Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.
Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.
The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.
The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.
The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance, retrofit
& operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs
The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operationsfrom the corporate headquarters in Dammam, Saudi Arabia.
Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.
All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.
Factories and Productions
Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facilityin Italy operated by Geoclima.
The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.
Quality & Product Certificates
The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZACs products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.
Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditionersmanufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the ConcealedUnits up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin Air Handling Units
up to 138,316 CFM and the Water Chillers up to 600 TR cooling capacity. In addition, centrifugal chillers - powered by MHcompressors - are available up to 5,000 TR.
5/19/2018 ASY(R-134)Series Screw Chiller
3/51
INDEX
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Contents Page
Model decoding ........................................................................................................................................ 2
Unit features, standard specifications & options .................................................................................... 3-6
Microprocessor controller .......................................................................................................................... 7
Physical data ....................................................................................................................................... 8-11
Selection procedure ............................................................................................................................12-13
Performance data................................................................................................................................14-19
Electrical data ..................................................................................................................................... 20-22
Water side pressure drop ........................................................................................................................ 23
Recommended installation for sensor & water flow switch ...................................................................... 24
Unit dimensions .................................................................................................................................25-31
Typical schematic wiring diagram .......................................................................................................32-33
Typical sequence of operation ................................................................................................................. 34
Application guidelines .........................................................................................................................35-43
Rigging instructions ................................................................................................................................. 44
Installation clearance .............................................................................................................................. 45
Mounting location .................................................................................................................................... 46
Load distribution .................................................................................................................................. 47-48
1
5/19/2018 ASY(R-134)Series Screw Chiller
4/51
2
ASY
AIRCOOLED
SCREW
WATER
CHILLERS
MO
DELDECODING
8
ELECTRICAL
SUPPLY
(V-Ph-Hz)
4,5&6
UNITSIZE
050
060
070
080
090
100
120
130
140
150
160
170
180
190
200
215
230
240
250
270
295
310
330
350
375
400
420
450
475
500
540
560
590
H:2
08/230-3-6
0
M:3
80-3-6
0
(4WIRE)
F:4
60-3-6
0
1,2&3
BASIC
(SERIES)
B:
R-1
34a
7
REFRIGER-
ANT
9
CONDENSER
COIL
A
:ALUMINUMFIN
B:
PRE-C
OATED
ALUMINUMFIN
C:
COPPERFIN
D:
ALUMINUMFIN
WITHRes
isTec
COATING
E:
COPPERFIN
WITHRes
isTec
COATING
(SEENOTE#1
BELOW)
10
CIRCU
ITBREAKER
O
PTIONS
11
COOLER
OPTIONS
A:
STANDARDWITH
VICTAULICCONN
.
B:
FLANGECONN
.
(OPTIONAL)
C:
ASMESTAMPED
WITHVICTAULIC
CONN
.
(OPTIONAL)
D:
ASMESTAMPED
WITHFLANGE
CONN
.
(OPTIONAL)
A:
STANDARD
B:CO
M
PRESSOR
CIR
CUIT
BR
EAKER
13
HGBP
OPTIONS
A:
STANDARDUNIT
WITHOUTHGBP&
WITHOUTSUCTION
SERVICEVALVE
B:
WITHHGBP&
WITHOUTSUCTION
SERVICEVALVE
(OPTIONAL)
C:
WITHOUTHGBP&
WITHSUCTION
SERVICEVALVE
(OPTIONAL)
D:
WITHHGBP&
WITHSUCTION
SERVICEVALVE
(OPTIONAL)
NOTES:
1.F
OROTHERCOATING,S
PECIFYYOUR
REQUIREMENTSINWRITING.
2.C
OMPUTERSELECTEDDIGITS(FROM
'AA'TO'ZZ')DESCRIBINGOTHEROPTIONS&A
CCESSORIESORCOMBINATIONSTHEREOF,S
UCHAS:
-CONDENSERCOILGUARD
-COMPRESSOR&COOLERGUARD
-UNITMAINNON-FUSEDDISCONNE
CTSWITCH
-COMPRESSORENCLOSURE
-WATERFLOWSWITCH
-SPRINGISOLATOR
-MULTI-ResisTecPIPING
-MULTI-ResisTecSHEET
METAL
etc...
A:
STANDARDUNIT
WITHOU
TSUCTION
SERVIC
EVALVE
B:
UNITWITH
SUCTIO
NSERVICE
VALVE
(OPTIONAL)
14&15
OPTION
S
&
ACCESSORIES
SEENOTE
#2
BELOW
16&17
UL
OPTIONS
A:
STANDARD
UNIT
WITHOUTUL
B:
STANDARD
UNITWITHUL
LISTED
1
2
COMPR
ESSOR
OPT
IONS
5/19/2018 ASY(R-134)Series Screw Chiller
5/51
FEATURESThese ASY air cooled screw water chillers offer the ultimate combination of energy saving design, superior engineering
features and flexibility of application as required by todays market.
* These chillers incorporate the newest advanced microprocessor controller. This controller monitors analog and digita
inputs to achieve precise control & protective functions of the air cooled water chiller units. This microprocessorcontroller is complete with all the hardware and software necessary to control the chiller unit and ensures its efficiency
and reliability.
* Designed to conform toARI standard 550/590water chilling packages using the vapor compression cycle.
* Designed to conform toANSI/ASHRAE 15-1994Safety code for Mechanical Refrigeration.
* Compact unit design and excellent serviceability.
* All packaged chillers incorporate compact water coolers with enhanced inner grooved copper tubes bundled into a "U"shape and expanded into a steel tubular sheets which offer efficient water flow as well as heat transfer design resulting
in optimal unit performance.
