SOCOMEC general catalogue A. 134 ATyS APPLICATIONS atys_029_a_1_cat atys_030_a_1_cat atys_031_a_2_cat atys_003_a_1_cat 1 ATyS 3s ATyS 3e 125 to 1 600 A 125 to 1 600 A Normal / backup transfer with an external automatic control Normal / backup transfer with an internal automatic control (ATS) (IEC 60947-6-1) Load changeover External control FUNCTIONS AUXILIARY POWER SUPPLY Version 1 AC power supply Version 2 AC power supplies OPERATION By free auxiliary contacts for the I, 0, II positions Automatic for the I, 0, II positions Key-type / AUT selector switch MONITORING Main network: 3U, loss of one phase, phase sequence Main network: frequency Emergency network: 1U Emergency network: frequency Emergency network: 3U, loss of one phase, phase sequence CONFIGURATION Choice of logic: contactor or impulse Upper and lower thresholds, associated hysteresis Operating time delays Network priority FRONT DISPLAY Leds: status of supplies, positions, commands, faults, padlocking U F 3I, P, Q, S, PF, In monitored CONTROL/OPERATION Position I and II auxiliary contacts Position 0 auxiliary contacts Padlock and / AUT information auxiliary contacts Generator start-up command Fault relay output contact COM RS485 (JBUS MODBUS ® ) - option 2 inputs / 2 outputs - option REMOTE CONTROL INTERFACES ATyS D10 (visualisation) ATyS D20 (visualisation and control) see page see page PAGES A.140 A.140 Changeover switches SELECTION GUIDE Power Command Load M Example: between a transformer and a genset ATyS_gb.qxd 24/02/05 16:45 Page 134
Transcript
Page 1: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

SOCOMEC general catalogueA. 134

ATySA P P L I C A T I O N S

atys

_029

_a_1

_cat

atys

_030

_a_1

_cat

atys

_031

_a_2

_cat

atys

_003

_a_1

_cat

1ATyS 3s ATyS 3e

125 to 1600 A 125 to 1600 A

Normal /backup transfer • •with an external automatic controlNormal /backup transferwith an internal automatic control (ATS) (IEC 60947-6-1)

Load changeover • •External control

F U N C T I O N SAUXILIARY POWER SUPPLY

Version 1 AC power supply •Version 2 AC power supplies •

OPERATION

By free auxiliary contacts for the I, 0, II positions • •Automatic for the I, 0, II positions

Key-type /AUT selector switch •

MONITORING

Main network: 3U, loss of one phase, phase sequence

Main network: frequency

Emergency network: 1U

Emergency network: frequency

Emergency network: 3U, loss of one phase, phase sequence

CONFIGURATION

Choice of logic: contactor or impulse • •Upper and lower thresholds, associated hysteresis

Operating time delays

Network priority

FRONT DISPLAY

Leds: status of supplies, positions, commands, faults, padlocking •U

F

3I, P, Q, S, PF, In monitored

CONTROL/OPERATION

Position I and II auxiliary contacts • •Position 0 auxiliary contacts •Padlock and /AUT information auxiliary contacts •Generator start-up command

Fault relay output contact •COM RS485 (JBUS MODBUS®) - option •2 inputs /2 outputs - option •

REMOTE CONTROL INTERFACES

ATyS D10 (visualisation)

ATyS D20 (visualisation and control)

see page see page

P A G E S A.140 A.140

Changeover switches

SELECTION GUIDE

Power

Command

Load

M

Example: between atransformer and a genset

ATyS_gb.qxd 24/02/05 16:45 Page 134

Page 2: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

SOCOMEC general catalogue A. 135

Changeover switches

SELECTION GUIDE

see page

A.148

atys

_016

_a_1

_cat

Optional modules

atys

_012

_a_2

_cat

Voltage sensing and power supply kit

Bridging bars

atys

_031

_a_2

_cat

atys

_032

_a_1

_cat

atys

_033

_a_1

_cat

atys

_097

_a_1

_cat

see page

A.150

Remote control interfaces

ATyS D10 ATyS D20

atys

_148

_a_2

_cat

atys

_145

_b_1

_x_c

at

atys

_150

_b_1

_x_c

at

ATyS 6s ATyS 6e ATyS 6m Pilote125 to 1600 A 125 to 1600 A 125 to 1600 A ATyS C30

• • •

• • • •

• •

• • •

• •

• • • •

• • •

• •

• • •

• •

• • •

• • • •

• • • •

• • •

• • •

• • •

• •

• • •

• • •

• •

• • • •

• •

• •

• • • (std)

• • •

• • •

see page see page see page see page

A.144 A.144 A.144 A.151

acce

s_04

0_a_

2_ca

t

ATyS_gb.qxd 24/02/05 16:45 Page 135

Page 3: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 136

The ATyS rangeATyS 3ATyS 6ATyS 3 and 6 accessoriesPilote ATyS C30SMVE & SMVSOther motorised changeoverswitches

Changeover switches

The ATyS range

SOCOMEC general catalogue

Description

Manual operation

The ATyS range of products integrates electrical and mechanicalinterlocking systems in order to guarantee safe transfer operation.All the products are fitted with manual operation.Electrical operation is achived by an electronicaly drivenmotorised module:• either remotely controlled: ATyS 3 products are driven by volt-

free dry contacts allowing switching operation between positionI, 0 or II, from an external control logic (control relays type PiloteATyS C30).

• or automaticaly controlled: ATyS 6 products include controlrelays, timers and test functions to manage a Normal /Backupswitching operation.

Most of ATyS 3 functionalities are included in ATyS 6 versions.Position information as well as source availability andvoltage/frequency information are displayed directly on the product.The control unit (motorised and electronic modules) can beremoved for preventive maintenance purposes withoutdisconnection of the power unit and whilst keeping the backupmanual control operational !

Electrical control (remote control)

Power supply

• Standard voltages: 230 VAC, 50/60 Hz.Other voltages on request: 12, 24, 48 and 110 VDC.

• Voltage tolerances: ± 20 % on the AC versions.• Consumption: according to the rating of the device (cf. electrical

specifications).• AC versions of the ATyS 3e, 6s, 6e and 6m are equipped with two

power sources: one defined as power source and one asbackup power source .2

1

Simplified diagram

AUT position

priority power source

backup power source

switching operation possibility

1

2

svrm

o_07

7_c_

1_gb

_cat

Padlocking

Up to three padlocks can be usedto lock the device.When padlocked:• manual operation is not possible,• electrical controls are disabled.Padlocking in the 3 positions: I, 0an II, in option.

atys

_008

_a_1

_cat

Auxiliary Contacts (ACs)

• ATyS 3s is fitted with factory mounted NO/NC pre-breakingcontacts for positions I and II. ATyS 3e and 6s are fitted with NOsignalling contacts for positions I, 0, II

• ATyS 3e, 6e and 6m also offer NO contacts: an auxiliary contactto inform of the position of the “AUT” selector switch, and anauxiliary contact to signal the use of the device’s locking

• Each product can be supplied, with an optional NO/NCpre-breaking contact for the extra positions I and II.

