Welcome to the Camfil Farr Training Academy
1
© CAM
FIL
FARR
23-
04-0
8
By the end of this webinar you will have an update on the new EN779:2012 standard and the opportunity to have clean Indoor Air Quality and energy efficiency with Low Energy Air Filters
EN779:2012 will be arriving
Peter Dyment 07-02-2012
WHEN?
The latest indications are the standard will be due for publication later this year. The situation will be updated over the next few months.
We are all trusting that a decision to proceed will be forthcoming so that our industry can make progress and plan for the future.
3
© CAM
FIL
FARR
23-
04-0
8
EN779 as a filter test standard has been with us since 1993and was updated in 2002.What is EN779:2012 about and why is it important?
It is the updated European Standard that gives a laboratory test and class to benchmark HVAC air filter particulate efficiency.
It uses a test aerosol of 0.4 micron and ASHRAE dust to load (not test) the filter and increase air filter resistance in stages.
4
© CAM
FIL
FARR
23-
04-0
8
5
© CAM
FIL
FARR
23-
04-0
8
EN779:2002 Test Rig
The EN779:2002 test is usually performed by an independent test house on air filters up to F9 classification and a test report is issued. What is new in the 2012 update?
EN779 was revised in 2002 because of the problem regarding the inconsistent particulate life performance of synthetic media filters.
6
© CAM
FIL
FARR
23-
04-0
8
SINTEF test results Norway (1995) show real lifetime performance losses
Synthetic F7 Class filters have been marketed for many years but some a have a working particulate efficiency dropping as low as 10%.
EN13779 advises that F7 is the minimum filter class required for cleaning air and thereby making it safe to inhale. Clearly this standard assumes a consistent F7 performance.
7
© CAM
FIL
FARR
23-
04-0
8
8
© CAM
FIL
FARR
23-
04-0
8
EN779:2012 has set the minimum particulate efficiency (ME) of 35% on an F7 grade filter. This will exclude inferior synthetic media HVAC filters.
Min Effy. 35%
9
© CAM
FIL
FARR
23-
04-0
8
Table 1— Classification of air filters1)
Group Class Final test pressure
drop
Average arrestance (Am) of synthetic dust
Average efficiency (Em)
of 0,4 µm particles
Minimum Efficiency2)
of 0,4 µm particles Pa % % %
Coarse G1 250 50 Am 65 - -
G2 250 65 Am 80 - -
G3 250 80 Am 90 - -
G4 250 90 Am - -
Medium M5 450 - 40 Em 60 -
M6 450 - 60 Em 80 -
Fine F7 450 - 80 Em 90 35
F8 450 - 90 Em 95 55
F9 450 - 95 Em 70
NOTE 1) The characteristics of atmospheric dust vary widely in comparison with those of the synthetic loading dust used in the tests. Because of this the test results do not provide a basis for predicting either operational performance or life. Loss of media charge or shedding of particles or fibres can also adversely affect efficiency. 2) Minimum efficiency is the lowest efficiency among the initial efficiency, discharged efficiency and the lowest efficiency throughout the loading procedure of the test.
Test standard for coarse and fine air filters
10
© CAM
FIL
FARR
23-
04-0
8
Indoor Air Quality approach 2012Particulate Efficiency
ME (Minimum Efficiency) - F7 > 35% - F8 > 55% - F9 > 70%
Average efficiency – as before with caution - nothing to change
11
© CAM
FIL
FARR
23-
04-0
8
Indoor Air Quality approach 2012
Keep the IAQ level high! Risk of decreasing efficiency from competitors!
12
© CAM
FIL
FARR
23-
04-0
8
IAQ approach for 2012
When the outdoor air quality has been categorized, EN13779:2007 clearly specifies the filter class that is required to achieve preferred indoor air quality:
Recommendations in EN13779: 2007
13
© CAM
FIL
FARR
23-
04-0
8
Indoor Air improvement during 50 years
2011 filters for good IAQ
Particulate
1961 filters for good IAQ
14
© CAM
FIL
FARR
23-
04-0
8
Indoor Air improvement during 50 years
2011 filters for good IAQ
Particulate
1961
G4 – M6
F7
Protecting equipment
IAQ / healthF9
15
© CAM
FIL
FARR
23-
04-0
8
Indoor Air improvement during 50 years
2011
Particulate
2012
1960 G4 – M6
F7 – F9
Protecting equipment
IAQ health
EN779:2012
16
© CAM
FIL
FARR
23-
04-0
8
Indoor Air improvement during 50 years
2011
Particulate
2012
1961
G4 – F6F7 – F9
Protecting equipment
IAQ health
Risk ?Possibility!
17
© CAM
FIL
FARR
23-
04-0
8
Why is there a risk during 2012 ?• Glass fibre media F7 >60% efficiency – optimum
• The new EN779:2012 ME = 35% for F7 (Minimum Efficiency)
• Could lead to over 40% less clean air
18
© CAM
FIL
FARR
23-
04-0
8
Eurovent Energy Efficiency Rating Programme
Based on…… - EN779:2012
ME - F7 > 35% - F8 > 55% - F9 > 70%
19
© CAM
FIL
FARR
23-
04-0
8
• ME - F7 50 > 35% - F8 70 > 55% - F9 80 > 70%
dP lower
Energy rating higher
Eurovent Energy Efficiency Rating Programme
20
© CAM
FIL
FARR
23-
04-0
8
Why a is there a risk in 2012 ?
• Traditional glass fibre media F7 > 60% minimum efficiency – in built up environment• Synthetic F7 charged media – ME = 16-20%
• Synthetic media has to improve to reach minimum 35% ME (minimum efficiency) – with increased pressure drop
• New glass media >45% efficiency – lower pressure drop
21
Check the Indoor Air Quality Factor (IAQ factor)
21
The IAQ factor is found by dividing the LCC by the ME. It tells you have much filter performance you are getting for your money.
EG. M7 F7 bag = 24.7 IAQG4 S-Flo-F7 bag = 154.6 IAQ
IAQ Factor is 6.25 X
per % Minimum Efficiency (ME)
22
© CAM
FIL
FARR
23-
04-0
8
HVAC Air Filtration Hi-Flo F7
Synthetic Competitor F7 S-Flo F7
All medias shown at the same magnification
Synthetic medias rely on electrostatic charge for good particulate efficiency
23
© CAM
FIL
FARR
23-
04-0
8
What is the 2012 HVAC product opportunity?• Synthetic media filters will have to improve to reach 35% minimum
particulate efficiency (ME) – meaning an increased pressure drop
• Reduce pressure drop with LEAF – keep minimum efficiency high (ME) usually about 55% to 60% for F7.
• Never compromise on filter particulate efficiency !
• Save energy – better LCC – Eurovent Energy Classification Programme
• That is an improvement opportunity!
24
THANK YOU for attending this webinar session
ANY QUESTIONS?Please do not hesitate to contact Camfil Farr for any additional information or to
arrange a visit.For more information about clean air solutions, improving air quality, low energy
air filters, CRC (Carbon Reduction Commitment), AHUs (Air Handling Units) and the EPBD, visit
www.keepthecityout.co.ukwww.lowenergyairfilter.co.uk
blog and subscribe to the RSS Feed