+ All Categories
Home > Documents > A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

Date post: 07-Nov-2014
Category:
Upload: madhulika-srinivas
View: 139 times
Download: 7 times
Share this document with a friend
Description:
A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi
Popular Tags:
24
Operation Manual GEA Aircooled Condensing Units C-Range
Transcript
Page 1: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

Operation Manual

GEA Aircooled Condensing UnitsC-Range

Page 2: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Introduction C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 2

Description Introduction.................................................................................................................3 Scope of this Manual..................................................................................................3 "HEALTH and SAFETY at WORK ACT" (UK) ...........................................................3 Installation / Servicing Safety Instructions..............................................................4 Aircooled Condensing Units .....................................................................................5 STANDARD UNITS (Single Compressor Units) .......................................................6 V.R.F. UNITS (Twin Compressor Units)....................................................................6 R407C Refrigerant Charges.......................................................................................7 Oil Charging ................................................................................................................7 Drawing Schedule.......................................................................................................8 10311-C-146.................................................................................................................9 10311-C-147.............................................................................................................. 10 10311-D-204.............................................................................................................. 11 10311-D-201.............................................................................................................. 12 10311-D-202.............................................................................................................. 13 10311-D-203.............................................................................................................. 14 10311-D-221.............................................................................................................. 15 10311-D-223.............................................................................................................. 16 Storage and Operating Environment..................................................................... 17 Receiving the Equipment........................................................................................ 17 Condenser Location on Site................................................................................... 18 Noise Considerations.............................................................................................. 19 Cable Segregation ................................................................................................... 19 Suppression ............................................................................................................. 19 Refrigeration Pipework ........................................................................................... 20 Electrical................................................................................................................... 21 Mains Supply............................................................................................................ 21 Pre-operational Checklist ....................................................................................... 22 Control of Refrigerant Discharge........................................................................... 22 Servicing: Direct Expansion Systems................................................................... 23

Page 3: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Introduction

PR-2007-0345-GB Subject to modifications Status 05/2007 3

Introduction GEA Denco thank you for purchasing their Air Conditioning Products.

This manual has been compiled to help ensure the correct installation of the equipment. Please read it fully BEFORE COMMENCING THE WORK.

All installation work, including the running and connecting of services, must be carried out only by COMPETENT PERSONS.

The manual does not cover the detailed commissioning, operation or servicing, which are the subject of separate Operating and Maintenance instructions and which, also, must be carried out only by COMPETENT PERSONS.

The equipment has been designed and manufactured within a Quality Assurance System conforming to ISO 9001, and Quality Controlled to ensure that it reaches you in perfect condition.

It is important for you to appreciate that failure to follow the instructions in this manual may result in damage, incorrect operation or danger to health and safety, and may invalidate the warranty. Any works planned that are not covered in this manual must be discussed with, and are subject to the approval of GEA Denco.

Scope of this Manual This Installation Manual covers the following ranges of Aircooled Condensing Units:

- Aircooled Condensing Unit: CT18, CT22 and CT28 - Aircooled Condensing Unit: CS28, CS34 and CS40 - Aircooled Condensing Unit: CM40, CM48 and CM61 - Aircooled Condensing Unit: CP61, CP72, CP81 and CP90 - Aircooled Condensing Unit: CL90, CL11, CL12, CL16 and CL19 - Aircooled Condensing Unit: CPV48 (Variable Refrigerant Flow Model) - Aircooled Condensing Unit: CLV48, CLV61, CLV72, and CLV81 (Variable

Refrigerant Flow Models) For the actual model type and number refer to the Serial Plate fitted to the Unit.

"HEALTH and SAFETY at WORK ACT" (UK) - The 1974 Act is aimed at securing your health, safety and welfare. - The Act is also designed to protect people, other than those at work, against risks

to health or safety arising out of or in connection with the activities of people at work.