Specifications

Voltage (V) 24 48 110/127 220/240 320/440 480Rated operational current (A) - IEC 947.5.1 (6000 cycles)

AC-12 5 5 5 5 5 5

AC-13 4 4 3 2.5 2 1.5

AC-14 max. 72 VA

AC-15 4 4 3 2.5 2 1.5

DC-12 5 2 0.6 0.4

DC-13 3 1 0.3 0.15

DC-14 0.6 0.15 0.04 0.02

General features

Back up manual operation

The product can still be switchedwithout any power source usingthe manual operation.The handle allows direct operationof the changeover shaft.The switch cannot be manuallyoperated in automatic mode(AUT) or padlocked.

atys

_013

_a_1

_cat

ATyS_gb.qxd 24/02/05 16:45 Page 136

Page 4: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 137

Changeover switches

The ATyS range

SOCOMEC general catalogue

ATyS 3s simplified wiring diagram

ATyS 3e complementary features

ATyS 3e complementary features

General

• The switching operation can be driven by an external drycontact. “Pulsed contact logic” (impulse) or “maintained contactlogic” (contactor), are both recognised on the control inputs.

• The type of logic must be selected during configuration(programming).

• Switching time: see electrical specifications.• It is possible to inhibit electrical switching commands using a dry

contact (not on ATyS 3s).• Priority: the first order received has priority as long as it is

present. A zero command is always priority, excepted in case ofcontrols inhibition.

Impulse logic

• The switching command is a pulsed dry contact lasting at least30 ms.

• When the order disappears, the product remains in position.The impulse can be of infinite duration without causing anydisturbance.

power source

power source

1: control position 0

2: control position I

3: control position II

4: configuration of the control logic

5: NO/NC position and pre-breaking contact for position I

6: NO/NC position and pre-breaking contact for position II

2

1

• Front panel display (LEDs): switch position, power supply status,control mode active

• Number of operations display• Optional modules: an RS485 communication module and/or a

2 inputs /2 outputs module.• Parameters configuration using keypad.• Dual power sources operation: self powered from main and

backup supplies.• Fault relay output.

Contactor logic

• The transfer command is a maintained dry contact.• If command I or II disappears, the device returns to zero

position.• A 0 command drives the device into zero position, irrespective of

the status of the I and II commands.

command I

command O

command II

position I

position O

position II

svrm

o_07

9_b_

1_gb

_cat

command I

command O

command II

position I

position O

position II

atys

_024

_a_1

_gb_

cat

5 6

4 3 2 1

21

313 314 315 316 317 101 102

General features

ATyS 3 motorised switches

Control logic

atys

_025

_c_1

_x_c

at

5

6710 9 8

2 1

13 14 24 34 43 44 53 54

6463

102

202

201

101

317

316

315

313

314

11

4

3

21at

ys_0

94_c

_1_x

_cat

power source

power source

1: control position 0

2: control position I

3: control position II

4: inhibition of the control position

5: fault relays

6: auxiliary contact, closed when the switch is padlocked

7: auxiliary contact, closed when the switch is in “AUT” mode

8: auxiliary contact, closed when the switch is in position 0

9: auxiliary contact, closed when the switch is in position II

10: auxiliary contact, closed when the switch is in position I

11: slots for optional modules

2

1

ATyS_gb.qxd 24/02/05 16:45 Page 137

Page 5: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 138

The ATyS rangeATyS 3ATyS 6ATyS 3 and 6 accessoriesPilote ATyS C30SMVE & SMVSOther motorised changeoverswitches

Changeover switches

The ATyS range

SOCOMEC general catalogue

ATyS 6: Automatic Transfer Switches

The ATyS 6 is an automatic transfer equipment to be used inbackup power systems with interruption of the supply to the loadduring transfer.It integrates:- over/undervoltages, over/under frequencies, phase

sequence and phase failure control (depending on theversion),

- specified timers,• to start /stop a generator set,• to transfer the load from 1 source to the other.

These sources may be 2 transformers, or one transformer and agenerator set.

The product includes control modes such as “test on-load”, “testoff-load”, “switch position control” (transfer I, 0, II) and a “semi-automatic mode” requiring validation before re-transfering the loadto the main source.Due to its features and electrical characteristics, the ATyS 6range is IEC 60947-6-1 compliant.

General features

Operating principle

Control

• Overvoltage and overfrequency thresholds: from 102 % to120 % of the nominal value.

• Undervoltage and underfrequency thresholds: from 80 % to98 % of the nominal value.

• Overvoltage and overfrequency hysteresis: from 101 % to 119 %of the nominal value.

• Undervoltage and underfrequency hysteresis: from 81 % to99 % of the nominal value.

Metering

• 3U on network and on ATyS 6e and 6m.1U on network on ATyS 6s.

• Frequency on network and on ATyS 6e, 6m.• Timers on ATyS 6s, 6e, 6m.• 3I, In, P, Q, S, PF (3 phases) on ATyS 6m.Timers• MFT: Main (priority) source Failure Timer (0 to 60 s).• DTT: Delay to Transfer Timer (0 to 60 s). Controls the backup

source stability before transfer.• 0MF: Dead band stay in 0 position after Main (priority) source

Failure (0 to 20 s). It allows the load residual voltage to decreaseunder a non critical value before transfer to backup source(necessary in case of rotating loads).

• MRT: Main (priority) source Return Timer (0 to 30 mn). Controlsthe main’s availability before transferring back the load.

• 0MR: Dead band stay in 0 position after Main (priority) sourceReturn (0 to 20 s). It allows the load residual voltage to decreaseunder a non critical value before transfer to priority source(necessary in case of rotating loads).

• CDT: Cool Down Timer (0 to 10 mn) allows the generator setcooling down before stop operation (for generator application).

Outputs electrical characteristics

• “Generator start signal” output: NO, 5 A, AC1, 30 VDC and230 VAC, 4 mm2 wire (for generator application).

• “Fault relay” output: 5 A, AC1, 230 VAC.

21

2

21

Control modes

• Test on-load (load transfer): allows loss of main’s networksimulation. The complete automatic cycle is then followed.Can be activated from the keypad of the device or remotely froman external dry contact.

• Test off-load (without load transfer): allows a generator set startand stop operation.Can be activated from the keypad of the device.

• Control I, 0, II: allows the product to be driven into one of thepositions ; the automatic cycle is then no longer active.Can be activated from the keypad of the device’s front or usingand external dry contact (ATyS 6e and 6m versions).

• Semi automatic: when this mode is active, any transfer back tothe main network must be acknowledged on the keypad of theproduct.These modes must be selected during configuration (programming).

Other features

• A fault relay output (not on ATyS 6s): a dry contact closes in caseof product internal fault.

• Delay to Transfer Timer (DTT) can be set up to its maximumvalue to allow enough time for the synchronisation of severalgenerators. A specific input can be used to allow transfer.

• Upgrading of the device by means of optional modules: anRS485 communication module (JBUS/MODBUS), and/or“Network priority, status report” module (cf. accessories).

