140 APPLICATION FOR APPROVAL OF CONSTRUCTION CHANGE DOCUMENT – CCD CATEGORY A/B This application is for construction changes, as defined in IR A-6, to approved contract documents. This form shall be completed by the Design Professional in General Responsible Charge of the project, in accordance with California Code of Regulations, Title 24, Part 1, Section 4-338 (c) and in compliance with DSA IR A-6.
School District/Owner: DSA File #:
-
Project Name/School: DSA App. #:
-
APPLICANT CCD Cat. A / B, #: Date Submitted: Attached Pages?: No Yes (_____pages)
For CCD Cat. B, this is a voluntary submittal, DSA required submittal (attach DSA notification requiring submission).
Firm Name: Contact Name:
Email: Phone Number: Address: City: State: Zip:
A DSA 301-N, DSA 301-P, or 90-Day Letter has been issued for this project.
For project currently under construction.
To obtain DSA approval of existing uncertified building(s).
DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE Name of Design Professional in General Responsible Charge: Professional License #: Discipline:
Design Professional in General Responsible Charge Statement: The attached Construction Change Documents have been examined by me for design intent and appear to meet the appropriate requirements of Title 24, California Code of Regulations and the project specifications. They are acceptable for incorporation into the construction of the project. Signature: _______________________________________________________________________________________ DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE
CHECK THIS BOX: To confirm that all CCD drawings and, when applicable, first sheet or index of calculations and specifications have been stamped and signed by the Responsible Design Professional listed on DSA 1 for this this project. Brief description of construction change (attach additional sheets if needed):
List of DSA approved drawings affected by this CCD:
DSA USE ONLY For business office use only
Date Sent Return By Delivery Method
DSA Stamp
SSS Date Approved / Disapproved / Not Req’d
FLS Date Approved / Disapproved / Not Req’d
ACS Date Approved / Disapproved / Not Req’d
Remarks
DSA 140 (rev 12-16-16) Page 1 of 1 DIVISION OF THE STATE ARCHITECT DEPARTMENT OF GENERAL SERVICES STATE OF CALIFORNIA
Long Beach Unified School District 19 62
Longfellow HVAC Alteration 03 118620
2 03/26/19 37
TSK, Inc. Juan Cervera
[email protected] (213) 614-0900
888 S. Figueroa Street #2020
Los Angeles CA 90017
James Windom Kimsey
28235 Architectural
Owner requested existing kitchen hood to be upgraded to a Type 1 hood. This CCD revises architectural reflectedceiling plan, structural attachments, mechanical equipment, and electrical requirements based on new kitchen hood.
A124, A128, S4, P114, M006-M008, M114, E002, E003, E114, FA001-FA003, FA134
SSS Date Approved
ACS Date Approved
FLS Date Approved
_____ ________
_____ ________
_____ ________
Not Approved Not Required
Not Approved Not Required
Not Approved Not Required
AS 05/08/2019
SH 12/06/2018
✔
✔
✔
Approved Sheets: CCD2-ASK1, CCD2-ASK2,SK-S8, SK-S9, P-114, M-006, M-007, M-008,M-114, E002, E003, E114, FA001, FA002,FA003 and FA134.
1 | 1
PRINCIPALS
J. Windom Kimsey, FAIA | Michael J. Purtill, AIA | Patrick Pusich, AIA | Hazim J. Rabadi, AIA | Shelly A. Lyons | George G. Tate, AIA R e t i r ed | William E. Snyder, FAIA R e t i r ed
www. tska .com
l a s v e g a s | l o s a n g e l e s | r e n o | s h e n z h e n
tsk T A T E S N Y D E R K I M S E Y
CONSTRUCTION CHANGE DOCUMENT
CONSTRUCTION CHANGE DOCUMENT NO: 02
DATE: 10/24/2018
TO: Balfour Beatty Construction
1501 Quail Street, Suite 130
Newport Beach, CA 92660
RE: Longfellow Elementary School HVAC Alteration
Long Beach Unified School District
DSA A# 03-118620 / File 19-62
DISCIPLINE: ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
DESCRIPTION: Owner requested existing kitchen hood to be upgraded to a Type 1 hood. This CCD
revises architectural reflected ceiling plan, structural attachments, mechanical
equipment, and electrical requirements based on new kitchen hood.
Please note attached sheet(s).
This information is intended to clarify plans or specifications.
Submit quotations to job inspector for verification of quantities by signature.
Submit fully itemized charges and/or credits, showing net totals.
Verify there shall be no change in cost.
This change order is effective now, pending formal change order approval.
FROM: Juan Cervera
Senior Project Manager
Tate Snyder Kimsey, Inc.
(E) CEILING TO BEREMOVED
REMOVE (E) GLUE-UPACOUSTIC TILES
1tWINDOW TAG, SEE SHEET A601FOR WINDOW RELATED SCOPE
REMOVE (E) 2'x4' ACOUSTICCEILING TILES
DIRECTION OF (E) CEILINGJOIST FRAMING
1
1
2
6
2
6
7
7
12
12
CLASSROOM
4103
CLASSROOM
4101
ALLGENDER
RESTROOM
4102A
ALLGENDER
RESTROOM
4104A
ALLGENDER
RESTROOM
4102B
ALLGENDER
RESTROOM
4104B
STORAGE
4105
22
22BUILDING 3
24' -
2"
4' -
3"
5' -
0"
4' -
5"
4
4
TYPOF 2
TYPOF 2
17
17
2
2
6
6
9
13
13
TYP4
7
14
14
14
15
12
12
12
MECHANICALROOM
ALLGENDER
RESTROOM
5101
AUDITORIUM
5103
ALLGENDER
RESTROOM
5102
LOBBY
5100
BOY'SRESTROOM
5106
STORAGE
5107
VESTIBULE
5105
VESTIBULE
5104
STAGE
5108CAFETERIA
5113
LOUNGE
5114
KITCHEN
5115
OFFICE/STORAGE
5117
ALLGENDER
RESTROOM
5118
W.H
5116
VESTIBULE
5118A
STORAGE
5109
VESTIBULE
5111
VESTIBULE
5112
GIRL'SRESTROOM
5110
6
TYP OF 4
6
TYP OF 8
1819
20
21
23
TYP OF 4
6
6
6
TYP OF 3
15CCD
2
1
CCD6-SK-03
KEYNOTES
GENERAL NOTES
LEGEND
KEYPLAN
Long BeachUnified
School District
Clie
ntC
onsu
l tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
Shee
t Ti
tleSh
eet N
o.Sh
eet In
fo
DATE:
PROJ MGR:
SCALE:
JOB No.:
Issu
eA
gen
c y A
ppro
val
AC
DIV. OF THE STATE ARCHITECT
IDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:
A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arc
hite
ctSt
am
ps
1
5
4
Scale
Gra
ph i
cKey
Pl a
nN
otes
/ L
egen
ds
CDEF
LBUSD No.:
Facilities Management
316 West 2nd StreetSuite PH
Los Angeles, CA 90012phone: 213.614.0900
fax: 213.929.2247www.tska.com
1/8" = 1'-0"
Lo
ng
fello
w E
S H
VA
C A
ltera
tio
n
3800 O
live A
ve,
Long B
each, C
A 9
0807
64725-327
CCD2-ASK1
DEMOLITION RCPBLDG 4 & 5
JCJ
07/10/18
9119-1617-440
LO
NG
FE
LLO
W E
LE
ME
NT
AR
Y S
CH
OO
L
CC
D2
19-62
03-118620
1 (E) SOFFIT TO REMAIN, P.I.P
2 REMOVE (E) GLUE-ON ACOUSTIC TILES AND HARDLID CEILING. (E) CEILING JOISTS TO REMAIN -P.I.P
3 (E) CEILING JOISTS TO REMAIN - P.I.P
4 REMOVE PARTIAL CEILING FOR INSTALLATION OFNEW WORK.
5 REMOVE (E) GYP SOFFIT FRAMING
6 REMOVE (E) CEILING MOUNTED LIGHT FIXTURES
7 REMOVE (E) CEILING FAN
8 REMOVE (E) SUSPENDED ACOUSTICAL CEILING GRIDSYSTEM
9 REMOVE (E) ACCESS PANEL
10 (E) LOUVER ABOVE DOOR TO REMAIN, P.I.P
11 REMOVE (E) ACOUSTIC TILE CEILING, (E) CEILINGJOISTS & HANGERS
12 REMOVE (E) CEILING. (E) CEILING JOISTS TO REMAIN- P.I.P
13 REMOVE (E) HVAC EQUIP IN ATTIC SPACE
14 REMOVE (E) KITCHEN HOOD
15 REMOVE (E) GLUE-UP AND PLASTER CEILING, (E)CEILING JOISTS TO REMAIN
16 REMOVE (E) CEILING & JOISTS
17 REMOVE (E) WALL MOUNTED HEATER - TYP.
18 REMOVE (E) PROJECTOR SCREEN
19 REMOVE (E) PROJECTOR
20 (E) CEILING ACCESS PANEL TO REMAIN - P.I.P
21 REMOVE (E) LOUVER
22 REMOVE (E) PLASTER CEILING AS REQUIRED FORINSTALLATION OF (N) WORK. SEE STRUCTURALDRAWINGS
23 REMOVE (E) REGISTERS
24 PROTECT (E) CABLING AND STUB OUT ABOVE NEWCEILING FOR DISTRICT REINSTALLATION.
25 REMOVE (E) NON-STRUCTURAL WOOD CEILINGJOISTS ABOVE (E) SUSPENDED CEILING
26 (E) SOFFIT TO BE REMOVED
1 THE CONTRACTOR IS RESPONSIBLE FOR THEREMOVAL & PROCESSING OF ANY HAZARDOUSMATERIALS ENCOUNTERED DURING DEMOLITIONWORK AS REQUIRED BY LOCAL STATE LAWS.
2 IN ADDITION TO DEMOLITION SHOWN, CUT, CAP,MOVE OR REMOVE ITEMS AS NECESSARY TOPROVIDE ACCESS OR TO ALLOW ALTERATIONS &NEW WORK TO PROCEED, INCLUDE SUCH ITEMS: 1)REMOVAL OF ABANDONED ITEMS & ITEMS SERVINGNO USEFUL PURPOSE SUCH AS ALL ABANDONEDPIPING, DUCTING, & WIRING. 2) CLEANING OFSURFACES, & REMOVAL OF SURFACE FINISHES ASNEEDED TO INSTALL NEW WORK & FINISHES
1/8" = 1'-0"
1DEMOLITION - BLDG 4 RCP
1/8" = 1'-0"
2DEMOLITION - BLDG 5 RCP
REFERENCE SHEET A124
CCD
2
2 06/07/2018 CCD-2
(REVISED A124)
CCD
2
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
9
A301
ACT
KITCHEN
5115
LOUNGE
5114CAFETERIA
5113
STAGE
5108
AUDITORIUM
5103
STORAGE
5107
ALL GENDERRESTROOM
5106
VESTIBULE
5104
VESTIBULE
5105
STORAGE
5109ALL GENDERRESTROOM
5110
VESTIBULE
5111
VESTIBULE
5112ALL GENDERRESTROOM
5102
LOBBY
5100
ALL GENDERRESTROOM
5101
TYP4
2
ACT
3
3
A501
GYP
GYP
OFFICE/STORAGE
5117 W.H
5116
ALL GENDERRESTROOM
5118
VARIES
CAFETERIA
5113
9
10
GYP
GYP
GYP
15
12
14
EQ3 EQ3
EQ
4E
Q4
4' - 0".
EQ
2E
Q2
EQ1 EQ1
1'-6" MIN. 18' -
1"
4' -
1"
11"
8' -
2"
6' - 7"
12"
12"
19
CCD
2
1
CCD6-SK-03
21
(N) LIGHT FIXTURES(SEE ELECTRICAL PLANS)
(N) GYP. BOARD CEILING
(N) 2'x4' SUSPENDED ACOUSTICALCEILING
(N) SUPPLY AIR REGISTER(SEE MECHANICAL PLANS)
(N) RETURN AIR REGISTER(SEE MECHANICAL PLANS)
(N) EXHAUST AIR REGISTER(SEE MECHANICAL PLANS)
1tWINDOW TAG, SEE SHEET A601FOR WINDOW RELATED SCOPE
DIRECTION OF (E) CEILINGJOIST FRAMING
(N) 2'x6', 4'X4', 4' X 8' SURFACE MOUNTEDCEILING
KEYNOTES
GENERAL NOTES
LEGEND
KEYPLAN
Long BeachUnified
School District
Clie
ntC
onsu
l tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
Shee
t Ti
tleSh
eet N
o.Sh
eet In
fo
DATE:
PROJ MGR:
SCALE:
JOB No.:
Issu
eA
gen
c y A
ppro
val
AC
DIV. OF THE STATE ARCHITECT
IDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:
A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arc
hite
ctSt
am
ps
1
5
4
Scale
Gra
ph i
cKey
Pl a
nN
otes
/ L
egen
ds
CDEF
LBUSD No.:
Facilities Management
316 West 2nd StreetSuite PH
Los Angeles, CA 90012phone: 213.614.0900
fax: 213.929.2247www.tska.com
1/8" = 1'-0"
Lo
ng
fello
w E
S H
VA
C A
ltera
tio
n
3800 O
live A
ve,
Long B
each, C
A 9
0807
64725-327
CCD2-ASK2
REFLECTEDCEILING PLAN
BLDG 4 & 5
JCJ
06/04/18
9119-1617-440
LO
NG
FE
LLO
W E
LE
ME
NT
AR
Y S
CH
OO
L
CC
D2
19-62
03-118620
1/8" = 1'-0"
2RCP - BLDG 5
REFERENCE SHEET A128
1 INCLUDE ALL FIELD AND PERIMETER BLOCKING ASREQUIRED TO FASTEN PAINTED GYPSUM BOARDCEILINGS
2 UNLESS OTHERWISE NOTED, ALL INTERIOR WALLSSHOWN ON THE FLOOR PLAN ARE TO EXTEND TOTHE UNDERSIDE OF THE ROOF SHEATHING WITH ONELAYER OF 5/8" THICK TYPE "X" GYPSUM BOARD EACHSIDE OF STUD FACE. ALL STUD WALLS TO CONTAINSOUND INSULATION BATTS, FULL HEIGHT
1 (E) LOCATION ON ACCESS PANEL TO ATTIC SPACE-P.I.P
2 (N) ACCESS PANEL, SEE DETAIL 12/A501
3 PATCH & REPAIR CEILING AS REQUIRED BY (N) WORK
4 SEAL (N) CEILING AROUND (E) EQUIPMENT
5 (N) ROLLER SHADES, SEE DETAIL 6/A501
6 (N) CEILING MOUNTED PROJECTOR. MOUNTED ONT-BAR SYSTEM WITH EXTRON PCM-340 AND PCM-AM
7 (N) CEILING MOUNTED PROJECTION SCREEN PERDETAIL 7/A501
8 PATCH & REPAIR LATH & PLASTER CEILING ASREQUIRED BY (N) WORK
9 (N) LONG THROW WALL MOUNTED PROJECTOR, SEEDETAIL 12/A303 SIM.
10 (N) MOTORIZED PROJECTOR SCREEN
12 (N) 2'X4' SURFACE MOUNTED CEILING
14 (N) 4'X4', 4'X8', AND 2'X6' SURFACE MOUNTED CEILINGTILES
15 (N) 4'X4' SURFACE MOUNTED CEILING
16 EDGE OF (N) GYP. BD. ABOVE
17 (N) LIGHTS PER ELECTRICAL
18 ILLUMINATED EXIT SIGN, SEE ELECTRICAL DRAWINGS
19 (E) KITCHEN HOOD TO BE REPLACED, SEEMECHANICAL DRAWINGS
20 (N) WOOD FRAMED CEILING W/ GYP. BD. FINISH
21 (N) CLASS K FIRE EXTINGUISHER
CCD
2
2 06/07/2018 CCD-2
(REVISED A128)
CCD
2
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
S0.1
12
MECH. UNIT 100 LBS.
MECH. UNIT 450 LBS.
MECH. UNIT 200 LBS.
LAP (N) 2x10 PER DET.S0.1
16
TYP.B
S-4
.
.
.
.
.
.
(E)2x10 AT 16" O.C.
(E)2x10 AT 16" O.C.
8' -
0"
B
S-4
HOOD AND PLENUM(961 LBS. TOTAL)
LAP (N) 2x10 PER DET.S0.1
16
INLINE SUPPLYFAN 160 LBS.
EXHAUST UTILITYFAN 275 LBS.
B
S-4
1
SK-S9
(E)2x14 AT16" O.C.
LAP (N) 2x10PER DET.
S0.1
16
MECH. UNIT 200 LBS.TYP.B
S-4
S0.1
13
S0.1
0.6
EXTENT OF (E)2x14AND (N)LAPPED 2x14'S
(E)2x10 AT 16" O.C.
LAP (N) 2x10PER DET. S0.1
16.
.
.
(E)2x10 AT 16" O.C..
.
BUILDING #5
KEY PLAN
888 S Figueroa StreetLas Vegas, CA 90017Tel. 213 . 614 . 0900
A R C H I T E C T S
R e v . D a t e D e s c r i p t i o n
P r o j e c t
C o n t r a c t N o .
D r a w i n g N o .
R E F :
tsk
DIVISION OF THE STATE ARCHITECT
DSA FILE#:
APPLICATION #:
CCD#:
New Sheet SK-S803/26/19
Longfelllow E.S. HVAC Alteration
17-052.00
PARTIAL LOW ROOF FRAMING PLAN
CCD-2
3/32" = 1'-0"SK-S8
1 PARTIAL LOW ROOF FRAMING PLAN - BLDG 5
03-118620
19-62
(REVISED 2/S-4)
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
4x4 BLKG. w/ SIMPSONU44 HANGER (TYP.)
SISTERED JOIST WHEREOCCURS PER PLAN
(E) PLATFORMSHEATHING
1/2" DIA. ALL-THREADHANGER ROD (TYP.) @EA. CORNER (42" O.C.MAX.) W/ROD STIFF.PER
HANGER BRACKETPER MANUF. (TYP.)
#10x3" EMBED WOODSCREWS @ MOUNTINGBRACKET PER MANUF.(32" O.C. MAX. SPACING)
(E) 2x6 STUDS AT 16" O.C.
A
SECTION A
HOOD PER PLAN,MAX OP WT=838#
HOOD PER PLAN,MAX OP WT=838#
10" M
AX
.
1/2" DIA. ALL-THREADHANGER ROD (TYP.) @ EA.CORNER (42" O.C. MAX.)W/ROD STIFF. PER
DOUBLE NUT & WASHER(TYP.)
2"x2"x1/4" ANGLE BRACEEACH WAY @ CORNERS
(2)5/8" DIA. M.B.
4x4 BLKG. w/ SIMPSON"A34" EA. SIDE EA. END
3" M
IN.
1/2" DIA. THRU-BOLTAT 42" O.C. MAX.
(N) 4x BLKG. W/A35 T&B w/#6x3/4" WOOD SCREWS
S0.1
16
S0.1
17
(E)2x14JOISTS AT 16"O.C.
2" M
IN.
(N)4x10 BLOCKINGW/SIMPSON A35EA. SIDE EA. ENDTYP.
3"
PLENUM PER MECH'L,MAX OP WT=123#
(N) A34 T&B EA. END
(E) 1" DIAGONAL SHTG.
S0.1
17
2" M
AX
.
4x4 BLKG. W/SIMPSON"U44" HANGER TYP.
888 S Figueroa StreetLas Vegas, CA 90017Tel. 213 . 614 . 0900
A R C H I T E C T S
R e v . D a t e D e s c r i p t i o n
P r o j e c t
C o n t r a c t N o .
D r a w i n g N o .
R E F :
tsk
DIVISION OF THE STATE ARCHITECT
DSA FILE#:
APPLICATION #:
CCD#:
New Sheet SK-S903/21/19
Longfelllow E.S. HVAC Alteration
17-052.00
ANCHORAGE OF SUSPENDED HOOD
CCD-2
3/4" = 1'-0"SK-S9
1 ANCHORAGE OF SUSPENDED HOOD
03-118620
19-62
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
CLASSROOM4101
CLASSROOM4103
STORAGE4105
ALL GENDERRESTROOM
4102ALL GENDERRESTROOM
4104
(E)3/4"CW
(E)2
"CW
1"C1"C
STAGE5108
CAFETERIA5113
AUDITORIUM5103
KITCHEN5115
LOUNGE5114
STORAGE5107
STORAGE5109
LOBBY5100
ALL GENDERRESTROOM
5101
ALL GENDERRESTROOM
5102
VESTIBULE5112
VESTIBULE5111
ALL GENDERRESTROOM
5110
ALL GENDERRESTROOM
5106VESTIBULE
5105VESTIBULE
5104
1"C
1"C
(E)1
1/4
"CW
(E)2
1/2
"G
(E)1 1/4"G(E)2 1/2"CW
(E) TO REMAIN
ALL GENDERRESTRROM
5118
W.H.5116
OFFICE/STORAGE5117
(E)1 1/4"G
(E) G
ALL GENDERRESTROOM
4102
ALL GENDERRESTROOM
4104
2"CW
(E)2
"CW
(E)3
/4"C
W
(E)3/4"CW
ALL GENDERRESTROOM
5102
(E)1
1/4
"CW
(E)2
1/2
"G
(E)2 1/2"G
(E)2 1/2"CW
1 1/4"CW
ALL GENDERRESTROOM
5101
(E)2
1/2
"G
(E)1
1/4
"CW
3/4"CW
3/4"
CW
No. 27963
Exp. 6/30/20
REGISTERED
PROFESSIONAL
ENGINEER
BRAD
LEYE. SEVERSON
M
ECHANICA
L
STA
T E OF CAL IFOR
NIA
LPV 626 714-7506 FAX 626 714-7512 Pasadena, California 91103 751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
KEYPLAN
As indicated
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
P-114
PLUMBINGFLOOR PLANBLDG. 4 & 5
BES10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
CAD
P-114PLUMBING FLOOR PLAN BLDG. 4 1
P-114PLUMBING FLOOR PLAN BLDG. 5 2
SHEET NOTES:ALL PLUMBING FIXTURES AND ASSOCIATEDPIPING IN THIS AREA SHALL BE REPLACEDUNLESS OTHERWISE NOTED; SEE ENLARGEDPLAN THIS SHEET.
PROVIDE NEW SINK AND CONNECT TOEXISTING WASTE AND WATER PIPING;OFFSET IF REQUIRED (SEE ARCH'L. PLANS FORADDITIONAL IN FORMATION).
FAN COIL UNIT (SEE HVAC PLANS); RUNCONDENSATE TO APPROVED RECEPTOR ASINDICATED.
REPLACE (E) DRINKING FOUNTAIN WITH NEWDUAL HT DF. CONNECT TO (E) WASTE & WATERPIPING; OFFSET IF REQUIRED (SEE ARCH.PLANS FOR ADDITIONAL INFORMATION).
EXISTING DRINKING FOUNTAIN TO REMAIN.
