Page 1: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

ASBESTOS SURVEY AND

LEAD PAINT REPORT

For the building located at:

1900 SW 4TH AVENUE PORTLAND, OREGON

Prepared for: Portland State University

CERTIFIED ENVIRONMENTAL CONSULTING, INC. 12806 NE 40TH CIRCLE

VANCOUVER, WASHINGTON 98682

Prepared by: Tom Thompson

Page 2: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

EXECUTIVE SUMMARY Dear Mr. Torres, Enclosed are the results of the asbestos survey conducted by C.E.C., Inc. located at 1900 SW 4th Avenue, in Portland, Oregon. This survey was coordinated with you and conducted December 6, 2002 through January 3, 2003, by Tom Thompson, an AHERA certified inspector. Please note that the asphalt roofing material was not tested due to potential damaged caused by testing. These materials should be considered asbestos containing materials until testing can be completed. Do not drill through, sand on or otherwise disturb material. All samples were taken in a random manner as required by EPA AHERA rules and analyzed using polarized light microscopy with dispersion staining according to EPA and OR-OSHA Methodology. Asbestos was identified in the brown floor tile mastic, beige floor tile and mastic, pipe joint insulation, and the tan floor tile mastic (See sample data sheet attached). The following survey is divided into the following sections: ◊ Summary sheet - details the type and construction of the building with approximate amounts of

asbestos in the building. ◊ Sample result sheet - contains sample numbers and results, description of materials and

homogeneous areas of material. ◊ Assessment of materials - contains an assessment of asbestos materials. ◊ Response actions recommended - contains the response actions we recommend. ◊ Laboratory analysis sheet - contains the results of our laboratory analysis. ◊ Inspector’s certifications ◊ Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition of the ACM was detected through on-site observation and physical determination. NOTE: This asbestos survey report is available to Portland State University, and not to be reproduced in total or part without written consent of Portland State University . We appreciate the opportunity to have worked with you. If you have any questions or if we can be of any further service, please contact this office. Sincerely, Rene Garrett President

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 3: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SUMMARY SHEET

Owner or Representative: Ruben Torres Address: 1900 SW 4th Avenue City: Portland State: Oregon Owner's Representative: Mr. Ruben Torres Portland State University

630 SW Mill Street Portland, Oregon 97201

Owner/Rep. Telephone Number: (503) 544-5388 Surveyed by: Tom Thompson - Accreditation Number: 1000987

CONSTRUCTION DATA: Year Built: Approx: 1978__ Size : Approx: 204,000 SQ FT Construction Type: Concrete, Steel Roof Construction: Asphalt Roofing Material-not tested Heating System: Hot Water Attic Insulation: Not Applicable_ Pipe Insulation: Fiberglass with some Asbestos Containing Materials

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 4: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

Summary Data

PRODUCT AMOUNT FRIABLE CONDITION SAMPLE # RESULTS

BROWN FLOOR TILE MASTIC

APPROX. 1,200 SQ FT NO GOOD 8, 37 5% CHRYSOTILE

BEIGE FLOOR TILE AND MASTIC

APPROX. 30,805 SQ

FT NO GOOD 10, 19, 27,

28, 57 3% TO 6%

CHRYSOTILE

PIPE JOINT INSULATION

4 VISIBLE FITTINGS

YES GOOD 25 15% AMOSITE

TAN FLOOR TILE MASTIC 650 SQ FT NO GOOD 51, 56 5% CHRYSOTILE

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 5: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

