+ All Categories
Home > Documents > AS3823-2-2005.pdf

AS3823-2-2005.pdf

Date post: 02-Jun-2018
Category:
Upload: leed-en
View: 216 times
Download: 0 times
Share this document with a friend

of 73

Transcript
  • 8/10/2019 AS3823-2-2005.pdf

    1/73

    AS/NZS 3823.2:2005

    Australian/New Zealand Standard

    Performance of electrical appliancesAirconditioners and heat pumps

    Part 2: Energy labelling and minimumenergy performance standard (MEPS)requirements

    AS/NZS

    3823.2:2005

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Mar2006

  • 8/10/2019 AS3823-2-2005.pdf

    2/73

    AS/NZS 3823.2:2005

    This Joint Australian/New Zealand Standard was prepared by Joint TechnicalCommittee EL-015, Quality and Performance of Household Electrical Appliances.It was approved on behalf of the Council of Standards Australia on8 December 2005 and on behalf of the Council of Standards New Zealand on21 December 2005.

    This Standard was published on 30 December 2005.

    The following are represented on Committee EL-015:

    Australian Association of Certification Bodies

    Australian Consumers Association

    Australian Electrical and Electronic Manufacturers Association

    Australian Industry Group

    Australian Retailers Association

    Business New Zealand

    Consumer Electronic Suppliers Association

    Department of Minerals and Energy, Qld

    Department of Industrial Relations, Qld

    Electrical Compliance Testing Association

    Energy Efficiency and Conservation Authority New Zealand

    Ministry of Energy and Utilities, New South Wales

    National Appl iance and Equipment Energy Efficiency Committee

    National Association of Testing Authorities Australia

    New Zealand Manufacturers Federation

    Office of the Chief Electrical Inspector, Victoria

    Office of the Technical Regulator, South Australia

    Additional Interests:

    Air Conditioning and Refrigeration Equipment Manufacturers Association

    Institute of Refrigeration Heating and Air Conditioning Engineers ofNew Zealand

    Institution of Professional Engineers New Zealand

    Primary Industries and Resources, South Australia

    Testing Interest Australia

    Keeping Standards up-to-date

    Standards are living documents which reflect progress in science, technology andsystems. To maintain their currency, all Standards are periodically reviewed, andnew editions are published. Between editions, amendments may be issued.Standards may also be withdrawn. It is important that readers assure themselvesthey are using a current Standard, which should include any amendments whichmay have been published since the Standard was purchased.

    Detailed information about joint Australian/New Zealand Standards can be found byvisiting the Standards Web Shop at www.standards.com.au or Standards NewZealand web site at www.standards.co.nz and looking up the relevant Standard inthe on-line catalogue.

    Alternatively, both organizations publish an annual printed Catalogue with fulldetails of all current Standards. For more frequent listings or notification ofrevisions, amendments and withdrawals, Standards Australia and Standards NewZealand offer a number of update options. For information about these services,users should contact their respective national Standards organization.

    We also welcome suggestions for improvement in our Standards, and especiallyencourage readers to notify us immediately of any apparent inaccuracies orambiguities. Please address your comments to the Chief Executive of eitherStandards Australia or Standards New Zealand at the address shown on the back

    cover.

    This Standard was issued in draft form for comment as DR 05316.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    3/73

    AS/NZS 3823.2:2005

    Australian/New Zealand Standard

    Performance of electrical appliancesAirconditioners and heat pumps

    Part 2: Energy labelling and minimumenergy performance standard (MEPS)requirements

    COPYRIGHT

    Standards Australia/Standards New Zealand

    All rights are reserved. No part of this work may be reproduced or copied in any form or byany means, electronic or mechanical, including photocopying, without the written

    permission of the publisher.

    Jointly published by Standards Australia, GPO Box 476, Sydney, NSW 2001 and Standards

    New Zealand, Private Bag 2439, Wellington 6020

    ISBN 0 7337 7077 0

    Originated as AS/NZS 3823.2:1998.Previous edition AS/NZS 3823.2:2003.Fifth edition 2005.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    4/73

    AS/NZS 3823.2:2005 2

    PREFACE

    This Standard was prepared by the Joint Standards Australia/Standards New Zealand

    Committee EL-15, Quality and Performance of Household Electrical Appliances, tosupersede AS/NZS 3823.2:2003 (including Amendment 1).

    The AS/NZS 3823 series comprises five Parts, as follows:

    AS/NZS

    3823 Performance of electrical appliancesAirconditioners and heat pumps

    3823.1.1 Part 1.1: Test methodsNon-ducted airconditioners and heat pumpsTesting

    and rating for performance

    3823.1.2 Part 1.2: Test methodsDucted airconditioners and air-to-air heat pumps

    Testing and rating for performance

    3823.1.3 Part 1.3 Water-source heat pumpsTesting and rating for performance:

    Water-to-air and brine-to-air heat pumps

    3823.2 Part 2: Energy labelling and minimum energy performance standard (MEPS)requirements (this Standard)

    3823.3 Part 3: Calculation of performance for minimum energy performance

    standard (MEPS) requirements

    The overall objective of the AS/NZS 3823 series of Standards is to promote high levels of

    performance and energy efficiency in airconditioners and heat pumps. The Parts of the

    AS/NZS 3823 series are summarized as follows:

    (a) Part 1.1 includes performance test procedures for rating non-ducted airconditioners

    and heat pumps, to be used in conjunction with Part 2.

    (b) Part 1.2 includes performance test procedures for rating ducted airconditioners and

    heat pumps, to be used in conjunction with Part 2.

    (c) Part 1.3 includes performance test procedures for rating water-to-air heat pumps and

    airconditioners with water cooled condensers, to be used in conjunction with Part 2.

    (d) Part 2 specifies minimum energy performance standard (MEPS) requirements and

    includes algorithms for the calculation of the energy efficiency star rating,

    performance requirements, details of energy labels and requirements for valid

    applications for registration.

    (e) Part 3 specifies procedures for calculating the performance (simulation) of

    airconditioners of the vapour compression type up to a rated cooling capacity of

    65 kW, for minimum energy performance standard (MEPS) requirements, in lieu of

    physical tests.

    The main changes in this Standard are the introduction of a revised timetable and levels for

    minimum energy performance standard requirements for single-phase units in the years up

    to 2008 and the notification of a revised energy labelling algorithm for introduction from

    2008. This edition also includes references to Part 1.3 for water sourced heat pumps.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    5/73

    3 AS/NZS 3823.2:2005

    Similar to the previous revisions of this Standard it is possible to use either physical tests or

    simulated performance tests (described in AS/NZS 3823.3) to demonstrate compliance withthe minimum energy performance standard requirements for three-phase and some single-

    phase units (units which do not carry an energy label). Only physical tests can be used todemonstrate compliance with energy labelling. Suppliers of three-phase, single-phase

    ducted and single-phase commercial units may choose to fix energy labels to products; ifso, then all of the usual requirements for energy labelling will apply (including therequirement for a physical test). The status of energy labelling and minimum energyperformance standard (MEPS) Australian regulatory programs and their date of

    implementation, for the various airconditioning equipment configurations, is provided in

    Appendix E.

    This Standard is published with the approval of the combined state and territory regulatory

    authorities and is structured to be suitable for reference in legislation calling up minimum

    energy performance standards and also for reference in energy labelling regulatorylegislation.

    Key regulatory dates in this Standard and other changes are as follows:(a) The change in scope of the mandatory energy labelling program for household

    airconditioners and heat pumps from a 7.5 kW cooling requirement to a single-phase

    requirement was 1 October 2001.

    (b) Introduction of MEPS for three-phase airconditioners was 1 October 2001.

    (c) Introduction of MEPS for single-phase airconditioners was 1 October 2004.

    (d) Single-phase ducted units, which are registered to any relevant MEPS level under thisStandard, may carry an energy label on a voluntary basis.

    (e) Revised three-phase MEPS levels will be introduced on 1 October 2007 (no change

    from 2003 edition of this Standard).(f) Single-phase MEPS levels for some categories of products originally proposed for

    1 October 2007 have been advanced to 1 April 2006 and an additional MEPS level for

    1 October 2008 has also been included.

    (g) Class A efficiency levels will be valid for the next iteration of MEPS after 2008.

    (h) A minor change to the wording on the energy label for variable output compressors.

    Section 4 of this Standard sets out the transition provisions for energy labelling and MEPSunder this Standard.

    New Zealand Energy Efficiency (Energy Using Products) Regulations 2002 had a

    commencement date of 1 April 2002 for energy performance labelling of single-phaseairconditioners and 1 July 2002 for MEPS for three-phase airconditioners which currentlyincludes only the requirements of the 2003 edition of this Standard. The revised MEPS

    levels and introductory dates for single phase units in New Zealand will be addressed by anamendment to this Standard, which is expected in early 2006.

    The terms normative and informative have been used in this Standard to define the

    application of the appendix to which they apply. A normativeappendix is an integral partof a Standard, whereas an informativeappendix is only for information and guidance.