1" CONDENSATE DRAIN DOWN IN WALL ANDSPILL TO FIXTURE SIDE OF LAV/SINK P-TRAP.OVERFLOW TO SPILL TO EASILY OBSERVABLELOCATION.
INSTALL NEW FIXTURE AT LOCATIONINDICATED; OFFSET OR EXTEND TO EXISTINGWASTE VENT, CW AND HW PIPING ASREQUIRED; SEE ARCH'L. PLANS FORADDITIONAL IN FORMATION; FIELD VERIFYEXACT POC.
CONNECT TO (E) PIPING; FIELD VERIFYEXACT POC.
EXISTING INSTANTANEOUS WATER HEATER.
3/4" CW & HW DOWN TO NEW LAVATORY;PROVIDE W/ TEMPERED VALVE SET @ 110°F FOR HW SERVICE.
REPLACE (E) DRINKING FOUNTAIN(S) WITHNEW DUAL HT DF.
PROVIDE NEW GAS MOTORIZED SOV IN (E) GASPIPING SERVING APPLIANCES UNDER HOOD,AND INTERLOCK W/NEW HOOD ANSUL SYSTEM;FIELD VERIFY EXACT LOCATION OF (E) GASPIPE, & PROVIDE ACCESS PANELS REQUIRED.
1
2
3
4
5
6
7
8
P-114BLDG. 4 GIRL'S & BOY'S RESTROOM ENLARGED PLUMBING PLAN 3
5
3
36
1
SKAH
2
2
P.O.C.P.O.C.
SKAH
2WCAH
8
7LVAH
7
WCAH
7LVAH
7
8
3
3
3
DFBH
4
P-114BLDG. 5 ALL GENDER RESTROOM ENLARGED PLUMBING PLAN 4
P-114BLDG. 5 ALL GENDER RESTROOM ENLARGED PLUMBING PLAN - 5
LVCH
7WCCH
7
P.O.C.
8
WCCH
7LVCH
7
P.O.C.
8
(E)HB
1
6
(E)2-1/2"CW
(E)2-1/2"G
3
3
6
8
8
8
8
8
8
8 8
FDA1
8
P-114BLDG. 5 STAFF RESTROOM ENLARGED PLUMBING PLAN 6
1
WCCH
7LVCH
7
8
8
8
P.O.C.
9
6P-114
3P-114
4P-114
5P-114
9
8
5
10
FDA1
8
10
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
USER GROUP ADULTS
USER GROUP ADULTS
USER GROUP ADULTS
USER GROUP 5-12 YEARS OLD
DFBH
11
11
7
12
12
2
2
2 06/04/18 CCD-2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
KITCHEN HOOD UNITINSTALLATION NOTES
AND WIRING DIAGRAMKITCHEN HOOD EXHAUST CONTROL 3SCALE
NONE
KITCHEN HOOD EXHAUST DUCT ENCLOSURE DETAILSCALE
NONE2
KITCHEN EXHAUST FAN INSTALLATION (GEF-1) SCALE
NONE1
MMANAGEMENT SYSTEMSIGNAL TO ENERGY
M
120 V / 1 ph
REMOTE START/STOP SWITCHW/ PILOT LIGHT
M
E
RELAY (NO.)
MAGNETIC STARTER
115 V / 1ph
(TYP.)
208 V / 1ph
GEF1
GSF1
SEE STRUCTURAL PLANS6"X LEVEL WOOD PLATFORM;
22 GA. GALV. S/M CAP
FLEXIBLE CONNECTIONFAN INLET, AND PROVIDE WITH
TRANSITION DUCT TO ROUND
CENTRIFUGAL EXHAUST FANVERTICAL DISCHARGE
(WHERE APPLICABLE)
(E) ROOF
MIN. 4" EMBEDMENT @ EA(2) 3/8"O LAG SCREW WITH
(TYPICAL)REQUIRED FLASHINGCANT STRIP W/
WITH 1" DEFLECTION (TYP FOR 4)VIBRATION ISOLATORSEISMIC MOUNT"VIBREX" TYPE RMU-EQ-SH
MOTOR HOUSING
(E) ROOF STRUCTURE
ISOLATOR PER CALC. MA-3
ADDITIONAL INFORMATIONAND DETAIL 13/SO.1 FOR
2.
1. EXHAUST DUCT SHALL HAVE A CLEARANCE OF 3 IN. MIN. AND12 IN. MAX. FROM COMBUSTIBLES PROTECTED WITH TWO (2)LAYERS OF 5/8" GYPSUM BOARD FURNISHED AND INSTALLEDUNDER THE FINISHES DIVISION OF THE SPECIFICATIONS.
KITCHEN HOOD UNIT INSTALLATION SHALL BE CHECKED,STARTED, TESTED AND ADJUSTED BY, OR UNDER DIRECTSUPERVISION OF THE KITCHEN HOOD UNIT MANUFACTURER'SREPRESENTATIVE.
MINIMUM VELOCITY = 1500 FPMMAXIMUM VELOCITY = 2500 FPM
HOOD SHALL BE 22 GAUGEMINIMUM THICKNESS OF
14x18 PRE FRABRICATED CLEAN OUT DOOR(SUPPLIED BY 3M MANUFACTURER)
AND COMBUSTIBLES OR 3" MINIMUMPROVIDE 18" BETWEEN DUCTS
FROM PROTECTED COMBUSTIBLES
WALL JOINTS
DUCTWORK SHALL BE 16 GA.GALVANIZED W/ WELDED
ROOF
EXHAUSTFAN
INTAKES AND 10' ABOVE ADJOINING GRADE LEVEL
EXHAUST TERMINATION SHALL BE 10' MINIMUM FROMADJACENT BUILDING, PROPERTY LINE, OR AIR
KITCHEN HOOD: REFER TO SHEET M-007
--
WRAP DUCT ALL ROUND WITH3M "FIRE BARRIER DUCT WRAP 15A"SEE DETAIL ON SHEET M-008
NON-RATEDCEILING
SA CONNECTION(TYP 2)
DUCTS SHALL BE CONSTRUCTED OF 18 GA.STAINLESS STEEL OR 16 GA. CARBONSTEEL PER CMC 510.5
1/4" O x 1-1/2"L LAG SCREW AT12" O.C. MIN. (3) EACH SIDE
321
REMARKSMODELUNIT
KITCHEN FAN SCHEDULE
4(LBS)WT.
OPER.
5 6
USF-316-BI-GGEF-1
MAKE
GREENHECK 275
SERVICE
HOOD
ELECTRICAL DATA
VHP PH
3/4 208 1
TOTALCFM
ESP(IN)
SONES
13.21446 1.25
WATTS
-
UP BLAST DISCHARGE1
2 INTERLOCK WITH KITCHEN AC UNIT AND MAKE UP AIR
X
3 UL OR ETL LISTED FOR GREASE APPLICATION
X
321
REMARKSMODELUNIT
KITCHEN MAKE UP AIR UNIT SCHEDULE
4(LBS)WT.
OPER.
5 6
BSQ-120-4GSF-1
MAKE
GREENHECK 200 X
SERVICE
HOOD
ELECTRICAL DATA
VHP PH
1/4 115 1
TOTALCFM
ESP(IN)
RPM
1186868 0.55
WATTS
-
PROVIDED W/ FACTORY FILTERS1
2 INTERLOCK WITH KITCHEN EXHAUST FAN GEF-1
X
FOOD SERVICE EXHAUST/MAKE-UP AIR BALANCE SCHEDULESYSTEM MAKE-UP AIR AIR (CFM)EXHAUST AIR (CFM)SERVICE
-GSF-1 868HOOD
TOTAL 1446 868
PRESSURIZATION =
TRANSFER AIR (CFM)
-
MECHANICALLY HEATED/COOLED, NOT EXCEEDING
THE SUPPLY FLOWREQUIRED TO MEET THE
SPACE HEATING ANDCOOLING LOAD
AC OUTSIDE AIR (CFM)
8680 + + 500
1446GEF-1 -HOOD
-1446 + = -78
0 500
X
500FC-E4
No. 27963
Exp. 6/30/20
REGISTERED
PROFESSIONAL
ENGINEER
BRAD
LEYE. SEVERSON
M
ECHANICA
L
STA
T E OF CAL IFOR
NIA
LPV 626 714-7506 FAX 626 714-7512 Pasadena, California 91103 751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
Arch
itect
Sta m
ps
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY: 1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
M-006
MECHANICALSCHEDULES AND
DETAILS
Checker10/23/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2
2 06/04/18 CCD-2
(NEW SHEET)
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
6'-0" MINIMUMFOR MIXING DIFFUSERS
6'-0"
6'-0"
15'-0"
18"MIN.
EA
Transfer Air
ExhaustHood
Kitchen Dining Room
RestroomExhaust
EA SA RA
HVAC Unit
OA
LESS THAN 50 FPM VELOCITY
MAXIMUM VELOCITYAT HOOD LIP IS 75 FPM
GAYLORDVENTILATOR
60-80 FPMVELOCITY
SA RA
HVAC Unit
OA
FOR DIFFUSERS:6'-0" TO 15'-0" FROM VENTILATOR, KEEPVELOCITY BELOW 150 FPM AT DIFFUSER
MUA Unit
OA
TYPICAL DESIGN
VELOCITY ATDIFFUSER< 150 FPM VELOCITY AT
DIFFUSER< 300 FPM
VELOCITY ATDIFFUSER< 300 FPM
VELOCITY ATDIFFUSER< 150 FPM
FOR DIFFUSERS:15'-0" OR MORE FROM VENTILATOR, KEEPVELOCITY BELOW 300 FPM AT DIFFUSER
GAYLORD"PBW"
EXHAUSTDUCT
SUPPLYDUCT
GAYLORD"PBW"
GAYLORDVENTILATOR
TOTAL "PBW" VOLUMENOT TO EXCEED60% OF EXHAUST
EA - Exhaust AirSA - Supply AirRA - Return AirOA - Outside Air
Gaylord Capture Performance GuaranteeGaylord warrants the Capture Performance of the ventilator, only if the Exhaust AirVolumes are correct, per the Exhaust Air Volume Guidelines, and the Make-up AirVolumes are correct and the make-up air is delivered correctly, per the Make-up AirDelivery Guidelines as stated below.
Exhaust Air Volume Guidelines:1. The amount of air exhausted by the Gaylord Ventilator shall be between 100%
and 110% of the values shown on the Plan View for the Exhaust Ducts for eachventilator
Make-up Air Delivery Guidelines:1. Gaylord "PBW" Plenum boxes shall be included for each ventilator2. The amount of make-up air delivered through the Gaylord "PBW" plenum boxes
shall be between 90% and 100% of the values shown on the Plan View for theSupply Ducts for each ventilator
3. The make-up air delivered using Gaylord "PBW" plenum boxes shall notexceed 60% of the exhaust volume of the ventilator
4. Ceiling diffusers shall be at least 6'-0" from all sides of the ventilator and thevelocity at the diffuser shall not exceed 150 Feet per Minute (FPM)
OR Ceiling diffusers shall be 15'-0" from all sides of the ventilator and the velocity
at the diffuser shall not exceed 300 Feet per Minute (FPM)5. The maximum velocity of the make-up air from Transfer Air, Diffusers, etc. shall
not exceed 75 FPM at the ventilator lip6. Cross drafts from pass through windows, hallways, or other openings shall not
exceed 50 FPM7. All forms of make-up air introduction (PBW, Transfer Air, Diffusers, etc.) must
be evenly distributed around each ventilator to prevent unequal pressurization8. Kitchen pressurization shall not exceed -0.02"W.G. relative to the dining or
adjacent spaces, as stated in NFPA-96 and ASHRAE Standard 1549. For more information on acceptable methods of Make-up Air Delivery reference
ASHRAE Standard 154.
Following these guidelines will result in proper capture and containment at theventilator and enact the Gaylord Capture Performance Guarantee. If jobsiteconditions cannot accommodate these guidelines, consult factory for alternativedesign.
REV
INSTALLATION INFORMATION
DRWN.BY DATE REVISIONS CHECKED BY
MODEL #
DRAWING NO.:
DRAWN BY:
INDUSTRIESGAYLORD R
± 1/4" (6mm)DIMENSION TOLERANCE
WORK ORDER #
GAYLORD
DATE: SHEET NO.:REV.:
ITEM #CHECKED BY: ELECT. CHECK: F.P. CHECK: S.E. APPROVAL:
R
(800) 547-9696TOLL FREE:10900 S.W. AVERY ST.FAX NO.:E-MAIL:
TUALATIN, OR 97062 (503) [email protected]
TELEPHONE: (503) 691-2010
This plan is made from available information, but measurements are to beverified by contractors, installers and others in connection with this job. GaylordIndustries accepts no responsibility for work done by contractors, installers andothers, and will not stand any expense for charges made necessary by localbuilding codes, ordinances, structural conditions or by the substitution or changesin equipment shown in this plan. This plan must be verified and approved byproper parties before fabrication can be started and approval shall not be madeunless contractors, installers and others have reviewed applicable codes withcode authorities. Reference is made to the general notes, which are a part ofthese plans and all contractors, installers and others utilizing these plans areadvised they are responsible for examining and becoming familiar with saidgeneral notes before commencing any work hereunder. Any inconsistenciesbetween these plans and the general notes, or between these plans, the generalnotes, and local building codes or ordinances must be immediately called to theattention of Gaylord Industries in writing so that any such inconsistencies can beresolved.
Gaylord Industries must be notified of any changes made to the plan in a clear andconspicuous manner. Gaylord Industries will not be responsible for any incidental orconsequential damages incurred by others as a result of contractors, installers and othersfailure to notify Gaylord of changes to the plan.
ATTENTION - This plan is the property of Gaylord Industriesand is confidential and proprietary. It is not to be copied,reproduced, or distributed, in whole or part, nor be used inanyway detrimental to Gaylord Industries. If you havereceived this plan without Gaylord's permission, please (i) donot read it, (ii) reply to the sender that you received thedrawing in error, and (iii) erase and/or destroy the drawing.
R
ESIL T DC
CM
IntertekUS
GENERAL NOTES FOR NON-WATER WASH VENTILATORS
THE GAYLORD VENTILATOR TESTING, LISTINGAND COMPLIANCE REFERENCES:
APPROVAL NOTICE
IMPORTANT NOTICE
APPROVED FOR FABRICATION
SPACE CONDITIONS IN HOT AND HUMID CLIMATES / STEAM COOKING EQUIPMENT
ELECTRICAL1. Locate Fan Start/Stop Switch in a convenient location.
Refer to the wiring diagram for required voltage.2. If ventilators are equipped with light fixtures, provide a
separate light circuit to the ventilator as shown onelectrical plan.
EXHAUST VOLUME REQUIREMENTS3. Exhaust Volumes as shown on the drawings are
determined by established Gaylord engineering methodsand in accordance with the terms of the ventilator'slisting. These air volume levels require that the make-upair be brought into the space in such a way that it doesnot negatively affect the ventilator. See the Make-up AirRequirements and the "Typical Design" drawing.
4. Ventilator static pressure is noted on each ventilator planview. Total duct system and other external static's mustbe added to the ventilator static for determining the totalsystem static pressure drop. Static based on operationat mean sea level at 75°F kitchen ambient.
MAKE-UP AIR REQUIREMENTS5. Make-up air is critical to the performance of the
ventilator.6. The total amount of make-up air (supply air) brought into
the kitchen must be between 90% and 100% of the totalexhaust volume. It should be brought in throughout thekitchen evenly for best results. See the "Typical Design"drawing.
AIR FLOW RATES7. Exhaust and Supply Air Flow Rates were established
under controlled laboratory conditions. Greater Exhaustand/or lesser Supply Air Flows may be required forcomplete vapor removal in specific installations.
INSTALLATION8. Ventilators to be installed in accordance with NFPA-96
and all other local applicable codes. Contractors mustreview applicable codes with code authorities beforeapproving drawings for fabrication. Special attentionmust be given to code regulations relative to clearancesfrom surrounding combustible and limited combustibleconstruction (walls, ceiling, etc.).
9. Ventilators manufactured in multiple sections are factorypre-wired to a single connection point. Ventilator wiringis disconnected for shipment to be reconnected byelectrical contractor.
10. Ventilators manufactured in multiple sections may havedrains factory interconnected (see drawing) to a singleoutlet point. Ventilator plumbing is disconnected forshipment to be reconnected by plumbing contractor.
11. All ductwork beyond the ventilator duct take-off collar tobe provided and installed by others, in accordance withapplicable codes. Exhaust ducts must be continuouslywelded liquid tight.
12. All ventilators are equipped with hanging brackets.Hanging rods to be supplied by ventilator installer.Hanging weight of the ventilator(s) is noted on eachdrawing.
13. Ventilators manufactured in multiple sections areprovided with bolts, clips, and all necessary hardware forreconnecting by the ventilator installer.
CONSTRUCTION14. Ventilators are manufactured in strict accordance with
Gaylord specifications.15. Ventilators constructed of 18 Ga. stainless steel, Type
300 series, No. 4 finish unless otherwise noted ondrawings.
FIRE EXTINGUISHING SYSTEM16. Fire extinguishing system to be installed in accordance
with NFPA-96. Refer to "FIRE PROTECTION SYSTEMNOTES" for information on supplier and installation.
17. Caution: Fire extinguishing system piping installed onthe ventilator at job site should be coordinated withGaylord to ensure piping does not interfere with theventilator's operation/performance. Improper installationmay void the Listings of the ventilator.
18. IMPORTANT NOTE: NFPA-96 requires that all gas andelectric cooking equipment, that is protected by surfacefire protection, must automatically shut off uponactivation of the fire extinguishing system.
19. IMPORTANT NOTE: Most building departments requireseparate hood and fire protection permits prior toinstallation. The hood permit is typically obtainedthrough the plan review department and the fireprotection permit from the fire prevention bureau. It isthe responsibility of the installing contractor to check withlocal building departments for their requirements and toobtain necessary permits.
LIGHTING20. Light fixtures in ventilators will provide less than 30 foot
candles of light at the cooking surface as a standard,unless otherwise noted on Section View. Confirm if thisamount of light is acceptable with local health codes.
Gaylord recommends the kitchen temperature be kept between 74°F to 79°F with a dew point not exceeding 55°F to prevent excesscondensation and or dripping in the hood over heavy steam producing equipment such as Steamers, Kettles, Dim Sum Counters, etc.If this is not possible, please consult the factory for increased air volume levels to prevent condensation buildup and potentialdripping. Please refer to ASHRAE STD's 62.1-2010, 55-2010, and "The ASHRAE Guide for Buildings in Hot & Humid Climates" toaddress occupancy comfort and reduce the growth of pathogenic or allergenic organisms. It should be noted that exceeding thesevalues can result in increased potential for unsanitary conditions.
IMPORTANT NOTE: Gaylord Ventilators are designed to meetthe National codes listed below. Local codes may vary. GaylordIndustries must be notified in writing of local codes that mayaffect the ventilator design.
NATIONAL FIRE PROTECTION ASSOCIATION The exhaust ventilator meets all requirements of the latest edition of NFPA-96.
NATIONAL SANITATION FOUNDATION The exhaust ventilator is NSF listed to: Standard #2 - "Food Service Equipment"
INTERNATIONAL & UNIFORM MECHANICAL CODE The exhaust ventilator meets all requirements of IMC and UMC.
UNDERWRITERS LABORATORIES, INC. The exhaust ventilator is UL Listed. *
INTERTEK TESTING SERVICES The exhaust ventilator is ETL Listed. *
* UL and ETL listed exhaust ventilators are tested to standard: UL 710 - "Exhaust Hoods for Commercial Cooking Equipment".
Prior to releasing the ventilator for fabrication, this drawing mustbe signed by an authorized representative of the companyordering the equipment and returned to GAYLORDINDUSTRIES. By approving these drawings, the companyordering the equipment agrees to the general notes, accepts theequipment as shown, and has verified the following have beenchecked:
1. All dimensions such as duct size and location, drain and hotwater location, ceiling height, overall size of ventilator,clearances to beams and other obstructions.
2. The location of the cooking equipment in relation to theventilator is correct as shown for proper placement of thesurface fire protection nozzles.
Any changes in cooking equipment location, necessitating therelocation of the surface fire protection nozzles must be broughtto the attention of GAYLORD INDUSTRIES in writing, prior tothe kitchen being turned over to operating personnel.
Revise and Resubmit
Without changes With changes as shown
Signature Date
REV
INSTALLATION INFORMATION
DRWN.BY DATE REVISIONS CHECKED BY
MODEL #
DRAWING NO.:
DRAWN BY:
INDUSTRIESGAYLORD R
± 1/4" (6mm)DIMENSION TOLERANCE
WORK ORDER #
GAYLORD
DATE: SHEET NO.:REV.:
ITEM #CHECKED BY: ELECT. CHECK: F.P. CHECK: S.E. APPROVAL:
R
(800) 547-9696TOLL FREE:10900 S.W. AVERY ST.FAX NO.:E-MAIL:
TUALATIN, OR 97062 (503) [email protected]
TELEPHONE: (503) 691-2010
This plan is made from available information, but measurements are to beverified by contractors, installers and others in connection with this job. GaylordIndustries accepts no responsibility for work done by contractors, installers andothers, and will not stand any expense for charges made necessary by localbuilding codes, ordinances, structural conditions or by the substitution or changesin equipment shown in this plan. This plan must be verified and approved byproper parties before fabrication can be started and approval shall not be madeunless contractors, installers and others have reviewed applicable codes withcode authorities. Reference is made to the general notes, which are a part ofthese plans and all contractors, installers and others utilizing these plans areadvised they are responsible for examining and becoming familiar with saidgeneral notes before commencing any work hereunder. Any inconsistenciesbetween these plans and the general notes, or between these plans, the generalnotes, and local building codes or ordinances must be immediately called to theattention of Gaylord Industries in writing so that any such inconsistencies can beresolved.
Gaylord Industries must be notified of any changes made to the plan in a clear andconspicuous manner. Gaylord Industries will not be responsible for any incidental orconsequential damages incurred by others as a result of contractors, installers and othersfailure to notify Gaylord of changes to the plan.
ATTENTION - This plan is the property of Gaylord Industriesand is confidential and proprietary. It is not to be copied,reproduced, or distributed, in whole or part, nor be used inanyway detrimental to Gaylord Industries. If you havereceived this plan without Gaylord's permission, please (i) donot read it, (ii) reply to the sender that you received thedrawing in error, and (iii) erase and/or destroy the drawing.
WIRING BY GAYLORDFIELD WIRING BY OTHERS
THE HOLDING COILS WITHIN THE MAGNETIC STARTERS MUSTMATCH THE SUPPLY VOLTAGE. MAGNETIC STARTERS ARESUPPLIED BY OTHERS.
ALL EXTERNAL CONTROL WIRING SHALL BE 12 GAUGEMINIMUM OR AS PER APPLICABLE CODES.
