AQUAREA HYDRAULIC GUIDE Bi-Bloc Solutions H GENERATION heating & cooling
Transcript
Page 1: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

AQUAREA HYDRAULIC GUIDEBi-Bloc SolutionsH GENERATION

heating & cooling

Page 2: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

AQUAREA BI-BLOC HYDRAULIC DATA TABLE 4

TABLE OF RECOMMENDATIONS FOR HYDRAULIC CONNECTION DIAMETERS 5

EXPANSION VESSEL SIZING CHECK 5

CHARACTERISTIC CIRCULATION PUMP CURVES (MANOMETRIC HEIGHTS AVAILABLE) 6

AQUAREA “ALL-IN-ONE” H GENERATION BI-BLOC HYDRAULIC SCHEME DIAGRAMS:

HEATING + INTEGRATED DOMESTIC HOT WATER

Application7

New Renovation

1-Zone Configurations: 71 direct underfloor heating zone + integrated domestic hot water ✔ 7

1 direct radiator heating zone + integrated domestic hot water ✔ 8

1 floor heating zone with buffer tank + integrated domestic hot water ✔ 8

1 radiator heating zone with buffer tank + integrated domestic hot water ✔ 9

1 radiator heating zone with buffer tank + swimming pool + integrated domestic hot water ✔ ✔ 9

1 direct fan coil zone + integrated domestic hot water ✔ 10

1 fan coil zone with buffer tank via bypass + integrated domestic hot water ✔ 10

2-Zone Configurations: 112 floor heating zones with buffer tank + integrated domestic hot water ✔ 11

2 radiator heating zones with buffer tank + integrated domestic hot water ✔ 11

2 direct radiator heating zones + integrated domestic hot water ✔ ✔ 12

2 direct floor heating zones + integrated domestic hot water ✔ ✔ 12

2 radiator heating zones + direct underfloor heating + integrated domestic hot water ✔ ✔ 13

2 radiator heating zones with buffer tank + underfloor heating + integrated domestic hot water ✔ 13

Configurations with backup heater 141 floor heating zone with buffer tank + backup heat pump + integrated domestic hot water ✔ ✔ 14

1 radiator heating zone with buffer tank + backup heat pump + integrated domestic hot water ✔ ✔ 14

1 radiator heating zone with buffer tank + swimming pool + boiler backup + integrated domestic hot water ✔ 15

2 radiator heating zones with buffer tank + backup boiler + integrated domestic hot water ✔ 15

2 radiator heating zones with buffer tank + underfloor heating + backup boiler + integrated domestic hot water ✔ ✔ 16

3

AQUAREA H GENERATION BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC TAPWATER TANK (OPTIONAL) 17

Configuration with External domestic tapwater tank: 17

External domestic tapwater tank: generic diagram applicable to all the following configurations - SOLUTION No. 1 - 3-way valve external to the module 17

External domestic tapwater tank: generic diagram applicable to all the following configurations - SOLUTION No. 2 - 3-way valve internal to the module - buffer tank system 18

Application

New Renovation

1-Zone Configurations: 181 direct fan coil zone ✔ 18

1 direct underfloor heating zone ✔ 19

1 direct radiator heating zone ✔ 19

1 radiator heating zone with buffer tank + swimming pool ✔ ✔ 20

1 floor heating zone with buffer tank ✔ 20

1 radiator heating zone with buffer tank ✔ 21

1 fan coil heating zone with bypass ✔ 21

2-Zone Configurations: 222 radiator heating zones with buffer tank ✔ ✔ 22

2 floor heating zones with buffer tank ✔ ✔ 22

2 radiator heating zones with buffer tank + underfloor heating ✔ ✔ 23

Configurations with Standby Generator: 231 floor heating zone with buffer tank + backup heat pump ✔ ✔ 23

1 radiator heating zone with buffer tank + backup heat pump ✔ ✔ 24

1 radiator heating zone with buffer tank + backup boiler ✔ 24

1 radiator heating zone with buffer tank + swimming pool + backup boiler ✔ 25

2 radiator heating zones with buffer tank + backup boiler ✔ 25

2 fan coil heating zones with buffer tank + underfloor heating + backup heat pump ✔ ✔ 26

2 radiator heating zones with buffer tank + underfloor heating + backup boiler ✔ 26

2 radiator heating zones with buffer tank + underfloor heating + solar heating ✔ ✔ 27

2 radiator heating zones with buffer tank + underfloor heating + solar domestic hot water ✔ ✔ 27

Cascaded Configurations: 283 cascaded heat pumps with 2 radiator heating zones with buffer tank + underfloor heating + domestic hot water via HPM ✔ 28

3 Tichelmann loop cascaded heat pumps + 1 radiator heating zone with buffer tank via HPM ✔ 28

ACCESSORIES 29H Generation controllers 29

All-Generation controllers 30

Hydraulic 31

TABLE OF CONTENTS

Page 3: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

4 5

Aquarea Bi-Bloc Hydraulic Data Table

Indoor unit Outdoor unitNom. flow

(at ΔT5 °C) in litres/min

Minimum water volume (litre)

Expansion vessel volume (litre)

Heating connection diameter

Supply/Return

Domestic hot water connection diameter

WH-SDC03H3E5-1 WH-UD03HE5-1 9.2

No 10 litres pre-inflated to 1 bar 1" 1/4 male 3/4"

WH-SDC05H3E5-1 WH-UD05HE5-1 14.3

WH-SDC07H3E5-1 WH-UD07HE5-1 20

WH-SDC09H3E5-1 WH-UD09HE5-1 25.8

WH-SDC12H6E5 WH-UD12HE5 34.4

WH-SDC16H6E5 WH-UD16HE5 45.8

WH-SDC09H3E8 WH-UD09HE8 25.8

WH-SDC12H9E8 WH-UD12HE8 34.4

WH-SDC16H9E8 WH-UD16HE8 45.8

WH-ADC0309H3E5(B) WH-UD03HE5-1 9.2

WH-ADC0309H3E5(B) WH-UD05HE5-1 14.3

WH-ADC0309H3E5(B) WH-UD07HE5-1 20

WH-ADC0309H3E5(B) WH-UD09HE5-1 25.8

WH-ADC1216H6E5 WH-UD12HE5 34.4

WH-ADC1216H6E5 WH-UD16HE5 45.8

WH-ADC0916H9E8 WH-UD09HE8 25.8

WH-ADC0916H9E8 WH-UD12HE8 34.4

WH-ADC0916H9E8 WH-UD16HE8 45.8

Indoor unit Outdoor unitNom. flow

(at ΔT5 °C) in litres/min

Minimum water volume (litre)

