Date post: | 04-Apr-2018 |
Category: |
Documents |
Upload: | sanjeevchhabra |
View: | 215 times |
Download: | 0 times |
of 54
7/29/2019 Auto%20transformerR4.pdf
1/54
TECHNICALSPECIFICATIONSECTION:AUTOTRANSFORMER
CONTENT
SL.NO CL.NO. DESCRIPTION PAGENO.
1. 1.0 General 2
2. 2.0 Performance 3
3. 3.0 ConstructionDetails 4
4. 3.1.2 TankCover 5
5. 3.1.8 TemperatureIndicators 8
6. 3.3 Windings 10
7. 3.4 InsulatingOil 10
8. 3.5 TerminalArrangements 13
9. 3.9 TapChangingequipment 17
10. 4.0 Fittings 27
11. 5.0 InspectionandTesting 28
12. 5.2 FactoryTests 33
13. 5.2.7 TankTests 35
14. 6.0 Technicalparameters 39
15. 7.0 BushingCurrentTransformer 48
16. 8.0 OilStorageTank 52
17. 9.0 OilSamplingBottle 53
TECHNICALSPECIFICATIONSECTION:AUTOTRANSFORMER
Tech Specification,Section: Autotransformer Page 1 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
2/54
1 General
1.1 This specification covers design, engineering, manufacture, testing atmanufacturer'sworks,deliveryatsiteincludingallmaterials,accessories,
spares,unloading,handling,properstorageatsite,erection,testingandcommissioningoftheequipmentspecified.
1.2 Theautotransformers shall ingeneral haveconstantohmic impedancebetweenHVandIVonalltaps.However,incaseofparalleloperationwiththeexistingtransformer,
i) The impedance, vector group, OLTC connection & range etc. of thetransformeristobematchedwiththatoftheexistingtransformer.
ii) Necessaryprovision is to be kept in the transformer controlscheme forparallel operationwiththeexistingMaster/Follower/Independent /Off type
OLTCcontrolscheme.iii) Matching of physical dimension, orientation etc. to facilitate
interchangeabilitywiththeexistingsparesinglephasetransformer,ifnecessary.
1.3 Externalor internalreactorsshallnotbeusedtoachievetheHV/LVandIV/LVimpedancespecified.
1.4ReferenceDrawings
Thelistofdrawingsindicatedbelowformapartofthisspecification.
i. StandarddimensionsforOIP 0000-T-E-A-001condenserbushings(Lowerportion)ii. Standardfoundationfor 0000-000-T-E-A-003 Autotransformeriii. Typicalarrangement 000S3-YE4-014ofautotransformerwithregulatingwindingattheendofserieswinding
1.5 Transportation
TheContractorshalldespatchthetransformerfilledwithoilorinanatmosphereofnitrogenordryair.Intheformercasethecontractorshalltakecareoftheweightlimitationontransportandhandlingfacilityatsite.In the latter case, necessary arrangement shall be ensured by thecontractortotakecareofpressuredropofnitrogenordryairduringtransitandstoragetill completionofoil fillingduringerection.Agas pressuretestingvalvewithnecessarypressuregaugeandadaptorvalveshallbeprovided.Transformershallalsobefittedwithsufficientnumberofimpactrecordersduringtransportationtomeasurethemovementduetoimpactinallthreedirections.
2 Performance
Tech Specification, Section: Autotransformer Page 2 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
3/54
2.1 Theautotransformersshallbeusedforbi-directionalflowofratedpower.
2.2 Transformersshallbecapableofoperatingundernaturalcooledconditionuptothespecified load. Theforcedcooling equipmentshall comeintooperationbypre-setcontactsofwindingtemperatureindicatorandthe
transformershalloperateasaforcedcoolingunit initiallyasONAFuptospecified loadand thenasOFAF. Cooling shall be sodesigned thatduringtotalfailureofpowersupplytocoolingfansandoilpumps,thetransformershallbeabletooperateatfullloadforatleastten(10)minuteswithout the calculatedwinding hot spot temperatureexceeding 150C.Transformersfittedwith twocoolers,eachcapableofdissipating50percent of the loss at continuous maximum rating, shall be capable ofoperatingfor20minutesintheeventoffailureoftheoilcirculatingpumporblowersassociatedwithonecoolerwithoutthecalculatedwindinghotspot temperature exceeding 150C at continuous max. rating. Thecontractor shall submit supporting calculations for the above for
Employer'sapproval.
2.3 Thetransformersshallbecapableofbeingoperated,withoutdanger,on
any tapping at the rated MVA with voltage variation of 10%correspondingtothevoltageofthetapping.
2.4 ThemaximumfluxdensityinanypartofthecoreandyokeattheratedMVA, voltage and frequency shall be such that under 10 per centcontinuousovervoltageconditionitdoesnotexceed1.9Tesla.
2.5 DGA of oil shall be periodically monitored by the Employer and the
interpretationofDGAresultswillbeasperIEC-599.
2.6 RadioInterferenceandNoiseLevel
2.6.1 The transformers shall be designed with particular attention to thesuppressionofmaximumharmonicvoltage,especially thethirdandfifthsoastominimiseinterferencewithcommunicationcircuit.
2.6.2 Thenoise levelof transformer,whenenergised at normalvoltageandfrequencywithfansandpumpsrunningshallnotexceed,whenmeasuredunder standard conditions, the values specified in NEMA standard
publicationTR-1.
2.7 ThetransformersshallbecapableofbeingloadedinaccordancewithIS:6600/IEC-354.There shall be no limitation imposed by bushings, tapchangersetc.oranyotherassociatedequipment.
2.8 The transformer and all its accessories including CTs etc. shall bedesignedtowithstandwithoutinjury,thethermalandmechanicaleffectsofanyexternalshortcircuittoearthandofshortcircuitsattheterminalsofanywindingforaperiodof3secs.TheshortcircuitleveloftheHV&IVSystemtowhichthesubjecttransformerswillbeconnectedis40kA(sym,
rms,3phasefaulton400kV&220kV)&31.5kA(sym,rms,3phasefaulton132kV).
Tech Specification, Section: Autotransformer Page 3 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
4/54
2.9 Transformer shall be capable of withstanding thermal and mechanicalstressescausedbysymmetricalorasymmetricalfaultsonanywinding.
2.10 Transformersshallwithstand,withoutinjuriousheating,combinedvoltage
and frequency fluctuations which produce the following over fluxingconditions:
i) 125%for1-minute140%for5-seconds
ii) Biddershallindicate150%and170%overvoltagewithstandtime.
2.11 TheaircorereactanceofHVwindingoftransformershallnotbelessthan20%.
2.12 TertiaryWindings(forautotransformersabove100MVA)
2.12.1 The tertiary windings shall be suitable for connection of reactors orcapacitorswhichwouldbesubjectedtofrequentswitching.Allthewindingsshallbecapableofwithstandingthesestressesthatmaybecausedbysuchswitching.
2.12.2 The Tertiary winding shall be designed to withstand mechanical and
thermalstressesduetodeadshortcircuitonitsterminals.
2.12.3 Thetertiarywindingshallbesuitableforconnection toLTTransformerfor
auxiliarysupply.
3 ConstructionDetails
Thefeaturesandconstructiondetailsofeachpowertransformershallbeinaccordancewiththerequirementstatedhereunder.
3.1 TankandTankAccessories
3.1.1 Tank
3.1.1.1 Tankshallpreferablybeofweldedconstructionandfabricatedfromtestedqualitylowcarbonsteelofadequatethickness.
3.1.1.2 All seams and those joints not required to beopenedat site shall befactorywelded,andwhereverpossibletheyshallbedoublewelded.Aftercompletionoftankandbeforepainting,dyepenetrationtestshallbecarriedoutonweldedpartsofjackingbosses,liftinglugsandallloadbearing members. The requirement of post weld heat treatment oftank/stressrelievingshallbebasedonrecommendationofBS-5500table4.4.3.1.
3.1.1.3Tankstiffenersshall beprovided forgeneral rigidityandtheseshall be
designedtopreventretentionofwater.
Tech Specification, Section: Autotransformer Page 4 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
5/54
3.1.1.4 Thetransformershallbeofbelltypetankwiththejointatabout500mmabove the bottomof the tank. In case the joint is welded it shall beprovidedwith flangessuitable forrepeatedwelding. The jointshall beprovidedwithasuitablegaskettopreventweldsplatterinsidethetank.Propertankshieldingshallbedonetopreventexcessivetemperaturerise
ofthejoint.
3.1.1.5 Eachtankshallbeprovidedwith:
(a) Liftinglugssuitableforliftingtheequipmentcompletewithoil.
(b) Aminimumoffourjackingpadsinaccessiblepositiontoenablethetransformercompletewithoiltoberaisedorloweredusinghydraulicjacks.
(c) Suitablehaulageholesshallbeprovided.
3.1.1.6 Thetankshallbedesignedinsuchawaythatitcanbemountedontheplinthdirectly.
3.1.1.7Thebaseofeachtankshallbesodesignedthatitshallbepossibletomove thecompletetransformerunit byskidding inanydirectionwithoutinjurywhenusingplatesorrails.
3.1.2 TankCover
3.1.2.1 The tank cover shall preferably be sloped to prevent retention of rain
waterandshallnotdistortwhenlifted.
3.1.2.2 Atleasttwoadequatelysizedinspectionopeningsoneateachendofthetank, shall be provided for easy access to bushings and earthconnections. The inspection covers shall not weighmore than 25 kg.Handlesshallbeprovidedontheinspectioncovertofacilitatelifting.
3.1.2.3 The tank covers shall be fitted with pockets at the position of maximumoiltemperatureatmaximumcontinuousratingforbulbsofoilandwindingtemperatureindicators.Itshallbepossibletoremovethesebulbswithoutloweringtheoilinthetank.Thethermometershallbefitted
withacaptivescrewtopreventtheingressofwater.
3.1.2.4 Bushingturrets,coversof inspectionopenings,thermometerpocketsetc.shallbedesignedtopreventingressofwaterintoorleakageofoilfromthetank.
3.1.2.5 Allboltedconnectionsshallbefittedwithweatherproof,hotoilresistant,resilient gasket in between for complete oil tightness. If gasket iscompressible,metallicstops/othersuitablemeansshallbeprovidedtopreventover-compression.
3.1.3 AxlesandWheels
Tech Specification, Section: Autotransformer Page 5 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
6/54
3.1.3.1 Thetransformershallbemountedeitheronrollersoronconcreteplinthfoundationdirectly,aspermanufacturer'sstandardpractice.
3.1.3.2 The roller mounted transformers are to be provided with flanged bi-directional wheels and axles. This set ofwheels and axles shall be
suitableforfixingtotheundercarriageoftransformertofacilitateitsmovement on rail track. Suitable locking arrangement along withfoundationboltsshallbeprovidedforthewheelstopreventaccidentalmovementoftransformer.
3.1.3.3 Therailtrackgaugeshallbe1676mm.
3.1.3.4 Biddercansupplyonesetof trolleysinplaceofwheelassemblyrollersfor movement of transformer per sub-station for plinth mountedtransformer.
3.1.4 FoundationandAntiEarthquakeClampingDevice
3.1.4.1Toprevent transformer movement during earthquake, suitable clampingdevicesshallbeprovidedforfixingthetransformertothefoundation.
3.1.5 Conservator&OilPreservationSystem
3.1.5.1 Mainconservatorshallhaveaircelltypeconstantoilpressuresystemtopreventoxidationandcontaminationofoilduetocontactwithmoisture,andshallbefittedwithmagneticoillevelgaugewithlowoillevelpotentialfreecontacts.
3.1.5.2 OLTCshall haveconventional typeconservatorwithprismatic oil levelgauge.
3.1.5.3 Conservatortank
3.1.5.3.1Conservatortankshallhaveadequatecapacitywithhighestandlowestvisible-levels to meet the requirements of expansion of total cold oilvolumeinthetransformerandcoolingequipmentfromminimumambienttemperatureto100C.