    Statements expressed in mandatory terms in notes to figures, are deemed to be requirements

    of this Standard.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    6/73

    AS/NZS 3823.2:2005 4

    CONTENTS

    Page

    SECTION 1 SCOPE AND GENERAL

    1.1 SCOPE ........................................................................................................................ 6

    1.2 EXCLUSIONS ............................................................................................................ 6

    1.3 APPLICATION ........................................................................................................... 7

    1.4 OBJECTIVE................................................................................................................ 7

    1.5 REFERENCED DOCUMENTS .................................................................................. 7

    1.6 DEFINITIONS ............................................................................................................ 8

    1.7 MEASURED QUANTITIES ..................................................................................... 10

    1.8 ROUNDING.............................................................................................................. 10

    1.9 CLAIMS OF CAPACITY AND ENERGY CONSUMPTION .................................. 10

    SECTION 2 CALCULATIONS FOR THE ENERGY LABEL

    2.1 SCOPE ...................................................................................................................... 11

    2.2 GENERAL ................................................................................................................ 11

    2.3 NUMBER OF TESTS AND PROCESSING OF DATA............................................ 11

    2.4 COMPARATIVE ENERGY CONSUMPTION (CEC).............................................. 12

    2.5 STAR RATING INDEX (SRI) .................................................................................. 12

    2.6 STAR RATING......................................................................................................... 13

    2.7 EXAMPLE OF ENERGY EFFICIENCY CALCULATIONS ................................... 13

    2.8 ENERGY LABEL VALIDITY (CHECK TESTING)................................................ 13

    2.9 MAXIMUM COOLING TEST.................................................................................. 14

    2.10 TOP ENERGY SAVER AWARD ............................................................................. 14

    SECTION 3 PERFORMANCE CRITERIA

    3.1 GENERAL ................................................................................................................ 15

    3.2 MINIMUM ENERGY PERFORMANCE STANDARD............................................ 15

    3.3 CLASS A EFFICIENCY AIRCONDITIONERS....................................................... 18

    3.4 TEST CONDITIONS FOR DETERMINING MINIMUM ENERGY

    PERFORMANCE STANDARDS AND HIGH EFFICIENCY CLAIMS................... 19

    3.5 NUMBER OF TESTS AND PROCESSING OF DATA............................................ 19

    3.6 MINIMUM ENERGY PERFORMANCE STANDARD REQUIREMENTS

    COMPLIANCE ......................................................................................................... 20

    3.7 MEPS VALIDITY (CHECK TESTING)................................................................... 20

    3.8 VARIABLE OUTPUT COMPRESSORS.................................................................. 213.9 COEFFICIENT OF PERFORMANCE AT LOW TEMPERATURE ......................... 21

    3.10 STANDBY POWER AND CRANK CASE HEATERS ............................................ 21

    3.11 LOAD CONTROL CAPABILITY ............................................................................ 21

    3.12 POWER FACTOR..................................................................................................... 21

    SECTION 4 APPLICATION AND TEST RESULT FORMATS

    4.1 APPLICATION FOR REGISTRATION ................................................................... 22

    4.2 HOLDING OF RECORDS........................................................................................ 23

    4.3 DATE OF MANUFACTURE INFORMATION........................................................ 24

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    7/73

    5 AS/NZS 3823.2:2005

    Page

    SECTION 5 PRINTING AND PLACEMENT OF ENERGY LABELS

    5.1 PLACEMENT ........................................................................................................... 25

    5.2 MATERIAL AND SHAPE........................................................................................ 25

    5.3 COLOURS ................................................................................................................ 25

    5.4 LABEL REQUIREMENTS....................................................................................... 26

    5.5 SAMPLE LABELS.................................................................................................... 26

    APPENDICES

    A EXAMPLES OF ENERGY EFFICIENCY CALCULATIONS ................................. 31

    B FORMAT OF APPLICATION FOR REGISTRATION OF AN

    AIRCONDITIONER FOR ENERGY LABELLING AND MEPS............................. 35

    C FORMAT OF SUMMARY TEST RESULTS FOR AN ENERGY LABELLING

    AND/OR MEPS APPLICATION WHERE FULL TEST REPORTS ARE NOT

    PROVIDED............................................................................................................... 53

    D ENERGY LABEL DIMENSIONS ............................................................................ 57

    E ENERGY LABELLING AND MEPS REQUIREMENTS FOR VARIOUS

    AIRCONDITIONING EQUIPMENT CONFIGURATIONS..................................... 62

    F NEW ENERGY LABELLING ALGORITHMS........................................................ 66

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    8/73

    AS/NZS 3823.2:2005 6

    COPYRIGHT

    STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND

    Australian/New Zealand Standard

    Performance of electrical appliancesAirconditioners and heat pumps

    Part 2: Energy labelling and minimum energy performance standard (MEPS)requirements

    S E C T I O N 1 S C O P E A N D G E N E R A L

    1.1 SCOPE

    This Standard specifies the energy labelling requirements for single-phase non-ductedairconditioners of the vapour compression type for household use and the minimum energyperformance standard (MEPS) requirements for single-phase and three-phase

    airconditioners of the vapour compression type up to a rated cooling capacity of 65 kW and

    that fall within the scope of AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3.

    Particular regulatory requirements for different categories of airconditioning equipment and

    validity dates are summarized in Appendix E of this Standard.

    The revised MEPS levels and introductory dates for single phase units beyond 2004 in NewZealand will be addressed by an amendment to this Standard.

    This Standard does not specify electrical safety requirements.

    This Standard specifies the following values for cooling and heating, as applicable:

    (a) Rated power (input).

    (b) Rated capacity (output).

    (c) Energy efficiency ratio (EER) for cooling.

    (d) Coefficient of performance (COP) for heating.

    (e) Comparative energy consumption (CEC).

    (f) Star Rating Index (SRI).

    (g) Star rating.

    (h) Some of the requirements for energy label validity.

    (i) The performance criteria for energy labelling validity.

    (j) Test report format.

    (k) Printing requirements for airconditioner appliance energy labels.

    (l) Minimum energy performance standard requirements.

    1.2 EXCLUSIONS

    The following equipment is excluded from the scope of this Standard:

    (a) Close controlled airconditioners, pending the development of MEPS levels for theseproducts.

    (b) Multi-split systems (i.e., those having more than one indoor unit with an independent

    control for each indoor unit) pending the development of a suitable test method.Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    9/73

    7 AS/NZS 3823.2:2005

    COPYRIGHT

    (c) Evaporative coolers or any other cooling systems that are not of the vapourcompression type.

    (d) Ground-water-sourced or ground-loop-sourced heat pumps within the scope of

    Part 1.3.

    NOTE: Water loop heat pumps as defined in Part 1.3 are included within the scope of this

    Standard.

    (e) Unbalanced airconditioners and spot coolers (these include many portable types).

    (f) Commercial chillers which are used in commercial buildings to provide chilled-water

    for space cooling equipment.

    (g) Models that have been granted exemption by the relevant Australian/New Zealandregulatory authority due to their specific design for applications such as process

    heating or cooling or for heating or cooling of spaces to conditions that are not

    intended for human comfort.

    1.3 APPLICATION

    This Standard shall be read in conjunction with AS/NZS 3823.1.1, AS/NZS 3823.1.2,

    AS/NZS 3823.1.3 and AS/NZS 3823.3, as applicable.

    Products that have water-cooled condensers as well as water-source heat pumps fall withinthe scope of this Standard and shall meet the relevant labelling and/or MEPS requirements

    for the cooling function. For these products, the cooling and heating performance shall bedetermined and declared in accordance with AS/NZS 3823.1.3. Cooling only products with

    water-cooled condensers that are included within the scope of AS/NZS 3823.1.1 and

    AS/NZS 3823.1.2 shall be tested to AS/NZS 3823.1.3 wherever possible.

    1.4 OBJECTIVE

    The objective of this Standard is to

    (a) provide detailed information on the performance and energy labelling requirements

    which an airconditioning appliance has to meet in order to carry a valid energyefficiency label;

    (b) provide detailed information on the performance requirements which an

    airconditioning appliance has to meet in order meet minimum energy performancestandard requirements; and

    (c) describe the circumstances in which alternatives to physical testing may be used to

    demonstrate and verify compliance with minimum energy performance standardrequirements.

    1.5 REFERENCED DOCUMENTS

    The following documents are referred to in this Standard:

    AS

    2706 Numerical valuesRounding and interpretation of limiting values

    2834 Computer accommodation

    AS/NZS3823 Performance of household electrical appliancesAirconditioners and heat

    pumps

    3823.1.1 Part 1.1: Test methodsNon-ducted airconditioners and heat pumpsTestingand rating for performance

    3823.1.2 Part 1.2: Test methodsDucted airconditioners and air-to-air heat pumps

    Testing and rating for performanceAccessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    10/73

    AS/NZS 3823.2:2005 8

    COPYRIGHT

    3823.1.3 Part 1.3: Water-source heat pumpsTesting and rating for performance:

    Water-to-air and brine-to-air heat pumps3823.3 Part 3: Calculation of performance for minimum energy performance

    standard (MEPS) requirements

    1.6 DEFINITIONS

    For the purposes of this Standard the definitions given in AS/NZS 3823.1.1,

    AS/NZS 3823.1.2, AS/NZS 3823.1.3 and those below apply.

    1.6.1 Check test

    A full or part test in accordance with AS/NZS 3823.1.1, AS/NZS 3823.1.2,AS/NZS 3823.1.3 or AS/NZS 3823.3, as applicable, to verify the performance or energy

    consumption, or both, of an individual model.

    1.6.2 Class A efficiency

    Rating for an airconditioner that meets the minimum EER cooling values specified in

    Clause 3.3.