- Do not attempt to carry out work of a dangerous nature. - It is your legal duty to take reasonable care of your own health and safety and of

other people who may be affected by your conduct. - You must co-operate with your employer in order to comply with any duty or

requirement specified in the Act. - You must abide by the statutory safety rules of the Company in which you are

working. - Remember that, in law, you are liable for the same penalties as your employer or

site agent if you do not comply with the relevant requirements of the Act.

Page 4: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Installation / Servicing Safety Instructions C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 4

Installation / Servicing Safety Instructions The following instructions are also provided to remind you of the need to take safety precautions when working on the installed equipment.

Electrical - In direct expansion systems incorporating Aircooled Condensers, the starting of

these units is controlled by the associated Air Handling Units. Therefore these units should be isolated electrically BEFORE any servicing/maintenance is attempted using the isolators fitted to the units.

- Isolate at mains isolator BEFORE any access panels are removed for servicing or maintenance. Mains isolator should be used to stop Unit in emergency conditions.

- Refer to the wiring diagrams and the units rating plate for the mains electrical supply for which the unit is suitable. The units MUST NOT be used on other electrical supplies without the prior approval of the Equipment Supplier.

- Observe all electrical safety labels fitted to various parts of the unit / system. - Observe all national / local codes of practice for electrical installation (e.g. IEE

Wiring Regulations).

Mechanical - It should be noted that Aircooled Condensers are delivered with a 5 psig Nitrogen

holding charge, which MUST be released before any work is carried out. - Any part of a refrigeration circuit which is being serviced should be fully removed

of refrigerant gas BEFORE any work is attempted on any of the refrigeration components. See Control of Refrigerant Discharge.

- If any heat or flame is to be used on or near to the unit and its associated installation due care should be taken to avoid contact with any combustible surfaces. Furthermore, it should be noted that some refrigerants may give off toxic fumes when heated. Whenever heat or flame is used, the working area should be thoroughly ventilated BEFORE and DURING the operation. Proper fire precautions should be observed and any necessary fire safety equipment should be on hand, typical for electrical, oil or foam fires.

- Observe any safety labels fitted to various parts of the unit / system.

General Beware of the following danger areas within the unit when running:

(a) Any rotating components (fans, pulleys, etc.).

(b) Sharp edges (coil fins, sheet metal, etc.).

(c) Hot or cold refrigeration pipework.

(d) Possible live electrical components or terminals.

Page 5: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Aircooled Condensing Units

PR-2007-0345-GB Subject to modifications Status 05/2007 5

Aircooled Condensing Units The correct installation of Condensing Units together with the associated Air Handling Units is of vital importance if the unit is to perform satisfactorily. The correct sizing of any interconnecting pipework is imperative to ensure that excessive pressure drops do not cause operational problems, whilst pipe velocities are sufficient to ensure oil return, all these factors being site dependent.

It is also recommended that any work required on the refrigeration circuit be carried out by a CITY and GUILDS 2077 FULLY QUALIFIED REFRIGERATION ENGINEER.

Unit Specification Components are mounted on a rigid aluzink steel base and enclosed by plastic coated metal side sections and top lid. The base has plastic coated steel channel feet to assist in transporting and sitting the unit. The feet have holes for securing the unit in position when installed.

The coil and fan(s) are mounted vertically so that air is drawn through the coil and discharged horizontally through a plastic-coated wire fan guard. The fan(s) and guard(s) are mounted on an aluzink steel diaphragm. The compressor and electrical components are mounted in a sealed compartment at the end of the unit.

Access to this compartment is by a removable panel fitted with a door interlocked mains isolator. If required, additional access to this area and to the fan(s), can be provided by removing the lid and side panels, which are held in place by self-tapping screws.

The refrigerant pipework between the compressor and condenser is fitted with a vibration eliminating connector. The compressor suction pipework is looped to prevent vibration damage. Condenser liquid and compressor suction pipes terminate as stub connections protruding through a recessed, aluzink service panel. The compressor is protected by HP/LP switches, and condenser pressure is controlled by a fan switch (fan speed controller may be fitted as an option). HP/LP service tappings are on the compressor valves.