1 COMPUTER FLOORING

ELECTRICAL MECHANICAL

ROOM SUB BASEMENT

COMPUTER FLOORS THROUGHOUT NONE DETECTED

2 COVE BASE MASTIC

ELECTRICAL MECHANICAL

ROOM SUB BASEMENT

THROUGHOUT NONE DETECTED

3 PIPE JOINT INSULATION

BATTERY ROOM SUB BASEMENT THROUGHOUT NONE DETECTED

4 PIPE JOINT INSULATION

MEN’S RESTROOM LOWER LEVEL THROUGHOUT NONE DETECTED

5 GYPSUM WALLBOARD OUTSIDE LAYER P2 THROUGHOUT NONE DETECTED

6 GYPSUM WALLBOARD INSIDE LAYER P2 THROUGHOUT NONE DETECTED

7 FALSE CEILING TILE P 106 SELECTIVE

THROUGHOUT NONE DETECTED

8 BROWN FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04)

SELECTIVE THROUGHOUT

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

9 BLACK FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04) NONE DETECTED

10 BEIGE FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04)

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

11 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED

12 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED

13 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 6: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

14 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED

15 FALSE CEILING TILE 2ND FLOOR SELECTIVE

THROUGHOUT NONE DETECTED

16 DUCT INSULATION MASTIC

FAN ROOM 2A AND B

SELECTIVE THROUGHOUT NONE DETECTED

17 DUCT TAPE FAN ROOM 2A AND B NONE DETECTED

18 LIGHT BROWN

FLOOR TILE AND MASTIC

WEST STAIRWAY NONE DETECTED

19 BEIGE FLOOR TILE AND MASTIC

2ND FLOOR PHONE ROOM

SELECTIVE THROUGHOUT 2ND

FLOOR IN CORE AREA UNDER

CARPET AND AS 1ST AND 2ND LAYERS,

ROOM 211

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

20 DUCT INSULATION MASTIC

PLAZA LEVEL FAN ROOM 1 AI THROUGHOUT NONE DETECTED

21 DUCT TAPE PLAZA LEVEL FAN ROOM 1 AI NONE DETECTED

22 FIRE DOOR CORE PLAZA LEVEL ELECTRICAL ROOM THROUGHOUT NONE DETECTED

23 GRAY FLOOR TILE AND MASTIC STORAGE ROOM 170 NONE DETECTED

24 FALSE CEILING TILE

STORAGE ROOM 115

SELECTIVE THROUGHOUT NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682

Page 7: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

25 PIPE JOINT INSULATION

MECHANICAL ROOM SFG8

NO MORE ENCOUNTERED

HOWEVER MAY BE PRESENT BEHIND

WALLS THROUGHOUT

15% AMOSITE

26 PIPE INSULATION MECHANICAL

ROOM SFG8 LOWER LEVEL

SELECTIVE THROUGHOUT NONE DETECTED

27 BEIGE FLOOR TILE AND MASTIC ROOM 20-12

THROUGHOUT LOWER LEVEL

NORTH

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

28 BEIGE FLOOR TILE AND MASTIC

AT DOORWAY ROOM 55

THROUGHOUT LOWER LEVEL

NORTH

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

29 GRAY FLOOR TILE AND MASTIC

ST 40 CONFERENCE ROOM BREAK ROOM ST 40 NONE DETECTED

30 GREEN FLOOR TILE AND MASTIC ST 40 NONE DETECTED

31 PINK FLOOR TILE AND MASTIC ST 55-17 NONE DETECTED

32 COVE BASE MASTIC ST 55-17 THROUGHOUT NONE DETECTED

33 GYPSUM WALLBOARD ST 55-17 NONE DETECTED

34 FIRE PROOFING LOADING DOCK NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682

Page 8: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

35 FIRE PROOFING LOADING DOCK NONE DETECTED

36 FIRE PROOFING LOADING DOCK NONE DETECTED

37 BROWN FLOOR TILE AND MASTIC

ELECTRICAL ROOM (00-22)

ADJACENT ELECTRICAL ROOM

(00-22)