    1.6.3 Close controlled airconditioners

    An airconditioner that meets the requirements of AS 2834 for Environment Type 1

    conditions and satisfies the requirements of the process carried out in the airconditionedroom.

    1.6.4 Comparative energy consumption (CEC)

    The nominal energy consumption of a model of airconditioner. It is the estimate of energyused by a single unit per hour of use at rated power for cooling and/or heating, as

    applicable. It assumes the unit operates under standard conditions (as defined in

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3) (see also Clause 2.3). TheCEC appears on the energy label as Power input. (Units: kW.)

    1.6.5 Ducted airconditioners

    An airconditioner model configuration where the indoor side is situated remote to the space

    to be conditioned. The conditioned air is supplied or extracted via a duct.

    1.6.6 Family of models

    A range of models of the one brand, for which a single set of test reports is applicable andwhere each of the models has the same relevant physical characteristics, comparativeenergy consumption, energy efficiency rating, performance characteristics and refrigerant.

    The term modelis synonymous with family of models.

    NOTE: A product that has single-phase and three-phase variants will have to be separately

    registered and cannot be considered as one family (as MEPS requirements for single- and three-

    phase variants may be different). Single- and three-phase products may be separately registered

    using a single test report that covers these variants, as long as the product tested has the lowest

    EER and COP of all the relevant variants.

    1.6.7 Multi-split system

    A split system airconditioner with a refrigeration system having a single outdoor unit and

    two or more indoor units, each indoor unit being independently controlled.

    1.6.8 Non-ducted airconditioner

    An airconditioner model configuration where the indoor side is situated partly or wholly

    within the space to be conditioned. The conditioned air is supplied and extracted directly toand from the conditioned space.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    11/73

    9 AS/NZS 3823.2:2005

    COPYRIGHT

    1.6.9 Rated capacity

    The nominal rated capacity claimed by the manufacturer of an airconditioner modeldetermined as follows, as applicable:

    (a) Rated total cooling capacity As claimed by the manufacturer in accordance with

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 for temperaturecondition T1. (Units: W or kW.)

    (b) Rated heating capacity As claimed by the manufacturer in accordance withAS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 for temperaturecondition H1. (Units: W or kW.)

    The rated capacity appears on the energy label as Capacity Output(heating and/or coolingas applicable. (Units: kW).

    For variable output capacity equipment, the rated capacity of each model shall not exceed

    the maximum continuous output rating possible by the unit. Short term peak outputs shallnot be used for rated capacity.

    1.6.10 Rated power

    Effective power input of the airconditioner model as claimed by the manufacturer in

    accordance with AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 during thedetermination of rated cooling capacity and rated heating capacity, as applicable. (Units: W

    or kW.)

    1.6.11 Split system

    An airconditioner with separate indoor and outdoor components that are connected with

    refrigerant piping. The indoor unit usually lies within the conditioned space and may beinstalled or portable/mobile.

    NOTE: The indoor unit in some configurat ions may feed into a duct system. Some split ducted

    system indoor units may have no fan and are designed to operate with an existing system (e.g.,gas heater).

    1.6.12 Spot cooler

    A unitary airconditioner that lies wholly within a conditioned space and that draws air forboth the evaporator and condenser from the conditioned space and expels both of these backinto the conditioned space.

    1.6.13 Star rating

    The number of stars displayed on the energy label. Available stars are between a minimumof one and a maximum of six, shown in half star intervals. The star rating is calculated from

    the Star Rating Index (see Clause 2.6). (Dimensionless.)1.6.14 Star rating index (SRI)

    An indication of the claimed energy efficiency of a model at rated conditions. A higher SRI

    indicates a higher energy efficiency. It is derived from the measured EER or measuredCOP, as applicable (see Clause 2.5).

    1.6.15 Statements of intention

    1.6.15.1 Shall

    Indicates that a statement is mandatory.

    1.6.15.2 Should

    Indicates a recommendation.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    12/73

    AS/NZS 3823.2:2005 10

    COPYRIGHT

    1.6.16 Three-phase model

    A model where at least one component in the airconditioning system requires an externalthree-phase power supply.

    1.6.17 Single-phase model

    A model where all components in the airconditioning system that require an external powersupply require only single-phase power.

    NOTE: Some components of an airconditioner system may be supplied a.c. or d.c. power via

    internal wiring.

    1.6.18 Twin (or triple) split

    A split system airconditioner comprising a single outdoor unit with two (or three) indoorunits that are controlled by a single controller.

    1.6.19 Unbalanced airconditioner

    An unbalanced airconditioner is a unitary airconditioner that lies wholly within a

    conditioned space and that draws air from the conditioned space and expels this to outdoors.An unbalanced airconditioner is usually ducted (where the exhaust air from the heatexchanger is expelled from the conditioned space via a flexible duct, pipe or opening) butmay be connected to a pipe or other opening such as a window. These units are typically

    portable or mobile.

    1.6.20 Unitary airconditioner

    An airconditioner where the evaporator, condenser and associated refrigeration components

    (e.g., compressor) are contained within a single casing. Unitary airconditioners may be non-ducted (e.g., window/wall units) or ducted (e.g., single packaged units).

    1.7 MEASURED QUANTITIESQuantities used in this Standard shall be measured during tests carried out in accordance

    with AS/NZS 3823.1.1, AS/NZS 3823.1.2, AS/NZS 3823.1.3 or AS/NZS 3823.3, asapplicable.

    1.8 ROUNDING

    Unless otherwise stated, numbers shall be rounded and recorded to five significant figures

    in accordance with AS 2706.

    1.9 CLAIMS OF CAPACITY AND ENERGY CONSUMPTION

    Any unqualified claims of capacity and energy consumption shall be rated values forcondition T1 or H1, as applicable (see Clauses 1.6.9 and 1.6.10). Other claims of capacity

    and energy consumption shall be qualified by the conditions under which these values are

    determined. The use of 'horsepower' as a unit of measure for air conditioner output capacityshall not be used because it does not directly correlate to the output capacity in kW and is

    therefore misleading.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    13/73

    11 AS/NZS 3823.2:2005

    COPYRIGHT

    S E C T I O N 2 C A L C U L A T I O N S F O R T H E

    E N E R G Y L A B E L

    2.1 SCOPE

    This Section sets out the equations and procedures for calculating the CEC, SRI values andthe star rating, which appear on an energy label. This Section applies to all single-phase

    non-ducted appliances that fall within the Scope of this Standard, and to three-phase

    appliances and ducted single-phase appliances which the supplier elects to register or haverecords kept for energy labelling.

    2.2 GENERAL

    Energy labels may not be fixed to appliances that do not comply with the requirements ofthis Section. Energy labels are provided for cooling only units, heating only units and

    heating and cooling units. Units that have the capability to both heat and cool shall be

    labelled as a heating and cooling unit, except where the heating is provided only by meansof resistive heating, in which case it shall be labelled as cooling only (refer to Clause 5.3.4).

    The capacity and energy values shown on the energy label are based on the rated capacity

    and the rated power, as claimed by the manufacturer. The values on the energy label shallbe consistent with the capacity on the models rating nameplate or all other data in anyassociated product literature (or both) for the specified conditions. The Star Rating Index of

    the airconditioner shall be based on the tested average energy efficiency ratio (EER), and

    the tested average coefficient of performance (COP), as applicable, for the unit(s) tested.

    The results of the unit(s) tested are used to assess the validity of the rated capacity and the

    rated power. The determination of tested capacity (cooling and heating) and tested total

    power input for the unit(s) used for the purposes of energy labelling shall be conductedusing the calorimeter test method as specified in AS/NZS 3823.1.1 or AS/NZS 3823.1.2 for

    condition T1 for cooling or condition H1 for heating, as applicable, or AS/NZS 3823.1.3Table 1 for cooling and Table 2 for heating. Determinations using the outdoor air-

    enthalpy/psychrometric test method of these Standards or determinations using the

    simulation method specified in AS/NZS 3823 are not acceptable.

    2.3 NUMBER OF TESTS AND PROCESSING OF DATA

    2.3.1 Number of units required

    For the purposes of verification of the rated values of a model at least one unit of the

    nominated model shall be tested for capacity, effective power input and EER on cooling orheating and, where applicable, capacity, effective power input and COP on heating inaccordance with AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3. At the

    suppliers discretion more than one unit may be tested.

    2.3.2 Number of tests per unit

    Only one valid test from each unit tested shall be considered when determining the energy

    label data in accordance with AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3.

    2.3.3 Verification of rated values

    As a prerequisite to the determination of values for an energy label, the unit(s) tested shall

    each comply with the following validity criteria for cooling and heating, as applicable:

    (a) Tested effective power input for each unit ......... .......... ......... ...... 1.05 rated power.

    (b) Tested cooling and heating capacity for each unit .......... ......... . 0.95 rated capacity.Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    14/73

    AS/NZS 3823.2:2005 12

    COPYRIGHT

    2.4 COMPARATIVE ENERGY CONSUMPTION (CEC)

    The CEC of an airconditioner model is calculated by the following equation:

    )(kWpowerratedCEC = . . . 2.4

    CEC is in kW rounded to the nearest 0.01. Rated power is in kilowatts.The CEC is determined for cooling and heating, as applicable.

    2.5 STAR RATING INDEX (SRI)

    2.5.1 General

    The equations for SRI in the following clauses are derived from a market analysis in 1998

    and were introduced in 2000. The revised equations to be introduced in 2008 reflectimprovements in airconditioner efficiency achieved since the introduction of EnergyLabelling. These are documented in Appendix F. The original air conditioner equations

    were introduced in 1987.