The Condensing Units are normally delivered with a 5 p.s.i.g. holding charge of nitrogen.

The Condensing Units are normally wired for direct starting from the Air Handling Unit's controls. A four (4) core 3 phase and neutral cable is required for the power supply, which is normally supplied from the MCB’s within the Air Handling Unit. For Standard (single compressor) units, a four (4) core cable is required between the Air Handling Unit and Condensing Unit for control signal and alarms, whilst for V.R.F. (twin compressor) units a seven (7) core cable is required. The HP/LP switches have normally open contacts for use when alarm signals are required. These alarms are connected into the microprocessor controls using the additional cores in the signal cable. Signal cables must be segregated from cables carrying mains potential (refer to "Cable Segregation" later in this Manual).

The compressors are robust, hermetic scroll type running on refrigerant R407C, and are complete with isolation valves, crankcase heater and oil level sight glass. The compressor is provided with an electrical contactor.

For details of compressor size fitted to each Condensing Unit see tables overleaf.

Page 6: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units STANDARD UNITS (Single Compressor Units) C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 6

STANDARD UNITS (Single Compressor Units) CU Model

Compressor Copeland

Face Area m2

Airflow † m3/s

Notes

CT 18 ZR18K4E CT 22 ZR22K3E 0.300 0.61 CT 28 ZR28K3E CS 28 ZR28K3E CS 34 ZR34K3E 0.450 0.91 CS 40 ZR40K3E CM 40 ZR40K3E CM 48 ZR48K3E 0.700 1.19 CM 61 ZR61KCE CP 61 ZR61KCE CP 72 ZR72KCE CP 81 ZR81KCE 0.876 1.83 CP 90 ZR90K3E CL 90 ZR90K3E CL 11 ZR11M3E CL 12 ZR12M3E CL 16 ZR16M3E 1.410 3.40 CL 19 ZR19M3E

† The plastic-bladed propeller fans provide the above volumes with no restrictions on air inlet and air outlet. Restrictions will reduce airflow with corresponding reduction in performance.

V.R.F. UNITS (Twin Compressor Units) CU Model

Compressor Copeland

Face Area m2

Airflow † m3/s

Notes

CPV 48 ZR48K3E 0.876 1.83 CLV 48 ZR48K3E CLV 61 ZR61KCE 1.410 3.40 CLV 72 ZR72KCE CLV 81 ZR81KCE

† The plastic-bladed propeller fans provide the above volumes with no restrictions on air inlet and air outlet. Restrictions will reduce airflow with corresponding reduction in performance.

Page 7: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range R407C Refrigerant Charges

PR-2007-0345-GB Subject to modifications Status 05/2007 7

R407C Refrigerant Charges

Condensing Unit

R407C Charge kgs

R407C Charge lbs

CT18 - CT28 0.95 2.1 CS28 - CS40 1.3 2.9 CM40 - CM61 1.9 4.2 CP61 - CP90 2.2 4.8 CL90 - CL19 3.3 7.2

Condensing Unit

R407C Charge kgs

R407C Charge lbs

CPV48 2.2 4.8 CLV48 - CLV90 3.3 7.2

IMPORTANT: The figures shown above are for the Aircooled Condensing Units ONLY and do not include the Air Handling Unit or for any interconnecting pipework. Refer to Air Handling Unit Range Installation Manuals for the actual Air Handling Unit R407C refrigerant charges.

Oil Charging Recommended Refrigeration Oils within GEA Denco Equipment

Unit fitted with Copeland Compressors

Refrigerant In Compressor or Recharging Oil

To Top Up Oil

R407C RL32-CF RL32-S

R134a RL32-CF RL32-S

The refrigerant compressor is filled with sufficient oil for standard installations where the liquid line run is under thirty (30) metres. Where runs are longer than this, additional oil as indicated above is required. As a guide, 5 g of oil should be added for each additional 1.0 kg of refrigerant charge. Additional oil should be added to ensure correct operation of oil traps (where fitted).

