ANSI-J-STD-607-A Harger Lightning & Grounding
Transcript
Page 1: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

ANSI-J-STD-607-A

Harger Lightning & Grounding

Page 2: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Purpose

The purpose of this presentation is to give the user a better understanding of the requirements set forth by ANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications

Page 3: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

ANSI J-STD-607-A

This standards specifies the requirements for a uniform telecommunications grounding and bonding infrastructure that shall be followed within commercial buildings where telecommunications equipment will be installed.

Page 4: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications

Definition:All forms of information that are conveyed within the building, for example voice, data, video, environmental control, security, audio, etc.

Page 5: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications Grounding Infrastructure

Large Building Scope

Large Commercial Buildings

Page 6: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Small Commercial Buildings

Telecommunications Grounding Infrastructure Small Building Scope

Page 7: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Main Elements of Telecomm Grounding and Bonding Structures

Telecomm Main Grounding Busbar (TMGB)

Telecomm Bonding Conductor (TBC)

Telecomm Bonding Backbone (TBB)

Telecomm Grounding Busbar (TGB)

Grounding Equalizer, (Formerly TBBIBC)

Page 8: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications Main Grounding Busbar (TMGB)

Page 9: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications Main Grounding Busbar (TMGB)

Serves as the dedicated extension of the building grounding electrode system for the telecommunications infrastructure.Also serves as the central attachment point for the telecommunications bonding backbone (TBB) and equipment.Typically 1 per building.

Page 10: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

TMGB Requirements

Have minimum dimensions of ¼” thick, 4” wide and variable in lengthBe listed by a nationally recognized testing laboratoryShall be insulated from its support by a minimum of 2”Located so that it is accessible to telecommunications personnelThe busbar shall be cleaned prior to fastening of conductors and an anti-oxidant should be applied to the contact area to control corrosion and reduce contact resistance

Page 11: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connections to TMGB/TGB

Surface Surface PreparationPreparation

Antioxidant Antioxidant AppliedApplied

Mechanical Mechanical ConnectionConnection

1

Page 12: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connections to the TMGB

Panel Board Alternating Current Electrical Ground (ACEG)Metallic RacewaysTBCTBB

Page 13: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Panelboard

5.2.6.1 Where a panelboard (electrical power panel) is located in the same room or space as the TMGB that panelboard’s alternating current equipment ground (ACEG) bus (when equipped) or the panelboard enclosure shall be bonded to the TMGB.

5.2.6.2 The TMGB shall be as close to the panelboard as practicable and shall be installed to maintain clearances required by applicable electrical codes.

Page 14: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Panel Board

The standard does not specify what size conductor to use when bonding the panel board to the TMGB. We recommend a minimum of #6 AWG and a maximum length of 13’

Page 15: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Conductor Connections to the TMGB

5.2.7.1 The connections of the bonding conductor for telecommunications and the TBB to the TMGB shall utilize exothermic welding, listed compression lugs, suitable and equivalent one hole non-twisting lugs, or other irreversible compression type connections. Two-hole lugs are preferred.

5.2.7.2 The connections of the bonding telecommunications equipment to the TMGB shall utilize exothermic welding, listed compression lugs, or other irreversible compression type connections. Two-hole lugs are preferred.

Page 16: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

2-Hole Compression Lugs

Although they’re only recommended by the standard and not required, we strongly advocate their use2-hole lugs offer more surface area than a 1-hole lug2-hole lugs are much less apt to loosen over time versus a 1-hole lug

Page 17: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Compression Lugs

Inspection Port

Long Barrel

2-Holes

Page 18: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connection Process

Trim insulation back so thatbared conductor is slightly longer than barrel.

Page 19: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connection Process

Insert conductor so that itButts up against end of barrel.View this thru inspection port.

Page 20: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connection Process

2 crimp minimum

Make sure end of conductorremains at end of barrel;make first crimp,repeat crimping process

Page 21: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connection Process

2 Crimp Minimum

Page 22: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Metallic Raceways/Equipment Racks

All metallic raceways for telecommunications cabling located within the same room or space as the TMGB shall be bonded to the TMGB. However, for metallic pathways containing grounding conductors where the pathway is bonded to the grounding conductor, no additional bond to the TMGB is required.

Page 23: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Bonding Metallic Raceways/Equipment Racks

Locate an area on the rack or raceway to attach a bonding conductor. This location should have adequate access while providing minimal obstruction to rack mounted equipment. Remove any paint, oxidation and dust from the surface using a grinding tool.Apply a generous coating of aluminum Antioxidant Joint Compound to the mounting surface.Attach bonding conductor using a two-hole compression lug and stainless steel hardware.Wipe off any excess antioxidant material.

Page 24: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Other Attachments to the TMGB

The primary protector grounding conductor shall be connected to the TMGB. This conductor is intended to conduct lightning and ac fault currents from the telecommunication primary protectors. A minimum of 300 mm (1 ft) separation shall be maintained between this insulated conductor and any dc power cable, switchboard cable, or high frequency cables, even when placed in rigid metal conduit or EMT.