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

38 GRAY FLOOR TILE AND MASTIC

ELECTRICAL ROOM (00-22) NONE DETECTED

39 TAN FLOOR TILE AND MASTIC 85 LOWER LEVEL

SELECTIVE THROUGHOUT

CENTER SECTOR LOWER LEVEL

NONE DETECTED

40 BLACK SHEET VINYL

CENTRAL LOWER LEVEL NONE DETECTED

41 WHITE FLOOR TILE AND MASTIC

CENTRAL LOWER LEVEL NONE DETECTED

42 FALSE CEILING TILE

CENTRAL LOWER LEVEL NONE DETECTED

43 COVE BASE MASTIC CENTRAL LOWER LEVEL NONE DETECTED

44 GYPSUM WALLBOARD

CENTRAL LOWER LEVEL NONE DETECTED

45 PIPE JOINT INSULATION

LOWER LEVEL L080-00

SELECTIVE THROUGHOUT NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 9: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

46 PIPE JOINT INSULATION

LOWER LEVEL L080-00

SELECTIVE THROUGHOUT NONE DETECTED

47 PIPE JOINT INSULATION

LOWER LEVEL L080-00

SELECTIVE THROUGHOUT NONE DETECTED

48 SPRAYED ON FIRE PROOFING

ABOVE CEILING LOWER LEVEL

CENTRAL THROUGHOUT NONE DETECTED

49 PIPE JOINT INSULATION G090 IN WALL SELECTIVE

THROUGHOUT NONE DETECTED

50 SKIM COAT G090 INSIDE WALL SELECTIVE THROUGHOUT NONE DETECTED

51 TAN FLOOR TILE AND MASTIC

STAIR LANDING #3 LOWER LEVEL

SELECTIVE THROUGHOUT

THESE LANDINGS

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

52 TAN FLOOR TILE AND MASTIC

TOP LAYER CLASSROOM 2501 NONE DETECTED

53 ORANGE FLOOR TILE AND MASTIC

BOTTOM LAYER CLASS ROOM 2501

BOTTOM LAYER 00-22 NONE DETECTED

54 CREAM FLOOR TILE AND MASTIC TOP LAYER 00-07 NONE DETECTED

55 SPOTTED BROWN FLOOR TILE AND

MASTIC TOP LAYER 00-07 NONE DETECTED

56 TAN FLOOR TILE AND MASTIC

BOTTOM LAYER 00-07

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682

Page 10: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

57 BEIGE FLOOR TILE AND MASTIC

2ND FLOOR ROOM 211

SELECTIVE THROUGHOUT 2ND

FLOOR IN CORE AREA UNDER

CARPET AND AS 1ST AND 2ND LAYERS

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

58 COVE BASE MASTIC 2ND FLOOR ROOM 211

SELECTIVE THROUGHOUT NONE DETECTED

59 PLASTER 2ND FLOOR ROOM 211 THROUGHOUT NONE DETECTED

60 GRAY SHEET VINYL ROOM 209 NONE DETECTED

61 WHITE FLOOR TILE AND MASTIC ROOM 209 CLOSET NONE DETECTED

62 GRAY FLOOR TILE AND MASTIC

TOP LAYER ROOM 212

SELECTIVE THROUGHOUT 2ND FLOOR AS 1ST AND

2ND LAYERS, BOTTOM LAYER 210

NONE DETECTED

63 GRAY FLOOR TILE AND MASTIC

BOTTOM LAYER ROOM 212 NONE DETECTED

64 FLOOR COVERING AND MASTIC

TOP LAYER ROOM 210 NONE DETECTED

65 GYPSUM WALLBOARD

OUTSIDE LAYER PLAZA LEVEL

HALLWAY THROUGHOUT NONE DETECTED

66 GYPSUM WALLBOARD

INSIDE LAYER PLAZA LEVEL

HALLWAY THROUGHOUT NONE DETECTED

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682

Page 11: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

SAMPLE RESULTS

1900 SW 4TH AVENUE, PORTLAND, OREGON

SAMPLE # SAMPLE DESCRIPTION SAMPLE LOCATION HOMOGENEOUS

AREA ASBESTOS CONTENT

67 CEILING TILE HALLWAY PLAZA LEVEL THROUGHOUT NONE DETECTED

68 CEILING TILE ROOM 175 NONE DETECTED

69 PLASTER MECHANICAL ROOM 175

SELECTIVE THROUGHOUT NONE DETECTED

