+ All Categories
Home > Documents > Autopilot Teory

Autopilot Teory

Date post: 01-Jun-2018
Category:
Upload: eqda
View: 267 times
Download: 2 times
Share this document with a friend

of 27

Transcript
  • 8/9/2019 Autopilot Teory

    1/70

      Publication No. 1-0485-009

      March 1999 Rev L

    AutoPILOT

    CONTROL DOCUMENT

    AND ENTITY PARAMETERS

    9303 W. Sam Houston Parkway South, Houston, TX 77099-5296 PH:(713)272-0404 FAX:(713)272-2272

    Please contact the manufacturer if the informationpresented in the manual does not match your unit.

  • 8/9/2019 Autopilot Teory

    2/70

    Document 1-0485-009 Rev Li

    AutoPILOT

    CONTROL DOCUMENT

    AND ENTITY PARAMETERS

    CONTENTS

    1.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    1.1 THE AutoPILOT LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    1.2 CONCEPT OF ENTITY APPROVAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    1.3 BARRIER INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    1.4 WIRING INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    2.0 AutoPILOT SYSTEM LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2.1 POWER INPUT SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2.1.1 Internal Power Source with External Solar Panel . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2.1.2 ISCOM 3-0474-004 (Intrinsically-Safe Power and Communications) . . . . . . . . . . 62.1.3 6V ISCOM (Intrinsically-Safe Power and Communications) . . . . . . . . . . . . . . . . 10

    2.2 LOCAL RS-232 (CHIT) SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    2.3 ANALOG INPUT SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.4 AutoMITTER SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    2.5 RTD INPUT SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    2.6 AutoPULSE INPUT SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.0 AutoPILOT ENTITY LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.1 LOCAL RS-232 PORT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    3.1.1 Application #1 - Local Communication Port to IS Apparatus . . . . . . . . . . . . . . . 24

    3.2 ANALOG INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    3.2.1 Application #1 - Analog Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . 26

    3.2.2 Application #2 - Analog Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . 27

    3.3 DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    3.3.1 Application #1 - Discrete Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . 29

    3.3.2 Application #2 - Discrete Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . 30

    3.4 MEB 2DI/DO DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . 31

    3.4.1 Application #1 - MEB 2DI/DO Discrete Input to Non IS Apparatus . . . . . . . . . . 32

    3.4.2 Application #2 - MEB 2DI/DO Discrete Input to IS/Simple Apparatus . . . . . . . . 33

    3.5 MEB 4 DI DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . 34

    3.5.1 Application #1 - MEB 4 DI Discrete Input to Non IS Apparatus . . . . . . . . . . . . . 35

    3.5.2 Application #2 - MEB 4 DI Discrete Input to IS/Simple Apparatus . . . . . . . . . . 36

    3.6 DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3.6.1 Application #1 - Discrete Output to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . 38

    3.6.2 Application #2 - Discrete Output to IS Apparatus . . . . . . . . . . . . . . . . . . . . . . . . 39

    Click on the contents line to go to the desired section.Click on the table of contents button to return.

  • 8/9/2019 Autopilot Teory

    3/70

    Document 1-0485-009 Rev Lii

    3.7 MEB 2DI/DO DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . 40

    3.7.1 Application #1 - MEB 2DI/DO Discrete Output to Non IS Apparatus . . . . . . . . 41

    3.7.2 Application #2 - MEB 2DI/DO Discrete Output to IS Apparatus . . . . . . . . . . . . 42

    3.8 MEB 4 DO DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . 43

    3.8.1 Application #1 - MEB 4 DO Discrete Output to Non IS Apparatus . . . . . . . . . . . 44

    3.8.2 Application #2 - MEB 4 DO Discrete Output to IS Apparatus . . . . . . . . . . . . . . 45

    3.9 PULSE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463.9.1 Application #1 - Pulse Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.9.2 Application #2 - Pulse Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . . . 48

    3.10 MEB PULSE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    3.10.1 Application #1 - MEB Pulse Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . 50

    3.10.2 Application #2 - MEB Pulse Input to IS Apparatus/Simple Apparatus . . . . . . . 51

    3.11 ANALOG OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    3.11.1 Application #1 - Analog Output to Non-IS Apparatus . . . . . . . . . . . . . . . . . . . . 53

    3.11.2 Application #2 - Analog Output to IS Apparatus/Simple Apparatus . . . . . . . . . 54

    3.12 DUAL ANALOG OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . 55

    3.12.1 Application #1 - MEB 2D/A Analog Output to Non-IS Apparatus . . . . . . . . . . 563.12.2 Application #2 - MEB 2D/A Analog Output to IS/Simple Apparatus . . . . . . . . 57

  • 8/9/2019 Autopilot Teory

    4/70

    Document 1-0485-009 Rev L1

    AutoPILOT

    CONTROL DOCUMENT

    AND ENTITY PARAMETERS

    1.0 GENERAL INFORMATION

    1.1 THE AutoPILOT LISTING

    The AutoPILOT is UL-Listed for use in Class I Division 1, Groups C and D hazardous locations for

    United States installations, and C-UL listed for Class I Division 1, Groups C and D hazardous

    locations for Canadian installations. It is intrinsically safe when connected according to this control

    document. The AutoPILOT has an Operating Temperature Code of T3C. WARNING:

    Substitution of components may impair the intrinsic safety of the AutoPILOT.

    The listing includes connections for a System Approval and Entity Approval. The AutoPILOTlisting includes the following maximum number and type of electrical connections:

    • One Power Input (System Listing)

    • Three Host Ports (RS-232 port; System Listing for use with ISCOM 3-0474-004 or 6V

    ISCOM 3-0474-016 or 3-0474-025)

    • One CHIT Port (Local RS-232 port; System Listing for use with CHIT, or with Entity

    Parameters)

    • Analog Inputs (Three with System Listing for use with specified transducers, or One with

    Entity Parameters)

    • One Comm 3 Terminator IS connection to up to four AutoMITTERs (System Listing)

    • One RTD Input (System Listing)

    • Up to ten Discrete Inputs (with Entity Parameters)

    • Up to ten Discrete Outputs (with Entity Parameters)

    • Up to four Pulse Inputs (System Listing with AutoPULSE, or with Entity Parameters)

    • Up to four 4-20 mA Analog Outputs with +24V Loop Power Inputs (with Entity Parameters)

    Power Systems available with System Listing include the following options. ISCOM model

    numbers must be verified to ensure safety.

    • Internal +6VDC/12 AH, rechargeable battery with an external 2-watt solar panel

    • ISCOM 3-0474-004 (UL Listed Associated Apparatus)

    • 6V ISCOM 3-0474-016 (UL Listed Associated Apparatus)

    • 6V ISCOM 3-0474-025 (UL and C-UL Listed Associated Apparatus)

  • 8/9/2019 Autopilot Teory

    5/70

    Document 1-0485-009 Rev L2

    1.2 CONCEPT OF ENTITY APPROVAL

    The concept of an Entity Approval allows connection of intrinsically-safe apparatus and intrinsically-

    safe associated apparatus, including barriers, that have not been specifically approved as a system.

    Refer to Article 504 of the National Electrical Code, NFPA 70, for acceptable wiring methods,

    sealing methods, and separation of intrinsically-safe and non-intrinsically safe wiring for United

    States installations, or Section 18 of the Canadian Electrical Code for wiring, sealing and separationrequirements for Canadian installations.

    Under Entity Approval, connection between an intrinsically-safe apparatus and an intrinsically-safe

    associated apparatus is limited as follows:

    1. The approvedMaximum Open-Circuit Voltage (Voc) of the associated apparatus must be less

    than or equal to the Maximum Safe Input Voltage (Vmax) of the intrinsically-safe apparatus.

    (Voc  Vmax)

    2. The approved Maximum Short-Circuit Current (Isc) of the associated apparatus must be lessthan or equal to the Maximum Safe Input Current (Imax) of the intrinsically-safe apparatus.

    (Isc  Imax)

    3. The approved Maximum Allowable Capacitance (Ca) of the associated apparatus must be

    greater than or equal to the sum of the Internal Capacitance (Ci)  of the intrinsically-safe

    apparatus and the Wiring Capacitance (Cw). (Ca  Ci + Cw)

    4. The approved Maximum Allowable Inductance (La)  of the associated apparatus must be

    greater than or equal to the sum of the Internal Inductance (Li)  of the intrinsically-safe

    apparatus and the Wiring Inductance (Lw). (La  Li + Lw)

    Note

    If the wiring parameters (capacitance and inductance) are not known, use the following

    parameters:

    • Wiring Capacitance of 60 pF per foot

    • Wiring Inductance of 0.2 H per foot

    A 100-foot cable has a Cw of 6000 pF (0.006 F) and a Lw of 20 H.

