+ All Categories
Home > Documents > Ar 1112 33 Dbr Civil 11oct12 r0 Final

Ar 1112 33 Dbr Civil 11oct12 r0 Final

Date post: 14-Apr-2018
Category:
Upload: pravin1307
View: 236 times
Download: 0 times
Share this document with a friend

of 13

Transcript
  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    1/13

    DESIGN BASIS REPORT

    CIVIL

    INNOVATION CAPMUS MUMBAI

    Consultants Client

    Arnita SEZ Consultants Pvt. Ltd M/s. BASF INDIA LIMITED.305 to 308 Wellington Business Park 1

    3r

    Floor, Near Mittal Estate,

    Andheri East , Mumbai 400 059, India

    Tel: +91 22 67775200

    Fax: +91 22 67775299

    Mail:[email protected],

    [email protected]

    Mail: [email protected]

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    2/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :2 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    DOCUMENT APPROVAL SHEET

    Revision

    Sr. No. Rev. No. Date Issued on Remarks

    1. 0 12/10/12 APPROVAL

    ARNITA SEZ CONSULTANTS PVT.LTD.

    Name Signature Date

    Prepared By Pradip Nikam 10/10/12

    Checked By Prashant Khandekar 11/10/12

    Approved By Ramesh Chavan 12/10/12

    BASF INDIA LTD.

    Name Signature Date

    Reviewed By Mr. S. S. Naik

    Checked By

    Approved By

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    3/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :3 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    Sr. No. CONTENT

    1 Project Brief

    2 Site Location

    3 Provision of Future Horizontal / Vertical Expansion

    4 Geotechnical Observation

    5 Design Units

    6 Unit Weight of Materials Used

    7 Method of Design and Conceptualization.

    8 Grade of Concrete and Steel Used

    9 Design Loads

    10 Basic Loads and Load Combinations

    11 Standard Codes Used

    12 Softwares Used

    13 Building Drawings / Layouts Used

    14 Recommendations

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    4/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :4 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    1. Project Brief :M/s BASF India Ltd. proposes to put up Innovation Campus Mumbai project facility at their

    Turbhe site, Navi Mumbai. The facility contains mainly 3 buildings, viz. Main building, Kilo lab

    building, Parking structure, Utility Area and other infrastructure facility like Process water

    tank, Fire water tank, Solvent store and pipe rack.

    The proposed Main building is Ground + 12 storeys and the approximate built up area is

    5,00,000 sq.ft. The building houses various areas like Office, Standard labs, Technology labs,

    Application labs, Auditorium and Dining area. The total height of building measured from

    ground is 60 m approximately.

    The proposed Kilo lab building is ground + 4 storeys structure with a total built up area of

    60,000 sq.ft. The building houses stores, leather lab, construction chemicals lab and kilo lab.

    The total height of structure measured from ground is 27 m approximately.

    The proposed parking building shall be ground + 10 storeys with a car parking for 650 cars

    approximately. The height of building measured from ground is 31 m approximately.

    The utility area is proposed to be close to the Main building. The various utilities like cooling

    tower, DG, transformer, Breaker, STP and rainwater harvesting tank and flushing tank areproposed.

    The existing Fire water tank and the existing Process water tank provided presently on the

    west side boundary are proposed to be demolished and reconstructed near the east side

    boundary. The tanks will be designed for existing + proposed capacity after adding the water

    requirements for the proposed buildings.

    As the proposed buildings will be located on existing site, various existing structures will also

    be demolished. The underground utilities also will be rerouted or removed depending onthe requirements.

    This report describes the overall design brief for the systems proposed and to be installed for

    Main building. The report will be extended for other structures after conclusion of the

    structures.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    5/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :5 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    As only Main Building is concluded and released for civil design, DBR for other

    buildings and structures are not included here.

    2. Site Location: The site is located at TTC Industrial area, Turbhe, Navi Mumbai. Site comes under MPCB RED zone Approachable by a 12 M wide Turbhe- Belapur Road.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    6/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :6 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    3. Provision of Future Horizontal / Vertical Expansion:This is covered in the Input summary of individual structures.

    4. Geotechnical Observation:The work of soil investigation for tentative SBC is carried out by V.T.GANPULE

    GROUND ENGINEERING CONSULTANT, Mumbai. The results are worked out by

    observation of two trial pits on site and lab reports of samples collected from the trial

    pits. The tentative recommended SBC for first stage of the project is 80 T/m2

    at 2.5m

    depth from N.G.L. The final SBC to be reconfirmed by bore explorations and lab study

    after demolition of existing structures.

