www.solerpalau.com AXIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial flow fans CHGT Range of adjustable pitch aerofoil blade, axial flow cabinet fans designed for smoke extraction in fire conditions and certified F400-120 and F300-120 (CE marked). Fan casing manufactured from heavy gauge galvanised sheet steel internally lined with 25mm thickness fireproof fibreglass acoustic insulation (M0). All models incorporate separate high grade diecast aluminium blades locked within a pressed sheet steel hub. Motors Available, depending upon the model: - with three phase motors in 4 or 6 poles. - with three phase two speed motors 4/8 or 6/12 poles. F400-120 and F300-120 motors are IP55 class H insulation. Electrical supplies: Three phase 230/400V-50Hz up to 3 kW. Three phase 400V-50Hz, for higher power motors and two speed motors. (See characteristics chart). Additional information Standard air direction: form (A) configuration (motor over impeller). On request Air direction: form (B) configuration (impeller over motor). Constructive configuration models from 400 to 800 Constructive configuration models from 900 to 1250 F400-120 F300-120 Specific applications F300-120 Car Parks Industrial kitchens Officially approved to EN12101-3 standard (certificate number 0370-CPD-0420) Officially approved to EN12101-3 standard (certificate number 0370-CPD-0955) Highly versatile range due to different number of available blades and adjustable pitch angles Impellers with 3, 5, 6, 7 or 9 blades with adjustable pitch angles, allowing the most optimum selection to achieve with every kind of installation requirements.
Transcript
Page 1: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

Range of adjustable pitch aerofoil blade, axial flow cabinet fans designed for smoke extraction in fire conditions and certified F400-120 and F300-120 (CE marked).Fan casing manufactured from heavy gauge galvanised sheet steel internally lined with 25mm thickness fireproof fibreglass acoustic insulation (M0).All models incorporate separate high grade diecast aluminium blades locked within a pressed sheet steel hub.

MotorsAvailable, depending upon the model:- with three phase motors in 4 or 6 poles.- with three phase two speed motors 4/8 or 6/12 poles.F400-120 and F300-120 motors are IP55 class H insulation.Electrical supplies:

Three phase 230/400V-50Hz up to 3 kW.Three phase 400V-50Hz, for higher power motors and two speed motors.(See characteristics chart).

Additional informationStandard air direction: form (A) configuration (motor over impeller).

On requestAir direction: form (B) configuration (impeller over motor).

Constructive configurationmodels from 400 to 800

Constructive configuration models from 900 to 1250

F400-120

F300-120

Specific applications

F300-120Car Parks Industrial

kitchensOfficiallyapproved toEN12101-3standard (certificatenumber0370-CPD-0420)

Officiallyapproved toEN12101-3standard (certificatenumber0370-CPD-0955)

Highly versatile range due to different number of available blades and adjustable pitch angles

Impellers with 3, 5, 6, 7 or 9 blades with adjustable pitch angles, allowing the most optimum selection to achieve with everykind of installation requirements.

Page 2: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

Motor approved S1 and S2F400-120 or F300-120certified motors approved forrunning continuously (S1) or for emergency operation (S2).

Corrosion resistanceCasings manufactured fromgalvanised sheet steel. Design enables the casing side panels to be removed and the motorimpeller assembly accessed.

Easy to installRobust base supports facilitate the installation.(Models from 900 to 1250)

Impeller dynamicallybalancedImpeller dynamicallybalanced, according to ISO1940 standard, providingvibration free operation.

Wide blade design: higher pressureWide blade design to ensure the highest efficient airflowperformances.Configuration 1: models from 400 to 630.Configuration 2: models from 710 to 1250.

1 2

REfERENCE

MOTORSf300-120

1 SPEED4 POLES 0,55 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45

6 POLES 0,55 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22

2 SPEED4/8 POLES 0,55/0,09 0,75/0,12 1,1/0,18 1,5/0,25 2,2/0,37 3/0,55 4/0,75 5,5/1 7,5/1,5 11/3 14/3,5 17/4,3 20/5 28/6,5 37/9,2 44/11

6/12 POLES 0,55/0,09 0,75/0,12 1,1/0,18 1,5/0,25 2,2/0,37 3/0,55 4/0,65 6/1,2 7,5/1,5 9/1,8 12/2,4 17,5/3,5 20/5

MOTORSf400-120

1 SPEED4 POLES 0,55 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45

6 POLES 0,55 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22

2 SPEED4/8 POLES 0,55/0,09 0,75/0,12 1,1/0,18 1,5/0,25 2,2/0,37 3/0,55 4/0,75 5,5/1 7,5/1,5 11/3 14/3,5 17/4,3 20/5 28/6,5 37/9,2 44/11

6/12 POLES 0,55/0,09 0,75/0,12 1,1/0,18 1,5/0,25 2,2/0,37 3/0,55 4/0,65 6/1,2 7,5/1,5 9/1,8 12/2,4 17,5/3,5 20/5

* Note: For 2 speed motors, the powers may have small variations depending on the motor manufacturer.

1 - : Product range2 - : Number of poles3 - : Diameters4 - : Number of blades5 - : Blade pitch angle6 - : Airflow direction7 - : Motor power

C H G T / 6 - 1 0 0 0 - 6 / 8 / A - 1,5 KW

1 2 3 4 5 6 7

Page 3: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

TECHNICAl CHARACTERISTICS - MOTORS f300-120

CHGT 1 SPEED MODElSTECHNICAl CHARACTERISTICS - 4 POlES - 1450 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Model Motor power(kW)

full load current(A)

Weight(Kg)

230 V 400 VCHGT/4-400-6/-0,55 0,55 2,36 1,36 47

CHGT/4-450-6/-0,55 0,55 2,36 1,36 49

CHGT/4-500-6/-0,55 0,55 2,36 1,36 54 CHGT/4-500-6/-0,75 0,75 3,20 1,85 60 CHGT/4-500-6/-1,1 1,1 4,23 2,44 62

CHGT/4-560-6/-0,55 0,55 2,36 1,36 59 CHGT/4-560-6/-0,75 0,75 3,20 1,85 65 CHGT/4-560-6/-1,1 1,1 4,52 2,61 67 CHGT/4-560-6/-1,5 1,5 5,70 3,29 72 CHGT/4-560-6/-2,2 2,2 8,23 4,75 78

CHGT/4-630-6/-0,75 0,75 3,20 1,85 69CHGT/4-630-6/-1,1 1,1 4,52 2,61 75 CHGT/4-630-6/-1,5 1,5 5,70 3,29 80 CHGT/4-630-6/-2,2 2,2 8,23 4,75 86 CHGT/4-630-6/-3 3 11,21 6,47 89

CHGT/4-710-3/-0,75 0,75 3,20 1,85 101CHGT/4-710-3/-1,1 1,1 4,52 2,61 107CHGT/4-710-3/-1,5 1,5 5,70 3,29 112CHGT/4-710-3/-2,2 2,2 8,00 4,61 118CHGT/4-710-3/-3 3 8,23 4,75 121

CHGT/4-710-6/-1,1 1,1 8,30 4,80 110CHGT/4-710-6/-1,5 1,5 5,50 3,20 115CHGT/4-710-6/-2,2 2,2 8,30 4,80 121CHGT/4-710-6/-3 3 11,30 6,50 124CHGT/4-710-6/-4 4 – 8,60 136

CHGT/4-800-3/-1,1 1,1 4,52 2,61 110 CHGT/4-800-3/-1,5 1,5 5,70 3,29 112CHGT/4-800-3/-2,2 2,2 8,23 4,75 118CHGT/4-800-3/-3 3 11,21 6,47 122CHGT/4-800-3/-4 4 – 8,18 134CHGT/4-800-3/-5,5 5,5 – 11,00 147

CHGT/4-800-6/-1,5 1,5 5,70 3,29 115CHGT/4-800-6/-2,2 2,2 8,23 4,75 120CHGT/4-800-6/-3 3 11,21 6,47 123CHGT/4-800-6/-4 4 – 8,18 135CHGT/4-800-6/-5,5 5,5 – 11,00 148CHGT/4-800-6/-7,5 7,5 – 14,20 162

CHGT/4-800-9/-2,2 2,2 8,04 4,64 138CHGT/4-800-9/-3 3 11,21 6,47 141CHGT/4-800-9/-4 4 – 7,62 153CHGT/4-800-9/-5,5 5,5 – 10,60 166CHGT/4-800-9/-7,5 7,5 – 14,20 180CHGT/4-800-9/-11 11 – 22,10 207We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight(Kg)

230 V 400 VCHGT/4-900-6/-3 3 11,21 6,47 180CHGT/4-900-6/-4 4 – 8,18 188CHGT/4-900-6/-5,5 5,5 – 11,00 201CHGT/4-900-6/-7,5 7,5 – 14,20 215CHGT/4-900-6/-11 11 – 22,10 242CHGT/4-900-6/-15 15 – 29,10 270

CHGT/4-900-9/-4 4 – 9,5 181CHGT/4-900-9/-5,5 5,5 – 12,5 194CHGT/4-900-9/-7,5 7,5 – 16 208CHGT/4-900-9/-11 11 – 22,10 235CHGT/4-900-9/-15 15 – 29,10 263CHGT/4-900-9/-18,5 18,5 – 35,10 311

CHGT/4-1000-6/-4 4 – 8,18 175CHGT/4-1000-6/-5,5 5,5 – 11,00 188CHGT/4-1000-6/-7,5 7,5 – 14,20 202CHGT/4-1000-6/-11 11 – 22,10 229CHGT/4-1000-6/-15 15 – 29,10 257CHGT/4-1000-6/-18,5 18,5 – 35,10 305CHGT/4-1000-6/-22 22 – 41,00 306CHGT/4-1000-9/-22 22 – 41,00 311

CHGT/4-1000-9/-5,5 5,5 – 11,00 193CHGT/4-1000-9/-7,5 7,5 – 14,20 207CHGT/4-1000-9/-11 11 – 22,10 208CHGT/4-1000-9/-15 15 – 29,10 262CHGT/4-1000-9/-18,5 18,5 – 35,10 310

CHGT/4-1250-6/-15 15 – 29,10 414CHGT/4-1250-6/-18,5 18,5 – 35,10 462CHGT/4-1250-6/-22 22 – 41,00 463CHGT/4-1250-6/-30 30 – 56,00 523CHGT/4-1250-6/-37 37 – 67,40 624CHGT/4-1250-6/-45 45 – 81,60 670

CHGT/4-1250-9/-15 15 – 29,10 419CHGT/4-1250-9/-18,5 18,5 – 35,10 467CHGT/4-1250-9/-22 22 – 41,00 468CHGT/4-1250-9/-30 30 – 56,00 528CHGT/4-1250-9/-37 37 – 67,40 629CHGT/4-1250-9/-45 45 – 81,60 675CHGT/4-1250-9/-15 15 – 29,10 419CHGT/4-1250-9/-18,5 18,5 – 35,10 467CHGT/4-1250-9/-22 22 – 41,00 468CHGT/4-1250-9/-30 30 – 56,00 528CHGT/4-1250-9/-37 37 – 67,40 629CHGT/4-1250-9/-45 45 – 81,60 675