    When two intrinsically-safe devices are connected and installed in the hazardous location, the same

    four entity approval concepts apply. However, they must be applied from both directions: first with

    the AutoPILOT as the intrinsically-safe apparatus connected to an intrinsically-safe associated

    apparatus (such as a pressure transmitter), then the AutoPILOT as the intrinsically-safe associated

    apparatus connected to the intrinsically-safe apparatus (pressure transmitter).

  • 8/9/2019 Autopilot Teory

    6/70

    Document 1-0485-009 Rev L3

    1.3 BARRIER INFORMATION

    When the device connected to the AutoPILOT is not an approved intrinsically-safe device for use

    in the hazardous location, it must be installed in an non-hazardous area, and an intrinsically-safe

    barrier must be wired between the AutoPILOT and the device. The general requirements of the

    selected barrier are as follows:

    The barrier output must be limited by a resistor such that the output voltage verses current plot

    is a straight line between Voc and Isc.

    The barrier must be approved for the installation location and hazardous area, and be installed

    as instructed by the barrier manufacturer.

    The barrier ground must be connected to the Earth Ground.

    Typical Single-Channel, Shunt-Diode, Resistive Barrier

    Typical Dual-Channel, Shut-Diode, Resistive & Diode Barrier

     for 4-20mA Applications

  • 8/9/2019 Autopilot Teory

    7/70

    Document 1-0485-009 Rev L4

    1.4 WIRING INFORMATION

    When installed in the United States in a Class I Division 1 hazardous location, all customer wiring

    to the AutoPILOT connections with entity parameters must be made according to Article 504

    (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing

    methods. For Canadian Class I Division 1 installations, all customer wiring to the AutoPILOT

    connections with entity parameters must be made according to Section 18-066 of the CanadianElectrical Code. Multiple circuits that run in the same multiple-conductor cable must have a

    minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor.

  • 8/9/2019 Autopilot Teory

    8/70

    Document 1-0485-009 Rev L5

    2.0 AutoPILOT SYSTEM LISTING

    The System Listing of the AutoPILOT includes power systems, RS-232 communication ports,

    connections to a standard suite of analog/digital transmitters, connection to up to four

    AutoMITTERs, one dedicated external RTD input, and connections to the AutoPULSE Indexer. The

    System listing provides two power options: an internal battery with external solar panel, or one of 

    the Intrinsically Safe COMmunication interfaces (ISCOM). The communication ports included inthe system listing are the Local Port (used with the CHIT) and up to three Host Ports (used with an

    ISCOM). The AutoPILOT Main Board provides system termination for three analog inputs from

    a suite of optional low-power transmitters, for the optional Rosemount 205 Digital Combo

    Transmitter, or for the optional Honeywell MXA145 or MXG170 combination transmitters. The

    Comm 3 Terminator option provides an intrinsically safe power and communication connection to

    up to four AutoMITTERs wired in parallel, with each AutoMITTER having one temperature input

    which can be system wired to one of the Flow Automation RTD Temperature Probe assemblies. The

    RTD1 input at TB5 connects to one of the Flow Automation RTD Temperature Probe assemblies.

    For positive displacement (PD) meters, a system connection may be made between the AutoPULSE

    Indexer and the AutoPILOT or MEB Pulse Input Board(s).

    2.1 POWER INPUT SYSTEM CONNECTION

    The AutoPILOT is powered by one of two power systems: an internal rechargeable battery with an

    external solar panel, or an Intrinsically Safe Communication System (ISCOM 3-0474-004 or 6V

    ISCOM 3-0474-016 or 3-0474-025). ISCOM model numbers must be verified to ensure safety.

    2.1.1 Internal Power Source with External Solar Panel

    The intrinsically safe battery assembly consists of a +6 Vdc, 12 AH rechargeable battery with

    associated protective components. The battery assembly charge is maintained with a 2-watt solar

    panel. The battery assembly mounts inside the enclosure internal chassis on the backpanel, and may

    be shipped outside the unit to avoid shipping damage. To install the battery assembly, lift the battery

    assembly above the bracket retaining lip, and lower the battery assembly into the bracket. The power

    leads from the battery assembly connect to the flow computer at the power distribution terminal

    block TB1 mounted on the equipment panel at positions 1-3 (POS) and 4-6 (NEG).

    Mount the solar panel assembly to the pole, route the solar panel wiring through the bottom of the

    flow computer enclosure, then connect it to the two-position Molex connector of the battery

    assembly.

    When the battery needs to be changed, the entire battery assembly must be replaced. Order the

    replacement Division 1 battery assembly from Flow Automation (PN# 3-0485-026).

  • 8/9/2019 Autopilot Teory

    9/70

    Document 1-0485-009 Rev L6

    2.1.2 ISCOM 3-0474-004 (Intrinsically-Safe Power and Communications)

    The ISCOM 3-0474-004 provides the AutoPILOT with an intrinsically safe +6 Vdc input power, and

    an RS-232 link with a Host communication port. ISCOM model numbers must be verified to ensure

    safety. This option is not available for Canadian installations. When installed in a Class I Division

    1 hazardous location in the United States, all customer wiring to the AutoPILOT must be made

    according to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70,including wiring and sealing methods. Multiple circuits that run in the same multiple-conductor

    cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer

    to the ISCOM Installation and Wiring Manual (PN# 1-0446-004) for proper installation guidelines

    of the ISCOM 3-0474-004.

    ISCOM 3-0474-004 Non Intrinsically-Safe Connections

    The non intrinsically-safe connections of the ISCOM 3-0474-004 are made to a power source (+8

    Vdc to +16 Vdc) and an RS-232 communication device. When installed in the nonhazardousarea, the power source and the communication device are not part of the Listed System and

    shall not use or generate more than 250 Volts. The ISCOM 3-0474-004 when mounted inside the

    AutoLINK may be installed in a Division 2 or nonhazardous area. Refer to the ISCOM Installation

    and Wiring Manual (Flow Automation Part Number 1-0446-004) for proper connection of these

    devices to the ISCOM 3-0474-004.

    ISCOM 3-0474-004 to AutoPILOT Intrinsically-Safe Connections

    The connection between the ISCOM 3-0474-004 and AutoPILOT is an intrinsically-safe connection.

    The cable length between the ISCOM 3-0474-004 and the AutoPILOT shall not exceed 200 feet.

    Because the AutoPILOT with Div I Comm Expansion Board option provides up to three RS-232

    ports, three ISCOMs 3-0474-004 can be connected to the AutoPILOT in non-hazardous area

    installations, while the AutoLINK provides only one ISCOM 3-0474-004. Only the primary

    ISCOM connected to the AutoPILOT Main Board can supply power to the flow computer.

    The IS Power Outputs of a secondary or tertiary ISCOM 3-0474-004 must not be connected.

    Refer to Figure 2-1-1 or Figure 2-1-2 for typical System Connection wiring between the ISCOM 3-

    0474-004 and AutoPILOT.

  • 8/9/2019 Autopilot Teory

    10/70

    Document 1-0485-009 Rev L7

    Connection of the ISCOM 3-0474-004 to the AutoPILOT is as follows:

     Primary

     ISCOM

      3-0474-004 Power Distribution AutoPILOT

      IS Output Terminal Block Main Board

    PWR (1) TB1 position 1-3 (POS) No connection

    GND (2) TB1 position 4-6 (NEG) No connection

    SBAT (3) No connection +5 (TB2-9)

    HRTS (4) No connection RTS (TB2-4)

    HTX (5) No connection TX (TB2-3)

    HDCD (6) No connection DCD (TB2-5)

    HCTS (7) No connection CTS (TB2- 2)

    HRX (8) No connection RX (TB2-1)

     2nd or 3rd 

    ISCOM Div I Div I

      3-0474-004 Comm Expansion Bd. Comm Expansion Bd.

      IS Output Comm 4 Comm 5

    PWR (1) No Connection No connection

    GND (2) GND (TB1-8) GND (TB2-8)

    SBAT (3) No Connection No connection

    HRTS (4) RTS (TB1-4) RTS (TB2-4)

    HTX (5) TXD(TB1-3) TXD(TB2-3)

    HDCD (6) DCD (TB1-5) DCD (TB2-5)

    HCTS (7) CTS (TB1- 2) CTS (TB2- 2)HRX (8) RXD (TB1-1) RXD (TB2-1)

  • 8/9/2019 Autopilot Teory

    11/70

    Document 1-0485-009 Rev L8

    Figure 2-1-1: Typical Nonhazardous ISCOM 3-0474-004 to AutoPILOT Connection

    Notes:

    1. Not part of Listed System. Shall not use or generate more than 250 Volts.

    2. Maximum cable length between ISCOM 3-0474-004 and AutoPILOT is 200 Feet.

    3. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,

    for proper sealing between hazardous and nonhazardous areas, and separation between

    intrinsically-safe and non intrinsically-safe wiring.