70 LIGHT BROWN

FLOOR TILE AND MASTIC

ROOM 140 SELECTIVE

THROUGHOUT THIS AREA

NONE DETECTED

71 GRAY FLOOR TILE AND MASTIC ROOM 170 SELECTIVE

THROUGHOUT NONE DETECTED

72 CEILING TILE ROOM 170 NONE DETECTED

73 COVE BASE MASTIC ROOM 170 NONE DETECTED

74 DUCT INSULATION MASTIC ROOM 120 THROUGHOUT NONE DETECTED

Page 12: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

ASSESSMENT OF MATERIALS

Building: 1900 SW 4TH AVENUE, PORTLAND, OREGON

Sample #'s

Functional Space Asbestos Type %

Material & Condition Comments Sq. & Linear Footage

8, 37

MAIN MECHANICAL ROOM (00-04), ELECTRICAL ROOM (00-22),

ADJACENT ELECTRICAL ROOM (00-22)

CHRYSOTILE 5% BROWN FLOOR

TILE MASTIC (GOOD)

SEE RESPONSE ACTIONS

1,200 SQ FT

25 MECHANICAL ROOM SFG8 AMOSITE 15% PIPE JOINT

INSULATION

SEE RESPONSE ACTIONS

4 VISIBLE FITTINGS

Inspector: Tom Thompson - Accreditation Number: 1000987

Signature: __________________________________ Date: January 10, 2003

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 13: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

ASSESSMENT OF MATERIALS

Building: 1900 SW 4TH AVENUE, PORTLAND, OREGON

Sample #'s

Functional Space Asbestos Type %

Material & Condition Comments Sq. & Linear Footage

10, 19, 27, 28, 57

MAIN MECHANICAL

ROOM (00-04), 2ND FLOOR PHONE

ROOM, SELECTIVE

THROUGHOUT 2ND FLOOR IN CORE

AREA UNDER CARPET AND AS

1ST AND 2ND LAYERS, ROOM 211, ROOM 20-12, THROUGHOUT LOWER LEVEL

NORTH, AT DOORWAY ROOM

55

CHRYSOTILE 3% TO 6%

BEIGE FLOOR TILE AND MASTIC

(GOOD)

SEE RESPONSE ACTIONS

APPROX. 30,805 SQ

FT

Inspector: Tom Thompson - Accreditation Number: 1000987

Signature: __________________________________ Date: January 10, 2003

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 14: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

ASSESSMENT OF MATERIALS

Building: 1900 SW 4TH AVENUE, PORTLAND, OREGON

Sample #'s

Functional Space Asbestos Type %

Material & Condition Comments Sq. & Linear Footage

51, 56

STAIR LANDING # 3 LOWER LEVEL,

SELECTIVE THROUGHOUT

THESE LANDINGS, BOTTOM LAYER

00-07

CHRYSOTILE 5% TAN FLOOR TILE

MASTIC (GOOD)

SEE RESPONSE ACTIONS

APPROX. 650 SQ FT

Inspector: Tom Thompson - Accreditation Number: 1000987

Signature: __________________________________ Date: November 22, 2002

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 15: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

RESPONSE ACTIONS RECOMMENDED

Building: 1900 SW 4TH AVENUE, PORTLAND, OREGON

MATERIAL LOCATION RECOMMENDED RESPONSE ACTIONS

FLOOR TILE MASTIC

MAIN MECHANICAL ROOM (00-04), ELECTRICAL ROOM

(00-22), THROUGHOUT, STAIR LANDING #3 LOWER LEVEL, SELECTIVE THROUGHOUT

THESE LANDINGS, BOTTOM LAYER 00-07

Floor tile mastic is a non- friable material that poses minimal health or environmental risks in its current state. Non-asbestos floor tile with asbestos containing mastic must be assumed to be contaminated. Do not drill through, sand on, puncture, break or otherwise disturb material.

