Asbestos & Lead Based Paint Assessment
City of Anderson 710 A&B Beechwood Avenue
Anderson, South Carolina 29624
Prepared for: City of Anderson
Community Development Department 601 South Main Street
Anderson, South Carolina 29624
Prepared by: Apex Environmental Management, Inc.
7 Winchester Court Mauldin, South Carolina 29662
Project Number: 1115-232
March 4, 2015
7 Winchester Court Mauldin, SC 29662 864.404.3210 office 864.404.3213 fax www.apex-ehs.com
SERVICES
Indoor Air Quality
Mold Remediation
Asbestos & Lead
Industrial Hygiene
Worker Health & Safety
Mold Consulting
Moisture
Management Plans
Safety
Assessment
Environmental Site Assessments
Hazard
Communication
Apex Project Number 1115-232
March 4, 2016 Ms. Erica Craft City of Anderson Community Development Department 601 South Main Street Anderson, South Carolina 29624 Reference: Asbestos and Lead-Based Paint Assessment Services 710 A&B Beechwood Avenue
Anderson, South Carolina 29624 Dear Ms. Craft: Apex Environmental Management, Inc. (Apex) is pleased to provide the results of our assessment services for the referenced property in accordance with Apex proposal number 1115-231P dated November 10, 2015. This report and the associated attachments summarize our evaluation of the conditions observed at the project site. The findings presented by Apex are based upon sampling performed in the subject building. There is a chance that undetected ACM may exist in the building between walls or in other areas that would only be exposed during demolition or structural renovations. Should material be discovered that could potentially contain asbestos during the demolition process, additional samples of the material should be collected by a licensed asbestos inspector and submitted to an accredited laboratory for analytical interpretation. Our recommendations are based on the guidelines presented in EPA and/or OSHA regulations. Please note that this document is not a specification for asbestos removal. It does not contain means and methods for abatement. Quantities are estimates and contractors must verify amounts prior to bidding or removal. If you are planning an abatement project, please contact Apex to discuss the requirements. Use of this document without the express written consent of Apex is at the sole risk of the user and or/abatement contractor. The conclusions and/or recommendations contained in this report are based on our understanding of the applicable standards at the time this report was prepared. No warranty, expressed or implied, is made. If you have any questions please feel free to contact us at (864) 404-3210. Respectfully submitted, APEX ENVIRONMENTAL MANAGEMENT, INC. Thomas H. Oliver Tedman K. Shultz Director of Operations Project Manager Appendices
ASBESTOS AND LEAD BASED PAINT ASSESSMENT
CITY OF ANDERSON 710 A&B BEECHWOOD AVENUE
ANDERSON, SOUTH CAROLINA 29624
APEX PROJECT NO. 1115-232
TABLE OF CONTENTS SECTION
I Asbestos & Lead Evaluation Report II Asbestos & LBP Data Tables III Laboratory Analytical Results IV Photographic Log
V SC DHEC Asbestos Inspector License
SECTION I
Asbestos & Lead Evaluation Report
1
Date:
3/4/2016 Page Number: 1 of 4
Client: City of Anderson Client Contact: Ms. Erica Craft Client Address:
601 South Main Street Anderson, SC 29624
Client Phone Number:
(864) 231-2223
Project:
Asbestos and Lead Evaluation
Property Address:
710 A&B Beechwood Ave. Anderson, SC
Assessor: Ted Shultz Date of
Assessment: 2/18/2016
Company:
Apex Environmental Management 7 Winchester Court Mauldin, SC 29662
Phone Number (864) 404-3210
Purpose of Assessment:
Demolition Age of Structure:
50 ± years
Building Type:
Residential Number of Stories:
1
Foundation: Brick & CMU Block Crawlspace
Approximate Square Footage
1,800 SF
EXTERIOR BUILDING MATERIALS INTERIOR BUILDING MATERIALS Pitched wooden roof with shingles felt. Brick siding. Wooden windows. Window glazing.
Multiple types & layers of vinyl floor with no mastic.
Plaster with texture & finish. Drywall with no joint compound & tape. Wooden floors.
ASBESTOS/LEAD EVALUATION REPORT APEX PROJECT NUMBER: 1115-232
City of Anderson 710 A&B Beechwood Avenue Apex Project No. 1115-232 March 4, 2016
2
SCOPE OF THE SURVEY The objectives of the asbestos and lead assessment included the following:
Identification of suspect asbestos-containing material (ACM) and lead based paints (LBP) in readily observable locations. Limited demolition of building finishes was conducted.
