40
Axial Fans www.systemair.de
Transcript

Ax

ial

Fan

s

www.systemair.de

2

Systemair GmbH is part of the Systemair Group with head-quarters in Skinskatteberg, Sweden. The production facilities are located in Sweden, Norway, Denmark, Germany, Slovenia, Lithuania, Canada, Slovakia and Spain with a total production area of more than 130 000 sqm.

Systemair GmbH, Boxberg-Windischbuch, Germany

Systemair AB, Skinnskatteberg, Sweden

Complete Range of Axial Fans

Whatever requirements and applications you may have, the axial fan range of Systemair is just as global and comprising. The fields of operation range from huge shopping cen-tres, to underground car parks, up to tunnel- and MRT-projects in the whole world. Safety related fans such as smoke exhaust and explosion proof fans are part of our core competence.

Our quality management system which is certified to ISO 9001: 2000 is one reason for our high quality standards. In our modern R&D centre we test in compliance with the international standards ISO and AMCA.

At Systemair you benefit from an international network from more than 50 companies. This guarantees you response times even with international projects, as the contact per-son is never far away. You are sincerely invited to visit our production site for axial fans in Germany or our headquarters in Sweden to convince yourself on-site of our high quality standards.

This catalogue shows you the entire spectrum of our possibilities. Have a look at an Axial Fan program at its best and trust our decade-long experience. Our expert team will be pleased to

be at your disposal!

3

Contents

General technical description 4 - 5

Axial fans AXC 6 - 7

Smoke extract axial fans 300°C / 120 min. AXC (B) 8 - 9

Stock ranges AXC / AXC (B) 10 - 11

Smoke extract axial fans 400°C / 120 min. HA 12 - 13

Smoke extract axial fans 600°C / 120 min. HABV 14 - 15

Bifurcated axial fans AXCBF 16 - 17

Explosion proof medium pressure axial fans AXC-EX / AXCBF-EX 18 - 21

Car park jet fans AJR / AJ8 22 - 23

Tunnel jet fans AJ (T) 24 - 27

Special applications 28

List of references 29 - 31

Fan Specifications 32 - 39

Systemair test rigs , Skinnskatteberg, Sweden

Systemair test rigs, Boxberg-Windischbuch, Germany

44

General technical description

Systemair offers a wide range of axial fans in various designs. For most applications in the ventilating or air conditioning sector as well as in a lot of industrial and commercial applications a Systemair fan can be selected. Some examples are: mining, tunnelling with truly reversi-ble impellers, car park ventilation, applications in explosi-on hazardous areas and high temperature fans to extract heat and smoke in case of a fire.

Finding the right solution is important from many aspects: Trust in the product and producer, safety in the applica-tion, lowest possible energy consumption, good and

Available fan ranges

matching functionality, the cost benefit ratio, a space saving design, the delivery just in time and many more.

This brochure gives you an overview of our complete axial fan product range, so you can choose the right fan for your application. Performance curves and technical details for the required fan duties are available from our selection programme, which can be downloaded from our homepage: www.systemair.de. You can, of course, also order it directly from our customer support.

Fan range ApplicationImpeller diameter (mm)

-20°/55°C 200°C300°C/120min

400°C/120min

600°C/120min

Car Park Jet Tunnel JetExplosive atmosphere

AXC supply/exhaust 315 - 2.000 x

AXC (B) exhaust 315 - 1.600 x x

AXCBFbifurcated

motor out of airstream

250 - 800 x

HA (F) exhaust 315 - 1.600 x

HABV exhaust 450 - 1.800 x x

AJR / AJ8impulse

ventilation315 - 400 x x

AJR (B) / AJ8 (B)impulse

ventilation315 - 400 x x

AXCEX exhaust/supply 315 - 1.600 x x

AXCBF-EX exhaust 250 - 800 x x

AJ impulse ventila-tion reversible 500 - 1.600 x x

AJ (T)* impulse ventila-tion reversible

500 - 1.600

710 - 1.400 x

xx

...-P wall mounting 315 - 1.000 x x x x

...-D roof mounting 315 - 1.800 x x x x

...-G high pressure 315 - 2.000 x x x

Quality:

ISO 9001:2000: Quality management system, monitored by DQS group. Certificate on www.systemair.de.

DIN 24166: Technical terms of delivery for fans.

Fan description

project:customer:contact:date:page:

29.04.20081

Axial Fan:AXC 900-10 / 21° - 6

Tel:Fax:Mail:

Systemair GmbHSeehöfer Str. 45D-97944 Windischbuch

+49 (0) 79 30 / 92 72-0+49 (0) 79 30 / 92 [email protected]

fan data

air volume [m3/h] 20.000air density [kg/m³] 1,200static pressure [Pa] 243dynamic pressure [Pa] 46total pressure [Pa] 289air velocity [m/s] 8,74efficiency [%] 71,1shaft power [kW] 2,38max. shaft power [kW] 2,41blade angle [°] 21

motor data

size 132Stype of construction B3protection class/Iso class IP55 / Fpower supply 3x400V /50Hznumber of poles 6

Characteristics:

960 1/min - 3,00 kW - 7,00 A

In case of order, rated motor datacan stightly deviate depending on motor brand!

sound dataHz

Lw-dBdB(A) 3m

63 125 250 500 1000 2000 4000 8000Sum.

87,6 90,6 92,6 90,6 89,6 85,6 79,6 73,697,643,9 57,0 66,5 69,9 72,1 69,3 63,1 55,075,5

fan price /grosswithout accessories

Dimensions [mm]Da Di hF Tk E F bF K L s zxd1004 894 580 934 830 900 80 612 700 4,0 24x12Weight [kg](without accessories)

165

airflow [m3/h]

42.0

0041

.000

40.0

0039

.000

38.0

0037

.000

36.0

0035

.000

34.0

0033

.000

32.0

0031

.000

30.0

0029

.000

28.0

0027

.000

26.0

0025

.000

24.0

0023

.000

22.0

0021

.000

20.0

0019

.000

18.0

0017

.000

16.0

00

15.0

00

14.0

00

13.0

00

12.0

00

11.0

00

10.0

00

9.00

0

8.00

0

7.00

0

dPTo

t [P

a]

350

300

250

200

150

100

50

0

P1

[kW

]

4,54

3,53

2,52

1,51

0,50

8° 10° 12° 14° 16° 18° 20° 22° 24°

26° 28° 30° 32°

Pd2

8° 10° 12° 14° 16° 18° 20°

22° 24°

26° 28°

30° 32°

Systemair is working in accordance with the following standards:

* EN 12101-3 certification in progress

CE-marking: The CE marking is a mandatory conformi-ty mark in the European Economic Area. By affixing the CE marking, the manufacturer asserts that the item meets all the essential requirements of the relevant European Directive(s).

55

GFLCounterflange

RSA (B)Silencer

EV-AXCEVH (F400) EVH (F600)Flexible connection LRK (F)

Air operateddamper

Fan

ESD-FBellmouth inlet

SGProtection guard

MFAMounting feet

SD (4x)AV rubber mounts

MP (4x angle 90°)Mounting brackets

FSD (4x)AV spring mounts

Fan installation with accessories

Testing:

DIN ISO 5801: “industrial fans, performance testing…”

DIN 24163: “fans, performance testing…”

AMCA 210-99: “Laboratory methods of testing fans foraerodynamic performance rating”

EN 12101-3: “smoke and heat control systems - powered smoke and heat exhaust…”

ISO 13350: Jet fans

EC-declaration of conformity. Certificate on www.systemair.de

• As per EC Machinery Directive 98/37/EEC Annex IIA, fans for ventilation… the following harmonized stan- dards are used:

- EN 60 204-1: “safety of machinery - electrical equip- ment, general requirements”

- EN 292-1: “safety of machinery, design”

- EN 294: “safety of machinery, safety distances”

- EN 60 034-1: “rotating electric machinery, ratings and performance”

• As per EC low Voltage Directive 73/23/EEC and 93/68/EEC the following harmonized standards are used:

- EN 60 204-1: “safety of machinery - electrical equip- ment, general requirements” - EN 60 034-5: “rotating electric machinery, protection classification”

• As per EMC-directive 89/336/EEC and EMC-directive 93/68/EEC the following harmonized standards are used:

- EN 61000-6-2 and 6-3: electromagnetic compatibility

REVon/off switch

66

Standard features:

• Aerofoil impeller with adjustable pitch angle for maximum efficiency

• Die cast aluminium hub and blades

• Long casing, hot dip galvanized steel, to DIN EN ISO 1461

• Spun flanges for high rigidity, to DIN 24154 series 3

• Terminal box in IP65 mounted at the outside of the casing for easy wiring

• Single- or three-phase motors IP55, insulation class F, in accordance with EN 60034-5/IEC 85

• Suitable for operating temperatures of up to 55°C

• Inspection hole to verify correct direction of rotation

AXC Axial Fans

The Systemair AXC range of long cased medium pressure axial fans is available in sizes from 315 up to 2.000 mm impeller diameter. The adjustable pitch angle setting offers a wide performance and maximum flexibility to match precisely indivi-dual airflow requirements. The AXC axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. Three years warranty make it a safe choice.