Page 4: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

TECHNICAl CHARACTERISTICS - MOTORS f300-120

CHGT 1 SPEED MODElSTECHNICAl CHARACTERISTICS - 6 POlES - 950 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Model Motor power(kW)

full load current(A)

Weight(Kg)

230 V 400 VCHGT/6-500-6/-0,55 0,55 2,79 1,61 56

CHGT/6-560-6/-0,55 0,55 2,79 1,61 78

CHGT/6-630-6/-0,55 0,55 2,79 1,61 85CHGT/6-630-6/-0,75 0,75 3,27 1,89 89CHGT/6-630-6/-1,1 1,1 5,27 3,04 92

CHGT/6-710-3/-0,55 0,55 2,79 1,61 98CHGT/6-710-3/-0,75 0,75 3,27 1,89 102

CHGT/6-710-6/-0,55 0,55 2,90 1,70 101CHGT/6-710-6/-0,75 0,75 4,20 2,40 105CHGT/6-710-6/-1,1 1,1 4,90 2,82 108

CHGT/6-800-3/-0,55 0,55 2,79 1,61 104CHGT/6-800-3/-0,75 0,75 3,27 1,89 108CHGT/6-800-3/-1,1 1,1 5,27 3,04 111CHGT/6-800-3/-1,5 1,5 6,75 3,90 115

CHGT/6-800-6/-0,55 0,55 2,79 1,61 107CHGT/6-800-6/-0,75 0,75 3,27 1,89 111CHGT/6-800-6/-1,1 1,1 5,27 3,04 114CHGT/6-800-6/-1,5 1,5 6,75 3,90 118CHGT/6-800-6/-2,2 2,2 9,28 5,36 126

CHGT/6-800-9/-0,75 0,75 3,60 2,08 115CHGT/6-800-9/-1,1 1,1 5,07 2,93 118CHGT/6-800-9/-1,5 1,5 6,55 3,78 122CHGT/6-800-9/-2,2 2,2 9,28 5,36 130CHGT/6-800-9/-3 3 11,81 6,82 147

CHGT/6-900-6/-1,5 1,5 6,75 3,90 161CHGT/6-900-6/-2,2 2,2 9,28 5,36 169CHGT/6-900-6/-3 3 11,81 6,82 186CHGT/6-900-6/-4 4 – 9,20 192We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight

(Kg)230 V 400 VCHGT/6-900-9/-1,5 1,5 6,75 3,90 165CHGT/6-900-9/-2,2 2,2 9,28 5,36 173CHGT/6-900-9/-3 3 11,81 6,82 190CHGT/6-900-9/-4 4 – 9,20 196CHGT/6-900-9/-5,5 5,5 – 13,00 206

CHGT/6-1000-6/-1,5 1,5 6,75 3,90 159CHGT/6-1000-6/-2,2 2,2 9,28 5,36 167CHGT/6-1000-6/-3 3 11,81 6,82 184CHGT/6-1000-6/-4 4 – 9,20 190CHGT/6-1000-6/-5,5 5,5 – 13,00 200CHGT/6-1000-6/-7,5 7,5 – 15,00 233

CHGT/6-1000-9/-2,2 2,2 9,28 5,36 172CHGT/6-1000-9/-3 3 11,81 6,82 189CHGT/6-1000-9/-4 4 – 9,20 195CHGT/6-1000-9/-5,5 5,5 – 13,00 205CHGT/6-1000-9/-7,5 7,5 – 15,00 238

CHGT/6-1250-6/-4 4 – 9,20 347CHGT/6-1250-6/-5,5 5,5 – 13,00 357CHGT/6-1250-6/-7,5 7,5 – 15,00 390CHGT/6-1250-6/-11 11 – 21,70 415CHGT/6-1250-6/-15 15 – 27,60 453

CHGT/6-1250-9/-5,5 5,5 – 13,00 362CHGT/6-1250-9/-7,5 7,5 – 15,00 395CHGT/6-1250-9/-11 11 – 21,70 420CHGT/6-1250-9/-15 15 – 27,60 458CHGT/6-1250-9/-18,5 18,5 – 36,10 508CHGT/6-1250-9/-22 22 – 41,40 530

Page 5: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

TECHNICAl CHARACTERISTICS - MOTORS f300-120

CHGT 2 SPEED MODElSTECHNICAl CHARACTERISTICS - 4/8 POlES - 1450/730 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V1 V2 V1 V2CHGT/4/8-400-6/-0,55/0,09 0,55 0,09 1,7 0,65 47

CHGT/4/8-450-6/-0,55/0,09 0,55 0,09 1,7 0,65 49

CHGT/4/8-500-6/-0,55/0,09 0,55 0,09 1,7 0,65 54 CHGT/4/8-500-6/-0,75/0,12 0,75 0,12 1,86 0,84 60 CHGT/4/8-500-6/-1,1/0,18 1,1 0,18 2,73 1,21 62

CHGT/4/8-560-6/-0,55/0,09 0,55 0,09 1,7 0,65 59 CHGT/4/8-560-6/-0,75/0,12 0,75 0,12 1,86 0,84 65 CHGT/4/8-560-6/-1,1/0,18 1,1 0,18 2,73 1,21 83CHGT/4/8-560-6/-1,5/0,25 1,5 0,25 3,65 1,6 93CHGT/4/8-560-6/-2,2/0,37 2,2 0,37 4,7 1,66 101

CHGT/4/8-630-6/-0,75/0,12 0,75 0,12 1,86 0,84 72CHGT/4/8-630-6/-1,1/0,18 1,1 0,18 2,73 1,21 90CHGT/4/8-630-6/-1,5/0,25 1,5 0,25 3,65 1,6 100CHGT/4/8-630-6/-2,2/0,37 2,2 0,37 4,7 1,66 108CHGT/4/8-630-6/-3/0,55 3 0,55 6,29 2,35 109

CHGT/4/8-710-3/-0,75/0,12 0,75 0,12 1,86 0,84 101CHGT/4/8-710-3/-1,1/0,18 1,1 0,18 2,73 1,21 103CHGT/4/8-710-3/-1,5/0,25 1,5 0,25 3,65 1,6 113CHGT/4/8-710-3/-2,2/0,37 2,2 0,37 4,7 1,66 120CHGT/4/8-710-3/-3/0,55 3 0,55 6,29 2,35 121

CHGT/4/8-710-6/-1,1/0,18 1,1 0,18 2,73 1,21 106CHGT/4/8-710-6/-1,5/0,25 1,5 0,25 3,65 1,6 116CHGT/4/8-710-6/-2,2/0,37 2,2 0,37 4,7 1,66 123CHGT/4/8-710-6/-3/0,55 3 0,55 6,29 2,35 124CHGT/4/8-710-6/-4/0,75 4 0,75 8,44 2,55 131

CHGT/4/8-800-3/-1,1/0,18 1,1 0,18 2,73 1,21 109CHGT/4/8-800-3/-1,5/0,25 1,5 0,25 3,65 1,6 119CHGT/4/8-800-3/-2,2/0,37 2,2 0,37 4,7 1,66 127CHGT/4/8-800-3/-3/0,55 3 0,55 6,29 2,35 128CHGT/4/8-800-3/-4/0,75 4 0,75 8,44 2,25 135CHGT/4/8-800-3/-5,5/1,1 5,5 1,1 11,7 3,7 157We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V1 V2 V1 V2CHGT/4/8-800-6/-1,5/0,25 1,5 0,25 3,65 1,6 122CHGT/4/8-800-6/-2,2/0,37 2,2 0,37 4,7 1,66 130CHGT/4/8-800-6/-3/0,55 3 0,55 6,29 2,35 131CHGT/4/8-800-6/-4/0,75 4 0,75 8,44 2,25 138CHGT/4/8-800-6/-5,5/1,1 5,5 1,1 11,7 3,7 160CHGT/4/8-800-6/-7,5/1,5 7,5 1,5 15,9 4,72 173

CHGT/4/8-800-9/-2,2/0,37 2,2 0,37 4,7 1,66 134CHGT/4/8-800-9/-3/0,55 3 0,55 6,29 2,35 135CHGT/4/8-800-9/-4/0,75 4 0,75 8,44 2,25 142CHGT/4/8-800-9/-5,5/1,1 5,5 1,1 11,7 3,7 164CHGT/4/8-800-9/-7,5/1,5 7,5 1,5 15,9 4,72 177

CHGT/4/8-900-6/-3/0,55 3 0,55 6,29 2,35 174CHGT/4/8-900-6/-4/0,75 4 0,75 8,44 2,25 181CHGT/4/8-900-6/-5,5/1,1 5,5 1,1 11,7 3,7 203CHGT/4/8-900-6/-7,5/1,5 7,5 1,5 15,9 4,72 216CHGT/4/8-900-6/-11/3 11 3 21 7 249CHGT/4/8-900-6/-14/3,5 14 3,5 26,5 8,45 269

CHGT/4/8-900-9/-4/0,75 4 0,75 8,44 2,25 185CHGT/4/8-900-9/-5,5/1,1 5,5 1,1 11,7 3,7 207CHGT/4/8-900-9/-7,5/1,5 7,5 1,5 15,9 4,72 220CHGT/4/8-900-9/-11/3 11 3 21 7 253CHGT/4/8-900-9/-14/3,5 14 3,5 26,5 8,45 273CHGT/4/8-900-9/-17/4,3 17 4,3 33,4 12,3 301

CHGT/4/8-1000-6/-4/0,75 4 0,75 8,44 2,25 179

Page 6: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

TECHNICAl CHARACTERISTICS - MOTORS f300-120

CHGT 2 SPEED MODElSTECHNICAl CHARACTERISTICS - 6/12 POlES - 950/475 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V1 V2 V1 V2CHGT/6/12-500-6/-0,55/0,09 0,55 0,09 2,07 0,94 62

CHGT/6/12-560-6/-0,55/0,09 0,55 0,09 2,07 0,94 84

CHGT/6/12-630-6/-0,55/0,09 0,55 0,09 2,07 0,94 91CHGT/6/12-630-6/-0,75/0,12 0,75 0,12 2,28 1,02 93CHGT/6/12-630-6/-1,1/0,18 1,1 0,18 4,49 1,67 105

CHGT/6/12-710-3/-0,55/0,09 0,55 0,09 2,07 0,94 104CHGT/6/12-710-3/-0,75/0,12 0,75 0,12 2,28 1,02 106

CHGT/6/12-710-6/-0,55/0,09 0,55 0,09 2,07 0,94 107CHGT/6/12-710-6/-0,75/0,12 0,75 0,12 2,28 1,02 109CHGT/6/12-710-6/-1,1/0,18 1,1 0,18 4,49 1,67 121

