Transcript
  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    1/28

    Standards

    Certification

    Education & Training

    Publishing

    Conferences & Exhibits

    Managing Alarms at

    Gladstone Power Station

    A Case HistoryISA Safety Symposium Houston May 23-24 2006

    Presented by Alan Armour

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    2/28

    2

    OVERVIEW OF GLADSTONE POWER STATION

    6 X 280MW COALFIREDBOILER/TURBINES

    1st UNIT ON LINE IN 1976

    RAPID LOAD CHANGE

    SEAWATER COOLED CONDENSERS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    3/28

    3

    Insert picture of old controlpanel and text from page7

    CHRONICLE OF ALARM MANAGEMENT AT GPS1976-1994

    ALARMS PROVIDED BY SEPARATE DATAACQUISITION SYSTEM

    2216 ALARM POINTS PER UNIT

    HARD COPY TO PRINTERS

    ARCHIVED AS PRINTOUTS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    4/28

    4

    OTHER FEATURES

    MANUAL ALARM ANALYSIS

    UNIT TRIPS PROVIDED HUNDREDS OF PAGES

    HEAVY ALARM TRAFFIC

    NO PRIORITY SYSTEM

    STANDARD NOMENCLATURE MANAGEMENT

    BASIC SUPPRESSION OF OUT OF SERVICE PLANT ELEMENTARY INHIBITED ALARM PROCEDURES

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    5/28

    5

    CONTROLSYSTEMSOVERVIEW

    FOXBORO I/A DCS (SINCE 1994)

    8 CONTROL DESKS

    OVER 30,000 I/O, 3600 ALARMS/UNIT

    CENTRALISEDCONTROL ROOM

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    6/28

    6

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    7/287

    1994 - PRESENT

    ALARMS INTEGRATED WITH DCS

    HISTORIAN

    EXTENSIVE ALARM REVIEW

    3600 ALARM POINTS PER UNIT

    INTRODUCTION OF THREE ALARM PRIORITIES

    SOME ALARMS SENT TO PAGERS

    INITIAL TRAFFIC OVER 2500 ALARMS PER DAYPER UNIT

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    8/288

    ISSUES WITH ALARMS SINCE UPGRADE

    MASSIVE ALARM FLOODS

    IMPORTANT ALARMS MISSED

    MISMANAGED INHIBITED ALARMS

    UNNECESSARY DAMAGE TO PLANT

    FRUSTRATEDOPERATION STAFF

    AUDIBLEALARM SYSTEM VANDALISED

    LOW OPERATOR PRODUCTIVITY

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    9/289

    ALARM DESTINATION REVIEW

    BEGINNING OF ALARM TRAFFIC MANAGEMENT

    BENCH MARKS ESTABLISHED

    ADDRESSED TRAFFIC ISSUES USING THESQUEAKING WHEEL PRIORITY METHOD

    SET UP SPECIAL PLANT MODIFICATION DOCUMENTFOR ALARMS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    10/2810

    0

    200

    400

    600

    800

    1000

    1200

    01/08/2001

    13/08/2001

    25/08/2001

    06/09/2001

    18/09/2001

    30/09/2001

    12/10/2001

    24/10/2001

    06/11/2001

    18/11/2001

    30/11/2001

    12/12/2001

    24/12/2001

    05/01/2002

    17/01/2002

    29/01/2002

    10/02/2002

    22/02/2002

    06/03/2002

    18/03/2002

    30/03/2002

    11/04/2002

    23/04/2002

    06/05/2002

    18/05/2002

    30/05/2002

    11/06/2002

    23/06/2002

    05/07/2002

    17/07/2002

    29/07/2002

    TOTAL P1 ALARMS

    TOTAL P2 ALARMS

    TOTAL P3 ALARMS

    2001/2 ANALYSIS-DAILY COUNT

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    11/2811

    8%

    44%

    48%TOTAL P1 ALARMS

    TOTAL P2 ALARMS

    TOTAL P3 ALARMS

    2001/2 ANALYSIS - ALARMS BY PRIORTY

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    12/2812

    PURCHASED ALARM MANAGEMENT SOFTWARE

    TASK FORCE FORMED

    INTRODUCTION OF INHIBITED ALARM MANAGEMENT

    INTRODUCTION OF STANDING ALARM MANAGEMENT

    INCORPORATED EEMUA GUIDELINES

    RISK ANALYSIS

    CONTINUING PRESSURE FROM PRODUCTIONMANAGEMENT TO FURTHER REDUCE TRAFFIC

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    13/2813

    LOGMATE(TIPS)