    4. Refer to Installation Manual 1-0446-004 for ISCOM 3-0474-004 installation and wiring

    instructions.

  • 8/9/2019 Autopilot Teory

    12/70

    Document 1-0485-009 Rev L9

    Figure 2-1-2: Typical AutoLINK ISCOM 3-0474-004 to AutoPILOT Connection

    Notes:

    1. Maximum cable length between ISCOM 3-0474-004 and AutoPILOT is 200 Feet.

    2. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,

    for proper sealing between hazardous and nonhazardous areas, and separation between

    intrinsically-safe and non intrinsically-safe wiring.

    3. Refer to Installation Manual 1-0446-004 for ISCOM 3-0474-004 installation and wiring

    instructions. Refer to AutoLINK manual 1-0488-001 for AutoLINK installations.

  • 8/9/2019 Autopilot Teory

    13/70

    Document 1-0485-009 Rev L10

    2.1.3 6V ISCOM (Intrinsically-Safe Power and Communications)

    The 6V ISCOM provides the AutoPILOT with an intrinsically safe +6 Vdc input power, and an RS-

    232 link with a Host communication port. 6V ISCOM 3-0474-016 is Listed for United States

    installations, while the 6V ISCOM 3-0474-025 is Listed for United States or Canadian installations.

    ISCOM model number must be verified to ensure safety. When installed in a Class I Division 1

    hazardous location in the United States, all customer wiring to the AutoPILOT must be madeaccording to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70,

    including wiring and sealing methods. For Canadian installations, all customer wiring to the

    AutoPILOT installed in a Class I Division 1 hazardous location must be made according to Section

    18-066 of the Canadian Electrical Code. Multiple circuits that run in the same multiple-conductor

    cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer

    to the 6V ISCOM Installation and Wiring Manual (PN# 1-0474-004) for proper installation

    guidelines of the 6V ISCOM 3-0474-016 or 3-0474-025.

    6V ISCOM 3-0474-016 or 3-0474-025 Non Intrinsically-Safe Connections

    The non intrinsically-safe connections of the 6V ISCOM 3-0474-016 or 3-0474-025 are made to a

    power source (+8 Vdc to +16 Vdc) and an RS-232 communication device. When installed in the

    nonhazardous area, the power source and the communication device are not part of the Listed

    System and shall not use or generate more than 125 Volts. The 6V ISCOM 3-0474-016 or 3-

    0474-025 when mounted inside the AutoLINK may be installed in a Division 2 or nonhazardous

    area. Refer to the 6V ISCOM Installation and Wiring Manual (PN# 1-0474-004) for proper

    connection of these devices to the 6V ISCOM 3-0474-016 or 3-0474-025.

    6V ISCOM 3-0474-016 or 3-0474-025 to AutoPILOT Intrinsically-Safe Connections

    The connection between the 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is an

    intrinsically-safe connection. The cable length between the 6V ISCOM 3-0474-016 or 3-0474-025

    and the AutoPILOT shall not exceed 200 feet. Because the AutoPILOT with Div I Comm Expansion

    Board option provides up to three RS-232 ports, three 6V ISCOMs 3-0474-016 or 3-0474-025 can

    be connected to the AutoPILOT in non-hazardous area installations, while the AutoLINK provides

    only one 6V ISCOM 3-0474-016 or 3-0474-025. Only the primary ISCOM connected to the

    AutoPILOT Main Board can supply power to the flow computer. The IS Power Outputs of 

    a secondary or tertiary 6V ISCOM 3-0474-016 or 3-0474-025 must not be connected. Refer to

    Figures 2-1-3 and 2-1-4 for typical System Connection wiring between the 6V ISCOM 3-0474-016

    or 3-0474-025 and AutoPILOT.

  • 8/9/2019 Autopilot Teory

    14/70

    Document 1-0485-009 Rev L11

    Connection of the 6V ISCOM 3-0474-016 or 3-0474-025 to the AutoPILOT is as follows:

      Primary 6V ISCOM

      3-0474-016 or 3-0474-025 Power Distribution AutoPILOT

      IS Output Terminal Block Main Board

    VSAFE (TB2-6) TB1 position 1-3 (POS) No connection

    GND (TB2-7) TB1 position 4-6 (NEG) No connectionRTS-IN (TB2-5) No connection RTS (TB2-4)

    TX-IN (TB2-4) No connection TX (TB2-3)

    DCD-OUT (TB2-3) No connection DCD (TB2-5)

    CTS-OUT (TB2-2) No connection CTS (TB2- 2)

    RX-OUT (TB2-1) No connection RX (TB2-1)

    2nd or 3rd  6V ISCOM Div I Div I

     3-0474-016 or 3-0474-025 Comm Expansion Bd. Comm Expansion Bd.

      IS Output Comm 4 Comm 5

     VSAFE (TB2-6) No Connection No connection

      GND (TB2-7) GND (TB1-8) GND (TB2-8)

    RTS-IN (TB2-5) RTS (TB1-4) RTS (TB2-4)

      TX-IN (TB2-4) TXD(TB1-3) TXD(TB2-3)

    DCD-OUT (TB2-3) DCD (TB1-5) DCD (TB2-5)

    CTS-OUT (TB2-2) CTS (TB1- 2) CTS (TB2- 2)

     RX-OUT (TB2-1) RXD (TB1-1) RXD (TB2-1)

  • 8/9/2019 Autopilot Teory

    15/70

    Document 1-0485-009 Rev L12

    Figure 2-1-3: 6V ISCOM 3-0474-016 or 3-0474-025 to AutoPILOT Connection

    Notes:

    1. Not part of Listed System. Shall not use or generate more than 125 Volts.

    2. Maximum cable length between 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is 200

    Feet.

    3. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,

    for proper sealing between hazardous and nonhazardous areas, and separation between

    intrinsically-safe and non intrinsically-safe wiring. For Canadian installations, refer to Section

    18-066 and 18-106 of the Canadian Electrical Code for separation and sealing requirements.

    4. Refer to Installation Manual 1-0474-004 for 6V ISCOM 3-0474-016 or 3-0474-025 installation

    and wiring instructions.

  • 8/9/2019 Autopilot Teory

    16/70

    Document 1-0485-009 Rev L13

    Figure 2-1-4: 6V ISCOM 3-0474-016 or 3-0474-025 AutoLINK to AutoPILOT Connection

    Notes:

    1. Maximum cable length between 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is 200

    Feet.

    2. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,

    for proper sealing between hazardous and nonhazardous areas, and separation between

    intrinsically-safe and non intrinsically-safe wiring. For Canadian installations, refer to Section

    18-066 and 18-106 of the Canadian Electrical Code for separation and sealing requirements.

    3. Refer to Installation Manual 1-0474-004 for 6V ISCOM 3-0474-016 or 3-0474-025 installation

    and wiring instructions. Refer to AutoLINK manual 1-0488-001 for AutoLINK

    interconnections.

  • 8/9/2019 Autopilot Teory

    17/70

    Document 1-0485-009 Rev L14

    2.2 LOCAL RS-232 (CHIT) SYSTEM CONNECTION

    The AutoPILOT provides an RS-232 compatible Local communication port for software

    configuration and calibration of the flow computer. Connection to the port is made using the six-

    position LEMO connector located on the bottom of the flow computer enclosure. The interface to

    the port is made only to the Class I Division 1 CHIT with a coiled cable (PN# 3-0330-014) or a 25-

    foot cable (PN# 3-0330-071).