Asbestos survey with sample collection by a South Carolina accredited inspector. Suspect ACM analysis by polarized light microscopy (PLM) utilizing CEI Labs (CEI) as
an NVLAP certified laboratory, their accreditation number is 101768-0. Transmission electron microscopy (TEM) analysis of non-friable organically bound
materials suspected to contain asbestos and testing negatively by PLM analysis. Lead inspection by a lead inspector certified by the Environmental Protection Agency
and licensed to conduct LBP surveys in South Carolina. In situ analysis of suspected lead based paints by X-ray fluorescence (XRF). Presenting the results in a report identifying confirmed ACMs and LBPs.
METHODS Asbestos Containing Materials In order to determine if the suspect materials observed during the visual survey contained asbestos, representative bulk samples were collected and placed in sealed packages. Twenty-six (26) bulk samples were collected during the survey and submitted to CEI Labs (CEI) in Cary, North Carolina for analysis using the EPA recommended method of Polarized Light Microscopy (PLM) coupled with dispersion staining (Method No. EPA 600/M4-82-020, Dec. 1982). CEI participates in the National Voluntary Laboratory Accreditation Program (NVLAP). Their NVLAP accreditation number is 101768-0 . EPA regulations require that multiple samples of each homogeneous material be collected for laboratory analysis. In accordance with South Carolina Regulation 61-86.1, non-friable organically bound materials that are reported to be non-asbestos containing by PLM analysis must also be analyzed by Transmission Electron Microscopy (TEM). Ten (10) samples were analyzed using TEM. Lead-Based Paint Lead painted surfaces were analyzed in place using X-ray fluorescence. Painted surfaces were selected based on color of topcoat, underlying layers and substrate on which it was painted. RESULTS Asbestos Containing Materials The EPA defines an asbestos-containing material (ACM) as a material containing more than 1% asbestos. OSHA defines ACM as a material containing any amount of asbestos. Provided below is a general discussion of the asbestos containing materials identified in the residence. A specific PLM and TEM table is located in Appendix II of this report and identifies positive materials and designates approximate quantities.
City of Anderson 710 A&B Beechwood Avenue Apex Project No. 1115-232 March 4, 2016
3
No materials sampled during the assessment were identified to be asbestos containing. Lead Based Paint OSHA does not recognize a threshold level of lead for definition purposes, only the presence or absence of lead. The current OSHA regulations recognize an airborne action level of thirty micrograms per cubic meter (30 µg/m3) during an eight-hour workday and a permissible exposure level of fifty micrograms per cubic meter (50 µg/m3) for employees. Currently, the EPA defines LBP as paint containing in excess of, or equal to, 1.0 mg/cm3. The XRF analytical results and approximate locations of the paint samples collected are included in the Lead Analysis Report in Appendix II. Several surfaces in the building tested positive for lead in excess of the regulatory definition: Exterior White wooden door frames Interior No surfaces tested positive for LBP RECOMMENDATIONS AND DISCUSSION Asbestos Containing Materials No asbestos was present in the materials sampled within the structure. Therefore, no recommendations are necessary at this time.
Lead-Based Paint
1. Currently the South Carolina Department of Health and Environmental Control (SCDHEC) define LBP as paint containing greater than 1.0 milligrams per square centimeter (mg/cm2) lead or in excess of, or equal to, 0.5 percent lead. Building materials identified as being painted with LBP should be segregated from the other building materials and recycled or disposed of in a municipal lined landfill. The removed wastes would need to be containerized and further tested by Toxic Characteristic Leaching procedures (TCLP) to determine if the waste is classified as hazardous. The remaining building materials that are not painted with LBP may be disposed of in a construction and demolition landfill. However, the landfills should be contacted to determine their specific disposal requirements.
2. Occupational Safety and Health Administration Lead Regulations apply to actions
initiated on lead containing materials. This regulation applies to lead concentrations greater than the analytical limit of detection. This regulation sets exposure levels on airborne lead and does not reference the percent lead in paint. Therefore, initial personal air monitoring should be conducted on workers performing work on surfaces which have a lead concentration of 0.1 mg/ cm2 or above to satisfy the OSHA requirements. If a baseline exposure lower than the OSHA Action Level of 30
City of Anderson 710 A&B Beechwood Avenue Apex Project No. 1115-232 March 4, 2016
4
micrograms per cubic meter (g/m3) is established, personal air monitoring may be terminated. The full OSHA lead standard should be referenced for compliance.
