+ All Categories
Home > Documents > Annual Testing of Stairwell Pressurization Systems & Other ...c.ymcdn.com/sites/ · Annual Testing...

Annual Testing of Stairwell Pressurization Systems & Other ...c.ymcdn.com/sites/ · Annual Testing...

Date post: 17-May-2018
Category:
Upload: vukiet
View: 258 times
Download: 8 times
Share this document with a friend
26
Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems Presented by Mike Locke, MechTech Inc. SIA – All SIAs are listed in this presentation April 13, 2016 1
Transcript

Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems

Presented byMike Locke, MechTech Inc. SIA – All SIAs are listed in this presentationApril 13, 2016

1

Testing requirements are reviewed with each National Code Revision every 3 years

Reasons for Revisions to the Testing Requirements

AFD was receiving feedback that the enforcement of the annual requirements was not familiar to a number of building Owners & Managers.

AFD was also receiving feedback that the testing was disruptive to the occupants of the facilities during certain portions of the testing.

2

Reasons for Revisions to the Testing Requirements

AFD was further receiving feedback that the testing was expensive and that some of the testing agencies were not responding to requests for testing proposals in a timely manner.

3

AFD sent out a request for all Special Inspection Agencies (SIA’s) to provide confidential pricing information for typical projects. As would be expected, pricing varied based on the complexity and type of system.

AFD’s response to the Owners & Managers concerns:

AFD then requested ideas from SIA’s for revisions that would assist in cost reduction of testing but not compromise the integrity of the intent of the stairwell pressurizationSystems. 4

AFD reviewed the existing testing requirements and incorporated some of the ideas from the SIA’s as well as pertinent sections of the 2012 and 2015 National Codes.

AFD’s response continued:

AFD approved the Revisions to the Annual Stairwell Pressurization Testing on March 04, 2016 with the revised requirements effective on March 07, 2016 per email to all AFD approved SIA Firms

5

Main Revisions that will effect Cost and Interruption to Occupants 

1 – Deleted requirement to have a Fire Alarm Contractor onsite during the testing.

Frees up $ to do Annual FireAlarm Testing right before SIA Smoke Control System Testing

6

Main Revisions that will improve Cost Factor and Interruption to Occupants 

2 – Deleted the requirement for theThree (3) Stairwell and Vestibule Doors Open on 3 consecutive floors Plus an Exterior Exit Door Open Test.

This requirement was causing occupant complaints and multiple tests to repair/renovate or fine tune a system to achieve the required results.

7

Main Revisions that will improve Cost Factor and Interruption to Occupants 

# 2 – Continued

Replaced the  3 Door Open Test with a requirement for testing with All Doors Closed PLUS an Open Exterior Exit Door.

This new requirement will essentially eliminate the disruption to the occupants because only the stairwells will be pressurized and air will be flowing out the exterior door.

8

Main Revisions that will improve Cost Factors and Interruption to Occupants 

3 – Deleted requirement to Retest Door Opening Forces during the 3 Door plus Exit Door Open Test.Door Opening Force Testing is Only Required during the Closed Door Test.

4 – Clarified the Vestibule to Stairwell and Vestibule to Floor Pressurization Criteria as follows:

9

Main Revisions that will improve Cost Factors and Interruption to Occupants 

# 4 Continued:Previous testing requirements stated that the “Vestibule to Stair and Vestibule to Floor” Pressurization must be a minimum of ‐0.05” wg and +0.05”wg respectively. This has always meant that a total of +0.10” wg differential was required from the Stairwell to the Floor.

10

Main Revisions that will improve Cost Factors and Interruption to Occupants 

4 Continued:

However, testing of some of the newer buildings revealed that the relative “tightness” of the Vestibule to the Floor was creating a situation where the overall differential pressure was in compliance with the +0.10” wg but the “Vestibule to Stair”differential was less than ‐0.05” because the differential was dependent on having an airflow path from the Vestibule to the Floor.11

• Illustration of Tightly Sealed Vestibule to Floor :

Stairwell Vestibule

Floor

-.02” wg +0.09” wg

+0.11” = Pass

Manual or Barometric Damper with Fire DamperTo Allow Airflow from Stairwell to Vestibule

12

Tightly Sealed Vestibule/Door/ThresholdCauses Stairwell andVestibule to Essentially Equalize in PressureBut Overall Pressure Differential from Stairwell To Floor is OK.

Main Revisions that will improve Cost Factors and Interruption to Occupants 

5 – AFD provided new Testing Report format that illustrates the minimum data to be included in a SIA Report.The SIA report may include additional data but the new test forms are the minimum criteria.Please Note that the SIA is Required to Report all Test Failures and should NOT submit a report until system passes.

13

Main Revisions that will improve Cost Factors and Interruption to Occupants 

6 – Please also Note that the Austin Fire Department is readily available to answer any questions from an SIA regarding any alternate testing for buildings constructed prior to 1996 or for any specialized systems such as a “Pressure Sandwich” or Atrium Exhaust.

14

Included in this Presentation are:1 ‐ Minimum Test Data Forms 2 – List of currently approved SIA Firms

15

Available through AAFAME are:1 ‐ Marked up copy of the previous

Testing requirements2 – Copy of Current Testing Requirements

AUSTIN FIRE DEPARTMENT APPROVED BUILDING SMOKE-CONTROL SPECIAL INSPECTION AGENCIES

Austin Air Balancing Corporation

1

1106 West 6th Street Suite 206Austin, Texas 78703512-477-7247contact: Sutton Page or Charles Page

www.austinairbalancing.comCompany has full test and balancecapability.

