Autodaptive ® Capacitor Control M‑2501B CONTROLS Capacitor Control for Pole‑Top Capacitor Banks Increases effectiveness of installed capacitors for voltage control to reduce system losses Adapts reference voltage, bandwidth and switching time delay to changing conditions such as long-term load growth on distribution circuits and short-term variations in expected loads When mated with a CAMP (Capacitor Automated Monitoring and Protection) interface module, the M-2501B provides remote control, monitoring and reporting features
Transcript
Page 1: Autodaptive® Capacitor Control M‑2501B

Autodaptive®

Capacitor Control M‑2501B

CONTROLS

Capacitor Control for Pole‑Top Capacitor Banks

• Increaseseffectivenessofinstalledcapacitors forvoltagecontroltoreducesystemlosses

• Adaptsreferencevoltage,bandwidthand switchingtimedelaytochangingconditions suchaslong-termloadgrowthondistribution circuitsandshort-termvariationsinexpectedloads

• WhenmatedwithaCAMP™(Capacitor AutomatedMonitoringandProtection)interface module,theM-2501Bprovidesremotecontrol, monitoringandreportingfeatures

Page 2: Autodaptive® Capacitor Control M‑2501B

M‑2501B Autodaptive Capacitor Control

–2–

The M‑2501B Autodaptive® Capacitor Control increases the effectiveness of installed distribution system ca‑pacitor banks by controlling circuit voltage and reducing system losses due to VAr flow. The control monitors the average voltage at the point of installation, voltage changes caused by capacitor bank switching and the number of switch operations to effect optimum capacitor bank control considering local system conditions.

The control’s infrared communications feature allows local/monitoring through the M‑2501B's infrared port. Also, when equipped with the Beckwith Electric M‑2980 CAMP™ (Capacitor Automated Monitoring and Protection) adapter, the M‑2501B provides wireless control, near real‑time system data, alarms and failure polling of remote capacitor banks to SCADA networks.

Control OperationThe control makes its switching decisions based on algorithms using time and voltage measurements. Set‑table, upper and lower voltage limits and fixed voltage setpoint level may also be implemented. The control will not call for a switch operation which would cause the voltage to violate these voltage levels. If the site voltage drifts outside these settings, the control will act through the adaptable nonlinear timers to switch the bank if necessary. The control adapts to system source impedances by responding to small voltage changes near a substation and larger voltage changes near the end of the line.

Control ElementsUpper and Lower Voltage Levels for monitoring – Operational range is 98 to 132 V in increments of 1 V with a 6 V minimum between limits. Operation at voltage levels has a 10 second maximum time delay, subject to a 5 minute reclosing delay.

Fixed Voltage Setpoint – The fixed voltage setpoint can be set from 98.0 V to 132.0 V. When enabled, the M‑2501B will not adapt to a changing voltage profile, but will switch the capacitor bank around the fixed voltage setpoint, using an adaptive timer.Upper and Lower Voltage Rails – Adaptable to ±5 % from the average voltage. Operation at voltage rails has a time delay of 1.0 second, subject to a 5‑minute reclosing delay. The Lower Voltage Rail helps to miti‑gate voltage collapse.

Reference Voltage – Internally‑calculated voltage level adapted from average voltage level which is used for switching decisions, or may have a setpoint between 98 V and 132 V.

Desired Number of Operations – Seeks to maintain 1 to 2 open and close operations per day based on a weekly average.

Open and Close Contact Seal-In Durations – 15 seconds.

Non-Defeatable Reclosing Delay – 5 minutes after an open operation to allow for capacitor discharge.

Manual OperationThe control may be placed in manual operation one or both of the following ways: 1. User can remove the Lexan® cover to access the two manual switches on the front panel of the

control. These are the Auto/Manual switch and the Manual Open/Manual Close switch. This al‑lows manual initiation of the open or close function after a 30‑second time delay (subject to five minute reclosing delay) by the control's internal microcontroller. When the Auto/Manual switch is in the Manual position, no Automatic operation is possible, and no user setpoints are written.

2. The control may be placed in manual operation mode using either the local infrared communica‑tions port, or, if equipped with the M‑2980 CAMP Adapter, a wireless command from a SCADA network. This allows manual initiation of the open or close function by M‑2941 BecoEye+ Field Communication device or SCADA network command after a 30‑second time delay (subject to five minute reclosing delay) by the control's internal microcontroller. An operations counter can be reset in the manual operation mode. A second operations counter is non‑resettable.

If both modes of manual operation are implemented, the control will not return to Automatic Operation until both are removed.

Page 3: Autodaptive® Capacitor Control M‑2501B

–3–

M‑2501B Autodaptive Capacitor Control

InputsLine and Switch Power Input: 110–120 V ac nominal, 60 Hz (50 Hz), 1‑phase for monitoring.

Unit calibrated for operational accuracies from 59.85 Hz to 60.15 Hz (49.85 Hz to 50.15 Hz).

Line Input RatingsContinuous Withstand: 145 V acOne‑second Withstand: 240 V acOne‑cycle Withstand: 480 V acVoltage Measurement Resolution: ±0.07 %Voltage Measurement Accuracy (fundamental component): ±0.7 %

Output ContactsOpen and Close contacts are rated to make and carry 10 A at 120 V ac continuous and 45 A at 120 V ac for 100 ms.