E-2)
E-1)
WIRING NOTESN/O
TYPICAL FIRE SYSTEM WIRING DIAGRAM (ANSUL SHOWN)
VOLTAGE FREE N/O AND N/CCONTACTS FOR
INTERCONNECTION TO THEBUILDING ALARM SYSTEM
(4) FIRE SYSTEM DUAL MICRO SWITCHESLOCATED IN AUTOMAN. SWITCHES SHOWN INCOCKED POSITION (SYSTEM READY)
N/C
MS3N/C
MS2N/O
N/OMS1
N/C
EXHAUST FAN(S), MOTOR, MAGNETICSTARTER SWITCH AND FAN ELECTRICALSERVICE BY OTHERS.SEE NOTE E-2
SUPPLY FAN(S), MOTOR, MAGNETICSTARTER SWITCH AND FAN ELECTRICALSERVICE BY OTHERS.SEE NOTE E-2
[ ] 50Hz[ ] 60Hz
SUPPLY VOLTAGE
[ ] 220V[ ] 120V
ANSUL PIPING BY FIRESUPPRESSION INSTALLER
ROOF TOP ANSULPIPING BY GAYLORD
INTERIOR HOOD ANSULPIPING BY GAYLORD
=
=
=
DISTRIBUTION PIPING REQUIREMENTS PER 3 GALLON TANK
REQUIREMENTSPIPE SIZEMAXIMUM LENGTH
MAXIMUM RISE
MAXIMUM 90° ELBOWMAXIMUM TEESMAXIMUM FLOW NUMBERS
SUPPLY3/8 IN.40 FT.(12.2 M)6 FT.(1.8 M)9111*
BRANCH LINE3/8 IN.8 FT.(2.4 M)4 FT.(1.2 M)424
DUCTBRANCH LINE3/8 IN.4 FT.(1.2 M)2 FT.(0.6 M)422
PLENUMBRANCH LINE3/8 IN.12 FT.(3.7 M)2 FT.(0.6 M)644
APPLIANCE
*EXCEPTIONS1. TWELVE (12) FLOW NUMBERS ARE ALLOWED IN ANY ONE TANK FOR DUCT AND PLENUM PROTECTION ONLY.2. TWELVE (12) FLOW NUMBERS ARE ALLOWED IN ANY ONE TANK USING ONLY TWO-FLOW APPLIANCE NOZZLES. 3. TWELVE (12)FLOW NUMBERS ARE ALLOWED IN ANY ONE TANK USING ONLY THREE-FLOW APPLIANCE NOZZLES.
REV
INSTALLATION INFORMATION
DRWN.BY DATE REVISIONS CHECKED BY
MODEL #
DRAWING NO.:
DRAWN BY:
INDUSTRIESGAYLORD R
± 1/4" (6mm)DIMENSION TOLERANCE
WORK ORDER #
GAYLORD
DATE: SHEET NO.:REV.:
ITEM #CHECKED BY: ELECT. CHECK: F.P. CHECK: S.E. APPROVAL:
R
(800) 547-9696TOLL FREE:10900 S.W. AVERY ST.FAX NO.:E-MAIL:
TUALATIN, OR 97062 (503) [email protected]
TELEPHONE: (503) 691-2010
This plan is made from available information, but measurements are to beverified by contractors, installers and others in connection with this job. GaylordIndustries accepts no responsibility for work done by contractors, installers andothers, and will not stand any expense for charges made necessary by localbuilding codes, ordinances, structural conditions or by the substitution or changesin equipment shown in this plan. This plan must be verified and approved byproper parties before fabrication can be started and approval shall not be madeunless contractors, installers and others have reviewed applicable codes withcode authorities. Reference is made to the general notes, which are a part ofthese plans and all contractors, installers and others utilizing these plans areadvised they are responsible for examining and becoming familiar with saidgeneral notes before commencing any work hereunder. Any inconsistenciesbetween these plans and the general notes, or between these plans, the generalnotes, and local building codes or ordinances must be immediately called to theattention of Gaylord Industries in writing so that any such inconsistencies can beresolved.
Gaylord Industries must be notified of any changes made to the plan in a clear andconspicuous manner. Gaylord Industries will not be responsible for any incidental orconsequential damages incurred by others as a result of contractors, installers and othersfailure to notify Gaylord of changes to the plan.
ATTENTION - This plan is the property of Gaylord Industriesand is confidential and proprietary. It is not to be copied,reproduced, or distributed, in whole or part, nor be used inanyway detrimental to Gaylord Industries. If you havereceived this plan without Gaylord's permission, please (i) donot read it, (ii) reply to the sender that you received thedrawing in error, and (iii) erase and/or destroy the drawing.
EXH
SUP
1)REMOVE 2"x4" SHIPPING BLOCK FROM BOTTOM OFVENTILATOR.
SECURE BOTTOM VENTILATOR FLANGE TO STRUCTURALWALL USING #10 SCREWS (MIN.) ON A MAXIMUM OF 32"CENTERS. (SEE DETAIL #1)
INSTALL VENTILATOR.
"CAPTURE WALL"INSTALLATION DETAILS
2)
3)
ATTACH "CAPTURE WALL" TO VENTILATOR USING SCREWSAND CAGE NUTS PROVIDED AT PRE-DRILLED LOCATIONS.
4)
SECURE BOTTOM OF "CAPTURE WALL" TO STRUCTURALWALL USING #10 SCREWS (MIN.) ON A MAXIMUM OF 32"CENTERS. (SEE DETAIL #3)
5)
IF LOCAL JURISDICTION ALLOWS :INSTALLER TO APPLY SILICONE CAULK ON ALL JOINTSCONNECTING TO BUILDING WALL AND VERTICAL SEAMS (IFAPPLICABLE).
6) CONDITIONSVERIFY CEILING
EXACT FLOOR TO STRUCTURAL CEILING AND FLOOR TOFINISH CEILING HEIGHTS MUST BE VERIFIED FORVENTILATOR DESIGN. INCORRECT HEIGHTS MAY CAUSE THEVENTILATOR TO NOT FIT PROPERLY OR COMPLY WITHCLEARANCES SPECIFIED IN APPLICABLE CODES ANDSTANDARDS. CAUTION: IF THE FINISHED CEILING IS HIGHERTHAN THE TOP OF THE VENTILATOR, ENCLOSURE PANELSMAY BE REQUIRED.
FLOOR TO FINISH CEILING: _____________
FLOOR TO STRUCTURAL CEILING: _____________(VERIFY)
FIRE SUPPRESSIONSYSTEM NOTES
ANSUL R-102-ASEF
LOCATION OF FIRE SUPPRESSION NOZZLES MUSTBE VERIFIED IN RELATION TO THE COOKINGEQUIPMENT, PRIOR TO VENTILATOR FABRICATION.
FP-1)
ANSUL FIRE SYSTEM FACTORY PRE-PIPED CHEMICAL LINESINCLUDING DUCT, PLENUM AND APPLIANCE DROPS WITH ALLNOZZLES INSTALLED PER COOKING EQUIPMENTARRANGEMENT ON GAYLORD APPROVED DRAWINGS. ALLEXPOSED CHEMICAL PIPING CHROME PLATED OR CHROMESLEEVED. INCLUDES FACTORY PRE-PIPED DETECTION LINESWITH SURFACE MOUNTED DETECTOR BRACKETS.INSTALLATION BY CERTIFIED FACTORY INSTALLERS.
COMPLETE SYSTEM INCLUDING APPLIANCE DROPS ANDSURFACE MOUNTED DETECTION BRACKETS, WITH FIELDINSTALLATION BY GAYLORD.
INCLUDES:* TANK(S) AND RELEASE ASSEMBLY(S)* CHEMICAL* DETECTOR CABLE* FUSIBLE LINKS WITH LINKAGE* EXPELLANT GAS CARTRIDGE(S) (PROVIDED BY FIRE SUPPRESSION INSTALLER)* (1) REMOTE MANUAL PULL STATION* (1) GAS VALVE PER FIRE SYSTEM WITH A MAXIMUM SIZE OF 2-1/2"* (1) MANUAL RESET RELAY PER FIRE SYSTEM, IF REQUIRED* PLANS AND PERMITS (ON JOBS INSIDE OF THE UNITED STATES AND NON-MARINE JOBS)* PARTS AND INSTALLATION OF CHEMICAL AND DETECTION LINES FROM TANK(S) TO CONNECTION POINTS ON HOOD* INSTALLATION OF TANKS AND RELATED COMPONENTS* INSTALLATION OF DETECTOR CABLE AND FUSIBLE LINKS* INSTALLATION OF REMOTE MANUAL PULL STATION* JOB SITE REPOSITIONING OF NOZZLES AS PER GAYLORD APPROVED DRAWINGS, IF REQUIRED TO MEET SYSTEM DESIGN REQUIREMENTS* TRIP TEST AND CERTIFICATION (ON JOBS INSIDE OF THE UNITED STATES AND NON-MARINE JOBS)
* UNION LABOR AND PREVAILING WAGE* INSTALLATION OF GAS VALVE(S)* ELECTRICAL DISCONNECTS* PARTS AND LABOR FOR ANY ELECTRICAL INTERCONNECTIONS* JOB SITE REPOSITIONING OF NOZZLES IF COOKING EQUIPMENT IS NOT INSTALLED PER GAYLORD APPROVED DRAWINGS* PLANS AND PERMITS ON JOBS OUTSIDE OF THE UNITED STATES AND ON MARINE JOBS* TRIP TEST AND CERTIFICATION ON JOBS OUTSIDE OF THE UNITED STATES AND ON MARINE JOBS* HAND HELD FIRE EXTINGUISHER(S)* INSPECTION AND SERVICING* RECESSED ANSUL CABINET(S)
EXCLUDES:
WARNING : ANY CHANGES IN THEHOOD DESIGN OR MAKES/MODELS OF
COOKING EQUIPMENT MAY AFFECTTHE SIZE OF AND/OR REQUIRED
AIRFLOWS FOR THE HOOD.NOTE: COOKING EQUIPMENT MODEL,MANUFACTURER & LOCATION MUST
BE VERIFIED FOR FIRESUPPRESSION PRIOR TO FABRICATION.
ESIL T DC
CM
IntertekUS
CEILING ACCESSBY GENERAL
CONTRACTOR
BOTTOMVENTILATOR FLANGEBY GAYLORD
DETAIL 1
BOTTOM OFHOOD APRON
"CAPTURE WALL"& CAGE NUT
BY GAYLORD
SCREWBY GAYLORD
FASTEN TO STRUCTURAL WALLUSING #10 SCREW (MIN.)BY VENTILATOR INSTALLER
"CAPTURE WALL"INSTALLED IN FIELD
BY VENTILATOR INSTALLER
INTERMITTENTLYWELDED "CAPTURE WALL"ATTACHMENT FLANGE
STRUCTURALWALL
1.375
2.0
DETAIL 2
MTG. BRACKETBY GAYLORD
FASTEN TO WALLBY VENTILATORINSTALLER
TOP OFVENTILATOR
MOUNTING RODSBY VENTILATOR
INSTALLER
1.0
DETAIL 3
FASTEN TOSTRUCTURAL WALLUSING #10 SCREW (MIN.)BY VENTILATOR INSTALLER
"CAPTURE WALL"BY GAYLORD
1.9375
0.5625
1.50
0.625
HOOD
1/2" ALLTHREAD ROD
NUTS
WASHERS
NUTS
℄
MOUNTING BRACKET DETAIL
A)
C)
B)FRONT AND REAR MOUNTING BRACKETS HAVE∅0.625" HOLES. BRACKETS TO BE SUPPORTED WITHIN 12"OF EACH END OF EACH SECTION, WITH A MAXIMUM SPANOF 72" BETWEEN SUPPORTS.
INTERIOR MOUNTING BRACKET(S) TO BE SUPPORTEDWITHIN 36" OF EACH END OF EACH SECTION, WITH AMAXIMUM SPAN OF 72" BETWEEN SUPPORTS.
VERIFY ALL MAKES AND MODELS OF COOKING EQUIPMENTAND LOCATION IN RELATION TO VENTILATOR PRIOR TOFABRICATION.
VENTILATOR NOTES(NON-WATER WASH)
VERIFY IF THIS HOOD IS EXHAUSTED ON ITS OWNEXHAUST FAN OR IS IT EXHAUSTED ON A COMMONEXHAUST FAN SHARED WITH OTHER HOODS.
VERIFY NUMBER OF SUPPLY (MAKE-UP AIR) FANS.B)
A)
VERIFY EXHAUST & SUPPLYFANS
ALL EXPOSED SURFACES ARE STAINLESS STEEL
REMOVABLE S/S PERFORATED PANEL(S)
PBW PLENUM FEATURES
**
VENTILATOR WIRING NOTES(NON-WATER WASH)
*LIGHT FIXTURES, VAPOR PROOF, U.L. LISTED,FURNISHED, INSTALLED AND WIRED BY GAYLORD.*
100W LT.FIXTURERTD RTD
DCAP1
EXH EXH
ITEMNO. MODEL
L (in) D (in)
SIZE
H (in)
HOOD INFORMATIONAIR FLOW REQUIREMENTS
DUCT COLLARSIZE
D (in)L (in)CFM
(EACH)
WEIGHT(LBS)DUCT S.P.
("W.G.)
S.P. TESTPORT ("W.G.) QTYDUCT
TYPE
TOTAL HOOD S.P.:TOTAL EXHAUST:TOTAL SUPPLY:
TOTAL WEIGHT:
10
8
SUP
REV
INSTALLATION INFORMATION
DRWN.BY DATE REVISIONS CHECKED BY
MODEL #
DRAWING NO.:
DRAWN BY:
INDUSTRIESGAYLORD R
± 1/4" (6mm)DIMENSION TOLERANCE
WORK ORDER #
GAYLORD
DATE: SHEET NO.:REV.:
ITEM #CHECKED BY: ELECT. CHECK: F.P. CHECK: S.E. APPROVAL:
R
(800) 547-9696TOLL FREE:10900 S.W. AVERY ST.FAX NO.:E-MAIL:
TUALATIN, OR 97062 (503) [email protected]
TELEPHONE: (503) 691-2010
This plan is made from available information, but measurements are to beverified by contractors, installers and others in connection with this job. GaylordIndustries accepts no responsibility for work done by contractors, installers andothers, and will not stand any expense for charges made necessary by localbuilding codes, ordinances, structural conditions or by the substitution or changesin equipment shown in this plan. This plan must be verified and approved byproper parties before fabrication can be started and approval shall not be madeunless contractors, installers and others have reviewed applicable codes withcode authorities. Reference is made to the general notes, which are a part ofthese plans and all contractors, installers and others utilizing these plans areadvised they are responsible for examining and becoming familiar with saidgeneral notes before commencing any work hereunder. Any inconsistenciesbetween these plans and the general notes, or between these plans, the generalnotes, and local building codes or ordinances must be immediately called to theattention of Gaylord Industries in writing so that any such inconsistencies can beresolved.
Gaylord Industries must be notified of any changes made to the plan in a clear andconspicuous manner. Gaylord Industries will not be responsible for any incidental orconsequential damages incurred by others as a result of contractors, installers and othersfailure to notify Gaylord of changes to the plan.
ATTENTION - This plan is the property of Gaylord Industriesand is confidential and proprietary. It is not to be copied,reproduced, or distributed, in whole or part, nor be used inanyway detrimental to Gaylord Industries. If you havereceived this plan without Gaylord's permission, please (i) donot read it, (ii) reply to the sender that you received thedrawing in error, and (iii) erase and/or destroy the drawing.
MAXIMUM VENTILATOR DIMENSION:_______ L. x _______ W._______ H.TOTAL ESTIMATED HANGING WEIGHT:____ LBS.
VENTILATORS MANUFACTURED IN MULTIPLE SECTIONSARE PROVIDED WITH BOLTS, CLIPS, AND ALL NECESSARYHARDWARE FOR RECONNECTING BY THE VENTILATORINSTALLER. CONTROL AND LIGHTING WIRING AREPRE-WIRED AND DISCONNECTED FOR SHIPMENT. WIRINGMUST BE RECONNECTED BY APPLICABLE TRADES.
LONGFELLOW ELEMENTARY
Long Beach, CA
18-0572 05-31-18 02 02
RD
8'-2" 5'-3"3'-4"
961
ELX-GBD-DCA-63 H-1 18057201
PBW-16 (T1) PBW-1 18057202
ANSUL R-102-ASEF-1T-5N-7F FP-5 18057203
01 RD 06-01-18 REVISED SIZE OF SUPPLY DUCT COLLAR TO FIT BETWEEN BEAMS
02 RD 06-01-18 REVISED TO TWO DUCTS
PBW-1 PBW 98 16 8 SUPPLY 2 0.11 434 8 10 123
H-1 ELX 98 63 30 0.35 EXHAUST 2 0.60 723 7 10 838
0.6" W.G.1446 CFM868 CFM
960 LBS
L1L2
PRESET TO 90°F AT FACTORYINSTALLED IN HOOD
B)A)
C)
GAYLORD AUTOSTARTDCA NOTES
IN SOME CLIMATES AND/OR CONDITIONS, IT MAY BENECESSARY TO ADJUST THE TEMPERATURE SETTING INTHE FIELD BY OTHERS
X
X
LS1LS2
TOVENTILATOR
LIGHTS
LIGHT SWITCH PROVIDED ANDINSTALLED IN FIELD J-BOX BY
ELECTRICAL CONTRACTOR
FAN ON/OFF SWITCH PROVIDEDAND INSTALLED IN FIELD J-BOXBY ELECTRICAL CONTRACTOR
FLEX CONDUIT(TYP)
Add'lSection(s)(IF APPLICABLE)
FIELD J-BOX(TYP.)
Add'lHood(s)
(IF APPLICABLE)
FLEX CONDUIT(TYP)L1L2GND EF1
1st Hood1st Section
DCAP
12 VDC
UP TO 4RTDS
DATA
T1T2
L1L2 EFGND
T1T2
T3T4
DCAS
12 VDC
UP TO 4RTDS
DATADATA
DCAP
12 VDC
UP TO 4RTDS
DATA
T1T2
L1L2 EFGND
L1L2GND EF1
ELECTRICAL SERVICE FOR LIGHTS, 20 AMP MAX, BYELECTRICAL CONTRACTOR. MUST BE FUSEDSEPARATELY FROM FAN CIRCUIT. WIRED TO SHUNTTRIP BREAKER THAT TRIPS IN THE EVENT OF ANSULACTUATION.
2
120VAC/20 AMPSERVICE FROM
BREAKER PANEL
L2
L1
SHUNT TRIP BREAKER WITH COILCLEARING CONTACTS LOCATED INELECTRICAL PANEL, FURNISHED BYOTHERS, INSTALLED BY ELECTRICALCONTRACTOR.
POWERSUPPLY
FOR MECHANICAL GAS VALVE ANDELECTRICAL SHUNT TRIP SHUT-OFF
Method 2
TO COOKINGEQUIPMENT
N/O
N/CMS4
1/2" EMT CONDUIT TOMECHANICAL GAS VALVE
101-20 (CARBON DIOXIDECARTRIDGE)BY FIRE PROTECTIONCONTRACTOR
1/2" EMT CONDUIT TO REMOTEPULL STATION BY FIRE
PROTECTION CONTRACTOR
42 . 3 4 1 3
CABINET DEPTH: 7.5"
60 . 3 0 4 2
TANK1
(3 GAL.)
DETECTION LINE TOVENTILATOR BY FIREPROTECTION CONTRACTOR
Method 2
WET CHEMICAL LINE TOVENTILATOR BY FIRE
PROTECTION CONTRACTOR
TYPICAL ANSUL TANK SCHEMATIC
(FOR VENTILATOR)
ANSUL FUSE-LINKINLET
ANSULCHEMICAL INLETTANK 1
FUSE-LINK DETECTORBRACKET (TYP.)
FUSE LINKINLET
CHEMICAL INLETTANK 1-4N-6F
PLENUMNOZZLE
#1N35.25 F.P. DROP
FUSE LINKDETECTOR
9
#260
39
#260
6518
DUCTNOZZLE
#1W
DUCTNOZZLE
#1W
LONGFELLOW ELEMENTARY
LONG BEACH, CA
18-0572 05-31-18 1
RD
LONGFELLOW ELEMENTARY
LONG BEACH, CA
18-0572 05-31-18 02 03
RD
ELX-GBD-DCA-63 H-1 18057201
PBW-16 (T1) PBW-1 18057202
ANSUL R-102-ASEF-1T-5N-7F FP-5 18057203
02 RD 06-01-18 REVISED TO TWO DUCTS
LONGFELLOW ELEMENTARY
Long Beach, CA
18-0572 05-31-18 02 04
RD
ELX-GBD-DCA-63 H-1 18057201
ANSUL R-102-ASEF-1T-5N-7F FP-5 18057203
02 RD 06-01-18 REVISED TO TWO DUCTS
11
8
8'-2"
8'-2"AT L-M DUTY
63
16
6
8'-2"
8
9 3.52.5
46"CAPTURE WALL"
BY GAYLORD
4
6316
30
1512 MIN
83EQUIPMENT
HEIGHT(MAX)
7'-0"MOUNTING
HEIGHT
10'-1 1/2"FINISHEDCEILINGHEIGHT(VERIFY)
6
6
24.5 49
7 7
10 10
6
24.5
8 (TYP)
10(TYP)
49
008
O.B. RANGEMONTAGUE
136-11E007
CONV OVENMONTAGUE
2-70A
= DUCT NOZZLE
= APPLIANCE NOZZLE
= PLENUM NOZZLE
D
P
A
NOZZLE
1N
FLOW POINTCALCULATION CHART
TOTAL: 5 7
FLOWSQUANTITY
1W 2 1 (EACH)
1 (EACH)
260 2 (EACH)
1
2
H-1
ITEM # CFM/LF TOTAL CFMDUCT COLLAR
H-1 (2) 7" X 10" 177 1446
STATICPRESSURE
0.60" W.G.
VELOCITY
1446 FPM
ITEM # TOTAL CFMDUCT COLLAR
PBW-1 (2) 8" X 10" 868
STATICPRESSURE
0.11" W.G.
VELOCITY
833 FPM
HOOD EXHAUST INFORMATION CHART HOOD SUPPLY INFORMATION CHART
MECHANICALGAS VALVE
MANUALPULL STATION
ANSUL CABINETITEM FP-1
P#1N
#260A
#260A
D#1W
D#1W
S.P. TEST PORTS.P.: 0.27" W.G.
H-1
PBW-1MIN. OVERHANG
TO COOKINGSURFACE (TYP)
PLAN VIEW
ELEVATION VIEW
DETAIL 1
DETAIL 2
DETAIL 3
SECTION VIEW
11'-2" (VERIFY)
GAYLORD DWG. #16-1265HOOD #H-1 MODEL #ELX-GBD-AS-60
TOTAL HOOD HANGING WEIGHT: 817 LBSPLENUM BOX #PBW-1 MODEL #PBW-16TOTAL PLENUM BOX WEIGHT: 123 LBS
E.T.L. LISTING #3192993CRT-002
HOOD CARTRIDGES
ITEM # CARTRIDGE MAX. RATINGQTY.