- Refrigerants R407C and R134a can ONLY be used with ester oils, however refrigerant R22 should be used with mineral oils. Mineral and ester oils MUST NEVER be mixed.

- Ester oils are very hygroscopic and therefore must not be exposed to the air for any length of time.

Page 8: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Drawing Schedule C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 8

Drawing Schedule The following drawings are included:

Condensing Unit Drawing Number CT18 to CP90 and CPV48 10311-C-146 CL90 to CL19 CLV48 to CLV90 10311-C-147

The following Schematic Wiring Diagrams using 24 Volt controls are included:

Condensing Unit Drawing Number CT18 to CT28 (1 phase) 10358-C-204 CT22 to CP81 10358-C-201 CP90 10311-C-202 CL90 to CL19 10311-C-203 CPV48 10311-C-221 CLV48 to CLV90 10311-C-223

Page 9: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range 10311-C-146

PR-2007-0345-GB Subject to modifications Status 05/2007 9

10311-C-146

Page 10: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units 10311-C-147 C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 10

10311-C-147

Page 11: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range 10311-D-204

PR-2007-0345-GB Subject to modifications Status 05/2007 11

10311-D-204

Page 12: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units 10311-D-201 C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 12

10311-D-201

Page 13: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range 10311-D-202

PR-2007-0345-GB Subject to modifications Status 05/2007 13

10311-D-202

Page 14: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units 10311-D-203 C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 14

10311-D-203

Page 15: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range 10311-D-221

PR-2007-0345-GB Subject to modifications Status 05/2007 15

10311-D-221

Page 16: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units 10311-D-223 C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 16

10311-D-223

Page 17: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Storage and Operating Environment

PR-2007-0345-GB Subject to modifications Status 05/2007 17

Storage and Operating Environment 1. Storage and operating conditions for the Aircooled Condensing Unit are as follows:

Maximum Storage Ambient 55 oC Minimum Storage Ambient 0 oC Maximum Operating Ambient 50 oC Minimum Operating Ambient † 5 oC Maximum Humidity 90 % non condensing

† For Operating Ambients below 5oC the following is recommended:

For Ambients down to –25oC: it is recommended that a "Winter Start Kit" be fitted. This consists of separate HP and LP switches and an LP timer. This is sometimes fitted to the Air Handling Unit as standard.

For Ambients down to -40oC: it is recommended that a "Extra Low Ambient Temperature Kit (ELATE)" be fitted. This consists of a horizontal liquid receiver with trace heating and pressure relief valve situated in a special section under the main unit, and includes separate HP and LP switches and an LP timer. This Kit increases the overall height of the Condensing Unit by approximately 400mm.

Receiving the Equipment On receipt, the equipment should be carefully checked against the Despatch Note and examined carefully for damage. Any shortage or damage should be reported to the Carrier immediately. Ensure the equipment is stored in a suitable safe environment before installation into its working place.

Please note that Aircooled Condensing Units (version "X") are supplied with a 5 p.s.i.g. Nitrogen holding charge.

Offloading and Lifting It is recommended that wherever possible all lifting and handling of equipment should be carried out with the packing pallet in position. When slinging or using a fork-lift or stack-a-truck to lift the unit, the two support points should be sufficiently apart to give stability when lifting and suitably placed to distribute the load on the forks. When lifting by crane, use spreader bars to prevent compressing the top of the equipment (see General Arrangement drawings for relevant unit centre of gravity). Care should be taken not to drop the unit and should this inadvertently happen, it should be immediately unpacked and inspected for damage.