High efficiency impellers

The die cast aerofoil aluminium impellers can be offered with full or fractional solidities, maximum effi-ciencies can be obtained. Different impeller/hub configurations allow high pressure drops.

Sturdy casing

AXC axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range. Also available with super short casing and with an acoustically insulated box.

Motors

The built-in motors are equipped with PTC thermistors for optimum motor protection. Single or two speed motors. 60 Hz applications on request. Speed controllable by frequency converter.

Multi stage fans

For higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.

Quality

Systemair is ISO 9001: 2000 approved. The Systemair quality is regularly monitored by TÜV Süd.

Warranty

Systemair offers a three year warranty on all AXC fan models. The Systemair warranty conditions apply.

AXC AXC-G

Ordering code

AXC 630 - 9 / 22° - 2 -

2-pole motor

Pitch angle

Number of blades

Impeller diameter

Axial fan

G Two stage, two fans in series B Sound insulated

77

315

355

400

450

500

560

630

710

800

900

1000

1250

0 15.000 30.000 45.000 60.000 75.000 90.000 105.000 120.000 135.000 150.000 165.000 180.000 195.000 210.000 225.000 240.000 255.000

0 15.000 30.000 45.000 60.000 75.000 90.000 105.000 120.000 135.000 150.000 165.000 180.000 195.000 210.000 225.000 240.000 255.000

max. 2.150 Pa static

max. 1.600 Pa static

max. 1.300 Pa static

max. 1.000 Pa static

max. 780 Pa static

max. 660 Pa static

max. 840 Pa static

max. 1.100 Pa static

max. 1.200 Pa static

max. 1.600 Pa static

max. 2.600 Pa static

Air volume [m³/h]

Siz

e

1400

AXC-G

1600

315

355

400

450

500

560 E

560

630

710

710 E

800

900

1000

1120

1250

1400

1600

1800

2000

Air volume [m³/h]

Siz

e

AXC55°C

on request

on request

max. 900 Pa static - 6-pole

max. 1300 Pa static - 4-pole

max. 720 Pa static - 6-pole

max. 1100 Pa static - 4-pole

max. 750 Pa static - 4-pole

max. 600 Pa static - 4-pole

max. 500 Pa static - 4-pole

max. 400 Pa static - 4-pole

max. 1423 Pa static - 2-pole

max. 1400 Pa static - 2-pole

max. 950 Pa static - 2-pole

max. 1280 Pa static - 2-pole

max. 750 Pa static - 2-pole

max. 600 Pa static - 2-pole

max. 450 Pa static - 2-pole

max. 350 Pa static - 2-pole

max. 300 Pa static - 2-pole

max. 2.600 Pa static

max. 1.450 Pa static

max. 1.850 Pa static

Performance GuideAXC and AXC-G Standard TemperatureSelection programme at www.systemair.de

88

AXC (B) Smoke Extract Axial FansAXC (B) Smoke extract axial fans certified for 300°C/2h in accordance with EN 12101-3

AXC (B) AXC (B)-G

The Systemair AXC (B) range of long cased smoke extract axial fans is available in sizes from 315 up to 1.600 mm impeller diameter. The adjusta-ble pitch angle setting offers a wide performance and maximum flexibility to match precisely individual airflow requirements. The AXC (B) axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. High tempera-ture testing at Technical University Munich, Germany. Three years war-ranty make it a safe choice.

High efficiency impellers

The die cast aerofoil aluminium impellers can be offered with full or fractional solidities, maximum efficien-cies can be obtained.

Sturdy casing

AXC axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range.

Motors

Motor in the air stream. Frequency converter controllable only for standard ventilation on request. Single or two speed motors.

Multi stage fans

For higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.

Quality

Systemair is ISO 9001: 2000 appro-ved. The Systemair quality is regularly monitored by TÜV Süd.

Standard features:

• Aerofoil impeller with adjustable pitch angle

• Die cast aluminium hub and blades

• Long casing, hot dip galvanized steel, to DIN EN ISO 1461

• Spun flanges for high rigidity, to DIN 24154 series 3

• Terminal box in IP65 mounted at the outside of the casing for easy wiring

• Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85

• Suitable for operating temperatures of up to 55°C continuous or once for

300°C/2h

• Inspection hole to verify correct direction of rotation

Ordering code

AXC 630 - 9 / 22° - 2 (B) -

300°/120 min.

2-pole motor

Pitch angle

Number of blades

Impeller diameter

Axial fan

Warranty

Systemair offers a three year war-ranty on all AXC (B) fan models. The Systemair warranty conditions apply.

G Two stage, two fans in series B Sound insulated

99

Performance guideAXC (B) for 300°C / 120 min.

0 15.000 30.000 45.000 60.000 75.000 90.000 105.000 120.000 135.000 150.000 165.000 180.000 195.000 210.000 225.000

315

355

400

450

500

560

630

710

800

900

1000

1120

1250

1400

1600

Air volume [m³/h]

Siz

e

AXC (B)

max. 900 Pa static - 6-pole

max. 1300 Pa static - 4-pole

max. 720 Pa static - 6-pole

max. 1100 Pa static - 4-pole

max. 750 Pa static - 4-pole

max. 600 Pa static - 4-pole

max. 500 Pa static - 4-pole

max. 400 Pa static - 4-pole

max. 1400 Pa static - 2-pole

max. 950 Pa static - 2-pole

max. 750 Pa static - 2-pole

max. 600 Pa static - 2-pole

max. 450 Pa static - 2-pole

max. 350 Pa static - 2-pole

max. 300 Pa static - 2-pole

315

355

400

450

500

560

630

710

800

900

1000

1250

0 15.000 30.000 45.000 60.000 75.000 90.000 105.000 120.000 135.000 150.000 165.000 180.000 195.000 210.000 225.000

max. 2.150 Pa static

max. 1.600 Pa static

max. 1.300 Pa static

max. 1.000 Pa static

max. 780 Pa static

max. 660 Pa static

max. 840 Pa static

max. 1.100 Pa static

max. 1.200 Pa static

max. 1.600 Pa static

max. 2.600 Pa static

Air volume [m³/h]

Siz

e

1400

AXC (B)-G

1600

max. 2.600 Pa static

max. 1.450 Pa static

max. 1.850 Pa static

Selection programme on www.systemair.de

1010

Stock Ranges

Stock range is defined as a pre-selected range with fixed blade angles, where Systemair keeps a certain stock of motors for short delivery times. Subject to being unsold.

qv [m³/h]

qv [m³/s]

P s [

Pa]

500

400

300

200

100

0

0 2.000 4.000 6.000 8.000 10.000 12.000 14.000

0 0,55 1,11 1,66 2,22 2,77 3,33 3,88

1

AXC

1 - 315 / 22°-22 - 315 / 32°-23 - 355 / 22°-24 - 355 / 32°-25 - 400 / 16°-26 - 400 / 24°-27 - 400 / 30°-28 - 450 / 24°-29 - 500 / 12°-2

2 3 45 7 986

qv [m³/h]

qv [m³/s]

P s [

Pa] 1200

1000

800

600

400

200

0

0 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000

0 1,38 2,77 4,16 5,55 6,94 8,33 9,72 11,11

10

AXC

10 - 500 / 22°-211 - 560 / 18°-212 - 560 / 24°-213 - 630 / 24°-214 - 630 / 30°-2

11 12 13 14

AXC Standard Temperature

1 315/22°-2 0,55 kW

2 315/32°-2 1,1 kW

3 355/22°-2 1,1 kW

4 355/32°-2 1,5 kW

5 400/16°-2 1,1 kW

6 400/24°-2 2,2 kW

7 400/30°-2 2,2 kW

8 450/24°-2 3 kW

9 500/12°-2 2,2 kW

AXC Standard Temperature

10 500/22°-2 4 kW

11 560/18°-2 7,5 kW

12 560/24°-2 11 kW

13 630/24°-2 15 kW

14 630/30°-2 18,5 kW

1111

Stock Ranges Stock Ranges

qv [m³/h]

qv [m³/s]

P s [

Pa]

750

600

450

300

150

0

0 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000

0 2,77 5,55 8,33 11,11 13,88 16,66 19,44 22,22

15 16

1718

19

20

22 23

24

26

28

21

25 27 29

qv [m³/h]

qv [m³/s]

P s [

Pa] 1200

1000

800

600

400

200

0

0 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000 55.000

0 1,38 2,77 4,16 5,55 6,94 8,33 9,72 11,11 12,5 13,88 15,27

6

AXC (B) F300

1 - 315 / 32°-22 - 355 / 22°-23 - 400 / 16°-24 - 450 / 18°-25 - 500 / 12°-26 - 500 / 22°-27 - 560 / 18°-28 - 630 / 24°-29 - 630 / 16°-410 - 630 / 26°-411 - 710 / 18°-412 - 710 / 26°-413 - 800 / 18°-414 - 800 / 28°-4 15 - 900 / 18°-416 - 900 / 26°-417 - 1000 / 10°-418 - 1000 / 18°-4