This report summarizes our evaluation of the conditions observed at the site. The findings prepared by Apex are based upon testing performed in the structures. Our recommendations are based on the guidelines presented in EPA, State of South Carolina and OSHA asbestos regulations. Please note that this document is not a specification for asbestos or lead paint removal. It does not contain means and methods for asbestos or lead paint abatement. If you are planning an asbestos or lead paint abatement project, please contact Apex to discuss the requirements. Use of this document without the express written consent of Apex is at the sole risk of the user and/or abatement contractor. Quantities provided in this report are estimated. Contractors must verify material amounts prior to bidding or removal. This report summarizes our evaluation of the conditions observed at the site. The findings prepared by Apex are based upon testing performed in the building space. Additional ACM or LBP may exist (undetected) in other areas due to their inaccessibility or due to the limited nature of our testing. Our assessment procedures and recommendations are based on the guidelines presented in EPA, State of South Carolina or OSHA asbestos regulations. A copy of this report must be submitted to SCDHEC at least ten (10) working days prior to demolition when applying for a demolition permit.
SECTION II
Asbestos & LBP Data Tables
Project Name: COA 700 A & B Beechwood Avenue ACM/LBP Sampled By: Ted Shultz
Project Location: 700 A & B Beechwood Avenue, Anderson, SC Project Manager: Rebecca Shultz
Project Number: 1115-232 Date: 2/18/2016
1
2
3 TEM - NAD
4
5
6 TEM - NAD
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23 TEM - NAD
PLM - NAD
PLM - NAD
PLM - NADFriable Damaged 8 EAWindow glazing
Throughout Drywall with no joint compound or tape
Windows
Throughout Plaster with texture & finish PLM - NAD
PLM - NAD
Friable Damaged 4,500 SF
Friable Damaged 4,500 SF
B bathroomMultplie layers of tan, beige & white
vinyl floors with no masticNon-Friable G 40 SF
A & B kitchen12" x 12' self-stick floor tile & tan & with white square pattern vinyl floor
with no masticNon-Friable G 300 SF
ASBESTOS SURVEY PLM & TEM FIELD DATA SHEET
QuantityAnalytical ResultsFriable/Non
FriableLocationSample No. ConditionSample Description
QuantityAnalytical ResultsFriable/Non
FriableLocationSample No. ConditionSample Description
24
25
26 TEM - NAD
NAD = No Asbestos Detected LF = Linear Feet EA = Each
Bold = Positive For Asbestos SF = Square Feet
Non-Friable Damaged 2,200 SFPLM - NAD
Roof Roof shingles (2 layers) & felt
Project Name: COA 710 A & B Beechwood Avenue ACM/LBP Sampled By: Ted Shultz
Project Location: 710 A & B Beechwood Avenue, Anderson, SC Project Manager: Rebecca Shultz
Project Number: 1115-232 Date: 2/18/2016
16 side porch post white wood 0.0017 side porch door frame white wood 1.6718 interior door frame white wood NA19 interior door frame white wood 0.2520 interior wall white plaster 0.0021 interior book shelf white wood 0.4722 interior base board white wood NA23 interior base board white wood 0.3424 interior window frame white wood 0.2525 interior door frame white wood 0.19
Bold = Positive for LBP in excess of 1.0 mg/cm2 NA = Insufficient Test Time
FIELD DATA SHEETLBP ANALYSIS
Sample No. Sample Location Component Color SubstrateAnalytical Result
(mg/m3)
SECTION III
Laboratory Analytical Results
February 24, 2016
Apex Environmental Management7 Winchester CourtMauldin, SC 29662
CLIENT PROJECT: COA 710 Beechwood AveCEI LAB CODE: B16-1659
Dear Customer:
Enclosed are asbestos analysis results for PLM Bulk samples received at our laboratory onFebruary 19, 2016. The samples were analyzed for asbestos using polarizing light microscopy(PLM) per the EPA 600 Method.
Sample results containing >1% asbestos are considered asbestos-containing materials(ACMs) per EPA regulatory requirements. The detection limit for the EPA 600 Method is <1%asbestos by weight as determined by visual estimation.