• Connection with the remote control interface ATyS D10 and D20 (noton ATyS 6s version).

Specifications

Network failure

Automatic mode (AUT)

Generator start

MFT

Network availability

Switch to position 0

Switch to position

Switch to position

Generator stop

Switch to position 0

Semi automatic mode

Network availability

DTT

0MFMRT

0MR

CDT

no

yes

Manualoperation

Network : priority power sourceNetwork : backup power source2

1

2

1

2 1

1

Example (generator application):

atys

_028

_b_1

_gb_

cat

ATyS_gb.qxd 24/02/05 16:45 Page 138

Page 6: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 139

Changeover switches

The ATyS range

SOCOMEC general catalogue

ATyS 6: Automatic Transfer Switches

Main accessories

ATyS 6 simplified wiring diagram

Optional modules for ATyS 3e, 6e, 6m

73210

209208

207206

205204

203202

20174

Pow

er 2

30 V

AC

2Pow

er 230 VAC

F1F2

13

5 6 7 8 9

1211

10

4

16

32

1

14

1

15

13 14 24 34 43 44 53 54

101

102

103

104

105

106

313

314

315

316

317

6364

RJ

Volta

ge s

ensin

gL1

L2L3

N

Voltage s

ensin

gL1

L2L3

N

17

1: control position 0

2: control position I

3: control position II

4: inhibition of the control inputs (0-I-II)

5: auxiliary contact, closed when theswitch is in position I

6: auxiliary contact, closed when theswitch is in position II

7: auxiliary contact, closed when theswitch is in position 0

8: auxiliary contact, closed when theswitch is in “AUT” mode

9: auxiliary contact, closed when theswitch is padlocked

10: gen-set start command

11: auxiliary power supply (foroptional modules control)

12: remote “test on-load” input

13: DTT inhibit input. Transferinitiated as soon as the input isclosed when DTT = max. value.

14: fault output

15: remote control interface

16: Current transformers

17: Slots for optional modules (onATyS 6e and 6m).

No. 1 - communication module:

RS485 2 or 3-wire link with JBUS/MODBUS protocol at a trans-mission speed up to 38400 bauds, half duplex.

No. 2

- 2 inputs/2 outputs module on the ATyS 3e:

This module is equipped with:

• an input to override the changeover position (control I, 0, II) toanother network if and only if it is present. When it disappears, theload is transferred back to the original network, considered ashaving priority.

• an input detecting the availability of the backup network.• an output allowing load shedding according to the position of

the product.• a fault output (NO contact) activated in case of product

malfunction.

- 2 inputs/2 outputs module on the ATyS 6e and 6m:

This module is equipped with:

• an input to allow remote manual retransfer.• an input selecting the network priority.• an input allowing to report on the front of the ATyS the status of

an external protective device.• an output to allow load shedding.• an output (NO contact) linked to source availability (closed

when available).• an output (NO contact) linked to source availability (closed

when available).2

1

Voltage sensing and power supply kit

Remote control interface

Allows voltage sensing and power supply connections through acontrolled routing of the conductors, in order to avoid the use ofspecific protection devices (fuse/mcb).

Enables operations, configurations and displays of all the functionsremotely.It can be connected to an ATyS 6e or 6m via an RJ 45 type link.When connected, all features available on the front of the productare inhibited. Maximum connection distance: 3 m.2 modeles:• ATyS D10 (visualisation).• ATyS D20 (visualisation and control).

atys

_026

_c_1

_x_c

at

atys

_011

_a_1

_cat

atys

_150

_b_1

_x_c

at

Aty

s_11

3_a_

1_ca

t

Some terminals are spécific to ATyS6e and 6m versions

ATyS_gb.qxd 24/02/05 16:45 Page 139

Page 7: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 140

FunctionsATyS 3 products are 3 and 4-pole switchesremotely controlled by volt freecontacts. They are a combination of twoload-break switches mounted back toback electrically and mechanicallyinterlocked.They provide switching, source inversionor changeover under load of two lowvoltage power circuits, as well as safetyisolation.Motorised unit can be replaced (sparepart) without disconnection of the powercables.For more information see page, A. 136.

Conformity to standards• IEC 60947-3• NF EN 60947-3• NBN EN 60947-3• BS EN 60947-3

General characteristics• 3 stable positions (I, 0, II).• AC-22 and AC-23 switching under load.• Isolation by fully visible breaking.• Electrical control by volt free dry

contacts.• Emergency manual operation• Padlocking in 0 position (I and II

optional).• 1 power supply for the ATyS 3s.• 2 power supplies for the ATyS 3e and

possibility to add optional modules suchas RS 485 communication port.

Available on request• Specific power supply.• Overlapping contacts (I, I + II, II).• 6 or 8- pole switches.• Different ratings between switches I and

II for high currents• By-pass switches.

�� Functions

ReferencesCharacteristicsAccessories: see page A. 148Dimensions: see page A. 152

Changeover switches

ATyS 3 motorisedswitches125 to 1600 A

SOCOMEC general catalogue

atys

_003

_a_1

_cat

atys

_103

_a_1

_cat

ATyS 3e

Pilote C30

ATyS 3s

ATyS D10

atys

_140

_b_1

_f_c

at

ATyS 3s

ATyS_gb.qxd 24/02/05 16:45 Page 140

Page 8: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

Standard device - 230 VAC

A. 141

Changeover switches

ATyS 3 motorised switches

References

atys

_001

_a_1

_cat

atys

_002

_a_1

_cat

125 A 160 A 250 A 400 A

ATyS 3s

No. of poles Reference £/ea Reference £/ea Reference £/ea Reference £/ea

3 pole 1523 3012 consult us 1523 3016 consult us 1523 3025 consult us 1523 3040 consult us4 pole 1523 4012 consult us 1523 4016 consult us 1523 4025 consult us 1523 4040 consult us

ATyS 3e

3 pole 1533 3012 consult us 1533 3016 consult us 1533 3025 consult us 1533 3040 consult us4 pole 1533 4012 consult us 1533 4016 consult us 1533 4025 consult us 1533 4040 consult us

Other voltages

12, 24, 48, 110 VDC consult us consult us consult us consult us consult us consult us consult us consult us

Accessories

Plug-in optional modules (ATyS 3e)

COM RS485 (No. 1) 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us2 inputs /2 outputs (No. 2) 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us

Bridging bars (1 part)

1 pole 4109 0019 10.42 4109 0019 10.42 4109 0025 14.36 4109 0039 15.57

Position I and II auxiliary contacts (factory fitted)

2nd AC ATyS 3s 1599 1002 consult us 1599 1002 consult us 1599 1012 consult us 1599 1012 consult us2nd AC ATyS 3e 1599 0002 consult us 1599 0002 consult us 1599 0012 consult us 1599 0012 consult us

Terminal shrouds (1 set)(1)(2)

3 pole 2694 3014 8.02 2694 3014 8.02 2694 3021 15.34 2694 3021 15.344 pole

top /bottom/ front (I) / rear (II)top /bottom/ front (I) / rear (II) 2694 4014 6.40 2694 4014 6.40 2694 4021 11.98 2694 4021 11.98

