+ All Categories
Home > Documents > ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE … · September 2017, 1st International Conference...

ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE … · September 2017, 1st International Conference...

Date post: 10-Oct-2020
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
29
May 2017, Andreas Falk ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE ENERGY): FOCUS PV SMA Solar Technology AG September 2017 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India Andreas Falk, Ancillary services with VRE
Transcript

May 2017, Andreas Falk

ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE ENERGY): FOCUS PV

SMA Solar Technology AG

September 2017 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India Andreas Falk, Ancillary services with VRE

CONTENT

2

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

MOTIVATION – PV IS RELEVANT FOR THE SYSTEM

Relevance of PV is increasing:

> Current situation in Germany: 37 GW PV installed base: 40-50% OF THE LOAD is covered

> Present plan for grid development counts with 50-60 GW ( This is rather conservative): ABOVE 80% OF THE LOAD is covered With such a scenario more and more hours with DOMINATING PV supply can be considered

3

In case of PV dominates generation, PV has to generate sufficient ancillary services

Da

tes:

EEX

Tra

nsp

are

nzpl

attf

orm

0

10

20

30

40

50

60

0:00 4:00 8:00 12:00 16:00 20:00 0:00

Po

we

r (G

W)

time

Example (2016) real data

Solar

Wind

Konventionell0

10

20

30

40

50

60

0:00 4:00 8:00 12:00 16:00 20:00 0:00

Po

we

r (G

W)

time

...same day with double the wind and PV power in 2030

Solar 2035

Wind 2035

Konv 2035

Load profile with distributed generation

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

DENA-Study „Ancillary services 2030“

CHARACTERIZATION OF ANCILLARY SERVICES

4

High system responsibility requires more system interaction and new operation modes

Local global

Reactive power management

Sec. reserve

Spinning reserve

Black start capability

Zone of influence

aut

ono

mo

us

coo

rdin

ate

d

Sy

ste

m in

tera

ctio

n

Static voltage control

Dynamic voltage control

Power reduction @ high frequency

Prim. reserve

Established functions for grid connected PV

Future functions for grid connected PV

> Basic demand for RENEWABLE SOURCES for ancillary services

> Static voltage support

> Dynamic voltage support

> Frequency support in case of over frequency

> Additional developments in the direction of:

> Control and coordinated operation

> Active power reserve

> Black start

Most important contribution of« 3. GENERATION » PV- Systems

> Aggregated operation of many distributed PV-plants as a tool for VOLTAGE SUPPORT MANAGEMENT

> Provision of ACTIVE POWER RESERVE for frequency support (e.g. with batteries)

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CONTENT

5

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

REACTIVE POWER MANAGEMENT (WITHOUT AND WITH VRE)

Motivation

> Transmission and distribution grids NEED REACTIVE POWER to fulfil their tasks even with light load

> Reactive power demand of the grid VARIES WITH LOADS. Reactive power flow may change its direction

Status Quo

> POWER STATIONS cover the reactive power in both directions

> VRE sources NEED LAGGING REACTIVE POWER for local voltage support in the distribution grid

Challenge for the future

> Nearly the entire reactive power has to be COVERED FROM VRE.

> VRE sources connected on HV-grid or/ and a large number of COORDINATED VRE SOURCES in LV- and MV-grids must TAKE OVER THE ROLE OF POWER STATIONS

6

Flexible, distributed and coordinated reactive power generation is necessary

So

urc

e:

„FN

N H

inw

eis

Blin

dle

istu

ng

sma

na

ge

me

nt

in V

ert

eilu

ng

sne

tze

n“

Light load without decentralized generation

Heavy load with decentralized generation

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

PV CONTRIBUTION TO REACTIVE POWER MANAGEMENT

Challenge

> Utilization of distributed PV plants

Solution

> PV-Systems with extended reactive power capability

> “VPP-Gateway”-Technology

> Connection to control (standard-protocol)

> Aggregation + protocol conversion Open point

> Regulation / Ability to charge the service

7

Base technologies do exist. The regulation framework is missing in some cases.

„VPP-Gateway“

Control center

P

Q

Q at distribution transformer controlled via external set point

Q

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

Reactive power capacity at maximum power. A P/Q diagram must be defined within the thrashed lines in the following diagram. Most of the UTILITYs require the operation of the power plant inside the P/Q diagram within 0.95 pu ≤ V < 1.05 pu of the nominal grid voltage.