3.1.5.3.2Theconservatorshallbefittedinsuchapositionsothatitcanberemoved for cleaning purposes. Suitable provision shall be kept toreplaceaircell,whereverapplicable.
3.1.5.3.3 Conservator shall be positioned so as not to obstruct any electricalconnectiontotransformer.
3.1.5.4 OilPreservationEquipment
Therequirementsofaircelltypeoilsealingsystemaregivenbelow.
3.1.5.4.1Contactoftheoilwithatmosphereisprohibitedbyusingaflexibleaircellofnitrilerubberreinforcedwithnyloncloth.
Tech Specification, Section: Autotransformer Page 6 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
7/54
3.1.5.4.2Thetemperatureofoilis likelytoriseupto100Cduringoperation.Assuchaircellusedshallbesuitableforoperatingcontinuouslyat100C.
3.1.5.4.3Aircellofconservatorshallbeabletowithstandthevacuumduring
installation/maintenanceperiods. Otherwiseprovision shall be kept toisolatetheconservatorfromthemaintankwhenthelatterisundervacuumbyprovidingavacuumsealingvalveorothersuitablemeansinthepipeconnectingmaintankwiththeconservator.
3.1.5.4.4Theconnectionofaircelltothetopoftheconservatorisbyairproofsealpreventingentranceofairintotheconservator.
3.1.5.5 DehydratingFilterBreather
Conservatorshallbefittedwithadehydratingfilterbreather.Itshallbeso
designedthat:
a) Passageofairisthroughsilicagel.
b) Silicagelisisolatedfromatmospherebyanoilseal.
c) Moistureabsorptionindicatedbya changeincolourofthetintedcrystals canbeeasilyobservedfromadistance.
d) Breatherismountednotmorethan1200mmaboverailtoplevel.
e) Tominimisetheingressofmoisturefollowingshallbeprovided.
i. Three breathers (of identical size) shall be connected inseriesformaintankconservator.
ii. Twobreathers(eachof2.5litresminimumvolume)shallbeconnectedinseriesforOLTCtankconservator.
3.1.6 PressureReliefDevice
Adequatenumberofpressure reliefdevicesshallbeprovidedatsuitablelocations.Theseshallbeofsufficientsizeforrapidreleaseofanypressure
thatmaybegeneratedinthetankandwhichmayresultindamagetoequipment. Thedevice shall operate at astatic pressure less than thehydraulictestpressureofthetransformertank.Itshallbemounteddirectlyonthetank.Onesetofelectricallyinsulatedcontactsshallbeprovidedforalarm/tripping..Dischargeofpressurereliefdeviceshallbeproperlytakenthroughpipesanddirectedawayfromthetransformer/otherequipmentandthisshallbepreventedfromsprayingonthetank.FollowingroutinetestsshallbeconductedonPRD
a. Airpressuretestb. Liquidpressuretest
c. Leakagetestd. Contacttest
Tech Specification, Section: Autotransformer Page 7 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
8/54
e. Dielectrictest.
3.1.7 BuchholzRelay
A double float/reed type Buchholz relay shall be provided. Any gas
evolvedin the transformer shall collectin thisrelay. The relay shall beprovided with a test cock suitable for a flexible pipe connection forcheckingitsoperationand takinggassample. Acopper/stainlesssteeltubeshall beconnectedfromthegas collector toa valve locatedabout1200mmabovegroundleveltofacilitatesamplingwiththetransformerinservice. Thedevice shall be provided with twoelectrically independentungroundedcontacts,oneforalarmongasaccumulationandtheotherfortrippingonsuddenriseofpressure.
3.1.8 TemperatureIndicators
3.1.8.1 OilTemperatureIndicator(OTI)
Alltransformersshallbeprovidedwitha150mmdialtypethermometerfortop oil temperature indication. The thermometer shall have adjustable,electrically independent ungrounded alarmand trip contacts, maximumreading pointer and resetting device shall be provided in the OTI. Atemperaturesensingelementsuitablylocatedinapocketontopoilshallbefurnished. This shall beconnectedto theOTIbymeansofcapillarytubing.Temperatureindicatordialsshallhavelineargradationstoclearly
readatleastevery2C.AccuracyclassofOTIshallbe1.5%orbetter.
3.1.8.2 WindingTemperatureIndicator(WTI)
Adeviceformeasuringthehotspottemperatureofeachwindingshallbeprovided(HV,IVandLV).Itshallcomprisethefollowing:
i) Temperaturesensingelement.
ii) Imagecoil.
iii) AuxiliaryCTs,ifrequiredtomatchtheimagecoil,shallbefurnishedand mountedinthecoolercontrolcabinet.
iv) 150 mm dia local indicating instrument with maximum readingpointer and two adjustable electrically independent, ungroundedcontacts; besides that required for control of cooling equipment ifany, one for high winding temperature alarm and one for trip.Temperatureindicatordialsshallhavelineargradationstoclearlyreadatleastevery2C.
v) Calibrationdevice.
vi) AccuracyclassofWTIshallbe1.5%orbetter.
Tech Specification, Section: Autotransformer Page 8 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
9/54
vii) Inadditiontotheabove,thefollowingequipmentshallbeprovidedfor remoteindicationofwindingtemperatureforeachofthewinding:
a) Signaltransmitterforeachwinding
Signal transmitter shall have additional facility to transmit signal forrecordingwindingtemperatureatEmployer'sdataacquisitionsystem,forwhichaduplexplatinumRTDwithnominalresistanceof100ohmsatzerodegree centigrade shall be supplied. The RTD shall be three wireungroundedsystem.ThecalibrationshallbeasperSAMA(USA)standardor equivalent. The RTD may be placed in the pocket containingtemperaturesensingelementandimagecoilforWTIsystemwhichwillbeusedforbothremoteWTIandDAS.NecessaryequipmentforsendingthesignaltoremoteWTIandDASshallbeprovided.Inlieu,separateRTDforeachofthefunctionsshallbeprovided.
b) Remotewindingtemperatureindicator
ItshallbesuitableforflushmountingonEmployer'spanel.ThisshallnotberepeaterdialoflocalWTIandwilloperatebysignaltransmitter.
Anyspecialcable required forshieldingpurpose, forconnectionbetweencoolercontrolcabinetandremoteWTIcontrolcircuit,shallbeinthescopeofContractor.OnlyoneRWTIwithafourpointselectorswitchshallbeprovidedforallthethreewindings(HV,IVandLV).
3.1.9 EarthingTerminals
3.1.9.1 Two(2)earthingpads(eachcompletewithtwo(2)nos.holes,M10bolts,plain and spring washers) suitable for connection to 75 x 12 mmgalvanisedsteelgroundingflatshallbeprovidedeachatpositionclosetoearthofthetwo(2)diagonallyoppositebottomcornersofthetank.
3.1.9.2 Twoearthingterminalssuitableforconnectionto75x12mmgalvanisedsteelflatshallalsobeprovidedoncooler,marshallingboxandanyotherequipmentmountedseparately.
3.2 Core
3.2.1 The coreshallbeconstructed fromhigh grade,non-ageing, cold rolled,supergrainoriented,siliconsteellaminations.
3.2.2 The design of the magnetic circuit shall be such as to avoid staticdischarges,developmentofshortcircuitpathswithinitselfortotheearthedclampingstructureandproductionoffluxcomponentatrightanglestotheplaneoflaminationswhichmaycauselocalheating.
3.2.3 Theinsulationofcoretoboltsandcoretoclampplatesshallbeableto
withstandavoltageof2KV(rms)for1minute.
Tech Specification, Section: Autotransformer Page 9 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
10/54
3.2.4 Core and winding shall be capable of withstanding the shock duringtransport,installationandservice.Adequateprovisionshallbemadetoprevent movement of core and winding relative to tank during theseconditions.
3.2.5 All steel sectionsused for supportingthecoreshallbe thoroughlysandblastedaftercutting,drillingandwelding.
3.2.6 Each core lamination shall be insulated with a material that will notdeteriorateduetopressureandhotoil.
3.2.7 Thesupporting frameworkofthecoreshallbesodesignedastoavoidpresence of pockets which would prevent complete emptying of tankthroughdrainvalveorcausetrappingofairduringoilfilling.
3.2.8 Adequateliftinglugswillbeprovidedtoenablethecoreandwindingstobe
lifted.
3.3 Windings
3.3.1 TheContractorshallensurethatwindingsofall400kVclasstransformersaremadeindustproofandconditionedatmosphere.
3.3.2 Theconductorsshallbeofelectrolyticgradecopperfreefromscalesandburrs.
3.3.3 Theinsulationoftransformerwindingsandconnectionsshallbefreefrom
insulating compounds which are liable to soften, ooze out, shrink orcollapseand be non-catalytic and chemically inactive in transformer oilduringservice.
3.3.4 Coilassemblyand insulatingspacersshall besoarrangedastoensurefreecirculationofoilandtoreducethehotspotofthewinding.
3.3.5 Thecoilswouldbemadeup,shapedandbracedtoprovideforexpansionandcontractionduetotemperaturechanges.
3.3.6 The conductor shall be transposed at sufficient intervals in order to
minimize eddy currents and to equalise thedistribution of currents andtemperaturealongthewinding.
3.4 InsulatingOil
3.4.1 The insulating oil shall conform to all parameters specified below, whiletested at supplier's premises. No inhibitors shall be used in oil. Thecontractor shall furnish test certificates from the supplier against theiracceptancenormsasmentionedbelow,priortodespatchofoilfromrefinerytosite.
----------------------------------------------------------------------------------------------
Tech Specification, Section: Autotransformer Page 10 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
11/54
Sl. Characteristics Requirements MethodofTestNo.----------------------------------------------------------------------------------------------1. Appearance Theoilshall Arepresentative
beclearand sampleoftheoil
transparentand shallbeexaminedfreefromsusp- ina100mmthickendedmatteror layer,atambientsediment temperature.
2. Densityat 0.89gm/cm3 IS:144829.5C(max.)
3. Kinematic 27cSt IS:1448Viscocityat27C(Max.)
4. Interfacial 0.04N/m IS:6104tensionat27C(Min.)
5. Flashpoint 140C IS:1448Penskey-Marten(closed)(Min.)
6. Pourpoint -6C IS:1448(Max.)
7. Neutralization 0.03mgKOH/gm IS:335value(total Appendix-Aacidity)(Max.)
8. Corrosivesulph- Non-Corrosive IS:335ur(intermsof Appendix-Bclassificationofcopperstrip)
9. Electricstrength
(breakdownvoltage)(Min.)
(a) Newuntreated 30kV(rms)(if IS:6792oil thisvalueisnot
attainedtheoilshallbetreated)
(b) Aftertreatment 60kV(rms)
10. Dielectricdiss-ipationfactor 0.002 IS:6262
(tandelta)at90C(Max.)
Tech Specification, Section: Autotransformer Page 11 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
12/54
11. Resistivity IS:6103(Min.)(ohmcm)
(a) at90C 35x1012
(b) at27C 1500x1012
12. Oxidationstability
(a) Neutralization 0.40mgKOH/gmvalueafteroxidation(Max.)
(b) Totalsludgeafter 0.10percentbyoxidation(Max) weight
13. Presenceof Theoilshall IS:335Appendix-Doxidation notcontaininhibitor anti-oxidant
additives14. Watercontent
(Max.)
