VA TECH Transmission & Distribution 1 Cc/Hydro_Präs/Interne RS.ppt PEEBLES REYROLLE Overcurrent and Earth Fault Protection
Transcript

VA TECH Transmission & Distribution

1Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Overcurrent and Earth Fault Protection

VA TECH Transmission & Distribution

2Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

ARGUS 1-6 - Protection Functions

VA TECH Transmission & Distribution

3Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Phase and Earth Fault Characteristics

4 Independent Stages1 x transient free LOWSET, 0.1 - 52.5 In, 0 - 20 sec1 x SHAPED, 0.1 - 2.5In, T.M. 0.025 - 1.6

NI, EI, VI, LTI, DTL2 x transient free HIGHSET , 0.1 - 52.5 In, 0 - 20 sec

SHAPED

LS

HS1

HS2

TIME

CURRENT

24ms

VA TECH Transmission & Distribution

4Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Grading with Electro-Mechanical RelaysFAULTClashing conductors or re-sealing cableR1R2

Loss of grading /discrimination may occur:

If R2 Electromechanical & R1 Inst. reset or if R2 DTL reset and R1 electromechanical

Some compromise may be necessary where more than two relay points are in series

R3D

isc

Trav

el

Electro-mechanical Relay

Time

TRIP

% o

f Alg

orith

m

Argus (Inst. Reset)

Time

Argus (DTL Reset)

TRIP

VA TECH Transmission & Distribution

5Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

C.B. Failure Protection

RL1 RL11

&

Protectionalgorithmoperated

Fault triggeroutput relay

operatedDT L 10 - 20s

DT L 20 - 20s

RL1 RL11

T im e D elay > C B O perating T im e +Safety M arg in

O utput relays arranged to tripupstream circuit breaker

VA TECH Transmission & Distribution

6Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Trip circuit supervision - H6 Scheme

T RIPCOIL

52a

52a

52b

+ -

RL1 RL11

ARG US

TRIP

C.B .

Fuse Link

If trip circuit not healthy relaydisp lays "T RIP CCT FAIL"

TRIP CCT FAIL

2K7

Recom m endedS.I. Settings:

20m s p .u.400m s d .o .O /P 1 - 3 (NC contact)

External resistor = 2K7 O hm s110V system 50V Status Input

Rem ote Alarm

T CS can be set for each status input andtherefore can be used to monitor:

1st and 2nd trip coils or,all phases of phase segregated CB

VA TECH Transmission & Distribution

7Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Status Inputs

Initiate output relaysTime delayed pick-upTime delayed drop-off

Inhibit characteristic (except starters)

Change settings groups

Reset LEDs and Output Contacts

Trigger Waveform Storage

Synchronise Clock

Opto-isolated inputs

VA TECH Transmission & Distribution

8Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus protection summary

Wide range of IDMTL curves and DTL

Three independent high set/low set characteristics

Sensitive/restricted earth fault

Circuit breaker fail protection

Delayed or instantaneous reset

Low AC and DC burdens

True RMS measurement

Combined 1A and 5A current inputs

Full communications to IEC 60870-5-103

Self supervision/monitoring features

Trip circuit supervision

VA TECH Transmission & Distribution

9Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus Applications

VA TECH Transmission & Distribution

10Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Blocking scheme logic

HS150msDTL

HS150msDTL

Inst. LSBlockInst. LSBlock

Power Flow

Metallic connection required between relaying points

IDMT characteristic of relays toward source have a supplementary HS1 trippingcharacteristic with a DTL of 50ms

Inst. LS output of downstream relay arranged to block upstream HS1 characteristic