H-1 6 XGS 350 CFM/LF
CARTRIDGESIZE
11" X 15.5"
MIN. OVERHANGTO COOKING
SURFACE (TYP)
SHOP NOTES (T1)
* PBW TO BE MADE OF 300 SERIES STAINLESS
(3) WIRES AND GROUND, FOR DCA CONTROL, IN FLEXIBLECONDUIT, EXTENDING 6' BEYOND END OF VENTILATOR BYGAYLORD. WIRED TO SUPPLY VOLTAGE AND FAN ON/OFFSWITCH BY ELECTRICAL CONTRACTOR.
1
(2) WIRES AND GROUND, FOR LIGHT(S), IN FLEXIBLECONDUIT, EXTENDING 6' BEYOND END OF VENTILATORBY GAYLORD. WIRED TO LIGHT SWITCH BYELECTRICAL CONTRACTOR.
2
15
No. 27963
Exp. 6/30/20
REGISTERED
PROFESSIONAL
ENGINEER
BRAD
LEYE. SEVERSON
M
ECHANICA
L
STA
T E OF CAL IFOR
NIA
LPV 626 714-7506 FAX 626 714-7512 Pasadena, California 91103 751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
Arch
itect
Sta m
ps
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY: 3/16" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
M-007
MECHANICALDETAILS
Checker10/23/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2
2 06/04/18 CCD-2
FASTEN TO WALL USING #10 x 3"EMBED WD SCREW BY VENTILATORINSTALLER
USING #10 x 3" EMBED WD SCREW
(NEW SHEET)
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
No. 27963
Exp. 6/30/20
REGISTERED
PROFESSIONAL
ENGINEER
BRAD
LEYE. SEVERSON
M
ECHANICA
L
STA
T E OF CAL IFOR
NIA
LPV 626 714-7506 FAX 626 714-7512 Pasadena, California 91103 751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
Arch
itect
Sta m
ps
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY: 12" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
M-008
MECHANICALDETAILS
Checker10/23/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2
2 06/04/18 CCD-2
(NEW SHEET)
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
CLASSROOM4101
CLASSROOM4103
STORAGE4105
ALL GENDERRESTROOM
4102ALL GENDERRESTROOM
4104
20"x14"(1"L)
20"x14"(1"L)
8"ø8"ø
EI120 CFM
EI120 CFM
14"x
8"
20"x10"
18"x12"(1"L)
18"x12"(1"L)
T
T
B450 CFM
b650 CFM
(TYP.4)
(TYP.2)
16"x
10"
16"x
10"
12"x8"
12"x8"
12"x8"
16"x
10"
12"x8"12"x8
"
12"x8"
12"x8"
16"x
10"
b650 CFM(TYP.2)
B450 CFM(TYP.4)
14"x
10"
14"x
10"
14"x
10"
14"x
10"
LOUNGE5114
KITCHEN5115
CAFETERIA5113
STAGE5108
AUDITORIUM5103
LOBBY5100
ALL GENDERRESTROOM
5102
ALL GENDERRESTROOM
5101
STORAGE5109
STORAGE5107
VESTIBULE5105
ALL GENDERRESTROOM
5106VESTIBULE
5104
VESTIBULE5111
ALL GENDERRESTROOM
5110
VESTIBULE5112
b1300 CFM
B900 CFM
B900 CFM 24
"x20
"
12"ø
16"ø
14"ø
E5700 CFM
E5700 CFM
14"ø
14"ø
18"x20"
18"x32"
18"x32"
18"x20"
(E)1
8"x1
5"(E
)28"
x10"
(E)1
8"x1
5"(E
)28"
x10"
24"x18"
46"x11"
T
B250 CFM
B850 CFM(TYP.4)
24"x
16"
b1350 CFM
b1350 CFM
32"x16"
20"x
14"
6"ø
B150 CFM
U/C
30"x16"
10"ø
14"ø 14"ø
14"ø
14"ø
CO2
24"x32"SD
TCO2
T
CO2
f1000 CFM
24"x18"
24"x18"
ALL GENDERRESTRROM
5118
W.H.5116
OFFICE/STORAGE5117
14"ø
f1000 CFM
14"ø
24"x18"
16"x
16"
16"x
16"
16"x16"
16"x16"
B1800 CFM
B1800 CFM
B1800 CFM
B1800 CFM
30"x30" 30"x30"
30"x30" 30"x30"
32"x
16" 16
"ø8"
ø14"ø
16"x10"
12"x12"
8"x10"
8"x10"
No. 27963
Exp. 6/30/20
REGISTERED
PROFESSIONAL
ENGINEER
BRAD
LEYE. SEVERSON
M
ECHANICA
L
STA
T E OF CAL IFOR
NIA
LPV 626 714-7506 FAX 626 714-7512 Pasadena, California 91103
751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
KEYPLAN
1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
M-114
MECHANICALFLOOR PLANBLDG. 4 & 5
BES10/23/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
CAD
M-114MECHANICAL FLOOR PLAN BLDG. 4 1
M-114MECHANICAL FLOOR PLAN BLDG. 5 2
P.O.C.
P.O.C.
P.O.C.
SHEET NOTES:DUCTED HORIZONTAL FAN COIL UNIT ABOVECEILING, SEE DETAIL 2/M-002.
FILTERED OA SUPPLY W/ MERV 16 FILTERS, SEEDETAIL 6/M-002.
OA LOUVER (MIN. FA AS INDICATED).
20x14 RELIEF LOUVER.
OUTDOOR CONDENSING UNIT ON GRADE, SEEDETAIL 3 & 9 ON M-002.
INLINE EXHAUST FAN. SEE DETAIL 6/M-002.
OUTDOOR CONDENSING UNIT ON ROOF, SEEDETAIL 9 ON M-002.
SEE ARCH. PLANS AND SHT A-014 FORADDITIONAL INFORMATION ON UNIT LOCATION.
NEW OA LOUVER (MIN. FA AS INDICATED).
EXISTING REGISTER TO BE REBALANCED TO AIRQUANTITY INDICATED.
EXISTING EXHAUST FAN TO REMAIN OR BEREBALANCED WHERE INDICATED AS REQUIRED.
TRANSITION TO (E) DUCT SIZE, AND PROVIDECONNECTION AS REQUIRED; FIELD VERIFYEXACT EXISTING DUCT SIZE.
ALL EXISTING DUCTWORK BEING REUSED SHALLBE CLEANED; SEE SPECIFICATIONS FORADDITIONAL INFORMATION.
24"x12" DOOR LOUVER.
REFRIGERANT PIPING BELOW GRADE INOVERSIZED CONDUIT.
REFRIGERANT PIPING FROM CORRESPONDINGFC UNIT, & RUN DOWN TO BELOW GRADE.
PROVIDE WALL CAP (SIZE AS INDICATED).
EXISTING RA DUCT DOWN TO EXISTING RAREGISTER, REBALANCE TO AIR QUANTITYINDICATED.
MIN. 4" CONCRETE PAD; SEE STRUCTURALDETAIL 5/S-0.1 AND ARC. SHT A-014
TYPE-I GREASE EXHASUT HOOD (BY OTHERS).REFER TO SHEET M-006 FOR ADITIONALINFORMATION.
NON COMBUSTIBLE CEILING PANELS, 18"MINIMUM ALL AROUND THE HOOD.
12"x12" WELDED GREASE EXHAUST DUCT IN (2)LAYERS OF APPROVED GREASE DUCT WRAPFROM NEW CONNECTION AT HOOD OFFSET TORISER AS SHOWN. SLOPE HORIZONTAL DUCT ATMINIMUM 1/4" PER FOOT. PROVIDE ACCESSIBLECLEANOUT(S) AS REQUIRED.
10"x7" WELDED GREASE EXHAUST DUCT IN (2)LAYERS OF APPROVED GREASE DUCT WRAPFROM NEW CONNECTION AT HOOD OFFSET TORISER AS SHOWN. SLOPE HORIZONTAL DUCT ATMINIMUM 1/4" PER FOOT. PROVIDE ACCESSIBLECLEANOUT(S) AS REQUIRED.
1
2
3
4
5
6
7
8
9
10
11
12
7
11
7
1
FCD-1
1
SFD-1
2
HPD-1
HPD-2
FCD-2
3
4
4
9
1FCE-3
SFE-2
2
FCE-4
1
HPE-1
5HPE-3
5
17 EFE-1
EFE-2
17
12
12
9
SFE-1
1FCE-1
FCE-2
1
HPE-2
5HPE-4
5
11
13
11
13
11
11
6
6
14
13
14
(2 SF FA)
EFE-3
17 (10x10)
15
16
17
18
8
8
(240 CFM)
14
(8 SF FA)
(18x18)
8
8 8
8
(18x18)
181700 CFM
181700 CFM
(14.5 SF FA)
16
16
15 15
16
16
19
1919
(ON ROOF ABV.)
(ON ROOF ABV.)
SEE DETAIL 5/M-002 (TYP FOR 3)
GEF1
GSF1
20 TYPE-IHOOD21
23
22
20
21
22
(ON ROOF)
2
2
23
23
AC UNIT OR FAN SHALLSHUTDOWN VIA SIGNAL FROMFACP UPON ACTIVATION OF FIREALARM SYSTEM PER CMC & CBC
2 06/04/18 CCD-2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVEDDIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
UNIT FLA VOLTS PHASE VA MOP POLES
HP-A-1 mod1 29 208 3 10448 50 3
HP-A-1 mod2 29 208 3 10448 50 3
HP-A-2 mod1 29 208 3 10448 50 3
HP-A-2 mod2 29 208 3 10448 50 3
CU-A-2 12 208 1 2496 20 2
HP-B-1 44 208 3 15852 80 3
HP-B-2 mod1 36 208 3 12970 60 3
HP-B-2 mod2 36 208 3 12970 60 3
HP-C-1 mod1 44 208 3 15852 80 3
HP-C-1 mod2 36 208 3 12970 60 3
HP-C-2 mod1 44 208 3 15852 80 3
HP-C-2 mod2 36 208 3 12970 60 3
HP-D-1 15.6 208 3 5620 30 3
HP-D-2 15.6 208 3 5620 30 3
HP-E-1 41.4 208 3 14915 60 3
HP-E-2 41.4 208 3 14915 60 3
HP-E-3 41.4 208 3 14915 60 3
HP-E-4 15.6 208 3 5620 30 3
0
FC-A-1 1.68 208 1 349 15 2
FC-A-2 1.44 208 1 300 15 2
FC-A-3 1.44 208 1 300 15 2
FC-A-4 1.44 208 1 300 15 2
FC-A-5 1.44 208 1 300 15 2
FC-A-6 1.44 208 1 300 15 2
FC-A-7 1.44 208 1 300 15 2
FC-A-8 1.44 208 1 300 15 2
FC-A-9 2.52 208 1 524 15 2
FC-B-1 0.25 208 1 52 15 2
FC-B-2 1.44 208 1 300 15 2
FC-B-3 1.44 208 1 300 15 2
FC-B-4 1.44 208 1 300 15 2
FC-B-5 1.44 208 1 300 15 2
FC-B-6 1.44 208 1 300 15 2
FC-B-7 1.44 208 1 300 15 2
FC-B-8 1.44 208 1 300 15 2
FC-B-9 1.68 208 1 349 15 2
FC-C-1 1.44 208 1 300 15 2
FC-C-2 1.44 208 1 300 15 2
FC-C-3 1.44 208 1 300 15 2
FC-C-4 1.44 208 1 300 15 2
FC-C-5 1.44 208 1 300 15 2
FC-C-6 1.44 208 1 300 15 2
FC-C-7 1.44 208 1 300 15 2
FC-C-8 1.44 208 1 300 15 2
FC-C-9 1.44 208 1 300 15 2
FC-C-10 1.44 208 1 300 15 2
FC-C-11 1.44 208 1 300 15 2
FC-C-12 1.44 208 1 300 15 2
FC-D-1 8 208 1 1664 15 2
FC-D-2 8 208 1 1664 15 2
FC-E-1 6.4 208 3 2306 15 3
FC-E-2 6.4 208 3 2306 15 3
FC-E-3 6.4 208 3 2306 15 3
FC-E-4 8 208 1 1664 15 2
0
SF-A-1 7.6 208 1 1581 15 2
SF-A-2 7.6 208 1 1581 15 2
EF-A-1 3 120 1 360 15 1
EF-A-2 1 120 1 120 15 1
EF-A-3 1.5 120 1 180 15 1
SF-B-1 7.6 208 1 1581 15 2
SF-B-2 8.8 208 1 1830 15 2
EF-B-1 3 120 1 360 15 1
EF-B-2 1 120 1 120 15 1
SF-C-1 8.8 208 1 1830 15 2
SF-C-2 8.8 208 1 1830 15 2
EF-C-1 3 120 1 360 15 1
EF-C-2 3 120 1 360 15 1
EF-C-3 1.5 120 1 180 15 1
SF-D-1 5.4 208 1 1123 15 1
SF-E-1 6.6 208 3 2378 15 3
SF-E-2 6.6 208 3 2378 15 3
EF-E-1 4 120 1 480 15 1
EF-E-2 4 120 1 480 15 1
EF-E-3 1 120 1 120 15 1
LARGEST MOTOR 43412 0.25 10853
TOTAL VA 256383
SYS VOLTS 208 AMPS 712
M
VOLTAGE DROP CALCULATIONSFORMULA IS
V=AxLxXxZ/C.M. Z=1+y(T-75)WHERE
V=volts dropped y=.00323 for copper wireA=current of load in amps .00330 for aluminum wireL=length of run one way only X=21.6 for 1 PH copper wireC.M.=size of wire in circular mils. 35.4 for 1 PH aluminum wireT=operating temp of wire in Celsius 18.7 for 3 PH copper wire
30.7 for 3 PH aluminum wire
FEEDER MSA-MA A 123 FEEDER MSA-MB A 115L 25 L 270X 18.7 X 18.7T 75 T 75y 0.00323 y 0.00323C.M. 250000 C.M. 250000V 0.2 V 2.3
WIRE SIZE BELOW SYS. V 208 WIRE SIZE BELOW SYS. V 208250 % DROP 0.11% 250 % DROP 1.12%
FEEDER MSA-MC A 201 FEEDER MSA-ME A 195L 70 L 265X 18.7 X 18.7T 75 T 75y 0.00323 y 0.00323C.M. 300000 C.M. 300000V 0.9 V 3.2
WIRE SIZE BELOW SYS. V 208 WIRE SIZE BELOW SYS. V 208300 % DROP 0.42% 300 % DROP 1.55%
#8 AWG COPPER A 16 #6 AWG COPPER A 16MAXIMUM FULL LOAD L 170 MAXIMUM FULL LOAD L 270BRANCH CIRCUIT X 21.6 BRANCH CIRCUIT X 21.6LENGTH TO CENTROID T 75 LENGTH TO CENTROID T 75FOR 20A CIRCUITS y 0.00323 FOR 20A CIRCUITS y 0.00323120V C.M. 16510 120V C.M. 26240
V 3.6 V 3.6WIRE SIZE BELOW SYS. V 120 WIRE SIZE BELOW SYS. V 1208 % DROP 2.97% 6 % DROP 2.96%
#10 AWG COPPER A 16 #12 AWG COPPER A 16MAXIMUM FULL LOAD L 108 MAXIMUM FULL LOAD L 68BRANCH CIRCUIT X 21.6 BRANCH CIRCUIT X 21.6LENGTH TO CENTROID T 75 LENGTH TO CENTROID T 75FOR 20A CIRCUITS y 0.00323 FOR 20A CIRCUITS y 0.00323120V C.M. 10380 120V C.M. 6530
V 3.6 V 3.6WIRE SIZE BELOW SYS. V 120 WIRE SIZE BELOW SYS. V 12010 % DROP 3.00% 12 % DROP 3.00%
NONE1 SINGLE LINE DIAGRAM
DEMAND CALCULATIONS
OCT 2016PF CORRECTION 0.9CEC 25%EXISTING DEMAND BASE LINE
NEW HVAC LOADS
NEW SERVICE TOTAL
DEMAND CALCULATIONS
125.0138.9
34.7173.6
256.4
430.01194
KWKVAKVAKVA
KVA
KVAAMPS
3P250AF250AT
65KAIC
3P400AF300AT
65KAIC
'MA' 'MB' 'MC' 'ME'
ALL NEW EQUIPMENT SHALL BE 65KAIC RATEDSERIES RATINGS MAY BE EMPLOYED FOR BRANCHCIRCUIT BREAKERS ASSUMING PANEL MAIN CIRCUITBREAKER IS 65KAIC RATED
3P250- 3P300- 3P300-
3" C4 #250+1 #4 GND25'VD=0.11%
BLDG 1 BLDG 2 BLDG 3 BLDG 5
8 9 10 113P250AF
250AT65KAIC
3P250-
#2 #2 #2 #2TO BLDG COLD WATER TYPICAL
3P400AF300AT
65KAIC
3" C4 #250+1 #4 GND270'VD=1.12%
3" C4 #300+1 #4 GND70'VD=0.42%
3" C4 #300+1 #4 GND265'VD=1.55%
NEMA 3R PANELS TYPICAL
MA MB MC ME
'AO'1 1/4" C4 #2+1 #8 GND
3P600AF600AT
TYPE
DP1PORTABLES
400A, 120/208V, 3PH, 4W
1 2 3 4 5
PNL"CC"
PNL"BA"
PNL"AA"
PNL"AB"
2P100A2P150A2P200A
(4) 4"FROM SCE
1" C1 #3/0 CU GNDEXISTING SYSTEM
'MSA' NEMA 1
2 1/2" C3 #4/0+1 #2 GND
2P400A
3P1200A65K
1200A, 120/208V, 3PH, 4W
(2) 2" C3 #4/0 EA+1 #2 GND
RSE-SIERRA65 KAIC DESIGNPENDING SCE
PNL"XA"
PNL"XCC"
PNL"CB"
PNL"CA"
PNL"D"
PNL"XD"
PNL"XC"
PNL"XB"
2 1/2" C3 #4/0+1 #2 GND
1 1/2" C3 #2+1 #6 GND
1 1/2" C3 #2+1 #6 GND
BLDG A BLDG ABLDG B
1 1/2" C3 #2/0+1 #2 GND
1 1/2" C3 #2/0+1 #2 GND
1 1/2" C3 #2+1 #6 GND
1 1/2" C3 #1/0+1 #4 GND
2" C3 #2+1 #6 GND
1 1/2" C3 #2/0+1 #2 GND
BLDG C BLDG C BLDG C
BLDG C
BLDG C BLDG D BLDG D
2P200A
BLDG EBLDG A
BLDG B
DIMMERBDPNL"EA"
PNL"EB"
1 1/2" C3 #2+1 #6 GND
BLDG E
6 7
PNL"BB"
2P125A
BLDG B
PNL"K"
BLDG E
2" C4 #1+1 #6 GND
TEMPERING OUTSIDE AIR
DEMAND CALCULATIONS
OCT 2016PF CORRECTION 0.9CEC 25%EXISTING DEMAND BASE LINE
NEW HVAC LOADS
HP-AHP-BHP-C
NEW SERVICE TOTAL
125.0138.9
34.7173.6
223.2
18.728.832.4
476.71324
KWKVAKVAKVA
KVA
KVAKVAKVA
KVAAMPS
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
E002
ELECTRICALSINGLE LINE
DIAGRAM
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2 06/04/18 CCD-2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
PANELBOARD: MA FAULT CURRENT: REFER TO ONE-LINE DIAGRAM EQUIPMENT GROUND BUSBUS AMPS: 250A AIC RATING: 65000 SERIES RATEDMAIN SIZE/TYPE: 250A MCB SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: SURFACESECTION: 1 LOCATION: SERVICE ENTRANCE RATED
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 FC-A-1 175 15 2 2 15 150 FC-A-2 23 175 150 45 FC-A-3 150 15 2 2 15 150 FC-A-4 67 150 150 89 FC-A-5 150 15 2 2 15 150 FC-A-6 1011 150 150 1213 FC-A-7 150 15 2 2 15 150 FC-A-8 1415 150 150 1617 FC-A-9 262 15 2 2 15 790 SF-A-1 1819 262 790 2021 SF--A-2 790 15 2 2 20 1,248 CU-A-2 2223 790 1,248 2425 EF-A-1 360 15 1 3,483 HP-A-2 mod1 2627 EF-A-2 120 15 1 3 50 3,483 2829 EF-A-3 240 15 1 3,483 3031 OUTLETS-EQUIP YARD A 360 20 1 3,483 HP-A-2 mod2 3233 MCU-A1 - A2 180 15 2 3 50 3,483 3435 180 3,483 3637 HP-A-1 mod1 3,483 3,483 HP-A-1 mod2 3839 3,483 50 3 3 50 3,483 4041 3,483 3,483 4243 NOT AVAILABLE 1 1 NOT AVAILABLE 4445 NOT AVAILABLE 1 1 NOT AVAILABLE 4647 NOT AVAILABLE 1 1 NOT AVAILABLE 4849 PNLBD AO 1,680 1 NOT AVAILABLE 5051 SUB-FEED BREAKER 2,280 90 3 1 NOT AVAILABLE 5253 2,520 1 NOT AVAILABLE 54
SUBTOTAL 6,619 7,327 7,774 11,687 12,145 12,786 SUBTOTAL
TOTAL PHASE A - VA 18,306 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 153 COOLING 51,678 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 19,472 HEATING 0 SIGN/DISPLAY 1.25 AMPS 162 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 20,560 RECEPTACLES 6,660 1.0/.5 EXISTING 1.00 AMPS 171 MOTORS 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 58,338 SUPP HEAT 1.00 SHOW WINDOW 1.25 58,338 VA AMPS 162 MISC EQUIP 1.00 LTG TRACK 1.00 162 A
PANELBOARD NOTES
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
PANELBOARD: MB FAULT CURRENT: REFER TO ONE-LINE DIAGRAM EQUIPMENT GROUND BUSBUS AMPS: 250A AIC RATING: 65000 SERIES RATEDMAIN SIZE/TYPE: 250A MCB SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: SURFACESECTION: 1 LOCATION: SERVICE ENTRANCE RATED
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 FC-B-1 26 15 2 2 15 150 FC-B-2 23 26 150 45 FC-B-3 150 15 2 2 15 150 FC-B-4 67 150 150 89 FC-B-5 150 15 2 2 15 150 FC-B-6 1011 150 150 1213 FC-B-7 150 15 2 2 15 150 FC-B-8 1415 150 150 1617 FC-B-9 175 15 2 2 15 790 SF-B-1 1819 175 790 2021 SF-B-2 915 15 2 1 2223 915 1 2425 EF-B-1 360 15 1 1 2627 EF-B-2 120 15 1 1 2829 OUTLETS-EQUIP YARD B 180 20 1 1 3031 MCU-B1 - B2 - B3 270 15 2 4,323 HP-B-2 mod1 3233 270 3 60 4,323 3435 1 4,323 3637 HP-B-1 5,284 4,323 HP-B-2 mod2 3839 5,284 80 3 3 60 4,323 4041 5,284 4,323 42
SUBTOTAL 6,414 6,915 6,853 9,886 9,096 9,736 SUBTOTAL
TOTAL PHASE A - VA 16,300 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 136 COOLING 48,720 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 16,010 HEATING 0 SIGN/DISPLAY 1.25 AMPS 133 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 16,589 RECEPTACLES 180 1.0/.5 EXISTING 1.00 AMPS 138 MOTORS 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 48,900 SUPP HEAT 1.00 SHOW WINDOW 1.25 48,900 VA AMPS 136 MISC EQUIP 1.00 LTG TRACK 1.00 136 A