Thank you for your business and we look forward to continuing good relations. If you have anyquestions, please feel free to call our office at 919-481-1413.
107 New Edition Court • Cary, NC 27511 • 919.481.1413
Tianbao Bai, Ph.D., CIHLaboratory Director
Kind Regards,
ASBESTOS ANALYTICAL REPORTBy: Polarized Light Microscopy
Prepared for
Apex Environmental Management
TEL: 866-481-1412www.ceilabs.com
CLIENT PROJECT:
CEI LAB CODE:
TEST METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
REPORT DATE:
TOTAL SAMPLES ANALYZED:
# SAMPLES >1% ASBESTOS:
COA 710 Beechwood Ave
B16-1659
22
02/24/16
Asbestos Report SummaryBy: POLARIZING LIGHT MICROSCOPY
PROJECT: COA 710 Beechwood Ave CEI LAB CODE: B16-1659
Client ID Lab ID Color Sample DescriptionASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B147591A Tan,Patterned Floor Tile None Detected1
B147591B Clear Mastic None Detected
B147591C Beige,Gray Sheet Vinyl None Detected
B147592A Tan,Patterned Floor Tile None Detected2
B147592B Clear Mastic None Detected
B147592C Beige,Gray Sheet Vinyl None Detected
B147593 Sample Submitted for TEMAnalysis
3
B147594A Tan,Gray Sheet Vinyl None Detected4
B147594B Beige,Gray Sheet Vinyl None Detected
B147594C Off-white,Gray Sheet Vinyl None Detected
B147595A Tan,Gray Sheet Vinyl None Detected5
B147595B Beige,Gray Sheet Vinyl None Detected
B147595C Off-white,Gray Sheet Vinyl None Detected
B147596 Sample Submitted for TEMAnalysis
6
Layer 1 B147597 White Texture None Detected7
Layer 2 B147597 White Plaster Skim Coat None Detected
Layer 3 B147597 Gray Plaster Base Coat None Detected
Layer 1 B147598 White Texture None Detected8
Layer 2 B147598 White Plaster Skim Coat None Detected
Layer 3 B147598 Gray Plaster Base Coat None Detected
Layer 1 B147599 White Texture None Detected9
Layer 2 B147599 White Plaster Skim Coat None Detected
Layer 3 B147599 Gray Plaster Base Coat None Detected
Layer 1 B147600 White Texture None Detected10
Layer 2 B147600 Gray Plaster None Detected
Layer 1 B147601 White Texture None Detected11
Layer 2 B147601 White Plaster Skim Coat None Detected
Layer 3 B147601 Gray Plaster Base Coat None Detected
Layer 1 B147602 White Texture None Detected12
Layer 2 B147602 White Plaster Skim Coat None Detected
Page 1 of 2
Asbestos Report SummaryBy: POLARIZING LIGHT MICROSCOPY
PROJECT: COA 710 Beechwood Ave CEI LAB CODE: B16-1659
Client ID Lab ID Color Sample DescriptionASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
Layer 3 B147602 Gray Plaster Base Coat None Detected
Layer 1 B147603 White Texture None Detected13
Layer 2 B147603 White Plaster Skim Coat None Detected
Layer 3 B147603 Gray Plaster Base Coat None Detected
B147604 Gray Drywall None Detected14
B147605 Gray Drywall None Detected15
B147606 Gray Drywall None Detected16
B147607 Gray Drywall None Detected17
B147608 Gray Drywall None Detected18
B147609 Gray Drywall None Detected19
B147610 Gray Drywall None Detected20
B147611 White Window Glazing None Detected21
B147612 White Window Glazing None Detected22
B147613 Sample Submitted for TEMAnalysis
23
Layer 1 B147614 Off-white,Black Roof Shingle None Detected24
Layer 2 B147614 Black Roof Shingle None Detected
Layer 3 B147614 Black Felt Paper None Detected
Layer 1 B147615 Off-white,Black Roof Shingle None Detected25
Layer 2 B147615 Black Roof Shingle None Detected
Layer 3 B147615 Black Felt Paper None Detected
B147616 Sample Submitted for TEMAnalysis
26
Page 2 of 2
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
Tan,PatternedFloor Tile1
B147591AHeterogeneous
Non-fibrousBound
100% Vinyl None Detected
ClearMasticB147591B Homogeneous
Non-fibrousBound
100% Mastic None Detected
Beige,GraySheet VinylB147591C 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Tan,PatternedFloor Tile2
B147592AHeterogeneous
Non-fibrousBound
100% Vinyl None Detected
ClearMasticB147592B Homogeneous
Non-fibrousBound
100% Mastic None Detected
Beige,GraySheet VinylB147592C 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Sample Submitted forTEM Analysis
3B147593
Tan,GraySheet Vinyl4
B147594A20%5%
Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Page 1 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
Beige,GraySheet VinylB147594B 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Off-white,GraySheet VinylB147594C 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Tan,GraySheet Vinyl5
B147595A20%5%
Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Beige,GraySheet VinylB147595B 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Off-white,GraySheet VinylB147595C 20%
5%Heterogeneous
FibrousBound
50%25%
CelluloseFiberglass
VinylBinder
None Detected
Sample Submitted forTEM Analysis
6B147596
White7
B147597
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147597Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
Page 2 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
GrayPlaster Base Coat
B147597Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
White8
B147598
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147598Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
GrayPlaster Base Coat
B147598Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
White9
B147599
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147599Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
GrayPlaster Base Coat
B147599Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
Page 3 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
White10
B147600
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
GrayPlaster
B147600Homogeneous
Non-fibrousBound
Lab Notes: No skim coat present.