8

• This may imply the need to oversize the inverters. • E.g. the inverter must be able to supply Q= 0.5 pu and P=0.9

pu even if the voltage is 0.95 pu at S=100% Snom. • Transformers and other electrical components have an

influence on the power factor (reactive power self consumption of the plant)at the connection point, especially if a capacity behavior is required (0.95 pu ≤U < 1 pu), so that the reactive power provided at inverter terminals has to be even higher than 0.5 pu

VOLTAGE SUPPORT CAPABILITY DEPENDS ON AC-VOLTAGE AND SIZING OF THE EQUIPMENT

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

VECTOR DIAGRAM

λ =1 (unity power factor) ⇒medium AC voltage required

λ =0,9 (legging) ⇒high AC voltage possible

λ =0,9 (leading) ⇒low AC voltage required

Vgrid

Iinverter

Vinverter Vinverter Vinverter

Vgrid Vgrid

Vgrid inductivity (inside

the PV-plant)

Vgrid resistor (inside the PV-plant)

→ Required Inverter voltage depends a lot on reactive power needs

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

10

A preliminary assessment with special tools in order to estimate the obligations of a solar PV plant is necessary during an early stages of project implementation. It determines the number of inverters needed to realize the interconnection requirements for active and reactive power at the POI (Point of interconnection) See such an expertise on the left side

VOLTAGE SUPPORT WITH REACTIVE POWER INJECTION

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CONTENT

11

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

12

Active Power Limitation on command: Needs communication link to each inverter or every entire PV-plant Reduction of active power depending on grid frequency: • in case of grid failures • in case of power surplus • to avoid grid instabilities

Active power limitation by frequency – Capabilities of the inverter should allow individual adjustment regarding the needs of the utility.

TRADITIONAL FREQUENCY SUPPORT: POWER REDUCTION IN CASE OF OVER FREQUENCY

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

UTILITY MAY CEASE POWER PRODUCTION IN CASE OF OVER FREQUENCY

The Grid operator can send for instance a stop command to the plant. The plant stops power injection within a certain time and remains active (stay connected) until the stop signal disappears.

13

The plant is a black box for the operator. Important is the behavior at POI

POI

Actual values

Power Plant Controller

Actuating values

Stop command

Utility

Monitoring Data

HV transformer (optional)

Power Analyzer

Actuating values

Example for plant controller operation

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

FREQUENCY SUPPORT IN CASE OF UNDER FREQUENCY

APR (Active Power Reserve) to be activated during under frequency:

• Two Different ways to comply with standards ( Main difference: Availability demand in case an under frequency occur)

14

STORAGE

99.9 % Availability

PV harvest is not reduced

Operates during all irradiation conditions

Other grid management functions (peak shaving, more sophisticated frequency behavior, fast response)

Curtailment

<98% Availability (poor behavior during power gradients e.g. moving clouds)

PV harvest is reduced due to curtailment

Disposable until power drops until a certain level, below this level it is not possible to provide active power reserve

Could be a proper alternative in grids with a lot of single plants operating with active power reserve (statistical balancing)

The agreement with the Utility will determine which one should be used

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

ACTIVE POWER RESERVE: PLANT OPERATES BELOW MPP AND INJECTS ADDITIONAL POWER IF NECESSARY

15

POI

Actual values

Power Plant Controller

Actuating values

HV transformer (optional)

Power Analyzer

Actuating values

Irradiation sensors

Irradiation sensors

SMA Calibration algorithm

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

16

Probabilistic forecast for different reliabilities in Germany

PROBABILISTIC FORECAST FOR A SINGLE PLANT

Example power feed-in and minute reserve potential for the verification method “fixed generation schedule” for overall Germany See also: Providing Control Reserve with PV Systems- Goal and Results of the Project PV-Regel, Daniel Premm,…,International ETG Congress 2015, November 17-18, Bonn, Germany

AS lower the requirements regarding probabilistic forecast are and as higher the no. of distributed plants been involved is, as lower are the losses for active power reserve provision.

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CURTAILMENT AND THE USE OF SENSORS

An alternative to storage is the operation of the plant with certain Active Power Reserve (operating the inverters at a lower power output than they could)

In order to calculate the potential available power from the PV plant, it is required to use irradiation sensors throughout the plant.

A special algorithm calibrates the sensors with the present power of the inverters. This results in very good accuracy. The Power Plant Controller will receive the information from the sensors and send the commands to the inverters to run at a different set point below MPP.

According to the IEC 61724-1 standard, the PV system performance can be measured with enough accuracy as long as there is a minimum number of irradiation sensors:

17 September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

LARGE-SCALE STORAGE INTEGRATION AS AN ALTERNATIVE FOR APR

SUPPORTS THE GROWTH OF RENEWABLE ENERGIES

Frequency support can be implemented very easily while using a battery. Support in both direction possible.