PIPE JOINT INSULATION MECHANICAL ROOM SFG8

Pipe joint insulation is a friable material that is currently in good condition. Must be maintained in an intact condition and kept encapsulated with a high vehicular latex paint. Do not drill through, sand on or otherwise disturb material. Must be removed prior to renovation or demolition. Pipe joint insulation between walls must be removed prior to demolition or renovation. * Quantity of material is an estimate only. Destructive testing was not an option and piping blue prints were not available and all non- visible pipes behind walls must be assumed to be asbestos containing.

Management Planner: Tom Thompson - Accreditation Number: 1001009 Signature: ________________________________ Date: January 10, 2003

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 16: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

RESPONSE ACTIONS RECOMMENDED

Building: 1900 SW 4TH AVENUE, PORTLAND, OREGON

MATERIAL LOCATION RECOMMENDED RESPONSE ACTIONS

FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04), 2ND FLOOR PHONE ROOM, THROUGHOUT 2ND

FLOOR IN CORE AREA UNDER CARPET AND AS 1ST

AND 2ND LAYERS, ROOM 211, ROOM 20-12, THROUGHOUT LOWER LEVEL NORTH, AT

DOORWAY ROOM 55

Floor tile and mastic are non-friable materials that are currently in good condition. Do not drill through, sand on, break or otherwise disturb material. Must be removed prior to renovation or demolition.

Management Planner: Tom Thompson - Accreditation Number: 1001009 Signature: ________________________________ Date: January 10, 2003

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

Page 17: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT

MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

1 COMPUTER FLOORING

ELECTRICAL MECHANICAL

ROOM SUB BASEMENT

NONE DETECTED EPOXY, VINYL, ADHESIVE

2 COVE BASE MASTIC

ELECTRICAL MECHANICAL

ROOM SUB BASEMENT

NONE DETECTED ADHESIVE, CLAY

3 PIPE JOINT INSULATION

BATTERY ROOM SUB BASEMENT NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE

4 PIPE JOINT INSULATION

MEN’S RESTROOM

LOWER LEVEL NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE,

5 GYPSUM WALLBOARD

OUTSIDE LAYER P2 NONE DETECTED

20% CELLULOSE, 3% FIBERGLASS,

CALCIUM SULFATE, BINDER

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 18: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

6 GYPSUM WALLBOARD INSIDE LAYER P2 NONE DETECTED

20% CELLULOSE, 3% FIBERGLASS,

CALCIUM SULFATE, BINDER

7 FALSE CEILING TILE P106 NONE DETECTED 65% CELLULOSE, PERLITE, BINDER

8 BROWN FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04)

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

CALCIUM CARBONATE, VINYL, BINDER, TAR

9 BLACK FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04)

NONE DETECTED CALCIUM CARBONATE, VINYL, BINDER, ADHESIVE

10 BEIGE FLOOR TILE AND MASTIC

MAIN MECHANICAL ROOM (00-04)

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

CALCIUM CARBONATE, VINYL, BINDER, TAR

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 19: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

11 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED 20% CELLULOSE,

CALCIUM SILICATE, BINDER

12 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED 15% CELLULOSE, 8% FIBERGLASS, MICA, CALCITE

13 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED 20% CELLULOSE,

CALCIUM SILICATE, FERROUS OXIDE

14 FIRE PROOFING 2ND FLOOR

MECHANICAL SPACE

NONE DETECTED 15% CELLULOSE, 8% FIBERGLASS, MICA, CALCITE

15 FALSE CEILING TILE 2ND FLOOR NONE DETECTED 50% CELLULOSE, PERLITE, BINDER

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 20: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