7

8

5

1

2

3 4

9 10

1112

1314

15 16

17 18

AXC Standard Temperature

15 630/16°-4 1,1 kW

16 630/20°-4 1,5 kW

17 630/26°-4 2,2 kW

18 710/18°-4 2,2 kW

19 710/26°-4 4 kW

20 800/18°-4 4 kW

21 800/22°-4 5,5 kW

22 900/18°-4 7,5 kW

23 900/22°-4 11 kW

24 900/26°-4 15 kW

25 1000/10°-4 7,5 kW

26 1000/18°-4 15 kW

27 1000/22°-4 15 kW

28 1000/24°-4 18,5 kW

29 1250/14°-4 37 kW

AXC (B) F300

1 315/32°-2 1,1 kW

2 355/22°-2 1,1 kW

3 400/16°-2 1,1 kW

4 450/18°-2 2,2 kW

5 500/12°-2 2,2 kW

6 500/22°-2 4 kW

7 560/18°-2 7,5 kW

8 630/24°-2 15 kW

9 630/16°-4 1,1 kW

10 630/26°-4 2,2 kW

11 710/18°-4 2,2 kW

12 710/26°-4 4 kW

13 800/18°-4 4 kW

14 800/28°-4 7,5 kW

15 900/18°-4 7,5 kW

16 900/26°-4 15 kW

17 1000/10°-4 7,5 kW

18 1000/18°-4 15 kWStock range is defined as a pre-selected range with fixed blade angles, where Systemair keeps a certain stock of motors for short delivery times. Subject to being unsold.

1212

HA Smoke Extract Axial FansHA (F) Smoke extract axial fans certified for 400°C/2h in accordance with EN 12101-3

HA (F)

The Systemair HA (F) range of long cased smoke extract axial fans is available in sizes from 315 up to 1.600 mm impeller diameter. The HA (F) axial fans have been perfor-mance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. High temperature testing at Technical University Munich, Germany. Three years warranty make it a safe choice.

ImpellersFully welded steel impellers tailored to match precisely individual air flow and pressure requirements.

Sturdy casing

HA (F) axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range.

Motors

Motor in the air stream. Frequency converter controllable only for stan-dard ventilation. Single or two speed motors.

Two stage fansFor higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.

Quality

Systemair is ISO 9001: 2000 appro-ved. The Systemair quality is regular-ly monitored by TÜV Süd.

Standard features:

• Welded steel impellers

• Long casing, hot dip galvanized steel, to DIN EN ISO 1461

• Spun flanges for high rigidity, to DIN 24154 series 3

• Terminal box in IP65 mounted at the outside of the casing for easy wiring

• Motors IP55, insulation class H, in accordance with EN 60034-5/IEC 85

• Suitable for operating temperatures of up to 55°C continuous or once for

400°C/2h

• Inspection hole to verify correct direction of rotation

Ordering code

HA 630 - 8 / 22° - 2 (F) -

400°/120 min.

2-pole motor

Pitch angle

Number of blades

Impeller diameter

Axial fan

Warranty

Systemair offers a three year war-ranty on all HA (F) fan models. The Systemair warranty conditions apply.

G Two stage, two fans in series B Sound insulated

1313

Performance guideHA for 400°C / 120 min.Selection programme on www.systemair.de

0 50.000 100.000 150.000 200.000 250.000

Air volume [m³/h]

450

500

560

630

710

800

900

1.000

1.120

1.250

1.400

1.600

max. 510 Pa static

max. 370 Pa static

max. 310 Pa static

max. 790 Pa static

max. 800 Pa static

max. 540 Pa static

max. 440 Pa static

max. 410 Pa static

max. 300 Pa static

max. 300 Pa static

max. 640 Pa static

max. 750 Pa static

max. 1000 Pa static

max. 600 Pa static

max. 880 Pa static

HA400 °C

Siz

e

450

500

560

630

710

800

900

1.000

1.120

1.250

1.400

1.600

1.800

HABV600 °C

0 50.000 100.000 150.000 200.000 250.000 300.000

max. 250 Pa static

max. 450 Pa static

max. 600 Pa static

max. 800 Pa static

max. 350 Pa static

max. 430 Pa static

max. 570 Pa static

max. 720 Pa static

max. 850 Pa static

max. 1.070 Pa static

max. 700 Pa static

max. 800 Pa static

max. 800 Pa static

Siz

e

Air volume [m³/h]

1414

Ordering code

HABV 630 - 8 / 22° - 2

2-pole motor

Pitch angle

Number of blades

Impeller diameter

Axial fan 600°/120 min.

HABVwith inlet guide vane

HABV Smoke Extract Axial FansHABV Smoke extract axial fans certified for 600°C/2h in accordance with EN 12101-3

The Systemair HABV range of long cased smoke extract axial fans is available in sizes from 450 up to 1.800 mm impeller diameter. The pitch angle can be individually set before manufacturing and offers a wide performance and flexibility range to precisely match airflow requirements. The HABV axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. High temperature testing at Technical University Munich, Germany. Three years warranty make it a safe choice.

Sturdy casing

HABV axial fan casings are heavy gauge, hot dip galvanized upon completion, with spun flanges for high rigidity. Integrated inlet guide vane. Insulated motor enclosure with cooling duct for motor cooling.

Motors

Motor outside the stream in insulated enclosure with cooling duct. Quality

Systemair is ISO 9001: 2000 appro-ved. The Systemair quality is regularly monitored by TÜV Süd.

Standard features:

• Welded steel impellers

• Long casing, hot dip galvanized steel, to DIN EN ISO 1461, with integrated guide vane

• Spun flanges for high rigidity, to DIN 24154 series 3

• Terminal box in IP65 mounted at the outside of the casing for easy wiring

• Motors IP55, insulation class H, in accordance with EN 60034-5/IEC 85

• Motor encapsulated, with cooling duct

• Suitable for operating temperatures of up to 55°C continuous or once for

600°C/2h

Warranty

Systemair offers a three year war-ranty on all HABV fan models. The Systemair warranty conditions apply.

1515

0 50.000 100.000 150.000 200.000 250.000

Air volume [m³/h]

450

500

560

630

710

800

900

1.000

1.120

1.250

1.400

1.600

max. 510 Pa static

max. 370 Pa static

max. 310 Pa static

max. 790 Pa static

max. 800 Pa static

max. 540 Pa static

max. 440 Pa static

max. 410 Pa static

max. 300 Pa static

max. 300 Pa static

max. 640 Pa static

max. 750 Pa static

max. 1000 Pa static

max. 600 Pa static

max. 880 Pa static

HA400 °C

Siz

e

450

500

560

630

710

800

900

1.000

1.120

1.250

1.400

1.600

1.800

HABV600 °C

0 50.000 100.000 150.000 200.000 250.000 300.000

max. 250 Pa static

max. 450 Pa static

max. 600 Pa static

max. 800 Pa static

max. 350 Pa static

max. 430 Pa static

max. 570 Pa static

max. 720 Pa static

max. 850 Pa static

max. 1.070 Pa static

max. 700 Pa static

max. 800 Pa static

max. 800 Pa static

Siz

e

Air volume [m³/h]

Performance guideHABV for 600°C 120 min.

1616

AXCBF Bifurcated Axial Fans

The Systemair AXCBF range of bifurcated medium pressure axial fans has been developed for appli-cations with an atmosphere which would either require special motors or reduce the lifetime of a standard motor. The motors of AXCBF are out of the airstream. Available in sizes from 250 up to 800 mm impel-ler diameter. The stock range offers a standard selection with maximum airflow for the installed motor po-wer. Three years warranty make it a safe choice.

Sturdy casing

AXCBF bifurcated axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. The motor compartment allows easy access to the motor terminal box for wiring.

Motors

Single or three phase B3 foot moun-ted motors, totally enclosed and fan cooled. Single phase motors are speed controllable by transformer, with a limitation to ambient temperature of maximum 60°C.

Standard features:

• Stock range, short delivery time

• Aerofoil impeller with adjustable pitch angle

• Die cast aluminium hub and blades

• Bifurcated casing, hot dip galvanized steel, to EN ISO 1461

• Spun flanges for high rigidity, to DIN 24154 series 3

• Single and three phase motors, IP55, insulation class F, in accordance

with EN 60034-5, IEC 85. Terminal box mounted directly onto the motor.

• Suitable for operating temperatures of up to 200°C

Ordering code

AXCBF 630 D 4 - 26°

Pitch angle

4-pole motor

D = 400 V E = 230 V

Impeller diameter

Bifurcated axial fan

Quality

Systemair is ISO 9001: 2000 approved. The Systemair quality is regularly moni-tored by TÜV Süd.

Warranty

Systemair offers a three year warranty on all AXCBF fan models. The Systemair warranty conditions apply.