    ALARM

    MANAGER

    ANNUNCIATOR

    LIGHTS,AUDIBLEHISTORIAN

    PROCESSGUARD

    (MATRIKON)

    HISTORIAN

    REPORTS

    INHIBITEDALARMSREPORTS

    STANDINGALARMS

    > 2 DAYS

    ALARMS BYTAG

    (TOP 20)

    ALARMS BY

    PRIORITY-INTERVAL

    I/A SYSTEM

    REPORTS

    ALARM MANAGEMENT TEAM

    MANAGEMENTOPERATIONSENGINEERINGMAINTENANCE

    DCS SYSTEMS

    ENGINEER

    DCS FOXBORO I/A

    (1 CONTROL SYSTEMS TECHNICIAN, 2 OPERATORS, 1 PROCESS ENGINEER, ALL PART TIME)

    ALARM MANAGEMENT STRUCTURE

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    14/2814

    2003

    OPERATION STAFF REDUCED BY 18 (3 OFFEACH SHIFT, AND 3 OFF DAY SHIFT)

    ALARM MANAGEMENT NOW A KEY ELEMENTIN PLANT OPERATIONS

    ALARMS SCREENS FOR UNITS NOWDUPLICATED AND MONITORED FROM 1CENTRAL CONTROL DESK

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    15/2815

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    16/2816

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    17/2817

    STANDING ALARMS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    18/2818

    STANDING ALARMS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    19/28

    19

    SMART ALARM EXAMPLE

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    20/28

    20

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    21/28

    21

    Tag

    Alarm

    Count Tag Description

    4_SH_TEMP:STM_OTMP_ALM 3 BLR STM OUT TEMP H2

    4_A_PASS_FF:5RM_2_ALM 2 A5 ROT MANIFOLD SPEED TRIP

    4_AIR_HTR:AH_GO_ALM 2 AIR HTR GAS OUT TEMP L1

    4_CW_TW:BACKFLUSH_2 2 BACKFLUSH REQUIRED

    4_RH_TEMP:RH_DEV_ALM1 2 RH STM TEMP DEV HI

    4_AIR_AUX:AIRINJ_1_ALM 1 AIR INJECTION SUBLOOP OFF

    4_AIR_FLOW :A_O2_ALM_H1 1 A FLUE GAS O2 H1

    4_AIR_HTR:AH_DEV 1 A-B AIR HT AIR IN TC DEV HI

    4_D_PULV:PA_DMP_ALM 1 D PULV PA DAMP AUTO OFF

    4_D_PULV:PLV_STR_ALM 1 D PULV START SEQ FLT

    4_D_PULV:SD_FLT_ALM 1 D PULV SLEEVE DAMP FLT4_E_PULV:PA_DMP_ALM 1 E PULV PA DAMP AUTO OFF

    4_E_PULV:SD_FLT_ALM 1 E PULV SLEEVE DAMP FLT

    4_F_PULV:PA_DMP_ALM 1 F PULV PA DAMP AUTO OFF

    4_F_PULV:PLV_STR_ALM 1 F PULV START SEQ FLT

    4_F_PULV:SD_FLT_ALM 1 F PULV SLEEVE DAMP FLT

    4_FW_FLOW:DL_ALM_H1 1 DRUM LEVEL ALARM H1

    4_RH_TEMP:PSS_MST_ALM1 1 REAR PASS DAMP MAST AUTO OFF

    4_TURB_WSE:VTMIN_1_ALM 1 TURB STRESS MARGIN L1

    Total: 25

    Gladstone Power Station

    Unit 4 Alarm Count By Tag

    09/08/04

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4_SH

    _TEM

    P:ST

    M_OT

    ...

    4_A_

    PASS

    _FF:5

    RM_..

    .

    4_AIR

    _HTR

    :AH_GO_

    ALM

    4_CW

    _TW

    :BACK

    FLUS

    H_2

    4_RH

    _TEM

    P:RH_

    DEV.

    ..

    4_AIR

    _AUX

    :AIR

    INJ_

    1_AL

    M

    4_AIR

    _FLO

    W:A_

    O2_A

    ...