In this application the storage system complement the PV power plant to fulfill requirements that cannot naturally fulfilled with the renewable source alone

Storage provides renewable energy with the same grid-stabilizing characteristics of conventional power plants through the comprehensive provision of ancillary services

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE 18

RAMP RATE CONTROL WITH BATTERY SUPPORT

19

Which features to be fulfiled by Storage System?

Fulfillment of Regulations and Grid Requirements1

Ramp-Rate Control of PV Plants: Batteries provide reserve power to “firm” the output of the PV system and ensure stable power supply. Makes PV power “dispatchable”

Frequency Control/Regulation: Batteries provide/absorb power to support frequency in the grid

provides reserve power without running fossil generators

2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7

x 104

-0.5

0

0.5

1

2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7

x 104

0

0.2

0.4

0.6

0.8

1

PPV

PStrg

Target Value

Target Value

PCombined

SoC

1Day Profile for gradients of 1%Pn/min Requirements

May 2017, Andreas Falk, Inverter Topologies

LARGE-SCALE STORAGE INTEGRATION SUPPORTS THE GROWTH OF RENEWABLE ENERGIES

20

Conventional Power Plants

Various Loads

Power Grid

Ancillary Services

• Scheduling & Dispatch • Reactive Power supply

Renewable Power Plants

Renewable Integration • Ramp-Rate Control • Frequency Control P(f) • Peak shifting and shaving

Weak grid

Industrial Hybrid (Off-Grid or grid-connected) • All grid applications • Optimized Operation of Genset • Energy shifting

Large Commercial Loads

Ancillary Services

• Frequency control P(f)

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CONTENT

21

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

DYNAMIC VOLTAGE CONTROL MEANS THE RESPONSE OF THE POWER PLANT DURING A VOLTAGE DIP

The power plant must remain connected to the grid and operate normally throughout the zone A in the following figure:

22

1.0

0.0 segt

puV

Zona A

Zona B

Zona B

0.9

1.1

PB1 PB2

PB3 PB4

PA1 PA2

PA3

PB5

1.0

0.0 segt

puV

Zona A

Zona B

Zona B

PB1 PB2

PB3 PB4

PB6

PA1 PA2

PA3

0.9

1.1

PB5

• Type B, C • Type D

In zone B stop of operation is allowed (example for Mexican grid regulations)

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

DYNAMIC VOLTAGE CONTROL MEANS THE RESPONSE OF THE POWER PLANT DURING A VOLTAGE DIP

23

Inverter Protection >140% for 1 ms = trip

Voltage Ride Through (LVRT/HVRT) Voltage ride through in the Sunny Central is wider than the requirements. Behavior can be adjusted as per the local requirements

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

BEHAVIOR DURING A THREE PHASE VOLTAGE DIP

Imax I32 (I21)

d 33,3 -11,9 11,7 41,7 -45,5 31,1 81,7 -83,3 55,0

3ph fault to 25%Un @ 2.27 MW, 50 °C, 3300A set point, 400 ms voltage dip

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CONTENT

25

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

WHAT IS INTER AREA OSCILLATION?

Amplitude of the voltage in high voltage grid can vary with +/ - 10% and a frequency between 0.2 until 2 Hz

What to do? Injection of reactive power to damp the voltage oscillation (inter area oscillation damping) See also: A Contribution to Thorough Comprehension of POD Provided by FACTS Devices, Thomas Graber,…; University of Erlangen-Nürberg, Germany, International ETG Congress 2015, November 17-18, 2015, Bonn, Germany

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

REQUIREMENTS FOR INTER AREA OSCILLATION DAMPING

Optimal placement: Distributed sources are in favor to solve such problems, because they may available at all places in the future

Reaction time: Dead time of the plant controller must be small enough to react ⇒ Dynamic sensors and communication means in the power plant

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

CONTENT

28

Voltage support

Frequency support

Dynamic voltage control during a voltage dip

Inter area oscillation damping

Summary

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE

SUMMARY

Large PV-power plants can deliver all ancillary services to operate the grids: • Voltage support (with reactive power) • Frequency support (with active power reduction or active power reserve) • Dynamic voltage support • Inter area oscillation damping

Future services: • Spinning reserve. • Black start capability ⇒Both features can be achieved with batteries more favorable

Contact: [email protected] – Tel.: (0561) 9522-3313

September 2017, 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India, Andreas Falk, Ancillary services with VRE


Recommended