CHGT/6/12-800-3/-0,55/0,09 0,55 0,09 2,07 0,94 110CHGT/6/12-800-3/-0,75/0,12 0,75 0,12 2,28 1,02 112CHGT/6/12-800-3/-1,1/0,18 1,1 0,18 4,49 1,67 124CHGT/6/12-800-3/-1,5/0,25 1,5 0,25 4,24 1,67 127

CHGT/6/12-800-6/-0,55/0,09 0,55 0,09 2,07 0,94 107CHGT/6/12-800-6/-0,75/0,12 0,75 0,12 2,28 1,02 115CHGT/6/12-800-6/-1,1/0,18 1,1 0,18 4,49 1,67 127CHGT/6/12-800-6/-1,5/0,25 1,5 0,25 4,24 1,67 130CHGT/6/12-800-6/-2,2/0,37 2,2 0,37 5,9 2,3 131

CHGT/6/12-800-9/-0,75/0,12 0,75 0,12 2,28 1,02 119CHGT/6/12-800-9/-1,1/0,18 1,1 0,18 4,49 1,67 131CHGT/6/12-800-9/-1,5/0,25 1,5 0,25 4,24 1,67 134CHGT/6/12-800-9/-2,2/0,37 2,2 0,37 5,9 2,3 135CHGT/6/12-800-9/-3/0,55 3 0,55 8,87 3,80 147

CHGT/6/12-900-6/-1,1/0,18 1,1 0,18 4,49 1,67 174CHGT/6/12-900-6/-1,5/0,25 1,5 0,25 4,24 1,67 181CHGT/6/12-900-6/-2,2/0,37 2,2 0,37 5,9 2,3 191CHGT/6/12-900-6/-3/0,55 3 0,55 8,87 3,80 216CHGT/6/12-900-6/-4/0,65 4 0,65 10 3,5 210We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V1 V2 V1 V2CHGT/6/12-900-9/-1,5/0,25 1,5 0,25 4,24 1,67 185CHGT/6/12-900-9/-2,2/0,37 2,2 0,37 5,9 2,3 195CHGT/6/12-900-9/-3/0,55 3 0,55 8,87 3,80 220CHGT/6/12-900-9/-4/0,65 4 0,65 10 3,5 206CHGT/6/12-900-9/-6/1,2 6 1,2 14,4 5,5 262

CHGT/6/12-1000-6/-1,5/0,25 1,5 0,25 4,24 1,67 171CHGT/6/12-1000-6/-2,2/0,37 2,2 0,37 5,9 2,3 172CHGT/6/12-1000-6/-3/0,55 3 0,55 8,87 3,80 209CHGT/6/12-1000-6/-4/0,65 4 0,65 9,31 2,94 209CHGT/6/12-1000-6/-6/1,2 6 1,2 13,40 5,58 256

CHGT/6/12-1000-9/-2,2/0,37 2,2 0,37 5,73 2,18 177CHGT/6/12-1000-9/-3/0,55 3 0,55 8,87 3,80 214CHGT/6/12-1000-9/-4/0,65 4 0,65 9,31 2,94 214CHGT/6/12-1000-9/-6/1,2 6 1,2 13,40 5,58 261CHGT/6/12-1000-9/-7,5/1,5 7,5 1,5 16,40 6,49 268

CHGT/6/12-1250-6/-4/0,65 4 0,65 9,31 2,94 365CHGT/6/12-1250-6/-6/1,2 6 1,2 13,40 5,58 413CHGT/6/12-1250-6/-7,5/1,5 7,5 1,5 16,40 6,49 390CHGT/6/12-1250-6/-9/1,8 9 1,8 18,90 7,08 445CHGT/6/12-1250-6/-12/2,4 12 2,4 23,40 8,07 506CHGT/6/12-1250-6/-17,5/3,5 17,5 3,5 40 14,5 538

CHGT/6/12-1250-9/-6/1,2 6 1,2 13,40 5,58 418CHGT/6/12-1250-9/-7,5/1,5 7,5 1,5 16,40 6,49 450CHGT/6/12-1250-9/-9/1,8 9 1,8 18,90 7,08 458CHGT/6/12-1250-9/-12/2,4 12 2,4 23,40 8,07 511CHGT/6/12-1250-9/-17,5/3,5 17,5 3,5 40 14,5 542CHGT/6/12-1250-9/-20/5 20 5 54,2 23,5 564

Page 7: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

Model Motor power(kW)

full load current(A)

Weight

(Kg)230 V 400 VCHGT/4-400-6/-0,55 0,55 2,36 1,36 36

CHGT/4-450-6/-0,55 0,55 2,36 1,36 38

CHGT/4-500-6/-0,55 0,55 2,36 1,36 43CHGT/4-500-6/-0,75 0,75 3,20 1,85 49CHGT/4-500-6/-1,1 1,1 4,23 2,44 51

CHGT/4-560-6/-0,55 0,55 2,36 1,36 45CHGT/4-560-6/-0,75 0,75 3,20 1,85 51CHGT/4-560-6/-1,1 1,1 4,52 2,61 53CHGT/4-560-6/-1,5 1,5 5,70 3,29 58CHGT/4-560-6/-2,2 2,2 8,23 4,75 64

CHGT/4-630-6/-0,75 0,75 3,20 1,85 53CHGT/4-630-6/-1,1 1,1 4,52 2,61 59CHGT/4-630-6/-1,5 1,5 5,70 3,29 64CHGT/4-630-6/-2,2 2,2 8,23 4,75 70CHGT/4-630-6/-3 3 11,21 6,47 73

CHGT/4-710-5/-1,1 1,1 4,52 2,61 84CHGT/4-710-5/-1,5 1,5 5,70 3,29 85

CHGT/4-710-7/-2,2 2,2 8,23 4,75 91CHGT/4-710-7/-3 3 11,21 6,47 94CHGT/4-710-7/-4 4 – 8,18 107CHGT/4-710-7/-5,5 5,5 – 11,00 120

CHGT/4-800-3/-1,1 1,1 4,52 2,61 89CHGT/4-800-3/-1,5 1,5 5,70 3,29 91CHGT/4-800-3/-2,2 2,2 8,23 4,75 97CHGT/4-800-3/-3 3 11,21 6,47 101CHGT/4-800-3/-4 4 – 8,18 113CHGT/4-800-3/-5,5 5,5 – 11,00 126

CHGT/4-800-6/-1,5 1,5 5,70 3,29 94CHGT/4-800-6/-2,2 2,2 8,23 4,75 99CHGT/4-800-6/-3 3 11,21 6,47 102CHGT/4-800-6/-4 4 – 8,18 114CHGT/4-800-6/-5,5 5,5 – 11,00 127CHGT/4-800-6/-7,5 7,5 – 14,20 141

CHGT/4-800-9/-2,2 2,2 8,04 4,64 117CHGT/4-800-9/-3 3 11,21 6,47 120CHGT/4-800-9/-4 4 – 7,62 132CHGT/4-800-9/-5,5 5,5 – 10,60 145CHGT/4-800-9/-7,5 7,5 – 14,20 159We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight

(Kg)230 V 400 VCHGT/4-900-6/-3 3 11,21 6,47 180CHGT/4-900-6/-4 4 – 8,18 188CHGT/4-900-6/-5,5 5,5 – 11,00 201CHGT/4-900-6/-7,5 7,5 – 14,20 215CHGT/4-900-6/-11 11 – 22,10 242CHGT/4-900-6/-15 15 – 29,10 270

CHGT/4-900-9/-4 4 – 9,50 181CHGT/4-900-9/-5,5 5,5 – 12,50 194CHGT/4-900-9/-7,5 7,5 – 16,00 208CHGT/4-900-9/-11 11 – 22,10 235CHGT/4-900-9/-15 15 – 29,10 263CHGT/4-900-9/-18,5 18,5 – 35,10 311

CHGT/4-1000-6/-4 4 – 8,18 175CHGT/4-1000-6/-5,5 5,5 – 11,00 188CHGT/4-1000-6/-7,5 7,5 – 14,20 202CHGT/4-1000-6/-11 11 – 22,10 229CHGT/4-1000-6/-15 15 – 29,10 257CHGT/4-1000-6/-18,5 18,5 – 35,10 305CHGT/4-1000-6/-22 22 – 41,00 306

CHGT/4-1000-9/-5,5 5,5 – 11,00 193CHGT/4-1000-9/-7,5 7,5 – 14,20 207CHGT/4-1000-9/-11 11 – 22,10 208CHGT/4-1000-9/-15 15 – 29,10 262CHGT/4-1000-9/-18,5 18,5 – 35,10 310CHGT/4-1000-9/-22 22 – 41,00 311

CHGT/4-1250-6/-15 15 – 29,10 414CHGT/4-1250-6/-18,5 18,5 – 35,10 462CHGT/4-1250-6/-22 22 – 41,00 463CHGT/4-1250-6/-30 30 – 56,00 523CHGT/4-1250-6/-37 37 – 67,40 624CHGT/4-1250-6/-45 45 – 81,60 670

CHGT/4-1250-9/-15 15 – 29,10 419CHGT/4-1250-9/-18,5 18,5 – 35,10 467CHGT/4-1250-9/-22 22 – 41,00 468CHGT/4-1250-9/-30 30 – 56,00 528CHGT/4-1250-9/-37 37 – 67,40 629CHGT/4-1250-9/-45 45 – 81,60 675

TECNICAl CHARACTERISTICS - MOTORS f400-120

CHGT 1 SPEED MODElSTECHNICAl CHARACTERISTICS - 4 POlES - 1450 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Page 8: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

Model Motor power(kW)

full load current(A)

Weight(Kg)

230 V 400 VCHGT/6-500-6/-0,55 0,55 2,79 1,61 45

CHGT/6-560-6/-0,55 0,55 2,79 1,61 64

CHGT/6-630-6/-0,55 0,55 2,79 1,61 69CHGT/6-630-6/-0,75 0,75 3,27 1,89 73CHGT/6-630-6/-1,1 1,1 5,27 3,04 76

CHGT/6-710-5/-0,55 0,55 2,79 1,61 80CHGT/6-710-5/-0,75 0,75 3,27 1,89 84CHGT/6-710-5/-1,1 1,1 5,27 3,04 87

CHGT/6-710-7/-1,5 1,5 6,75 3,90 93

CHGT/6-800-3/-0,55 0,55 2,79 1,61 83CHGT/6-800-3/-0,75 0,75 3,27 1,89 87CHGT/6-800-3/-1,1 1,1 5,27 3,04 90CHGT/6-800-3/-1,5 1,5 6,75 3,90 94

CHGT/6-800-6/-0,55 0,55 2,79 1,61 86CHGT/6-800-6/-0,75 0,75 3,27 1,89 90CHGT/6-800-6/-1,1 1,1 5,27 3,04 93CHGT/6-800-6/-1,5 1,5 6,75 3,90 97CHGT/6-800-6/-2,2 2,2 9,28 5,36 105