* High Energy Efficiency Ratio (EER) semi-hermetic compact twin screw compressorsare provided in these units.
* Single point power connection (for models ASY050B - ASY500B) to minimize job site installation cost and time. Duapoint power connection for models ASY540B - ASY590B.
* Completely wired control panel with the advanced microprocessor controller provides all the necessary operat-ing and safety controls.
* Compressors are with part winding start.
* Low noise condenser fans, direct drive at 1000 RPM with rolled form venturi design to eliminate short circuiting ofairflow.
* All fans are die cast aluminum propeller type with aerodynamic design, top discharge, provided with protectivegrille mounted on top panel within the unit casing.
* All condenser fan motors are totally enclosed air over type (TEAO) with class ''F'' winding insulation and balbearings. Inherent thermal protection of the automatic reset type and specially designed for outdoor applica-
tion is included.
3
CAPACITY CONTROL
These chillers are equipped with stepless capacity control system as standard for very accurate response to load require-
ments and best part load efficiency. Each compressor is equipped with a slider controller that enables to modulate capac-ity between 25% to 100%, thus giving a broad range to control total chiller capacity between 10% to 100% on an average
This system has the following advantages:
1. Infinite capacity modulation that allows the compressor capacity to exactly match the cooling load.
2. Reduce compressor cycling which leads to better operational reliability.
3. Reduce operating cost.
4. For units with Hot gas bypass (optional): The unit modulates to approximately 50% of its compressor lowest unloaded
capacity.
STANDARD SPECIFICATIONS
5/19/2018 ASY(R-134)Series Screw Chiller
6/51
4
SEMI-HERMETIC COMPACT TWIN SCREW COMPRESSORSAll compressors are compact semi-hermetic twin screwof the high capacity and efficiency due to their perfect profile
form ratio 5:6. They are simple and of robust construction with slider control valve for capacity unloading, discharge shut-off valves with optional suction service valves, built-in check valve in discharge gas outlet, oil sight glass, oil fill/drain
service valve, directly flanged-on three stage oil separator with long-life fine filter 10 microns mesh size, robust axiabearings in tandem configuration, suction gas filter, internal pressure relief valve and manual lock-out electronic protection
system for thermal motor winding temperature, phase reversal, discharge gas temperature protection controls.
CONDENSER COILSW-configuration condenser coils are corrugated fin and tube type, constructed of seamless 3/8" dia. & 0.011" (0.27 mm)thick copper tubes, mechanically bonded to aluminum fins for maximum heat transfer efficiency.
As a standard on aluminum fins, ZAC provides Coil Coating, which is a single component of aluminum
impregnated coating applied on the fins of heat exchanging coils. The product has been designed for Middle Eastclimate conditions. A high chemical, abrasion and UV resistance has been proven in both laboratories and on field
environment. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenanceor rejuvenation purposes.
The fins have full self spacing collars which completely cover each tube. The staggered tube design improves thethermal efficiency. End plates support sheets are 14 gauge galvanized steel, formed to provide structural strength.
Each coil is pressure tested in the factory at not less than 450 psi air pressure.
COMPACT DESIGN SHELL AND TUBE WATER COOLERSThe DX shell & tube cooler with removable U shaped bundled tubes are made of internally grooved copper tubes
expanded into a heavy steel tubular sheets.
The chiller cooler & baffles are constructed of steel and brass respectively. The coolers are insulated with heavy closedcellular foam insulation (3/4" thick). All chiller barrels are fitted with vent, drain connection and victaulic water pipeconnection as standard.
WATER SIDE REFRIGERANT SIDE
DESIGN PRESSURE,
(BAR/PSIG)
TEST PRESSURE,
(BAR/PSIG)
DESIGN PRESSURE,
(BAR/PSIG)
TEST PRESSURE,
(BAR/PSIG)
16/235 22.8/335 29/426 41.5/610CE (STD)
10/147 11.3/165 15.5/228 23.3/342ASME (option)
CABINETAll units are of heavy gauge (G-90) galvanized steel. Steel sheet panels are zinc coated and galvanized by hot dipprocess of lock-forming quality conforming to ASTM A 653 commercial weight G-90 followed by air dry paint or backed on
electrostatic polyester dry powder coat.
CONTROL PANEL
The control panel design is equivalent to NEMA 4 (IP55) with hinged door for easy access ensuring dust and weather-proof construction. Internal power and control wiring is neatly routed, adequately anchored and all wires are identified
with cable markers as per NEC standards applicable to HVAC industry.
The electrical controls used in the control panel are UL approved which are reliable in operation at high ambient condi-
tions for a long period.
CONDENSER FANSCondenser fans, the impeller and motors are so constructed to form an integral unit. All fan motors shall be three phasewith class ''F'' winding insulation and ball bearings for high ambient application. These fan motors are of totally enclosed
air over type (TEAO) with inherent thermal protection of automatic reset type.
SHELL & TUBE
HEAT
EXCHANGER(COOLER)
5/19/2018 ASY(R-134)Series Screw Chiller
7/51
5
STANDARD CONTROL & SAFETY DEVICESMICROPROCESSOR CONTROLLER: This controller monitors analog and digital inputs to achieve precise control & safety
functions of the unit.
COMPRESSOR IN-BUILT PROTECTION DEVICE: Protects the compressor by monitoring:
A) Motor winding temperature in case of overload.
B) Discharge gas temperature in case of overheating.
C) Phase reversal for direction of rotation.
STARTERS: The starter is operated by the control circuit and provides power to the compressor motors. These devices arerated to handle safely both RLA and LRA of motors.