AXCBF

1717

Performance guideAXCBF Bifurcated Axial Fan

Stock range

Model Curve No.Voltage/frequency

V/HzInstalled motor

kWIntegrated motor

protection

AXCBF 250D2-32 2 400/50 0,37 PTC

AXCBF 250D4-32 1 400/50 0,25 PTC

AXCBF 250E2-32 2 230/50 0,37 ---

AXCBF 250E4-32 1 230/50 0,25 ---

AXCBF 315D2-30 3 400/50 0,75 PTC

AXCBF 315D4-32 4 400/50 0,25 PTC

AXCBF 315E2-30 3 230/50 0,75 ---

AXCBF 315E4-32 4 230/50 0,25 ---

AXCBF 400D2-22 5 400/50 2,2 PTC

AXCBF 400D4-32 6 400/50 0,55 PTC

AXCBF 500D2-20 7 400/50 4,0 PTC

AXCBF 500D4-32 8 400/50 1,1 PTC

AXCBF 630D4-26 9 400/50 2,2 PTC

AXCBF 800D4-18 10 400/50 4,0 PTC

qv [m³/h]

qv [m³/s]

P s [

Pa]

1.400

1.200

1.000

800

600

400

200

0

0 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 18.000 20.000

0 0,55 1,11 1,66 2,22 2,77 3,33 3,88 4,44 5 5,55

1

2

3

4 5

7 986 10

1818

AXC-EX / AXCBF-EX Explosion Proof Axial FansExplosion proof axial fans with ATEX certification in accordance with EN 14986 Standard features:

• Stock range, short delivery time

• Aerofoil impeller with adjustable pitch angle

• Die cast aluminium hub and blades

• Casing, hot dip galvanized steel, to EN ISO 1461

• Aluminium anti-spark ring

• Spun flanges for high rigidity, to DIN 24154 series 3

• Single and three phase motors, IP55, insulation class F, in accordance with EN 60034, IEC 85. Supplied with terminal box Exe mounted at the outer side of the casing. Admissible ambient temperatures from -20° to +40°C, other temperatures on request

• AXC-EX: Inspection hole to verify correct direction of rotation

• AXCBF-EX with motor outside the airstream

AXC-EX

Explosion protection

Gases, vapours and mists which occur during storage, production or processing of flammable substances, together with the oxygen in the air, form an explosive atmosphere. In case this atmosphere is ignited, explosions take place which can be harmful to human beings and dama-ge property. Ignition sources can be for example hot temperatures on surfaces, mechanically generated sparks, static electricity or electrical installations.

Protective standards have been developed in many countries to ensure a high level of safety. In the European Union regulations have been harmonized in EC-directives

Testing authority

Authority

StandardizationManufacturer

Installer

Employer

94/9/EC (ATEX 95, equipment directive, manufacturers or impor-ters) and 99/92/EC (ATEX 137, workplace directive: operation of installations, users).

In short, those directives define the measures to be taken to avoid the ignition of potentially explo-sive atmospheres, i.e. atmospheres which could become explosive due to local and operational conditions. The required safety level depends on the danger potential in the very installation.

In the EC-directives hazardous areas are divided into zones, defining the probability of an explosive atmos-phere (in accordance with IEC 60079-10).

The NEC (National Electrical Code) of USA and the CEC (Canadian Electrical Code) of Canada divide into Classes and Divisions, which might deviate from the EC direc-tives. Gases, vapours or mists are classified in Class 1, then divided into Divisions 1 or 2, then into Gas Groups. Please pay attention which standard has been applied (EC-directives or NEC/CEC).

AXCBF-EX

Zone

Duration of the occurrence of an explosive atmosphere

Equip-ment

category

Gases, vapours,mists

0continuously, for a long period, frequently

1G

1 occasionally 2G

2rarely and for a short period

3G

Ignition source

Air (oxygen)Flammablematerial

Three factors needed for an explosion

1919

Manufacturers of equipment with a potential ignition source (like electric motors, rotating parts) have to ensure that the equipment fulfils the safety requirements given in the relevant directives and codes (grouping and category).

The EC-directives then divide the equipment into Groups. Equipment group I covers mining systems, where a very high or high degree of safety is required.

Equipment group II covers other explosive areas and is divided into categories from category 1 (very high degree of safety, even for inde-pendently occurring faults), category 2 (high degree of safety, even for occurrence of a fault) and category 3 (normal degree of safety – in normal operation conditions).

Electrical equipment of category 2 must undergo an EC type examina-tion, carried out by a notified body. For electrical equipment of catego-ry 3 and non-electrical equipment the manufacturer is authorized to document conformity with the requirements of the EC-directive. CE-marking of the equipment confirms that it has been manufac-tured in compliance with all relevant EC-directives.

Equipment group II is further classi-fied into 3 explosion groups or gas groups. The IEC system is applied in Europe, where IIA is the lowest hazardous gas group, IIB medium and IIC the most volatile gas group. The NEC directives of North America define it the opposite way, where Group A is the most hazardous gas group.

Temperature classesTemperature classes determine the maximum surface temperature of a product at an ambient temperature of max. 40°C, for example an elec-trical apparatus, which should always be lower than the ignition tem-perature of the gas/air or vapour/air mixture in which it is used. The ignition temperature is the lowest temperature at which a hot surface

Temperature class Temperature in °C

T1 450

T2 300

T3 200

T4 135

T5 100

T6 85

Gas groups and temperature classes, some examples:

* extract from the table flammable liquids and gases by E.Brandes and W. Möller, LEL - UEL (lower explosive limit, upper explosive limit)

Systemair offers the following types of ignition protection (for electrical apparatus in explosive gas atmosphere):

MaterialExplosive limit (Vol. %, LEL-UEL)*

Temperature class Explosion/gas group (IEC)

Propane 1,7 - 10,8 T1 IIA

Ethanol 3,3 - 19 T2 IIB

Hydrogen 4 - 77 T1 IIC

Acetylene 2,3 - 100 T2 IIC

Methane 4,4 - 17 T1 IIA

Type of igniti-on protection

Nomenclature RegionInstallation location

Principle Standard applied

Non sparking apparatus "nA"

Ex nA (EEx nA) IEC, EU Zone 2Prevent occurence of sparks

IEC/EN 60079-15

Increased safety "e"

Ex e (EEx e) IEC, EU Zone 1

Prevent excessive temperatures and the occurrence of sparks

IEC/EN 60079-7

Flameproof enclosure "d"

Ex d (EEx d) IEC, EU Zone 1

Enclosure with-standing an explo-sion from within the apparatus

IEC/EN 60079-1

can ignite a respective explosive atmosphere. Flammable gases and vapours are classified into tempe-rature classes according to their inflammability. Temperature classes range from T1 to T6.

2020

AXC-EX / AXCBF-EX Explosion Proof Axial Fans

Marking of an explosion protected fan

In Europe the label must show as a minimum:

a) the CE-mark

b) the code no. of the certifying body

c) the Ex mark, group, category and indi-cation relating to gases (G) or dust (D)

d) temperature range of ambient air

QualitySystemair is ISO 9001: 2000 approved.

WarrantySystemair offers a three year warran-ty. The Systemair warranty conditions apply.

Size Pole Pitch angle Motor kW

450 2 24° 3

500 2 16° 3

500 2 26° 5,5

560 2 18° 5,5

560 2 24° 7,5

630 2 16° 7,5

355 4 32° 0,37

400 4 32° 0,37

450 4 32° 0,55

500 4 22° 0,55

500 4 28° 0,75

560 4 20° 0,75

560 4 26° 1,1

630 4 22° 1,1

630 4 30° 3

710 4 30° 4

800 4 18° 4

800 4 28° 7,5

900 4 18° 7,5

900 4 26° 11

Size Pole Pitch angle Motor kW

250 2 32° 0,37

315 2 30° 0,75

400 2 22° 2,2

500 2 20° 4

250 4 32° 0,25

315 4 32° 0,25

400 4 32° 0,55

500 4 30° 1,1

630 4 26° 2,2

800 4 18° 4

Stock range AXCBF-EX (400V / 50Hz) Ex d

Stock range AXC-EX (400V / 50Hz) Ex d

Prototype testing institute: SIRA Test and certification Ltd.Rake Lane, EcclestoneChester; CH4 9JN; EnglandRegistration no. 0518 Inspection certificate no. of EC-prototype testing(SIRA 07ATEX6341X) Monitoring institute

ZELM Ex e. K.Prüf- und ZertifizierungsstelleSiekgraben 56 D – 38124 Braunschweig Registration no. 0820

2121

Performance guideAXC-EX explosion proof

0 50.000 100.000 150.000 200.000

Air volume [m³/h]

900

1000

1120

1250

1400

1600

AXC-EX

800

630

710

560

450

500

400

355

315

Siz

e

max. 634 Pa static - 6-pole

max. 500 Pa static - 6-pole

max. 1011 Pa static - 4-pole

max. 736 Pa static - 4-pole

max. 716 Pa static - 4-pole

max. 578 Pa static - 4-pole

max. 458 Pa static - 4-pole

max. 362 Pa static - 4-pole

max. 1130 Pa static - 2-pole

max. 916 Pa static - 2-pole

max. 730 Pa static - 2-pole

max. 524 Pa static - 2-pole

max. 354 Pa static - 2-pole

max. 354 Pa static - 2-pole

max. 280 Pa static - 2-pole

Ordering code

AXCBF - EX

AXC - EX 560 - 9 / 22° - 4 (D/E/NA)

D = flameproof (Ex d) E = increased safety (Ex e) NA = non sparking (Ex nA)

4-pole motor

Pitch angle

Number of blades

Impeller diameter

Explosion proof axial fan

2222

Jet fan systems for car park ventilationAJR and AJ8 for safe daily ventilation and smoke extraction (300°C/2h) in accordance with EN 12101-3.