(i) Newuntreated 50ppm IS:2362oil
(ii) Aftertreatment 15ppm IS:1866
15. AgeingCharacter-isticsafter96hrsasperASTM-D1934/IS:12177withcatalyst(copper)
(a) Resistivity(Min)(ohmcm)
at27C 2.5x1012at90C 0.2x1012
(b) Tandeltaat90C(Max.) 0.2
(c) Totalacidity(Max.) 0.05mgKOH/gm
(d) Sludgecontentwt.(Max.) 0.05%(Byweight)
16. PCBcontent Lessthan2ppm
Tech Specification, Section: Autotransformer Page 12 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
13/54
3.4.2 Subsequentlyoilsamplesshallbedrawn
i) Priortofillinginmaintankatsiteandshallbetestedfor
1. BDV
2. Moisturecontent
TheacceptancenormsforaboveparametersshallbeasperCl.3.4.1above.
ii) Prior to energisation at site and shall be tested for followingproperties
&acceptancenorms:
1. BDV(kVrms) 60kV(min.)
2. Moisturecontent 15ppm(max.)
3. Tan-deltaat90C 0.05(max.)
4. Resistivityat90C 1x1012ohm-cm(min.)
5. InterfacialTension 0.03N/m(min.)
3.4.3 Atmanufacturer'sworksoilsampleshallbedrawnbeforeandafterheatruntestandshallbetestedforfollowing:
1) BDV 60kV(min.)
2) Moisturecontent 15ppm
3) Dissolvedgasanalysis:
SamplesforDGAshallbetakenfromsamplingdevicewithin24hourspriortocommencementoftemperaturerisetestandimmediatelyafterthistest.
TheacceptancenormswithreferencetovariousgasgenerationratesduringthetemperaturerisetestshallbeasperIS:10593(basedonIEC-599).
3.4.4 Sufficientquantityofoilnecessaryformaintainingrequiredoillevelintank,radiators,conservatoretctillcommissioningshallbesupplied.
3.5 TerminalArrangements
3.5.1 Bushings
3.5.1.1The electrical and mechanical characteristics of bushings shall be inaccordancewithIS:2099andIS:3347.
Tech Specification, Section: Autotransformer Page 13 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
14/54
3.5.1.2 Bushingforvoltageof420kV,245kV,145kVand52kVshallbeoftheoilfilledcondensertype.36kVbushingshallbesolidporcelainoroilcommunicating type. Mountingdimensionsof 420kV, 245 kV,145kVand 52 kV bushing shall be as per drawing No.0000-T-E-A-001.
Dimensionsof36kVbushingshallconformtoIS:3347Part-V.
3.5.1.3 Oil Filled condenser typebushing shall beprovidedwith at least thefollowingfittings.:
(a) Oillevelgauge.
(b) Oilfillingpluganddrainvalveifnothermeticallysealed.
(c) Tapforcapacitanceandtandeltatest.
3.5.1.4 Where current transformers are specified, the bushings shall beremovablewithoutdisturbingthecurrenttransformers.
3.5.1.5 Bushingsofidenticalratingshallbeinterchangeable.
3.5.1.6 Porcelainusedinbushingmanufactureshallbehomogenous,freefromlamination,cavitiesandotherflawsorimperfectionsthatmightaffectthemechanicalordielectricqualityandshallbethoroughlyvitrified,toughandimpervioustomoisture.
3.5.1.7 Clampsandfittingsshallbeofhotdipgalvanisedsteel.
3.5.1.8 Bushing turrets shall be provided with vent pipes, to route any gascollectionthroughtheBuchholzrelay.
3.5.1.9 Noarcinghornsshallbeprovidedonthebushings.
3.5.1.10Suitableinsulatingcap(preferablyofporcelain)shallbeprovidedontheterminalofBushingoftertiarywindingtoavoidaccidentalexternalshortcircuit.
3.6 TerminalMarking
TheterminalmarkingandtheirphysicalpositionshallbeasperIS:2026.
3.7 NeutralEarthingArrangement
3.7.1 Theneutralterminalofautotransformershallbebroughttothegroundlevelbyabrass/tinnedcoppergroundingbar,supportedfromthetankbyusingporcelaininsulators.Theendofthebrass/tinnedcopperbarshallbebroughttothebottomofthetank,ataconvenientpoint,formakingboltedconnectiontotwo(2)75x12mmgalvanisedsteelflatsconnectedtoEmployer'sgroundingmat.
3.8 CoolingEquipmentanditsControl
Tech Specification, Section: Autotransformer Page 14 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
15/54
3.8.1 CoolingEquipment
3.8.1.1 Thecoolershallbedesignedusing2x50%radiatorbanks. Designofcoolingsystemshallsatisfytheperformancerequirements.
3.8.1.2 Eachradiatorbankshall have itsown cooling fans,oilpumps,oil flowindicator,shutoffvalvesatthetopandbottom(80mmsize),liftinglugs,topandbottomoilfillingvalves,airreleaseplugatthetop,adrainandsamplingvalveandthermometerpocketfittedwithcaptivescrewcapontheinletandoutlet.
3.8.1.3 Requirednumberof standbyfansofapproximately20%capacityshallalsobeprovidedwitheachradiatorbank.
3.8.1.4 Cooling fansshallnotbedirectlymountedonradiatorbankwhichmay
causeunduevibration.Theseshallbelocatedsoastopreventingressof rainwater. Each fanshallbesuitablyprotectedbygalvanisedwireguard. The exhaust air flow from cooling fan shall not be directedtowardsthemaintankinanycase.
3.8.1.5 Two(2),100%centrifugaloraxialonlineoilpumps (outofwhichonepump shall be standby) shall be provided with each radiator bank.MeasuresshallbetakentopreventmaloperationofBuchholzrelaywhenalloilpumpsaresimultaneouslyputintoservice.Thepumpshallbesodesignedthatuponfailureofpowersupplytothepumpmotor,thepumpimpellerwillnotlimitthenaturalcirculationofoil.
3.8.1.6 Anoilflowindicatorshallbeprovidedfortheconfirmationoftheoilpumpoperatinginanormalstate.Anindicationshallbeprovidedintheflowindicatortoindicatereverseflowofoil/lossofoilflow.
3.8.1.7 Coolingfansandoilpumpmotorsshallbesuitableforoperationfrom415volts,threephase50HzpowersupplyandshallconformtoIS:325.Eachcoolingfanandoilpumpmotorsshallbeprovidedwithstarterthermaloverloadandshortcircuitprotection.Themotorwindinginsulationshallbeconventionalclass'B'type.MotorsshallhavehoseproofenclosureequivalenttoIP:55asperIS:4691.
3.8.1.8 Thecooleranditsaccessoriesshallpreferablybehotdipgalvanisedorcorrosionresistantpaintshouldbeappliedtoit.
3.8.1.9 Expansion joint shallbeprovided, oneeachon topandbottomcoolerpipeconnections.
3.8.1.10 Airreleasedeviceandoilplugshallbeprovidedonoilpipeconnections.Drainvalvesshallbeprovidedinorderthateachsectionofpipeworkcanbedrainedindependently.
3.8.2 CoolingEquipmentControl(ONAN/ONAF/OFAFCOOLING)
Tech Specification, Section: Autotransformer Page 15 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
16/54
3.8.2.1 Automatic operation control of fans/pumps shall be provided (withtemperature change) from contacts of winding temperature indicator.TheContractorshallrecommendthesettingofWTIforautomaticchangeover of cooler control fromONAN toONAFand then toOFAF. Thesettingshallbesuchthathuntingi.e.frequentstart-upoperationsfor
smalltemperaturedifferentialdonotoccur.
3.8.2.2 Suitablemanualcontrol facility for cooler fans and oil pumps shall beprovided.
3.8.2.3 Thechangeovertostandbyoilpumpincaseoffailureofserviceoilpumpshallbeautomatic.
3.8.2.4Selectorswitchesandpushbuttons,shallalsobeprovidedinthecoolercontrolcabinettodisconnecttheautomaticcontrolandstart/stopthefansandpumpmanually.
3.8.3 IndicatingDevices
Followinglampindicationsshallbeprovidedincoolercontrolcabinet:
a) ControlSupplyfailure.
b) Coolingfanfailureforeachbank.
c) Coolingpumpfailureforeachpump.
d) Nooilflow/reverseoilflowforpumps.
e) Commonthermaloverloadtrip.
Onepotentialfreeinitiatingcontactforalltheaboveconditionsshallbewiredindependentlytotheterminalblocksofcoolercontrolcabinet.
3.8.4 Valves
3.8.4.1 Allvalvesuptoandincluding100mmshall beofgunmetalorofcaststeel/castiron.Largervalvesmaybeofgunmetalormayhavecastironbodieswithgunmetalfittings.Theyshallbeoffullwaytypewithinternal
screwandshallopenwhenturnedcounterclockwisewhenfacingthehandwheel.
3.8.4.2 Suitablemeansshallbeprovidedforlockingthevalvesintheopenandclosepositions. Provisionisnotrequiredforlocking individualradiatorvalves.
3.8.4.3 Each valve shall be provided with the indicator to show clearly thepositionofthevalve.
3.8.4.4 Allvalvesflangesshallhavemachinedfaces.
Tech Specification, Section: Autotransformer Page 16 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
17/54
3.8.4.5 All valves in oil line shall be suitable for continuous operation withtransformeroilat100C.
3.8.4.6 Theoilsamplingpointformaintankshallhavetwoidenticalvalvestobeputinseries.Oilsamplingvalveshallhaveprovisiontofixrubberhoseof
10mmsizetofacilitateoilsampling.3.8.4.7 A valve or other suitable means shall be provided to fix the on line
dissolvedgasmonitoringsystemtofacilitatecontinuousdissolvedgasanalysis.Thelocation&sizeofthesameshallbefinalisedduringdetailengineeringstage.
3.8.4.8 Suitablevalvesshallbeprovided totakesampleofoilfrom theOLTCchamberduringoperationofthetransformer.
3.8.4.9 Aftertesting,insidesurfaceofallcastironvalvescomingincontactwithoilshallbeappliedwithonecoatofoilresistingpaint/varnishwithtwo
coatsof redoxide zincchromateprimer followedbytwo coats of fullyglossyfinishingpaintconforming toIS:2932andofashade(preferablyred or yellow) distinct and different from that of main tank surface.OutsidesurfaceexceptgasketsettingsurfaceofbutterflyvalvesshallbepaintedwithtwocoatsofredoxidezincchromateconformingtoIS:2074followedbytwocoatsoffullyglossyfinishingpaint.
3.8.4.10 Allhardwareusedshallbecadmiumplated/electrogalvanised.
3.9 TapChangingEquipment
3.9.1 TapChangeSwitchGeneralRequirement
OLTCshallbemotoroperatedforlocalaswellasremoteoperation.Anexternalhandleshallbeprovidedforlocalmanualoperation.Thishandleshallbesuitableforoperationbyamanstandingatgroundlevel.
3.9.2 OnLoadTapChangingGear(OLTC)
3.9.2.1 Each single/ three phase transformer shall be provided with voltagecontrol equipment of the tap changing type for varying its effectivetransformation ratio whilst the transformers are on load and without
producingphasedisplacement.
3.9.2.2 The requirements of on load tapchanging equipment are given herebelow:
a) The current diverting contacts shall be housed in a separate oilchamber not communicating with the oil in main tank of thetransformer.
b) Thecontactsshallbeaccessiblefor inspectionwithout loweringoillevelinthemaintankandthecontacttipsshallbereplaceable.