  • 8/9/2019 Autopilot Teory

    18/70

    Document 1-0485-009 Rev L15

    2.3 ANALOG INPUT SYSTEM CONNECTIONS

    The AutoPILOT System listing includes connections to direct mounted combination transmitters,

    remote mounted AutoMITTERs, and/or three analog inputs for use with low power single analog

    transmitters (differential pressure, static pressure, and temperature). Refer to Section 2.4 for

    AutoMITTER connections. The following single transmitters are included under the System Listing:

    • Druck Static Pressure Transmitter Model PDCR143-8003 (25 to 3000 psi range)

    • Rosemount Static Pressure Transmitter Model 3051C Low Power (3626 psi maximum range)

    • Rosemount Differential Pressure Transmitter Model 2024 (2000 psi maximum range)

    • Rosemount Differential Pressure Transmitter Model 3051C Low Power (3626 psi maximum

    range)

    • Flow Automation RTD Temperature Transmitter Model 465A

    The standard low-power transmitters may be factory wired to the AutoPILOT Main Board with a

    maximum cable length of 25 feet or less between the AutoPILOT and the transmitters. See Figure

    2-3-1 for typical wiring of the Analog Input System Connection (Direct Wired). The AutoPILOTMain Board Analog Input Direct Wired connections are as follows:

      CHANNEL   SIG AGND XPWR

      AI1 TB4-1 TB4-2 TB4-3

      AI2 TB4-4 TB4-5 TB4-6

      AI3 TB4-7 TB4-8 TB4-9

    The single transmitters may also be wired to one of six junction box assemblies included in the

    system listing. The 3-0485-158, 3-0485-195 or 3-0485-255 assembly is used for transducers whichcannot power cycle (typically Rosemount 3051's), and has XPWR connected to the power input at

    TB1 position 1-3 (POS) on the internal chassis power distribution terminal block. The 3-0485-156,

    3-0485-194 or 3-0485-254 assembly is used with power cycling transducers, and has XPWR

    connected to the AutoPILOT Main Board at TB4-3. Cabling from the junction box assembly to the

    transmitters is limited to 25 feet maximum cable length. See Figure 2-3-2 for typical wiring of the

    Analog Input System Connection (Junction Box) assembly.

  • 8/9/2019 Autopilot Teory

    19/70

    Document 1-0485-009 Rev L16

    The connections to any analog input junction box assembly are as follows:

    JB TB1 SIG

    1 AGND

    2 XPWR

    3 AI1

    4 AI2

    5 AI3

    Figure 2-3-1: Typical Analog Input System Connection (Direct Wired)

    Figure 2-3-2: Typical Analog Input System Connection (Junction Box)

  • 8/9/2019 Autopilot Teory

    20/70

    Document 1-0485-009 Rev L17

    The Rosemount Model 205 Digital Combo Transmitter (0-250" DP, maximum 3626 psi) is also a

    system connection to the AutoPILOT. The 205 transmitter provides digital, temperature

    compensated, differential and static pressure signals. The digital combo transmitter mounts directly

    to the bottom of the AutoPILOT enclosure and connects to the AutoPILOT Main Board through the

    205 Interface Board.

    The Honeywell combination transmitter MXA145 (0-400" DP, maximum 1500 psia) or MXG170(0-400" DP, maximum 3000 psig) are also system connections to the AutoPILOT, mount directly

    to the bottom of the AutoPILOT enclosure, and connect to the AutoPILOT Main Board through the

    Honeywell transducer interface board. The Honeywell transducer interface board has station ID

     jumpers which may need to be user configured. If the flow computer software version was initially

    developed to use the Rosemount 205, then jumpers J1 through J4 on the Honeywell interface board

    must be installed. If the software version was developed to use a Honeywell combination transducer,

    then J1 is removed, and J2 through J4 installed on the interface board.

    2.4 AutoMITTER SYSTEM CONNECTIONS

    The AutoPILOT provides an optional system connection through the Comm 3 Terminator board to

    up to four remote mounted AutoMITTER transducers. Comm 3 Terminator assembly 3-0485-333

    is used for 6V input power systems as described in Section 2.1 for use with the Division 1

    AutoPILOT for United States and Canadian installations. Each AutoMITTER uses one of the

    Honeywell combination transmitters to provide differential and static pressure measurements, and

    an optional temperature input. All AutoMITTERs are wired in parallel to the Comm 3 Terminator

    intrinsically safe output, which provides a +6V power and RS-485 communication buss to and from

    the AutoMITTERs, with a total cable length of 2250 feet or less. Each AutoMITTER also has an

    optional RTD input, which may be system wired to the 3-0465-029 or 3-0465-033 Temperature

    Probe assembly using up to 25 feet of cable. When installed in a Class I Division 1 hazardous

    location in the United States, all wiring to and from the AutoMITTER is intrinsically safe wiring,

    and must be made according to Article 504 (Intrinsically Safe Systems) of the National Electrical

    Code, NFPA 70. For Canadian installations, all wiring to and from the AutoMITTER is intrinsically

    safe wiring, and must be made according to Sections 18-066 and 18-106 of the Canadian Electrical

    Code. Multiple circuits that run in the same multiple-conductor cable must have a minimum

    insulation thickness of 0.01 inch (0.25 mm) on each conductor.

  • 8/9/2019 Autopilot Teory

    21/70

    Document 1-0485-009 Rev L18

    AutoPILOT to AutoMITTER Intrinsically Safe Connections

    The connection between the Comm 3 Terminator and the AutoMITTER(s) is intrinsically safe

    wiring, and must be installed according to Article 504 (Intrinsically Safe Systems) of the National

    Electrical Code, NFPA 70, for United States installations, or according to Sections 18-066 and 18-

    106 of the Canadian Electrical Code for Canadian installations. The total cable length between the

    AutoPILOT and all AutoMITTERs must not exceed 2250 feet. Refer to Figure 2-4 for typicalsystem connection wiring between the AutoPILOT and AutoMITTERs.

    WARNING:

    REPLACE THE WIRING SEPARATOR AFTER MAKING

    CONNECTIONS TO THE AutoMITTER.

    Connections between the AutoPILOT Comm 3 Terminator and each AutoMITTER are as follows:

      Comm 3

     IS OUTPUT AutoMITTER

    TX+ (TB2-5) RX+ (TB1-1)

    TX- (TB2-4) RX- (TB1-2)

    RX- (TB2-2) TX- (TB1-3)

    RX+ (TB2-1) TX+ (TB1-4)

    GND (TB2-6) GND (TB1-5)

    +6V (TB2-7) BAT (TB1-6)

    Shielded cable is recommended for use between the Comm 3 Terminator and the AutoMITTER(s),

    with the drain wire connected to the Comm 3 Terminator at TB2-3.

  • 8/9/2019 Autopilot Teory

    22/70

    Document 1-0485-009 Rev L19

    Figure 2-4: AutoPILOT to AutoMITTER System Connections

    Notes:

    1. Up to four AutoMITTERs may be connected in parallel to one Comm 3 Terminator output.

    2. Maximum total cable length connected to the Comm 3 Terminator intrinsically safe output and

    all AutoMITTERs is 2250 feet.

    3. Maximum cable length for each AutoMITTER system Temperature Probe assembly connection

    is 25 feet.

    4. For United States installations, all wiring to and from the AutoMITTER is intrinsically safe and

    must be installed according to Article 504 of the National Electrical Code, NFPA 70. For

    Canadian installations, all wiring to and from the AutoMITTER is intrinsically safe and must be

    installed according to Sections 18-066 and 18-106 of the Canadian Electrical Code.

  • 8/9/2019 Autopilot Teory

    23/70

    Document 1-0485-009 Rev L20

    2.5 RTD INPUT SYSTEM CONNECTIONS

    The AutoPILOT provides process temperature measurement using the standard Model 465A

    Temperature Transmitter into an Analog Input, or the 3-0465-029 or 3-0465-033 Temperature Probe

    assembly factory wired to RTD1, with a maximum cable length of 25 feet. Each AutoMITTER may

    also use one of the Temperature Probe assemblies. All connections to and from the AutoMITTER

    are intrinsically safe wiring, and must be installed according to Article 504 of the National ElectricalCode, NFPA 70, for United States installations, or according to Sections 18-066 and 18-106 of the

    Canadian Electrical Code for Canadian installations. The Temperature Probe assemblies differ in

    the condulet housing only, and come standard with the Stark composite-body RTD probe or the

    optional stainless-steel body RTD probe. Both probe elements are 100-ohm, platinum RTD sensors.

    The Main Board RTD2 connections are not used for an external input, and are terminated with a

    100-ohm resistor.