16 DUCT INSULATION MASTIC

FAN ROOM 2A AND B NONE DETECTED ADHESIVE,

CALCIUM CARBONATE

17 DUCT TAPE FAN ROOM 2A AND B NONE DETECTED 60% CELLULOSE,

CALCITE, ADHESIVE

18 LIGHT BROWN

FLOOR TILE AND MASTIC

WEST STAIRWAY NONE DETECTED CALCIUM CARBONATE, VINYL, BINDER, ADHESIVE

19 BEIGE FLOOR TILE AND MASTIC

2ND FLOOR PHONE ROOM

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

CALCIUM CARBONATE, VINYL, BINDER, TAR

20 DUCT INSULATION MASTIC

PLAZA LEVEL FAN ROOM 1AI NONE DETECTED ADHESIVE,

CALCIUM CARBONATE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 21: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

21 DUCT TAPE PLAZA LEVEL FAN ROOM 1 AI NONE DETECTED 60% CELLULOSE,

CALCITE, ADHESIVE

22 FIRE DOOR CORE PLAZA LEVEL ELECTRICAL

ROOM NONE DETECTED 15% FIBERGLASS,

PERLITE, CALCITE, BINDER

23 GRAY FLOOR TILE AND MASTIC

STORAGE ROOM 170 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

24 FALSE CEILING TILE STORAGE ROOM 115 NONE DETECTED 50% CELLULOSE,

PERLITE, BINDER

25 PIPE JOINT INSULATION

MECHANICAL ROOM SFG8 15% AMOSITE MAGNESIUM CARBONATE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 22: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

26 PIPE INSULATION MECHANICAL

ROOM SFG8 LOWER LEVEL

NONE DETECTED 65% FIBERGLASS, 20% CELLULOSE, FOIL, ADHESIVE

27 BEIGE FLOOR TILE AND MASTIC ROOM 20-12

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

CALCIUM CARBONATE, VINYL, BINDER, TAR

28 BEIGE FLOOR TILE AND MASTIC

AT DOORWAY ROOM 55

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

CALCIUM CARBONATE, VINYL, BINDER, TAR

29 GRAY FLOOR TILE AND MASTIC

ST 40 CONFERENCE

ROOM NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

30 GREEN FLOOR TILE AND MASTIC ST 40 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 23: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-06-02 THROUGH 12-10-02 DATE RECEIVED: 12-10-02 DATE COMPLETED: 12-11-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

31

PINK FLOOR TILE AND MASTIC ST 55-17 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

32 COVE BASE MASTIC ST 55-17 NONE DETECTED SILICONE CEMENT

33 GYPSUM WALLBOARD ST 55-17 NONE DETECTED

20% CELLULOSE, 3% FIBERGLASS,

CALCIUM SULFATE, BINDER

34 FIRE PROOFING LOADING DOCK NONE DETECTED 15% CELLULOSE, 8% FIBERGLASS, MICA, CALCITE

35 FIRE PROOFING LOADING DOCK NONE DETECTED 15% CELLULOSE, 8% FIBERGLASS, MICA, CALCITE

36 FIRE PROOFING LOADING DOCK NONE DETECTED 15% CELLULOSE, 8% FIBERGLASS, MICA, CALCITE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 24: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-09-02 DATE RECEIVED: 12-09-02 DATE COMPLETED: 12-26-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

37 BROWN FLOOR TILE AND MASTIC

ELECTRICAL ROOM (00-22)