Terminal screens (1 set top and bottom)

3 pole 1509 3012 consult us 1509 3012 consult us 1509 3025 consult us 1509 3025 consult us4 pole 1509 4012 consult us 1509 4012 consult us 1509 4025 consult us 1509 4025 consult us

Padlocking (factory fitted)

“Padlocking in the 3 positions I, 0 and II” option 1599 0003 consult us 1599 0003 consult us 1599 0003 consult us 1599 0003 consult us

Handle key interlocking accessories (factory fitted)

Locking using RONIS EL11AP lock in padlocked position 1509 1006 consult us 1509 1006 consult us 1509 1006 consult us 1509 1006 consult us

Mounting spacers1 set of 2 1509 0001 consult us 1509 0001 consult us 1509 0001 consult us 1509 0001 consult us

Control voltage transformer

400/230 VAC 1599 4063 consult us 1599 4063 consult us 1599 4063 consult us 1599 4063 consult us

SOCOMEC general catalogue

NO/NC changeoverNO/NC changeover

(1) To shroud front switch top and bottom 2 references required.(2) To fully shroud front and rear / top and bottom 4 references required.

ATyS_gb.qxd 24/02/05 16:45 Page 141

Page 9: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

Standard device - 230 VAC

A. 142

��

FunctionsReferencesCharacteristicsAccessories: see page A. 148Dimensions: see page A. 152

References

ATyS 3s

No. of poles Reference £/ea Reference £/ea Reference £/ea Reference £/ea

3 pole 1523 3063 consult us 1523 3080 consult us 1523 3100 consult us 1523 3120 consult us4 pole 1523 4063 consult us 1523 4080 consult us 1523 4100 consult us 1523 4120 consult us

Reference £/ea

1523 3160 consult us1523 4160 consult us

ATyS 3e

3 pole 1533 3063 consult us 1533 3080 consult us 1533 3100 consult us 1533 3120 consult us4 pole 1533 4063 consult us 1533 4080 consult us 1533 4100 consult us 1533 4120 consult us

Other voltages

12, 24, 48, 110 VDC consult us consult us consult us consult us consult us consult us consult us consult us consult us consult us

Accessories

Plug-in optional modules (ATyS 3e)

COM RS485 (No. 1) 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us2 inputs /2 outputs (No. 2) 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us

1599 2000 consult us1599 2001 consult us

Bridging bars (1 part)

1 pole 4109 0063 20.35 4109 0080 24.98 4109 0080 24.98 4109 0120 32.68 4109 0160 32.68

Position I and II auxiliary contacts (factory fitted)

2nd AC ATyS 3s 1599 1022 consult us 1599 1032 consult us 1599 1032 consult us 1599 1032 consult us2nd AC ATyS 3e 1599 0022 consult us 1599 0032 consult us 1599 0032 consult us 1599 0032 consult us

1599 1032 consult us1599 0032 consult us

Terminal shrouds (1 set)(1)(2)

3 pole 2694 3051 11.984 pole 2694 4051 12.38

1533 31601533 4160

Terminal screens (1 set)

3 pole 1509 3063 consult us 1509 3080 consult us 1509 3080 consult us 1509 3080 consult us4 pole 1509 4063 consult us 1509 4080 consult us 1509 4080 consult us 1509 4080 consult us

1509 3080 consult us1509 4080 consult us

Padlocking (factory fitted)

“Padlocking in the 3 positions I, 0 and II” option 1599 0003 consult us 1599 0004 consult us 1599 0004 consult us 1599 0004 consult us 1599 0004 consult us

Handle key interlocking accessories (factory fitted)

Locking using RONIS EL11AP lock in padlocked position 1509 1006 consult us 1509 1004 consult us 1509 1004 consult us 1509 1004 consult us 1509 1004 consult us

Mounting spacers

1 set of 2 1509 0001 consult us

Control voltage transformer

400/230 VAC 1599 4063 consult us 1599 4120 consult us 1599 4120 consult us 1599 4120 consult us 1599 4120 consult us

Changeover switches

ATyS 3 motorisedswitches125 to 1600 A

SOCOMEC general catalogue

NO/NC changeoverNO/NC changeover

top /bottom/ front / reartop /bottom/ front / rear

top /bottomtop/bottom

(1) To shroud front switch top and bottom 2 references required.(2) To fully shroud front and rear / top and bottom 4 references required.

atys

_003

_a_2

_cat

atys

_107

_a_1

_cat

atys

_104

_a_1

_cat

630 A 800 A 1000 A 1250 A 1600 A

ATyS_gb.qxd 24/02/05 16:46 Page 142

Page 10: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 143

Changeover switches

ATyS 3 motorised switches

SOCOMEC general catalogue

Rated voltage Load duty category A/B(1) A /B(1) A /B(1) A /B(1) A /B(1) A /B(1) A /B(1) A /B(1) A /B(1)

Characteristics (according to IEC 60947-3)

125 A 160 A 250 A 400 A 630 A 800 A

Rated operational currents Ie (A)

400 VAC AC-21 A/AC-21 B 125/125 160/160 250/250 400/400 630/630 800/800AC-22 A/AC-22 B 125/125 160/160 250/250 400/400 630/630 800/800AC-23 A/AC-23 B 125/125 160/160 250/250 250/250 500/500 800/800

690 VAC AC-20 A/AC-20 B 125/125 160/160 250/250 400/400 630/630 800/800AC-21 A/AC-21 B 125/125 160/160 200/250 200/250 500/500 800/800AC-22 A/AC-22 B 125/125 125/125 125/160 125/160 315/315 800/800AC-23 A/AC-23 B 63/80 63/80 100/125 100/125 160/200 200/250

220 VDC DC-20 A/DC-20 B 125/125 160/160 250/250 400/400 630/630 800/800DC-21 A/DC-21 B 125/125 160/160 250/250 250/250 630/630 800/800DC-22 A/DC-22 B 125/125 160/160 250/250 250/250 500/500 800/800DC-23 A/DC-23 B 125/125 125/125 200/200 200/200 500/500 800/800

440 VDC DC-20 A/DC-20 B 125/125 160/160 250/250 400/400 630/630 800/800DC-21 A/DC-21 B 125(2)/125(2) 125(2)/125(2) 200(2)/200(2) 200(2)/200(2) 500(2)/500(2) 800(3)/800(3)

DC-22 A /DC-22 B 125(2)/125(2) 125(2)/125(2) 200(2)/200(2) 200(2)/200(2) 500(2)/500(2) 800(3)/800(3)

DC-23 A /DC-23 B 125(3)/80(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3) 500(3)/500(3) 800(3)/800(3)

(1) A/B: Category with index A = frequent operation - Category with index B = infrequent operation.(2) 3-pole device with 2 pole in series for the “+” and 1 for the “-”.(3) 4-pole device with 2 pole in series by polarity.(4) For a rated operating voltage Ue = 400 VAC.(5) Total transfer time from when command given to final positions (under the nominal conditions).

