8/7/2019 AUTO SELECT
1/13
AUTO SELECT
8/7/2019 AUTO SELECT
2/13
WHAT IS AUTO SELECT?
Auto selector sometimes also known
as override control. One controller canoverride a manipulated variable from
another controller when operatingconditions exceed the limit or
constraint specified.
8/7/2019 AUTO SELECT
3/13
WHY DO WE USE AUTO
SELECT?
It is used to choose appropriatecontrolled variables for a specific
reason. Automatic selector can choose
the highest or the lowest or the median
from two or more controlled variables.
8/7/2019 AUTO SELECT
4/13
WHEN DO WE USE AUTO
SELECT?
Selectors facilitate on-line modification ofcontrol strategies as a function of changing
operating conditions without disturbing theprocess. The typical used are:
Protection of equipment
Auctioneering
Redundant Instrumentation Variable structuring or median select.
8/7/2019 AUTO SELECT
5/13
PROTECTION OF
EQUIPMENT
8/7/2019 AUTO SELECT
6/13
As shown in Figure 9.7, there are twocontrollers (i.e TIC1 and TIC2) producing
two controller output signals (MV1 andMV2) connecting to the auto selector. Oneof the output controller signals is selectedto the final control element (TCY) based onwhich one is the lowest. Under normalcondition, it is designed that the selector
selects MV 1 based on measurement doneby TE1. However, if there is a disturbance(air leak) the heater become too hot due tothe deviation measured at TE1. TIC 1 willproduces high signal of MV1 and theselector will switch to MV2. At thismoment TIC2 will overrides TIC1 incontrolling the heater. Hence it protectsheater from burn out due to large signalprovided by MV1.
8/7/2019 AUTO SELECT
7/13
AUCTIONEERING
8/7/2019 AUTO SELECT
8/13
Auctioneering describes theapplication of an auto-selector
where multiple inputs of a similarnature are polled and one is
selected as the highest or lowest.Figure 9.8 shows a reactor where
the process is to controlled basedon the highest temperature.
Coolant will be supplied to theprocess to modify the reaction
based on the highest temperature. Ifone controlled variable is used, itmay not necessary indicate thehottest section of the reactor.
8/7/2019 AUTO SELECT
9/13
REDUNDANT
INSTRUMENTATION
Redundant instrumentation is a
common application of auto-selector where a high or lowselector is used to choose a
functioning measurement in the
event of a measurement failure. Asshown in Figure 9.8, if one of thetransmitter fails, the auto select will
refers to the highest transmitterreading
8/7/2019 AUTO SELECT
10/13
VARIABLE STRUCTURING
OR MEDIAN SELECT
8/7/2019 AUTO SELECT
11/13
A median selector is an arrangementwhere high and low selectors are used to
detect the median/middle of a series ofsignals. This is very useful system whenthe measurement output to a controller, ifdriven to the highest or lowest extreme,
could cause disruption of the process. Theplant/equipment is then protected againstan individual instrument extremely driven
in either direction.
Fig. 9.9 is a diagram of a typical chemicalprocess application of median-select. Theconfiguration below allows only median
temperature signal pass through to thetemperature controller.
8/7/2019 AUTO SELECT
12/13
ADVANTAGES Multiple signals from transmitter can bemanipulated to control a loop with highersensitivity (high-low select) or by taken
the average/median of the signalsmeasured (median select).
In the event of instrument failure,redundant instrumentation play importantrole to avoid disruption in the process
In the case of override control, it canprotects against exceeding equipmentoperating condition.
8/7/2019 AUTO SELECT
13/13