Unpacking Units Remove the wooden crate (if applicable) using appropriate tools and taking care not to damage the cardboard protection and unit beneath. The cardboard case should then be lifted from the unit. Beneath the cardboard case is a protective polythene cover.

NOTE: A door interlocked type isolator is fitted, its handle and fascia are packed within the control panel.

Levelling Units The unit should be set in an upright position - level in both directions. Failure to carry out levelling correctly may cause operational problems. Pack as required below to bring into alignment.

Page 18: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Condenser Location on Site C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 18

Condenser Location on Site ❒ Ensure that the site is level and that it can support the

weight of the equipment. ❒ Condensing Units must be located in an unobstructed

position to ensure adequate air circulation through the cooling coils. Care must be taken to avoid "short circuit" air paths and recirculation of air from one unit to another.

❒ Whenever possible, position Condensing Units that they are reasonably sheltered from strong winds and avoid prevailing winds blowing directly onto the fan(s). Units should be bolted down in case of high winds.

❒ Condensing Units should not be sited more than 15m (50ft) above or 4m (13ft) below the base of the air conditioning unit.

❒ Access space should be provided as detailed on the sketches below but allowing at least 1 metre free access in front of the compressor/switchgear section on Condensing Units

Important: NOTE: All Condensers are supplied with a 5 psig NITROGEN holding charge.

Access Access is gained by means of a removable panel secured by two screws. The panel also contains the interlocked door isolator, which will have to be turned to the `OFF' position, before the panel can be removed. This panel is situated on the left-hand side of the unit (looking at the fan). For major service work such as replacing the compressor, the top and side panels may be removed. The compressor is of the fully hermetic type and, apart from the usual service checks, no other maintenance is necessary.

Page 19: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Noise Considerations

PR-2007-0345-GB Subject to modifications Status 05/2007 19

Noise Considerations It is important that the problems of noise are considered at all points in the installation of equipment. In order to reduce these problems, the following measures are suggested, dependent upon site conditions:

- Abrupt bends in pipework should be avoided by fitting long turn elbows or forming long radius bends.

- All pipes should be rigidly supported to a solid structure. - Where pipes pass through walls or partitions, provide an oversize sleeve and

pack with fibreglass or similar insulation material. - Insulate pipes, and box in with sound-deadening material to solid structures.

Noise Levels The airborne noise emission does not exceed 70 dB(A) at three (3) metres under load conditions measured using a Precision Impulse Sound Level Meter (BS 5969 Type 1) in freefield conditions.

Cable Segregation Ensure that segregation is maintained between control wiring (24V AC or DC) and mains potential wiring (415V/240V AC) throughout the entire installation.

The ramifications are:

- Control signals to condensing units must be run in a separate cable to the mains power cabling.

- Where it is unavoidable that power and signal/control cables run in close proximity, ensure that there is a gap of AT LEAST 30 mm between each category.

- Ideally power and signal/control cables should never cross, but if unavoidable, ensure that they cross at 90o (right angles) to each other.

IMPORTANT: Any additional equipment installed in the control section, or supplied from it, will render the warranty invalid, unless it is verified and approved by the GEA Denco Technical Department.

Suppression All relay and contactor coils within the condensing units are fitted with CR network type suppressors (120 OHM + 0.1 microfarad). These are mounted either directly across the coil connections, or mounted on PCB's to which the relay or contactor is connected.

If additional relays or contactors (240V or 24V AC) or any other inductive load capable of generating electromagnetic interference (EMI's) is to be installed within the equipment (or directly supplied from it). Ensure that these components are suppressed as close to the source of EMI generation as possible.

NOTE: Remember! Any additional equipment installed in the Unit must be verified and approved by the GEA Denco Limited Technical Department, and must comply with EMC Standards in force.

Page 20: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Refrigeration Pipework C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 20

Refrigeration Pipework Pipes must be properly sized, and the pipework system designed, having regard to ensuring oil return to compressors and avoidance of excessive pressure drops.