Thermal current Ith (40 °C)Rated insulation voltage Ui (V) 800 800 800 800 1000 1000Rated impulse withstand voltage Uimp (kV) 8 8 8 8 12 12

Fuse protected short-circuit withstand (kA rms prospective)(4)

Prospective short-circuit current (kA rms) 100 100 50 18 70 50Associated fuse rating gG (A) 125 160 250 400 630 800

Overload capacityRated short-time withstand current 1s Icw (kA rms)Rated peak withstand current (kA peak)(4)

720

720

930

930

1345

2655

ConnectionMinimum Cu cable section (mm2) 35 50 95 185 2 x 150 2 x 185Minimum Cu busbar section (mm2) - - - - 2 x 30 x 5 2 x 40 x 5Maximum Cu cable section (mm2) 50 95 150 240 2 x 300 2 x 300Maximum Cu busbar width (mm) 25 25 32 32 50 63Min. tightening torque (Nm) 9 9 20 20 20 -

Switching timeI - II or II - I (s)(5) 0.75 0.75 1.3 1.3 1.3 2.6I - O or II - O (s)(5) 0.45 0.45 0.85 0.85 0.85 1.6Duration of “electrical blackout” (s) 0.3 0.3 0.6 0.6 0.6 1.5

Power-supply toleranceSupply 230 VAC min/max +/- 20 % (V) 184/276 184/276 184/276 184/276 184/276 184/276

Control supply power demand (During transfer)Supply 230 VAC inrush/nominal (VA) 420/80 420/80 400/100 400/100 420/110 450/120

Mechanical characteristicsEndurance (number of operating cycles) 10000 10000 8000 8000 5000 4000Weight 3 p switch (ATyS 3s) (kg) 3.2 3.3 3.7 4.7 5.2 19.6Weight 4 p switch (ATyS 3s) (kg) 3.3 3.4 3.8 5.2 5.7 23.1

1000 A 1250 A 1600 A

1000/1000 1250/1250 1600/16001000/1000 1250/1250 1600/16001000/1000 1250/1250 1250/12501000/1000 1250/1250 1600/1600800/800 800/800 1000/1000800/800 800/800 1000/1000200/250 200/250 500/500

1000/1000 1250/1250 1600/16001000/1000 1250/1250 1250/12501000/1000 1250/1250 1250/12501000/1000 1250/1250 1250/12501000/1000 1250/1250 1600/1600

1000(3)/1000(3)1250(3)/1250(3)1250(3)/1250(3)

1000(3)/1000(3)1250(3)/1250(3)1250(3)/1250(3)

1000(3)/1000(3)1250(3)/1250(3)1250(3)/1250(3)

1000 1000 100012 12 12

100 100 1001000 1250 2 x 800

3580

3580

50110

2 x 240 - -2 x 50 x 5 2 x 60 x 5 2 x 80 x 54 x 185 4 x 185 6 x 185

63 63 100- 20 40

2.6 2.6 2.61.6 1.6 1.61.5 1.5 1.6

184/276 184/276 184/276

450/120 450/120 450/120

4000 4000 300023.1 24.6 41.724.6 29.6 48.7

ATyS_gb.qxd 24/02/05 16:46 Page 143

Page 11: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 144

atys

_007

_a_1

_cat

atys

_028

_b_1

_gb_

cat

FunctionsATyS 6 products are electric 3 or 4-poleautomatic transfer switches.They are a combination of two electricaland mechanical interlocked superposedload-break switches mounted back toback.They provide switching and automaticsource inversion of two low voltage powercircuits as well as safety isolation.Control unit can be replaced (spare part)without disconnection of the powercables.For more information see page, A. 136.

Conformity to standards• IEC 60947-6-1• IEC 60947-3• NF EN 60947-6-1• NF EN 60947-3• BS EN 60947-3• NBN EN 60947-3• GB 14048

General characteristics• Complete integration of the changeover

logic for Normal /Backup applicationsbetween a transformer and a generatorset or between two transformers

• 3 stable positions (I, 0, II).• AC-22, AC-23 and AC-31 switching.• Isolation by visual breaking.• Electrical control by volt free dry contact

(not on ATyS 6s).• Emergency manual control.• Padlocking in 0 (I and II optional).

Available on request• Specific power supply.• 6 or 8-pole switches.• Different ratings between switches I and

II for high currents.• By-pass switches.

�� Functions

ReferencesCharacteristicsAccessories: see page A. 148Dimensions: see page A. 152

Changeover switches

ATyS 6 automatictransfer switches125 to 1600 A

SOCOMEC general catalogue

Network failure

Automatic mode (AUT)

Generator start

MFT

Network availability

Switch to position 0

Switch to position

Switch to position

Generator stop

Switch to position 0

Semi automatic mode

Network availability

DTT

0MFMRT

0MR

CDT

no

yes

Manualoperation

Network : priority power sourceNetwork : backup power source2

1

2

1

2 1

1

Example (generator application):

Typical application

�ATySATS3 U sensing + 21

0, I, II controlFault relayOption COM + I/OMetering (I, P, Q, S, PF)

6sX

6eXXXXX

6mXX

XXXX

Timers

• MFT: Main (priority) source Failure Timer (0 to 60 s).

• DTT: Delay to Transfer Timer (0 to 60 s). Controls the backup source stability before transfer.

• OMF: Dead band stay in 0 position after Main (priority) source Failure (0 to 20 s). It allows the loadresidual voltage to decrease under a non critical value before transfer to backup source(necessary in case of rotating loads).

• MRT: Main (priority) source Return Timer (0 to 30 mn). Controls the main’s availability beforetransferring back the load.

• OMR: Dead band stay in 0 position after Main (priority) source Return (0 to 20 s). It allows the loadresidual voltage to decrease under a non critical value before transfer to priority source(necessary in case of rotating loads).

• CDT: Cool Down Timer (0 to 10 min.) allows the generator set cooling down before stop operation(for generator application).

ATyS_gb.qxd 24/02/05 16:46 Page 144

Page 12: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

Standard device - 230 VAC

A. 145

Changeover switches

ATyS 6 automatic transfer switches

References

atys

_005

_a_1

_cat

atys

_006

_a_1

_cat

125 A 160 A 250 A 400 A

ATyS 6s

No. of poles Reference £/ea Reference £/ea Reference £/ea Reference £/ea

3 pole 1553 3012 consult us 1553 3016 consult us 1553 3025 consult us 1553 3040 consult us4 pole 1553 4012 consult us 1553 4016 consult us 1553 4025 consult us 1553 4040 consult us

ATyS 6e

3 pole 1563 3012 consult us 1563 3016 consult us 1563 3025 consult us 1563 3040 consult us4 pole 1563 4012 consult us 1563 4016 consult us 1563 4025 consult us 1563 4040 consult us

ATyS 6m

3 pole 1573 3012 consult us 1573 3016 consult us 1573 3025 consult us 1573 3040 consult us4 pole 1573 4012 consult us 1573 4016 consult us 1573 4025 consult us 1573 4040 consult us

Other voltages

12, 24, 48 of 110 VDC consult us consult us consult us consult us consult us consult us consult us consult us

