Downloaded Fr
Proceedings of IMECE2008 2008 ASME International Mechanical Engineering Congress and Exposition
October 31–November 6, 2008, Boston, Massachusetts, USA
IMECE2008-68478
EXPERIMENTAL STUDY OF A TWO-PHASE HEAT TRANSPORT DEVICE DRIVEN BY ELECTROHYDRODYNAMIC CONDUCTION PUMPING
Matthew R. Pearson
Department of Mechanical, Materials, and Aerospace Engineering,
Illinois Institute of Technology Chicago, Illinois, USA
Jamal Seyed-Yagoobi
Department of Mechanical, Materials, and Aerospace Engineering,
Illinois Institute of Technology Chicago, Illinois, USA
Proceedings of IMECE2008 2008 ASME International Mechanical Engineering Congress and Exposition
October 31-November 6, 2008, Boston, Massachusetts, USA
IMECE2008-68478
ABSTRACT Heat pipes are well-known as simple and effective heat
transport devices, utilizing two-phase flow and the capillary
phenomenon to remove heat. However, the generation of
capillary pressure requires a wicking structure and the overall
heat transport capacity of the heat pipe is generally limited by
the amount of capillary pressure generation that the wicking
structure can achieve. Therefore, to increase the heat transport
capacity, the capillary phenomenon must be either augmented
or replaced by some other pumping technique. Electro-
hydrodynamic (EHD) conduction pumping has been
demonstrated as an effective method for pumping liquid films
by using DC electric fields and a dielectric working fluid.
Beyond increased pumping capacity, EHD conduction pumping
offers other advantages over capillary pumping, such as active
control of the pumping capacity via the intensity of the applied
electric field. This experimental study demonstrates the
prospects of a macro-scale two-phase heat transport device that
is driven by EHD conduction pumping. Various liquid film
thicknesses are considered. In each case, the performance of the
EHD-driven heat transport device at various electric field
intensities is compared to the capabilities of the same device
under gravity alone. The effect of tilt on the device is also
considered.
INTRODUCTION Heat pipes are well-known for their ability to transport
large amounts of heat over relatively long distances. These
devices use two-phase flow and capillary forces to create a self-
circulating two-phase flow that carries the heat from a heat
source to a heat sink. Liquid is drawn from the condenser to the
evaporator through some wicking structure, whereupon it
evaporates. More information about traditional heat pipes can
1
om: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Ter
be found in Ref. [1]. Limitations do exist that serve to limit the
heat transport capacity of heat pipes. Frequently, the capillary
limitation (the limited pumping generation that the wicking
structure can provide) is the most limiting factor in heat pipe
operation. For this reason, there has been interest in how the
wicking structure of a heat pipe might be augmented or
replaced by some other pumping method. EHD pumping
mechanisms are one such method.
EHD phenomena involve the interaction of electric fields
and flow fields in a dielectric fluid medium. This interaction
can induce fluid motion by an electric body force. The electric
body force density acting on the molecules can be expressed as
[2]
�� � ��� � ���� �
�� ���
������ ��. (1)
The first term represents the Coulomb force, which is the force
acting on the free charges in an electric field. The second
(dielectrophoretic) and third (electrostriction) terms represent
the polarization force acting on polarized charges. The third
term is relevant only for compressible fluids. EHD pumping
has shown extensive potential due to its simple, lightweight,
non-mechanical design, low power consumption, low
acoustical noise, and the ease with which pumping can be
controlled by adjusting the applied voltage.
A variety of EHD pumping mechanisms are based on the
Coulomb force: conduction pumping, induction pumping, and
ion-drag pumping. All of these methods work by creating
regions of non-zero charge density within the working fluid,
but they differ in the manner of generating the Coulomb force.
Ion-drag pumping relies on the injection of ions into the liquid
from sharp liquid/solid interfaces, while induction pumping
uses an AC travelling wave to attract and repel charge induced
in the liquid due to gradients or discontinuities of electric
Copyright © 2008 by ASME
ms of Use: http://asme.org/terms
Down
conductivity, often due to temperature gradients [3].