Tech Specification, Section: Autotransformer Page 17 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
18/54
c) TheBiddershallindicatethesafeguardsinordertoavoidharmfularcingatthecurrentdivertingcontactsintheeventofoperationoftheOLTCgearunderoverloadconditionsofthetransformer.NecessarytoolsandtacklesshallbefurnishedformaintenanceofOLTCgear.
d) The OLTC oil chamber shall have oil filling and drain plug, oilsamplingvalve,reliefventandlevelglass.Itshallalsobefittedwithaoilsurgerelaytheoutletofwhichshallbeconnectedtoaseparateconservatortank.
e) The diverter switch or arcing switch shall be designed so as toensurethat its operation once commenced shall be completedindependentlyofthecontrolrelaysorswitches,failureofancillarysupplies etc.To meet any contingency which may result inincompleteoperationofthediverterswitch,adequatemeansshallbeprovidedtosafeguardthetransformeranditsancillaryequipment.
f) Tapchangershallbesomountedthatbellcoveroftransformercanbelifted without removingconnectionsbetweenwindingsandtapchanger.
g) Local OLTC control cabinet shall be mounted on the tank inaccessible position. It should be adequately ventilated andprovidedwithanti-condensationmetalcladheaters.Allcontactorsrelaycoilsandotherpartsshallbeprotectedagainstcorrosion,deteriorationduetocondensation,fungietc.
h) Operatingmechanismforonloadtapchangershallbedesignedtogothroughonestepoftapchangepercommand.Subsequenttapchangesshallbeinitiatedonlybyaneworrepeatcommand.
i) On load tap changer shall be equipped with a time delayedINCOMPLETESTEPalarmconsistingofanormallyopencontactwhich closes, if the tap changer fails to make a complete tapchange.Thealarmshallnotoperateformomentarylossofauxiliarypower.
j) Theselsynunitsorapprovedequivalentsshallbe installedinthe
localOLTCcontrolcabinettoprovidetappositionindicationforthetransformer.TheBiddershallalsoprovideasetofinstrumentsfortap position indication in the control room. Complete mountingdetailsshallbeincludedintheapproveddiagram.
k) Transformer on load tap shall be equipped with a fixed resistornetworkcapableofprovidingdiscretevoltagestepsforinputtothesupervisorysystem.
l) Limit switches shall be provided to prevent overrunning of themechanismandshallbedirectlyconnectedinthecircuitofthe
operatingmotor.Inaddition,amechanicalstopshallbeprovidedtopreventover-runningofthemechanismunderanycondition.
Tech Specification, Section: Autotransformer Page 18 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
19/54
m) Limit switches may be connected in the control circuit of theoperating motor provided that a mechanical de-clutchingmechanismisincorporated.
n) Thermal device or othermeans shall be provided toprotect themotorandcontrolcircuit. All relays,switches, fusesetc. shallbemountedinthelocalOLTCcontrolcabinetandshallbeclearlymarkedforthepurposeofidentification.
o) Apermanently legible lubrication chart if required, shall be fittedwithinthelocalOLTCcontrolcabinet.
p) Any 'DROP DOWN' tanks associated with the tap changingapparatusshallbefittedwithguiderodtocontrolthemovementsduringliftingorlowering.
q) Afivedigitcountershallbefittedtothetapchangingequipmenttoindicatethenumberofoperationscompleted.
r) All relays and operating devices shall operate correctly at anyvoltagebetweenthelimitsspecified.
s) Itshallnotbepossibletooperatetheelectricdrivewhenthemanualoperatinggearisinuse.
t) Itshallnotbepossibleforanytwocontrolstobeinoperationatthe
sametime.
u) The equipment shall be suitable for supervisory control andindication with make before break multi-way switch, having onepotential freecontact foreach tapposition. This switch shall beprovided in addition to any other switch/switches which may berequiredforremotetappositionindication.
v) Operationfromthe localorremotecontrolswitchshallcauseonetap movement only until thecontrol switch is returned to the offpositionbetweensuccessiveoperation.
w) Allelectricalcontrolswitchesandthelocaloperatinggearshallbeclearlylabelledinasuitablemannertoindicatethedirectionoftapchanging.
x) TransferofsourceintheeventoffailureofoneACsupplyshallnotaffectthetapchanger.
3.9.3 OLTCControlofThreePhaseTransformers
Eachthreephasetransformershallbesuitableforlocalandremote
control.Thecontrolfeatureshallprovidethefollowing:
Tech Specification, Section: Autotransformer Page 19 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
20/54
3.9.3.1 LocalElectricalControl
(a) 'Local-remote' selector switch mounted in the local OLTC controlcabinetshallswitchcontrolofallloadtapchangersasfollowings:
i) Whentheselectorswitchisin'local'position,itshallbepossibletooperatethe'raise-lower'controlswitchesspecified inclause3.9.3.1(b) below. Remote control of the raise-lower functionsshallbeprevented.
ii) Whentheselectorswitchisin'remote'positionthelocalOLTCcontrolcabinetmounted'raise-lower'switchspecifiedinclause3.9.3.1(b) belowshall be in-operative. Remote control of theraise/lowerfunctionshallbepossiblefromtheremotecontrolpanel.The'local-remote'selectorswitchshallhaveatleasttwo
spare contacts per position which are closed in thatpositionbutopenintheotherposition.
(b) A'raise-lower'controlswitch/pushbuttonshallbeprovidedinthelocalOLTCcontrolcabinet.Thisswitchshallbeoperativeonlywhen'local
remote'selectorswitchisin'local'position.
(c) AnOFF-ONtapchangercontrolswitchshallbeprovidedinthelocalOLTCcontrolcabinetofthetransformer.Thetapchangershallbein-operativeintheOFFposition.AlsotheOFF-ONswitchshallhaveatleastonesparecontactperpositionwhichisclosedinthatposition
butopenintheotherposition.
3.9.3.2 ManualControl
ThecrankingdeviceformanualoperationoftheOLTCgearshallberemovableandsuitableforoperationbyamanstandingatgroundlevel.Themechanismshallbecompletewiththefollowing:
a) Mechanicaltappositionindicatorwhichshallbeclearlyvisiblefromnear thetransformer.
b) Amechanicaloperationcounter.
c) Mechanical stops to prevent over-cranking of the mechanismbeyondthe extremetappositions.
d) Themanualcontrol considered as backup tothemotor operatedloadtapchangercontrolshallbeinterlockedwiththemotortoblockmotor start-up during manual operation. The manual operatingmechanismshallbelabelledtoshowthedirectionofoperationforraisingtheHVterminalvoltageandvice-versa.
3.9.3.3 RemoteElectricalGroupControl
Tech Specification, Section: Autotransformer Page 20 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
21/54
TheOLTCcontrolschemeofferedshallhaveprovisionofremoteelectricalgroup control during the parallel operation of transformer. This is inadditiontoindependentcontrolofOLTC:
i) AfourpositionselectorswitchhavingMaster,Follower,Independent
andOffpositionshallbeprovidedintheremoteOLTCcontrolpanelforeachtransformer.ThisshallbewiredtoenableoperatortoselectoperationofOLTCineitherMaster,FollowerorIndependentmode.
ii) Outofsteprelayswithtimercontactsshallalsobeprovidedtogivealarmandindicationincasetappositioninallthetransformersundergroupcontrolarenotinsameposition.
iii) MasterPosition
If the selector switch is inMasterposition, it shall bepossible to
controltheOLTCunitsinthefollowermodebyoperatingthecontrolsof the master unit. Independent operation of the units underFollowermodeshallhavetobeprevented.Howevertheunitsunderindependentmodewillbecontrolledindependently.
iv) FollowerPosition
IftheselectorswitchisinFollowermode,controlofOLTCshallbepossibleonlyfrompaneloftheMasterunit.
v) IndependentPosition
InthispositionofSelectorSwitch,ControlofOLTCofindividualunitshallonlybepossible.
3.9.4 OLTCControlofsinglephaseTransformer
ForthreesinglephaseunitsoperatingasthreephasebanktheOLTCgearshallbesuitableforlocalandremotecontrol.Thecontrolfeaturesshallprovidethefollowing:
i) LocalElectricalControl
a) 'Local-remote'selectorswitchmountedinthelocalOLTCcontrolcabinetshallswitchcontrolofallonloadtapchangersasunder:
Whentheselectorswitchisin'local'position,itshallbepossibletooperateanyofthe'raise-lower'controlswitchesspecifiedinsection(iii)and(iv)below.
Controloftheraise-lowerfunctionfromthecontrolpanelshallbeprevented.
When the selector switch is 'remote' position the raise-lowerfunctionsformswitches in localOLTCcontrolcabinetsaswell as
Tech Specification, Section: Autotransformer Page 21 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
22/54
cooler control cabinet specified in Section (iii) and (iv) shall beinoperative.Remotecontroloftheraise-lowerfunctionofthethreephasetransformerbanksshallbepossiblefromthecontrolpanel.
Theremote-localselectorswitchshallbehaveatleasttwospare
contactsperposition.
b) 'Independent-combined selector switch shall be provided forsinglephasetransformeronlyandshallbemountedinthecoolercontrolcabinet.Thisswitchshallcontroltheonloadtapchangersasfollows.
Whentheselectorswitchincombinedposition,itshallbepossibletoraise-lowertapsbyoperatingthecombined'raise-lower'switchincoolercontrolcabinetortheremoteraise-lowerswitch.Independentoperationofeachsinglephasetransformerwillbeprevented.
When the selector switch is in independent position it shall bepossible to raise-lowertapsby operating individuallyeach singlephase transformer through their individual 'raise-lower' controlswitch mounted in Local OLTC Control Cabinet. Combinedoperation of all the three (3) single phase transformers will beprevented.
c) Acombined raise-lower control switchshall beprovided in thecooler control cabinet for a bank of three single phasetransformers only. This switch shall be functional only when
'local-remote'selectorswitchisinlocalpositionand'Independentcombined'selectorswitchisincombinedposition.
d) An individual 'raise-lower'controlcabinet foreachsinglephasetransformer. This switch shall be functional only when 'local-remote' selector switch is in local position and 'individual-combined'selectorswitchisinindividualposition.
ii) LocalManualcontrol
The cranking device for manual operation for OLTC gear shall beremovableandsuitableforoperationbyamanstandingatgroundlevel.
Themechanismshallbecompletewiththefollowing.
a) Mechanicaltappositionindicatorwhichshallbeclearlyvisiblefromnearthetransformer.
b) Amechanicaloperationcounter.c) Mechanical stops to prevent over-crankingof themechanismbeyond
theextremetappositions.d) Themanualcontrol consideredasback upto themotor operatedon
loadtapchargercontrolshallbeinterlockedwiththemotortoblockmotor start-up during manual operation. The manual operatingmechanism shall be labelled to show the direction of operation for
raisingthevoltageandvice-versa.iii) RemoteElectricalGroupControl
Tech Specification, Section: Autotransformer Page 22 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
23/54
The remoteOLTCschemeofferedshall haveprovisionto raiseor lowertaps only for the complete bank of three single phase transformers.Individual single phase OLTC operation shall not be possible from theremotecontrolpanel.
TheOLTCcontrolschemeshallhaveprovisionofremoteelectricalgroupcontrolwhenthethreephasebankisinparalleloperationwiththreephasetransformers/threephasebanksofsinglephasetransformers.
a) A four positionselector switch havingMaster, Follower, IndependentandOffpositionshallbeprovidedintheremoteOLTCcontrolpanelforthree(3)phasebankofsinglephasetransformers.Thisshallbewiredtoenable the operator to select operation of OLTC in either Master,FollowerorIndependentmode.
b) Out of step relayswith timercontacts shall alsobeprovided to givealarmandindicationincasetapsofalthetransformersundercontrolarenotinsameposition.
c) MasterPosition
Iftheselectorswitchisinmasterposition,itshallbepossibletocontroltheOLTCunitsofothertransformerbanks/threephasetransformerinthefollowermadebyoperationthemasterunit.
d) FollowerPosition
IftheselectorswitchisinFollowerpositioncontrolofOLTCshallbepossibleonlyfrompanelwheremastermodeisselected.
e) IndependentPosition
Inindependentpositionofselectorswitch,controlofOLTCshallbepossibleonlyfromthepanelwhereindependentmodeisselected.
3.9.5 Thecontrolcircuitsshallcomplywithfollowingconditions:
3.9.5.1 Aninterlocktocutoffelectricalcontrolautomaticallyuponrecoursebeingtakentothemanualcontrolinemergency.
3.9.5.2 Reinforcement of the initiating impulse for a tap change, ensuring apositivecompletiononceinitiatedtothenext(higherorlower)tap.