35%65%
BinderSilicates
None DetectedLayer 2
White11
B147601
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147601Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
GrayPlaster Base Coat
B147601Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
White12
B147602
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147602Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
Page 4 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
GrayPlaster Base Coat
B147602Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
White13
B147603
10%Heterogeneous
Non-fibrousBound
80%5%5%
Talc Calc CarbSilicatesPaint
None DetectedLayer 1
Texture
WhitePlaster Skim Coat
B147603Homogeneous
Non-fibrousBound
65%30%5%
BinderSilicatesPaint
None DetectedLayer 2
GrayPlaster Base Coat
B147603Homogeneous
Non-fibrousBound
35%65%
BinderSilicates
None DetectedLayer 3
GrayDrywall14
B14760410%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
GrayDrywall15
B14760510%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
GrayDrywall16
B14760610%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
Page 5 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
GrayDrywall17
B14760710%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
GrayDrywall18
B14760810%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
GrayDrywall19
B14760910%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
GrayDrywall20
B14761010%Homogeneous
FibrousBound
85%5%
Cellulose GypsumSilicates
None Detected
WhiteWindow Glazing21
B147611Heterogeneous
Non-fibrousBound
85%10%5%
BinderCalc CarbPaint
None Detected
WhiteWindow Glazing22
B147612Heterogeneous
Non-fibrousBound
85%10%5%
BinderCalc CarbPaint
None Detected
Sample Submitted forTEM Analysis
23B147613
Off-white,Black24
B147614
25%Heterogeneous
FibrousBound
40%35%
Fiberglass TarSilicates
None DetectedLayer 1
Roof Shingle
Page 6 of 8
ASBESTOS BULK ANALYSISBy: POLARIZING LIGHT MICROSCOPY
CEI Lab Code: B16-1659Date Received: 02-19-16Date Analyzed: 02-22-16Date Reported: 02-24-16
Client IDLab ID
LabAttributes
LabDescription
ASBESTOS%
ASBESTOS BULK PLM, EPA 600 METHODNON-ASBESTOS COMPONENTS
Non-Fibrous
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
Fibrous
BlackRoof Shingle
B14761480%Homogeneous
FibrousBound
20%Cellulose Tar None DetectedLayer 2
BlackFelt Paper
B14761425%Heterogeneous
FibrousBound
40%35%
Fiberglass TarSilicates
None DetectedLayer 3
Off-white,Black25
B147615
25%Heterogeneous
FibrousBound
40%35%
Fiberglass TarSilicates
None DetectedLayer 1
Roof Shingle
BlackRoof Shingle
B14761580%Homogeneous
FibrousBound
20%Cellulose Tar None DetectedLayer 2
BlackFelt Paper
B14761525%Heterogeneous
FibrousBound
40%35%
Fiberglass TarSilicates
None DetectedLayer 3
Sample Submitted forTEM Analysis
26B147616
Page 7 of 8
LEGEND: Non-Anth = Non-Asbestiform AnthophylliteNon-Trem = Non-Asbestiform TremoliteCalc Carb = Calcium Carbonate
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
LIMIT OF DETECTION: <1% by visual estimation
REGULATORY LIMIT: >1% by weight
Due to the limitations of the EPA 600 method, nonfriable organically bound materials (NOBs) such asvinyl floor tiles can be difficult to analyze via polarized light microscopy (PLM). EPA recommends thatall NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by TransmissionElectron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is notcovered under NVLAP accreditation.