CHGT/6-800-9/-0,75 0,75 3,60 2,08 94CHGT/6-800-9/-1,1 1,1 5,07 2,93 97CHGT/6-800-9/-1,5 1,5 6,55 3,78 101CHGT/6-800-9/-2,2 2,2 9,28 5,36 109CHGT/6-800-9/-3 3 11,81 6,82 126

CHGT/6-900-6/-1,5 1,5 6,75 3,90 161CHGT/6-900-6/-2,2 2,2 9,28 5,36 169 CHGT/6-900-6/-3 3 11,81 6,82 186CHGT/6-900-6/-4 4 – 9,20 192

CHGT/6-900-9/-1,5 1,5 6,75 3,90 165CHGT/6-900-9/-2,2 2,2 9,28 5,36 173CHGT/6-900-9/-3 3 11,81 6,82 190CHGT/6-900-9/-4 4 – 9,20 196CHGT/6-900-9/-5,5 5,5 – 13,00 206We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight(Kg)

230 V 400 VCHGT/6-1000-6/-1,5 1,5 6,75 3,90 159CHGT/6-1000-6/-2,2 2,2 9,28 5,36 167CHGT/6-1000-6/-3 3 11,81 6,82 184CHGT/6-1000-6/-4 4 – 9,20 190CHGT/6-1000-6/-5,5 5,5 – 13,00 200CHGT/6-1000-6/-7,5 7,5 – 15,00 233

CHGT/6-1000-9/-2,2 2,2 9,28 5,36 172CHGT/6-1000-9/-3 3 11,81 6,82 189CHGT/6-1000-9/-4 4 – 9,20 195CHGT/6-1000-9/-5,5 5,5 – 13,00 205CHGT/6-1000-9/-7,5 7,5 – 15,00 238

CHGT/6-1250-6/-4 4 – 9,20 347CHGT/6-1250-6/-5,5 5,5 – 13,00 357CHGT/6-1250-6/-7,5 7,5 – 15,00 390CHGT/6-1250-6/-11 11 – 21,70 415CHGT/6-1250-6/-15 15 – 27,60 453

CHGT/6-1250-9/-5,5 5,5 – 13,00 362CHGT/6-1250-9/-7,5 7,5 – 15,00 395CHGT/6-1250-9/-11 11 – 21,70 420CHGT/6-1250-9/-15 15 – 27,60 458CHGT/6-1250-9/-18,5 18,5 – 36,10 508CHGT/6-1250-9/-22 22 – 41,40 530

TECHNICAl CHARACTERISTICS - MOTORS f400-120

CHGT 1 SPEED MODElSTECHNICAl CHARACTERISTICS - 6 POlES - 950 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Page 9: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

Model Motor power(kW)

full load current(A)

Weight(Kg)

V. 1 V. 2 V. 1 V. 2CHGT/4/8-800-6/-1,5/0,25 1,5 0,25 3,65 1,6 101CHGT/4/8-800-6/-2,2/0,37 2,2 0,37 4,7 1,66 109CHGT/4/8-800-6/-3/0,55 3 0,55 6,29 2,35 110CHGT/4/8-800-6/-4/0,75 4 0,75 8,44 2,25 117CHGT/4/8-800-6/-5,5/1,1 5,5 1,1 11,7 3,7 139CHGT/4/8-800-6/-7,5/1,5 7,5 1,5 15,9 4,72 152

CHGT/4/8-800-9/-2,2/0,37 2,2 0,37 4,7 1,66 113CHGT/4/8-800-9/-3/0,55 3 0,55 6,29 2,35 114CHGT/4/8-800-9/-4/0,75 4 0,75 8,44 2,25 121CHGT/4/8-800-9/-5,5/1,1 5,5 1,1 11,7 3,7 143CHGT/4/8-800-9/-7,5/1,5 7,5 1,5 15,9 4,72 156

CHGT/4/8-1000-9/-14/3,5 14 3,5 26,5 8,45 202CHGT/4/8-1000-9/-17/4,3 17 4,3 33,4 12,3 230CHGT/4/8-1000-9/-20/5 20 5 38,6 14,1 245

CHGT/4/8-1250-6/-14/3,5 14 3,5 26,5 8,45 424CHGT/4/8-1250-6/-17/4,3 17 4,3 33,4 12,3 452CHGT/4/8-1250-6/-20/5 20 5 38,6 14,1 467CHGT/4/8-1250-6/-30/8 30 8 52 18 525CHGT/4/8-1250-6/-37/9,2 37 9,2 74,2 25,4 650CHGT/4/8-1250-6/-44/11 44 11 80,2 27,2 715

CHGT/4/8-1250-9/-14/3,5 14 3,5 26,5 8,45 429CHGT/4/8-1250-9/-17/4,3 17 4,3 33,4 12,3 457CHGT/4/8-1250-9/-20/5 20 5 38,6 14,1 472CHGT/4/8-1250-9/-30/8 30 8 52 18 530CHGT/4/8-1250-9/-37/9,2 37 9,2 74,2 25,4 655CHGT/4/8-1250-9/-44/11 44 11 80,2 27,2 720

Model Motor power(kW)

full load current(A)

Weight(Kg)

V. 1 V. 2 V. 1 V. 2CHGT/4/8-400-6/-0,55/0,09 0,55 0,09 1,7 0,65 36

CHGT/4/8-450-6/-0,55/0,09 0,55 0,09 1,7 0,65 38

CHGT/4/8-500-6/-0,55/0,09 0,55 0,09 1,7 0,65 43CHGT/4/8-500-6/-0,75/0,12 0,75 0,12 1,86 0,84 49CHGT/4/8-500-6/-1,1/0,18 1,1 0,18 2,73 1,21 51

CHGT/4/8-560-6/-0,55/0,09 0,55 0,09 1,7 0,65 45CHGT/4/8-560-6/-0,75/0,12 0,75 0,12 1,86 0,84 51CHGT/4/8-560-6/-1,1/0,18 1,1 0,18 2,73 1,21 69CHGT/4/8-560-6/-1,5/0,25 1,5 0,25 3,65 1,6 79CHGT/4/8-560-6/-2,2/0,37 2,2 0,37 4,7 1,66 87

CHGT/4/8-630-6/-0,75/0,12 0,75 0,12 1,86 0,84 56CHGT/4/8-630-6/-1,1/0,18 1,1 0,18 2,73 1,21 74CHGT/4/8-630-6/-1,5/0,25 1,5 0,25 3,65 1,6 84CHGT/4/8-630-6/-2,2/0,37 2,2 0,37 4,7 1,66 92CHGT/4/8-630-6/-3/0,55 3 0,55 6,29 2,35 93

CHGT/4/8-710-5/-1,1/0,18 1,1 0,18 2,73 1,21 100CHGT/4/8-710-5/-1,5/0,25 1,5 0,25 3,65 1,6 103

CHGT/4/8-710-7/-2,2/0,37 2,2 0,37 4,7 1,66 105CHGT/4/8-710-7/-3/0,55 3 0,55 6,29 2,35 106CHGT/4/8-710-7/-4/0,75 4 0,75 8,44 2,25 113CHGT/4/8-710-7/-5,5/1,1 5,5 1,1 11,7 3,7 135

CHGT/4/8-800-3/-1,5/0,25 1,5 0,25 3,65 1,6 98CHGT/4/8-800-3/-2,2/0,37 2,2 0,37 4,7 1,66 106CHGT/4/8-800-3/-3/0,55 3 0,55 6,29 2,35 107CHGT/4/8-800-3/-4/0,75 4 0,75 8,44 2,25 114CHGT/4/8-800-3/-5,5/1,1 5,5 1,1 11,7 3,7 136We reserve right to supply different motors and hence data may change.

TECHNICAl CHARACTERISTICS - MOTORS f400-120

CHGT 2 SPEED MODElSTECHNICAl CHARACTERISTICS - 4/8 POlES - 1450/730 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Page 10: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

TECHNICAl CHARACTERISTICS - MOTORS f400-120

CHGT 2 SPEED MODElSTECHNICAl CHARACTERISTICS - 6/12 POlES - 950/475 RPM

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V. 1 V. 2 V. 1 V. 2CHGT/6/12-500-6/-0,55/0,09 0,55 0,09 2,07 0,94 51

CHGT/6/12-560-6/-0,55/0,09 0,55 0,09 2,07 0,94 70

CHGT/6/12-630-6/-0,55/0,09 0,55 0,09 2,07 0,94 75CHGT/6/12-630-6/-0,75/0,12 0,75 0,12 2,28 1,02 77CHGT/6/12-630-6/-1,1/0,18 1,1 0,18 4,49 1,67 89

CHGT/6/12-710-5/-0,75/0,12 0,75 0,12 2,28 1,02 91

CHGT/6/12-710-7/-1,1/0,18 1,1 0,18 4,49 1,67 94CHGT/6/12-710-7/-1,5/0,25 1,5 0,25 4,24 1,67 97

CHGT/6/12-800-3/-0,55/0,09 0,55 0,09 2,07 0,94 89CHGT/6/12-800-3/-0,75/0,12 0,75 0,12 2,28 1,02 91CHGT/6/12-800-3/-1,1/0,18 1,1 0,18 4,49 1,67 103CHGT/6/12-800-3/-1,5/0,25 1,5 0,25 4,24 1,67 106CHGT/6/12-800-6/-0,55/0,09 0,55 0,09 2,07 0,94 86CHGT/6/12-800-6/-0,75/0,12 0,75 0,12 2,28 1,02 94CHGT/6/12-800-6/-1,1/0,18 1,1 0,18 4,49 1,67 106CHGT/6/12-800-6/-1,5/0,25 1,5 0,25 4,24 1,67 109CHGT/6/12-800-6/-2,2/0,37 2,2 0,37 5,9 2,3 110

CHGT/6/12-800-9/-0,75/0,12 0,75 0,12 2,28 1,02 98CHGT/6/12-800-9/-1,1/0,18 1,1 0,18 4,49 1,67 110CHGT/6/12-800-9/-1,5/0,25 1,5 0,25 4,24 1,67 113CHGT/6/12-800-9/-2,2/0,37 2,2 0,37 5,9 2,3 114CHGT/6/12-800-9/-3/0,55 3 0,55 8,87 3,80 126

CHGT/6/12-900-6/-1,1/0,18 1,1 0,18 4,49 1,67 174CHGT/6/12-900-6/-1,5/0,25 1,5 0,25 4,24 1,67 181CHGT/6/12-900-6/-2,2/0,37 2,2 0,37 5,9 2,3 191CHGT/6/12-900-6/-3/0,55 3 0,55 8,87 3,80 216CHGT/6/12-900-6/-4/0,65 4 0,65 10 3,5 210We reserve right to supply different motors and hence data may change.

