VA TECH Transmission & Distribution
1Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Overcurrent and Earth Fault Protection
VA TECH Transmission & Distribution
2Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
ARGUS 1-6 - Protection Functions
VA TECH Transmission & Distribution
3Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Phase and Earth Fault Characteristics
4 Independent Stages1 x transient free LOWSET, 0.1 - 52.5 In, 0 - 20 sec1 x SHAPED, 0.1 - 2.5In, T.M. 0.025 - 1.6
NI, EI, VI, LTI, DTL2 x transient free HIGHSET , 0.1 - 52.5 In, 0 - 20 sec
SHAPED
LS
HS1
HS2
TIME
CURRENT
24ms
VA TECH Transmission & Distribution
4Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Grading with Electro-Mechanical RelaysFAULTClashing conductors or re-sealing cableR1R2
Loss of grading /discrimination may occur:
If R2 Electromechanical & R1 Inst. reset or if R2 DTL reset and R1 electromechanical
Some compromise may be necessary where more than two relay points are in series
R3D
isc
Trav
el
Electro-mechanical Relay
Time
TRIP
% o
f Alg
orith
m
Argus (Inst. Reset)
Time
Argus (DTL Reset)
TRIP
VA TECH Transmission & Distribution
5Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
C.B. Failure Protection
RL1 RL11
&
Protectionalgorithmoperated
Fault triggeroutput relay
operatedDT L 10 - 20s
DT L 20 - 20s
RL1 RL11
T im e D elay > C B O perating T im e +Safety M arg in
O utput relays arranged to tripupstream circuit breaker
VA TECH Transmission & Distribution
6Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Trip circuit supervision - H6 Scheme
T RIPCOIL
52a
52a
52b
+ -
RL1 RL11
ARG US
TRIP
C.B .
Fuse Link
If trip circuit not healthy relaydisp lays "T RIP CCT FAIL"
TRIP CCT FAIL
2K7
Recom m endedS.I. Settings:
20m s p .u.400m s d .o .O /P 1 - 3 (NC contact)
External resistor = 2K7 O hm s110V system 50V Status Input
Rem ote Alarm
T CS can be set for each status input andtherefore can be used to monitor:
1st and 2nd trip coils or,all phases of phase segregated CB
VA TECH Transmission & Distribution
7Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Status Inputs
Initiate output relaysTime delayed pick-upTime delayed drop-off
Inhibit characteristic (except starters)
Change settings groups
Reset LEDs and Output Contacts
Trigger Waveform Storage
Synchronise Clock
Opto-isolated inputs
VA TECH Transmission & Distribution
8Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus protection summary
Wide range of IDMTL curves and DTL
Three independent high set/low set characteristics
Sensitive/restricted earth fault
Circuit breaker fail protection
Delayed or instantaneous reset
Low AC and DC burdens
True RMS measurement
Combined 1A and 5A current inputs
Full communications to IEC 60870-5-103
Self supervision/monitoring features
Trip circuit supervision
VA TECH Transmission & Distribution
9Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus Applications
VA TECH Transmission & Distribution
10Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Blocking scheme logic
HS150msDTL
HS150msDTL
Inst. LSBlockInst. LSBlock
Power Flow
Metallic connection required between relaying points
IDMT characteristic of relays toward source have a supplementary HS1 trippingcharacteristic with a DTL of 50ms
Inst. LS output of downstream relay arranged to block upstream HS1 characteristic
If metallic link is lost graded IDMT protection is not affected
VA TECH Transmission & Distribution
11Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Busbar ProtectionSettings
GE
MFA
CTO
R 1
CA
PA
CITO
R 1
TEN
SIO
N
STA
ND
3
STA
ND
2
STA
ND
1
PA
Y O
FF
GE
MFA
CTO
R 2
CA
PA
CITO
R 2
STA
ND
4
STA
ND
5
RE
EL
RE
EL
938A250A
938A250A
938A250A
938A250A
190A30A
780A120A
560A80A
480A80A
480A80A
240A40A
84A12A
2400A, 0.15s320A, 0.15s
2400A, 0.15s320A, 0.15s
2400A, 0.15s320A, 0.15s
BLOCK SIGNAL
Output from RL1 P/F & E/F Starters, Instantaneous operation
P/F LS TRIP SETTINGE/F LS TRIP SETTING
P/F BLOCKE/F BLOCK
780AFWD. P/F BLOCK SETTING
SI1 SI1 SI1INHIBIT LS
VA TECH Transmission & Distribution
12Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
RADIAL SUBSTATION
Startgenerators
Select alternate settings group
LocalGeneration
Industrial system draws power from grid system duringnormal operation
Argus relays normally use settings group 1
On loss of mains:Local generation switched in.Non essential loads trippedArgus relays on essential circuits switched to settingsgroup 2 to reflect new load and fault currents
Non-essentialloads
Trip non-essential loads
Alternative setting groups
VA TECH Transmission & Distribution
13Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Applications Summary
Blocking schemes for faster clearance
Busbar zone schemes for low cost busbar protection
Alternative protection setting groups
Status inputs can be time lagged for pick-up and/or drop-off and operate output contact(s)
VA TECH Transmission & Distribution
14Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus family of relays
Argus 2 - directional overcurrent and earth fault with bi-directional elements
Argus 3/4 - integrated overcurrent, earth fault & autoreclose 4 shot autoreclose fully programmable with different sequences for phase fault, earth fault and from an external signal
Argus 5/6 - directional overcurrent and earth fault with autoreclose
Argus 7 - check synchronising relay with independent settings for check and system synchronising, dead line/bus switching and manual close guard feature
Argus 8 - Under/overvoltage Under/overfrequency relay
VA TECH Transmission & Distribution
15Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Dual Directional ElementsIndependent FWD. And REV. SettingsIndependent control for each characteristicSeparate outputs for FWD. And REV.