  • 8/9/2019 Autopilot Teory

    24/70

    Document 1-0485-009 Rev L21

    2.6 AutoPULSE INPUT SYSTEM CONNECTION

    For flow corrector applications, the AutoPILOT provides a system connection to the AutoPULSE

    Indexer. The AutoPULSE mounts directly to the bottom of the AutoPILOT enclosure for the System

    listing, and connects to the AutoPILOT Main Board through the AutoPILOT or MEB Pulse Input

    Board(s). The AutoPULSE also connects directly to the top of a standard turbine or positive

    displacement (PD) meter. Up to two Pulse Input Boards may be installed in each unit, with twoindexer inputs per board. Either Pulse Input Board has a 7-position DIP configuration for each input,

    with PL1 configured with switch SW2 and PL2 configured with SW1. The AutoPULSE is

    configured as a contact closure type input, with switch positions 2, 4, 6, and 7 typically set to the

    "ON" position on the Pulse Input Board. A unique address which determines the software

    configuration must be set using jumpers JP4 and JP2 for each AutoPILOT Pulse Input board

    installed in the unit, or JP1 and JP2 for the MEB Pulse Input Board.. The Pulse Input address

     jumpers are configured as follows:

    Jumper JP1 (MEB)

     Jumper JP4 (AP) Jumper JP2 BOARD NO.

    Not Installed Not Installed 1

    Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    25/70

    Document 1-0485-009 Rev L22

    3.0 AutoPILOT ENTITY LISTING

    The Entity Listing of the AutoPILOT includes the following connections:

    One RS-232 Communication Port (AutoPILOT Main Board - Local Port)

    The following connections to the optional Digital I/O Board are included in the Entity Listing:

    One Analog Input Two Discrete Inputs

    Two Discrete Outputs

    The following buttsplice connections to the optional MEB 2DI/DO Board(s) are included in the

    Entity Listing:

    Up to four Discrete Inputs

    Up to four Discrete Outputs

    The following buttsplice connections to the optional MEB 4 DI Board(s) are included in the Entity

    Listing: Up to eight Discrete Inputs

    The following buttsplice connections to the optional MEB 4 DO Board(s) are included in the Entity

    Listing:

    Up to eight Discrete Outputs

    The following buttsplice connections to the optional AutoPILOT or MEB Pulse Input Board(s) are

    included in the Entity Listing:

    Up to four Pulse Inputs

    The following buttsplice connections to the optional Digital/Analog (D/A) or 2D/A Board(s) are

    included in the Entity Listing:

    Up to two +24V power inputs

    Up to four Analog Outputs

  • 8/9/2019 Autopilot Teory

    26/70

    Document 1-0485-009 Rev L23

    3.1 LOCAL RS-232 PORT ENTITY CONNECTIONS

    The Local RS-232 port has entity parameters for connection to an intrinsically-safe handheld or PC

    device other than the UL and C-UL-listed Flow Automation CHIT. The port provides serial

    communication for software configuration and calibration of the AutoPILOT. Connection is made

    using the six-position LEMO connector mounted in the bottom of the AutoPILOT’s enclosure.

    When installed in a Class I Division 1 hazardous location, all customer wiring to the AutoPILOTmust be made according to Article 504 (Intrinsically Safe Systems) of the National Electrical Code,

    NFPA 70, including wiring and sealing methods for United States installations, or according to

    Section 18-066 of the Canadian Electrical Code for Canadian installations. Multiple circuits that run

    in the same multiple-conductor cable must have a minimum insulation thickness of 0.01 inch (0.25

    mm) on each conductor. Refer to Section 1.4, Wiring Information, for proper connection to the

    AutoPILOT.

    The LEMO provides the following connections:

    SIGNAL LEMO Connection

      CRX Position #6

      CTX Position #3

      CEN* Position #4

      GND Position #2,5

    The CEN* signal must be connected to ground in the plug mating to the LEMO connector on the

    AutoPILOT. The AutoPILOT uses the CEN* input to activate the Local RS-232 port when a

    connection is made.

  • 8/9/2019 Autopilot Teory

    27/70

    Document 1-0485-009 Rev L24

    3.1.1 Application #1 - Local Communication Port to IS Apparatus

    Typical AutoPILOT Local RS-232 IS Connection to IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT AutoPILOT

      CTX-GND CRX-GND

    Voc = 9.23 Vdc Voc = 9.23 Vdc

    Isc = 84 mA Isc = 84 mA

    Vmax = 16 Vdc Vmax = 16 Vdc

    Imax = 250 mA Imax = 250 mACi = 0 Ci = 0

    Li = 0 Li = 0

    Ca = 2 F Ca = 2 F

    La = 1 mH La = 1 mH

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.3. Terminals CRX-GND and CTX-GND have not been evaluated for parallel connection.

    4. LEMO Mating Plug can be ordered under Flow Automation Part Number 5-3521-801.

  • 8/9/2019 Autopilot Teory

    28/70

    Document 1-0485-009 Rev L25

    3.2 ANALOG INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes one analog input on the optional AutoPILOT Digital I/O

    Board for use with a single 0-5 Vdc maximum range analog transmitter (differential pressure, static

    pressure, or temperature). Transducers with voltage output ranges such as 0.8-3.2 Vdc or 1-5 Vdc

    units may be used with software scaling provided the 0-volt minimum and 5-volt maximum limits

    are not exceeded. The transmitter is wired to TB2 of the Digital I/O Bd. When installed in a ClassI Division 1 hazardous location, all customer wiring to the AutoPILOT must be made according to

    Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring

    and sealing methods for United States installations, or according to Section 18-066 of the Canadian

    Electrical Code for Canadian installations. Multiple circuits that run in the same multiple-conductor

    cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer

    to the Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection

    to the AutoPILOT.

    The AutoPILOT Digital I/O Board Analog Input connections are identified as follows:

    CHANNEL   IN AGND

    AI3 TB2-9 TB2-10

  • 8/9/2019 Autopilot Teory

    29/70

    Document 1-0485-009 Rev L26

    3.2.1 Application #1 - Analog Input to Non IS Apparatus

    Typical Analog Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      IN-AGND

    Vmax = 12 VDC

    Imax = 250 mACi = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    30/70

    Document 1-0485-009 Rev L27

    3.2.2 Application #2 - Analog Input to IS Apparatus/Simple Apparatus

     

    Typical Analog Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      IN-AGND

    Voc = 9.23 Vdc

      Isc = 0.266 mA

    Vmax = 12 VdcImax = 250 mA

    Ci = 0

    Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.3. Simple Apparatus is a non-energy storing device that will not store or generate more than:

    • 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    31/70

    Document 1-0485-009 Rev L28

    3.3 DISCRETE INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two discrete inputs on the optional Digital I/O Board and

    up to eight discrete inputs on optional MEB 2DI/DO or MEB 4 DI board(s). The inputs are wired

    to TB2 of the Digital I/O Bd. Refer to Section 3.4 for MEB 2DI/DO discrete input connections or

    Section 3.5 for MEB 4 DI connections. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum)

    is provided by the flow computer for each input. When installed in a Class I Division 1 hazardouslocation, all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically

    Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for

    United States installations, or according to Section 18-066 of the Canadian Electrical Code for

    Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have

    a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,

    Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.

    The Digital I/O Board Discrete Input connections are identified as follows:

      INPUT  SIG GND

    DI1 TB2-5 TB2-6

    DI2 TB2-7 TB2-8

  • 8/9/2019 Autopilot Teory

    32/70

    Document 1-0485-009 Rev L29

    3.3.1 Application #1 - Discrete Input to Non IS Apparatus

     

    Typical Discrete Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      SIG-GND

    Vmax = 12 Vdc

    Imax = 250 mACi = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    33/70

    Document 1-0485-009 Rev L30

    3.3.2 Application #2 - Discrete Input to IS Apparatus/Simple Apparatus

     

    Typical Discrete Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 0.853 mA

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

    3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    34/70

    Document 1-0485-009 Rev L31

    3.4 MEB 2DI/DO DISCRETE INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two discrete inputs on each optional MEB 2DI/DO board.

    Up to two boards may be installed in a unit. The inputs are wired to TB2 of the 2 DI/DO Board

    using cabling and numbered buttsplices. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum)

    is provided by the flow computer for each input. When installed in a Class I Division 1 hazardous

    location, all customer wiring to the AutoPILOT must be made according to Article 504 (IntrinsicallySafe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for

    United States installations, or according to Section 18-066 of the Canadian Electrical Code for

    Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have

    a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,

    Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.

    The 2 DI/DO Board Discrete Input connections are identified as follows:

      BOARD NO.   INPUT SIG   GND   CABLE NO.

    1 DI1 141 142 Cable 17

    1 DI2 143 144 Cable 17

    2 DI1 149 150 Cable 18

    2 DI2 151 152 Cable 18

    A unique address which determines the software configuration must be set using jumpers J1 through

    J3 for each 2 DI/DO board installed in the unit. The address jumpers are configured as follows:

     Jumper J3 Jumper J2 Jumper J1 BOARD NO.