    The SRI for a model of airconditioner for cooling and heating, as applicable, shall bedetermined in accordance with Clauses 2.5.2 and 2.5.3 respectively, using the measured

    average values of EER and COP for the unit(s) tested, as applicable. The SRI shall also becalculated and reported for appliances registered only for compliance with minimum energyperformance standard requirements. The value for EER and COP shall be in Watts/Watt.

    2.5.2 SRI cooling

    The SRI for cooling is calculated by the following equation:

    [ ] 3/17)10EERaverageTested(coolingSRI = . . . 2.5(1)

    2.5.3 SRI heating

    The SRI for heating is calculated by the following equation:

    [ ] 3/20)10COPaverageTested(heatingSRI = . . . 2.5(2)

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    15/73

    13 AS/NZS 3823.2:2005

    COPYRIGHT

    2.6 STAR RATING

    The star rating is based on the SRI and is obtained from Table 2.1.

    TABLE 2.1

    DERIVATION OF STAR RATING

    Star Rating Index

    (SRI)Star rating

    SRI

  • 8/10/2019 AS3823-2-2005.pdf

    16/73

    AS/NZS 3823.2:2005 14

    COPYRIGHT

    2.9 MAXIMUM COOLING TEST

    Appliances that carry an energy label shall meet the requirements of the maximum coolingtest set out in AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, as applicable,

    when tested to temperature condition T1 as specified for the maximum cooling test. This

    test may be conducted using either a calorimeter or the outdoor air-enthalpy/psychrometrictest method.

    While all units within a model are required to meet the maximum cooling tests requirementsof AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, only one unit need be testedto confirm this for the purposes of energy labelling and MEPS. Evidence of such a test

    report should be provided on registration.

    2.10 TOP ENERGY SAVER AWARD

    The Top Energy Saver Award Winner (TESAW) is an award system that Governments havecreated to recognize the most efficient products on the market. Products, which have

    qualified for an award may display the text for the relevant award year on the energy labelas specified in Section 5.

    NOTE: Background, criteria, and the method of applying for The Top Energy Saver Award

    Winner is given on www.energyrating.gov.au website.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    17/73

    15 AS/NZS 3823.2:2005

    COPYRIGHT

    S E C T I O N 3 P E R F O R M A N C E C R I T E R I A

    3.1 GENERAL

    The performance criteria set out in Clauses 3.2 to 3.7 shall be met by all units.

    NOTE: Where a system has more than one power supply (e.g., a split system), the whole system

    is considered to be three-phase for the purposes of this Standard where at least one of the external

    power supply systems is three-phase. See Clause 1.6.16 for a definition of a three-phase model.

    3.2 MINIMUM ENERGY PERFORMANCE STANDARD

    For airconditioners manufactured in Australia or New Zealand or imported after the dates

    specified, the EER cooling shall be greater than or equal to the minimum limits given inTable 3.1 or Table 3.2, as applicable. For the purposes of determining the relevant MEPS

    level in Table 3.1 or Table 3.2, rated capacity shall be rounded to the nearest 0.1 kW.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    18/73

    AS/NZS 3823.2:2005 16

    COPYRIGHT

    TABLE 3.1

    MINIMUM ENERGY PERFORMANCE STANDARDS (MEPS)

    MINIMUM REQUIREMENTS FOR AIR COOLED CONDENSER AIR

    CONDITIONERS

    Configuration Cooling

    only or

    reverse

    cycle

    Phase Rated

    cooling

    capacity

    (kW)

    Min

    EER

    1-Oct-

    2001

    Min

    EER

    1-Oct-

    2004

    Min

    EER

    1-Apr-

    2006

    Min

    EER

    1-Oct-

    2007

    Min

    EER

    1-Oct-

    2008

    C/O 1

  • 8/10/2019 AS3823-2-2005.pdf

    19/73

    17 AS/NZS 3823.2:2005

    COPYRIGHT

    C/O 1 0

  • 8/10/2019 AS3823-2-2005.pdf

    20/73

    AS/NZS 3823.2:2005 18

    COPYRIGHT

    TABLE 3.2

    MEPSMINIMUM EER FOR WATER COOLED CONDENSER

    AIRCONDITIONERS(see Note 1)

    Supply

    (No. of

    phases)

    Cooling capacity/Type1 Oct. 2001

    (see Note 2)1 Oct. 2004 1 Oct. 2007

    All capacitiesCooling only (ducted and

    non-ducted)

    N/A 2.45 3.50

    1All capacitiesReverse cycle (ducted and

    non-ducted)

    N/A 2.30 3.50

    < 10 kW 2.25 2.25 3.50

    1012.5 kW 2.30 2.30 3.50

    12.615.5 kW 2.35 2.35 3.50

    15.618.0 kW 2.40 2.40 3.50

    18.118.9 kW 2.45 2.45 3.50

    19.025.0 kW 2.45 2.45 3.50

    25.130.0 kW 2.50 2.50 3.50

    30.137.5 kW 2.55 2.55 3.50

    37.639.0 kW 2.60 2.60 3.50

    39.045.5 kW 2.60 2.60 3.20

    3

    45.665.0 kW 2.65 2.65 3.20

    NOTES:

    1 This table includes requirements for airconditioners with water cooled condensers and water sourced

    heat pumps.

    2 In New Zealand, MEPS became mandatory on 1 July 2002.

    3 The revised MEPS levels and introductory dates for levels beyond 2004 in New Zealand will be

    addressed by an amendment to this Standard.

    3.3 CLASS A EFFICIENCY AIRCONDITIONERS

    The EER cooling for an airconditioner that claims to be Class A efficiency shall be greater

    than or equal to the minimum limits given in Table 3.3.

    TABLE 3.3

    FUTURE MEPS LEVELS BEYOND 2008

    (CLASS A EFFICIENCY)

    MINIMUM EER COOLING

    AIRCONDITIONERS WITH AIR COOLED CONDENSERS

    Rated cooling capacity

    (kW)

    Minimum EER cooling

    (W/W)

    kW 10.0 Under consideration

    10.0 < kW 19.0 3.35

    19.0 < kW 39.0 3.65

    kW > 39.0 3.35Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    21/73

    19 AS/NZS 3823.2:2005

    COPYRIGHT

    3.4 TEST CONDITIONS FOR DETERMINING MINIMUM ENERGY

    PERFORMANCE STANDARDS AND HIGH EFFICIENCY CLAIMS

    The unit shall be operated at rated capacity under the cooling capacity test with

    CONDITION T1 in accordance with AS/NZS 3823.1.1 or AS/NZS 3823.1.2 orAS/NZS 3823.1.3 for the determination of cooling capacity, effective power input, energy

    efficiency ratio and compliance with minimum EER cooling requirements.

    Appliances with variable output compressors, which do not meet the minimum energyperformance standard requirements at rated capacity under CONDITION T1 in

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, may be tested at part load

    operation. Variable output compressors shall be deemed to comply with the minimum EERcooling requirements of this standard if they achieve the minimum required EER when theyare operated at not less than 50% of their rated cooling capacity, under CONDITION T1. A

    separate test report with supporting data is required if compliance with MEPS is not at

    100% of rated capacity.

    3.5 NUMBER OF TESTS AND PROCESSING OF DATA

    For the purposes of demonstrating compliance with minimum energy performance standard

    requirements a report shall be prepared as follows:

    (a) For units registered for energy labelling (on either a mandatory or voluntary basis)and MEPS: one physical test conducted in accordance with AS/NZS 3823.1.1 or

    AS/NZS 3823.1.2 for CONDITION T1 for cooling and CONDITION H1 for heating,or one physical test conducted in accordance with AS/NZS 3823.1.3 to Table 1 for

    cooling and Table 2 for heating, as applicable:

    or

    (b) For units registered for MEPS only: either a simulation of performance as specified in

    AS/NZS 3823.3, or one physical test conducted in accordance with ASNZS 3823.1.1or AS/NZS 3823.1.2 for CONDITION T1 for cooling and CONDITION H1 for

    heating, or one physical test conducted in accordance with AS/NZS 3823.1.3 to Table1 for cooling and Table 2 for heating, as applicable.

    Where appliances are of a configuration not within the scope of AS/NZS 3823.3 (e.g.,

    where technology that cannot be accurately modelled is used, such as unitary systems wherethere is thermal interaction between internal components, water cooled units, non steady

    state behaviour such as defrosting) there is no alternative to a physical test.

    The applicability of energy labelling and MEPS program elements together with relevantapplication dates shall be in accordance with the provisions of Appendix E.

    As a prerequisite to the verification of MEPS compliance, any physical test result used tosupport an application for MEPS shall meet the validity criteria for cooling as set out inClause 2.3.3. For product registered using simulation to AS/NZS 3823.3, the rated capacity

    shall not exceed the capacity obtained by simulation.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    22/73

    AS/NZS 3823.2:2005 20

    COPYRIGHT

    3.6 MINIMUM ENERGY PERFORMANCE STANDARD REQUIREMENTS

    COMPLIANCE

    Evidence of minimum energy performance standard requirements compliance can be

    provided by a report on a physical test to AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or

    AS/NZS 3823.1.3 requirements or for certain product types a report on a simulation test toAS/NZS 3823.3 requirements as specified in Clause 3.5. The report shall demonstrate that

    each appliance meets or exceeds the minimum EER cooling requirement for the appliancecapacity. The claimed capacity and power consumption for both cooling and heating, if

    applicable, shall be substantiated by physical testing or simulation of appliance

    performance for the standard rating conditions set out in Clause 3.5.