Expansion vessel volume (litre)

Connection diameter Supply/Return

Domestic hot water connection diameter

WH-SXC09H3E5 WH-UX09HE5 25.8

No 10 litres pre-inflated to 1 bar 1" 1/4 male 3/4"

WH-SXC12H6E5 WH-UX12HE5 34.4

WH-SXC09H3E8 WH-UX09HE8 25.8

WH-SXC12H9E8 WH-UX12HE8 34.4

WH-SXC16H9E8 WH-UX16HE8 45.8

WH-ADC1216H6E5 WH-UX09HE5 25.8

WH-ADC1216H6E5 WH-UX12HE5 34.4

WH-ADC0916H9E8 WH-UX09HE8 25.8

WH-ADC0916H9E8 WH-UX12HE8 34.4

WH-ADC0916H9E8 WH-UX16HE8 45.8

Indoor unit Outdoor unitNom. flow

(at ΔT5 °C) in litres/minMinimum water volume

(litre)Expansion vessel volume

(litre)Connection diameter

Supply/ReturnWH-SHF09F3E5 WH-UH09FE5 25.8 30

10 litrespre-inflated to 1 bar

1" 1/4 maleWH-SHF12F6E5 WH-UH12FE5 34.4 50

WH-SHF09F3E8 WH-UH09FE8 25.8 30

WH-SHF12F9E8 WH-UH12FE8 34.4 50

HIGH PERFORMANCE RANGE

T-CAP RANGE

HIGH TEMPERATURE RANGE

1st step: Calculate vessel’s performance 2nd step: Check volume of water treated by the vessel

Table of Recommendations for Hydraulic Connection Diameters

Expansion Vessel Sizing Check

The diameters are given for copper tubes with a water temperature of 50 °C. For use of other materials, comply with the inner diameter of this table. Adhering to these diameters leads to noise-free heating water flow, with no piping erosion or significant heat loss.

Pi = hydraulic pressure applied to the vessel membrane (weight of the water column) using cold water, in bar.

Pg = inflating pressure of the vessel (Pg = Pi - 0.2 bar)

Pt = Set pressure of the heating valve - 10% (usually 2.7 bar)

Vvase = expansion vessel volume

Vrec = collection vessel volume = Vvase x Rdt vessel

Vtot = total volume of water that can be processed by the expansion vessel at max. water temperature

Direct Decoupled

3 kW Heat Pump 22/20 mm 22/20 mm

5 kW Heat Pump 28/26 mm 22/20 mm

7 kW Heat Pump 28/26 mm 28/26 mm

9 kW Heat Pump 32/30 mm 28/26 mm

12 kW Heat Pump 35/33 mm 32/30 mm

16 kW Heat Pump 42/ 39 mm 35/33 mm

Temp. 10 °C 20 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C

Dilation coefficient 0.0003 0.0018 0.0048 0.0058 0.0079 0.0098 0.0121 0.0145 0.0170

CONCLUSION:

If Vtot is less than the actual volume of the installation, a second vessel must be added.

Vessel performance = (Pt + 1) - (Pg + 1) (Pt + 1)

Vtot = Vrec/dilation coefficient

Page 4: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

6 7

Characteristic circulation pump Curves

140150

130120110100

908070605040302010

00 105 20 30 4015 25 35

Min. Duty : 50

Max. Duty : C5

Manometric flow curve for H series pump: Heat pump from 3 to 9 kW

Flow rate of water (L/min)

Pump

exte

rnal

pres

sure

dro

p (k

Pa)

140150

130120110100

908070605040302010

00 10 20 30 40 50 60

Min. Duty : 50

Max. Duty C516kW rated Duty 97

12kW rated Duty 839kW rated Duty 74

Manometric flow curve for H series pump: Heat pump from 9 to 16 kW

Flow rate of water (L/min)

Pump

exte

rnal

pres

sure

dro

p (k

Pa)

All Panasonic H Generation heat pumps use electric backup for defrosting assistance. For this process to be viable, Panasonic insists that the recommended diameters be observed and that the pressure drops in the existning heating system to be kept under control. In the event of a fault or failure due to a condenser flow problem, Panasonic will refuse to uphold the warranty if the manufacturer’s recommendations are not met.

General warning:

Pump curve, 2nd zone only for All-In-One WH-ADC0309H3E5B

Flow rate of water (L/min)

Pump speeds

Pump

exte

rnal

pres

sure

dro

p (k

Pa)

70

60

50

40

30

20

10

00 10 20 30 40

6 & 7

5

432

1

GENERAL RECOMMENDATIONS

During renovation, if the pressure drops in the existing system cannot be correctly evaluated, a hydraulic buffer tank must be systematically installed.

11

3

8

4

1

2

7

6

9

5

10

1 direct floor heating zone + integrated domestic hot water

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 Sanitary expansion vessel Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

6 Thermostatic mixing valve Compulsory if anti-

legionella is activatedNot provided

7 Safety valve and closing valve Compulsory Not provided8 Air separator Optional Not provided9 Differential valve As per recommendation Not provided

10 Underfloor heating safety Recommended Not provided

11 Room controller* OptionalControl (integrated in the module) that can be made remote

SCHEMATIC DIAGRAM

1-ZONE CONFIGURATIONS

The validity of this solution is subject to the following points:· The circulation pump must be able to withstand the pressure drops of the most resistive heating

loop while ensuring sufficient flow· If the system includes accessories that can vary the flow, then at least 50% of the loops must

remain in free passage. If this is not possible, install a differential valve.