    Not Installed Not Installed Not Installed 1

    Not Installed Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    35/70

    Document 1-0485-009 Rev L32

    3.4.1 Application #1 - MEB 2DI/DO Discrete Input to Non IS Apparatus

    Typical MEB 2DI/DO Discrete Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      2 DI/DO

      SIG-GND

    Vmax = 12 Vdc

    Imax = 250 mACi = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    36/70

    Document 1-0485-009 Rev L33

    3.4.2 Application #2 - MEB 2DI/DO Discrete Input to IS/Simple Apparatus

     

    Typical MEB 2DI/DO Discrete Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      2 DI/DO

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 0.853 mA

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0

    Li = 0Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

    3. Simple Apparatus is a non-energy storing device that will not store or generate more than:

    • 1.2 Volts• 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    37/70

    Document 1-0485-009 Rev L34

    3.5 MEB 4 DI DISCRETE INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes four discrete inputs on each optional MEB 4 DI board. Up

    to two boards may be installed in a unit. The inputs are wired to TB2 of the MEB 4 DI Board using

    cabling and numbered buttsplices. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum) is

    provided by the flow computer for each input. When installed in a Class I Division 1 hazardous

    location, all customer wiring to the AutoPILOT must be made according to Article 504 (IntrinsicallySafe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for

    United States installations, or according to Section 18-066 of the Canadian Electrical Code for

    Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have

    a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,

    Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.

    The MEB 4 DI Board Discrete Input connections are identified as follows:

      BOARD NO.   INPUT SIG   GND   CABLE NO.

    1 DI1 205 206 Cable 25

    1 DI2 207 208 Cable 25

    1 DI3 209 210 Cable 25

    1 DI4 211 212 Cable 25

    2 DI1 213 214 Cable 26

    2 DI2 215 216 Cable 26

    2 DI3 217 218 Cable 26

    2 DI4 219 220 Cable 26

    A unique address which determines the software configuration must be set using jumpers J1 through

    J3 for each MEB 4 DI board installed in the unit. The address jumpers are configured as follows:

     Jumper J3 Jumper J2 Jumper J1 BOARD NO.

    Not Installed Not Installed Not Installed 1

    Not Installed Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    38/70

    Document 1-0485-009 Rev L35

    3.5.1 Application #1 - MEB 4 DI Discrete Input to Non IS Apparatus

    Typical MEB 4 DI Discrete Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      MEB 4 DI

      SIG-GND

    Vmax = 12 VdcImax = 250 mA

    Ci = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    39/70

    Document 1-0485-009 Rev L36

    3.5.2 Application #2 - MEB 4 DI Discrete Input to IS/Simple Apparatus

    Typical MEB 4 DI Discrete Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      MEB 4 DI

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 0.853 mA

    Vmax = 12 Vdc

    Imax = 250 mACi = 0

    Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

    3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    40/70

    Document 1-0485-009 Rev L37

    3.6 DISCRETE OUTPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two discrete outputs on the optional Digital I/O Board and

    up to eight discrete outputs on the optional MEB 2DI/DO or MEB 4 DO board(s). The outputs are

    wired to TB2 of the Digital I/O Board. Refer to Section 3.7 for MEB 2DI/DO discrete output

    connections or Section 3.8 for MEB 4 DO connections. When installed in a Class I, Division 1,

    hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing

    methods for United States installations, or according to Section 18-066 of the Canadian Electrical

    Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable

    must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the

    Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the

    AutoPILOT.

    The Digital I/O Board Discrete Output connections are identified as follows:

      OUTPUT  SIG GND

      DO1 TB2-1 TB2-2

      DO2 TB2-3 TB2-4

    The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as

    current sinks to be detected as a level signal. Since they are active devices, each output requires an

    external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s

    input power, although a common ground between the flow computer and external power source must

    be provided.

  • 8/9/2019 Autopilot Teory

    41/70

    Document 1-0485-009 Rev L38

    3.6.1 Application #1 - Discrete Output to Non IS Apparatus

    Typical Discrete Output IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      SIG-GND

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    42/70

    Document 1-0485-009 Rev L39

    3.6.2 Application #2 - Discrete Output to IS Apparatus

    Typical Discrete Output IS Connection to IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 12.77 mA

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    43/70

    Document 1-0485-009 Rev L40

    3.7 MEB 2DI/DO DISCRETE OUTPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two discrete outputs on each optional MEB 2DI/DO board.

    Up to two boards may be installed in a unit. The outputs are wired to TB2 of the 2 DI/DO Board

    using cabling and numbered buttsplices. When installed in a Class I Division 1 hazardous location,

    all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically Safe

    Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for UnitedStates installations, or according to Section 18-066 of the Canadian Electrical Code for Canadian

    installations. Multiple circuits that run in the same multiple-conductor cable must have a minimum

    insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3, Barrier

    Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.

    The 2 DI/DO Board Discrete Output connections are identified as follows:

      BOARD NO. OUTPUT SIG GND CABLE NO.

    1 DO1 145 146 Cable 17

    1 DO2 147 148 Cable 17

    2 DO1 153 154 Cable 18

    2 DO2 155 156 Cable 18

    The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as

    current sinks to be detected as a level signal. Since they are active devices, each output requires an

    external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s

    input power, although a common ground between the flow computer and external power source mustbe provided.

    A unique address which determines the software configuration must be set using jumpers J1 through

    J3 for each 2 DI/DO board installed in the unit. The address jumpers are configured as follows:

     Jumper J3 Jumper J2 Jumper J1 BOARD NO.

    Not Installed Not Installed Not Installed 1

    Not Installed Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    44/70

    Document 1-0485-009 Rev L41

    3.7.1 Application #1 - MEB 2DI/DO Discrete Output to Non IS Apparatus

     

    Typical MEB 2DI/DO Discrete Output IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      2 DI/DO

      SIG-GND

    Vmax = 12 Vdc

    Imax = 250 mACi = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    45/70

    Document 1-0485-009 Rev L42

    3.7.2 Application #2 - MEB 2DI/DO Discrete Output to IS Apparatus

     

    Typical MEB 2DI/DO Discrete Output IS Connection to IS Apparatus

    ENTITY PARAMETERS

      2 DI/DO

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 12.77 mA

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    46/70

    Document 1-0485-009 Rev L43

    3.8 MEB 4 DO DISCRETE OUTPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes four discrete outputs on each optional MEB 4 DO board.

    Up to two boards may be installed in a unit. The outputs are wired to TB2 of the MEB 4 DO Board

    using cabling and numbered buttsplices. When installed in a Class I Division 1 hazardous location,

    all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically Safe

    Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for UnitedStates installations, or according to Section 18-066 of the Canadian Electrical Code for Canadian

    installations. Multiple circuits that run in the same multiple-conductor cable must have a minimum

    insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3, Barrier

    Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.

    The MEB 4 DO Board Discrete Output connections are identified as follows:

      BOARD NO. OUTPUT SIG GND CABLE NO.

    1 DO1 269 270 Cable 33

    1 DO2 271 272 Cable 33

    1 DO3 273 274 Cable 33

    1 DO4 275 276 Cable 33

    2 DO1 277 278 Cable 34

    2 DO2 279 280 Cable 34

    2 DO3 281 282 Cable 34

    2 DO4 283 284 Cable 34

    The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as

    current sinks to be detected as a level signal. Since they are active devices, each output requires an

    external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s

    input power, although a common ground between the flow computer and external power source must

    be provided.

    A unique address which determines the software configuration must be set using jumpers J1 through

    J3 for each MEB 4 DO board installed in the unit. The address jumpers are configured as follows:

     Jumper J3 Jumper J2 Jumper J1 BOARD NO.Not Installed Not Installed Not Installed 1

    Not Installed Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    47/70

    Document 1-0485-009 Rev L44

    3.8.1 Application #1 - MEB 4 DO Discrete Output to Non IS Apparatus

     

    Typical MEB 4 DO Discrete Output IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      MEB 4 DO

      SIG-GND

    Vmax = 12 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    48/70

    Document 1-0485-009 Rev L45

    3.8.2 Application #2 - MEB 4 DO Discrete Output to IS Apparatus

    Typical MEB 4 DO Discrete Output IS Connection to IS Apparatus

    ENTITY PARAMETERS

      MEB 4 DO

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 12.77 mA

    Vmax = 12 VdcImax = 250 mA

    Ci = 0

    Li = 0

    Ca = 1 F

    La = 10 H

    Notes:

    1. Refer to Section 1.4 for Wiring Information.2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    49/70

    Document 1-0485-009 Rev L46

    3.9 PULSE INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two pulse inputs on each optional AutoPILOT or MEB

    Pulse Input Board, and up to two AutoPILOT Pulse Input Boards may be installed in each unit. The

    inputs are wired to TB3 of the AutoPILOT Pulse Input Board(s) using cabling and buttsplices. Refer

    to Section 3.10 for MEB Pulse Input Board connections. When installed in a Class I, Division 1

    hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504

    (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing

    methods for United States installations, or according to Section 18-066 of the Canadian Electrical

    Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable

    must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the

    Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the

    AutoPILOT.