Conduction pumping produces a non-zero charge density in
“heterocharge layers” near the electrodes through bulk electric
conduction through the liquid. As a result, the problems of ion-
drag pumping (specifically, degradation of the electrical
properties of the working fluid and potentially hazardous
operation) and induction pumping (specifically, the need for a
gradient in electric conductivity) can be avoided while still
maintaining the ability to pump using the Coulomb force [3].
There has been some research on the use of EHD
enhancement of a two-phase system such as a heat pipe or
capillary-pumped loop. None of these studies has considered
the use of conduction pumping of a two-phase, stratified, liquid
film. Jones [4] proposed replacing the capillary wick structure
of a heat pipe from the condenser to the evaporator with an
EHD pump that utilized polarization forces to generate
pumping. Jones and Perry [5] demonstrated this concept
successfully, but the performance was poor compared to
existing capillary driven heat pipes, due to a significant
mismatch of the circumferential capillary groove and EHD
pumping capabilities. Loehrke and Debs [6] further improved
the EHD heat pipe of Jones and Perry [5] and were able to
achieve equivalent thermal throughput of conventional axial-
groove heat pipes at an adverse tilt of 1.7 cm compared to only
0.3 cm for the conventional heat pipe. In a later study, Bologa
and Savin [7] used the dielectrophoretic force to enhance the
heat transport capacity in an experimental heat pipe operating
as a two phase thermo-siphon. By enhancing the rate of
condensation with EHD, the heat transport capacity was
increased 53% at an applied voltage of 36 kV.
Enhancement of the heat pipe transport capacity utilizing
the Coulomb force was investigated by Babin et al. [8]. They
used an ion-drag pump to generate the Coulomb force and to
increase the capillary limit of the heat pipe. Using R-11 as the
working fluid and a two-stage ion-drag pump located in the
liquid passage, a 20% increase in the transport capacity was
achieved at an applied voltage of 20 kV. Enhancement of the
heat transport capacity of a monogroove heat pipe with EHD
pumping was investigated by Bryan and Seyed-Yagoobi [9].
The EHD pump was located on the liquid channel in the
adiabatic section of the heat pipe, and the working fluid was
refrigerant R-123. The two experimental goals were to
2
loaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Ter
determine the magnitude of heat transport enhancement that
could be achieved using the EHD conduction pump and to
demonstrate the controllability and recovery of the heat pipe
during dry out. Both were successfully accomplished. Over
100% enhancement in the transport capacity was achieved
using the EHD conduction pump operating at 20 kV, but at
very low current levels on the order of ten micro-amps. The
EHD pump was also able to provide immediate recovery from
dry out when the heat pipe had been experiencing progressive
evaporator dry out.
At the time of the study by Bryan and Seyed-Yagoobi [9],
the conduction pumping phenomenon was not understood and
the flow generation was incorrectly attributed to polarization
forces (dielectrophoretic force). Once the conduction pumping
phenomenon had been clarified [10], the EHD-driven heat pipe
was revisited by Jeong and Seyed-Yagoobi [11] using
electrodes better optimized for conduction pumping. With these
improved electrodes, even more significant increases in heat
transport capacity were accomplished. For example, under
3 mm of favorable tilt, the total heat transport capacity
increased from 520 W with no EHD to 920 W with an applied
voltage of 10 kV. The improvements were even more
spectacular when a 3 mm adverse tilt was applied to the heat
pipe — heat transport capacity increased from 200 W with no
EHD to 800 W with an applied voltage of 10 kV.
EHD conduction pumping has also been investigated
recently as the pumping mechanism for a two-phase loop. In
studies by Jeong and Didion [12,13], up to 13.2 kPa of
pumping head generation was achieved using an EHD
conduction pump installed in the liquid line, with higher head
generation attainable by simply adding additional electrode
pairs to the pump. Under such conditions, the heat pipe was
shown to provide thermal control capacity for 35.8 W/cm2 of
heat flux.
The present study differs greatly from previous studies of
EHD-conduction-driven heat pipes because it uses the
conduction pumping of a stratified two-phase flow (liquid
film), whereas previous conduction-driven heat pipes have used
a single-phase conduction pump installed in the liquid line.