    NOTE: An example of airconditioner assessment for MEPS is provided in Appendix A.

    3.7 MEPS VALIDITY (CHECK TESTING)

    Check testing of a product may be either by a physical test or a simulation test. In the caseof dispute, test results obtained by physical testing, using the procedures defined in

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, take precedence over testresults obtained using a simulation model. In the case of a physical test, check testing will

    be undertaken using the calorimeter method wherever possible as this provides a more

    reliable result for verification purposes.

    Generally a screening test is conducted on a single model and if this fails any of the criteriabelow, up to 3 additional units are tested in Stage 2. The rated data shall be accepted as

    valid if the product satisfies the EER requirement and data from the verification test meetsall of the following criteria.

    (a) Tested effective power input ......... .......... ......... ......... ......... ........ 1.10 rated power.

    (b) Tested cooling and heating capacity .......... ......... ......... ......... ... 0.90 rated capacity.

    (c) Tested EER .......................................................MEPS limit and 0.90 rated EER.

    (d) Tested COP ..................................................................................0.90 rated COP.

    NOTES:

    1 Simulation models provide an estimate of system optimum performance under idealized

    operating conditions. Modelling may not take into account variables introduced in the

    physical manufacture of a system, such as airflow across the coils. For this reason actual tests

    may show a performance lower than that estimated by the simulation model. Physical tests

    take priority in this Standard and performance claims based on a simulation model are made

    at the applicants own risk.

    2 More details on check testing and validity criteria can be found in the Administrative

    Guidelines. The most up to date version can be obtained from the www.energyrating.gov.au

    website.

    Where a physical check test is undertaken to validate a registration, the laboratory should

    provide all relevant physical measurements (such as pressure drops and refrigeranttemperatures etc.) that will allow the physical check test to be fully compared with the

    original test report or the simulation result (refer to Appendix C).

    Check testing will be undertaken using the conditions (e.g. settings, duct pressure and airflow rates) specified in the application for registration for MEPS and energy labelling

    (where applicable).

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    23/73

    21 AS/NZS 3823.2:2005

    COPYRIGHT

    3.8 VARIABLE OUTPUT COMPRESSORS

    Products that have variable output compressors (e.g., multi-speed or inverter-driven orvariable speed compressors) have this indicated on the www.energyrating.gov.au website

    and on the energy label (where applicable). These products may also claim EER and COPfigures (as applicable) at 50% of the rated capacity for CONDITIONS TI and HI in

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 (as applicable) for display onthe www.energyrating.gov.auwebsite. Performance data shall be displayed on the websiteonly when the claim is supported by test data at the time of registration or listing.

    NOTE: Such products can have a high relative eff iciency at part load. If these products are

    identified to the relevant regulatory authority and supporting test data is provided, the part load

    performance figures will be displayed on the www.energyrating.gov.au website. Generally, an

    output in the range of 50% to 60% is acceptable for this listing.

    3.9 COEFFICIENT OF PERFORMANCE AT LOW TEMPERATURE

    NOTE: Minimum coefficient of performance of heat pumps at low ambient temperature is under

    consideration by regulatory authorities.

    3.10 STANDBY POWER AND CRANK CASE HEATERS

    All products shall have the following data measured for the model as set out in

    AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 (as applicable):

    (a) Off mode power consumption (Watts).

    (b) Passive standby mode power consumption, where applicable (Watts).

    (c) Whether or not the product has any form of crank case heating.

    (d) Where a crank case heater is present, the average crank case heater powerconsumption under outdoor conditions specified in the relevant standards for all

    airconditioner types (i.e., whether cooling only, heating only or reverse cycle).

    During registration or listing, the above data shall be provided as set out in Appendix C.Relevant data will be displayed on the www.energyrating.gov.auwebsite.

    3.11 LOAD CONTROL CAPABILITY

    Planning is under way to mandate facilities for external load control and communicationscapability for certain airconditioner types within the scope of this standard. These will beincluded in a future amendment to this Standard.

    3.12 POWER FACTOR

    The average power factor during cooling and heating capacity rating tests shall be reportedfor all products.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    24/73

    AS/NZS 3823.2:2005 22

    COPYRIGHT

    S E C T I O N 4 A P P L I C A T I O N A N D T E S T

    R E S U L T F O R M A T S

    4.1 APPLICATION FOR REGISTRATION

    4.1.1 General

    Where the relevant regulatory authority requires registration or approval of energy labels or

    minimum energy performance standard requirements, Clauses 4.1.2 and 4.1.6 shall apply.

    NOTE: Australia requires registration for energy labell ing and MEPS. Three-phase heating only

    models do not require registration for MEPS; however, data to support claimed performance are

    still required under Clause 4.2.

    4.1.2 Registration

    For an energy labelling and MEPS application in accordance with Appendix B, a test report

    to AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 or a summary report inaccordance with Appendix C shall be provided. For a MEPS application in accordance withAppendix B, a test report to AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3 or

    a summary report in accordance with Appendix C shall be provided where physical testshave been conducted. Where a simulation to AS/NZS 3823.3 has been conducted for a

    MEPS application in accordance with Appendix B, a report in accordance with

    Appendices A and B of AS/NZS 3823.3 shall be provided.

    NOTES:

    1 Applications in the form of computer printouts, which present all the application data in a

    similar layout to the forms in Appendix B, are equally valid.

    2 Where HPRATE has been used for a simulation to support a MEPS application, a copy of the

    project (sys) file is regarded as equivalent to a report in accordance with Appendices A and Bof AS/NZS 3823.3. Where values other than the defaults for pressure drop, subcooling or

    superheating are used in the project file (see Appendix A), test data to support the use of

    these values will be required.

    For registration, the relevant state regulatory authority shall be contacted.

    NOTE: Detai ls of the relevant regulatory bodies are available from www.energyrating.gov.au

    website.

    4.1.3 Test report

    A test report in accordance with AS/NZS 3823.1.1, AS/NZS 3823.1.2, AS/NZS 3823.1.3 or

    AS/NZS 3823.3, as applicable, for each model tested shall be held by the appliance supplierif not supplied with the original registration.

    The documents required by this Section shall be made available to the relevant regulatory

    authority upon request. Records shall be retained for at least five years after the last date ofmanufacture or import, whichever is applicable.

    4.1.4 MEPS transition

    All products within the scope of MEPS manufactured or imported for sale in Australia on orafter the relevant MEPS date shall meet the relevant MEPS requirements. Such units shall

    hold a valid registration at the time of sale, which shall indicate compliance with theseMEPS requirements.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    25/73

    23 AS/NZS 3823.2:2005

    COPYRIGHT

    Single phase non-ducted household products

  • 8/10/2019 AS3823-2-2005.pdf

    26/73

    AS/NZS 3823.2:2005 24

    COPYRIGHT

    4.3 DATE OF MANUFACTURE INFORMATION

    The date of manufacture may be non-encrypted, encrypted or able to be determined from aserial number or other markings on the appliance and shall be visible when the appliance is

    in its position of normal use. Information on how to determine the date of manufacture shall

    be provided on the registration form (see Appendix C).NOTES:

    1 Regulators will use the date of manufacture as a guide as to when a product may have been

    available for sale in Australia. It is therefore preferable to be able to determine at least the

    month and year of manufacture from information on the appliance. This does not however

    preclude the use of other markings, for example serial numbers, which indicate those

    appliances manufactured within a period of time, with such details given on the registration

    form.

    2 Irrespective of the information marked on the appliance, local manufacturers or importers

    may be required to provide evidence of the actual manufactured or imported date if requested

    by a regulator.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    27/73

    25 AS/NZS 3823.2:2005

    COPYRIGHT

    S E C T I O N 5 P R I N T I N G A N D P L A C E M E N T O F

    E N E R G Y L A B E L S

    5.1 PLACEMENT

    The label shall be adhered, or attached as a swing tag, on the front of the unit or displayfront. The label may be attached to the exterior of the packaging. The label shall be

    attached to the unit when the unit is removed from its packaging for display purposes.

    5.2 MATERIAL AND SHAPE

    The label shall be of durable cardboard, if it is to be attached as a swing tag, or be self-adhesive and shall be cut to one of the outlines shown in Figures 5.2, 5.3 or 5.4, as

    applicable. A trim or die cut margin of up to 2 mm around the label is acceptable.

    5.3 COLOURS5.3.1 Cooling only label

    The cooling only label shall be of a white background, and shall be printed in the following

    four colours (see Figure 5.2):

    (a) Pantone 300 (Blue).

    (b) Pantone Black.

    (c) Pantone 116 (Yellow).

    (d) Pantone 340 (Green).

    5.3.2 Heating and cooling label

    The heating and cooling label shall be of a white background, and shall be printed in the

    following five colours (see Figure 5.3):

    (a) Pantone 300 (Blue).

    (b) Pantone Black.

    (c) Pantone Warm Red.

    (d) Pantone 116 (Yellow).

    (e) Pantone 340 (Green).

    5.3.3 Heating only label

    The heating only label shall be of a white background, and shall be printed in the following

    four colours (see Figure 5.4):

    (a) Pantone Warm Red.

    (b) Pantone Black.

    (c) Pantone 116 (Yellow).