Air Technologies, Inc. P.O. Box 129 Manchaca, TX 78628 512-280-3398Contact: Chad Mathews, Estimator

[email protected]

Engineered Air Balance Company 4400 Piedras Drive South, Suite 150 San Antonio, Texas 78228210-736-9494Contact: Gary L. Miller, P.E.

[email protected] has full test and balance capability

MechTech Inc. Services 102 Broad St. Unit 3149Forney, Texas 751261-800-328-3588972-552-9399Contact: Michael D. Locke

[email protected] has full test and balance capability.

PHI Service Agency, Inc. 2120 W. Braker Lane, Suite G Austin, Texas 78758512-339-4757Contact: Bill Kruckenberg

Austin Branch [email protected]

Company has full test and balancecapability.

1

TAB Technologies 3901 S. Lamar, Suite 130Austin, Texas 78704512-486-3633 (office)512-486-3601 (fax)Contact: Tyler Lewis

[email protected] has full test and balance capability

TNT System Solutions, Inc P.O Box 0327 Spicewood,Texas 78669 512-845-4500 (office)Contact: Denny Kapowitz

[email protected]

Company has full test and balance capability.

Testing Specialties, Inc. 12001 Network Blvd., #124San Antonio, Texas 78249-3355 210-492-8885 (office)210-492-8887 (fax)Contact: Wes Harvey, P.E.

[email protected]

Company has full test and balance capability.

Last revision on 3/7/2016

AFD Requirements for other types of Smoke Management Systems such as Atrium Exhaust and Zoned Pressure Systems will be handled based on the original design and discussion with AFD

Mike Locke  (800) 328‐3588

Thank You All for your Attendance Today and 

Lets open the floor to questions

18

SPECIAL INSPECTION AGENCYANNUAL STAIRWELL PRESSURIZATION SYSTEM TEST

REPORT

Date

Special Inspection Agency Name Project NameProject Address

SUBMITTED TOAustin Fire Department Fire

Marshal’s Office505 Barton Springs Road, Suite

200Austin, TX 78704

CERTIFICATION PAGE

Special Inspection Agency Name Project NameProject Address

Certified By: Name AABB or NEBB number:Certification Expiration date:

Provide seal here

Date:

Special Inspection Agency Name Project NameProject Address

INSTRUMENT CALIBRATION REPORT

Manufacturer Model Serial # Instrument Type Calibration Date

ANNUAL STAIRWELL PRESSURIZATION SYSTEM TEST REPORT

SUMMARYSpecial Inspection Agency Name 

Project NameProject Address

Function Pass Fail CommentsSystem operates from onepull, one heat detector, onesmoke detector and one

water flow switch (4 devices total)

Firefighter’s smoke controlpanel operatesproperly

Firefighter’s smoke control panel is in acceptable condition.  All 

status lights and switches function as intended

System operates onemergency power

Pressure difference from stair to vestibule to floor/corridor is 0.10”

w.g. minimumWith open ground floor exterior stairwell door pressure difference 

from stair to vestibule to floor/corridor is 0.10”w.g.Excess pressure reliefdevice(s) and/or VFD

pressure controls operateproperly

All fans, belts and control dampers inspected for proper operation andcondition (belts replaced every 5

years)Control dampers/barometric 

dampers have properorientation and are in good

operating conditionDoors latch properly and can be 

opened by a force of notgreater than 30 lbs.

ANNUAL STAIRWELL PRESSURIZATION SYSTEM TEST REPORTSpecial Inspection Agency Name 

Project NameProject Address

Technician: Test Date:

CLOSED DOOR TESTStairwell ID:

Floor ID

Vestibule to Stair pressure (inch

w.g.)

Vestibule to Floor/corridor 

pressure (inch w.g.)

Total Pressure fromStair to 

Floor/corridor (inchw.g.)

Stairdoorpull(lbs.)

Vestibule door pull (lbs.)

ANNUAL STAIRWELL PRESSURIZATION SYSTEM TEST REPORTSpecial Inspection Agency Name 

Project NameProject Address

Technician: Test Date:

CLOSED DOORS PLUS OPEN GROUNDFLOOR STAIR DOOR TEST

Stairwell ID:Floor ID

Vestibule to Stair pressure (inch w.g.)

Vestibule to Floor/corridorpressure (inch w.g.)

Total Pressure from Stair toFloor/corridor (inch w.g.)

ANNUAL STAIRWELL PRESSURIZATION SYSTEM TEST REPORTSpecial Inspection Agency Name 

Project NameProject Address

Technician: Test Date:

System Activation Verification

Indicate Specific Location and Fire Alarm System ID of each device

Floor ID Manual pull Heat detector Smoke detector

Fire sprinkler water flow

Special Inspection Agency Name Project NameProject Address

Report Summary

What year was the building constructed?  If you don’t know,email us and ask.  We will research the date of construction, thebuilding code was enforced at the time and what the smokecontrol requirements were.  How many floor levels and stairtowers does the building have?  Does the building have stairvestibules?  Is there a relief vent at the top of each stair tower? Provide a general description of the building (e.g., 10 floors ofopen parking garage with 10 floors of office occupancies abovegarage level 10).  Are VFD fans provided?  Note any problems that you encountered.  Is a follow up test or inspection by usrequired?  Is there anything we need to know about?  If you seesomething that is not correct, email us or call us to discuss it.


Recommended