AJ8 AJR

Ordering code

AJRAJ8 400 - 2/4

2/4-pole motor

Impeller diameter

Jet fans for car park ventilation (R) circular or (8) octagonal

Ordering code

AJRAJ8 400 - 2/4 (B)

For smoke extraction, F300

2/4-pole motor

Impeller diameter

Jet fans for car park ventilation (R) circular or (8) octagonal

Systemair Jet fans AJR and AJ8 offer highest system performance at low installation and running costs. They are available in impeller diameter 315, 355 and 400 mm. The system provides day-by-day ventilation as well as smoke extraction. For straight airflow the silencers have integrated inlet cones and guide vanes. The sound attenuating material is non-inflammable accor-ding to DIN 4102, corresponding with EU guideline 97/69. As acces-sory deflectors on the outlet side are available.

Safety first

The dual purpose fans guarantee rapid smoke extraction, smoke cooling and limit smoke spread in the event of fire. This means better smoke control compared to

conventional systems. Systemair jet fans have been tested in accordance with EN 12101-3 and are CE-labelled.

Cost-effective solution

Jet fan systems do not require ex-pensive and complex duct systems. Thus additional savings are gained in exhaust air fans due to reduced system resistance. The “on demand” ventilation due to CO detectors allows an energy-saving operation.

CFD Analysis

Systemair offers an accurate CFD-simulation to every project. A fee is charged and reimbursed when ordering. The simulation is needed to confirm the optimum perfor-mance of the system.

Standard features:

• Adjustable aluminium impellers for maximum efficiency

• Casing manufactured from galvanized sheet steel

• IEC standard motors IP55 for CO exhaust (40°C – 55°C) or IP54 for high

temperature (300°C/2h) applications

• Fully reversible blade settings available on request

• Terminal box IP66/67 for easy access at the outer fan casing

• Pre-assembled mounting brackets for safe and easy ceiling suspension

• Removable fan module also after installation for easy maintenance

• Two design versions: circular AJR and octagonal AJ8

Control System

Systemair’s custom-tailored control system meets the requirements of your specific project. CO sensors determine the ventilation rate according to demand. When used for smoke extract, the control system must be connected to fire detection system.

Warranty

Systemair offers a three year warranty on all Jet fan models. The Systemair warranty conditions apply.

2323

Performance guideAJR / AJ8 and AJR (B) / AJ8 (B)

Data for reversible jet fans on request.

Air volume related to air density 1.2 kg/m³

Jet fan type400V/50Hz

ThrustAir

volume

Motor rated power

Motor rated

currentSpeed

Sound level at 3 m, from

center of casingWeight

Tempe-rature

N m³/h kW A l/min. LpA dB kg

AJR 315-2 23 4400 0,75 1,8 2900 65 78 55°C

AJR 315-2/4 23 / 6 4400/2200 0,75/0,17 1,74/0.63 2860/1420 65 / 50 80 55°C

AJR 355-2 37 6300 1,1 2,5 2900 71 84 55°C

AJR 355-2/4 37 / 9 6300/3150 1,4/0,3 3,13/1,11 2880/1430 71 / 56 86 55°C

AJR 400-2 55 7700 1,5 3,3 2840 74 93 55°C

AJR 400-2/4 55 / 11 7700/3850 1,9/0,4 4,18/1,47 2885/1435 74 / 59 95 55°C

AJR 315-2 (B) 23 4400 0,75 1,8 2900 65 78 300°C/2h

AJR 315-2/4 (B) 23 / 6 4400/2200 0,75/0,15 1,6/0,4 2880/1450 65 / 50 80 300°C/2h

AJR 355-2 (B) 37 6300 1,1 2,5 2870 71 84 300°C/2h

AJR 355-2/4 (B) 37 / 9 6300/3150 1,3/0,25 3,1/0,68 2905/1460 71 / 56 86 300°C/2h

AJR 400-2 (B) 55 7700 1,5 3,2 2870 74 93 300°C/2h

AJR 400-2/4 (B) 55 / 11 7700/3850 1,8/0,37 3,9/0,95 2880/1455 74 / 59 95 300°C/2h

Jet fan type400V/50Hz

ThrustAir

volume

Motor rated power

Motor rated

currentSpeed

Sound level at 3 m, from

center of casingWeight

Tempe-rature

N m³/h kW A l/min. LpA dB kg

AJ8 315-2 23 4400 0,75 1,8 2900 65 82 55°C

AJ8 315-2/4 23 / 6 4400/2200 0,75/0,17 1,74/0.63 2860/1420 65 / 50 84 55°C

AJ8 355-2 37 6300 1,1 2,5 2900 71 88 55°C

AJ8 355-2/4 37 / 9 6300/3150 1,4/0,3 3,13/1,11 2880/1430 71 / 56 90 55°C

AJ8 400-2 55 7700 1,5 3,3 2840 74 97 55°C

AJ8 400-2/4 55 / 11 7700/3850 1,9/0,4 4,18/1,47 2885/1435 74 / 59 99 55°C

AJ8 315-2 (B) 23 4400 0,75 1,8 2900 65 82 300°C/2h

AJ8 315-2/4 (B) 23 / 6 4400/2200 0,75/0,15 1,6/0,4 2880/1450 65 / 50 84 300°C/2h

AJ8 355-2 (B) 37 6300 1,1 2,5 2870 71 88 300°C/2h

AJ8 355-2/4 (B) 37 / 9 6300/3150 1,3/0,25 3,1/0,68 2905/1460 71 / 56 90 300°C/2h

AJ8 400-2 (B) 55 7700 1,5 3,2 2870 74 97 300°C/2h

AJ8 400-2/4 (B) 55 / 11 7700/3850 1,8/0,37 3,9/0,95 2880/1455 74 / 59 99 300°C/2h

2424

Tunnel Jet Fans

AJ (T)

Types of Tunnel Design

Cut & Cover Tunnel Circular Tunnel

Ring Road Tunnel

The Systemair Matthews & Yates Division has been involved with specialist fan engineering in tunnel ventilation for more than 25 years. A number of important references all over the world prove our com-petence.

Depending on the tunnel design, size and traffic flow, various solutions for ventilation are available.

These are generally:

a) Fully Transverse

Air is supplied from one side of the tunnel and extracted from the other, picking up fumes in the process. Most suited to long tunnels but costly due to the large sized ducts required.

b) Semi Transverse

Fresh air is supplied uniformly over the length of the tunnel causing the foul air to escape longitudinally from the tunnel.

Semi transverse ventilation systems use ducting for supply and often in conjunction with jet fans for certain sensitive areas.

Standard features:

• Thrust efficiency in excess of 40 N/kW

• Adjustable aluminium impellers for maximum efficiency

• Terminal box on the casing for easy on-site wiring

• IEC standard motors as specified in IEC 34; high temperature motors for smoke removal

• Motors can be supplied to suit 50 Hz and 60 Hz supplies.

• Standard bearings are sealed for life, extended lubricators as an option

• Unidirectional or fully reversible in either direction

Division

c) Longitudinal

Widely accepted as the most economical of the three systems and normally used for tunnels up to approximately 1 km in length, depen-ding on traffic flow. Jet fans mounted in the tunnel roof will provide posi-tive longitudinal ventilation and have the ability for reversal in emergencies or to work with prevailing winds. The number and size of fans depends on the maximum air flow required to maintain the level of carbon monoxide and diesel smoke at acceptable levels.

The complete design and manufac-ture of the entire range is backed

up by the latest resources including CAD/CAM systems and CFD soft-ware in accordance with AMCA. Quality is to the highest international standard and we are fully certified to ISO 9001. EN 12101-3 certification is in progress.

2525

TYPICAL CAPACITIES AVAILABLE

Jet Fan Sizemm

Max. Thrust N

Max. Motor PowerkW

Motor Speedrpm (50Hz)

Max. Velocitym/s

500 235 6,5 2880 31,1

560 360 13,5 2880 33,3

630 640 27,0 2880 42,0

710 950 40,0 2880 42,9

800 452 13,0 1440 13,9

900 725 25,0 1440 30,3

1000 1100 35,0 1440 35,3

1120 1690 65,0 1440 37,8

1250 2110 75,0 1440 39,6

1400 1766 50,0 960 30,9

1600 1989 50,0 960 30,2

The above details are for Uni-Directional jet fans. Truly Reversible jet fans will give approximately 5% lower thrust than those shown in the table.