    The Pulse Input Board cabling is identified as follows:

      BOARD NO. INPUT SIG GND CABLE NO.

    1 PL1 1 2 Cable 11 PL2 3 4 Cable 1

    2 PL1 5 6 Cable 2

    2 PL2 6 8 Cable 2

    Each input can be configured for use with different pulse input devices, including a slot sensor, a

    dry-contact switch, or a magnetic pulse input. Use switch SW2 (seven-position DIP switch) to

    configure PL1 and switch SW1 to configure PL2 on each board. Set the configuration switches

    determined by the input type as follows:

    INPUT TYPE SWITCH(S) ON

    Slot Sensor 2, 3* or 4* and 6

    Magnetic 1 and 5

    Contact Closure 2, 3* or 4*, 6 and 7

    * Positions #3 and #4 provide a nominal +5 Vdc wetting voltage. Position #3 has a nominal

    current output of 2.5 mA, with position #4 providing 100 A. Select the desired current

    output necessary for the application.

    A unique address which determines the software configuration must be set using jumpers JP4 and

    JP2 for each Pulse Input board installed in the unit. The Pulse Input address jumpers are configuredas follows:

    Jumper JP4 Jumper JP2 BOARD NO.

    Not Installed Not Installed 1

    Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    50/70

    Document 1-0485-009 Rev L47

    3.9.1 Application #1 - Pulse Input to Non IS Apparatus

     

    Typical Pulse Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT

      SIG-GND

    Vmax = 16 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    51/70

    Document 1-0485-009 Rev L48

    3.9.2 Application #2 - Pulse Input to IS Apparatus/Simple Apparatus

    Typical Pulse Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

     AutoPILOT

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 5 mA

    Vmax = 16 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Ca = 1 F

    La = 2 mH

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

    3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    52/70

    Document 1-0485-009 Rev L49

    3.10 MEB PULSE INPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes two pulse inputs on each optional MEB Pulse Input Board.

    Up to two MEB Pulse Input Boards may be installed in each unit. The inputs are wired to TB3 of 

    the MEB Pulse Input Board(s) using cabling and buttsplices. When installed in a Class I, Division

    1 hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504

    (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing

    methods for United States installations, or according to Section 18-066 of the Canadian Electrical

    Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable

    must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the

    Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the

    AutoPILOT.

    The MEB Pulse Input Board cabling is identified as follows:

      BOARD NO. INPUT SIG GND CABLE NO.

    1 PL1 101 102 Cable 5

    1 PL2 103 104 Cable 5

    2 PL1 105 106 Cable 6

    2 PL2 107 108 Cable 6

    Each input can be configured for use with different pulse input devices, including a slot sensor, a

    dry-contact switch, or a magnetic pulse input. Use switch SW2 (seven-position DIP switch) to

    configure PL1 and switch SW1 to configure PL2 on each board. Set the configuration switches

    determined by the input type as follows:

    INPUT TYPE SWITCH(S) ON

    Slot Sensor 2, 3* or 4* and 6

    Magnetic 1 and 5

    Contact Closure 2, 3* or 4*, 6 and 7

    * Positions #3 and #4 provide a nominal +5 Vdc wetting voltage. Position #3 has a nominal

    current output of 2.5 mA, with position #4 providing 100 A. Select the desired current output

    necessary for the application.

    A unique address which determines the software configuration must be set using jumpers JP1 and

    JP2 for each MEB Pulse Input board installed in the unit. The address jumpers are configured as

    follows:

    Jumper JP1 Jumper JP2 BOARD NO.

    Not Installed Not Installed 1

    Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    53/70

    Document 1-0485-009 Rev L50

    3.10.1 Application #1 - MEB Pulse Input to Non IS Apparatus

     

    Typical MEB Pulse Input IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      MEB PI

      SIG-GND

    Vmax = 16 Vdc

    Imax = 250 mACi = 0

    Li = 0

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    54/70

    Document 1-0485-009 Rev L51

    3.10.2 Application #2 - MEB Pulse Input to IS Apparatus/Simple Apparatus

    Typical MEB Pulse Input IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      MEB PI

      SIG-GND

    Voc = 8.44 Vdc

      Isc = 5 mA

    Vmax = 16 Vdc

    Imax = 250 mA

    Ci = 0Li = 0

    Ca = 1 F

    La = 2 mH

    Notes:

    1. Refer to Section 1.4 for Wiring Information.

    2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

    3. Simple Apparatus is a non-energy storing device that will not store or generate more than:

    • 1.2 Volts• 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    55/70

    Document 1-0485-009 Rev L52

    3.11 ANALOG OUTPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes connections for the +24 Vdc Input Power and 4-20 mA

    Analog Output of the optional Digital/Analog (D/A) Board or 2D/A Board. Power for the D/A

    Board must be provided from an external +24 Vdc source through a barrier. Up to two D/A boards

    may be installed in each unit. The Input Power is wired to TB1 and the Analog Output is wired to

    TB3 of the D/A Board(s) using cabling and buttsplices. Refer to Section 3.12 for 2D/A Boardconnections. When installed in a Class I Division 1 hazardous location, all customer wiring to the

    AutoPILOT must be made according to Article 504 (Intrinsically Safe Systems) of the National

    Electrical Code, NFPA 70, including wiring and sealing methods for United States installations, or

    according to Section 18-066 of the Canadian Electrical Code for Canadian installations. Multiple

    circuits that run in the same multiple-conductor cable must have a minimum insulation thickness of 

    0.01 inch (0.25 mm) on each conductor. Refer to the Section 1.3, Barrier Information, and Section

    1.4, Wiring Information, for proper connection to the AutoPILOT.

    The Analog Output is configured for +24 Vdc output operation only, which is recommended for

    driving total loop resistance of 250 to 750 ohms (including any barrier resistance). The associatedapparatus connected across to the current output must have a 250-ohm minimum resistance to analog

    ground.

    The D/A Board Analog Output cabling is identified as follows:

      SIGNAL AOI GND   CABLE NO.

      AO1 9 10 Cable 3

    Connect the external +24V input power to the D/A Board cabling as follows:

     SIGNAL   +VIN GND   CABLE NO.

    EXT PWR 11 12 Cable 3

    If a second D/A Board is installed, the cabling is identified as follows:

      SIGNAL AOI GND   CABLE NO.

      AO2 13 14 Cable 4

     SIGNAL   +VIN GND   CABLE NO.

    EXT PWR 15 16 Cable 4

    A unique address which determines the software configuration must be set using jumpers J4 and J3for each D/A board installed in the unit. The D/A address jumpers are configured as follows:

    Jumper J4 Jumper J3 BOARD NO.

    Not Installed Not Installed 1

    Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    56/70

    Document 1-0485-009 Rev L53

    3.11.1 Application #1 - Analog Output to Non-IS Apparatus

     

    Typical 4-20 mA Analog Output IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

      AutoPILOT AutoPILOT

      +VIN-GND AOI-GND

    Vmax = 28 Vdc Vmax = 28 Vdc

    Imax = 150 mA Imax = 150 mA

    Ci = 0 Ci = 0.1 F

    Li = 0 Li = 0

    Notes:

    1. Power Sources must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    57/70

    Document 1-0485-009 Rev L54

    3.11.2 Application #2 - Analog Output to IS Apparatus/Simple Apparatus

    Typical Analog Output IS Connection to IS Apparatus/Simple Apparatus

    ENTITY PARAMETERS

      D/A BOARD D/A BOARD

      +VIN-GND AOI-GND

    Vmax = 28 Vdc Voc = 28 Vdc

    Imax = 150 mA Isc = 150 mA

    Ci = 0 Vmax = 28 Vdc

    Li = 0 Imax = 150 mA

    Ci = 0.1 FLi = 0

    Ca = 0.3 F

    La = 1 mH

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.6. Simple Apparatus is a non-energy storing device that will not store or generate more than:

    • 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    58/70

    Document 1-0485-009 Rev L55

    3.12 DUAL ANALOG OUTPUT ENTITY CONNECTIONS

    The AutoPILOT’s Entity Listing includes connections for the +24 Vdc Input Power and dual 4-20

    mA Analog Outputs of the optional MEB 2 Digital/Analog (2D/A) Board. Power for the 2D/A

    Board must be provided from an external +24 Vdc source through a barrier. Up to two 2D/A boards

    may be installed in each unit. The Input Power is wired to TB1 and the Analog Outputs are wired

    to TB3 of the 2D/A Board(s) using cabling and buttsplices. When installed in a Class I Division 1hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504

    (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing

    methods for United States installations, or according to Section 18-066 of the Canadian Electrical

    Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable

    must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the

    Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the

    AutoPILOT.