CRANKCASE HEATERS: Each compressor has immersion type crankcase heater. The compressor crankcase heater is
always on when the compressors are de-energized. This protects the system against refrigerant migration, oil dilution andpotential compressor failure.
HIGH PRESSURE SWITCH: This switch provides an additional safety protection in the case of excessive discharge
pressure.
UNDER & OVER VOLTAGE AND PHASE PROTECTION: Protects against low & high incoming voltage as well as singlephasing, phase reversal and phase imbalance by de-energizing the control circuit. It is an automatic reset device, but it canbe set up for manual reset.
COMPRESSOR CIRCUIT BREAKERS: Protects against compressor branch circuit fault. When tripped (manually or
automatically), the breaker opens the power supply to the compressor and control circuit through auxiliary contacts.
HARD WIRE TO BMS: Communicate the controller to site BMS thru hard wire:
1. Remote Unit Enable/Disable (Start/Stop) a digital input to the controller that allows the user to Start and normallyshutdown the chiller unit from remote or control room.
2. Unit General Alarm a digital output signal from the controller to indicate that alarm is existing in the chiller.
3. Compressor Circuit Enable/Disable a digital input to the controller that allows the user to Start and normally shutdown
the compressor from remote or control room.
4. Second Temperature Control Set point a digital input to the controller that allows the user to enable the second sepoint. Value for the second temperature control set point can be modified at the controller parameter.
5. Set point correction an analog input to the controller that allows the user adjust the temperature control set point viaexternal analog signal (4-20mA).
STANDARD ACCESSORIESUNIT ON-OFF SWITCH: ON-OFF switch is provided for manually switching the unit control circuit.
INDICATOR LIGHTS: LED lights indicates power ON to the units, MENU adjustment and FAULT indications due to trip onsafety devices.
ELECTRONIC EXPANSION VALVE: Electronic expansion valve is used to regulate the refrigerant flow to the water cooler
and maintain a constant superheat and load optimization.
FILTER DRIER (REPLACEABLE CORE TYPE): Refrigerant circuits are kept free of harmful moisture, sludge, acids and oicontaminating particles by the filter drier.
SIGHT GLASS: A moisture indicating sight glass is installed in the liquid line. An easy-to-read color indicator showsmoisture contents and provides a mean for checking the system refrigerant charge.
LIQUID LINE SOLENOID VALVE: Closes when the compressor is off to prevent any liquid refrigerant from accumulating in
the water cooler during the off cycle.
CONTROL CIRCUIT TRANSFORMER: On 460V-3Ph-60Hz power supply factory mounted and wired control circuit trans-former is furnished eliminating the need for running a separate 220 volt control circuit power supply.
5/19/2018 ASY(R-134)Series Screw Chiller
8/51
6
OPTIONS(All options are at extra cost. Please check with your nearest dealer/sales office)
HOT GAS BYPASS SYSTEM: Hot gas bypass is provided on the lead circuit to permit operation of the system down to 50% of
its unloaded capacity. Under low ambient condition, it controls temperature by eliminating the need to cycle the compressor onand off, ensuring narrow temperature swing and lengthen the life span of the compressor.
WATER FLOW SWITCH: Paddle type field adjustable flow switch for water cooler circuits. Interlock into unit safety circuits
so that the unit will remain off until water flow is determined.
UNIT MOUNT SPRING ISOLATORS: This housed spring assemblies have a neoprene friction pad on the bottom toprevent vibration transmission.
LIQUID COOLERS:ASME code stamped liquid cooler.
PRESSURE GAUGES: Suction & discharge pressures gauges.
SUCTION SERVICE VALVE: Compressor suction port service valves.
NON-FUSED MAIN DISCONNECT SWITCHES: De-energize power supply during servicing/repair works as well as withdoor interlock.
CONDENSER COIL GUARD:Protects the condenser coils from physical damage.
COMPRESSOR/COOLER GUARD:Protects the compressor from vandalism.
COMPRESSOR OIL LEVEL SWITCH: This monitors the oil level inside the compressor.
COMPRESSOR ENCLOSURE BOX: Reduces compressor operating noise and keeps the compressor clean.
FLANGED COOLER CONNECTION: Easy on-site piping connections.
COOLER HEATER WRAPPED: Prevents freezing up of water on low ambient temperature.
COPPER FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments. Provided with 12 FPI as standard
COATED COPPER FINS/TUBES CONDENSER COILS: For seashore or acid corrosive environments.
BMS: BACNET-IP, MODBUS-RS485, GSM and stand alone remote display panel.
POWER LINE ANALYZER: Performs motor current limitation. Protects against high motor current & over/under voltage.
: A two component coating system that withstands the extreme climate conditions. The coating can be
applied to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre- treatmentand layer build up. Please check ResisTec product informationsheets, the heat exchangers can not be coated using thistype. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance or rejuvenation
purposes.
UL LISTED CHILLERS: ASY chillers in the range of ASY050B thru ASY500B can be optionally offered as UL listed. These
chillers are UL listed under UL file number SA13167.
HAND HELD CONTROLLER: Enables the chiller technician to monitor and serve the chiller by plugging this portable wiredcontroller into the chiller controller. With built-in magnets, it provides convenient access for chiller status diagnoses and
trouble shooting.
EXTERNAL COMPRESSOR MOTOR OVERLOAD RELAY:Added protection for compressor motor thermal overloadingand prolonged stalling of the motor.
DUAL MAIN POWER ENTRY: Provide flexibility of connecting the chiller to the field power supply. Applicable for chille
models ASY090B - ASY500B.
EXTENDED MAIN BUSBAR: Provide extended termination for multi cable that may require for chiller with Single poweEntry point. This is applicable only for ASY180B - ASY590B.