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

CALCIUM CARBONATE, VINYL, BINDER, TAR

38 GRAY FLOOR TILE AND MASTIC

ELECTRICAL ROOM (00-22) NONE DETECTED

1% CELLULOSE CALCIUM CARBONATE,

VINYL, BINDER, TAR

39 TAN FLOOR TILE AND MASTIC 85 LOWER LEVEL NONE DETECTED

1% CELLULOSE, CALCIUM CARBONATE,

VINYL, BINDER, TAR

40 BLACK SHEET VINYL

CENTRAL LOWER LEVEL NONE DETECTED

10% CELLULOSE, VINYL, CALCITE,

ADHESIVE

41 WHITE FLOOR TILE AND MASTIC

CENTRAL LOWER LEVEL NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 25: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-09-02 DATE RECEIVED: 12-09-02 DATE COMPLETED: 12-26-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

42 FALSE CEILING TILE CENTRAL LOWER LEVEL NONE DETECTED 65% CELLULOSE,

PERLITE, BINDER

43 COVE BASE MASTIC CENTRAL LOWER LEVEL NONE DETECTED SILICONE CEMENT

44 GYPSUM WALLBOARD

CENTRAL LOWER LEVEL NONE DETECTED

20% CELLULOSE, CALCIUM SULFATE,

BINDER

45 PIPE JOINT INSULATION

LOWER LEVEL L080-00 NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE

46 PIPE JOINT INSULATION

LOWER LEVEL L080-00 NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 26: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-09-02 DATE RECEIVED: 12-09-02 DATE COMPLETED: 12-26-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

47 PIPE JOINT INSULATION

LOWER LEVEL L080-00 NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE

48 SPRAYED ON FIRE PROOFING

ABOVE CEILING LOWER LEVEL

CENTRAL NONE DETECTED 20% CELLULOSE,

CALCIUM SILICATE

49 PIPE JOINT INSULATION G090 IN WALL NONE DETECTED 30% FIBERGLASS,

CALCIUM SILICATE

50 SKIM COAT G090 INSIDE WALL NONE DETECTED CALCIUM CARBONATE,

QUARTZ, CEMENT

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 27: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-30-02 DATE RECEIVED: 12-30-02 DATE COMPLETED: 12-31-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

51 TAN FLOOR TILE AND MASTIC

STAIR LANDING #3 LOWER LEVEL

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

CALCIUM CARBONATE, VINYL, BINDER, TAR

52 TAN FLOOR TILE AND MASTIC

TOP LAYER CLASSROOM 2501 NONE DETECTED

1% CELLULOSE, CALCIUM CARBONATE,

VINYL, BINDER, TAR

53 ORANGE FLOOR TILE AND MASTIC

BOTTOM LAYER CLASSROOM 2501 NONE DETECTED

1% CELLULOSE, CALCIUM CARBONATE,

VINYL, BINDER, TAR

54 CREAM FLOOR TILE AND MASTIC TOP LAYER 00-07 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

55 SPOTTED BROWN FLOOR TILE AND

MASTIC TOP LAYER 00-07 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 28: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 12-30-02 DATE RECEIVED: 12-30-02 DATE COMPLETED: 12-31-02