Model Motor power(kW)

full load current(A)

Weight(Kg)

V. 1 V. 2 V. 1 V. 2CHGT/6/12-900-9/-1,5/0,25 1,5 0,25 4,24 1,67 185CHGT/6/12-900-9/-2,2/0,37 2,2 0,37 5,9 2,3 195CHGT/6/12-900-9/-3/0,55 3 0,55 8,87 3,80 220CHGT/6/12-900-9/-4/0,65 4 0,65 10 3,5 206CHGT/6/12-900-9/-6/1,2 6 1,2 14,4 5,5 262

CHGT/6/12-1000-6/-1,5/0,25 1,5 0,25 4,24 1,67 171CHGT/6/12-1000-6/-2,2/0,37 2,2 0,37 5,9 2,3 172CHGT/6/12-1000-6/-3/0,55 3 0,55 8,87 3,80 209CHGT/6/12-1000-6/-4/0,65 4 0,65 9,31 2,94 209CHGT/6/12-1000-6/-6/1,2 6 1,2 13,40 5,58 256

CHGT/6/12-1000-9/-2,2/0,37 2,2 0,37 5,73 2,18 177CHGT/6/12-1000-9/-3/0,55 3 0,55 8,87 3,80 214CHGT/6/12-1000-9/-4/0,65 4 0,65 9,31 2,94 214CHGT/6/12-1000-9/-6/1,2 6 1,2 13,40 5,58 261CHGT/6/12-1000-9/-7,5/1,5 7,5 1,5 16,40 6,49 268CHGT/6/12-1250-6/-4/0,65 4 0,65 9,31 2,94 365CHGT/6/12-1250-6/-6/1,2 6 1,2 13,40 5,58 413CHGT/6/12-1250-6/-7,5/1,5 7,5 1,5 16,40 6,49 390CHGT/6/12-1250-6/-9/1,8 9 1,8 18,90 7,08 445CHGT/6/12-1250-6/-12/2,4 12 2,4 23,40 8,07 506CHGT/6/12-1250-6/-17,5/4,3 17,5 3,5 40 14,5 538

CHGT/6/12-1250-9/-6/1,2 6 1,2 13,40 5,58 418CHGT/6/12-1250-9/-7,5/1,5 7,5 1,5 16,40 6,49 450CHGT/6/12-1250-9/-9/1,8 9 1,8 18,90 7,08 458CHGT/6/12-1250-9/-12/2,4 12 2,4 23,40 8,07 511CHGT/6/12-1250-9/-17/4,3 17,5 3,5 40 14,5 542CHGT/6/12-1250-9/-20/5 24 6 54,2 23,5 564

Page 11: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

DIMENSIONS (mm)

D C

E

DF

A

B

Model A £ B C D E f

400 509 423 440 40 520 588

450 567,6 473 483 40 563 650

500 638 523 525 40 605 719

560 718,6 583 570 40 650 370

630 808 653 570 40 650 370

710 907,6 750 640 40 720 438

800 1007,6 850 640 40 720 438

Models 400 to 800

D DC

E

CF

G H

BA

80

D D

EBA

Model £ A £ B C D E f G H

900 1126,5 950 700 50 800 503 860 1076,5

1000 1256,5 1055 700 50 800 503 860 1206,5

1250 1476,5 1275 900 50 1000 310 1060 1426,5

Models 900 to 1250

Page 12: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

MOuNTING ACCESSORIES

CVD CGT/CHGTProtection guards.Wire protection guards for mountingon the inlet or discharge sides of the cabinets.

PER-CN CHGTAluminium and sheet steel louvre back draft shutter (without bird guard) for CHGT and CGT series.

70

A

B

Model cabinet Inlet and discharge

Protection guard model A B

CHGT-400 CVD/400 CGT/CHGT 424 313,5

CHGT-450 CVD/450 CGT/CHGT 474 341,5

CHGT-500 CVD/500 CGT/CHGT 524 369,5

CHGT-560 CVD/560 CGT/CHGT 584 403,5

CHGT-630 CVD/630 CGT/CHGT 654 422,5

CHGT-710 CVD/710 CGT/CHGT 751 503,8

CHGT-800 CVD/800 CGT/CHGT 851,5 560,2

CHGT-900 CVD/900 CGT/CHGT 951,5 616,2

CHGT-1000 CVD/1000 CGT/CHGT 1056,5 675

CHGT-1250 CVD/1250 CGT/CHGT 1276,5 798,3

A (Interior measurement)

E

e70

NV = NUM. TAL Ø 4.1

NH = NUM. TAL Ø 4.1

Ø 4.1

Ø 4.1

E

e

10

10

Model A

400 428

450 478

500 528

560 585

630 655

710 752

800 852

900 952

1000 1057

1250 1277

A

B

130 Model cabinet A B

ACOP RECT CHGT/CGT 400 F400 428 428

ACOP RECT CHGT/CGT 450 F400 478 478

ACOP RECT CHGT/CGT 500 F400 528 528

ACOP RECT CHGT/CGT 560 F400 585 585

ACOP RECT CHGT/CGT 630 F400 655 655

ACOP RECT CHGT/CGT 710 F400 752 752

ACOP RECT CHGT/CGT 800 F400 852 852

ACOP RECT CHGT/CGT 900 F400 952 952

ACOP RECT CHGT/CGT 1000 F400 1057 1057

ACOP RECT CHGT/CGT 1250 F400 1277 1277

Dimensions in mm.

Dimensions in mm.

ACOP RECT CHGT/CGT f400Rectangular flexible connector.

Page 13: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

ExAMPlE Of SElECTING CHGT/ CGT fANS

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA

210-99 Standards.

CGT

Number of poles 4

Nominal diameter (mm) 1000

Number of blades 3

CGT/4-1000-3/_°-_ kW

Hz A B C

63 22 20 18

125 19 19 17

250 13 11 12

500 6 5 6

1000 4 5 5

2000 6 7 6

4000 11 13 12

8000 18 20 20

Table of correction factors for the calculation of the sound power level spectrum.

Spectrum sound power level

Hz dB(A) B lw dB(A)

63 95 20 75

125 95 19 76

250 95 11 84

500 95 5 90

1000 95 5 90

2000 95 7 88

4000 95 13 82

8000 95 20 75

Sound pressure spectrum

Hz dB(A) Atten. lw dB(A)

63 75 20 55

125 76 20 56

250 84 20 64

500 90 20 70

1000 90 20 70

2000 88 20 68

4000 82 20 62

8000 75 20 55

Working point:Airflow..................: 40,000 m3/hr = 11,1 m3/sPressure..: 23.4 mm c.a.

Taking as an example the following point: airflow axis (horizontal axis) at 40.000m3/h. (Airflow=11.1 m3/s) and at a static pressure of 23.4 mmWG (vertical axis at theleft side of the intersection).On those conditions the intersection point lies on the fan performance curve with 18º blade pitch angle (green line) with a dynamic pressure of 12.4 mmWG (red line)tracing at 40.000 m3/h point and clearly visible at upper vertical axis in the left side of the intersection).From this point, in the lower intersection that at 18º the absorbed power on the power scale on the left is 4768 W and that the upper red line corresponds, accordingto what can be read at the right lower side scale, to a motor power of 5,5 kW (S&P always recommends to work with a minimum security margin of 10% on theabsorbed power at the axis).Its total sound power level is 99 dB(A), (the sound level average value).The sound spectrum can be calculated from the noise area (the three areas delimited by grey lines): A, B, or C.In this case the working point is at the B area. To obtain the value of the spectrum for every octave band.For every eighth, the coefficient should be subtracted from the total sound power level.

At 3 meters of distance, the sound pressure level is 79 dB(A).

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

The resulting model would be CHGT/4-1000/3-16-5,5 kW.

BC

A

psf psf(Pa)

Pabs(W)15000

14000

13000

12000

10000

9000

8000

7000

6000

4000

3000

2000

10005000 15000 25000 35000 45000 55000

8º 10º12º

14º16º

18º20º 22º

24º 26º

28º

30º

32º

65000 75000

11000

(mmWG)

350

300

250

200

150

100

50

400

450

500

35

30

25

23,495

12,4

99

95 96 94 95 97

8º10º12º14º16º

18º

20º 22º 24º26º28º 30º32º

96 94 96 98 Lw dB(A)

989697101 100

40000

40000

4768

20

15

10

55000

2 4 6 8 10 12 14 16 18 20

15000 25000 35000 45000 55000

15

Absorbed power (W)

Recommended motorpower (kW)

11

5.5

7.5

43

65000 75000

40

45

50

qv [m3/h]

qv [m3/s]

qv [m3/h]

Page 14: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 2 POlE MOTORS

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

CGT

Number of poles 2

Nominal diameter (mm) 400

Number of blades 6

CGT/2-400-6/_°-_ kW

Hz A B C

63 42 43 36

125 29 30 23

250 17 17 14

500 8 6 8

1000 4 4 5

2000 5 6 5

4000 9 10 8

8000 17 19 14

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

80

70

60

50

40

30

20

10

0

800

700

600

500

400

300

200

100

0

psf psf(Pa) (mmWG)

8°10°12°14°

16°

18° 34°32°30°28°26°24°

22°

20°

94 99 94 92 93

93

92 96 92 91 93

97 92 91 93 Lw dB(A)

1000

0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3

2000 3000 4000 5000 6000 7000 8000 9000 10000 qv [m3/h]

qv [m3/s]

Pabs (W )

2400

2000

1600

1200

800

400

01000 2000 3000 4000 5000 6000 7000 8000 9000 10000 qv [m3/h]

Absorbed power (W) motorRecommended

power (kW)

2.2

1.5

1.1

8° 10° 12° 14° 16° 18° 20°22° 24°

26°28°

30°32°

34°

Page 15: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 2 POlE MOTORS

CGT

Number of poles 2

Nominal diameter (mm) 450

Number of blades 6

CGT/2-450-6/_°-_ kW

Hz A B C

63 42 43 36

125 29 30 23

250 17 17 14

500 8 6 8

1000 4 4 5

2000 5 6 5

4000 9 10 8

8000 17 19 14

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

90

80

70

60

50

40

30

20

10

0

900

800

700

600

500

400

300

200

100

0

3000

2500

2000

1500

1000

5001000 3000 5000 7000 9000 11000 13000

psf psf(Pa) (mmWG)

1000

0.4 0.8 1.2 1.6 2 2.4 2.8 3.2 3.6

qv [m3/h]

qv [m3/s]

3000 5000 7000 9000 11000 13000

8°10°12°14°

16°

18°

20°22°24°26° 28°

94

97

96 99 95 95

100 96 95 Lw dB(A)

102 98 97

Absorbed power (W) motorRecommended

power (kW)

2.2

1.5

3

28°

26°

24°22°

20°18°

16°14°12°

10°8°

qv [m3/h]

Pabs (W )

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 16: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 400

Number of blades 6

CHGT/4-400-6/_°-_ kWCGT/4-400-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

16

18

20

14

12

10

8

6

4

2

0

160

180

200

140

120

100

80

60

40

20

0

psf psf(Pa) (mmWG)

8º10º12º14º

16º

18º

20º22º

24º26º 28º30º32º34º36º38º

65 75 72 69 69 70

70 74 71 70 71

72 75 73 72 72 73

71 Lw dB(A)

0

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

1000 2000 3000 4000 5000 6000 qv [m3/h]

qv [m3/s]

0.25

Pabs(W)300

250

200

150

100

50

00 1000 2000 3000 4000 5000 6000 qv [m3/h]

8º10º 12º 14º

16º 18º 20º22º

24º26º

28º

30º

32º

34º

36º

38º

motorRecommended

power (kW)Absorbed power (W)

(*) CGT Series only.CHGT Series motor 0,55.