NEW

* Refer to the accessories at the end of the guide

H GENERATIONAQUAREA “ALL-IN-ONE” BI-BLOCHYDRAULIC SCHEME heating + integrated domestic hot water

SupplyReturn

and/or

DHW

DCW

Page 5: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

8 9

1 heating zone + integrated domestic hot water

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Buffer tank Compulsory PAW-BTANK50L6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Underfloor heating safety Recommended Not provided

8 Room controller* OptionalControl (integrated in the module) that can be made remote

9 Filling valve with check valve Compulsory Not provided10 Safety valve and closing valve Compulsory Not provided11 Sanitary expansion vessel Recommended Not provided

12 Thermostatic mixing valve Compulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 Sanitary expansion vessel Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

7 Safety valve and closing valve Compulsory Not provided8 Air separator Optional Not provided9 Differential valve As per recommendation Not provided

10 Room controller* Optional Control (integrated in the module) that can be made remote

8

3

10

1

4 2

7 5

9

6

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

1 floor heating zone with buffer tank + integrated domestic hot water

8

5 6

7

3

1

2 9

10 11

12

4

The validity of this solution is subject to the following points:· The circulation pump must be able to withstand the pressure drops of the most resistive heating

loop while ensuring sufficient flow· If the system includes accessories that can vary the flow, then at least 50% of the transmitters

must remain in free passage. If this is not possible, install a differential valve.

RENOVATION

NEW

* Refer to the accessories at the end of the guide

13

9

12

4

1

14

6 2

7 5

8

15

10

3

11

11

1 radiator heating zone with buffer tank + swimming pool + integrated domestic hot water

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Safety valve and closing valve Compulsory Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

9 Buffer tank Compulsory PAW-BTANK50L10 Secondary circulation pump Compulsory Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Sanitary expansion vessel Recommended Not provided6 Filling valve with check valve Compulsory Not provided7 Safety valve and closing valve Compulsory Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

9 Buffer tank Compulsory Not provided10 3-way motorized mixing valve Recommended Not provided11 Secondary circulation pump Compulsory Not provided12 Pool heat exchanger Compulsory Not provided

13 Room controller* Optional Control (integrated in the module) that can be made remote

14CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 3 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

15 Pool pump Depending on system Not provided

1 radiator heating zone with buffer tank + integrated domestic hot water

8

2

3

11

4

6

5

9

1

10

7

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

AQUAREA “ALL-IN-ONE” BI-BLOC HYDRAULIC SCHEME: HEATING + INTEGRATED DOMESTIC HOT WATER

RENOVATION

RENOVATION

* To view all the selectable accessories, please refer to the A2W Aquarea contract catalog or contact your Panasonic dealer.

NEW

* Refer to the accessories at the end of the guide

SupplyReturn

SupplyReturn

SupplyReturn

SupplyReturn

and/or

and/orand/or

and/or

DHW

DHW

DHW

DHW

DCW

DCW

DCW

DCW

Page 6: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

10 11

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Safety valve and closing valve Compulsory Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

9Buffer volume 30 to 50 L depending on heat pump model

Recommended PAW-BTANK50L

10 Differential valve As per recommendation Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One V2 module with integrated filter + valves

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided7 Safety valve and closing valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

9Buffer volume 30 to 50 L depending on heat pump model

Recommended PAW-BTANK50L

10 Smooth bypass Compulsory Not provided11 Secondary circulation pump Compulsory Not provided

12 Room controller* OptionalControl (integrated in the module) that can be made remote

RENOVATION

* To view all the selectable accessories, please refer to the A2W Aquarea contract catalog or contact your Panasonic dealer.

NEW

1 direct fan coil zone + integrated domestic hot water

1 fan coil zone with buffer tank via bypass + integrated domestic hot water

1

3

11

1

4

9

10

2

7

5

6

8

1

8

12

9 11

10 3

5

4

2

7 6

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

* Refer to the accessories at the end of the guide

2 floor heating zones with buffer tank + integrated domestic hot water

2 radiator heating zones with buffer tank + integrated domestic hot water

10

10

11

6

7

7

8

8

9

9 3

4

1

2 5

11

12 13

14

2-ZONE CONFIGURATIONS

SCHEMATIC DIAGRAM:

SCHEMATIC DIAGRAM:

RENOVATION

RENOVATION

This solution is preferable to an existing system, if a buffer tank is present and/or if the pressure drops of the secondary system cannot be correctly evaluated.

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Buffer tank Compulsory Not provided7 3-way motorized mixing valve Compulsory Not provided8 Secondary circulation pump Compulsory Not provided9 Underfloor heating safety Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

10 Room controller* Optional Control (integrated in the module) that can be made remote

11CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

12 Safety valve and closing valve Compulsory Not provided13 Sanitary expansion vessel Recommended Not provided

14 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Buffer tank Compulsory Not provided7 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Room controller* Optional Control (integrated in the module) that can be made remote

9CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + AW-A2W-TSBU + PAW-A2W-TSHC

10 Safety valve and closing valve Compulsory Not provided11 Sanitary expansion vessel Recommended Not provided

12 Thermostatic mixing valve Compulsory if anti-

legionella is activatedNot provided

7

8

6

9

7

8

3

4

1

2 5

10 11

12

* Refer to the accessories at the end of the guide

AQUAREA “ALL-IN-ONE” BI-BLOC HYDRAULIC SCHEME: HEATING + INTEGRATED DOMESTIC HOT WATER

SupplyReturn

SupplyReturn

SupplyReturn

SupplyReturn

and/orand/or

and/or

and/or

DHW

DHW

DHW DHW

DCW

DCW

DCWDCW

Page 7: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

12 13

2 direct radiator heating zones + integrated domestic hot water

2 direct floor heating zones + integrated domestic hot water

10

10

9 3

1

4

2 8

5

7

7

6

3 11

11

1

4

10

2 10 7

5

9

9

6

8

4 SCHEMATIC DIAGRAM:

SCHEMATIC DIAGRAM:

AQUAREA “ALL-IN-ONE” BI-BLOC HYDRAULIC SCHEME: HEATING + INTEGRATED DOMESTIC HOT WATER

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module, 2 zones with integrated filter + valves + drain valve

Compulsory WH-ADC0309H3E5B

2 Valve Optional Not provided3 Filling valve with check valve Compulsory Not provided4 Magnetite filter Recommended Not provided5 Sanitary expansion vessel Recommended Not provided

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

7 Differential valveDepending on configuration

Not provided

8 Safety valve and closing valve Compulsory Not provided9 Air separator Optional Not provided

10 Room controller* Optional Control (integrated in the module) that can be made remote

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module, 2 zones with integrated filter + valves + drain valve

Compulsory WH-ADC0309H3E5B

2 Valve Optional Not provided3 Filling valve with check valve Compulsory Not provided4 Magnetite filter Recommended Not provided5 Sanitary expansion vessel Recommended Not provided

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

7 Safety valve and closing valve Compulsory Not provided8 Air separator Recommended Not provided

9 Differential valveDepending on configuration

Not provided

10 Underfloor heating safety Recommended Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

RENOVATION

RENOVATION

NEW

NEW

The validity of this solution is subject to the following points:· If the system includes accessories that can vary the flow, then at least 50% of the transmitters

must remain in free passage. If this is not possible, install a differential valve.· The circulation pump must be able to withstand the pressure drops of the most resistive heating

loop while ensuring sufficient flow

If more than 50% of the floor manifold loops can be closed using an automatic device, then the installation of a differential valve is required.

If the two zones are supplied with different temperatures, then the zone working with the highest temperature must be connected to the low output of the module (direct circuit output).

* Refer to the accessories at the end of the guide

9 11

11

1

7

10

3

4 2

5

8

8

6

2 heating zones + direct underfloor heating + integrated domestic hot water

2 radiator heating zones with buffer tank + underfloor heating + integrated domestic hot waterSCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module, 2 zones with integrated filter + valves + drain valve

Compulsory WH-ADC0309H3E5B

2 Valve Optional Not provided3 Filling valve with check valve Compulsory Not provided4 Safety valve and closing valve Compulsory Not provided5 Sanitary expansion vessel Recommended Not provided

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

7 Magnetite filter Recommended Not provided

8 Differential valveDepending on configuration

Not provided

9 Air separator Optional Not provided10 Underfloor heating safety Recommended Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module, 1 zone with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided7 Safety valve and closing valve Compulsory Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

9 Buffer tank Compulsory Not provided10 Secondary circulation pump Compulsory Not provided11 3-way motorized mixing valve Compulsory Not provided12 Underfloor heating safety Recommended Not provided

13 Room controller* Optional Control (integrated in the module) that can be made remote

14CZ-NS4P integrated circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

The validity of this solution is subject to the following points:· The circulation pump must be able to

withstand the pressure drops of the most resistive heating loop while ensuring sufficient flow

· If the system includes accessories that can vary the flow, then at least 50% of the loops must remain in free passage. If this is not possible, install a differential valve.

This solution is preferable to an existing system, if a buffer tank is present and/or if the pressure drops of the secondary system cannot be correctly evaluated.

RENOVATION

RENOVATION

NEW

10

13

9

14

13

11

12

3

4

1

7 6

8

5

2 10

* Refer to the accessories at the end of the guide

SupplyReturn

SupplyReturn

SupplyReturn

SupplyReturn

and/or

and/or

and/or

and/or

DHW

DHW

DHW

DHW

DCW

DCW

DCW

DCW

Page 8: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

14 15

1 floor heating zone with buffer tank + backup heat pump + integrated domestic hot water

1 radiator heating zone with buffer tank + backup heat pump + integrated domestic hot water

PAC en appoint

10 9

12

13

11

14

8

1

4

3

2

7 5

6

12 10 9

11

8

1

4

3

13

2

7 5

6

CONFIGURATIONS WITH BACKUP

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

AQUAREA “ALL-IN-ONE” BI-BLOC HYDRAULIC SCHEME: HEATING + INTEGRATED DOMESTIC HOT WATER

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 Sanitary expansion vessel Recommended Not provided

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

7 Safety valve and closing valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Air separator Optional Not provided9 Buffer tank Compulsory Compulsory

10 Secondary circulation pump Compulsory Not provided11 Underfloor heating safety Recommended Not provided

12 Room controller* Optional Control (integrated in the module) that can be made remote

13 Backup heat pump connected in parallel Compulsory Not provided14 Anti-freeze valve Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 Sanitary expansion vessel Recommended Not provided

6 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

7 Safety valve and closing valve Compulsory Not provided8 Air separator Optional Not provided9 Buffer tank Compulsory Compulsory

10 Secondary circulation pump Compulsory Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

12 Backup heat pump connected in parallel Compulsory Not provided13 Anti-freeze valve Recommended Not provided

The applicability of this solution is governed by a setting in “bivalent parallel” mode only and by the use of a backup heat pump with production temperatures ≤ 55 °C.

The applicability of this solution is governed by a setting in “bivalent parallel” mode only and by the use of a backup heat pump with production temperatures ≤ 55 °C.