Ordering code

AJ 1000-10 / 22° - 4 (T...)

Temperature class

4-pole motor

Pitch angle

Number of blades

Impeller diameter

Jet tunnel fan

Sturdy casing

Casings are heavy gauge, hot dip gal-vanized upon completion, with spun flanges for high rigidity. Additionally painted or in stainless steel as an option. Silencers are offered with standard length 1 x fan diameter. Other lengths are available on request.

Motors

Standard or high temperature motors for periods of 1 or 2 hours at temperatures of 250°C, 300°C or as may be specified in the design of the tunnel.

AccessoriesDrop rods for fixing to tunnel ceiling that will suit the customer's requirements.

Anti-vibration-hangers to suit the degree of isolation required.

Quality

Systemair is ISO 9001: 2000 appro-ved. The Systemair quality is regularly monitored by TÜV Süd.

Warranty

Systemair offers a three year war-ranty on all AJ (T) fan models. The Systemair warranty conditions apply.

2626

Tunnel Jet Fans

Jet Fans provide Ventilation which reduces the Carbon Monoxide (CO) to acceptable levels and cover all other likely pollutants generated by petrol engines, i.e. nitric oxide (NO), nitrogen dioxide (NO2), sulphur dio-xide (SO2).

Jet Fans can limit the concentration of CO (in parts per million by volu-me) to suit requirements i.e.

• 250 parts/mill: Extreme traffic con- ditions• 150 parts/mill: Peak traffic flow• 100 parts/mill: Off peak traffic flow (this is the maximum exposure for full time tunnel staff).

With diesel-engined traffic the ex-haust smoke affects visibility within the tunnel and is the limiting factor rather than CO.

Visibility levels (Diesel smoke parti-cles per cubic metre of air) are nor-mally defined as follows:

• 1 Dmg/m³: clear for practical purposes

• 9 Dmg/m³: visibility very poor, traffic must move slowly.

Thrust Measurement

Continuous research and develop-ment is our major consideration and our goal is to satisfy worldwide de-mand for our ventilation products. Jet fan measurements are carried out in accordance with ISO 13350. To further develop our jet fan tech-nology and for customers witness testing, a new rig was commissioned to the latest international standards. This accurately determines the actual thrust by the suspended configurati-on method.

Incorporated within the rig is an ad-justable position transducer measu-ring system. High temperature smoke spill testing is carried out to satisfy the wide ran-ge of demands for our export mar-kets. Testing to the EN 12101-3 is in progress.

Division

2727

ROAD TUNNEL INFORMATION REQUEST

Please provide the following information (if available)

Tunnel Length (m)

Cross Sectional Area (m²)

Hydraulic Diameter (m)

Dimensions / Drawing

Number of Lanes

c Flow (Uni-directional or Bi-directional)

Type of Wall Construction (Rough or Smooth)

Altitude Above Sea Level (m)

Tunnel Gradient (Slope)

Wind Velocity Outside Tunnel (m/s)

Tunnel Location (Urban or Rural)

Number of Vehicles Using Tunnel (per hour, per day)

Ratio of Cars to Heavy Goods Vehicles (%)

Design Size of Fire (MW)

Year of Tunnel Opening

Concentration of CO (ppm)

Concentration of NO2 (ppm)

Concentration of Smoke (ppm)

Average of CO Emissions (ppm)

Average of NO2 Emissions (ppm)

Ambient Temperature Levels (°C)

For the purposes of calculation. If any of the following are not known, then those from PIARC (1995) will be used.

Please provide any further details that may be available and could be of assistance in relation to the tunnel design.

2828

Wall mounted axial fans

AXC...-P AXC...(B)-P F300 / EN 12101-3 certified. CE labelled. Monitored by TÜV Süd.HA...(F)-P F400 / EN 12101-3 certified. CE labelled. Monitored by TÜV Süd.

• Square wall plate with inlet cone manufactured from steel, hot dip galvanised upon completion.• IEC standard or smoke extract motors, single or two speed. With protection guard. • Terminal box supplied loose.• Up to impeller diameter 1000. • AXC: Adjustable aluminium impellers. HA: Welded steel impellers.

Axial roof fans (exhaust and supply fans)

AXC...-DAXC...(B)-D F300HA...(F)-D F400HABV-D F600

• Casing manufactured from steel, hot dip galvanised upon completion.• Delivered with roof cowl and base frame. • No wind or snow load testing required for this design.

Axial fan with insulated box

• Double skin panels manufactured from galvanized steel• 20 mm mineral wool insulation• Axial fans on spring anti vibration mounts, horizontal installation, with mounting feet on U-profile inside the box• Reduction of approx. 7 dB

AXC-P

HA-D

Ordering code

... - P Wall mounted axial fans

... - D Axial roof fans

... - B Axial fan with insulated box

Box version

Special Applications

29

List of References

Year Site Fans

2008 TAV Bologna - Firenze, Italy 43 pcs. 500 mm Truly Reversible Jet Fans

Urban Railways of Athens, Greece 60 pcs. 710 mm Truly Reversible Jet Tunnel Fans (545N)

2007 Rome Underground, Italy 2 pcs. 1800 mm, 6 pcs. 1600 mm Truly Reversible Axial Fans, 2 pcs. 1250 mm 2 Stage Truly Reversible Axial Fans

2005/6 Rome Underground, Italy 6 pcs. 1400 mm, 7 pcs. 1600 mm, 4 pcs. 2000 mm Truly Reversible Axial Fans, 2 pcs. 1259 mm 2 Stage Axial Fans, 213 pcs. 450 mm Axial Fans

2005/6 Kaohsiung MRT, Taiwan 64 pcs. 1800 mm Truly Reversible Axial Fans, 32 pcs. 1400 mm Axial Fans, 56 pcs. 900 mm Truly Reversible Jet Fans, 26 pcs. 1120 mm Truly Reversible Jet Fans, 103 pcs. 48'' Axial Fans, 128 pcs. 38'' Axial Fans, 70 pcs. 19'' Axial Fans

2004 Milan Metro, Italy 16 pcs. 75'' Axial Fans

2002 Platamonas Railway Tunnel, Greece 20 pcs. 900 mm Truly Reversible Jet Fans

1998 MRT 348 - Taipei, Taiwan 12 pcs. 75'' GV 6P Axial flow fans, 8 pcs. 900 mm Uni-directional Jet Tunnel Fans

1996 Pan Chau - Wan Pan Subway, Taiwan 8 pcs. 2500 mm, 8 pcs. 2250 mm Truly Reversible Axial Fans

1994 Kon Kan Railway, India 98 pcs. 640 mm Uni-directional Jet Fans (570N)

Year Site Fans

2008 Dartford Tunnel, UK 28 pcs. 610 mm Uni-directional Jet Tunnel Fans (350N)

2008 Arahthos-Metsovo, Greece 36 pcs. 1120 mm Truly Reversible Jet Tunnel Fans (1400N)

2008 Ikonio Tunnel, Greece 24 pcs. 710 mm Truly Reversible Jet Tunnel Fans (635N)

2008 Madeira Tunnels, Portugal 10 pcs. 1000 mm Truly Reversible Jet Tunnel Fans

2007 Keratsini Tunnel, Greece 24 pcs. 710 mm Truly Reversible Jet Tunnel Fans (950N)

2006 Amoreiras - Marques Tunnel, Portugal 10 pcs. 710 mm, 8 pcs. 630 mm, 6 pcs. 380 mm Truly Reversible Jet Fans

MRT - Metro and Train Tunnel Jet Fans

Road Tunnel Jet Fans

3030

List of References

Road Tunnel Jet Fans

Year Site Fans

2005 Dartford River Crossing, England 16 pcs. 710 mm Uni-directional Jet Tunnel Fans

2004 Metsova & Dodini Tunnel, Greece 82 pcs. 1120 mm Truly Reversible Jet Fans

2004 Ham Bao Tunnel, Taiwan 48 pcs. 1250 mm Jet fans, 8 pcs. 2500 mm Axial Fans

2003 Madeira Tunnels, Portugal 117 pcs. 1000 mm Truly Reversible Jet Fans

1997 Lainberg Tunnel, Austria 16 pcs. 1000 mm 4P Truly Reversible Jet Fans (720N)

1996 Taarnby Tunnel, Denmark 44 pcs. 1120 mm Truly Reversible Jet Fans (1500N)

1996 Cabo Girao - Quinta Grande, 75 pcs. 1000 mm Jet Tunnel Fans Ribeira Brava, Madeira

1995 Autostrada Messina - Palermo, Italy 156 pcs. 1000 mm Jet Fans, 124 pcs. 1000 mm (1100N), 32 pcs. 1000 mm (600N) Jet Fans