All refrigeration pipework should be installed to national and local standards as detailed in GEA Denco Code of Practice CP 12.

All soldering / brazing should be done in accordance with the requirements of the European Pressure Equipment Directive (P.E.D.), which includes soldering / brazing certification.

Extreme care should be taken to keep refrigeration tubing clean and dry before installation and the following procedures will help to adhere to good practice:

1. Only refrigeration grade copper tubing correctly sealed against contamination should be used.

2. Do not carry out installation outside whilst it is raining.

3. Always cap the free end of tubing whilst carrying out installation.

4. Do not leave dehydrated compressors or filter/driers open to the atmosphere.

5. Use only copper eutectic or specialist soft solders containing at least 3.5% silver on suction and liquid lines and high temperature copper eutectic rods or silver solder on discharge lines. It is suggested that one of the following are used:

(a) Copper to copper - Eutectic 1805 (2% silver) - no flux. (b) Copper to brass - Eutectic 1805 - flux 1802. (c) Copper to steel - Eutectic 1810 (2% silver) - flux 1820.

NB: STANDARD SOFT SOLDER MUST NOT BE USED.

6. With any high temperature rod where oxidisation is liable to take place use an inert gas such as dry nitrogen or carbon dioxide to avoid scale formation inside the tubing. Dry nitrogen is preferred.

7. When using soldering paste or flux use the minimum required to prevent contamination of the filter and joint. Flux only the male part of the connection - never the female. After making the joint remove the surplus flux with a damp cloth.

8. Where vibration eliminators are used the ends should be wrapped with a damp cloth and rods with a melting temperature of no greater than 650oC (1200oF) should be used to avoid damage to the internal joints.

Leak Testing After all lines are connected, but before they are insulated, the system must be leak tested. The use of an electronic leak detector or halide torch is recommended. For a satisfactory installation, the system MUST be leak tight.

Leak testing should be carried out before initial charging and after any service work has been carried out, and before evacuation. This is done by charging refrigerant gas until system pressure is approximately 1.4 bar and then pressurising with dry nitrogen to a maximum pressure of 24 bar. Refer to Control of Refrigerant Discharge.

Page 21: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Electrical

PR-2007-0345-GB Subject to modifications Status 05/2007 21

Electrical WARNING: DANGEROUS VOLTAGE LEVELS EXIST WITHIN THIS EQUIPMENT. USUAL ELECTRICAL SAFETY PRECAUTIONS MUST BE OBSERVED. THIS EQUIPMENT MUST BE EARTHED.

All installation wiring associated with this equipment must comply with the latest edition of the IEE Regulations to national and local codes of practice, and any relevant British Standards. A set of relevant electrical schematic drawings for the unit are secured inside the electrical hinged door for your reference.

Mains Supply This equipment in its standard form, is designed to operate with an electrical supply of 400-415 V/3 phase/4 wire/50 Hz or 380 V/3 phase/4 wire/50 Hz .

The phase sequence to the isolator is shown on the schematic wiring diagrams.

The classification of this equipment is Class 1, as defined in the IEE Regulations and BS 2754 (1976) as:

"Equipment in which protection against electric shock does not rely on basic insulation only, but which includes an additional safety precaution in such a way that means are provided for the connection of accessible conductive parts to the protective [earthing] conductor in the fixed wiring of the installation in such a way that accessible conductive parts cannot become live in the event of a failure of the basic insulation".

Always use the appropriate holes provided in the gland plate for terminating incoming and outgoing cables. Do not remove any blanking plugs from redundant holes as these protect against particle ingress. Use the correct gland for the type/size of cable being installed.

IMPORTANT: As a matter of common sense NEVER cut additional entry holes into the top of the electrical enclosure as this will deposit swarf, etc onto the delicate printed circuit boards directly underneath.