Conduction pumping has been successfully applied to pump
liquid films using electrodes embedded in the bottom channel
surface [14,15,16]. The pumping of a liquid film has several
Fig. 1. Section views of experimental two-phase heat transport device
Evaporator (51 mm)
Adiabatic/pumping sect ion (152 mm) Condenser (203 mm)
Water inlet Water outlet
Electrode Board
Heater
Glass viewing windows Pressure p ort
Vapor thermocouple port
Copyright © 2008 by ASME
ms of Use: http://asme.org/terms
Down
advantages, in particular the simplicity of the device because
the channel cross-section can be a simple rectangle without
need for any separation of the liquid and vapor phases for
pumping purposes.
EXPERIMENTAL SETUP The experimental two-phase heat transport device is shown
in Figs. 1 and 2. The total length of the channel is
This length is divided into an evaporator section
adiabatic pumping section (152 mm), and condenser section
(203 mm). The approximate width of the channel is
Glass windows running the entire length of the channel are
situated on the front and top walls of the channel to provide
clear visualization of the device’s internal workings. The
refrigerant HCFC-123 is used as the working fluid.
plates on the bottom of the channel act as the heat transfer
medium in the evaporator and condenser sections. Electrodes
are installed along the bottom of the channel in the adiabatic
pumping section, between the two copper plates of the
evaporator and the condenser.
The electrodes are manufactured as a printed circuit board
(PCB) using etching techniques, with the dimensions shown in
Fig. 3. The board material is FR-4 epoxy glass and the
electrodes are copper with a tin/lead reflow finish. The upper
surface of the PCB contains the electrodes and the lower
surface contains two bus lines (high voltage and ground).
0.4 mm vias provide the electrical connections between the
electrodes and the bus lines. The high voltage supply
delivered by a EW50R12 high voltage power supply by
Glassman High Voltage, Inc. Two feedthroughs
high voltage and one for ground), manufactured by CeramTec
North America, provide electrical connectivity from the high
voltage power supply to inside the pressure-sealed two
channel. These feedthroughs have a voltage rating of
and a current rating of 55 A. For the studies of EHD, a voltage
Fig. 2. Photograph of the two-phase heat transfer device. The
valves and pipes at the bottom-right of the image are for the
connection of refrigerant supply tank, refrigerant recovery device,
and vacuum pump
of the device because
section can be a simple rectangle without
need for any separation of the liquid and vapor phases for
phase heat transport device is shown
. The total length of the channel is 406 mm.
This length is divided into an evaporator section (51 mm),
, and condenser section
the channel is 57 mm.
Glass windows running the entire length of the channel are
situated on the front and top walls of the channel to provide
of the device’s internal workings. The
123 is used as the working fluid. Copper
plates on the bottom of the channel act as the heat transfer
medium in the evaporator and condenser sections. Electrodes
are installed along the bottom of the channel in the adiabatic
pumping section, between the two copper plates of the
are manufactured as a printed circuit board
, with the dimensions shown in
4 epoxy glass and the
electrodes are copper with a tin/lead reflow finish. The upper
surface of the PCB contains the electrodes and the lower
s (high voltage and ground).
vias provide the electrical connections between the
electrodes and the bus lines. The high voltage supply is
high voltage power supply by
Glassman High Voltage, Inc. Two feedthroughs (one for the
high voltage and one for ground), manufactured by CeramTec
North America, provide electrical connectivity from the high
sealed two-phase
feedthroughs have a voltage rating of 20 kVDC
For the studies of EHD, a voltage
fer device. The
right of the image are for the
connection of refrigerant supply tank, refrigerant recovery device,
3
loaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Te
of 5 kV was used in all tests. This represented the highest
voltage that could be used without the risk of arcing.
gradients in temperature (and therefore electrical conductivity)
do exist within the liquid film, the DC electric field imposed by
the power supply will produce only conduction pumping, as
induction pumping requires a AC traveling
field. [3] Ion-injection is also assumed t
there is likely to be some minor injection of ions at the corners
of the electrodes.
Heat is delivered to the evaporator by an ULTRAMIC®
600 ceramic heater by Watlow Electric Manufacturing
Company. The nominal power rating of the heate
and its dimensions are 35 mm ×
3 mm. This corresponds to a maximum heat flux of 100
Shin-Etsu X23-7762 thermal compound
improved thermal contact between the heater and t
surface of the evaporator plate. A T
bonded to the lower surface of heater, is used to monitor the
heater temperature. The heater power is controlled by a variable
transformer, with a Watlow 965 temperature controller u
shut off power to the heater if the temperature of the heater
exceeds 110°C. The voltage drop across the heater and the
current flow through the heater are both measured separately
using digital multimeters. The lower surface
insulated using 0.5 in. thick cork to ensure that most of the heat
is delivered through the copper to the refrigerant.
removed at the condenser using a chilled water supply provided
by a NESLAB HX-150 chiller by
Inc.