PANELBOARD NOTES
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
PANELBOARD: MC FAULT CURRENT: REFER TO ONE-LINE DIAGRAM EQUIPMENT GROUND BUSBUS AMPS: 400A AIC RATING: 65000 SERIES RATEDMAIN SIZE/TYPE: 300A MCB SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: SURFACESECTION: 1 LOCATION: SERVICE ENTRANCE RATED
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 FC-C-1 150 15 2 2 15 150 FC-C-2 23 150 150 45 FC-C-3 150 15 2 2 15 150 FC-C-4 67 150 150 89 FC-C-5 150 15 2 2 15 150 FC-C-6 1011 150 150 1213 FC-C-7 150 15 2 2 15 150 FC-C-8 1415 150 150 1617 FC-C-9 150 15 2 2 15 150 FC-C-10 1819 150 150 2021 FC-C-11 150 15 2 2 15 150 FC-C-12 2223 150 150 2425 SF-C-1 915 15 2 2 15 915 SF-C-2 2627 915 915 2829 EF-C-1 - C-4 540 15 1 1 20 180 OUTLETS-EQUIP YARD D 3031 EF-C-2 360 15 1 1 20 3233 SF-D-1 562 15 2 1 20 180 EF-C-3 3435 562 2 15 832 FC-D-1 3637 HP-D-1 1,872 832 3839 1,872 30 3 2 15 832 FC-D-1 4041 1,872 832 4243 HP-D-2 1,872 2 15 270 MCU-C1 - C2 - C3 4445 1,872 30 3 270 4647 1,872 1 4849 HP-C-1 mod1 5,284 5,284 HP-C-2 mod1 5051 5,284 80 3 3 80 5,284 5253 5,284 5,284 5455 HP-C-1 mod2 4,323 4,323 HP-C-2 mod2 5657 4,323 60 3 3 60 4,323 5859 4,323 4,323 6061 Space 1 1 space 6263 Space 1 1 space 6465 Space 1 1 space 6667 not available 1 1 not available 6869 not available 1 1 not available 7071 not available 1 1 not available 72
SUBTOTAL 15,225 15,427 15,052 12,223 12,403 12,050 SUBTOTAL
TOTAL PHASE A - VA 27,449 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 229 COOLING 84,253 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 27,830 HEATING 0 SIGN/DISPLAY 1.25 AMPS 232 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 27,102 RECEPTACLES 1.0/.5 EXISTING 1.00 AMPS 226 MOTORS 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 82,381 SUPP HEAT 1.00 SHOW WINDOW 1.25 84,253 VA AMPS 229 MISC EQUIP 1.00 LTG TRACK 1.00 234 A
PANELBOARD NOTESSINGLE SECTION PANELBOARD
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
PANELBOARD: ME FAULT CURRENT: REFER TO ONE-LINE DIAGRAM EQUIPMENT GROUND BUSBUS AMPS: 400A AIC RATING: 65000 SERIES RATEDMAIN SIZE/TYPE: 300A MCB SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: SURFACESECTION: 1 LOCATION: SERVICE ENTRANCE RATED
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 FC-E-1 900 900 FC-E-2 23 900 15 3 3 15 900 45 900 900 67 FC-E-3 900 2 15 790 FC-E-4 89 900 15 3 790 1011 900 1 SPACE 1213 SF-E-1 1,272 900 SF-E-2 1415 1,272 15 3 3 15 900 1617 1,272 900 1819 1 1 20 SPARE 2021 1 1 15 480 EF-E-1 2223 1 1 15 480 EF-E-2 2425 1 1 15 120 EF-E-3 2627 1 1 20 180 OUTLETS - EQUIP YARD E 2829 1 1 20 SPARE 3031 HP-E-1 4,968 4,968 HP-E-2 3233 4,968 60 3 3 60 4,968 3435 4,968 4,968 3637 HP-E-3 4,968 1,872 HP-E-4 3839 4,968 60 3 3 30 1,872 4041 4,968 1,872 42
SUBTOTAL 13,008 13,008 13,008 9,550 10,090 9,120 SUBTOTAL
TOTAL PHASE A - VA 22,558 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 188 COOLING 72,753 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 23,098 HEATING 0 SIGN/DISPLAY 1.25 AMPS 192 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 22,128 RECEPTACLES 1.0/.5 EXISTING 1.00 AMPS 184 MOTORS 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 67,785 SUPP HEAT 1.00 SHOW WINDOW 1.25 72,753 VA AMPS 188 MISC EQUIP 1.00 LTG TRACK 1.00 202 A
PANELBOARD NOTES
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
PANELBOARD: K (EXISTING) FAULT CURRENT: REFER TO ONE-LINE DIAGRAMBUS AMPS: 125A AIC RATING: FCA +10% MINIMUM, FULLY RATEDMAIN SIZE/TYPE: 125A MCB SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: SURFACESECTION: 1 LOCATION:
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 SPARE 20 1 1 20 TEACHER'S LTG 23 SPARE 20 1 1 20 DINING RM LTG (CENT & S) 45 SPARE 20 1 1 20 FANS DINING RM 67 SPARE 20 1 1 20 DINING RM LTG (CENT & N) 89 KITCHEN'S WEST WALL 20 1 1 20 SPARE 1011 TEACHER'S RM PLUG (E) 20 1 2 20 ATTIC AIR BLOWER 1213 TEACHER'S RM PLUG (W) 20 1 1415 TEACHER'S RM PLUG (S) 20 1 1 20 ATTIC LTG/CLOCK 1617 SPARE 20 1 1 20 OUTSIDE LTG 1819 SPARE 20 1 1 20 SPARE 2021 BUNN WARMER 20 1 1 20 SPARE 2223 SPARE 20 1 1 20 2425 SPACE 1 1 20 P1 & P2 BOILER RM 2627 SPACE 1 1 20 P1 & P2 BOILER RM 2829 IDF 20 1 1 20 3031 SPARE 20 1 1 20 SPARE 3233 SPARE 20 1 1 15 630 GSF-1 SUPPLY FAN 34 N35 SPARE 20 1 ////////// ////////////////////// 36 ST37 SPARE 20 1 1 20 300 ANSUL- HOOD LT 38 N39 SPARE 50 2 2 15 790 GEF-1 EXHAUST HOOD 40 N41 790 42 N
SUBTOTAL 300 1,420 790 SUBTOTAL
TOTAL PHASE A - VA 300 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 3 COOLING 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 1,420 HEATING 0 SIGN/DISPLAY 1.25 AMPS 12 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 790 RECEPTACLES 1.0/.5 EXISTING 1.00 AMPS 7 MOTORS 2,510 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 2,510 SUPP HEAT 1.00 SHOW WINDOW 1.25 2,510 VA AMPS 7 MISC EQUIP 1.00 LTG TRACK 1.00 7 A
PANELBOARD NOTESN-NEW CIRCUIT ST - SHUNT TRIP
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
PANELBOARD: AO FAULT CURRENT: REFER TO ONE-LINE DIAGRAMBUS AMPS: 100A AIC RATING: 65000 SERIES RATEDMAIN SIZE/TYPE: MLO SERVES:VOLTS/PHASE: 208Y/120V, 3PH, 4W MOUNTING: RECESSEDSECTION: 1 LOCATION:
CKT DESCRIPTION VOLTAMPS/PHASE WIRE BKR P P BKR WIRE VOLTAMPS/PHASE DESCRIPTION CKTNO. A B C NO. AMP AMP NO. A B C NO.
1 LIGHTING-OFFICES 1 1 360 OUTLETS-1102 23 1 1 360 OUTLETS-1103-1104 45 1 1 360 OUTLETS-1102-1103 67 1 1 360 OUTLETS-1103 89 1 1 360 OUTLETS-1101 1011 1 1 360 OUTLETS-1101 1213 1 1 360 OUTLETS-1101 1415 1 1 360 OUTLETS-1101 1617 1 1 600 VENDING-1106 1819 1 1 600 VENDING-1106 2021 1 1 1,200 COFFEE-1106 2223 1 1 1,200 MICROWAVE-1106 2425 1 1 2627 1 1 2829 1 1 30
SUBTOTAL 1,680 2,280 2,520 SUBTOTAL
TOTAL PHASE A - VA 1,680 LOAD CONN. VA DF LOAD CONN. VA DF AMPS 14 COOLING 1.00 REFRIGERATION 1.00
TOTAL PHASE B - VA 2,280 HEATING 0 SIGN/DISPLAY 1.25 AMPS 19 LIGHTING 1.25 KITCHEN 1.00
TOTAL PHASE C - VA 2,520 RECEPTACLES 6,480 1.0/.5 EXISTING 1.00 AMPS 21 MOTORS 1.00 LARGE MOTOR 1.25 TOTAL DEMAND
TOTAL PNLBD - VA 6,480 SUPP HEAT 1.00 SHOW WINDOW 1.25 6,480 VA AMPS 18 MISC EQUIP 1.00 LTG TRACK 1.00 18 A
PANELBOARD NOTES
LTG TRACK - TRACK LENGTHSIGN/DISPLAY - SIGNAGE & DISPLAY CASE
NONE.PANEL SCHEDULE MA
NONE.PANEL SCHEDULE MB
NONE.PANEL SCHEDULE MC
NONE.PANEL SCHEDULE ME
NONE.PANEL SCHEDULE K
NONE.PANEL SCHEDULE AO
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
E003
ELECTRICALPANEL
SCHEDULE
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2 06/04/18 CCD-2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
S
SS
SPSP
PVT
SP
VL
SP
PVT
VL
ICS
ICS
3E-005
3E-005
APVT
BPVT
APVT
BPVT
J
2m
2m2m
2
2
3
2
2
3
9 6 5
5
5
10
10
36,38
40,42
33,35
MC-33,35& 36,38& 40,42
MC-37,39,41#10
MC-43,45,47#10
N
SEE DETAIL FOR EXTRON AVSYSTEM WIRING AND 11OV
CIRCUITRY.
EXIST.IDF CABINET
N
NN
NN
SEE DETAIL FOR EXTRON AVSYSTEM WIRING AND 11OV
CIRCUITRY.
MC-30
ON ROOF WITHHP-D1-2
XRW
XRW
IDFCAB'T.
HPD-1
HPD-2
FCD-2
FCD-1
SFD-1
WAP
WAP
N N
S
S
S
SS
S
S
S
S
S
S
S
J
J
ICS
SP
SP
SP
VL
MLC
APVT
BPV
T
SP
J
J
J
J
J
J
2m
3m
3m
2m
3m
m
m
2m
3m
m
m
2
2
2
2
2
2
2
2
1 1 1 1 4
4
4
4
13
12
14
ME-31,33,351"C.(RIGID),3#4THWN CU.
ME-38,40,421/2"C.(RIGID),3#10THWN CU.
ME-37,39,411"C.(RIGID),3#4THWN CU.
ME-32,34,361"C.(RIGID),3#4THWN CU.
ME-8,10& 14,16,18& 26
6,8
14,16,18
26
ME-1,3,5& 2,4,5& 13,15,17
13,15,17
1,3,5
2,4,6
ME-22,24
22
24
ME-7,9,11
NEW PANEL "ME"WEATHERPROOF
CONNECT TOMOTORIZED SCREEN
MOTORIZED SCREEN
PROVIDE UP-DOWN 3 POSITIONSWITCH WITH ENGRAVEDNAMEPLATE "SCREEN"EXISTING DUPLEX RECEPTACLECONNECT SCREEN CIRCUITRY TOEXISTING RECEPTACLE
VERIFY EXISTING DUPLEX RECEPTACLE INFIELD PRIOR TO START OF WORK ANDCONNECT NEW ICS 120V CIRCUITRY TOEXISTING RECEPTACLE.
3/4"C., (WITH PULL LINE FOR ICS WIRING BYOTHER)
N N
3/4"C., (SIGNAL DATA WIRING)
K-40,42
K-34
K-38
ME-12
12
ME-20
20
3/4"C., (SIGNAL DATA WIRING)
RAUROUTE TOEX IDF CKT
'K'
IDFCAB'T.
SFE-2
FCE-4
FCE-3
EFE-3
FCE-1
EFE-1
EFE-2
HPE-3HP
E-2HPE-4
HPE-1
FCE-2
SFE-1
GEF1
GSF1
SP
APVT
BPVT
VL
PVT
1
2
3
REFERENCE NOTES:
SYMBOL LEGEND
4
1. FOR ADDITIONAL WIRING, INFORMATION AND SCOPE OFWORK ON THE EXTRON AV SYSTEM REFER TO SHEETE-005.
AV CONSTRUCTION NOTES:
5
6
7
8
9
10
FOR NEW HVAC EQUIPMENT PROVIDE 120VOR 208V.,1∅.,2W ELECTRICAL CONNECTIONS ASREQUIRED AND 30A,2P MOTOR RATED TOGGLE TYPEDISCONNECT AT UNIT.
EXISTING 2 CIRCUIT PLUGMOLD TO REMAIN IN PLACEAND IN SERVICE FOR SCHOOL USE.
EXISTING DATA AND POWER OUTLETS @+8'-6" A.F.F.SERVING EXISTING WIRELESS WYFY "WAP" ANTENNA.
PROVIDE 1/2"C.,2#12 BRANCH CIRCUITRY ANDCONNECT TO NEAREST EXISTING 120V PANEL (SPARE20A,1P C/B). SERVING THE AREA.
PROVIDE 1/2"C.,2#12 BRANCH CIRCUITRY INTER-CONNECT WITH EXISTING LIGHTING OR POWERBRANCH CIRCUITRY SERVING THE AREA.
OUTLET FOR THE CONNECTION OF NEW ELECTRICHAND DRYER +42" A.F.F. (REFER TO ARCHITECTURALPLAN FOR EXACT LOCATION. FROM OUTLETCONTRACTOR SHALL PROVIDE 1/2"C.,2#12 BRANCHCIRCUITRY AND CONNECT TO EXISTING ELECTRICHAND DRYER (WHICH IS SCHEDULE TO BE REMOVEDAND DEMO) BRANCH CIRCUITRY IN THE THE AREA.
TO SUPPORT THE INSTALLATION OF NEW DATACABLING AND/OR ICS SYSTEM WIRING, CONTRACTORSHALL PROVIDE AND SECURE TO ROOF JOIST ORROOF RAFTER J-HOOK SUPPORT SYSTEM WITHJ-HOOKS SPACE 48" O.C.
FOR DATA AND ICS CABLING ROUTING THROUGH FIRERATED WALL AND TO MAINTAIN FIRE RATING OF WALL,CONTRACTOR SHALL PROVIDE (3) 36" LENGTH 2"CONDUIT SLEEVES. ALL SLEEVE SHALL BE FIRECAULK AFTER ALL DATA AND ICS CABLING HAS BEENINSTALLED.
APPLY TO KINDERGARTEN CLASSROOM ONLY -CEILING PULL DOWN PROJECTION SCREEN.
EXTRON VLR 120 VOICE LIFT RECEIVER MOUNTED INLAY-IN CEILING. THE OUTLET BOX LOCATED FLUSHIN CEILING, 4 GANG OUTLET BOX WITH BARRIER TOSEPARATE 120V BRANCH CIRCUITRY FROM DATADIGITAL SIGNAL WIRING. FROM RECEPTACLE PROVIDE120V BRANCH CIRCUITRY CIRCUIT 1/2"C.,2#12 ANDCONNECT TO EXISTING HEATER CIRCUITRY SERVINGTHE ROOM. CONTRACTOR IS RESPONSIBLE FORCOMPLETE OPERATING SYSTEM WITH PROGRAMMINGAND COMMISSIONING OF SYSTEM.DISTRICT SPECIFIED SYSTEM IS EXTRON. REFER TODISTRICT STANDARD AND CURRENT REQUIREMENTSFOR DETAILS.
EXTRON FF 120 FLAT FIELD SPEAKER MOUNTED INLAY-IN CEILING. SEE DETAIL A/E005.
PVT HDMI/RGB/AUDIO INPUT WALL PLATE ALLMOUNTED IN 2 GANG BOX AND MOUNTED +18"A.F.F. FROM OUTLET BOX STUB 3/4"C. ORWIREMOLD (FOR AV WIRING) ABOVE FOR EXTRON AVSYSTEM.
PVT DUAL HDMI/AUDIO WALL PLATE ALL MOUNTED IN2 GANG BOX AND MOUNTED +18" A.F.F. FROMOUTLET BOX STUB 3/4"C. OR WIREMOLD (FOR AVWIRING) ABOVE FOR EXTRON AV SYSTEM.
MULTI-LINK CONTROLLER WALL PLATE ALL MOUNTEDIN 2 GANG BOX AND MOUNTED +18" A.F.F. FROMOUTLET BOX STUB 3/4"C. OR WIREMOLD (FOR AVWIRING) ABOVE FOR EXTRON AV SYSTEM.
WHERE NEW 15A DOUBLE DUPLEX RECEPTACLES ANDDATA OUTLET ARE TO BE INSTALLED. THE OUTLETSHALL BE MOUNTED IN 4000 RACEWAY WIREMOLDAND OUTLET SHALL BE PLACE +18" A.F.F. NEWDUAL CHANNEL WIREMOLD SHALL BE RUNVERTICALLY UP WALL TO CEILING WITH 1/2"C. 2#12BRANCH CIRCUITRY CONNECTED TO NEARESTEXISTING HEATER 120V POWER SERVING THE AREA.
EXISTING CEILING MOUNTED WIRELESS WYFI DATAANTENNA TO BE SALVAGE DURING CEILING DEMOAND BE REUSED AND RE-INSTALLED IN NEW T-BARCEILING.
CONNECT NEW OUTLET TO EXISTING CKT AVAILABLEFROM DEMOLITION IN AREA. IDENTIFY CIRCUIT NUMBERFOR AS-BUILTS AND IDENTIFY BEW USAGE IN EXISTINGPANEL DIRECTORY.
11
12
13
14
PROVIDE NEMA WEATHERPROOF COMBINATION SIZE "0"MAG STARTER WITH 30AS.,2P 15AF FUSED DISCONNECTFOR THE ELECTRICAL CONNECTIONS AS REQUIRED TOHOOD EXHAUST UNIT.
RUN AND CONNECT TO HOOD ON/OFF SWITCH.
PROVIDE OUTLET BOX ADJACENT TO HOOD AND MAKETHE FOLLOWING ELECTRICAL CONNECTIONS:
- 1/2"C.,2#12 TO ANSUL EQUIPMENT.- 1/2"C.,2#12 TO HOOD LIGHTS- 1/2"C.,2#12 BETWEEN SNAP SWITCH AND CIR.
K-34 SHUNT TRIP FOR GSF-1 SHUT DOWN.
(NOTE: CONTRACTOR SHALL COORDINATE ALL ELECTRICALWORK WITH HOOD SUPPLIER AND MECHANICAL).
PROVIDE NEMA WEATHERPROOF 32"W.x 48"H.X 8"D.PULL BOX AND FUSED DISCONNECT FOR THEELECTRICAL CONNECTIONS AS REQUIRED TO HVACUNIT.
NN
WAP
A
A
A
A
TYP FOR ENTIREBUILDING EXTERIOR
A
A
B
B
L
L
TYPOF 2
CLASSROOM4101
CLASSROOM4103
ALL GENDERRESTROOM
4102
ALL GENDERRESTROOM
4104
STORAGE4105
TYP FOR ENTIREBUILDING EXTERIOR
PATCH & REPAIR (E)PLASTER WALLS. PREPFOR NEW PAINTFINISH
(N) WOOD FRAMED CEILING @ 9'-0" A.F.F.W/ GYP. BD. FINISH. PAINT. PROVIDE (N)SURFACE-MOUNTED LED LIGHT FIXTURELOBBY
5100
ALL GENDERRESTROOM
5101
ALL GENDERRESTROOM
5102
AUDITORIUM5103
STAGE5108
STORAGE5107
VESTIBULE5105
ALL GENDERRESTROOM
5106
VESTIBULE5104
STORAGE5109
VESTIBULE5111
ALL GENDERRESTROOM
5110
VESTIBULE5112
CAFETERIA5113
KITCHEN5115
LOUNGE5114
W.H5116
ALL GENDERRESTROOM
5118
OFFICE/STORAGE5117 LPV
626 714-7506 FAX 626 714-7512Pasadena, California 91103
751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
KEYPLAN
1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
E114
ELECTRICALPOWER PLANBLDGS 4 & 5
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
1/8" = 1'-0"
1ELECTRICAL POWER PLAN BLDGS 4
1/8" = 1'-0"
2ELECTRICAL POWER PLAN BLDGS 5
2 06/04/18 CCD-2
2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVEDDIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
DS
DH
110cdAV
J
FCPS-24
NFS2-3030
DAA-5025
AM
AR
MM ETS
PROTECTOWIREMONITOR MODULE
FS
TS
FA
1A/1V
AV110cd
DH
DS
MM ETS
AV
IF
ERFAV
AV
110cd
THE SEISMIC ANCHORAGE OF ELECTRICAL EQUIPMENT SHALL CONFORM TOCBC 2016 AND NFPA 13 LATEST EDITION CODES AND PERMITS: ALL EQUIPMENT, INSTALLATION, ETC., SHALL CONFORM TO LOCAL ELECTRICAL,
MECHANICAL AND OTHER APPLICABLE CODES. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS ANDINSPECTIONS. COPIES OF ALL PERMITS AND INSPECTION REPORTS SHALL BE SUBMITTED TO THE ARCHITECT.CODES INCLUDE BUT NOT LIMITED TO:
TITLE 24, PART 2, CCR (2016 CALIFORNIA BUILDING CODE W/AMENDMENTS)TITLE 24, PART 3, CCR (2016 CALIFORNIA ELECTRICAL CODE W/AMENDMENTS)TITLE 24, PART 4, CCR (2016 CALIFORNIA MECHANICAL CODE W/AMENDMENTS)TITLE 24, PART 5, CCR (2016 CALIFORNIA PLUMBING CODE W/AMENDMENTS)TITLE 24, PART 9, CCR (2016 CALIFORNIA FIRE CODE W/AMENDMENTS)2016 CALIFORNIA GREEN BUILDINGS STANDARDS CODES)2016 CALIFORNIA REFERENCED STANDARDS CODE (PART 12, TITLE 24, CCR)
NFPA 13 - 2010 NFPA 72 - 2010
REFERENCED CODE SECTIONS FOR APPLICABLE STANDARDS 2010 CBC, CHAPTER 35 2010 CFC, CHAPTER 45
NFPA STANDARDS AND GUIDES NFPA 72 NATIONAL FIRE ALARM CODES (CALIFORNIA AMENDED, 2010 EDITION) NOTE: SEE UL STANDARD 1971 FOR "VISUAL DEVICES".