    (d) Pantone 340 (Green).

    5.3.4 Electric heating

    Where a unit incorporates user-controlled electric heating devices, the note shown in

    Figure 5.1 shall be included on the label. The text of the note shall be printed inPantone Warm Red (see Figure 5.1, Note 2) under the power input.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    28/73

    AS/NZS 3823.2:2005 26

    COPYRIGHT

    Where the unit has manually switchable electric heating devices as its sole form of heating,

    a cooling only label shall be used. Where the unit has manually switchable electric heatingdevices as supplementary heating, a heating and cooling label shall be used.

    NOTE: User-controlled electric heating devices are not included in the determination of unit

    energy performance, while automatically controlled devices are included.

    5.4 LABEL REQUIREMENTS

    The font shall be Gill Sans, Humanist 521 or Hammersmith. The preferred font is Gill Sansas illustrated in the Figures. Only one font shall be used on a label. The fields (a), (b), (c),(d) and (e) of Figure 5.1 shall comply with the following requirements:

    (a) Field a This band shall terminate according to the appliances star rating, eitherbisecting the relevant star for a rating of half a star or, for a rating of only full stars,bisecting the gap between the relevant star and the next highest on the scale.

    (b) Field b The brand and the model designation shall be inserted here. The wordingshould be complete and concise. The lines shall not exceed a measure of 65 mm. Theyshould have normal spacing of letter, line and word and they shall be centred

    horizontally in the area allowed. In the case of split systems, where the indoor andoutdoor components have different model numbers, model numbers for both shallappear on the label.

    (c) Field c This panel shall contain the rated total cooling capacity and rated heatingcapacity, as applicable (capacity output), and the comparative energy consumption(CEC) (power input) for cooling and heating, as applicable. The Figures that apply to

    the particular appliance shall be of the font and size indicated and shall be centred in

    the blue panel for cooling and the red panel for heating. The spacing between thefigures of a three-figure number is the same as for a four-figure number.

    (d) Field d All models shall include this text and the associated check boxes. Yesshallbe ticked if the model meets the requirements of Clause 3.8. Otherwise, Noshall beticked.

    (e) Field e This panel shall form a solid green bar. Where the product has qualified forand has been approved to receive a TESAW award, the text shown in Figure D4 forthe relevant award year may be shown on the energy label. Appendix D shows

    additional information about label dimensions for this option.

    NOTE: In addition to the requirements of this Section, label dimensions should be in accordance

    with Appendix D. Additional material to assist in the printing of labels may be available from,

    and any queries regarding such should be directed to, the relevant regulatory authority.

    5.5 SAMPLE LABELS

    Examples of printed energy labels for airconditioning appliances are shown in Figures 5.2,5.3 and 5.4.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    29/73

    27 AS/NZS 3823.2:2005

    COPYRIGHT

    NOTES:

    1 The preferred label width is 90 mm. For online printing, the external diameter of the red/blue star rating

    arch may be reduced to 86 mm to allow for a 2 mm registration error such that the red print does not

    extend over the label edge or result in a white band underneath it (see Appendix D).

    2 This text shall be omitted if there is no user-controlled electric heating device installed (see Clause 5.3.4).

    3 The fields (a), (b), (c), (d) and (e) of this Figure shall contain the information as required by Clause 5.4.

    4 Font definitions for the reverse cycle label in this Figure are applicable to cooling only and heating only

    labels.

    5 See Clause 5.3 for specification of colours. On some printers and display devices, the colours in this

    sample label may appear different to those specified.

    FIGURE 5.1 DETAILS OF LABELHEATING AND COOLING UNIT

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    30/73

    AS/NZS 3823.2:2005 28

    COPYRIGHT

    NOTE: See Clause 5.3 for specif ication of colours. On some printers and display devices, the colours in this

    sample label may appear different to those specified.

    FIGURE 5.2 EXAMPLE OF LABELCOOLING ONLY UNIT

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    31/73

    29 AS/NZS 3823.2:2005

    COPYRIGHT

    NOTE: See Clause 5.3 for specif ication of colours. On some printers and display devices, the colours in this

    sample label may appear different to those specified.

    FIGURE 5.3 EXAMPLE OF LABELHEATING AND COOLING UNIT

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    32/73

    AS/NZS 3823.2:2005 30

    COPYRIGHT

    NOTE: See Clause 5.3 for specif ication of colours. On some printers and display devices, the colours in this

    sample label may appear different to those specified.

    FIGURE 5.4 EXAMPLE OF LABELHEATING ONLY UNIT

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    33/73

    31 AS/NZS 3823.2:2005

    COPYRIGHT

    APPENDIX A

    EXAMPLES OF ENERGY EFFICIENCY CALCULATIONS

    (Informative)

    A1 GENERAL

    This Appendix provides an example of energy efficiency calculations. Paragraphs A2 andA3 show the calculations involved in the determination of the energy label details for a

    hypothetical single-phase reverse cycle household airconditioner for MEPS and energylabelling and the determination of CEC, SRI and star rating. Paragraph A4 shows thecalculations involved in the determination of MEPS testing and compliance for a

    hypothetical reverse-cycle three-phase split packaged airconditioner.

    A2 TEST RESULTS, AVERAGES AND RATED VALUES

    A hypothetical single-phase reverse cycle window/wall household airconditioner isconsidered for MEPS and energy labelling.

    On cooling, it has a rated capacity of 4.45 kW with a rated power input of 1.61 kW.

    On heating, it has a rated capacity of 4.75 kW with a rated power input of 1.64 kW.

    This unit is a single-phase airconditioner within the scope of AS/NZS 3823.1.1 and

    according to Appendix E, compliance requirements are for labelling and MEPS (L).

    Data from testing one sample in accordance with AS/NZS 3823.1.1 is shown in Tables A1and A2. Values are for CONDITION T1 for cooling and CONDITION H1 for heating.

    Before the energy labelling details are calculated, the unit should be checked for MEPScompliance.

    A2.1 Verification of MEPS requirements

    In order to verify that this particular model complies with MEPS, the unit is required toexceed the MEPS levels for that model as listed in Table 3.1. The tested EER in Table A1 is2.689 while the rated EER is 2.764.

    This unit complies with the MEPS requirements for 2004 (single-phase reverse cycle non-ducted) as the rated and tested EER exceed the minimum EER specified in Table 3.1 (i.e.,EER >2.3). While the rated value for EER just meets the MEPS 2006 requirements for

    single-phase non-ducted non-split reverse cycle (i.e., EER >2.75), the test result does notsupport this claim, so compliance with this requirement cannot be claimed.

    A2.2 Verification of rated values

    The test results should now be analysed to ensure that they verify the claimed rated valuesas specified in Clause 2.3.3. For capacity and effective power input, the test value for thetest unit is compared with the rated values to ensure that they lie within the required units.

    A summary of the verification comparisons for cooling and heating are contained inTables A3 and A4.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    34/73

    AS/NZS 3823.2:2005 32

    COPYRIGHT

    TABLE A1

    COOLING TEST RESULTS

    Specification RatedTested

    unit 1

    Cooling capacity (kW) 4.45 4.415

    Effective power input (kW) 1.61 1.642

    EER 2.764 2.689

    TABLE A2

    HEATING TEST RESULTS

    Specification RatedTested

    unit 1

    Heating capacity (kW) 4.75 4.772

    Effective power input (kW) 1.64 1.701

    COP 2.896 2.805

    TABLE A3

    VERIFICATION OF RATED

    COOLING SPECIFICATIONS

    (PROPORTION OF RATED RESULT)

    Tested/Rated Unit 1

    Verification

    limit for

    each unit

    Cooling capacity 0.992 0.95

    Effective power input 1.020 1.05

    NOTES:

    1 The tested value for cooling capacity is greater than

    0.95 of the rated capacity for each unit, so the rated

    capacity is valid.

    2 The tested value for effective power input is less

    than 1.05 the rated power for each unit, so the rated

    power is valid.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    35/73

    33 AS/NZS 3823.2:2005

    COPYRIGHT

    TABLE A4

    VERIFICATION OF RATED

    HEATING SPECIFICATIONS

    (PROPORTION OF RATED RESULT)

    Tested/Rated Unit 1Verification

    limit for

    each unit

    Heating capacity 1.005 0.95

    Effective power input 1.037 1.05

    NOTES:

    1 The tested value for heating capacity is greater

    than 0.95 of the rated capacity for each unit, so

    the rated capacity is valid.

    2 The tested value for effective power input is less

    than 1.05 the rated power for each unit, so the

    rated power is valid.

    A3 CALCULATION OF ENERGY LABEL VALUES

    A3.1 Calculation of comparative energy consumption (CEC)

    When the rated specifications have been verified, the CEC can be calculated from the rated

    power.

    CEC is calculated in accordance with Clause 2.4.

    Example:

    (a) CEC cooling = rated power

    = 1.61 kW

    (b) CEC heating = rated power

    = 1.64 kW

    A3.2 Calculation of Star Rating Index (SRI)

    SRI for cooling and heating are calculated from the applicable equations in Clause 2.5.Note that the tested values for EER and COP (not the rated values) are used to calculate

    SRI.