A pressure transducer and backup pressure gauge are used
to monitor the pressure of the chamber. A pressure release
valve is set to approximately 100
dangerous pressure rises caused by the heating of the working
fluid. A DV-6 vacuum tube from Teledyne Hastings
Instruments is used to ensure a deep vacuum of at least
500 µm Hg exists before charging the device with refrigerant.
Two T-type thermocouple probes are inserted into the chamber,
one in the vapor phase and one in the liquid p
Unfortunately, the liquid temperature reading is greatly
influenced by the temperature of the chilled water, due to the
placement of the thermocouple. This placement was
unavoidable due to the need to handle very thin liquid films.
Therefore, the liquid temperature is not monitored during
experiments and the saturation conditions and refrigerant purity
are judged based on the vapor temperature reading.
Fig. 3. Electrode design (all dimensions in
5.1
5.1
1.22 4.06
152
kV was used in all tests. This represented the highest
voltage that could be used without the risk of arcing. Although
gradients in temperature (and therefore electrical conductivity)
exist within the liquid film, the DC electric field imposed by
the power supply will produce only conduction pumping, as
induction pumping requires a AC traveling-wave-type electric
injection is also assumed to be small, although
there is likely to be some minor injection of ions at the corners
Heat is delivered to the evaporator by an ULTRAMIC®
Watlow Electric Manufacturing
. The nominal power rating of the heater is 1225 W
× 35 mm with a thickness of
This corresponds to a maximum heat flux of 100 W/cm2.
thermal compound is used to provide
between the heater and the copper
. A T-type surface thermocouple,
bonded to the lower surface of heater, is used to monitor the
The heater power is controlled by a variable
transformer, with a Watlow 965 temperature controller used to
shut off power to the heater if the temperature of the heater
C. The voltage drop across the heater and the
current flow through the heater are both measured separately
The lower surface of the heater is
in. thick cork to ensure that most of the heat
is delivered through the copper to the refrigerant. Heat is
removed at the condenser using a chilled water supply provided
chiller by Thermo Fisher Scientific,
A pressure transducer and backup pressure gauge are used
to monitor the pressure of the chamber. A pressure release
valve is set to approximately 100 kPa gage to prevent any
dangerous pressure rises caused by the heating of the working
m tube from Teledyne Hastings
Instruments is used to ensure a deep vacuum of at least
Hg exists before charging the device with refrigerant.
type thermocouple probes are inserted into the chamber,
one in the vapor phase and one in the liquid phase.
Unfortunately, the liquid temperature reading is greatly
influenced by the temperature of the chilled water, due to the
placement of the thermocouple. This placement was
unavoidable due to the need to handle very thin liquid films.
uid temperature is not monitored during
experiments and the saturation conditions and refrigerant purity
are judged based on the vapor temperature reading.
. Electrode design (all dimensions in mm)
16.51
0.97
50.8
Copyright © 2008 by ASME
rms of Use: http://asme.org/terms
Down
All data presented in this work were obtained at a
refrigerant saturation temperature of 30.0°C ± 0.2°C. The
corresponding saturation pressure, based on saturation tables
for HCFC-123, was 109.5 kPa absolute. If the measured
pressure in the system exceeded 111.5 kPa (due to the leakage
of air into the device during periods of inactivity) then the
refrigerant was recovered, a deep vacuum was pulled, and the
device was charged with fresh refrigerant. For each data point,
the chiller set point temperature was fixed. The heater power
was then manually adjusted using the variable transformer until
the device reached steady state within the chosen saturation
temperature range. Once steady state was reached, all data
readings were recorded. The chiller set point temperature was
then reduced in preparation for the next data point. Chiller set
point temperatures from 30°C to 5°C were chosen in 1, 2 or
3°C increments.