MAIN POWER TERMINAL LUGS: A ready to install power main terminal lugs for easy connection of main cable in thefield. The lug has wide range to accept cable sizes and designed to fix a maximum of 4 cables per lug.
5/19/2018 ASY(R-134)Series Screw Chiller
9/51
7
MICROPROCESSOR CONTROLLERThe microprocessor controller works on the state of art microprocessor technology. This standalone controller monitorsanalog and digital inputs to achieve precise control and safety functions of the unit.
The Software works on the Proportional Integral Derivative (PID) algorithm for precise control logic. Also it has with built-inAdaptive control logic that prevents unnecessary service call, while the controller manage to operate the chiller at safe and
designed operating limits.The simple to use push button keyboard allows accessing to the operating conditions, control set points and alarm history
that are clearly displayed on a multi-line back illuminated LCD panel.
An easy to install serial port/modem optionallows remote monitoring of the operating parameters. With correspondingwindows software, the system allows data to be viewed in tabular or graphic format as well as interact with system set up
This chiller controller is compatible with the Building Management System (BMS) BACNET/MODBUS protocols throughcorresponding optional gateway interfaces.
It is also compatible with GSM protocol through GSM optional gateway that sends up to 3 mobile phone SMS messageswhenever alarm take place, indicating the type of alarm, the corresponding compressor, the related chiller and which location
The microprocessor consists of the following hardware:
1. User Interface Board: Provided with simple to use push button keyboard and menu driven software to access operatingconditions, control set points & alarm history that are clearly displayed on the LCD panel.
2. Main Board: This controls up to two (2) compressor system.3. Auxiliary Boards: Required for controlling an additional two (2) or more compressors.
4. Remote Monitoring System [Optional]: The micro controller is complete with all hardware and software necessary to
remotely monitor and control the chiller unit.
DISPLAY INFORMATION:
In the normal operating mode the 20 x 4 characters LCD panel display the system status, the temperature of the water inlet
& outlet, the set point, run time of the compressor & the alarm history.
Easily accessible measurements for each circuit include the following:
Suction and discharge temperatures
Suction and discharge pressures
Water inlet/outlet temperatures
Compressor status
Fan status
Liquid line solenoid status
Unit/Compressor run time
Compressor amps (optional)
Unit amps (optional)
Unit 3 phase voltage (optional)The control temperature is continuously displayed on the 3 Digit 7 segments LED Display. The 3 LED lights indicate thePower ON, Menu adjustment and Fault.
SYSTEM PROTECTION:
The following system protection is provided to ensure system reliability:
Compressor winding overheating
Low suction pressure
High discharge pressure
Freeze protection
Low oil level (optional)
Sensor error/Thermistor malfunction
Time delay Anti recycle time for compressor
Serial communication error
Compressor/fan motor overload
Compressor/fan motor circuit breaker
Compressor reverse rotation
Under/over voltage
Low/high superheat
5/19/2018 ASY(R-134)Series Screw Chiller
10/51
8
UNIT SIZE ASY050B ASY060B ASY070B ASY080B ASY090B ASY100B ASY120B ASY130B ASY140B ASY15
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-13 800-683-16 800-683-19 800-683-22 800-683-13 (2) 800-683-13 (2) 800-683-16 (2) 800-683-19 (2) 800-683-19 (2) 800-683-1
380V-3Ph-60Hz 800-683-14 800-683-17 800-683-20 800-683-23 800-683-14 (2) 800-683-14 (2) 800-683-17 (2) 800-683-20 (2) 800-683-20 (2) 800-683-2
460V-3Ph-60Hz 800-683-15 800-683-18 800-683-21 800-683-24 800-683-15 (2) 800-683-15 (2) 800-683-18 (2) 800-683-21 (2) 800-683-21 (2) 800-683-2
NUMBER OF COMPRESSORS 1 1 1 1 2 2 2 2 2 2
OIL CHARGE PER COMPRESSOR, Liters 15 22 22 22 15 15 22 22 22 22
CAPACITY CONTROL (STEPLESS) % 100 - 50 100 - 25
MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC
OIL LUBRICATION INJECTION
TOTAL CRANKCASE HEATER WATTS 200 300 300 300 400 400 600 600 600 600
REFRIGERANT R-134a
EXPANSION DEVICE ELECTRONIC EXPANSION VALVE
CONTROL VOLTAGE 220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8214 3/8314 3/8414 3/8414 3/8414 3/8414 3/8314 3/8414 3/8414 3/83
COILTotal face area, Sq. ft. 87.5 87.5 87.5 87.5 100.1 100.1 140 140 140 175
AIRFLOW, CFM 45264 43920 47644 47644 63798 63798 93256 87032 87032 11657
NUMBER OF FAN/FAN DIA.,mm 4/762 4/762 4/800 4/800 6/800 6/800 8/800 8/800 8/800 10/80
FAN MOTOR RPM @ 230/380/460-3-60 1100/1100/1100 1100/1100/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/11001080/1080
COOLER
COOLER PART NUMBER 800-893-00 800-893-01 800-893-01 800-893-01 800-893-02 800-893-02 800-893-03 800-893-04 800-893-04 800-893
SHELL DIAMETER, mm 219 273 273 273 324 324 324 324 324 406
TOTAL LENGTH, mm 2314 2152 2152 2152 2496 2496 2696 2677 2677 2739
WATER HOLDING VOLUME, Liters 49 76.5 76.5 76.5 120 120 128 117 117 206
WATER IN/OUT PIPE DIA.mm 75 100 100 100 125 125 125 125 125 150
ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. 800-516-68(2) N.A. N.A. 800-516-69(2) 800-516-6
EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. T.E.V. N.A. N.A. T.E.V. T.E.V
GENERAL
NUMBER OF REFRIGERANT CIRCUITS 1 1 1 1 2 2 2 2 2 2
REFRIGERANT CHARGE PER COMP., kg 33 39 45 50 33 33 39 45 47 48
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.)72.2/68.7/63.4 72.6/69.1/63.8 75.4/71.9/66.6 75.6/72.1/66.8 74.4/71/65.7 74.5/71/65.7 75.3/71.8/66.5 78.4/74.9/69.6 78.4/74.9/69.6 78.7/75.2/
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 1865/1914 2336/2412 2455/2531 2472/2548 3220/3340 3233/3353 4319/4447 4468/4585 4494/4611 4998/52
SHIPPING /OPERATING WEIGHTS (Copper coils), kg 1990/2039 2529/2605 2735/2811 2751/2827 3540/3660 3553/3673 4627/4755 4914/5031 4941/5058 5383/55
PHYSICAL DATA
NOTES: 1. All compressors with slider control valve unloading.2. All compressors operate at 3500 RPM @ 60Hz.3. Cooler vent and drain size are 1/2" MPT.4. All coolers are single face refrigerant connection.5. Sound pressure level : 2dBA.* CU/CU option has 12FPI.