3.9.5.3 "Step-by-Step" operation ensuringonly one tap change from each tapchangingimpulseandalock-outofthemechanismifthecontrolswitch(orpushbutton)remainsinthe"operate"position.
3.9.5.4 Aninterlocktocut-outelectricalcontrolwhenittendstooperatethegear
beyondeitheroftheextremetappositions.
Tech Specification, Section: Autotransformer Page 23 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
24/54
3.9.5.5 Anelectricalinterlocktocut-offacounterimpulseforreversestepchangebeing initiatedduringaprogressingtapchangeanduntil themechanismcomestorestandresetscircuitsforafreshposition.
3.9.5.6 Tap change in progress indication shall be provided by means of an
indicatinglampat theEmployer'scontrolpanel. Necessarycontacts forthisandforremotetappositionindicatoratEmployer'scontrolpanelshallbeprovidedbytheBidder.
3.9.5.7 Protective apparatus, considered essential by the Bidder according tospecialitiesofthegear.
3.10 LocalOLTCControlCabinet,CoolerControlCabinetand RemoteTapChangerControlPanel
3.10.1 Eachsingle/threephasetransformerunitshallbeprovidedwithlocalOLTC
controlcabinet,coolercontrolcabinetandRTCCpanel.
3.10.2 The sheet steel used for cooler controlcabinet and local OLTCcontrolcabinetshallbeatleast2.5mmthick.ThedegreeofprotectionshallbeIP:55 in accordance with IS:13947. The gaskets used shall be ofneoprenerubber.Alltheseparatelymountedcabinetsandpanelsshallbefreestandingfloormountedtypeandhavedomedorslopingroof.Allthecontrolcabinetsshallbeprovidedwithsuitableliftingarrangement.
3.10.3 Aspaceheater,andcubiclelightingwithON-OFFswitchshallbeprovidedineachpanel.
3.10.4 Necessaryshortingofterminalsshallbedoneatthecoolercontrolcabinet,local OLTC cabinet and remote OLTC panel. All the CT secondaryterminals in the cooler control cabinet shall have provision for shortcircuitingtoavoidCTopencircuitwhileitisnotinuse.
3.10.5 CoolerControlCabinet
3.10.5.1 Thecoolercontrolcabinetshall haveall necessarydevicesmeant forcoolercontrolandlocaltemp.indicators.AllthecontactsofvariousprotectivedevicesmountedonthetransformerandallthesecondaryterminalsofthebushingCTsshallalsobewireduptotheterminalboard
in the cooler controlcabinet. All thenecessary terminals for remoteconnectiontoEmployer'spanelshallbewireduptothecoolercontrolcabinet.
3.10.5.2 Thecoolercontrolcabinetshallhavetwo(2)sections.Onesectionshallhavethecontrolequipmentexclusivelymeant forcoolercontrol. Theothersectionshallhousethetemperatureindicators,aux.CTsandtheterminalboardsmeantforterminationofvariousalarmandtripcontactsaswellasvariousbushingCTsecondary.AlternativelythetwosectionsmaybeprovidedastwoseparatepanelsdependingonthestandardpracticeoftheBidder.
Tech Specification, Section: Autotransformer Page 24 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
25/54
3.10.5.3 Thetemperatureindicatorsshallbesomountedthatthedialsareabout1200mm fromground level. Glazed door of suitable size shall beprovidedforconvenienceofreading.
3.10.5.4 Deleted.
3.10.6 LocalOLTCControlCabinet
The Local OLTC control cabinet shall house all necessary devicesmeantforOLTCcontrolandindication.Itshallbecompletewiththefollowing:
I) A circuit breaker/contactor with thermal overload devices forcontrolling theACAuxiliarysupplytotheOLTCmotor.
ii) Cubiclelightwithdoorswitch.
iii) Spaceheaterstopreventcondensationofmoisture.
iv) Padlockingarrangementforhingeddoorofcabinet.
v) CableterminalglandsforpowerandcontrolcablestotheOLTCgear.
3.10.7 RemoteTapChangerControlPanel.
3.10.7.1 TheContractor shall supply a Remote TapChanger Control (RTCC)
panelsuitableforremoteoperationofOnloadtapchanginggear.
3.10.7.2 TheRTCCpanelshallhouseactuatingswitchforelectricalraise/lowercontrol,tappositionindicator,signallampsfor"Tapchangeinprogress"and"Tapchangeroutofstep",andallotherauxiliarydevicesforremoteelectricalcontroloftheOLTC.Fortappositionindicator,thedualoutputtypeOLTCtransducershallbeprovidedintheRTCCpanel.TheoneoftheoutputofthistransducershallbeusedforlocalindicationoftappositioninRTCCpanelandotheroutput(0-10mAor4-20mAshallbeusedforRTUs.
3.10.7.3TheRTCCpanelshallbelocatedinEmployer'scontrolroom.Thesize&colouroftheRTCCpanelshallmatchwithEmployer'scontrolpanel.Thematchingdetailsshallbefurnishedatthetimeofaward.
3.11 AuxiliaryPowerSupplyofOLTC,CoolerControlandPowerCircuit
3.11.1 Twoauxiliarypowersupplies,415volt, threephasefour(4)wireshallbeprovidedbytheEmployeratcoolercontrolcabinetforOLTCandcoolercontrolandpowercircuit.
3.11.2 All loads shall be fed byone of the two feeders through anelectrically
interlockedautomatictransferswitchhousedinthecoolercontrolcabinetforonloadtapchangercontrolandcoolercircuits.
Tech Specification, Section: Autotransformer Page 25 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
26/54
Designfeaturesofthetransferswitchshallincludethefollowing:
a) Provisionfortheselectionofoneofthefeederasnormalsourceandotherasstandby.
b) Uponfailureofthenormal source, the loads shall beautomaticallytransferredafteranadjustabletimedelaytostandbysources.
c) Indicationtobeprovidedatcoolercontrolcabinetforfailureofnormalsource and for transfer to standby source and also for failure totransfer.
d) Automatic re-transfer tonormalsourcewithout anyintentional timedelayfollowingre-energizationofthenormalsource.
e) Boththetransferandthere-transfersshallbedeadtransfersandACfeedersshallnotbeparalleledatanytime.
3.11.3 PowerSupplyforOLTCCircuits
a) ACfeedershallbebroughttothelocalOLTCcontrolcabinetbytheContractoraftersuitableselectionatcoolercontrolcabinetforwhichdescriptionisgivenin3.11.2above,forcontrolpowercircuitofOLTC.
b) TheContractorshallderiveACpowerforOLTCcontrolcircuitryfromtheACfeederasmentionedabovebyusingappropriatelyrateddry
typetransformers.IfthecontrolcircuitisoperatedbyDCsupply,thensuitable main and standby converters shall be provided by theContractortobeoperatedfromACpowersource.
3.11.4 PowerSupplyforCoolerCircuits
3.11.4.1ControlandpowersuppliesaretobegivenforCoolercircuitsaftertheselectionasmentionedin3.11.2above.
3.11.4.2TheContractorshallderiveACpowerforCoolerControlCircuitryfromtheACfeederas mentionedabovebyusingappropriately rated dry type
transformer.IfthecontrolcircuitisoperatedbyDCsupplythensuitablemainandstandbyconvertorsshallbeprovidedbytheContractor,tobeoperatedfromACpowersource.
3.11.5 Necessary isolating switches and HRC fuses shall be provided atsuitablepointsasperEmployer'sapprovedscheme.
4 Fittings
4.1 The following fittings shall be provided with each three phasetransformercoveredinthisspecification:
Tech Specification, Section: Autotransformer Page 26 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
27/54
4.1.1 Conservatorformaintankwithoilfillingholeandcap,isolatingvalves,drainvalve,magneticoillevelgaugewithlowlevelalarmcontactsanddehydratingbreather..
4.1.2 ConservatorforOLTCwithdrainvalve,oilsurgeRelay,fillingholewith
cap,prismaticoillevelgaugeandsilicagelbreather.
4.1.3 Oilpreservationequipment.
4.1.4 Pressurereliefdeviceswithalarm/tripcontacts.
4.1.5 Buchholz relay double float/reed type with isolating valves on bothsides,bleedingpipewithpetcockattheendtocollectgasesandalarmandtripcontacts.
4.1.6 Airreleaseplug.
4.1.7 Inspectionopeningsandcovers.
4.1.8 Bushing with metal parts and gaskets to suit the terminationarrangement.
4.1.9 Winding temperature indicators for local and remotemounting. Oneremotewindingtemperatureindicatorwithafourpointselectorswitchshallbeprovidedforthethreewindingsforthreephaseunittohaveselectionofanyofthethreewindings.
4.1.10 Cover liftingeyes, transformer liftinglugs, jackingpads, towingholesandcoreandwindingliftinglugs.
4.1.11 Protectedtypemercuryoralcoholinglassthermometer.
4.1.12 Bottom and top filter valves with threaded male adaptors, bottomsamplingvalveanddrainvalve.
4.1.13 Ratinganddiagramplatesontransformersandauxiliaryapparatus.
4.1.14 Flangedbi-directionalwheels/Trolleyformovement
4.1.15 Coolercontrolcabinet.
4.1.16 Onloadtapchanginggear.
4.1.17 Coolingequipment.
4.1.18 Bushingcurrenttransformers.
4.1.19 Oilflowindicator.
4.1.20 Drainvalves/plugsshallbeprovidedinorderthateachsectionofpipeworkcanbedrainedindependently.
Tech Specification, Section: Autotransformer Page 27 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
28/54
4.1.21 Terminalmarkingplates.
4.1.22 Valvesscheduleplates.
4.2 The fittings listed above are only indicative and other fittings whichgenerallyare required forsatisfactoryoperationof thetransformeraredeemedtobeincluded.
5 InspectionandTesting
TheContractorshallcarryoutacomprehensiveinspectionandtestingprogramme duringmanufacture of the equipment. An indication ofinspectionenvisagedbytheEmployerisgivenunderClause5.1.Thisishowevernot intended to formacomprehensiveprogrammeasit isContractor'sresponsibilitytodrawupandcarryoutsuchaprogrammein
the form of detailed quality plan duly approved by Employer fornecessaryimplementation.
5.1 Inspection
5.1.1 TankandConservator
5.1.1.1 Certificationofchemicalanalysisandmaterialtestsofplates.
5.1.1.2 Checkforflatness.
5.1.1.3 Electricalinterconnectionof top and bottombybraidedtinnedcopperflexible.
5.1.1.4 Welder'squalificationandweldprocedure.
5.1.1.5 Testingofelectrodesforqualityofbasematerialsandcoatings.
5.1.1.6 Inspectionofmajorweldpreparation.
5.1.1.7 Crackdetectionofmajorstrengthweldseamsbydyepenetrationtest.
5.1.1.8 Measurementoffilmthicknessof:
i) Oilinsolublevarnish.
ii) Zincchromatepaint.
iii) Finishedcoat.
5.1.1.9 Check correct dimensions between wheels, demonstrate turning ofwheelsthrough90Candfurtherdimensionalcheck.
Tech Specification, Section: Autotransformer Page 28 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
29/54
5.1.1.10Checkforphysicalpropertiesofmaterialsforliftinglugs,jackingpads,etc.AllloadbearingweldsincludingliftinglugweldsshallbesubjectedtoNDT.
5.1.1.11Leakagetestoftheconservator.
5.1.1.12Certificationofalltestresults.
5.1.2 Core
5.1.2.1 Sample testing of core materials for checking specific loss, bendproperties,magnetisationcharacteristicsandthickness.