    5. Design Units:IS metric units are used to design the project.

    6. Unit weight of materials used:Material Grade Density Remark

    PCC M:20 20 kN/m3

    RCC M:75 25 kN/m3

    Steel Fe-500 D 78.5 kN/m3 Reinforcement

    Brick-

    20 kN/m

    3

    With plaster

    Siporex - 10 kN/m3 With plaster

    7. Method of Design and Conceptualization:The aim of design is to achieve an acceptable probability that the structures

    being designed will perform satisfactorily during their intended life as per IS code. The

    structures are designed to sustain all the presumed floor loads and have adequate

    durability and resistance to the effects of earthquake and fire, for which they are

    designed. It shall be further understood that design calculations alone do not produce

    a safe, serviceable, durable structure. Suitable materials, good workmanship, quality

    control and good supervision are required to translate the designs into structures as

    intended by the Design Engineer.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    7/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :7 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    The building is considered without expansion joint, to avoid the issues of

    waterproofing and finishing of wide gap from outside and inside.

    The structures are designed based on Limit State Method of Design as per IS

    code provision.

    Main BuildingRefer Input summary for design input details.

    The building is RCC framed structure with post tensioned floor; excluding

    staircases. Shear walls are provided at various locations to take care of the lateral

    forces due to earthquake and wind. The design and analysis is done by using ETAB,

    SAFE and ADAPT softwares also standard excel spread sheets are used for foundation

    design. Earthquake analysis of building is carried out by Response Spectrum method

    by using ETAB software.

    8. Grade of Concrete and steel used:Self-compacting M: 75 grade of concrete and Fe 500D steel is considered for

    design of the structure.

    9. Design Loads:9.1 Dead load:

    Dead load includes unit weight/mass of materials, components in a building that

    apply to the dead weight in the design of buildings and shall be considered as per IS:

    875 (Part 1) 1987 (Reaffirmed: 1997). It includes self-weight, weight of false ceiling,

    floor finish and water proofing load etc. Details of dead load on each floor are as per

    input summary provided for each of the building/structure.

    9.2 Imposed load:

    Imposed / live loads shall be considered as per IS: 875 (Part 2) 1987

    (Reaffirmed: 1997). However, presence of any heavy equipment in any particular area

    needs to be informed to the design engineer and it may require providing additional

    members. Details of Imposed/ live load on each floor are as per input summary

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    8/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :8 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    provided for each of the building/structure.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    9/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :9 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    9.3 Earthquake Load:

    The project is located at Turbhe Navi Mumbai and as per IS: 1893 -2002

    (Part-1)the region falls under zone III. Details of earthquake load are as per input

    summary provided for each of the building/structure.

    9.4 Wind load:

    The project is located at Turbhe Navi Mumbai and as per IS 875 (Part 3) 1987

    (Reaffirmed: 1997)the region falls under basic wind speed 44 m/s. Details of wind

    load are as per input summary provided for each of the building/structure.

    9.5 Any Specific Additional Load.

    Client has to inform, in case of any specific loads to be considered.

    10.Basic loads and Load Combinations:Following are the basic loads used for building design.

    1 Dead Load (DL) - Self-weight/ finish/suspended ceiling etc.2 Live Load (LL) - Live Load.3 Earthquake in X (EQX) - Earthquake Load in X direction (+ve and -ve)4 Earthquake in Y (EQY) - Earthquake Load in Y direction (+ve and -ve)5 Wind load (WLX) - Wind load in X direction (+ve and -ve)6 Wind load (WLY) - Wind load in Y direction (+ve and -ve)7 Temperature load (TL) - Loads due to temperature variation.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    10/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :10 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    Following are the load combinations used for building design as per IS 875 (Part 5) 1987

    (Reaffirmed: 1997)Load combo. No. Load Case details

    11 1.5 ( DL + LL )

    Load combinations for Earthquake and Temp. Loads

    12 1.5 ( DL + EQX + TL)

    13 1.5 ( DL EQX + TL )

    14 1.5 ( DL + EQY + TL )

    15 1.5 ( DL EQY + TL )

    16 1.2 ( DL + LL + EQX + TL)

    17

    1.2 ( DL + LL EQX + TL)

    18 1.2 ( DL + LL + EQY + TL)

    19 1.2 ( DL + LL EQY + TL )

    20 0.90 ( DL + 1.5 EQX + TL )

    21 0.90 ( DL 1.5 EQX + TL)

    22 0.90 ( DL + 1.5 EQY + TL)

    23 0.90 ( DL 1.5 EQY + TL)

    Load combinations for Wind and Temp. Loads

    Load combo. No. Load Case details

    24 1.5 ( DL + WX + TL )