If metallic link is lost graded IDMT protection is not affected

VA TECH Transmission & Distribution

11Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Busbar ProtectionSettings

GE

MFA

CTO

R 1

CA

PA

CITO

R 1

TEN

SIO

N

STA

ND

3

STA

ND

2

STA

ND

1

PA

Y O

FF

GE

MFA

CTO

R 2

CA

PA

CITO

R 2

STA

ND

4

STA

ND

5

RE

EL

RE

EL

938A250A

938A250A

938A250A

938A250A

190A30A

780A120A

560A80A

480A80A

480A80A

240A40A

84A12A

2400A, 0.15s320A, 0.15s

2400A, 0.15s320A, 0.15s

2400A, 0.15s320A, 0.15s

BLOCK SIGNAL

Output from RL1 P/F & E/F Starters, Instantaneous operation

P/F LS TRIP SETTINGE/F LS TRIP SETTING

P/F BLOCKE/F BLOCK

780AFWD. P/F BLOCK SETTING

SI1 SI1 SI1INHIBIT LS

VA TECH Transmission & Distribution

12Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

RADIAL SUBSTATION

Startgenerators

Select alternate settings group

LocalGeneration

Industrial system draws power from grid system duringnormal operation

Argus relays normally use settings group 1

On loss of mains:Local generation switched in.Non essential loads trippedArgus relays on essential circuits switched to settingsgroup 2 to reflect new load and fault currents

Non-essentialloads

Trip non-essential loads

Alternative setting groups

VA TECH Transmission & Distribution

13Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Applications Summary

Blocking schemes for faster clearance

Busbar zone schemes for low cost busbar protection

Alternative protection setting groups

Status inputs can be time lagged for pick-up and/or drop-off and operate output contact(s)

VA TECH Transmission & Distribution

14Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus family of relays

Argus 2 - directional overcurrent and earth fault with bi-directional elements

Argus 3/4 - integrated overcurrent, earth fault & autoreclose 4 shot autoreclose fully programmable with different sequences for phase fault, earth fault and from an external signal

Argus 5/6 - directional overcurrent and earth fault with autoreclose

Argus 7 - check synchronising relay with independent settings for check and system synchronising, dead line/bus switching and manual close guard feature

Argus 8 - Under/overvoltage Under/overfrequency relay

VA TECH Transmission & Distribution

15Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Dual Directional ElementsIndependent FWD. And REV. SettingsIndependent control for each characteristicSeparate outputs for FWD. And REV.

20ms operating time for directional detection

Directional P/F300 or 450 deg. (I w.r.t. V)

Directional E/F00, -150, -450,-650, -900 (I w.r.t. V)

Directional SEF-900

2 out of 3 Gate Overcurrent Logic

Argus 2

CharacteristicAngle (C .A.)

C.A.+900

C.A.+900

FW D .ZO N E

REV.ZO NE

Forward zoneleading boundary+ 87.50

Forward zoneleading boundary+ 87.50

VA TECH Transmission & Distribution

16Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 4/64 pole relay with auto-reclose

1 to 4 shots (instantaneous or IDMT), 5th is Lockout IDMTA.R. sequences for P/F, E/F, SEF, ExternalSupports sequence reclosingFrequent operations counterTrip and Lockout (Supervisory)Hot line Working

CB Open/Closed Status Indication

9 Status Inputs, 7 Output Contacts

User Configurable Alarm Inputs13 alphanumeric characters

R6 / R8 Case

VA TECH Transmission & Distribution

17Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 4/6 - Sequence Co-ordinated Reclosing

Pole MountedRecloser

LocalConsumers

Consumers

2 Inst +Time Lag

2 Inst + GradedTime Lag

PMR

Argus

2 'Delayed' Inst +Graded Time Lag

Resetbefore trip

ArgusCount

A

Argus 4/6 configured for sequence co-ordination

Reduces supply interruption to localcustomers on occurrence of remote fault

VA TECH Transmission & Distribution

18Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 7 - Key Features

Check and system synchronising relay for 50Hz or 60Hz systems

Independent phase angle (Line and Bus Voltages), slip frequency (Line and Bus Freq) and slip timer settings

Independent undervoltage blocking and differential voltage blocking (Line and Bus)

Split system detection with split timer (90-170 Deg)

Options for dead line and/or dead bus charging (Sync bypass logic)