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

56 TAN FLOOR TILE AND MASTIC

BOTTOM LAYER 00-07

MASTIC: 5% CHRYSOTILE

FLOOR TILE: NONE DETECTED

CALCIUM CARBONATE, VINYL, BINDER, TAR

57 BEIGE FLOOR TILE AND MASTIC

2ND FLOOR ROOM 211

FLOOR TILE: 3% CHRYSOTILE

MASTIC: 6% CHRYSOTILE

TRACE <1% CELLULOSE,

CALCIUM CARBONATE, VINYL, BINDER, TAR

58 COVE BASE MASTIC 2ND FLOOR ROOM 211 NONE DETECTED ADHESIVE, CLAY

59 PLASTER 2ND FLOOR ROOM 211 NONE DETECTED CALCIUM CARBONATE,

PERLITE, CEMENT

60 GRAY SHEET VINYL ROOM 209 NONE DETECTED 10% CELLULOSE, VINYL, CALCITE,

ADHESIVE

61 WHITE FLOOR TILE AND MASTIC

ROOM 209 CLOSET NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

62 GRAY FLOOR TILE AND MASTIC

TOP LAYER ROOM 212 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

63 GRAY FLOOR TILE AND MASTIC

BOTTOM LAYER ROOM 212 NONE DETECTED

1% CELLULOSE, CALCIUM CARBONATE,

VINYL, BINDER, TAR

64 FLOOR COVERING AND MASTIC

TOP LAYER ROOM 210 NONE DETECTED SYNTHETIC RUBBER,

SILICONE CEMENT

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 29: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 01-03-03 DATE RECEIVED: 01-03-03 DATE COMPLETED: 01-06-03

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

65 GYPSUM WALLBOARD

OUTSIDE LAYER PLAZA LEVEL

HALLWAY NONE DETECTED

20% CELLULOSE, 3% FIBERGLASS,

CALCIUM SULFATE, BINDER

66 GYPSUM WALLBOARD

INSIDE LAYER PLAZA LEVEL

HALLWAY NONE DETECTED

20% CELLULOSE, 3% FIBERGLASS,

CALCIUM SULFATE, BINDER

67 CEILING TILE HALLWAY PLAZA LEVEL NONE DETECTED 65% CELLULOSE,

PERLITE, BINDER

68 CEILING TILE ROOM 175 NONE DETECTED 65% CELLULOSE, PERLITE, BINDER

69 PLASTER MECHANICAL ROOM 175 NONE DETECTED CALCIUM CARBONATE,

AGGREGATE, CEMENT

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:

Page 30: ASBESTOS SURVEY AND LEAD PAINT REPORT€¦ · Lead paint report. C.E.C. has investigated accessible areas of this facility in locating suspect ACM. The current extent and condition

CERTIFIED ENVIRONMENTAL CONSULTING, INC.

BULK SAMPLE ANALYSIS REPORT MR. RUBEN TORRES SOURCE: 1900 SW 4TH AVENUE, PORTLAND, OREGON PORTLAND STATE UNIVERSITY SAMPLED BY: TOM THOMPSON

630 SW MILL STREET LAB #: N-2217/02-1009 PORTLAND, OREGON 97201 ANALYZED BY: TOM THOMPSON

DATE SAMPLED: 01-03-03 DATE RECEIVED: 01-03-03 DATE COMPLETED: 01-06-03

ANALYTICAL METHOD: EPA, 40 CFR Part 763, Section 1, Subpart F, Appendix A, PLM/Dispersion Staining

SAMPLE

ID #

SAMPLE DESCRIPTION

SAMPLE LOCATION

ASBESTOS CONTENT

OTHER MATERIAL

70 LIGHT BROWN

FLOOR TILE AND MASTIC

ROOM 140 NONE DETECTED CALCIUM CARBONATE, VINYL, BINDER, ADHESIVE

71 GRAY FLOOR TILE AND MASTIC ROOM 170 NONE DETECTED CALCIUM CARBONATE,

VINYL, BINDER, ADHESIVE

72 CEILING TILE ROOM 170 NONE DETECTED 60% CELLULOSE, PERLITE, BINDER

73 COVE BASE MASTIC ROOM 170 NONE DETECTED SILICONE CEMENT

74 DUCT INSULATION MASTIC ROOM 120 NONE DETECTED CALCITE, ADHESIVE

ANALYST:______________________________________________ REVIEWED BY:_________________ DEVIATION FROM METHOD: NONE. PERCENTAGES ARE ESTIMATES. TEST RESULTS PERTAIN ONLY TO ITEMS TESTED. * DETECTION LIMIT IS LESS THAN 1% ASBESTOS. NON ASBESTOS MATERIALS ARE NOT NECESSARILY LISTED.

12806 N.E. 40TH CIRCLE VANCOUVER, WASHINGTON 98682 PORTLAND (503) 221-7904 VANCOUVER (360) 254-9385 Fax (360) 891-9633

CLIENT:


Recommended