5/19/2018 ASY(R-134)Series Screw Chiller
11/51
9
UNIT SIZE ASY160B ASY170B ASY180B ASY190B ASY200B ASY215B ASY230B ASY240B ASY250B ASY27
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-22 (2) 800-683-22 (2) 800-683-16 (3) 800-683-16 (3) 800-683-16 (3) 800-683-22 (3) 800-683-22 (3) 800-683-16 (4) 800-683-1
380V-3Ph-60Hz 800-683-23 (2) 800-683-23 (2) 800-683-17 (3) 800-683-17 (3) 800-683-17 (3) 800-683-23 (3) 800-683-23 (3) 800-683-17 (4) 800-683-2
460V-3Ph-60Hz 800-683-24 (2) 800-683-24 (2) 800-683-18 (3) 800-683-18 (3) 800-683-18 (3) 800-683-24 (3) 800-683-24 (3) 800-683-18 (4) 800-683-2
NUMBER OF COMPRESSORS 2 2 3 3 3 3 3 3 4 4
OIL CHARGE PER COMPRESSOR, Liters 22 22 22 22 22 22 22 22 22 22
CAPACITY CONTROL (STEPLESS) % 100 - 25 100 - 16 100 - 12
MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC
OIL LUBRICATION INJECTION
TOTAL CRANKCASE HEATER WATTS 600 600 900 900 900 900 900 900 1200 1200
REFRIGERANT R-134a
EXPANSION DEVICE ELECTRONIC EXPANSION VALVE
CONTROL VOLTAGE 220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8314 3/8414 3/8314 3/8414 3/8414 3/8414 3/8314 3/83
COILTotal face area, Sq. ft. 175 175 210 210 210 240 240 240 304 304
AIRFLOW, CFM 116570 108790 139884 133524 130548 140892 138276 138276 192048 19204
NUMBER OF FAN/FAN DIA.,mm 10/800 10/800 12/800 12/800 12/800 12/800 12/800 12/800 16/800 16/80
FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/11001080/1080
COOLER
COOLER PART NUMBER 800-893-05 800-893-05 800-893-06 800-893-06 800-893-06 800-893-07 800-893-08 800-893-08 800-893-04(2) 800-893-0
SHELL DIAMETER, mm 406 406 406 406 406 406 406 406 324 406
TOTAL LENGTH, mm 2739 2739 2749 2749 2749 3241 3741 3741 2677 2739
WATER HOLDING VOLUME, Liters 206 206 190 190 190 225 260 260 234 412
WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 150 125 150
ECONOMIZER
PART NUMBER N.A. 800-516-69(2) N.A. 800-516-69(2) 800-516-69(3) N.A. 800-516-69 800-516-69(3) N.A. N.A
EXPANSION DEVICE N.A. T.E.V. N.A. T.E.V. T.E.V. N.A. T.E.V. T.E.V. N.A. N.A
GENERAL
NUMBER OF REFRIGERANT CIRCUITS 2 2 3 3 3 3 3 3 4 4
REFRIGERANT CHARGE PER COMP., kg 50 54 39 42/39 42 50/45 54/50 54 39 45
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.)78.9/75.4/70.1 78.9/75.4/70.1 77.1/73.6/68.3 77.1/73.6/68.3 77.1/73.6/68.3 80.3/76.8/71.5 80.4/76.9/71.6 80.4/76.9/71.6 81.4/77.9/72.6 81.4/77.9/
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 5003/5209 5149/5355 6542/6732 6663/6853 6724/6914 6885/7110 7040/7300 7070/7330 8745/8979 9208/96
SHIPPING /OPERATING WEIGHTS (Copper coils), kg 5388/5594 5708/5914 7004/7194 7264/7454 7393/7583 7572/7797 7805/8065 7836/8096 9414/9648 9876/102
PHYSICAL DATA
NOTES: 1. All compressors with slider control valve unloading.2. All compressors operate at 3500 RPM @ 60Hz.3. Cooler vent and drain size are 1/2" MPT.4. All coolers are single face refrigerant connection.5. Sound pressure level : 2dBA.* CU/CU option has 12FPI.