RESULTS Three different film thicknesses were considered: 2 mm,
4 mm, and 6 mm. In all three cases, the heat transport device
was carefully oriented to the horizontal position. The resulting
boiling curves are shown in Figs. 4–6. For all heat fluxes
considered, pool boiling was present in the evaporator.
Although pool boiling is generally avoided in traditional heat
pipes in order to avoid disrupting the capillary pressure
generation, pool boiling provides no problems for the EHD-
driven pumping mechanism.
For the 2 mm film, Fig. 4 shows that without EHD the
burnout of the evaporator occurred at a heat flux of
14.4 W/cm2. Without any EHD pumping, the liquid film flows
due to gravity, with the phase-change processes in the
evaporator and condenser causing a slight gradient in film
thickness and a resulting gravity-driven flow to the evaporator.
From visual observation of the evaporator section, it was clear
that the burnout was caused by dryout of the evaporator, with
insufficient liquid being pumped into the evaporator by gravity.
Application of 5 kV EHD to supplement the gravitational body
force caused immediate re-wetting of the evaporator due to the
enhanced pumping. With EHD active, dryout of the evaporator
did not occur until a heat flux of 51.4 W/cm2, representing an
improvement of 350%.
For the 4 mm case, the thicker film allowed a higher
gravity-driven flow rate to exist. As a result, the no-EHD
burnout heat flux increased to 45.6 W/cm2, as shown in Fig. 5.
In this case, burnout was once again caused by the drying out
of the evaporator due to insufficient liquid flow rate.
Application of 5 kV EHD caused a slight increase in the slope
of the boiling curve, representing an improvement in the heat
transfer coefficient at the evaporator. The burnout heat flux also
increased to a value of 54.8 W/cm2. Furthermore, when the
burnout heat flux was reached with EHD active, liquid was still
present in the evaporator section. Therefore, the mechanism of
burnout is not caused by insufficient liquid flow rate but by
hydrodynamic phenomena occurring very near the evaporator
surface, akin to the critical heat flux (CHF) condition in pool
boiling.
4
loaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Te
Fig. 4. Boiling curve for the 2 mm film, no tilt.
Fig. 5. Boiling curve for the 4 mm film, no tilt.
Fig. 6. Boiling curve for the 6 mm film, no tilt..
0
10
20
30
40
50
60
0 10 20 30 40 50 60 70 80 90
He
at
Flu
x (
q")
[W
/cm
2]
Heater Superheat (Th − Tv) [°C]
0 kV 5 kV
0
10
20
30
40
50
60
0 10 20 30 40 50 60 70 80 90
He
at
Flu
x (
q")
[W
/cm
2]
Heater Superheat (Th − Tv) [°C]
0 kV 5 kV
0
10
20
30
40
50
60
0 10 20 30 40 50 60 70 80 90
He
at
Flu
x (
q")
[W
/cm
2]
Heater Superheat (Th − Tv) [°C]
0 kV 5 kV
Copyright © 2008 by ASME
rms of Use: http://asme.org/terms
Down
Further increasing the film thickness to 6 mm, EHD is
shown to provide very small increases in the slope of the
boiling curve. However, the curves eventually cross such that
the burnout heat flux actually appears to be slightly lower with
the EHD pumping than without it. The burnout condition (a
CHF condition as the evaporator section was still filled with
liquid) occurred at 51.3 W/cm2. Without EHD, this same heat
flux did not cause burnout. Unfortunately, higher heat flux
levels could not be applied because no additional heat could be
removed from the condenser, its performance somewhat
reduced by the thick level of liquid present there.
To further consider the effectiveness of the EHD film
pumping performance, the heat pipe, containing a 4 mm-thick
liquid film, was inclined such that the evaporator side of the
setup was 14 mm higher than the condenser side of the setup.
This inclination was such that without EHD the evaporator was
completely dry, with the “shore-line” of the liquid film aligned
just below the leading edge of the evaporator plate. Because the
evaporator was initially at dryout, no 0 kV data could be
obtained (small heater heat fluxes caused the heater
temperature to reach the maximum allowable temperature). As
such, the burnout condition is artificially marked at 0 W/cm2 in
Fig. 7. However, with 5 kV of applied voltage to the electrodes,
the fluid was pumped very effectively up the incline such that
fluid wet the evaporator. As a result, evaporator dryout and the
associated heater burnout occurred at 20.5 W/cm2. For this case
of adverse tilt, a 2 mm film thickness was attempted, but the
EHD pumping, while present, was not sufficient to wet the
evaporator. For the 6 mm film thickness, so much liquid was
collected in the condenser section due to the adverse tilt that
heat removal by the condenser was extremely limited and heat
fluxes of interest could not be studied.