1995 Cheung Ching Tunnel, Hong Kong 72 pcs. 1250 mm Jet Fans

1992 Dartford River Crossing, England 30 pcs. 610 mm Jet Tunnel Fans (380N)

1986 Leopold II Tunnel, Brussels 50 pcs. 24'' Jet Fans, 28 pcs. 2500 mm

Explosion Proof Axial Fans

Year Site Fans

2008 KPPC Aromatic main control Bldg., Kuwait 13 pcs. bifurcated explosion proof Axial Fans

2007 KOC Facility upgrade, Kuwait 30 pcs. bifurcated explosion proof Axial Fans

2003-2007 Sakhalin Island, Russia 12 pcs. 30'' and 8 pcs. 24'' explosion proof Axial Fans, special design for - 40°C ambient temperature

2000-2004 Sonatrach Pipe Line, Algeria 60 pcs. 30'' high pressure explosion proof Axial Fans, 60 pcs. 75'' explosion proof oil cooler fans

1998 Intercontinental pipe line "Interconnector", 8 pcs. 30'' high pressure explosion proof Axial Fans, Bacton, UK 4 pcs. 24'' explosion proof emergency standby-fans

3131

List of References

Year Site Fans

2008 Porto Arabia parcels Pearl Qatar, Qatar 68 pcs. 400 mm 2 speed F300 Car Park Jet Fans

2008 Jordan Gate, Amman, Jordan 180 pcs. 315 mm Car Park Jet Fans

2008 Business Center Apollo 2, Slovakia 185 pcs. 315 mm Car Park Jet Fans

2007 Teraspark - Denizli, Turkey 25 pcs. 315 mm Car Park Jet Fans

2007 Oasis Mall, Dubai, U.A.E. 67 pcs. 400 mm Car Park Jet Fans

2007 Sehr-i Bazaar F Blok, Istanbul, Turkey 20 pcs. 355 mm Car Park Jet Fans

2007 Lakeside Park, Bratislava, Slovakia 38 pcs. 315 mm Car Park Jet Fans

2006 The Dubai Mall, Dubai, U.A.E 1850 pcs. 315 mm Car Park Jet Fans

Car Park Jet Fans

High Temperature Axial Fans

Year Site Fans

2008 Porto Arabia parcels Pearl Qatar, Qatar F300 single speed: 4 pcs. 1000 mm, 16 pcs. 900 mm, 8 pcs. 710 mm F300 two speed: 2 pcs. 1000 mm, 2 pcs. 900 mm, 30 pcs. 800 mm, 2 pcs. 710 mm, 8 pcs. 630 mm

2008 Tallinn Airport, Estonia Various F400 Axial Fans sizes 315-500 mm

2007-2008 Electricity Substations, Qatar 77pcs. of different sizes F400, 315-1250 mm Axial Fans

2007 Metroport Shopping Mall, Turkey 48 pcs. 710 mm F300, 16 pcs. 1000 mm F300 Axial Fans

2007 Graphisoft "M" Bldg. II Budapest, Hungary 9 pcs. 560 mm F400 Axial Fans

2007 Sun Palace, Budapest, Hungary 1 pc. 900 mm, 7 pcs. 630mm, 7 pcs. 500 mm, 1 pc. 450 mm, 1 pc. 400 mm, F400 Axial Fans

2006 Mega Center Ljubljana, Slovenia 4 pcs. 900 mm, 5 pcs. 630 mm, 1 pc. 500 mm two stage F300 Axial Fans

2006 Ikea, Slovakia 5 pcs. 630 mm F300, 17 pcs. 1000 mm F300 Axial Fans

2003 Sulaibiya Waste Water Treatment, Kuwait 82 pcs. 15-30'' High Temperature Axial Fans

1998 TSH Projects Egger, Hexham, UK 1 pc. 1600 mm INOX

1990 Opel Rüsselsheim, Germany 2 pcs. 1600 mm, 1 pc. 1800 mm,various 1400 mm and 1250 mm F600 Axial Fans

1989 Munich Airport, Germany 3 pcs. 2000 mm, F600 Axial Fans

32

Fan Specification

Type: AXC, AXC-G, AXC-P, AXC-D

Unit consisting of:

• The fan casing from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of casing. Flanges and hole pattern in accordance with DIN 24154-3. Inspection hole to verify correct direction of rotation of the fan impeller.

• Adjustable impeller manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Single or three phase IEC motor. Insulation class F; protection class IP 55; design B3; with cold conductor for motor protection; motor in the air stream. Motor pre-wired to the terminal box positioned at the outer casing. Single or two speed motors available. Speed controllable by frequency converter.

• AXC-G: two stage fan (two fans in series)

• AXC-P: plate mounted axial fan with protection guard and terminal box supplied loose

• AXC-D: axial fan for roof mounting, supplied with base frame, roof cowl and bird guard. Snow load classification: 0

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerpower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: AXC __ __ __ - __ / __ __ -__

Dimensions (connection dia./length, AXC only) [mm]Weight: (without accessories) [kg]

Accessories:

Sound attenuator RSANon return damper (self acting) LRKSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) mounting bracket, vertical assembly MPSet (4 pieces) AV rubber mounts SDSet (4 pieces) AV spring mounts FSDFlexible connection EV-AXCCounter flange GFLInlet cone ESD-FProtection guard for inlet cone SGProtection guard SGOn- / Off- switch REV

AXC Direct Driven Axial Fans

33

Fan SpecificationAXC (B) Direct Driven Smoke Extract Axial Fans

Type: AXC (B), AXC (B)-G, AXC (B)-P, AXC (B)-D

Unit certified in accordance with EN 12101-3 at Technical University Munich for 300 °C / 120 min. CE labelled, monito-red by TÜV Süd. Application classes: LB dual purpose; IF for use outside a building; IB/AB for use inside/outside smoke reservoir; WG insulated when outside the smoke reservoir.

Unit consisting of:

• The fan casing from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of casing. Flanges and hole pattern in accordance with DIN 24154-3. Inspection hole to verify correct direction of rotation of the fan impeller.

• Adjustable impeller manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Three phase IEC high temperature motor 300 °C / 120 min. Insulation class H; protection class IP 54; design B3; Mo-tor in the air stream. Motor pre-wired to the heat resistant terminal box positioned at the outer casing. Cable conduit in stainless steel. Single or two speed motors available.

• AXC (B)-G: two stage fan (two fans in series)

• AXC (B)-P: plate mounted axial fan with protection guard and terminal box supplied loose

• AXC (B)-D: axial fan for roof mounting, supplied with base frame, roof cowl and bird guard. Snow load classification: 0

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerpower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: AXC __ __ __ - __ / __ __ -__-__-__

Dimensions (connection dia./length, AXC only) [mm]Weight: (without accessories) [kg]

Accessories:

Sound attenuator RSANon return damper (self acting) LRKSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) mounting bracket, vertical assembly MPSet (4 pieces) AV spring mounts FSDFlexible connection EVHCounter flange GFLInlet cone ESD-FProtection guard for inlet cone SGProtection guard SG

34

Fan Specification

Type: HA (F), HA (F)-G, HA (F)-P, HA (F)-D

Unit certified in accordance with EN 12101-3 at Technical University Munich for 400 °C / 120 min. CE labelled, monito-red by TÜV Süd. Application classes HA (F)-D: LB dual purpose; IF/ND for use outside the building only on a roof top. Application classes HA (F): LB dual purpose; IF for use outside a building; IB/AB for use inside/outside smoke reservoir; WG insulated when outside the smoke reservoir.

Unit consisting of:

• The fan casing from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of casing. Flanges and hole pattern in accordance with DIN 24154-3. Inspection hole to verify correct direction of rotation of the fan impeller.

• Welded impeller manufactured from steel, coated. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Three phase IEC high temperature motor 400 °C / 120 min. Insulation class H; protection class IP 55; design B3; Mo-tor in the air stream. Motor pre-wired to the heat resistant terminal box positioned at the outer casing. Cable conduit in stainless steel. Single or two speed motors available.

• HA (F)-G: two stage fan (two fans in series)

• HA (F)-P: plate mounted axial fan with protection guard and terminal box supplied loose

• HA (F)-D: axial fan for roof mounting, supplied with base frame, roof cowl and bird guard. Snow load classification: 0

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerPower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: HA __ __ __ - __ / __ __ -__-__-__

Dimensions (connection dia./length, HA only) [mm]Weight: (without accessories) [kg]

Accessories:

Sound attenuator RSANon return damper (self acting) LRKSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) mounting bracket, vertical assembly MPSet (4 pieces) AV spring mounts FSDFlexible connection EVHCounter flange GFLInlet cone ESD-FProtection guard for inlet cone SGProtection guard SGGuide vane NL

HA (F) Direct Driven Smoke Extract Axial Fans

35

Fan Specification

Type: HABV, HABV-G, HABV-D

Unit certified in accordance with EN 12101-3 at Technical University Munich for 600 °C / 120 min. CE labelled, monito-red by TÜV Süd. Application classes HABV: LB dual purpose; IF for use outside a building; IB/AB for use inside/outside smoke reservoir; WG insulated when outside the smoke reservoir.