Page 25: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Other Attachments to the TMGB

When the outside plant cable in the TEF incorporate a cable shield isolation gap, the cable shield on the building side of the gap shall be bonded to the TMGB.In buildings where the backbone cable incorporates a shield or metallic member, this shield or metallic member shall be bonded to the TMGB or TGB.

Page 26: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Bonding Conductor for Telecommunications

5.3.1 The bonding conductor for telecommunications shall bond the TMGB to the service equipment (power) ground.

5.3.2 The bonding conductor for telecommunications shall be, as a minimum, the same size as the Telecommunications Bonding Backbone Conductor (TBB).

Page 27: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecomm Bonding Conductor(Bond to Electrical Service Ground)

Page 28: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications Bonding Backbone (TBB)

The TBB is a conductor that interconnects all TGBs with the TMGBOriginates at the TMGB extends throughout the building using the telecommunications backbone pathways, and connects to the TGBs in all telecommunications rooms and equipment rooms.

TBB

Page 29: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

TBB Function

The intended function of a TBB is to reduce or equalize potential differences between telecommunications systems. While the TBB will carry some current under ac power ground fault conditions, it is not intended to provide the only ground fault return path.

Page 30: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

TBB Material Requirements

The TBB shall be a copper conductor. The minimum TBB conductor size shall be a No. 6 AWG. The TBB should be sized at 2 kcmil per linear foot of conductor length up to a maximum of 3/0 AWG. The TBB may be insulated; if the TBB is insulated, the insulation shall meet the fire ratings of its pathway. The sizing of the TBB is not intended to account for the reduction or control of electromagnetic interference.

Page 31: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

TBB Installation Requirements

The TBB conductors should be installed without splices. Where splices are necessary, the number of splices should be a minimum and they shall be accessible and located in telecommunications spaces. Joined segments of a TBB shall be connected using exothermic welding, irreversible compression-type connectors, or equivalent.

Page 32: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Conductor Sizing

Applies to TBB, GE & TBC

Page 33: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

TBB no-no’s

The interior water piping system of the building shall not be used as a TBB.The metallic cable shield shall not be used as a TBB.

Page 34: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Grounding Equalizer

Conductor that connects elements of the telecommunications grounding infrastructure. (Formerly TBBIBC).Interconnects multiple TBB’s on the top floor and every 3rd floor in betweenFollows same sizing requirements as the TBB.

Page 35: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Telecommunications Grounding Busbar (TGB)

The TGB is the grounding connection point for telecommunicationssystems and equipment in the area served by that telecommunications room or equipment room.The TGB shall have minimum dimensions of ¼” thick by 2” wide and variable in length.Shall be listed by a nationally recognized testing laboratory.

Page 36: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connections to the TGB

5.5.2.1 The TBBs and other TGBs within the same space shall be bonded to the TGB with a conductor the same size as the TBB.5.2.6.1 Where a panelboard (electrical power panel) is located n the same room or space as the TMGB that panelboard’s alternating current equipment ground (ACEG) bus (when equipped) or the panelboard enclosure shall be bonded to the TMGB.

Page 37: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Connections to the TGB

The TGB shall be bonded to the GE where required (Top Floor and every 3rd floor in between).

All metallic raceways for telecommunications cabling located within the same room or space as the TGB shall be bonded to the TGB

Connections of the TBB and the GE to the TGB shall utilize exothermic weld connections, listed compression two hole lug connectors, suitable and equivalent one-hole non-twisting lugs or other irreversible compression type connectors. Two-hole connectors are preferred.

TGB

Page 38: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Other Attachments to the TGB

Multiple TGBs may be installed within the same telecommunications room to aid in minimizing bonding conductor lengths and terminating space. In all cases, multiple TGBs within a room shall be bonded together with a conductor the same size as the TBB or with splice bars.

In buildings where the backbone telecommunications cabling incorporates a shield or metallic member, this shield or metallic member shall be bonded to the TGB where the cables are terminated or where pairs are broken out.

Short metallic pathways (e.g. wall and floor sleeves) are not required to be bonded.

Page 39: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Bonding to the Metal Building Frame

In a metal frame (structural steel) building, where the steel framework is readily accessible within or external to the room; each TGB and TMGB shall be bonded t the vertical steel metal frame using a minimum No. 6 AWG conductor.

When practicable because of shorter distances and, where horizontal steel members are permanently electrically bonded to vertical column members, the TGB may be bonded to these horizontal members in lieu of the vertical column members.

Page 40: ANSI-J-STD-607-A - · PDF fileANSI-J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for ... Serves as the dedicated extension of the building grounding

Summary

For over the past hour, we have presented a large amount of information concerning grounding and bonding, hopefully some of it was informative. If there are other issues you would like addressed, please contact us. Thank you for your time.