LED IndicatorsStatus LEDs are located on the bottom of the control and are visible from the front of the control.

Automatic Mode (Yellow): Illuminated when control is in Automatic mode.

Manual Mode (Blue): Illuminated when the control is in Manual mode. Blinks for five minutes after a capaci‑tor bank Open operation has been initiated in the Manual mode.

Open (Green): Illuminated when control believes bank is open, and during the 15 seconds when a manual Close operation is in progress. Blinks for 30 seconds before and 15 seconds after a manual Open operation has been initiated.

Closed (Red): Illuminated when control believes the bank is closed, and during the 15 seconds that a manual Open operation is in progress. Blinks for 30 seconds before and 15 seconds after a manual Close operation has been initiated.

The status LEDs dim automatically in low ambient light conditions.

CommunicationsThe control communicates using the local infrared data transmission. When paired with the M‑2980 CAMP interface module, two‑way communications can be established with the control remotely using the DNP 3.0 protocol. The M‑2980 is radio/modem configurable with current options including either 900 MHz radio or CDMA cellular modem. All DNP 3.0 capable serial communications devices can be supported in the M‑2980 design. Contact Beckwith Electric for specific radio/modem requirements.

When interrogated (Blinced), the control uploads status information for display and graphing. The following information is available:

• ReferenceVoltage • Bandwidth • SwitchPosition • SiteVoltage • CountofOperations • H'AdaptiveTimeLimit • Auto/ManualStatus • ResettableCountofOperations • 24-hourVoltagePlot • 24-hourVRQFPlot • GraphofLast16Operations

The M‑2841 BecoEye+ Upload Utility provides the means to transfer M‑2501 Data Records from the M‑2941 to a PC hosting the M‑2841 software. The M‑2841 Upload Utility also provides a graphing capability of Data Record information.

Page 4: Autodaptive® Capacitor Control M‑2501B

M‑2501B Autodaptive Capacitor Control

–4–

Tests and StandardsThe M‑2501B Autodaptive Capacitor Control complies with the following type tests and standards:

Voltage WithstandDielectric Withstand:

IEC 60255‑5 2,500 V ac

All input and output terminals to chassis or instrument ground for one minute. Input and output circuits are electrically isolated form each other, from other circuits, and from ground.

Impulse Voltage:

IEC 60255‑5 5,000 V pk, +/– polarity applied to each independent circuit to earth 1.2 µs by 50 µs, 500 ohms impedance, three surges at 5 second intervals

Surge Withstand Capability:

ANSI/IEEE 2,500 V pk‑pk Oscillatory each independent circuit to earthC37.90.1 2,500 V pk‑pk Oscillatory between each independent circuit1989 5,000 V pk Fast Transient each independent circuit to earth 5,000 V pk Fast Transient between each independent circuit

Electromagnetic Compatibility – ImmunityElectrostatic Discharge

IEC61000‑4‑2Level 3 (+/– 6 Kv) – point contact discharge

Fast Transient Disturbance

IEC 61000‑4‑4 Level 4 (+/– 4 Kv, 2.5 kHz)

Radio Frequency Conducted Disturbance

IEC 61000‑4‑6 10 v/emf, 150 kHz to 80 MHz

Radio Frequency Radiated Disturbance

IEC 60255‑22‑3 10 v/m, 27 MHz to 500 MHz

Voltage Dips, Short Interruptions, and Voltage Variations

IEC 61000‑4‑11

Electromagnetic Compatibility – EmissionsEN 55022 CISPR 22Conducted emissions from 150 kHz to 30 MHzRadiated emissions from 30 MHz to 1000 MHzClass A Limits

Page 5: Autodaptive® Capacitor Control M‑2501B

–5–

M‑2501B Autodaptive Capacitor Control

Atmospheric EnvironmentTemperatureIEC 60068‑2‑1 Cold, –40 C for 96 hoursIEC 60068‑2‑2 Dry Heat, +65 C for 96 hoursIEC 60068‑2‑3 Damp Heat, +40 C @ 93% RH for 96 hours (non‑condensing)IEC 60068‑2‑30 Damp Heat, +55 C @ 95% RH (condensing)

Environmental Protection: The printed circuit board has an acrylic coating which is qualified to MIL‑I‑46058C. This coating provides protection against moisture and adverse environmental conditions.

PhysicalThe control’s circuitry is contained in a standard meter housing with a Lexan® shatterproof cover.

Mounting: The control mounts to a standard four‑ or six‑blade meter socket. The four‑blade contacts provide Line In, Line Neutral, Open Output, and Close Output connections.

Size: 6.75" diameter x 5.0" deep (17.15 cm x 12.7 cm)

Weight: 2.5 lbs (1.1 kg)

Patent & WarrantyThe M‑2501B control is covered by U.S. Patents 5,646,512, 5,544,064 5,744,366, 5,541,498 and 5,315,527 with additional patents pending.

The M‑2501B control is covered by a five year warranty from date of shipment.

Specification is subject to change without notice.