    4_AIR

    _HTR

    :AH_DEV

    4_D_

    PULV

    :PA_DMP

    _ALM

    4_D_

    PULV

    :PLV_

    STR_

    ALM

    4_D_

    PULV

    :SD_FLT

    _ALM

    4_E_

    PULV

    :PA_

    DMP_

    ALM

    4_E_

    PULV

    :SD_

    FLT_

    ALM

    4_F_

    PULV

    :PA_DMP

    _ALM

    4_F_

    PULV

    :PLV_

    STR_

    ALM

    4_F_

    PULV

    :SD_FLT

    _ALM

    4_FW

    _FLO

    W:D

    L_AL

    M_H1

    4_RH

    _TEM

    P:PSS

    _MS.

    ..

    4_TU

    RB_WSE

    :VTMI

    N_...

    Tag Name

    AlarmC

    ount

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    22/28

    22

    Condition Data

    1 2 3 Total Count Total Percent

    Timestamp Count Percent Count Percent Count Percent

    8/9/04 1:00 1 100% 1 100%8/9/04 2:00 1 100% 1 100%

    8/9/04 3:00 1 13% 4 50% 3 38% 8 100%

    8/9/04 5:00 1 50% 1 50% 2 100%

    8/9/04 6:00 1 100% 1 100%

    8/9/04 7:00 1 33% 2 67% 3 100%

    8/9/04 8:00 2 67% 1 33% 3 100%

    8/9/04 15:00 1 100% 1 100%

    8/9/04 16:00 1 100% 1 100%

    8/9/04 18:00 1 100% 1 100%

    8/9/04 20:00 2 100% 2 100%

    8/9/04 23:00 1 100% 1 100%

    Gladstone Power Station Unit 4

    Alarm Distribution by Priority per Hour

    0%

    10%

    20%

    30%

    40%

    50%

    60%

    70%

    80%

    90%

    100%

    8/9/04 1:00 8/9/04 2:00 8/9/04 3:00 8/9/04 5:00 8/9/04 6:00 8/9/04 7:00 8/9/04 8:00 8/9/04

    15:00

    8/9/04

    16:00

    8/9/04

    18:00

    8/9/04

    20:00

    8/9/04

    23:00

    Distribution

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    TotalCount

    1 2 3 Total Count

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    23/28

    23

    AlarmPerformance Metrics

    Alarm Performance Metrics (EEMUA Guidelines)

    (1) Average number of alarms per hourLevel of interruption

    (2) Maximum number of alarms per hourWorst case loading

    (3) % of hours when there were >30 alarms per hour% time system is upset

    Alarm System Performance

    Maximum # Alarms per Hr

    Average#Ala

    rmsperHr 1 -Overloaded

    2 - Reactive

    3 - Stable4 - Robust

    5 - Predictive

    600060060

    600

    60

    6 X

    ImpossibleImpossible

    Benchmark &Assessment

    +

    MATRIKON

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    24/28

    24

    OTHER BENEFITS OF ALARM MANAGEMENT

    FASTER START UP AND SHUT DOWN TIMES. REDUCED SICK LEAVE FROM OPERATION STAFF. (BETTER

    WORK SATISFACTION, LESS STRESS)

    MAINTENANCE CAN BETTER PLAN WORK.

    BETTER RECOVERY FROM ABNORMAL SITUATIONS(REDUCED TRIPS, LESS DAMAGE TO PLANT ETC).

    REDUCED LOSSES.

    OPERATORS ARE LESS ALARM DRIVEN IN THEIR WORK.

    EASIER TO IDENTIFY AND RESOLVE PROCESS PROBLEMS

    REQUESTS FROM OPERATIONS FOR MORE ALARMS!

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    25/28

    25

    GLADSTONE POWER STATION

    UNIT TRIPS 1996-2006

    0

    2

    4

    6

    8

    10

    12

    14

    TIME

    Series1

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    26/28

    26

    FUTURE WORK

    REDUCE ALARM FLOODS DURING ABNORMAL SITUATIONS

    CHANGES TO AUDIBLE ALARM PHILOSOPHY

    REDUCE CONSEQUENTIAL ALARM TRAFFIC

    MORE WORK ON STANDING ALARMS

    INCLUDE ALARM TRAFFIC DATA IN KPI CALCULATIONS

    FURTHER DEVELOP PACKAGE TO REDUCE ADMINISTRATIONCOSTS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    27/28

    27

    ACKNOWLEDGEMENTS

    NRG GLADSTONE POWER STATION MATRIKON

    SIT

    EEMUA

    INVENSYS

  • 7/30/2019 Armour Managingthealarmmanager Gladstonepower

    28/28

    QUESTION TIME