As an additional study, a 9 mm favorable tilt (i.e. the
evaporator being below the condenser) was considered for the
case of a 2 mm film thickness. Figure 8 shows reasonable
increases in the slope of the boiling curve, suggesting that the
EHD pumping force remained important even in the presence
of a large gravitational body force. Without EHD, the critical
heat flux condition occurred at 51.7 W/cm2. With EHD, heat
fluxes of 56.8 W/cm2 were achieved without burnout
occurring. Further increases in heat flux were not possible due
to limitations in heat removal by the condenser. Thicker films
were not considered for the favorable tilt because of extensive
pooling of liquid in the evaporator section.
For all test cases with an 5 kV applied voltage, the steady-
state current and power consumption of the EHD conduction
pump remained below 100 µA and 0.5 W, respectively, which
is a trivial amount relative to the power input of the heater (e.g.
613 W of heater power corresponds to 50 W/cm2 of heat flux).
DISCUSSION OF RESULTS As a feasibility study of the concept of an EHD
conduction-driven heat pipe, the results are promising.
Conduction pumping head generation has been shown, by
Atten and Seyed-Yagoobi [10] to increase approximately
linearly with the number of electrode pairs, provided that those
5
loaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Ter
pairs are spaced a sufficient distance apart that they do not
interact. Power consumption would then increase linearly too.
Therefore, the liquid film can be pumped over much longer
distances by extending the adiabatic/pumping section and
incorporating additional electrodes, while retaining very
modest power consumption levels.
From visual observation of the heat transport device during
experiment runs, it is clear that the incorporation of electrodes
in the condenser section would likely serve to significantly
improve performance. In the current configuration, the
condenser represents a very large load on the EHD pump and
even when EHD is enabled, liquid is supplied to the electrodes
in the adiabatic/pumping section due to gravity alone.
Therefore, the film thickness in the condenser decreases
slightly as it approaches the EHD pump, such that for thin films
(e.g. 2 mm), the thickness of the film at this boundary between
the condenser and the adiabatic/pumping section becomes very
small, choking the flow and limiting the EHD pumping
performance. The inclusion of electrodes along the length of
Fig. 7. Boiling curve for the 4 mm film, 14 mm of adverse tilt.
Fig. 8. Boiling curve for the 2 mm film, 9 mm of favorable tilt.
0
5
10
15
20
25
0 10 20 30 40 50 60 70 80 90
He
at
Flu
x (
q")
[W
/cm
2]
Heater Superheat (Th − Tv) [°C]
0 kV 5 kV
0
10
20
30
40
50
60
0 10 20 30 40 50 60 70 80 90
He
at
Flu
x (
q")
[W
/cm
2]
Heater Superheat (Th − Tv) [°C]
0 kV 5 kV
Copyright © 2008 by ASME
ms of Use: http://asme.org/terms
Dow
the condenser would likely eliminate these problems, and the
flow of liquid in the condenser could be significantly
augmented by the presence of an EHD body force. This effect
is evidenced in Fig. 8 where the favorable tilt served to assist
the flow of liquid out of the condenser section and assist the
EHD pumping mechanism. Even with the gravity-driven flow
being very effective, the data show further improvements to the
heat transfer coefficient and heat flux capacity once EHD-
assistance was provided, aided by the gravity-driven flow in the
condenser section. For thicker films, a larger gravitational body
force can exist in the condenser, but the extension of the
pumping section into the condenser is still expected to cause
significant improvements in pumping.
Visual observations also lead the investigators to believe
that the placement of electrodes in the evaporator would also be
extremely beneficial, particularly for thin films and adverse
tilts. For example, Fig. 7 shows the performance of the heat
transport device under a significant adverse tilt. It must be
noted that at such a tilt, electrodes were effective in wetting
only the first 50% of the evaporator length. Consequently, the
area over which evaporation was occurring was approximately
halved. Once the liquid passed the last electrode, it quickly lost
momentum as it travelled uphill along the evaporator. The
presence of additional electrodes to continue the pumping of
liquid along the entire length is expected to yield significant
performance improvements for these adverse tilts by allowing
100% of the area of the evaporator to be wetted.
