Inspector's Signature ≤ 8.3% ≤ 2.0% Y 1/4" Pass ≥ 4.0' ≤2.0% < 4.0' Pass Fail Pass Fail Company/Agency ADA Curb Ramp New Construction Inspection Form (Perpendicular) Certification No. Print name clearly Project No. Date (mm/dd/yy) Ramp Position Corner Position East-West Road Name North-South Road Name Sheet No. Fail 8.3% |5.0%| TURN SPACE MISCELLANEOUS Calibration Date RAMP RUN 1 (mm/dd/yy) < 10% Traversable Intersection No. Comments: N/A ≥ 4.0'* 1 < 4.0'* 1 ≤ * See also Standard Drawings to assess provisions not shown: (inlets, alignment, etc.) Ramp Style LANDING Slope of Road ≤2.0% <10% < 4.0' 10% NONE Y * The passing value for Gutter Flow Slope (GFS) depends on the Intersection Control Type. At a Midblock (MB), GFS must be Slope of the Road, at Signalized or Uncontrolled (SU), GFS must be ≤ 5.0%, and at Stop or Yield (SY), GFS must be ≤ 2.0%. * 1 If Back of Ramp Obstruction is Yes, turn space length Y must be minimum 5.0 ft. * 2 Clear Space area is the width of Ramp Run 1 and extends 4.0 ft into the roadway. N 5.0'* 1 < 5.0'* 1 Longest distance from corner to back of curb (see dwg on BT form) Detectable warning extends full width of ramp throat opening > 1/2" ≤1/2" PE Stamp (required for private development) >8.3% >2.0% N >1/4" >* >8.3% >|5.0%| Running Slope 1 Length 1 Cross Slope 1 Detectable Warning (Y,N) Lip Height Gutter Flow Slope Curb Running Slope (avg) Counter Slope (+/-) *2 Flare Slope 1 ≤ 10% ≥ 4.0' >2.0% >2.0% < 5.0' 5.0' Width X Length Y Back of Ramp Obstruction (Y/N) Slope X Slope Y Flare Slope 2 Clear Width (feet) Intersection Control Type Horizontal Gaps WashCo ADA 01 (4-2020)
Transcript
Page 1: AMP RUN 1 Pass Fail Ramp Style Running Slope Position · Fail Pass Fail Company/Agency ADA Curb Ramp New Construction Inspection Form (Perpendicular) Print name clearly Certification

Inspector's Signature

≤ 8.3%

≤ 2.0%

Y

1/4"

Pass

≥ 4.0'

≤2.0%

< 4.0'

Pass

Fail

Pass Fail

Company/Agency

ADA Curb Ramp New Construction Inspection Form (Perpendicular)

Certification No.Print name clearly

Project No.

Date (mm/dd/yy)

Ramp Position

CornerPosition

East-West Road NameNorth-South Road Name Sheet No.

Fail

≤ 8.3%

≤|5.0%|

TURN SPACE

MISCELLANEOUS

Calibration Date

RAMP RUN 1

(mm/dd/yy)

< 10%

Traversable

Intersection No.

Comments:

N/A

≥ 4.0'*1 < 4.0'*1

≤ *

See also Standard Drawings to assess provisions not shown: (inlets, alignment, etc.)

Ramp Style

LANDING

Slope of Road

≤2.0%

<10%

< 4.0'

≤ 10%

NONE

Y

* The passing value for Gutter Flow Slope (GFS)depends on the Intersection Control Type. At aMidblock (MB), GFS must be ≤ Slope of the Road, atSignalized or Uncontrolled (SU), GFS must be ≤5.0%, and at Stop or Yield (SY), GFS must be ≤ 2.0%.

* 1 If Back of Ramp Obstruction is Yes, turn spacelength Y must be minimum 5.0 ft.

* 2 Clear Space area is the width of Ramp Run 1 andextends 4.0 ft into the roadway.

N

≥ 5.0'*1 < 5.0'*1

Longest distance from corner to back of curb (see dwg on BT form)Detectable warning extends full width of ramp throat opening

> 1/2"≤1/2"

PE Stamp (required for private development)

>8.3%

{ŜŜ ƘǘǘLJǎΥκκǿǿǿΦƻNJŜƎƻƴΦƎƻǾκƻŘƻǘκ9ƴƎƛƴŜŜNJƛƴƎκ5ƻŎdzƳŜƴǘǎ ψwƻŀŘǿŀȅ9ƴƎκ!5!ψ9ȄƘƛōƛǘ!ΦLJŘŦ ŦƻNJ ƳƻNJŜ ŎƻNJƴŜNJ ǎǘȅƭŜǎΦ

¦ǎŜ ²ŀǎƘƛƴƎǘƻƴ /ƻdzƴǘȅ ŎƻNJƴŜNJ ƴdzƳōŜNJƛƴƎ ǎȅǎǘŜƳΦ

>2.0%

N

>1/4"

>*

>8.3%

>|5.0%|

Running Slope 1

Length 1

Cross Slope 1

Detectable Warning (Y,N)

Lip Height

Gutter Flow Slope

Curb Running Slope (avg)

Counter Slope (+/-) *2

Flare Slope 1

≤ 10% ≥ 4.0'

>2.0%

>2.0%

< 5.0' ≥ 5.0'

Width X

Length Y

Back of Ramp Obstruction (Y/N)

Slope X

Slope Y

Flare Slope 2

Clear Width (feet)

Intersection Control Type

Horizontal Gaps

WashCo ADA 01 (4-2020)