SEQUENCE OF OPERATION
BLDGPOWERFAILURE
AREASMOKE
DETECTORAREA HEATDETECTOR
PULLSTATION
ANSULHOOD
MONITORMODULE
SPRINKLER
Water flowswitch
Tamperswitch
ANNUNCIATE AT FIRE CONTROL PANEL(SUPERVISION & TROUBLE) ALARM YES YES YES YES YES YES YES
SOUND CONTROL PANEL TROUBLEBUZZER YES ON WIRING
FAULTON WIRING
FAULTON WIRING
FAULT NO ON WIRINGFAULT YES
ACTIVATE AUDIBLE ALARM/ VOICE EVACSPEAKER SIGNALS NO YES YES YES NO YES NO
ACTIVATE VISUAL ALARM SIGNALS NO YES YES YES NO YES NO
HVAC >2000 CFM FAN SHUT DOWNACTIVATION (VIA ADDRESSABLE RELAY)
NOTPROVIDED YES NO NO YES NO NO
CENTRAL STATION SIGNALS (UNTILRESET) YES YES YES YES NO YES YES
NEW FIRE ALARM SYMBOLS LEGENDSYMBOL DESCRIPTION
NEW ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR. NOTIFIER FSP-851A CSFM#7272-0028:0206 WITH BASE NOTIFIERB710LPBP CSFM#7272-0028:0206
NEW ADDRESSABLE HEAT DETECTOR (TO BE LOCATED IN ATTIC SPACE). NOTIFIER FST-851 CSFM#7270-0028:0196 WITHBASE NOTIFIER B710LPBP CSFM#7270-0028:0196
NEW ADDRESSABLE MANUAL PULL STATION +48" TO TOP. NOTIFIER NBG-12LX CSFM#7270-0028:0196 WITH BASE NOTIFIERB710LPBP CSFM#7150-0028:0199
NEW CEILING MOUNTED COMBINATION AUDIO MIN. 1W (85.4 dBA) SPEAKER U.O.N/STROBE DEVICE (WITH SELECTABLECANDELA AND WATTAGE TAPS SEE PLANS). GENTEX #SSPK24CLPPW CSFM LISTING#7320-0569:0137
STROBE CANDELA LEVEL115cd @ 0.290A., 95cd @ 0.220A., 75cd @ 0.200A., 30cd @ 0.120A., 15cd @ 0.120A.
SPEAKER WATTAGE TAPS1/8W (73.7 dBA.), 1/2W (79.6 dBA), 1W (82.5 dBA), 2W (85.4 dBA), 4W (87.9 dBA)
NEW WALL MOUNTED COMBINATION AUDIO SPEAKER/STROBE DEVICE (WITH SELECTABLE CANDELA AND WATTAGE TAPSSEE PLANS). GENTEX #SSPK24WLPW CSFM LISTING#7320-0569:0140
STROBE CANDELA LEVEL110cd @ 0.224A., 75cd @ 0.180A., 60cd @ 0.137A., 30cd @ 0.096A., 15cd @ 0.078A.
SPEAKER WATTAGE TAPS1/8W (73.7 dBA.), 1/4W (76.7 dBA). 1/2W (79.6 dBA), 1W (82.5 dBA), 2W (85.4 dBA), 4W (87.9 dBA)
NEW WEATHERPROOF EXTERIOR VOICE EVAC MIN. 2W (85.4 dBA) SPEAKER U.O.N WITH BACKBOX GENTEX #WSSPKRCSFM#7320-0569:0141
WP NEW WEATHERPROOF EXTERIOR VOICE EVAC 2W SPEAKER/STROBE DEVICE (WITH SELECTABLE CANDELA ANDWATTAGE TAPS SEE PLANS) WITH BACKBOX GENTEX #WSSPKR CSFM#7320-0569:0141 @
STROBE CANDELA LEVEL110cd @ 0.224A., 75cd @ 0.180A., 60cd @ 0.137A., 30cd @ 0.096A., 15cd @ 0.078A.
SPEAKER WATTAGE TAPS1/8W (73.7 dBA.), 1/4W (76.7 dBA). 1/2W (79.6 dBA), 1W (82.5 dBA), 2W (85.4 dBA), 4W (87.9 dBA)
WALL JUNCTION BOX, MOUNTING HEIGHT AS INDICATED ON PLAN, SIZE PER N.E.C; U.O.N. @ SHEET AS INDICATED ONPLAN. 120V, U.O.N. CONTRACTOR SHALL PROVIDE AND INSTALL JUNCTION BOXES SIZE TO ACCOMMODATE QUANTITIESOF WIRES PER N.E.C. SECTION 314.18 AND TABLE 314.18(A), 5" BOX 4/16" SQ. X 21/8"D. BOX.
NEW NOTIFIER FIRE ALARM USUAL (FLASHER POWER SUPPLY, NOTIFIER FCPS-24S8 FOR STROBE FLASHER UNIT).CSFM#7315-0028:225
FIRE ALARM CONTROL PANEL WITH VOICE CONTROL CENTER (VOICE EVAC). NOTIFIER NFS2#3030 WITH AUDIO OPTIONDVC VOICE TRANSPONDER. CSFM#7165-0028:0224 INTELLIGENT.
NEW OR EXISTING NOTIFIER #DAA-5025 INTELLIGENT AUDIO TRANSPONDER POWER SUPPLIES (FOR FREE MAIN VOICEEVAC SPEAKER). CSFM#7170-0028:223, 7170-0028:244.
ADDRESSIBLE MONITOR MODULAR - NOTIFIER FMM-1(A) CSFM#7165-0028:0224
ADDRESSIBLE CONTROL RELAY MODULAR - NOTIFIER FCM-1 CSFM#7165-0028:0219
PROTECTOWIRE LINEAR HEAT DETECTOR ASSEMBLY. SYSTEM SENSOR #PHSC-190-EPR (-M). CSFM#7270-0854:101
SYSTEM SENSOR M500MB MONITOR MODULE.
NEW FLOW SWITCH
NEW TAMPER SWITCH
NEW 3/4" FIRE ALARM SYSTEM CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALL (WITH ALARM WIRES ASREQUIRED). FA - ONE CABLE, 2FA - TWO SET OF CABLES
NEW 3/4" FIRE ALARM SYSTEM CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALL (WITH AUDIO AND VISUAL CABLES).1V - VISUAL CABLE, 1A - AUDIO VOICE EVAC CABLES
1. THE FIRE ALARM SYSTEM SHALL COMPRISE AUTOMATIC ADDRESSABLE MANUAL PULLS, SMOKE/HEAT DETECTIONS SYSTEM AND CONFORM TOARTICLE 760 OF THE 2013 CALIFORNIA ELECTRICAL CODE.
2. UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE MADE IN THEPRESENCE OF THE FIRE MARSHALL OR ENFORCING AGENCY.
3. A STAMPED SET OF APPROVED FIRE ALARM PLANS SHALL BE ON THE JOB SITE. AND USED FOR INSTALLATION. ANY DEVIATION FOR THEAPPROVED PLANS, INCLUDING THE SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE FIRE MARSHALL OR ENFORCING AGENCY.
4. FIRE ALARM DRAWINGS ARE SCHEMATIC IN NATURE ONLY. CONTRACTOR SHALL ROUTE CONDUIT RACEWAY AS FIELD CONDITION PERMIT OR ASINDICATED ON PLANS. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND CODE OR RECOGNIZED STANDARDS, SHALL BE BROUGHT TO THEATTENTION OF THE INSPECTOR OF RECORD.
5. ALL DEVICES OF THE FIRE ALARM SYSTEMS SHALL BE APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHALL.
6. A CERTIFICATE OF COMPLETION SHALL BE PREPARED BY THE INSTALLER AND GIVEN TO THE FIRE MARSHALL UPON COMPLETION OF THEINSTALLATION.
7. CONSULT INSTALLER PRIOR TO MAKING ANY MODIFICATIONS TO THE SYSTEMS WIRING.
8. UPON COMPLETION OF THE INSTALLATION, THE INSTALLER SHALL SUPPLY THE OWNER WITH WRITTEN OPERATING, TESTING AND MAINTENANCEINSTRUCTIONS, POINT-TO-POINT AS-BUILT DRAWINGS AND EQUIPMENT SPECIFICATIONS.
A. THE SYSTEM SHALL BE TESTED IN THE PRESENCE OF AND IN A MANNER ACCEPTABLE TO THE ENFORCING AGENCY AND A COMPLETE TESTINGAND INSPECTION FORM SHALL BE PROVIDED FOR LOCAL FIRE AND/OR DSA INSPECTOR SIGNATURE.
9. 120 VAC, 60HZ INPUT POWER FOR THE FIRE ALARM CONTROLS SHALL BE A DEDICATED CIRCUIT BREAKER PROPERLY LABELED "FIRE ALARM".
10. 120 VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.
11. THE LOCATION OF THE FIRE ALARM CONTROL PANEL AND THE ANNUNCIATOR SHALL BE APPROVED BY THE FIRE MARSHALL OR ENFORCINGAGENCY.
12. ALL OPENINGS IN RATED ASSEMBLIES SHALL BE REPAIRED PER UFC, NEC, UBC AND STANDARD BUILDING CODES ON EFFECT AT THE TIME OFAPPROVAL. THE SYSTEM SHALL CONFORM TITLES 19 AND 24 AS APPLICABLE TO THIS PROJECT (CBC PART 2, CH. 7, TITLE 24).
13. ALL BACK BOXES SHALL BE AS RECOMMENCED BY MANUFACTURER. CONTRACTOR SHALL LOCATE JUNCTION BOXES AS REQUIRED AND PER CECCODES.
14. ALL PANELS SHALL BE MOUNTED WITH CLEARANCES FOR OBSERVATION AND TESTING, AND ALL FIRE ALARM JUNCTION BOXES SHALL BE MARKEDFOR IDENTIFICATION.
15. ALL WIRING OF INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPLE POINT OF ANNUNCIATION (THE FIREALARM CONTROL PANEL IS TO SUPERVISE THE ANNUNCIATOR PANEL, ALL CIRCUITS AND INITIATING DEVICES).
16. WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT FOR IN AND OUT. POINT COMMON ANNUNCIATION AND T-TAPPING AREPROHIBITED.
A. EXCEPTION: ADDRESSABLE SYSTEMS, MAPNET CONDUCTORS WIRED CLASS "B" MAY BE T-TAPPED.
17. ALL FIRE ALARM WIRING SHALL BE RUN IN MINIMUM 3/4 " CONDUIT.
A. ALL CONDUIT SIZES SHOWN AND INDICATED ON DRAWING ARE MINIMUMS. CONTRACTOR TO ADJUST SIZES FOR FIELD CONDITIONS (I.E. NUMBEROF BENDS, ETC.) BUT SHALL NOT BE SMALLER THAN 3/4".
18. ALL FIRE ALARM SYSTEM WIRING TERMINATIONS IN MAIN PULL BOXES AND TERMINAL CABINETS SHALL BE ON BOX MOUNTED TERMINAL BLOCKS.
19. ALL FIRE ALARM WIRING MUST TEST FREE OF OPENS, SHORTS AND GROUNDS. SEE INSTALLATION MANUALS FOR FIELD WIRING SPECIFICATIONSFOR ADDITIONAL INSTALLATION REQUIREMENTS.
20. (2) PRIMARY PHONE LINE SHALL BE DEDICATED FOR THE FIRE ALARM SYSTEM TO COMMUNICATE WITH U.L. LISTED CENTRAL STATION.
21. WIRING COLOR CODE SHALL BE CONSISTENT THROUGHOUT THE SYSTEM AND SHALL ALLOW FOR EASY IDENTIFICATION OF INITIATING, INDICATINGAND AUXILIARY CIRCUITS.
22. CABINET TERMINALS SHALL BE NUMBERED AND CODED. FLEXIBLE CONNECTORS SHALL BE USED FOR DEVICES MOUNTED IN SUSPENDED PANELS.
23. THE FIRE DEPARTMENT WILL TEST AND VERIFY ADEQUATE AUDIBILITY BEING PROVIDED THROUGHOUT, PARTICULARLY IN OPEN WORK AREAS ANDIN TESTING AREAS.
A. AUDIBLE DEVICES(S) TO BE AT LEASE 15 DBA ABOVE THE AMBIENT SOUND LEVELS, BUT NOT LESS THAN THE 75 DBA AT 10' OR MORE THAN11ODBA AT THE MINIMUM HEARING DISTANCE. AUDIBLE DEVICES SHALL SOUND THE TEMPORAL FIRE ALARM SIGNAL.
24. CONDUIT AND JUNCTION BACK BOXES ARE NOT TO BE USED FOR UNRELATED WIRING.
25. ALL CONDUIT MOUNTING BOXES, AND PANELS SHALL BE HUNG AND FASTENED WITH FITTINGS TO ENSURE POSITIVE GROUNDING THROUGHOUT THEENTIRE SYSTEM.
26. PLACE THE BOTTOM OF THE WALL MOUNTED STROBE EXACTLY 80" ABOVE THE FLOOR TO BOTTOM OF LENS AND MAKE SURE THE TOP OF THESTROBE IS AT LEAST 6" BELOW THE CEILING. PLACE THE TOP OF THE STROBE 6" BELOW THE CEILING IF THE CEILING IS TOO LOW, AND MAKE SUREIT PROTRUDES LESS THAN 4" IF IN A WALKWAY, CORRIDOR OR AISLE. NOTE THAT THESE MOUNTING REQUIREMENTS ALSO APPLY TO COMBINATIONHORN/STROBE OR SPEAKER/STROBE APPLIANCES THAT ARE WALL MOUNTED (NFPA 72, CH.6).
A. MANUAL PULL STATIONS SHALL BE MOUNTED +48" ABOVE FINISHED FLOOR TO CENTER OF BOX. STROBE SHALL BE CEILING OR WALL MOUNTEDAT +80" A.F.F. AND EXTERIOR HORNS HALL BE MOUNTED AT +90" A.F.F.
27. STROBES SHALL BE VISIBLE IN ALL LOCATIONS THROUGHOUT THE BUILDING PER NFPA 72, CHAPTER 6, SECTION 6-4.
A. VISUAL DEVICES SHALL NOT EXCEED 2 FLASHER PER SECOND AND SHALL NOT BE SLOWER THAN 1 FLASH EVERY SECOND.
28. PROVIDE 24 HOUR TELEPHONE NUMBER OF CENTRAL STATION NEAR ANNUNCIATOR AND FIRE ALARM CONTROL PANEL.
29. ALL FIRE ALARM DEVICES LOCATED IN STUDENT RESTROOM FACILITIES ARE TO HAVE VANDAL-RESISTANT GUARDS INSTALLED.
30. ALL MANUAL PULL STATIONS IN AREAS WHERE STUDENTS HAVE ACCESS (I.E. LIBRARY, AUDITORIUM, ETC.) ARE TO HAVE PLASTIC COVERS WITHVANDAL ALARM.
31. FIRE ALARM SYSTEM SHALL COMPLY WITH NFPA 72, 10.4.3, 10.4.4, 10.6.5.3, 10.6.5.4, 10.6.5.5, 10.6.6.2, 10.26.3.4.2, AND 10.26.3.4.3.
32. ON SMOKE DETECTORS CONTRACTOR SHALL MAINTAIN 36" DISTANCE FROM SUPPLY AIR DIFFUSER.
2TYPICAL DEVICE WIRING
1SMOKE/HEAT DETECTOR/PULL STATION, AUDIO/VISUAL DEVICE MOUNTING DETAILS
CODES AND STANDARDS
WIRING SCHEDULEDESIGN. CIRCUIT TYPE DESCRIPTION MODEL
M NOTIFICATION LOOP 2 TWISTED PAIR, 16 AWG FPLRWESTPENN CABLE FPLP 2 PAIR #16 TWISTED,CSFM #7161-0859:0101
FA SLC INTELLIGENT LOOPNETWORK COMM
1 TWISTED PAIR, 18 AWG FPLR(FA2 = 2 SET OF CABLES)
WESTPENN CABLE FPLP 2 PAIR #16 TWISTED,CSFM #7161-0859:0101
1A VOICE EVAC SPEAKER OUTPUTSIGNAL CIRCUIT CABLE 2#16 AWG (RED/BLACK)
WESTPENN CABLE FPLP SHIELDED 2 PAIR #16,#14 0R #12 TWISTED, CSFM #7161-0859:0101
1V STROBE SIGNAL OUTPUTCIRCUIT CABLE 2#14 AWG (RED/BLACK)
WESTPENN CABLE FPLP 2#14 OR 2#12 , CSFM#7161-0859:0101
1A/1V 1A & 1V CABLE
MIN. 3/4" CONDUIT SYSTEM WITH BOTH VOICEEVAC SPEAKER OUTPUT SIGNAL CIRCUIT
CABLE AND STROBE SIGNAL OUTPUT CIRCUITCABLE
REFER TO 1A AND 1V ABOVE FOR CABLE TYPE
2A/2V (2) SET OF 1A & 1V CABLES
1" CONDUIT SYSTEM WITH (2) SET BOTH VOICEEVAC SPEAKER OUTPUT SIGNAL CIRCUITS
CABLES AND STROBE SIGNAL OUTPUTCIRCUITS CABLES OR LOOP
REFER TO 1A AND 1V ABOVE FOR CABLE TYPE
NOTES:1. ALL CABLE SHALL BE INSTALLED PER NEC/CEC PA VOICE CIRCUIT.2. ALL WIRING SHALL CONFORM TO NEC 760 PART A & C FOR A POWER-LIMITED SUPPLY.3. ALL WIRING IN WET LOCATIONS SHALL BE THWN, UL LISTED FOR OUTDOOR USE OR EQUAL.4. ALL FIRE ALARM CABLING SHALL BE RUN IN MINIMUM 3/4" CONDUIT RACEWAY UNLESS OTHERWISE NOTED.
UPGRADE THE FIRE ALARM SYSTEM FOR THE ENTIRE SCHOOL CAMPUS WHICH INCLUDE MULI-PURPOSE,ADMINISTRATION, LIBRARY, CLASSROOM, TOILET FACILITY AND PORTABLE CLASSROOM BUILDINGS.
3CONDUIT PENETRATING FIRE RATED GYPSUM WALLBOARD
1-2 HOUR FIRE RATEDGYPSUM WALL BOARD
S
S
SMOKE AND/OR HEAT DETECTOR
-
+S -
H -
-
+
-
+
COMBINATION AUDIBLE SPEAKER/STROBE UNIT
S +
H +
COMBOAUDIBLE/STROBE
++
--
TO NEXTDEVICE ORE.O.L RESISTOR
FROM CONTROLUNIT ORPREVIOUS DEVICE
TO NEXTDEVICE ORE.O.L RESISTOR
FROM CONTROLUNIT ORPREVIOUS DEVICE
-
+
H -
H +
-
+
-
+
OUTDOOR VOICE EVAC SPEAKER UNIT
AUDIBLETO NEXTDEVICE ORE.O.L RESISTOR
FROM CONTROLUNIT ORPREVIOUS DEVICE
SCOPE OF WORK
6" MIN.12" MAX.
4" MIN.
8'-6"
90" MIN. A.F.F.AUDIBLE DEVICE
96" MAX. A.F.F.VISUAL/AUDIO
VISUAL DEVICETOP OF LENS
80" MIN. A.F.F.VISUAL/AUDIO
VISUAL DEVICEBOTTOM OF LENS
48" MAX. A.F.F.
PROTECTOWIREATTIC SPACE
ACCESSIBLE CEILING CAVITY
T BAR CEILING
WOOD OR METAL STUD
CP 25N/S CAULK
1/4" MINIMUM DIA. BOARD OF 3M FIREBARRIER CP 25N/S CAULK, PER U.L. 1474FIRE TEST OF THROUGH PENETRATION
FIRE STOP.
METALLIC PIPEOR EMT CONDUIT
1-2 HOUR FIRE RATEDGYPSUM WALL BOARD
METALLIC PIPEOR EMT CONDUIT
WOOD OR METAL STUD
CP 25N/S CAULK
1/4" MINIMUM DIA. BOARD OF 3M FIREBARRIER CP 25N/S CAULK, PER U.L. 1474FIRE TEST OF THROUGH PENETRATION FIRE
STOP.