Unit consisting of:

• The fan casing with integrated inlet guide vane from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges welded on inlet and outlet side of casing. Insulated motor enclosure with cooling duct for motor cooling; when installed inside smoke reservoir cooling air has to be supplied from outside the smoke reservoir. Flanges and hole pattern in accordance with DIN 24154-3. Inspection hole to verify correct direction of rotation of the fan impeller.

• Welded impeller manufactured from steel, coated. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Three phase IEC high temperature motor. Insulation class H; protection class IP 55; design B3; Motor capsulated from the air stream. Automatic motor cooling through cooling duct up to 400 Pa max. pressure drop in the cooling duct. Motor pre-wired to the terminal box positioned in the cooling duct connection. Single or two speed motors available.

• HABV-G: two stage fan (two fans in series)

• HABV-D: axial fan for roof mounting, supplied with base frame, roof cowl and bird guard. Snow load classification: 0

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerpower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: HABV __ __ __ - __ / __ __ -__-__-__

Dimensions (connection dia./length, HABV only) [mm]Weight: (without accessories) [kg]

Accessories:

Flexible connection for cooling duct EV-KLSound attenuator (at discharge side only) RSANon return damper (self acting) LRKSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) mounting bracket, vertical assembly MPSet (4 pieces) AV spring mounts FSDFlexible connection EVHCounter flange GFLInlet cone ESD-FProtection guard for inlet cone SGProtection guard SG

HABV Direct Driven Smoke Extract Axial Fans

36

Fan SpecificationAXCBF Bifurcated Axial Fans, Motor outside the airstream

Type: AXCBF

Unit consisting of:

• The bifurcated fan casing from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of casing. Flanges and hole pattern in accordance with DIN 24154-3.

• Adjustable impeller manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Single or three phase IEC motor. Insulation class F; protection class IP 55; design B3; Motor out of the air stream, terminal box mounted directly onto the motor. Suitable for constant temperatures of 200°C; temperature limit for speed controlled motors max. 60°C. Single or two speed motors available. Speed control of 400V three phase motors by frequency converter, of 230 V single phase motors by transformer.

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerPower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: AXCBF __ __ __ - __ / __ __ -__

Dimensions (connection dia./length) [mm]Weight: (without accessories) [kg]

Accessories:

Sound attenuator RSANon return damper (self acting) LRKSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) AV rubber mounts SDSet (4 pieces) AV spring mounts FSDFlexible connection (70°C) EV-AXCFlexible connection (200°C) EVHCounter flange GFLProtection guard SGOn- / Off- switch REVMotor protection by cold conductor PTC

37

Type: AXC-EX, AXCBF-EX

Unit certified in accordance with ATEX 95, EC-directive 94/9/EC by Sira certificate-no. 07ATEX6341X, EC type exami-nation for category 2. For zone 1 and zone 2 applications, to be installed inside the explosion hazardous area, for gases of IEC class IIB and IIC. Certificate to be downloaded on www.systemair.de. CE-labelled, monitored by TÜV Süd.

Unit consisting of:

• The fan casing from hot-dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of casing. Flanges and hole pattern in accordance with DIN 24154-3.

• Adjustable impeller manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3. Air direction: over motor.

• Additional motor nameplate in metal at the outer fan casing.

• Single or three phase explosion proof IEC motor, ATEX certified, stock range in Ex d with motor cable cast to the motor, single or dual speed. Insulation class F; protection class IP 55; design B3.

• AXC-EX: Motor in the air stream. Motor pre-wired to the terminal box positioned at the outer casing. Speed control by frequency converter. Terminal box in Ex(e), IP 65, manufactured from polyester-resin

• AXCBF-EX: Bifurcated motor outside the air stream; terminal box mounted directly onto the motor.

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Static pressure drop [Pa]Dynamic pressure drop [Pa]Absorbed impellerPower at shaft P2 [kW]Total efficiency [%]Sound Power Level LW [dB(A)]

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Brand: Systemair

Type: AXC-EX __ __ __ - __ / __ __ -__ AXCBF-EX __ __ __ - __ / __ __ -__

Dimensions (connection dia./length) [mm]Weight: (without accessories) [kg]

Accessories:

Sound attenuator RSANon return damper (self acting) LRK-EXSet (2 pieces) mounting feet, horizontal assembly MFASet (4 pieces) mounting bracket, vertical assembly MPSet (4 pieces) AV rubber mounts SDSet (4 pieces) AV spring mounts FSDFlexible connection EV-AXC-EXCounter flange GFLInlet cone ESD-FProtection guard SGOn- / Off- switch (for installation outside the explosion hazardous area only) REVMotor protection by cold conductor PTC

Fan SpecificationAXC-EX Inline Axial Fan / AXCBF-EX Bifurcated Axial Fan

38

AJR / AJ8 Jet Fans for Car Park Ventilation

Type: AJR / AJ8 / AJR (B) / AJ8 (B)AJR/AJ8 for ambient temperature, AJR(B), AJ8(B) for 300°C 120 min smoke and heat extract applications, fully certified in accordance with EN 1201-3, with CE certificate of conformity.

Unit consisting of:

• The fan casing from hot dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of the casing.

• The silencers at the inlet and outlet side of the fan unit, outside casing manufactured from pre-galvanized steel, inside perforated, pre-galvanized steel. Insulated with mineral wool, non-inflammable in accordance with DIN 4102. With integrated inlet cones, both at inlet and outlet side. With guide vane integrated in the outlet silencer, to straighten the airflow.

• AJR: with mounting rail fixed at the fan casing, to allow dismounting of the fan unit when installed

• AJ8: with mounting brackets fixed at the fan casing

• Adjustable pitch impeller manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• AJR/AJ8: Three phase IEC motor, Insulation class F, protection class IP55. Motor in the airstream, prewired to the ter-minal box positioned at the outer casing. Single or two speed motors available. Speed controllable by frequency conver-ter. Motor protection by PTC as a standard.

• AJR(B)/AJ8(B): Three phase high temperature IEC motor to withstand 300°C/2h, Insulation class H, protection class IP54. Motor in the airstream, prewired to the terminal box positioned at the outer casing. Cable glands manufactured from steel. Single or two speed motors available, suitable for operation also in ambient temperatures.

• Terminal box: AJR/AJ8: IP 65, manufactured from polypropylene. AJR(B)/AJ8(B): IP 65, manufactured from die cast aluminium.

• Protection guards at the inlet and outlet of the silencer

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Thrust: [N]Absorbed impellerPower at shaft P2 [kW]Sound pressure level Lp(A) in 3 m at 45° angle :Temperature / time:

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Accessories:

Set (4pcs) AV rubber mountsDeflectors(s) On/off switch for ambient temperatures

Fan Specification

39

AJ (T) Jet fans for Tunnel Ventilation

Type: AJ (T) For smoke and heat extraction, with motors for temperatures of 300°C, 250°C or 200°C at 60 or 120 min.

Unit consisting of:

• The fan casing from hot dip galvanized steel in accordance with EN ISO 1461. Flanges press formed on inlet and outlet side of the casing. Standard execution, unless indicated otherwise.

• The silencers at the inlet and outlet side of the fan unit. Length minimum 1x fan impeller diameter, outside casing ma-nufactured from pre-galvanized steel, inside perforated, pre-galvanized steel. Insulated with mineral wool, non-inflamma-ble in accordance with DIN 4102. With integrated inlet cones, both at inlet and outlet side. Standard execution, unless indicated otherwise.

• With 2 or 4 ceiling mounting brackets, depending on the fan size

• Adjustable pitch impeller, manufactured from die cast aluminium. Balanced statically and dynamically in accordance with DIN ISO 1940-1, to quality Q = 6,3.

• Three phase high temperature IEC motor for 250°C/60 min., insulation class H, protection class IP55. Standard exe-cution, unless indicated otherwise. Motor in the airstream, prewired to the terminal box positioned at the outer casing. Single or two speed motors available. Cabling protected by a stainless steel cable conduit, cable glands manufactured from steel.

• Terminal box: manufactured from steel, painted, in IP 65.

Technical Data

FanAir volume (1,2 kg/m³) [m³/h]Thrust: [N]Absorbed impellerPower at shaft P2 [kW]Sound Power Level LW [dB(A)]Temperature / time:

Motor

Rated power at shaft P2 [kW]Rated current [A]Rated speed [rpm]Voltage / Frequency [V/Hz]

Accessories:

Set (4 or 6 pcs) AV sylomer mounts

Fan Specification

Systemair GmbH • D-97944 Boxberg-Windischbuch • Tel.: +49 (0) 79 30 / 92 72 - 0 • Fax: +49 (0) 79 30 / 92 72 - 92 • [email protected] AB • SE-739 30 Skinnskatteberg, Schweden • Tel.: +46 (0) 222 /440 00 • Fax: +46 (0) 222 / 440 99 • [email protected]

www.systemair.de 06/2

008

/ E4

095


Recommended