    Example:(a) SRI cooling = [ (EERav 10)17 ] / 3

    = [ (2.689 10) 17 ] / 3

    = 3.2967

    (b) SRI heating = [ (COPav 10) 20 ] / 3

    = [ (2.805 10) 20 ] / 3

    = 2.6833

    Star rating is as given in Table 2.1. Therefore, the cooling star rating for this model is 3.0

    and the heating star rating for this model is 2.5.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    36/73

    AS/NZS 3823.2:2005 34

    COPYRIGHT

    A4 MEPS FOR AIRCONDITIONERS

    A hypothetical reverse cycle three-phase split packaged airconditioner is considered forMEPS.

    On cooling, it has a rated capacity of 23.3 kW with a rated power input of 9.2 kW.

    On heating, it has a rated capacity of 28.6 kW with a rated power input of 9.7 kW.

    This unit is an airconditioner within the scope of AS/NZS 3823.1.1 and according to

    Appendix E, and compliance requirements are for MEPS (M).

    Data from testing a single sample in accordance with AS/NZS 3823.1.1 yields a result of

    22.9 kW cooling capacity and an effective power input of 9.31 kW, yielding a tested EER

    of 2.4597. Data from testing a single sample in accordance with AS/NZS 3823.1.1 yields aresult of 28.0 kW heating capacity and an effective power input of 9.9 kW, yielding a testedCOP of 2.8283.

    Before MEPS compliance is verified, the test results should be analysed to ensure that they

    verify the claimed rated values as specified in Clause 2.3.3. For capacity and effectivepower input, the test values for each test unit are compared with the rated values to ensure

    that they lie within the required limits. In this case the measured cooling capacity is 0.983

    of the rated value and the effective power input is 1.012 of the rated value, so the claimedvalues are valid. Similarly, the claimed heating results are valid.

    The rated capacity of the model is 23.3 kW, therefore from Table 3.1 the MEPS 2001

    requirement is that EER shall be > 2.45. As the tested value is 2.4597, which is greater than2.45, the model complies with MEPS 2001. This unit does not comply with the MEPS

    requirements for 2007, or the Class A Efficiency requirements specified in Table 3.3.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    37/73

    35 AS/NZS 3823.2:2005

    COPYRIGHT

    APPENDIX B

    FORMAT OF APPLICATION FOR REGISTRATION OF ANAIRCONDITIONER FOR ENERGY LABELLING AND MEPS

    (Normative)

    B1 INTRODUCTION

    This Appendix sets out the required format for submitting an application for registration.

    NOTES:

    1 The contact details supplied by applicants in this form or online may be used by other

    Government agencies to keep applicants informed of forthcoming regulatory changes that

    may affect the product registered under this Standard. Otherwise, contact details are treated as

    private and confidential.

    2 NOTICE OF RIGHT TO DISCLOSE INFORATIONThe information you submit on this

    application will be used for the purposes of assessing your application and the performance ofstatutory responsibilities. The information, which you have submitted may be disclosed to

    other state and territory or New Zealand energy efficient government bodies (or their agents)

    who may use the information only for the purposes of carrying out their duties and or

    responsibilities including comparing efficiency claims. The information will also be entered

    onto the Online Registration Database. More information about this database is available at

    www.energyrating.gov.au website.

    B2 SCOPE

    This Appendix sets out the required format for submitting an application for registrationand record keeping.

    B3 GUIDANCE ON THE USE OF THIS APPLICATION FORM

    The Appendix has been formatted and structured to align with the online registration system

    for energy labelling and MEPS.

    The preferred method of making an application for energy labelling and/or MEPS is via theonline registration system to ensure compliance with the most current registration

    information requirements. To use this system, you need to apply for a user name andpassword. Once a user name has been issued, you will have full access to the online system.Details on how to apply for a user name and password and how to log on to the online

    system can be found at www.energyrating.gov.auwebsite.

    B3.1 All registrations

    If the unit meets a subsequent MEPS level in addition to the one currently in force, this

    should be indicated in the application (refer to Section 4 for details). Only a single unitneeds to be tested and report submitted when applying for energy labelling to this Standard(AS/NZS 3823.2:2005). Any units that carry an energy label shall be accompanied by a

    physical test (simulation for energy labelling is not permitted). Any MEPS only application

    may be accompanied by either a physical test or a simulation. Where energy labelling is notmandatory, the applicant may choose to label the product on a voluntary basis, but all the

    normal rules for energy labelling will apply (e.g., physical test is required).

    B3.2 Submissions to the New Zealand regulator

    Applicants who have listed their product with the New Zealand regulator and intend to relyon the goods access provisions of the Trans Tasman Mutual Recognition Arrangement tosell that product in Australia without registering it with an Australian regulator shallcomply with the following conditions:A

    ccessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    38/73

    AS/NZS 3823.2:2005 36

    COPYRIGHT

    (a) The company responsible for the manufacture or importation of this product shall

    have its registered offices in New Zealand.

    (b) In respect of the product imported or manufactured by the applicant, this product

    shall be either imported into New Zealand (but not directly into Australia) or

    manufactured in New Zealand (not in Australia).(c) If this product is imported into Australia, then it shall be imported through

    New Zealand.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    39/73

    37 AS/NZS 3823.2:2005

    COPYRIGHT

    B4 APPLICATION FORM

    APPLICATION FOR REGISTRATION OF

    AN AIRCONDITIONER FOR ENERGY EFFICIENCY

    (Please type or print)

    SECTION 1 APPLICATION DETAILS

    I hereby apply for registration of an electrical appliance/s for the purpose of energy labelling

    (where applicable) and MEPS.

    SECTION 2 APPLICANT DETAILS

    Name of applicant:

    Company name:

    Company address:

    Name:

    Address:

    Position/Title:

    Telephone:

    Facsimile:

    Contact person:

    (A name, addressand contact detailsfor a person inAust ralia or

    New Zealand shallbe provided)

    E-mail:

    The Standard to which this application is

    made?

    AS/NZS 3823.2 (2003)

    AS/NZS 3823.2 (2005)

    What is this application for? MEPS only/Labelling and

    MEPS

    Is this product to be used exclusively for

    commercial applications?

    Yes/No

    Is the application for a single model or a

    family of models?

    Single/Family

    (indicate correct answer)

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    40/73

    AS/NZS 3823.2:2005 38

    COPYRIGHT

    SECTION 3 DESCRIPTION OF APPLIANCE

    Brand name:

    System

    Name

    Indoor Unit* Outdoor

    Unit*

    Model 1

    Model 2

    Model 3

    Model designation (List all models

    covered by this application. This

    can either be a number or name or

    combination of the two that will

    identify the particular product. Add

    additional rows if more than 3

    models)

    * Indicate only for split systems

    Family model designation, if

    applicable, for above models:Model/family number(s) to appear

    on the energy rating label where

    provided and on the energyrating

    website:

    (indicate correct answer)

    Display

    List of individual models noted above

    Or

    Family model designation noted above

    Country of manufacture: Australia/NZ/Otherplease specify

    Where is this product to be sold:

    (indicate each country)

    NOTE: The response will determine

    how the model will be displayed on

    Government energy rating websites in

    Australia and New Zealand. If a model

    is not indicated as being available in a

    country, that model will not appear on

    websites specific to that country.

    Australia

    New Zealand

    Others

    (See pick list on electronic registration system)

    Year and month in which model

    first available in Australia orNew Zealand:

    Year Month

    Date of manufacture traceability (of

    package unit or indoor unit if split

    system):

    Is the date of manufacture

    permanently marked on the rating

    plate in a non-encrypted format?

    Yes

    Date format:

    No

    Provide details:

    If yes, provide an example of the

    date format.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    41/73

    39 AS/NZS 3823.2:2005

    COPYRIGHT

    If no, provide details on how to

    determine (from the serial number

    or other permanent markings for

    this model) whether the date of

    manufacture was either

    (a) in the 5 year period prior to

    the introduction of MEPS; or

    (b) in the 5 year period

    subsequent to the

    introduction of MEPS.

    Date of manufacture traceability (of

    outdoor unit if split system):

    Is the date of manufacture

    permanently marked on the rating

    plate in a non-encrypted format?

    Yes

    Date format:

    No

    Provide details:

    If yes, provide an example of the

    date format.

    If no, provide details on how to

    determine (from the serial number

    or other permanent markings for

    this model) whether the date of

    manufacture was either

    (a) in the 5 year period prior to

    the introduction of MEPS; or

    (b) in the 5 year periodsubsequent to the

    introduction to MEPS.

    Does this model or family replace

    or supplement another model or

    family with identical energy

    consumption and energy efficiency

    rating?

    (indicate correct answer)

    Yes/No

    If yes, indicate relevant details: Model name Model number Registration

    number

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    42/73

    AS/NZS 3823.2:2005 40

    COPYRIGHT

    SECTION 4 TESTING AND TEST REPORT

    Is a test report or a summary

    report in accordance with

    Appendix C attached?