FIRE ALARM SPECIFICATIONS
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
FA001
FIRE ALARMSYMBOLS
CALCULATIONSDETAILS
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2 06/04/18 CCD-2
2
2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
DS DS DSDS DS DS DS DS DS DS DSDS DS DS
DS DS DSDS DS DSDS DS DSDS
DS DS DS DSDS DS DS DS DS
DS DS DS DS DS
DS DS DS
DS DS DS DS
DS DS
DSDS
DS
DS
DS
DS
DSDS DSDS DS DS DS DS DSDS DS DS
DS DS DS DS DS DS DS DSDS DSDS
DS
DS DS
DS DSDS DS DS DS DSDS DS DS
DS DS DS DS DS DS DSDS DS DS
DS DS DSDS DSDS DS DSDS
DS DS DSDS DS
DS DS DSDS DS DSDS
DS DS DS DS DS DS DS DS DS
DS DSDS DSDS DS DS DS DS
DS DS DS DS DS
DS DS DSDS
DH DH
DH
DS DS DS DS
DS
DH DH
DS DSDS DSDS DSDS DSDS DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DSDS
DH DH
DH DH DH
DH
DS DS
DS
DS
DS
DS
DS
DS DS
DS DS
DS DS DS
DH DH DH
DH
J
WP
S
WP
S30cd
AV30cdAV
75cdAV
75cdAV
75cdAV
110cdAV
110cdAV
15cdAV
WP
S15/75cd
AV15cdAV
15cdAV
30cdAV
15cdAV
15cdAV
110cdAV
110cdAV
WP
S75cdAV
75cdAV
75cdAV
WP
S
110cdAV
75cdAV
75cdAV
110cdAV
75cdAV
110cdAV
15cdAV
WP
S110cd
AV75cdAV
110cdAV
75cdAV
75cdAV
WP
S
WP
S15/75cd
AV75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
15/75cdAV
15/75cdAV
15/75cdAV
15/75cdAV
15cdAV
15cdAV
75cdAV
WP
S75cdAV
WP
S15/75cd
AV15/75cd
AV
WP
S
WP
S75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
110cdAV
WP
S
WP
S
WP
S
15cdAV
30cdAV
30cdAV
WP
S
WP
S
WP
S
WP
S
WP
S
WP
S
WP
S
WP
S75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
75cdAV
WP
S75cdAV
WP
S75cdAV
WP
S75cdAV
75cdAV
75cdAV
110cdAV
WP
AV
WP
AV
75cdAV
110cdAV
WP
AV
30cdAV
15cdAV
WP
AV
110cdAV
WP
AV
WP
S
30cdAV
110cdAV
WP
AV
75cdAV
75cdAV
75cdAV
15cdAV
110cdAV
110cdAV
AV110cd
AV110cd
AV15cd
AV15cd
AV110cd
AV110cd
F15cd
AV15cd
AV15cd
AV15cd
AV110cd
AV110cd
F15cd
AV110cd
AV15cd
AV75cd
AV15cd
NONE1RISER DIAGRAM
1
3
2
3
2
2
4
4
3
2
ETS MM
ETSMM
ETS MM
ETS MM
LINEARPROTECTOWIRE
LINEARPROTECTOWIRE
LINEARPROTECTOWIRE
LINEARPROTECTOWIRE
AR AMAR
C01 C02FA
C04FA
C06FA
C08FA
C10FA FA
C11 C12FA
C13FA
C14FA
C15FA
C16FA
C18FA
C20FA
FA FAC23A
FAC23B
FA FA FA FAC30
FA FA FA FA FA FA FA
FA
C32 C34 C36 C38 C39 C40FA
FA
FAC44
FA FAC45
FA FAC47 C48
FA FA FA FA FA FAC51 C52 C55 C56 C59 C60
C64FA FA FA
C67FA
C68FA
C69 C70
D01 D02FA
D03FA FA
D10FA
D08FA
D06FA
D12 D13FA FA FA
D14 D16
D21FA
D17
FA
FA
FA
FA
D04FA
FA
FAD15
FAD19
E01 E02FA
E03FA
E04FA
E05FA
E06FA
E07FA
E08FA
E09FA
E10FA FA
E11 E12FA
E13 E14 E15FA
E16FA
E17FA
E18FA
E19FA FA
FA
FA FA FAE26
FAE27
FAE28
FAE29
FAE30
FA FA FA FA FA FA FA FAE31 E32 E33 E34 E35 E36 E37
FAE21 E22 E23 E24 E25
FA FA
1A
1V 1V
1A
1V
1V
1V
1A
1V
1A 1A 1A
1V
1A1A 1A
B01 B02FA
B03FA
B04FA
B06 B08FA
B10FA
B12FA
B14FA
B16FA
B18FA
B19FA
C22FA FA FA
B28 B30FA FA FA FA FA FA FA FA
FA
FA
B31 B32 B34 B35 B37 B38
B40 B41
FA
B44FA FA
B46FA
B48FA FA FA
B51 B52 B55 B56 B57
B21 B22 B24 B26FA
B39FA
FA
FA FAB27A B27B
A01 A02FA FA
A05FA
A06FA
A08FA
A09FA
A10FA
A12FA
A14 A16FA
FAA28 A30
FA FA FA FA FA FA FA
FA
A32 A33 A35 A36 A37
FAA42
FA
A43FA FA
A45FA
A46 A47FA
A48FA
A49FA FA FA FA
A51 A52 A54 A56 A57
A21 A23 A25
FA
FAA39
FA
FA
FA FAA40 A41
FAA60
FAA61 A64 A65 A68
FA
FA
EOL
FA
V1-02
1A 1A
1V1V
1A
1V
1A 1A 1A
1V
1A
1V
1A
1V
1A
V1-02A V1-03 V1-04 V1-05 V1-06 V1-08 V1-09
1V1V
1A
V2-01
1V
1A
V2-03
1V
1A
V2-04
1V
1A
V2-05
1V
1A
V2-06 V2-07 V2-08 V2-09
1A 1A
V2-10
1V1V 1V 1V1V 1V
1A
V2-11
1V
1A
V2-12
1A
A2-01V3-01
1A 1A
1V1V
1A 1A 1A 1A
1V
1A 2A
A2-02V3-02
A1-03 A2-04V3-04
A2-05V3-05
A2-05AV3-06
A2-07V3-07
A2-08V4-08
1V
1A
1V
1A
1V
1A
A2-11V4-09
1V
1A
A1-12V4-08
1A
A1-14V4-05
1V
1A
1V 1V 1V
A2-03V3-03
A2-06 A2-10V4-11
A2-09
1A1A
1V
EOL EOL
EOL EOLEOL
EOL
CIR. V1
1A
CIR. V2
CIR. V4 CIR. V4
1A
A3-01V1-01
1A 1A
1V
1A
1V
1A 1A 1A
1V
1A
1V
1A
1V
1A
1V
1A
A3-02 A3-04V1-03
A3-05 A3-08V1-06
A3-09V1-07
A3-10V1-08
A3-11V1-09
1A
A3-12V2-01
1A 1A
A3-14V2-06
2V
1A
A3-15V2-05
2V
1A
A3-16V2-04
2V
1A
A3-17V2-03
1A
V2-02
2A
V4-01
1A
V4-02
1A 1A
A3-19DV4-04
1V1V1V
1A EOL
CIR. V1
1A
CIR. A3 A3-03V1-02
1V
A3-06V1-01
A3-07V1-01
1V
A3-13
2V
A3-18
2V
A3-19V2-01
A3-20V1-08
A3-21V3-06
A3-22V3-05
1A1A
A3-23V3-04
1A
A3-24V3-03
1A1A
V3-01
EOLEOL
EOL
1VTO FCPS CIR. V3
1V 1V 1V 1V 1V
2VTO FCPS CIR. V2, V4
A3-19CV4-03
EOL1VCIR. V4
A3-19E
1V1V 1V
EOL
1A 1A 1A
EOL
EOL
1V1V1V1V1V1V1V1V
1A 1A
CIR. A4
CIR. V1
CIR. V2
FACP
NEW NSF2# 3030 WITH VOICE EVAC
DAA-5075
REMOTEANNUN.
CIR. V3
FA
FA
V4-05
2A
V4-06
2A 2A
A3-28V4-07
2A
A3-27A3-26
2V 2V
A3-30A3-29
A3-31
2A
2A/2V
1A
D09
601 6022FA
6032FA
6042FA
P01
P02
FA2
P04
FA2 P03
1V
1A1AA1-02 A1-02
V1-02
FAP01A
V1-01
FAP05 P06
FA
A1-03V1-03
1V
FAP07 P08
FA
A1-05V1-04
FAP09 P10
FA
1AA1-06
V1-051V
FAP11 P12
FA
A1-08V1-06
1V
A1-04 A1-071A1A1A
1V
1V
1AA1-09
V1-01
FAP13
P14
FA2
P16
FA2 P15
FA
A1-10
1V
1AA1-11
V2-01A1-12
FAP17
P18
FA2
P20
FA2 P19
FA
1A
FAP21
P22
FA2
P24
FA2 P23
FA FAP25
P26
FA2
P28
FA2 P27
FA FAP29
P30
FA2
P32
FA2 P31
FA FAP33
P34
FA2
P36
FA2 P35
FA FAP37
P38
FA2
P40
FA2 P39
FA FAP41
P42
FA2
P44
FA2 P43
FA
FA
A1-13V2-02
1AA1-15
1AA1-18
1AA1-21
1A 1A 1A 1A 1AA1-14
V2-03A1-16
V2-04A1-17
V2-05A1-19
V2-06A1-20
V2-07
EOLEOLEOL
1A
1V
1V 1V 1V 1V 1V
FA
FA
FA
FAFA
FA
FA
A3-19A A3-19B
A1-09AV1-08A
A1-09BV1-08B
2V2A
2V 2A
2W110cd
2V 2A
2W
1A 1A 1A 2W2W 2W 2W
2V 2A
A1-13AV4-074W
110cd
1V
A1-13V4-06
1V
A1-03AV3-03A
2V 2A
A1-03BV3-03B
2V2A
2W110cd
2WA1-15
V4-04
A1-15AV4-03
2V 2A
1A
1V 2A
2W110cd
A1-16V4-02
A1-17V4-01
2V 2A
A1-11AV4-102W
110cd
A2-09
EOL
EOL
V1-01A4-01 A4-17
V2-01V2-02A4-16
V2-03V2-04A4-15
V2-05A4-13V2-07 V1-06
A4-14A4-11 A4-12V2-08V1-10
A4-08V1-09V1-08
A4-07V1-07A4-06
V1-06A4-05A4-04
V1-05V1-04A4-03
V1-03A4-02
V1-02
2V2A
A4-05AV1-06A
A4-081A 1A
V2-09A4-12A
1A1A
A4-16A
2W 2W 1/8W 2W 2W4W
2W 2W 2W 2W 2W4W4W4W
1/8W 1/8W1/8W 1/8W
1/8W 1/8W1/8W
1/8W 1/4W
1/8W 1/8W 2W 2W
1/4W 4W 4W
4W
FA
FA
2V2A
2W2WA1-16A
V1-08AA1-16B
V2-08B
2W 2W
A1-02 A1-02A A1-15A A1-22A1-21A1-20A1-19A1-18A1-17A1-16A1-15A1-14A1-13A1-12A1-11A1-10A1-09A1-08A1-06A1-05A1-04A1-03
1/8W1/4W 1/8W 1/4W 1/8W1/8W1/4W1/4W 1/4W 2W 2W 2W 2W 2W
1/4W
1/8W
2W
FA
FA FA
2W2W2W2W
2W
2W
A3-25
2FA
2FA
C24 C28C25 C29 D11
1A
FA
T
FA
1A 1A1A
CIR. V1
CIR. V2
FA
A1-07
2W 1/2W 2W2W
1/2W 1/2W1W 1W 1W
1/2W
A1-20AV2-11A
2A2V
1/8W2V2A
A1-20BV2-11B
1/8W2V2A
A1-20BV2-11B
1/8W
A66FA
A67FA
A67AFA FA
FAC22 C23 C26
FA2FA2E12A E12B
E28BE28A 2FA2FA E32A2FA
A1-01V1-01
1V
1A
1V
1A1/8W
A3-08AV1-06A
1/2W
1V 1A
A3-11AV1-09A
1/2W
1V 1A
E12DFA2
E12CTYPE 1 EXH HOOD ANSUL SYSTEM
CLASSROOM BUILDING "3" CLASSROOM BUILDING "4"
CLASSROOM BUILDING "5"
CLASSROOM BUILDING "2"
CLASSROOM BUILDING "1"
NOTIFICATION SIGNAL CIR. 1
NOTIF
ICAT
ION
SIGN
AL C
IR. 2
FCPS-24
DAA-5025
FCPS-24
DAA-5025
FCPS-24
NOTIF
ICAT
ION
ALAR
M CI
R. A
1
NOTIF
ICAT
ION
ALAR
M CI
R. A
2
FIRE ALARM CONTROL PANEL CONNECT TOEXISTING NEAREST 120V PANEL (EACH ON ITSOWN DEDICATED SEPARTE CIRCUIT)
FIRE ALARM CONTROL PANEL CONNECTTO EXISTING NEAREST 120V PANEL (EACHON ITS OWN DEDICATED SEPARTECIRCUIT)
FIRE ALARM CONTROL PANEL CONNECTTO EXISTING NEAREST 120V PANEL (EACHON ITS OWN DEDICATED SEPARTECIRCUIT)
RESTROOM BUILDING "6"
PORT. C.R. 29 PORT. C.R. 27,28 PORT. C.R. 25,26 PORT. C.R. 30 PORT. C.R. 31 PORT. C.R. 32 PORT. C.R. 33 PORT. C.R. 34 PORT. C.R. 35 PORT. C.R. 36 PORT. C.R. 36FCPS-24
DAA-5025
FIRE ALARM CONTROL PANEL CONNECTTO EXISTING NEAREST 120V PANEL (EACHON ITS OWN DEDICATED SEPARTECIRCUIT)
NOTIF
ICAT
ION
SIGN
AL C
IR. 3
NOTIF
ICAT
ION
SIGN
AL C
IR. 4
3/4"C.,4-PAIR PHONE CABLE (2 OUTSIDE PHONE LINE)CONNECTED TO SCHOOL CAMPUS TELEPHONETERMINAL PUNCH HANDELING THE TELEPHONECOMPANY PHONE SERVICE.
NOTIF
ICAT
ION
SIGN
AL C
IR. 4
REFERENCE NOTES1
2
3
4
FIRE ALARM NOTES1. CONTRACTOR SHALL MAINTAIN A MINIMUN 3'-0"
DISTANCE BETWEEN THE SMOKE DETECTORSHALL HVAC SUPPLY AIR DIFFUSER.
2. DUE TO MAINTENANCE PURPOSES ANDACCESS TO THE ATTIC SPACE PROTECTOWIRELINEAR HEAT DETECTOR SHALL BE USED INTHE ATTIC SPACE IN LIEU OF HEAT DETECTORDEVICES.
FACP (NOTIFIER NSF2 #3030 WITH OICE EVAC)FURNISHED AND INSTALLED UNDER THISCONTRACT
NEW NOTIFIER FCPS-24 AND TERMINALCABINETS
NEW NOTIFIER DAA-5025 INTELLIGENT AUDIOTRANSPONDER POWER SUPPLY
EXISTING PULL BOX AT BUILDING SEE SITE PLANE-135.
FOR CONNECTION OF FA EQUIPMENTCONTRACTOR SHALL PROVIDE 1/2"C.,2#12 ANDCONNECT TO NEAREST 120 VOLT PANEL (SPARE20A,1P DEDICATED CIRCUIT) SERVING THESPACE OR AREA.
5
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
FA002
FIRE ALARMRISER DIAGRAM
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2 06/04/18 CCD-2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
FACP BATTERY CALCULATION (ADMIN BUILDING "1")QTY DESCRIPTION SUP. SUP CURRENT ALARM ALARM
CURENT
1 MAIN CIRCUIT BOARD 0.120000 0.120000 0.170000 0.170000
1 DACT-UD2 0.100000 0.100000 0.132000 0.132000
1 SLC-2LS EXPENDER MODULE 0.085000 0.085000 0.085000 0.085000
0 4XMTF 0.120000 0.120000 0.170000 0.170000
1 IPDACT-2 0.120000 0.120000 0.170000 0.170000
0 IPDATC-2/2UD 0.120000 0.120000 0.170000 0.170000
ANN-BUS DEVICES
1 ANN-80(-W) 0.015000 0.015000 0.040000 0.040000
1 ANN-LED 0.028000 0.000000 0.088000 0.000000
1 ANN-RLED 0.028000 0.000000 0.088000 0.000000
0 ANN-RLY 0.015000 0.000000 0.075000 0.000000
1 ANN-1/0 0.035000 0.000000 0.200000 0.170000
0 ANN-6/PG 0.045000 0.000000 0.045000 0.000000
ACB ANNUNCIATORS
0 ACM-8RF 0.030000 0.000000 0.158000 0.000000
0 ACM-16ATF 0.040000 0.000000 0.056000 0.000000
0 ACM-32AF 0.040000 0.000000 0.056000 0.000000
0 AEM-16ATF 0.002000 0.000000 0.018000 0.000000
0 AEM-32AF 0.002000 0.000000 0.018000 0.000000
0 AFM-16ATF 0.040000 0.000000 0.056000 0.000000
0 AFM-32AF 0.040000 0.000000 0.056000 0.000000
0 AFM-16AF 0.025000 0.000000 0.065000 0.000000
0 LDM-32F 0.040000 0.000000 0.056000 0.000000
0 LDM-32F 0.002000 0.000000 0.018000 0.000000
0 LCD-80F 0.025000 0.000000 0.064000 0.000000
RESETTABLE POWER
0 4-WIRE DETECTOR HEADS 0.000000 0.000000 0.000000 0.000000
ADDRESSABLE DEVICES
BEAM355 0.002000 0.000000 0.000000
BEAM3669 0.002000 0.000000 0.000000
BEAM1224 0.017000 0.000000 0.000000
CP355 0.000300 0.000000 0.000000
187 SMOKE DETECTOR FST-851A 0.000300 0.056100 0.056100
SD355T 0.000300 0.000000 0.000000
AD355 0.000300 0.000000 0.000000
28 HEAT DETECTOR FST-851 0.000300 0.008400 0.008400
H356R 0.000300 0.000000 0.000000
H356HT 0.000300 0.000000 0.000000
D360P 0.000300 0.000000 0.000000
D360RP 0.000300 0.000000 0.000000
D360PL 0.000300 0.000000 0.000000
D360RPL 0.000300 0.000000 0.000000
D365PL 0.000300 0.000000 0.000000
8 MM LINAIR DETECTOR 0.000400 0.003200 0.003200
1 FMM-1 MODULE 0.003500 0.003500 0.003500
2 FCM-1 CONTROL MODULE 0.000750 0.001500 0.001500
MMF-301 0.000375 0.000000 0.000000
MMF-302 0.000270 0.000000 0.000000
MMF-302-G 0.002000 0.000000 0.000000
10 PULL STATIONS NBG-12LX 0.000230 0.002300 0.002300
CMF-300 0.000390 0.003900 0.000000
CMF-300-6 0.002250 0.000000 0.000000
CRF-300 0.000270 0.000000 0.000000
CRF-300-6 0.001450 0.000000 0.000000
B00 0.000400 0.000000 0.000000
B501BH-2 0.001000 0.000000 0.000000
B501BHT-2 0.001000 0.000000 0.000000
B224RB 0.000500 0.000000 0.000000
B224BI 0.000450 0.000000 0.000000
B200SR 0.000500 0.000000 0.000000
1 MAXIMUM ALARM DRAW FOR ADDRESSABLE DEVICE (SLC 1) 0.400000 0.400000
1 MAXIMUM ALARM DRAW FOR ADDRESSABLE DEVICE (SLC 2) 0.400000 0.400000
EOLR 0.020000 0.000000 0.020000 0.000000
MISCELLANEOUS DEVICE 1 0.000000 0.000000 0.000000 0.000000
MISCELLANEOUS DEVICE 2 0.000000 0.000000 0.000000 0.000000
MISCELLANEOUS DEVICE 3 0.000000 0.000000 0.000000 0.000000
MISCELLANEOUS DEVICE 4 0.000000 0.000000 0.000000 0.000000
1 NAC #1 0.000000 0.723000 0.000000
1 NAC #2 0.000000 0.306000 0.000000
1 NAC #3 0.000000 1.377000 0.000000
1 NAC #4 0.000000 0.630000 0.000000
TOTAL SUP: 0.758900 TOTAL ALARM 1.982000
SUPERVISORY CURRET: TOTAL SUP X24 (#HRS) = 18.213600 AMP/HRS
ALARM CURRENT X 15/60 (HRS OF ALARM) = 0.476750 AMP/HRS
BATTERY CAPACITY REQUIRED = 18.690350 AMP/HRS
PLUS (+) 30% DERATING FACTOR = 5.607105
TOTAL SECONDARY REQUIRED = 24.297455
BATTERIES PROVIDED WITH CHARGING SYSTEM = 62.780883 (2 PCS)
AVAILABLE SPARE = 38.483428
ECC-50/100 BATTERY CALCULATION (ADMIN BUILDING"1")
QTY DESCRIPTION SUP. SUPCURRENT ALARM ARLARM
CURENT
1 ECC-5/100 PRIMARY CONSOLE 0.272000 0.272000 0.446000 0.446000
1 ECC-50W-25/70V 0.100000 0.000000 0.235000 0.235000
0 ECC-50W-25/70V (AS BACKUP) 0.100000 0.000000 0.000000 0.000000
0 ECC-CE6 CIRCUIT EXPENDER 0.200000 0.000000 0.169000 0.000000
0 ECC-RTZM 0.055000 0.000000 0.060000 0.000000
0 ECC-FFT FIREFIGHTER TELEPHONE 0.120000 0.000000 0.230000 0.000000
0 2. OPERATOR INTERFACE DEVICES
0 ECC-LOC LOCAL OPERATOR CONSOLE 0.085000 0.000000 0.100000 0.000000
0 ECC-RM REMOTE MICROPHONE 0.050000 0.000000 0.064000 0.000000
0 ECC-RPU REMOTE PAGE UNIT 0.050000 0.000000 0.068000 0.000000
0 3. ADDITIONAL AMPLIFIERS
0 ECC-50DA 0.012000 0.000000 0.012000 0.000000
0 ECC-125DA 0.012000 0.000000 0.012000 0.000000
0 ECC-50DBDA 0.012000 0.000000 0.012000 0.000000
0 4. SPEAKERS
0 SPEAKER (4W) 0.000000 0.000000 0.057000 0.000000
24 SPEAKER (2W) 0.000000 0.000000 0.028600 0.686400
14 SPEAKER (1W) 0.000000 0.000000 0.014300 0.200200
2 SPEAKER (1/2W) 0.000000 0.000000 0.007100 0.014200
3 SPEAKER (1/4W) 0.000000 0.000000 0.003570 0.010710
6 SPEAKER (1/8W) 0.000000 0.000000 0.001780 0.010680
CUSTOM WATT DESCRIPTION 0.000000 0.000000 0.000000 0.000000
TOTAL WATTS 1.068000
6 OUTPUT CIRCUITS
0 NAC OUTPUT 0.000000 0.000000 0.000000 0.000000
0 NON-RESETTABLE OUTPUT 0.000000 0.000000 0.000000 0.000000
6. ADDTITIONAL DEVICES
0 POWER SUPERVISION RELAYS 0.025000 0.000000 0.025000 0.000000
0 SP-SVC VOLUME CONTROL 0.010000 0.000000 0.010000 0.000000
TOTAL SUP: 0.272000 TOTAL ALARM 1.6032
SUPERVISORY CURRET: TOTAL SUP X24 (#HRS) = 6.528000 AMP/HRS
ALARM CURRENT X 15/60 (HRS OF ALARM) = 0.400797 AMP/HRS
BATTERY CAPACITY REQUIRED = 6.928798 AMP/HRS
PLUS (+) 30% DERATING FACTOR = 2.078639
TOTAL SECONDARY REQUIRED = 9.007437
BATTERIES PROVIDED WITH CHARGING SYSTEM = 55.000000 (2 PCS)
AVAILABLE SPARE = 45.992563
WORSE CASE VOLTAGE DROPCALCULATION BLDG #3
VISUAL CIRCUIT #50 AUDIO/VISUAL DEVICE (115cd) @ 0.2170 A = 0.0000 A0 AUDIO/VISUAL DEVICE (110cd) @ 0.1630 A = 0.0000 A
10 AUDIO/VISUAL DEVICE (75cd) @ 0.1170 A = 1.1700 A0 AUDIO/VISUAL DEVICE (30cd) @ 0.0910 A = 0.0000 A1 VISUAL DEVICE (15cd) @ 0.0300 A = 0.0300 A
TOTAL = 1.2000 A
1.2000 A X 290 X 21.50= 1.1458 VD6,530 (#12)
1.15 A X 100 = 4.7741 VD%24 V
FCPS-24 BATTERY CALCULATIONBUILDING #3
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
115CD STROBE 0 0.0000 0.2170 0.0000 A 0.0000 A110CD STROBE 0 0.0000 0.1630 0.0000 A 0.0000 A75CD STROBE 14 0.0000 0.1170 0.0000 A 1.6380 A30CD STROBE 3 0.0000 0.0910 0.0000 A 0.2730 A
15/75CD STROBE 8 0.0000 0.1170 0.0000 A 0.9360 A15CD STROBE 3 0.0000 0.0300 0.0000 A 0.0900 A
CONTROL PANEL 1 0.3850 6.0000 0.3850 A 6.0000 ATOTAL STANDBY CURRENT = 0.3850 A 8.9370 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM8.9370 A X 15/60 = 2.2343 AMP HR.
