17
This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429 Signed and sealed for and on behalf of Exova (UK) Limited trading as Warrington Certification Sir Ken Knight Paul Duggan Chairman Certification Manager Impartiality Committee CERTIFICATE OF APPROVAL No CF 5072 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 Page 1 of 17 ARABIAN VERMICULITE INDUSTRIES P.O. Box 7137, Dammam 31462 Tel: +966 3847 1450 Fax: +966 3847 1575 Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: _____________________________________________________________________________________________________ CERTIFIED PRODUCT TECHNICAL SCHEDULE Avikote WB1200 TS15 Intumescent Coatings for Steelwork Issued: 15 th March 2012 Reissued: 18 th November 2016 Valid to: 11 th February 2018
Transcript
Page 1: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

Signed and sealed for and on behalf of Exova (UK) Limited trading as Warrington Certification

Sir Ken Knight Paul Duggan Chairman Certification Manager

Impartiality Committee

CERTIFICATE OF APPROVAL No CF 5072

This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products

The undermentioned products of 1

Page 1 of 17

ARABIAN VERMICULITE INDUSTRIES

P.O. Box 7137, Dammam 31462 Tel: +966 3847 1450 Fax: +966 3847 1575

Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions

appended hereto: _____________________________________________________________________________________________________

CERTIFIED PRODUCT TECHNICAL SCHEDULE

Avikote WB1200 TS15 Intumescent Coatings for Steelwork

Issued: 15th March 2012

Reissued: 18th November 2016

Valid to: 11th February 2018

Page 2: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 2 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 1. This approval relates to the use of Avikote WB1200 for the fire protection of I-shaped

steel sections, hollow steel sections and solid steel rods. The precise scope is given in Tables 1 to 4I which show the total dry film thickness of Avikote WB1200 (excluding primer and top sealer) required to provide fire resistance periods in accordance with BS476: Part 21: 1987. The scope includes periods of fire resistance of 30 minutes up to 120 minutes for differing I-sections, hollow sections and section factors (A/V), and for periods of fire resistance of 30 minutes up to 120 minutes for solid steel rods with differing section factors (A/V) and design temperatures in the range 350

oC to 750

oC.

2. This certification is designed to demonstrate compliance of the product or system

specifically with Approved Document B (England and Wales), Section D of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account.’

3. The products are approved on the basis of:

i) Initial type testing. ii) A design appraisal against TS15.

iii) Certification of quality management system to ISO 9001: 2000. iv) Inspection and surveillance of factory production control v) Audit testing

4. The data referring to three-sided fire exposure of beams relate to beams supporting

concrete floor slabs. Separate consideration is required where this is not the case. 5. The data shown are applicable to steel sections blast cleaned to Swedish Standard

Sa 2.5 or equivalent and primed with a suitable and compatible primer. Specifications of surface preparations, primers and top sealers is available from Arabian Vermiculite Industries whose responsibility is to ensure that Avikote WB1200 is compatible for use in respect of both ambient and fire conditions. The total dry film thickness of primer should not exceed 0.1mm.

6. The data shown is applicable to Avikote WB1200 applied by spray to horizontal, vertical,

flexural and compression members supporting loads up to the maximum design loads specified in BS449: Part 2.

7. The approval relates to on going production. Product and/or its immediate packaging is

identified with the manufacturers’ name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate.

Page 3: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 3 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 1

Table 1: Three Sided Protection to Universal Beams - 620oC design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes

Section factor

m-1

Thickness mm

Section factor m

-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

320 0.929 215 0.929 90 0.929 210 1.696

220 0.932 95 0.949 215 1.728

225 0.961 100 0.981 220 1.761

230 0.991 105 1.014 225 1.793

235 1.020 110 1.046 230 1.826

240 1.049 115 1.078 235 1.858

245 1.079 120 1.111 240 1.891

250 1.108 125 1.143 245 1.923

255 1.138 130 1.176 250 1.956

260 1.167 135 1.208 255 1.988

265 1.197 140 1.241 260 2.021

270 1.226 145 1.273 265 2.080

275 1.256 150 1.306 270 2.180

280 1.285 155 1.338 275 2.280

285 1.315 160 1.371 280 2.380

290 1.344 165 1.403 285 2.480

295 1.374 170 1.436 290 2.580

300 1.403 175 1.468 295 2.680

305 1.433 180 1.501 300 2.780

310 1.462 185 1.533 305 2.880

315 1.492 190 1.566 310 2.980

320 1.521 195 1.598 315 3.070

200 1.631 320 3.145

205 1.663

DFT is intumescent thickness only. Table applies to beams with concrete slab. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 4: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 4 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 1 continued