    (indicate correct answer)

    YesA single physical test report is attached

    YesA simulation test report is attached

    YesA summary report to Appendix C is attached

    NoNo test reports are attached

    If no report is attached, note the

    source registration number of the

    appliance upon which this

    application relies for its report:

    (proceed to Sect ion 5 if no report

    attached)

    Test laboratory type:

    (indicate correct answer)

    Own in-house laboratory:

    Independent laboratory:

    Test laboratory name:

    Test laboratory address:

    Test laboratory location:

    (indicate correct answer)

    Australia:

    New Zealand:Other(please specify):

    Test laboratory accreditation: NATA

    NATA recognized (please specify)

    Unknown/none

    Other(please specify):

    Test Standard used:

    (indicate relevant Standard, year,

    revision and any amendment)

    AS/NZS 3823.1.1 (non-ducted)

    AS/NZS 3823.1.2 (ducted)

    AS/NZS 3823.1.3 (water sourced/cooled)

    AS/NZS 3823.3 (simulation)

    Other(please specify)

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    43/73

    41 AS/NZS 3823.2:2005

    COPYRIGHT

    Modelling software used (a) Nil (physical test report/s supplied)

    (b) Oakridge softwareNOT using default

    settings

    (c) Oakridge softwareusing default settings (HP

    Rate File Lodged with this application)

    NOTE: HPRATE and Oakridge MK III

    and IV do not support modelling of

    certain airconditioner types such as

    window wall models, unitary systemswhere there is thermal interaction of

    the components, any heat mode

    where defrost ing occurs, models with

    water cooled condensers

    If Oakridge software was used,

    which version was used?

    MK III MK IV MK V

    Test report numbers:

    (fill in as applicable)

    Does this airconditioner have

    separate indoor and outdoor

    units?

    Yes/No

    Test room indoor type used:Calorimeter/Enthalpy test room/not applicable

    (simulation)

    Test room outdoor type used:Calorimeter/Enthalpy test room/water loop

    equipment/not applicable (simulation)

    Test

    unit

    SERIAL

    NUMBER

    Unitary unit or

    indoor unit if split

    system

    SERIAL

    NUMBER

    Outdoor unit if

    split system

    Test

    date

    Serial number of test units/s and

    date tested:

    (Fill in fields as applicable to the

    applicationUnit 2 and 3 only

    need to be filled in for labelling

    applications to the 2001

    Standard)

    Rated voltage and frequency of

    tested unit/s

    Unitary unit or

    indoor unit if

    split system

    Outdoor unit if

    split system

    Rated voltage

    range (V)

    Rated frequency

    (Hz)

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    44/73

    AS/NZS 3823.2:2005 42

    COPYRIGHT

    Tested voltage and frequency of

    tested unit/s

    Unitary unit or

    indoor unit if

    split system

    Outdoor unit if

    split system

    Tested voltage

    (V)

    Test frequency

    (HZ)

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    45/73

    43 AS/NZS 3823.2:2005

    COPYRIGHT

    SECTION 5 SPECIFIC APPLICANCE DETAILS

    Appliance dimensions

    (Advisory only):

    (for split systems note only

    dimensions of the internal unit)

    Width (mm): Height (mm): Depth (mm):

    Aircondi tioner type:

    (indicate correct answer)

    Cooling only

    Reverse cycle

    Heating only

    Power supply: Single-phase

    Three-phase

    Refrigerant: R22, R114, R502, R134, R32, R123, R124, R125

    R143A, R152A, R290, R410A, R3212560, R507

    R14312555, R404, R407

    Other (please specify)

    A/C Configuration 1Air

    distribution:

    (indicate correct answer)

    Ducted/Non ducted

    A/C Configuration 2Type:

    (indicate correct answer)

    Window/Wall

    Spot cooler

    Portable cooler

    Single split systemDouble/triple split system

    Multiple split system

    Packaged

    Non-ducted split system indoor

    unit mounting:

    Wall-hung

    Under ceiling

    Floor mounted

    Cassette

    Floor/Ceiling

    A/C conf iguration 3Heat

    transfer:

    (indicate correct answer)

    Heat source (heating)

    Air

    Cooling tower

    (Reversible)

    Water loop (refer

    AS/NZS 3823.1.3)

    Ground water or

    Ground loop (refer

    AS/NZS 3823.1.3)

    N/ACooling only

    Heat sink (cooling)

    Air

    Cooling tower

    Water loop (refer

    AS/NZS 3823.1.3)

    N/AHeating only

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    46/73

    AS/NZS 3823.2:2005 44

    COPYRIGHT

    Does this airconditioner have a

    variable output compressor? (e.g.

    variable speed drive (inverter) or

    a multi-speed compressor)

    (indicate correct answer)

    Yes/No

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    47/73

    45 AS/NZS 3823.2:2005

    COPYRIGHT

    SECTION 6 TEST RESULTS

    TEST RESULTSCOOLINGCONDITION T1

    COOLING

    POWER

    Rated effective power input (kW)*

    Labelled CEC (kW)*

    (Fill in for labelling applications only)

    Tested cooling power inputTest 1 (kW)**

    COOLING

    CAPACITY

    Rated sensible cooling capacity (kW)*

    Rated dehumidifying effect (kW)*

    NOTE: 1 litre water extracted per hour = 0.683 kW

    Rated total cooling capacity (kW)*

    Tested total cooling capacityTest 1 (kW)**

    EER EERTest 1**

    Does the air-cooled condenser evaporate the condensate?

    (indicate correct answer)

    Yes/No

    Indicate fan and any other settings for determination of rated capacity:

    Indicate method of obtaining fixed output on airconditioners with variable

    output capacity:

    For ducted systems, indicate air flow rate (cubic metres/second):

    For ducted systems, indicate static pressure (Pa):

    Average power factor for the cooling test:

    Does this model comply with the maximum cooling test for

    Condition T1: (include correct answer)Note this only applies to applications for energy labellingIf the

    application is for MEPS only then select N/A.

    Supply a test report on a single unit to support this claim (see Clause 2.9).

    Yes/No/N/A

    * to 2 decimal places

    ** to 3 decimal places

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    48/73

    AS/NZS 3823.2:2005 46

    COPYRIGHT

    TEST RESULTSHEATINGCONDITION H1

    Does this model incorporate electric resistance heating?

    (indicate correct answer)

    Yes/No

    HEATING

    POWER

    Rated effective power input (kW)*

    Labelled CEC (kW)*

    (Fill in for labelling applications only)

    Tested heating power inputTest 1 (kW)**

    (Fill in for labelling applications only)

    HEATING

    CAPACITY

    Rated total heating capacity (kW)*

    Tested heating capacityTest 1 (kW)**

    (Fill in for labelling applications only)

    COP COPTest 1**

    (Fill in for labelling applications only)

    Indicate fan and any other settings for determination of rated capacity:

    For ducted systems, indicate air flow rate (cubic metres/second):

    Indicate method of obtaining fixed output on airconditioners with variable

    output capacity:

    For ducted systems, indicate static pressure (Pa):

    Average power factor for the heating test:

    RESULT SUMMARYFor labelling applications only

    COOLING HEATING

    Tested EER** and COP** (as applicable):

    Star Rating Index (see Clause 2.5):

    Star Rating:

    * to 2 decimal places

    ** to 3 decimal places

    Does this model have a crank case heater? Yes/No

    Average power in off mode (where applicable).(Where present, off mode power shall include the energyconsumption of the crankcase heater measured at 20Cas defined in the relevant Part 1 Standard).

    Watts

    Average power in passive standby mode (whereapplicable).Where present, passive standby mode power shall includethe energy consumption of the crankcase heatermeasured at 20C as defined in the relevant Part 1Standard).

    Watts

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    49/73

    47 AS/NZS 3823.2:2005

    COPYRIGHT

    If a crankcase heater is present, state the average powerat an ambient of 7C in off mode (or in passive standbymode if off mode is not applicable).Include the energy consumption of the crankcase heaterdefined in the relevant Part 1 Standard.

    Watts

    Data for both off mode and passive standby mode wherepresent. All products have at least one of these modes.Refer to relevant Part 1 for definitions and conditions.

    Accessedb

    yRMITUNIVERSITYLIBRARYon29Ma

    r2006

  • 8/10/2019 AS3823-2-2005.pdf

    50/73

    AS/NZS 3823.2:2005 48

    COPYRIGHT

    SECTION 7 VOLUNTARY DECLARATIONLOW TEMPERATURE HEATING

    PERFORMANCE

    NOTE: At the time of the publication of this Standard the requirements of this Section were

    under consideration by regulatory authorities.

    SECTION 8 VOLUNTARY DECLARATIONVARIABLE OUTPUT COMPRESSOR

    PERFORMANCE

    NOTE: This Section is to be filled in only by those manufacturers that wish to indicate part

    load performance of products that have a variable output compressors (e.g., multi-speed or

    inverter-driven compressor) on the www.energyrating.gov.au website as set out in

    Clause 3.8. Only EER and COP will be shown on the website.

    Voluntary declarationPart load (50%)

    (Applicable to applications to AS/NZS 3823.2 only for air-conditioners with variable

    output compressors)

    Have you supplied a test report for part load operation

    as part of this application?

    (indicate correct answer)

    Yes/No

    Do you want part load data to be indicated on the

    energyrating website?

    (indicate correct answer)

    Yes/No

    Part load test results

    COOLING

    POWER

    (50% LOAD)

    Tested cooling power input (kW)**

    (Not applicable to heating only airconditioners)

    COOLING

    CAPACITY

    (50% LOAD)

    Tested total cooling capacity (kW)**

    (Output should be in the range 50% to 60% rated

    capacity)

    (Not applicable to heating only airconditioners)

    EER

    (50% LOAD)

    EER

    (Not applicable to heating only airconditioners)

    COOLING

    CAPACITY

    Where applicable indicate method of obtaining fixed

    output on airconditioners with variable output

    capacity

    HEATING POWER

    (50% LOAD)

    Tested heating power input (kW)**

    (Not applicable to cooling only airconditioners)

    HEATING

    CAPACIT


Recommended