RENOVATION

RENOVATION

NEW

NEW

* Refer to the accessories at the end of the guide

2 radiator heating zones with buffer tank + backup boiler + integrated domestic hot water

9

12

11

11

8

4

1

3

5 13

7 6

10

2

1 radiator heating zone with buffer tank + swimming pool + boiler backup + integrated domestic hot water

9

14 15

13

3

1

4

7 6

5

2

8

10

11

12

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 Filling valve with check valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided7 Safety valve and closing valve Compulsory Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

9 50-100 L buffer tank Compulsory Not provided10 Secondary circulation pump Compulsory Not provided11 Pool heat exchanger Compulsory Not provided12 Pool pump Compulsory Not provided

13 Room controller* Optional Control (integrated in the module) that can be made remote

14CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 3 PAW-A2W-TSHC probes

Compulsory CZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

15 Boiler connected in parallel Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Filling valve with check valve Compulsory Not provided4 Magnetite filter Recommended Not provided

5 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

6 Sanitary expansion vessel Recommended Not provided7 Safety valve and closing valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Air separator Optional Not provided9 50-100 L buffer tank Compulsory Not provided

10 Secondary circulation pump Compulsory Not provided

11 Room controller* Optional Control (integrated in the module) that can be made remote

12CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

13 Boiler connected in parallel Compulsory Not provided

RENOVATION

RENOVATION

* Refer to the accessories at the end of the guide

SupplyReturn

SupplyReturn

SupplyReturn

SupplyReturn

and/or

and/or

and/or

and/or

DHWDHW

DHW

DHW

DCWDCW

* Insulated external pipes

* Insulated external pipes

DCW

DCW

Backup HP

Page 9: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

16 17

AQUAREA “ALL-IN-ONE” BI-BLOC HYDRAULIC SCHEME: HEATING + INTEGRATED DOMESTIC HOT WATER

No. DescriptionType of

recommendationPanasonic Reference

1All-In-One module with integrated filter + valves + drain valve

Compulsory Depending on power

2 Valve Optional Not provided3 Filling valve with check valve Compulsory Not provided4 Air separator Optional Not provided5 Safety valve and closing valve Compulsory Not provided6 Sanitary expansion vessel Recommended Not provided7 Magnetite filter Recommended Not provided

8 Thermostatic mixing valveCompulsory if anti-

legionella is activatedNot provided

No. DescriptionType of

recommendationPanasonic Reference

9 50-100 L buffer tank Compulsory Not provided10 Secondary circulation pump Compulsory Not provided11 3-way motorized mixing valve Compulsory Not provided12 Underfloor heating safety Recommended Not provided

13 Room controller* Optional Control (integrated in the module) that can be made remote

14CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

15 Boiler connected in parallel Compulsory Not provided

RENOVATION

2 radiator heating zones with buffer tank + underfloor heating + backup boiler + integrated domestic hot water

9

15

10

11

14

13

10

13

4

7

1

3

12 2

5 6

8

SCHEMATIC DIAGRAM

* Refer to the accessories at the end of the guide

Optional external domestic hot water tank: generic diagram applicable to all the following configurations - SOLUTION No. 1 - 3-way valve external to the module

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 3-way motorized directional valve Compulsory PAW-3WYVLV-SI5 Buffer tank Compulsory Not provided6 Secondary circulation pump Compulsory Not provided7 Filling valve with check valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Room controller* OptionalControl (integrated in the module) that can be made remote

9 Sanitary expansion vessel + manometer Recommended Not provided10 Safety valve and closing valve Compulsory Not provided

11PAW-TS1 sanitary probe (6m) / PAW-TS2** (20m) / PAW-TS4 (6m / Ø = 6mm) as required

CompulsoryPAW-TS1 (6m) / PAW-TS2 (20m) / PAW-TS4 (6m / Ø = 6mm) as required

12 Heat pump compatible domestic hot water Compulsory Not provided13 Thermostatic mixing valve Optional Not provided

12

2

3

8 4

5

1

13

6

10

7

9

11

SCHEMATIC DIAGRAM Sensor for tap water supplied with all Panasonic domestic hot water tanks - do not provide any additional probe

* Refer to the list of accessories at the end of the guide. ** PAW-TS2: Factory supplied with all Panasonic tanks

SupplyReturn

and/or

and/or

DHW

DHW

DCW

DCW

AQUAREA H GENERATION BI-BLOC HYDRAULIC SCHEME Heating Only + external domestic hot water tank (optional)

CONFIGURATIONS WITH OPTIONAL EXTERNAL DOMESTIC HOT WATER TANK

Page 10: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

18 19

Optional external domestic hot water tank: generic diagram applicable to all the following configurations - SOLUTION No. 2 - 3-way valve internal to the module - system with buffer tank

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power + CZ-NV1 2 Domestic hot water integrated 3-way valve kit Optional CZ-NV13 Air separator Optional Not provided4 Magnetite filter Recommended Not provided5 30-50 L Buffer tank Compulsory Not provided6 Secondary circulation pump Compulsory Not provided7 Filling valve with check valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Room controller* OptionalControl (integrated in the module) that can be made remote

9 Sanitary expansion vessel + manometer Recommended Not provided10 Safety valve and closing valve Compulsory Not provided

11PAW-TS1 sanitary probe (6m) / PAW-TS2** (20m) / PAW-TS4 (6m / Ø = 6mm) as required

CompulsoryPAW-TS1 (6m) / PAW-TS2 (20m) / PAW-TS4 (6m / Ø = 6mm) as required

12Heat pump compatible domestic hot water tank

Compulsory Not provided

13 Thermostatic mixing valve Optional Not provided

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided

4Buffer tank with a capacity of 30 to 50 L depending on heat pump power

Compulsory PAW-BTANK50L

No. DescriptionType of

recommendationPanasonic Reference

5 Filling valve with check valve Compulsory Not provided

6 Room controller* or pilot wire OptionalControl (integrated in the module) that can be made remote

7 Differential valve As per recommendation Not provided

18 19

+

3

4

8

5

1

13

6

10

12

11

7

9

1 2

SCHEMATIC DIAGRAM Domestic hot water sensor supplied with all Panasonic hot tapwater tanks - do not provide any additional sensor

1 direct fan coil zone

2 6

3 5

1

4

7

1-ZONE CONFIGURATIONS

SCHEMATIC DIAGRAM The validity of this solution is subject to the following points:· The circulation pump must be able to withstand the pressure drops of the most resistive heating loop

while ensuring sufficient flow· If the fan coils are not equipped with a 3-way valve a differential valve is required.NEW

* Refer to the list of accessories at the end of the guide. ** PAW-TS2: Factory supplied with all Panasonic tanks

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

1 direct underfloor heating zone

1 direct radiator heating zone

2 6 3

1

54

7

2

3

5

4

1

6

1-ZONE CONFIGURATIONS

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

The validity of this solution is subject to the following points:· The circulation pump must be able to withstand the pressure drops of the most resistive heating

loop while ensuring sufficient flow· If the system includes accessories that can vary the flow, then at least 50% of the loops must remain

in free passage. If this is not possible, install a differential valve.