The electrodes in the current setup do not extend across the
entire width of the channel, as shown in Fig. 3. As a result,
there was generally some backflow of liquid along the sides of
the channel from the evaporator back to the condenser. This
flow could be seen by the trajectory of bubbles departing from
the leading edge of the evaporator – those in the central portion
of the channel departed away from the adiabatic/pumping
section while those very close to the walls of the channel
departed towards the adiabatic/pumping section. Therefore,
removing this gap is expected to result in improved pumping
and heat flux performance due to the higher volume of liquid
film that is subject to an EHD body force, the reduction or
removal of the backflow and associated pumping losses that
occur as a result.
In many aspects, the horizontal, EHD-driven flow of the
current heat transport device is analogous to studies of the
boiling of vertical, falling films that are gravity-driven (see,
e.g., Refs. [17,18,19]). However, the current research has
illustrated notable differences between the two flows. In the
case of vertical flows, studies have considered the flow over a
heated surface but the flowing film is allowed to continue
beyond that surface. Therefore, if the liquid film mass flow rate
entering the evaporator exceeds the mass rate of evaporation
then excess liquid leaves the evaporator. In the current EHD-
driven experimental device, the end of the device is closed;
therefore, any excess liquid mass accumulates in the
evaporator, thickening the film there, until the pressure head of
the thickened film balances the pressure generation of the EHD
pump. From observations of vertical falling films, for example
6
nloaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Te
by Mudawwar et al. [17], the critical heat flux occurs when the
main part of the liquid film separates from the heated wall due
to the vigorous vapor generation at the surface. In the case of a
vertical film, gravity can do nothing to prevent this separation
as there is no component of gravitational force directed toward
the wall. However, in the case of the horizontal film in the
present study, gravity assists in bringing the liquid to the heater
surface (as it does with pool boiling), which could potentially
lead to higher heat fluxes than for vertical, falling films.
In the present study, no attempt has been made to tune the
voltage applied to the electrodes. It has been mentioned that if
the rate of pumping exceeds the mass rate of evaporation then
some liquid accumulates in the evaporator section, thickening
the film in that location. This thickening may possibly serve to
diminish the maximum heat flux – bubbles can escape from the
surface more quickly when the film is thinner [19]. This
phenomenon may be the reason that the boiling curves in Fig. 6
appear to cross, with the critical heat flux occurring at a lower
heat flux when EHD pumping is active. The thinner film in the
evaporator that exists when EHD is switched off may enable a
higher critical heat flux by allowing the nucleating vapor
bubbles to escape more quickly.
CONCLUSIONS An experimental two-phase device driven by the EHD
conduction pumping phenomenon has been fabricated and
demonstrated. The results have shown that the use of EHD can
provide significant increases in the maximum heat flux of the
device when compared to the use of gravity alone. Performance
improvements have also been demonstrated for both adverse
and favorable tilts. For thin films, the maximum heat flux
corresponds to evaporator dryout, which is caused by
insufficient pumping. For thicker films, the maximum heat flux
corresponds to a critical heat flux condition, as liquid is still
present in the evaporator section. Through examination of the
data and from visual observations of the evaporation and EHD
pumping processes, several improvements to the design have
been proposed. Most notably: (1) The need for electrodes along
the entire length of the device, not just in the central adiabatic
section, in order to provide increased liquid flow rates,
especially for thinner films, and (2) Further study of the boiling
processes in the evaporator and an effort to adapt the models of
vertical, falling films to the case of horizontal film motion.
NOMENCLATURE � = electric field vector
� = electric field magnitude ��� �� = electric body force
� = temperature
= electric permittivity
� = mass density
�� = charge density
Copyright © 2008 by ASME
rms of Use: http://asme.org/terms
Down
ACKNOWLEDGEMENTS The authors thank NASA Headquarters – Microgravity
Fluid Physics Program and the NASA Goddard Space Flight
Center for their financial support of this research project. The
first author also thanks the National Science Foundation
Graduate Research Fellowship Program for their support of his
graduate studies.