5.1.2.2 Checkonthequalityofvarnishifusedonthestampings:
i) Measurementofthicknessandhardnessofvarnishonstampings.
ii) Solventresistancetesttocheckthatvarnishdoesnotreactinhotoil.
iii) Checkoverallqualityofvarnishbysamplingtoensureuniformshining colour, no bare spots, no over burnt varnish layer and nobubblesonvarnishedsurface.
5.1.2.3 Checkontheamountofburrs.
5.1.2.4 Bowcheckonstampings.
5.1.2.5 Checkfortheoverlappingofstampings.Cornersofthesheetaretobepart.
5.1.2.6 Visualanddimensionalcheckduringassemblystage.
5.1.2.7 Checkforinterlaminarinsulationbetweencoresectorsbeforeandafterpressing.
5.1.2.8 Checkoncompletedcore formeasurementofiron lossandcheck foranyhotspotbyexcitingthecoresoastoinducethedesignedvalueof
fluxdensityinthecore.
5.1.2.9 Visualanddimensionalchecksforstraightnessandroundnessofcore,thicknessoflimbsandsuitabilityofclamps.
5.1.2.10 Highvoltagetest(2kVforoneminute)betweencoreandclamps.
5.1.2.11 Certificationofalltestresults.
5.1.3 InsulationMaterial
5.1.3.1. Samplecheckforphysicalpropertiesofmaterials.
Tech Specification, Section: Autotransformer Page 29 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
30/54
5.1.3.2 Checkfordielectricstrength.
5.1.3.3 Visualanddimensionalchecks.
5.1.3.4 Checkforthereactionofhotoiloninsulatingmaterials.
5.1.3.5 Dimensionstabilitytestathightemperatureforinsulatingmaterial.
5.1.3.6 Trackingresistancetestoninsulatingmaterial
5.1.3.7 Certificationofalltestresults.
5.1.4 Winding
5.1.4.1 Sample check on winding conductor for mechanical properties andelectricalconductivity.
5.1.4.2 Visualanddimensionalchecksonconductorforscratches,dentmarksetc.
5.1.4.3 SamplecheckoninsulatingpaperforpHvalue,burstingstrengthandelectricstrength.
5.1.4.4 Checkforthereactionofhotoiloninsulatingpaper.
5.1.4.5 Checkforthebondingoftheinsulatingpaperwithconductor.
5.1.4.6 Check and ensure that physical condition of all materials taken forwindingsissatisfactoryandfreeofdust.
5.1.4.7 Checkforabsenceofshortcircuitbetweenparallelstrands.
5.1.4.8 Checkforbrazedjointswhereverapplicable.
5.1.4.9 Measurement of voltage ratio to be carried out when core/yoke iscompletelyrestackedandallconnectionsareready.
5.1.4.10 Conductorenameltestforcheckingofcracks,leakageandpinholes.
5.1.4.11 Conductorflexibilitytest
5.1.4.12Heatshrinktestforenamelledwire.
5.1.4.13 Certificationofalltestresults.
5.1.5 ChecksBeforeDryingProcess
5.1.5.1 Check condition of insulation on the conductor and between thewindings.
Tech Specification, Section: Autotransformer Page 30 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
31/54
5.1.5.2 Check insulationdistancebetween highvoltage connections, cablesandearthandotherliveparts.
5.1.5.3 Checkinsulatingdistancesbetweenlowvoltageconnectionsandearthandotherparts.
5.1.5.4 Insulationofcoreshallbetestedat2kV/minutebetweencoretoboltsandcoretoclampplates.
5.1.5.5 Checkforpropercleanlinessandabsenceofdustetc.
5.1.5.6 Certificationofalltestresults.
5.1.6 ChecksDuringDryingProcess
5.1.6.1 Measurementand recording of temperature, vacuumanddrying time
duringvacuumtreatment.
5.1.6.2 CheckforcompletenessofdryingbyperiodicmonitoringofIRandTandelta.
5.1.6.3 Certificationofalltestresults.
5.1.7 AssembledTransformer
5.1.7.1 Check completed transformer against approved outline drawings,provisionforallfittings,finishleveletc.
5.1.7.2 Testtocheckeffectiveshieldingofthetank.
5.1.7.3 Jackingtestwithoilonalltheassembledtransformers.
5.1.7.4 Dyepenetrationtestshallbecarriedoutafterthejackingtest.
5.1.8 BoughtOutItems
5.1.8.1 ThemakesofallmajorboughtoutitemsshallbesubjecttoEmployer'sapproval.
5.1.8.2 The Contractor shall also prepare a comprehensive inspection andtestingprogramme for all bought out/sub-contracted items and shallsubmitthesametotheEmployerforapproval.Suchprogrammeshallincludethefollowingcomponents:
a) BuchholzRelay.
b) Axlesandwheels.
c) Windingtemperatureindicatorsforlocalandremotemounting.
d) Oiltemperatureindicators.
Tech Specification, Section: Autotransformer Page 31 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
32/54
e) Bushings.
f) Bushingcurrenttransformers.
g) Coolercontrolcabinet.
h) Coolingequipment.
Tech Specification, Section: Autotransformer Page 32 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
33/54
i) Oilpumps.
j) Fans/AirBlowers
k) Tapchangegear.
l) Terminalconnectors.
TheabovelistisnotexhaustiveandtheContractorshallalsoincludeotherboughtoutitemsinhisprogramme.
5.2 FactoryTests
5.2.1 RoutineTests
All standard routine testsinaccordancewith IS:2026withdielectric tests
corresponding to Method 2 shall be carried out on each transformer.OperationanddielectrictestingofOLTCshallalsobecarriedoutasperIS:2026.
Following additional routine tests shall also be carried out on eachtransformer:
5.2.1.1 MagneticCircuitTest
After assembly each core shall be tested for 1 minute at 2000 Voltsbetweenallbolts,sideplatesandstructuralsteelwork.
5.2.1.2 OilleakagetestontransformertankasperClause5.2.7.1below.
5.2.1.3 Magneticbalancetest
5.2.1.4 Measurementofno-loadcurrentwith415V,50HzacsupplyonLVside.
5.2.1.5 Frequencyresponseanalysis(FRA)
5.2.1.6 Highvoltagewithstandtestshallbeperformedonauxiliaryequipmentandwiringaftercompleteassembly.
5.2.2 TypeTests
FollowingtypetestsshallbeconductedononeTransformerofeachrating:
5.2.2.1 Temp.RiseTestasperIS:2026(Part-II)
Gaschromatographicanalysisonoilshallalsobeconductedbeforeandafter this testandthevaluesshall be recorded in the test report. ThesamplingshallbeinaccordancewithIEC567.FortheevaluationofthegasanalysisintemperaturerisetesttheprocedureshallbeasperIS:9434
(basedonIEC:567)andresultswillbeinterpretedasperIS:10593(basedonIEC-599).
Tech Specification, Section: Autotransformer Page 33 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
34/54
The temperature rise test shall be conducted at a tap for the worstcombination of loading on the three windings of the transformer. TheContractorbeforecarryingoutsuchtestshallsubmitdetailedcalculationsshowingalternativespossible,onvarioustapsandforthethreetypesof
ratings of the transformer and shall recommend the combination thatresultsinhighesttemperatureriseforthetest.
5.2.2.2 TankvacuumTestasperCl.no.5.2.7.2(i)below.
5.2.2.3 TankpressureTestasperCl.no.5.2.7.2(ii)below.
5.2.2.4 Deleted.
5.2.2.5 Measurement of capacitance and tan delta to determine capacitancebetweenwindingandearth.
5.2.2.6 LightningImpulsewithstandtestinallphasesasper IS:2026(Astypetest,onlyfor220kVclass&below)
5.2.3 Additionaltypetests
Followingadditionaltypetestsotherthantypeandroutinetestsshallalsobecarriedoutononeunitofeachtype:
5.2.3.1 Measurement of zero Seq. reactance (As per IS:2026, for 3-phasetransformeronly.)
5.2.3.2 Measurementofacousticnoiselevel.
5.2.3.3 Measurementofpowertakenbyfansandoilpumps.
5.2.3.4 Measurementofharmoniclevelinnoloadcurrent.
5.2.3.5 Deleted.
5.2.3.6 Measurement of transferred surge on LV (tertiary) winding due to HVlightningimpulseandIVlightningimpulse.
5.2.4 Deleted
5.2.5 Routinetestsonbushings
Thefollowingtestsshallbeconductedonbushings
5.2.5.1Testforleakageoninternalfillings.
5.2.5.2 Measurement of creepage distance, dielectric dissipation factor andcapacitance.
5.2.5.3Drypowerfrequencytestonterminalandtapping.
Tech Specification, Section: Autotransformer Page 34 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
35/54
5.2.5.4 Partial discharge test followed by dielectric dissipation factor andcapacitancemeasurement.
5.2.6 TypeTestsonfittings:
Allthefollowingfittingsshallconformtotypetestsandthetypetestreportsshallbefurnishedbythecontractoralongwiththedrawingsofequipment/fittingsaspertheclauseno.9.2oftheSectionGTR.Thelistoffittingsandthetypetestrequirementis:
1. Bushing(TypeTestasperIS:2099/IEC:137)2. Buchholzrelay(TypeTestasperIS:3637andIP-55Testonterminalbox)3. OLTC(TemperatureRiseofcontact,Shortcircuitcurrenttest,Mechanical
test and Dielectric Test as per IEC:214 and IP-55 test on drivingmechanismbox)
4. CoolerControlcabinet(IP-55test)5. PressureReliefdeviceTest
ThepressureReliefDeviceofeachsizeshallbesubjectedtoincreaseinoilpressure.ItshalloperatebeforereachingthetestpressurespecifiedintransformertankpressuretestatCl.No.5.2.7.2(ii)below.Theoperatingpressureshallberecorded.Thedeviceshallsealoffafterexcesspressurehasbeenreleased.Theterminalbox/boxesofPRDshouldconformtodegreeofprotectionasperIP-55ofIS:13947.
6. MagneticOilLevelgauge&TerminalBoxforIP-55degreeofprotection.7. AirCell(Flexibleairseparator)Oilsidecoating,AirsideunderCoating,
AirsideoutercoatingandcoatedfabricasperIS:3400/BS:903/IS:7016.8. OTI&WTISwitchsetting&operation,Switchdifferential,Switchrating.9. OilpumpVacuumTestat250torrmaximum,oilpressuretestat1kg/cm2
for24hrs.,Temperaturerisetestbyresistancemethod,IP-55degreeofprotectionforterminalbox.
10.CoolingfanandmotorassemblyFreeairdelivery,Temperaturerise,soundlevel,runningatreducedvoltage,IP-55degreeofprotectionforterminalbox.
5.2.7 TankTests
5.2.7.1 RoutineTests
OilLeakageTest
All tanksandoil filledcompartmentsshall betested foroil tightnessbybeingcompletelyfilledwithairoroilofaviscositynotgreaterthanthatofinsulating oil conforming to IS:335 at the ambient temperature andapplyingapressureequaltothenormalpressureplus35KN/Sq.m(5psi)measuredatthebaseofthetank.Thepressureshallbemaintainedforaperiodofnotlessthan12hoursforoilandonehourforairduringwhichtimenoleakshalloccur.
5.2.7.2 TypeTests
Tech Specification, Section: Autotransformer Page 35 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
36/54
(i) VacuumTest
Onetransformertankofeachsizeshallbesubjectedtothespecifiedvacuum.Thetankdesigned forfullvacuumshallbe testedataninternal
pressureof3.33KN/Sq.mabsolute(25torr)foronehour.Thepermanentdeflectionofflatplateafterthevacuumhasbeenreleasedshallnotexceedthevaluesspecifiedbelow:
-------------------------------------------------------------------------------------HorizontalLength Permanentdeflectionofflatplate(inmm) (inmm)-------------------------------------------------------------------------------------
Uptoandincluding750 5.0
751to1250 6.5
1251to1750 8.0
1751to2000 9.5
2001to2250 11.0
2251to2500 12.5
2501to3000 16.0
Above3000 19.0
-------------------------------------------------------------------------------------
(ii) PressureTest
One transformer tank of each size, its radiator, conservator vessel andother fittings together or separately shall be subjected to a pressurecorresponding to twicethenormal headofoil or to thenormalpressureplus35KN/m2whicheverislowermeasuredatthebaseofthetankand
maintained foronehour. thepermanentdeflectionofflatplatesaftertheexcesspressurehasbeenreleasedshallnotexceedthe figurespecifiedaboveforvacuumtest.