Terminate all site earth cable conductors to gland plate earth bolt(s) provided. Ensure that the mains electrical supply is of the correct voltage, frequency, phase and rating. Ensure that the cable sizes are of adequate size for the maximum load of the equipment under normal automatic running conditions [see relevant data sheets dependant upon unit configuration].

NOTE: Supply cable sizes must not be determined from maximum FLA figures only - other criteria must be considered, e.g. length of run (and associated volt-drop), installation methods and grouping factors, disconnect times etc. All of these have a de-rating influence on the current-carrying capacity of cables, and are detailed in Appendix 9 of the IEE Regulations.

Before connection to the equipment, check each installed cable for continuity and short circuit (phase/phase, phase/neutral, phase/earth and neutral/earth). Check the tightness of all electrical connections before switching on supply. Check all site connected items before switching on supply.

IMPORTANT NOTE: The Condensing Units incorporate scroll compressors that will only compress in one rotational direction. The rotational direction is dependent upon the phasing of the power to motor terminal connections (L1, L2 and L3). Verification of correct rotational direction is made by observing that the suction pressure drops and discharge pressure rises when the compressor is energised. Reverse rotation results in a sound level above that with correct rotation, as well as substantially reduced current drawn compared to tabulated values. There is no negative impact on durability caused by operating the scroll compressors in the reverse direction, however, after several minutes the compressor internal protection will trip. THIS PROTECTIVE DEVICE SHOULD NEVER BE BY-PASSED FOR ANY REASON.

Page 22: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units Pre-operational Checklist C-Range

PR-2007-0345-GB Subject to modifications Status 05/2007 22

Pre-operational Checklist After all necessary installation work has been completed and before the mains supply is applied to the unit, ensure you have read all the previous sections of this manual, and that the relevant parts have been fully complied with.

- If the unit has been stored in a colder environment than its final permanent site, allow an adequate period for acclimatisation and evaporation of any condensation that may have occurred before the mains power supply is connected to the unit.

- Keep access panels/doors closed as much as possible to prevent the unnecessary ingress of dust or other particles.

- Ensure that all exterior access panels have been replaced to provide correct airflow when switched on.

- When the unit is running, if switched off do not switch back on for a period of at least 20 seconds.

ALWAYS REPLACE THIS MANUAL IN THE SERVICES SECTION OF THE UNIT.

WARNING: DANGEROUS VOLTAGE LEVELS EXIST WITHIN THIS EQUIPMENT. USUAL ELECTRICAL SAFETY PRECAUTIONS MUST BE OBSERVED.

Control of Refrigerant Discharge By international agreement the world-wide use of certain refrigerants will be reduced in stages. To this end listed below are suggestions on how refrigeration engineers can make a contribution by the discontinuing of releasing any refrigerant gas to the atmosphere. Release of refrigerant to the atmosphere is an offence under Section 33 of the Environmental Protection Act 1990.

DO NOT ….. DO ….. (1) Blow off refrigerants to atmosphere. (1) Pump down into a receiver or empty cylinder using Reclaim Equipment. (2) Use refrigerants to clean coils etc. (2) Clean coils etc. using a hand brush, vacuum or compressed air. (3) Leak test using pure refrigerant. (3) Leak test using Nitrogen and just a trace of refrigerant gas. (4) Recharge before mending leaks. (4) Find and mend leaks before recharging system. (5) Dispose refrigerant gas to waste. (5) Send used refrigerant gas back for reprocessing.

Page 23: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GEA Aircooled Condensing Units C-Range Servicing: Direct Expansion Systems

PR-2007-0345-GB Subject to modifications Status 05/2007 23

Servicing: Direct Expansion Systems

Action Notes Generally inspect unit for any problems, including noise, sealing, leaks, insulation, bearings, drains etc.

-

Check fan mounts, cleanliness and operation. - Check pipework connections for leaks also condition of local insulation.

-

Check generally condition and fixing of all pipework and insulation etc. - Check that compressor is securely fixed, anti-vibration mounts are tight and oil level is correct.