20ms operating time for directional detection
Directional P/F300 or 450 deg. (I w.r.t. V)
Directional E/F00, -150, -450,-650, -900 (I w.r.t. V)
Directional SEF-900
2 out of 3 Gate Overcurrent Logic
Argus 2
CharacteristicAngle (C .A.)
C.A.+900
C.A.+900
FW D .ZO N E
REV.ZO NE
Forward zoneleading boundary+ 87.50
Forward zoneleading boundary+ 87.50
VA TECH Transmission & Distribution
16Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 4/64 pole relay with auto-reclose
1 to 4 shots (instantaneous or IDMT), 5th is Lockout IDMTA.R. sequences for P/F, E/F, SEF, ExternalSupports sequence reclosingFrequent operations counterTrip and Lockout (Supervisory)Hot line Working
CB Open/Closed Status Indication
9 Status Inputs, 7 Output Contacts
User Configurable Alarm Inputs13 alphanumeric characters
R6 / R8 Case
VA TECH Transmission & Distribution
17Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 4/6 - Sequence Co-ordinated Reclosing
Pole MountedRecloser
LocalConsumers
Consumers
2 Inst +Time Lag
2 Inst + GradedTime Lag
PMR
Argus
2 'Delayed' Inst +Graded Time Lag
Resetbefore trip
ArgusCount
A
Argus 4/6 configured for sequence co-ordination
Reduces supply interruption to localcustomers on occurrence of remote fault
VA TECH Transmission & Distribution
18Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 7 - Key Features
Check and system synchronising relay for 50Hz or 60Hz systems
Independent phase angle (Line and Bus Voltages), slip frequency (Line and Bus Freq) and slip timer settings
Independent undervoltage blocking and differential voltage blocking (Line and Bus)
Split system detection with split timer (90-170 Deg)
Options for dead line and/or dead bus charging (Sync bypass logic)
Integrated manual close guard function
Line & bus voltage trimming
VA TECH Transmission & Distribution
19Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 7 - Close guard feature Prevents an operator from initiating a manual circuit breaker close before the check synchronising relay operates
Removes the need for additional relays e.g. B66
VA TECH Transmission & Distribution
20Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 8 product variants
AG8 - 104-112
Three phase 4 stage under/overvoltage + negative sequence overvoltage
AG8 - 204-212
Three phase 4 stage under/overvoltage + negative sequence overvoltage + 4 stage under/overfrequency
AG8 - 101-103
Single phase 4 stage under/overvoltage + neutral voltage displacement
AG8 - 201-203
Single phase 4 stage under/overvoltage + neutral voltage displacement + 4 stage under/overfrequency
VA TECH Transmission & Distribution
21Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
ARGUS Interface and Monitoring
VA TECH Transmission & Distribution
22Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Alpha Numeric LCD Display2 rows, 16 characters
5 Pushbuttons and available with cover on:
View menuReset fault data displayReset latched output relaysReset TRIP LED
3 LED’sHealthyTripStart
Operator interface
VA TECH Transmission & Distribution
23Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Menu Structure R ELAYID ENT IF IER
SET T ING SDISPLAY
MO D E
SYST EMCO N FIG U R ATIO N
ST AT U SIN PUT S
PRO T EC T IO N
CBMAINT EN AN C E
D AT AST O R AG E
C O M MSIN T ERF AC E
O UT PU TR ELAYS
FAU LTD AT A
IN ST R U M ENT SD ISPLAY
MO D E
REYD ISPEVO LU T IO N
LED T EST FAU LTIND IC AT IO N S
D irection
Auto -Reclose
VA TECH Transmission & Distribution
24Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Argus 1 - Instrumentation and Monitoring
A=233.4 B=235.6C=234.0 E=000.7
a=00.53 b=00.53c=00.53 e=00.00
Relay S tatus11_1_1_
Trip Count = 5
Sum of I2
023178(M A)2
Can be set as default byscrolling to desired m eter
screen and pressing ENTER
Prim ary CurrentsUser input of CT ratios requ ired
Second ary C urrents
O utput R elays1 = re lay energised
Status Inputs1 = re lay energised
T rip C ounter
I2 Sum m ationPole with h ighest load
Status Inputs1_ _ _ _
VA TECH Transmission & Distribution
26Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
The Argus Fault Recorder
100 Event Records available over data com m s link
15:27:17.385, 22/02/00 Rey Raised A-HS2 Starter
15:27:17.507, 22/02/00 Rey Raised A-HS2 TripIEC Raised A-general trip
15:27:17.510, 22/02/00 Rey Raised W aveform stored
15:27:17.600, 22/02/00 IEC Cleared A-HS2 Starter
Trip LED F ive fau lt records available from re lay facia
Five waveform recordsavailable over data com m s link
02/22 15:27:17Trip A
FAULT 1Fault data >>>
FAULT 5Fault data >>>
TEST/RESET
W aveform triggerenabled
Data storage triggered by:
Operation of protection+
Output relays
VA TECH Transmission & Distribution
27Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Reydisp Evolution
VA TECH Transmission & Distribution
28Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Communications
Communications to IEC60870-5-103 protocol
Fibre optic with SMA connectors
May be connected in a loop with 254 relays
Fibre optic hub available for star configuration
VA TECH Transmission & Distribution
29Cc/Hydro_Präs/Interne RS.ppt
PEEBLES REYROLLE
Ring Connected Data Comms
F.O Cables
Sigma3
TXRX
RX
RXRXRX
TX
TX TX TX
RS232
PCs to be equipped with Reydisp software
Up to 254 relays can be connected in single loop
Each relay to have unique address LocalPC
RemotePC