The validity of this solution is subject to the following points:· The circulation pump must be able to withstand the pressure drops of the most resistive heating

loop while ensuring sufficient flow· If the system includes accessories that can vary the flow, then at least 50% of the transmitters must

remain in free passage. If this is not possible, install a differential valve.

NEW

NEW

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Underfloor heating safety Recommended Not provided4 Magnetite filter Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

5 Filling valve with check valve Compulsory Not provided

6 Room controller* OptionalControl (integrated in the module) that can be made remote

7 Differential valve As per recommendation Not provided

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

4 Room controller* OptionalControl (integrated in the module) that can be made remote

5 Filling valve with check valve Compulsory Not provided6 Differential valve As per recommendation Not provided

* Refer to the accessories at the end of the guide

and/or

and/or

and/or

and/or

DHW

DCW

DCW

DCW

DCW

Page 11: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

20 21

1 radiator heating zone with buffer tank + swimming pool

2

3

10

5

7

4 8

11 1

6

9

7

SCHEMATIC DIAGRAM

1 floor heating zone with buffer tankSCHEMATIC DIAGRAM

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 Buffer tank Compulsory Not provided6 3-way motorized mixing valve Recommended Not provided7 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Pool heat exchanger Compulsory Not provided9 Pool pump Depending on system Not provided

10 Room controller* OptionalControl (integrated in the module) that can be made remote

11CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 3 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory PAW-BTANK50L

No. DescriptionType of

recommendationPanasonic Reference

5 Filling valve with check valve Compulsory Not provided6 Secondary circulation pump Compulsory Not provided7 Underfloor heating safety Recommended Not provided

8 Room controller* OptionalControl (integrated in the module) that can be made remote

RENOVATION

RENOVATION

NEW

2

8

3

4 6

5

1

7

* Refer to the accessories at the end of the guide

1 radiator heating zone with buffer tank

2

3

7

6

4 5

1

SCHEMATIC DIAGRAM

1 fan coil zone with buffer tank via bypass

2

5

8

3

6

7

1

4

SCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory PAW-BTANK50L

No. DescriptionType of

recommendationPanasonic Reference

5 Secondary circulation pump Compulsory Not provided

6 Room controller* OptionalControl (integrated in the module) that can be made remote

7 Filling valve with check valve Compulsory Not provided

RENOVATION

RENOVATION

· If the fan coils are not equipped with a 3-way valve a differential valve is required in the secondary circuit.

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided

4Buffer tank with a capacity of 30 to 50 L depending on heat pump power

Compulsory PAW-BTANK50L

No. DescriptionType of

recommendationPanasonic Reference

5 Smooth bypass Compulsory Not provided6 Secondary circulation pump Compulsory Not provided7 Filling valve with check valve Compulsory Not provided

8 Room controller* or pilot wire OptionalControl (integrated in the module) that can be made remote

* Refer to the accessories at the end of the guide

and/or

and/or

and/or

and/orDCW

DCWDCW

DCW

Page 12: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

22 23

2 radiator heating zones with buffer tank

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

2-ZONE CONFIGURATIONS

2 floor heating zones with buffer tank

2

3

7

4

5

8

6

7

1

2

3

9

9

4

5

6

10

6

7

7

1

8

8

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM:

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Filling valve with check valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

6 Secondary circulation pump Compulsory Not provided

7 Room controller* OptionalControl (integrated in the module) that can be made remote

8CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Filling valve with check valve Compulsory Not provided6 3-way motorized mixing valve Compulsory Not provided7 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Underfloor heating safety Recommended Not provided

9 Room controller* OptionalControl (integrated in the module) that can be made remote

10CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

RENOVATION

RENOVATION

NEW

NEW

* Refer to the accessories at the end of the guide

2 radiator heating zones with buffer tank + underfloor heating

2

3

6

9

9 4

5

6 7

10

1

8

SCHEMATIC DIAGRAM

5

6

4

7

3

2

2

3

1

8 9

1 zone with buffer tank, underfloor heating + backup heat pumpSCHEMATIC DIAGRAM

CONFIGURATIONS WITH BACKUP HEAT PUMP

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Filling valve with check valve Compulsory Not provided6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 3-way motorized mixing valve Compulsory Not provided8 Underfloor heating safety Recommended Not provided

9 Room controller* OptionalControl (integrated in the module) that can be made remote

10CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

6 Filling valve with check valve Compulsory Not provided

7 Room controller* OptionalControl (integrated in the module) that can be made remote

8 Backup heat pump connected in parallel Compulsory Not provided9 Underfloor heating safety Recommended Not provided

RENOVATION

RENOVATION

NEW

NEWThe applicability of this solution is governed by a setting in “bivalent parallel” mode only and by the use of a backup heat pump with production temperatures ≤ 55 °C.

* Refer to the accessories at the end of the guide

and/or

and/or

and/or

and/or

and/or

DCW

DCW

DCWDCW

Main HP

Backup HP

Page 13: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

24 25

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

1 radiator heating zone with buffer tank + backup heat pump

5

6

4

3

2

2 7

3

9

8

1

SCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Secondary circulation pump Compulsory Not provided6 Filling valve with check valve Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Room controller* OptionalControl (integrated in the module) that can be made remote

8CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 1 PAW-A2W-TSHC probe

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

9 Backup heat pump connected in parallel Compulsory Depending on power

RENOVATION

NEW

If the backup heat pump can produce a supply temperature > 55 °C, then “alternative” mode must be selected for backup management.