Accessories

Plug-in optional modules (ATyS 6e and 6m)

COM RS485 (No. 1) 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us2 inputs /2 outputs (No. 2) 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us

Voltage sensing and power supply kit

3 pole 1559 3012 consult us 1559 3012 consult us 1559 3025 consult us 1559 3040 consult us4 pole 1559 4012 consult us 1559 4012 consult us 1559 4025 consult us 1559 4040 consult us

Bridging bars (1 part)

1 pole 4109 0019 10.42 4109 0019 10.42 4109 0025 14.36 4109 0039 15.57

Remote control interface (ATyS 6e and 6m)

ATyS D10 1599 2010 consult us 1599 2010 consult us 1599 2010 consult us 1599 2010 consult usATyS D20 1599 2020 consult us 1599 2020 consult us 1599 2020 consult us 1599 2020 consult us

Position I and II auxiliary contacts (factory fitted)

2nd AC NO/NC changeover 1599 0002 consult us 1599 0002 consult us 1599 0012 consult us 1599 0012 consult us

Terminal shrouds (1 set)(1)(2)

3 pole 2694 3014 consult us 2694 3014 8.02 2694 3021 15.34 2694 3021 15.344 pole 2694 4014 6.40 2694 4014 6.40 2694 4021 11.98 2694 4021 11.98

Terminal screens (1 set top and bottom)

3 pole 1509 3012 consult us 1509 3012 consult us 1509 3025 consult us 1509 3025 consult us4 pole 1509 4012 consult us 1509 4012 consult us 1509 4025 consult us 1509 4025 consult us

Padlocking (factory fitted)

“Padlocking in the 3 positions I, 0 and II” option 1599 0003 consult us 1599 0003 consult us 1599 0003 consult us 1599 0003 consult us

Handle key interlocking accessories (factory fitted)

Locking using RONIS EL11AP lock in padlocked position 1509 1006 consult us 1509 1006 consult us 1509 1006 consult us 1509 1006 consult us

Mounting spacers

1 set of 2 1509 0001 consult us 1509 0001 consult us 1509 0001 consult us 1509 0001 consult us

Control voltage transformer

400/230 VAC 1599 4063 consult us 1599 4063 consult us 1599 4063 consult us 1599 4063 consult us

SOCOMEC general catalogue

top /bottom/ front (I) / rear (II)top /bottom/ front (I) / rear (II)

(1) To shroud front switch top and bottom 2 references required.(2) To fully shroud front and rear / top and bottom 4 references required.

ATyS_gb.qxd 24/02/05 16:46 Page 145

Page 13: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

Standard device - 230 VAC

A. 146

��

FunctionsReferencesCharacteristicsAccessories: see page A. 148Dimensions: see page A. 152

References

ATyS 6s

No. of poles Reference £/ea Reference £/ea Reference £/ea Reference £/ea

3 pole 1553 3063 consult us 1553 3080 consult us 1553 3100 consult us 1553 3120 consult us4 pole 1553 4063 consult us 1553 4080 consult us 1553 4100 consult us 1553 4120 consult us

Reference £/ea

1553 3160 consult us1553 4160 consult us

ATyS 6e

3 pole 1563 3063 consult us 1563 3080 consult us 1563 3100 consult us 1563 3120 consult us4 pole 1563 4063 consult us 1563 4080 consult us 1563 4100 consult us 1563 4120 consult us

1563 3160 consult us1563 4160 consult us

ATyS 6m

3 pole 1573 3063 consult us 1573 3080 consult us 1573 3100 consult us 1573 3120 consult us4 pole 1573 4063 consult us 1573 4080 consult us 1573 4100 consult us 1573 4120 consult us

1573 3160 consult us1573 4160 consult us

Other voltages

12, 24, 48 of 110 VDC consult us consult us consult us consult us consult us consult us consult us consult us consult us consult us

Accessories

Plug-in optional modules (ATyS 6e and 6m)

COM RS485 (No. 1) 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us 1599 2000 consult us2 inputs /2 outputs (No. 2) 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us 1599 2001 consult us

1599 2000 consult us1599 2001 consult us

Voltage sensing and power supply kit

3 pole 1559 3063 consult us 1559 3080 consult us 1559 3080 consult us 1559 3120 consult us4 pole 1559 4063 consult us 1559 4080 consult us 1559 4080 consult us 1559 4120 consult us

1559 3160 consult us1559 4160 consult us

Bridging bars (1 part)

1 pole 4109 0063 20.35 4109 0080 24.98 4109 0080 24.98 4109 0120 32.68 4109 0160 32.68

Position I and II auxiliary contacts (factory fitted)

2nd AC NO/NC changeover 1599 0022 1599 0032 1599 0032 1599 0032 1599 0032

Terminal shrouds (1 set)(1)(2)

3 pole 2694 3051 11.98 - - -4 pole 2694 4051 12.38 - - -

--

Terminal screens (1 set top and bottom)

3 pole 1509 3063 1509 3080 1509 3080 1509 30804 pole 1509 4063 1509 4080 1509 4080 1509 4080

1509 31601509 4160

Padlocking (factory fitted)

“Padlocking in the 3 positions I, 0 and II” option 1599 0003 1599 0004 1599 0004 1599 0004 1599 0004

Handle key interlocking accessories (factory fitted)

Locking using RONIS EL11AP lock in padlocked position 1509 1006 1509 1004 1509 1004 1509 1004 1509 1004

Mounting spacers

1 set of 2 1509 0001 - - - -

Control voltage transformer

400/230 VAC 1599 4063 1599 4120 1599 4120 1599 4120 1599 4120

Changeover switches

ATyS 6 automatictransfer switches125 to 1600 A

SOCOMEC general catalogue

top /bottom/ front (I) / rear (II)top /bottom/ front (I) / rear (II)

Remote control interface (ATyS 6e and 6m)

ATyS D10 1599 2010 1599 2010 1599 2010 1599 2010 1599 2010ATyS D20 1599 2020 1599 2020 1599 2020 1599 2020 1599 2020

(1) To shroud front switch top and bottom 2 references required.(2) To fully shroud front and rear / top and bottom 4 references required.

atys

_007

_a_2

_cat

atys

_095

_a_1

_cat

atys

_096

_a_1

_cat

630 A 800 A 1000 A 1250 A 1600 A

ATyS_gb.qxd 24/02/05 16:46 Page 146

Page 14: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 147

Changeover switches

ATyS 6 automatic transfer switches

SOCOMEC general catalogue

Characteristics (according to IEC 60947-6-1)

Characteristics according to standard IEC 60947-3, see page A. 143: ATyS 3

125 A 160 A 250 A 400 A 630 A 800 A

Rated operational currents Ie (A)B(1) B(1) B(1) B(1) B(1) B(1)

415 VAC AC-31 B

Rated voltage Load duty category

125 160 250 400 630 800

(1) Category with index B = infrequent operation.(2) For a rated operating voltage Ue = 400 VAC.(3) Total transfer time from when command given to final positions (under the nominal conditions).