3/84143/8314
3/84143/8314
800-683-22 (2)800-683-19 (1)
800-683-23 (2)800-683-20 (1)
800-683-24 (2)800-683-21 (1)
5/19/2018 ASY(R-134)Series Screw Chiller
12/51
10
UNIT SIZE ASY295B ASY310B ASY330B ASY350B ASY375B ASY400B ASY420B ASY450B ASY475B ASY50
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-22 (4) 800-683-16 (6) 800-683-19 (6) 800-683-19 (6) 800-683-22 (6) 800-683-
380V-3Ph-60Hz 800-683-23 (4) 800-683-17 (6) 800-683-20 (6) 800-683-20 (6) 800-683-23 (6) 800-683-
460V-3Ph-60Hz 800-683-24 (4) 800-683-18 (6) 800-683-21 (6) 800-683-21 (6) 800-683-24 (6) 800-683-
NUMBER OF COMPRESSORS 4 4 6 6 6 6 6 6 6 6
OIL CHARGE PER COMPRESSOR, Liters 22 22 22/15 22 22 22 22 22 22 22
CAPACITY CONTROL (STEPLESS) % 100 - 12 100 - 8
MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC
OIL LUBRICATION INJECTION
TOTAL CRANKCASE HEATER WATTS 1200 1200 1600 1800 1800 1800 1800 1800 1800 180
REFRIGERANT R-134a
EXPANSION DEVICE ELECTRONIC EXPANSION VALVE
CONTROL VOLTAGE 220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8414 3/8414 3/8414 3/8414 3/8314 3/8414 3/8414 3/84
COILTotal face area, Sq. ft. 304 304 430.7 430.7 430.7 521.3 521.3 521.3 521.3 521.
AIRFLOW, CFM 180560 180560 224046 220770 220770 281490 275110 269038 269038 2690
NUMBER OF FAN/FAN DIA.,mm 16/800 16/800 18/800 18/800 18/800 22/800 22/800 22/800 22/800 22/80
FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080
COOLER
COOLER PART NUMBER 800-893-05(2) 800-893-05(2) 800-893-09(2) 800-893-09(2) 800-893-06(2) 800-893-06(2) 800-893-06(2) 800-893-10(2) 800-893-10(2) 800-893-
SHELL DIAMETER, mm 406 406 406 406 406 406 406 457 457 457
TOTAL LENGTH, mm 2739 2739 2741 2741 2749 2749 2749 2754 2754 275
WATER HOLDING VOLUME, Liters 412 412 412 412 380 380 380 488 488 488
WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 200 200 200
ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. 800-516-69(3) 800-516-
EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. T.E.V. T.E.V
GENERAL
NUMBER OF REFRIGERANT CIRCUITS 4 4 6 6 6 6 6 6 6 6
REFRIGERANT CHARGE PER COMP., kg 50/45 50 39/33 39 45 47 50/45 50/45 54/50 54
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 81.5/78/72.7 81.6/78.1/72.8 79.4/75.8/70.6 79.4/75.9/70.6 82.9/79.3/74.1 83.1/79.5/74.3 83.2/79.7/74.4 83.2/79.7/74.4 83.3/79.8/74.5 83.3/79.8
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 9441/9853 9474/9886 11809/12221 12668/13080 12808/13188 13039/13419 13248/13628 13777/14265 13856/14344 13902/14
SHIPPING /OPERATING WEIGHTS (Copper coils), kg 10441/10823 10444/10856 13021/13433 14042/14454 14182/14562 14186/14566 14654/15034 15439/15927 15518/16006 15564/16
PHYSICAL DATA
NOTES: 1. All compressors with slider control valve unloading.2. All compressors operate at 3500 RPM @ 60Hz.3. Cooler vent and drain size are 1/2" MPT.4. All coolers are single face refrigerant connection.5. Sound pressure level : 2dBA.* CU/CU option has 12FPI.
3/84143/8314
3/84143/8314
800-683-22 (2)800-683-19 (2)
800-683-23 (2)800-683-20 (2)
800-683-24 (2)800-683-21 (2)
800-683-16 (4)800-683-13 (2)
800-683-17 (4)800-683-14 (2)
800-683-18 (4)800-683-15 (2)
800-683-22 (3)800-683-19 (3)
800-683-23 (3)800-683-20 (3)
800-683-24 (3)800-683-21 (3)
800-683-22 (4)800-683-19 (2)
800-683-23 (4)800-683-20 (2)
800-683-24 (4)800-683-21 (2)
5/19/2018 ASY(R-134)Series Screw Chiller
13/51
11
UNIT SIZE ASY540B ASY560B ASY590B
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-19 (8)
380V-3Ph-60Hz 800-683-20 (8)
460V-3Ph-60Hz 800-683-21 (8)
NUMBER OF COMPRESSORS 8 8 8
OIL CHARGE PER COMPRESSOR, Liters 22 22 22
CAPACITY CONTROL (STEPLESS) % 100 - 6
MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC
OIL LUBRICATION INJECTION
TOTAL CRANKCASE HEATER WATTS 1800 1800 1800
REFRIGERANT R-134a
EXPANSION DEVICE ELECTRONIC EXPANSION VALVE
CONTROL VOLTAGE 220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8414 3/8414 3/8414
COILTotal face area, Sq. ft. 608 608 608
AIRFLOW, CFM 361120 361120 361120
NUMBER OF FAN/FAN DIA.,mm 32/800 32/800 32/800
FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100
COOLER
COOLER PART NUMBER 800-893-41(2) 800-893-41(2) 800-893-41(2)
SHELL DIAMETER, mm 508 508 508
TOTAL LENGTH, mm 3326 3326 3326
WATER HOLDING VOLUME, Liters 802 802 802
WATER IN/OUT PIPE DIA.mm 200 200 200
ECONOMIZER
PART NUMBER N.A. N.A. N.A.
EXPANSION DEVICE N.A. N.A. N.A.