5.2.8 Pre-ShipmentChecksatManufacturer'sWorks
5.2.8.1 Check for interchangeability of components of similar transformers formountingdimensions.
5.2.8.2 Check forproperpackingandpreservationofaccessorieslikeradiators,bushings, dehydrating breather, rollers, buchholz relay, fans, control
cubicle,connectingpipes,conservatoretc.
Tech Specification, Section: Autotransformer Page 36 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
37/54
5.2.8.3 Checkforproperprovisionforbracingtoarrestthemovementofcoreandwindingassemblyinsidethetank.
5.2.8.4 Gastightnesstesttoconfirmtightness.
5.2.8.5 Derivationofleakagerateandensuretheadequatereservegascapacity.
5.3 InspectionandTestingatSite
TheContractorshallcarryoutadetailedinspectionandtestingprogrammeforfieldactivitiescoveringareasrightfromthereceiptofmaterialstageupto commissioning stage. An indicativeprogramme of inspection asenvisagedbytheEmployerisgivenbelowandinthedocumentNo.OS/T&C/Bay/95 (Pre commissioning Procedures and Formats forsubstationbayequipment),whichwillbeavailableintherespectivesitesand shall be referred by the contractor. However, it is contractor's
responsibilitytodrawupandcarryoutsuchaprogrammedulyapprovedbytheEmployer.TestingofoilsampleatsiteshallbecarriedoutasperCl.3.4above.
5.3.1 ReceiptandStorageChecks
5.3.1.1 Check and record condition of each package, visible parts of thetransformeretc.foranydamage.
5.3.1.2 Checkandrecordthegaspressureinthetransformertankaswellasinthegascylinder.
5.3.1.3 Visualcheckforwedgingofcoreandcoilsbeforefillingupwithoilandalsocheckconditionsofcoreandwindingingeneral.
5.3.1.4 Check and record reading of impact recorder at receipt and verify theallowablelimitsaspermanufacturer'srecommendations.
5.3.2 InstallationChecks
5.3.2.1 Inspection and performance testing of accessories like tap changers,coolingfans,oilpumpsetc.
5.3.2.2 (i) Checkthedirectionofrotationoffansandpumps.
(ii) Checkthebearinglubrication.
5.3.2.3 Checkwholeassemblyfortightness,generalappearanceetc.
5.3.2.4 Oilleakagetest
5.3.2.5 Capacitance and tan delta measurement of bushing beforefixing/connectingto thewinding, contractorshall furnish thesevaluesfor
sitereference.
Tech Specification, Section: Autotransformer Page 37 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
38/54
5.3.2.6 Leakagetestonbushingbeforeerection.
5.3.2.7 Measureand record thedewpoint ofnitrogen in themain tankbeforeassembly.
5.3.3 CommissioningChecks
5.3.3.1 Checkthecolourofsilicagelinsilicagelbreather.
5.3.3.2 Checktheoillevelinthebreatherhousing,conservatortanks,coolingsystem,condenserbushingetc.
5.3.3.3 Checkthebushingforconformityofconnectiontothelinesetc,
5.3.3.4 Checkforcorrectoperationofallprotectiondevicesandalarms:
(i) Buchholzrelay.
(ii) Excessivewindingtemperature.
(iii) Excessiveoiltemperature.
(iv) Lowoilflow.
(v) Lowoillevelindication.
(vi) Fanandpumpfailureprotection.
5.3.3.5 Checkfortheadequateprotectionontheelectriccircuitsupplyingtheaccessories.
5.3.3.6 Check resistance of all windings on all steps of the tap changer.Insulationresistancemeasurementforthefollowing:
(i) Controlwiring.(ii) Coolingsystemmotorandcontrol.(iii) Mainwindings.(iv) Tapchangermotorandcontrol.
5.3.3.7 Checkforcleanlinessofthetransformerandthesurroundings.
5.3.3.8 Continuouslyobservethetransformeroperationatnoloadfor24hours.
5.3.3.9 Graduallyputthetransformeronload,checkandmeasureincreaseintemperatureinrelationtotheloadandchecktheoperationwithrespecttotemperatureriseandnoiseleveletc.
5.3.3.10 Phaseoutandvectorgrouptest.
5.3.3.11 Ratiotestonalltaps.
5.3.3.12 Magnetisingcurrenttest.
Tech Specification, Section: Autotransformer Page 38 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
39/54
5.3.3.13 CapacitanceandTandeltameasurementofwindingandbushing.
5.3.3.14 DGAofoiljustbeforecommissioningandafter24hoursenergisationatsite.
5.3.3.15Frequencyresponseanalysis(FRA).
5.3.3.16ContractorshallprepareacomprehensivecommissioningreportincludingallcommissioningtestresultsandforwardtoEmployerforfuturerecord.
6 TechnicalParameters
i)315MVAAuto ii)105MVAautoTransformer transformer
6.1.1 Rating-H.V./I.V : i)315MVA/ ii)105MVA/105MVA315MVA
LV(Tertiary) : 105MVAreactive ii)35MVAreactive&2and5MVAactive MVAactive
6.1.2 Cooling : I)ONAN/ONAF/OFAF
6.1.3 Ratingatdifferent
cooling : 60%/80%/100%
6.1.4 TypeofTransformer: ConstantohmicImpedancetype(Refernote1)
6.1.5 Voltageratio : 400/220/33kV
6.1.6 Frequency : 50Hz
6.1.7 Phases : Three
6.1.8 Impedance(ReferNote1)
i) HV-IVimpedanceat75C :
- Max.Voltagetap : 10.3%
- Principaltap : 12.5%
- Min.Voltagetap : 15.4%
ii) HV/LVimpedance : 60%*
Tech Specification, Section: Autotransformer Page 39 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
40/54
iii) IV/LVimpedance : 45%*
(*impedanceareminimumindicativeonly.)
6.1.9 Service : Outdoor
6.1.10 Duty : Continuous
6.1.11 Overloadcapacity : AsperIS:6600-1972/IEC-354
6.1.12 Temperatureriseover50CAmbientTemp.
Oftopoilmeasuredby thermometer : 50C
Ofwindingmeasuredbyresistancemethod : 55C
6.1.13 Max.designAmbienttemp. : 50C
6.1.14 Windings H.V. I.V. L.V.
i) SystemFaultlevel(kA) : 40 40 25
ii) 1.2/50microsec. : 1300 950 250impulsewithstandvoltagekVp
iii) 20/200/500micro : 1050 -- --secondswitchingsurgewithstandvoltagekVp
iv) Oneminutepower : -- -- 95frequencywithstand
voltageKV(rms)
v) Windingconnection : Star Star delta
vi) Neutral : Solidlygrounded --
vii) Insulation : Graded Graded --
6.1.15 VectorGroup : ------YNaOd11------
6.1.16 TapChanger
i) Taprange : Tapchangershallbelocatedonthe220kV
Tech Specification, Section: Autotransformer Page 40 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
41/54
sideoftheserieswindingforachieving10%ofHVvariationinthestepof1.25%.ItshallbeofconstantfluxvoltagevariationtypeasperCl.3.2ofIS:2026Part-IV-1977.
ii) Tapcontrol : Fullcapacity-onloadtapchangersuitableforgroup/independent,remote/localelectricalandlocalmanualoperationandbi-directionalpowerflow.
6.1.17 Bushing : HV IV Neut- LVral
i) Ratedvoltage(kV) : 420 245 36 52
ii) Ratedcurrent : 800 1250 800 3150
(Amp)
iii) 1.2/50microsec.lightningimpulse: 1425 1050 170 250withstandvoltage(kVp).
iv) 250/2500microsec. : 1050 -- -- --Switchingimpulsewithstandvoltage(kVp).
v) Oneminutepower : 630 460 75 95
frequencywithstandvoltagekV(rms)
vi) Minimumtotal : 10500 6125 9001300
creepagedistances(mm)
vii) Mounting : Tank Tank Tank Tankcover cover side side
6.1.18 Partialdischargelevel: 500pico-columb
6.1.19 Noiselevel : AsperNEMA-TR-1.
6.2.1 TechnicalParameters 167MVAsinglephaseautotransformer
6.2.1 Rating-H.V./I.V : 167MVA/167MVA
LV(Tertiary) : 55MVAreactive and2MVAactive
6.2.2 Cooling : ONAN/ONAF/OFAF
Tech Specification, Section: Autotransformer Page 41 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
42/54
6.2.3 Ratingatdifferentcooling : 60%/80%/100%
6.2.4 TypeofTransformer : Constantohmic
impedancetype(Refernote1)
6.2.5 Voltageratio : 400/220/33kV
6.2.6 Frequency : 50Hz
6.2.7 Phases : Three
6.2.8 Impedance(ReferNote1)
i) HV-IVimpedance
at75
C :- Max.Voltagetap : 10.3%
- Principaltap : 12.5%
- Min.Voltagetap : 15.4%
ii) HV/LVimpedance : 60%*
iii) IV/LVimpedance : 45%*
(*impedanceareminimumindicativeonly.)
6.2.9 Service : Outdoor
6.2.10 Duty : Continuous
6.2.11 Overloadcapacity : AsperIS:6600-1972/IEC-354
6.2.12 Temperatureriseover50CAmbientTemp.
Oftopoilmeasuredby thermometer : 50C
Ofwindingmeasuredbyresistancemethod : 55C
6.2.13 Max.designAmbienttemp. : 50C
6.2.14 Windings H.V. I.V. L.V.
i) SystemFaultlevel(kA) : 40 40 25
Tech Specification, Section: Autotransformer Page 42 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
43/54
ii) 1.2/50microsec. : 1300 950 250impulsewithstandvoltagekVp
iii) 20/200/500micro : 1050 -- --
secondswitchingsurgewithstandvoltagekVp
iv) Oneminutepower : -- -- 95frequencywithstandvoltageKV(rms)
v) Windingconnection : Star Star delta
vi) Neutral : Solidlygrounded --
vii) Insulation : Graded Graded --
6.2.15 VectorGroup : ------YNaOd11------
6.2.16 TapChanger
i) Taprange : Tapchangershallbelocatedonthe220kV
sideoftheserieswindingforachieving10%ofHVvariationinthestepof1.25%.Itshallbeofconstantfluxvoltagevariationtypeas
perCl.3.2ofIS:2026Part-IV-1977.
ii) Tapcontrol : Fullcapacity-onloadtapchangersuitableforgroup/independent,remote/localelectricalandlocalmanualoperationandbi-directionalpowerflow.
6.2.17 Bushing : HV IV Neut- LVral
i) Ratedvoltage(kV) : 420 245 36 52
ii) Ratedcurrent : 1250 2000 2000 3150(Amp)
iii) 1.2/50microsec.lightningimpulse: 1425 1050 170 250withstandvoltage(kVp).
iv) 250/2500microsec. : 1050 -- -- --Switchingimpulsewithstandvoltage(kVp).
v) Oneminutepower : 630 460 75 95
Tech Specification, Section: Autotransformer Page 43 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
44/54
frequencywithstandvoltagekV(rms)
vi) Minimumtotal : 10500 6125 9001300
creepagedistances(mm)
vii) Mounting : Tank Tank Tank Tankcover cover side side
6.2.18 Partialdischargelevel: 500pico-columbs
6.2.19 Noiselevel : AsperNEMA-TR-1.
6.3 TechnicalParameters 100 MVA,220/132 kV 3 phase Auto
transformer.