    25 1.5 ( DL WX + TL )

    26 1.5 ( DL + WY + TL )

    27 1.5 ( DL WY + TL )

    28 1.2 ( DL + LL + WX + TL )

    29 1.2 ( DL + LL WX + TL )

    30 1.2 ( DL + LL + WY + TL )

    31 1.2 ( DL + LL WY + TL)

    32 0.90 ( DL + 1.5 WX + TL)

    33 0.90 ( DL 1.5 WX + TL )

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    11/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :11 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    34 0.90 ( DL + 1.5 WY + TL)

    35 0.90 ( DL 1.5 WY+ TL )

    11.Standard Codes Used:Code No. Indian Standard Code Name

    IS 456 - 2000 Plain and Reinforced Concrete - Code of Practice

    (Fourth Revision).

    IS 1893-2002 Criteria for Earthquake Resistant Design of Structures Part 1 -

    General Provisions and Buildings.

    IS 13920-1993

    Edition 1.2

    Ductile Detailing of Reinforced Concrete Structures Subjected to

    Seismic Forces - Code of Practice.

    IS 800 - 1984 Code of Practice for General Construction in steel (First Revision).

    IS 875 1987

    Part 1

    Code of Practice For Design Loads (Other Than Earthquake) For

    Buildings and Structures. Dead Loads.( Second Revision )

    IS 875 1987

    Part 2

    Code of Practice For Design Loads (Other Than Earthquake) For

    Buildings and Structures. Imposed Loads.( Second Revision )

    IS 875 1987

    Part 3

    Code of Practice For Design Loads (Other Than Earthquake) For

    Buildings and Structures. Wind Loads.( Second Revision )

    NBC National Building Code of India 2005

    12.Softwares Used:Softwares used for structural analysis and designs of the building are ETAB-9.7.3,

    SAFE V12 and ADAPT PT 2012.

    13.Building drawings / Layouts Used:Sr.No Drawing Drawing No

    (1112-33-PER-ABA - )

    Date

    1 GROUND FLOOR PLAN - 101 - R2 12.10.2012

    2 FIRST FLOOR PLAN - 102 - R2 12.10.2012

    3 SECOND & THIRD FLOOR PLAN -103 & 104 - R2 12.10.2012

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    12/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :12 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    4 FOURTH TO NINTH FLOOR PLAN -105 to 110 - R2 12.10.2012

    5 TENTH FLOOR PLAN - 111- R2 12.10.2012

    6 ELEVENTH FLOOR PLAN - 112 R1 12.10.2012

    14.Recommendations:14.1 Fire resistance:

    The structural elements are designed for a fire resistance of Two hours. In

    case of specific requirement from the user, over and above the requirements of the

    code, same shall be noted and structural elements shall be detailed accordingly.

    14.2 Cracking:Adherence to the detailing rules will generally take care of these criteria.

    However, in case, cracking has to be limited to any particular width, reference shall be

    made to the provisions of the code. Checks in RCC or Pre -stressed Concrete design

    shall be done. Design is done for cracked section.

    14.3 Vibration:

    Isolation of source of vibration shall be done to avoid discomfort to the

    occupants, structural damage and to check interference of functions of various

    sensitive instruments. This may be achieved with flexible structural elements. Thedesigner will do the detailing based on user requirements. Checks for equipment load

    details in regards to vibration are done. All equipments should be provided with anti-

    vibration pads.

    14.4 Durability:

    The designer checks for the effects of the environment for which the structure

    is exposed. Adequate covers have been provided and reasons for extra cover

    thickness shall be given, wherever required. Covers provided as per IS 456. No extra

    cover required.

    14.5 Workmanship:

    Dimensional tolerances, good and proper amount of curing are essentials for a

    good workmanship. Any extra deviation can introduce extra moments and also less

    curing will introduce cracks. In case of severe environments, specialist products shall

    be specified.

  • 7/30/2019 Ar 1112 33 Dbr Civil 11oct12 r0 Final

    13/13

    Arnita SEZ Consultants Pvt.Ltd. M/s. BASF INDIA LTD.

    Prepared By : Mr. Pradip Nikam

    Approved By : Mr. Ramesh Chavan

    DESIGN BASIS REPORT

    CIVIL

    Page No. :13 o f 13

    Rev. : 0

    Date : 12-10

    -2012

    14.6 Special Hazards:

    The building is classified as non-hazardous. No extra partial safety factors are

    used. Structure in question is classified as ordinary hazard, hence does not qualify as

    building for effects of severe hazards.


Recommended