1 radiator heating zone with buffer tank + backup boiler (alternative mode)

2

6

4 3

7 5

9

1

8

SCHEMATIC DIAGRAM

RENOVATION

This configuration is preferred when the boiler supply temperature can be > 55 °C

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 50-100 L buffer tank Compulsory Not provided6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Room controller* OptionalControl (integrated in the module) that can be made remote

8CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 1 PAW-A2W-TSHC probe

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

9 Boiler connected in parallel Recommended Not provided

* Refer to the accessories at the end of the guide

1 radiator heating zone with buffer tank + swimming pool + backup boiler

2

3

5 7

10

4

6

11

8

1

12

9

SCHEMATIC DIAGRAM

2 radiator heating zones with buffer tank + backup boilerSCHEMATIC DIAGRAM

2

5

3

4

9 7

8

6

7

1

RENOVATION

RENOVATION

No. DescriptionType of

recommendationPanasonic Reference

1 Hydraulic module with integrated filter + valves Compulsory Depending on power 2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 50-100 L buffer tank Compulsory Not provided5 Filling valve with check valve Compulsory Not provided6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Room controller* OptionalControl (integrated in the module) that can be made remote

8CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

9 Boiler connected in parallel Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 50-100 L buffer tank Compulsory Not provided6 Secondary circulation pump Compulsory Not provided7 Pool heat exchanger Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

8 Room controller* OptionalControl (integrated in the module) that can be made remote

9 3-way motorized mixing valve Recommended Not provided

10CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 3 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

11 Boiler connected in parallel Compulsory Depending on power12 Pool pump Depending on system Not provided

* Refer to the accessories at the end of the guide

Main HP

Backup HP

and/or

and/or

and/or

and/orand/or

DCW

DCWDCW

DCW

Page 14: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

26 27

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

5

3

2

2 3

1

11

6

9

9 4

6 7

10

8

2 zones with buffer tank, fan coil + underfloor heating + backup heat pumpSCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Filling valve with check valve Compulsory Not provided6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 3-way motorized mixing valve Compulsory Not provided8 Underfloor heating safety Recommended Not provided

9 Room controller* OptionalControl (integrated in the module) that can be made remote

10CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

11 Backup heat pump connected in parallel Compulsory Not provided

RENOVATION

NEW

2 radiator heating zones with buffer tank + underfloor heating + backup boiler SCHEMATIC DIAGRAM

2

3

4

11

6

9

10

1

9 7

6 8

5

RENOVATION

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Filling valve with check valve Compulsory Not provided5 50-100 L buffer tank Compulsory Not provided6 Secondary circulation pump Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 3-way motorized mixing valve Compulsory Not provided8 Underfloor heating safety Recommended Not provided

9 Room controller* OptionalControl (integrated in the module) that can be made remote

10CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

11 Boiler connected in parallel Compulsory Not provided

* Refer to the accessories at the end of the guide

2 radiator heating zones with buffer tank + underfloor heating + solar domestic hot water

2 radiator heating zones with buffer tank + underfloor heating + solar heating

SCHEMATIC DIAGRAM

SCHEMATIC DIAGRAM

2

3

8

8

5 6

5

9

10

12

4

11

1

13

17

15

16

7

14

2

3

12

12

9

13

6

1

7

11

8 4

5

10

14

15

10

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Magnetic valve Recommended Not provided5 Extra expansion vessel + safety valve Recommended Not provided

6Buffer tank with integrated solar heat exchanger

Compulsory Not provided

7 Solar transfer group Compulsory Not provided8 Heating circuit 3-point motorized mixing valve Recommended Not provided

No. DescriptionType of

recommendationPanasonic Reference

9 3-way motorized mixing valve Compulsory Not provided10 Secondary circulation pump Compulsory11 Underfloor heating safety Recommended

12 Room controller* OptionalControl (integrated in the module) that can be made remote

13CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

14 Filling valve with check valve Compulsory15 Solar sensor Compulsory PAW-A2W-TSSO

No. DescriptionType of

recommendationPanasonic Reference

1Hydraulic module with integrated filter + valves + domestic hot water CZ-NV1 kit

Compulsory Depending on power

2 Air separator Optional Not provided3 Magnetite filter Recommended Not provided4 Buffer tank Compulsory Not provided5 Secondary circulation pump Compulsory6 3-way motorized mixing valve Compulsory Not provided7 Underfloor heating safety Recommended

8 Room controller* OptionalControl (integrated in the module) that can be made remote

No. DescriptionType of

recommendationPanasonic Reference

9CZ-NS4P integrated optional circuit board + 1 PAW-A2W-TSBU probe + 2 PAW-A2W-TSHC probes

CompulsoryCZ-NS4P + PAW-A2W-TSBU + PAW-A2W-TSHC

10 Filling valve with check valve Compulsory11 Bivalent solar domestic hot water tank Recommended PAW-TG30C2E3STD -112 PAW-TS1 or TS2 sanitary sensor** Compulsory PAW-TS1 or TS2 13 Safety valve and closing valve Compulsory14 Thermostatic mixing valve Compulsory15 Solar transfer group Compulsory16 Sanitary expansion vessel + safety valve Recommended17 Sensor + PAW-A2W-TSSO solar sensor Compulsory PAW-A2W-TSSO

RENOVATION

RENOVATION

NEW

NEW

* Refer to the accessories at the end of the guide ** Must be selected if solar tank is not a TG30

and/or

and/or

and/or

and/or

and/orDCW

DCW

DHW

DCW

DCW

Main HP

Backup HP

Page 15: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

28 29

AQUAREA BI-BLOC HYDRAULIC SCHEME HEATING ONLY + EXTERNAL DOMESTIC HOT WATER TANK (optional)

3 Tichelmann loop cascaded heat pumps + 1 radiator heating zone with buffer tank via HPMSCHEMATIC DIAGRAM

No. DescriptionType of

recommendationPanasonic Reference

1 Inner hydraulic module x 3 Compulsory Depending on power2 Check valve Recommended Not provided3 Air separator Optional Not provided4 Magnetite filter Optional Not provided5 Filling valve with check valve Compulsory Not provided6 50 L buffer tank Compulsory Not provided