-

Check operation of compressor crankcase heater. - Check operating pressures. If not correct check for leaks. Check operation of ALL pressure switches and safety devices., - - Check refrigerant temperatures. - Check that electrical connections are tight. - Check Condensing Unit for rust. Clean off any rust, prime and top

coat. Ensure that Aircooled Condensing Units are free from leaves, dirt, debris, etc.

-

Page 24: A_VK_PR-2007-0345-GB_DENCO-C-Range_BA_2007-05_150dpi

GB Denco Ltd.UK-HR4 8DS HerefordTel. +44 / 1432 / 277 277

N GEA Klimaprodukter ASN-0484 OsloTel. +47 / 220 / 27990

UA GEA Ukraina t.o.v.UA-01135 KyivTel. +38 / 044 / 4619356

TR ISISANTR-80700 BalmumcuIstanbulTel. +90 / 212 / 2757171

SLO GEA KlimatizacijskaTehnika d.o.o.SI-1000 LjubljanaTel. +386 / 1 / 2573850

SK GEA Klimatizácia s.r.o.SK-83104 BratislavaTel. +421 / 7 / 44457917

GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

SRB

S GEA EXOSVentilation ABS-74528 EnköpingTel. +46 / 171 / 85530

RUS GEA KondicionerMoskvaRU-105094 MoskvaTel. +7 / 495 / 9566674

P Nónio, Lda.P-1269-090 LisboaTel. +351 / 21 / 3826160

LV GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

LT GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

L GEA Happel LuxembourgL-4940 BascharageTel. +352 / 26 / 502970

IS Rafn JenssonIS-110 ReykjavikTel. +354 / 56 / 780-30

PL GEAKlimatyzacja Sp. z o.o.PL-54610 WroclawTel. +48 / 71 / 3737952

HR GEA Klima-rashladnatehnika d.o.o.HR-10000 ZagrebTel. +385 / 1 / 6064900

FIN OY TEKNOCALOR ABFIN-01300 VantaaTel. + 358 / 9 / 82546020

F GEA Happel France sarlF-59436 Roncq CedexTel. +33 / 3 / 20689020

EST GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

E GEA Air TreatmentMarketing ServicesInt. GmbH - oficina EspañaE-28036 MadridTel. +34 / 91 / 3837701

DK GEA Klimateknik ApSDK-2610 RødovreTel. +45 / 38 / 887070

H GEA Klimatechnika KftH-1037 BudapestTel. +36 / 1 / 4393200

D GEA HappelKlimatechnik GmbHD-44625 HerneTel. +49 / 2325 / 468-00

CZCZ-46312 LiberecTel. +420 / 48 / 5225-111GEA Klimatizace spol. s r.o.CZ-46312 LiberecTel. +420 / 48 / 5225-303

GEA LVZ, a.s.

CH GEA KlimatecSchweiz AGCH-3065 Bolligen-StationTel. +41 / 31 / 9171919

BY GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

BIH GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

BG EVISS Ltd.BG-7000 RousseTel. +359 / 82 / 81000

B GEA Happel Belgium N.V.B-1130 BrusselsTel. +32 / 2 / 2406161

A GEAKlimatechnik GmbHA-4673 GaspoltshofenTel. +43 / 7735 / 8000-0

NL GEA HappelNederland B.V.NL-2909 LLCapelle a/d IjsselTel. +31 / 10 / 2350606

RO GEA Klimatechnik s.r.l.RO-300222 TimisoaraTel. +40 / 356 / 423703

GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

MWE

Our Market in Europe

Air Treatment Division For detailed information on all corporate areas,go to www.gea-airtreatment.com or contactus by email [email protected] company of GEA Group

PR-2

007-

0345

-GB

• S

ub

ject

to

mo

dif

icat

ion

s •

Stat

us

05/2

007

• C

op

yrig

ht

GEA

Air

Tre

atm

ent


Recommended