GENERAL
NUMBER OF REFRIGERANT CIRCUITS 8 8 8
REFRIGERANT CHARGE PER COMP., kg 45/39 45 50/45
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 83.6/80.1/74.8 84.4/80.9/75.6 84.6/81/75.8
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 2 x 9355/2 x 9756 2 x 9390/2 x 9791 2 x 9423/2 x 9824
SHIPPING /OPERATING WEIGHTS (Copper coils), kg 2 x 10325/2 x 10726 2 x 10360/2 x 10761 2 x 10393/2 x 10794
PHYSICAL DATA
NOTES: 1. All compressors with slider control valve unloading.2. All compressors operate at 3500 RPM @ 60Hz.3. Cooler vent and drain size are 1/2" MPT.4. All coolers are single face refrigerant connection.5. Sound pressure level : 2dBA.* CU/CU option has 12FPI.
800-683-19 (4)800-683-16 (4)
800-683-22 (4)800-683-19 (4)
800-683-20 (4)800-683-17 (4)
800-683-21 (4)800-683-18 (4)
800-683-23 (4)800-683-20 (4)
800-683-24 (4)800-683-21 (4)
5/19/2018 ASY(R-134)Series Screw Chiller
14/51
12
DESIGN REQUIREMENTS
The following design requirements must be known to select a package chiller.1. Required cooling capacity in tons
2. Leaving chilled water temperature in 0F (LCWT)3. Chilled water flow rate in GPM
4. Chilled water cooling range in 0F (water in temp. _water out temp.)5. Design ambient temperature6. Minimum ambient temperature
7. Altitude8. Electrical power supply
SAMPLE SELECTION
Select an Air Cooled Packaged chiller for the following conditions:
Required system capacity is 115 tons at 540F entering chilled waterand 440F leaving water. Design ambient temperature is 95 0F.
Altitude is 2000 feet above sea level.Water cooler fouling factor is 0.00010. Power supply: 380V-3Ph-60Hz.
STEP-1:UNIT SELECTIONEntering the capacity performance data at given LCWT and ambient temperature.
ASY120B chiller unit at sea level will produce 116.5 tons and 129.3 kW compressorpower input at 440F leaving chilled water temperature with 100F water temperature
difference and 950F ambient temperature.
For the conditions required, the unit actual cooling capacity when corrected for
altitude (0.99) and fouling factor (1.0).Capacity = 116.5x0.99x1.0 = 115.3 Tons, which then exceeds the requirements.
So the selection is correct.
STEP-2: CHILLED WATER FLOW (GPM):
Water GPM =
Required capacity (Tons) x 24
=
115 x 24
= 276 GPM Cooling Range, T 10
0F
SELECTION PROCEDURE (English units)
ELEVATION ABOVE
SEA LEVEL (FT.)
CAPACITY
CORRECTION
FACTOR
0
2000
4000
6000
8000
10000
1.00
0.99
0.98
0.97
0.96
0.95
TABLE - 2
EVAPORATOR FOULING
FACTOR (HR-FT2-0F/BTU)
0.00010
0.00025
0.00050
0.00075
0.00100
CAPACITY
CORRECTION
FACTOR
1.000
0.992
0.978
0.965
0.951
POWER
INPUT
FACTOR
1.000
0.997
0.990
0.984
0.978
ARI
STANDARDS
ARI-550/590
Referring to pressure drop chart (page # 23), pressure drop at 276 GPM = 13.5 ft. of water for selected model.
NOTE:The total flow rate should be divided by 2 for models ASY250B - ASY590B to find out the total pressure drop.
STEP-3:ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuit
ampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.
STEP-4:CHILLED WATER PUMP SELECTION
For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop calcu-lated in step 2.
STEP-5: LCWT CORRECTION
Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water temperaturerange is above 100F and subtract correction from design leaving chilled water temperature (LCWT) when water temperature
range is below 100F.
EXAMPLE:
If LCWT rise is 12.50F, enter correction curve at 12.50F and read the correction factor of 0.2. The corrected LCWT is 44+0.2 = 44.20F
NOTE: 1. When the chilled water temperature rise is less than 50F, the high water flow rate will result to excessive pressure
drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.2. Please refer to water pressure drop curves.
TABLE - 1
TABLE - 3
CHILLED WATER TEMPERATURE RISE (0F)
CORRECTIONFACTOR(0F)
0
-0.2
-0.45 10
+0.4
+0.2
+0.6
15 2
5/19/2018 ASY(R-134)Series Screw Chiller
15/51
DESIGN REQUIREMENTS
The following design requirements must be known to select a proper package chiller.1. Required cooling capacity in kilowatt (kW)
2. Leaving chilled water temperature in 0C (LCWT)3. Chilled water flow rate in LPS
4. Chilled water cooling range in 0C (water in temp. _water out temp.)5. Design ambient temperature6. Minimum ambient temperature
7. Altitude8. Electrical power supply
SAMPLE SELECTION
Select an Air Cooled Packaged chiller for the following conditions:
Required system capacity is 390 kW at 120C entering chilled water
and 60C leaving water. Design ambient temperature is 350C.
Altitude is 600 meter above sea level.Water cooler fouling factor is 0.000018. Power supply: 380V-3Ph-60Hz.
STEP-1:UNIT SELECTIONEntering the capacity performance data at given LCWT and ambient temperature.
ASY120B chiller unit at sea level will produce 408.1 kW and 129.1 kW compressorpower input at 60C leaving chilled water temperature with 60C water temperature
difference and 350C ambient temperature.
For the conditions required, the unit actual cooling capacity when corrected for
altitude (0.99) and fouling factor (1.0).Capacity = 408.1x0.99X1.0 = 404 kW, which then exceeds the requirements.