No. DescriptionType of

recommendationPanasonic Reference

7 Secondary circulation pump Compulsory Not provided

8HPM1 regulator + 1 HPMB1 probe + 1 HPMAH1 probe

CompulsoryPAW-HPM1 + PAW-HPMB1 + PAW-HPMAH1

9 HPMUH outdoor sensor Compulsory HPMUH

10 Room controller OptionalPAW-A2W-RTWIRED (wired) or PAW-A2W-RTWIRELESS (wireless)

No. DescriptionType of

recommendationPanasonic Reference

1 Inner hydraulic module x 3 Compulsory Depending on power

2 Directional 3-way domestic hot water valve Compulsory (delivered with Panasonic tanks + domestic hot water probe)

3 Check valve Recommended Not provided4 Air separator Optional Not provided5 Magnetite filter Recommended Not provided6 50 L buffer tank Compulsory Not provided

7HPM1 regulator + 1 HPMB1 sensor + 1 HPMAH1 sensor

CompulsoryPAW-HPM1 + PAW-HPMB1 + PAW-HPMAH1

No. DescriptionType of

recommendationPanasonic Reference

8 Secondary circulation pump Compulsory Not provided9 3-way motorized mixing valve Compulsory Not provided

10 Underfloor heating safety Recommended Not provided

11 Room controller OptionalPAW-A2W-RTWIRED (wired) or PAW-A2W-RTWIRELESS (wireless)

12 Filling valve with check valve Compulsory Not provided13 Safety valve and closing valve Compulsory Not provided14 Thermostatic mixing valve Optional Not provided15 Outdoor sensor Compulsory HPMUH

3 cascaded heat pumps with 2 radiator heating zones with buffer tank + underfloor heating + domestic hot water via HPMSCHEMATIC DIAGRAM

CASCADED CONFIGURATIONS

5

1

3

1 1

2 2 2

4

6 7

10

8

9

14

12

13

1 1 1

2

4

5

6

7 15

8

9

10

11

11

3 3 3

8

* Refer to the accessories at the end of the guide

Outdoor temperature sensor

Outdoor sensor (optional)

Reference: PAW-A2W-TSOD

Temperature sensor

Water flow temperature sensor (only with CZ-NS4P)

Reference: PAW-A2W-TSHC

Water temperature sensor

Buffer tank sensor (only with CZ-NS4P)

Reference: PAW-A2W-TSBU

Solar temperature sensor

Solar sensor probe (only with CZ-NS4P)

Reference: PAW-A2W-TSSO

Room sensor

Room sensor for supply temperature feedback

Reference: PAW-A2W-TSRT

Circuit board

Additional multifunction circuit board

Reference: CZ-NS4P

Room controller

Wired LCD room thermostat with weekly schedule timer

Reference: PAW-A2W-RTWIRED

Room controller

Wireless LCD room thermostat with weekly schedule timer

Reference: PAW-A2W-RTWIRELESS

RENOVATION

RENOVATION

and/or

DCW

DCW

DHW

H GENERATION REGULATIONMultizone (from 1 to 2 zones)

Page 16: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

3130

ACCESSORIES

Cloud connectivity

Connectivity interface for remote control

Reference: CZ-TAW1

Bivalent regulator

Regulator for the management of a boiler backup.

Reference: PAW-A2W-BIV

Water temperature sensor

Water flow sensor for the heating circuit for connection to the HPM manager.

Reference: PAW-HPMAH1

Temperature sensor

Temperature sensor with setpoint adjustment for connection to the HPM manager.

Reference: PAW-HPMR4

Outdoor temperature sensor

Outdoor temperature sensor for connection to the HPM manager

Reference: PAW-HPMUH

Water sensor

Water sensor for buffer tank for connection to the HPM manager.

Reference: PAW-HPMB1

Remote regulator with touch screen

Remote control regulator with integrated room probe. Touch interface.

Reference: PAW-HPMED

HPM regulator

Regulator for swimming pool, solar domestic hot water or remote domestic hot water management.

Reference: PAW-HPM1

Domestic Hot water Tanks (3-way valve, backup heater and sensor included)

Buffer tank

50 L buffer tank with polyurethane insulation (4 connections) equipped with an automatic drain and wall mounting

Reference: PAW-BTANK50L

Stainless steel tanks Enameled steel tanks2-coil steel enameled tank for solar installation + heat

pump)

Model DGC200 PAW-TD30C1E5 PAW-TG20C1E3STD-1 PAW-TG30C1E3STD-1 PAW-TG40C1E3STD-1 PAW-TG30C2E3STD-1

Water volume L 194 280 185 285 396 284

Dimensions Height/Diameter

mm 1,265 / 595 1,745 / 595 1,507 / 580 1,565 / 680 1,888 / 760 1,417 / 760

Electric booster kW 1.5 1.5 3 3 3 3

Material inside the tank

Stainless steel Stainless steel Enameled steel Enameled steel Enameled steel Enameled steel

Heating time HHHH HHHH HHHH HHHH HHHH HHHH

Loss of energy HHHH HHHH HHHH HHHH HHHH HHHH

Guarantee 10 years 10 years 2 years 2 years 2 years 2 years

3-way valve connection kit

Hot water kit with integrated 3-way valve

Reference: CZ-NV1

HYDRAULICALL-GENERATION REGULATIONCascade or multizone (from 1 to 6 zones)

Page 17: AQUAREA HYDRAULIC GUIDE - Panasonic PRO Club

32

Due t

o con

tinuo

us pr

oduc

t inn

ovat

ion, t

he da

ta in

this

cata

log is

valid

exce

pt fo

r typ

ogra

phica

l erro

rs an

d may

be su

bject

to m

inor m

odifi

catio

ns by

the m

anuf

actu

rer w

ithou

t prio

r not

ice in

orde

r to i

mpro

ve th

e pro

duct

. The

tota

l or p

artia

l rep

rodu

ction

of th

is ca

talog

is pr

ohibi

ted w

ithou

t the

expr

ess p

ermi

ssion

of P

anas

onic

UK Lt

d.