    The Analog Outputs are configured for +24 Vdc output operation only, which is recommended for

    driving total loop resistance of 250 to 750 ohms (including any barrier resistance). The associatedapparatus connected across each current output must have a 250-ohm minimum resistance to analog

    ground. The 2D/A Board Analog Output cabling is identified as follows:

      BOARD NO. NAME SIGNAL GND CABLE NO.

    1 AOI1 117 118 Cable 9

    1 AOI2 119 120 Cable 9

    1 +VIN 121 122 Cable 10

    2 AOI1 123 124 Cable 112 AOI2 125 126 Cable 11

    2 +VIN 127 128 Cable 12

    A unique address which determines the software configuration must be set using jumpers J6 and J7

    for each 2D/A board installed in the unit. The 2D/A address jumpers are configured as follows:

    Jumper J7 Jumper J6 BOARD NO.

    Not Installed Not Installed 1

    Not Installed Installed 2

  • 8/9/2019 Autopilot Teory

    59/70

    Document 1-0485-009 Rev L56

    3.12.1 Application #1 - MEB 2D/A Analog Output to Non-IS Apparatus

     

    Typical MEB 2D/A 4-20 mA Analog Output IS Connection to Non IS Apparatus

    ENTITY PARAMETERS

     2D/A BOARD 2D/A BOARD

      +VIN-GND AOI-GND

    Vmax = 28 Vdc Vmax = 28 Vdc

    Imax = 150 mA Imax = 150 mA

    Ci = 0 Ci = 0.1 F

    Li = 0 Li = 0

    Notes:

    1. Power Sources must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.

  • 8/9/2019 Autopilot Teory

    60/70

    Document 1-0485-009 Rev L57

    3.12.2 Application #2 - MEB 2D/A Analog Output to IS/Simple Apparatus

    Typical MEB 2D/A Analog Output IS Connection to IS/Simple Apparatus

    ENTITY PARAMETERS

     2D/A BOARD 2D/A BOARD

      +VIN-GND AOI-GND

    Vmax = 28 Vdc Voc = 28 Vdc

    Imax = 150 mA Isc = 150 mA

    Ci = 0 Vmax = 28 Vdc

    Li = 0 Imax = 150 mA

    Ci = 0.1 FLi = 0

    Ca = 0.3 F

    La = 1 mH

    Notes:

    1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.

    2. All circuits connected to both sides of the barrier must be segregated from all other wiring.

    3. Refer to Section 1.3 for Barrier Information.

    4. Refer to Section 1.4 for Wiring Information.

    5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United

    States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.6. Simple Apparatus is a non-energy storing device that will not store or generate more than:

    • 1.2 Volts

    • 100 mA

    • 25 mW

    • 20 microjoules

  • 8/9/2019 Autopilot Teory

    61/70

    FLOW COMPUTER INSTALLATION

    GROUNDING GUIDELINES

    ADDENDUM - A

  • 8/9/2019 Autopilot Teory

    62/70

    A-1

    GROUNDING PROCEDURES FOR FLOW COMPUTER INSTALLATIONS 

    A proper ground connection between the flow computer and an earth-ground connection protects the

    meter run and the flow computer from natural and man-made electrical transients that may be present

    on the system. Several factors determine the grounding configuration of the meter-run installation,

    especially the flow-computer mounting and cathodic protection of the pipeline. The flow computermay be mounted to a 2-inch vertical stand-pipe, using two 2-inch pipe clamps or U-bolts and saddle

    brackets supplied with the system. The stand-pipe can be mounted directly on the pipeline using a

    saddle, or be mounted in the ground. The selected method of mounting the flow computer and the

    cathodic protection of the pipeline determines the grounding method to be used.

    In all installations, the flow computer system must be grounded to a suitable earth-ground. The flow

    computer provides a chassis ground lug located on the lower left side of the flow computer

    enclosure. The lug is marked with the ground symbol. The chassis-ground wire must be a minimum

    of an 12-AWG stranded wire and as short as possible. The DC resistance from the lug to earth

    ground should measure less than one ohm. Install the earth ground as outlined in Articles 250

    (Grounding) and 501 (Class I Locations) of the National Electrical Code for United Statesinstallations. For Canadian installations, install the earth ground as outlined in Sections 10 and 18

    of the Canadian Electrical Code.

    This guideline deals with the following three installation configurations:

    Meter runs without cathodic protection

    Meter runs with cathodic protection using isolating flanges

    Meter runs with cathodic protection using isolating fittings

  • 8/9/2019 Autopilot Teory

    63/70

    A-2

    Meter Runs without Cathodic Protection

    Flow computer installation on meter runs without cathodic protection can be mounted directly on

    the pipeline or on a stand-alone vertical stand-pipe. Refer to Exhibit 1. The ground conductor

    connects between the flow computer and the earth ground. The Flow Automation Temperature

    Transducer may be grounded through the pipeline. If any pressure/pulse transducers orAutoMITTERS are remotely mounted, connect the chassis ground of these transducers to the

    pipeline or earth ground.

    Exhibit 1: Meter-Run Installation without Cathodic Protection

  • 8/9/2019 Autopilot Teory

    64/70

    A-3

    Meter Runs with Cathodic Protection Using Isolating Flanges

    Isolating flanges can be used to electrically isolate the meter run (including the flow-computer

    system, the orifice/turbine meters, and AutoMITTERs) from the pipeline with cathodic protection.

    The flow computer can be mounted directly on the isolated section of pipeline or on a stand-alone

    vertical stand-pipe. Refer to Exhibit 2. The ground conductor connects between the flow computerand the earth ground. Mount a ground strap to the isolated meter-run section and connect it to the

    earth ground to protect the Temperature Transducer and any remotely mounted pressure/pulse

    transducers. Connect any AutoMITTER grounds directly to earth ground.

    Exhibit 2: Meter Run Installation with Isolating Flanges

  • 8/9/2019 Autopilot Teory

    65/70

    A-4

    Meter Runs with Cathodic Protection Using Isolating Fittings

    Isolating fittings can be used to electrically isolate the meter run from the pipeline with cathodic

    protection. Refer to Exhibit 3. Install an isolated fitting or gasket between the following

    connections:

    all metallic tubing runs between the orifice meter and pressure transducers/manifolds (includingremotely mounted units or AutoMITTERs)

    all metallic connections or tubing runs between the flow computer and turbine meter/pulse

    transducers

    any Temperature Transducer and its pipe-mount, including those connected to AutoMITTERs

    Mount the flow computer on a stand-alone vertical stand-pipe. The ground conductor connects

    between the flow computer and the earth ground. Connect the cases of the Temperature Transducers,

    any remotely mounted pressure transducer cases, or AutoMITTER chassis grounds, to the earth

    ground.

    Exhibit 3: Meter Run Installation with Isolating Fittings

  • 8/9/2019 Autopilot Teory

    66/70

    RTD PROBE CUTTING

    AND WIRING PROCEDURES

    ADDENDUM - B

  • 8/9/2019 Autopilot Teory

    67/70

    B-1

    1.0 CUTTING THE TEMPERATURE PROBE TO LENGTH 

    Flow Automation recommends the temperature probe length be measured from the inside bottom

    surface of the RTD Housing to the desired depth in the thermowell. This measurement takes into

    consideration the combined lengths of the thermowell and mounting hardware when the temperature

    probe is installed on the pipeline. When installed in the thermowell, the tip of the probe must notcontact the bottom of the thermowell, to electrically isolate the probe from transient currents. Cut

    the temperature probe as follows:

    1. Measure or calculate the desired length of the temperature probe.

    2. Remove the heat shrink from the top of the temperature probe.

    3. Carefully, remove the small plastic sleeve from the top of the temperature probe. Caution: Do

    not discard the small plastic sleeve. It protects the wires from the edge of the probe.

    4. Measure and mark the body of the temperature probe to the desired length, measuring from thetip of the temperature probe.

    5. When using the standard Stark temperature probe, the composite-probe body is pre-scored.

    Hand break the probe body at the desired score, then pull the portion to be removed from the

    tr


Recommended