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 17: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 450

Number of blades 6

CHGT/4-450-6/_°-_ kWCGT/4-450-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

B C16

18

20

22

24

26

14

12

10

8

6

4

2

0

160

180

200

220

240

260

140

120

100

80

60

40

20

0

psf psf(Pa) (mmWG)

8º10º 12º

14º

16º

18º

20º 24º 30º

38º

69 74 75 73 73 74

74

76 78 76 76 76 77

78 74 74 74 75 Lw dB(A)

10000

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2

2000 3000 4000 5000 6000 7000 8000 qv [m3/h]

qv [m3/s]

0.37

0.55

0.25

Pabs(W)600

550

500

450

400

350

300

250

200

150

100

50

0 1000 2000 3000 4000 5000 6000 7000 8000 qv [m3/h]

8º 10º12º

14º 16º18º

20º22º

24º26º

28º30º

32º

34º

36º38º

motorRecommended

power (kW)Absorbed power (W)

(*) CGT Series only.

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 18: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 500

Number of blades 6

CHGT/4-500-6/_°-_ kWCGT/4-500-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

B C16

18

20

22

24

26

28

30

14

12

10

8

6

4

2

0

160

180

200

220

240

260

280

300

140

120

100

80

60

40

20

0

psf psf(Pa) (mmWG)

10º 12º14º

16º

18º

20º22º

24º26º 30º 32º

34º36º

38º

73 81 78 76 76 77

77778078

79 81 79 79 79 81

78 79 Lw dB(A)

1000

0.4 0.8 1.2 1.6 2 2.4 2.8 3.2

2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 qv [m3/h]

qv [m3/s]

Pabs(W)

1000

900

800

700

600

500

400

300

200

1001000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 qv [m3/h]

38º

36º

34º

32º

30º

28º26º

24º22º

20º18º16º14º12º

10º8º

1.1

0.75

0.55

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 19: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 560

Number of blades 6

CHGT/4-560-6/_°-_ kWCGT/4-560-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

C

A

B16

18

20

22

24

26

28

30

32

34

14

12

10

8

6

4

2

0

160

180

200

220

240

260

280

300

320

340

140

120

100

80

60

40

20

0

psf psf(Pa) (mmWG)

Pabs(W)

8º10º 12º 14º

16º

18º

20º22º

24º26º

28º30º

32º

34º

36º

38º81

8079838477

81 83 80 80 81

848382828483

83 Lw dB(A)

1000

0.5 1 1.5 2 2.5 3 3.5 4 4.5

3000 5000 7000 9000 11000 13000 15000 17000 qv [m3/h]

qv [m3/s]

2.2

1.5

1.1

0.75

0.55

38º

36º34º

32º30º

28º

26º24º

22º20º18º

16º14º12º10º8º

2000

1800

1600

1400

1200

1000

800

600

400

2001000 3000 5000 7000 9000 11000 13000 15000 17000 qv [m3/h]

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 20: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 630

Number of blades 6

CHGT/4-630-6/_°-_ kWCGT/4-630-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

B C

psf psf(Pa) (mmWG)

45045

40

35

30

25

20

15

10

5

0

400

350

300

250

200

150

100

50

0

10º 12º14º

16º

18º

20º22º 24º

26º28º 30º

32º

34º

36º

38º

919088909387

89 91 87 87 89

908987878989

90 Lw dB(A)

2000

1 2 3 4 5 6 7

5000 8000 11000 14000 17000 20000 23000 26000 qv [m3/h]

qv [m3/s]

Absorbed power (W)Recommendedmotorpower (W)

Pabs(W)

3000

2000 5000 8000 11000 14000 17000 20000 23000 26000

2600

2200

1800

1400

1000

600

200qv [m3/h]

38º

36º

34º

32º

30º

28º

26º24º

22º20º

18º16º14º

12º10º8º

3

2.2

1.5

1.1

0.75

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 21: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT f300 / CGT

CHGT f300 / CGT

Number of poles 4

Nominal diameter (mm) 710

Number of blades 3

CHGT/4-710-3/_°-_ kWCGT/4-710-3/_°-_ kW

Hz A B C

63 22 22 22

125 19 19 19

250 13 13 13

500 6 6 6

1000 4 4 4

2000 6 6 6

4000 11 11 11

8000 18 18 18

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

B C

0 5000 10000 15000 20000 25000 30000

1 2 3 4 5 6 7 8

0

5

10

15

20

25

30

35

40

0

50

100

150

200

250

300

350

400

14°

16°

18°

20°24°22°

26° 28° 30°32°

0 5000 10000 15000 20000 25000 300000

400

800

1200

1600

2000

2400

2800

3200

Pabs (W)

0.75

1.1

1.5

2.2

3

32°30°

28°26°

24°22°

20°18°16°

14°12°10°

9189889092

91 LwdB(A)89889192

90919389

12°

10°

92

qv [m3/h]

psf psf(Pa)

qv [m3/h]

qv [m3/s]

Recommendedmotorpower (KW)Absorbed power (W)

(mmWG)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 22: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

A

B C

0 5000 10000 15000 20000 25000 30000

1 2 3 4 5 6 7 8

0

5

10

15

20

25

30

35

40

0

50

100

150

200

250

300

350

400

14°

16°

18°

20°24°22°

26° 28° 30°32°

0 5000 10000 15000 20000 25000 300000

400

800

1200

1600

2000

2400

2800

3200

Pabs (W)

0.75

1.1

1.5

2.2

3

32°30°

28°26°

24°22°

20°18°16°

14°12°10°

9189889092

91 LwdB(A)89889192

90919389

12°

10°

92

qv [m3/h]

psf psf(Pa)

qv [m3/h]

qv [m3/s]

Recommendedmotorpower (KW)Absorbed power (W)

(mmWG)

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT f300 / CGT

CHGT f300 / CGT

Number of poles 4

Nominal diameter (mm) 710

Number of blades 6

CHGT/4-710-6/_°-_ kWCGT/4-710-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 6 5 6

1000 5 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

B C

0 5000 10000 15000 20000 25000 30000

1 2 3 4 5 6 7 8

0

5

10

15

20

25

30

35

40

45

50

55

60

0

50

100

150

200

250

300

350

400

450

500

550

6008°

14°16°

18°

20°

24°

22°

26°28°30°32°

0 5000 10000 15000 20000 25000 300000

500

1000

1500

2000

2500

3000

3500

4000

Pabs (W)

1.1

1.5

2.2

3

4

32°30°

28°26°

24°22°

20°

18°16°14°12°

10°8°

9291919393

93 LwdB(A)91919493

92939691

12°10°

93

psf psf(Pa)

qv [m3/h]

qv [m3/h]

qv [m3/s]

Recommendedmotorpower (KW)Absorbed power (W)

(mmWG)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 23: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT f400

CHGT f400

Number of poles 4

Nominal diameter (mm) 710

Number of blades 5 or 7

CHGT/4-710-_/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 12 14 11

8000 18 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

AB

C

psf psf(Pa)

500

450

400

350

300

250

200

150

100

50

0

50

45

40

35

30

25

20

15

10

5

00 5000

1 2 3 4 5 6 7 8 9

10000 15000 20000 25000 30000 35000 qv [m3/h]

qv [m3/s]

Pabs (W)

5.5

4

3

2.2

1.5

1.1

5500

4500

3500

2500

1500

5000 5000 10000 15000 20000 25000 30000 35000 qv [m3/h]

38°

36°

34°

32°

30°28°

26°24°

22°20°18°16°

14°12°10°8°

8° 14°

16°

18°

20°22°26°24°

28°30°

32°34°

36°38°

898886889185

90 91 87 87 89

929189899192

90 LwdB(A)

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 24: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 800

Number of blades 3

CHGT/4-800-3/_°-_ kWCGT/4-800-3/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 12 14 11

8000 18 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

B

A

C

psf psf(Pa)

400

350

300

250

200

150

100

50

0

40

35

30

25

20

15

10

50

0

10° 12°14°16°18°

20°22°

24° 26°28°

30°32°

87

92

94 91 90 91 93

90 88 89 91 Lw dB(A)

90 88 88 90

0 5000 10000 15000 20000 25000 30000 35000 40000

1 2 3 4 5 6 7 8 9 10 11

qv [m3/h]

qv [m3/s]

Pabs (W)

5.5

4

3

2.2

1.5

1.1

32°

30°

28°

26°24°

22°20°

18°16°

14°12°10°8°

5500

5000

4500

4000

3500

3000

2500

2000

1500

1000

5000 5000 10000 15000 20000 25000 30000 35000 40000 qv [m3/h]

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 25: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 800

Number of blades 6

CHGT/4-800-6/_°-_ kWCGT/4-800-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 12 14 11

8000 18 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

A

BC

psf psf(Pa)

600

550

500

450

400

350

300

250

200

150

100

50

0

60

55

50

45

40

35

30

25

20

15

10

5

00 5000 10000 15000 20000 25000 30000 35000 40000

12108642

45000

8° 14°

16°

18°

20°22°24°26°28°30° 32°

89 93

93

95 94 92 93 94

93 90 91 92 Lw dB(A)

90 90 91

qv [m3/h]

qv [m3/s]

Pabs (W )

7000

6000

5000

4000

3000

2000

10000 5000 10000 15000 20000 25000 30000 35000 40000 45000 qv [m3/h]

7.5

5.5

4

3

2.2

1.5

32°

30°

28°

26°24°

22°

20°18°

16°14°12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 26: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 800

Number of blades 9

CHGT/4-800-9/_°-_ kWCGT/4-800-9/_°-_ kW

Hz A B C

63 40 38 32

125 26 19 19

250 14 9 11

500 6 5 7

1000 4 5 5

2000 7 7 6

4000 12 13 10

8000 20 21 17

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

60060

55

50

45

40

35

30

25

20

15

10

5

05000

2 4 6 8 10 12

10000 15000 20000 25000 30000 35000 40000 45000

550

500

450

400

350

300

250

200

150

100

50

0qv [m3/h]

qv [m3/s]

8° 14°16°

18°

20° 22° 24° 26° 28°30°

32°

90

94

96 96 93 93 95

95 91 91 93 Lw dB(A)

95 92 90 92

Pabs (W)

8000

7000

6000

5000

4000

3000

2000

10005000 10000 15000 20000 25000 30000 35000 40000 45000 qv [m3/h]

32°30°

28°

26°24°

22°20°

18°16°14°

12°10°8°

7.5

5.5

4

3

2.2

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 27: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 900