Thermal current Ith (40 °C)Rated insulation voltage Ui (V) 800 800 800 800 1000 1000Rated impulse withstand voltage Uimp (kV) 8 8 8 8 12 12

Fuse protected short-circuit withstand (kA rms prospective)Prospective short-circuit current (kA rms)(2) 100 100 50 18 70 50Associated fuse rating gG (A)(2) 125 160 250 400 630 800Peak current value (kA peak) 18 18 23 23 45 41

Overload capacityRated short-time withstand current (30 ms) Icw (kA rms) 10 10 10 10 12,6 16Rated peak withstand current (kA peak)(2) 17 17 17 17 25.2 27.2

Operating classMaterial class PC PC PC PC PC PC

ConnectionMinimum Cu cable section (mm2) 35 50 95 185 2 x 150 2 x 185Minimum Cu busbar section (mm2) - - - - 2 x 30 x 5 2 x 40 x 5Maximum Cu cable section (mm2) 50 95 150 240 2 x 300 2 x 300Maximum Cu busbar width (mm) 25 25 32 32 50 63Min. tightening torque (Nm) 9 9 20 20 20 -

Switching timeI - II or II - I (s)(3) 0.75 0.75 1.3 1.3 1.3 2.6I - O or II - O (s)(3) 0.45 0.45 0.85 0.85 0.85 1.6Duration of “electrical blackout” (s) 0.3 0.3 0.6 0.6 0.6 1.5

Power-supply toleranceSupply 230 VAC min/max +/- 20 % (V) 184/276 184/276 184/276 184/276 184/276 184/276

Control supply power demand (During transfer)Supply 230 VAC inrush/nominal (VA) 420/80 420/80 400/100 400/100 420/110 450/120

Mechanical characteristicsEndurance (number of operating cycles) 10000 10000 8000 8000 5000 4000Weight 3 p switch (kg) 4 4.1 4.5 5.5 6 20.4Weight 4 p switch (kg) 4.1 4.2 4.6 6 6.5 23.9

1000 A 1250 A 1600 A

B(1) B(1) B(1)

1000 1250 1600

1000 1000 100012 12 12

100 100 1001000 1250 2 x 80080 80 96

20 25 3240 52.5 67.5

PC PC PC

2 x 240 - -2 x 50 x 5 2 x 60 x 5 2 x 80 x 54 x 185 4 x 185 6 x 185

63 63 100- 20 40

2.6 2.6 2.61.6 1.6 1.61.5 1.5 1.6

184/276 184/276 184/276

450/120 450/120 450/120

4000 4000 300023.9 25.4 36.925.4 30.4 42.9

ATyS_gb.qxd 24/02/05 16:46 Page 147

Page 15: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

Accessories description Reference £/ea

COM RS485 (No. 1) 1599 2000 consult us2 inputs /2 outputs (No. 2) 1599 2001 consult us

UseNo. 1 - COM module:control and state feedback of thechangeover switch via a 2 or 3-wire RS485 link with protocolJBUS/MODBUS® andtransmission speed up to38400 bauds.No. 2 - 2 inputs/2 outputs:• For ATyS 3e only:

2 inputs: changeover control+ network availability and,2 outputs: a load shedder relay+ default relay.

• For ATyS 6e and 6m only:2 inputs /2 outputsprogrammable.

See “Products references” pages- ATyS 3- ATyS 6.

Terminal shrouds and terminal screens

A. 148

AccessoriesPilote ATyS C30Dimensions

Voltage sensing and power supply kit

atys

_012

_a_1

_cat

ReferencesFor ATyS 6

Rating (A) No. of poles Reference £/ea

125 … 160 3 1559 3012 consult us125 … 160 4 1559 4012 consult us250 3 1559 3025 consult us250 4 1559 4025 consult us400 3 1559 3040 consult us400 4 1559 4040 consult us630 3 1559 3063 consult us630 4 1559 4063 consult us800 … 1000 3 1559 3080 consult us800 … 1000 4 1559 4080 consult us1250 3 1559 3120 consult us1250 4 1559 4120 consult us1600 3 1559 3160 consult us1600 4 1559 4160 consult us

UseProvides voltage sensing andpower connection to theelectronic module.The routing of the conductors iscontrolled, which means that nospecific protective device isnecessary for these connections.NB: the 3-pole version does notintegrate the power supply.Can be fitted on the top orbottom of the switch.Connections can be adapted toany type of network.

Plug-in optional modules

atys

_010

_a_1

_cat

References

SOCOMEC general catalogue

Bridging bars - See pages “SIRCOVER”

Changeover switches

ATyS 3 and 6accessories125 to 1 600 A

Control voltage transformerReferencesRating (A) Reference £/ea

125 … 630 1599 4063 consult us800 … 1600 1599 4120 consult us

UseAllows a 230 VAC device to besupplied with 400 VAC.

ATyS_gb.qxd 24/02/05 16:46 Page 148

Page 16: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 149

Changeover switches

ATyS 3 and 6 accessories

SOCOMEC general catalogue

Additional auxiliary contacts

acce

s_06

5_a_

1_ca

t

ReferencesFor ATyS 3s

Rating (A) Reference £/ea

125 … 160 1599 1002 consult us250 … 400 1599 1012 consult us630 1599 1022 consult us800 … 1600 1599 1032 consult us

For ATyS 3e, 6s, 6e and 6m

Rating (A) Reference £/ea

125 … 160 1599 0002 consult us250 … 400 1599 0012 consult us630 1599 0022 consult us800 … 1600 1599 0032 consult us

UsePre-breaking and signalling ofpositions I and II: 1 additionalNO/NC auxiliary contacts ineach position.Factory fitted.Low level AC: please consult us.

PadlockingReferencesUse

Allows locking of the operationin the 3 positions I, 0 and II.Factory fitted.

Handle key interlocking accessoriesReferencesLocking using RONIS EL11AP lock in padlocked position

Rating (A) Reference £/ea

125 … 630 1509 1006 consult us800 … 1600 1509 1004 consult us

“Padlocking in the 3 positions” option

Rating (A) Reference £/ea

125 … 630 1599 0003 consult us800 … 1600 1599 0004 consult us

UseLocking of the electrical and themanual operation by means of aRONIS EL11AP lock.Factory fitted.NB: possibility of locking inanother position, if the“Padlocking in the 3 positions”option is ordered.

Mounting spacers

atys

_009

_a_1

_cat

ReferencesRating (A) Pack qty Reference £/ea

125 … 630 2 pieces 1509 0001 consult us

UseRaises the device’s terminals10 mm away from the bottom ofthe enclosure or frame on whichthe device is mounted.This may also be used toreplace the original mountingspacers.

atys

_125

_a_1

_cat

atys

_101

_a_1

_cat

ATyS_gb.qxd 24/02/05 16:46 Page 149

Page 17: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 150 SOCOMEC general catalogue

�� Accessories

Pilote ATyS C30Dimensions

Changeover switches

ATyS 3 and 6accessories125 to 1600 AAccessories

Remote control interfaces for ATyS 6e, 6m and C30

UseATyS D10: Allows sourcesavailability and changeoverstate remote display.

atys

_145

_b_1

_x_c

at

UseATyS D20: Allows sourcesavailability, changeover state,metering, configuration andcontrol remotely.

atys

_150

_b_1

_x_c

at

Doormounting2 holes Ø 22,5 mm.Master ATyS connection viaRJ45 8/8 type link.