Integrated manual close guard function

Line & bus voltage trimming

VA TECH Transmission & Distribution

19Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 7 - Close guard feature Prevents an operator from initiating a manual circuit breaker close before the check synchronising relay operates

Removes the need for additional relays e.g. B66

VA TECH Transmission & Distribution

20Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 8 product variants

AG8 - 104-112

Three phase 4 stage under/overvoltage + negative sequence overvoltage

AG8 - 204-212

Three phase 4 stage under/overvoltage + negative sequence overvoltage + 4 stage under/overfrequency

AG8 - 101-103

Single phase 4 stage under/overvoltage + neutral voltage displacement

AG8 - 201-203

Single phase 4 stage under/overvoltage + neutral voltage displacement + 4 stage under/overfrequency

VA TECH Transmission & Distribution

21Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

ARGUS Interface and Monitoring

VA TECH Transmission & Distribution

22Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Alpha Numeric LCD Display2 rows, 16 characters

5 Pushbuttons and available with cover on:

View menuReset fault data displayReset latched output relaysReset TRIP LED

3 LED’sHealthyTripStart

Operator interface

VA TECH Transmission & Distribution

23Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Menu Structure R ELAYID ENT IF IER

SET T ING SDISPLAY

MO D E

SYST EMCO N FIG U R ATIO N

ST AT U SIN PUT S

PRO T EC T IO N

CBMAINT EN AN C E

D AT AST O R AG E

C O M MSIN T ERF AC E

O UT PU TR ELAYS

FAU LTD AT A

IN ST R U M ENT SD ISPLAY

MO D E

REYD ISPEVO LU T IO N

LED T EST FAU LTIND IC AT IO N S

D irection

Auto -Reclose

VA TECH Transmission & Distribution

24Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Argus 1 - Instrumentation and Monitoring

A=233.4 B=235.6C=234.0 E=000.7

a=00.53 b=00.53c=00.53 e=00.00

Relay S tatus11_1_1_

Trip Count = 5

Sum of I2

023178(M A)2

Can be set as default byscrolling to desired m eter

screen and pressing ENTER

Prim ary CurrentsUser input of CT ratios requ ired

Second ary C urrents

O utput R elays1 = re lay energised

Status Inputs1 = re lay energised

T rip C ounter

I2 Sum m ationPole with h ighest load

Status Inputs1_ _ _ _

VA TECH Transmission & Distribution

26Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

The Argus Fault Recorder

100 Event Records available over data com m s link

15:27:17.385, 22/02/00 Rey Raised A-HS2 Starter

15:27:17.507, 22/02/00 Rey Raised A-HS2 TripIEC Raised A-general trip

15:27:17.510, 22/02/00 Rey Raised W aveform stored

15:27:17.600, 22/02/00 IEC Cleared A-HS2 Starter

Trip LED F ive fau lt records available from re lay facia

Five waveform recordsavailable over data com m s link

02/22 15:27:17Trip A

FAULT 1Fault data >>>

FAULT 5Fault data >>>

TEST/RESET

W aveform triggerenabled

Data storage triggered by:

Operation of protection+

Output relays

VA TECH Transmission & Distribution

27Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Reydisp Evolution

VA TECH Transmission & Distribution

28Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Communications

Communications to IEC60870-5-103 protocol

Fibre optic with SMA connectors

May be connected in a loop with 254 relays

Fibre optic hub available for star configuration

VA TECH Transmission & Distribution

29Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Ring Connected Data Comms

F.O Cables

Sigma3

TXRX

RX

RXRXRX

TX

TX TX TX

RS232

PCs to be equipped with Reydisp software

Up to 254 relays can be connected in single loop

Each relay to have unique address LocalPC

RemotePC

VA TECH Transmission & Distribution

30Cc/Hydro_Präs/Interne RS.ppt

PEEBLES REYROLLE

Star Connected Data Comms

Star connected data commsIncreased Security

Sigma 1 F.O. Hub

F.O Cables

Sigma1

LocalPC

RemotePC