6.3.1 Rating-H.V./I.V : I)100MVA/100MVA
LV(Tertiary) : No
6.3.2 Cooling : I)ONAN/OFAF
6.3.3 Ratingatdifferentcooling : 60%/100%
6.3.4 TypeofTransformer: ConstantohmicImpedancetype(Refernote1)
6.3.5 Voltageratio : 220/132kV
6.3.6 Frequency : 50Hz
6.3.7 Phases : Three
6.3.8 Impedance(ReferNote1)
i) HV-IVimpedanceat75C :
- Max.Voltagetap : 10.3%
- Principaltap : 12.5%
- Min.Voltagetap : 15.4%
6.3.9 Service : Outdoor
6.3.10 Duty : Continuous
Tech Specification, Section: Autotransformer Page 44 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
45/54
6.3.11 Overloadcapacity : AsperIS:6600-1972/IEC-3546.3.12 Temperatureriseover
50CAmbientTemp.
Oftopoilmeasuredby thermometer : 50C
Ofwindingmeasuredbyresistancemethod : 55C
6.3.13 Max.designAmbienttemp. : 50C
6.3.14 Windings H.V. I.V.i) SystemFaultlevel(kA) : 40 31.5
ii) 1.2/50microsec. : 950 550impulsewithstandvoltagekVp
iii) 20/200/500micro : -- --secondswitchingsurgewithstandvoltagekVp
iv) Oneminutepower : 395 230frequencywithstand
voltageKV(rms)
v) Windingconnection : Star Star
vi) Neutral : Solidlygrounded
vii) Insulation : GradedGraded
6.3.15 VectorGroup : ------YNaOd11------
6.3.16 TapChanger
i) Taprange : Tapchangershallbelocatedonthe132kVsideoftheserieswindingforachieving5%to10%ofHVvariationinthestepof1.25%.ItshallbeofconstantfluxvoltagevariationtypeasperCl.3.2ofIS:2026Part-IV-1977.
ii) Tapcontrol : Fullcapacity-onloadtapchangersuitableforgroup/independent,remote/localelectricalandlocalmanualoperationandbi-directionalpowerflow.
6.3.17 Bushing : HV IV Neut-
Tech Specification, Section: Autotransformer Page 45 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
46/54
ral
i) Ratedvoltage(kV) : 245 145 36
ii) Ratedcurrent : 800 800 800
(Amp)
iii) 1.2/50microsec.lightningimpulse: 1050 650 170withstandvoltage(kVp).
iv) 250/2500microsec. : -- -- --Switchingimpulsewithstandvoltage(kVp).
v) Oneminutepower : 460 275 75
frequencywithstandvoltagekV(rms)
vi) Minimumtotal : 6125 3625 900creepagedistances(mm)
vii) Mounting : Tank Tank Tankcover cover side
6.4 TechnicalParameters 50MVA,132/66kV3phaseAutotransformer.
6.4.1 Rating-H.V./I.V : I)50MVA/50MVA
LV(Tertiary) : No
6.4.2 Cooling : I)ONAN/OFAF
6.4.3 Ratingatdifferentcooling : 60%/100%
6.4.4 TypeofTransformer: ConstantohmicImpedancetype
6.4.5 Voltageratio : 132/66kV
6.4.6 Frequency : 50Hz
6.4.7 Phases : Three
6.4.8 Impedance(ReferNote1)
i) HV-IVimpedance
at75C :
Tech Specification, Section: Autotransformer Page 46 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
47/54
- Max.Voltagetap : 8.26%
- Principaltap : 10.0%
- Min.Voltagetap : 12.34%
6.4.9 Service : Outdoor
6.4.10 Duty : Continuous
6.4.11 Overloadcapacity : AsperIS:6600-1972/IEC-354
6.4.12 Temperatureriseover50CAmbientTemp.
Oftopoilmeasuredby
thermometer : 50
C
Ofwindingmeasuredbyresistancemethod : 55C
6.4.13 Max.designAmbienttemp. : 50C
6.4.14 Windings H.V. I.V.i) SystemFaultlevel(kA) : 31.5 31.5
ii) 1.2/50microsec. : 550 325
impulsewithstandvoltagekVp
iii) 20/200/500micro : -- --secondswitchingsurgewithstandvoltagekVp
iv) Oneminutepower : 230 140frequencywithstandvoltageKV(rms)
v) Windingconnection : Star Star
vi) Neutral : Solidlygrounded
vii) Insulation : GradedGraded
6.4.15 VectorGroup : ------YnaO------
6.4.16 TapChanger
i) Taprange : Tapchangershallbelocatedonthe66kVsideoftheserieswindingforachieving+/to10%of
Tech Specification, Section: Autotransformer Page 47 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
48/54
7/29/2019 Auto%20transformerR4.pdf
49/54
7.3 Current transformer secondary leads shall be brought out to aweatherproof terminalboxneareachbushing. These terminalsshallbewiredouttocoolercontrolcabinet/marshallingboxusingseparatecablesforeachcore.
7.4 BushingCurrenttransformerparametersindicatedinthisspecificationaretentative and liable to changewithin reasonable limits. TheContractorshallobtainEmployer'sapprovalbeforeproceedingwiththedesignofbushingcurrenttransformers.
7.5 TechnicalParameters
7.5.1 Current TransformerParametersfor1-ph, 105MVAand3-ph315MVA400/220/33kVAutoTransformers
Oneachphaseconnection
HV IV NeutralSide side side
(a) Ratio
Core-1 1000/1A 1000/1A 1000/1A
Core-2 600/1A 1000/1A -
(b) Minimumkneepointvoltageandaccuracyclass:
Core-1 1000V 1000V 1000VClassPS ClassPS ClassPS
Core-2 0.2class 0.2class -
30VAISF530VAISF5
(c) MaximumCTResistance
Core-1 2.5ohms 2.5ohms 2.5ohms
Core-2 - - -
(d) Application
Core-1 Restricted Rest- Restricted(Nearthewdg) earth ricted earth
fault earth faultfault
Core-2 Metering Metering -
(e) Maximummagnetisation Core-160mA 60mA60mA
Tech Specification, Section: Autotransformer Page 49 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
50/54
current(atknee Core2- - -pointvoltage)
7.5.2 CurrentTransformerParametersfor1-ph,167MVA,400/220/33kVAutoTransformers
Oneachphaseconnection
HV IV NeutralSide side side
(a) Ratio
Core-1 1600/1A 1600/1A 1600/1A
Core-2 1000/1A 1600/1A -
(b) Minimumkneepointvoltageandaccuracyclass:
Core1 1600V 1600V1600V
ClassPS ClassPS ClassPS
Core-2 0.2class 0.2class
30VAISF5 30VAISF5----
(c) MaximumCTResistance
Core-1 4.0ohms 4.0ohms 4.0ohmsCore-2 - - -
(d) Application
Core-1 Restricted Rest- Restricted(Nearthewdg) earth ricted earth
fault earth faultfault
Core-2 Metering Metering -
(e) Maximummagn Core-1 25mA 25mA25mAetisationcurrent Core2 - - -(atkneepointvoltage)
7.5.3 Current Transformer Parameters for3-ph,100MVA,220/132kV AutoTransformers
Tech Specification, Section: Autotransformer Page 50 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
51/54
Oneachphaseconnection
HV IV NeutralSide side side
(a) Ratio
Core-1 600/1A 600/1A 600/1A
Core-2 300/1A 500/1A -
(b) Minimumkneepointvoltageandaccuracyclass:
Core-1 600V 600V 600VClassPS ClassPS ClassPS
Core-2 0.2class 0.2class -
30VAISF530VAISF5(c) MaximumCTResistance
Core-1 1.5ohms 1.5ohms 1.5ohms
Core-2 - - -
(d) Application
Core-1 Restricted Rest- Restricted(Nearthewdg) earth ricted earth
fault earth faultCore-2 Metering Metering -
(e) MaximummagnetisationCore-1100mA 100mA 100mA
current(atknee Core2- - -pointvoltage)
7.5.4 Current Transformer Parameters for 3-ph, 50MVA, 132/66kV Auto
TransformersOneachphaseconnection
HV IV NeutralSide side side
(a) Ratio
Core-1 300/1A 300/1A 300/1A
Core-2 300/1A 300/1A -
(b) Minimumkneepointvoltageandaccuracy
Tech Specification, Section: Autotransformer Page 51 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
52/54
class:
Core-1 600V 600V 600VClassPS ClassPS ClassPS
Core-2 0.5class 0.5class -15VAISF515VAISF5
(c) MaximumCTResistance
Core-1 1.5ohms 1.5ohms 1.5ohms
Core-2 - - -
(d) Application
Core-1 Restricted Rest- Restricted
(Nearthewdg) earth ricted earthfault earth fault
Core-2 Metering Metering -
(e) MaximummagnetisationCore-1100mA 100mA 100mA
current(atknee Core2- - -pointvoltage)
7.6 NOTE:
7.6.1 AccuracyclassPSasperIS:2705
7.6.2 Class(fortherelevantprotectionandduties)asperIEC185.
7.6.3 Parameters of WTI CT for each winding shall be provided by the
contractor.
8.0 OilStorageTank
8.1 General
Thisspecificationcoverssupplyofoilstoragetankof15cubicmetercapacityalongwithcompleteaccessories.
8.2 Standard
TheoilstoragetankshallbedesignedandfabricatedasperrelevantIndianStandardse.g.IS:803orotherinternationallyacceptablestandards.
8.3 Specifications
Transformeroilstoragetanksshallbetowable&restedonpneumatictyres
ofadequatequantity&size.Thetankshallbetocylindricalshape&
Tech Specification, Section: Autotransformer Page 52 of 54C/ENGG/SPEC/TRF REV NO: 04
7/29/2019 Auto%20transformerR4.pdf
53/54
mountedhorizontallyandmadeofmildsteelplateofadequatethickness.Sizeofthestoragetankshallbeasfollows:
Diameter : 2.5meter
Capacity : 15cubicmetre
Thetankshallbedesignedforstorageofoilatatemperatureof100C.
8.3.1 The Bidder may further note that maximum height of any part of thecompleteassemblyofthestoragetankshallnotexceed4.0metresaboveroadtop.
8.3.2 Thetankshallhaveadequatenumberofjackingpadsothatitcanbekepton jackwhile completely filledwith oil. Thetankshall beprovidedwithsuitablesaddlessothattankcanberestedongroundafterremovingthe
pneumatictyres.
8.3.3 The tankshall alsofittedwithmanhole,outside& insideaccessladder,silicagelbreatherassembly,inlet&outletvalve,oilsamplingvalvewithsuitableadopter,oildrainagevalve,airventetc.Pullinghookonbothendsofthetankshallbeprovidedsothatthetankcanbepulledfromeitherendwhilecompletelyfilledwithoil.Biddershallindicatetheenginecapacityinhorsepowertopullonetankcompletelyfittedwithoil.Oillevelindicatorshallbeprovidedwithcalibrationintermsoflitresothatatanytimeoperatorcanhaveanideaofoil inthe tank. Suitablearrangement shallalsobeprovidedtopreventoverflowinthetank.Fournos.suitablerubber
hoseswithcouplersandunionseachnotlessthan10metrelongshallalsobeprovided.
8.3.4 Theinternal&externalsurfacestobepaintedshallbeshotorsandblastedtoremoveallrustandscaleofforeignadheringmatterorgrease.Allsteelsurfacesincontactwithinsulatingoilshallhavepaintedwith twocoatsofheat&oilresistantanti-corrosivepaint.Allsteelsurfacesexposedtoweathershallbegivenaprimarycoatofzincchromate,secondcoatofoil&weatherresistantpainto