Number of blades 6

CHGT/4-900-6/_°-_ kWCGT/4-900-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

BA

C

psf psf(Pa)

70070

65

60

55

50

45

40

35

30

25

20

15

10

5

05000

2 4 6 8 10 12 14 16 18

15000 25000 35000 45000 55000 65000

650

550

600

500

450

400

350

300

250

200

150

100

50

0qv [m3/h]

qv [m3/s]

8° 14°

16°

18°

20°22°24°26° 28°30°

32°

95939397

97 96

99 97 95 96 98

93 94 96 Lw dB (A)

93

Pabs (W )

14000

13000

12000

11000

10000

9000

8000

7000

6000

5000

4000

3000

2000

10005000 15000 25000 35000 45000 55000 65000 qv [m3/h]

15

11

7.5

5.5

4

3

32°30°

28°

26°24°

22°20°

18°16°

14°12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 28: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 900

Number of blades 9

CHGT/4-900-9/_°-_ kWCGT/4-900-9/_°-_ kW

Hz A B C

63 40 38 32

125 26 19 19

250 14 9 11

500 6 5 7

1000 4 5 5

2000 7 7 6

4000 12 13 10

8000 20 21 17

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

psf psf(Pa)

70070

65

60

55

50

45

40

35

30

25

20

15

10

5

0

650

600

550

500

450

400

350

300

250

200

150

100

50

0

8°10°12°14°16°

18°

20°22°

24°26°

28°30°32°

94

98

100 99 96 97 99

98 94 95 97 Lw dB (A)

98 95 94 96

5000

2 4 6 8 10 12 14 16 18

15000 25000 35000 45000 55000 65000 qv [m3/h]

qv [m3/s]

16000

14000

12000

10000

8000

6000

4000

20005000 15000 25000 35000 45000 55000 65000

Pabs (W )

qv [m3/h]

32°

30°

28°26°

24°22°

20°18°

16°

14°12°10°8°

15

11

7.5

5.5

4

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Pabs (W)

16000

14000

12000

10000

8000

6000

4000

2000

18000

5000 15000 25000 35000 45000 55000 65000 qv [m3/h]

motorRecommended

power (kW)Absorbed power (W)

18.5

15

11

7.5

5.5

48° 10° 12° 14°

16°18°

20°22°

24°26°

28°30°

32°

Page 29: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 1000

Number of blades 6

CHGT/4-1000-6/_°-_ kWCGT/4-1000-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

850

800

750

550

600

650

700

500

450

400

350

300

200

150

100

250

50

85

80

75

55

60

65

70

50

45

40

35

30

20

15

10

25

5

96 99 96 96 98

101 99 96 97

103 100 98 99 101

100 Lw dB (A)

10000

3 5 7 9 11 13 15 17 19 21

20000 30000 40000 50000 60000 70000 80000 qv [m3/h]

qv [m3/s]

Pabs (W )

21000

19000

17000

15000

13000

11000

9000

7000

5000

3000

100010000 20000 30000 40000 50000 60000 70000 80000 qv [m3/h]

32°30°

28°

26°24°

22°20°

18°16°

14°12°10°8°

22

18.5

15

11

7.5

5.54

10°12°

14°

16°

18°

20° 22° 24° 26° 28° 30° 32°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 30: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 1000

Number of blades 9

CHGT/4-1000-9/_°-_ kWCGT/4-1000-9/_°-_ kW

Hz A B C

63 40 38 32

125 26 19 19

250 14 9 11

500 6 5 7

1000 4 5 5

2000 7 7 6

4000 12 13 10

8000 20 21 17

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

850

800

750

550

600

650

700

500

450

400

350

300

200

150

100

250

50

85

80

75

55

60

65

70

50

45

40

35

30

20

15

10

25

510000 20000 30000 40000 50000 60000 70000 80000 90000

4 6 8 10 12 14 16 18 20 22 24

qv [m3/h]

qv [m3/s]

97 101 98 97 99

102 101 97 98 100 Lw dB (A)

104 102 99 100 102

8°10°12°14°

16°

18°

20°22°24° 26° 28°30° 32°

Pabs (W )26000

22000

18000

14000

10000

6000

200010000 20000 30000 40000 50000 60000 70000 80000 90000 qv [m3/h]

32°

30°

28°

26°24°

22°20°

18°16°

14°12°10°8°

22

18.5

15

11

7.5

5.5

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 31: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 1250

Number of blades 6

CHGT/4-1250-6/_°-_ kWCGT/4-1250-6/_°-_ kW

Hz A B C

63 38 38 31

125 22 21 19

250 12 9 12

500 5 5 6

1000 4 5 5

2000 7 8 6

4000 13 14 11

8000 21 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

95095

850

750

650

550

450

350

250

150

50 5

15

25

35

45

55

65

75

85 8°

10°12°14°

16°

18°

20°22°

24°26° 28°30° 32°

104

104 107 Lw dB (A)109

105

105

102

102

106 108110 106 104

103 105

20000

6 10 14 18 22 26 30 34 38 42

40000 60000 80000 100000 120000 140000 160000 qv [m3/h]

qv [m3/s]

Pabs(W)

48000

44000

40000

36000

32000

28000

24000

20000

16000

12000

800020000 40000 60000 80000 10000 120000 140000 160000 qv [m3/h]

32º

30º28º

26º

24º

22º

20º

18º

16º

14º12º10º8º

45

37

30

22

18.5

15

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 32: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 4

Nominal diameter (mm) 1250

Number of blades 9

CHGT/4-1250-9/_°-_ kWCGT/4-1250-9/_°-_ kW

Hz A B C

63 40 38 32

125 26 19 19

250 14 9 11

500 6 5 7

1000 4 5 5

2000 7 7 6

4000 12 13 10

8000 20 21 17

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

B

A

C

psf psf(Pa)

1250125

115

105

95

85

75

65

55

45

35

25

15

5

1150

1050

950

850

750

650

550

450

350

250

150

50

8°10°12°14°

16°

18°

20° 22° 24°

104 105 102 103

105109

110 106 104 106

102 104 Lw dB(A)

20000

8 12 16 20 24 28 32 36 40 44

40000 60000 80000 100000 120000 140000 160000 qv [m3/h]

qv [m3/s]

Pabs(W)

20000 40000 60000 80000 100000 120000 140000 160000

45

37

30

22

18.5

15

24°

22°

20°

18°16°

14°12°

10°

qv [m3/h]

(mmWG)

motorRecommended

power (kW)Absorbed power (W)45000

40000

35000

30000

25000

20000

15000

10000

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 33: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 500

Number of blades 6

CHGT/6-500-6/_°-_ kWCGT/6-500-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

9

10

11

12

8

7

6

5

4

3

2

1

0

90

100

110

120

80

70

60

50

40

30

20

10

0

psf psf(Pa) (mmWG)

qv [m3/h]

qv [m3/s]

8°10°12°14°

16°

18°

20°24° 28° 32°34°

36°38°

62 70 68 66

66 69 69 Lw dB(A)67 67 67

716969697068

66 67

0

0 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4

1000 2000 3000 4000 5000 6000 7000 90008000

Pabs (W )350

300

250

200

150

100

00 1000 2000 3000 4000 5000 6000 7000 8000 9000

50

qv [m3/h]

0.37

38°

36°

34°32°

30°28°

26°24°

22°20°18°16°14°12°10°8°

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 34: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 560

Number of blades 6

CHGT/6-560-6/_°-_ kWCGT/6-560-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa) (mmWG)

150

140

130

120

110

100

90

80

70

60

50

40

30

20

10

0

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

8°10°12°

14°

16°

18°

20°22°

24°26°

28°30°32°

34°

36°

38°66 73 71 69 70

70 72 7071 71

747372727372

72 Lw dB(A)

1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000

0.4 0.8 1.2 1.6 2 2.4 2.8 3.2

qv [m3/h]

qv [m3/s]

Pabs (W )

600

500

400

300

200

100

0

0.55

0.37

38°36°

34°32°

30°28°

26°24°

22°20°

18°16°14°12°10°8°

1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 qv [m3/h]

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 35: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 630

Number of blades 5

CHGT/6-630-6/_°-_ kWCGT/6-630-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

18

20

16

14

12

10

8

6

4

2

0

180

200

160

140

120

100

80

60

40

20

0

psf psf(Pa) (mmWG)

10°12°14°

16°

18°

20°22°24°26°

28°30°32°

34°

36°

38°70 76

76

76 76 76 76 76 78

76 74 74 75 76 Lw dB(A)

76 73 73

1000

0.5 1 1.5 2 2.5 3 3.5 4 4.5

3000 5000 7000 9000 11000 13000 15000 17000 qv [m3/h]

qv [m3/s]

motorRecommended

power (kW)Absorbed power (W)Pabs (W )

1000

900

800

700

600

500

400

300

200

100

01000 3000 5000 7000 9000 11000 13000 15000 17000 qv [m3/h]

1.1

0.75

0.55

0.37

38°

36°

34°

32°30°

28°26°

24°22°

20°18°16°

14°12°10°8°

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 36: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT f300 / CGT

CHGT f300 / CGT

Number of poles 6

Nominal diameter (mm) 710

Number of blades 3

CHGT/6-710-3/_°-_ kWCGT/6-710-3/_°-_ kW

Hz A B C

63 25 25 25

125 17 17 18

250 9 9 9

500 5 5 5

1000 5 5 5

2000 9 9 9

4000 14 15 15

8000 22 22 22

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

0 4000 8000 12000 16000 20000

1 2 3 4 5

0

2

4

6

8

10

12

14

16

18

0

20

40

60

80

100

120

140

160

180

14°

16°

18°

20°24°

22°26° 28° 30° 32°

0 4000 8000 12000 16000 200000

200

400

600

800

1000

Pabs (W )

0.55

0.7532°

30°

28°26°

24°22°

20°18°

16°14°12°

10°8°

8180787981

81 LwdB(A)80788081

81818278

12°

10°

82

psf psf(Pa)

qv [m3/h]

qv [m3/h]

qv [m3/s]

Recommendedmotorpower (KW)Absorbed power (W)

(mmWG)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 37: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT f300 / CGT

CHGT f300 / CGT

Number of poles 6

Nominal diameter (mm) 710

Number of blades 6

CHGT/6-710-6/_°-_ kWCGT/6-710-6/_°-_ kW

Hz A B C

63 33 32 33

125 16 15 15

250 8 7 8

500 5 4 5

1000 5 4 5

2000 10 10 10

4000 17 16 16

8000 25 25 25

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

0 4000 8000 12000 16000 20000

1 2 3 4 5

0

5

10

15

20

25

0

50

100

150

200

2508° 14°16°

18°

20°

24°

22°

26°28°30° 32°

0 4000 8000 12000 16000 200000

200

400

600

800

1000

1200

Pabs (W )

0.55

0.75

1.1

Recommendedmotorpower (KW)Absorbed power (W)

