE NOT TO BE SCALED

    RevisionsDateByNo.

    Telephone: (613) 499-207768 William St. Suite 200Brockville, Ont.

    0 MP 2020-12-01 FOR REVIEW

    1 MP 2020-12-03 ISSUED FOR TENDER

  • UP - FUTURE STAIR

    PROVIDE PRE-FRAMING SW2SW1-SW4

    SW1

    SW3

    SW4

    F2

    F2

    F2

    M

    L1

    EX2

    WPGFI

    GFIEL1

    F-1FURNACE


Recommended