Table 1: Three Sided Protection to Universal Beams - 620oC

design temperature

Thickness required for a Fire Resistance duration of

120 minutes

Section factor m

-1 Thickness

mm Section factor

m-1

Thickness mm

45 0.929 185 2.912

50 0.966 190 2.970

55 1.056 195 3.028

60 1.145 200 3.087

65 1.235 205 3.145

70 1.324 210 3.204

75 1.414 215 3.262

80 1.503 220 3.321

85 1.593 225 3.380

90 1.682 230 3.438

95 1.772 235 3.497

100 1.861 240 3.555

105 1.951 245 3.614

110 2.040 250 3.672

115 2.098 255 3.731

120 2.156 260 3.789

125 2.214 265 3.848

130 2.273 270 3.906

135 2.331 275 3.965

140 2.389 280 4.023

145 2.447 285 4.082

150 2.505 290 4.140

155 2.563 295 4.199

160 2.621 300 4.258

165 2.680 305 4.316

170 2.738 310 4.375

175 2.796 312 4.400

180 2.854

DFT is intumescent thickness only. Table applies to beams with concrete slab. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 5: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 5 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 2

Table 2: Four sided protection to Universal Columns – 550oC design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes

Section factor m

-1 Thickness

mm Section factor

m-1

Thickness mm

Section factor m

-1 Thickness

mm

320 0.917 145 0.917 235 1.763

150 0.939 240 1.812

155 0.988 245 1.860

160 1.036 250 1.909

165 1.085 255 1.957

170 1.133 260 2.006

175 1.182 265 2.054

180 1.230 270 2.103

185 1.278 275 2.151

190 1.327 280 2.200

195 1.375 285 2.248

200 1.424 290 2.297

205 1.472 295 2.345

210 1.521 300 2.394

215 1.569 305 2.442

220 1.618 310 2.491

225 1.666 315 2.539

230 1.715 320 2.588

DFT is intumescent thickness only. Table applicable to 4 sided beams. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 6: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 6 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 2 continued

Table 2: Four sided protection to Universal Columns – 550oC design temperature

Thickness required for a Fire Resistance duration of

90 minutes 120 minutes Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

45 0.917 185 2.504 40 0.917 140 3.348

50 0.933 190 2.562 45 1.008 145 3.471

55 0.991 195 2.621 50 1.131 150 3.587

60 1.050 200 2.679 55 1.254 155 3.671

65 1.108 205 2.737 60 1.378 160 3.756

70 1.166 210 2.795 65 1.501 165 3.841

75 1.224 215 2.853 70 1.624 170 3.925

80 1.282 220 2.910 75 1.747 175 4.010

85 1.341 225 2.967 80 1.870 180 4.094

90 1.399 230 3.024 85 1.993 185 4.179

95 1.457 235 3.080 90 2.117 190 4.263

100 1.515 240 3.137 95 2.240 195 4.348

105 1.573 245 3.194 100 2.363 200 4.432

110 1.631 250 3.251 105 2.486 205 4.519

115 1.690 255 3.308 110 2.609 210 4.615

120 1.748 260 3.365 115 2.732 215 4.712

125 1.806 265 3.422 120 2.856 220 4.808

130 1.864 270 3.479 125 2.979 225 4.904

135 1.922 275 3.536 130 3.102 230 5.000

140 1.981 280 3.632 135 3.225

145 2.039 285 3.787

150 2.097 290 3.942

155 2.155 295 4.097

160 2.213 300 4.252

165 2.271 305 4.407

170 2.330 310 4.547

175 2.388 315 4.663

180 2.446 320 4.779

DFT is intumescent thickness only. Table applicable to 4 sided beams. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 7: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 7 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 3

Table 3: Hollow Column Sections – 520oC design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes

Section factor m

-1

Thickness mm

Section factor m

-1

Thickness mm

Section factor m

-1

Thickness mm

Section factor m

-1

Thickness mm

120 0.484 225 1.339 40 0.683 140 2.064

125 0.496 230 1.381 45 0.756 145 2.122

130 0.538 235 1.424 50 0.828 150 2.180

135 0.581 240 1.466 55 0.900 155 2.238

140 0.623 245 1.508 60 0.972 160 2.296

145 0.665 250 1.550 65 1.044 165 2.353

150 0.707 255 1.577 70 1.117 170 2.411

155 0.749 260 1.603 75 1.189 175 2.469

160 0.791 265 1.630 80 1.261 180 2.527

165 0.833 270 1.656 85 1.333 185 2.798

170 0.876 275 1.683 90 1.406 190 3.212

175 0.918 280 1.709 95 1.478 195 3.626

180 0.960 285 1.736 100 1.550 200 4.040

185 1.002 290 1.762 105 1.622 205 4.258

190 1.044 295 1.789 110 1.694 210 4.476

195 1.086 300 1.815 115 1.767 215 4.695

200 1.129 305 1.841 120 1.833 220 4.913

205 1.171 310 1.866 125 1.891 225 5.131

210 1.213 315 1.892 130 1.949 230 5.349

215 1.255 320 1.917 135 2.007

220 1.297

DFT is intumescent thickness only. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 8: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 8 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 3 continued

Table 3: Hollow Column Sections – 520oC design temperature

Thickness required for a Fire Resistance duration of

90 minutes 120 minutes

Section factor m

-1 Thickness

mm Section factor

m-1

Thickness mm

40 0.688 40 1.379

45 0.874 45 1.911

50 1.060 50 2.444

55 1.246 55 2.976

60 1.433 60 3.508

65 1.619 65 4.040

70 1.805 70 4.177

75 1.991 75 4.314

80 2.178 80 4.451

85 2.364 85 4.589

90 2.550 90 4.726

95 2.736 95 4.863

100 2.923 100 5.000

105 3.109 105 5.137

110 3.295 110 5.274

115 3.481 115 5.411

120 3.668 120 5.549

125 3.854

130 4.040

135 4.573

140 5.107

DFT is intumescent thickness only. Additional result tables for a range of steel design temperatures are also available. Consult manufacturer.

Page 9: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 9 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4A

Table 4A: Protection to Solid Steel Rods – 350oC

Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

105 1.457 60 1.457

110 1.667 65 2.094

115 1.906 70 2.819

120 2.146 75 3.545

125 2.385 80 4.270

130 2.573

135 2.684

140 2.795

145 2.906

150 3.017

155 3.128

160 3.238

165 3.349

170 3.460

175 3.571

180 3.682

185 3.793

190 3.903

195 4.014

200 4.125

DFT is intumescent thickness only.

Page 10: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 10 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4B

Table 4B: Protection to Solid Steel Rods – 400oC

Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

125 1.457 55 1.457

130 1.619 65 1.554

135 1.809 70 1.997

140 1.998 75 2.440

145 2.188 80 2.884

150 2.377 85 3.327

155 2.548 90 3.770

160 2.643 95 4.214

165 2.738 100 4.633

170 2.833

175 2.928

180 3.023

185 3.118

190 3.213

195 3.308

200 3.403

DFT is intumescent thickness only.

Page 11: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 11 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4C

Table 4C: Protection to Solid Steel Rods – 450oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

145 1.457 60 1.495 40 1.630

150 1.502 65 1.702 45 1.833

155 1.648 70 1.909 50 2.037

160 1.795 75 2.115 55 2.241

165 1.942 80 2.322 60 2.445

170 2.089 85 2.529 65 3.326

175 2.235 90 2.848

180 2.382 95 3.167

185 2.529 100 3.487

190 2.615 105 3.806

195 2.701 110 4.125

200 2.786 115 4.444

DFT is intumescent thickness only.

Page 12: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 12 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4D

Table 4D: Protection to Solid Steel Rods – 500oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

170 1.457 65 1.457 40 1.457

175 1.523 70 1.532 45 1.624

180 1.643 75 1.749 50 1.804

185 1.763 80 1.966 55 1.985

190 1.882 85 2.182 60 2.165

195 2.002 90 2.399 65 2.346

200 2.122 95 2.620 70 2.526

100 2.848 75 3.668

105 3.076 77 4.125

110 3.304

115 3.532

120 3.760

125 3.988

130 4.216

135 4.444

DFT is intumescent thickness only.