Connection cable not delivered.

Drillings.

1

atys

_147

_a_1

_cat

Ø 22.5

4036

20

= =

96 x 96

atys

_161

_a_1

_cat

Dedicated to applications requiring back panel mounting of the power switching. Interfaces are self powered from master ATyS productconnection (6e, 6m, C30).Maximum connection distance: 3 m.

ReferencesReference

ATyS D10 1599 2010

ReferencesReference

ATyS D20 1599 2020

(1) RJ45 type link for ATySconnection.

ATyS_gb.qxd 24/02/05 16:46 Page 150

Page 18: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 151SOCOMEC general catalogue

Changeover switches

Pilote ATyS C30at

ys_1

48_a

_1_c

atat

ys_1

49_b

_1_g

b_ca

t

FunctionsPilote ATyS C30 allows any type of changeover control: ATyS 3, SMV, contactors, breakers or other motorisedswitches.

Conformity to standards

General characteristics• Modular design• DIN rail mounting• ATyS D10 or D20 possible connection• Outputs relays for changeover control• Inputs for auxiliary position contacts• Metering 3U on network 1• Metering 1U on network 2• 2 inputs programmable (test…)• 2 outputs programmable.

• IEC 61010-1• IEC 61000-4-2• IEC 61000-4-3• IEC 61000-4-4• IEC 61000-4-5• IEC 61000-4-6

• IEC 61000-4-8• IEC 61000-4-11• IEC 60068-2-6• IEC 60068-2-11• IEC 60068-2-30

ATyS 3s

ATyS D10 or D20

ATyS C30

2

1

4

3

Load

ReferencePilote ATyS C30 Reference

1599 3030

Electrical characteristics

Power supply from metering inputsMeasurement range 200 … 400 VAC/±20 %Frequency 50/60 HzAccuracy ±1 %

1. Metering and power

2. Orders and position information feedback

3. Generator set “Start /Stop” control

4. ATyS interfaces connection

atys

_418

_a_1

_x_c

at

13 14 23 24 33 34 43 44 53 54 301302303304310311320321

205203106105104103

L3’L1’L1L2L3N

4 5

6 7 8 9 10

11 12

321

1. Generator set “Start /Stop”control

2. Pos 1: control power circuit3. Pos 2: control power circuit4. O1: programmable output5. O2: programmable output

6. CA0: auxiliary contact position 07. CA1: auxiliary contact position 18. CA2: auxiliary contact position 29. I1: programmable input10. I2: programmable input11. Metering 3U network 1 + power

supply 112. Metering 1U network 2 + power

supply 2

Terminals

ATyS_gb.qxd 24/02/05 16:46 Page 151

Page 19: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 152 SOCOMEC general catalogue

AccessoriesPilote ATyS C30Dimensions

Changeover switches

ATyS 3 and 6accessories125 to 1600 ADimensions

1. Locking bracket with 3 padlocks max.

2. Maximum handle radius, operating angle 2 x 90°.

3. Connection and disconnection area.

4. Stand off with mounting spacer accessory.

5. Terminal shrouds.

6. Cut out dimension.

7. Handle.

10

W

U

MJ

J1

X T T T 11

C

H

Z2

Z1

10.5 Y Y

85

48

F

A

120

140

270

V

223

119

=

Fix.

180

Fix.

195

BA

CA

CA

AA

AC

101

=

Ø7

Ø9

Fix.

180

Fix.

195

1

32

3

3

4

5

7

50.5

20

138

165

6

CA

W

U

50.5

20

138

101

6

• ATyS 3e, 6s, 6e, 6m• ATyS 3s

• 125 to 630 A

atys

_018

_c_x

_cat

Overall dimensions

Terminal shrouds

Switch bodySwitch

mountingConnection terminals

A 3p. A 4p. C AC F 3p. F 4p. H J 3p. J 4p. M 3p. M 4p. T U V W X 3p. X 4p. Y Z1 Z2 AA BA CA

304 340 244 235 286,5 322,5 151 154 184 120 150 36 20 25 9 28 22 3,5 38 134 135 115 10304 340 244 235 286,5 322,5 151 154 184 120 150 36 20 25 9 28 22 3,5 38 134 135 115 10345 395 244,5 280 328 378 153 195 245 160 210 50 25 30 11 33 33 3,5 39,5 134,5 160 130 15345 395 244,5 280 328 378 153 195 245 160 210 50 35 35 11 33 33 3,5 39,5 134,5 170 140 15394 459 320,5 400 377 437 221 244 304 210 270 65 45 50 13 42,5 37,5 5 53 190 260 220 20

Rating(A)

125160250400630

J 1

3434353534

ATyS_gb.qxd 24/02/05 16:46 Page 152

Page 20: ATyS atys 003 a 1 cat - ZEB Power · The ATyS range SOCOMEC general catalogue ATyS 3s simplified wiring diagram ATyS 3e complementary features ATyS 3e complementary features General

A. 153

Changeover switches

ATyS 3 and 6 accessories

SOCOMEC general catalogue

Dimensions• 800 to 1600 A

F

12.5

=

207

169

166

280

250

166

V

=

250

AA

12.5

391.5

293

253.5

Z1

Y Y 48

94

X

M 51.5

J

T T T

1

3

BAC

23

34

5

7

U

50.5

20

138

214

6

50.5

20

138

150

6

• ATyS 3e, 6s, 6e, 6m• ATyS 3s

atys

_019

_c_x

_cat

1. Locking bracket with 3 padlocks max.

2. Maximum handle radius, operating angle 2 x 90°.

3. Connection and disconnection area.

4. Terminal screens.

5. Phase barrier shield.

6. Cut out dimension.

7. Handle.

Overall dimensions

Terminal shrouds

Switch bodySwitch

mountingConnection terminals

B AC F 3p. F 4p. J 3p. J 4p. M 3p. M 4p. T U V X Y Z1 AA

370 461 504 584 306,5 386,5 255 335 80 50 60,5 60 7 66,5 321370 461 504 584 306,5 386,5 255 335 80 50 60,5 60 7 66,5 321370 461 504 584 306,5 386,5 255 335 80 60 65 60 7 66,5 330380 481 596 716 398,5 518,5 347 467 120 90 44 66 8 67,5 288

Rating(A)

800100012501600

svr_

077_

a_1_

x_ca

t

svr_

078_

b_1_

x_ca

t

svr_

098_

a_1_

x_ca

t

33 8.58.5

50

3310

ø 9

ø 15

16 x 11

60

28.5 15.7515.75

28.5

15

15

5 5

12,5

25 253030

454590

ø12,5

Connection terminals

• 800 to 1000 A • 1250 A • 1600 A

ATyS_gb.qxd 24/02/05 16:46 Page 153