STANDBY CURRENT x 24 HRS = AMP/HR FOR ALARM0.3850 A X 24 = 9.2400 AMP HR.
BATTERY SIZE = 12 AMP HR.
WORST CASE VOLTAGE DROP % CALCULATION FORBUILDING #5
PANEL ECC WIRE GAUGE 16
CIRCUIT NO. 0.515720 AREA CIR. MILL 2580
SYSTEM VOLTAGE 70 DC RESISTANCEOHM/FT 5.2900
DISTANCE IN FEET 466
ALARM TOTAL
MODEL NUMBER DESCRIPTION QTY CURRENT CURRENT
SYSTEM SENSOR SPSR SPEAKER (4W) 4 0.057000 0.228000
SYSTEM SENSOR SPSR SPEAKER (2W) 9 0.028600 0.257400
SYSTEM SENSOR SPRK SPEAKER (1W) 1 0.014300 0.014300
SYSTEM SENSOR SPRK SPEAKER (1/2W) 0 0.007100 0.000000
SYSTEM SENSOR SPRK SPEAKER (1/4W) 0 0.003570 0.000000
SYSTEM SENSOR SPRK SPEAKER (1/8W) 9 0.001780 0.016020
CIRCUIT TOTAL CURRENT 0.5157
RESISTANCE OPERATING VOLTAGE %VOLTAGE
(OHMS) VOLTS DROP DROP
4.9303 70 2.5426 3.6323
NOTE: % VOLTAGE FROP SHALL NOT EXCEED 10%
RESISTANCE (2 X DISTANCE IN FEET X WIRE RESISTANCE IN OHMS) / (1000)
DROPPEDVOLTAGE = (CURRENT X RESISTANCE)
% VOLTAGEDROP (SYSTEM VOLTAGE/DROPPED VOLTAGE) X 100
WORST CASE VOLTAGE DROP % CALCULATION FORPORTABLE BUILDING #29
PANEL ECC WIRE GAUGE 14
CIRCUIT NO. 0.414700 AREA CIR. MILL 2580
SYSTEM VOLTAGE 70 DC RESISTANCEOHM/FT 3.2600
DISTANCE IN FEET 1243
ALARM TOTAL
MODEL NUMBER DESCRIPTION QTY CURRENT CURRENT
SYSTEM SENSOR SPSR SPEAKER (4W) 0 0.057000 0.000000
SYSTEM SENSOR SPSR SPEAKER (2W) 8 0.028600 0.228800
SYSTEM SENSOR SPRK SPEAKER (1W) 13 0.014300 0.185900
SYSTEM SENSOR SPRK SPEAKER (1/2W) 0 0.007100 0.000000
SYSTEM SENSOR SPRK SPEAKER (1/4W) 0 0.003570 0.000000
SYSTEM SENSOR SPRK SPEAKER (1/8W) 0 0.001780 0.000000
CIRCUIT TOTAL CURRENT 0.4147
RESISTANCE OPERATING VOLTAGE %VOLTAGE
(OHMS) VOLTS DROP DROP
8.1044 70 3.3609 4.8013
NOTE: % VOLTAGE FROP SHALL NOT EXCEED 10%
RESISTANCE (2 X DISTANCE IN FEET X WIRE RESISTANCE IN OHMS) / (1000)
DROPPEDVOLTAGE = (CURRENT X RESISTANCE)
% VOLTAGEDROP (SYSTEM VOLTAGE/DROPPED VOLTAGE) X 100
WORST CASE VOLTAGE DROP % CALCULATION FORBUILDING #3
PANEL ECC WIRE GAUGE 12
CIRCUIT NO. 0.583780 AREA CIR. MILL 6530
SYSTEM VOLTAGE 70 DC RESISTANCEOHM/FT 2.0500
DISTANCE IN FEET 1310
ALARM TOTAL
MODEL NUMBER DESCRIPTION QTY CURRENT CURRENT
SYSTEM SENSOR SPSR SPEAKER (4W) 3 0.057000 0.171000
SYSTEM SENSOR SPSR SPEAKER (2W) 4 0.028600 0.114400
SYSTEM SENSOR SPRK SPEAKER (1W) 19 0.014300 0.271700
SYSTEM SENSOR SPRK SPEAKER (1/2W) 2 0.007100 0.014200
SYSTEM SENSOR SPRK SPEAKER (1/4W) 2 0.003570 0.007140
SYSTEM SENSOR SPRK SPEAKER (1/8W) 3 0.001780 0.005340
CIRCUIT TOTAL CURRENT 0.5838
RESISTANCE OPERATING VOLTAGE %VOLTAGE
(OHMS) VOLTS DROP DROP
5.3710 70 3.1355 4.4793
NOTE: % VOLTAGE FROP SHALL NOT EXCEED 10%
RESISTANCE (2 X DISTANCE IN FEET X WIRE RESISTANCE IN OHMS) / (1000)
DROPPEDVOLTAGE = (CURRENT X RESISTANCE)
% VOLTAGEDROP (SYSTEM VOLTAGE/DROPPED VOLTAGE) X 100
WORST CASE VOLTAGE DROP % CALCULATION FORBUILDING #2
PANEL ECC WIRE GAUGE 16
CIRCUIT NO. 0.512950 AREA CIR. MILL 2580
SYSTEM VOLTAGE 70 DC RESISTANCEOHM/FT 5.2900
DISTANCE IN FEET 769
ALARM TOTAL
MODEL NUMBER DESCRIPTION QTY CURRENT CURRENT
SYSTEM SENSOR SPSR SPEAKER (4W) 0 0.057000 0.000000
SYSTEM SENSOR SPSR SPEAKER (2W) 14 0.028600 0.400400
SYSTEM SENSOR SPRK SPEAKER (1W) 7 0.014300 0.100100
SYSTEM SENSOR SPRK SPEAKER (1/2W) 1 0.007100 0.007100
SYSTEM SENSOR SPRK SPEAKER (1/4W) 1 0.003570 0.003570
SYSTEM SENSOR SPRK SPEAKER (1/8W) 1 0.001780 0.001780
CIRCUIT TOTAL CURRENT 0.5129
RESISTANCE OPERATING VOLTAGE %VOLTAGE
(OHMS) VOLTS DROP DROP
8.1360 70 4.1734 5.9620
NOTE: % VOLTAGE FROP SHALL NOT EXCEED 10%
RESISTANCE (2 X DISTANCE IN FEET X WIRE RESISTANCE IN OHMS) / (1000)
DROPPEDVOLTAGE = (CURRENT X RESISTANCE)
% VOLTAGEDROP (SYSTEM VOLTAGE/DROPPED VOLTAGE) X 100
FCPS-24 BATTERY CALCULATIONBUILDING #1
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
EXTERIOR SPEAKER 6 0.0000 0.0690 0.0000 A 0.4140 A115CD STROBE 24 0.0000 0.2170 0.0000 A 5.2080 A110CD STROBE 1 0.0000 0.1630 0.0000 A 0.1630 A75CD STROBE 4 0.0000 0.1170 0.0000 A 0.4680 A30CD STROBE 3 0.0000 0.0910 0.0000 A 0.2730 A15CD STROBE 2 0.0000 0.0670 0.0000 A 0.1340 A15CD STROBE 8 0.0000 0.0300 0.0001 A 0.2400 A
SMOKE/HEATMODULE 26 0.0000 0.0065 0.0001 A 0.1690 A
CONTROL PANEL 1 0.3850 6.0000 0.3850 A 6.0000 ATOTAL STANDBY CURRENT = 0.3852 A 13.0690 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM13.0690 A X 15/60 = 3.2672 AMP HR.
STANDBY CURRENT x 24 HRS = AMP/HR FOR ALARM0.3852 A X 24 = 9.2437 AMP HR.
BATTERY SIZE = 12 AMP HR.
DAA-5075 BATTERY CALCULATIONFOR BUILDING #5
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
SPEAKER (4W) 4 0.0000 0.0570 0.0000 A 0.2280 ASPEAKER (2W) 9 0.0000 0.0286 0.0000 A 0.2574 ASPEAKER (1W) 1 0.0000 0.0143 0.0000 A 0.0143 A
SPEAKER (1/2W) 0 0.0000 0.0071 0.0000 A 0.0000 ASPEAKER (1/4W) 0 0.0000 0.0036 0.0000 A 0.0000 ASPEAKER (1/8W) 9 0.0000 0.0018 0.0000 A 0.0162 A
0.0000 A 0.5159 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM0.5159 A X 15/60 = 0.1290 AMP HR.
BATTERY SIZE = 7 AMP HR.
DAA-5075 BATTERY CALCULATIONFOR BUILDING #3
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
SPEAKER (4W) 3 0.0000 0.0570 0.0000 A 0.1710 ASPEAKER (2W) 4 0.0000 0.0286 0.0000 A 0.1144 ASPEAKER (1W) 19 0.0000 0.0143 0.0000 A 0.2717 A
SPEAKER (1/2W) 2 0.0000 0.0071 0.0000 A 0.0142 ASPEAKER (1/4W) 2 0.0000 0.0036 0.0000 A 0.0072 ASPEAKER (1/8W) 3 0.0000 0.0018 0.0000 A 0.0054 A
0.0000 A 0.5839 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM0.5839 A X 15/60 = 0.1460 AMP HR.
BATTERY SIZE = 7 AMP HR.
DAA-5075 BATTERY CALCULATIONFOR PORTABLE BUILDING #29
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
SPEAKER (4W) 0 0.0000 0.0570 0.0000 A 0.0000 ASPEAKER (2W) 8 0.0000 0.0286 0.0000 A 0.2288 ASPEAKER (1W) 13 0.0000 0.0143 0.0000 A 0.1859 A
SPEAKER (1/2W) 0 0.0000 0.0071 0.0000 A 0.0000 ASPEAKER (1/4W) 0 0.0000 0.0036 0.0000 A 0.0000 ASPEAKER (1/8W) 0 0.0000 0.0018 0.0000 A 0.0000 A
0.0000 A 0.4147 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM0.4147 A X 15/60 = 0.1037 AMP HR.
BATTERY SIZE = 7 AMP HR.
FCPS-24 BATTERY CALCULATIONBUILDING #5
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
115CD STROBE 0 0.0000 0.2170 0.0000 A 0.0000 A110CD STROBE 9 0.0000 0.1630 0.0000 A 1.4670 A75CD STROBE 1 0.0000 0.1170 0.0000 A 0.1170 A30CD STROBE 0 0.0000 0.0910 0.0000 A 0.0000 A
15/75CD STROBE 0 0.0000 0.1170 0.0000 A 0.0000 A15CD STROBE 9 0.0000 0.0300 0.0000 A 0.2700 A
CONTROL PANEL 1 0.3850 6.0000 0.3850 A 6.0000 ATOTAL STANDBY CURRENT = 0.3850 A 7.8540 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM7.8540 A X 15/60 = 1.9635 AMP HR.
STANDBY CURRENT x 24 HRS = AMP/HR FOR ALARM0.3850 A X 24 = 9.2400 AMP HR.
BATTERY SIZE = 12 AMP HR.
WORSE CASE VOLTAGE DROPCALCULATION BLDG #5
VISUAL CIRCUIT #50 AUDIO/VISUAL DEVICE (115cd) @ 0.2170 A = 0.0000 A3 AUDIO/VISUAL DEVICE (110cd) @ 0.1630 A = 0.4890 A1 AUDIO/VISUAL DEVICE (75cd) @ 0.1170 A = 0.1170 A0 AUDIO/VISUAL DEVICE (30cd) @ 0.0910 A = 0.0000 A5 VISUAL DEVICE (15cd) @ 0.0300 A = 0.1500 A
TOTAL = 0.7560 A
0.7560 A X 290 X 21.50= 0.7218 VD6,530 (#12)
0.72 A X 100 = 3.0077 VD%24 V
FCPS-24 BATTERY CALCULATIONPORTABLE BUILDING #29
DEVICE QTY. CURRENTSTANDBY (A)
CURRENTALARM (A)
TOTALSTANDBY (A)
TOTALALARM (A)
115CD STROBE 0 0.0000 0.2170 0.0000 A 0.0000 A110CD STROBE 0 0.0000 0.1630 0.0000 A 0.0000 A75CD STROBE 13 0.0000 0.1170 0.0000 A 1.5210 A30CD STROBE 0 0.0000 0.0910 0.0000 A 0.0000 A
15/75CD STROBE 0 0.0000 0.1170 0.0000 A 0.0000 A15CD STROBE 0 0.0000 0.0300 0.0000 A 0.0000 A
CONTROL PANEL 1 0.3850 6.0000 0.3850 A 6.0000 ATOTAL STANDBY CURRENT = 0.3850 A 7.5210 A
ALARM X ALARM TIME / 60 = AMP/HR FOR ALARM7.5210 A X 15/60 = 1.8803 AMP HR.
STANDBY CURRENT x 24 HRS = AMP/HR FOR ALARM0.3850 A X 24 = 9.2400 AMP HR.
BATTERY SIZE = 12 AMP HR.
WORSE CASE VOLTAGE DROPCALC. PORTABLE BLDG #29
VISUAL CIRCUIT #50 AUDIO/VISUAL DEVICE (115cd) @ 0.2170 A = 0.0000 A3 AUDIO/VISUAL DEVICE (110cd) @ 0.1630 A = 0.4890 A1 AUDIO/VISUAL DEVICE (75cd) @ 0.1170 A = 0.1170 A0 AUDIO/VISUAL DEVICE (30cd) @ 0.0910 A = 0.0000 A5 VISUAL DEVICE (15cd) @ 0.0300 A = 0.1500 A
TOTAL = 0.7560 A
0.7560 A X 290 X 21.50= 0.7218 VD6,530 (#12)
0.72 A X 100 = 3.0077 VD%24 V
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
KEYNOTES
GENERAL NOTES
KEYPLAN
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
KEYPLAN
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
FA003
FIRE ALARMCALCULATIONS
Checker10/23/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
2 06/04/18 CCD-2
2
2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019
DSDS
DSDS
DSDS
DSDS
DS
DS
DS
DS
DS
DS
DS
MM ETS
75cd AV
75cdAV
WPS
15cdAV
15cdAV
PROTECTOWIRE LINEAR HEAT DETECTOR(TYPICAL)
V4-01
V4-02
A3-19E
D01
D02 D03 D08
D04 D06
D10 D11
D12
D15
D16D17
D09
D21 D19
D13D14
A3-19A
A3-19B
EOLV4-04A3-19D
V4-03A3-19C
2W1/8W
1/8W
2W
2W
TO CLASSROOM BUILDING 3.PROVIDE AND RUN NEW FACABLING IN NEW 1-1/4"C.
EXISTINGWEATHERPROOF6"SQ. PULL BOX
FA
FA
FA
FA
FA FA
FA
FAFAFA
FA
FA
FAFA
FA
FA
FA
2A/1V
2A/1V 2A
/1V
2A/1V
2A/1V
FA
FA FA
FA
FA
DS
DS
DS
DS DS
DS
DS
DS
DS
DSDS
DS DSDS
DH
DH
DS
DS
DS
DS
DH
DH
DS
DS
DS AM
DSDHDH
DH
DH
DH DH
DH
AV110cd
AV110cd AV
15cdF
15cd
AV110cd AV110cd
F15cd
AV110cd
AV15cd
AV 15cd
AV15cd
AV75cd
AV 110cd
AV110cd
AV15cd
AV15cd
AV15cd
WPS
WP S
WPS
WPS110cdAV
30cdAV
5
NEW HOODTYPE 1 INKITCHEN AREA.
NEW NOTIFIER DAA-5025 INTELLIGENT AUDIOTRANSPONDER POWER SUPPLY ANDFAPS-24 POWER SUPPLY CABINETS.
NEW TYPE 1 HOOD ANSUL SYSTEM PROVIDE ANDCONNECT TP ANSUL SYSTEM SNAP SWITCH FAMONITORING AND CONTROL RELAYS (RELAY SHUTDOWN RECEPTACLES BELOW HOOD WITH 120V 2PCONTROL RELAY TO INTERCONNECT 120V BRANCHCIRCUITRY).
CONTROL RELAY SHALL BE PROGRAM WITH AREASMOKE DETECTOR FOR HVAC SHUT DOWN.
A4-17 V2-01
A4-01V1-01
A4-02V1-03
A4-04
V1-05
V2-02
V2-03
A4-15V2-04
A4-14
V2-05A4-12V2-08
A4-13V2-07
A4-03V1-04
V1-02
A4-05V1-06
A4-06V1-07 A4-07
V1-08A4-08V1-10
A1-11
V2-09
E01 E02 E03
E04
E05
E06
E07
E08
E09
E10 E11
E12C
E13
E14
E15
E16
E18
E19E21
E22
E24E23
E33
E35E34
E36
E37
E25
E26
E27E29E31
A4-16
V2-06
EOL
EOL
A4-12A
A4-06A
A4-03A
A4-16A
A4-16B
MECH RM5119
2W
2W
2W
2W
1/8W
1/8W
4W
2W
2W
2W
4W
4W
2W
EOL
1/8W
2W
1/8W
1/8W
1/8W
4W
1/8W
A4-05AV1-06A
1/2W
E12A
E12B
E12
E12D
FA
FA
FAFA
FA
FA
FA FA
FA
FA
FA
FA
FAFAFAFA
FA
FA
FA
FA
FAFA FA
FAFA
FA
2FA
2FA
FAFA
2FA1A
1A/1V 1A/1V
1A/1V
1A/1V
1A/1V
1A/1V
2A
1A/1V
2A
1A/1V
1A/1V
1A/1V
1A/1V
2A
2A/2V
1A/1V
1A/1V
1V
1A/1V
1A/1V
1A/1V
2FA 2F
A
2FA
1A/1V
FA
FA
2FA
FAFA
FA
2FA
2FA
2FA
2FA
FA
FA
470LF
AR
AR
WEATHERPROOF VOICE EVAC. SPEAKER AT 10'-0"A.F.F.
FIRE ALARM DEVICES AT RESTROOMS SHALL HAVEVANDAL RESISTANT GUARDS.
PROVIDE STUDENT GUARD ON MANUAL PULLSTATION.
FOR HVAC EQUIPMENT FAN SHUT-DOWN (VIA AREASMOKE DETECTOR), CONTRACTOR SHALL CONTROLRELAY MODULAR AT LIBRARY HVAC EQUIPMENT ACUNIT (CONTROL PANEL). CONTROL RELAY SHALL BEPROGRAM TO SHUT-DOWN UNIT DURING ALARMCONDITION AND THE AREA SMOKE DETECTORSSERVING THE LIBRARY SHALL BE PROGRAM TOACTIVATE THE CONTROL RELAY. CONTRACTOR SHALLPROVIDE (1/2"C.2#14 CONTROL WIRES) ANDCONNECT RELAY FROM C CONTACT TO THESHUT-DOWN CONTROL POINTS OF THE HVACEQUIPMENT CONTROL PANEL.
REFERENCE NOTES:
4
3
2
1
A
A
A
A
TYP FOR ENTIREBUILDING EXTERIOR
A
A
B
B
L
L
TYPOF 2
CLASSROOM4101
CLASSROOM4103
ALL GENDERRESTROOM
4102
ALL GENDERRESTROOM
4104
STORAGE4105
TYP FOR ENTIREBUILDING EXTERIOR
PATCH & REPAIR (E)PLASTER WALLS. PREPFOR NEW PAINTFINISH
(N) WOOD FRAMED CEILING @ 9'-0" A.F.F.W/ GYP. BD. FINISH. PAINT. PROVIDE (N)SURFACE-MOUNTED LED LIGHT FIXTURE
LOBBY5100
ALL GENDERRESTROOM
5101
ALL GENDERRESTROOM
5102
AUDITORIUM5103
STAGE5108
STORAGE5107
VESTIBULE5105
ALL GENDERRESTROOM
5106
VESTIBULE5104
STORAGE5109
VESTIBULE5111
ALL GENDERRESTROOM
5110
VESTIBULE5112
CAFETERIA5113
KITCHEN5115
LOUNGE5114
W.H5116
ALL GENDERRESTROOM
5118
OFFICE/STORAGE5117
LPV626 714-7506 FAX 626 714-7512
Pasadena, California 91103751 N. Fair Oaks Ave. Suite 201
AMPE, INC.A
EXP. 09-2019
T
RI CALEL ECT
TAMENAH RETSOFWEH
E
CA L I F ORNI A
S T A T E OF
FORPDERETSIGER REEN
IGNE
LANOISS
E-21308S
0
Long BeachUnified
School District
Clie
ntCo
n sul
tant
Proj
ect
PTN No.:
2425 Webster AvenueLong Beach, CA 90810
She e
t Titl
eSh
e et N
o.Sh
e et I
nfo
DATE:CHECKED BY:
SCALE:
JOB No.:
Issu e
Age n
cy A
ppro
val
AC
DIV. OF THE STATE ARCHITECTIDENTIFICATION STAMP
OFFICE OF REGULATION SERVICES
DATE
FILE NO:A#:
FLS SS
REV. DATE DESCRIPTION
AB
2
3
Arch
itect
Sta m
ps
1
5
4
Scal
eG
raph
icKe
y Pl
anN
otes
/ L
e gen
ds
CDEF
LBUSD No.:
Maintenance and Operations
888 South Figueroa StreetSuite 2020
Los Angeles, CA 90017phone: 213.614.0900
fax: 213.929.2247www.tska.com
LON
GFE
LLO
W E
LEM
ENTA
RY
SCH
OO
L
DRAWN BY:
8 16 24
1/8" = 1'-0"
KEYPLAN
1/8" = 1'-0"
Long
fello
w E
S H
VAC
Alte
ratio
n
3800
Oliv
e Av
e ,L o
ng B
each
, CA
9 080
7
64725-327
FA134
FIRE ALARMFLOOR PLANBLDGS 4 & 5
Checker10/18/18
17-052.00
9119-1617-440
DSA
APPR
OVE
D
19-623-118620
Author
1/8" = 1'-0"
1FIRE ALARM FLOOR PLAN BLDGS 4
1/8" = 1'-0"
2FIRE ALARM FLOOR PLAN BLDGS 5
2 06/04/18 CCD-2
2
(AS REVISED)
THIS APPROVAL IS FOR ITEMS WITHINTHE CLOUDED AREAS ONLY. FOROTHER INFORMATION NOT CONTAINEDWITHIN THE CLOUDED AREAS, REFERTO ORIGINAL DSA APPROVED PLANSAND OTHER APPROVED DOCUMENTS.
APPROVED DIV. OF THE STATE ARCHITECT
APP. INC:REVIEWED FOR
SS FLS ACS
DATE:
03-118620 0
✔ ✔
05/08/2019