So the selection is correct.
STEP-2: CHILLED WATER FLOW (LPS):
Water LPS =
Required capacity (kW) x 0.239
=
390 x 0.239
= 15.5 LPS Cooling Range, T 6
0C
SELECTION PROCEDURE (Metric units)
ELEVATION ABOVE
SEA LEVEL (Meter)
CAPACITY
CORRECTION
FACTOR
0
600
1200
1800
2400
3000
1.00
0.99
0.98
0.97
0.96
0.95
Referring to pressure drop chart (page # 23), pressure drop at 15.5 LPS = 34.4 kPa for selected model.
NOTE:The total flow rate should be divided by 2 for models ASY250B - ASY590B to find out the total pressure drop.
STEP-3:ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuitampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.
STEP-4:CHILLED WATER PUMP SELECTION
For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure dropcalculated in step 2.
STEP-5: LCWT CORRECTION
Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water tempera-ture range is above 60C and subtract correction from design leaving chilled water temperature (LCWT) when watertemperature range is below 60C.
EXAMPLE:If LCWT rise is 7.40C, enter correction curve at 7.40C and read the correction factor of 0.11. The corrected LCWT is 60C+0.11 = 6.110C
NOTE: 1. When the chilled water temperature rise is less than 30C, the high water flow rate will result to excessive pressure
drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.2. Please refer to water pressure drop curves.
TABLE - 2
EVAPORATOR FOULING
FACTOR (M2-0C/W)
0.000018
0.000044
0.000088
0.000132
0.000176
CAPACITY
CORRECTION
FACTOR
1.000
0.992
0.978
0.965
0.951
POWER
INPUT
FACTOR
1.000
0.997
0.990
0.984
0.978
ARI
STANDARDS
ARI-550/590
TABLE - 1
TABLE - 3
CHILLED WATER TEMPERATURE RISE (0C)
CORRECTIONFACTOR(0C)
+0.33
+0.22
+0.11
-0.11
-0.2254 6 7 8
0
109
13
5/19/2018 ASY(R-134)Series Screw Chiller
16/51
5/19/2018 ASY(R-134)Series Screw Chiller
17/51
5/19/2018 ASY(R-134)Series Screw Chiller
18/51
5/19/2018 ASY(R-134)Series Screw Chiller
19/51
5/19/2018 ASY(R-134)Series Screw Chiller
20/51
5/19/2018 ASY(R-134)Series Screw Chiller
21/51
5/19/2018 ASY(R-134)Series Screw Chiller
22/51
5/19/2018 ASY(R-134)Series Screw Chiller
23/51
5/19/2018 ASY(R-134)Series Screw Chiller
24/51
5/19/2018 ASY(R-134)Series Screw Chiller
25/51
23
WATER SIDE PRESSURE DROP
CURVE No. Maximum GPMMODEL No.
ASY050B
ASY060B
ASY070B
ASY080B
ASY090B
ASY100B
ASY120B
ASY130B
ASY140B
ASY150B
ASY160B
ASY170B
ASY180B
ASY190B
ASY200B
ASY215B
1
2
2
2
3
3
4
5
5
6
6
6
7
7
7
8
138
170
192
214
265
271
325
356
372
411
437
455
498
522
534
593
Minimum GPM
82
98
108
124
164
184
203
222
251
267
272
315
301
343
365
375
CONVERSION FACTOR: GPM = 0.063 Liters per second.
Feet of water = 2.989 Kilo Pascal (kpa).
NOTE: 1. If an application requires certain water flow rate outside these limits, please check with your nearest dealer/sales office.2. If the chiller has 2 evaporators, then the total water flow must be divided by 2 while applying the above curves (applicable for models
ASY250B - ASY590B.
CURVE No. Maximum GPMMODEL No.
ASY230B
ASY240B
ASY250B
ASY270B
ASY295B
ASY310B
ASY330B
ASY350B
ASY375B
ASY400B
ASY420B
ASY450B
ASY475B
ASY500B
ASY540B
ASY560B
ASY590B
8
8
5
6
6
6
6
6
77
7
9
9
9
10
10
10
620
633
708
768
826
866
925
971
1048
1095
1164
1242
1297
1332
1514
1577
1662
Minimum GPM
412
447
425
450
502
537
572
601
634
650
710
779
866
886
896
924
995
PRESSUREDROP(F
T.OFWATER)
110 20
2
3
4
8
6
5
7
910
60
30
20
50
40
70
100
9
0
80
200
FLOW RATE - GPM604030 50 9070 80 100 300200 400 500 600 15001000800700 900 1200
1 2 3 4 5 6
7
9
8
10
5/19/2018 ASY(R-134)Series Screw Chiller
26/51
RECOMMENDED INSTALLATIONLEAVING/RETURN WATER TEMPERATURE SENSOR & WATER FLOW SWITCH
24
NOTE: 1. For chiller with 2 coolers, leaving water temperature sensor and return water temperature sensor should be installed in the water pipingmain header of every chiller.
2. Water flow switch should be installed vertically on the horizontal pipe line closed to the leaving water port of every cooler.
OUTININ OUT
CHILLER # 1
CONTROL PANEL
COOLER 1 COOLER 2
CHILLER # 2
CHILLER # n
LEAVINGWATER
RETURNWATER
LWTLEAVING WATER SENSOR
(FIELD INSTALLATION]
FLS2
(FIELD INSTALLATION]
FLS1
(FIELD INSTALLATION]
RWT
RETURN WATER SENSOR(FIELD INSTALLATION]
FS
FS
LWT
RWT
> or