Page 13: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 13 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4E

Table 4E: Protection to Solid Steel Rods – 550oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

200 1.457 75 1.457 40 1.457

80 1.458 45 1.496

85 1.726 50 1.662

90 1.994 55 1.828

95 2.261 60 1.994

100 2.529 65 2.160

105 2.682 70 2.327

110 2.836 75 2.493

115 2.989 77 2.671

120 3.143 80 3.107

125 3.296 85 3.834

130 3.450 87 4.125

135 3.603

140 3.757

145 3.910

150 4.064

155 4.217

160 4.371

165 4.524

DFT is intumescent thickness only.

Page 14: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 14 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4F

Table 4F: Protection to Solid Steel Rods – 600oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

200 1.457 85 1.457 45 1.457

90 1.495 50 1.522

95 1.702 55 1.674

100 1.909 60 1.826

105 2.115 65 1.978

110 2.322 70 2.130

115 2.529 75 2.283

120 2.662 80 2.435

125 2.795 85 2.739

130 2.928 90 3.272

135 3.061 95 3.805

140 3.194 100 4.338

145 3.327

150 3.460

155 3.593

160 3.726

165 3.859

170 3.992

175 4.125

180 4.258

185 4.391

190 4.524

DFT is intumescent thickness only.

Page 15: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 15 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4G

Table 4G: Protection to Solid Steel Rods – 650oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

200 1.457 100 1.457 60 1.457 40 1.457

105 1.483 65 1.537 45 1.538

110 1.710 70 1.743 50 1.709

115 1.938 75 1.949 55 1.880

120 2.165 80 2.155 60 2.051

125 2.393 85 2.361 65 2.221

130 2.573 90 2.599 70 2.392

135 2.684 95 2.962 75 2.848

140 2.795 100 3.326 80 4.444

145 2.906 105 3.689

150 3.017 110 4.052

155 3.128 115 4.416

160 3.238

165 3.349

170 3.460

175 3.571

180 3.682

185 3.793

190 3.903

195 4.014

200 4.125

DFT is intumescent thickness only.

Page 16: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 16 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4H

Table 4H: Protection to Solid Steel Rods – 700oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

200 1.457 115 1.457 70 1.457 45 1.457

120 1.495 75 1.459 50 1.561

125 1.702 80 1.726 55 1.717

130 1.909 85 1.992 60 1.873

135 2.115 90 2.259 65 2.029

140 2.322 95 2.526 70 2.186

145 2.529 100 2.693 75 2.342

150 2.610 105 2.859 80 2.498

155 2.690 110 3.026 85 3.441

160 2.771 115 3.192 90 4.581

165 2.851 120 3.359

170 2.932 125 3.525

175 3.013 130 3.692

180 3.093 135 3.859

185 3.174 140 4.025

190 3.254 145 4.192

195 3.335 150 4.358

200 3.416 155 4.525

DFT is intumescent thickness only.

Page 17: ARABIAN VERMICULITE INDUSTRIES...This certificate is the property of Exova (UK) Limited trading as Warrington Certification Reg. Office: Exova (UK) Limited, Lochend Industrial Estate,

This certificate is the property of Exova (UK) Limited trading as Warrington Certification

Reg. Office: Exova (UK) Limited, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Co. Reg. No. SC070429

CERTIFICATE No CF 5072

ARABIAN VERMICULITE INDUSTRIES

Page 17 of 17 Signed E/057

Issued: 15th

March 2012 Reissued: 18

th November 2016

Valid to: 11th

February 2018

Avikote WB1200 Table 4I

Table 4I: Protection to Solid Steel Rods – 750oC Design temperature

Thickness required for a Fire Resistance duration of

30 minutes 60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

Section factor

m-1

Thickness mm

200 1.457 140 1.457 85 1.457 60 1.457

145 1.619 90 1.537 65 1.576

150 1.858 95 1.949 70 1.792

155 2.098 100 2.361 75 2.009

160 2.337 105 2.592 80 2.226

165 2.543 110 2.701 85 2.442

170 2.613 115 2.811 90 3.061

175 2.683 120 2.920 95 3.948

180 2.753 125 3.030

185 2.823 130 3.139

190 2.893 135 3.249

195 2.963 140 3.358

200 3.033 145 3.468

150 3.577

155 3.687

160 3.796

165 3.906

170 4.015

175 4.125

180 4.235

185 4.344

190 4.454

DFT is intumescent thickness only.


Recommended