REFERENCES [1] Peterson, G. P., 1994, An introduction to heat pipes:
modeling, testing, and applications, Wiley, New York.
[2] Melcher, J. R., 1981, Continuum Electromechanics, MIT
Press, Cambridge, MA.
[3] Seyed-Yagoobi, J., 2005, "Electrohydrodynamic pumping
of dielectric liquids," Journal of Electrostatics, 63(6–10),
pp. 861–869.
[4] Jones, T. B., 1974, "An Electrohydrodynamic Heat Pipe,"
Mechanical Engineering, 96(1), pp. 27–32.
[5] Jones, T. B. and Perry, M. P., 1974, "Electro-
hydrodynamic Heat Pipe Experiments," Journal of
Applied Physics, 45(5), pp. 2129–2132.
[6] Loehrke, R. I. and Debs, R. J., 1975, "Measurement of the
Performance of an Electrohydrodynamic Heat Pipe,"
AIAA Paper 75-659.
[7] Bologa, M. K. and Savin, I. K., 1990, "Electro-
hydrodynamic Heat Pipes," Proceedings of the 7th
International Heat Pipe Conference, Minsk, pp. 549–562.
[8] Babin, B. R., Peterson, G. P., and Seyed-Yagoobi, J.,
1993, "Experimental Investigation of an Ion-Drag Pump
Assisted Heat Pipe," Journal of Thermophysics and Heat
Transfer, 7(2), pp. 340–345.
[9] Bryan, J. E. and Seyed-Yagoobi, J., 1997, "Heat transport
enhancement of monogroove heat pipe with
electrohydrodynamic pumping," Journal of
Thermophysics and Heat Transfer, 11(3), pp. 454–460.
[10] Atten, P. and Seyed-Yagoobi, J., 2003, "Electro-
hydrodynamically induced dielectric liquid flow through
pure conduction in point/plane geometry," IEEE
Transactions on Dielectrics and Electrical Insulation,
10(1), pp. 27–36.
[11] Jeong, S.-I. and Seyed-Yagoobi, J., 2002, "Performance
enhancement of a monogroove heat pipe with
electrohydrodynamic conduction pumping," Proceedings
of the ASME International Mechanical Engineering
Congress and Exposition, New Orleans, LA.
[12] Jeong, S.-I. and Didion, J., 2007, "Thermal control
utilizing an electro-hydrodynamic conduction pump in a
two-phase loop with high heat flux source," Journal of
Heat Transfer, 129(11), pp. 1576–1583.
[13] Jeong, S.-I. and Didion, J., 2008, "Performance
characteristics of electrohydrodynamic conduction pump
in two-phase loops," J. Thermophysics Heat Transfer,
22(1), pp. 90–97.
[14] Yazdani, M. and Seyed-Yagoobi, J., "Electrically induced
dielectric liquid film flow based on conduction
7
loaded From: http://proceedings.asmedigitalcollection.asme.org/ on 04/01/2014 Ter
phenomenon," Physics of Fluids, submitted for
publication.
[15] Yazdani, M. and Seyed-Yagoobi, J., "Numerical
investigation of EHD conduction pumping of liquid film
in the presence of evaporation," Journal of Heat Transfer,
submitted for publication.
[16] Siddiqui, M. A. W. and Seyed-Yagoobi, J.
"Experimental study of pumping of liquid film with
electric conduction phenomenon," IEEE Transactions on
Industry Applications, submitted for publication.
[17] Mudawwar, I. A., Incropera, T. A., and Incropera, F. P.,
1987, "Boiling heat transfer and critical heat flux in liquid
films falling on vertically-mounted heat sources,"
International Journal of Heat and Mass Transfer, 30(10),
pp. 2083–2095.
[18] Ueda, T., Inoue, M., and Nagatome, S., 1981, "Critical
heat flux and droplet entrainment rate in boiling of falling
liquid films," International Journal of Heat and Mass
Transfer, 24(7), pp. 1257–1266.
[19] Mesler, R., 1979, "Nucleate boiling in thin liquid films,"
Boiling Phenomena, Vol. 2., Hemisphere Publishing
Corporation, Washington, DC, pp. 813–819.
Copyright © 2008 by ASME
ms of Use: http://asme.org/terms