This report relates only to the samples tested or analyzed and may not be reproduced, except in full,without written approval by CEI Labs, Inc. CEI Labs makes no warranty representation regarding theaccuracy of client submitted information in preparing and presenting analytical results. Interpretation ofthe analytical results is the sole responsibility of the client. This report may not be used by the client toclaim product endorsement by NVLAP or any other agency of the U.S. Government.
Page 8 of 8
ANALYST: APPROVED BY:Tianbao Bai, Ph.D., CIHLaboratory Director
Taylor B. Metcalf
February 24, 2016
Apex Environmental Management7 Winchester CourtMauldin, SC 29662
CLIENT PROJECT: COA 710 Beechwood AveCEI LAB CODE: T16-0239
Dear Customer:
Enclosed are asbestos analysis results for TEM bulk samples received at our laboratory onFebruary 22, 2016. The samples were analyzed for asbestos using transmission electronmicroscopy (TEM) per Chatfield Method.
Sample results containing > 1% asbestos are considered asbestos-containing materials(ACMs) per the EPA regulatory requirements. The detection limit for the TEM Chatfieldmethod is <1% depending on the processed weight and constituents of the sample.
Thank you for your business and we look forward to continuing good relations. If you have anyquestions, please feel free to call our office at 919-481-1413.
107 New Edition Court • Cary, NC 27511 • 919.481.1413
Tianbao Bai, Ph.D., CIHLaboratory Director
Kind Regards,
ASBESTOS ANALYTICAL REPORTBy: Transmission Electron Microscopy
Prepared for
Apex Environmental Management
TEL: 866-481-1412www.ceilabs.com
CLIENT PROJECT:
CEI LAB CODE:
TEST METHOD: Bulk ChatfieldEPA 600 / R93 / 116
REPORT DATE:
COA 710 Beechwood Ave
T16-0239
02/24/16
ASBESTOS BULK ANALYSISBy: TRANSMISSION ELECTRON MICROSCOPY
CEI Lab Code: T16-0239Date Received: 02-22-16Date Analyzed: 02-23-16Date Reported: 02-24-16
Client IDLab ID
MaterialDescription
TEM BULK CHATFIELD / EPA 600 / R93 / 116
Client: Apex Environmental Management7 Winchester CourtMauldin, SC 29662
Project: COA 710 Beechwood Ave
SampleWeight
(g)
OrganicMaterial
%
Acid SolubleMaterial
%
Acid InsolubleMaterial
%Asbestos
%
T471523 Tan, Patterned Floor Tile 0.23 24.8 74.8 .4 None
Detected
T471533 Beige Gray Sheet Vinyl 0.114 31.6 61.4 7 None
Detected
T471543 Clear Mastic 0.122 55.7 15.6 28.7 None
Detected
T471556 Tan Gray Sheet Vinyl 0.205 45.9 51.7 2.4 None
Detected
T471566 Beige Gray Sheet Vinyl 0.245 56.7 18.4 24.9 None
Detected
T471576 Off-white Sheet Vinyl 0.342 52.3 20.2 27.5 None
Detected
T4715823 White Window Glazing 0.413 11.4 83.1 5.5 None
Detected
T4715926 Off-white Black Roof
Shingle0.289 27.3 55.4 17.3 None
Detected
T4716026 Black Roof Shingle 0.409 19.6 28.1 52.3 None
Detected
T4716126 Black Felt Paper 0.209 95.2 3.3 1.5 None
Detected
Page 1 of 2
LEGEND: None
METHOD: CHATFIELD & EPA/600/R-93/116
LIMIT OF DETECTION: Varies with the weight and constituents of the sample (<1%)
REGULATORY LIMIT: >1% by weight
This report relates only to the samples tested or analyzed and may not be reproduced, except in full,without written approval by CEI Labs, Inc. CEI Labs makes no warranty representation regarding theaccuracy of client submitted information in preparing and presenting analytical results. Interpretation ofthe analytical results is the sole responsibility of the client.
Page 2 of 2
ANALYST: APPROVED BY:Tianbao Bai, Ph.D., CIHLaboratory Director