32°

30°

28°26°

24°

22°20°

18°16°

14°12°

10°8°

8281818282

83 LwdB(A)81818382

82838580

12°10°

83

psf psf(Pa) (mmWG)

qv [m3/h]

qv [m3/h]

qv [m3/s]

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 38: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

CBA

0 4000 8000 12000 16000 20000

1 2 3 4 5

0

5

10

15

20

25

0

50

100

150

200

2508° 14°16°

18°

20°

24°

22°

26°28°30° 32°

0 4000 8000 12000 16000 200000

200

400

600

800

1000

1200

Pabs (W )

0.55

0.75

1.1

Recommendedmotorpower (KW)Absorbed power (W)

32°

30°

28°26°

24°

22°20°

18°16°

14°12°

10°8°

8281818282

83 LwdB(A)81818382

82838580

12°10°

83

psf psf(Pa) (mmWG)

qv [m3/h]

qv [m3/h]

qv [m3/s]

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT

CHGT

Number of poles 6

Nominal diameter (mm) 710

Number of blades 5 or 7

CHGT/6-710-_/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 13 16 13

8000 19 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

psf psf(Pa)

24024

20

16

12

8

4

00

0 1 2 3 4 5

3000 6000 9000 12000 15000 18000 21000

200

160

120

80

40

0qv [m3/h]

qv [m3/s]

74 80 78 77

77

81 8180 8079

78

78 79 Lw dB(A)79 79

18°

14°

16°

20°22°24°26°28°

30°32°

Pabs (W )

1500

1300

1100

900

700

500

300

1000 3000 6000 9000 12000 15000 18000 21000 qv [m3/h]

1.5

1.1

0.75

0.55

32°30°

28°

26°24°

22°20°

18°16°14°12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 39: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 800

Number of blades 3

CHGT/6-800-3/_°-_ kWCGT/6-800-3/_°-_ kW

Hz A B C

63 25 25 22

125 19 17 18

250 11 9 10

500 6 5 6

1000 4 5 4

2000 8 9 8

4000 13 14 14

8000 20 22 23

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

psf psf(Pa)

18018

16

14

12

10

8

6

4

2

00

0 1 2 3 4 5 6 7

4000 8000 12000 16000 20000 24000 28000

160

140

120

100

80

60

40

20

0qv [m3/h]

qv [m3/s]

81

83 80 80 81 83

7879

76 78 78 8079

79 81 Lw dB(A)

8°10°12°14°16°

18°

20°22° 24°

26°28°

30°32°

Pabs (W )

1500

1250

1000

750

500

250

00 4000 8000 12000 16000 20000 24000 28000 qv [m3/h]

32°

30°

28°

26°

22°24°

20°18°

16°14°12°10°8°

1.5

1.1

0.75

0.55

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 40: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 800

Number of blades 6

CHGT/6-800-6/_°-_ kWCGT/6-800-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

psf psf(Pa)

300

250

200

150

100

50

0

30

25

20

15

10

5

00

0 1 2 3 4 5 6 7

4000 8000 12000 16000 20000 24000 28000 qv [m3/h]

qv [m3/s]

10°12° 14°

16°

18°

20°22°24° 26°28°30°32°

78 80 80 81

81 82 Lw dB(A)82

84 83 82 83 84

82 80

82

Pabs (W )

2.2

1.5

1.1

0.75

0.55

32°

30°

28°

26°

22°

24°

20°18°

16°14°12°10°

0 4000 8000 12000 16000 20000 24000 28000

2200

2000

1800

1600

1400

1200

1000

800

600

400

200qv [m3/h]

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 41: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 800

Number of blades 9

CHGT/6-800-9/_°-_ kWCGT/6-800-9/_°-_ kW

Hz A B C

63 37 31 29

125 22 15 16

250 11 8 10

500 5 5 6

1000 4 5 5

2000 9 9 7

4000 14 15 11

8000 22 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

300

250

200

150

100

50

0

30

25

20

15

10

5

02000

1 2 3 4 5 6 7 8

5000 8000 11000 14000 17000 20000 23000 26000 29000 qv [m3/h]

qv [m3/s]

8° 14°

16°

18°

20° 22° 24° 26° 28°30° 32°

79 82 82

83 84 82 82

85 85 83 84 85

83 Lw dB(A)

8184

Pabs (W )

3

2.2

1.5

1.1

0.75

32°

30°

28°26°

22°24°

20°18°

16°14°12°10°8°

2800

2400

2000

1600

1200

800

4002000 5000 8000 11000 14000 17000 20000 23000 26000 29000 qv [m3/h]

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 42: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 900

Number of blades 6

CHGT/6-900-6/_°-_ kWCGT/6-900-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

360

320

280

240

120

160

200

40

80

0

36

32

28

24

12

16

20

4

8

02000

1 2 3 4 5 6 7 8 9 10 11

6000 10000 14000 18000 22000 26000 30000 34000 38000 42000 qv [m3/h]

qv [m3/s]

8° 14°10°12°

16°

18°

20°22°24°26°28°30° 32°

82

86

88 86 85 86 88

85 83 84 86 Lw dB(A)

83 858386

Pabs (W )

4000

3500

3000

2500

2000

1500

1000

500

02000 6000 10000 14000 18000 22000 26000 30000 34000 38000 42000 qv [m3/h]

4

3

2.2

1.5

32°

30°

28°

26°22° 24°

20°18°

16°14°

12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 43: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 900

Number of blades 9

CHGT/6-900-9/_°-_ kWCGT/6-900-9/_°-_ kW

Hz A B C

63 37 31 29

125 22 15 16

250 11 8 10

500 5 5 6

1000 4 5 5

2000 9 9 7

4000 14 15 11

8000 22 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

C

BA

psf psf(Pa)

360

320

280

240

120

160

200

40

80

0

36

32

28

24

12

16

20

4

8

0

8° 14°10°12°

16°

18°

20°22°

24°26°28°30°32°

83 85 85

85858787

87 89878889

87 Lw dB(A)

8487

5000

2 3 4 5 6 7 8 9 10 11 12

10000 15000 20000 25000 30000 35000 40000 45000 qv [m3/h]

qv [m3/s]

Pabs (W )

5500

5000

4500

4000

3500

3000

2000

2500

1500

1000

5005000 10000 15000 20000 25000 30000 35000 40000 45000 qv [m3/h]

32°30°

28°26°

22° 24°20°

18°16°

14°12°10°8°

5.5

4

3

2.2

1.5

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 44: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 1000

Number of blades 6

CHGT/6-1000-6/_°-_ kWCGT/6-1000-6/_°-_ kW

Hz A B C

63 22 20 18

125 19 19 17

250 13 11 12

500 6 5 6

1000 4 5 5

2000 6 7 6

4000 11 13 12

8000 18 20 12

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CBA

psf psf(Pa)

380

340

300

260

140

180

220

60

100

20

38

34

30

26

14

18

22

6

10

25000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000

2 3 4 5 6 7 8 9 10 11 12 13 14 15

qv [m3/h]

qv [m3/s]

85 86 888688

90 86 89 Lw dB(A)8588

92 88 89 9189

8° 14°10°12°

16°

18°

20° 22° 24° 26° 28° 30° 32°

Pabs (W )

7000

6000

5000

4000

3000

2000

1000

05000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 qv [m3/h]

5.5

4

3

2.2

1.5

7.5

32°30°

28°26°

22°24°

20°18°

16°14°12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 45: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 1000

Number of blades 9

CHGT/6-1000-9/_°-_ kWCGT/6-1000-9/_°-_ kW

Hz A B C

63 37 31 29

125 22 15 16

250 11 8 10

500 4 5 6

1000 4 5 5

2000 9 9 7

4000 14 15 11

8000 22 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

C

BA

psf psf(Pa)

380

340

300

260

140

180

220

100

60

20

38

34

30

26

14

18

22

10

6

210000

3 5 7 8 11 13 15

15000 20000 25000 30000 35000 40000 45000 50000 55000 60000 qv [m3/h]

qv [m3/s]

10°12°14°

16°

18°

20° 22° 24° 26°28° 30° 32°

86 88 898790

91 88 90 Lw dB(A)8890

93 89 90 9291

Pabs (W )

7000

6000

5000

4000

3000

2000

100010000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000 qv [m3/h]

5.5

4

3

2.2

7.5

32°

30°

28°

26°

22°24°

20°18°

16°14°

12°10°8°

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 46: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 1250

Number of blades 6

CHGT/6-1250-6/_°-_ kWCGT/6-1250-6/_°-_ kW

Hz A B C

63 33 33 28

125 18 15 18

250 9 8 10

500 5 5 5

1000 5 5 5

2000 8 10 7

4000 15 16 13

8000 23 25 21

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

CB

A

psf psf(Pa)

460

420

380

340

220

260

300

180

140

100

60

20

46

42

38

34

22

26

30

18

14

10

6

210000

4 6 8 10 12 14 16 18 20 22 24 26 28 30

20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 qv [m3/h]

qv [m3/s]

8°10°12°14°

16°

18°

20°22°24°

26° 28°30° 32°

93 92 959394

97

99 95 94 96 98

92 94 96 Lw dB(A)94

Pabs (W )14000

10000

12000

8000

4000

6000

200010000 20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 qv [m3/h]

32°

30°28°

26°

22°

24°

20°18°

16°

14°12°10°8°

15

11

7.5

5.5

4

(mmWG)

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Page 47: AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or

www.solerpalau.com

AXIAL FLOW CABINET FANSCHGT Series

Cylindrical cased axial flow fans CHGT

PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT

CHGT / CGT

Number of poles 6

Nominal diameter (mm) 1250

Number of blades 9

CHGT/6-1250-9/_°-_ kWCGT/6-1250-9/_°-_ kW

Hz A B C

63 37 31 29

125 22 15 16

250 11 8 10

500 5 5 6

1000 4 5 5

2000 9 9 7

4000 14 15 11

8000 22 23 19

Table of correction factors for the calculation of the sound power level spectrum.

THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.

TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.

AB

C

psf psf(Pa) (mmWG)

580

540

380

340

500

300

460

260

140

180

420

220

100

60

20

58

54

38

34

50

30

46

26

14

18

42

22

10

6

2

2

1000020000 30000 40000 50000 60000 70000 80000 90000 100000 110000 120000

6 8 10 12 14 16 18 20 22 24 26 28 30 32

qv [m3/h]

qv [m3/s]

10°8° 12°14°

16°

18°

20° 22° 24° 26°28°30°32°

94 94 96

98 96

94

94

100 97 97 9995

95 97 Lw dB(A)

96

Pabs (W )

22000

20000

20000 30000 40000 50000 60000 70000 80000 90000 100000110000 120000

18000

16000

12000

14000

10000

100002000

6000

8000

4000

qv [m3/h]

32°30°

28°26°

22°24°

20°18°

16°14°

12°10°8°

22

18.5

15

11

7.5

5.5

motorRecommended

power (kW)Absorbed power (W)

- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.


Recommended